CC-Link IE Field Network Remote IO-Link Module
User's Manual
-NZ2GF2S-60IOLD8
-SW1DNN-IOLCDTM-BD
Page 2
Page 3
SAFETY PRECAUTIONS
WARNING
Indicates that incorrect handling may cause hazardous conditions, resulting in
death or severe injury.
CAUTION
Indicates that incorrect handling may cause hazardous conditions, resulting in
minor or moderate injury or property damage.
(Read these precautions before using this product.)
Before using this product, please read this manual and the relevant manuals carefully and pay full attention to safety to handle
the product correctly.
The precautions given in this manual are concerned with this product only. For the safety precautions of the programmable
controller system, refer to the user's manual for the CPU module used.
In this manual, the safety precautions are classified into two levels: "WARNING" and "CAUTION".
Under some circumstances, failure to observe the precautions given under "CAUTION" may lead to serious
consequences.
Observe the precautions of both levels because they are important for personal and system safety.
Make sure that the end users read this manual and then keep the manual in a safe place for future reference.
[Design Precautions]
WARNING
● In the case of a communication failure in the network, data in the master/local module are held. Check
Data link status (each station) (SW00B0 to SW00B7) and configure an interlock circuit in the program
to ensure that the entire system will operate safely.
● When the module is disconnected due to a communication failure in the network or the CPU module is
in the STOP status, all outputs are held or turned off according to the parameter setting.
Configure an interlock circuit in the program to ensure that the entire system will always operate
safely even in such a case. Failure to do so may result in an accident due to an incorrect output or
malfunction.
● Outputs may remain on or off due to a failure of the module. Configure an external circuit for
monitoring output signals that could cause a serious accident.
● Do not use any "use prohibited" signals as a remote input or output signal. These signals are reserved
for system use. Do not write any data to the "use prohibited" area in the remote register or the remote
buffer memory. If these operations are performed, correct operation of the module cannot be
guaranteed.
[Design Precautions]
CAUTION
● Do not install the control lines or communication cables together with the main circuit lines or power
cables. Keep a distance of 100mm or more between them. Failure to do so may result in malfunction
due to noise.
● During control of an inductive load such as a lamp, heater, or solenoid valve, a large current
(approximately ten times greater than normal) may flow when the output is turned from off to on.
Therefore, use a module that has a sufficient current rating.
1
Page 4
[Installation Precautions]
WARNING
● Shut off the external power supply (all phases) used in the system before mounting or removing the
module. Failure to do so may result in electric shock or cause the module to fail or malfunction.
[Installation Precautions]
CAUTION
● Use the module in an environment that meets the general specifications in this manual. Failure to do
so may result in electric shock, fire, malfunction, or damage to or deterioration of the product.
● Do not directly touch any conductive parts and electronic components of the module. Doing so can
cause malfunction or failure of the module.
● Securely connect the cable connectors. Poor contact may cause malfunction
● After the first use of the product, do not connect/disconnect the connector more than 50 times (IEC
61131-2/JIS B 3502 compliant). Exceeding the limit may cause malfunction.
[Wiring Precautions]
WARNING
● Shut off the external power supply (all phases) used in the system before wiring. Failure to do so may
result in electric shock or cause the module to fail or malfunction.
2
Page 5
[Wiring Precautions]
CAUTION
● Individually ground the FG terminal of the programmable controller with a ground resistance of 100
ohms or less. Failure to do so may result in electric shock or malfunction.
● Check the rated voltage and terminal layout before wiring to the module, and connect the cables
correctly. Connecting a power supply with a different voltage rating or incorrect wiring may cause a fire
or failure.
● Tighten the terminal block screws within the specified torque range. Undertightening can cause short
circuit, fire, or malfunction. Overtightening can damage the screw and/or module, resulting in drop,
short circuit, fire, or malfunction.
● Prevent foreign matter such as dust or wire chips from entering the module. Such foreign matter can
cause a fire, failure, or malfunction.
● Place the cables in a duct or clamp them. If not, dangling cable may swing or inadvertently be pulled,
resulting in damage to the module or cables or malfunction due to poor contact.
● Do not install the control lines or communication cables together with the main circuit lines or power
cables. Keep a distance of 100mm or more between them. Failure to do so may result in malfunction
due to noise.
● When disconnecting the cable from the module, do not pull the cable by the cable part. For the cable
with connector, hold the connector part of the cable. For the cable connected to the terminal block,
loosen the terminal screw. Pulling the cable connected to the module may result in malfunction or
damage to the module or cable.
● When an overcurrent caused by a failure of an external device or a programmable controller flows for
a long time, it may cause smoke and fire. To prevent this, configure external safety circuits, such as
fuses, for the module power supply and external power supply.
● Mitsubishi programmable controllers must be installed in control panels. Wiring and replacement of a
module must be performed by qualified maintenance personnel with knowledge of protection against
electric shock. For wiring methods, refer to "INSTALLATION AND WIRING" in this manual for the
module.
● Do not connect an output device of an SIO device to the channel set to IO-Link mode. Failure to do so
may cause malfunction.
[Startup and Maintenance Precautions]
WARNING
● Do not touch any terminal while power is on. Doing so will cause electric shock or malfunction.
● Shut off the external power supply (all phases) used in the system before cleaning the module or
retightening the terminal block screws and connector screws. Failure to do so may cause the module
to fail or malfunction.
3
Page 6
[Startup and Maintenance Precautions]
CAUTION
● Do not disassemble or modify the modules. Doing so may cause failure, malfunction, injury, or a fire.
● Do not drop or apply strong shock to the module. Doing so may damage the module.
● Shut off the external power supply (all phases) used in the system before mounting or removing the
module. Failure to do so may cause the module to fail or malfunction.
● After the first use of the product, do not mount/remove the module more than 50 times (IEC 61131-2/
JIS B 3502 compliant). Exceeding the limit may cause malfunction.
● After the first use of the product, do not connect/disconnect the connector more than 50 times (IEC
61131-2/JIS B 3502 compliant). Exceeding the limit may cause malfunction.
● Before handling the module or the cable to be connected to the module, touch a conducting object
such as a grounded metal to discharge the static electricity from the human body. Failure to do so may
cause the module to fail or malfunction.
● Startup and maintenance of a control panel must be performed by qualified maintenance personnel
with knowledge of protection against electric shock. Lock the control panel so that only qualified
maintenance personnel can operate it.
[Disposal Precautions]
CAUTION
● When disposing of this product, treat it as industrial waste.
4
Page 7
CONDITIONS OF USE FOR THE PRODUCT
(1) Mitsubishi programmable controller ("the PRODUCT") shall be used in conditions;
i) where any problem, fault or failure occurring in the PRODUCT, if any, shall not lead to any major or serious accident;
and
ii) where the backup and fail-safe function are systematically or automatically provided outside of the PRODUCT for the
case of any problem, fault or failure occurring in the PRODUCT.
(2) The PRODUCT has been designed and manufactured for the purpose of being used in general industries.
MITSUBISHI SHALL HAVE NO RESPONSIBILITY OR LIABILITY (INCLUDING, BUT NOT LIMITED TO ANY AND ALL
RESPONSIBILITY OR LIABILITY BASED ON CONTRACT, WARRANTY, TORT, PRODUCT LIABILITY) FOR ANY
INJURY OR DEATH TO PERSONS OR LOSS OR DAMAGE TO PROPERTY CAUSED BY the PRODUCT THAT ARE
OPERATED OR USED IN APPLICATION NOT INTENDED OR EXCLUDED BY INSTRUCTIONS, PRECAUTIONS, OR
WARNING CONTAINED IN MITSUBISHI'S USER, INSTRUCTION AND/OR SAFETY MANUALS, TECHNICAL
BULLETINS AND GUIDELINES FOR the PRODUCT.
