NOTE: Test conditions are based on AS/NZS 3823.1.1.
Cooling: Indoor Dry-bulb temperature 27°C Wet-bulb temperature 19°C
Outdoor Dry-bulb temperature 35°C Wet-bulb temperature (24°C)
Heating: Indoor Dry-bulb temperature 20°C Wet-bulb temperature 15.5°C
Outdoor Dry-bulb temperature 7°C Wet-bulb temperature 6°C
Refrigerant piping length (one way): 5 m
1 Measured under rated operating frequency.
NOTE: Test conditions are based on AS/NZS 3823.1.1.
Cooling: Indoor Dry-bulb temperature 27°C Wet-bulb temperature 19°C
Outdoor Dry-bulb temperature 35°C Wet-bulb temperature (24°C)
Heating: Indoor Dry-bulb temperature 20°C Wet-bulb temperature 15.5°C
Outdoor Dry-bulb temperature 7°C Wet-bulb temperature 6°C
Refrigerant piping length (one way): 5 m
1 Measured under rated operating frequency.
7
Outdoor model MUZ-GE50VAMUZ-GE50VA2MUZ-GE50VAD
OBH532E
Power supply
Capacity
Rated frequency (Min.-Max.)
Breaker Capacity
Power input 1 (Total)
Running current 1
(Total)
Power factor 1 (Total)
Electrical data
Starting current 1 (Total)
Coeffi cient of performance
(COP) 1 (Total)
Model
Output
Compressor
Current 1
Refrigeration oil
(Model)
Model
Fan motor
Current 1
Dimensions W × H × D
Weight
Dehumidifi cationCooling
Cooling
Air fl ow 1
Heating
Sound level 1
Cooling
Special remarks
Fan speed
Heating
Fan speed regulator
Refrigerant fi lling capacity
(R410A)
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
High
Med.
Low
High
Med.
Low
Cooling
Heating
High
Med.
Low
High
Med.
Low
kW
A16
W
A
%
A7.4
W900
A
L0.45 (NEO22)
A
mm840 × 850 × 330
kg54
L/h1.81.6
m3/h
dB(A)
rpm
kg1.55
5.0 (1.4 - 5.4)4.8 (1.4 - 5.4)
1,6401,480
7.46.8
9694
3.053.24
6.696.09
Single phase, 230 V, 50 Hz
5.8 (1.4 - 7.2)
1,650
7.4
96
3.52
SNB130FGBHT
6.72
RC0J60-AA
0.32
0.32
–
2,940
1,740
–
2,940
2,142
54
56
–
780
480
–
780
580
2
NOTE: Test conditions are based on AS/NZS 3823.1.1.
Cooling: Indoor Dry-bulb temperature 27°C Wet-bulb temperature 19°C
Outdoor Dry-bulb temperature 35°C Wet-bulb temperature (24°C)
Heating: Indoor Dry-bulb temperature 20°C Wet-bulb temperature 15.5°C
Outdoor Dry-bulb temperature 7°C Wet-bulb temperature 6°C
Refrigerant piping length (one way): 5 m
1 Measured under rated operating frequency.
8
Outdoor model
OBH532E
MUZ-GE60VA
MUZ-GE60VAD
MUZ-GE71VA
MUZ-GE71VAD
MUZ-GE80VA MUZ-GE80VA2
MUZ-GE80VAD
Power supply
Capacity
Rated frequency (Min.-Max.)
Breaker Capacity
Power input 1 (Total)
Running current 1
(Total)
Power factor 1 (Total)
Electrical data
Starting current 1 (Total)
Coeffi cient of performance
(COP) 1 (Total)
Model
Output
Compressor
Current 1
Refrigeration oil
(Model)
Model
Fan motor
Current 1
Dimensions W × H × D
Weight
Dehumidifi cationCooling
Cooling
Air fl ow 1
Heating
Sound level 1
Cooling
Special remarks
Fan speed
Heating
Fan speed regulator
Refrigerant fi lling capacity
(R410A)
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
High
Med.
Low
High
Med.
Low
Cooling
Heating
High
Med.
Low
High
Med.
Low
kW
A20
W
A
%
A7.89.511.311.2
W9001,200
A
L0.35 (FV50S)0.4 (FV50S)
A
mm840 × 880 × 330
kg5053
L/h1.92.22.92.7
m3/h
dB(A)
rpm
kg1.551.90
6.0 (1.5 - 7.5)7.1 (2.4- 8.7)
6.8 (2.0 - 9.3)8.1 (2.2 - 9.9)9.0 (2.2 - 11.1)
1,7602,1302,5602,460
1,7702,1102,5402,550
7.89.411.310.8
7.89.511.2
98999899
989799
3.403.413.333.123.17
3.843.833.843.543.53
SNB130FGBMTSNB172FEKMT
6.626.448.028.069.899.399.43
6.376.348.138.179.839.87
0.840.930.830.86
0.930.82
3,4923,426
3,0663,006
1,6921,512
2,9522,892
2,9522,892
2,2262,280
480450
620650
Single phase, 230 V, 50 Hz
RC0J60-BC
55
55
950
840
810
810
3
NOTE: Test conditions are based on AS/NZS 3823.1.1.
Cooling: Indoor Dry-bulb temperature 27°C Wet-bulb temperature 19°C
Outdoor Dry-bulb temperature 35°C Wet-bulb temperature (24°C)
Heating: Indoor Dry-bulb temperature 20°C Wet-bulb temperature 15.5°C
Outdoor Dry-bulb temperature 7°C Wet-bulb temperature 6°C
Refrigerant piping length (one way): 5 m
1 Measured under rated operating frequency.
8.0 (2.4 - 9.2)
7.8 (2.4 - 9.2)
9
Specifi cations and rated conditions of main electric parts
OBH532E
Item
Smoothing
capacitor
Diode module
Model
(C62, C63)
(DB61)15 A 600 V25 A 600 V
(DB65)25 A 600 V
(
C61
MUZ-
GE25VA
)
MUZ-
GE25VAD
MUZ-
GE33VA
MUZ-
GE35VA
MUZ-
GE35VA2
MUZ-
GE35VAD
MUZ-
GE42VA
600 μF/620 μF 420 V—
—600 μF/620 μF 420 V
MUZ-
GE42VAD
MUZ-
GE50VA
MUZ-
GE50VA2
MUZ-
GE50VAD
(F62)—
Fuse
Intelligent
(F701, F801, F901)
(F601,F880, F901)
(F61)T20AL250V
T3.15AL250V
—
(IC932)—
power module /
Power module
1.
Expansion valve
coil
Reactor
Power factor
controller
Current-limiting
PTC thermistor
(PTC64, PTC65)33 Ω
(IPM)15 A 600 V20 A 600 V
(LEV)12 VDC
(L61)18 mH23 mH
(L)—
(PFC)—
Terminal block(TB1, TB2)3 P
(X63)3 A 250 V
Relay
(X64)20 A 250 V
(X601)—
(X602)—
R.V.coil(21S4)220 - 240 VAC
IGBT(TR821)30 A 600 V
1.
Intelligent power module: MUZ-GE25VA -
Power module: Other models
A1
, MUZ-GE35/50VA
Specifi cations and rated conditions of main electric parts
Item
Smoothing
capacitor
Diode module
Fuse
Intelligent power
module
(C61, C62, C63)
(
CB1, CB2, CB3
)
(DB61)—
(DB65)—
(F62)
(F61)—
(F701, F801, F901)
(F601,F880, F901)
(IC932)5A 600 V
(IPM) 20 A 600 V—20 A 600 V—20 A 600 V—
MUZ-GE60VA
T2.0AL250V
MUZ-GE60VAD
—
MUZ-GE71VA
T2.0AL250V
MUZ-GE71VAD
—
560 μF 450 V
—
—
T3.15AL250V
MUZ-GE80VA MUZ-GE80VA2
T2.0AL250V
MUZ-GE80VAD
—
Model
IGBT module(IC700)—20 A 600 V—20 A 600 V—20 A 600 V
Expansion valve
coil
Reactor
Power factor
controller
Current-limiting
PTC thermistor
(PTC64, PTC65)33 Ω
(LEV)12 VDC
(L61)—
(L)340 μH
(PFC) 20 A 600 V—20 A 600 V—20 A 600 V—
(IC820)—20 A 600 V—20 A 600 V—20 A 600 V
Terminal block(TB1, TB2)3 P
(X63)—
Relay
(X64)20 A 250 V
(X601)3 A 250V
(X602)3 A 250V
R.V.coil(21S4)220 - 240 VAC
IGBT(TR821)—
10
4
OBH532E
NOISE CRITERIA CURVES
MUZ-GE25VA
MUZ-GE25VAD
90
80
70
60
50
40
30
20
OCTAVE BAND SOUND PRESSURE LEVEL, 0 dB = 20μPa
10
63125250500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
FUNCTION
COOLING
HEATING
SPL(dB(A))LINE
46
48
NC-10
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
MUZ-GE33VA
MUZ-GE35VA
90
80
70
60
50
40
30
20
OCTAVE BAND SOUND PRESSURE LEVEL, 0 dB = 20μPa
10
63125250500 1000 2000 4000 8000
FUNCTION
COOLING
HEATING
BAND CENTER FREQUENCIES, Hz
SPL(dB(A))
47
48
NC-10
LINE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
MUZ-GE35VA2
MUZ-GE35VAD
90
80
70
60
50
40
30
20
OCTAVE BAND SOUND PRESSURE LEVEL, 0 dB = 20μPa
10
63125250500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
FUNCTION
COOLING
HEATING
SPL(dB(A))
NC-10
MUZ-GE42VA
LINE
47
48
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
MUZ-GE42VAD
90
80
70
60
50
40
30
20
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB = 20 μPa
10
63125250500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
FUNCTION
COOLING
HEATING
SPL(dB(A))LINE
50
51
NC-10
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
11
MUZ-GE50VA
OBH532E
MUZ-GE50VA2
MUZ-GE50VAD
FUNCTION
COOLING
HEATING
SPL(dB(A))LINE
54
56
MUZ-GE60VA
MUZ-GE60VAD
FUNCTION
COOLING
HEATING
SPL(dB(A))LINE
55
55
90
80
70
60
50
40
30
20
OCTAVE BAND SOUND PRESSURE LEVEL, 0 dB = 20μPa
10
63125250500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
MUZ-GE71VA
MUZ-GE71VAD
FUNCTION
COOLING
HEATING
NC-10
SPL(dB(A))LINE
55
55
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
90
80
70
60
50
40
30
20
OCTAVE BAND SOUND PRESSURE LEVEL, 0 dB = 20μPa
10
63125250500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
MUZ-GE80VA
MUZ-GE80VA2
MUZ-GE80VAD
FUNCTION
COOLING
HEATING
NC-10
SPL(dB(A))LINE
55
55
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
90
80
70
60
50
40
30
20
OCTAVE BAND SOUND PRESSURE LEVEL, 0 dB = 20μPa
NC-10
10
63125250500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
90
80
70
60
50
40
30
20
OCTAVE BAND SOUND PRESSURE LEVEL, 0 dB = 20μPa
10
63125250500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
40
30
OCTAVE BAND SOUND
20
10
6312525
NC-10
BAND
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
Test conditions
Cooling: Dry-bulb temperature 35°C Wet-bulb temperature (24°C)
Heating: Dry-bulb temperature 7°C Wet-bulb temperature 6°C
Calculation: X g = 55 g/m × (Refrigerant piping length (m) – 10)
NOTE: Refrigerant piping exceeding 7 m (MUZ-GE25/33/35/42/50) or 10 m (MUZ-GE60/71/80) requires additional
refrigerant charge according to the calculation.
