Mitsubishi MUZ-HC25VA-E1, MUZ-HC35VA-E1, MUZ-HC35VA-E2, MUZ-HC35VAB-E1, MUZ-HC35VAB-E2 Service Manual

Page 1
SPLIT-TYPE AIR CONDITIONERS
OUTDOOR UNIT
Revision B:
• MUZ-HC35VA-E2 and MUZ-HC35VAB-E2 have been added.
Please void OBH467 REVISED EDITION-A.
SERVICE MANUAL
Models
MUZ-HC25VA ­MUZ-HC35VA ­MUZ-HC35VA ­MUZ-HC35VAB ­MUZ-HC35VAB -
E1
E1
E2
E1
E2
HFC
utilized
R410A
Indoor unit service manual MSZ-HC•VA Series (OBH466) MSZ-CHC•VA Series (OBH522)
No. OBH467
REVISED EDITION-B
NOTE:
RoHS compliant products have <G> mark on the spec name plate.
CONTENTS
1. TECHNICAL CHANGES ··································· 3
2. PART NAMES AND FUNCTIONS ····················· 4
3. SPECIFICATION ················································ 5
4. NOISE CRITERIA CURVES ······························ 7
5. OUTLINES AND DIMENSIONS ························ 8
6. WIRING DIAGRAM ············································ 9
8. PERFORMANCE CURVES ····························· 13
9. ACTUATOR CONTROL ··································· 24
10. SERVICE FUNCTIONS ···································· 25
11. TROUBLESHOOTING ····································· 25
12. DISASSEMBLY INSTRUCTIONS ···················· 40
PARTS CATALOG (OBB467)
Page 2
Revision A:
•Table “ADDITIONAL REFRIGERANT CHARGE” of “7.
REFRIGERANT SYSTEM DIAGRAM
Revision B:
• MUZ-HC35VA-E2 and MUZ-HC35VAB-E2 have been added.
” has been corrected.
2
Page 3
1
TECHNICAL CHANGES
MUZ-HA25VA -E1 MUZ-HC25VA ­MUZ-HA35VA -E1 MUZ-HC35VA ­MUZ-HA35VA -E1 MUZ-HC35VAB -
1. Outdoor model has been changed.
MUZ-HC35VA -E1 MUZ-HC35VA ­MUZ-HC35VAB -E1 MUZ-HC35VAB -
1. REFRIGERANT SYSTEM has been changed.
E1
E1
E1
E2
E2
3
Page 4
2
PART NAMES AND FUNCTIONS
MUZ-HC25VA MUZ-HC35VA MUZ-HC35VAB
Air inlet
Piping
Drain hose
Air outlet
Drain outlet
ACCESSORIES
Drain socket 1
4
Page 5
3
Breaker capacity A 10 Running current 1 (Total) A 3.7 4.2 4.8 4.8 5.3 4.8 Power input 1 (Total) W 770 880 980 995 1130 995 Power factor Starting current 1 (Total) A 4.2 4.8 5.3
Electrical data
Coeffi cient of performance (C.O.P)
Compressor
Fan motor
Dehumidication /h 1.4 - 2.0 - 2.0 - Air fl ow 1 m3/h 1,812 1,788 1,800 1,776 1,800 1,776 Sound level 1 dB(A) 46 47 47 48 47 48 Fan speed rpm 810 800 800 790 800 790 Fan speed regulator 1 Refrigerant fi lling capacity (R410A) kg 0.73 0.75
Special remarks
Refrigeration oil (Model) NEO22
NOTE: Test conditions are based on ISO 5151. Cooling: Indoor Dry-bulb temperature 27°C Wet-bulb temperature 19°C Outdoor Dry-bulb temperature 35°C Heating: Indoor Dry-bulb temperature 20°C Outdoor Dry-bulb temperature 7°C Wet-bulb temperature 6°C Refrigerant piping length (one way): 5 m 1 Measured under rated operating frequency.
SPECIFICATION
Outdoor model MUZ-HC25VA MUZ-HC35VA MUZ-HC35VAB
Function Cooling Heating Cooling Heating Cooling Heating
Power supply Single phase 230 V, 50 Hz
Rated frequency (Min.-Max.)
Capacity
1 (Total) % 90 91 89 90 93 90
Model KNB065FDTH(C)
Output W 500 550 Current Model RA6V21-AB or BB or BD Current 1 A 0.24
Dimensions W × H × D mm 684 × 540 × 255
1 A 3.24 3.74 4.34 4.34 4.84 4.34
Weight kg 25
kW
1 (Total) 3.25 3.64 3.21 3.62 3.01 3.62
2.5
(0.9-3.0)
3.2
(0.9-4.4)
3.15
(1.0-3.7)
E1
E2
3.6
(0.9-4.8)
KNB073FEDH KNB073FGDH
KNB073FGDHC
3.4
(1.0-3.7)
3.6
(0.9-4.8)
5
Page 6
Specifi cations and rating conditions of main electric parts
Item
Model
MUZ-HC25
MUZ-HC35VA-
MUZ-HC35VAB-
E1
E1
MUZ-HC35VA-
MUZ-HC35VAB-
Current transformer (CT) 20 A
Smoothing capacitor (C61, C62) 500 μF 420 V Diode module
(DB61) 15 A 600 V
(DB65) 10 A 600 V
Fuse
(F61) T20AL250V
(F701, F801) T3.15AL250V
Intelligent power module (IPM) 10 A 600 V
Expansion valve coil (LEV) DC 12 V
Reactor (L61) 18 mH 7 A
Current-detecting resistor
(R61) 45 mΩ 5 W
(R825) 25 mΩ 5 W
Current-limiting PTC thermistor (PTC64) 33 Ω
Terminal block (TB1,TB2) 3 P Relay
(X61) 5 A 250 V
(X63) 3 A 250 V
(X64) 20 A 250 V
R.V. coil (21S4) SHF-4-10W5
Outdoor fan motor thermal fuse Open 152°C (RA6V21-AB) or Open 126°C (RA6V21-BB or BD) IGBT (TR821) 30 A 600 V
E2
E2
6
Page 7
4
NOISE CRITERIA CURVES
MUZ-HC25VA
FUNCTION
COOLING HEATING
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
SPL(dB(A)) LINE
46 47
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
MUZ-HC35VA
FUNCTION
COOLING
HEATING
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
SPL(dB(A))
47 48
LINE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
MUZ-HC35VAB
FUNCTION
COOLING
HEATING
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
SPL(dB(A))
47 48
LINE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
Test conditions Cooling : Dry-bulb temperature 35°C
Heating : Dry-bulb temperature 7°C Wet-bulb temperature 6°C
OUTDOOR UNIT
1m
MICROPHONE
7
Page 8
5
OUTLINES AND DIMENSIONS
MUZ-HC25VA MUZ-HC35VA MUZ-HC35VAB
381.5
Air in
540
17.5
Handle
Air in
Air out
Drain hole
2 holes 10 × 16
33
ø
40
47.5
Bolt pitch for
22.5
264-280
installation
REQUIRED SPACE
100 mm or more
300
255
20.8
144.6
89.6
Basically open 100 mm or more without any obstruction in front and on both sides of the unit.
100 mm or more
Open two sides of left, right, or rear side.
Service panel
Liquid refrigerant pipe joint Refrigerant pipe (flared) ø6.35
40°
43°
Unit : mm
100 mm or more
350 mm or more
270
10
61
243
105
Bolt pitch for installation
500
684
Service port
145.5
Gas refrigerant pipe joint Refrigerant pipe (flared) ø9.52
8
Page 9
6
MUZ-HC25VA MUZ-HC35VA-
WIRING DIAGRAM
E1
MUZ-HC35VAB-
E1
9
Page 10
MUZ-HC35VA-
E2
MUZ-HC35VAB-
E2
10
Page 11
7
REFRIGERANT SYSTEM DIAGRAM
MUZ-HC25VA MUZ-HC35VA-
E1
MUZ-HC35VAB-
E1
Unit : mm
Refrigerant pipe ø9.52 (with heat insulator)
Flared connection
Flared connection
Refrigerant pipe ø6.35 (with heat insulator)
Muffler
Stop valve (with service port)
Stop valve (with strainer)
4-way valve
Discharge temperature thermistor RT62
Capillary tube
ø
3.0 × ø1.4 × 450 (HC25)
ø
3.0 × ø1.4 × 235 (HC35)
Check
Capillary tube
valve
ø ø
Muffler
Compressor
Defrost thermistor RT61
3.0 × ø1.4 × 800 (HC25)
3.0 × ø1.4 × 600 (HC35)
Refrigerant flow in cooling Refrigerant flow in heating
Outdoor heat exchanger
Strainer
R.V. coil heating ON cooling OFF
MUZ-HC35VA-
Refrigerant pipe ø9.52 (with heat insulator)
Refrigerant pipe ø6.35 (with heat insulator)
E2
MUZ-HC35VAB-
Flared connection
Flared connection
E2
Muffler
Stop valve (with service port)
Capillary tube
ø
3.0 × ø2.0 × 260
Stop valve (with strainer)
4-way valve
Discharge temperature thermistor RT62
LEV
Muffler
Compressor
Refrigerant flow in cooling Refrigerant flow in heating
Outdoor heat exchanger
Defrost thermistor RT61
Strainer #100
R.V. coil heating ON cooling OFF
11
Page 12
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
MUZ-HC25VA MUZ-HC35VA MUZ-HC35VAB
Refrigerant piping: m
Max. Length
A
Max. Height difference
B
10 5 9.52 6.35
Indoor unit
Max. Height
difference
B
Max. Length A
Outdoor unit
Piping size O.D: mm
Gas Liquid
ADDITIONAL REFRIGERANT CHARGE (R410A : g)
Model
Outdoor unit
precharged
5 m 6 m 7 m 8 m 9 m 10 m
MUZ-HC25VA MUZ-HC35VA
1,150
0 0 0 90 120 150
MUZ-HC35VAB
NOTE : Refrigerant piping exceeding 7 m requires additional refrigerant charge according to the calculation.
Refrigerant piping length (one way)
Calculation: X g = 30 g/m (Refrigerant piping length (m) - 5)
12
Page 13
PERFORMANCE CURVES8
MUZ-HC25VA MUZ-HC35VA MUZ-HC35VAB
The standard specifications apply only to the operation of the air conditioner under normal conditions. Since operating condi­tions vary according to the areas where these units are installed, the following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198 ~ 264 V, 50 Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature : °C WB (2) Indoor outlet air wet-bulb temperature : °C WB (3) Outdoor intake air dry-bulb temperature : °C DB (4) Total input: W (5) Indoor intake air dry-bulb temperature : °C DB (6) Outdoor intake air wet-bulb temperature : °C WB (7) Total input : W Indoor air wet/dry-bulb temperature difference on the left side of the following chart shows the difference between the indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.
How to measure the indoor air wet-bulb/dry-bulb temperature difference
1. Attach at least 2 sets of wet and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.
2. Attach at least 2 sets of wet and dry-bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once (twice) to start the EMERGENCY COOL (HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
}
}
Cooling
Heating
INDOOR UNIT
Wet and dry-bulb thermometers
OUTDOOR UNIT
Wet and dry-bulb thermometers
13
Page 14
8-1. CAPACITY AND INPUT CURVES
7.9
9.8
7.3
9.0
6.7
8.3
6.1
7.5
5.5
6.8
5.0
6.1
difference (degree)
4.4
5.4
Indoor air Wet-bulb temperature
at Rated frequency
MUZ-HC25VA
8.3
6.7
7.5
6.1
6.8
5.5
6.1
5.0
5.4
4.4
difference (degree)
Indoor air Wet-bulb temperature
3.9
4.8
10.8
9.9
9.1
8.2
7.4
6.7
5.9
at Rated frequency
at Rated frequency
MUZ-HC35VAB
MUZ-HC35VA
9.1
8.2
7.4
6.7
5.9
5.2
1.5
1.4
1.3
1.2
1.1
1.0
0.9
Capacity correction factor
Indoor intake air Wet-bulb temperature (°C)
18 20 25 30 35 40 43
Outdoor intake air Dry-bulb temperature (°C)
1.3
1.2
1.1
Cooling capacity
Total input (cooling)
26
24
26
24
1.0
0.9
0.8
Input correction factor
Indoor intake air Wet-bulb temperature (°C)
18 20 25 30 35 40 43
Outdoor intake air Dry-bulb temperature (°C)
22 20 18
22 20 18
at Rated frequency
MUZ-HC25VA
22.4
20.5
20.7
18.9
19.0
17.4
17.2
15.8
15.5
14.2
13.8
12.6
12.1
11.0
difference (degree)
Indoor air Wet-bulb temperature
10.3
9.5
at Rated frequency
MUZ-HC25VA
at Rated frequency
MUZ-HC35VA
MUZ-HC35VA
at Rated frequency
MUZ-HC35VAB
22.4
20.7
19.0
17.2
15.5
13.8
12.1
10.3
at Rated frequency
at Rated frequency
MUZ-HC35VAB
(°C)
ure
mperat
Indoor intake air Dry-bulb temperature (°C)
Indoor intake air Dry-bulb te
Outdoor intake air Wet-bulb temperature (°C)
Outdoor intake air Wet-bulb temperature (°C)
NOTE: The above broken lines are for the heating operation without any frost and defrost operation.
