Mitsubishi OB307C Service Manual

SERVICE MANUAL
HFC
utilized
R410A
SPLIT-TYPE, AIR CONDITIONERS SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
Wireless type Models
MSC-A07WV ­MSC-A09WV ­MSC-A12WV ­MSC-A07WV ­MSC-A09WV ­MSC-A12WV -
(WH) (WH) (WH) (WH) (WH) (WH)
· MU-A07WV -
· MU-A09WV -
· MU-A12WV -
· MUH-A07WV -
· MUH-A09WV -
· MUH-A12WV -
Revision C:
MUX-A10/A19/A20/A25/A26WV - can be connected to MSC-A07/A09/A12YV -
Please void OB307 REVISED EDITION-B.
E1
E1
.
No. OB307
REVISED EDITION-C
E1E1 E1E1 E1E1
E1E1 E1E1 E1E1
Multi system type Models
MSC-A07WV ­MSC-A09WV ­MSC-A12WV -
MSC-A07WV ­MSC-A09WV ­MSC-A12WV -
Remote controller
E1
E1
E1
(WH) (WH) (WH)
Indication of model name
· MUX-A10WV -
· MUX-A19WV -
· MUX-A20WV -
· MUX-A25WV -
· MUX-A26WV -
E1E1 E1E1 E1E1 E1 E1
CONTENTS
1. TECHNICAL CHANGES ····································2
2. PART NAMES AND FUNCTIONS······················6
3. INDOOR / OUTDOOR CORRESPONDENCE TABLE ···························8
4. SPECIFICATION·················································9
5. NOISE CRITERIA CURVES·····························15
6. OUTLINES AND DIMENSIONS·······················18
7. WIRING DIAGRAM ··········································22
9. PERFORMANCE CURVES······························40
10. MICROPROCESSOR CONTROL ····················75
11. SERVICE FUNCTIONS·····································86
12. TROUBLESHOOTING ······································88
13. DISASSEMBLY INSTRUCTIONS···················105
14. PARTS LIST····················································116
NOTE:
•As for indoor units MSC-A07/A09/A12YV - , refer to the service manual OB329.
•As for outdoor units MUX-A22WV - , refer to the service manual OB318 REVISED EDITION-A.
•As for outdoor units MXZ-A18/A26/A32WV - , refer to the service manual OB319.
E1
E1
E1
Revision C:
•MUX-A10/A19/A20/A25/A26WV - can be connected to MSC-A07/A09/A12YV -
E1E1
.
1
MSC-07RV- ➔MSC-A07WV-
MSC-09RV- MSC-A09WV­MSC-12RV- MSC-A12WV-
1. Rated voltage has changed. (220-240V➔230V)
2. Indoor model has changed.
MU-07RV- ➔MU-A07WV-
1. Refrigerant has changed. (R22➔R410A)
2. Compressor has changed. (RH130VGCT➔RN092VHSHT)
MU-09RV- MU-A09WV-
1. Refrigerant has changed. (R22➔R410A)
2. Compressor has changed. (RH140VGCT➔RN099VHSHT)
MU-12RV- MU-A12WV-
1. Refrigerant has changed. (R22➔R410A)
2. Compressor has changed. (RH220VHAT➔RN135VHSHT)
MUH-07RV- MUH-A07WV-
1. Refrigerant has changed. (R22➔R410A)
2. Compressor has changed. (RH130VGCT➔RN092VHSHT)
TECHNICAL CHANGES
E1E4
E1E4
E1E4
E1E4
E1E4
E1E4
E1E4
MUH-09RV- MUH-A09WV-
1. Refrigerant has changed. (R22➔R410A)
2. Compressor has changed. (RH165VGCT➔RN104VHSHT)
MUH-12RV- MUH-A12WV-
1. Refrigerant has changed. (R22➔R410A)
2. Compressor has changed. (RH220VHAT➔RN135VHSHT)
MUX-10RV- MUX-A10WV-
1. Outdoor model has changed.
2. Refrigerant has changed. (R22➔R410A)
MUX-19TV- MUX-A19WV­MUX-20TV- MUX-A20WV­MUX-25TV- MUX-A25WV-
1. Refrigerant has changed. (R22➔R410A)
MUX-24RV- MUX-A26WV-
1. Outdoor model has changed.
2. Refrigerant has changed. (R22➔R410A)
E1E4
E1E4
E1E2
E1E1
E1E1
E1E1
E1E2
2
Refrigerating
oil
Refrigerant
New refrigerant
R410A
HFC-32: HFC-125 (50%:50%)
Pseudo-azeotropic refrigerant
Not included
A1/A1
72.6
-51.4
1.557 64
Non combustible
0
1730
From liquid phase in cylinder
Possible
Incompatible oil
Non Non
Previous refrigerant
R22
R22 (100%)
Single refrigerant
Included
A1
86.5
-40.8
0.94
44.4
Non combustible
0.055 1700
Gas phase
Possible
Compatible oil
Light yellow
Non
Refrigerant Composition (Ratio) Refrigerant handling Chlorine Safety group (ASHRAE) Molecular weight Boiling point (:) Steam pressure [25:](Mpa) Saturated steam density [25:](Kg/K) Combustibility ODP w1 GWP w2 Refrigerant charge method Additional charge on leakage Kind Color Smell
w1:Ozone Destruction Parameter : based on CFC-11 w2 :Global Warmth Parameter : based on CO
2
INFORMATION FOR THE AIR CONDITIONER WITH R410A REFRIGERANT
New Specification Current Specification
The incompatible refrigerating oil easily separates from refrigerant and is in the upper layer inside the suction muffler. Raising position of the oil back hole enables to back the refrigerating oil of the upper layer to flow back to the compressor.
Since refrigerant and refrigerating oil are compatible each, refrigerating oil backs to the compressor through the lower position oil back hole.
Compressor
Suction muffler
Oil back hole
Refrigerating oil
Refrigerant
Compressor
Suction muffler
Oil back hole
Refrigerating oil /Refrigerant
Compressor
• This room air conditioner adopts an HFC refrigerant (R410A) which never destroys the ozone layer.
• Pay particular attention to the following points, though the basic installation procedure is same as that for R22 conditioners. 1 As R410A has working pressure approximate 1.6 times as high as that of R22, some special tools and piping parts/
materials are required. Refer to the table below.
2 Take sufficient care not to allow water and other contaminations to enter the R410A refrigerant during storage and
installation, since it is more susceptible to contaminations than R22.
3 For refrigerant piping, use clean, pressure-proof parts/materials specifically designed for R410A. (Refer to 2. Refrigerant
piping.)
4 Composition change may occur in R410A since it is a mixed refrigerant. When charging, charge liquid refrigerant to prevent
composition change.
NOTE : The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/ff[Gauge])
3
-30 -20 -10 0 10 20
30
40 50 60
-0.5
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
(MPa [Gauge])
R410A R22
Conversion chart of refrigerant temperature and pressure
Saturated liquid pressure
(:)
NOTE : The unit of pressure has been changed to MPa on the
R410A tools Can R22 tools be used?