The standard specifications apply only to the operation of the air conditioner under normal conditions. Since operating conditions vary according to the areas where these units are installed, the following information has been provided to clarify the
operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198 ~ 264 V, 50 Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature:°C [WB]
(2) Indoor outlet air wet-bulb temperature:°C [WB]
(3) Outdoor intake air dry-bulb temperature:°C [DB]
(4) Total input:W
(5) Indoor intake air dry-bulb temperature:°C [DB]
(7) Total input:W
Indoor air wet and dry bulb temperature difference on the left side of the following chart shows the difference between the
indoor intake air wet and dry bulb temperature and the indoor outlet air wet and dry bulb temperature for your reference at
service.
}
}
Cooling
Heating(6) Outdoor intake air wet-bulb temperature:°C [WB]
How to measure the indoor air wet and dry bulb temperature difference
1.
Attach at least 2 sets of wet and dry bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet
and dry bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.
2. Attach at least 2 sets of wet and dry bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once (twice) to start the EMERGENCY COOL (HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
INDOOR UNITOUTDOOR UNIT
Wet and dry bulb
thermometers
FRONT VIEW
8-1. CAPACITY AND INPUT CURVES
10.2
9.4
8.6
7.9
7.1
6.4
5.7
9.7
9.0
8.2
7.5
6.8
6.1
5.4
9.3
8.6
7.9
7.2
6.5
5.8
5.2
6.6
7.8
8.4
6.1
7.2
7.7
5.6
6.6
7.1
5.1
6.0
6.5
4.6
5.5
4.9
4.4
5.9
5.3
4.7
difference (°C)
4.2
3.7
Indoor air Wet-bulb temperature
10.4
9.5
8.7
8.0
7.2
6.5
5.7
9.0
8.3
7.6
6.9
6.3
5.6
5.0
10.4
9.5
8.7
8.0
7.2
6.5
5.7
10.1
9.3
8.5
7.7
7.0
6.3
5.6
Wet and dry bulb
thermometers
BACK VIEW
1.5
Cooling capacity (
1.4
1.3
1.2
1.1
1.0
Capacity correction factors
0.9
-10-5 0 5 1015202530354045
Outdoor intake air Dry-bulb temperature(°C)
at Rated frequency)
Indoor intake air Wet-bulb
temperature( )
26
24
22
20
18
MUZ-GE33VA
MUZ-GE35VA
MUZ-GE35VA2
MUZ-GE25VA
MUZ-GE25VAD
MUZ-GE35VAD
MUZ-GE42VA
MUZ-GE42VAD
MUZ-GE50VA
MUZ-GE50VA2
MUZ-GE50VAD
MUZ-GE60VA
MUZ-GE60VAD
MUZ-GE80VA
MUZ-GE80VA2
MUZ-GE71VA
MUZ-GE71VAD
MUZ-GE80VAD
31
7.1
OBH532E
6.6
5.6
6.0
5.1
5.5
4.6
4.9
4.2
difference (°C)
4.4
3.7
3.9
3.3
Indoor air Wet-bulb temperature
MUZ-GE25VA
MUZ-GE25VAD
MUZ-GE33VA
18.2
16.8
15.4
14.0
12.6
11.2
9.8
8.4
difference (°C)
7.0
5.6
Indoor air Dry-bulb temperature
22.7
21.0
19.2
17.5
15.7
14.0
12.2
10.5
8.7
7.0
6.5
5.9
5.3
4.7
4.1
MUZ-GE35VA
MUZ-GE35VA2
MUZ-GE35VAD
8.7
8.0
7.2
6.5
5.7
5.0
MUZ-GE42VA
27.0
24.9
22.8
20.7
18.7
16.6
14.5
12.4
10.4
8.3
MUZ-GE42VAD
8.6
7.9
7.1
6.4
5.7
5.0
MUZ-GE50VA
26.2
24.1
22.1
20.1
18.1
16.1
14.1
12.1
10.1
8.0
8.2
7.5
6.8
6.1
5.4
4.8
MUZ-GE50VA2
MUZ-GE50VAD
7.9
7.2
6.5
5.8
5.2
4.6
MUZ-GE60VA
20.0
18.5
16.9
15.4
13.9
12.3
10.8
9.2
7.7
6.2
MUZ-GE60VAD
7.6
6.9
6.3
5.6
5.0
4.4
MUZ-GE71VA
23.8
21.9
20.1
18.3
16.4
14.6
12.8
11.0
MUZ-GE71VAD
9.1
7.3
8.7
8.0
7.2
6.5
5.7
5.0
Total input (Cooling :
8.5
7.7
7.0
6.3
5.6
4.9
MUZ-GE80VA
1.3
1.2
1.1
1.0
0.9
Input correction factors
0.8
-10-5 0 5 1015202530354045
MUZ-GE80VA2
MUZ-GE80VAD
Outdoor intake air Dry-bulb temperature (°C)
Heating capacity (
26.4
24.4
22.3
20.3
18.3
16.2
14.2
12.2
10.2
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
0.5
Capacity correction factor
8.1
0.4
-20-15-10-5051015
Indoor intake air Dry-bulb temperature ( )
Outdoor intake air Wet-bulb temperature (°C)
at Rated frequency
Indoor intake air Wet-bulb
temperature( )
at Rated frequency)
)
22
26
24
20
18
15
20
26
MUZ-GE50VA
MUZ-GE50VA2
26.2
24.1
22.1
20.1
18.1
16.1
14.1
12.1
10.1
8.0
MUZ-GE50VA
MUZ-GE50VA2
MUZ-GE50VAD
MUZ-GE50VAD
20.0
18.5
16.9
15.4
13.9
12.3
10.8
9.2
7.7
6.2
MUZ-GE60VA
MUZ-GE80VA
MUZ-GE80VA2
MUZ-GE71VA
MUZ-GE60VAD
MUZ-GE60VAD
23.8
21.9
20.1
18.3
16.4
14.6
12.8
11.0
9.1
7.3
MUZ-GE71VAD
MUZ-GE71VA
MUZ-GE71VAD
MUZ-GE60VA
MUZ-GE80VAD
26.4
24.4
22.3
20.3
18.3
16.2
14.2
12.2
10.2
MUZ-GE80VA
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
Input correction factor
0.5
8.1
0.4
-20-15-10-5051015
MUZ-GE80VA2
MUZ-GE80VAD
Total input (Heating :
Indoor intake air Dry-bulb temperature ( )
Outdoor intake air Wet-bulb temperature (°C)
at Rated frequency
)
MUZ-GE33VA
MUZ-GE35VA
MUZ-GE35VA2
MUZ-GE35VAD
MUZ-GE25VA
MUZ-GE25VAD
18.2
22.7
16.8
21.0
15.4
19.2
14.0
17.5
12.6
15.7
11.2
14.0
9.8
12.2
8.4
7.0
5.6
10.5
8.7
7.0
MUZ-GE25VA
MUZ-GE25VAD
MUZ-GE33VA
difference (°C)
Indoor air Dry-bulb temperature
MUZ-GE42VA
27.0
24.9
22.8
20.7
18.7
16.6
14.5
12.4
10.4
8.3
MUZ-GE42VA
MUZ-GE35VA
MUZ-GE35VA2
MUZ-GE35VAD
MUZ-GE42VAD
MUZ-GE42VAD
NOTE: The above broken lines are for the heating operation without any frost and defrost operation.
