Mitsubishi Electric MUZ-FH25VE - E1, MUZ-FH35VE - E1, MUZ-FH50VE - E1, MUZ-FH25VE, MUZ-FH35VE Service Manual

...
Page 1
SERVICE MANUAL
CONTENTS
1. TECHNICAL CHANGES ··································· 3
2. PART NAMES AND FUNCTIONS ····················· 3
3. SPECIFICATION ················································ 4
4. NOISE CRITERIA CURVES ······························ 7
5. OUTLINES AND DIMENSIONS ························ 8
6. WIRING DIAGRAM ············································ 9
8. PERFORMANCE CURVES ····························· 13
9. ACTUA TOR CONTROL ··································· 24
10. SERVICE FUNCTIONS ···································· 25
11. TROUBLESHOOTING ····································· 26
12. DISASSEMBLY INSTRUCTIONS ···················· 47
Models
SPLIT-TYPE AIR CONDITIONERS
NOTE: RoHS compliant products have <G> mark on the spec name plate.
HFC
utilized
R410A
No. OBH624
REVISED EDITION-A
OUTDOOR UNIT
Indoor unit service manual MSZ-FH•VE Series (OBH623)
PARTS CATALOG (OBB624)
MUZ-FH25VE
-
E1
MUZ-FH35VE
-
E1
MUZ-FH50VE
-
E1
Please void OBH624.
Revision A:
MUZ-FH50VE- E1 has been added.
MUZ-FH25VE MUZ-FH35VE
Page 2
2
<Preparation before the repair service>
Prepare the proper tools. Prepare the proper protectors. Provide adequate ventilation. After stopping the operation of the air conditioner, turn off the power-supply breaker and remove the power plug. Discharge the capacitor before the work involving the electric parts.
<Precautions during the repair service>
Do not perform the work involving the electric parts with wet hands. Do not pour water into the electric parts. Do not touch the refrigerant. Do not touch the hot or cold areas in the refrigeration cycle. When the repair or the inspection of the circuit needs to be done without turning off the power, exercise great caution not to
touch the live parts.
Use the specifi ed refrigerant only
Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of. Correct refrigerant is specified in the manuals and on the spec labels provided with our products. We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions.
Revision A:
MUZ-FH50VE-
E1
has been added.
OBH624A
Page 3
3
MUZ-FH25VE -
E1
MUZ-FH35VE -
E1
MUZ-FH50VE -
E1
1. New model
TECHNICAL CHANGES
1
Air outlet
Drain outlet
Piping
Drain hose
Air inlet
(back and side)
MUZ-FH25VE MUZ-FH35VE
PART NAMES AND FUNCTIONS
2
ACCESSORIES
Model
MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE
Drain socket 1
MUZ-FH50VE
Piping
Air outlet
Drain outlet
Air inlet
(back and side)
Drain hose
OBH624A
Page 4
4
Outdoor model MUZ-FH25VE MUZ-FH35VE
Power supply Single phase, 230 V, 50 Hz
Capacity Rated frequency (Min.-Max.)
Cooling
kW
2.5 (1.4 - 3.5) 3.5 (0.8 - 4.0)
Heating 3.2 (1.8 - 5.5) 4.0 (1.0 - 6.3)
Breaker Capacity A 10
Electrical data
Power input 1 (Total)
Cooling
W
485 820
Heating 580 800
Running current 1 (Total)
Cooling
A
2.6 3.9
Heating 2.9 3.8
Power factor 1 (Total)
Cooling
%
81 91
Heating 86 91
Starting current
1 (Total) A 2.9 3.9
Coeffi cient of performance (COP)
1 (Total)
Cooling 5.15 4.27 Heating 5.52 5.00
Compressor
Model SNB140FRUMT Output W 950
Current 1
Cooling
A
2.04 3.32
Heating 2.34 3.22
Refrigeration oil (Model) L 0.35 (FV50S)
Fan motor
Model RC0J50-CI Current 1
Cooling
A
0.28 0.30
Heating 0.28 0.30 Dimensions W × H × D mm 800 × 550 × 285 Weight kg 37
Special remarks
Dehumidifi cation Cooling L/h 0.2 0.8
Air fl ow 1
Cooling
High
m3/h
1,806
Low 1,038
Heating
High 2,016
Med. 1,710
Low 1,326
Sound level 1
Cooling
dB(A)
46 49
Heating 49 50
Fan speed
Cooling
High
rpm
810
Low 490
Heating
High 900
Med. 770
Low 610 Fan speed regulator 3 Refrigerant fi lling capacity (R410A) kg 1.15
NOTE: Test conditions are based on ISO 5151. Cooling: Indoor Dry-bulb temperature 27°C Wet-bulb temperature 19°C Outdoor Dry-bulb temperature 35°C Heating: Indoor Dry-bulb temperature 20°C Outdoor Dry-bulb temperature 7°C Wet-bulb temperature 6°C Refrigerant piping length (one way): 5 m 1 Measured under rated operating frequency.
SPECIFICATION
3
OBH624A
Page 5
5
Outdoor model MUZ-FH50VE
Power supply Single phase, 230 V, 50 Hz
Capacity Rated frequency (Min. - Max.)
Cooling
kW
5.0 (1.9 - 6.0)
Heating 6.0 (1.7 - 8.7)
Breaker Capacity A 16
Electrical data
Power input 1 (Total)
Cooling
W
1,380
Heating 1,480
Running current 1 (Total)
Cooling
A
6.1
Heating 6.5
Power factor
1 (Total)
Cooling
%
98
Heating 98
Starting current 1 (Total) A 6.5
Coeffi cient of performance (COP) 1 (Total)
Cooling 3.62
Heating 4.05
Compressor
Model SNB172FEKMT Output W 1,200
Current 1
Cooling
A
4.98
Heating 5.37
Refrigeration oil (Model) L 0.40(FV50S)
Fan motor
Model RC0J60-BC Current
1
Cooling
A
0.83
Heating 0.84 Dimensions W × H × D mm 840 × 880 × 330 Weight kg 55
Special remarks
Dehumidifi cation Cooling L/h 2.0
Air fl ow 1
Cooling
High
m3/h
3,006
Med. 3,006
Low 1,626
Heating
High 2,892 Med. 2,892
Low 2,280
Sound level 1
Cooling
dB(A)
51
Heating 54
Fan speed
Cooling
High
rpm
840
Med. 840
Low 480
Heating
High 810 Med. 810
Low 650 Fan speed regulator 3 Refrigerant fi lling capacity (R410A) kg 1.55
NOTE: Test conditions are based on ISO 5151. Cooling: Indoor Dry-bulb temperature 27°C Wet-bulb temperature 19°C Outdoor Dry-bulb temperature 35°C Heating: Indoor Dry-bulb temperature 20°C Outdoor Dry-bulb temperature 7°C Wet-bulb temperature 6°C Refrigerant piping length (one way): 5 m 1 Measured under rated operating frequency.