14
Page 15
8-2. CAPACITY AND INPUT CORRECTION BY OPERATIONAL FREQUENCY OF COMPRESSOR
MUZ-HC25VA
Correction of Cooling capacity
1.5
Correction of Cooling total input
1.5
Correction of Heating capacity
2.0
Correction of Heating total input
2.0
1.0
0.5
Capacity correction factors
0.0 0 50 100 150(Hz)
The operational frequency of compressor
MUZ-HC35VA
Correction of Cooling capacity
1.5
1.0
0.5
Capacity correction factors
0.0 0 50 100 150(Hz)
The operational frequency of compressor
1.0
0.5
Input correction factors
0.0 0 50 100 150(Hz)
The operational frequency of compressor
Correction of Cooling total input
1.5
1.0
0.5
Input correction factors
0.0 0 50 100 150(Hz)
The operational frequency of compressor
1.5
1.0
0.5
Capacity correction factors
0.0 0 50 100 150(Hz)
The operational frequency of compressor
Correction of Heating capacity
2.0
1.5
1.0
0.5
Capacity correction factors
0.0 0 50 100 150(Hz)
The operational frequency of compressor
1.5
1.0
0.5
Input correction factors
0.0 0 50 100 150(Hz)
The operational frequency of compressor
Correction of Heating total input
2.0
1.5
1.0
0.5
Input correction factors
0.0 0 50 100 150(Hz)
The operational frequency of compressor
MUZ-HC35VAB
Correction of Cooling capacity
1.5
1.0
0.5
Capacity correction factors
0.0 0 50 100 150(Hz)
The operational frequency of compressor
Correction of Cooling total input
1.5
1.0
0.5
Input correction factors
0.0 0 50 100 150(Hz)
The operational frequency of compressor
Correction of Heating capacity
2.0
1.5
1.0
0.5
Capacity correction factors
0.0 0 50 100 150(Hz)
The operational frequency of compressor
Correction of Heating total input
2.0
1.5
1.0
0.5
Input correction factors
0.0 0 50 100 150(Hz)
The operational frequency of compressor
8-3. TEST RUN OPERATION (How to operate fixed-frequency operation)
1. Press EMERGENCY OPERATION switch to COOL or HEAT mode (COOL: Press once, HEAT: Press twice).
2. Test run operation starts and continues to operate for 30 minutes.
3. Compressor operates at rated frequency in COOL mode or 58 Hz in HEAT mode.
4. Indoor fan operates at High speed.
5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (Operation frequency of compressor varies).
6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on remote controller.
15
Page 16
8-4. OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
COOL operation
Both indoor and outdoor unit are under the same tempera-
ture/humidity condition.
Operation: TEST RUN OPERATION (Refer to 8-3.)
Dry-bulb temperature (°C) Relative humidity (%)
20 50 25 60 30 70
Outdoor low pressure
MUZ-HC25VA
1.4
14
1.2
12
[Gauge]
2
10
kgf/cm
8 6 4
2
1.0
MPa [Gauge]
0.8
0.6
0.4
0.2 18
Ambient temperature (°C) Ambient humidity (%)
3215 2050256030
70 (%)
NOTE : The unit of pressure has been changed to MPa on the international system of units (SI unit system). The conversion factor is: 1 (MPa [Gauge]) = 10.2 (kgf/cm2[Gauge])
35(°C)
14 12
[Gauge]
2
10
kgf/cm
8 6 4
2
MUZ-HC35VA
1.4
1.2
1.0
MPa [Gauge]
0.8
0.6
0.4
0.2 18
Ambient temperature (°C) Ambient humidity (%)
3215 2050256030
35(°C)
70 (%)
14 12
[Gauge]
2
10
kgf/cm
8 6 4
2
MUZ-HC35VAB
1.4
1.2
1.0
MPa [Gauge]
0.8
0.6
0.4
0.2 18
Ambient temperature (°C) Ambient humidity (%)
Outdoor unit current
MUZ-HC25VA
(A) (A) (A)
6
MUZ-HC35VA MUZ-HC35VAB
6
6
3215 2050256030
35(°C)
70 (%)
5
4
3
2
15 205025
18
60 Ambient temperature (°C) Ambient humidity (%)
3230
35(°C)
70 (%)
5
4
3
2
15 205025
18
60 Ambient temperature (°C) Ambient humidity (%)
70 (%)
HEAT operation
Condition:
Dry bulb temperature (°C) 20.0 2 7 15 20.0
Wet bulb temperature (°C) 14.5 1 6 12 14.5
Operation: Test run operation (refer to 8-3.)
Outdoor unit current
MUZ-HC25VA MUZ-HC35VA
(A) (A) (A)
3.0
2.5
2.0
1.5
1.0
0.5
0.0 2
5 10 15 20 25 (°C)
Ambient temperature (°C)
Indoor Outdoor
4.0
3.5
3.0
2.5
2.0
1.5
1.0 2
5 10 15 20 25 (°C)
Ambient temperature (°C)
3230
35(°C)
5
4
3
2
15 205025
18
Ambient temperature (°C) Ambient humidity (%)
MUZ-HC35VAB
4.0
3.5
3.0
2.5
2.0
1.5
1.0 2
5 10 15 20 25 (°C)
Ambient temperature (°C)
60
3230
35(°C)
70 (%)
16
Page 17
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-HC25VA
CAPACITY: 2.5 kW SHF: 0.79 INPUT: 770 W
INDOOR
DB (°C)
INDOOR
WB (°C)
21 18 2.94 1.79 0.61 616 2.81 1.72 0.61 647 2.70 1.65 0.61 678 2.60 1.59 0.61 708 21 20 3.06 1.50 0.49 647 2.94 1.44 0.49 685 2.85 1.40 0.49 701 2.75 1.35 0.49 732 22 18 2.94 1.91 0.65 616 2.81 1.83 0.65 647 2.70 1.76 0.65 678 2.60 1.69 0.65 708 22 20 3.06 1.62 0.53 647 2.94 1.56 0.53 685 2.85 1.51 0.53 701 2.75 1.46 0.53 732 22 22 3.19 1.31 0.41 670 3.08 1.26 0.41 712 3.00 1.23 0.41 732 2.88 1.18 0.41 762 23 18 2.94 2.03 0.69 616 2.81 1.94 0.69 647 2.70 1.86 0.69 678 2.60 1.79 0.69 708 23 20 3.06 1.75 0.57 647 2.94 1.67 0.57 685 2.85 1.62 0.57 701 2.75 1.57 0.57 732 23 22 3.19 1.43 0.45 670 3.08 1.38 0.45 712 3.00 1.35 0.45 732 2.88 1.29 0.45 762 24 18 2.94 2.14 0.73 616 2.81 2.05 0.73 647 2.70 1.97 0.73 678 2.60 1.90 0.73 708 24 20 3.06 1.87 0.61 647 2.94 1.79 0.61 685 2.85 1.74 0.61 701 2.75 1.68 0.61 732 24 22 3.19 1.56 0.49 670 3.08 1.51 0.49 712 3.00 1.47 0.49 732 2.88 1.41 0.49 762 24 24 3.35 1.24 0.37 701 3.23 1.19 0.37 739 3.15 1.17 0.37 762 3.05 1.13 0.37 801 25 18 2.94 2.26 0.77 616 2.81 2.17 0.77 647 2.70 2.08 0.77 678 2.60 2.00 0.77 708 25 20 3.06 1.99 0.65 647 2.94 1.91 0.65 685 2.85 1.85 0.65 701 2.75 1.79 0.65 732 25 22 3.19 1.69 0.53 670 3.08 1.63 0.53 712 3.00 1.59 0.53 732 2.88 1.52 0.53 762 25 24 3.35 1.37 0.41 701 3.23 1.32 0.41 739 3.15 1.29 0.41 762 3.05 1.25 0.41 801 26 18 2.94 2.38 0.81 616 2.81 2.28 0.81 647 2.70 2.19 0.81 678 2.60 2.11 0.81 708 26 20 3.06 2.11 0.69 647 2.94 2.03 0.69 685 2.85 1.97 0.69 701 2.75 1.90 0.69 732 26 22 3.19 1.82 0.57 670 3.08 1.75 0.57 712 3.00 1.71 0.57 732 2.88 1.64 0.57 762 26 24 3.35 1.51 0.45 701 3.23 1.45 0.45 739 3.15 1.42 0.45 762 3.05 1.37 0.45 801 26 26 3.45 1.14 0.33 739 3.35 1.11 0.33 778 3.30 1.09 0.33 801 3.20 1.06 0.33 824 27 18 2.94 2.50 0.85 616 2.81 2.39 0.85 647 2.70 2.30 0.85 678 2.60 2.21 0.85 708 27 20 3.06 2.24 0.73 647 2.94 2.14 0.73 685 2.85 2.08 0.73 701 2.75 2.01 0.73 732 27 22 3.19 1.94 0.61 670 3.08 1.88 0.61 712 3.00 1.83 0.61 732 2.88 1.75 0.61 762 27 24 3.35 1.64 0.49 701 3.23 1.58 0.49 739 3.15 1.54 0.49 762 3.05 1.49 0.49 801 27 26 3.45 1.28 0.37 739 3.35 1.24 0.37 778 3.30 1.22 0.37 801 3.20 1.18 0.37 824 28 18 2.94 2.61 0.89 616 2.81 2.50 0.89 647 2.70 2.40 0.89 678 2.60 2.31 0.89 708 28 20 3.06 2.36 0.77 647 2.94 2.26 0.77 685 2.85 2.19 0.77 701 2.75 2.12 0.77 732 28 22 3.19 2.07 0.65 670 3.08 2.00 0.65 712 3.00 1.95 0.65 732 2.88 1.87 0.65 762 28 24 3.35 1.78 0.53 701 3.23 1.71 0.53 739 3.15 1.67 0.53 762 3.05 1.62 0.53 801 28 26 3.45 1.41 0.41 739 3.35 1.37 0.41 778 3.30 1.35 0.41 801 3.20 1.31 0.41 824 29 18 2.94 2.73 0.93 616 2.81 2.62 0.93 647 2.70 2.51 0.93 678 2.60 2.42 0.93 708 29 20 3.06 2.48 0.81 647 2.94 2.38 0.81 685 2.85 2.31 0.81 701 2.75 2.23 0.81 732 29 22 3.19 2.20 0.69 670 3.08 2.12 0.69 712 3.00 2.07 0.69 732 2.88 1.98 0.69 762 29 24 3.35 1.91 0.57 701 3.23 1.84 0.57 739 3.15 1.80 0.57 762 3.05 1.74 0.57 801 29 26 3.45 1.55 0.45 739 3.35 1.51 0.45 778 3.30 1.49 0.45 801 3.20 1.44 0.45 824 30 18 2.94 2.85 0.97 616 2.81 2.73 0.97 647 2.70 2.62 0.97 678 2.60 2.52 0.97 708 30 20 3.06 2.60 0.85 647 2.94 2.50 0.85 685 2.85 2.42 0.85 701 2.75 2.34 0.85 732 30 22 3.19 2.33 0.73 670 3.08 2.24 0.73 712 3.00 2.19 0.73 732 2.88 2.10 0.73 762 30 24 3.35 2.04 0.61 701 3.23 1.97 0.61 739 3.15 1.92 0.61 762 3.05 1.86 0.61 801 30 26 3.45 1.69 0.49 739 3.35 1.64 0.49 778 3.30 1.62 0.49 801 3.20 1.57 0.49 824 31 18 2.94 2.94 1.00 616 2.81 2.81 1.00 647 2.70 2.70 1.00 678 2.60 2.60 1.00 708 31 20 3.06 2.73 0.89 647 2.94 2.61 0.89 685 2.85 2.54 0.89 701 2.75 2.45 0.89 732 31 22 3.19 2.45 0.77 670 3.08 2.37 0.77 712 3.00 2.31 0.77 732 2.88 2.21 0.77 762 31 24 3.35 2.18 0.65 701 3.23 2.10 0.65 739 3.15 2.05 0.65 762 3.05 1.98 0.65 801 31 26 3.45 1.83 0.53 739 3.35 1.78 0.53 778 3.30 1.75 0.53 801 3.20 1.70 0.53 824 32 18 2.94 2.94 1.00 616 2.81 2.81 1.00 647 2.70 2.70 1.00 678 2.60 2.60 1.00 708 32 20 3.06 2.85 0.93 647 2.94 2.73 0.93 685 2.85 2.65 0.93 701 2.75 2.56 0.93 732 32 22 3.19 2.58 0.81 670 3.08 2.49 0.81 712 3.00 2.43 0.81 732 2.88 2.33 0.81 762 32 24 3.35 2.31 0.69 701 3.23 2.23 0.69 739 3.15 2.17 0.69 762 3.05 2.10 0.69 801 32 26 3.45 1.97 0.57 739 3.35 1.91 0.57 778 3.30 1.88 0.57 801 3.20 1.82 0.57 824