26
20
15
32
8-2. CAPACITY AND INPUT CORRECTION BY OPERATIONAL FREQUENCY OF COMPRESSOR
OBH532E
MUZ-GE25VA MUZ-GE25VAD
Correction of Cooling capacity
1.5
Correction of Cooling input
3.0
Correction of Heating capacity
1.5
Corr ect ion of Heating input
2.0
1.0
0.5
Capacity cor rection f actor s
0.0
050100
The operational frequency
of compressor (Hz)
MUZ-GE33VA
Correction o f Cooling capa city
1.5
1.0
0.5
Capacity cor rection f actor s
0.0
050100
The operational frequency
of compressor (Hz)
MUZ-GE35VA
Correction o f Cooling capa city
1.5
1.0
0.5
Capacity cor rection f actor s
0.0
050100
The operational frequency
of compressor (Hz)
MUZ-GE35VA2 MUZ-GE35VAD
Correction of Cooling capacity
1.5
Input correction factors
2.0
1.0
0.0
050100
The operational frequency
of compressor (Hz)
Correction of C ooling input
2.0
1.5
1.0
0.5
Input cor rection f actor s
0.0
050100
The operational frequency
of compressor (Hz)
Correction of C ooling input
2.0
1.5
1.0
0.5
Input correction factors
0.0
050100
The operational frequency
of compressor (Hz)
Correction of Cooling input
2.0
1.0
0.5
Capacity correction factors
0.0
050100150
The operational frequency
of compressor (Hz)
Correction of Heating capacity
1.5
1.0
0.5
Capacity correction factors
0.0
050100
The operational frequency
of compressor (Hz)
Correction of Heating capacity
1.5
1.0
0.5
Capacity cor rection fac tors
0.0
050100
The operational frequency
of compressor (Hz)
Correction of Heating capacity
1.5
1.5
1.0
0.5
Input correction factors
0.0
050100150
The operational frequency
of compressor (Hz)
Correction of Heating input
2.0
1.5
1.0
0.5
Input correction factors
0.0
050100
The operational frequency
of compressor (Hz)
Correction of Heating input
2.0
1.5
1.0
0.5
Input correction factors
0.0
050100
The operational frequency
of compressor (Hz)
Correction of Heating input
2.0
1.0
0.5
Capacity correction factors
0.0
050100
The oper ationa l f requency
of compressor (Hz)
MUZ-GE42VA MUZ-GE42VAD
Correction of Cooling capacity
1.5
1.0
0.5
Capacity correction factors
0.0
050100
The oper ationa l f requency
of compressor (Hz)
1.5
1.0
0.5
Input correction factors
0.0
050100
The oper ationa l f requency
of compressor (Hz)
Correction of Cooling input
2.0
1.5
1.0
0.5
Input correction factors
0.0
050100
The oper ationa l f requency
of compressor (Hz)
1.0
0.5
Capacity correction factors
0.0
050100
The operational frequency
of compressor (Hz)
Correction of Heating capacity
1.5
1.0
0.5
Capacity correction factors
0.0
050100
The operational frequency
of compressor (Hz)
33
1.5
1.0
0.5
Capacity correction factors
0.0
050100
The operational frequency
of compressor (Hz)
Correction of Heating input
1.5
1.0
0.5
Capacity correction factors
0.0
050100
The operational frequency
of compressor (Hz)
MUZ-GE50VA
OBH532E
Correction of Cooling capacity
1.5
Correction of Cooling input
1.5
Correction of Heating capacity
1.5
Correction of Heating input
2.0
1.0
0.5
Capacity correction factors
0.0
050100
The operational frequency
of compressor (Hz)
MUZ-GE50VA2 MUZ-GE50VAD
Correction of Cooling capacity
1.5
1.0
0.5
Capacity correction factors
0.0
050100
The operational frequency
of compressor (Hz)
MUZ-GE60VA MUZ-GE60VAD
Correction of Cooling capacity
2.0
1.5
1.0
0.5
Input correction factors
0.0
050100
The operational frequency
of compressor (Hz)
Correction of Cooling input
2.0
1.5
1.0
0.5
Input correction factors
0.0
050100
The oper ationa l f requency
of compressor (Hz)
Correction of Cooling input
2.0
1.5
1.0
0.5
Capacity correction factors
0.0
1.5
1.0
0.5
Capacity correction factors
0.0
2.0
1.5
1.5
1.0
0.5
Capacity correction factors
050100
The operational frequency
of compressor (Hz)
Correction of Heating capacity
050100
The operational frequency
of compressor (Hz)
Correction of Heating capacity
0.0
050100
The operational frequency
of compressor (Hz)
Correction of Heating input
2.0
1.5
1.0
0.5
Capacity correction factors
0.0
050100
The operational frequency
of compressor (Hz)
Correction of Heating input
2.0
1.5
1.0
0.5
Capacity correction factors
0.0
050100150
The operational frequency
of compressor (Hz)
MUZ-GE71VA MUZ-GE71VAD
Correction of Cooling capacity
2.0
1.5
1.0
0.5
Capacity correction factors
0.0
050100150
The oper ationa l f requency
of compressor (Hz)
MUZ-GE80VA
Correction of Cooling capacity
2.0
1.5
1.0
1.0
0.5
Input correction factors
0.0
050100150
The oper ationa l f requency
of compressor (Hz)
Correction of Cooling input
2.0
1.5
1.0
0.5
Input correction factors
0.0
050100150
The operational frequency
of compressor (Hz)
Correction of Cooling input
2.0
1.5
1.0
1.0
0.5
Capacity correction factors
0.0
050100150
The oper ationa l f requency
of compressor (Hz)
Correction of Heating capacity
2.0
1.5
1.0
0.5
Capacity correction factors
0.0
050100150
The operational frequency
of compressor (Hz)
Correction of Heating capacity
2.0
1.5
1.0
1.0
0.5
Capacity correction factors
0.0
050100150
The operational frequency
of compressor (Hz)
Correction of Heating input
2.0
1.5
1.0
0.5
Capacity correction factors
0.0
050100150
The oper ationa l f requency
of compressor (Hz)
Correction of Heating input
2.0
1.5
1.0
0.5
Capacity correction factors
0.0
050100150
The oper ationa l f requency
of compressor (Hz)
0.5
Input correction factors
0.0
050100150
The operational frequency
of compressor (Hz)
0.5
Capacity correction factors
0.0
050100150
The operational frequency
of compressor (Hz)
34
0.5
Capacity correction factors
0.0
050100150
The oper ationa l f requency
of compressor (Hz)
MUZ-GE80VA2 MUZ-GE80VAD
OBH532E
Correction of Cooling capacity
2.0
2.0
Correction of Cooling input
Correction of Heating capacity
2.0
Correction of Heating input
2.0
1.5
1.0
0.5
Capacity correction factors
0.0
050100150
The oper ationa l f requency
of compressor (Hz)
1.5
1.0
0.5
Input correction factors
0.0
050100150
The oper ationa l f requency
of compressor (Hz)
1.5
1.0
0.5
Capacity correction factors
0.0
050100150
The operational frequency
of compressor (Hz)
1.5
1.0
0.5
Capacity correction factors
0.0
050100150
The oper ationa l f requency
of compressor (Hz)
8-3. TEST RUN OPERATION (How to operate fixed-frequency operation)
1. Press EMERGENCY OPERATION switch to start COOL or HEAT mode (COOL: Press once, HEAT: Press twice).
2. Test run operation starts and continues to operate for 30 minutes.
3.
Compressor operates at rated frequency in COOL mode or 58 Hz (MUZ-GE25/33/35/42/50/60)/74 Hz (MUZ-GE71/80) in HEAT mode.
4. Indoor fan operates at High speed.
5.
After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (operation frequency of compressor varies).
6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on
remote controller.
8-4. OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
COOL operation
Both indoor and outdoor unit are under the same temperature/
The fan motor turns ON/OFF, interlocking with the compressor.
[ON] The fan motor turns ON 5 seconds before the compressor starts up.
[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
5 seconds15 seconds
ON
Compressor
OFF
ON
Outdoor fan
motor
OFF
9-2. R.V. COIL CONTROL
Heating
Cooling
Dry
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
9-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR
Discharge temperature
thermistor
Indoor coil temperature
thermistor
Defrost thermistorHeating: Defrosting
Fin temperature thermistorProtection
Ambient temperature
thermistor
Outdoor heat exchanger temperature thermistor
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
Compressor
R.V.coil
Outdoor fan
motor
SensorPurpose
ON
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
Protection
Cooling: Coil frost prevention
Heating: High pressure protec-
10-1. CHANGE IN DEFROST SETTING
Changing defrost finish temperature
<JS> To change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P.C. board. (Refer to
11-6-1.)
Defrost fi nish temperature (°C)
MUZ-GE
Jumper wire
25VA33VA
Soldered (Initial setting)5101059101010
JS
MUZ-GE25/35/42/50VAD do not have this changing function. The defrost finish temperature is fixed to the temperatures
shown in the table below. The JS wire for these models is used for changing the demand response capability.
Defrost fi nish temperature (°C)
25VAD 35VAD 42VAD 50VAD
5105 9
None (Cut)813131018181818
MUZ-GE
35VA
35VA2
42VA
50VA
50VA2
60VA
60VAD
71VA
71VAD
80VA
80VA2
80VAD
10-2. PRE-HEAT CONTROL SETTING
PRE-HEAT CONTROL
MUZ-GE25/33/35/42/50
When moisture gets into the refrigerant cycle, it may interfere the start-up of the compressor at low outside temperature.
The pre-heat control prevents this interference. The pre-heat control turns ON when the discharge temperature thermistor is 20°C or below. When the pre-heat control turns ON, the compressor is energized. (About 50 W)
MUZ-GE60/71/80
Prolonged low load operation, in which the thermostat is OFF for a long time, at low outside temperature (0°C or less)
may cause the following troubles. To prevent those troubles, activate the pre-heat control.
1) If moisture gets into the refrigerant cycle and freezes, it may interfer the start-up of the compressor.