OBH624A
Page 6
6
Specifi cations and rated conditions of main electric parts
Model
Item
MUZ-FH25VE MUZ-FH35VE
Smoothing capacitor
(C61, C62) 600 μF/ 620 μF 420 V
Diode module (DB61) 15 A 600 V Fuse
(F61) T20AL250V
(F701, F801, F901)
T3.15AL250V
Power module
(IC700) 15 A 600 V (IC932) 8A600V
Expansion valve coil
(LEV) 12 V DC
Reactor (L61) 23 mH Power factor
controller
(IC820) 20A 600V
Circuit protection
(PTC64, PTC65) 33 Ω
Terminal block (TB) 5 P
Relay
(X63) 3 A 250 V (X64) 20 A 250 V (X69) 10A 230V
R.V.coil (21S4) 220 - 240 V AC
Specifi cations and rated conditions of main electric parts
Model
Item
MUZ-FH50VE
Smoothing capacitor
(CB1, CB2, CB3)
560 μF 450 V
Fuse
(F601, F880, F901)
T3.15AL250 V
IGBT module
(IC932) 5 A 600 V (IC700) 20 A 600 V
Expansion valve coil
(LEV) 12 V DC
Reactor (L) 340 μH Diode module (IC820) 20 A 600 V Circuit
protection
(PTC64, PTC65) 33 Ω
Terminal block (TB1, TB2) 3 P
Relay
(X64) 20 A 250 V (X65) 20 A 250 V
(X69) 10 A 250 V (X601) 3 A 250 V (X602) 3 A 250 V
R.V. coil (21S4) 220 - 240 V AC
OBH624A
Page 7
7
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
COOLING
FUNCTION
SPL(dB(A)) LINE
HEATING
46 49
NC-10
MUZ-FH25VE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
COOLING
FUNCTION
SPL(dB(A))
LINE
HEATING
49 50
NC-10
MUZ-FH35VE
NOISE CRITERIA CURVES
4
Test conditions Cooling: Dry-bulb temperature 35°C Heating: Dry-bulb temperature 7°C Wet-bulb temperature 6°C
OUTDOOR UNIT
MICROPHONE
1 m
MUZ-FH50VE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
COOLING
FUNCTION
SPL(dB(A)) LINE
HEATING
51
NC-10
54
OBH624A
Page 8
8
10
69
800
302.5 500 Bolt pitch for installation
150
22.3
Handle
550
280
164.5
99.5
170.5
23
Service panel
Service port
285
344.5
44
400
Air in
Air out
Air in
17.5
Bolt pitch for
installation
304~325
40
Liquid refrigerant pipe joint Refrigerant pipe (flared) ø6.35
Gas refrigerant pipe joint Refrigerant pipe (flared) ø9.52
43
35
2 holes 10 X 21
REQUIRED SPACE
100 mm or more
350 mm or more
200 mm or more
100 mm or more
100 mm or more
Drain hole ø42
Unit: mm
MUZ-FH25VE MUZ-FH35VE
OUTLINES AND DIMENSIONS
5
MUZ-FH50VE
417.5
40
42
Drain hole
175
500
330
50
Air in
Air out
2-holes 10 21
360
840
109
81
880
452
Service panel
99.5
164.5 195
35
44
Liquid refrigerant pipe joint Refrigerant pipe (flared)
Ø 6.35
Gas refrigerant pipe joint Refrigerant pipe (flared)
Ø 12.7
350 mm or more
100 mm or more
REQUIRED SPACE
500 mm or more
100 mm or more
500 mm or more
OBH624A
Page 9
9
WIRING DIAGRAM
6
MUZ-FH25VE MUZ-FH35VE
OBH624A
Page 10
10
MUZ-FH50VE
OBH624A
Page 11
11
Unit: mm
MUZ-FH25VE MUZ-FH35VE
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve (with strainar)
Stop valve
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe ø9.52 (with heat insulator)
Refrigerant pipe ø6.35 (with heat insulator)
R.V. coil heating ON cooling OFF
Strainer #100
LEV
Ambient temperature thermistor RT65
Muffler
Capillary tube ø4.0×ø2.4×240
Outdoor heat exchanger temperature thermistor RT68
Capillary tube ø3.0×ø2.0×210
Muffler
REFRIGERANT SYSTEM DIAGRAM
7
MUZ-FH50VE
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve
Stop valve
Capillary tube
ø
4.0
×
ø
2.4×100 Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe
ø
12.7
(with heat insulator)
Refrigerant pipe ø6.35 (with heat insulator)
LEV
Muffler
R.V. coil heating ON cooling OFF
Muffler
#100
Strainer
#100
Outdoor heat exchanger temperature thermistor RT68
Ambient temperature thermistor RT65
Strainer
#100
OBH624A
Page 12
12
Max. Length A
Max. Height
difference
B
Indoor unit
Outdoor unit
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Model
Refrigerant piping: m Piping size O.D: mm
Max. Length A Max. Height difference B Gas Liquid
MUZ-FH25/35 20 12 9.52 6.35 MUZ-FH50 30 15 12.7 6.35
ADDITIONAL REFRIGERANT CHARGE (R410A: g)
Model
Outdoor unit
precharged
Refrigerant piping length (one way)
7 m 8 m 9 m 10 m 11 m 12 m 13 m 14 m 15 m 20 m
MUZ-FH25/35 1,150
0 30 60 90 120 150 180 210 240 390
Calculation: X g = 30 g/m × (Refrigerant piping length (m) - 7)
Model
Outdoor unit
precharged
Refrigerant piping length (one way)
7 m 10 m 15 m 20 m 25 m 30 m
MUZ-FH50 1,550 0 60 160 260 360 460
Calculation: X g = 20 g/m × (Refrigerant piping length (m) – 7)
OBH624A
Page 13
13
PERFORMANCE CURVES8
The standard specifications apply only to the operation of the air conditioner under normal conditions. Since operating condi­tions vary according to the areas where these units are installed, the following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198 ~ 264 V, 50 Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature: °C [WB]
}
Cooling
(2) Indoor outlet air wet-bulb temperature: °C [WB] (3) Outdoor intake air dry-bulb temperature: °C [DB] (4) Total input: W (5) Indoor intake air dry-bulb temperature: °C [DB]
}
Heating(6) Outdoor intake air wet-bulb temperature: °C [WB] (7) Total input: W Indoor air wet and dry bulb temperature difference on the left side of the following chart shows the difference between the indoor intake air wet and dry bulb temperature and the indoor outlet air wet and dry bulb temperature for your reference at service.
How to measure the indoor air wet and dry bulb temperature difference
1. Attach at least 2 sets of wet and dry bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet and dry bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.
2. Attach at least 2 sets of wet and dry bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once (twice) to start the EMERGENCY COOL (HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE
INDOOR UNIT
OUTDOOR UNIT
Wet and dry bulb thermometers FRONT VIEW
Wet and dry bulb thermometers BACK VIEW
Cooling capacity (
at Rated frequency)
0.9
1.0
1.1
1.2
1.3
1.4
1.5
-10-5 0 5 1015202530354045 Outdoor intake air Dry-bulb temperature(°C)
Capacity correction factors
26
24
20 18
22
Indoor intake air Wet-bulb temperature( )
MUZ-FH35VE
MUZ-FH25VE
Indoor air Wet-bulb temperature
difference (°C)
6.4
5.9
5.5
5.0
4.6
4.1
3.7
9.5
8.7
8.0
7.3
6.6
5.9
5.3
MUZ-FH50VE
13.6
12.5
11.4
10.3
9.3
8.3
7.3
8-1. CAPACITY AND INPUT CURVES
OBH624A
Page 14
14
NOTE: The above broken lines are for the heating operation without any frost and defrost operation.
