This document is protected by the law of copyright, whereby all rights established therein remain with the company Mitsubishi
Electric Corporation. Reproduction of this document or parts of this document is only permissible within the limits of the legal
determination of Copyright Law. Alteration or abridgement of the document is not permitted without the explicit written
approval of the company Mitsubishi Electric Corporation.
PRECAUTIONS REGARDING WARRANTY
This product is jointly developed and manufactured with Molex. Thus, warranty information is different from that of other
MELSEC products. Check the restrictions described below and purchase the product.
Gratis Warranty Term
Warranty period is one year after delivery. (Maximum of 18 months after produced)
Repair and Analysis
Please note that repairs and failure analysis are refused due to the structure of this product. Therefore, free replacement is
arranged for the failure of our responsibility during the warranty period.
1
Page 4
SAFETY PRECAUTIONS
WARNING
Indicates that incorrect handling may cause hazardous conditions, resulting in
death or severe injury.
CAUTION
Indicates that incorrect handling may cause hazardous conditions, resulting in
minor or moderate injury or property damage.
(Read these precautions before using this product.)
Before using this product, please read this manual and the relevant manuals carefully and pay full attention to safety to handle
the product correctly.
The precautions given in this manual are concerned with this product only. For the safety precautions of the programmable
controller system, refer to the user's manual for the CPU module used.
In this manual, the safety precautions are classified into two levels: "WARNING" and "CAUTION".
Under some circumstances, failure to observe the precautions given under "CAUTION" may lead to serious
consequences.
Observe the precautions of both levels because they are important for personal and system safety.
Make sure that the end users read this manual and then keep the manual in a safe place for future reference.
[Design Precautions]
WARNING
● When the safety remote I/O module detects an error in an external power supply or a failure in the
odule, it turns off the outputs. Configure an external circuit to ensure that the power source of
m
azard is shut off by turning off the outputs. Failure to do so may result in an accident due t
h
i
ncorrect output or malfunction.
● When a load current exceeding the rated current or an overcurrent caused by a load short-circuit
flows, the safety remote I/O module defines it as a fault and turns off the outputs. Note that if the
vercurrent state continues for a long time, it may cause smoke and fire. To prevent this, configure a
o
ternal safety circuit, such as a fuse.
ex
● At the start-up of the system, if the load power supply is short-circuited by the output wiring of t
sa
fety remote I/O module, a load may turn on just after the power-on. Configure an interlock circuit to
ensure that the entire system will always operate safely.
● When a communication failure occurs in the network, data in the master module are held. Check Dat
ink status (each station) (SW00B0 to SW00B7) and configure an interlock circuit in the program t
l
e
nsure that the entire system will operate safely.
● When a communication failure occurs in the network, the failed station becomes the following status
Check the communication status information and configure an interlock circuit in the program to
ensure that the entire system will operate safely. Failure to do so may result in an accident due t
ncorrect output or malfunction.
i
(1) All inputs from remote I/O stations are turned off.
(2) All outputs from remote I/O stations are turned off.
● Do not use any "use prohibited" signals as a safety remote I/O signal and a remote control/monitor
signal since they are used by the system. If any of the "use prohibited" signals are used (turned on or
off), the correct operation of the module cannot be guaranteed.
● Do not read/write data from/to the remote register since all areas of the remote register are "u
p
rohibited" areas. If data is read or written from/to the remote register, correct operation of the modul
cannot be guaranteed.
a
o an
he
o
o an
se
n
a
.
e
2
Page 5
[Design Precautions]
CAUTION
● Do not install the control lines or communication cables together with the main circuit lines or power
cables. Keep a distance of 100mm or more between them. Failure to do so may result in malfunction
due to noise.
● Select the external devices to be connected to the module by referring to the performance
specifications in this manual and considering the maximum inrush current. Connecting a device
exceeding the maximum inrush current may cause malfunction or failure of the module.
● During control of an inductive load such as a lamp, heater, or solenoid valve, a large current
(approximately ten times greater than normal) may flow when the output is turned from off to on.
Therefore, use a module that has a sufficient current rating.
[Installation Precautions]
WARNING
● Shut off the load power supply (all phases) used in the system before mounting or removing a
module. Failure to do so may result in electric shock or cause the module to fail or malfunction.
[Installation Precautions]
CAUTION
● Use the module in an environment that meets the general specifications in this manual. Failure to do
so may result in electric shock, fire, malfunction, or damage to or deterioration of the product.
● Do not directly touch any conductive parts and electronic components of the module. Doing so can
cause malfunction or failure of the module.
● Securely fix the module with mounting screws. Failure to do so may cause the module to fail due to
increasing effects of vibrations.
● Securely connect the cable connectors. Poor contact may cause malfunction.
● After the first use of the product, do not connect/remove the connectors more than 50 times (IEC
61131-2/JIS B 3502 compliant). Exceeding the limit may cause malfunction.
[Wiring Precautions]
WARNING
● Shut off the load power supply (all phases) used in the system before wiring. Failure to do so may
result in electric shock or cause the module to fail or malfunction.
3
Page 6
[Wiring Precautions]
CAUTION
● Individually ground the FG metal fitting of the programmable controller with a ground resistance of 100
ohms or less. Failure to do so may result in electric shock or malfunction.
● Check the rated voltage and terminal layout before wiring to the module, and connect the cables
correctly. Connecting a power supply with a different voltage rating or incorrect wiring may cause a fire
or failure.
● Tighten the waterproof caps within the specified torque range. Undertightening can cause short
circuit, fire, or malfunction. Overtightening can damage the waterproof cap, resulting in short circuit or
malfunction.
● The module meets IP67 only when all of the waterproof plugs and waterproof caps are attached and
the cover of the station number setting switch is securely fixed with a screw.
● Prevent foreign matter such as dust or wire chips from entering the module. Such foreign matter can
cause a fire, failure, or malfunction.
● Place the cables in a duct or clamp them. If not, dangling cable may swing or inadvertently be pulled,
resulting in damage to the module or cables or malfunction due to poor contact.
● Do not install the control lines or communication cables together with the main circuit lines or power
cables. Keep a distance of 100mm or more between them. Failure to do so may result in malfunction
due to noise.
● When disconnecting the cable from the module, do not pull the cable by the cable part. For the cable
with connector, hold the connector part of the cable. Pulling the cable connected to the module may
result in malfunction or damage to the module or cable.
● When an overcurrent caused by an error of an external device or a failure of the programmable
controller flows for a long time, it may cause smoke and fire. To prevent this, configure an external
safety circuit, such as a fuse.
● Wiring and replacement of a module must be performed by qualified maintenance personnel with
knowledge of protection against electric shock. For wiring methods, refer to "INSTALLATION AND
WIRING" in this manual.
[Startup and Maintenance Precautions]
WARNING
● Do not touch any connector while power is on. Doing so will cause electric shock or malfunction.
● Shut off the load power supply (all phases) used in the system before cleaning the module or
retightening screws or connector screws. Failure to do so may cause the module to fail or malfunction.
4
Page 7
[Startup and Maintenance Precautions]
CAUTION
● Do not disassemble or modify the module. Doing so may cause failure, malfunction, injury, or a fire.
● Do not drop or apply strong shock to the module. Doing so may damage the module.
● Shut off the load power supply (all phases) used in the system before mounting or removing a
module. Failure to do so may cause the module to fail or malfunction.
● After the first use of the product, do not connect/remove the connectors more than 50 times (IEC
61131-2/JIS B 3502 compliant). Exceeding the limit may cause malfunction.
● Before handling the module or connection cables, touch a conducting object such as a grounded
metal to discharge the static electricity from the human body. Failure to do so may cause the module
to fail or malfunction.
● Startup and maintenance of a control panel must be performed by qualified maintenance personnel
with knowledge of protection against electric shock. Lock the control panel so that only qualified
maintenance personnel can operate it.
[Disposal Precautions]
CAUTION
● When disposing of this product, treat it as industrial waste.
[Transportation Precautions]
CAUTION
● For shipping, always use the original packaging.
5
Page 8
CONDITIONS OF USE FOR THE PRODUCT
(1) Although MELCO has obtained the certification for Product's compliance to the international safety standards
IEC61508, ISO13849-1 from TUV Rheinland, this fact does not guarantee that Product will be free from any malfunction
or failure. The user of this Product shall comply with any and all applicable safety standard, regulation or law and take
appropriate safety measures for the system in which the Product is installed or used and shall take the second or third
safety measures other than the Product. MELCO is not liable for damages that could have been prevented by
compliance with any applicable safety standard, regulation or law.
(2) MELCO prohibits the use of Products with or in any application involving, and MELCO shall not be liable for a default, a
liability for defect warranty, a quality assurance, negligence or other tort and a product liability in these applications.
(a) power plants,
(b) trains, railway systems, airplanes, airline operations, other transportation systems,
(c) hospitals, medical care, dialysis and life support facilities or equipment,
(d) amusement equipments,
(e) incineration and fuel devices,
(f) handling of nuclear or hazardous materials or chemicals,
(g) mining and drilling,
(h) and other applications where the level of risk to human life, health or property are elevated.
INTRODUCTION
Thank you for purchasing the CC-Link IE Field Network waterproof/dustproof remote I/O module (with safety functions)
(hereafter abbreviated as safety remote I/O module).
This manual describes the specifications, procedures before operation, installation and wiring, functions, parameter settings,
maintenance and inspection, and troubleshooting of the safety remote I/O module.
Before using this product, please read this manual and the relevant manuals carefully and develop familiarity with the
functions and performance of the safety remote I/O module to handle the product correctly. When applying the program and
circuit examples provided in this manual to an actual system, ensure the applicability and confirm that it will not cause system
control problems.
Please make sure that the end users read this manual.
Unless otherwise specified, this manual describes the examples in which the safety remote I/O signals and
remote I/O signals of the safety remote I/O module are assigned as follows.
• Safety remote input: SA\X0 to SA\X1B
• Safety remote output: SA\Y0 to SA\Y3
• Remote input signal: RX0 to RX4F
• Remote output signal: RY0 to RY4F
• Remote register: RWr0 to RWrB, RWw0 to RWwB
For how to assign remote I/O signals and remote register, refer to the following.
Specifications, procedures before operation, installation and wiring, functions,
parameter settings, maintenance and inspection, and troubleshooting of the safety
remote I/O module
Specifications, procedures before operation, system configuration, wiring, and
communication examples of Ethernet, CC-Link IE Controller Network, and CC-Link
IE Field Network
Functions, parameter settings, programming, troubleshooting, I/O signals, and
buffer memory of CC-Link IE Field Network
Dedicated instructions for the intelligent function modulese-Manual
Functions, parameter settings, troubleshooting, and buffer memory of CC-Link IE
Field Network
Functions, parameter settings, I/O signals, buffer memory, programming, and
troubleshooting of the simple motion module
Functions related to the synchronous control, and programming of the simple
motion module
Print book
e-Manual
PDF
Print book
e-Manual
PDF
Print book
e-Manual
PDF
PDF
Print book
e-Manual
PDF
Print book
e-Manual
PDF
Print book
e-Manual
PDF
10
Page 13
TERMS
Unless otherwise specified, this manual uses the following terms.
Ter mDescription
Buffer memoryA memory in an intelligent function module, where data (such as setting values and monitoring values) exchanged with a
CC-Link IE Field NetworkA high-speed and large-capacity open field network that is based on Ethernet (1000BASE-T)
Cyclic transmissionA function by which data are periodically exchanged among stations on the same network using link devices (RX, RY,
Dark testA function that diagnoses contacts including external devices using OFF pulses
Data linkA generic term for cyclic transmission and transient transmission
Dedicated instructionAn instruction that simplifies programming for using functions of intelligent function modules
DisconnectionA process of stopping data link if a data link error occurs
Engineering toolThe product name of the software package for the MELSEC programmable controllers
Initial processing stateThe state of having set the minimum required parameters on the module, so that data communication with external
Link special register (SW)Word data that indicates the operating status and data link status of a module on CC-Link IE Field Network
Link special relay (SB)Bit data that indicates the operating status and data link status of a module on CC-Link IE Field Network
Local stationA station that performs cyclic transmission and transient transmission with the master station and other local stations.
LoopbackA function that, upon occurrence of an error, disconnects only the station where the error occurred, and maintains data
Master stationA station that controls the entire network. This station can perform cyclic transmission and transient transmission with all
Master/local moduleAn abbreviation for the CC-Link IE Field Network master/local module
NCAn abbreviation for a normally closed contact. The contact opens with an operation (such as switch operation).
NOAn abbreviation for a normally open contact. The contact closes with an operation (such as switch operation).
REMFRAn abbreviation for ZP.REMFR.
Remote buffer memoryBuffer memory in a remote device station and intelligent device station
Remote device stationA station that exchanges I/O signals (bit data) and I/O data (word data) with another station by cyclic transmission. This
Remote input (RX)Bit data input from a slave station to the master station (For some areas in a local station, data are input in the opposite
Remote output (RY)Bit data output from the master station to a slave station (For some areas in a local station, data are output in the opposite
Remote register (RWr)Word data input from a slave station to the master station (For some areas in a local station, data are input in the opposite
Remote register (RWw)Word data output from the master station to a slave station (For some areas in a local station, data are output in the
REMTOAn abbreviation for ZP.REMTO.
Reserved stationA station reserved for future use. This station is not actually connected, but counted as a connected station
Safety categoryA safety level specified in EN954-1 The safety level is divided into 5 levels (B, 1 to 4).
Safety deviceA device that can be used in safety programs
Safety functionA function provided to protect a person from the hazards of machines
Safety remote I/O moduleA generic term for the NZ2GFS12A2-16DTE and the NZ2GFS12A2-14DT
Safety remote input (SA\X)A safety device (safety input) that can be used in safety programs
Safety remote output (SA\Y)A safety device (safety output) that can be used in safety programs
Safety remote stationA remote station to perform safety communications
Sink outputA output in which a current flows from the load into the output terminal when the output transistor turns on
Slave stationA generic term for stations other than a master station: local station, remote I/O station, remote device station, and
Source outputA output in which a current flows out from the output terminal to the load when the output transistor turns on
Safety CPU are stored
RWw, and RWr)
devices is possible
The station is controlled by programs in the Safety CPU or other equivalent modules on the station.
links only with the normally operating stations. Data links can be maintained even with normally operating stations
connected past the faulty station whose line was disconnected.
stations. Only one master station can be used in a network.
station responds to a transient transmission request from another station.
direction.)
User's manual for the master/local module used
direction.)
User's manual for the master/local module used
direction.)
User's manual for the master/local module used
opposite direction.)
User's manual for the master/local module used
intelligent device station
11
Page 14
TermDescription
Transient transmissionA function of communication with another station, which is used when requested by a dedicated instruction or an
engineering tool
12
Page 15
1PRODUCT LINEUP
1.1Safety Remote I/O Module
Safety remote I/O module
The following table lists the safety remote I/O module product lineup.
Typ eSpecificationsModule power
supply current
Input partNegative
common type
Output partSource +
source type
Input partNegative
common type
Output partSource + sink
type
Waterproof connector
24VDC, 12 points
Waterproof connector
24VDC, 1.0A/1 point, 4
points
Waterproof connector
24VDC, 12 points
Waterproof connector
24VDC, 2.0A/1 point, 2
points
The following table lists applicable waterproof connectors.
of a model name indicates a numerical value representing the length of each cable.
For details on applicable waterproof connectors, refer to the website of each manufacturer.
For power supply
The following table lists applicable waterproof connectors for power supply.
Typ eModelConnection cable
ConnectorCable
7/8"
5 pins
Male (OUT)
7/8"
5 pins
Female (IN)
7/8"
5 pins
Male (OUT)
7/8"
5 pins
Female (IN)
7/8"
5 pins
Male (OUT)-Female (IN)
1A5006-345.08 to 11.43mmMolex, LLC
1A5000-34
105006K13M
105000K13M
115030K13M
diameter
Manufacturer
For I/O
The following table lists applicable waterproof connectors for I/O.
Typ eModelConnection cable
ConnectorCable
M12
5 pins
Male (one-touch)
M12
5 pins
Male (one-touch)-Female (screw)
M12
5 pins
Male (screw)
M12
5 pins
Male (screw)-Female (screw)
A codeWA5006-313.3 to 6.6mmMolex, LLC
WA5006-324.1 to 8.1mm
W05006E03M
8W5030E03M
8A5006-313.3 to 6.6mm
8A5006-324.1 to 8.1mm
805006J06M
885030J06M
diameter
Manufacturer
14
1 PRODUCT LINEUP
1.2 Recommended Connector List
Page 17
Y-branch connector for I/O
The following table lists applicable Y-branch connectors for I/O.
Typ eModelConnection cable
ConnectorCable
M12
5 pins
Male
A code0812-05EMF-00001Molex, LLC
diameter
Manufacturer
For communications
The following table lists applicable waterproof connectors for communications.
Typ eModelConnection cable
ConnectorCable
M12
8 pins
Male
M12
8 pins
Male
M12
8 pins
Male
M12
8 pins
Male
Cable onlySC-E5EW-MMitsubishi Electric System &
X code-X codeE22E06020MMolex, LLC
X code-RJ45E26E06020M
X codeJ80026A01005.5 to 9.0mmTelegartner Karl Gartner
X codeIE-PS-M12X-P-AWG22/27FH5.5 to 9.0mmWeidmueller Interface GmbH
diameter
Manufacturer
GmbH
& Co. KG
Service Co., Ltd.
1
Waterproof cap
The following table lists applicable waterproof caps.
Typ eModelConnection cable
ConnectorCable
M12120358-0007Molex, LLC
7/8"
Male (OUT)
7/8"
Female (IN)
65-0085
65-0086
diameter
Manufacturer
1 PRODUCT LINEUP
1.2 Recommended Connector List
15
Page 18
2PART NAMES
(1)
(2)
(3)
(4)
(5)
(6)
(1)
Part names of the safety remote I/O module
This section describes the part names of the safety remote I/O module.
No.NameApplication
(1)FG metal fittingMetal fitting for connecting FG
(2)Power supply connectorsConnectors for the module power supply (24VDC) and load power supply (24VDC)
(3)I/O connectorConnector for I/O signals
(4)Signal labelLabel for describing signal names
(5)Station number setting switchRotary switch for setting a station number or tests
(6)Communication
connectors
P1PORT1 connector for CC-Link IE Field Network
P2PORT2 connector for CC-Link IE Field Network
For the tightening torque of screws for the FG metal fitting, refer to the following.
Page 39 Fixing the safety remote I/O module
Page 35 Setting the Station Number
Page 88 Unit Test
Connect an Ethernet cable.
Page 41 Wiring of Ethernet cable
Connect an Ethernet cable.
Page 41 Wiring of Ethernet cable
16
2 PART NAMES
Page 19
Names of the LEDs of the safety remote I/O module
(1)(2)
(3)
(4)
(5)(6)
(7)(8)
(9)
(10)
This section describes the names of the LEDs of the safety remote I/O module.
2
No.NameDescription
(1)PW LEDIndicates the voltage status of the module power supply.
(2)L PW LEDIndicates the voltage status of the load power supply.
(3)I/O LEDIndicates the on/off state of I/Os.
(4)SAFETY LEDIndicates the safety communication status of the safety remote I/O module.
(5)RUN LEDIndicates the operating status of the safety remote I/O module.
(6)MODE LEDIndicates the mode of the safety remote I/O module.
Green: The module power supply has no voltage error.
Red: The module power supply has a voltage error.
Off: The module power supply is off or has a voltage error.
Green: The load power supply has no voltage error.
Red: The load power supply has a voltage error.
Off: The load power supply is off or has a voltage error.
Green: I/O signals are on.
Red: An I/O circuit error or double wiring discrepancy was detected.
Red (flashing): An error occurred at one terminal of double wiring, or an error common to all I/O circuits except the terminal
flashing red occurred.
Off: I/O signals are off.
On: Safety communication is established.
Off: Safety communication is not established.
On: Operating normally.
Off: A major error occurred.
On: The unit test is completed. (online)
Flashing: In unit test mode
Off: Error occurred, Offline
2 PART NAMES
17
Page 20
No.NameDescription
(7)ERR. LEDIndicates the error status of the safety remote I/O module.
(8)D LINK LEDIndicates the data link status of the safety remote I/O module.
(9)L ER LEDIndicates the port status.
(10)LINK LED
*1
On: A module error occurred.
Flashing: A minor error occurred.
Off: Operating normally.
On: Communications are normal.
Flashing: Communications are interrupted.
Off: Disconnected
On: Module received abnormal data, or module performing loopback.
Off: Module received normal data, or module not performing loopback.
Indicates the link status.
On: Link-up in progress
Off: Link-down in progress
*1 The LINK LED may be on at power-on, but this does not indicate an error.
Safety remote I/O module status and LED status
This section describes the correspondence between the safety remote I/O module status and the LED status.
Checking the
position of the
setting target
module
Safety drive modeData link in operationOnOnOnOffOnOn
Unit testIn progressOnOnFlashingOffOffOff
Normal
completion
Abnormal
completion
Communication errorCyclic stopOnOnOnOffFlashingOff
ErrorMajor errorOnOff
Moderate
error
WarningMinor errorOnOn
Data link statusLED status
PW LEDRUN LEDMODE LED ERR. LEDD LINK
LED
Data link in operationOnOnOnOffOnOff
Cyclic stopOnOnOnOffFlashingOff
Data link in operation/
cyclic stop
OnOnOffOffOffOff
OnOnOffOnOffOff
OnOn
OnOnOnOff
*1
*1
*1
On
On
Flashing
*3*2*6
*5
*2*6
*2*2
SAFETY
LED
Flashing
*1 Either On or Off.
*2 Either On, Flashing, or Off.
*3 When the module is failed, the LED may not turn on.
*4 For the status of the module, refer to the following.
Page 83 Checking Module Status
*5 Either On or Flashing.
*6 Either Flashing or Off.
2 PART NAMES
18
Page 21
3SPECIFICATIONS
This chapter describes the specifications of the safety remote I/O module.
3.1General Specifications
ItemSpecifications
Operating ambient
temperature
Storage ambient
temperature
Operating ambient
humidity
Storage ambient
humidity
Vibration resistanceCompliant with JIS
Shock resistanceCompliant with JIS B 3502 and IEC 61131-2 (147m/, 3 times each in X, Y, and Z directions)
Operating atmosphereNo corrosive gases
Operating altitude
Installation locationInside/outside a control panel
Overvoltage category
Pollution degree
Equipment classClass
Safety elementHFT=1, SIL3 PLe, SC 3, Type B
*1 Only when all necessary waterproof connectors and caps have been installed and the station number setting switch cover has been
properly tightened with a screw, the module conforms to IP67. For the tightening torque range of the screw for the station number setting
switch cover, refer to the following.
Page 36 Tightening torque
*2 Do not use or store the safety remote I/O module under pressure higher than the atmospheric pressure of altitude 0m. Doing so may
cause malfunction. When using the safety remote I/O module under pressure, please consult your local Mitsubishi representative.
*3 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power
distribution network and the machinery within premises.
Category applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand level for the
equipment with the rated voltage of 300V or less is 2500V.
*4 This index indicates the degree to which conductive material is generated in terms of the environment in which the equipment is used.
Pollution degree 2 is when only non-conductive pollution occurs. A temporary conductivity caused by condensing must be expected
occasionally.
0 to 55
-25 to 75
Conforming to IP67
5 to 95%RH, non-condensing
B 3502 and IEC
61131-2
*2
0 to 2000m
*3
or less
*4
2 or less
*1
FrequencyConstant
Under intermittent
vibration
Under continuous
vibration
5 to 8.4Hz3.5mm10 times each in X,
8.4 to 150Hz9.8m/
5 to 8.4Hz1.75mm
8.4 to 150Hz4.9m/
acceleration
Half amplitudeNumber of sweeps
Y, and Z directions
3
When complying with the EMC Directive, refer to the following.
Page 126 EMC, Low Voltage, and Machinery Directives
3 SPECIFICATIONS
3.1 General Specifications
19
Page 22
3.2Performance Specifications
NZ2GFS12A2-16DTE safety remote I/O module
ItemNZ2GFS12A2-16DTE
Input specificationsOutput specifications
Station typeRemote device station
Number of input pointsSingle wiring: 12 points
Rated input voltage24VDC (ripple ratio: 5% or less) (allowable voltage
Rated input current6mA TYP. (24VDC)
Max. number of simultaneous input points100%
ON voltage/ON current11VDC or higher / 2mA or higher (compliant with IEC
OFF voltage/OFF current5VDC or lower / 1.5mA or lower (compliant with IEC
Input typeNegative common
Input resistanceApprox. 4k
Input circuit response
time
Safety remote station input response timeInput circuit response time + Input ON/OFF delay
Safety refresh response processing time10ms
Power supply current for input device
Number of output pointsSingle wiring: 4 points
Rated load voltage24VDC (ripple ratio: 5% or less) (allowable voltage
Load power supplyProtection functionLoad power supply overvoltage protection function,
Max. load current1.0A/point
Max. inrush currentCurrent is limited by the overload protection function.
Leakage current at OFF0.1mA or less
Max. voltage drop at ON1.0VDC or lower
Protection functionOutput overload short circuit protection
Double output typeSource + Source type
Output circuit
response time
Safety remote station output response timeOutput circuit response time
Communication partM12 waterproof connector, 8 pins, female, X-code
61131-2 Standard digital input type 3)
61131-2 Standard digital input type 3)
setting
(0 to 1000ms in 1ms steps)
(Initial setting: 5ms)
0.4A/1 terminal
12ms maximum
2s maximum
7/8" waterproof connector, 5 pins, male (IN)/female (OUT)
range: 20.4 to 28.8VDC)
load power supply overcurrent protection function
24
3 SPECIFICATIONS
3.2 Performance Specifications
Page 27
ItemNZ2GFS12A2-14DT
Input specificationsOutput specifications
Applicable waterproof
connector
Cyclic transmissionRX/RY points80 points
Communication cableAn Ethernet cable that meets the 1000BASE-T standard: Category 5e or higher (double shielded, STP),
Module power supplyVoltage24VDC (ripple ratio: 5% or less) (allowable voltage range: 20.4 to 28.8VDC)
Weight0.89kg
For power supplyPage 14 Recommended Connector List
For I/O
Y-branch connector
for I/O
For communications
RWr/RWw points16 points
SA\X / SA\Y pointsSA\X: 28 points
Current (current
consumption)
Protection functionModule power supply overvoltage protection function, module power supply overcurrent protection function
Max. current8A
SA\Y: 4 points
straight cable
190mA
*1 When using the test pulse output for the power supply for input device, use double insulation cables depending on applications used and
the safety category (SIL/CAT) required.
3
3 SPECIFICATIONS
3.2 Performance Specifications
25
Page 28
External connection
+24V(L PW)
24G(L PW)
+24V(L PW_IN)
+24V(PW_IN)
24G(L PW_IN)
24G(PW_IN)
FG
+24V(L PW)
+24V(PW)
24G(L PW)
24G(PW)
24G(PW)
FG
+24V(PW)
+24V(PW)
24G(PW)
24G(L PW)
24G(PW)
24G(L PW)
+24V(PW)
+24V(L PW)
+24V(L PW)
24G(L PW)
DC/DC
DC/DC
POWER IN
POWER OUT
5
1
3
4
2
5
1
3
4
2
5
1
3
4
2
5
1
3
4
2
5
1
3
4
2
24G(PW)
T0
T1
X1
X0
+24V(L PW)
24G(L PW)
24G(L PW)
Y0+
Y0-
5
1
3
2
4
Load power supply
Module power supply
Safety switch
Power supply connector
Power supply connector
Input
M12 connector
Safety relay
Safety relay
Load
Output
M12 connector
Photocoupler
Internal
circuit
Non-isolation
Internal power
supply (PW)
Internal power
supply (L PW)
Non-isolation
24VDC
24VDC
Current
detection
circuit
(2)
(3)
(1)
(4)
(5)
(4)
(3)
(5)
(2)
(1)
Power supply connectors
(1)24G (L PW)
Pin numberSignal namePin numberSignal name
7/8" connector
Male (IN)
(1)24G (L PW_IN)7/8" connector
(2)24G (PW_IN)(2)24G (PW)
Female (OUT)
(3)FG(3)FG
(4)+24V (PW_IN)(4)+24V (PW)
(5)+24V (L PW_IN)(5)+24V (L PW)
26
3 SPECIFICATIONS
3.2 Performance Specifications
Page 29
I/O connector
(2)
(3)
(5)
(1)
(4)
Pin numberSignal namePin numberSignal name
X0
X1
X2
X3
X4
X5
X6
X7
(1)T1X8
(2)X1(2)X9
(3)24G (PW)(3)24G (PW)
(4)X0(4)X8
(5)T0(5)T8
(1)T3XA
(2)X3(2)XB
(3)24G (PW)(3)24G (PW)
(4)X2(4)XA
(5)T2(5)TA
(1)T5Y0(1)+24V (L PW)
(2)X5(2)Y0-
(3)24G (PW)(3)24G (L PW)
(4)X4(4)Y0+
(5)T4(5)24G (L PW)
(1)T7Y1(1)+24V (L PW)
(2)X7(2)Y1-
(3)24G (PW)(3)24G (L PW)
(4)X6(4)Y1+
(5)T6(5)24G (L PW)
X9
XB
(1)T9
(1)TB
3
Safety remote I/O module safety response time
The safety response time of the safety remote I/O module is shown below.