2) If liquid refrigerant collects in the compressor, a failure in the compressor may occur.
The pre-heat control turns ON when the compressor temperature is 20°C or below. When the pre-heat control turns ON,
the compressor is energized. (About 70 W)
Pre-heat control setting
<JK>
ON: To activate the pre-heat control, cut JK wire of the inverter P.C. board.
OFF: To deactivate the pre-heat control, solder JK wire of the inverter P.C. board.
(Refer to 11-6.1)
NOTE: When the inverter P.C. board is replaced, check the Jumper wires, and cut/solder them if necessary.
2) Check the indoor/outdoor connecting wire for miswiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, and after confirming the horizontal vane is closed, turn OFF the breaker and/or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic
control P.C. board.
3) When removing the electrical parts, be careful of the residual voltage of smoothing capacitor.
4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.
5) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
<Incorrect>
<Correct>
Lead wiring
3. Troubleshooting procedure
1) Check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.
To make sure, check how many times the OPERATION INDICATOR lamp is flashing on and off before starting serv-
ice work.
2) Before servicing, check that the connector and terminal are connected properly.
3) When the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
4) Refer to 11-2 and 11-3.
Housing point
65
11-2. FAILURE MODE RECALL FUNCTION
OBH532E
Outline of the function
This air conditioner can memorize the abnormal condition which has occurred once.
Even though LED indication listed on the troubleshooting check table (11-3.) disappears, the memorized failure details
can be recalled.
This mode is very useful when the unit needs to be repaired for the abnormality which does not recur.
1. Flow chart of failure mode recall function for the indoor/outdoor unit
MSZ-GE25/33/35/42/50VA
MSZ-GE35/50VA2
MSZ-GE60/71/80VA
MSZ-GE80VA2
MSZ-GE60/71/80VAD
MSZ-GE25/35/42/50VAD
Operational procedure
The cause of abnormality cannot be found because the abnormality does not recur.
Setting up the failure mode recall function
Turn ON the power supply.
<Preparation of the remote controller>
While pressing both OPERATION SELECT button and TOO COOL button (MSZ-
GE25/33/35/42/50)/TEMP button (MSZ-GE60/71/80) on the remote controller
at the same time, press RESET button.
First, release RESET button.
Hold down the other two buttons for another 3 seconds. Make sure that the indicators on the LCD screen shown in the right fi gure are all displayed. Then release
the buttons.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1
1. Regardless of normal or abnormal
condition, a short beep is emitted
once the signal is received.
Does the upper lamp of OPERATION INDICATOR lamp on the
indoor unit blink at the interval of 0.5 seconds?
Blinks: Either indoor or outdoor unit is abnormal. Beep is
emitted at the same timing as the blinking of The upper
lamp of OPERATION INDICATOR lamp. 2
Yes
Judgment of indoor/outdoor abnormality
Before blinking, does the upper lamp of OPERATION INDICATOR lamp stay ON for 3 seconds?
Stays ON for 3 seconds (without beep):
The outdoor unit is abnormal.
The indoor unit is abnormal.
Check the blinking pattern, and identify the abnormal point by referring to the
indoor unit failure mode table. (Refer to indoor unit service manual.)
Make sure to check at least two consecutive blinking cycles. 2
(Blinks)
No
No
(OFF)
Indoor unit is normal.
But the outdoor unit might be abnormal because there are
some abnormalities that can not be recalled with this way.
Confi rm if outdoor unit is abnormal according to the de-
tailed outdoor unit failure mode recall function.
(Refer to 11-2.2)
Yes
The outdoor unit is abnormal.
Check the blinking pattern, and identify the abnormal point by referring
to the outdoor unit failure mode table. (Refer to 11-2.3)
Make sure to check at least two consecutive blinking cycles.
3
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures.
Turn OFF the power supply and turn it ON again.
Press RESET button of the remote controller.
Repair the failure parts.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" mentioned above.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed)
with the remote controller headed towards the indoor unit.
Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.
Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
2. Blinking pattern when the indoor unit is abnormal:
2.5-second OFF
Blinking at 0.5second interval
2.5-second OFF
Blinking at 0.5second interval
ON
OFF
Repeated cycleRepeated cycle
Beeps
3.Blinking pattern when the outdoor unit is abnormal:
2.5-second OFF3-second ON
Blinking at 0.5second interval
Beeps
2.5-second OFF
Repeated cycle
3-second ON
ON
OFF
No beepBeeps
Repeated cycle
No beepBeeps
Repeated cycle
66
Beeps
Blinking at 0.5second interval
Repeated cycle
2. Flow chart of the detailed outdoor unit failure mode recall function
OBH532E
Operational procedure
The outdoor unit might be abnormal.
Check if outdoor unit is abnormal according to the following procedures.
Make sure that the remote controller is set to the failure mode recall function.
With the remote controller headed towards the indoor unit, press TOO
COOL or TOO WARM button (MSZ-GE25/33/35/42/50)/TEMP
button (MSZ-GE60/71/80) to adjust the set temperature to 25°C. 1
Does the upper lamp of OPERATION INDICATOR
lamp on the indoor unit blink at the interval of 0.5
seconds?
Blinks: The outdoor unit is abnormal. Beep is emitted
at the same timing as the blinking of the upper
lamp of OPERATION INDICATOR lamp. 2
The outdoor unit is abnormal.
Check the blinking pattern, and identify the abnormal point by referring to
the outdoor unit failure mode table (11-2.3.).
Make sure to check at least two consecutive blinking cycles.
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures.
Turn OFF the power supply and turn it ON again.
Press RESET button of the remote controller.
Repair the failure parts.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" (11-2.1.).
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with
the remote controller headed towards the indoor unit.
Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.
Release the failure mode recall function according to "Releasing the failure mode recall function" men-
tioned above.
NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
Yes
(Blinks
)
or
No
(OFF)
2
1. Regardless of normal or abnormal condition, 2 short
beeps are emitted as the signal is received.
The outdoor unit is normal.
Release the failure mode recall function according to the left mentioned procedure.
2.Blinking pattern when outdoor unit is abnormal:
2.5-second OFF3-second ON
ON
OFF
No beep
Repeated cycle
Blinking at 0.5second interval
Beeps
2.5-second OFF3-second ON
No beepBeeps
Repeated cycle
67
Blinking at 0.5-
second interval
Repeated cycle
3. Outdoor unit failure mode table
OBH532E
The upper
lamp of
OPERATION
INDICATOR
lamp
(Indoor unit)
OFF None (Normal) —————
1-time fl ash
Any signals from the inverter P.C.
board cannot be received normally for
3 minutes.
Although the inverter P.C. board sends
signal "0", signal "1" has been received
30 consecutive times.
Overcurrent protection cut-out operates 3 consecutive times within 1
minute after the compressor gets
started.
Thermistor shorts or opens during
compressor running.
Large current fl ows into the intelligent
power module (IPM)/ IGBT module
(IC700)/ power module (IPM). 1.
Waveform of compressor current is
distorted.
Temperature of discharge temperature
thermistor exceeds 116°C, compressor
stops.
Compressor can restart if discharge
temperature thermistor reads 100°C or
less 3 minutes later.
Temperature of indoor coil thermistor
exceeds 70°C in HEAT mode.
Temperature of outdoor heat
exchanger temperature thermistor
exceeds 70°C in COOL mode.
Temperature of fi n temperature
thermistor on the inverter P.C. board
exceeds 75 ~ 80°C, or temperature of
P.C. board temperature thermistor on
the inverter P.C. board exceeds 70 ~
75°C.
Outdoor fan has stopped 3 times in a
row within 30 seconds after outdoor
fan start-up.
Nonvolatile memory data cannot be
read properly.
The interphase short circuit occurs
in the output of the intelligent power
module (IPM)/ IGBT module (IC700)/
power module (IPM).
The compressor winding shorts circuit.
1.
•Refer to 11-5. How
to check miswiring and
serial signal error.
•Refer to 11-5. How
to check miswiring and
serial signal error.
Reconnect
•
connectors.
Refer to 11-5. "How
•
to check inverter/
compressor".
Check the stop valve.
•
Refer to 11-5.
•
"Check of outdoor
thermistors".
Defective outdoor
thermistors can be
identifi ed by checking
the blinking pattern of
LED.
Reconnect
•
compressor connector.
Refer to 11-5. "How
•
to check inverter/
compressor".
Check the stop valve.
•
Reconnect
•
compressor connector.
Refer to 11-5. "How
•
to check inverter/
compressor".
Check the refrigerant
•
circuit and the
refrigerant amount.
Refer to 11-5. "Check
•
of LEV".
Check the refrigerant
•
circuit and the
refrigerant amount.
Check the stop valve.
•
Check around the
•
outdoor unit.
Check the outdoor unit
•
air passage.
Refer to 11-5. "Check
•
of outdoor fan motor".
Refer to 11-5. "Check
•
of outdoor fan motor".
Refer to 11-5. "Check
of inverter P.C. board".
Replace the inverter
•
P.C. board.
Refer to 11-5. "How
•
to check inverter/
compressor".
Indoor/outdoor
unit failure
mode recall
function
Outdoor unit
failure mode
recall function
○○
○○
○○
—
—
—
—
—
—
○○
○
○
○
○
○
○
10-time fl ash
2.5 seconds
OFF
Discharge temperature
Temperature of discharge temperature
thermistor has been 50°C or less for
—
20 minutes.
NOTE: Blinking patterns of this mode differ from the ones of Troubleshooting check table (11-3.).
1.
Intelligent power module (IPM): MUZ-GE25VA -A1, MUZ-GE35/50VA
IGBT module (IC700): MUZ-GE60/71/80VAD
Power module (IPM): Other models
68
Refer to 11-5. "Check
•
of LEV".