0.8
0.9
1.0
1.1
1.2
1.3
-10-5 0 5 1015202530354045 Outdoor intake air Dry-bulb temperature (°C)
Input correction factors
26
24
22 20 18
Indoor intake air Wet-bulb temperature( )
Indoor air Wet-bulb temperature
difference (°C)
5.5
5.0
4.6
4.1
3.7
3.2
8.0
7.3
6.6
5.9
5.3
4.6
MUZ-FH35VE
11.4
10.3
9.3
8.3
7.3
6.4
MUZ-FH50VE
MUZ-FH25VE
Total input (Cooling :
at Rated frequency
)
Indoor air Dry-bulb temperature
difference (°C)
15.9
14.6
13.4
12.2
11.0
9.8
8.5
7.3
6.1
4.9
MUZ-FH25VE
19.8
18.3
16.8
15.2
13.7
12.2
10.7
9.1
7.6
6.1
MUZ-FH35VE
26.9
24.8
22.7
20.7
18.6
16.5
14.5
12.4
10.3
8.3
MUZ-FH50VE
Outdoor intake air Wet-bulb temperature (°C)
-15 -10 -5 0 5 10 15
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
Heating capacity (
at Rated frequency)
Capacity correction factor
15
20
26
Indoor intake air Dry-bulb temperature ( )
Indoor air Dry-bulb temperature
difference (°C)
15.9
14.6
13.4
12.2
11.0
9.8
8.5
7.3
6.1
4.9
MUZ-FH25VE
19.8
18.3
16.8
15.2
13.7
12.2
10.7
9.1
7.6
6.1
MUZ-FH35VE
26.9
24.8
22.7
20.7
18.6
16.5
14.5
12.4
10.3
8.3
MUZ-FH50VE
Outdoor intake air Wet-bulb temperature (°C)
-15 -10 -5 0 5 10 15
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
Total input (Heating :
at Rated frequency
)
Input correction factor
15
20
26
Indoor intake air Dry-bulb temperature ( )
OBH624A
Page 15
15
8-2. CAPACITY AND INPUT CORRECTION BY OPERATIONAL FREQUENCY OF COMPRESSOR
0 50 100
0.5
1.0
1.5
0 50 100
0.5
1.0
1.5
0 50 100
0.5
1.0
1.5
0 50 100
1
2
3
050100
150
0.5
1.0
1.5
2.0
0 50 100
150
1
2
3
0 50 100
150
0.5
1.0
1.5
2.0
0 50 100
150
1
2
3
MUZ-FH25VE
MUZ-FH35VE
Correction of Cooling capacity
The operational frequency of compressor (Hz)
Capacity correction factors
Correction of Cooling input
The operationalfrequency of compressor(Hz)
Input correction factors
Correction of Heating capacity
The operationalfrequency of compressor (Hz)
Capacity correction factors
Correction of Heating input
The operational frequency of compressor (Hz)
Input correction factors
Correction of Cooling capacity
The operational frequency of compressor (Hz)
Capacity correction factors
Correction of Cooling input
The operational frequency of compressor (Hz)
Input correction factors
Correction of Heatingcapacity
The operational frequency of compressor (Hz)
Capacity correction factors
Correction of Heatinginput
The operational frequency of compressor (Hz)
Input correction factors
Correction of Cooling capacity
Capacity correction factors
Correction of Cooling input
Input correction factors
Correction of Heating capacity
Capacity correction factors
MUZ-FH50VE
Correction of Heating input
Capacity correction factors
The operational frequency of compressor (Hz)
The operational frequency of compressor (Hz)
The operational frequency of compressor (Hz)
The operational frequency of compressor (Hz)
0 50 100
0.5
1.0
1.5
2.0
0 50 100
0.5
1.0
1.5
2.0
0 50 100 150
0.5
1.0
1.5
2.0
0 50 100 150
0.5
1.0
1.5
2.0
2.5
8-3. HOW TO OPERATE FIXED-FREQUENCY OPERATION
<Test run operation>
1. Press EMERGENCY OPERATION switch to start COOL or HEAT mode (COOL: Press once, HEAT: Press twice).
2. Test run operation starts and continues to operate for 30 minutes.
3. Compressor operates at rated frequency in COOL mode or 58 Hz in HEAT mode.
4. Indoor fan operates at High speed.
5.
After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (operation frequency of compressor varies).
6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on remote controller.
OBH624A
Page 16
16
15 20 25 30 35
0.4
0.5
0.6
0.7
0.8
0.9
15 20 25 30 35
0.4
0.5
0.6
0.7
0.8
Ambient temperature(°C) Ambient humidity(%)
15 20 25 30 35
0.3
0.4
0.5
0.6
0.7
0.8
(kgf/cm2[Gauge])(MPa[Gauge])
6
5
4
7
8
9
(kgf/cm2[Gauge])(MPa [Gauge])
3
5
4
6
7
50 60 70
Ambient temperature(°C) Ambient humidity(%)
50 60 70
Ambient temperature(°C) Ambient humidity(%)
Outdoor low pressure
MUZ-FH25VE MUZ-FH35VE
MUZ-FH50VE
(kgf/cm2[Gauge])(MPa[Gauge])
50 60 70
3
5
4
6
7
8
COOL operation
Both indoor and outdoor unit are under the same temperature/
humidity condition.
Operation: TEST RUN OPERATION (Refer to 8-3.)
8-4. OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
Dry-bulb temperature (°C) Relative humidity (%)
20 50 25 60 30 70
NOTE: The unit of pressure has been changed to MPa on the international system of units (SI unit system) The conversion factor is: 1 (MPa [Gauge]) = 10.2 (kgf/cm2 [Gauge])
15 20502560307035
1.5
2.0
2.5
3.0
15 20502560307035
2.5
3.0
3.5
4.0
4.5
Ambient temperature (°C) Ambi
ent humidity(%)
Outdoor current (A)
Ambient temperature (°C) Ambient humidity(%)
Outdoor current (A)
MUZ-FH35VEMUZ-FH25VE
Outdoor unit current
15 20502560307035
3
4
5
6
7
8
MUZ-FH50VE
Ambient temperature (°C) Ambient humidity(%)
Outdoor current (A)
0510
15 20 25
4.0
4.5
5.0
5.5
6.0
0510
15 20 25
4.0
4.5
5.0
5.5
6.0
0 5 10 15 20 25
3
4
5
6
7
8
Ambient temperature (°C)
Outdoor current (A)
Ambient temperature (°C)
Outdoor current (A)
MUZ-FH35VEMUZ-FH25VE
Outdoor unit current
MUZ-FH50VE
Ambient temperature (°C)
Outdoor current (A)
Condition:
Operation: Test run operation (Refer to 8-3.)