("Prohibited Application")
Prohibited Applications include, but not limited to, the use of the PRODUCT in;
• Nuclear Power Plants and any other power plants operated by Power companies, and/or any other cases in which the
public could be affected if any problem or fault occurs in the PRODUCT.
• Railway companies or Public service purposes, and/or any other cases in which establishment of a special quality
assurance system is required by the Purchaser or End User.
• Aircraft or Aerospace, Medical applications, Train equipment, transport equipment such as Elevator and Escalator,
Incineration and Fuel devices, Vehicles, Manned transportation, Equipment for Recreation and Amusement, and
Safety devices, handling of Nuclear or Hazardous Materials or Chemicals, Mining and Drilling, and/or other
applications where there is a significant risk of injury to the public or property.
Notwithstanding the above restrictions, Mitsubishi may in its sole discretion, authorize use of the PRODUCT in one or
more of the Prohibited Applications, provided that the usage of the PRODUCT is limited only for the specific
applications agreed to by Mitsubishi and provided further that no special quality assurance or fail-safe, redundant or
other safety features which exceed the general specifications of the PRODUCTs are required. For details, please
contact the Mitsubishi representative in your region.
5
Page 8
INTRODUCTION
Thank you for purchasing the CC-Link IE Field Network remote IO-Link module (hereafter abbreviated as IO-Link module).
This manual describes the procedures, system configuration, parameter settings, functions, and troubleshooting of the IO-
Link module.
Before using this product, please read this manual and the relevant manuals carefully and develop familiarity with the
functions and performance of the IO-Link module to handle the product correctly.
When applying the program examples provided in this manual to an actual system, ensure the applicability and confirm that it
will not cause system control problems.
Please make sure that the end users read this manual.
Relevant product
NZ2GF2S-60IOLD8
Unless otherwise specified, this manual provides program examples in which the remote I/O signals and the
remote register of an IO-Link module are assigned as follows.
• Remote input signal: RX0 to RX2F
• Remote output signal: RY0 to RY2F
• Remote register: RWr0 to RWr83, RWw0 to RWw83
For the assignment of remote I/O signals and remote registers, refer to the following.
User's manual for the master/local module used
The RJ71GF11-T2 is used as the master/local module in this manual.
e-Manual refers to the Mitsubishi Electric FA electronic book manuals that can be browsed using a dedicated
tool.
e-Manual has the following features:
• Required information can be cross-searched in multiple manuals.
• Other manuals can be accessed from the links in the manual.
• The hardware specifications of each part can be found from the product figures.
• Pages that users often browse can be bookmarked.
• Sample programs can be copied to an engineering tool.
Part names, specifications, procedures before operation, system
configuration, installation, wiring, parameter settings, functions, programming,
and troubleshooting of the IO-Link module
Print book
e-Manual
PDF
10
Page 13
TERMS
Unless otherwise specified, this manual uses the following terms.
Ter mDescription
CC-Link IE Field NetworkA high-speed and large-capacity open field network that is based on Ethernet (1000BASE-T)
CommDTM(Communication DTM)A software module used to configure the communication setting required for communications between a personal
computer and field devices via the IO-Link master.
CPU moduleA generic term for the MELSEC iQ-R series CPU module, MELSEC-Q series CPU module, and MELSEC-L series CPU
module
CQ input signalAn external input signal input by the IO-Link master via the CQ line when the operation mode is the SIO (sink input)
CQ output signalAn external output signal output by the IO-Link master via the CQ line when the operation mode is the SIO (source
Cyclic transmissionA function by which data are periodically exchanged among master stations and other stations on the same system
Data linkA generic term for cyclic transmission and transient transmission
Dedicated instructionAn instruction for using the functions of a module
Device DTMA software module used to configure the parameter settings of field devices or monitor field devices.
DI signalAn external input signal input by the IO-Link master via the DI line when the operation mode is the IO-Link (sink input)
DisconnectionA process of stopping data link if a data link error occurs
DTM catalogBy registering the M_CommDTM-IOLink, the DTM catalog displays a list of available DTMs.
DTM(Device Type Manager)A software module used to configure the communication settings, set parameters of field devices, or monitor field
Engineering toolAnother term for the software package for the MELSEC programmable controllers
FDCAn abbreviation for the MELSOFT FieldDeviceConfigurator
FDT frame applicationA generic term for applications to use a DTM. An FDT frame application complies with the FDT/DTM open standard
FDT(Field Device Tool)Software standard specifications for management, maintenance, adjustment, and development of field devices
Global labelA label that is valid for all the program data when multiple program data are created in the project.
Intelligent device stationA station that exchanges I/O signals (bit data) and I/O data (word data) with another station by cyclic transmission. This
IO-Link deviceAn external device that supports IO-Link
IO-Link masterPerforms communications with the IO-Link sensor and actuator in the IO-Link module
IO-Link modeA generic term for the IO-Link (standard) mode and IO-Link (sink input) mode
IO-Link moduleAn abbreviation for the CC-Link IE Field Network remote IO-Link module
IODD DTM ConfiguratorA software program that operates the IODD file (device description file of IO-Link) as the Device DTM.
IODD(IO-Link Device Description)This description consists of the XML file containing the IO-Link device information and the image file in the png format.
ISDUData read from or written to parameters of IO-Link devices
LabelA label that represents a device in a given character string
Link deviceA device (RX, RY, RWr, or RWw) in a module on CC-Link IE Field Network
Link special register (SW)Information that indicates the operating status and data link status of a module on CC-Link IE Field Network in units of
Link special relay (SB)Bit data that indicates the operating status and data link status of a module on CC-Link IE Field Network
Local stationA station that performs cyclic transmission and transient transmission with the master station and other local stations.
M_CommDTM-IOLinkCommDTM that supports communications with the IO-Link device via the IO-Link module.
Master stationA station that controls the entire network. This station can perform cyclic transmission and transient transmission with all
Master/local moduleAn abbreviation for the CC-Link IE Field Network master/local module
MELSOFT FieldDeviceConfigurator Configuration Tool, which is developed by Mitsubishi Electric Corporation.
Module labelA label that represents one of memory areas (I/O signals and buffer memory areas) specific to each module in a given
mode
output) mode
using link devices
mode
devices when an FDT frame application is used.
There are two types of global label: a module specific label (module label), which is generated automatically by GX
Works3, and an optional label, which can be created for any specified device.
station can perform transient transmission as well. This station responds to a transient transmission request from
another station and also issues a transient transmission request to another station.
This description is supplied from a manufacturer of an IO-Link device.
16 bits (1 word)
stations. Only one master station can be used in a network.
MELSOFT FieldDeviceConfigurator complies with the FDT/DTM open standard and is used for parameter settings,
maintenance, and adjustment of field devices as an FDT frame application.
character string. For the module used, GX Works3 automatically generates this label, which can be used as a global
label.
11
Page 14
TermDescription
REMFRA generic term for JP.REMFR and ZP.REMFR
Remote input (RX)Bit data input from a slave station to the master station (For some areas in a local station, data are input in the opposite
direction.)
User's manual for the master/local module used
Remote output (RY)Bit data output from the master station to a slave station (For some areas in a local station, data are output in the
opposite direction.)
User's manual for the master/local module used
Remote register (RWr)Word data input from a slave station to the master station in units of 16 bits (1 word) (For some areas in a local station,
Remote register (RWw)Word data output from the master station to a slave station in units of 16 bits (1 word) (For some areas in a local station,
REMTOA generic term for JP.REMTO and ZP.REMTO
Reserved stationA station reserved for future use. This station is not actually connected, but counted as a connected station.
SIO deviceAn existing general-purpose I/O device that does not support IO-Link
SIO modeA generic term for the SIO (sink input) mode and SIO (source output) mode
Slave stationA generic term for a local station, remote I/O station, remote device station, and intelligent device station
Transient transmissionA function of communication with another station, which is used when requested by a dedicated instruction or an
data are input in the opposite direction.)
User's manual for the master/local module used
data are output in the opposite direction.)
User's manual for the master/local module used
engineering tool
12
Page 15
1PART NAMES
(1)(2) (6)(7)(3)
(8)(10)(9)(9)
(4)(5)
This section describes part names of the IO-Link module.
No.NameApplication
(1)P1PORT1 connector for CC-Link IE Field Network (RJ45 connector)
L ER LED• On: Module received abnormal data, or module performing loopback
LINK LEDIndicates the link status
P2PORT2 connector for CC-Link IE Field Network (RJ45 connector)
L ER LED(Same as the LEDs of P1 connector)
LINK LED
(2)PW LEDIndicates the power supply status of the IO-Link module.
RUN LEDIndicates the operating status of the IO-Link module.
MODE LEDIndicates the mode of the IO-Link module.
D LINK LEDIndicates the data link status of the IO-Link module.
ERR. LEDIndicates the error status of the IO-Link module.
(3)CH1 to CH8 LED (green)Indicates the operating status of each channel in IO-Link mode.
CH1 to CH8 LED (yellow)Indicates on/off of input or output for each channel in SIO mode
(4)CH1 to CH8 ERR. LEDIndicates the error status of each channel in IO-Link mode or SIO mode.
(5)I/O PW LEDIndicates the status of the power supply from the external power supply.
(6)Function setting switchA switch for the fast link-up function ( Page 30 Function setting switch setting)
An Ethernet cable is connected. ( Page 37 Wiring of Ethernet cable)
• Off: Module received normal data, or module not performing loopback
• On: Link-up in progress
• Off: Link-down in progress
An Ethernet cable is connected. ( Page 37 Wiring of Ethernet cable)
• On: Power supply ON
• Off: Power supply OFF
• On: Operating normally
• Off: A major error has occurred.
• On: Online mode
• Flashing: Unit test mode
• Off: In offline mode, or the unit test is completed.
• On: Data link in operation (cyclic transmission in progress)
• Flashing: Data link in operation (cyclic transmission stopped)
• Off: Data link not performed (disconnected or in unit test mode)
• On: A moderate or major error has occurred.
• Flashing: A minor error has occurred.
• Off: Operating normally
When a major error has been occurred, check RUN LED as well.
• On: Normal IO-Link communications
• Flashing: IO-Link communication error
• Off: Other than IO-Link mode
• On: I/O is on.
• Off: I/O is off.
• On: Channel error
• Off: Channels operating normally
• On: External power supply ON
• Off: External power supply OFF
*1
1
1 PART NAMES
13
Page 16
No.NameApplication
(7)Station number setting switchA rotary switch for setting station numbers and used for unit tests.
(8)Terminal block for module power
supply and FG
(9)DIN rail hookA hook to mount an IO-Link module on a DIN rail
(10)IO-Link terminal blockA terminal block to connect the external power supply and an external device
*1 IO-Link communication errors will occur if input process data and output process data are invalid. ( Page 156 Input process data,
Page 159 Output process data)
• Page 29 Setting station number setting switches
• Page 124 Unit Test
A terminal block to connect the module power supply (24VDC) and FG
14
1 PART NAMES
Page 17
2SPECIFICATIONS
This chapter describes the specifications of the IO-Link module.
2.1General Specifications
ItemSpecifications
Operating ambient
temperature
Storage ambient
temperature
Operating ambient
humidity
Storage ambient
humidity
Vibration resistance Compliant with JIS
Shock resistanceCompliant with JIS B 3502 and IEC 61131-2 (147m/, 3 times each in X, Y, and Z directions)
Operating
atmosphere
Operating altitude
Installation locationInside a control panel
Overvoltage
*3
category
Pollution degree
Equipment classClass
*1 Do not use or store the IO-Link module under pressure higher than the atmospheric pressure of altitude 0m. Doing so may cause
malfunction. When using the IO-Link module under pressure, please consult your local Mitsubishi representative.
*2 If the environment satisfies the operating ambient temperature, operating ambient humidity and other conditions, the module can be
used even outside the control panel.
*3 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power
distribution network and the machinery within premises.
Category applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand level for up to
the rated voltage of 300V is 2500V.
*4 This index indicates the degree to which conductive material is generated in terms of the environment in which the equipment is used.
Pollution degree 2 is when only non-conductive pollution occurs. A temporary conductivity caused by condensing must be expected
occasionally.
*5 Use the special coated products which comply with the IEC 60721-3-3 3C2 in the environment with the corrosive gases. For details on
the special coated products, please consult your local representative.
*6 When the programmable controller is used at altitude above 2000m, the withstand voltage performance and the upper limit of the
operating ambient temperature decrease. Please consult your local Mitsubishi representative.
0 to 55
-25 to 75
5 to 95%RH, non-condensing
B 3502 and IEC
61131-2
No corrosive gases
*1
*4
0 to 2000m
or less
2 or less
*6
FrequencyConstant
Under intermittent
vibration
Under continuous
vibration
*5
, flammable gases, less conductive dust
*2
5 to 8.4Hz3.5mm10 times each in X,
8.4 to 150Hz9.8m/
5 to 8.4Hz1.75mm
8.4 to 150Hz4.9m/
acceleration
Half amplitudeSweep count
Y, and Z directions
2
To use the IO-Link module complying with the EMC Directive, refer to "EMC and Low Voltage Directives" in
this manual. ( Page 193 EMC and Low Voltage Directives)
2 SPECIFICATIONS
2.1 General Specifications
15
Page 18
2.2Performance Specifications
NZ2GF2S-60IOLD8 IO-Link module
ItemNZ2GF2S-60IOLD8
Module typeCC-Link IE Field NetworkIntelligent device station
IO-LinkIO-Link master
Rated input voltage24VDC (ripple rate: 5% or less)
(allowable voltage range 20.4 to 28.8VDC (24VDC -15 to +20%))
Insulation methodBetween I/O and power supplyDigital isolator
Between channelsNone
Withstand voltage500VDC for 1 minute between all DC external terminals and the ground
Insulation resistance10M or higher between all DC external terminals and ground (500VDC
Noise immunityNoise voltage 500Vp-p, noise width 1s, noise frequency 25 to 60Hz (DC type
External interfaceCC-Link IE Field Network partRJ45 connector
Module power supply partTerminal block for module power supply and FG (spring clamp terminal block
IO-Link part40-point 2-piece spring clamp terminal block (push-in type)
Module operation start
*4
time
Applicable DIN railTH35-7.5Fe, TH35-7.5Al (compliant with IEC 60715)
Applicable wire sizeTerminal block for module power supply and FGCore: 0.5 to 2.0 (20 to 14 AWG), terminal slot size: 2.8mm 2.0mm
Applicable solderless
terminal
Operation modeThe following 6 modes are available.
IO-Link modeSupported protocolv1.1.2
Cyclic transmissionRX/RY points48 points
IO-Link mode
SIO mode• 1 channel: 0.2 seconds
IO-Link terminal block■For +24V/24G/FG
Terminal block for module power supply and FG
IO-Link terminal block
Number of channels8 channels max.