Check the refrigerant
•
circuit and the
refrigerant amount.
—
○
3. Outdoor unit failure mode table
OBH532E
The upper
lamp of
OPERATION
INDICATOR
lamp
(Indoor unit)
11-time fl ash
2.5 seconds
OFF
12-time fl ash
2.5 seconds
OFF
Abnormal point
(Failure mode / protection)
DC voltage 8-time fl ash
Each phase current of
compressor
Overcurrent Compressor
open-phase
LED indication
(Outdoor P.C. board)
2.5 seconds OFF
9-time fl ash
2.5 seconds OFF
10-time fl ash
2.5 seconds OFF
1.
Intelligent power module (IPM): MUZ-GE25VA -A1, MUZ-GE35/50VA
IGBT module (IC700): MUZ-GE60/71/80VAD
Power module (IPM): Other models
Condition Remedy
DC voltage of inverter cannot be
detected normally.
Each phase current of compressor
cannot be detected normally.
Large current fl ows into the intelligent
power module (IPM)/ IGBT module
(IC700)/ power module (IPM). 1.
The open-phase operation of
compressor is detected.
The interphase short circuit occurs
in the output of the intelligent power
module (IPM)/ IGBT module (IC700)/
power module (IPM). 1.
•
Refer to 11-5.
to check inverter/
compressor".
Reconnect
•
compressor connector.
Refer to 11-5. "How
•
to check inverter/
compressor".
"How
Indoor/outdoor
unit failure
mode recall
function
—
—
Outdoor unit
failure mode
recall function
○
○
14-time fl ash
2.5 seconds
OFF
Stop valve (Closed valve) 14-time fl ash
4-way valve/
Pipe temperature
(VAD)
2.5 seconds OFF
16-time fl ash
2.5 seconds OFF
Closed valve is detected by
compressor current.
The 4-way valve does not work
properly.
The indoor coil thermistor detects an
abnormal temperature.
Check the stop valve •
Check 4-way valve.
•
Replace inverter P.C.
•
board.
NOTE: Blinking patterns of this mode differ from the ones of Troubleshooting check table (11-3.).
11-3. TROUBLESHOOTING CHECK TABLE
No. Symptom LED indication
Outdoor unit
does not op-
1
erate.
2
3
4
5
6
7
'Outdoor unit
stops and
restarts 3
8
minutes later'
is repeated.
9
10
11
12
13
14
15
1-time fl ash every
2.5 seconds
6-time fl ash
2.5 seconds OFF
11-time fl ash
2.5 seconds OFF
14-time fl ash
2.5 seconds OFF
16-time fl ash
2.5 seconds OFF
(VAD)
2-time fl ash
2.5 seconds OFF
3-time fl ash
2.5 seconds OFF
4-time fl ash
2.5 seconds OFF
5-time fl ash
2.5 seconds OFF
8-time fl ash
2.5 seconds OFF
10-time fl ash
2.5 seconds OFF
12-time fl ash
2.5 seconds OFF
13-time fl ash
2.5 seconds OFF
Abnormal point/
Condition
Outdoor power system
Outdoor thermistors Discharge temperature thermistor, fi n temperature thermistor,
Outdoor control system
Serial signal The communication fails between the indoor and outdoor unit
Stop valve/
Closed valve
Outdoor unit
(Other abnormality)
4-way valve/
Pipe temperature
Overcurrent protection
Discharge temperature overheat protection
Fin temperature
/P.C. board temperature thermistor
overheat protection
High pressure protection
Compressor synchronous abnormality
Outdoor fan motor Outdoor fan has stopped 3 times in a row within 30 seconds
Each phase current
of compressor
DC voltage DC voltage of inverter cannot be detected normally. Refer to 11-5.
Overcurrent protection cut-out operates 3 consecutive times
within 1 minute after the compressor gets started.
defrost thermistor, outdoor heat exchanger temperature thermistor, P.C. board temperature thermistor or ambient temperature thermistor shorts or opens during compressor running.
Nonvolatile memory data cannot be read properly.
(The upper lamp of OPERATION INDICATOR lamp of the indoor unit lights up or fl ashes 7-time.)
for 3 minutes.
Closed valve is detected by compressor current. Check the stop valve. •
Outdoor unit is defective.Refer to 11-2.2. "Flow chart of the
The 4-way valve does not work properly.
The indoor coil thermistor detects an abnormal temperature.
Large current fl ows into the intelligent power module (IPM)/
IGBT module (IC700)/ power module (IPM). 1.
Temperature of discharge temperature thermistor exceeds
116°C, compressor stops. Compressor can restart if discharge
temperature thermistor reads 100°C or less 3 minutes later.
Temperature of fi n temperature thermistor on the heat sink
exceeds 75 ~ 80°C or temperature of P.C. board temperature
thermistor on the inverter P.C.board exceeds 70 ~ 75°C.
Temperature of indoor coil thermistor exceeds 70°C in HEAT
mode. Temperature of outdoor heat exchanger temperature
thermistor exceeds 70°C in COOL mode.
The waveform of compressor current is distorted.
after outdoor fan start-up.
Each phase current of compressor cannot be detected normally.
Condition Remedy
○○
Reconnect connector of compressor.
•
Refer to 11-5. "How to check in-
•
verter/compressor".
Check the stop valve.
•
Refer to 11-5. "Check of outdoor
•
thermistors".
Replace the inverter P.C. board. •
Refer to 11-5.
•
wiring and serial signal error.
•
detailed outdoor unit failure mode
recall function".
•
Refer to 11-5.
coil".
Replace the inverter P.C. board.
•
Reconnect the connector of the com-
•
pressor.
Refer to 11-5. "How to check in-
•
verter/compressor".
Check the stop valve.
•
Check the refrigerant circuit and
•
the refrigerant amount.
Refer to 11-5. "Check of LEV".
•
Check around the outdoor unit.
•
Check the outdoor unit air passage.
•
Refer to 11-5. "Check of outdoor
•
fan motor".
Check the refrigerant circuit and
•
the refrigerant amount.
Check the stop valve.
•
Reconnect connector of compressor.
•
Refer to 11-5. "How to check in-
•
verter/compressor".
Refer to 11-5. "Check of outdoor
•
fan motor.
Refer to 11-5. "Check of inverter
•
P.C. board.
Refer to 11-5. "How to check in-
•
verter/compressor".
•
verter/compressor".
"How to check mis-
"Check of R.V.
"How to check in-
69
11-3. TROUBLESHOOTING CHECK TABLE
OBH532E
No. Symptom LED indication
Outdoor unit
16
operates.
17
18
Outdoor unit
operates.
19
20
21
NOTE: 1. The location of LED is illustrated at the right fi gure. Refer to 11-6.1.
2. LED is lighted during normal operation.
The fl ashing frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the fl ashing frequency is “2”.
ON
2.5-second OFF
OFF
1-time fl ash
2.5 seconds OFF
3-time fl ash
2.5 seconds OFF
4-time fl ash
2.5 seconds OFF
7-time fl ash
2.5 seconds OFF
8-time fl ash
2.5 seconds OFF
9-time fl ash
2.5 seconds OFF
Abnormal point/
Condition
Frequency drop by
current protection
Frequency drop by
high pressure protection
Frequency drop by
defrosting in COOL
mode
Frequency drop by
discharge temperature protection
Low discharge temperature protection
MUZ-GE25/33/35/42/50
PAM protection PAM:
Pulse Amplitude Modulation
MUZ-GE60/71/80
Zero cross detecting
circuit
Inverter check mode The connector of compressor is disconnected, inverter check
0.5-second ON
2.5-second OFF
Current from power outlet is nearing breaker capacity. The unit is normal, but check the
Temperature of indoor coil thermistor exceeds 55°C in HEAT
mode, compressor frequency lowers.
Indoor coil thermistor reads 8°C or less in COOL mode, compressor frequency lowers.
Temperature of discharge temperature thermistor exceeds
111°C, compressor frequency lowers.
Temperature of discharge temperature thermistor has been
50°C or less for 20 minutes.
The overcurrent fl ows into IGBT (Insulated Gate Bipolar tran-
sistor: TR821) or the bus-bar voltage reaches 320 V or more,
PAM stops and restarts.
Zero cross signal cannot be detected.
mode starts.
Condition Remedy
0.5-second ON
Inverter P.C. board
following.
Check if the indoor fi lters are
•
clogged.
Check if the refrigerant is short.
•
Check if the indoor/outdoor unit air
•
circulation is short cycled.
Check the refrigerant circuit and
•
the refrigerant amount.
Refer to 11-5.
•
Refer to 11-5. "Check of outdoor
•
thermistors".
Refer to 11-5. "Check of LEV".
•
Check the refrigerant circuit and
•
the refrigerant amount.
This is not malfunction. PAM protection will be activated in the following cases:
1 Instantaneous power voltage
drop. (Short time power failure)
2 When the power supply voltage
is high.
Check if the connector of the com-
•
pressor is correctly connected.
Refer to 11-5. "How to check
inverter/compressor".
Measure the resistance using a tester. (Temperature: -10 ~ 40°C)
MUZ-GE60/71/80VA, MUZ-GE80VA2, MUZ-GE60/71/80VAD
Color of lead wire Normal (Ω)
RED – ORN
RED – WHT
RED – BLU
37 ~ 54
RED – YLW
WHT
V
WHT
RED
ORN
WHT
ORN
RED
(+12V)
RED BLK
W
U
LEV
YLW
BRN
LEV
LW
BLU
BLU
71
11-5. TROUBLESHOOTING FLOW
OBH532E
A How to check inverter/compressor
Disconnect the connector between
compressor and the intelligent power module
(IPM)/ IGBT module (IC700)/ power module
(IPM). 1.