HEAT operation
Indoor Outdoor
Dry bulb temperature (°C) 20.0 2 7 15 20.0
Wet bulb temperature (°C) 14.5 1 6 12 14.5
OBH624A
Page 17
17
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-FH25VE
CAPACITY: 2.5 kW SHF: 0.95 INPUT: 485 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
21 25 27 30
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 2.94 2.26 0.77 388 2.81 2.17 0.77 407 2.70 2.08 0.77 427 2.60 2.00 0.77 446 21 20 3.06 1.99 0.65 407 2.94 1.91 0.65 432 2.85 1.85 0.65 441 2.75 1.79 0.65 461 22 18 2.94 2.38 0.81 388 2.81 2.28 0.81 407 2.70 2.19 0.81 427 2.60 2.11 0.81 446 22 20 3.06 2.11 0.69 407 2.94 2.03 0.69 432 2.85 1.97 0.69 441 2.75 1.90 0.69 461 22 22 3.19 1.82 0.57 422 3.08 1.75 0.57 449 3.00 1.71 0.57 461 2.88 1.64 0.57 480 23 18 2.94 2.50 0.85 388 2.81 2.39 0.85 407 2.70 2.30 0.85 427 2.60 2.21 0.85 446 23 20 3.06 2.24 0.73 407 2.94 2.14 0.73 432 2.85 2.08 0.73 441 2.75 2.01 0.73 461 23 22 3.19 1.94 0.61 422 3.08 1.88 0.61 449 3.00 1.83 0.61 461 2.88 1.75 0.61 480 24 18 2.94 2.61 0.89 388 2.81 2.50 0.89 407 2.70 2.40 0.89 427 2.60 2.31 0.89 446 24 20 3.06 2.36 0.77 407 2.94 2.26 0.77 432 2.85 2.19 0.77 441 2.75 2.12 0.77 461 24 22 3.19 2.07 0.65 422 3.08 2.00 0.65 449 3.00 1.95 0.65 461 2.88 1.87 0.65 480 24 24 3.35 1.78 0.53 441 3.23 1.71 0.53 466 3.15 1.67 0.53 480 3.05 1.62 0.53 504 25 18 2.94 2.73 0.93 388 2.81 2.62 0.93 407 2.70 2.51 0.93 427 2.60 2.42 0.93 446 25 20 3.06 2.48 0.81 407 2.94 2.38 0.81 432 2.85 2.31 0.81 441 2.75 2.23 0.81 461 25 22 3.19 2.20 0.69 422 3.08 2.12 0.69 449 3.00 2.07 0.69 461 2.88 1.98 0.69 480 25 24 3.35 1.91 0.57 441 3.23 1.84 0.57 466 3.15 1.80 0.57 480 3.05 1.74 0.57 504 26 18 2.94 2.85 0.97 388 2.81 2.73 0.97 407 2.70 2.62 0.97 427 2.60 2.52 0.97 446 26 20 3.06 2.60 0.85 407 2.94 2.50 0.85 432 2.85 2.42 0.85 441 2.75 2.34 0.85 461 26 22 3.19 2.33 0.73 422 3.08 2.24 0.73 449 3.00 2.19 0.73 461 2.88 2.10 0.73 480 26 24 3.35 2.04 0.61 441 3.23 1.97 0.61 466 3.15 1.92 0.61 480 3.05 1.86 0.61 504 26 26 3.45 1.69 0.49 466 3.35 1.64 0.49 490 3.30 1.62 0.49 504 3.20 1.57 0.49 519 27 18 2.94 2.94 1.00 388 2.81 2.81 1.00 407 2.70 2.70 1.00 427 2.60 2.60 1.00 446 27 20 3.06 2.73 0.89 407 2.94 2.61 0.89 432 2.85 2.54 0.89 441 2.75 2.45 0.89 461 27 22 3.19 2.45 0.77 422 3.08 2.37 0.77 449 3.00 2.31 0.77 461 2.88 2.21 0.77 480 27 24 3.35 2.18 0.65 441 3.23 2.10 0.65 466 3.15 2.05 0.65 480 3.05 1.98 0.65 504 27 26 3.45 1.83 0.53 466 3.35 1.78 0.53 490 3.30 1.75 0.53 504 3.20 1.70 0.53 519 28 18 2.94 2.94 1.00 388 2.81 2.81 1.00 407 2.70 2.70 1.00 427 2.60 2.60 1.00 446 28 20 3.06 2.85 0.93 407 2.94 2.73 0.93 432 2.85 2.65 0.93 441 2.75 2.56 0.93 461 28 22 3.19 2.58 0.81 422 3.08 2.49 0.81 449 3.00 2.43 0.81 461 2.88 2.33 0.81 480 28 24 3.35 2.31 0.69 441 3.23 2.23 0.69 466 3.15 2.17 0.69 480 3.05 2.10 0.69 504 28 26 3.45 1.97 0.57 466 3.35 1.91 0.57 490 3.30 1.88 0.57 504 3.20 1.82 0.57 519 29 18 2.94 2.94 1.00 388 2.81 2.81 1.00 407 2.70 2.70 1.00 427 2.60 2.60 1.00 446 29 20 3.06 2.97 0.97 407 2.94 2.85 0.97 432 2.85 2.76 0.97 441 2.75 2.67 0.97 461 29 22 3.19 2.71 0.85 422 3.08 2.61 0.85 449 3.00 2.55 0.85 461 2.88 2.44 0.85 480 29 24 3.35 2.45 0.73 441 3.23 2.35 0.73 466 3.15 2.30 0.73 480 3.05 2.23 0.73 504 29 26 3.45 2.10 0.61 466 3.35 2.04 0.61 490 3.30 2.01 0.61 504 3.20 1.95 0.61 519 30 18 2.94 2.94 1.00 388 2.81 2.81 1.00 407 2.70 2.70 1.00 427 2.60 2.60 1.00 446 30 20 3.06 3.06 1.00 407 2.94 2.94 1.00 432 2.85 2.85 1.00 441 2.75 2.75 1.00 461 30 22 3.19 2.84 0.89 422 3.08 2.74 0.89 449 3.00 2.67 0.89 461 2.88 2.56 0.89 480 30 24 3.35 2.58 0.77 441 3.23 2.48 0.77 466 3.15 2.43 0.77 480 3.05 2.35 0.77 504 30 26 3.45 2.24 0.65 466 3.35 2.18 0.65 490 3.30 2.15 0.65 504 3.20 2.08 0.65 519 31 18 2.94 2.94 1.00 388 2.81 2.81 1.00 407 2.70 2.70 1.00 427 2.60 2.60 1.00 446 31 20 3.06 3.06 1.00 407 2.94 2.94 1.00 432 2.85 2.85 1.00 441 2.75 2.75 1.00 461 31 22 3.19 2.96 0.93 422 3.08 2.86 0.93 449 3.00 2.79 0.93 461 2.88 2.67 0.93 480 31 24 3.35 2.71 0.81 441 3.23 2.61 0.81 466 3.15 2.55 0.81 480 3.05 2.47 0.81 504 31 26 3.45 2.38 0.69 466 3.35 2.31 0.69 490 3.30 2.28 0.69 504 3.20 2.21 0.69 519 32 18 2.94 2.94 1.00 388 2.81 2.81 1.00 407 2.70 2.70 1.00 427 2.60 2.60 1.00 446 32 20 3.06 3.06 1.00 407 2.94 2.94 1.00 432 2.85 2.85 1.00 441 2.75 2.75 1.00 461 32 22 3.19 3.09 0.97 422 3.08 2.98 0.97 449 3.00 2.91 0.97 461 2.88 2.79 0.97 480 32 24 3.35 2.85 0.85 441 3.23 2.74 0.85 466 3.15 2.68 0.85 480 3.05 2.59 0.85 504 32 26 3.45 2.52 0.73 466 3.35 2.45 0.73 490 3.30 2.41 0.73 504 3.20 2.34 0.73 519
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH624A
Page 18
18
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-FH25VE
CAPACITY: 2.5 kW SHF: 0.95 INPUT: 485 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
35 40 46
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 2.45 1.89 0.77 475 2.25 1.73 0.77 504 2.08 1.60 0.77 524 21 20 2.58 1.67 0.65 495 2.40 1.56 0.65 519 2.23 1.45 0.65 548 22 18 2.45 1.98 0.81 475 2.25 1.82 0.81 504 2.08 1.68 0.81 524 22 20 2.58 1.78 0.69 495 2.40 1.66 0.69 519 2.23 1.54 0.69 548 22 22 2.73 1.55 0.57 514 2.55 1.45 0.57 543 2.38 1.35 0.57 563 23 18 2.45 2.08 0.85 475 2.25 1.91 0.85 504 2.08 1.76 0.85 524 23 20 2.58 1.88 0.73 495 2.40 1.75 0.73 519 2.23 1.62 0.73 548 23 22 2.73 1.66 0.61 514 2.55 1.56 0.61 543 2.38 1.45 0.61 563 24 18 2.45 2.18 0.89 475 2.25 2.00 0.89 504 2.08 1.85 0.89 524 24 20 2.58 1.98 0.77 495 2.40 1.85 0.77 519 2.23 1.71 0.77 548 24 22 2.73 1.77 0.65 514 2.55 1.66 0.65 543 2.38 1.54 0.65 563 24 24 2.88 1.52 0.53 534 2.70 1.43 0.53 558 2.55 1.35 0.53 582 25 18 2.45 2.28 0.93 475 2.25 2.09 0.93 504 2.08 1.93 0.93 524 25 20 2.58 2.09 0.81 495 2.40 1.94 0.81 519 2.23 1.80 0.81 548 25 22 2.73 1.88 0.69 514 2.55 1.76 0.69 543 2.38 1.64 0.69 563 25 24 2.88 1.64 0.57 534 2.70 1.54 0.57 558 2.55 1.45 0.57 582 26 18 2.45 2.38 0.97 475 2.25 2.18 0.97 504 2.08 2.01 0.97 524 26 20 2.58 2.19 0.85 495 2.40 2.04 0.85 519 2.23 1.89 0.85 548 26 22 2.73 1.99 0.73 514 2.55 1.86 0.73 543 2.38 1.73 0.73 563 26 24 2.88 1.75 0.61 534 2.70 1.65 0.61 558 2.55 1.56 0.61 582 26 26 3.03 1.48 0.49 553 2.85 1.40 0.49 577 2.68 1.31 0.49 601 27 18 2.45 2.45 1.00 475 2.25 2.25 1.00 504 2.08 2.08 1.00 524 27 20 2.58 2.29 0.89 495 2.40 2.14 0.89 519 2.23 1.98 0.89 548 27 22 2.73 2.10 0.77 514 2.55 1.96 0.77 543 2.38 1.83 0.77 563 27 24 2.88 1.87 0.65 534 2.70 1.76 0.65 558 2.55 1.66 0.65 582 27 26 3.03 1.60 0.53 553 2.85 1.51 0.53 577 2.68 1.42 0.53 601 28 18 2.45 2.45 1.00 475 2.25 2.25 1.00 504 2.08 2.08 1.00 524 28 20 2.58 2.39 0.93 495 2.40 2.23 0.93 519 2.23 2.07 0.93 548 28 22 2.73 2.21 0.81 514 2.55 2.07 0.81 543 2.38 1.92 0.81 563 28 24 2.88 1.98 0.69 534 2.70 1.86 0.69 558 2.55 1.76 0.69 582 28 26 3.03 1.72 0.57 553 2.85 1.62 0.57 577 2.68 1.52 0.57 601 29 18 2.45 2.45 1.00 475 2.25 2.25 1.00 504 2.08 2.08 1.00 524 29 20 2.58 2.50 0.97 495 2.40 2.33 0.97 519 2.23 2.16 0.97 548 29 22 2.73 2.32 0.85 514 2.55 2.17 0.85 543 2.38 2.02 0.85 563 29 24 2.88 2.10 0.73 534 2.70 1.97 0.73 558 2.55 1.86 0.73 582 29 26 3.03 1.85 0.61 553 2.85 1.74 0.61 577 2.68 1.63 0.61 601 30 18 2.45 2.45 1.00 475 2.25 2.25 1.00 504 2.08 2.08 1.00 524 30 20 2.58 2.58 1.00 495 2.40 2.40 1.00 519 2.23 2.23 1.00 548 30 22 2.73 2.43 0.89 514 2.55 2.27 0.89 543 2.38 2.11 0.89 563 30 24 2.88 2.21 0.77 534 2.70 2.08 0.77 558 2.55 1.96 0.77 582 30 26 3.03 1.97 0.65 553 2.85 1.85 0.65 577 2.68 1.74 0.65 601 31 18 2.45 2.45 1.00 475 2.25 2.25 1.00 504 2.08 2.08 1.00 524 31 20 2.58 2.58 1.00 495 2.40 2.40 1.00 519 2.23 2.23 1.00 548 31 22 2.73 2.53 0.93 514 2.55 2.37 0.93 543 2.38 2.21 0.93 563 31 24 2.88 2.33 0.81 534 2.70 2.19 0.81 558 2.55 2.07 0.81 582 31 26 3.03 2.09 0.69 553 2.85 1.97 0.69 577 2.68 1.85 0.69 601 32 18 2.45 2.45 1.00 475 2.25 2.25 1.00 504 2.08 2.08 1.00 524 32 20 2.58 2.58 1.00 495 2.40 2.40 1.00 519 2.23 2.23 1.00 548 32 22 2.73 2.64 0.97 514 2.55 2.47 0.97 543 2.38 2.30 0.97 563 32 24 2.88 2.44 0.85 534 2.70 2.30 0.85 558 2.55 2.17 0.85 582 32 26 3.03 2.21 0.73 553 2.85 2.08 0.73 577 2.68 1.95 0.73 601
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH624A
Page 19
19
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-FH35VE
CAPACITY: 3.5 kW SHF: 0.84 INPUT: 820 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
21 25 27 30