For the response time including the network delay time, refer to the following.
Mitsubishi Electric Safety Programmable Controller MELSEC iQ-R Series Machinery Directive (2006/42/EC) Compliance
■Input
Transmission interval monitoring time 2 + Safety remote station input response time
■Output
Transmission interval monitoring time 2 + Safety remote station output response time
3 SPECIFICATIONS
3.2 Performance Specifications
27
Page 30
3.3Function List
This section describes the function list, operation modes, and state transition.
Function list
■I/O functions
Function nameDescriptionReference
Input functionInput wiring selection
Output functionOutput wiring selection
function
Input ON delay, input OFF
delay functions
function
■Safety functions
Function nameDescriptionReference
Input diagnostic
function
Output diagnostic
function
Double input discrepancy
detection function
Input dark test functionThis function outputs test pulses to turn off the external input
Output dark test functionThis function outputs test pulses to turn off the external output
Output read-back functionThis function reads back output results and diagnoses whether the
This function selects double wiring or single wiring of the input
wiring.
This function changes an input signal when a predetermined time
has passed after an actual input change.
A delay time can be set for each input change pattern, OFF to ON
or ON to OFF. In addition, the function prevents incorrect inputs
caused by noise since a pulse of a certain time length is not taken
in a module.
This function selects double wiring or single wiring of the output
wiring.
This function discriminates failures by monitoring the discrepancy
state of doubled safety remote inputs (SA\X).
When the discrepancy state is detected, a minor error occurs. The
module will recover from the error by eliminating its cause.
signals (X0 to XB) that are on for a short time and diagnoses
contacts including external devices for failure.
When failure is detected, a minor error occurs. The module will
recover from the error by eliminating its cause.
To use this function, settings of "Input mode setting" and "Input test
pulse setting" are required.
signals (NZ2GFS12A2-16DTE: Y0 to Y3, NZ2GFS12A2-14DT: Y0
to Y1) that are on for a short time and diagnoses the internal circuit
for failure.
When failure is detected, a minor error occurs. The module will
recover from the error by eliminating its cause.
external output signals (NZ2GFS12A2-16DTE: Y0 to Y3,
NZ2GFS12A2-14DT: Y0 to Y1) are correctly output.
When an incorrect output is detected, a minor error occurs. The
module will recover from the error by eliminating its cause.
*1
*1
*1
Page 45 Input wiring selection
function
Page 49 Input ON delay, input OFF
delay functions
Page 50 Output wiring selection
function
Page 53 Double input discrepancy
detection function
Page 55 Input dark test function
Page 57 Output dark test function
Page 59 Output read-back function
*1 This operation differs from the operation of CC-Link IE Field Network remote I/O module (with safety functions). For the system,
configure an external interlock circuit or an interlock circuit using a ladder program. Do not use a stop of safety remote I/O module as an
interlock condition.
For the operation of CC-Link IE Field Network remote I/O module (with safety functions), refer to the following.
CC-Link IE Field Network Remote I/O Module (With Safety Functions) User's Manual
3 SPECIFICATIONS
28
3.3 Function List
Page 31
■Network function
Function nameDescriptionReference
User authentication functionThis function limits the users who can access the Safety CPU or
safety remote I/O module.
Page 60 User Authentication
Function
■Module function
Function nameDescriptionReference
Protection functionThis function protects the internal circuit from overvoltage or
overcurrent.
The safety remote I/O module does not support the CC-Link IE Field Network synchronous communication
function.
Page 61 Protection Functions
3
3 SPECIFICATIONS
3.3 Function List
29
Page 32
Operation mode and state transition
a
b
c
d
f
g
g
g
g
h
f
f
e
(1) Power supply OFF state
(2) Initial processing state(3) Unit test mode
(4) Standby mode
*1
(6) Moderate error state
(7) Major error state
(5) Safety drive mode
*1
The following describes the state transition and transition conditions of the safety remote I/O module.
*1 When a moderate error or major error has occurred, the state is changed into an error state.
■Operation mode/state
No.Mode/stateDescription
(1)Power supply OFF stateThe power supply is not turned on. Change the station number using the station number setting switch or wire
(2)Initial processing stateThe initial processing is performed at this state.
(3)Unit test modeThe unit test is performed at this state.
(4)Standby modeThe safety functions of the safety remote I/O module do not operate at this state. Set parameters in this
(5)Safety drive modeThe safety functions of the safety remote I/O module operate at this state.
(6)Moderate error stateA moderate error has occurred.
(7)Major error stateA major error has occurred.
the module at this state.
Page 35 INSTALLATION AND WIRING
Page 88 Unit Test
mode.
Page 62 PARAMETER SETTINGS
■Transition condition
Symbol Transition condition
aWhen the module is powered on
bWhen the station number setting switch 10 is set to TEST and the station number setting switch 1 is set to 0 in the power supply OFF state
cWhen the initial processing is completed successfully
dWhen Safety module enabled flag (address: 1005H) is on and the safety communication with the master station is established
eWhen the safety communication is disconnected
fWhen a moderate error has occurred
gWhen a major error has occurred
hWhen a parameter data error is eliminated. For parameter data errors, refer to the following.
30
3 SPECIFICATIONS
3.3 Function List
For Safety module enabled flag (address: 1005H), refer to the following.
Page 125 Safety module enabled flag (address: 1005H)
Page 95 Error Code List
To switch the operation mode/state from the unit test mode, moderate error state, or major error state, power
off and on the module.
Page 33
4PROCEDURES BEFORE OPERATION
Consideration of system configuration
Complete the following items prior to the module installation.
1. Determine a safety category required for configuring the safety system.
2. Determine function wiring required for configuring the safety system.
3. Determine the network number and station number of the safety remote I/O module.
Module mounting, wiring, and parameter setting
1. Mounting the module
Fix the safety remote I/O module with screws.
Page 37 Installation Environment and Installation Position
2. Wiring to the power supply module
Connect the safety remote I/O module to the power supply.
Page 40 Wiring the power supply
3. Station number setting
Set station numbers of the safety remote I/O module using the station number setting switch.
Page 35 Setting the station number with the station number setting switch
4. Wiring
Connect the Ethernet cable and external devices to the safety remote I/O module.
Page 41 Wiring of Ethernet cable
5. Powering on the safety remote I/O module
Stop the Safety CPU, and power on the safety remote I/O module.
6. Parameter setting
Set the module parameters of the master station module and the safety remote I/O module in the engineering tool.
Page 62 PARAMETER SETTINGS
Page 64 Module Parameter Setting of the Master Station
Page 67 Module Parameter Setting
4
7. Checking the entire system
According to the manuals of the Safety CPU and the master station module, check the entire system for wiring, the station
number setting switch, and so on.
8. Validating the safety remote I/O module
Enable the module parameters of the safety remote I/O module.
Page 67 Module parameter setting procedure
9. Starting the system
Change the status of the Safety CPU to RUN.
10. Starting the system operation
To replace the module, follow the procedure described below:
• Turn off the module power supply and remove the safety remote I/O module.
• Prepare a new safety remote I/O module and perform the procedure above from "Mounting the module" to
"Parameter setting". (The network parameter of the master station does not need to be set again.)
• After checking the operation, restart the control.
4 PROCEDURES BEFORE OPERATION
31
Page 34
MEMO
32
4 PROCEDURES BEFORE OPERATION
Page 35
5SYSTEM CONFIGURATION
This chapter describes the system configuration using a safety remote I/O module.
For CC-Link IE Field Network configuration, refer to the following.
User's manual for the master/local module used
5.1Applicable Systems
Applicable products
When using a safety remote I/O module, use the following products.
For the model of the Safety CPU and safety function module, refer to the following.
MELSEC iQ-R Module Configuration Manual
ModuleFirmware version
Safety CPU (RnSFCPU)01 or later
Safety function module (R6SFM)01 or later
Master station (RJ71GF11-T2)09 or later
Master station (RD77GF4, RD77GF8, RD77GF16, RD77GF32)05 or later
Information on "Master station" described above is the ones at the point when this manual was issued.
For latest information, please visit the website of CC-Link Partner Association.
www.cc-link.org
5
The safety remote I/O module cannot be used with a CPU module other than the Safety CPU.
Ethernet cable
For the specifications of the Ethernet cable, refer to the following.
MELSEC iQ-R Ethernet/CC-Link IE User's Manual (Startup)
Software package
The following engineering tool is required for the safety remote I/O module setting and CC-Link IE Field Network diagnostics.
Product nameVersion
GX Works31.050C or later
When the latest profile of the safety remote I/O module is necessary, please consult your local Mitsubishi
representative.
The profile is a setting file that stores information required for the start-up, operation, and maintenance of
devices supporting the CC-Link family. A module is added to "Module List" of "CC IE Field Configuration"
window by profile registration to an engineering tool. For the profile registration, refer to the following.
GX Works3 Operating Manual
5 SYSTEM CONFIGURATION
5.1 Applicable Systems
33
Page 36
5.2Safety Standards
Observe the following safety standards.
RegionStandard
GlobalIEC 61508: 2010, IEC 62061: 2012, ISO 13849-1
The following table lists safety parameters of the safety remote I/O module.
ItemNZ2GFS12A2-16DTENZ2GFS12A2-14DT
*1
PFDavg
*1
PFH
DCavg96.28%96.24%
MTTFd108 years109 years
MTBF195.7 years (40)207.4 years (40)
4.0710
4.7010
-4
-9
4.0710
4.6910
-4
-9
*1 Proof test interval is 20 years (module exchange interval).
34
5 SYSTEM CONFIGURATION
5.2 Safety Standards
Page 37
6INSTALLATION AND WIRING
This chapter describes the installation and wiring of the safety remote I/O module.
6.1Setting the Station Number
Setting the station number with the station number setting switch
Setting procedure
Set a station number with the station number setting switch on the front of the module. The setting value of the station number
becomes valid when the module is powered on. Thus, set the station number when the module is powered off.
1. Loosen the screw for the station number setting switch
cover with a screwdriver and open the cover.
6
2. Set a station number.
• The hundreds and tens places of the station number are set with x10.
• The ones place of the station number is set with x1.
*1
3. After setting the station number with the station number
setting switch, always close the station number setting
switch cover and tighten the screw for the cover with a
*2
screwdriver.
not been tightened properly, waterproof performance is
lost.
*1 When operating the station number setting switch, use a flathead screwdriver with 3.5mm or less width of the tip.
*2 For the tightening torque range of the screw for the station number setting switch cover, refer to the following.
Page 36 Tightening torque
When the cover is open or the screw has
6 INSTALLATION AND WIRING
6.1 Setting the Station Number
35
Page 38
Ex.
To set the station to 115, set the switch as shown below.
Setting range
Set the station number from 1 to 120. Setting the value other than 1 to 120 causes a communication error and the D LINK
LED flashes.
• Do not change the station number setting switch while the module power supply is on. Changing the station
number setting switch causes a minor error and the ERR. LED flashes. Returning the station number setting
switch to the previous setting eliminates the error five seconds later and the ERR. LED turns off.
• Do not set a same station number as another station number. If a duplicate station number is used, a
communication error occurs and the D LINK LED does not turn on.
Tightening torque
Tighten the screw for the station number setting switch cover within the following tightening torque range.
Screw typeTightening torque range
Station number setting switch cover (M3 screw)0.43 to 0.57Nm
• Do not put oil on the screw. Failure to do so may damage the screw.
• Tighten the screw with an applicable screwdriver. Tightening it with an inapplicable screwdriver may
damage the screw.
36
6 INSTALLATION AND WIRING
6.1 Setting the Station Number
Page 39
6.2Installation Environment and Installation Position
Installation environment
Installation location
Do not install the safety remote I/O module to a place where:
• Ambient temperature is outside the range of 0 to 55;
• IP67 is not satisfied;
• Condensation occurs due to rapid temperature change;
• Corrosive gas or combustible gas is present;
• Conductive powder such as iron powder, oil mist, salinity, or organic solvent is filled;
• The safety remote I/O module is exposed to direct sunlight;
• A strong electric field or strong magnetic field is generated; and
• The safety remote I/O module is subject to vibration and shock.
Installation surface
Install the safety remote I/O module on a flat surface. When the installation surface is uneven, excessive force is applied to
the printed-circuit board and may cause a defect.
6
6 INSTALLATION AND WIRING
6.2 Installation Environment and Installation Position
37
Page 40
Installation position
(2)
(1)
(2)
(1)
(2)
When installing the safety remote I/O module, provide a clearance between the module and the sides of neighboring
structures or parts to ensure good ventilation, avoid interference, and avoid stress on waterproof connectors.
To insert or remove a communication connector, provide a clearance sufficient to use a screwdriver.
When using a right-angle, waterproof connector or a Y branch connector, provide a clearance to avoid stress on cables.
(1) 0mm or longer
(2) 50mm or longer
Installation direction
The safety remote I/O module can be installed in six directions.
Fix the module with screws.
38
6 INSTALLATION AND WIRING
6.2 Installation Environment and Installation Position
Page 41
6.3Installation
Fixing the safety remote I/O module
When fixing the safety remote I/O module, tighten all of four screws.
Otherwise, the module will be greatly affected by vibration, causing failure of the module.
When installing the module, tighten screws within the following torque range.
Screw typeTightening torque range
Module mounting screw (M4 screw)0.824 to 1.11Nm
Screw for an FG metal fitting (M3 screw)0.425 to 0.575Nm
• Do not put oil on the screw. Failure to do so may damage the screw.
• Tighten the screw with an applicable screwdriver. Tightening it with an inapplicable screwdriver may
damage the screw.
6
6 INSTALLATION AND WIRING
6.3 Installation
39
Page 42
6.4Wiring
*1
(1)
Wiring the power supply
When wiring the power supply, connect it to the POWER IN terminal of the power supply connector of the safety remote I/O
module.
Transition wiring of the power supply
When installing multiple safety remote I/O modules, the power can be supplied to the modules through transition wiring.
For transition wiring, connect wires between the POWER OUT terminal of the safety remote I/O module that will be the power
supplier and the POWER IN terminal of another safety remote I/O module that will be a power supply destination.
*1 The largest current flows from the power supplier to the power supply connector of the first safety remote I/O module. Make sure that the
current does not exceed the current capacity (8A/pin) of the power supply connector. For a power supply to supply 24VDC, use a power
supply (SELV power supply) that does not exceed 30VAC (effective value), 42.4V (peak value), or 60VDC. Also, use a power supply
which is applied to "limited-energy circuit" defined in IEC61010-1.
(1) Power supply
For transition wiring, check the current consumption of each of the wired safety remote I/O modules.
For the current consumption of a safety remote I/O module, refer to the following.
Page 20 Performance Specifications
40
6 INSTALLATION AND WIRING
6.4 Wiring
Page 43
Wiring of Ethernet cable
Connecting the Ethernet cable
■Connecting
1. Power off the module power supply of the
safety remote I/O module and the power supply
of the external device.
2. Push the Ethernet cable connector into the
safety remote I/O module, paying attention to
the connector's direction.
6
3. Tighten the screw of the Ethernet cable.
4. Power on the module power supply.
5. Power on the power supply of the external
device.
6. Check that the LINK LED on the port into which
the Ethernet cable is connected is on.
*1 The time taken for the LINK LED to turn on after connection of the cable may vary. The LINK LED normally turns on in a few second.
However, if link-up processing is repeated due to a condition of a device on the line, the longer time may be required. If the LINK LED
does not turn on, refer to the following and take a corrective action.
Page 82 When the LINK LED turns off
*1
6 INSTALLATION AND WIRING
6.4 Wiring
41
Page 44
• PORT1 and PORT2 need not be distinguished. When only one connector is used in star topology, either
PORT1 or PORT2 can be connected.
• When two connectors are used in line topology or ring topology, an Ethernet cable can be connected to the
connectors in any combination. For example, the cable can be connected between PORT1s and between
PORT1 and PORT2.
• Connection between PORT1 and PORT1 or between PORT2 and PORT2
• Connection between PORT1 and PORT2
42
6 INSTALLATION AND WIRING
6.4 Wiring
Page 45
■Disconnecting
1. Power off the module power supply.
2. Loosen the screw of the Ethernet cable and
remove the Ethernet cable.
Precautions
■Laying Ethernet cables
• Place the Ethernet cables in a duct or clamp them. If not, dangling cable may swing or inadvertently be pulled, resulting in
damage to the module or cables or malfunction due to poor contact.
• Do not touch the core of the connector of the cable or the module, and protect it from dirt and dust. If any oil from your hand,
or any dirt or dust sticks to the core, it can increase transmission loss, causing data link to fail.
• Check the following:
• Is any Ethernet cable disconnected?
• Does any Ethernet cable short?
• Are the connectors securely connected?
6
■Connecting and disconnecting the Ethernet cable
Hold the connector part when connecting and disconnecting the Ethernet cable. Pulling the cable connected to the module
may result in damage to the module or cable or malfunction due to poor contact.
■Connectors without Ethernet cable
To prevent dust from entering the module, attach the provided waterproof caps.
The maximum station-to-station distance is 100m. However, the distance may be shorter depending on the operating
environment of the cable. For details, contact the manufacturer of the cables used.
■Bending radius of the Ethernet cable
There are restrictions on the bending radius of the Ethernet cable. Check the bending radius in the specifications of the
Ethernet cables used.
Attaching waterproof caps
Tighten the waterproof caps within the following torque range.
Screw typeTightening torque range
Waterproof cap0.30 to 0.34Nm
6 INSTALLATION AND WIRING
6.4 Wiring
43
Page 46
Precautions for wiring the safety remote I/O module to safety
devices
This section describes the precautions for the wiring. To wire the safety remote I/O module to each safety device according to
Category 4, perform both of the following for the safety remote I/O module.
• Double wiring inputs
Page 45 Double wiring function
• Double wiring outputs
Page 50 Double wiring function
• Executing the self-diagnostic function (dark test)
Page 55 Input dark test function
Page 57 Output dark test function
44
6 INSTALLATION AND WIRING
6.4 Wiring
Page 47
7FUNCTIONS
NC
NC
T0T1X0X1
Two inputs
Safety remote I/O module
NC
NO
T0T1X0X1
Two inputs
Safety remote I/O module
This chapter describes the functions available in the safety remote I/O module, and the setting procedures for those functions.
For details on safety remote I/O signals, remote I/O signals, and remote buffer memory, refer to the following.
• Page 104 Safety Remote I/O Signals
• Page 108 Remote I/O Signals
• Page 113 Remote Buffer Memory
7.1Input Function
This function safely inputs external signals. This function cannot be used in any modes other than the safety drive mode. All
the safety remote inputs (SA\X) are off in any modes other than the safety drive mode.
Input wiring selection function
This function selects double wiring or single wiring of the input wiring.
Double wiring function
The double wiring function supports double input wiring.
By verifying input signals of double wiring, safety inputs can be turned off even though one of the signals has an error.
The following two are the double wiring methods for safety remote input (SA\X).
• Double wiring example for input (NC/NC)
7
• Double wiring example for input (NC/NO)
7 FUNCTIONS
7.1 Input Function
45
Page 48
■Combination for double wiring
T0X0
NC
Safety remote I/O module
Use the following combinations of input terminals for double wiring to the safety remote I/O module.
Combination of input terminals
X0, X1X2, X3X4, X5X6, X7X8, X9XA, XB
The following table lists the relation of input terminals (X) and safety remote inputs (SA\X).
Safety remote input (SA\X)Input terminal (X)
SA\X0X0
SA\X1X1
toto
SA\XAXA
SA\XBXB
Single wiring function
This function can connect input devices with single wiring.
Connecting input devices with single wiring brings the safety category to SIL2/CAT2 PLd.
Diagnostic functions to detect input errors
Input errors can be detected by using the following diagnostic functions.
Diagnostic functionDescriptionReference
Double input discrepancy detection
function
Input dark test functionOutputs test pulses to turn off the external input signals (X0 to XB) that are on
Detects the discrepancy of double input signals.Page 53 Double input
discrepancy detection function
Page 55 Input dark test function
for a short time and diagnoses contacts including external devices for failure.
46
7 FUNCTIONS
7.1 Input Function
Page 49
Combination of double inputs
(1)
(2)
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Double input
discrepancy state
Input terminal status: X0
Input terminal status: X1
SA\X0
SA\X1
The safety remote I/O module evaluates the logic of input signals and reflects the results to safety remote inputs (SA\X).
When the double input signals differ, the double input discrepancy detection state is applied. The following tables list the
correspondence between each double input signal state and safety remote input (SA\X).
■Combination of double inputs (NC/NC)
Input terminal stateSafety remote input
(SA\X0 to SA\XB)
*1
Xn
OFFOFFOFFOFFONONOffOffOFF (Normal)
OFFON OFFOFFOFF
ONOFFOFFOFFOFF
ONONONONONONGreenGreenON (Normal)
Xn+1
*1
SA\Xm*2SA\Xm+
*2
1
*1 n: Even number from 0 to A
*2 m: Safety device address (even number from 0 to A) assigned to the master station
*3 After the double input discrepancy time has elapsed, the status changes to the listed status.
■Combination of double inputs (NC/NO)
Input terminal stateSafety remote input
(SA\X0 to SA\XB)
*1
Xn
OFFOFFOFFONOFFOFFRed
OFFONOFFONONONOffGreenOFF (Normal)
ONOFFONOFFONONGreenOffON (Normal)
ONONOFFONOFFOFFRed
Xn+1
*1
SA\Xm*2SA\Xm+
*2
1
Safety input status
(SA\XC to SA\X17)
SA\XC+
*2
m
SA\XC+
*2
m+1
*3
*3
OFF
OFF
*3
*3
Safety input status
(SA\XC to SA\X17)
SA\XC+
*2
m
SA\XC+
*2
m+1
I/O LED statusEvaluation result of double inputs
Xn
Red
Red
*1
*3
*3
Xn+1
Red
Red
*1
*3
*3
OFF (Discrepancy)
OFF (Discrepancy)
I/O LED statusEvaluation result of double inputs
Xn
*1
*3
*3
Xn+1
Red
Red
*1
*3
*3
OFF (Discrepancy)
ON (Discrepancy)
7
*1 n: Even number from 0 to A
*2 m: Safety device address (even number from 0 to A) assigned to the master station
*3 After the double input discrepancy time has elapsed, the status changes to the listed status.
■States of safety remote inputs (SA\X0, SA\X1) for X0 and X1 (double wiring (NC/NC))
(1) Even when the input terminal X0 turns on, SA\X0 does not turn on because X1 is off.
(2) When the double inputs are on (X0 and X1 are on), SA\X0 and SA\X1 turn on.
Even when SA\X0 and SA\X1 are off, the time when X0 and X1 are in double input discrepancy state is measured and if the measured time exceeds a set
detection time, a double input discrepancy detection error occurs.
7 FUNCTIONS
7.1 Input Function
47
Page 50
■States of safety remote inputs (SA\X0, SA\X1) for X0 and X1 (double wiring (NC/NO))
(1)
OFF
ON
OFF
ON
OFF
ON
OFF
ON
SA\X0
SA\X1
Double input
discrepancy state
Input terminal status: X0
Input terminal status: X1
(1) The same value as the input terminal is reflected.
Even when SA\X0 and SA\X1 are off, the time when X0 and X1 are in double input discrepancy state is measured and if the measured time exceeds a set
detection time, a double input discrepancy detection error occurs.
Setting procedure
Set the input wiring selection in "Wiring selection of input" from the "Parameter Processing of Slave Station" window of the
engineering tool.
For the procedure to display the "Parameter Processing of Slave Station" window, refer to the following.
Page 67 Module parameter setting procedure
ItemSetting range
Wiring selection of input X0/X1 to XA/XB1: Double wiring (NC/NC) (default)
2: Double wiring (NC/NO)
3: Single wiring
External input signal monitor function
The state of input terminals can be monitored. This function facilitates the investigation for the cause of a double input
discrepancy error. For details, refer to the following.
Page 111 External input monitor (RX30 to RX3F)
When "Wiring selection of input" is set to "3: Single wiring", both Xn and Xn+1 are single wiring.
External input monitors (RX30 to RX3F) are the remote control/monitor signals to investigate the cause of a
double input discrepancy error. Do not use them in a safety program.
48
7 FUNCTIONS
7.1 Input Function
Page 51
Input ON delay, input OFF delay functions
Ex.
Ex.
This function changes an input signal when a predetermined time has passed after an actual input change.
A delay time can be set for each input change pattern, OFF to ON or ON to OFF. In addition, the function prevents incorrect
inputs caused by noise since a pulse of a certain time length is not taken in a module.
Input ON delay
The ON delay is the minimum ON time of the actual input signal required before the safety input signal changes from OFF to
ON.
When 5ms is set, the safety input signal turns to ON after the actual input signal is ON for at least 5ms.
Input OFF delay
The OFF delay is the minimum OFF time of the actual input signal required before the safety input signal changes from ON to
OFF.
When 5ms is set, the safety input signal turns to OFF after the actual input signal is OFF for at least 5ms.
Setting procedure
The "Input ON delay" and "Input OFF delay" times can be set from the "Parameter Processing of Slave Station" window of the
engineering tool.
The setting range is 0 to 1000ms (in 1ms steps)
The default value is 5ms.
7
• When "Wiring selection of input" is set to "1: Double wiring (NC/NC)" or "2: Double wiring (NC/NO), set the
same value as Xn+1 for Xn (n: even number).
• When "Input mode setting" is set to "1: Not used", this parameter will be ignored.
• In addition to this setting value, the safety refresh response processing time and the hardware response
time are also added as delay time for safety input signal switching. (Safety refresh response processing
This function can connect output devices with single wiring.
Connecting output devices with single wiring brings the safety category to SIL2/CAT2 PLd.
Diagnostic functions to detect output errors
Output errors can be detected by using the following diagnostic functions.
Diagnostic functionDescriptionReference
Output dark test functionOutputs test pulses to turn off the outputs that are on for a short time and
diagnoses the internal circuit for failure.
Output read-back functionReads back output results and diagnoses whether the outputs are correctly
on or off.
Page 57 Output dark test
function
Page 59 Output read-back
function
7
Combination of double outputs
Both terminals of double outputs are turned on only when both safety remote outputs (SA\Y) are on. The safety remote I/O
module evaluates the logic of safety remote outputs (SA\Y) and determines the state of the output terminals. The following
tables list the correspondence between each state of safety remote output (SA\Y) and output terminal for double outputs.
■Combination of double outputs (source + source connection)
Safety remote output (SA\Y0
to SA\Y3)
*1
SA\Ym
OFFOFFOFFOFFONONOffOff
OFFON OFFOFFOFFOFF Red Red
ONOFFOFFOFFOFFOFFRedRed
ONONONONONONGreenGreen
*1 m: Safety device address (even number from 0 to 3) assigned to the master station
*2 n: Even number from 0 to 3
SA\Ym+1
Output terminal stateSafety output status (SA\X18 to
SA\X1B)
*1
Yn
*2
Yn+1
*2
SA\X18+m
*1
I/O LED status
SA\X18+m+1*1Yn
*2
Yn+1
*2
7 FUNCTIONS
7.2 Output Function
51
Page 54
■Combination of double outputs (source + sink connection)
(1)(1)
(2)
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
OFF
SA\Y0
SA\Y1
Discrepancy state
Output terminal: Y0
Output terminal: Y1
Discrepancy state
Safety remote output (SA\Y0
to SA\Y3)
*1
SA\Ym
OFFOFFOFFOFFONONOffOff
OFFONOFFOFFOFFOFFRedRed
ONOFFOFFOFFOFFOFFRedRed
ONONONONONONGreenGreen
SA\Ym+1
Output terminal stateSafety output status (SA\X18 to
SA\X1B)
*1
Yp+
*2
Yp-
*2
SA\X18+m
*1
I/O LED status
SA\X18+m+1*1Yp+
*2
Yp-
*2
*1 m: Safety device address (even number from 0 to 1) assigned to the master station
*2 p: 0, 1
■States of safety remote outputs (SA\Y0, SA\Y1) for Y0 and Y1 (double wiring (source + source
connection))
(1) When double outputs (source + source) are in the discrepancy state (SA\Y0 and SA\Y1 are different), Y0 and Y1 are off.
(2) When double outputs (source + source) are on (SA\Y0 and SA\Y1 are on), Y0 and Y1 are on.
If double outputs are in discrepancy state, a minor error (0207H: I/O data error) occurs.
Setting procedure
Set the output wiring selection in "Wiring selection of output" from the "Parameter Processing of Slave Station" window of the
engineering tool.
For the procedure to display the "Parameter Processing of Slave Station" window, refer to the following.
Page 67 Module parameter setting procedure
■Wiring selection of output (NZ2GFS12A2-16DTE)
ItemSetting range
Wiring selection of output Yn/Yn+1
(n: 0, 2)
■Wiring selection of output (NZ2GFS12A2-14DT)
ItemSetting range
Wiring selection of output Yn
(n: 0, 1)
1: Double wiring (default)
2: Single wiring
1: Double wiring (default)
52
When "Wiring selection of output" is set to "2: Single wiring", both Yn and Yn+1 are single wiring.
7 FUNCTIONS
7.2 Output Function
Page 55
7.3Input Diagnostic Function
(1)
OFF
ON
ON
OFF
OFF
ON
ON
OFF
ON
SA\X0
SA\X1
Double input
discrepancy time
Both OFF
Input terminal status: X0
Error status flag
Input terminal status: X1
Double input discrepancy detection function
This function discriminates failures by monitoring the discrepancy state of doubled safety remote inputs (SA\X).
When the discrepancy state is detected, a minor error occurs. The module will recover from the error by eliminating its cause.
Double input discrepancy detection
When the discrepancy state of double inputs continues for the set time or longer, a double input discrepancy detection error
occurs as an input error. For the double input discrepancy detection time, refer to the following.
Page 54 Double input discrepancy detection time
The following shows the operation details of the double input discrepancy detection for double wiring inputs (NC/NC
connection), X0 and X1.
7
(1) After the double input discrepancy detection time elapses, a double input discrepancy detection error occurs.
■Operation at error detection
When the discrepancy state of double inputs continues for the set time or longer, the minor error (double input discrepancy
detection error) state is applied to the safety remote I/O module. For the minor error state, refer to the following.
Page 95 Error Code List
The corresponding input points are turned off when the discrepancy state of inputs occurs.
7 FUNCTIONS
7.3 Input Diagnostic Function
53
Page 56
Double input discrepancy detection time
Even if double input discrepancy is detected, an error does not occur during the set detection time. The logic of input signals
is evaluated and is reflected to the safety remote inputs (SA\X).
The following tables list the relation of each double input evaluation result and the double input discrepancy detection time.
The relation varies depending on a combination of double inputs.
■Combination of double inputs (NC/NC)
Input terminal stateTime passed after the
*1
Xn
OFFOFFOFFOFFOFF (Normal)
OFFON< Double input discrepancy
OFFON Double input discrepancy
ONOFF< Double input discrepancy
ONOFF Double input discrepancy
ONONONONON (Normal)
Xn+1
*1
discrepancy state is applied
detection time
detection time
detection time
detection time
Safety remote inputEvaluation result of double
*2
SA\Xm
OFFOFFOFF (Discrepancy)
OFFOFFDouble input discrepancy
OFFOFFOFF (Discrepancy)
OFFOFFDouble input discrepancy
SA\Xm+1
*2
inputs
detection error
detection error
*1 n: Even number from 0 to A
*2 m: Safety device address (even number from 0 to A) assigned to the master station
*3 When the double input discrepancy detection time has not elapsed, the input is OFF and the safety input status is ON.
■Combination of double inputs (NC/NO)
Input terminal stateTime passed after the
*1
Xn
OFFOFF< Double input discrepancy
OFFOFF Double input discrepancy
OFFONOFFONOFF (Normal)
ONOFFONOFFON (Normal)
ONON< Double input discrepancy
ONON Double input discrepancy
Xn+1
*1
discrepancy state is applied
detection time
detection time
detection time
detection time
Safety remote inputEvaluation result of double
*2
SA\Xm
OFFONOFF (Discrepancy)
OFFONDouble input discrepancy
OFFONOFF (Discrepancy)
OFFONDouble input discrepancy
SA\Xm+1
*2
inputs
detection error
detection error
*3
*3
*3
*3
*1 n: Even number from 0 to A
*2 m: Safety device address (even number from 0 to A) assigned to the master station
*3 When the double input discrepancy detection time has not elapsed, the input is OFF and the safety input status is ON.
Setting procedure
Set the double input discrepancy detection time in "Double input discrepancy detection time" from the "Parameter Processing
of Slave Station" window of the engineering tool.
For the procedure to display the "Parameter Processing of Slave Station" window, refer to the following.
Page 67 Module parameter setting procedure
54
7 FUNCTIONS
7.3 Input Diagnostic Function
Page 57
■Double input discrepancy detection time
NC
NC
T0T1X0X1
Test pulse
Test pulse
Safety remote I/O module
100ms
2ms
ON
OFF
ItemSetting range
Double input discrepancy detection time Xn/Xn+1
(n: even number from 0 to A)
10 to 30000 (ms) (default value: 10)
• A double input discrepancy error is detected in signals after the input response time has passed. Therefore,
the time taken from when actual signals are in the discrepancy state until when a double input discrepancy
detection error occurs is equal to the input ON delay, input OFF delay time + double input discrepancy
detection time.
• Set the double input discrepancy detection time based on the following values: 100ms for mechanical
switches and 20ms for sensor inputs.
Input dark test function
This function outputs test pulses to turn off the external input signals (X0 to XB) that are on for a short time and diagnoses
contacts including external devices for failure.
When failure is detected, a minor error occurs. The module will recover from the error by eliminating its cause.
To use this function, settings of "Input mode setting" and "Input test pulse setting" are required.
The function detects internal circuit fixing, a short circuit caused by another safety input in one M12 connector as well as a
short circuit on 24G in the same M12 connector, on the condition that contacts of external devices are closed.
7
To use the input dark test function, use the test pulse output terminals (T0 to TB) and connect input devices.
To use the input dark test function, use the input terminals and test pulse output terminals (T0 to TB) of the safety remote I/O
module in the following combinations. An incorrect combination is regarded as a disconnection, and a minor error (input dark
test error) may occur.
The input dark test function can be used only when "Input mode setting" is set to "2: Input dark test execution".
Test pulse output terminalInput terminalTest pulse output terminalInput terminal
T0X0T6X6
T1X1T7X7
T2X2T8X8
T3X3T9X9
T4X4TAXA
T5X5TBXB
The test pulse is output every 100ms, and the pulse width is fixed at 2ms.
7 FUNCTIONS
7.3 Input Diagnostic Function
55
Page 58
Operation at error detection
When an error is detected in a diagnostic of the input dark test function, the minor error (input dark test error) state is applied.
For details on the minor error state, refer to the following.
Page 95 Error Code List
Setting procedure
■Input mode setting
Set whether to perform the input dark test function or not in "Input mode setting" from the "Parameter Processing of Slave
Station" window of the engineering tool.
For the procedure to display the "Parameter Processing of Slave Station" window, refer to the following.
Page 67 Module parameter setting procedure
ItemSetting range
Input mode setting X0 to XB1: Not used (default)
• When "Input mode setting" is set to "1: Not used", the input value is always 0, and the safety input status is
always ON.
• When "Input mode setting" is set to "2: Input dark test execution", set "Input test pulse setting" to "1: With
test pulse".
2: Input dark test execution
3: Input dark test non-execution
■Input test pulse setting
To perform the input dark test function, set "Input test pulse setting" from the "Parameter Processing of Slave Station" window
of the engineering tool.
For the procedure to display the "Parameter Processing of Slave Station" window, refer to the following.
Page 67 Module parameter setting procedure
ItemSetting range
Input test pulse setting X0 to XB1: With test pulse
2: Without test pulse (default)
56
7 FUNCTIONS
7.3 Input Diagnostic Function
Page 59
7.4Output Diagnostic Function
MC
MC
Y1
Y0
24G(L PW)
24G(L PW)
+24V(L PW)
Load
Load
Load power supply
Safety remote I/O
module
Output circuit
Test pulse
Test pulse
Read-back
circuit
MC
MC
Y0-
Y0+
24G(L PW)
+24V(L PW)
Load
Load
Load power supply
Safety remote I/O
module
Output circuit
Test pulse
Test pulse
Read-back
circuit
Output dark test function
This function outputs test pulses to turn off the external output signals (NZ2GFS12A2-16DTE: Y0 to Y3, NZ2GFS12A2-14DT:
Y0 to Y1) that are on for a short time and diagnoses the internal circuit for failure.
When failure is detected, a minor error occurs. The module will recover from the error by eliminating its cause.
For NZ2GF12A2-16DTE, the following can be detected: Internal circuit fixing, a short circuit on the power supply caused by an
external output signal, and a short circuit caused by another safety output in one M12 connector.
For NZ2GF12A2-14DT, the following can be detected: Internal circuit fixing, a short circuit on +24V caused by a source output
signal, a short circuit on 24G caused by a sink output signal, and disconnection of an output signal.
In addition, the OFF time for test pulses can be set depending on the usage environment.
• NZ2GFS12A2-16DTE
7
• NZ2GFS12A2-14DT
Depending on a timing, the output dark test pulse width may be shorter than the time set in "Output dark test
pulse time".
7 FUNCTIONS
7.4 Output Diagnostic Function
57
Page 60
Operation at error detection
When the module detects an error in a diagnostic of the output dark test function, the minor error (output dark test error) state
is applied and all output points are turned off. For details on the minor error state, refer to the following.
Page 95 Error Code List
Setting procedure
Set the following parameters for the output dark test function.
■Output mode setting
Set whether to perform the output dark test function or not in "Output mode setting" from the "Parameter Processing of Slave
Station" window of the engineering tool.
For the procedure to display the "Parameter Processing of Slave Station" window, refer to the following.
Page 67 Module parameter setting procedure
ModelItemSetting range
NZ2GFS12A2-16DTEOutput mode setting Y0 to Y31: Not used (default)
• For the NZ2GFS12A2-16DTE, when "Wiring selection of output" is set to "1: Double wiring", set the same
value for both Yn and Yn+1.
• When "Output mode setting" is set to "1: Not used", the output value is always OFF.
• Set the same value to both "Output mode setting" (Yn) and "Output mode setting" (Yn+1) regardless of the
setting of "Wiring selection of output" (Yn/Yn+1).
2: Output dark test execution
3: Output dark test non-execution
■Output dark test pulse time
Set the output dark test pulse time in "Output dark test pulse time" from the "Parameter Processing of Slave Station" window
of the engineering tool.
For the procedure to display the "Parameter Processing of Slave Station" window, refer to the following.
Page 67 Module parameter setting procedure
ModelItemSetting range
NZ2GFS12A2-16DTEOutput dark test pulse time Y0 to Y33 to 100 (100s) (default value: 7)
NZ2GFS12A2-14DTOutput dark test pulse time Y0 to Y1
• Adjust the output dark test pulse time depending on the installation environment or wiring length.
• For "Output dark test pulse time", using the default value is recommended because almost any applications
can operate with "Output dark test pulse time" set to the default value.
58
7 FUNCTIONS
7.4 Output Diagnostic Function
Page 61
Output read-back function
MC
MC
Y1
Y0
24G(L PW)
24G(L PW)
+24V(L PW)
Load
Load
Load power supply
Safety remote I/O
module
Output circuit
Read-back
circuit
Output signal
Output signal
24G(L PW)
+24V(L PW)
MC
MC
Y0-
Y0+
Load power supply
Safety remote I/O
module
Output circuit
Read-back
circuit
Load
Load
Output signal
Output signal
This function reads back output results and diagnoses whether the external output signals (NZ2GFS12A2-16DTE: Y0 to Y3,
NZ2GFS12A2-14DT: Y0 to Y1) are correctly output.
When an incorrect output is detected, a minor error occurs. The module will recover from the error by eliminating its cause.
By diagnosing whether the status of output terminals matches with the output data of the safety device, this function detects
output operation errors in the module. To use this function, setting parameters is not required.
• NZ2GFS12A2-16DTE
7
• NZ2GFS12A2-14DT
Operation at error detection
When the safety remote I/O module detects an error in an output read-back function diagnostic, the minor error (output read-
back error) state is applied and all output points are turned off. For details on the minor error state, refer to the following.
Page 95 Error Code List
• When an error is detected in the input dark test and input internal dark test, the minor error state is applied
to the module.
• The maximum output voltage in the output OFF state is 1.2V. However, even though the voltage exceeds
1.2V due to a short circuit or failure of the hardware, no error is detected until the voltage exceeds 7V. Thus,
connected devices may turn on although the output of the module is in the OFF state.
7 FUNCTIONS
7.4 Output Diagnostic Function
59
Page 62
7.5User Authentication Function
This function limits the users who can access the Safety CPU or safety remote I/O module.
Using this function permits only the specified users to access the Safety CPU or safety remote I/O module.
This function is implemented in the Safety CPU used. For details on the user authentication function, refer to the following.
MELSEC iQ-R CPU Module User's Manual (Application)
Online operations that require user authentication
The following table lists the online operations that require user authentication. No limitation is applied to the access levels of
the user authentication function. With any access level of "Administrators", "Developers", "AssistantDevelopers", and "Users",
the operations can be performed after the user authentication.
Operation nameNecessity of user authenticationOnline operation
"Parameter read"Necessary
"Parameter write"Necessary
"Error history read"Necessary
"Start of checking the module position"Necessary
"Stop of checking the module position"Necessary
"Error history clear request"Necessary
"Safety module validation"Necessary
"CC-Link IE Field Diagnostics"Not necessary"CC-Link IE Field Diagnostics"
"Remote Operation"Not necessary
*1
*1
*1
*1
"Parameter Processing of Slave Station"
"Command Execution of Slave Station"
*1 To access the remote buffer memory using a program and perform the operations, the user authentication is not necessary.
60
7 FUNCTIONS
7.5 User Authentication Function
Page 63
7.6Protection Functions
This function protects the internal circuit from overvoltage or overcurrent.
The following table lists protection functions.
: Available, : Not available
Function namePurposeDescriptionTarget module
NZ2GFS12A2
-16DTE
Module power supply
overvoltage protection
Module power supply
overcurrent protection
Load power supply
overvoltage protection
Load power supply
overcurrent protection
Output overload/short
circuit protection
Prevents ignition or burnouts from/of the
safety remote I/O module due to overvoltage
on the module power supply.
Prevents ignition or burnouts from/of the
safety remote I/O module due to overcurrent
on the module power supply.
Prevents ignition or burnouts from/of the
safety remote I/O module and load circuits
due to overvoltage on the load power
supply.
Prevents ignition or burnouts from/of the
safety remote I/O module and load circuits
due to overcurrent on the load power supply.
Prevents ignition or burnouts from/of the
safety remote I/O module due to overcurrent
or overheat resulting from short-circuits of
the output circuit.
This function operates when the module
power supply is in the overvoltage state.
After a voltage of 36VDC or higher applied
for 2 seconds or longer activates the
overvoltage protection, the safety state is
ensured and thus the function is disabled.
This function operates when the module
power supply is in the overcurrent state.
This function operates when the load power
supply is in the overvoltage state.
After a voltage of 36VDC or higher applied
for 2 seconds or longer activates the
overvoltage protection, the safety state is
ensured and thus the function is disabled.
This function operates when the load power
supply is in the overcurrent state.
This function operates when overcurrent
flows. The safety remote I/O module
recovers by eliminating the cause.
NZ2GFS12A2
-14DT
7
• The protection functions are intended to protect the internal circuit of a module, not to protect external
devices.
• An overload may cause the internal temperature of the module to rise, resulting in deterioration in output
elements and discoloration on the case and the printed-circuit board. When an abnormal load is found, turn
off the corresponding output immediately and eliminate the cause.
7 FUNCTIONS
7.6 Protection Functions
61
Page 64
8PARAMETER SETTINGS
Configure the following parameter settings.
• Module parameter setting of the master station
Page 64 Module Parameter Setting of the Master Station
The overview of the parameter setting procedure is shown below.
1. Preparation
Perform the following before parameter settings.
• Configure the system.
• Start the engineering tool.
• Set the Safety CPU to the TEST MODE.
For details on the TEST MODE of the Safety CPU, refer to the following.
MELSEC iQ-R CPU Module User's Manual (Application)
2. Network Configuration Settings
Write the network configuration settings to the Safety CPU.
Page 65 Module parameter setting procedure
3. Parameter Processing of Slave Station
Perform the parameter processing of slave station.
Page 67 Module parameter setting procedure
Step 1 to 7
*1
4. Safety Communication Setting
Write the safety communication setting of the master station to the Safety CPU.
Page 67 Module parameter setting procedure
Step 8 to 12
5. Checking the position of the setting target module
Perform the checking of the position of the safety remote I/O module where the parameters are set.
Page 67 Module parameter setting procedure
Step 13 to 18
6. Safety module validation
Switch the safety remote I/O module to the state where safety communications are enabled (safety drive mode).
Page 67 Module parameter setting procedure
Step 19 to 23
*1 Perform the operations to all safety remote I/O modules connected.
*1
*1
62
8 PARAMETER SETTINGS
Page 65
• Write the safety communication setting to the Safety CPU after completing "Parameter write" to all safety
remote I/O modules connected. Failure to do so may cause an error (parameter mismatch of Safety CPU
and safety remote I/O module) in the Safety CPU at the restart of the safety remote I/O module.
• No restrictions are provided on the access level for writing parameters to the safety remote I/O module.
However, when the access level is "Users", even though parameters have been set to the safety remote I/O
module, safety communications are disabled because the safety communication setting cannot be set in the
Safety CPU. To perform the safety communications, set the setting with "Developers" or a higher access
level. For details on the access levels, refer to the following.
GX Works3 Operating Manual
• If the safety remote I/O module is left with "Safety module validation" not being performed for 10 minutes or
longer, a minor error (safety module validation not performed) occurs.
8
8 PARAMETER SETTINGS
63
Page 66
8.1Module Parameter Setting of the Master Station
The following parameters are required to use the safety remote I/O module. The parameters are automatically set when a
safety remote I/O module is added in the "Network Configuration Settings". Change the start number and end number of the
RX/RY Setting or RWw/RWr Setting as necessary.
ItemDescription
STA#Set the station number of the safety remote I/O module.
Station TypeSet "Remote Device Station".
RX/RY SettingPoints80 points
RWw/RWr SettingPoints16 points
• When using the safety remote I/O module, always enable "Station-based Block Data Assurance" of the
master station. When it is disabled, correct operation of the safety remote I/O module cannot be
guaranteed. For the station-based block data assurance, refer to the following.
12. Write the parameters to the programmable controller again.
• When newly setting the module parameters of the safety remote I/O module, be sure to set "Safety
Communication Setting" and write the parameters to the programmable controller after that.
• When changing the station number or network configuration, be sure to set "Safety Communication Setting"
and write the parameters to the programmable controller as well.
• When changing only the module parameters of the safety remote I/O module without changing the station
number or network configuration, setting "Safety Communication Setting" is not required. However, be sure
to write the parameters to the programmable controller after that.
13. When parameter writing to the programmable controller is completed, select the target safety remote I/O module in the
"Network Configuration Settings" and display the "Command Execution of Slave Station" window.
[Network Configuration Settings] Select the target safety remote I/O module. [CC IE Field Configuration] [Online]
[Command Execution of Slave Station]
70
8 PARAMETER SETTINGS
8.2 Module Parameter Setting
Page 73
14. Select "Start of checking the module position" in "Method selection" and click the [Execute] button.
15. Clicking the [Execute] button displays a confirmation window. Check the contents and click the [Yes] button. The
SAFETY LED of the selected safety remote I/O module starts flashing. Visually check that the safety remote I/O module
on which the SAFETY LED is flashing is installed on the desired position. At the same time, visually check that the
SAFETY LEDs of other safety remote I/O modules not targeted for the position checking are not flashing.
16. After checking the module position is completed, select "Stop of checking the module position" in "Method selection" on
the "Command Execution of Slave Station" window and click the [Execute] button.
17. Clicking the [Execute] button displays a confirmation window. Check the contents and click the [Yes] button. The
SAFETY LED of the safety remote I/O module turns off.
18. Perform the operations from "Start of checking the module position" to "Stop of checking the module position" for all
safety remote I/O modules connected.
19. Select "Safety module validation" in "Method selection" and click the [Execute] button.
20. Clicking the [Execute] button displays the following confirmation window. Check the contents, and if the operations
mentioned on the window are completed, click the [Yes] button. When the operations are not completed, click the [No]
button. After performing the operations of "[Confirm 1]" and "[Confirm 2]", perform "Safety module validation" again.
21. Clicking the [Yes] button displays a confirmation window. Check the contents and click the [Yes] button. The following
window is displayed and the parameters set to the safety remote I/O module are validated.
8
When "Safety module validation" is executed with the Safety CPU set in SAFETY MODE, an error window is
displayed and the Safety module validation is stopped. For details on SAFETY MODE, refer to the following.
MELSEC iQ-R CPU Module User's Manual (Application)
8 PARAMETER SETTINGS
8.2 Module Parameter Setting
71
Page 74
22. Restart the safety remote I/O module. The SAFETY LED turns on and the mode shifts to the safety drive mode.
23. Perform the operations from "Safety module validation" to the restart of the safety remote I/O module for all safety
remote I/O modules connected.
"Safety module validation" is cancelled if the following situations arise after the validation performance.
• The parameters have been set again.
• A parameter data error has occurred.
When the safety remote I/O module where "Safety module validation" has been performed is connected to the
different system, the SAFETY LED turns off even though the validation of the safety remote I/O module is not
cancelled. Therefore, perform again "Parameter write" and "Safety module validation".
Module parameter list
This section shows lists of the module parameters of the safety remote I/O module. The following parameters cannot be set
from a program.
• Items to input from the pull-down list
Select a setting value from the pull-down list.
• Items to input in the text box
Input a numerical value within "Setting Range" as a setting value.
2Power supply voltage checkMeasure the voltage across
3Installation
status
4Connection
status
*1 The ambient temperature is a temperature in the control panel when the safety remote I/O module is installed in a control panel.
Looseness and
rattling
Looseness of
connecting plugs
*1
Warning
Shut off the power supply externally before cleaning. Failure to do so may cause the module to fail or malfunction.
Precautions
• Do not disassemble or modify the module. Doing so may cause failure, malfunction, injury, or a fire.
• Shut off the power supply externally (all phases) before mounting or removing the module. Failure to do so may cause the
module to fail or malfunction.
• Do not touch any conductive parts and electronic components of the module. Doing so can cause malfunction or failure of
the module.
Measure the temperature by
using a thermometer.
hygrometer.
24VDC terminals.
Check for looseness or rattling by
shaking the module lightly.
Check for looseness by shaking
connecting plugs lightly.
0 to 55Create the environment that
satisfies the judgment criterion.
5 to 95%RH
20.4 to 28.8VDCChange the supply power.
The module must be installed
securely.
The connecting plugs must not
be loose.
Retighten screws securely.
Make sure that the plugs are
securely connected.
78
9 MAINTENANCE AND INSPECTION
9.2 Periodic Inspection
Page 81
10 TROUBLESHOOTING
This chapter describes the errors that may occur while the safety remote I/O module is used and their troubleshooting.
10.1Checking the LEDs
This section describes how to troubleshoot the system by the LEDs.
When the PW LED is on in red
Check itemAction
Is the voltage of the module power supply within the specified range? Set the voltage value within the range of performance specifications.
Is the operating ambient temperature within the specified range?Set the operating ambient temperature within the range of general specifications.
When the PW LED does not turn on
Check itemAction
Is any LED other than the PW LED turned on?When any LED other than the PW LED turns on, the possible cause is a hardware
failure. Please consult your local Mitsubishi representative.
Is the module power supply wired?Wire the module power supply.
Is the module power supply turned on?Turn on the module power supply.
Is the voltage of the module power supply within the specified range? Set the voltage value within the range of performance specifications.
When the L PW LED is on in red
Check itemAction
Is the voltage of the load power supply within the specified range?Set the voltage value within the range of performance specifications.
Is the operating ambient temperature within the specified range?Set the operating ambient temperature within the range of general specifications.
10
When the L PW LED does not turn on
Check itemAction
Is the load power supply wired?Wire the load power supply.
Is the load power supply on?Turn on the load power supply.
Is the voltage of the load power supply within the specified range?Set the voltage value within the range of performance specifications.
When the I/O LED is on in red
Check itemAction
Is the voltage of the load power supply within the specified range?Set the voltage value within the range of performance specifications.
Is the supply current to the module power supply or the output current
whose I/O LED is on in red within the specified range?
Is the operating ambient temperature within the specified range?Set the operating ambient temperature within the range of general specifications.
Is any input or output where the LED is on in red short-circuited?Check the wiring of the input or output and remove the short-circuit.
Set the current value within the range of performance specifications.
10 TROUBLESHOOTING
10.1 Checking the LEDs
79
Page 82
When the I/O LEDs flash in red for all points
Check itemAction
Does the voltage of the module power supplied externally reach the
voltage of the specifications?
Are the device connection and wiring correct?Check that the device connection and wiring are correct.
Is the operating ambient temperature within the specified range?Set the operating ambient temperature within the range of general specifications.
Has any hardware failure occurred?If the same error occurs again even after performing the above actions and turning off
Check that module power supply voltage is within the range of specifications.
and on the module power supply, the module may be in failure. Please consult your
local Mitsubishi representative.
The above error is a module stop state (hardware failure), and thus other LEDs may not operate or the error history may not
be saved.
When the RUN LED does not turn on
Check itemAction
Does the voltage of the module power supplied externally reach the
voltage of the specifications?
Has any hardware failure occurred?
Check that the module power supply voltage is within the range of performance
specifications.
Page 20 Performance Specifications
After the check, turn off and on the module power supply.
If the RUN LED does not turn on even after the module power supply is turned off and
on, the module may be in failure. Please consult your local Mitsubishi representative.
When the RUN LED flashes
Check itemAction
Does the voltage of the module power supplied externally reach the
voltage of the specifications?
Are the device connection and wiring correct?Check that the device connection and wiring are correct.
Has any hardware failure occurred?If the same error occurs again even after performing the above actions and turning off
Check that module power supply voltage is within the range of specifications.
and on the module power supply, the module may be in failure. Please consult your
local Mitsubishi representative.
When the MODE LED flashes
Check itemAction
Is the safety remote I/O module in execution of the unit test?When the safety remote I/O module is in execution of the unit test, the MODE LED
turns off after the unit test is completed. Take corrective action according to the result
of the unit test.
Page 88 Unit Test
When the ERR. LED flashes or turns on
Check itemAction
Has any error occurred?Identify the error factor of the safety remote I/O module with the engineering tool and
take corrective actions.
Page 85 Checking error codes and warning codes
80
10 TROUBLESHOOTING
10.1 Checking the LEDs
Page 83
When the D LINK LED turns off
Check itemAction
Does the own station in network operate normally?Connect the engineering tool to the master station, and then check that a data link is
Are 1000BASE-T-compliant Ethernet cables used?Replace the cable with a 1000BASE-T-compliant Ethernet cable.
Is the station-to-station distance 100m or less?Change the station-to-station distance to 100m or less.
Does the cabling condition (bending radius) meet the specifications?Refer to the manual for the Ethernet cable used, and correct the bending radius.
Is any Ethernet cable disconnected?Replace the Ethernet cable.
Are other stations connected to the safety remote I/O module
normally operating?
Does the switching hub normally operate?• Check that a 1000BASE-T-compliant switching hub is used.
Is a same station number set to both the safety remote I/O module
and any of other stations?
established in the own station by using CC IE Field diagnostics.
User's manual for the master/local module used
User's manual for the master/local module used
Check that the power supplies of the other stations are turned on.
User's manual for the master/local module used
• Check that the power supply of the switching hub is turned on.
Two or more stations use a same station number.
Change the setting so that all the station numbers are different.
When the D LINK LED flashes
Check itemAction
Does the station number setting of the safety remote I/O module
match the station number of the safety remote I/O module specified in
the network configuration settings of the master station or in the CC
IE Field Configuration?
Does the station type match?Match the station type of the safety remote I/O module with the station type specified
Is the safety remote I/O module a reserved station?Change the setting of reserved/error invalid station to other than the reserved station
Is the station number setting switch set to other than 1 to 120?Change the setting within the range from 1 to 120.
Is stop of the data link checked through CC-Link IE Field Network
diagnostics?
Has the connection been changed to the other master station with a
different network number?
Match the station number of the safety remote I/O module with the station number
specified in the network configuration settings of the master station or in the CC IE
Field Configuration.
in the network configuration settings of the master station or in the CC IE Field
Configuration.
in the network configuration settings of the master station.
Check the link status through CC-Link IE Field Network diagnostics and start the link
when the data link is stopped.
• Correct the connection to the previous master station.
• To communicate with the master station with a different network number, switch the
power supply of the safety remote I/O module off and on.
10
When the L ER LED turns on
Check itemAction
Are Ethernet cables normal?• Check that 1000BASE-T-compliant Ethernet cables are used.
Does the switching hub in the system normally operate?• Check that a 1000BASE-T-compliant switching hub is used.
Are other stations connected to the safety remote I/O module
normally operating?
Is the mode of the module on the master station set to other than
Online?
Is there any noise affecting the system?• Check the status of wiring.
Is the loopback function enabled for the master station?When the loopback function is enabled, check that the ring topology is correctly
*1 When the safety remote I/O module is installed in the control panel or steel shelf, the FG metal fitting of the safety remote I/O module
can be connected electrically with them. Thus, if the control panel or steel shelf is not properly grounded, the noise may enter the FG
through the control panel or steel shelf.
User's manual for the master/local module used
• Check that the station-to-station distance is 100m or less.
• Check that the Ethernet cables are not disconnected.
User's manual for the master/local module used
• Check that the power supply of the switching hub is turned on.
Check that the power supplies of the other stations are turned on.
Change the mode of the module to Online.
• Ground the control panel or the steel shelf where a safety remote I/O module is
configured for the PORT where the L ER LED is on.
User's manual for the master/local module used
installed.
*1
10 TROUBLESHOOTING
10.1 Checking the LEDs
81
Page 84
When the LINK LED turns off
Check itemAction
Are Ethernet cables normal?• Check that 1000BASE-T-compliant Ethernet cables are used.
Do the switching hub and other stations in the system normally
operate?
User's manual for the master/local module used
• Check that the station-to-station distance is 100m or less.
• Check that the Ethernet cables are not disconnected.
• Check that a 1000BASE-T-compliant switching hub is used.
User's manual for the master/local module used
• Check that the power supplies of the switching hub and other stations are turned on.
If link-up processing is repeated due to a condition of a device on the line, it may take a longer time for the
LINK LED to turn on.
This phenomenon may be eliminated by changing the module PORT into which the Ethernet cable is
connected (example: PORT1 PORT2).
When the SAFETY LED turns off
Check itemAction
Have parameters been set to the safety remote I/O module?Set the parameters of the safety remote I/O module.
Page 67 Module parameter setting procedure
Has the safety communication setting been configured?Configure the safety communication setting. Then, write the parameters to the
programmable controller. For the safety communication setting, refer to the following.
User's manual for the CPU module used
Has the safety module validation been performed?Perform the safety module validation using the engineering tool.
Has the safety station interlock of the Safety CPU been canceled?Fully check the wiring and connection, and cancel the safety station interlock of the
Has any error occurred?Identify the error factor with the engineering tool and take corrective actions.
Is the operating ambient temperature within the specified range?Set the operating ambient temperature within the range of general specifications.
Safety CPU. For the safety station interlock, refer to the following.
User's manual for the CPU module used
Page 19 General Specifications
82
10 TROUBLESHOOTING
10.1 Checking the LEDs
Page 85
10.2Checking Module Status
Checking with the engineering tool
When the data link is established between the safety remote I/O module and the master station, errors can be checked on the
engineering tool.
• Page 83 Checking with "Command Execution of Slave Station"
• Page 85 Checking error codes and warning codes
When the user authentication function of the Safety CPU is enabled, perform the logon of the user
authentication function in advance. For the user authentication function, refer to the following.
Page 60 User Authentication Function
Checking with "Command Execution of Slave Station"
The following describes how to check errors with "Command Execution of Slave Station" in the "Network Configuration
Settings".
1. Select the safety remote I/O module in "List of stations" on the "CC IE Field Configuration" window.
10
2. Open the "Command Execution of Slave Station" window.
[CC IE Field Configuration] [Online] [Command Execution of Slave Station]
3. Set "Method selection" to "Error history read" and click the [Execute] button.
4. Clicking the "Execute" button displays a confirmation window. Check the contents and click the [Yes] button to read the
error history data.
5. When the following window is displayed, click the [OK] button.
10 TROUBLESHOOTING
10.2 Checking Module Status
83
Page 86
6. The error history of the safety remote I/O module is displayed in "Execution Result".
ItemContentsStorage example
Error and SolutionError codes and error details of the errors that have occurred are displayed.
Order of occurrence No.The order of error occurrence is displayed. (A value between 0 and 65535 is
[Error time] First two digits of the
year/Last two digits of the year
[Error time] Month/Day
[Error time] Hour/Minute
[Error time] Second/No Use
Error code details 1 to Error code
details 8
*2
*2
*2
*2
stored.)
The date and hour of error occurrence is displayed. (When the tens place of
Month, Hour, and Second is "0", "0" is omitted.)
The detailed information of some errors is stored. The data to be stored
depends on the error.
Page 98 Error code details
2015
829
1035
4000
*1
*1 Values of when an error occurs at 10:35:40, August 29th, 2015
*2 The clock information of the error that occurred is based on the clock information acquired from the Safety CPU of the master station.
When an error has occurred before the clock information is acquired from the Safety CPU, the error time is not recorded.
• The error history registers 15 errors at a maximum. If 16 or more errors occur, errors are deleted from the
oldest.
• If the same error occurs continuously, only the error that occurred latest is stored to the error history. Thus,
"Order of occurrence No." and "Error time" of the error history are updated at the timing an error occurs.
• Even after the module power supply is turned off and on, the error history remains.
• The clock information of the error that occurred is based on the clock information acquired from the Safety
CPU of the master station. To obtain the exact occurrence time of an error, set the clock information of the
Safety CPU to the actual time.
• To initialize the error history, set "Method selection" to "Error history clear request" on the "Command
Execution of Slave Station" window and click the [Execute] button.
84
10 TROUBLESHOOTING
10.2 Checking Module Status
Page 87
Checking error codes and warning codes
Ex.
Ex.
The latest error code and warning code of the safety remote I/O module can be checked with the remote register of the master
station.
■Checking the Error code (RX10 to RX1F)
Check the error codes with the remote register of the master station.
When the refresh target device for Warning code (RX20 to RX2F) is W102
10 TROUBLESHOOTING
10.2 Checking Module Status
85
Page 88
10.3Checking Network Status
(1)
(2)
(4)
(3)
(5)
*1
With CC-Link IE Field Network diagnostics, whether any network error has occurred or not can be checked through the
engineering tool connected to the Safety CPU.
How to use
1. Connect the engineering tool to the Safety CPU.
2. Start the CC-Link IE Field Network diagnostics from the menu of the engineering tool.
[Diagnostics] [CC-Link IE Field Diagnostics]
Item to be diagnosedDescriptionReference
(1)Display of network configuration
diagram and error status
Display of cable disconnection and
disconnected station
(2)Display of selected-station status and
(3)Communication TestThe transient communication route and whether the
(4)Reserved Station Function EnableA reservation for a station can be temporarily cleared, and the
(5)Remote OperationThe selected station can be reset through the remote operation. Page 87 Remote operation
error details
Station number setting of slave
stations
IP Communication TestThe reaching time and the route of the IP communication from
Cable TestThe cable status between the connected station and the
Link Start/StopThe network data link can be started or stopped.
Enable/Disable Ignore Station ErrorsA station not set as an error invalid station can be temporarily
The status of the CC-Link IE Field Network can be checked.
When an error or a warning has occurred in the safety remote I/
O module, the status of the station is displayed on an icon.
The communication status of the station selected in "Networks
Status" can be checked.
communication is established from the connected station to the
destination station can be checked.
the connected station to the target station can be checked. This
function cannot be used for the safety remote I/O module.
destination station can be checked.
clearing can be canceled. Also, the station numbers for the
modules set as reserved stations can be checked on a list.
set as an error invalid station, and the error invalid station
setting can be canceled. Also, the station numbers for the
modules set as (temporary) error invalid stations can be
checked on a list.
*1 The information displayed on the upper left of "Selected Station Communication Status Monitor" indicates the communication status of
the safety remote I/O module and does not indicate the error status of the selected module. For the error status of the module, refer to
the following.
Page 83 Checking Module Status
Remote operation
1. Select a slave station to be reset and click the [Remote Operation] button.
2. Clicking the [Yes] button starts the remote reset.
3. Click the [OK] button.
10
10 TROUBLESHOOTING
10.3 Checking Network Status
87
Page 90
10.4Unit Test
Run a unit test to check if there is any hardware failure in the safety remote I/O module.
1. Turn off the module power supply.
2. Connect the PORT1 and PORT2 connectors of the
safety remote I/O module with an Ethernet cable.
3. Set the station number setting switch as follows.
• x10: TEST
•x1: 0
For the setting procedure of the station number setting
switch, refer to the following.
Page 35 Setting procedure
4. Turn on the module power supply.
5. Unit test begins.
The MODE LED flashes while the unit test is being executed.
6. The MODE LED turns off when the unit test is
completed.
• If the test is completed normally, the ERR. LED does not
turn on, but remains off.
• If the test fails, the ERR. LED turns on. If the test fails,
replace the Ethernet cable and run the test again. If the
test fails again, it may be due to a hardware failure in the
safety remote I/O module. Please consult your local
Mitsubishi representative.
88
10 TROUBLESHOOTING
10.4 Unit Test
Page 91
10.5Troubleshooting by Symptom
This section describes troubleshooting for each phenomenon.
Perform the troubleshooting by symptom when the safety remote I/O module does not operate properly with no error. If an
error occurs in the safety remote I/O module, identify the cause of the error using the engineering tool.
Check the following items in the order from the top.
When the ON/OFF status of an external input cannot be read
Check itemAction
Is the SAFETY LED on?When the SAFETY LED is not on, the safety module validation has not been performed or the Safety CPU
Is the corresponding I/O LED of the safety
remote I/O module on when an external input
device is on?
Is the setting of the refresh device correct?Check and correct the device setting of the safety communication setting so that the setting of the refresh
Is there any incorrect setting in the wiring
selection of input?
is in the safety station interlock status. Take the following actions.
• Perform the safety module validation. For the safety module validation, refer to the following.
Page 67 Module parameter setting procedure
• Fully check the wiring and connection, and cancel the safety station interlock of the Safety CPU. For the
safety station interlock, refer to the following.
MELSEC iQ-R CPU Module User's Manual (Application)
If the LED does not turn on, there is a problem on the input wiring. Check the wiring confirming that the
input wiring is not disconnected or short-circuited, or the voltage of the input signal is correct. For the rated
input voltage range, refer to the following.
Page 20 Performance Specifications
Refer to the following as well.
Page 91 Troubleshooting for input circuit
device matches the setting in the program. For details on the device setting of the safety communication
setting, refer to the following.
Review the settings in the wiring selection of input.
Page 45 Input wiring selection function
10
When the ON/OFF status of an external output cannot be changed
Check itemAction
Is the SAFETY LED on?When the SAFETY LED is not on, the safety module validation has not been performed or the Safety CPU
Is the corresponding I/O LED of the safety
remote I/O module on?
Is the setting of the refresh device correct?Check and correct the refresh parameter so that the setting of the refresh device matches the setting in the
Is there any incorrect setting in the wiring
selection of output?
is in the safety station interlock status. Take the following actions.
• Perform the safety module validation. For the safety module validation, refer to the following.
Page 67 Module parameter setting procedure
• Fully check the wiring and connection, and cancel the safety station interlock of the Safety CPU. For the
safety station interlock, refer to the following.
MELSEC iQ-R CPU Module User's Manual (Application)
If the LED turns on, there is a problem on the output wiring. Check the wiring confirming that the output
wiring is not disconnected or short-circuited. Refer to the following as well.
Page 93 Troubleshooting for output circuit
program. For the setting of the refresh parameter, refer to the following.
Review the settings in the wiring selection of output.
Page 50 Output wiring selection function
When External output ON signal intermittently turns off
Check itemAction
Is an output dark test being executed?Check the specifications of the safety devices used, and review the setting of the output dark test pulse
OFF time.
Page 57 Output dark test function
10 TROUBLESHOOTING
10.5 Troubleshooting by Symptom
89
Page 92
When the safety remote I/O module cannot be accessed using the engineering tool
Check itemAction
Is the D LINK LED on?Check the D LINK LED. When the LED is not on, refer to the following to perform troubleshooting.
Is the version of the module on the master
station correct?
Is the version of the engineering tool supported? Check the version of the engineering tool, and if the version is not the applicable one, update the
Do the network parameter settings of the master
station and those of the Safety CPU match?
• Page 81 When the D LINK LED turns off
• Page 81 When the D LINK LED flashes
Refer to the following to check other LEDs.
Page 79 Checking the LEDs
Check the firmware version of the module on the master station, and if the version is not the applicable one,
replace the module with a module of the applicable version or later. For the applicable version, refer to the
following.
Page 33 Applicable products
engineering tool. For the applicable version, refer to the following.
Page 33 Software package
Perform "Verify with PLC" on the network parameters to check that those settings match. When they do not
match, execute "Write to PLC" and "Read from PLC" to match the network parameter settings, and write
the module parameters of the slave station.
90
10 TROUBLESHOOTING
10.5 Troubleshooting by Symptom
Page 93
10.6Fault Examples with the Safety Remote I/O Module
Xn
Tn
24G(PW)
Safety remote I/O module
(negative common)
Leakage current
Xn
Tn
24G(PW)
Safety remote I/O module
(negative common)
Leakage current
Xn
Tn
24G(PW)
Safety remote I/O module
(negative common)
Test pulse
not used
Xn
Tn
24G(PW)
Safety remote I/O module
(negative common)
Test pulse
used
IN
24G(PW)
Safety remote I/O module
Leakage current of 2mA
24VDC
Troubleshooting for input circuit
This section describes the troubleshooting for input circuit.
An input signal does not turn off.
■Cause
• Drive by a switch with LED indicator (test pulse not used)
• Drive by a switch with LED indicator (test pulse used)
■Action
Connect an appropriate resistor as shown below so that a current through the safety remote I/O module may become lower
than the OFF current.
10
For the calculation example of a resistor to be connected, refer to the following.
Page 91 Calculation example
■Calculation example
When the module power supply of the safety remote I/O module is on and a switch with LED indicator that has a leakage
current of 2mA at a maximum is connected
1. The OFF current through the safety remote I/O module is more than 1.5mA. Therefore, connect a resistor as shown
below.
I
= 0.5mA
R
Z: Input impedance
2mA
R
24VDC
IN
I
Z = 4kΩ
24G(PW)
= 1.5mA
Z
10 TROUBLESHOOTING
10.6 Fault Examples with the Safety Remote I/O Module
91
Page 94
2. To ensure that the OFF current of the safety remote I/O module is 1.5mA or lower, the current through the connected
Ex.
R≤
I
R
I
Z
0.5
1.5
× Z =× 4 = 12[kΩ]
W = V2R = 26.4
2
÷
5600 = 0.125[W]
÷
× 2[mA] = 4.67[V]
5.6[kΩ]
1
4[kΩ]
1
+
1
resistor should be 0.5mA or more, so that the value of the connected resistor is lower than 12 k.
: IZ = Z: R
I
R
3. When the resistor (R) is 5.6 k, the power capacity (W) of the resistor (R) becomes 0.125W.
V: Input voltage
4. Because the resistor requires the power capacity of 3 to 5 times as large as the actual current consumption, the resistor
connected to the terminal should be 5.6 k, and 0.5 to 0.75W.
5. OFF voltage when the resistor (R) is connected becomes 4.67V. This satisfies the condition that the OFF voltage of the
safety remote I/O module must be 5V or lower.
A signal incorrectly inputs data
■Cause
Noise is taken as input data.
■Action
• Set a long input ON/OFF delay.
1ms 5ms
For the setting procedure, refer to the following.
Page 49 Input ON delay, input OFF delay functions
If the above change has no effect, take the following two measures:
• To prevent excessive noise, avoid installing power cables together with I/O cables.
• Connect surge absorbers to noise-generating devices such as relays and conductors using the same power supply or take
other noise reduction measures.
92
10 TROUBLESHOOTING
10.6 Fault Examples with the Safety Remote I/O Module
Page 95
Troubleshooting for output circuit
Y1
Y0
24G (L PW)
24G (L PW)
+24V (L PW)
24G (L PW)
[2]
[1]
[3]
ON
OFF
Y1+
Y0+
Y1-
+24V (L PW)
24G (L PW)
ON
OFF
OFF
ON
Y0-
[3]
[2]
[1]
Load
Load
- Back EMF+
Safety remote I/O module
Source + Source output
Shut off
Load
Load
- Back EMF+
Safety remote I/O module
Sink + Source output
Shut off
Load
- Back EMF +
This section describes the troubleshooting for output circuit.
A load momentarily turns on when the load power supply is powered on
■Cause
When an inductive load is connected, the load [2] in the off state may turn on due to a sneak current from the back EMF at the
shutoff [1].
10
■Action
Take the action 1 or action 2 shown below.
1. To suppress the back EMF, connect a diode parallel to the load where the back EMF has been generated.
10.6 Fault Examples with the Safety Remote I/O Module
10 TROUBLESHOOTING
93
Page 96
2. Provide another current path by connecting a diode across positive and negative of the load power supply. When taking
Y1
Y0
24G (L PW)
24G (L PW)
+24V (L PW)
24G (L PW)
[2]
[1]
[3]
ON
OFF
C1
R1
D1
Load
Load
- Back EMF+
Safety remote I/O module
Source + Source output
Shut off
Ex.1
Y1+
Y0+
Y1-
+24V (L PW)
24G (L PW)
ON
OFF
OFF
ON
Y0-
C1
R1
D1
[1]
[2]
[3]
Load
Load
- Back EMF+
Safety remote I/O module
Sink + Source output
Shut off
Ex.1
the action described in Example 1 at a time, connect a diode parallel to C1 and R1.
D1:
Reverse voltage VR (VRM)
Forward current IF (IFM)
*1 Approximately 10 times as large as the rated voltage in the specifications
Example: 24VDC Approximately 200V
*2 Twice as much as the maximum load current in the specifications or more
Example: 8A 16A or higher
94
10 TROUBLESHOOTING
10.6 Fault Examples with the Safety Remote I/O Module
*2
*1
Page 97
10.7Error Code List
Error codes related to the safety remote I/O module
Errors of the safety remote I/O module are classified into the following three types.
Error status
Major errorError because of which the module stops, such as hardware failure. The safety functions (safety I/O, safety diagnostics, and safety
Moderate errorError because of which the module stops, such as a parameter error related to module operation. The safety functions (safety I/O, safety
Minor errorError after which the module continues its operation, such as double input discrepancy detection. The safety functions keep operating.
*1 When multiple errors have occurred, the error statuses are displayed in the order of error severity (Major error > Moderate error > Minor
error).
*1
Description
communications) stop.
diagnostics, and safety communications) stop.
List of error codes
Error code
(hexadecimal)
0001HMajor errorHardware failureA hardware failure was
0101HModerate errorSelf-diagnostic errorAn error was detected by the
*1
0102H
0103HModerate error
0105HModerate errorDate out of range errorIncorrect clock data was
0107HModerate errorRestart not performed
0201HMinor error
Classification Error nameDescription and causeAction
detected.
self-diagnostics.
Moderate errorOverload errorOvercurrent was detected in
Restoration
*2
possible
Restoration
possible
Power supply voltage
error
after safety module
validation
Safety module validation
not performed
the input power supply or
output power supply.
An error was detected in the
module power supply or load
power supply.
received from the CPU module.
The module has not been
restarted after the safety
module validation.
The safety module validation
has not been performed.
Set the operating ambient temperature within the range
of general specifications. If the operating ambient
temperature is within the range of general
specifications, there may be an influence from noise or
a hardware failure. If the same error occurs again even
after measures have been taken against noise, the
module may be in failure. Please consult your local
Mitsubishi representative.
• Review the connected devices, wiring, and voltage.
• Power on the load power supply at the same timing of
power-on of the module power supply.
• If the same error occurs again, the module may be in
failure. Please consult your local Mitsubishi
representative.
• Review the connected devices, wiring, and voltage.
• Power on the load power supply at the same timing of
power-on of the module power supply.
• There may be an influence from noise of external
wiring (such as power supply part and I/O signal part).
Review the connected devices and wiring.
• If the same error occurs again, the module may be in
failure. Please consult your local Mitsubishi
representative.
There may be an influence from noise or a hardware
failure. If the same error occurs again even after
measures have been taken against noise, the module
may be in failure. Please consult your local Mitsubishi
representative.
• Restart the safety remote I/O module. After the safety
remote I/O module validation, safety communications
can be established by restarting the module.
• If the same error occurs again even after the safety
remote I/O module has been restarted in no error
state, the module may be in failure. Please consult
your local Mitsubishi representative.
• Perform the safety module validation. After the safety
module validation, safety communications can be
established by restarting the module.
• If the same error occurs again even after "Safety
module validation" is executed in no error state, the
module may be in failure. Please consult your local
Mitsubishi representative.
10
10 TROUBLESHOOTING
10.7 Error Code List
95
Page 98
Error code
Classification Error nameDescription and causeAction
(hexadecimal)
0202HMinor error
Restoration
possible
*1
0203H
0204HMinor error
*1
0205H
*1
0206H
0207HMinor error
*1
0208H
*1
0209H
020AHMinor errorAccess error when
Minor error
Restoration
possible
Restoration
possible
Minor error
Restoration
possible
Minor error
Restoration
possible
Restoration
possible
Minor error
Restoration
possible
Minor error
Restoration
possible
Non-volatile mem ory data
error (error history)
Remote buffer memory
access error
Station number switch
changed error
Double input discrepancy
detection error
Input dark test errorDuring an input dark test, test
I/O data errorAn error was detected by the I/
Output read-back errorA discrepancy of an output
Output dark test errorDuring an output dark test, test
network parameters are
invalid
The error history data stored in
the non-volatile memory is
incorrect.
An area outside the range of
the remote buffer memory
areas has been accessed using
the REMFR/REMTO
instructions.
The station number setting
switches have been changed
with the module power-on.
A double input discrepancy was
detected in a pair of inputs (X0
and X1, X2 and X3, ...).
pulses were not detected.
O diagnostic.
read-back value and an output
value was detected.
pulses were not detected.
An access error has occurred
when network parameters are
invalid.
• The module will automatically recover immediately
after the error occurs. Note that the error history of
the errors that have occurred will be lost.
• If the same error occurs again, the module may be in
failure. Please consult your local Mitsubishi
representative.
• The module will automatically recover immediately
after the error occurs.
• Correct the setting data of the REMFR/REMTO
instruction to access the remote buffer memory.
The module will recover from this error by setting the
switches to the previous station number that was set
when the module power supply was powered on.
• Review the connected devices and wiring.
• When the connected devices and wiring have no
errors, there may be an influence from noise or a
hardware failure. Take measures to reduce noise.
• Power on the load power supply at the same timing of
power-on of the module power supply.
• If the same error occurs again even after the
measures have been taken, the module may be in
failure. Please consult your local Mitsubishi
representative.
• The module will recover from this error after the
double input discrepancy is eliminated.
• Review the connected devices and wiring.
• When the connected devices and wiring have no
errors, there may be an influence from noise or a
hardware failure. Take measures to reduce noise.
• Power on the load power supply at the same timing of
power-on of the module power supply.
• If the same error occurs again even after the
measures have been taken, the module may be in
failure. Please consult your local Mitsubishi
representative.
• If double outputs are in discrepancy state, eliminate
the error factor.
• Review the connected devices and wiring.
• When the connected devices and wiring have no
errors, there may be an influence from noise or a
hardware failure. Take measures to reduce noise.
• Power on the load power supply at the same timing of
power-on of the module power supply.
• If the same error occurs again even after the
measures have been taken, the module may be in
failure. Please consult your local Mitsubishi
representative.
• Review the connected devices and wiring.
• Check that 24V is supplied to the load power supply
using a tester.
• Check that the external connection is not overloaded.
• When the connected devices and wiring have no
errors, there may be an influence from noise or a
hardware failure. Take measures to reduce noise.
• Power on the load power supply at the same timing of
power-on of the module power supply.
• If the same error occurs again even after the
measures have been taken, the module may be in
failure. Please consult your local Mitsubishi
representative.
Correctly set module parameters of the master station.
96
10 TROUBLESHOOTING
10.7 Error Code List
Page 99
Error code
Classification Error nameDescription and causeAction
(hexadecimal)
020BHMinor errorSafety module validation
failure
0500HModerate error
Restoration
possible
Parameter data errorAn incorrect value or parameter
The safety module validation
failed.
data out of the range is set.
• The module will automatically recover immediately
after the error occurs.
• Check that no moderate error caused by the
parameter setting has occurred on the module using
the ERR. LED of the module and the error history. If
an error has occurred, eliminate the cause.
• If the same error occurs again even after "Safety
module validation" is executed in no error state, the
module may be in failure. Please consult your local
Mitsubishi representative.
• Review the connected devices, wiring, and voltage.
• Correct the module parameter settings and module
configuration.
• When the parameters are set again and the
parameter setting has succeeded, the module will
recover from this error.
*1 Detailed information of the error is stored in Error code details in Error history data. For Error code details, refer to the following.
Page 98 Error code details
*2 Restoration is possible only when the load power supply has a low-voltage error.
When multiple errors have occurred, only the latest error code is stored in Error code (RX10 to RX1F). The
errors that occurred before can be checked by executing "Error history read" from the "Network Configuration
Settings" in the engineering tool. For the error history, refer to the following.
Page 83 Checking with "Command Execution of Slave Station"
10
10 TROUBLESHOOTING
10.7 Error Code List
97
Page 100
Error code details
Error details of the following error codes are stored in Error code details in Error history data.
■Overload error (error code: 0102H)
A place where overcurrent was detected (in the module power supply or load power supply) is stored in Error code details 1.
b15b14b13b12b11b10b9b8b7b6b5b4b3b2b1b0
0 (fixed)(1)(2)
(1) 0: No error, 1: Overcurrent detected in the load power supply
(2) 0: No error, 1: Overcurrent detected in the module power supply
■Power supply voltage error (error code: 0103H)
Information on the voltage error (whether the error has occurred in the module power supply or load power supply, whether it
is an upper limit error or a lower limit error) is stored in Error code details 1.
b15b14b13b12b11b10b9b8b7b6b5b4b3b2b1b0
0 (fixed)(1)(2)(3)(4)
(1) 0: No error, 1: Load power supply voltage upper limit error
(2) 0: No error, 1: Load power supply voltage lower limit error
(3) 0: No error, 1: Module power supply voltage upper limit error
(4) 0: No error, 1: Module power supply voltage lower limit error
When a double input discrepancy has occurred, a number corresponding to a pair of double input terminals with discrepancy
is stored in Error code details 1.
• Error code details 1
b15b14b13b12b11b10b9b8b7b6b5b4b3b2b1b0
0 (fixed)(1)
(1) 000: Discrepancy of X0 and X1, 001: Discrepancy of X2 and X3, 010: Discrepancy of X4 and X5, 011: Discrepancy of X6 and X7, 100: Discrepancy of X8
and X9, 101: Discrepancy of XA and XB
■Input dark test error (error code: 0206H)
A number corresponding to an input terminal with the diagnostic error of input dark test is stored in Error code details 1.
• Error code details 1
b15b14b13b12b11b10b9b8b7b6b5b4b3b2b1b0
0 (fixed)(1)
(1) A number corresponding to an input terminal with the error is stored.
0000: X0
0001: X1
0010: X2
0011: X3
0100: X4
0101: X5
0110: X6
0111 : X7
1000: X8
1001: X9
1010: XA
1011: XB
98
10 TROUBLESHOOTING
10.7 Error Code List
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.