1.
Intelligent power module (IPM): MUZ-GE25VA -A1, MUZ-GE35/50VA
IGBT module (IC700): MUZ-GE60/71/80VAD
Power module (IPM): Other models
Check the voltage between terminals.
Is the voltage balanced?
Yes
Check the compressor.
No
See 11-5. “Check of open phase”.
Replace the inverter P.C. board.
See 11-5.
“Check of compressor”.
B Check of open phase
● With the connector between the compressor and the intelligent power module (IPM)/ IGBT module (IC700)/ power module
(IPM) disconnected, activate the inverter and check if the inverter is normal by measuring the balance of voltage between
the terminals. 1.
Output voltage is 50 - 130 V. (The voltage may differ according to the tester.)
<< Operation method>>
Start cooling or heating operation by pressing EMERGENCY OPERATION switch on the indoor unit. (TEST RUN OPERA-
TION: Refer to 8-3.)
<<Measurement point>>
At 3 points
BLK (U)-WHT (V)
BLK (U)-RED (W)
WHT(V)-RED (W)
NOTE: 1. Output voltage varies according to power supply voltage.
2. Measure the voltage by analog type tester.
3. During this check, LED of the inverter P.C. board fl ashes 9 times. (Refer to 11-6.1.)
Measure AC voltage between the lead wires at 3 points.
C Check of compressor
Refer to 11-5. “Check of compressor
winding”.
Is the compressor normal?
Refer to 11-5. “Check of compressor
operation time”.
Does the compressor operate continuously?
OK.
Yes
Yes
No
No
Replace the compressor.
Refer to 11-5. “Check of compressor start failure”.
7272
1.
OBH532E
Intelligent power module (IPM): MUZ-GE25VA -A1, MUZ-GE35/50VA
IGBT module (IC700): MUZ-GE60/71/80VAD
D Check of compressor winding
Power module (IPM): Other models
●Disconnect the connector between the compressor and the intelligent power module (IPM)/ IGBT module (IC700)/ power mod-
ule (IPM) , and measure the resistance between the compressor terminals.
1.
<<Measurement point>>
At 3 points
BLK-WHT
BLK-RED
WHT-RED
Measure the resistance between the lead wires at 3 points.
<<Judgement>>
Refer to 11-4.
0 [Ω] ················Abnormal [short]
Infinite [Ω] ·······Abnormal [open]NOTE: Be sure to zero the ohmmeter before measurement.
E Check of compressor operation time
<<Judgement>>
● Connect the compressor and activate the inverter. Then measure
the time until the inverter stops due to over current.
<<Operation method>>
Start heating or cooling operation by pressing EMERGENCY
OPERATION switch on the indoor unit. (TEST RUN OPERATION:
Refer to 8-3.)
<<Measurement>>
Measure the time from the start of compressor to the stop of
compressor due to overcurrent.
•Electrical circuit check
. Contact of the compressor connector
. Output voltage of inverter P.C. board and balance of them (See 11-5. )
. Direct current voltage between DB61(+) and (-) (MUZ-GE25/33/35/42/50)/
JP715(+) and JP30(-) (MUZ-GE60/71/80) on the inverter P.C. board
. Voltage between outdoor terminal block S1-S2
Does the compressor run for 10 seconds or
more after it starts?
No
After the compressor is heated with a drier,
does the compressor start? 1
Yes
Compressor start failure. Activate pre-heat control.
(Refer to 10-2. "PRE-HEAT CONTROL SETTING")
Yes
No
Check the refrigerant circuit.
Check the stop valve.
Thermistor Symbol Connector, Pin No. Board
DefrostRT61 Between CN641 pin1 and pin2
Discharge temperature RT62 Between CN641 pin3 and pin4
Fin temperature RT64Between CN642 pin1 and pin2
Ambient temperature RT65 Between CN643 pin1 and pin2
Outdoor heat exchanger temperature RT68 Between CN644 pin1 and pin3
Thermistor Symbol Connector, Pin No. Board
DefrostRT61 Between CN671 pin1 and pin2
Discharge temperature RT62 Between CN671 pin3 and pin4
Fin temperature RT64Between CN673 pin1 and pin2
Ambient temperature RT65 Between CN672 pin1 and pin2
Outdoor heat exchanger temperature RT68 Between CN671 pin5 and pin6
Inverter P.C. board
H Check of R.V. coil
First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 11-4.
In case CN721 (MUZ-GE25/33/35/42/50)/CN602 (MUZ-GE60/71/80) is disconnected or R.V. coil is open, voltage is
generated between the terminal pins of the connector although no signal is being transmitted to R.V. coil. Check if CN721
(MUZ-GE25/33/35/42/50)/CN602 (MUZ-GE60/71/80) is connected.
Unit operates COOL mode even if it is set to HEAT mode.
Disconnect connector between the
compressor and the intelligent power
module.
Turn ON the power supply and press
EMERGENCY OPERATION switch
twice (HEAT mode).
Is there 230 VAC between
CN721 (MUZ-GE25/33/35/42/50)/
CN602(MUZ-GE60/71/80)
the inverter P.C. board 3 minutes after the
power supply is turned ON?
Replace the 4-way valve.
and on
Yes
Replace the inverter
No
P.C. board.
Unit operates HEAT mode even if it is set to COOL mode.
Disconnect connector between
the compressor and the intelligent
power module.
Turn ON the power supply and
press EMERGENCY OPERATION
switch once (COOL mode).
Is there 230 VAC between
CN721 (MUZ-GE25/33/35/42/50
CN602(MUZ-GE60/71/80
inverter P.C. board 3 minutes after the
power supply is turned ON?
Disconnect the connector between
compressor and intelligent power
module.
Turn ON power supply and press
EMERGENCY OPERATION switch.
Does the upper lamp of
OPERATION INDICATOR on the
indoor unit light up?
Yes
No
Rectify indoor/outdoor
connecting wire.
Yes
Is there voltage 230 VAC
between the indoor terminal
block S1 and S2?
Replace the inverter
No
P.C. board.
260 - 300 VDC
DB61
Inverter P.C. board
(Solder side)
MUZ-GE25/33/35/42/50
Replace the indoor
electronic control P.C.
No
board.
Is there bus-bar voltage 325 - 370
VDC between JP715 (+) and JP30
(–) on the inverter P.C. board?
(Refer to 11-6.1.)
Check the electric parts in main circuit.
No
Yes
Does LED on the inverter P.C.
board light up or fl ash? (Refer
to 11-6.1.)
Yes
If light up, OK.
If fl ash, refer to 11-3.
325 -370 VDC
76
Replace the inverter
No
P.C. board.
JP715
JP30
MUZ-GE60/71/80
K Check of LEV (Expansion valve)
OBH532E
Turn ON the power supply.
<Preparation of the remote controller>
While pressing both OPERATION SELECT button
and TOO COOL button (MSZ-GE25/33/35/42/50)/
TEMP
controller at the same time, press RESET button.
First, release RESET button.
Hold down the other two buttons for another 3 sec-
onds. Make sure that the indicators on the LCD
screen shown in the right fi gure are all displayed.
Then release the buttons.
Press OPERATE/STOP (ON/OFF) button of the remote
controller (the set temperature is displayed) with the
remote controller headed towards the indoor unit. 1
Expansion valve operates in full-opening direction.
Do you hear the expansion valve "click,
click·······"?
Do you feel the expansion valve vibrate
on touching it ?
button (MSZ-GE60/71/80VA) on the remote
OK
Yes
No
MSZ-GE25/33/35/42/50VA
MSZ-GE35/50VA2
MSZ-GE60/71/80VA
MSZ-GE80VA2
MSZ-GE25/35/42/50VAD
1. Regardless of normal or abnormal
condition, a short beep is emitted once
the signal is received.
MSZ-GE60/71/80VAD
Is LEV coil properly fi xed to
the expansion valve?
Yes
Does the resistance of LEV
coil have the characteristics?
(Refer to 11-4.)
No
Replace the LEV coil.
NOTE: After check of LEV, do the undermentioned operations.
1. Turn OFF the power supply and turn it ON again.
2. Press RESET button on the remote controller.
No
Yes
Properly fi x the LEV coil to the expansion valve.
Measure each voltage between connector
pins of CN724 on the inverter P.C. board.
1. Pin
(-) — Pin (+)
2. Pin (-) — Pin (+)
3. Pin (-) — Pin (+)
4. Pin (-) — Pin (+)
Is there about 3 ~ 5 VAC between each?
NOTE: Measure the voltage with an analog
tester.
Replace the expansion valve.
Yes
Replace the inverter P.C.
No
board.
77
L Check of inverter P.C. board
OBH532E
Check the outdoor fan motor.
(Refer to 11-5. .)
Is the fuse (F901) blown on the inverter P.C. board?
No
Check the connection of the connectors
(CN931 , CN932) of the outdoor fan motor.
If the connection is poor, make it correct.
Only MUZ-GE50,60,71,80
Operate the outdoor unit by starting
EMERGENCY OPERATION.
Check the LED indication on the inverter P.C. board.
Does the LED fl ash 10 times?
Yes
(10-time fl ash)
Replace the inverter P.C. board.
Yes
No
Check the corresponding parts
following LED indication.
(Refer to 11-3.)
Is there rated voltage between outdoor terminal block S1 and S2?
Press EMERGENCY OPERATION switch once.
Does the upper lamp of OPERATION INDICATOR lamp light up? <Confi rmation of the power
to the indoor unit>
Is serial signal error indicated 6 minutes later?
Turn OFF the power supply.
Check once more if the indoor/outdoor
B
connecting wire is not miswiring.
Short-circuit outdoor terminal block S2
and S3.