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 25 27 30
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OUTDOOR DB (°C)
17
Page 18
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-HC25VA
CAPACITY: 2.5 kW SHF: 0.79 INPUT: 770 W
INDOOR
DB (°C)
INDOOR
WB (°C)
21 18 2.45 1.49 0.61 755 2.25 1.37 0.61 801 2.08 1.27 0.61 832 21 20 2.58 1.26 0.49 785 2.40 1.18 0.49 824 2.23 1.09 0.49 870 22 18 2.45 1.59 0.65 755 2.25 1.46 0.65 801 2.08 1.35 0.65 832 22 20 2.58 1.36 0.53 785 2.40 1.27 0.53 824 2.23 1.18 0.53 870 22 22 2.73 1.12 0.41 816 2.55 1.05 0.41 862 2.38 0.97 0.41 893 23 18 2.45 1.69 0.69 755 2.25 1.55 0.69 801 2.08 1.43 0.69 832 23 20 2.58 1.47 0.57 785 2.40 1.37 0.57 824 2.23 1.27 0.57 870 23 22 2.73 1.23 0.45 816 2.55 1.15 0.45 862 2.38 1.07 0.45 893 24 18 2.45 1.79 0.73 755 2.25 1.64 0.73 801 2.08 1.51 0.73 832 24 20 2.58 1.57 0.61 785 2.40 1.46 0.61 824 2.23 1.36 0.61 870 24 22 2.73 1.34 0.49 816 2.55 1.25 0.49 862 2.38 1.16 0.49 893 24 24 2.88 1.06 0.37 847 2.70 1.00 0.37 886 2.55 0.94 0.37 924 25 18 2.45 1.89 0.77 755 2.25 1.73 0.77 801 2.08 1.60 0.77 832 25 20 2.58 1.67 0.65 785 2.40 1.56 0.65 824 2.23 1.45 0.65 870 25 22 2.73 1.44 0.53 816 2.55 1.35 0.53 862 2.38 1.26 0.53 893 25 24 2.88 1.18 0.41 847 2.70 1.11 0.41 886 2.55 1.05 0.41 924 26 18 2.45 1.98 0.81 755 2.25 1.82 0.81 801 2.08 1.68 0.81 832 26 20 2.58 1.78 0.69 785 2.40 1.66 0.69 824 2.23 1.54 0.69 870 26 22 2.73 1.55 0.57 816 2.55 1.45 0.57 862 2.38 1.35 0.57 893 26 24 2.88 1.29 0.45 847 2.70 1.22 0.45 886 2.55 1.15 0.45 924 26 26 3.03 1.00 0.33 878 2.85 0.94 0.33 916 2.68 0.88 0.33 955 27 18 2.45 2.08 0.85 755 2.25 1.91 0.85 801 2.08 1.76 0.85 832 27 20 2.58 1.88 0.73 785 2.40 1.75 0.73 824 2.23 1.62 0.73 870 27 22 2.73 1.66 0.61 816 2.55 1.56 0.61 862 2.38 1.45 0.61 893 27 24 2.88 1.41 0.49 847 2.70 1.32 0.49 886 2.55 1.25 0.49 924 27 26 3.03 1.12 0.37 878 2.85 1.05 0.37 916 2.68 0.99 0.37 955 28 18 2.45 2.18 0.89 755 2.25 2.00 0.89 801 2.08 1.85 0.89 832 28 20 2.58 1.98 0.77 785 2.40 1.85 0.77 824 2.23 1.71 0.77 870 28 22 2.73 1.77 0.65 816 2.55 1.66 0.65 862 2.38 1.54 0.65 893 28 24 2.88 1.52 0.53 847 2.70 1.43 0.53 886 2.55 1.35 0.53 924 28 26 3.03 1.24 0.41 878 2.85 1.17 0.41 916 2.68 1.10 0.41 955 29 18 2.45 2.28 0.93 755 2.25 2.09 0.93 801 2.08 1.93 0.93 832 29 20 2.58 2.09 0.81 785 2.40 1.94 0.81 824 2.23 1.80 0.81 870 29 22 2.73 1.88 0.69 816 2.55 1.76 0.69 862 2.38 1.64 0.69 893 29 24 2.88 1.64 0.57 847 2.70 1.54 0.57 886 2.55 1.45 0.57 924 29 26 3.03 1.36 0.45 878 2.85 1.28 0.45 916 2.68 1.20 0.45 955 30 18 2.45 2.38 0.97 755 2.25 2.18 0.97 801 2.08 2.01 0.97 832 30 20 2.58 2.19 0.85 785 2.40 2.04 0.85 824 2.23 1.89 0.85 870 30 22 2.73 1.99 0.73 816 2.55 1.86 0.73 862 2.38 1.73 0.73 893 30 24 2.88 1.75 0.61 847 2.70 1.65 0.61 886 2.55 1.56 0.61 924 30 26 3.03 1.48 0.49 878 2.85 1.40 0.49 916 2.68 1.31 0.49 955 31 18 2.45 2.45 1.00 755 2.25 2.25 1.00 801 2.08 2.08 1.00 832 31 20 2.58 2.29 0.89 785 2.40 2.14 0.89 824 2.23 1.98 0.89 870 31 22 2.73 2.10 0.77 816 2.55 1.96 0.77 862 2.38 1.83 0.77 893 31 24 2.88 1.87 0.65 847 2.70 1.76 0.65 886 2.55 1.66 0.65 924 31 26 3.03 1.60 0.53 878 2.85 1.51 0.53 916 2.68 1.42 0.53 955 32 18 2.45 2.45 1.00 755 2.25 2.25 1.00 801 2.08 2.08 1.00 832 32 20 2.58 2.39 0.93 785 2.40 2.23 0.93 824 2.23 2.07 0.93 870 32 22 2.73 2.21 0.81 816 2.55 2.07 0.81 862 2.38 1.92 0.81 893 32 24 2.88 1.98 0.69 847 2.70 1.86 0.69 886 2.55 1.76 0.69 924 32 26 3.03 1.72 0.57 878 2.85 1.62 0.57 916 2.68 1.52 0.57 955
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
35 40 46
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OUTDOOR DB (°C)
18
Page 19
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-HC35VA
CAPACITY: 3.15 kW SHF: 0.76 INPUT: 980 W
INDOOR
DB (°C)
INDOOR
WB (°C)
21 18 3.70 2.15 0.58 784 3.54 2.06 0.58 823 3.40 1.97 0.58 862 3.28 1.90 0.58 902 21 20 3.86 1.78 0.46 823 3.70 1.70 0.46 872 3.59 1.65 0.46 892 3.47 1.59 0.46 931 22 18 3.70 2.29 0.62 784 3.54 2.20 0.62 823 3.40 2.11 0.62 862 3.28 2.03 0.62 902 22 20 3.86 1.93 0.50 823 3.70 1.85 0.50 872 3.59 1.80 0.50 892 3.47 1.73 0.50 931 22 22 4.02 1.53 0.38 853 3.87 1.47 0.38 907 3.78 1.44 0.38 931 3.62 1.38 0.38 970 23 18 3.70 2.44 0.66 784 3.54 2.34 0.66 823 3.40 2.25 0.66 862 3.28 2.16 0.66 902 23 20 3.86 2.08 0.54 823 3.70 2.00 0.54 872 3.59 1.94 0.54 892 3.47 1.87 0.54 931 23 22 4.02 1.69 0.42 853 3.87 1.63 0.42 907 3.78 1.59 0.42 931 3.62 1.52 0.42 970 24 18 3.70 2.59 0.70 784 3.54 2.48 0.70 823 3.40 2.38 0.70 862 3.28 2.29 0.70 902 24 20 3.86 2.24 0.58 823 3.70 2.15 0.58 872 3.59 2.08 0.58 892 3.47 2.01 0.58 931 24 22 4.02 1.85 0.46 853 3.87 1.78 0.46 907 3.78 1.74 0.46 931 3.62 1.67 0.46 970 24 24 4.22 1.44 0.34 892 4.06 1.38 0.34 941 3.97 1.35 0.34 970 3.84 1.31 0.34 1019 25 18 3.70 2.74 0.74 784 3.54 2.62 0.74 823 3.40 2.52 0.74 862 3.28 2.42 0.74 902 25 20 3.86 2.39 0.62 823 3.70 2.29 0.62 872 3.59 2.23 0.62 892 3.47 2.15 0.62 931 25 22 4.02 2.01 0.50 853 3.87 1.94 0.50 907 3.78 1.89 0.50 931 3.62 1.81 0.50 970 25 24 4.22 1.60 0.38 892 4.06 1.54 0.38 941 3.97 1.51 0.38 970 3.84 1.46 0.38 1019 26 18 3.70 2.89 0.78 784 3.54 2.76 0.78 823 3.40 2.65 0.78 862 3.28 2.56 0.78 902 26 20 3.86 2.55 0.66 823 3.70 2.44 0.66 872 3.59 2.37 0.66 892 3.47 2.29 0.66 931 26 22 4.02 2.17 0.54 853 3.87 2.09 0.54 907 3.78 2.04 0.54 931 3.62 1.96 0.54 970 26 24 4.22 1.77 0.42 892 4.06 1.71 0.42 941 3.97 1.67 0.42 970 3.84 1.61 0.42 1019 26 26 4.35 1.30 0.30 941 4.22 1.27 0.30 990 4.16 1.25 0.30 1019 4.03 1.21 0.30 1049 27 18 3.70 3.04 0.82 784 3.54 2.91 0.82 823 3.40 2.79 0.82 862 3.28 2.69 0.82 902 27 20 3.86 2.70 0.70 823 3.70 2.59 0.70 872 3.59 2.51 0.70 892 3.47 2.43 0.70 931 27 22 4.02 2.33 0.58 853 3.87 2.25 0.58 907 3.78 2.19 0.58 931 3.62 2.10 0.58 970 27 24 4.22 1.94 0.46 892 4.06 1.87 0.46 941 3.97 1.83 0.46 970 3.84 1.77 0.46 1019 27 26 4.35 1.48 0.34 941 4.22 1.44 0.34 990 4.16 1.41 0.34 1019 4.03 1.37 0.34 1049 28 18 3.70 3.18 0.86 784 3.54 3.05 0.86 823 3.40 2.93 0.86 862 3.28 2.82 0.86 902 28 20 3.86 2.86 0.74 823 3.70 2.74 0.74 872 3.59 2.66 0.74 892 3.47 2.56 0.74 931 28 22 4.02 2.49 0.62 853 3.87 2.40 0.62 907 3.78 2.34 0.62 931 3.62 2.25 0.62 970 28 24 4.22 2.11 0.50 892 4.06 2.03 0.50 941 3.97 1.98 0.50 970 3.84 1.92 0.50 1019 28 26 4.35 1.65 0.38 941 4.22 1.60 0.38 990 4.16 1.58 0.38 1019 4.03 1.53 0.38 1049 29 18 3.70 3.33 0.90 784 3.54 3.19 0.90 823 3.40 3.06 0.90 862 3.28 2.95 0.90 902 29 20 3.86 3.01 0.78 823 3.70 2.89 0.78 872 3.59 2.80 0.78 892 3.47 2.70 0.78 931 29 22 4.02 2.65 0.66 853 3.87 2.56 0.66 907 3.78 2.49 0.66 931 3.62 2.39 0.66 970 29 24 4.22 2.28 0.54 892 4.06 2.19 0.54 941 3.97 2.14 0.54 970 3.84 2.08 0.54 1019 29 26 4.35 1.83 0.42 941 4.22 1.77 0.42 990 4.16 1.75 0.42 1019 4.03 1.69 0.42 1049 30 18 3.70 3.48 0.94 784 3.54 3.33 0.94 823 3.40 3.20 0.94 862 3.28 3.08 0.94 902 30 20 3.86 3.16 0.82 823 3.70 3.04 0.82 872 3.59 2.94 0.82 892 3.47 2.84 0.82 931 30 22 4.02 2.81 0.70 853 3.87 2.71 0.70 907 3.78 2.65 0.70 931 3.62 2.54 0.70 970 30 24 4.22 2.45 0.58 892 4.06 2.36 0.58 941 3.97 2.30 0.58 970 3.84 2.23 0.58 1019 30 26 4.35 2.00 0.46 941 4.22 1.94 0.46 990 4.16 1.91 0.46 1019 4.03 1.85 0.46 1049 31 18 3.70 3.63 0.98 784 3.54 3.47 0.98 823 3.40 3.33 0.98 862 3.28 3.21 0.98 902 31 20 3.86 3.32 0.86 823 3.70 3.18 0.86 872 3.59 3.09 0.86 892 3.47 2.98 0.86 931 31 22 4.02 2.97 0.74 853 3.87 2.87 0.74 907 3.78 2.80 0.74 931 3.62 2.68 0.74 970 31 24 4.22 2.62 0.62 892 4.06 2.52 0.62 941 3.97 2.46 0.62 970 3.84 2.38 0.62 1019 31 26 4.35 2.17 0.50 941 4.22 2.11 0.50 990 4.16 2.08 0.50 1019 4.03 2.02 0.50 1049 32 18 3.70 3.70 1.00 784 3.54 3.54 1.00 823 3.40 3.40 1.00 862 3.28 3.28 1.00 902 32 20 3.86 3.47 0.90 823 3.70 3.33 0.90 872 3.59 3.23 0.90 892 3.47 3.12 0.90 931 32 22 4.02 3.13 0.78 853 3.87 3.02 0.78 907 3.78 2.95 0.78 931 3.62 2.83 0.78 970 32 24 4.22 2.79 0.66 892 4.06 2.68 0.66 941 3.97 2.62 0.66 970 3.84 2.54 0.66 1019 32 26 4.35 2.35 0.54 941 4.22 2.28 0.54 990 4.16 2.25 0.54 1019 4.03 2.18 0.54 1049
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 25 27 30
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OUTDOOR DB (°C)
19
Page 20
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-HC35VA
CAPACITY: 3.15 kW SHF: 0.76 INPUT: 980 W
INDOOR
DB (°C)
INDOOR
WB (°C)
21 18 3.09 1.79 0.58 960 2.84 1.64 0.58 1019 2.61 1.52 0.58 1058 21 20 3.24 1.49 0.46 1000 3.02 1.39 0.46 1049 2.80 1.29 0.46 1107 22 18 3.09 1.91 0.62 960 2.84 1.76 0.62 1019 2.61 1.62 0.62 1058 22 20 3.24 1.62 0.50 1000 3.02 1.51 0.50 1049 2.80 1.40 0.50 1107 22 22 3.43 1.30 0.38 1039 3.21 1.22 0.38 1098 2.99 1.14 0.38 1137 23 18 3.09 2.04 0.66 960 2.84 1.87 0.66 1019 2.61 1.73 0.66 1058 23 20 3.24 1.75 0.54 1000 3.02 1.63 0.54 1049 2.80 1.51 0.54 1107 23 22 3.43 1.44 0.42 1039 3.21 1.35 0.42 1098 2.99 1.26 0.42 1137 24 18 3.09 2.16 0.70 960 2.84 1.98 0.70 1019 2.61 1.83 0.70 1058 24 20 3.24 1.88 0.58 1000 3.02 1.75 0.58 1049 2.80 1.63 0.58 1107 24 22 3.43 1.58 0.46 1039 3.21 1.48 0.46 1098 2.99 1.38 0.46 1137 24 24 3.62 1.23 0.34 1078 3.40 1.16 0.34 1127 3.21 1.09 0.34 1176 25 18 3.09 2.28 0.74 960 2.84 2.10 0.74 1019 2.61 1.93 0.74 1058 25 20 3.24 2.01 0.62 1000 3.02 1.87 0.62 1049 2.80 1.74 0.62 1107 25 22 3.43 1.72 0.50 1039 3.21 1.61 0.50 1098 2.99 1.50 0.50 1137 25 24 3.62 1.38 0.38 1078 3.40 1.29 0.38 1127 3.21 1.22 0.38 1176 26 18 3.09 2.41 0.78 960 2.84 2.21 0.78 1019 2.61 2.04 0.78 1058 26 20 3.24 2.14 0.66 1000 3.02 2.00 0.66 1049 2.80 1.85 0.66 1107 26 22 3.43 1.85 0.54 1039 3.21 1.74 0.54 1098 2.99 1.62 0.54 1137 26 24 3.62 1.52 0.42 1078 3.40 1.43 0.42 1127 3.21 1.35 0.42 1176 26 26 3.81 1.14 0.30 1117 3.59 1.08 0.30 1166 3.37 1.01 0.30 1215 27 18 3.09 2.53 0.82 960 2.84 2.32 0.82 1019 2.61 2.14 0.82 1058 27 20 3.24 2.27 0.70 1000 3.02 2.12 0.70 1049 2.80 1.96 0.70 1107 27 22 3.43 1.99 0.58 1039 3.21 1.86 0.58 1098 2.99 1.74 0.58 1137 27 24 3.62 1.67 0.46 1078 3.40 1.56 0.46 1127 3.21 1.48 0.46 1176 27 26 3.81 1.30 0.34 1117 3.59 1.22 0.34 1166 3.37 1.15 0.34 1215 28 18 3.09 2.65 0.86 960 2.84 2.44 0.86 1019 2.61 2.25 0.86 1058 28 20 3.24 2.40 0.74 1000 3.02 2.24 0.74 1049 2.80 2.07 0.74 1107 28 22 3.43 2.13 0.62 1039 3.21 1.99 0.62 1098 2.99 1.86 0.62 1137 28 24 3.62 1.81 0.50 1078 3.40 1.70 0.50 1127 3.21 1.61 0.50 1176 28 26 3.81 1.45 0.38 1117 3.59 1.36 0.38 1166 3.37 1.28 0.38 1215 29 18 3.09 2.78 0.90 960 2.84 2.55 0.90 1019 2.61 2.35 0.90 1058 29 20 3.24 2.53 0.78 1000 3.02 2.36 0.78 1049 2.80 2.19 0.78 1107 29 22 3.43 2.27 0.66 1039 3.21 2.12 0.66 1098 2.99 1.98 0.66 1137 29 24 3.62 1.96 0.54 1078 3.40 1.84 0.54 1127 3.21 1.74 0.54 1176 29 26 3.81 1.60 0.42 1117 3.59 1.51 0.42 1166 3.37 1.42 0.42 1215 30 18 3.09 2.90 0.94 960 2.84 2.66 0.94 1019 2.61 2.46 0.94 1058 30 20 3.24 2.66 0.82 1000 3.02 2.48 0.82 1049 2.80 2.30 0.82 1107 30 22 3.43 2.40 0.70 1039 3.21 2.25 0.70 1098 2.99 2.09 0.70 1137 30 24 3.62 2.10 0.58 1078 3.40 1.97 0.58 1127 3.21 1.86 0.58 1176 30 26 3.81 1.75 0.46 1117 3.59 1.65 0.46 1166 3.37 1.55 0.46 1215 31 18 3.09 3.03 0.98 960 2.84 2.78 0.98 1019 2.61 2.56 0.98 1058 31 20 3.24 2.79 0.86 1000 3.02 2.60 0.86 1049 2.80 2.41 0.86 1107 31 22 3.43 2.54 0.74 1039 3.21 2.38 0.74 1098 2.99 2.21 0.74 1137 31 24 3.62 2.25 0.62 1078 3.40 2.11 0.62 1127 3.21 1.99 0.62 1176 31 26 3.81 1.91 0.50 1117 3.59 1.80 0.50 1166 3.37 1.69 0.50 1215 32 18 3.09 3.09 1.00 960 2.84 2.84 1.00 1019 2.61 2.61 1.00 1058 32 20 3.24 2.92 0.90 1000 3.02 2.72 0.90 1049 2.80 2.52 0.90 1107 32 22 3.43 2.68 0.78 1039 3.21 2.51 0.78 1098 2.99 2.33 0.78 1137 32 24 3.62 2.39 0.66 1078 3.40 2.25 0.66 1127 3.21 2.12 0.66 1176 32 26 3.81 2.06 0.54 1117 3.59 1.94 0.54 1166 3.37 1.82 0.54 1215
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
35 40 46
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OUTDOOR DB (°C)
20
Page 21
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-HC35VAB
CAPACITY: 3.4 kW SHF: 0.76 INPUT: 1130 W
INDOOR
DB (°C)
INDOOR
WB (°C)
21 18 4.00 2.32 0.58 904 3.83 2.22 0.58 949 3.67 2.13 0.58 994 3.54 2.05 0.58 1040 21 20 4.17 1.92 0.46 949 4.00 1.84 0.46 1006 3.88 1.78 0.46 1028 3.74 1.72 0.46 1074 22 18 4.00 2.48 0.62 904 3.83 2.37 0.62 949 3.67 2.28 0.62 994 3.54 2.19 0.62 1040 22 20 4.17 2.08 0.50 949 4.00 2.00 0.50 1006 3.88 1.94 0.50 1028 3.74 1.87 0.50 1074 22 22 4.34 1.65 0.38 983 4.18 1.59 0.38 1045 4.08 1.55 0.38 1074 3.91 1.49 0.38 1119 23 18 4.00 2.64 0.66 904 3.83 2.52 0.66 949 3.67 2.42 0.66 994 3.54 2.33 0.66 1040 23 20 4.17 2.25 0.54 949 4.00 2.16 0.54 1006 3.88 2.09 0.54 1028 3.74 2.02 0.54 1074 23 22 4.34 1.82 0.42 983 4.18 1.76 0.42 1045 4.08 1.71 0.42 1074 3.91 1.64 0.42 1119 24 18 4.00 2.80 0.70 904 3.83 2.68 0.70 949 3.67 2.57 0.70 994 3.54 2.48 0.70 1040 24 20 4.17 2.42 0.58 949 4.00 2.32 0.58 1006 3.88 2.25 0.58 1028 3.74 2.17 0.58 1074 24 22 4.34 1.99 0.46 983 4.18 1.92 0.46 1045 4.08 1.88 0.46 1074 3.91 1.80 0.46 1119 24 24 4.56 1.55 0.34 1028 4.39 1.49 0.34 1085 4.28 1.46 0.34 1119 4.15 1.41 0.34 1175 25 18 4.00 2.96 0.74 904 3.83 2.83 0.74 949 3.67 2.72 0.74 994 3.54 2.62 0.74 1040 25 20 4.17 2.58 0.62 949 4.00 2.48 0.62 1006 3.88 2.40 0.62 1028 3.74 2.32 0.62 1074 25 22 4.34 2.17 0.50 983 4.18 2.09 0.50 1045 4.08 2.04 0.50 1074 3.91 1.96 0.50 1119 25 24 4.56 1.73 0.38 1028 4.39 1.67 0.38 1085 4.28 1.63 0.38 1119 4.15 1.58 0.38 1175 26 18 4.00 3.12 0.78 904 3.83 2.98 0.78 949 3.67 2.86 0.78 994 3.54 2.76 0.78 1040 26 20 4.17 2.75 0.66 949 4.00 2.64 0.66 1006 3.88 2.56 0.66 1028 3.74 2.47 0.66 1074 26 22 4.34 2.34 0.54 983 4.18 2.26 0.54 1045 4.08 2.20 0.54 1074 3.91 2.11 0.54 1119 26 24 4.56 1.91 0.42 1028 4.39 1.84 0.42 1085 4.28 1.80 0.42 1119 4.15 1.74 0.42 1175 26 26 4.69 1.41 0.30 1085 4.56 1.37 0.30 1141 4.49 1.35 0.30 1175 4.35 1.31 0.30 1209 27 18 4.00 3.28 0.82 904 3.83 3.14 0.82 949 3.67 3.01 0.82 994 3.54 2.90 0.82 1040 27 20 4.17 2.92 0.70 949 4.00 2.80 0.70 1006 3.88 2.71 0.70 1028 3.74 2.62 0.70 1074 27 22 4.34 2.51 0.58 983 4.18 2.43 0.58 1045 4.08 2.37 0.58 1074 3.91 2.27 0.58 1119 27 24 4.56 2.10 0.46 1028 4.39 2.02 0.46 1085 4.28 1.97 0.46 1119 4.15 1.91 0.46 1175 27 26 4.69 1.60 0.34 1085 4.56 1.55 0.34 1141 4.49 1.53 0.34 1175 4.35 1.48 0.34 1209 28 18 4.00 3.44 0.86 904 3.83 3.29 0.86 949 3.67 3.16 0.86 994 3.54 3.04 0.86 1040 28 20 4.17 3.08 0.74 949 4.00 2.96 0.74 1006 3.88 2.87 0.74 1028 3.74 2.77 0.74 1074 28 22 4.34 2.69 0.62 983 4.18 2.59 0.62 1045 4.08 2.53 0.62 1074 3.91 2.42 0.62 1119 28 24 4.56 2.28 0.50 1028 4.39 2.19 0.50 1085 4.28 2.14 0.50 1119 4.15 2.07 0.50 1175 28 26 4.69 1.78 0.38 1085 4.56 1.73 0.38 1141 4.49 1.71 0.38 1175 4.35 1.65 0.38 1209 29 18 4.00 3.60 0.90 904 3.83 3.44 0.90 949 3.67 3.30 0.90 994 3.54 3.18 0.90 1040 29 20 4.17 3.25 0.78 949 4.00 3.12 0.78 1006 3.88 3.02 0.78 1028 3.74 2.92 0.78 1074 29 22 4.34 2.86 0.66 983 4.18 2.76 0.66 1045 4.08 2.69 0.66 1074 3.91 2.58 0.66 1119 29 24 4.56 2.46 0.54 1028 4.39 2.37 0.54 1085 4.28 2.31 0.54 1119 4.15 2.24 0.54 1175 29 26 4.69 1.97 0.42 1085 4.56 1.91 0.42 1141 4.49 1.88 0.42 1175 4.35 1.83 0.42 1209 30 18 4.00 3.76 0.94 904 3.83 3.60 0.94 949 3.67 3.45 0.94 994 3.54 3.32 0.94 1040 30 20 4.17 3.42 0.82 949 4.00 3.28 0.82 1006 3.88 3.18 0.82 1028 3.74 3.07 0.82 1074 30 22 4.34 3.03 0.70 983 4.18 2.93 0.70 1045 4.08 2.86 0.70 1074 3.91 2.74 0.70 1119 30 24 4.56 2.64 0.58 1028 4.39 2.54 0.58 1085 4.28 2.48 0.58 1119 4.15 2.41 0.58 1175 30 26 4.69 2.16 0.46 1085 4.56 2.10 0.46 1141 4.49 2.06 0.46 1175 4.35 2.00 0.46 1209 31 18 4.00 3.92 0.98 904 3.83 3.75 0.98 949 3.67 3.60 0.98 994 3.54 3.47 0.98 1040 31 20 4.17 3.58 0.86 949 4.00 3.44 0.86 1006 3.88 3.33 0.86 1028 3.74 3.22 0.86 1074 31 22 4.34 3.21 0.74 983 4.18 3.09 0.74 1045 4.08 3.02 0.74 1074 3.91 2.89 0.74 1119 31 24 4.56 2.82 0.62 1028 4.39 2.72 0.62 1085 4.28 2.66 0.62 1119 4.15 2.57 0.62 1175 31 26 4.69 2.35 0.50 1085 4.56 2.28 0.50 1141 4.49 2.24 0.50 1175 4.35 2.18 0.50 1209 32 18 4.00 4.00 1.00 904 3.83 3.83 1.00 949 3.67 3.67 1.00 994 3.54 3.54 1.00 1040 32 20 4.17 3.75 0.90 949 4.00 3.60 0.90 1006 3.88 3.49 0.90 1028 3.74 3.37 0.90 1074 32 22 4.34 3.38 0.78 983 4.18 3.26 0.78 1045 4.08 3.18 0.78 1074 3.91 3.05 0.78 1119 32 24 4.56 3.01 0.66 1028 4.39 2.89 0.66 1085 4.28 2.83 0.66 1119 4.15 2.74 0.66 1175 32 26 4.69 2.53 0.54 1085 4.56 2.46 0.54 1141 4.49 2.42 0.54 1175 4.35 2.35 0.54 1209
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 25 27 30
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OUTDOOR DB (°C)
21
Page 22
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-HC35VAB
CAPACITY: 3.4 kW SHF: 0.76 INPUT: 1130 W
INDOOR
DB (°C)
INDOOR
WB (°C)
21 18 3.33 1.93 0.58 1107 3.06 1.77 0.58 1175 2.82 1.64 0.58 1220 21 20 3.50 1.61 0.46 1153 3.26 1.50 0.46 1209 3.03 1.39 0.46 1277 22 18 3.33 2.07 0.62 1107 3.06 1.90 0.62 1175 2.82 1.75 0.62 1220 22 20 3.50 1.75 0.50 1153 3.26 1.63 0.50 1209 3.03 1.51 0.50 1277 22 22 3.71 1.41 0.38 1198 3.47 1.32 0.38 1266 3.23 1.23 0.38 1311 23 18 3.33 2.20 0.66 1107 3.06 2.02 0.66 1175 2.82 1.86 0.66 1220 23 20 3.50 1.89 0.54 1153 3.26 1.76 0.54 1209 3.03 1.63 0.54 1277 23 22 3.71 1.56 0.42 1198 3.47 1.46 0.42 1266 3.23 1.36 0.42 1311 24 18 3.33 2.33 0.70 1107 3.06 2.14 0.70 1175 2.82 1.98 0.70 1220 24 20 3.50 2.03 0.58 1153 3.26 1.89 0.58 1209 3.03 1.76 0.58 1277 24 22 3.71 1.70 0.46 1198 3.47 1.60 0.46 1266 3.23 1.49 0.46 1311 24 24 3.91 1.33 0.34 1243 3.67 1.25 0.34 1300 3.47 1.18 0.34 1356 25 18 3.33 2.47 0.74 1107 3.06 2.26 0.74 1175 2.82 2.09 0.74 1220 25 20 3.50 2.17 0.62 1153 3.26 2.02 0.62 1209 3.03 1.88 0.62 1277 25 22 3.71 1.85 0.50 1198 3.47 1.73 0.50 1266 3.23 1.62 0.50 1311 25 24 3.91 1.49 0.38 1243 3.67 1.40 0.38 1300 3.47 1.32 0.38 1356 26 18 3.33 2.60 0.78 1107 3.06 2.39 0.78 1175 2.82 2.20 0.78 1220 26 20 3.50 2.31 0.66 1153 3.26 2.15 0.66 1209 3.03 2.00 0.66 1277 26 22 3.71 2.00 0.54 1198 3.47 1.87 0.54 1266 3.23 1.74 0.54 1311 26 24 3.91 1.64 0.42 1243 3.67 1.54 0.42 1300 3.47 1.46 0.42 1356 26 26 4.11 1.23 0.30 1288 3.88 1.16 0.30 1345 3.64 1.09 0.30 1401 27 18 3.33 2.73 0.82 1107 3.06 2.51 0.82 1175 2.82 2.31 0.82 1220 27 20 3.50 2.45 0.70 1153 3.26 2.28 0.70 1209 3.03 2.12 0.70 1277 27 22 3.71 2.15 0.58 1198 3.47 2.01 0.58 1266 3.23 1.87 0.58 1311 27 24 3.91 1.80 0.46 1243 3.67 1.69 0.46 1300 3.47 1.60 0.46 1356 27 26 4.11 1.40 0.34 1288 3.88 1.32 0.34 1345 3.64 1.24 0.34 1401 28 18 3.33 2.87 0.86 1107 3.06 2.63 0.86 1175 2.82 2.43 0.86 1220 28 20 3.50 2.59 0.74 1153 3.26 2.42 0.74 1209 3.03 2.24 0.74 1277 28 22 3.71 2.30 0.62 1198 3.47 2.15 0.62 1266 3.23 2.00 0.62 1311 28 24 3.91 1.96 0.50 1243 3.67 1.84 0.50 1300 3.47 1.73 0.50 1356 28 26 4.11 1.56 0.38 1288 3.88 1.47 0.38 1345 3.64 1.38 0.38 1401 29 18 3.33 3.00 0.90 1107 3.06 2.75 0.90 1175 2.82 2.54 0.90 1220 29 20 3.50 2.73 0.78 1153 3.26 2.55 0.78 1209 3.03 2.36 0.78 1277 29 22 3.71 2.45 0.66 1198 3.47 2.29 0.66 1266 3.23 2.13 0.66 1311 29 24 3.91 2.11 0.54 1243 3.67 1.98 0.54 1300 3.47 1.87 0.54 1356 29 26 4.11 1.73 0.42 1288 3.88 1.63 0.42 1345 3.64 1.53 0.42 1401 30 18 3.33 3.13 0.94 1107 3.06 2.88 0.94 1175 2.82 2.65 0.94 1220 30 20 3.50 2.87 0.82 1153 3.26 2.68 0.82 1209 3.03 2.48 0.82 1277 30 22 3.71 2.59 0.70 1198 3.47 2.43 0.70 1266 3.23 2.26 0.70 1311 30 24 3.91 2.27 0.58 1243 3.67 2.13 0.58 1300 3.47 2.01 0.58 1356 30 26 4.11 1.89 0.46 1288 3.88 1.78 0.46 1345 3.64 1.67 0.46 1401 31 18 3.33 3.27 0.98 1107 3.06 3.00 0.98 1175 2.82 2.77 0.98 1220 31 20 3.50 3.01 0.86 1153 3.26 2.81 0.86 1209 3.03 2.60 0.86 1277 31 22 3.71 2.74 0.74 1198 3.47 2.57 0.74 1266 3.23 2.39 0.74 1311 31 24 3.91 2.42 0.62 1243 3.67 2.28 0.62 1300 3.47 2.15 0.62 1356 31 26 4.11 2.06 0.50 1288 3.88 1.94 0.50 1345 3.64 1.82 0.50 1401 32 18 3.33 3.33 1.00 1107 3.06 3.06 1.00 1175 2.82 2.82 1.00 1220 32 20 3.50 3.15 0.90 1153 3.26 2.94 0.90 1209 3.03 2.72 0.90 1277 32 22 3.71 2.89 0.78 1198 3.47 2.71 0.78 1266 3.23 2.52 0.78 1311 32 24 3.91 2.58 0.66 1243 3.67 2.42 0.66 1300 3.47 2.29 0.66 1356 32 26 4.11 2.22 0.54 1288 3.88 2.09 0.54 1345 3.64 1.96 0.54 1401
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
35 40 46
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OUTDOOR DB (°C)
22
Page 23
PERFORMANCE DATA HEAT operation at Rated frequency
MUZ-HC25VA
CAPACITY: 3.2 kW INPUT: 880 W
INDOOR
DB (°C)
15 2.02 572 2.43 686 2.85 774 3.26 836 3.68 889 4.06 915 4.48 933 21 1.92 616 2.30 730 2.72 810 3.10 871 3.52 915 3.90 942 4.30 977 26 1.73 660 2.14 774 2.53 854 2.94 915 3.36 959 3.74 986 4.16 1012
-10 -5 0 5 10 15 20
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
OUTDOOR WB (°C)
MUZ-HC35VA MUZ-HC35VAB
CAPACITY: 3.6 kW INPUT: 995 W
INDOOR
DB (°C)
15 2.27 647 2.74 776 3.20 876 3.67 945 4.14 1005 4.57 1035 5.04 1055 21 2.16 697 2.59 826 3.06 915 3.49 985 3.96 1035 4.39 1065 4.84 1104 26 1.94 746 2.41 876 2.84 965 3.31 1035 3.78 1085 4.21 1114 4.68 1144
-10 -5 0 5 10 15 20
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
NOTE Q : Total capacity (kW) INPUT : Total power input (W) DB: Dry-bulb temperature WB: Wet-bulb temperature
OUTDOOR WB (°C)
23
Page 24
9
ACTUATOR CONTROL
MUZ-HC25VA MUZ-HC35VA MUZ-HC35VAB
9-1. OUTDOOR FAN MOTOR CONTROL
The fan motor turns ON/OFF, interlocking with the compressor. [ON] The fan motor turns ON 5 seconds before the compressor starts up. [OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
5 seconds 15 seconds
ON
Compressor
OFF
ON
Outdoor fan motor
OFF
9-2. R.V. COIL CONTROL
Heating Cooling Dry NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
Compressor
R.V.coil
Outdoor fan motor
ON OFF OFF
ON OFF
ON OFF
ON OFF
<COOL>
<HEAT>
5 seconds
9-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR
Sensor Purpose
Discharge temperature thermistor Protection
Indoor coil temperature thermistor
Defrost thermistor
Fin temperature thermistor Protection
,
HC35VA-
E2
HC35VAB-
Cooling: Coil frost prevention
Heating: High pressure protection
Cooling: High pressure protection
Heating: Defrosting
E2
Compressor LEV
○○ ○ ○ ○○○ ○○○○○ ○○
5 seconds
Actuator
Outdoor fan
motor
R.V. coil
Indoor fan
motor
24
Page 25
10
SERVICE FUNCTIONS
MUZ-HC25VA MUZ-HC35VA MUZ-HC35VAB
10-1. CHANGE IN DEFROST SETTING
<JS> When the JS wire of the inverter P.C. board is cut/ soldered, the defrost finish temperature is changed. (Refer to
11-6-1.)
Jumper wire Defrost nish temperature (°C)
Soldered
(Initial setting)
JS
10-2. PRE-HEAT CONTROL SETTING
PRE-HEAT CONTROL
When moisture gets into the refrigerant cycle, it may interfere the start-up of the compressor at low outside tempera­ture. The pre-heat control prevents this interference. The pre-heat control turns ON when outside temperature is 20°C or below. When pre-heat control is turned ON, compressor is energized. (About 50 W)
<JK> When the JK wire of the inverter P.C. board is cut, pre-heat control is activated. (Refer to 11-6.1)
NOTE : When the inverter P.C. board is replaced, check the Jumper wires, and cut/solder them if necessary.
None
(Cut)
5
8
11
SERVICE FUNCTIONS
MUZ-HC25VA MUZ-HC35VA MUZ-HC35VAB
11-1. CAUTIONS ON TROUBLESHOOTING
1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for miswiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, and then after confirming the horizontal vane is closed, turn OFF the breaker and/or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board.
3) When removing the electrical parts, be careful to the residual voltage of smoothing capacitor.
4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.
5) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
Lead wiring
Housing point
3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.
To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
2) Before servicing check that the connector and terminal are connected properly.
3) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and
the components for bursting and discoloration.
4) Refer to 11-2. and 11-3.
25
Page 26
11-2. FAILURE MODE RECALL FUNCTION
Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (11-3.) disappears, the memorized failure details can be recalled. This mode is very useful when the unit needs to be repaired for the abnormality which doesn't recur.
1. Flow chart of failure mode recall function for the indoor/outdoor unit
Operational procedure
The cause of abnormality cannot be found because the abnormality doesn't recur.
Setting up the failure mode recall function
Turn ON the power supply. <Preparation of the remote controller>
While pressing both OPERATION SELECT button and TOO COOL button on the
remote controller at the same time, press RESET button.
First, release RESET button.
And release the other two buttons after all LCD in operation display section of the
remote controller is displayed after 3 seconds.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1
1. Regardless of normal or abnormal condition, a short
Does the upper lamp of OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: Either indoor or outdoor unit is abnormal. Beep is
emitted at the same timing as the blinking of the upper lamp of OPERATION INDICATOR lamp. 2
Judgment of indoor/outdoor abnormality
Before blinking, does the upper lamp of OPERATION INDICA­TOR lamp stay ON for 3 seconds? Stays ON for 3 seconds (without beep): The outdoor unit is abnormal.
The indoor unit is abnormal. Check the blinking pattern, and confi rm the abnormal point with the indoor unit failure mode table. (Refer to indoor unit service manual.) Make sure to check at least two consecutive blinking cycles. 2
Yes (Blinks)
No
No (OFF)
Yes
Indoor unit is normal. But the outdoor unit might be abnormal because there are some abnor­malities that can't be recalled with this way. Confi rm if outdoor unit is abnormal according to the detailed outdoor unit failure mode recall function. (Refer to 11-2.2)
The outdoor unit is abnormal. Check the blinking pattern, and confi rm the abnormal point with the outdoor unit failure mode table. (Refer to 11-2.3) Make sure to check at least two consecutive blinking cycles.
beep is emitted once the signal is received.
3
Releasing the failure mode recall function
Deleting the memorized abnormal condition
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller.
Repair the defective parts.
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" mentioned above.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed)
with the remote controller headed towards the indoor unit. Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
NOTE: 1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
2. Blinking pattern when the indoor unit is abnormal:
2.5-second OFF
Blinking at 0.5­second interval
2.5-second OFF
Blinking at 0.5­second interval
ON
OFF
Repeated cycle Repeated cycle
Beeps
3.Blinking pattern when the outdoor unit is abnormal:
2.5-second OFF 3-second ON
Blinking at 0.5­second interval
Beeps
Repeated cycle
2.5-second OFF 3-second ON
ON
OFF
No beep Beeps
Repeated cycle
No beep Beeps
Repeated cycle
Beeps
Blinking at 0.5-
second interval
Repeated cycle
26
Page 27
2. Flow chart of the detailed outdoor unit failure mode recall function
Operational procedure
The outdoor unit might be abnormal. Confi rm if outdoor unit is abnormal according to the following procedures.
Confi rm that the remote controller is in the failure mode recall function.
With the remote controller headed towards the indoor unit, press TOO COOL or TOO WARM button to adjust the set temperature to 25°C.
1
1. Regardless of normal or abnormal condition, 2 short beeps are emitted as the signal is received.
Does the upper lamp of OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: The outdoor unit is abnormal. Beep is emitted
at the same timing as the blinking of the upper lamp of OPERATION INDICATOR lamp. 2
Yes (Blinks
)
No (OFF)
The outdoor unit is abnormal. Check the blinking pattern, and confi rm the abnormal point with the out- door unit failure mode table (11-2.3.). Make sure to check at least two consecutive blinking cycles.
2
The outdoor unit is normal.
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller.
Release the failure mode recall function accord­ing to the left mentioned procedure.
Repair the defective parts.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" (11-2.1.).
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with
the remote controller headed towards the indoor unit.
Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.
Release the failure mode recall function according to "Releasing the failure mode recall function" men-
tioned above.
NOTE: 1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
2.Blinking pattern when outdoor unit is abnormal:
2.5-second OFF 3-second ON
ON
OFF
No beep
Repeated cycle
Blinking at 0.5­second interval
Beeps
2.5-second OFF 3-second ON
No beep Beeps
Repeated cycle
27
Blinking at 0.5­second interval
Repeated cycle
Page 28
3. Outdoor unit failure mode table
The upper
lamp of
OPERATION
INDICTOR
lamp (Indoor
unit)
OFF None (Normal)
2-time fl ash
2.5 seconds OFF
3-time fl ash
2.5 seconds OFF
4-time fl ash
2.5 seconds OFF
5-time fl ash
2.5 seconds OFF
6-time fl ash
2.5 seconds OFF
7-time fl ash
2.5 seconds OFF
9-time fl ash
2.5 seconds OFF
10-time fl ash
2.5 seconds OFF
11-time fl ash
2.5 seconds OFF
12-time fl ash
2.5 seconds OFF
14-time fl ash
2.5 seconds OFF
Abnormal point
(Failure mode / protection)
Outdoor power system
Discharge temperature thermistor
Defrost thermistor
Fin temperature thermistor 3-time fl ash 2.5
P.C. board temperature thermistor
Overcurrent 11-time fl ash 2.5
Compressor synchronous abnormality (Compressor start-up failure protection)
Discharge temperature
High pressure
Fin temperature/ P.C. board temperature
Nonvolatile memory data 5-time fl ash 2.5
Discharge temperature
DC voltage 8-time fl ash 2.5
Each phase current of compressor
Overcurrent Compressor open-phase
Stop valve (Closed valve) 14-time fl ash 2.5
LED indication
(Outdoor P.C. board)
—— —
1-time fl ash every
2.5 seconds
seconds OFF 4-time fl ash 2.5
seconds OFF
seconds OFF
12-time fl ash 2.5 seconds OFF
7-time fl ash 2.5 seconds OFF
seconds OFF
seconds OFF 9-time fl ash 2.5
seconds OFF 10-time fl ash 2.5
seconds OFF
seconds OFF
Condition Correspondence
Over current protection stop is continuously performed 3 times within 1 minute after the compressor gets started.
Thermistor shorts or opens during compressor running.
12 A (HC25) / 14 A (HC35) current fl ow into intelligent power module.
Waveform of compressor current is distorted.
Temperature of discharge temperature thermistor exceeds 116°C, compressor stops. Compressor can restart if discharge temperature thermistor reads 100°C or less 3 minutes later.
Temperature of indoor coil thermistor exceeds 70°C in HEAT mode. When defrost thermistor exceeds 70°C in COOL mode.
Temperature of fi n temperature thermistor on the inverter P.C. board exceeds 82°C (HC25) / 83°C (HC35), or temperature of P.C. board temperature thermistor on the inverter P.C. board exceeds 81°C (HC25) / 85° C (HC35).
Nonvolatile memory data cannot be read properly.
Temperature of discharge temperature thermistor has been 50°C or less for 20 minutes.
DC voltage of inverter cannot be detected normally.
Each phase current of compressor cannot be detected normally.
12 A (HC25) / 14 A (HC35) current fl ow into intelligent power module (IPM). When the open-phase operation of compressor is detected. When the interphase short out occurs in the output of the intelligent power module (IPM). When the compressor winding shorts out.
Closed valve is detected by compressor current.
• Reconnect connectors.
• Refer to 11-5. ”How to check inverter/ compressor”.
• Check stop valve.
• Refer to 11-5. ”Check of outdoor thermistors” . Defective outdoor thermistors can be identifi ed by checking the blinking pattern of LED.
• Reconnect compressor connector.
• Refer to 11-5. ”How to check inverter/ compressor”.
• Check stop valve.
• Reconnect compressor connector.
• Refer to 11-5. ”How to check inverter/ compressor”.
• Check refrigerant circuit and refrigerant amount.
• Refer to 11-5. ”Check of LEV”.
• Check refrigerant circuit and refrigerant amount.
• Check stop valve.
• Check around outdoor unit.
• Check outdoor unit air passage.
• Refer to 11-5. ”Check of outdoor fan motor”.
• Replace the inverter P.C. board.
• Refer to 11-5. ”Check of LEV”.
• Check refrigerant circuit and refrigerant amount.
• Refer to 11-5. ”How to check inverter/ compressor”.
• Reconnect compressor connector.
• Refer to 11-5. ”How to check inverter/ compressor”.
• Check stop valve.
NOTE: Blinking patterns of this mode differ from the ones of Troubleshooting check table (11-3.).
Indoor/outdoor
unit failure
mode recall
function
Outdoor unit failure mode
recall function
○○
○○
○○
○○
28
Page 29
11-3. TROUBLESHOOTING CHECK TABLE
No. Symptom LED indication
Outdoor unit does not oper-
1
ate.
2
3
4
5
6
‘Outdoor unit stops and
7
restarts 3 min­utes later’ is repeated.
8
9
10
11
12
13
Outdoor unit
14
operates.
15
16
Outdoor unit
17
operates.
18
19
NOTE : 1. The location of LED is illustrated at the right fi gure. Refer to 11-6.1.
2. LED is lighted during normal operation.
The fl ashing frequency shows the number of times the LED blinks after every 2.5-second OFF. (Example) When the fl ashing frequency is “2”.
1-time fl ash every
2.5 seconds
6-time fl ash 2.5 seconds OFF
11-time fl ash 2.5 seconds OFF
14-time fl ash 2.5 seconds OFF
2-time fl ash 2.5 seconds OFF
3-time fl ash 2.5 seconds OFF
4-time fl ash 2.5 seconds OFF
5-time fl ash 2.5 seconds OFF
8-time fl ash 2.5 seconds OFF
12-time fl ash 2.5 seconds OFF
13-time fl ash 2.5 seconds OFF
1-time fl ash 2.5 seconds OFF
3-time fl ash 2.5 seconds OFF
4-time fl ash 2.5 seconds OFF
7-time fl ash 2.5 seconds OFF
8-time fl ash 2.5 seconds OFF
9-time fl ash 2.5 seconds OFF
Abnormal point /
Condition
Outdoor power sys­tem
Outdoor thermistors Discharge temperature thermistor, fi n temperature thermistor,
Outdoor control sys­tem
Serial signal The communication fails between the indoor and outdoor unit
Stop valve / Closed valve
Outdoor unit (Other abnormality)
Overcurrent protec­tion
Discharge tempera­ture overheat protec­tion
Fin temperature / P.C. board temperature thermistor overheat protection
High pressure protec­tion
Compressor synchro­nous abnormality
Each phase current of compressor
DC voltage DC voltage of inverter cannot be detected normally.
Frequency drop by current protection
Frequency drop by high pressure protec­tion
Frequency drop by defrosting in COOL mode
Frequency drop by discharge tempera­ture protection
Low discharge tem­perature protection
PAM protection PAM: Pulse Amplitude Modulation
Inverter check mode The connector of compressor is disconnected, inverter check
Over current protection stop is continuously performed 3 times within 1 minute after the compressor gets started, or failure of restart of compressor has repeated 24 times.
defrost thermistor, P.C. board temperature thermistor shorts or opens during compressor running.
Nonvolatile memory data cannot be read properly. (The upper lamp of OPERATION INDICATOR lamp of the indoor unit lights up or fl ashes 7-time.)
for 3 minutes. Closed valve is detected by compressor current. • Check stop valve.
Outdoor unit is defective. • Refer to 11-2.2. “Flow chart of the
12 A (HC25) / 14 A (HC35) current fl ows into intelligent power module.
When overcurrent protection occurs within 10 seconds after
compressor starts, compressor restarts after 15 seconds.
Temperature of discharge temperature thermistor exceeds 116° C, compressor stops. Compressor can restart if discharge tem­perature thermistor reads 100°C or less 3 minutes later.
Temperature of fi n temperature thermistor on the heat sink ex- ceeds 82°C (HC25) / 83°C (HC35) or temperature of P.C. board temperature thermistor on the inverter P.C.board exceeds 81°C (HC25) / 85°C (HC35).
Indoor coil thermistor exceeds 70°C in HEAT mode. When the defrost thermistor exceeds 70°C in COOL mode.
The waveform of compressor current is distorted. • Reconnect connector of compres-
Each phase current of compressor cannot be detected normally • Refer to 11-5. “How to check in-
Current from power outlet exceeds 5.2 A (HC25) / 6.1 A (HC35), compressor frequency lowers.
Temperature of indoor coil thermistor exceeds 55°C in HEAT mode, compressor frequency lowers.
Indoor coil thermistor reads 8°C or less in COOL mode, com­pressor frequency lowers.
Temperature of discharge temperature thermistor exceeds 111° C, compressor frequency lowers.
Temperature of discharge temperature thermistor has been 50° C or less for 20 minutes.
The overcurrent fl ows into IGBT (Insulated Gate Bipolar tran- sistor: TR821) or when the bus-bar voltage reaches 320 V or more, PAM stops and restarts.
mode starts.
Condition Correspondence
• Reconnect connector of compres­sor.
• Refer to 11-5. “How to check in­verter/compressor”.
• Check stop valve.
• Refer to 11-5. thermistors”.
• Replace inverter P.C. board.
• Refer to 11-5. “How to check mis­wiring and serial signal error.
detailed outdoor unit failure mode recall function”.
• Reconnect connector of compres­sor.
• Refer to 11-5. “How to check in­verter/compressor”.
• Check stop valve.
• Check refrigerant circuit and refrig­erant amount.
• Refer to 11-5.
• Check around outdoor unit.
• Check outdoor unit air passage.
• Refer to 11-5. fan motor”.
• Check refrigerant circuit and refrig­erant amount.
• Check stop valve.
sor.
• Refer to 11-5. verter/compressor”.
verter/compressor”.
The unit is normal, but check the fol-
lowing.
• Check if indoor fi lters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air cir­culation is short cycled.
• Check refrigerant circuit and refrig­erant amount.
• Refer to 11-5. ”Check of LEV”.
• Refer to 11-5. thermistors”.
• Refer to 11-5.
• Check refrigerant circuit and refrig­erant amount.
• This is not malfunction.
• PAM protection will be activated in the following cases;
1 Instantaneous power voltage drop
(Short time power failure)
2 When the power supply voltage is
high.
• Check if the connector of the com­pressor is correctly connected.
• Refer to 11-5. “How to check in­verter/compressor”.
“Check of outdoor
”Check of LEV”.
“Check of outdoor
“How to check in-
“Check of outdoor
”Check of LEV”.
Inverter P.C. board (Parts side)
Flashing
LED
ON
OFF
2.5-second OFF
0.5-second ON
2.5-second OFF
29
0.5-second ON
Page 30
11-4. TROUBLE CRITERION OF MAIN PARTS
MUZ-HC25VA MUZ-HC35VA MUZ-HC35VAB
Part name Check method and criterion Figure
Defrost thermistor (RT61)
Discharge temperature thermistor (RT62) Fin temperature thermistor (RT64)
Compressor (MC)
Outdoor fan motor (MF) INNER FUSE RA6V21-AB
+0
°C CUT OFF
152
-5
RA6V21-BB 126 ± 2: CUT OFF
R.V. coil (21S4)
Measure the resistance with a tester.
Refer to 11-6. “Test point diagram and voltage”, 1. “Inverter P.C. board”, the chart of thermistor.
Measure the resistance with a tester. Before measurement, hold the thermistor with your hands to warm it up.
Refer to 11-6. “Test point diagram and voltage”, 1. “Inverter P.C. board”, the chart of thermistor.
Measure the resistance between the terminals with a tester. (Part temperature -10 – 40°C)
Normal
U-V
MUZ-HC25 MUZ-HC35
U-W
V-W
1.65 – 2.03 Ω 1.49 – 1.84 Ω
Measure the resistance between the terminals with a tester. (Part temperature -10 – 40°C)
Color of lead wire
RA6V21-AB RA6V21-BB, BD
Normal
WHT – BLK 305 – 374 Ω 222 – 272 Ω
BLK – RED 247 – 304 Ω 245 – 300 Ω
Measure the resistance between the terminals with a tester. (Part temperature -10˚C – 40°C)
Normal
1.32 – 1.62 kΩ
WHT
FUSE
RED BLK
23
V
BLK
RED
W
U
WHT
1
Expansion valve coil (LEV)
HC35VA­HC35VAB-
E2
E2
Measure the resistance using a tester. (Part temperature: -10 – 40°C)
Color of lead wire Normal
WHT – RED
RED – ORN YLW – BRN
38 – 50 Ω
BRN – BLU
WHT
RED
ORN
YLW
LEV
BRN
BLU
30
Page 31
11-5. TROUBLESHOOTING FLOW
A How to check inverter/compressor
Disconnect the connector (CN61) between compressor and the intelligent power module (IPM).
Check the voltage between terminals.
Are the voltages balanced?
Yes
Check the compressor.
No
See 11-5. “Check of open phase”.
Replace the inverter P.C. board.
See 11-5. “Check of compressor”.
B Check of open phase
With the connector between the compressor and the intelligent power module disconnected, activate the inverter and check if
the inverter is normal by measuring the balance of voltage between the terminals.
Output voltage is 50 - 130 V. (The voltage may differ according to the tester.)
<< Operation method>>
Start cooling or heating operation by pressing EMERGENCY OPERATION switch on the indoor unit. (TEST RUN OPERA­TION : Refer to 8-3.)
<<Measurement point>>
At 3 points BLK (U)-WHT (V) BLK (U)-RED (W) WHT(V)-RED (W)
NOTE : 1. Output voltage varies according to power supply voltage.
2. Measure the voltage by analog type tester.
3. During this check, LED of the inverter P.C. board fl ashes 9 times. (Refer to 11-6.1.)
Measure AC voltage between the lead wires at 3 points.
31
Page 32
C Check of compressor
Refer to 11-5. “Check of compressor winding”. Is the compressor normal?
No
Replace the compressor.
Yes
Refer to 11-5. “Check of compressor operation time”. Does the compressor operate continuously?
No
Refer to 11-5. “Check of compressor start failure”.
Yes
OK.
D Check of compressor winding
Disconnect the connector (CN61) between the compressor and intelligent power module, and measure the resistance be-
tween the compressor terminals.
<<Measurement point>>
At 3 points BLK-WHT BLK-RED WHT-RED
<<Judgement>>
Refer to 11-4. 0 [Ω] ················Abnormal [short] Infinite [Ω] ·······Abnormal [open] NOTE : Be sure to zero the ohmmeter before measurement.
Measure the resistance between the lead wires at 3 points.
E Check of compressor operation time
Connect the compressor and activate the inverter. Then measure
the time until the inverter stops due to over current. <<Operation method>> Start heating or cooling operation by pressing EMERGENCY
OPERATION switch on the indoor unit. (TEST RUN OPERATION: Refer to 8-3.) <<Measurement>> Measure the time from the start of compressor to the stop of
compressor due to overcurrent.
<<Judgement>>
0 second
1 second
2 seconds
10 seconds
10 minutes
Compressor starts
Abnormal (IPM failure) (Compressor winding short)
Abnormal (Compressor lock out) (Starting defect)
Abnormal (Poor contact,) (Outdoor P.C. board defect) (Disconnected connector)
Abnormal (Refrigerant circuit defect) (Closed valve)
Normal
32
Page 33
F Check of compressor start failure
Confi rm that ~ is normal.
•Electrical circuit check . Contact of the compressor connector (Including CN61) . Output voltage of inverter P.C. board and balance of them (See 11-5. . Direct current voltage between DB61(+) and (-) on the inverter P.C. board . Voltage between outdoor terminal block S1-S2
)
Does the compressor run for 10 seconds or more after it starts?
Yes
Check the refrigerant circuit. Check the stop valve.
No
After the compressor is heated with a drier, does the compressor start?
1
No
Replace the compressor.
Yes
Compressor start failure. Activate pre-heat control. (Refer to 10-2. "PRE-HEAT CONTROL SETTING")
G Check of outdoor thermistors
Disconnect the connector of thermistor in the outdoor P.C. board (see below table), and measure the resistance of thermistor.
Is the thermistor normal? (Refer to 11-6.1.)
Yes
No
1 Heat the compressor with a drier for about 20 minutes. Do not recover refrigerant gas while heating.
Heating part
Replace the thermistor except RT64. When RT64 is abnormal, replace the inverter P.C. board.
Reconnect the connector of thermistor. Turn ON the power supply and press EMERGENCY OPERATION switch.
Does the unit operate for 10 minutes or more without showing thermistor abnormality?
No
Replace the inverter P.C. board.
Yes
OK. (Cause is poor contact.)
Thermistor Symbol Connector, Pin No. Board
Defrost RT61 Between CN641 pin1 and pin2
Fin temperature RT64 Between CN642 pin1 and pin2
Inverter P.C. boardDischarge temperature RT62 Between CN641 pin3 and pin4
33
Page 34
H Check of R.V. coil
First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 11-4. In case CN721 is not connected or R.V. coil is open, voltage is generated between the terminal pins of the connector
although any signal is not being transmitted to R.V. coil.
Check if CN721 is connected.
Unit operates COOL mode even if it is set to HEAT mode.
Disconnect connector (CN61) between the compressor and the intelligent power module. Turn ON the power supply and press EMERGENCY OPERATION switch twice (HEAT mode).
Is there 230 VAC between CN721 and
on the inverter P.C. board 3 minutes
after the power supply is turned ON?
Yes
Replace the 4-way valve.
Replace the inverter
No
P.C. board.
Unit operates HEAT mode even if it is set to COOL mode.
Disconnect connector (CN61) between the compressor and the intelligent power module. Turn ON the power supply and press EMERGENCY OPERATION switch once (COOL mode).
Is there 230 VAC between CN721 and
on the inverter P.C. board 3 minutes
after the power supply is turned ON?
No
Replace the inverter
Yes
P.C. board.
I Check of outdoor fan motor
Check the resistance of fan motor. (Refer to 11-4.)
Is the resistance of fan motor normal?
Disconnect the connector CN771 on the inverter P.C. board. Disconnect the connector (CN61) between compressor and power transistor module. Turn ON the power supply and press the EMERGENCY OPERATION switch.
Does the upper lamp of OPERATION INDICATOR lamp on the indoor unit light up?
Yes
Replace the 4-way valve.
No
Replace the outdoor fan motor.
After 3 minutes, is there voltage 230 VAC between CN771 and
on the inverter P.C.
board?
Replace the outdoor fan motor.
Yes
Replace the inverter P.C. board.
No
34
Page 35
J Check of power supply
Disconnect the connector (CN61) between compressor and intelligent power module. Turn ON power supply and press EMERGENCY OPERATION switch.
Does the upper lamp of OPERATION INDICATOR lamp on the indoor unit light up?
Yes
No
Rectify indoor/outdoor connecting wire.
Yes
Is there voltage 230 VAC between the indoor terminal block S1 and S2?
Replace the indoor electronic control P.C.
No
board.
Is there voltage 280 - 370 VDC between DB61 (+) and DB61 (–) on the inverter P.C. board? (Refer to 11-6.1.)
No
Check the electric parts in main circuit.
Yes
Dose LED on the inverter P.C. board light up or fl ash? (Refer to 11-6.1.)
Yes
If light up, OK. If fl ash, refer to 11-3.
Replace the inverter
No
P.C. board.
DB61
Inverter P.C. board (Solder side)
280 ~ 370 VDC
35
Page 36
K How to check miswiring and serial signal error
Turn OFF the power supply.
Is there rated voltage in the power supply?
Yes
Turn ON the power supply.
Is there rated voltage between outdoor terminal block S1 and S2?
Press EMERGENCY OPERATION switch once.
Does the upper lamp of OPERATION INDICA­TOR lamp light up? <Confi rmation of the power to the indoor unit>
Is serial signal error indicated 6 minutes later?
Turn OFF the power supply. Check once more if the indoor/outdoor
B
connecting wire is not miswiring. Short-circuit outdoor terminal block S2 and S3.
Turn ON the power supply.
Yes
Yes
Yes
A
1
No
No
Check the power supply.
Check the wiring.
No
Is there any miswiring, poor contact, or wire disconnection of the
No
indoor/outdoor connect­ing wire?
1. Miswiring may damage indoor P.C. board during the operation. Be sure to confi rm the wiring is correct before the opera- tion starts.
3. Be sure to check this within 3 minutes after turning ON. After 3 minutes, LED blinks 6 times. Even when the inverter P.C. board or the outdoor electronic control P.C. board is normal, LED blinks 6 times after 3 minutes.
No
Yes
Correct them.
A
Turn OFF inverter-controlled lighting
• equipment. Turn OFF the power supply and then
• turn ON again. Press EMERGENCY OPERATION
• switch.
Reinstall
• either the unit or the light each other
No
away. Attach a fi lter on remote control receiv­ing section of the indoor unit.
Is serial signal error indicated 6 minutes later?
Yes
B
Does the LED on the inverter P.C. board or the outdoor electronic control P.C. board repeat "3.6-second-OFF and 0.8-second­ON quick blinking"? 3
Turn OFF the power supply. Remove the short-circuit between out­door terminal block S2 and S3. Turn ON the power supply. Is there amplitude of 10 to 20 VDC between indoor terminal block S2 and S3? <Confi rmation of serial signal> Is there rated voltage between indoor terminal block S1 and S2? <Confi rmation of power voltage>
Is there 2 VDC or less between CN10A (+) and JPG (GND)(-) on the indoor electronic control P.C. board?
Replace the indoor power P.C. board and the indoor terminal P.C. board
Be sure to release the failure-mode recall function after checking.
Yes
Yes
Yes
Is there 2 VDC or less between CN10A (+) and JPG (GND)(-) on the indoor electronic control P.C. board?
No
No Yes No
No (Lighted or not lighted)
No
Replace the indoor elec­tronic control P.C. board.
Replace the inverter P.C. board or the outdoor electronic control P.C. board.
2
2. Be careful to the residual
Is there any error of the in­door/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
voltage of smoothing capacitor.
Yes
No
Is there 2 VDC or less between CN10A (+) and JPG (GND)(-) on the indoor electronic control P.C. board?
Replace the indoor/outdoor connecting wire.
Yes
36
Page 37
L Check of LEV (Expansion valve)
Turn ON the power supply. <Preparation of the remote controller>
While pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button. First, release RESET button.
And release the other two buttons after all LCD except
the set temperature in operation display section of the remote controller is displayed after 3 seconds.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1
Expansion valve operates in full-opening direction.
Do you hear the expansion valve "click, click·······"? Do you feel the expansion valve vibrate on touching it ?
No
Yes
OK
1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received.
Is LEV coil properly fi xed to the expansion valve?
Yes
Does the resistance of LEV coil have the characteristics? (Refer to 11-4.)
No
Replace the LEV coil.
NOTE : After check of LEV, do the undermentioned operations.
1. Turn OFF the power supply and turn ON it again.
2. Press RESET button on the remote controller.
No
Yes
Properly fi x the LEV coil to the expansion valve.
Measure each voltage between connector pins of CN724 on the inverter P.C. board.
1. Pin
2. Pin (-) — Pin (+)
3. Pin (-) — Pin (+)
4. Pin (-) — Pin (+) Is there about 3 ~ 5 VAC between each? NOTE: Measure the voltage by an analog
(-) — Pin (+)
tester.
Replace the expansion valve.
Yes
Replace the inverter P.C.
No
board.
37
Page 38
M Electromagnetic noise enters into TV sets or radios
Is the unit earthed?
Yes
Is the distance between the antennas and the indoor unit within 3 m, or is the distance between the antennas and the outdoor unit within 3 m?
No
Is the distance between the TV sets or radios and the indoor unit within 1 m, or is the distance between the TV sets or radios and the outdoor unit within 3 m?
No
Are the antennas damaged? Is the coaxial cable damaged? Is there any poor contact in the anten­na wiring?
No
Is the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas close?
No
No
Yes
Yes
Yes
Yes
Earth the unit.
Extend the distance between the antennas and the indoor unit, and/or the antennas and the outdoor unit.
Extend the distance between the TV sets and/or radios and the indoor unit, or the TV sets or radios and the outdoor unit.
Replace or repair the antenna. Replace or repair the coaxial cable.
Extend the distance between the indoor/outdoor connecting wire of the air conditioner and the wir­ing of the antennas.
Even if all of the above conditions are fulfi lled, the electromagnetic noise may enter, depending on the electric fi eld strength or the installation condition (combination of specifi c conditions such as antennas or wiring). Check the following before asking for service.
1. Devices affected by the electromagnetic noise TV sets, radios (FM/AM broadcast, shortwave)
2. Channel, frequency, broadcast station affected by the electromagnetic noise
3. Channel, frequency, broadcast station unaffected by the electromagnetic noise
4. Layout of ; indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, earth wire, antennas, wiring from antennas, receiver
5. Electric fi eld intensity of the broadcast station affected by the electromagnetic noise
6. Presence or absence of amplifi er such as booster
7. Operation condition of air conditioner when the electromagnetic noise enters in
1) Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic noise.
2) Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button on the remote controller for power ON, and check for the electromagnetic noise.
3) After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the electromagnetic noise.
4) Press OPERATE/STOP (ON/OFF) button on the remote controller for power OFF, when the outdoor unit stops but the indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise.
38
Page 39
11-6. TEST POINT DIAGRAM AND VOLTAGE
1. Inverter P.C. board
MUZ-HC25VA MUZ-HC35VA MUZ-HC35VAB
Back side of unit
DB61 280 V ~ 370 V DC
(+)
(-)
Output to drive compressor (LDW, LDV, LDU)
LED monitor lamp
230V AC DB61
Smoothing capacitor (C62)
Fuse (F801)
Smoothing capacitor (C61)
Varistor (NR63)
Varistor (NR62)
Varistor (NR61)
Jumper wire for change
in defrost setting (JS)
Fuse (F701)
Jumper wire for pre-heat
control setting (JK)
Front side of unit
Defrost thermistor (RT61)
100
90
80
70
60
50
40
30
Resistance (kΩ)
20
10
0
-20 -10 0 10 20 30 40 Temperature (°C)
LEV (CN724)
Fin temperature
thermistor/RT64
(CN642)
Discharge temperature
thermistor/RT62
Defrost thermistor/RT61
(CN641)
Discharge temperature thermistor (RT62)
700
600
500
400
300
200
Resistance (kΩ)
100
0
0 102030405060708090100110120
Temperature (°C)
(CN641)
R.V.coil (CN721)
Output to drive outdoor fan motor (CN771)
Fin temperature thermistor (RT64)
200
180
160
140
120
100
80
60
Resistance (kΩ)
40
20
0
0 1020304050607080
Temperature (°C)
39
Page 40
12
DISASSEMBLY INSTRUCTIONS
<"Terminal with locking mechanism" Detaching points>
The terminal which has the locking mechanism can be detached as shown below. There are two types (refer to (1) and (2)) of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching.
(1) Slide the sleeve and check if there is a locking lever or not.
Sleeve
Slide the sleeve. Pull the terminal while
Locking lever
pushing the locking lever.
(2) The terminal with this connector has the locking mechanism.
12-1. MUZ-HC25VA MUZ-HC35VA MUZ-HC35VAB
OPERATING PROCEDURE PHOTOS
1. Removing cabinet and panels
(1)
Remove the screw fixing the service panel. (Photo 2)
(2)
Pull down the service panel and remove it. (Photo 2)
(3) Disconnect the power supply and indoor/outdoor con-
necting wire.
(4)
Remove the screws fixing the top panel. (Photo 1) (5) Remove the top panel. (Photo 1) (6) Remove the screws fixing the cabinet. (Photo 1) (7) Remove the cabinet. (8) Remove the screws fixing the back panel. (9) Remove the back panel.
Photo 1
Hold the sleeve, and pull out the terminal slowly.
Connector
NOTE: Turn OFF power supply before disassembling.
Screws of the top panel
Screws of the top panel
Photo 2
Screw of the
service panel
Direction to remove
Hooks
Screws of the cabinet
Service
panel
40
Page 41
OPERATING PROCEDURE PHOTOS
2. Removing the inverter assembly, inverter P.C. board
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the earth wires (Photo 3), the lead wire to
the reactor and the following connectors;
<Inverter P.C. board> CN641 (Defrost thermistor and discharge temperature
thermistor) CN721 (4-way valve) CN771 (Fan motor)
(3) Disconnect the compressor connector (CN61). (4)
Remove the screws fixing the relay panel. (Photo 3)
(5) Remove the inverter assembly. (See Photo 4.) (6) Remove the inverter P.C. board from the inverter
assembly.
3. Removing R.V. coil
(1) Remove the cabinet and panels. (Refer to 1.) (2) Remove the R.V. coil. (Photo 5)
Photo 3
Screws of the relay panel
Screw of the earth wires
Photo 4 (Inverter assembly)
Inverter P.C. board
Heat sink
4. Removing the discharge temperature thermistor and
defrost thermistor
(1) Remove the cabinet and panels. (Refer to 1.) (2) Pull out the discharge temperature thermistor from its
holder. (Photo 6)
(3) Pull out the defrost thermistor from its holder. (Photo 5)
Photo 5
R.V. coil
Defrost thermistor
41
Page 42
OPERATING PROCEDURE PHOTOS
5. Removing outdoor fan motor
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the connectors for outdoor fan motor. (3) Remove the propeller nut. (Photo 7) (4) Remove the propeller. (Photo 7) (5)
Remove the screws fixing the fan motor. (Photo 7)
(6) Remove the fan motor.
6. Removing the compressor and 4-way valve
(1) Remove the cabinet and panels. (Refer to 1.) (2) Remove the inverter assembly. (Refer to 2.) (3) Recover gas from the refrigerant circuit.
NOTE : Recover gas from the pipes until the pres-
sure gauge shows 0 MPa (0 kg/cm2).
(4) Detach the welded part of the suction and the dis-
charge pipe connected with compressor. (5) Remove the nuts of compressor legs. (6) Remove the compressor. (7) Detach the welded part of pipes connected with 4-way
valve. (Photo 8)
Photo 6
Discharge temperature thermistor
Photo 7
Propeller
Photo 8
Welded parts of 4-way valve
42
Screws of the outdoor fan motor
Page 43
43
Page 44
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Copyright 2007 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD Distributed in Aug. 2008. No. OBH467 REVISED EDITION-B 6 Distributed in Mar. 2007. No. OBH467 REVISED EDITION-A 6 Distributed in Jan. 2007. No. OBH467 6 Made in Japan
New publication, effective Aug. 2008 Specifications subject to change without notice.
Loading...