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 4.11 2.71 0.66 656 3.94 2.60 0.66 689 3.78 2.49 0.66 722 3.64 2.40 0.66 754 21 20 4.29 2.32 0.54 689 4.11 2.22 0.54 730 3.99 2.15 0.54 746 3.85 2.08 0.54 779 22 18 4.11 2.88 0.70 656 3.94 2.76 0.70 689 3.78 2.65 0.70 722 3.64 2.55 0.70 754 22 20 4.29 2.49 0.58 689 4.11 2.39 0.58 730 3.99 2.31 0.58 746 3.85 2.23 0.58 779 22 22 4.46 2.05 0.46 713 4.31 1.98 0.46 759 4.20 1.93 0.46 779 4.03 1.85 0.46 812 23 18 4.11 3.04 0.74 656 3.94 2.91 0.74 689 3.78 2.80 0.74 722 3.64 2.69 0.74 754 23 20 4.29 2.66 0.62 689 4.11 2.55 0.62 730 3.99 2.47 0.62 746 3.85 2.39 0.62 779 23 22 4.46 2.23 0.50 713 4.31 2.15 0.50 759 4.20 2.10 0.50 779 4.03 2.01 0.50 812 24 18 4.11 3.21 0.78 656 3.94 3.07 0.78 689 3.78 2.95 0.78 722 3.64 2.84 0.78 754 24 20 4.29 2.83 0.66 689 4.11 2.71 0.66 730 3.99 2.63 0.66 746 3.85 2.54 0.66 779 24 22 4.46 2.41 0.54 713 4.31 2.32 0.54 759 4.20 2.27 0.54 779 4.03 2.17 0.54 812 24 24 4.69 1.97 0.42 746 4.52 1.90 0.42 787 4.41 1.85 0.42 812 4.27 1.79 0.42 853 25 18 4.11 3.37 0.82 656 3.94 3.23 0.82 689 3.78 3.10 0.82 722 3.64 2.98 0.82 754 25 20 4.29 3.00 0.70 689 4.11 2.88 0.70 730 3.99 2.79 0.70 746 3.85 2.70 0.70 779 25 22 4.46 2.59 0.58 713 4.31 2.50 0.58 759 4.20 2.44 0.58 779 4.03 2.33 0.58 812 25 24 4.69 2.16 0.46 746 4.52 2.08 0.46 787 4.41 2.03 0.46 812 4.27 1.96 0.46 853 26 18 4.11 3.54 0.86 656 3.94 3.39 0.86 689 3.78 3.25 0.86 722 3.64 3.13 0.86 754 26 20 4.29 3.17 0.74 689 4.11 3.04 0.74 730 3.99 2.95 0.74 746 3.85 2.85 0.74 779 26 22 4.46 2.77 0.62 713 4.31 2.67 0.62 759 4.20 2.60 0.62 779 4.03 2.50 0.62 812 26 24 4.69 2.35 0.50 746 4.52 2.26 0.50 787 4.41 2.21 0.50 812 4.27 2.14 0.50 853 26 26 4.83 1.84 0.38 787 4.69 1.78 0.38 828 4.62 1.76 0.38 853 4.48 1.70 0.38 877 27 18 4.11 3.70 0.90 656 3.94 3.54 0.90 689 3.78 3.40 0.90 722 3.64 3.28 0.90 754 27 20 4.29 3.34 0.78 689 4.11 3.21 0.78 730 3.99 3.11 0.78 746 3.85 3.00 0.78 779 27 22 4.46 2.95 0.66 713 4.31 2.84 0.66 759 4.20 2.77 0.66 779 4.03 2.66 0.66 812 27 24 4.69 2.53 0.54 746 4.52 2.44 0.54 787 4.41 2.38 0.54 812 4.27 2.31 0.54 853 27 26 4.83 2.03 0.42 787 4.69 1.97 0.42 828 4.62 1.94 0.42 853 4.48 1.88 0.42 877 28 18 4.11 3.87 0.94 656 3.94 3.70 0.94 689 3.78 3.55 0.94 722 3.64 3.42 0.94 754 28 20 4.29 3.52 0.82 689 4.11 3.37 0.82 730 3.99 3.27 0.82 746 3.85 3.16 0.82 779 28 22 4.46 3.12 0.70 713 4.31 3.01 0.70 759 4.20 2.94 0.70 779 4.03 2.82 0.70 812 28 24 4.69 2.72 0.58 746 4.52 2.62 0.58 787 4.41 2.56 0.58 812 4.27 2.48 0.58 853 28 26 4.83 2.22 0.46 787 4.69 2.16 0.46 828 4.62 2.13 0.46 853 4.48 2.06 0.46 877 29 18 4.11 4.03 0.98 656 3.94 3.86 0.98 689 3.78 3.70 0.98 722 3.64 3.57 0.98 754 29 20 4.29 3.69 0.86 689 4.11 3.54 0.86 730 3.99 3.43 0.86 746 3.85 3.31 0.86 779 29 22 4.46 3.30 0.74 713 4.31 3.19 0.74 759 4.20 3.11 0.74 779 4.03 2.98 0.74 812 29 24 4.69 2.91 0.62 746 4.52 2.80 0.62 787 4.41 2.73 0.62 812 4.27 2.65 0.62 853 29 26 4.83 2.42 0.50 787 4.69 2.35 0.50 828 4.62 2.31 0.50 853 4.48 2.24 0.50 877 30 18 4.11 4.11 1.00 656 3.94 3.94 1.00 689 3.78 3.78 1.00 722 3.64 3.64 1.00 754 30 20 4.29 3.86 0.90 689 4.11 3.70 0.90 730 3.99 3.59 0.90 746 3.85 3.47 0.90 779 30 22 4.46 3.48 0.78 713 4.31 3.36 0.78 759 4.20 3.28 0.78 779 4.03 3.14 0.78 812 30 24 4.69 3.10 0.66 746 4.52 2.98 0.66 787 4.41 2.91 0.66 812 4.27 2.82 0.66 853 30 26 4.83 2.61 0.54 787 4.69 2.53 0.54 828 4.62 2.49 0.54 853 4.48 2.42 0.54 877 31 18 4.11 4.11 1.00 656 3.94 3.94 1.00 689 3.78 3.78 1.00 722 3.64 3.64 1.00 754 31 20 4.29 4.03 0.94 689 4.11 3.87 0.94 730 3.99 3.75 0.94 746 3.85 3.62 0.94 779 31 22 4.46 3.66 0.82 713 4.31 3.53 0.82 759 4.20 3.44 0.82 779 4.03 3.30 0.82 812 31 24 4.69 3.28 0.70 746 4.52 3.16 0.70 787 4.41 3.09 0.70 812 4.27 2.99 0.70 853 31 26 4.83 2.80 0.58 787 4.69 2.72 0.58 828 4.62 2.68 0.58 853 4.48 2.60 0.58 877 32 18 4.11 4.11 1.00 656 3.94 3.94 1.00 689 3.78 3.78 1.00 722 3.64 3.64 1.00 754 32 20 4.29 4.20 0.98 689 4.11 4.03 0.98 730 3.99 3.91 0.98 746 3.85 3.77 0.98 779 32 22 4.46 3.84 0.86 713 4.31 3.70 0.86 759 4.20 3.61 0.86 779 4.03 3.46 0.86 812 32 24 4.69 3.47 0.74 746 4.52 3.34 0.74 787 4.41 3.26 0.74 812 4.27 3.16 0.74 853 32 26 4.83 2.99 0.62 787 4.69 2.91 0.62 828 4.62 2.86 0.62 853 4.48 2.78 0.62 877
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH624A
Page 20
20
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-FH35VE
CAPACITY: 3.5 kW SHF: 0.84 INPUT: 820 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
35 40 46
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 3.43 2.26 0.66 804 3.15 2.08 0.66 853 2.91 1.92 0.66 886 21 20 3.61 1.95 0.54 836 3.36 1.81 0.54 877 3.12 1.68 0.54 927 22 18 3.43 2.40 0.70 804 3.15 2.21 0.70 853 2.91 2.03 0.70 886 22 20 3.61 2.09 0.58 836 3.36 1.95 0.58 877 3.12 1.81 0.58 927 22 22 3.82 1.75 0.46 869 3.57 1.64 0.46 918 3.33 1.53 0.46 951 23 18 3.43 2.54 0.74 804 3.15 2.33 0.74 853 2.91 2.15 0.74 886 23 20 3.61 2.24 0.62 836 3.36 2.08 0.62 877 3.12 1.93 0.62 927 23 22 3.82 1.91 0.50 869 3.57 1.79 0.50 918 3.33 1.66 0.50 951 24 18 3.43 2.68 0.78 804 3.15 2.46 0.78 853 2.91 2.27 0.78 886 24 20 3.61 2.38 0.66 836 3.36 2.22 0.66 877 3.12 2.06 0.66 927 24 22 3.82 2.06 0.54 869 3.57 1.93 0.54 918 3.33 1.80 0.54 951 24 24 4.03 1.69 0.42 902 3.78 1.59 0.42 943 3.57 1.50 0.42 984 25 18 3.43 2.81 0.82 804 3.15 2.58 0.82 853 2.91 2.38 0.82 886 25 20 3.61 2.52 0.70 836 3.36 2.35 0.70 877 3.12 2.18 0.70 927 25 22 3.82 2.21 0.58 869 3.57 2.07 0.58 918 3.33 1.93 0.58 951 25 24 4.03 1.85 0.46 902 3.78 1.74 0.46 943 3.57 1.64 0.46 984 26 18 3.43 2.95 0.86 804 3.15 2.71 0.86 853 2.91 2.50 0.86 886 26 20 3.61 2.67 0.74 836 3.36 2.49 0.74 877 3.12 2.31 0.74 927 26 22 3.82 2.37 0.62 869 3.57 2.21 0.62 918 3.33 2.06 0.62 951 26 24 4.03 2.01 0.50 902 3.78 1.89 0.50 943 3.57 1.79 0.50 984 26 26 4.24 1.61 0.38 935 3.99 1.52 0.38 976 3.75 1.42 0.38 1017 27 18 3.43 3.09 0.90 804 3.15 2.84 0.90 853 2.91 2.61 0.90 886 27 20 3.61 2.81 0.78 836 3.36 2.62 0.78 877 3.12 2.43 0.78 927 27 22 3.82 2.52 0.66 869 3.57 2.36 0.66 918 3.33 2.19 0.66 951 27 24 4.03 2.17 0.54 902 3.78 2.04 0.54 943 3.57 1.93 0.54 984 27 26 4.24 1.78 0.42 935 3.99 1.68 0.42 976 3.75 1.57 0.42 1017 28 18 3.43 3.22 0.94 804 3.15 2.96 0.94 853 2.91 2.73 0.94 886 28 20 3.61 2.96 0.82 836 3.36 2.76 0.82 877 3.12 2.55 0.82 927 28 22 3.82 2.67 0.70 869 3.57 2.50 0.70 918 3.33 2.33 0.70 951 28 24 4.03 2.33 0.58 902 3.78 2.19 0.58 943 3.57 2.07 0.58 984 28 26 4.24 1.95 0.46 935 3.99 1.84 0.46 976 3.75 1.72 0.46 1017 29 18 3.43 3.36 0.98 804 3.15 3.09 0.98 853 2.91 2.85 0.98 886 29 20 3.61 3.10 0.86 836 3.36 2.89 0.86 877 3.12 2.68 0.86 927 29 22 3.82 2.82 0.74 869 3.57 2.64 0.74 918 3.33 2.46 0.74 951 29 24 4.03 2.50 0.62 902 3.78 2.34 0.62 943 3.57 2.21 0.62 984 29 26 4.24 2.12 0.50 935 3.99 2.00 0.50 976 3.75 1.87 0.50 1017 30 18 3.43 3.43 1.00 804 3.15 3.15 1.00 853 2.91 2.91 1.00 886 30 20 3.61 3.24 0.90 836 3.36 3.02 0.90 877 3.12 2.80 0.90 927 30 22 3.82 2.98 0.78 869 3.57 2.78 0.78 918 3.33 2.59 0.78 951 30 24 4.03 2.66 0.66 902 3.78 2.49 0.66 943 3.57 2.36 0.66 984 30 26 4.24 2.29 0.54 935 3.99 2.15 0.54 976 3.75 2.02 0.54 1017 31 18 3.43 3.43 1.00 804 3.15 3.15 1.00 853 2.91 2.91 1.00 886 31 20 3.61 3.39 0.94 836 3.36 3.16 0.94 877 3.12 2.93 0.94 927 31 22 3.82 3.13 0.82 869 3.57 2.93 0.82 918 3.33 2.73 0.82 951 31 24 4.03 2.82 0.70 902 3.78 2.65 0.70 943 3.57 2.50 0.70 984 31 26 4.24 2.46 0.58 935 3.99 2.31 0.58 976 3.75 2.17 0.58 1017 32 18 3.43 3.43 1.00 804 3.15 3.15 1.00 853 2.91 2.91 1.00 886 32 20 3.61 3.53 0.98 836 3.36 3.29 0.98 877 3.12 3.05 0.98 927 32 22 3.82 3.28 0.86 869 3.57 3.07 0.86 918 3.33 2.86 0.86 951 32 24 4.03 2.98 0.74 902 3.78 2.80 0.74 943 3.57 2.64 0.74 984 32 26 4.24 2.63 0.62 935 3.99 2.47 0.62 976 3.75 2.32 0.62 1017
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH624A
Page 21
21
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-FH50VE
CAPACITY: 5.0 kW SHF: 0.73 INPUT: 1380 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
21 25 27 30
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 5.88 3.23 0.55 1104 5.63 3.09 0.55 1159 5.40 2.97 0.55 1214 5.20 2.86 0.55 1270 21 20 6.13 2.63 0.43 1159 5.88 2.53 0.43 1228 5.70 2.45 0.43 1256 5.50 2.37 0.43 1311 22 18 5.88 3.47 0.59 1104 5.63 3.32 0.59 1159 5.40 3.19 0.59 1214 5.20 3.07 0.59 1270 22 20 6.13 2.88 0.47 1159 5.88 2.76 0.47 1228 5.70 2.68 0.47 1256 5.50 2.59 0.47 1311 22 22 6.38 2.23 0.35 1201 6.15 2.15 0.35 1277 6.00 2.10 0.35 1311 5.75 2.01 0.35 1366 23 18 5.88 3.70 0.63 1104 5.63 3.54 0.63 1159 5.40 3.40 0.63 1214 5.20 3.28 0.63 1270 23 20 6.13 3.12 0.51 1159 5.88 3.00 0.51 1228 5.70 2.91 0.51 1256 5.50 2.81 0.51 1311 23 22 6.38 2.49 0.39 1201 6.15 2.40 0.39 1277 6.00 2.34 0.39 1311 5.75 2.24 0.39 1366 24 18 5.88 3.94 0.67 1104 5.63 3.77 0.67 1159 5.40 3.62 0.67 1214 5.20 3.48 0.67 1270 24 20 6.13 3.37 0.55 1159 5.88 3.23 0.55 1228 5.70 3.14 0.55 1256 5.50 3.03 0.55 1311 24 22 6.38 2.74 0.43 1201 6.15 2.64 0.43 1277 6.00 2.58 0.43 1311 5.75 2.47 0.43 1366 24 24 6.70 2.08 0.31 1256 6.45 2.00 0.31 1325 6.30 1.95 0.31 1366 6.10 1.89 0.31 1435 25 18 5.88 4.17 0.71 1104 5.63 3.99 0.71 1159 5.40 3.83 0.71 1214 5.20 3.69 0.71 1270 25 20 6.13 3.61 0.59 1159 5.88 3.47 0.59 1228 5.70 3.36 0.59 1256 5.50 3.25 0.59 1311 25 22 6.38 3.00 0.47 1201 6.15 2.89 0.47 1277 6.00 2.82 0.47 1311 5.75 2.70 0.47 1366 25 24 6.70 2.35 0.35 1256 6.45 2.26 0.35 1325 6.30 2.21 0.35 1366 6.10 2.14 0.35 1435 26 18 5.88 4.41 0.75 1104 5.63 4.22 0.75 1159 5.40 