Is the bus-bar voltage of the inverter P.C. board or the outdoor electronic control P.C. board normal?
(Refer to "TEST POINT DIAGRAM AND VOLTAGE" of the outdoor unit.)
1
Turn ON the power supply.
Yes
Yes
Yes
Yes
A
Yes
No
No
No
1. Miswiring may damage indoor electronic control P.C.
3. Be sure to check this within 3 minutes after turning ON.
Check the power supply.
No
Is there any miswiring,
poor contact, or wire
disconnection of the
indoor/outdoor connecting wire?
board during the operation.
Be sure to confi rm the wiring is correct before the opera-
tion starts.
After 3 minutes, LED blinks 6 times. Even when the
inverter P.C. board is normal, LED blinks 6 times after 3
minutes.
No
Check the wiring.
Correct them.
Yes
Check of power supply.
(Refer to 11-5. .)
No
Does the LED on the inverter P.C. board repeat "3.6-second-OFF and 0.8-second-ON quick blinking"? 3
Turn OFF the power supply.
Remove the short-circuit between outdoor terminal block S2 and S3.
Turn ON the power supply.
Is there rated voltage between indoor terminal block S1 and S2?
<Confi rmation of power voltage>
Is there amplitude of 10 to 20 VDC between indoor terminal block S2
and S3? <Confi rmation of serial signal>
A
Turn OFF inverter-controlled lighting
•
equipment.
Turn OFF the power supply and then
•
turn ON again.
Press EMERGENCY OPERATION
•
switch.
Reinstall
•
either the unit
or the light
away from
No
•
each other.
Attach a fi lter
on remote
control receiving section
of the indoor
unit.
Is serial signal
error indicated 6
minutes later?
Yes
B
Yes
No
Yes
No
Yes
Is there 2 VDC or less between CN10A (+)
and JPG (GND)(-) on the indoor electronic
control P.C. board?
Yes
Is there 2 VDC or less between
CN10A (+) and JPG (GND)(-) on
the indoor electronic control P.C.
board?
Replace the indoor power
P.C. board and the indoor
terminal P.C. board
No
NoYesNo
Replace the indoor electronic control P.C. board.
79
No
(Lighted
or not
lighted)
Check the wiring.
If there are any error of the indoor/outdoor connecting wire:
such as the damage of the wire, intermediate connection,
and/or poor contact to the terminal block, replace the indoor/
outdoor connecting wire.
Replace the inverter P.C. board. 2
2. Be careful of the residual voltage of smoothing
capacitor.
Is there 2 VDC or less between
(+) and JPG (GND)(-) on
CN10A
the indoor electronic control P.C.
board?
Yes
MUZ-GE60VA MUZ-GE60VAD MUZ-GE71VA MUZ-GE71VAD
OBH532E
MUZ-GE80VA MUZ-GE80VA2 MUZ-GE80VAD
Turn OFF the power supply.
Is there rated voltage in the power supply?
Turn ON the power supply.
Is there rated voltage between outdoor terminal block S1 and S2?
Press EMERGENCY OPERATION switch once.
Does the upper lamp of OPERATION INDICATOR lamp light up? <Confi rmation of the power
to the indoor unit>
Is serial signal error indicated 6 minutes
later?
Turn OFF the power supply.
Check once more if the indoor/outdoor
B
connecting wire is not miswiring.
Short-circuit outdoor terminal block S2
and S3. 1
Turn ON the power supply.
Is the bus-bar voltage of the inverter P.C. board normal?
(Refer to "TEST POINT DIAGRAM AND VOLTAGE" of the outdoor unit.)
Yes
Yes
Yes
Yes
A
Yes
No
No
Is there any miswiring,
poor contact, or wire
disconnection of the
No
indoor/outdoor connecting wire?
1. Miswiring may damage indoor electronic control P.C.
board during the operation.
Be sure to confi rm the wiring is correct before the opera-
tion starts.
3. Be sure to check this within 3 minutes after turning ON.
After 3 minutes, LED blinks 6 times. Even when the
inverter P.C. board is normal, LED blinks 6 times after 3
minutes.
Check the power supply.
No
No
Check the wiring.
Yes
No
Correct them.
Does the LED on the inverter P.C. board repeat "3.6-second-OFF and 0.8-second-ON quick blinking"? 3
Turn OFF the power supply.
Remove the short-circuit between outdoor terminal block S2 and S3.
A
Turn OFF inverter-controlled lighting
•
equipment.
Turn OFF the power supply and then
•
turn ON again.
Press EMERGENCY OPERATION
•
switch.
Reinstall
•
either the unit
or the light
away from
No
•
each other.
Attach a fi lter
on remote
control receiving section
of the indoor
unit.
Is serial signal
error indicated 6
minutes later?
Yes
B
Yes
Replace the indoor electronic control P.C. board.
No
(Lighted
or not
lighted)
Replace the inverter P.C. board. 2
2. Be careful of the residual voltage of smoothing
capacitor.
80
N Electromagnetic noise enters into TV sets or radios
OBH532E
Is the unit earthed?
Yes
Is the distance between the antennas
and the indoor unit within 3 m, or is the
distance between the antennas and the
outdoor unit within 3 m?
No
Is the distance between the TV sets or
radios and the indoor unit within 1 m, or
is the distance between the TV sets or
radios and the outdoor unit within 3 m?
No
Are the antennas damaged?
Is the coaxial cable damaged?
Is there any poor contact in the antenna wiring?
No
Is the indoor/outdoor connecting wire
of the air conditioner and the wiring of
the antennas close?
No
No
Yes
Yes
Yes
Yes
Earth the unit.
Extend the distance between the antennas and
the indoor unit, and/or the antennas and the
outdoor unit.
Extend the distance between the TV sets and/or
radios and the indoor unit, or the TV sets or
radios and the outdoor unit.
Replace or repair the antenna.
Replace or repair the coaxial cable.
Extend the distance between the indoor/outdoor
connecting wire of the air conditioner and the wiring of the antennas.
Even if all of the above conditions are fulfi lled, the electromagnetic noise may enter, depending on the electric fi eld strength
or the installation condition (combination of specifi c conditions such as antennas or wiring).
Check the following before asking for service.
1. Devices affected by the electromagnetic noise
TV sets, radios (FM/AM broadcast, shortwave)
2. Channel, frequency, broadcast station affected by the electromagnetic noise
3. Channel, frequency, broadcast station unaffected by the electromagnetic noise
4. Layout of:
indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, earth wire, antennas, wiring from antennas, receiver
5. Electric fi eld intensity of the broadcast station affected by the electromagnetic noise
6. Presence or absence of amplifi er such as booster
7. Operation condition of air conditioner when the electromagnetic noise enters in
1) Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic
noise.
2) Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button on the remote controller
for power ON, and check for the electromagnetic noise.
3) After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the
electromagnetic noise.
4) Press OPERATE/STOP (ON/OFF) button on the remote controller for power OFF, when the outdoor unit stops but the
indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise.
Defrost thermistor(RT61)
Ambient temperature thermistor(RT65)
Outdoor heat exchanger temperature thermistor(RT68)
100
90
80
70
60
50
40
30
Resistance(k )
20
10
0
-20 -10010 203040
Temperature( )
700
600
500
400
300
200
Resistance(k )
100
0
0 102030405060708090100110120
Discharge temperature thermistor(RT62)
Temperature( )
85
Fin temperature thermistor(RT64)
200
180
160
140
120
100
80
60
Resistance(k )
40
20
0
0 1020304050607080
Temperature( )
12
OBH532E
DISASSEMBLY INSTRUCTIONS
<"Terminal with locking mechanism" Detaching points>
The terminal which has the locking mechanism can be detached as shown below.
There are two types (refer to (1) and (2)) of the terminal with locking mechanism.
The terminal without locking mechanism can be detached by pulling it out.
Check the shape of the terminal before detaching.
(1) Slide the sleeve and check if there is a locking lever or not.(2) The terminal with this connector has the
Sleeve
locking mechanism.
Locking lever
Slide the sleeve.
Pull the terminal while
pushing the locking
lever.
Hold the sleeve, and
pull out the terminal
slowly.
(1) Remove the screw fixing the service panel.
(2) Pull down the service panel and remove it.
(3) Disconnect the power supply and indoor/outdoor con-
necting wire.
(4) Remove the screws fixing the top panel.
(5) Remove the top panel.
(6) Remove the screws fixing the cabinet.
(7) Remove the cabinet.
(8) Remove the screws fixing the back panel.
(9) Remove the back panel.
Photo 1
Screws of the
top panel
Screws of
the top panel
Back
panel
Photo 2
86
Screws of
the cabinet
Screws of
the cabinet
Screw of the
cabinet
Service
panel
Screws of the
terminal block
and the back
panel
Screw of the
service panel
Direction to
remove
Hooks
OPERATING PROCEDURE
OBH532E
PHOTOS
2. Removing the inverter assembly, inverter P.C. board
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the lead wire to the reactor and the following con-
nectors:
<Inverter P.C. board>
CN721 (R.V. coil)
CN932 (Fan motor)
CN641 (Defrost thermistor and discharge temperature ther-
mistor)
CN643 (Ambient temperature thermistor)
CN644 (Outdoor heat exchanger temperature thermistor)
CN724 (LEV)
(3) Remove the compressor connector (CN61).
(4) Remove the screws fixing the heat sink support and the sep-
arator.
(5) Remove the fixing screws of the terminal block support and
the back panel.
(6) Remove the inverter assembly.
(7) Remove the screw of the earth wire and screw of the termi-
nal block support.
(8) Remove the heat sink support from the P.C. board support.
(9) Remove the screw of the inverter P.C. board and remove the
inverter P.C. board from the P.C. board support.
