SPLIT-TYPE, AIR CONDITIONERS
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
Revision:
• MSC-07RV-, MSC-09RV-and MSC-12RV-have been
added.
• This service manual covers only change points.
Please refer to the service manual OB227 REVISED
EDITION-B for unchanged contents.
OB227 REVISED EDITION-B describes only for the indoor unit
and the connected outdoor unit of MU, MUH, MUX and MXZ
series.
• Please refer to the below service manual as for following models.
MXZ-32SV-: OB254
MXZ-18TV-: OB280
MUX-19TV-, MUX-20TV-and MUX-25TV-: OB284
PUMY-P125YMA and others : OC272 and others, and OC296
R-CONVERTER UNIT
8. PARTS LIST ·····················································27
1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
The specifications of indoor and outdoor fan motor
The data of Med. and Low speed have been added to indoor
fan motor specification as reference.
✼
✼The data value of indoor fan motor does not change even if
the indoor unit is connected to a multi-type or PUMY series
outdoor unit.
Remote controllers of COOL ONLY or COOL & HEAT
type are outdoor unit accessory.
Remote controller is included as an indoor unit accessory.
Two-way common remote controller
Two-way (using dip switch) remote controller
The specification of electronic control P.C. board is
compatible with remote controllers of COOL ONLY
and COOL & HEAT type.
Indoor electronic control P.C. board has changed
for two-way remote controller.
Indoor electronic control P.C. board has changed
for two-way remote controller.
Microprocessor programming flow has changed.
Indoor electronic control P.C. board for E3 is interchangeable
with the one for E2 except for MSC-12RV.
(New P.C. board) Indoor electronic control P.C. board has
changed.
Earth wire from the board is fixed to the electrical box with screw.
The shape of connector CN211 has changed. Indoor electronic
control P.C. board has been connected with
power monitor, receiver P.C. board using connector.
Indoor electronic control P.C. board has changed.
Microprocessor programming flow has changed to make the
communication between indoor unit and R-CONVERTER
possible.
Indoor unit gets to be connected to outdoor unit of PUMY
series (PUMY-P125YMA and others).
However, R-CONVERTER UNIT is necessary to connect
PUMY series.
Indoor electronic control P.C. board for E5 is interchangeable
with the one for E4.
The setting of fan speed control when fan speed is set to
"Auto" in COOL operation has been improved in order to
reach the set temperature faster than E1, E2, and E3.
The mark of terminal block has changed. Terminal block for E4
or E5 is interchangeable with the ones for E1, E2 and E3.
Winding resistance and shape of indoor fan motor have
changed. Indoor fan motor for E4 or E5 is not interchangeable
with the ones for E1, E2 and E3 except for MSC-12RV.
As for spare indoor fan motors for MSC-07/09RV-E1, E2, E3,
E4 and MSC-07/09RV-E5 are the same.
Fan motor rubber mount has changed from E3 because
the shape of fan motor was changed.
As for spare fan motor rubber mount sets for MSC-07/09/12RVE1, E2, E3, E4 and MSC-07/09/12RV-E5 are the same.
Circle shows the change point of the model.
Change point
No.
MSC-07RV-
E1
E2
E3
MSC-09RV-
E1
E2
E3
MSC-12RV-
E1
E2
E3E4E4
E4
E5
E5
E5
TECHNICAL CHANGES
3
1
2
3
4
5
6
7
8
9
10
11
12
13
Remote controller of COOL ONLY type is outdoor unit accessory.
Remote controller is included as an indoor unit accessory.
Compressor contactor (52C) has changed. Compressor
contactor for E2,E3,E4 are interchangeable with the ones for E1.
Compressor has changed. Compressors for E3 and E4 are not
interchangeable with the ones for E1 and E2.
Compressor capacitor has changed. Due to different shape,
compressor capacitor for E4 is not interchangeable with the
ones for E1, E2 and E3.
Fuse has been removed.
Wiring diagram has changed because fuse was removed.
The shape of propeller fan has changed. The number of
propeller fan has changed from four to three. Propeller fan for E4
is not interchangeable with the ones for E1, E2 and E3.
The shape, diameter of axis and fan speed of fan motor have
changed. Fan motor for E4 is not interchangeable with the ones
for E1, E2 and E3.
Fan motor capacitor has changed. 1.5+➔ 2.0+
Fan motor capacitor for E4 is not interchangeable with the
ones for E1, E2 and E3(MU-12RV only).
Refrigerant filing capacity has changed. 0.85kg➔ 0.80kg
The method of troubleshooting for outdoor unit has changed.
The repairing procedure when outdoor unit does not stop
has been added to troubleshooting.
Circle shows that change points apply to the models.
Change point
No.
MU-07RV-
E1
E2
E3
MU-09RV-
E1
E2
E3
MU-12RV-
E1
E2
E3
E4
E4
E4
4
No.
Remote controller of COOL & HEAT type is outdoor unit
1
accessory.
Remote controller is included as an indoor unit accessory.
2
Accumulator has been removed.
3
Compressor has changed.
4
Compressor capacitor has changed. Due to different
shape, compressor capacitor for E4 is not interchangeable
5
with the ones for E1,E2 and E3.
The mark of terminal block has changed. Terminal block
6
for E4 is interchangeable with the ones for E1, E2 and E3.
Deicer P.C. board has changed. Jumper wire of compulsory
defrosting mode has changed.
Jumper wire for defrost setting has changed.
(JPC-JPE➔JRF-JRG) (Refer to page 26.)
7
The defrosting intervals which are changed by setting a short
circuit are the same as E1, E2, and E3.
Deicer P.C. board for E4 is not interchangeable with the
ones for E1, E2 and E3.
Wiring diagram has changed according to the following
reasons; the shape of connectors CN711 and CN661 has
8
changed and R.V. coil relay (X62) has changed into SSR (SR62).
X62 has changed into SR62 in Example of Operation
time chart in HEAT operation.
9
Compared to E1, E2, and E3, no change has been made about
the operational condition for defrosting and tne control system of
R.V. coil (timing of switching on/off).
The shape of propeller fan has changed. The number of
propeller fan has changed from four to three. Propeller
10
fan for E4 is not interchangeable with the ones for E1,E2, and E3.
The shape and diameter of axis of fan motor have changed.
The shape of connector has changed.
11
Fan motor and connector for E4 are not interchangeable
with those for E1, E2 and E3.
Refrigerant filling capacity has changed. 0.80kg➔ 0.85kg
12
The method of checking serial signal error for E4 has been added.
13
The method of troubleshooting for outdoor unit has changed.
14
The method for checking thermistor has been added to
15
troubleshooting.
The method for checking 4-way valve has been added to
16
troubleshooting.
The repairing procedure when outdoor unit does not stop has
17
been added to troubleshooting.
Change point
(JP607-R853➔JPDS-JPSG)
Circle shows that change points apply to the models.
MUH-07RV-
E1
E2
E3
E4
MUH-09RV-
E1
E2
E3
E4
MUH-12RV-
E1
E2
E3
E4
MUX-10RV MUX-18RV MUX-24RV MXZ-18RV -
E1
E1
E1
E1
MUX-10RV MUX-18RV MUX-24RV MXZ-18RV -
E2
E2
E2
E2
1. Remote controller is unprovided as the outdoor unit accessory.
5
COOL ONLY
COOL
& HEAT
TWO-WAY
REMOTE CONTROLLER
Model
MS-07/09/12RV-
E1
MSH-07/09/12RV-
E1
MS-07/09/12RV-
E2
MSH-07/09/12RV-
E2
✕
✕
✕
✕
w
w When HEAT mode is selected
by the remote controller of
COOL & HEAT type, the unit
will operate in FAN mode.
1. Both of COOL ONLY and COOL & HEAT remote controller are unified into a two-way remote controller.
2. FAN mode operation is available in COOL ONLY unit. In this case the set room temperature
will be displayed on the remote controller, however, the room temperature can not be controlled by remote controller button.
HEAT operation is available in only HEAT & COOL type unit.
• The way of remodelling individual operation of P.C Board of remote controller has changed.
No. 1 unit
No. 2 unit
No. 3 unit
No. 4 unit
1 unit operation
No modification
–
–
–
2 units operation
Same as at left
Solder J1
–
–
3 units operation
Same as at left
Same as at left
Solder J2
–
4 units operation
Same as at left
Same as at left
Same as at left
Solder both J1 and J2
A maximum of 4 indoor units with wireless remote controllers can be used in a room.
In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be
modified according to the number of the indoor unit.
How to modify the remote controller P.C. board
Remove batteries before modification.
The board has a print as shown below :
NOTE : For remodelling, take out the bat-
teries and press the
OPERATE/STOP(ON/OFF)button
twice or 3 times at first.
After finish remodelling, put back
the batteries then press the
RESET button.
The P.C. board has the print “J1” and “J2”. Solder “J1” and “J2” according to the number of indoor unit as shown
in Table 1. After modification, press the RESET button.
Table 1
REMOTE CONTROLLER (How to set the type)
This remote controller setting needs to be switched according to the type of air conditioner (COOL & HEAT or COOL
ONLY).
If the setting is incorrect, the air conditioner does not operate normally. Therefore, check if the setting corresponds to
the type of air conditioner. If it does not, correct the setting as shown below.
Slide switch
Type
The position
of the slide
switch
COOL ONLYCOOL & HEAT
7
Installation plate
Installation plate fixing screw 4 o 25 mm
Remote controller mounting hardware
Fixing screw for 3 3.5 o 16 mm
Battery (AAA) for remote controller
Felt tape (Used for left or left-rear piping)
Deodorizing filter
Air cleaning filter
Wireless remote controller
Drain socket: MUH type
Drain cap: MUH type
1
1
2
1
5
1
2
2
1
1
1
<Indoor unit>
Installation plate
Installation plate fixing screw 4 o 25 mm
Remote controller mounting hardware
Fixing screw for 3 3.5 o 16 mm
Battery (AAA) for remote controller
Wireless remote controller
Felt tape (Used for left or left-rear piping)
Deodorizing filter
Air cleaning filter
Drain socket
Drain cap
1
2
1
5
1
2
2
1
1
1
1
<Indoor unit>
<Outdoor unit: MUH type>
<Outdoor unit>
9
0
1
1
2
3
4
5
6
7
8
0
1
1
2
3
4
5
6
7
8
9
• How to replace batteries
Insert the negative pole
of the batteries first.
Check if the polarity of
the batteries are correct.
HEAT
/FAN
/
RESET button
HEAT
/FAN
/
Weak batteries may cause the remote controller malfunction.
In this case, replace the batteries to operate the remote controller normally.
1 Remove the front lid and insert batteries.
2 Press the RESET button.
Then reattach the front lid.
NOTE : If the RESET button is not pressed, the remote controller may not operate correctly.
Air flow(High/Med. /Low )
Power outlet
Running current
Power input
Power factor
Starting current
Fan motor current
Model
Winding
resistance(at20:)
Dimensions WOHOD
Weight
Air direction
Sound level(High/Med. /Low )
Fan speed (High/Med. /Low )
Fan speed regulator
Thermistor RT11(at25:)
Thermistor RT12(at25:)
Outdoor model
Capacity
Dehumidification
Outdoor air flow
Power outlet
Running current
Power input
Auxiliary heater
Power factor
Starting current
Compressor motor current
Fan motor current
Model
Output
Winding
resistance(at20:)
Model
Winding
resistance(at20:)
Dimensions WOHOD
Weight
Sound level
Fan speed
Fan speed regulator
Refrigerant filling
capacity(R22)
Refrigerating oil (Model)
Air flow(High/Med. /Low )
Power outlet
Running current
Power input
Power factor
Starting current
Fan motor current
Model
Winding
resistance(at20:)
Dimensions WOHOD
Weight
Air direction
Sound level(High/Med. /Low )
Fan speed(High/Med. /Low )
Fan speed regulator
Thermistor RT11(at25:)
Thermistor RT12(at25:)
Outdoor model
Capacity
Dehumidification
Outdoor air flow
Power outlet
Running current
Power input
Auxiliary heater
Power factor
Starting current
Compressor motor current
Fan motor current
Model
Output
Winding
resistance(at20:)
Model
Winding
resistance(at20:)
Dimensions WOHOD
Weight
Sound level
Fan speed
Fan speed regulator
Refrigerant filling
capacity(R22)
Refrigerating oil (Model)
Thermistor RT61(at0:)