Gas leak detector
R410A has high pressures beyond the measurement range of existing gauges. Port diameters have been changed to prevent any other refrigerant from being charged into the unit.
Hose material and cap size have been changed to improve the pressure resistance.
Dedicated for HFC refrigerant.
6.35 mm and 9.52 mm
Description
Clamp bar hole has been enlarged to reinforce the spring strength in the tool. Provided for flaring work (to be used with R22 flare tool).
Provided to prevent the back flow of oil. This adapter enables you to use vacuum pumps.
It is difficult to measure R410A with a charging cylinder because the refrigerant bubbles due to high pressure and high-speed vaporization
No
No
No
Yes
Yes
New
New
New
Gauge manifold
Charge hose
Torque wrench
Flare tool Flare gauge
Vacuum pump adapter
Electronic scale for refrigerant charging
No : Not Substitutable for R410A Yes : Substitutable for R410A
No 12.7 mm
Wall thickness
Outside diameter
Pipe
mm
For liquid For gas
6.35
9.52
12.7
0.8 mm
0.8 mm
0.8 mm
Heat resisting foam plastic Specific gravity 0.045 Thickness 8 mm
Insulation material
international system of units(SI unit system).
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/ff[Gauge])
1.Tools dedicated for the air conditioner with R410A refrigerant
The following tools are required for R410A refrigerant. Some R22 tools can be substituted for R410A tools. The diameter of the service port on the stop valve in outdoor unit has been changed to prevent any other refrigerant being charged into the unit. Cap size has been changed from 7/16 UNF with 20 threads to 1/2 UNF with 20 threads.
2.Refrigerant piping
1 Specifications
Use the refrigerant pipes that meet the following specifications.
• Use a copper pipe or a copper-alloy seamless pipe with a thickness of 0.8 mm. Never use any pipe with a thickness less than 0.8mm, as the pressure resistance is insufficient.
4
2 Flaring work and flare nut
Flaring work for R410A pipe differs from that for R22 pipe. For details of flaring work, refer to Installation manual “FLARING WORK”.
Pipe diameter
mm
6.35
9.52
12.7
Dimension of flare nut
R410A
17 22 26
R22
17 22 24
3.Refrigerant oil
Apply the special refrigeration oil (accessories: packed with indoor unit) to the flare and the union seat surfaces.
4.Air purge
• Do not discharge the refrigerant into the atmosphere. Take care not to discharge refrigerant into the atmosphere during installation, reinstallation, or repairs to the refrigerant
circuit.
• Use the vacuum pump for air purging for the purpose of environmental protection.
5.Additional charge
For additional charging, charge the refrigerant from liquid phase of the gas cylinder. If the refrigerant is charged from the gas phase, composition change may occur in the refrigerant inside the cylinder and the outdoor unit. In this case, ability of the refrigerating cycle decreases or normal operation can be impossible. However, charging the liquid refrigerant all at once may cause the compressor to be locked. Thus, charge the refrigerant slowly.
Union
Stop valve
Indoor unit
Refrigerant gas cylinder operating valve
Liquid pipe Gas pipe
Service port
Outdoor unit
Gauge manifold valve (for R410A)
Charge hose (for R410A)
Refrigerant gas cylinder for R410A with siphon
Refrigerant (liquid)
Electronic scale for refrigerant charging
5
2
PART NAMES AND FUNCTIONS
INDOOR UNIT
MSC-A07WV ­MSC-A09WV ­MSC-A12WV -
Panel
Air filter
Air outlet
Horizontal vane
E1
E1
E1
Air cleaning filter (White bellows type)
Deodorizing filter (Gray sponge type)
Vertical vane
Operation section
Front panel
Air inlet
to Breaker
Power supply cord
Remote control receiving section
Remote controller
Display section
(When the front panel is opened)
Emergency operation switch
OUTDOOR UNIT
MU-A07WV - MUH-A07WV ­MU-A09WV - MUH-A09WV ­MU-A12WV - MUH-A12WV -
Air inlet
(back and side)
Piping
Drain hose
Operation indicator lamp
Receiving section
E1E1
E1E1
E1E1
MUX-A10WV-
E1
Air inlet
(back and side)
Piping
Drain hose
Air outlet
Drain outlet
Air outlet
Drain outlet
6
OUTDOOR UNIT
Installation plate Installation plate fixing screw 4 o 25 mm Remote controller holder Fixing screw for 3 3.5 o 16 mm Battery (AAA) for remote controller Wireless remote controller Felt tape (Used for left or left-rear piping) Deodorizing filter Air cleaning filter Refrigerant oil
1 5 1 2 2 1 1 1 1 1
<Indoor unit>
1
2
3
4
5
6
7
8
9
0
Drain socket Drain cap
1 2
<Outdoor unit: MUH type>
1
2
MUX-A19WV- MUX-A25WV­MUX-A20WV-
E1
ACCESSORIES
MSC-A07WV­MSC-A09WV­MSC-A12WV-
E1
E1
E1
E1E1
Air inlet
(Back and side)
Air outlet
Piping
Drainage hose
Drain outlet
MUX-A26WV-
MUH-A07WV­MUH-A09WV­MUH-A12WV-
E1
Air inlet
(Back and side)
Air outlet
Piping
Drainage hose
Drain outlet
E1
E1
E1
7
MUX-A19WV-
E1
MUX-A25WV-
E1
MUX-A20WV-
E1
MUX-A10WV-
E1
MUX-A26WV-
E1
Combination of
the connectable
indoor units
OUTDOOR UNIT
A: MSC-A12WV- E1
or
MSC-A12YV-
E1
B: MSC-A07WV- E1
or
MSC-A07YV-
E1
A:
MSC-A09WV- E1
B:
or
C:
MSC-A09YV- E1
A: B:
A: B:
A:
MSC-A12WV- E1 or B:
MSC-A12YV- E1
C:
MSC-A09WV- E1
or
D:
MSC-A09YV- E1
MSC-A12WV- E1
or
MSC-A12YV- E1
MSC-A07WV- E1
or
MSC-A07YV-
E1
REMOTE CONTROLLER
MSC-A07WV ­MSC-A09WV ­MSC-A12WV -
E1
E1
E1
Signal transmitting section
Operation display section
OPERATE /STOP (ON /OFF)button
Open the front lid.
ON/OFF
TOO
WARM
PM
AM
TOO
COOL
TEMPERATURE buttons
CLOCK
PM
AM
TOO
WARM
FAN
VANE
RESET
CLOCK
TOO
COOL
STOP
START
HR.
MIN.
OFF-TIMER button ON-TIMER button
HR. button
MIN. button
(TIME SET button)
CLOCK SET button
FAN SPEED CONTROL button
OPERATION SELECT button
ECONO COOL button
RESET button
ON/OFF
I FEEL
COOL
HEAT
DRY
/FAN
/
MODE
ECONO COOL
VANE CONTROL button
INDOOR / OUTDOOR CORRESPONDENCE TABLE3
MSC-A07WV - MSC-A09WV - MSC-A12WV ­MUX-A10WV - MUX-A19WV - MUX-A20WV - MUX-A25WV - MUX-A26WV -
E1E1E1
E1E1E1E1E1
8
4
Indoor model
Function
Indoor unit power supply
Air flow(High/Med. /Low ) Power outlet Running current Power input Power factor Starting current Fan motor current Model Winding resistance(at 20:) Dimensions WOHOD Weight Air direction Sound level(High/Med. /Low ) Fan speed (High/Med. /Low ) Fan speed regulator Thermistor RT11(at 25:) Thermistor RT12(at 25:) Outdoor model
Capacity Dehumidification Outdoor air flow Power outlet Running current Power input Auxiliary heater Power factor Starting current Compressor motor current Fan motor current
Model Output Winding resistance(at 20:) Model Winding resistance(at 20:) Dimensions WOHOD Weight Sound level Fan speed Fan speed regulator Refrigerant filling capacity (R410A) Refrigerating oil (Model)
K /h
A A
W
%
A A
"
mm
kg
dB
rpm
k" k"
kW
R/h
K /h
A A
W
A(kW)
%
A A A
W
"
  
"
mm
kg
dB
rpm
kg cc
MSC-A07WV -
E1
Single phase
230V,50Hz
10
0.17 35 90 —
0.17
WHT-BLK 413 BLK-RED 334 815O278O217
9 5
3 10 10
MU-A07WV -
E1
Single phase
230V,50Hz
10
2.76
0.22
RN092VHSHT
600 C-R 3.87 C-S 6.14
RA6V23-FC
WHT-BLK 353
BLK-RED 321 780o540o255
34 45
735
1
0.75
350 (NEO22 )
Cooling
474/372 /276
RC4V19-LA
36/31 /25
900/750 /600
2.3
0.9
1,686
2.98 675
98 23
3.24
MSC-A09WV - E1
Single phase
230V,50Hz
10
0.17 35
RC4V19-LA WHT-BLK 413 BLK-RED 334 815O278O217
9 5
3 10 10
MU-A09WV -
E1
Single phase
230V,50Hz
10
RN099VHSHT
700 C-R 3.40 C-S 4.56
RA6V23-FC WHT-BLK 353 BLK-RED 321
780o540o255
34 45
735
1
0.80
350 (NEO22 )
Cooling
474/384 /306
90 —
0.17
36/31 /25
900/770 /650
2.55
1.1
1,686
3.26 745
99 24
3.04
0.22
3.27
MSC-A12WV - E1
Single phase
230V,50Hz
582/444 /324
10
0.19 40
RC4V19-KA WHT-BLK 316 BLK-RED 299 815O278O217
10
5
3 10 10
MU-A12WV -
E1
Single phase
230V,50Hz
1.6
1,914
10
4.91
— 97 29
RN135VHSHT
900 C-R 2.79 C-S 3.36
RA6V33-DC WHT-BLK 301 BLK-RED 332
780o540o255
36 49
825
1
0.83
620 (NEO22)
Cooling
92 —
0.19
40/33 /26
930/760 /600
3.45
1,100
4.60
0.31
3.03
Electrical
data
Fan
motor
Special
remarks
Compressor
Electrical
data
Fan
motor
Special
remarks
Capacity
Coefficient of performance(C.O.P)
Outdoor unit power supply
Capacity
ww
ww
w
w
w
w
w
w
w
w
w
w
ww
w
w
ww
ww
w
w
SPECIFICATION
NOTE: Test conditions are based on ISO 5151.
Cooling : Indoor DB27°C WB19°C Indoor-Outdoor piping length : 5m
w Reference value
Outdoor DB35°C WB24°C
9
Indoor model
Function
Indoor unit power supply
Air flow(High/Med. /Low ) Power outlet Running current Power input Power factor Starting current Fan motor current Model Winding resistance(at 20:) Dimensions WOHOD Weight Air direction Sound level(High/Med. /Low ) Fan speed(High/Med. /Low ) Fan speed regulator Thermistor RT11(at 25:) Thermistor RT12(at 25:) Outdoor model
Capacity Dehumidification Outdoor air flow Power outlet Running current Power input Auxiliary heater Power factor Starting current Compressor motor current Fan motor current
Model Output Winding resistance (at 20:) Model Winding resistance (at 20:) Dimensions WOHOD Weight Sound level Fan speed Fan speed regulator Refrigerant filling capacity (R410A) Refrigerating oil (Model) Thermistor RT61 (at 0:)
K /h
A
A W %
A
A
"
mm
kg
dB
rpm
k" k"
kW
R/h
K /h
A
A W
A(kW)
%
A
A
A
W
"
  
"
mm
kg dB
rpm
kg
cc
k"
MSC-A07WV -
E1
Single phase
230V,50Hz
10
0.17 35 90 —
0.17
RC4V19-LA WHT-BLK 413 BLK-RED 334 815O278O217
9 5
3 10 10
MUH-A07WV -
E1
Single phase
230V,50Hz
1,686
10
23
0.22
RN092VHSHT
600 C-R 3.87 C-S 6.14
RA6V23-FB
WHT-BLK 353
BLK-RED 321 780o540o255
35 47
735
1
0.75
350 (NEO22)
33.18
Cooling
474/372 /276
36/31 /25
900/750 /600
2.3
0.9
2.98 675
98
2.76
3.24
Heating
510/420 /342
36/31 /25
950/820 /700
2.5 —
2.86 655
100
2.64
3.62
MSC-A09WV - E1
Single phase
230V,50Hz
10
0.17 35 90 —
0.17
RC4V19-LA WHT-BLK 413 BLK-RED 334 815O278O217
9 5
3 10 10
MUH-A09WV -
E1
Single phase
230V,50Hz
1,710
10
24
0.31
RN104VHSHT
700 C-R 3.40 C-S 4.56
RA6V33-DB WHT-BLK 301 BLK-RED 332
780o540o255
38 49
825
1
1.10
350 (NEO22)
33.18
Cooling
474/384 /306
36/31 /25
900/770 /650
2.55
1.1
3.26 745
99
2.95
3.27
Heating
588/456 /342
39/32 /25
1,050/870 /700
3.05 —
3.52
805
99
3.21
3.69
MSC-A12WV - E1
Single phase
230V,50Hz
10
0.19 40 92 —
0.19
RC4V19-KA WHT-BLK 316 BLK-RED 299 815O278O217
10
5
3 10 10
MUH-A12WV -
E1
Single phase
230V,50Hz
1,710
10
29
0.31
RN135VHSHT
900
C-R 2.79
C-S 3.36
RA6V33-DB WHT-BLK 301 BLK-RED 332
780o540o255
40 49
825
1
1.15
620 (NEO22)
33.18
Cooling
582/444 /324
40/33 /26
930/760 /600
3.4
1.6
4.51
1,020
98
4.20
3.21
Heating
606/498 /396
39/33 /26
960/830 /700
3.9 —
4.61
1,040
98
4.30
3.61
Electrical
data
Fan
motor
Special
remarks
Compressor
Electrical
data
Fan
motor
Special
remarks
Capacity
Coefficient of performance (C.O.P)
Outdoor unit power supply
Capacity
ww
ww
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
NOTE: Test conditions are based on ISO 5151.
Cooling : Indoor DB27°C WB19°C Heating : Indoor DB20°C Indoor-Outdoor piping length : 5m
w Reference value
Outdoor DB35°C WB24°C Outdoor DB 7°C/WB 6°C
10
NOTE: As for specification of indoor unit, refer to page 9 (MSC-A07/A09/A12WV) or OB329 (MSC-A07/A09/A12YV).
Outdoor model Function
Outdoor unit power supply
Indoor unit No.
Capacity Dehumidification Outdoor air flow
Capacity
Power outlet Running current Power input Auxiliary heater Power factor
Electrical
data
Starting current Compressor motor current Fan motor current
kW
R/h
K /h
A A
W
A(kW)
%
A A A
Coefficient of performance (C.O.P)
Model Output Winding
Compressor
resistance (at 20:)
W
"
Model Winding
Fan
motor
resistance (at 20:) Dimensions WOHOD Weight Sound level Fan speed
"
mm
kg
dB
rpm Fan speed regulator Refrigerant filling
Special
remarks
capacity (R410A) Refrigerating oil (Model)
kg cc
NOTE: Test conditions are based on ISO 5151.
Cooling : Indoor DB27°C WB19°C Heating : Indoor DB20°C
Outdoor DB35°C WB24°C Outdoor DB 7°C/WB 6°C
Indoor-Outdoor piping length : 5m
MUX-A10WV -
Cooling
Single phase
230V,50Hz
Single
Double
A or B
2.4
0.9 1,914
10
3.20 725
98.5
21
2.91
0.29
3.16
RN092VHSHT
600 C-R 3.87 C-S 6.14
RA6V33-FC
WHT-BLK 223
BLK-RED 221 780O540O255
35 49
825
1
0.90 (Room A+B) 350 (NEO22)
E1
A+B
1.4O2
0.2O2
3.25 730
97.7
2.96
3.50
MUX-A19WV -
Cooling
Single phase
230V,50Hz
Single
A
3.5
1.4
Single
B
2.4
0.9
E1
Double
A+B
3.5+2.4
1.4+0.9
2,460
20
5.73
1,280
3.51 785
8.96
2,005
97.1
97.2
97.3
48
5.16
2.94
8.39
0.57
2.65
2.93
2.84
MC1 : RN145VHSHT, MC2 : RN092VHSHT
MC1 : 1,000, MC2 : 600
C-R 2.43
MC1 : , MC2 :
C-S 3.80
C-R 3.87
C-S 6.14
RA6V60-GA
WHT-BLK 90 BLK-RED 146 840O640O330
66 52
730
1
1.00 (Room A)
0.80 (Room B)
MC1 : 620 (NEO22), MC2 : 350 (NEO22)
11
Outdoor model Function
Capacity Dehumidification Outdoor air flow Power outlet Running current Power input Auxiliary heater Power factor Starting current Compressor motor current Fan motor current
Model Output Winding resistance (at 20:) Model Winding resistance (at 20:) Dimensions WOHOD Weight Sound level Fan speed Fan speed regulator Refrigerant filling capacity (R410A) Refrigerating oil (Model)
kW
R/h
K /h
A A
W
A(kW)
%
A A A
W
"
"
mm
kg
dB
rpm
kg cc
Single phase
230V,50Hz
Double
A+B or A+C
2.6+2.8
0.9+1.1 2,460
20
8.18
1,850
98.3 47
7.61
0.57
2.81
MC1 : RN099VHSHT, MC2 : RN125VHSHT
MC1 : 650, MC2 : 800
RA6V60-GA
WHT-BLK 90 BLK-RED 146 840O640O330
65 52
730
1
0.80 (Room A)
1.00 (Room B+C)
MC1 : 350 (NEO22), MC2 : 350 (NEO22)
MUX-A20WV -
E1
Cooling
Compressor
Electrical
data
Fan
motor
Special
remarks
Capacity
Coefficient of performance (C.O.P)
Outdoor unit power supply
Indoor unit No.
Single
A
2.6
0.9
3.64 815
97.3
3.07
3.06
Single B or C
2.9
1.2
4.86
1,075
96.2
4.29
2.61
Double
B+C
1.75O2
0.3O2
4.86
1,090
97.5
4.29
3.02
Triple
A+B+C
2.5+1.75O2
0.8+0.3O2
8.41
1,885
97.5
7.84
3.02
C-R 3.40 C-S 4.56
MC1 : , MC2 :
C-R 2.86 C-S 5.72
NOTE: As for specification of indoor unit, refer to page 9 (MSC-A07/A09/A12WV) or OB329 (MSC-A07/A09/A12YV).
NOTE: Test conditions are based on ISO 5151.
Cooling : Indoor DB27°C WB19°C Heating : Indoor DB20°C Indoor-Outdoor piping length : 5m
Outdoor DB35°C WB24°C Outdoor DB 7°C/WB 6°C
12
NOTE: As for specification of indoor unit, refer to page 9 (MSC-A07/A09/A12WV) or OB329 (MSC-A07/A09/A12YV).
E1
Outdoor model Function
Outdoor unit power supply
MUX-A25WV -
Cooling
Single phase 230V,50Hz
Indoor unit No.
Capacity Dehumidification Outdoor air flow
Capacity
Power outlet Running current Power input Auxiliary heater Power factor
Electrical
data
Starting current Compressor motor current Fan motor current
kW
R/h
K /h
A A
W
A(kW)
%
A A A
Coefficient of performance (C.O.P)
Model Output Winding
Compressor
resistance (at 20:)
W
"
Model Winding
Fan
motor
resistance (at 20:) Dimensions WOHOD Weight Sound level Fan speed
"
mm
kg dB
rpm Fan speed regulator Refrigerant filling
Special
remarks
capacity (R410A) Refrigerating oil (Model)
kg cc
NOTE: Test conditions are based on ISO 5151.
Cooling : Indoor DB27°C WB19°C Heating : Indoor DB20°C
Outdoor DB35°C WB24°C Outdoor DB 7°C/WB 6°C
Indoor-Outdoor piping length : 5m
Single A or B
3.5
1.4 2,460
20
5.88
1,300
96.1 54
5.31
0.57
2.61
MC1 : RN145VHSHT, MC2 : RN145VHSHT
MC1 : 1,000, MC2 : 1,000
C-R 2.43
MC1 : , MC2 :
C-S 3.80
C-R 2.43 C-S 3.80
RA6V60-GA
WHT-BLK 90 BLK-RED 146 840O640O330
68 52
730
1
0.95 (Room A)
0.95 (Room B)
MC1 : 620 (NEO22), MC2 : 620 (NEO22)
Double
A+B
3.5O2
1.4O2
11.49 2,540
96.1
10.92
2.67
13
Outdoor model Function
Capacity Dehumidification Outdoor air flow Power outlet Running current Power input Auxiliary heater Power factor Starting current Compressor motor current Fan motor current
Model Output Winding resistance (at 20:) Model Winding resistance (at 20:) Dimensions WOHOD Weight Sound level Fan speed Fan speed regulator Refrigerant filling capacity (R410A) Refrigerating oil (Model)
kW
R/h
K /h
A A
W
A(kW)
%
A A A
W
"
"
mm
kg dB
rpm
kg cc
Compressor
Electrical
data
Fan
motor
Special
remarks
Capacity
Coefficient of performance (C.O.P)
Outdoor unit power supply
Indoor unit No.
MUX-A26WV -
E1
Cooling
Single phase 230V,50Hz
2,760
20
52
0.53
MC1 : RN145VHSHT, MC2 : RN125VHSHT
MC1 : 1,000, MC2 : 800
RA6V60-FA WHT-BLK 79 BLK-RED 80
840O850O330
76 52
730
1
1.05 (Room A+B)
1.05 (Room C+D)
MC1 : 620 (NEO22), MC2 : 350 (NEO22)
Single A or B
3.4
1.2
5.28
1,180
97.2
4.75
2.79
Single
C or D
2.75
1.1
4.54
1,015
97.2
4.01
2.62
Double
A+B
1.95O2
0.2O2
5.46
1,210
96.4
4.93
3.02
Double
A+C or A+D
or
B+C or B+D
Triple
A+B+C
or
A+B+D
Triple
A+C+D
or
B+C+D
3.4+2.7
1.2+1.1
9.57
2,095
95.2
9.04
2.81
Double
C+D
1.7O2
0.3O2
4.78
1,060
96.4
4.25
3.01
1.95O2+2.8
0.2O2+1.1
9.61
2,105
95.2
9.08
3.02
3.4+1.7O2
1.2+0.3O2
9.66
2,140
96.3
9.13
3.02
Four
A+B+C+D
1.95O2+1.7O2
0.2O2+0.3O2
9.75
2,210
98.6
9.22
3.09
C-R 2.43
C-S 3.80
MC1 : , MC2 :
C-R 2.86 C-S 5.72
NOTE: As for specification of indoor unit, refer to page 9 (MSC-A07/A09/A12WV) or OB329 (MSC-A07/A09/A12YV).
NOTE: Test conditions are based on ISO 5151.
Cooling : Indoor DB27°C WB19°C Heating : Indoor DB20°C Indoor-Outdoor piping length : 5m
Outdoor DB35°C WB24°C Outdoor DB 7°C/WB 6°C
14
NOISE CRITERIA CURVES5
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions,
Cooling : DB27: WB19: Heating : DB20: WB -:
MSC-A07WV- E1
COOL
High
FUNCTIONFAN SPEED
36
HEAT
SPL(dB
(A)) LINE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions.
Cooling : DB27: WB19: Heating : DB20: WB -:
MSC-A09WV- E1
COOL
High
FUNCTIONFAN SPEED
36
HEAT 39
SPL(dB
(A)) LINE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions,
Cooling : DB27: WB19:
MSC-A12WV- E1
COOL
FUNCTIONFAN SPEED
40
HEAT
High
39
SPL(dB
(A)) LINE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions,
Cooling : DB27: WB19:
MU-A07WV- E1 MU-A09WV- E1
COOL
FUNCTION
45
SPL(dB(A)) LINE
15
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions, Cooling :DB35: WB24:
Heating :DB 7: WB 6:
MUH-A09WV- E1 MUH-A12WV- E1
COOL
FUNCTION
49
HEAT
SPL(dB
(A)) LINE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions.
Cooling : DB27: WB19:
MUX-A10WV- E1
COOL
FUNCTION
49
SPL(dB(A)) LINE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions,
Cooling :DB35: WB24: Heating :DB 7: WB 6:
MUH-A07WV- E1
COOL
FUNCTION
47
HEAT
SPL(dB
(A)) LINE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions,
Cooling :DB35: WB24:
MU-A12WV- E1
COOL
FUNCTION
49
SPL(dB(A)) LINE
16
MUX-A19WV - E1 MUX-A20WV - E1 MUX-A25WV - E1
FUNCTION
COOL
SPL(dB(A)) LINE
52
MUX-A26WV - E1
FUNCTION
COOL
SPL(dB(A)) LINE
52
Test conditions.
90
80
70
60
50
40
30
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
APPROXIMATE
20
TERESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
Cooling :DB35: WB24:
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
Test conditions.
90
80
70
60
50
40
30
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
APPROXIMATE
20
TERESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
Cooling :DB35: WB24:
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
17
6
OUTLINES AND DIMENSIONS
MSC-A07WV ­MSC-A09WV -
INDOOR UNIT
Unit: mm
E1
E1
Installation plate
81.5
133.5
4.5
783
815
278
60
58
162
Wireless remote controller
606
Indoor unit
19
41
81.5
Air in
149
Power supply cord Lead to right 1.0m Lead to left 0.3m
7 or more
30 Air out
215
217
326326
5
Installation plate
Liquid line Gas line
{
Insulation
90 110
Drain hose (Connected part O,D)
Insulation
231.5
42
2.5
81.5
Wall hole
[9.52-0.43m
[37 O.D
[16
[28
271
[65
[6.35-0.5m
[21 I.D
MSC-A12WV -
INDOOR UNIT
278
60
58
162
E1
783
815
606
161.5
Installation plate
Indoor unit
149
19
Power supply cord Lead to right 1.0m Lead to left 0.3m
41
Air in
7 or more
30
Air out
215
217
326326
5
Installation plate
90 110
161.5
17.5
258
218.5
42
2.5
81.581.5
Wall hole
Liquid line Gas line
{
Insulation
Drain hose (Connected part O,D)
Insulation
[65
[6.35-0.5m
[9.52-0.43m
[37 O.D
[21 I.D
[16
[28
Wireless remote controller
18
MU-A07WV - MUH-A07WV ­MU-A09WV - MUH-A09WV ­MU-A12WV - MUH-A12WV -
Unit: mm
E1E1
E1E1
E1E1
REQUIRED SPACE
OUTDOOR UNIT
320
32
109
Air in
Drainage 3holes [33
540
260
10
40
Air in
147
122
110
Air out
500 780
74
100mm or more
320
285
255
25
155
90
100mm or more
400mm or more
Service panel
Liquid refrigerant pipe joint Refrigerant pipe (flared) [6.35
35-
43-
Gas refrigerant pipe joint
104
Refrigerant pipe (flared) [9.52 (MU-A07/A09WV
[12.7 (MU-A12WV (MUH-A12WV
100mm or more
350mm or more
(MUH-A07/A09WV
)
)
)
)
19
320
25
10-
126
76
120
56
260
10
780
500
122
40
540
320
285
255
Service panel
Gas refrigerant pipe joint Refrigerant pipe (flared) [9.52
Liquid refrigerant pipe joint Refrigerant pipe (flared) [6.35
Air out
Air in
Air in
176
226
109
32
110
147
Drainage 3holes [33
100mm or more
100mm or more
100mm or more
350mm or more
REQUIRED SPACE
400mm or more
OUTDOOR UNIT
500
840 61
264
10°
10°
Service panel
Open as a rule 500mm or more if the front and both sides are open
100mm or more 200mm or more if there are obstacles to both sides
Open as a rule 500mm or more if the back, both sides and top are open
350mm or more
100mm or more
B UNIT A UNIT
Gas refrigerant pipe joint Refrigerant pipe (flared) {9.52
Gas refrigerant pipe joint Refrigerant pipe (flared) {12.7
Liquid refrigerant pipe joint Refrigerant pipe (flared) {6.35
65 80
121
40
438
Air in
Air out
Air in
273
100
125
320
30
330
640
360
76
505050
Drainage 3holes {33
} }
34
Unit: mm
MUX-A10WV-
E1
MUX-A19WV-
E1
20
OUTDOOR UNIT
MUX-A20WV-
Drainage 3holes {33
34
125
Air in
100
320
E1
273
500
438
Air in
30
Air out
840 61
121
Unit: mm
Open as a rule 500mm or more if the front and both sides are open
100mm or more
100mm or more
330
360
Open as a rule 500mm or more if the back,
40
640
65
both sides and top are open
10°
10°
264
Service panel
Liquid refrigerant pipe joint Refrigerant pipe (flared) {6.35
C UNIT
}
B UNIT
}
A UNIT
}
5050505050
76
Gas refrigerant pipe joint Refrigerant pipe (flared) {9.52
200mm or more if there are obstacles to both sides
350mm or more
MUX-A25WV-
Drainage 3holes {33
125 Air in
273
34
100
320
E1
500
438
Air in
30
330
40
Air out
840 61
121
640
80
100mm or more
360
Open as a rule 500mm or more if the back, both sides and top are open
10°
10°
264
B UNIT
}
A UNIT
}
Open as a rule 500mm or more if the front and both sides are open
100mm or more 200mm or more if there are obstacles to both sides
350mm or more
Service panel
Liquid refrigerant pipe joint Refrigerant pipe (flared) {6.35
505050 76
Gas refrigerant pipe joint Refrigerant pipe (flared) {12.7
21
SYMBOL
NR11
RT11
RT12
SR141
NAME
NAME NAME INDOOR FAN CAPACITOR FUSE(3.15A) INDOOR FAN MOTOR (INNER FUSE) VANE MOTOR
VARISTOR ROOM TEMPERATURE THERMIST OR INDOOR COIL THERMISTOR SOLID STATE RELAY
TERMINAL BLOCK
SYMBOL
C11
F11
MF MV
SYMBOL
TB
T11
TRANSFORMER
CIRCUIT BREAKER
SR141
C11
RED
WHT
3
6
5
BRN
YLW
GRY
BLK
4
3
2
1
MF
121
CN
1 3 5
111
CN
112
CN
RT12
RT11
NR11
F11
ELECTRONIC CONTROL P.C. BOARD
CN211
TAB12
CN201
3 2 1
CN202
2 1
151
CN
5
5
BRN RED
BLU
WHT BLK
BLU
BRN
TB
L 3 N 2 1
12V
TO OUTDOOR UNIT CONNECTING
POWER SUPPLY CORD ~/N 230V 50Hz
GRN/YLW
POWER MONITOR, RECEIVER P.C.BOARD
REMOTE CONTROLLER
MV
FOR MUH OR MXZ TYPE
FOR MU OR MUX TYPE
12V
PE
101
CN
T11
GRN
LD103
OUTDOOR UNIT
330
850
E1
125
Air in
430
MUX-A26WV-
Drainage 3 holes
{33
100
273
438
Air in
Air out
121
Open as a rule 500mm or more if the front and both sides are open
40
34
30
500
840
100mm or more
360
Open as a rule
65
500mm or more if the back,
61
both sides and top are open
10°
10°
Gas refrigerant pipe joint Refrigerant pipe (flared) {9.52
80
Gas refrigerant pipe joint Refrigerant pipe (flared) {12.7
260
Service panel
Liquid refrigerant pipe joint Refrigerant pipe (flared) {6.35
D Unit
50 50
C Unit
5050
B Unit
50 50
A Unit
50
76
100mm or more 200mm or more if there are obstacles to both sides
350mm or more
Unit: mm
7
WIRING DIAGRAM
MSC-A07WV - MSC-A09WV - MSC-A12WV -
INDOOR UNIT
NOTE:1. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate.
/: Terminal block, : Connector
MODELS WIRING DIAGRAM
22
E1E1E1
SYMBOL TB1,TB2
21S4
52C
SYMBOL
MF NR61 RT61
SR61,SR62
T61
SYMBOL
C1
C65
DSAR
F61
MC
NAME
NAME NAME COMPRESSOR CAPACITOR OUTDOOR FAN CAPACITOR SURGE ABSORBER FUSE(2A) COMPRESSOR(INNER PROTECTOR)
OUTDOOR FAN MOTOR(INNER FUSE) VARISTOR DEFROST THERMISTOR SOLID STATE RELAY TRANSFORMER
TERMINAL BLOCK R.V. COIL COMPRESSOR CONTACTOR
MU-A07WV ­MU-A09WV ­MU-A12WV -
E1
E1
E1
OUTDOOR UNIT
FROM INDOOR UNIT
CONNECTING
12V
POWER SUPPLY ~/N 230V 50Hz
MODELS WIRING DIAGRAM
TB2
2
WHT
1
BLK
CIRCUIT BREAKER
TB1
PE
L
BRN
N
BLU
GRN/YLW
NO
52C
52C
COM
BRN WHT WHT
C2
DSAR
C1
WHT BLU RED
RED BLK
1 2 3
WHT
BLK
RED
C
MC
S
R
MF
SYMBOL
C1 C2
DSAR
NOTE:1. About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
COMPRESSOR CAPACITOR OUTDOOR FAN CAPACITOR SURGE ABSORBER
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate. /: Terminal block, : Connector
MUH-A07WV ­MUH-A09WV ­MUH-A12WV -
NAME
SYMBOL
MC
MF
TB1,TB2
E1
E1
E1
MODELS WIRING DIAGRAM
NAME NAME COMPRESSOR(INNER PROTECTOR) OUTDOOR FAN MOTOR(INNER FUSE) TERMINAL BLOCK
OUTDOOR UNIT
DSAR
TAB20
RT61
1 2 3
CN661
CN730
F61
T61
4
52C
3
C1
FROM INDOOR UNIT CONNECTING 12V
CIRCUIT BREAKER
POWER SUPPLY
~/N
50Hz
230V
PE
TB2
3
N
TB1
L
N
BLU
GRN/YLW
RED
BLK
BRN
BRN
BLU
SYMBOL
52C
R.V.coil
21S4
heating ON cooling OFF
CN721
SR62
SR61
NR61
DEICER P.C.BOARD
RED
BLK
COMPRESSOR CONTACTOR
CN711
C65
WHT
MC
S
MF
WHT
1
BLK
2
RED
3
C
R
NOTE:1. About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate. /: Terminal block, : Connector
23
MUX-A10WV -
E1
OUTDOOR UNIT
POWER SUPPLY
~ / N 230V 50Hz
CIRCUIT BREAKER
FROM INDOOR UNIT No.A CONNECTING
12V
FROM INDOOR UNIT No.B CONNECTING
12V
2
1
MODEL WIRING DIAGRAM
TB1
2 1
L
N
PE
TB2
WHT
X1
BLK YLW
X2
ORN
7
8 7
8
BRN
BRN
DSAR
21R1
21R2
BLU
BLU
BLU
BLU
BLU
BLU
BLU
2 1
2 1
NO
BRN
2
BLU BLU
BLU
BLU
52C
52C
1
2
TB3
F61
BLU
COM
BRN
BLU
WHT
5
6
5
6
X1
X1
X2
X2
F62
1
2
4
1
3 2 4
WHT
1
WHT
3
TB3
WHT
C2
C1
WHT BLU RED
RED
1
2 3
S
BLK
WHT
BLK
RED
C MC
MF
R
BRN BRN BRN
WHT
BLU
BLU
2 1
BLU
21R
SYMBOL
C1 C2
DSAR
F61,F62
MC
NOTE:1. About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
COMPRESSOR CAPACITOR OUTDOOR FAN CAPACITOR SURGE ABSORBER FUSE(2A) COMPRESSOR(INNER PROTECTOR)
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate. /: Terminal block, : Connector
NAME
SYMBOL
MF
TB1,TB2,TB3
X1 X2
21R
OUTDOOR FAN MOTOR(INNER FUSE) TERMINAL BLOCK RELAY(A) RELAY(B) SOLENOID COIL
NAME NAME
SYMBOL
21R1 21R2
52C
SOLENOID COIL(A) SOLENOID COIL(B) COMPRESSOR CONTACTOR
24
MUX-A19WV ­MUX-A25WV -
OUTDOOR UNIT
E1
E1
MODELS WIRING DIAGRAM
POWER SUPPLY ~/N
TB1
L
230V 50Hz
N
BRN
PE
CIRCUIT BREAKER
GRN/YLW
FROM INDOOR UNIT A CONNECTING
2 1
TB2
BLU YLW
12V FROM INDOOR
2
BLU
UNIT B CONNECTING
1
ORN
12V
SYMBOL
C1 C2
C61
DSAR
F61
NOTE:1. About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
COMPRESSOR CAPACITOR(MC1) COMPRESSOR CAPACITOR(MC2) OUTDOOR FAN CAPACITOR SURGE ABSORBER FUSE(3.15A)
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate. /: Terminal block, : Connector
NAME
BRN BLU
TB4
2
1
DSAR
3 2 1
3 2 1
SYMBOL
BLU
CN71
CN73
CN91
MC1
MC2 MF61 NR61
SR861
BRN
123
CN90
OUTDOOR CONTROL P.C. BOARD
F61
NR61
T61
SR861
52341
6
BLK
WHT
RED
MF61
COMPRESSOR(INNER PROTECTOR) COMPRESSOR(INNER PROTECTOR) OUTDOOR FAN MOTOR (INNER PROTECTOR) SURGE ABSORBER OUTDOOR FAN RELAY
LD1
LD2
RED
RED
C61
NAME NAME
BRN
X522
BRN
X521
3
4
X521X522
SYMBOL
TB1
TB2~TB4
T61 X521 X522
C1
BLU
RED
S
MC1
BLK
BLU
R
C
WHT
3
4
C2
RED
S
MC2
RC
BLK
WHT
TERMINAL BLOCK TERMINAL BLOCK TRANSFORMER COMPRESSOR CONTACTOR(MC1) COMPRESSOR CONTACTOR(MC2)
25
1
2
3
1
2
3
123
213
123123123
21R421R3
NR61
T61
1
2
43
43
C61
LD1
WHT
WHT
OUTDOOR CONTROL P.C. BOARD
BRN
BLU
BRN
BLU
BRN
BLU
BLU
X522
X521
BLK
SR865
SR866
SR863
SR861
LD2
RED
RED
RED
BLK
WHT
652341
BRN BLU
BLU
TB4
CN86
CN85
CN81
CN91
CN90
TB3
TB2
X521
BLU
BLU
X522
BLU
BLU
21RB
F61
CN74
CN73
CN71
FROM INDOOR
UNIT B
CONNECTING
12V
PE
CIRCUIT BREAKER
GRN/YLW
WHT
BLU
ORN
BLU
YLW
BLU
RED
RED
FROM INDOOR
UNIT A
CONNECTING
12V
1
2
1
2
C2
C1
RC
S
CR
S
MC2
FROM INDOOR
UNIT C
CONNECTING
12V
MF61
MC1
BLK
TB1
POWER SUPPLY
~/N
230V
50Hz
1
2
L
N
DSAR
BRN
MUX-A20WV -
E1
OUTDOOR UNIT
MODEL WIRING DIAGRAM
TERMINAL BLOCK
TRANSFORMER
COMPRESSOR CONTACTOR(MC1)
COMPRESSOR CONTACTOR(MC2)
SOLENOID COIL
SOLENOID COIL (B)
SOLENOID COIL (C)
T61
SYMBOL
TB2~TB4
NAME NAME
X521
X522
21R3
21RB
21R4
OUTDOOR FAN MOTOR(INNER PROTECTOR)
SURGE ABSORBER
OUTDOOR FAN RELAY
RELAY (21RB)
RELAY (C) (21R4)
RELAY (B) (21R3)
MF61
NR61
SYMBOL
SR861
SR863
SR865
SR866
TERMINAL BLOCK
TB1
NAME
COMPRESSOR CAPACITOR(MC1)
COMPRESSOR CAPACITOR(MC2)
C1
C2
SYMBOL
OUTDOOR FAN CAPACITOR
SURGE ABSORBER
FUSE(3.15A)
COMPRESSOR(INNER PROTECTOR)
COMPRESSOR(INNER PROTECTOR)
F61
C61
DSAR
MC1
MC2
2. Use copper conductors only. (For field wiring)
/: Terminal block, : Connector
3. Symbols below indicate.
NOTE:1. About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
26
MUX-A26WV -
E1
OUTDOOR UNIT
S
MC1
RC
C1
BLK
BLU
BRN
BLU
DSAR
BRN
X521
OUTDOOR CONTROL P.C. BOARD
CN90 13 2
BLU
GRN/YLW
BRN
TB4
BRN
2
BRN
RED
BLU
1
BLU
MODEL WIRING DIAGRAM
S
MC2
RC
BLK
T61
NR61
113
ORN
BLU
WHT
SR863
SR864
SR865
SR866
SR867
SR868
SR861
2
BRN
WHT
RED
C2
34
43
F61
BLU
X522 X521
2
3
X522
CN74CN73CN72CN71
2
3
1
WHT
BLU
BLU
21RB
BLU
123
BLU
21RA
BLU
123
BLU
21R4
123
BLU
BLU
21R3
123
BLU
BLU
21R2
BLU
BLU
123 123
BLU
RED
LD1
RED
LD2
621
RED
435
BLK
WHT
CN91
21R1
C61
MF61
CN83 CN84 CN85 CN86 CN81CN82
2
1
3
YLW
COMPRESSOR CONTACTOR(MC1)
COMPRESSOR CONTACTOR(MC2)
X521
X522
SYMBOL
NAME NAME
OUTDOOR FAN RELAY
RELAY (21RB)
SR861
SR863
SYMBOL
SOLENOID COIL (BALANCE)
SOLENOID COIL (BALANCE)
SOLENOID COIL (A)
21R1
21RA
21RB
RELAY (21RA)
RELAY (D) (21R4)
RELAY (C) (21R3)
RELAY (B) (21R2)
SR864
SR865
SR866
SOLENOID COIL (B)
SOLENOID COIL (C)
21R2
21R3
RELAY (A) (21R1)
SR867
SR868
SOLENOID COIL (D)
21R4
TERMINAL BLOCK
TRANSFORMER
T61
TB1~TB4
NAME
TB1
L
PE
112
CONNECTING
UNIT C
12V
TB3
CONNECTING
FROM INDOOR
UNIT B
12V
1
2
FROM INDOOR
CONNECTING
UNIT A
12V
CIRCUIT BREAKER
50Hz
TB2
2
FROM INDOOR
CONNECTING
UNIT D
1
12V
2
FROM INDOOR
N
~/N
230V
POWER SUPPLY
COMPRESSOR CAPACITOR(MC1)
COMPRESSOR CAPACITOR(MC2)
C1
C2
SYMBOL
OUTDOOR FAN CAPACITOR
SURGE ABSORBER
FUSE(3.15A)
COMPRESSOR(INNER PROTECTOR)
COMPRESSOR(INNER PROTECTOR)
F61
C61
DSAR
MC1
MC2
OUTDOOR FAN MOTOR(INNER PROTECTOR)
SURGE ABSORBER
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate.
MF61
NR61
NOTE:1. About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
/: Terminal block, : Connector
27
8
REFRIGERANT SYSTEM DIAGRAM
MSC-A07WV ­MSC-A09WV -
Unit:mm
E1
E1
MU-A07WV ­MU-A09WV -
E1
E1
INDOOR UNIT
Indoor heat exchanger
Room temperature thermistor RT11
Indoor coil thermistor RT12
Refrigerant pipe [9.52 (with heat insulator)
Flared connection
Flared connection
Refrigerant pipe [6.35 (with heat insulator)
OUTDOOR UNIT
Stop valve (with service port)
Muffler
Outdoor heat exchanger
Compressor
Strainer
Capillary tube
[3.0x[1.4x500(MU-A07WV) [3.0x[1.4x700(MU-A09WV)
Refrigerant flow in cooling
Unit:mm
MSC-A12WV -
INDOOR UNIT
Indoor heat exchanger
Room temperature thermistor RT11
E1
Indoor coil thermistor
RT12
Refrigerant pipe [12.7 (with heat insulator)
Flared connection
Flared connection
Refrigerant pipe [6.35 (with heat insulator)
Stop valve (with service port)
Stop valve
Compressor
Capillary tube [3.0x[1.4x550
MU-A12WV -
OUTDOOR UNIT
Muffler
Outdoor heat exchanger
Strainer
Refrigerant flow in cooling
E1
28
MSC-A07WV ­MSC-A09WV -
INDOOR UNIT
Unit:mm
E1
E1
Refrigerant pipe [ 9.52
(with heat insulator)
4-way valve
MUH-A07WV ­MUH-A09WV -
OUTDOOR UNIT
E1
E1
Indoor heat exchanger
Indoor coil thermistor RT12
Room temperature thermistor RT11
MSC-A12WV -
Defrost thermistor RT61
Outdoor heat exchanger
Flared connection
Stop valve (with service port)
Muffler
Capillary tube [3.0x[1.4x800(2 pcs)
(MUH-A07WV) [3.0x[1.4x500(2 pcs)
(MUH-A09WV)
R.V. coil heating ON cooling OFF
Flared connection
Strainer
Stop valve
Compressor
Capillary tube
[3.0x[1.6x350(MUH-A07WV) [3.0x[1.6x600(MUH-A09WV)
Check valve
Capillary tube [3.0x[1.4x1050(MUH-A07WV)
Refrigerant pipe [6.35
(with heat insulator)
[3.0x[1.4x1300(MUH-A09WV)
Refrigerant flow in cooling Refrigerant flow in heating
Unit:mm
E1
MUH-A12WV -
E1
INDOOR UNIT
Indoor heat exchanger
Room temperature thermistor RT11
Indoor coil thermistor RT12
Refrigerant pipe [12.7
(with heat insulator)
Flared connection
Flared connection
Refrigerant pipe [6.35
(with heat insulator)
4-way valve
Stop valve (with service port)
Strainer
Stop valve
Muffler
Compressor
Capillary tube [3.0x[1.6x1350
Check valve
Defrost thermistor RT61
OUTDOOR UNIT
Outdoor heat exchanger
Capillary tube [3.0x[1.4x500(2pcs)
Capillary tube [3.0x[1.6x400
R.V. coil heating ON cooling OFF
Refrigerant flow in cooling Refrigerant flow in heating
29
Piping size O.D : mm Length of connecting pipe : m
Model
Piping size O.D : mm Length of connecting pipe : m
Model
Refrigerant piping
Max. length : m
A
20
25
Indoor unit
Gas 0.43
Liquid 0.5
Gas
9.52
12.7
Liquid
6.35
Outdoor unit
Gas 0
Liquid 0
MSC-A07WV - E1 MUH-A07WV - E1
MSC-A09WV - E1 MUH-A09WV - E1
MSC-A12WV - E1 MUH-A12WV - E1
{ {
{
Refrigerant piping
Max. length : m
A
20
25
Indoor unit
Gas 0.43
Liquid 0.5
Gas
9.52
12.7
Liquid
6.35
Outdoor unit
Gas 0
Liquid 0
MSC-A07WV - E1 MU-A07WV - E1
MSC-A09WV - E1 MU-A09WV - E1
MSC-A12WV - E1 MU-A12WV - E1
{ {
{
Indoor unit
w Max. Height difference 10m
Height difference should be within 10m regardless of which unit, indoor or outdoor position is high.
Outdoor unit
Refrigerant Piping
Max.length
A
Model
Refrigerant piping length (one way)
Model
Refrigerant piping length (one way)
7m
0
10m
60
15m
160
20m
260
MSC-A07WV - E1 MUH-A07WV - E1
MSC-A09WV - E1 MUH-A09WV - E1
MSC-A12WV - E1 MUH-A12WV - E1
{
{
{
Calculation : Xg=20g/m 5 x(A-7)m
Outdoor unit precharged
750
800
830
25m
360
25m
360
7m
0
10m
60
15m
160
20m
260
MSC-A07WV - E1 MU-A07WV - E1
MSC-A09WV - E1 MU-A09WV - E1
MSC-A12WV - E1 MU-A12WV - E1
{ {
{
Calculation : Xg=20g/m x(A-7)m
Outdoor unit precharged
750
1100
1150
MAX. REFRIGERANT PIPING LENGTH
MAX. HEIGHT DIFFERENCE
ADDITIONAL REFRIGERANT CHARGE(R410A : g)
30
Loading...
+ 98 hidden pages