Rated load current (C/Q)200mA/channel, 4A/common
Rated load current (L+)1.6A/channel, 4A/common
Transmission speed• COM1: 4.8kbps
IO-Link modeCompliant with IO-Link standard
RWr/RWw points132 points
*5
*1*3
insulation resistance tester)
noise simulator condition)
(push-in type))
• 1 channel: 1.5 to 4 seconds
• 8 channels: 12 to 32 seconds
• 8 channels: 0.2 seconds
Core: 0.5 to 1.5 (20 to 16 AWG), terminal slot size: 2.4mm 1.5mm
■For CQ/L+/L-/DI
Core: 0.2 to 1.5 (24 to 16 AWG), terminal slot size: 2.4mm 1.5mm
*1
Page 35 Applicable solderless terminal
Page 39 Applicable solderless terminal
• Disabled mode
• IO-Link (standard) mode
• IO-Link (sink input) mode
• SIO (sink input) mode
• SIO (source output) mode
• Power supply mode
• COM2: 38.4kbps
• COM3: 230.4kbps
Determined by the IO-Link device connected. The transmission speed is
switched automatically.
16
2 SPECIFICATIONS
2.2 Performance Specifications
Page 19
ItemNZ2GF2S-60IOLD8
IO-Link (sink input)
mode
SIO (sink input) modeNumber of channels8 channels max.
SIO (source output)
mode
IO-Link cableCable typeUnshielded
Communication cableAn Ethernet cable that meets the 1000BASE-T standard:
Module power supplyVoltage24VDC (ripple rate: 5% or less)
External power supplyVoltage24VDC (ripple rate: 5% or less)
Weight0.24kg
Number of channels8 channels max.
Rated input current2.5mA TYP. (for 24VDC)
Input response time• 0ms
ON voltage/ON current12VDC or more/2mA or more
OFF voltage/OFF current6VDC or less/2mA or less
Rated input current2.4mA TYP. (for 24VDC)
Input response time
ON voltage/ON current11VDC or more/2mA or more
OFF voltage/OFF current6VDC or less/2mA or less
Number of channels8 channels max.
Rated load current200mA/point, 4A/common
Maximum inrush current650mA 100s or less
Leakage current at OFF0.1mA or less
Maximum voltage drop at ON0.88V or less, 0.2mA
Cable length20m maximum
Cable diameterCore 0.2 to 1.5
Current130mA (24VDC, all points ON)
Protection functionNone
FuseNone
Current95mA or less (24VDC, all points ON)
Protection functionNone
FuseNone
*2
•1ms
•1.5ms
•5ms
• 10ms (default value)
•20ms
•70ms
•0ms
•1ms
•1.5ms
•5ms
• 10ms (default value)
•20ms
•70ms
Category 5e or higher (double shielded, STP), straight cable
(allowable voltage range 20.4 to 28.8VDC (24VDC -15 to +20%))
(allowable voltage range 20.4 to 28.8VDC (24VDC -15 to +20%))
*1 Only one wire can be connected to a terminal. Multiple wires cannot be connected to a terminal. Connecting two or more wires may
cause a poor contact.
*2 For details on the input response time, refer to the following.
Page 192 Processing Time
*3 Use cables suitable for the current value used.
*4 The time taken for data link establishment with the master station at power-on is not included.
*5 The module operation start time written is a rough standard. The time depends on the response performance and data storage size of
the IO-Link device. In addition, because the start processing is performed for each channel, it takes longer time to start operation of the
module as the number of channels of which operation mode is set to IO-Link mode increases.
2
2 SPECIFICATIONS
2.2 Performance Specifications
17
Page 20
■External connection
FG
1
2
3
UNIT POWER
CABLE
1
2
3
+24V1
24G2
+24V3
24G4
NC5
FG6
7
NC8
L1+9
L1-10
CQ111
DI112
L2+13
L2-14
CQ215
DI216
L3+17
L3-18
CQ319
DI320
L4+21
L4-22
CQ423
DI424
L5+25
L5-26
CQ527
DI528
L6+29
L6-30
CQ631
DI632
L7+33
L7-34
CQ735
DI736
L8+37
L8-38
CQ839
DI840
+24V
*1
24G
NC
Signal
name
Pin
No.
Signal
name
Pin
No.
Non-insulated
IO-Link device
(IO-Link sensor)
SIO input
device (3-wire
sensor (PNP)
in SIO mode)
IO-Link device
(IO-Link sensor
(DI supported))
Module power
supply
IO-Link
terminal block
Terminal block for module
power supply and FG
Insulated
Digital
isolator
Internal
circuit
Load
External power supply
*1 Only one wire can be connected to a terminal of the terminal block for module power supply and FG. Multiple wires cannot be connected
18
to a terminal. Connecting two or more wires may cause a poor contact.
This section lists the functions of IO-Link modules.
IO-Link master functions
ItemDescriptionReference
IO-Link cyclic transmission functionCommunicates process data periodically with the IO-Link device
connected to each channel.
IO-Link transient communication functionReads/writes parameters at any timing from/to the IO-Link device
connected to each channel.
IO-Link device setting automatic upload/
download function
IO-Link device validation functionValidates compatibility and identity of the IO-Link device connected to
Disconnection detection functionDetects disconnection if communication with an IO-Link device is lost in
Input data masking functionCalculates ON/OFF values in IO-Link (standard) mode according to the
Swap functionSwaps the upper and lower bytes of data sent and received between
Bit segment functionSegments input process data using the bit count set for each channel.Page 78 Bit segment function
IO-Link communication retry count integration
function
Saves the parameters of the IO-Link device connected to each channel
in the IO-Link module, and as necessary, overwrites the parameters of
the IO-Link devices.
each channel.
IO-Link mode.
input process data.
the IO-Link module and the IO-Link device connected to each channel.
Counts the number of IO-Link communication retries for each channelPage 81 IO-Link communication
Page 64 IO-Link cyclic
transmission function
Page 66 IO-Link transient
communication function
Page 67 IO-Link device setting
automatic upload/download
function
Page 70 IO-Link device validation
function
Page 73 Disconnection detection
function
Page 74 Input data masking
function
Page 76 Swap function
retry count integration function
Input function
ItemDescriptionReference
Input OFF delay functionThis function turns off an X signal after a predetermined time passed
from when an actual input becomes off from on.
Input response time setting functionThis function prevents an incorrect input due to noise by setting the
response time until the module recognizes an actual input as the X
signal.
Page 83 Input OFF delay function
Page 85 Input response time
setting function
Output function
ItemDescriptionReference
Number of output ON times integration function The number of ON times of each output point is counted within the
range of 0 to 2147483647.
Output ON/OFF information hold functionThis function checks if the output has been turned once on or off.Page 88 Output ON/OFF
Page 87 Number of output ON
times integration function
information hold function
20
2 SPECIFICATIONS
2.2 Performance Specifications
Page 23
CC-Link IE Field Network communication function
ItemDescriptionReference
Cyclic transmissionPeriodically exchanges data among stations on the network using link
devices. An IO-Link module operates as an intelligent device station on
the CC-Link IE Field Network.
Transient transmissionReads or writes data on the IO-Link module in line with a dedicated
instruction from the master station.
The IO-Link module uses the REMFR instruction or REMTO instruction
to perform transient transmission.
Fast link-up functionShortens the time taken for data link establishment with the master
station at power-on.
Output HOLD/CLEAR setting functionWhether to hold or clear the last SIO output and output process data
can be set when the IO-Link module is disconnected from data link or
when the CPU module operating status is STOP.
Page 89 Cyclic transmission
Page 90 Transient transmission
Page 91 Fast link-up function
Page 94 Output HOLD/CLEAR
setting function
Others
ItemDescriptionReference
Event acquisition functionNotifies of IO-Link device events upon sending of event data from the
IO-Link device to the IO-Link module.
Protection functionProtects internal circuits from overcurrent and its heat using an
overload protection function and overheat protection function.
External power supply monitoring functionMonitors the ON/OFF status of the external power supplies of IO-Link
modules.
Device replacement functionEnables device replacement when the IO-Link module power supply is
on.
Page 96 Event Acquisition
Function
Page 97 Protection Function
Page 98 External Power Supply
Monitoring Function
Page 99 Device Replacement
Function
2
2 SPECIFICATIONS
2.2 Performance Specifications
21
Page 24
3PROCEDURES BEFORE OPERATION
This chapter describes the procedures before operation.
1. Station number setting
Set the IO-Link module station number.
Page 29 Setting station number setting switches
2. Function setting switch setting
Set the function setting switch.
Page 30 Function setting switch setting
3. Connection
Mount the IO-Link module on the DIN rail.
Page 33 Mounting the modules on a DIN rail
4. Wiring
Wire a power supply, an Ethernet cable, and an external device to the IO-Link module.
Page 35 Wiring with terminal block for module power supply and FG
Page 37 Wiring of Ethernet cable
Page 39 Wiring of IO-Link terminal block and external devices
5. Power-on
Power on the IO-Link module.
6. Parameter setting and programming
Set parameters and create a program.
Page 43 PARAMETER SETTING
Page 105 PROGRAMMING
To replace the IO-Link module, follow the procedure described below.
• Power off the IO-Link module and remove it.
• Prepare a new IO-Link module and perform the above procedure. (The network parameters of the CC-Link
IE Field Network master station do not need to be set again.)
• After checking the operation, restart the control.
22
3 PROCEDURES BEFORE OPERATION
Page 25
MEMO
3
3 PROCEDURES BEFORE OPERATION
23
Page 26
4SYSTEM CONFIGURATION
NZ2GF2S-60IOLD8
(1)
DeviceDTM
M_CommDTM-IOLink
IODD DTM Configurator
IODD
This chapter describes system configuration using an IO-Link module.
For CC-Link IE Field Network configuration, refer to the following.
User's manual for the master/local module used
4.1Applicable Systems
(1) Personal computer (engineering tool/FDC)
Applicable master station
When using an IO-Link module, use the following products as a master station.
Model
RJ71GF11-T2No restriction
RJ71EN71
R04ENCPU, R08ENCPU, R16ENCPU, R32ENCPU, R120ENCPU
QJ71GF11-T2
LJ71GF11-T2
*1 Simple motion modules and interface boards compatible with the CC-Link IE Field Network cannot be used.
Information on "Applicable master station" described above is the ones at the point when this manual was issued.
For latest information, please visit the website of CC-Link Partner Association.
www.cc-link.org
24
*1
4 SYSTEM CONFIGURATION
4.1 Applicable Systems
First five digits of serial number
Page 27
Ethernet cable
For the specifications of the Ethernet cable, refer to the following.
User's manual for the master/local module used
IO-Link cable
For details on IO-Link cables, refer to the following.
Page 35 Wiring with terminal block for module power supply and FG
Available software
The following software is available for settings and diagnostics of the IO-Link module. ( Manuals of each software)
Product nameFunctions/applications
GX Works2Software for system design, programming, debugging, and maintenance of the programmable controller.
GX Works3
MELSOFT NavigatorIntegrated application of GX Works2 and GX Works3.
FDCApplication for DTM.
M_CommDTM-IOLink
IODD DTM Configurator
When the latest software is required, please consult your local Mitsubishi representative.
Applicable profile
To use the parameter setting function of an IO-Link module, the profile is required.
The profile is a setting file that stores information required for the start-up, operation, and maintenance of devices supporting
the CC-Link family.
A module is added to "Module List" of the "CC IE Field Configuration" window by profile registration to an engineering tool. For
the profile registration, refer to the operating manual for the engineering tool used.
4
Applicable devices
Up to eight IO-Link devices and SIO devices can be connected in combination to the IO-Link module.
The IO-Link mode and SIO mode can be set separately on the channels of the IO-Link module.
Refer to the following for operation modes supported by connected external devices.
Operation modeDescription
Disabled modeSelect this mode when no devices are connected.
An error is not detected when a channel in disabled mode is operating.
IO-Link (standard) modeSelect this mode to communicate with IO-Link devices. Process data is sent
and received at the following communication speeds.
• COM1: 4.8kbps
• COM2: 38.4kbps
• COM3: 230.4kbps
IO-Link (sink input) modeSelect this mode to connect a source-type IO-Link device. In addition to IO-
SIO (sink input) modeSelect this mode to connect a source-type SIO (input) device. This mode
SIO (source output) modeSelect this mode to connect a sink-type SIO (output) device. This mode
Power supply modeSelect this mode to supply power to the device of another channel.
Link (standard) mode, digital input is also supported.
communicates with general devices and supports digital input.
communicates with general devices and supports digital input.
An error in the power line is only detected when a channel in power supply
mode is operating.
For setting examples and wiring methods, refer to the following.
Page 42 Using IO-Link devices that require power supplies for their
multiple terminals
For error codes and warning codes detectable in each operation mode, refer to the following.
Page 134 List of error codes and the warning codes
4 SYSTEM CONFIGURATION
4.1 Applicable Systems
25
Page 28
5INSTALLATION AND WIRING
24G
CQ
+24V
Sink input
IO-Link module
Inductive
load
Resistor Load
IO-Link
module
Load
IO-Link
module
Inductor
This section describes the installation and wiring of the IO-Link module.
5.1Before Using the I/O Link Module
Precautions when using SIO (sink input) mode
■Measures against back EMF
When connecting an inductive load, connect a diode in parallel with the load. Use the diode that satisfies the following
conditions:
• A reverse breakdown voltage is ten times as high as the circuit voltage or more.
• A forward current is twice as high as the load current or more.
SIO (sink input)
Precautions when using SIO (source output) mode
■Maximum switching frequency when L load is driven
The maximum switching frequency imposes a limit on the use; an ON state or an OFF state must not be changed without an
interval of at least one second.
■Load to be connected
When connecting a counter or timer utilizing a DC/DC converter as a load of the IO-Link module, select an IO-Link module
whose maximum load current is higher than the inrush current of a load to be connected. If the selection is based on the
average current of a load to be connected, an inrush current flows cyclically from the load while the IO-Link module is in an
ON state or in operation, which can cause failure of the module. If it is necessary to select a module on the basis of the
average current of a load to be connected, to alleviate the effect of the inrush current, take any of the following corrective
actions:
• Connecting a resistor in series with the load
• Connecting an inductor in series with the load
26
5 INSTALLATION AND WIRING
5.1 Before Using the I/O Link Module
Page 29
■Measures against reverse current
24G
+24V
CQ1
CQ2
24G
+24V
CQ1
CQ2
Load
IO-Link module
IO-Link module
Load
+24V
CQ
24G
IO-Link module
Additional circuit
In the following connections, a reverse current flows to the output element, which can cause failure.
When wiring, set up diodes as the following figures show:
• When connecting IO-Link modules in parallel
Source type
5
• When providing another circuit in parallel with an IO-Link module
Source type
5 INSTALLATION AND WIRING
5.1 Before Using the I/O Link Module
27
Page 30
■Measures against back EMF
+24V
CQ
24G
IO-Link module
Inductive
load
When connecting an inductive load, connect a diode in parallel with the load.
Use the diode that satisfies the following conditions:
• A reverse breakdown voltage is ten times as high as the circuit voltage or more.
• A forward current is twice as high as the load current or more.
Source type
■About element protection of the IO-Link module
If excessive noise affects the terminals of the IO-Link module, the output may be turned on to help the protection of the output
element. Adjust the voltage between terminals of the IO-Link module to fall within the operating load voltage range by taking
measures such as the following:
• To use an inductive load such as a relay, a surge suppressor is required on the load side as well. Take appropriate
measures, referring to the measures against back EMF as a guide.
• To prevent excessive noise, avoid installing power cables together with I/O cables.
28
5 INSTALLATION AND WIRING
5.1 Before Using the I/O Link Module
Page 31
5.2Setting Switch
Ex.
Setting station number setting switches
Setting procedure
Set the station number using the rotary switches on the front of the IO-Link module. The set value of the station number
becomes valid when the module is powered on. Thus, set the station number while the module power is off.
• The hundreds and tens places of the station number are set with 10.
• The ones place of the station number is set with 1.
To set the station number setting switches, use a flathead screwdriver with a tip width of 3.5mm or less.
To set the station number to 115, set the switches as shown below.
5
Setting range
Set the station number from 1 to 120. Setting the value other than 1 to 120 causes a communication error and the D LINK
LED flashes.
Do not set a station number duplicated with other station numbers. If the station number is duplicated, a
communication error occurs and the D LINK LED does not turn on.
5 INSTALLATION AND WIRING
5.2 Setting Switch
29
Page 32
Function setting switch setting
Enable or disable the fast link-up function using the function setting switches on the front of the IO-Link module. The setting
made by the function setting switches becomes valid when the module is powered on. Thus, set these switches while the
module power is off.
For details on the fast link-up function, refer to the following.
Page 91 Fast link-up function
No.Switch nameFunction nameSetting details
1Function setting switch 1
(F LINK P1)
2Function setting switch 2
(F LINK P2)
3Use prohibitedAlways set to Off.
4
PORT1 fast link-up functionEnables or disables the fast link-up function of PORT1.
• On: Enable
• Off: Disable
PORT2 fast link-up functionEnables or disables the fast link-up function of PORT2.
• On: Enable
• Off: Disable
• To set the function setting switches, use a flathead screwdriver with a tip width of 0.9mm or less.
• Do not change the function setting switch while the module is powered on. Changing the function setting
switch while the module is powered on causes a minor error and flashes the ERR. LED. Returning the
function setting switch to the previous setting eliminates the error and turns off the ERR. LED.
30
5 INSTALLATION AND WIRING
5.2 Setting Switch
Page 33
5.3Installation Environment and Installation Position
(1)(1)(1)
(1)(1)
(1)(1)
Installation environment
Installation location
Do not install the IO-Link module to the place under the following condition.
• Ambient temperature is outside the range from 0 to 55;
• Ambient humidity is outside the range from 5 to 95%RH;
• Condensation occurs due to rapid temperature change;
• Corrosive gas or combustible gas is present;
• Conductive powder such as dust and iron powder, oil mist, salinity, or organic solvent is filled;
• The I/O module is exposed to direct sunlight;
• A strong electric field or strong magnetic field is generated; and
• The I/O module is subject to vibration and shock.
Installation surface
Install the IO-Link module on the flat surface. When the installation surface is uneven, excessive force is applied to the
printed-circuit board and may cause a defect.
Installation position
5
When installing the IO-Link module in a control panel, provide clearance of at least 60mm (1) between the IO-Link module and
the sides of the control panel or neighboring modules to ensure good ventilation and easy IO-Link module replacement.
5 INSTALLATION AND WIRING
5.3 Installation Environment and Installation Position
The IO-Link module can be installed in six directions.
Use a DIN rail to install the IO-Link module.
32
5 INSTALLATION AND WIRING
5.3 Installation Environment and Installation Position
Page 35
5.4Installation
Mounting the modules on a DIN rail
An example of the use of the DIN rail stopper is described in the following procedure. Fix the module
according to the manual of the DIN rail stopper used.
Mounting procedure
1. Pull down all DIN rail hooks on the back of the modules.
The levers should be pulled down until they click.
2. Hang the upper tabs of the modules on a DIN rail, and
5
push the modules in position.
3. Lock the DIN rail hooks to the DIN rail to secure the
modules in position.
Push each hook up until it clicks. If the hooks are beyond the
reach, use a tool such as a driver.
4. Loosen the screw on DIN rail stopper.
5. Hitch the bottom hook of the DIN rail stopper to the
bottom of the DIN rail.
Hitch the hook according to the orientation of the arrow on
the front of the stopper.
6. Hitch the upper hook of the DIN rail stopper to the top of
the DIN rail.
5 INSTALLATION AND WIRING
5.4 Installation
33
Page 36
7. Slide the DIN rail stopper up to the left side of the
modules.
8. Hold the DIN rail stopper in the direction opposite to the
arrow on the stopper and tighten the screw with a driver.
9. Install the DIN rail stopper on the right side of the
module in the same procedure.
Install the stopper upside down for the right side.
Do not slide modules from the edge of the DIN rail when mounting them. The modules may be damaged.
Removal procedure
Remove the modules from the DIN rail by reversing the above procedure.
Applicable DIN rail models (compliant with JIS C 2812/IEC 60715)
• TH35-7.5Fe
• TH35-7.5Al
Interval between DIN rail mounting screws
Tighten the screws at intervals of 200mm or less.
DIN rail stopper
Use a stopper that is attachable to the DIN rail.
34
5 INSTALLATION AND WIRING
5.4 Installation
Page 37
5.5Wiring
Wiring with terminal block for module power supply and FG
Tightening torque
Tighten the terminal block mounting screws within the following specified torque range.
Tightening the screw too much may damage the IO-Link module case.
Screw typeTightening torque range
Terminal block mounting screw (M2.5 screw)0.2 to 0.3Nm
Wire to be used
The following describes the wire to be connected to the terminal block for module power supply and FG.
DiameterTypeMaterialTemperature rating
20 to 14 AWGCoreCopper wire75 or more
Applicable solderless terminal
The following table lists the applicable solderless terminal.
Product nameModelApplicable wire size Bar solderless terminal
tool
Bar solderless terminalAI 0.5-8WH, AI 0.5-10WH0.5CRIMPFOX6PHOENIX CONTACT GmbH & Co. KG
AI 0.75-8GY, AI 0.75-10GY0.75
AI 1-8RD, AI 1-10RD1.0
AI 1.5-8BK, AI 1.5-10BK1.5
Al 2.5-10BU2.0
Contact
5
Installing and removing the terminal block
To remove the terminal block, loosen the terminal block mounting screw with a flathead screwdriver.
To install the terminal block, tighten the terminal block mounting screw with a flathead screwdriver.
Failure to secure the terminal block may cause drop, short circuit, or malfunction.
5 INSTALLATION AND WIRING
5.5 Wiring
35
Page 38
Connecting and disconnecting the cable
(1)
2.0mm
2.8mm
Insertion slot
To connect the cable, fully insert a wire having a bar solderless terminal into a wire insertion opening.
After inserting the wire, pull it lightly to check that it is securely clamped.
A continuity check can be conducted using a test terminal (1).
To disconnect the cable, push in the open/close button with a flathead screwdriver.
With the button pushed in, pull out the wire having a bar solderless terminal.
Precautions
• Use a bar solderless terminal for the wiring to the push-in type spring clamp terminal block. If a stripped wire is inserted into
a wire insertion opening, the wire cannot be securely clamped.
• For how long the wire should be stripped, follow the specifications of the bar solderless terminal used. To attach a bar
solderless terminal to a wire, use a crimping tool.
• Before inserting a bar solderless terminal into a wire insertion opening (1), check the shape of the opening and the shape of
the terminal. Insert the terminal paying attention to the orientation. If a bar solderless terminal larger than the wire insertion
opening (1) is inserted, the terminal block may be damaged.
• To comply with the EMC Directive, use a separate power supply for each of the module power supply and the external
power supply.
36
5 INSTALLATION AND WIRING
5.5 Wiring
Page 39
Wiring of Ethernet cable
Either one can be used.
Wiring method
■Installation method
1. Turn off the power supplies of the IO-Link module and the external device.
2. Push the Ethernet cable connector into the IO-Link module until it clicks. Pay attention to the direction of the connector.
3. Power on the IO-Link module.
4. Power on the external device.
5. Check if the LINK LED on the port into which the Ethernet cable is connected is on.
*1 The time taken for the LINK LED to turn on after connection of the cable may vary. The LINK LED normally turns on in a few seconds.
However, if link-up processing is repeated due to a condition of a device on the line, the longer time may be required. If the LINK LED
does not turn on, refer to the following and take a corrective action.
Page 123 When the LINK LED is off
• When the fast link-up function is not used, PORT1 and PORT2 connectors do not need to be distinguished.
When only one connector is used in star topology, either PORT1 or PORT2 can be connected. For how to
connect Ethernet cables for using the fast link-up function, refer to the following.
Page 91 Fast link-up function
* 1
5
• When two connectors are used in line topology or ring topology, an Ethernet cable can be connected to the
connectors in any combination. For example, the cable can be connected between PORT1s and between
PORT1 and PORT2.
Connection between
PORT1s or PORT2s
Connection between
PORT1 and PORT2
■How to disconnect
1. Turn off the power supply of the IO-Link module.
2. Press the latch down and unplug the Ethernet cable.
5 INSTALLATION AND WIRING
5.5 Wiring
37
Page 40
Precautions
■Laying Ethernet cables
• Place the Ethernet cable in a duct or clamp them. If not, dangling cable may swing or inadvertently be pulled, resulting in
damage to the module or cables or malfunction due to poor contact.
• Do not touch the core of the connector of the cable or the module, and protect it from dirt and dust. If any oil from your hand,
or any dirt or dust sticks to the core, it can increase transmission loss, causing data link to fail.
• Regarding the Ethernet cable to be used, check that the Ethernet cable has no disconnections or short circuits, or problems
in the connection of the connector.
■Broken cable latch
Do not use Ethernet cables with broken latches. Doing so may cause the cable to unplug or malfunction.
■Connecting and disconnecting the Ethernet cable
Hold the connector part when connecting and disconnecting the Ethernet cable. Pulling the cable connected to the module
may result in damage to the module or cable or malfunction due to poor contact.
■Connectors without Ethernet cable
To prevent dust from entering the module, attach the provided connector cover.
This chapter describes the procedure for setting parameters of the IO-Link module.
6.1CC-Link IE Field Network Parameter Setting
Set the parameter of the IO-Link module with the network parameter written to the CPU module of the CC-Link IE Field
Network master station. For details on setting the CC-Link IE Field Network master station, refer to the following.
User's manual for the master/local module used
This function communicates process data periodically with the IO-Link device connected to each channel.
With this function, information on the IO-Link device can be acquired and the IO-Link device can be controlled.
The communication cycle (cycle time) is automatically set to the minimum cycle time of the connected IO-Link device.
A maximum of 32 bytes process data can be communicated. The data size and structure vary depending on the connected
IO-Link module.
To validate output process data, turn on CH Output data valid flag (RY8 to RYF).
When the minimum cycle time of the connected IO-Link device is less than 1.0ms, the cycle time is set to 1.0ms.
Operation mode
This function is enabled only in the following operation modes.
• IO-Link (standard) mode
• IO-Link (sink input) mode
Process data
Process data contains the following data.
■IO-Link (standard) mode
• Data masking results
• Input process data
• Output process data
■IO-Link (sink input) mode
• DI signal
• Input process data
• Output process data
• When CH Input data invalid flag (RX8 to RXF) is on, input process data is an undefined value and cannot be used with
programs.
• When CH Output data valid flag (RY8 to RYF) is off, the IO-Link module notifies the IO-Link device that the output
process data is invalid. When output process data is invalid, IO-Link device operates in accordance with the specifications
of the IO-Link device being used.
64
7 FUNCTIONS
7.1 IO-Link Master Functions
Page 67
Function combinations
Operating procedure
Window
The following shows a list of operations of the function combinations that deal with input process data.
Parameter settingSwap operationBit segment operationInput data masking operation
When "Number of Slicings" is 0Input process data that has been
When "Number of Slicings" is 1 or
more
For details on the functions, refer to the following.
Page 74 Input data masking function
Page 76 Swap function
Page 78 Bit segment function
swapped or not yet swapped is
stored in the remote register in
accordance with "Byte Position
Swap".
No operation.Input process data segmented is
No operation.Masking results for the process data
stored in the remote register in
accordance with "Bit Slicing Setting".
configuration defined in the IO-Link
device manual are stored in the
remote input in accordance with
"Input Data Mask". Data to be
masked is not affected by the swap or
bit segment operations.
IO-Link device setting automatic upload/download function
Precautions
This function saves the parameters of IO-Link device connected to each channel in the IO-Link module.
When the IO-Link devices are replaced, this function allows new IO-Link devices to inherit the IO Link device parameters that
have been stored in the old IO-Link devices.
The IO-Link device parameters can be uploaded manually. ( Page 69 Manual uploading)
• This function can be used only when the connected IO-Link device supports the data storage function.
• Since IO-Link device parameters vary depending on the IO-Link device, all IO-Link device parameters may not be saved.
Refer to the manual of the IO-Link device used.
• IO-Link device parameters are not uploaded or downloaded automatically when "Device Validation Setting" is not "0: Do not
validate" and the device validation result is unacceptable. For details on device validation, refer to IO-Link device validation
function. ( Page 70 IO-Link device validation function)
Operation mode
This function is enabled only in the following operation modes.
• IO-Link (standard) mode
• IO-Link (sink input) mode
When the operation mode is not the IO-Link mode, IO-Link device parameters stored on the non-volatile
memory of the IO-Link module are cleared.
Automatic uploading
IO-Link device parameters are automatically uploaded from IO-Link devices to the non-volatile memory of the IO-Link module.
Automatic downloading
IO-Link device parameters are automatically downloaded from the non-volatile memory of the IO-Link module to IO-Link
devices.
7
7 FUNCTIONS
7.1 IO-Link Master Functions
67
Page 70
Execution conditions
The following shows the conditions for automatic uploading and downloading of IO-Link device parameters.
*1 Even if the device validation result is match, the parameters may not be automatically downloaded properly if the structure of IO-Link
device parameters has been changed. When the firmware version of the IO-Link device is defined, the firmware version is checked
during automatic downloading, and a notification is issued as an event if the firmware version is different. (Parameters are automatically
downloaded even if the firmware versions are different.)
*2 If IO-Link device parameters are the same, they are not downloaded automatically and no processing is performed.
■When IO-Link device parameters on non-volatile memory do not exist
In the following cases, IO-Link device parameters do not exist on the non-volatile memory.
• When no IO-Link device parameters have been uploaded so far since the shipment from the factory
• When no IO-Link device parameters have been uploaded so far since when the operation mode was set to other than IO-
Link mode and the IO-Link device parameters on the non-volatile memory were cleared
■During processing of IO-Link device connections
This means the timing at which connections established with IO-Link devices operating in IO-Link mode are detected by the
IO-Link module.
Device validation
setting
validation/Identity validation
Compatibility validation/
Identity validation
Device validation result During processing of
IO-Link device
connections
Automatic uploading
MatchAutomatic downloading
MismatchNo processing
*1*2
During processing of
IO-Link device
parameter changes
■During processing of IO-Link device parameter changes
This means the case where IO-Link device parameters are changed by a device mounted on the IO-Link device.
68
7 FUNCTIONS
7.1 IO-Link Master Functions
Page 71
Manual uploading
Operating procedure
Parameters can be uploaded manually using "Manual upload" of "Command Execution of Slave Station" of the engineering
2. Open the "Command Execution of Slave Station" window.
From the list of stations, select an IO-Link module [CC IE Field Configuration] [Online] [Command Execution of
Slave Station].
3. Set "Method selection" to "Read Device Validation Data" and click the [Execute] button.
72
7 FUNCTIONS
7.1 IO-Link Master Functions
Connection of a non-compatible IO-Link device causes a device validation error to occur, preventing some
data of the currently connected IO-Link device from being acquired. 0 is displayed.
Page 75
Disconnection detection function
This function detects disconnection if communication with an IO-Link device is lost in IO-Link mode.
• Disconnections are detected even if an IO-Link device is not connected to a channel operating in IO-Link
mode.
• To disable disconnection detection when replacing an IO-Link device with another IO-Link or an SIO device
while the IO-Link module power is on, select the target channel in "Start Device Changeout" of "Command
Execution of Slave Station" of the engineering tool. ( Page 99 Device Replacement Function)
Operation mode
This function is enabled only in the following operation modes.
• IO-Link (standard) mode
• IO-Link (sink input) mode
Disconnection notification
The following occurs when a disconnection from the IO-Link device is detected.
• The ERR. LED flashes.
•CH ERR. LED of the target channel turns on.
•CH LED of the target channel flashes in green.
•CH Input data invalid flag (RX8 to RXF) for the target channel turns on.
•CH IO-Link device connection status flag (RX20 to RX27) for the target channel turns off.
• Warning status flag (RWr0.b12) turns on.
• A disconnection error (error code: 1806H) is stored in Warning code (RWr2).
• Occurrence of minor error (RX19) turns on.
7
Recovery from a disconnection
The following occurs in five seconds after recovery from a disconnection.
• The ERR. LED turns off.
•CH ERR. LED of the target channel turns off.
•CH LED of the target channel turns on in green.
•CH Input data invalid flag (RX8 to RXF) for the target channel turns off.
•CH IO-Link device connection status flag (RX20 to RX27) for the target channel turns on.
• Warning status flag (RWr0.b12) turns off.
• Warning code (RWr2) is cleared.
Occurrence of minor error (RX19) remains on. Occurrence of minor error (RX19) can be turned off by turning
on Occurrence of minor error clear request flag (RY19).
7 FUNCTIONS
7.1 IO-Link Master Functions
73
Page 76
Input data masking function
Ex.
000100010000000000100011
0001100000000000
0
Alarm
MSBLSB
ParameterMeasured value
Measured value
byte0
b7 b6 b5 b4 b3 b2 b1 b0
byte1
b7 b6 b5 b4 b3 b2 b1 b0
byte2
b7 b6 b5 b4 b3 b2 b1 b0
...
b15b0
(1)
(2)
(3)
(4)
This function calculates ON/OFF values in IO-Link (standard) mode according to the input process data.
With this function, changes in a specified bit of input process data can be detected easily.
Operation mode
This function is enabled only in IO-Link (standard) mode.
Description
Any bit from the first two bytes of input process data will be masked.
Set "Input Data Mask" depending on the process data structure of the IO-Link device used.
For information on IO-Link device process data structures, refer to the manual of the IO-Link device used.
If all input process data for the bits set to 1 in "Input Data Mask" is 1, CH Data masking results (RX0 to RX7) turn on.
If any of them is 0, CH Data masking results (RX0 to RX7) turn off.
• Input data masking results can be used with the input OFF delay function.
• When the bit segment function is enabled, input process data will be masked before bit segmentation. For
details on the bit segment function, refer to Bit segment function. ( Page 78 Bit segment function)
When the input data masking result is 1
byte0
b7 b6 b5 b4 b3 b2 b1 b0
ParameterMeasured value
byte1
b7
b6 b5 b4 b3 b2 b1 b0
MSBLSB
byte2
b7 b6 b5 b4 b3 b2 b1 b0
Measured value
(1)
(1) IO-Link device process data structure
(2) IO-Link device input process data value
(3) "Input Data Mask": 1000H
(4) Masking result
000100010000000000100011
b15b0
0001000000000000
When the input data masking result is 0
Alarm
...
(3)
1
(4)
(2)
(1) IO-Link device process data structure
(2) IO-Link device input process data value
(3) "Input Data Mask": 1800H
(4) Masking result
The number of ON times of each output point is counted within the range of 0 to 2147483647. The integration value remains
even though the IO-Link module is powered off.
Operation modes and data
This function is enabled only in the following operation modes and with the following data.
• SIO (source output) mode: CQ output signals
Checking and clearing the number of output ON times
The number of output ON times can be checked and cleared using a program.
ItemDescriptionReference
CH Number of output ON times integration value
(address: 299EH to 29ADH)
Number of output ON times integration value clear
command (address: 2E80H)
Number of output ON times integration value clear
completed (address: 2E81H)
Stores the integration value of the number of
output ON times integration function.
When the corresponding bit of output is turned on,
the integration value for the output with the number
of output ON times integration function is cleared.
After the integration value is cleared using Number
of output ON times integration value clear
command (address: 2E80H), the bit of the output
that has been cleared turns on.
Page 177 Number of output ON times integration
value
Page 184 Number of output ON times integration
value clear command
Page 185 Number of output ON times integration
value clear completed
7
• When the ON time and the OFF time of the target output signal are less than 10ms, the IO-Link module
cannot recognize the output change and the number of output ON times may not be counted.
• When the number of output ON times integration value exceeds 2147483647, the count stops. To integrate
the number of output ON times continuously, clear the integration value by using Number of output ON
times integration value clear command (address: 2E80H).
7 FUNCTIONS
7.3 Output Function
87
Page 90
Output ON/OFF information hold function
This function checks if the output has been turned once on or off.
Operation mode
This function is enabled only in the following operation modes and with the following data.
• SIO (source output) mode
Output ON information
Output ON information is stored in CH Output ON information (RWr4.b0, RWr14.b0, RWr24.b0, RWr34.b0, RWr44.b0,
RWr54.b0, RWr64.b0, RWr74.b0).
Whether the output has been turned on or not can be checked with CH Output ON information (RWr4.b0, RWr14.b0,
7.4 CC-Link IE Field Network Communication Function
95
Page 98
7.5Event Acquisition Function
Operating procedure
Window
Displayed items
This function notifies of IO-Link device events upon sending of event data from the IO-Link device to the IO-Link module.
As with the IO-Link module event history, the event history can be checked using "Command Execution of Slave Station".
( Page 132 Method for Checking the Event History)
The event acquisition function handles the following two items.
• Notification
• Warning
All types of abnormalities are acquired as errors.
Notification
Set the IO-Link device events set as notification as follows for each channel.
• Not acquire
• Acquire as event
Warning
Set the IO-Link device events set as warning as follows for each channel.