3. Removing R.V. coil
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the following connectors:
<Inverter P.C. board>
CN721 (R.V. coil)
(3) Remove the R.V. coil.
Photo 3
Screws of the heat sink
support and the separator
Screws of the terminal block
support and the back panel
Photo 4 (Inverter assembly)
Heat sink
Inverter
P.C. board
P.C. board
support
Screw of the terminal
block support
Terminal
block
support
4. Removing the discharge temperature thermistor,
defrost thermistor, outdoor heat exchanger temperature thermistor and ambient temperature thermistor
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the lead wire to the reactor and the following con-
nectors:
<Inverter P.C. board>
CN641 (Defrost thermistor and discharge temperature ther-
mistor)
CN643 (Ambient temperature thermistor)
CN644 (Outdoor heat exchanger temperature thermistor)
(3) Pull out the discharge temperature thermistor from its holder.
(4) Pull out the defrost thermistor from its holder. (Photo 6)
(5) Pull out the outdoor heat exchanger temperature thermistor
from its holder. (Photo 6)
(6) Pull out the ambient temperature thermistor from its holder.
Heat sink support
Photo 5
Screw of the
earth wire
Screw of the
R.V. coil
Discharge temperature thermistor
87
OPERATING PROCEDURE
OBH532E
PHOTOS
5. Removing outdoor fan motor
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the following connectors:
<Inverter P.C. board>
CN932 (Fan motor)
(3) Remove the propeller nut.
(4) Remove the propeller.
(5) Remove the screws fixing the fan motor.
(6) Remove the fan motor.
6. Removing the compressor and 4-way valve
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Remove the inverter assembly. (Refer to 2.)
(3) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure gauge
shows 0 MPa.
(4) Detach the brazed part of the suction and the discharge pipe
connected with compressor.
(5) Remove the nuts of compressor legs.
(6) Remove the compressor.
(7) Detach the brazed part of pipes connected with 4-way valve.
Photo 6
Photo 7
Outdoor heat
exchanger temperature thermistor
Defrost thermistor
Screws of the outdoor fan motor
88
Propeller
Photo 8
Propeller nut
Brazed parts of 4-way valve
12-2. MUZ-GE50VA MUZ-GE50VA2 MUZ-GE50VAD
OBH532E
NOTE: Turn OFF power supply before disassembly.
OPERATING PROCEDURE
1. Removing the cabinet
(1) Remove the screws of the service panel.
(2) Remove the screws of the top panel.
(3) Remove the screw of the valve cover.
(4) Remove the service panel.
(5) Remove the top panel.
(6) Remove the valve cover.
(7) Disconnect the power supply and indoor/outdoor connect-
ing wire.
(8) Remove the screws of the cabinet.
(9) Remove the cabinet.
(10)
Remove the screws of the back panel.
(11)
Remove the back panel.
PHOTOS
Photo 1
Screw of the top panel
Screws
of the
back
panel
Screws
of the
cabinet
Photo 2
Screw of the top panel
Screws
of the
cabinet
Screw
of the
service
panel
Screw
of the
valve
cover
Screws of
the back
panel
89
OPERATING PROCEDURE
OBH532E
PHOTOS
2. Removing the inverter assembly, inverter P.C. board
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the lead wire to the reactor and the following con-
nectors:
<Inverter P.C. board>
CN721 (R.V.coil)
CN931, CN932 (Fan motor)
CN641 (Defrost thermistor and discharge temperature ther-
mistor)
CN643 (Ambient temperature thermistor)
CN644 (Outdoor heat exchanger temperature thermistor)
CN724 (LEV)
(3) Remove the compressor connector (CN61).
(4) Remove the screws fixing the relay panel.
(5) Remove the inverter assembly.
(6) Remove the screw of the earth wire and screw of the
T.B.support.
(7) Remove the screw of the PB fixture.
(8) Remove the relay panel from the PB support.
(9) Remove the inverter P.C. board from the inverter assembly.
3. Removing R.V. coil
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the following connectors:
<Inverter P.C. board>
CN721 (R.V. coil)
(3) Remove the R.V. coil.
Photo 3
Photo 4 (Inverter assembly)
Heat sink
Hook of the
PB support
Inverter P.C.
board
PB support
Screws of the
relay panel
Screws of
the reactor
Screw of the
T.B. support
T.B. support
Hook of the
PB support
Photo5
Relay panel
Screw of the
PB fixture
Brazed parts of 4-way valve
Screw of the
earth wire
Screw of the
R.V. coil
90
OPERATING PROCEDUREPHOTOS
OBH532E
4. Removing the discharge temperature thermistor,
defrost thermistor, outdoor heat exchanger temperature thermistor and ambient temperature thermistor
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the lead wire to the reactor and the following
connectors:
<Inverter P.C. board>
CN641 (Defrost thermistor and discharge temperature ther-
mistor)
CN643 (Ambient temperature thermistor)
CN644 (Outdoor heat exchanger temperature thermistor)
(3) Pull out the discharge temperature thermistor from its hold-
er.
(4) Pull out the defrost thermistor from its holder.
(5) Pull out the outdoor heat exchanger temperature thermistor
from its holder.
(6) Pull out the ambient temperature thermistor from its holder.
5. Removing outdoor fan motor
(1)
Remove the top panel, cabinet and service panel. (Refer to 1.)
(2) Disconnect the following connectors:
<Inverter P.C. board>
CN931 and CN932 (Fan motor)
(3) Remove the propeller.
(4) Remove the screws fixing the fan motor.
(5) Remove the fan motor.
Photo 6
Outdoor heat
exchanger temperature thermistor
Photo 7
Ambient temperature
thermistor
Defrost thermistor
6. Removing the compressor and 4-way valve
(1)
Remove the top panel, cabinet and service panel. (Refer to 1.)
(2) Remove the back panel. (Refer to 1.)
(3) Remove the inverter assembly. (Refer to 2.)
(4) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure gauge
shows 0 MPa.
(5) Detach the brazed part of the suction and the discharge
pipe connected with compressor.
(6) Remove the compressor nuts.
(7) Remove the compressor.
(8) Detach the brazed parts of 4-way valve and pipe. (Photo 5)
(1) Remove the screws of the service panel.
(2) Remove the screws of the top panel.
(3) Remove the screw of the valve cover.
(4) Remove the service panel.
(5) Remove the top panel.
(6) Remove the valve cover.
(7) Disconnect the power supply and indoor/outdoor connect-
ing wire.
(8) Remove the screws of the cabinet.
(9) Remove the cabinet.
(10)
Remove the screws of the back panel.
(11)
Remove the back panel.
Photo 1
Screws of the top panel
Screws of the
cabinet
Photo 2
Screw of the back panel
Screws of the top panel
PHOTOS
Screws of the
cabinet
Screws of the
cabinet
92
Screws
of the
cabinet
Screw of
the valve
cover
Screws of the
service panel
Screws of the
back panel
OPERATING PROCEDURE
OBH532E
PHOTOS
2. Removing the inverter assembly, inverter P.C. board
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the lead wire to the reactor and the following con-
and outdoor heat exchanger temperature thermistor)
CN672 (Ambient temperature thermistor)
CN724 (LEV)
(3) Remove the compressor connector.
(4) Remove the screws fixing the relay panel.
(5) Remove the relay panel.
(6) Remove the earth wires and the lead wires of the inverter P.C.
board.
(7) Remove the screw of the PB support.
(8) Remove the inverter P.C. board from the relay panel.
3. Removing R.V. coil
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the following connector:
<Inverter P.C. board>
CN602 (R.V. coil)
(3) Remove the R.V. coil.
Photo 3
Inverter P.C
board
Screws
of the PB
support
Photo 4
Earth wires
Screws of
the relay
panel
Screw of the
relay panel
Screws of the
PB support
Screw of the
R.V. coil
Brazed parts of
4-way valve
93
OPERATING PROCEDUREPHOTOS
OBH532E
4. Removing the discharge temperature thermistor,
defrost thermistor, outdoor heat exchanger temperature thermistor and ambient temperature thermistor
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the lead wire to the reactor and the following
connectors:
<Inverter P.C. board>
CN671 (Defrost thermistor, discharge temperature thermis-
tor and outdoor heart exchanger temperature thermistor)
CN672 (Ambient temperature thermistor)
(3) Pull out the discharge temperature thermistor from its hold-
er.
(4) Pull out the defrost thermistor from its holder.
(5) Pull out the outdoor heat exchanger temperature thermistor
from its holder.
(6) Pull out the ambient temperature thermistor from its holder.
5. Removing outdoor fan motor
(1)
Remove the top panel, cabinet and service panel. (Refer to 1.)
(2) Disconnect the following connectors:
<Inverter P.C. board>
CN931 and CN932 (Fan motor)
(3) Remove the propeller.
(4) Remove the screws fixing the fan motor.
(5) Remove the fan motor.
Photo 5
Outdoor heat
exchanger temperature thermistor
Photo 6
Ambient temperature
thermistor
Defrost thermistor
6. Removing the compressor and 4-way valve
(1)
Remove the top panel, cabinet and service panel. (Refer to 1.)
(2) Remove the back panel. (Refer to 1.)
(3) Remove the inverter assembly. (Refer to 2.)
(4) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure gauge
(5) Detach the brazed part of the suction and the discharge
pipe connected with compressor.
(6) Remove the compressor nuts.
(7) Remove the compressor.
(8) Detach the brazed parts of 4-way valve and pipe. (Photo 4)
shows 0 MPa.
94
Photo 7
Brazed part of the
discharge pipe
Screws of the
outdoor fan motor
Discharge temperature
thermistor
Brazed part of the
suction pipe
OBH532E
95
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN