Mitsubishi Electric MUZ-HJ25VA - E1, MUZ-HJ35VA - E1, MUZ-HJ50VA - E1, MUZ-HJ25VA, MUZ-HJ35VA Service Manual

...
SERVICE MANUAL
CONTENTS
1. TECHNICAL CHANGES ···································3
2. PART NAMES AND FUNCTIONS ····················· 3
3. SPECIFICATION ················································ 4
4. NOISE CRITERIA CURVES ······························ 7
5. OUTLINES AND DIMENSIONS ························ 8
7. REFRIGERANT SYSTEM DIAGRAM ··············11
8. PERFORMANCE CURVES ····························· 13
9. ACTUA TOR CONTROL ··································· 24
10. SERVICE FUNCTIONS ···································· 25
11. TROUBLESHOOTING ····································· 25
12. DISASSEMBLY INSTRUCTIONS ···················· 42
Models
SPLIT-TYPE AIR CONDITIONERS
MUZ-HJ25VA
-
E1
MUZ-HJ35VA
-
E1
MUZ-HJ50VA
-
E1
HFC
utilized
R410A
No. OBH648
REVISED EDITION-A
OUTDOOR UNIT
Indoor unit service manual MSZ-HJ•VA Series (OBH647)
NOTE:
RoHS compliant products have <G> mark on the spec name plate.
PARTS CATALOG (OBB648)
MUZ-HJ25VA MUZ-HJ35VA
Revision A:
• MUZ-HJ50VA-E1 has been added. Please void OBH648.
2
<Preparation before the repair service>
Prepare the proper tools. Prepare the proper protectors. Provide adequate ventilation. After stopping the operation of the air conditioner, turn off the power-supply breaker and remove the power plug. Discharge the capacitor before the work involving the electric parts.
<Precautions during the repair service>
Do not perform the work involving the electric parts with wet hands. Do not pour water into the electric parts. Do not touch the refrigerant. Do not touch the hot or cold areas in the refrigeration cycle. When the repair or the inspection of the circuit needs to be done without turning off the power, exercise great caution not to
touch the live parts.
Use the specifi ed refrigerant only
Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of. Correct refrigerant is specified in the manuals and on the spec labels provided with our products. We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions.
Revision A:
• MUZ-HJ50VA-E1 has been added.
OBH648A
3
MUZ-HJ25VA -
E1
MUZ-HJ35VA -
E1
MUZ-HJ50VA -
E1
1. New model
1
TECHNICAL CHANGES
ACCESSORIES
Air outlet
Drain outlet
Piping
Drain hose
Air inlet
(Back and side)
MUZ-HJ25VA MUZ-HJ35VA
Drain socket 1
2
PART NAMES AND FUNCTIONS
Air outlet
Drain outlet
Piping
Drain hose
Air inlet
(Back and side)
MUZ-HJ50VA
OBH648A
4
3
SPECIFICATION
Outdoor model MUZ-HJ25VA MUZ-HJ35VA
Power supply Single phase, 230 V, 50 Hz
Capacity Rated frequency (Min.-Max.)
Cooling
kW
2.5 (1.3 - 3.0) 3.15 (1.4 - 3.5)
Heating 3.15 (0.9 - 3.5) 3.6 (1.1 - 4.1)
Breaker Capacity A 10
Electrical data
Power input 1 (Total)
Cooling
W
730 1,040
Heating 870 995
Running current 1 (Total)
Cooling
A
3.7 4.9
Heating 4.2 4.8
Power factor
1 (Total)
Cooling
%
85 92
Heating 90 90
Starting current
1 (Total) A 4.2 4.9
Coeffi cient of performance (COP) 1 (Total)
Cooling 3.42 3.03 Heating 3.62 3.62
Compressor
Model KNB065FUJHC KNB073FUVHC Output W 500 550
Current 1
Cooling
A
3.3 4.4
Heating 3.8 4.4
Refrigeration oil (Model) L 0.32 (NEO22)
Fan motor
Model RA6V21-BD Current
1 A 0.23 Dimensions W × H × D mm 699 × 538 × 249 Weight kg 24 25
Special remarks
Dehumidifi cation Cooling L/h 0.4 0.6 Air fl ow 1 m
3
/h 1,890 1,890
Sound level 1
Cooling
dB(A)
50 50
Heating 50 50 Fan speed rpm 840 840 Fan speed regulator 1 1 Refrigerant fi lling capacity (R410A) kg 0.70 0.72
NOTE: Test conditions are based on ISO 5151. Cooling: Indoor Dry-bulb temperature 27°C Wet-bulb temperature 19°C Outdoor Dry-bulb temperature 35°C Heating: Indoor Dry-bulb temperature 20°C Outdoor Dry-bulb temperature 7°C Wet-bulb temperature 6°C Refrigerant piping length (one way): 5 m 1 Measured under rated operating frequency.
OBH648A
5
Outdoor model MUZ-HJ50VA
Power supply Single phase, 230 V, 50 Hz
Capacity Rated frequency (Min.-Max.)
Cooling
kW
5.0 (1.3 - 5.0)
Heating 5.4 (1.4 - 6.5)
Breaker Capacity A 12
Electrical data
Power input 1 (Total)
Cooling
W
2,050
Heating 1,480
Running current
1
(Total)
Cooling
A
9.0
Heating 6.6
Power factor
1 (Total)
Cooling
%
99
Heating 97
Starting current
1 (Total) A 9.0
Coeffi cient of performance (COP) 1 (Total)
Cooling 2.44 Heating 3.65
Compressor
Model SNB130FGBHT Output W 900
Current
1
Cooling
A
8.5
Heating 5.9
Refrigeration oil (Model) L 0.45 (NEO22)
Fan motor
Model RC0J50-FA Current
1
Cooling
A
0.27
Heating 0.34 Dimensions W × H × D mm 800 × 550 × 285 Weight kg 36
Special remarks
Dehumidifi cation Cooling L/h 2.2
Air fl ow 1
Cooling
High
m
3
/h
1,872
Med. 1,872
Low 1,086
Heating
High 2,088
Med. 1,776
Low 1,386
Sound level 1
Cooling
dB(A)
50
Heating 51
Fan speed
Cooling
High
rpm
810
Med. 810
Low 490
Heating
High 900
Med. 770
Low 610 Fan speed regulator 3 Refrigerant fi lling capacity (R410A) kg 1.15
NOTE: Test conditions are based on ISO 5151. Cooling: Indoor Dry-bulb temperature 27°C Wet-bulb temperature 19°C Outdoor Dry-bulb temperature 35°C Heating: Indoor Dry-bulb temperature 20°C Outdoor Dry-bulb temperature 7°C Wet-bulb temperature 6°C Refrigerant piping length (one way): 5 m 1 Measured under rated operating frequency.
OBH648A
6
Specifi cations and rated conditions of main electric parts
Model
Item
MUZ-HJ25VA MUZ-HJ35VA
Smoothing capacitor (C61) 800 μF 420 V Diode module
(DB61) 15 A 600 V
(DB65) 10 A 600 V Fuse (F701, F801) T3.15AL250V Power module (IC700) 8 A 600 V 10 A 600 V Expansion valve coil (LEV) 12 VDC Reactor (L61) 18 mH Switching power transistor (IC821) 30 A 600 V Circuit protection (PTC64) 33 Ω Terminal block (TB) 3 P
Relay
(X61) 3 A 250 V (X63) 3 A 250 V (X64) 20 A 250 V
R.V. coil (21S4) 220 - 240 VAC
Specifi cations and rated conditions of main electric parts
Model
Item
MUZ-HJ50VA
Smoothing capacitor (C61, C62, C63) 600 μF/ 620 μF 420 V Diode module (DB61) 15 A 600 V
Fuse
(F61) T20AL250V
(F701, F801, F901) T3.15AL250V
Power module
(IC700) 15 A 600 V
(IC820) 20A 600V
(IC932) 8A600V Expansion valve coil (LEV) 12 VDC Reactor (L61) 23 mH
Circuit protection
(PTC64) 33 Ω (PTC65) 33 Ω
Terminal block (TB) 5 P Relay
(X63) 3 A 250 V (X64) 20 A 250 V
R.V. coil (21S4) 220 - 240 VAC
OBH648A
7
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
COOLING
FUNCTION
SPL(dB(A)) LINE
HEATING
50 50
NC-10
MUZ-HJ25VA
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
COOLING
FUNCTION
SPL(dB(A))
LINE
HEATING
50 50
Test conditions Cooling : Dry-bulb temperature 35°C
Heating : Dry-bulb temperature 7°C Wet-bulb temperature 6°C
OUTDOOR UNIT
MICROPHONE
1m
NC-10
MUZ-HJ35VA
4
NOISE CRITERIA CURVES
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
COOLING
FUNCTION
SPL(dB(A)) LINE
HEATING
50
NC-10
51
MUZ-HJ50VA
OBH648A
8
Unit : mm
MUZ-HJ25VA MUZ-HJ35VA
5
OUTLINES AND DIMENSIONS
REQUIRED SPACE
100 mm or more
350 mm or more
200 mm or more
100 mm or more
100 mm or more
MUZ-HJ50VA
10
69
800
302.5 500 Bolt pitch for installation
150
22.3
Handle
550
280
164.5
99.5
170.5
23
Service panel
Service port
285
344.5
44
400
Air in
Air out
Air in
17.5
Bolt pitch for
installation
304~325
40
Liquid refrigerant pipe joint Refrigerant pipe (flared) ø6.35
Gas refrigerant pipe joint Refrigerant pipe (flared) ø9.52
43°
35°
2 - 10 X 21 Oval hole
REQUIRED SPACE
350 mm or more
100 mm or more
Drain hole ø42
100 mm or more
100 mm or more
200 mm or more
41.5
270.3
157.7
43°
40°
102.7
13.5
538
Air in
Air in
Air out
349.5
55.7
121.4
249
17.9
699
500121
259
Bolt pitch for
installation
294~267
285
19.6
Liquid refrigerant pipe joint Refrigerant pipe (flared) ø6.35 Gas refrigerant pipe joint Refrigerant pipe (flared) ø9.52
Drain hole ø33
2 - 10.3 X 19.3 Oval hole
OBH648A
9
MUZ-HJ25VA
6
WIRING DIAGRAM
MUZ-HJ35VA
OBH648A
10
MUZ-HJ50VA
OBH648A
11
Unit : mm
MUZ-HJ25VA MUZ-HJ35VA
MUZ-HJ50VA
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve (with strainer)
Stop valve (with service port)
Refrigerant flow in cooling
Compressor
Muffler
4-way valve
Refrigerant flow in heating
Refrigerant pipe ø9.52 (with heat insulator)
Refrigerant pipe ø6.35 (with heat insulator)
R.V. coil heating OFF cooling ON
Strainer #100
Capillary tube
ø
3.0 × ø1.4 × 260
LEV
Muffler (HJ35 only)
7
REFRIGERANT SYSTEM DIAGRAM
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve (with strainer)
Stop valve (with service port)
Refrigerant flow in cooling
Compressor
Muffler
Muffler
4-way valve
Refrigerant flow in heating
Refrigerant pipe ø12.7 (with heat insulator)
Refrigerant pipe ø6.35 (with heat insulator)
R.V. coil heating ON cooling OFF
Strainer #100
Capillary tube
ø
4.0 × ø2.4 × 240
LEV
OBH648A
12
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Refrigerant piping: m
Piping size O.D: mm
Max. Length
A
Max. Height difference
B
Gas Liquid
MUZ-HJ25VA MUZ-HJ35VA
20 12
9.52
6.35
MUZ-HJ50VA 12.7
Max. Length A
Max. Height
difference
B
Indoor unit
Outdoor unit
ADDITIONAL REFRIGERANT CHARGE (R410A : g)
Model
Outdoor unit
precharged
Refrigerant piping length (one way)
5 m 6 m 7 m 8 m 9 m 10 m 11 m 12 m 13 m 14 m 15 m 20 m
MUZ-HJ25VA MUZ-HJ35VA MUZ-HJ50VA
700
0 0 0 20 40 60 80 100 120 140 160 260
720
1,150
Calculation: X g = 20 g/m (Refrigerant piping length (m) - 7)
NOTE : Refrigerant piping exceeding 7 m requires additional refrigerant charge according to the calculation.
OBH648A
13
The standard specifications apply only to the operation of the air conditioner under normal conditions. Since operating condi­tions vary according to the areas where these units are installed, the following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198 ~ 264 V, 50 Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature : °C WB (2) Indoor outlet air wet-bulb temperature : °C WB (3) Outdoor intake air dry-bulb temperature : °C DB (4) Total input: W (5) Indoor intake air dry-bulb temperature : °C DB (6) Outdoor intake air wet-bulb temperature : °C WB (7) Total input : W
Indoor air wet and dry bulb temperature difference on the left side of the following chart shows the difference between the indoor intake air wet and dry bulb temperature and the indoor outlet air wet and dry bulb temperature for your reference at service.
}
}
Cooling
Heating
MUZ-HJ25VA MUZ-HJ35VA MUZ-HJ50VA
How to measure the indoor air wet and dry bulb temperature difference
1. Attach at least 2 sets of wet and dry bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet and dry bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.
2. Attach at least 2 sets of wet and dry bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once (twice) to start the EMERGENCY COOL (HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
PERFORMANCE CURVES8
INDOOR UNIT OUTDOOR UNIT
Wet and dry bulb thermometers FRONT VIEW
Wet and dry bulb thermometers BACK VIEW
OBH648A
14
Indoor intake air Dry-bulb temperature (°C)
Outdoor intake air Wet-bulb temperature (°C)
Outdoor intake air Wet-bulb temperature (°C)
Indoor intake air Dry-bulb temperature (°C)
Heating capacity (at Rated frequency) Total input (Heating at Rated frequency)
Indoor air Wet-bulb temperature
difference (°C)
MUZ-HJ25VA
MUZ-HJ35VA
20.6
19.0
17.4
15.8
14.3
12.7
11.1
9.5
22.9
21.1
19.3
17.6
15.8
14.1
12.3
10.5
MUZ-HJ50VA
24.7
22.8
20.9
19.0
17.1
15.2
13.3
11.4
NOTE: The above broken lines are for the heating operation without any frost and defrost operation.
Indoor air Wet-bulb temperature
difference (°C)
Outdoor intake air Dry-bulb temperature (°C)
MUZ-HJ25VA
MUZ-HJ35VA
6.1
5.6
5.1
4.6
4.1
3.6
6.8
6.2
5.6
5.1
4.5
4.0
MUZ-HJ50VA
9.6
8.7
7.9
7.1
6.3
5.5
18 20 25 30 35 464540
0.8
0.9
1.0
1.1
1.2
1.3
Total input (Cooling :at Rated frequency)
Input correction factor
22 20 18
Indoor intake air Wet-bulb temperature (°C)
26
24
8-1. CAPACITY AND INPUT CURVES
Indoor air Wet-bulb temperature
difference (°C)
Outdoor intake air Dry-bulb temperature (°C)
MUZ-HJ25VA
MUZ-HJ50VA
7.2
6.7
6.1
5.6
5.1
4.6
4.1
11.4
10.5
9.6
8.7
7.9
7.1
6.3
MUZ-HJ35VA
8.0
7.4
6.8
6.2
5.6
5.1
4.5
18 20 25 30 35 40 4645
0.9
1.0
1.1
1.2
1.3
1.4
1.5
Indoor intake air Wet-bulb temperature (°C)
Cooling capacity (at Rated frequency)
Capacity correction factor
22 20 18
26
24
OBH648A
15
0 50 100
150
0.5
1.0
1.5
0 50 100
150
0.5
1.0
1.5
0 50 100
150
0.5
1.0
1.5
0 50 100
150
0.5
1.0
1.5
0 50 100
150
0.5
1.0
1.5
0 50 100
150
0.5
1.0
1.5
0 50 100
150
0.5
1.0
1.5
0 50 100
150
0.5
1.0
1.5
0 50 100
150
0.5
1.0
1.5
0 50 100
150
0.5
1.0
1.5
0 50 100
150
0.5
1.0
1.5
0 50 100
150
0.5
1.0
1.5
Correction of Cooling capacity
Capacity correction factors
The operational frequency of compressor
Correction of Cooling total input
Input correction factors
The operational frequency of compressor
Correction of Heating total input
Input correction factors
The operational frequency of compressor
Correction of Heating capacity
Capacity correction factors
The operational frequency of compressor
Correction of Cooling capacity
Capacity correction factors
The operational frequency of compressor
Correction of Cooling total input
Input correction factors
The operational frequency of compressor
Correction of Heating total input
Input correction factors
The operational frequency of compressor
Correction of Heating capacity
Capacity correction factors
The operational frequency of compressor
MUZ-HJ25VA
MUZ-HJ35VA
MUZ-HJ50VA
(Hz) (Hz) (Hz) (Hz)
Correction of Cooling capacity
Capacity correction factors
The operational frequency of compressor
Correction of Cooling total input
Input correction factors
The operational frequency of compressor
Correction of Heating total input
Input correction factors
The operational frequency of compressor
Correction of Heating capacity
Capacity correction factors
The operational frequency of compressor
(Hz) (Hz) (Hz) (Hz)
(Hz) (Hz) (Hz) (Hz)
8-2. CAPACITY AND INPUT CORRECTION BY OPERATIONAL FREQUENCY OF COMPRESSOR
8-3. HOW TO OPERATE FIXED-FREQUENCY OPERATION
<Test run operation>
1. Press EMERGENCY OPERATION switch to start COOL or HEAT mode (COOL: Press once, HEAT: Press twice).
2. Test run operation starts and continues to operate for 30 minutes.
3. Compressor operates at rated frequency in COOL mode or 58 Hz in HEAT mode.
4. Indoor fan operates at High speed.
5.
After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (operation frequency of compressor varies).
6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on remote controller.
OBH648A
Loading...