4.05 0.75 1214 5.20 3.90 0.75 1270 26 20 6.13 3.86 0.63 1159 5.88 3.70 0.63 1228 5.70 3.59 0.63 1256 5.50 3.47 0.63 1311 26 22 6.38 3.25 0.51 1201 6.15 3.14 0.51 1277 6.00 3.06 0.51 1311 5.75 2.93 0.51 1366 26 24 6.70 2.61 0.39 1256 6.45 2.52 0.39 1325 6.30 2.46 0.39 1366 6.10 2.38 0.39 1435 26 26 6.90 1.86 0.27 1325 6.70 1.81 0.27 1394 6.60 1.78 0.27 1435 6.40 1.73 0.27 1477 27 18 5.88 4.64 0.79 1104 5.63 4.44 0.79 1159 5.40 4.27 0.79 1214 5.20 4.11 0.79 1270 27 20 6.13 4.10 0.67 1159 5.88 3.94 0.67 1228 5.70 3.82 0.67 1256 5.50 3.69 0.67 1311 27 22 6.38 3.51 0.55 1201 6.15 3.38 0.55 1277 6.00 3.30 0.55 1311 5.75 3.16 0.55 1366 27 24 6.70 2.88 0.43 1256 6.45 2.77 0.43 1325 6.30 2.71 0.43 1366 6.10 2.62 0.43 1435 27 26 6.90 2.14 0.31 1325 6.70 2.08 0.31 1394 6.60 2.05 0.31 1435 6.40 1.98 0.31 1477 28 18 5.88 4.88 0.83 1104 5.63 4.67 0.83 1159 5.40 4.48 0.83 1214 5.20 4.32 0.83 1270 28 20 6.13 4.35 0.71 1159 5.88 4.17 0.71 1228 5.70 4.05 0.71 1256 5.50 3.91 0.71 1311 28 22 6.38 3.76 0.59 1201 6.15 3.63 0.59 1277 6.00 3.54 0.59 1311 5.75 3.39 0.59 1366 28 24 6.70 3.15 0.47 1256 6.45 3.03 0.47 1325 6.30 2.96 0.47 1366 6.10 2.87 0.47 1435 28 26 6.90 2.42 0.35 1325 6.70 2.35 0.35 1394 6.60 2.31 0.35 1435 6.40 2.24 0.35 1477 29 18 5.88 5.11 0.87 1104 5.63 4.89 0.87 1159 5.40 4.70 0.87 1214 5.20 4.52 0.87 1270 29 20 6.13 4.59 0.75 1159 5.88 4.41 0.75 1228 5.70 4.28 0.75 1256 5.50 4.13 0.75 1311 29 22 6.38 4.02 0.63 1201 6.15 3.87 0.63 1277 6.00 3.78 0.63 1311 5.75 3.62 0.63 1366 29 24 6.70 3.42 0.51 1256 6.45 3.29 0.51 1325 6.30 3.21 0.51 1366 6.10 3.11 0.51 1435 29 26 6.90 2.69 0.39 1325 6.70 2.61 0.39 1394 6.60 2.57 0.39 1435 6.40 2.50 0.39 1477 30 18 5.88 5.35 0.91 1104 5.63 5.12 0.91 1159 5.40 4.91 0.91 1214 5.20 4.73 0.91 1270 30 20 6.13 4.84 0.79 1159 5.88 4.64 0.79 1228 5.70 4.50 0.79 1256 5.50 4.35 0.79 1311 30 22 6.38 4.27 0.67 1201 6.15 4.12 0.67 1277 6.00 4.02 0.67 1311 5.75 3.85 0.67 1366 30 24 6.70 3.69 0.55 1256 6.45 3.55 0.55 1325 6.30 3.47 0.55 1366 6.10 3.36 0.55 1435 30 26 6.90 2.97 0.43 1325 6.70 2.88 0.43 1394 6.60 2.84 0.43 1435 6.40 2.75 0.43 1477 31 18 5.88 5.58 0.95 1104 5.63 5.34 0.95 1159 5.40 5.13 0.95 1214 5.20 4.94 0.95 1270 31 20 6.13 5.08 0.83 1159 5.88 4.88 0.83 1228 5.70 4.73 0.83 1256 5.50 4.57 0.83 1311 31 22 6.38 4.53 0.71 1201 6.15 4.37 0.71 1277 6.00 4.26 0.71 1311 5.75 4.08 0.71 1366 31 24 6.70 3.95 0.59 1256 6.45 3.81 0.59 1325 6.30 3.72 0.59 1366 6.10 3.60 0.59 1435 31 26 6.90 3.24 0.47 1325 6.70 3.15 0.47 1394 6.60 3.10 0.47 1435 6.40 3.01 0.47 1477 32 18 5.88 5.82 0.99 1104 5.63 5.57 0.99 1159 5.40 5.35 0.99 1214 5.20 5.15 0.99 1270 32 20 6.13 5.33 0.87 1159 5.88 5.11 0.87 1228 5.70 4.96 0.87 1256 5.50 4.79 0.87 1311 32 22 6.38 4.78 0.75 1201 6.15 4.61 0.75 1277 6.00 4.50 0.75 1311 5.75 4.31 0.75 1366 32 24 6.70 4.22 0.63 1256 6.45 4.06 0.63 1325 6.30 3.97 0.63 1366 6.10 3.84 0.63 1435 32 26 6.90 3.52 0.51 1325 6.70 3.42 0.51 1394 6.60 3.37 0.51 1435 6.40 3.26 0.51 1477
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH624A
Page 22
22
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-FH50VE
CAPACITY: 5.0 kW SHF: 0.73 INPUT: 1380 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
35 40 46
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 4.90 2.70 0.55 1352 4.50 2.48 0.55 1435 4.15 2.28 0.55 1490 21 20 5.15 2.21 0.43 1408 4.80 2.06 0.43 1477 4.45 1.91 0.43 1559 22 18 4.90 2.89 0.59 1352 4.50 2.66 0.59 1435 4.15 2.45 0.59 1490 22 20 5.15 2.42 0.47 1408 4.80 2.26 0.47 1477 4.45 2.09 0.47 1559 22 22 5.45 1.91 0.35 1463 5.10 1.79 0.35 1546 4.75 1.66 0.35 1601 23 18 4.90 3.09 0.63 1352 4.50 2.84 0.63 1435 4.15 2.61 0.63 1490 23 20 5.15 2.63 0.51 1408 4.80 2.45 0.51 1477 4.45 2.27 0.51 1559 23 22 5.45 2.13 0.39 1463 5.10 1.99 0.39 1546 4.75 1.85 0.39 1601 24 18 4.90 3.28 0.67 1352 4.50 3.02 0.67 1435 4.15 2.78 0.67 1490 24 20 5.15 2.83 0.55 1408 4.80 2.64 0.55 1477 4.45 2.45 0.55 1559 24 22 5.45 2.34 0.43 1463 5.10 2.19 0.43 1546 4.75 2.04 0.43 1601 24 24 5.75 1.78 0.31 1518 5.40 1.67 0.31 1587 5.10 1.58 0.31 1656 25 18 4.90 3.48 0.71 1352 4.50 3.20 0.71 1435 4.15 2.95 0.71 1490 25 20 5.15 3.04 0.59 1408 4.80 2.83 0.59 1477 4.45 2.63 0.59 1559 25 22 5.45 2.56 0.47 1463 5.10 2.40 0.47 1546 4.75 2.23 0.47 1601 25 24 5.75 2.01 0.35 1518 5.40 1.89 0.35 1587 5.10 1.79 0.35 1656 26 18 4.90 3.68 0.75 1352 4.50 3.38 0.75 1435 4.15 3.11 0.75 1490 26 20 5.15 3.24 0.63 1408 4.80 3.02 0.63 1477 4.45 2.80 0.63 1559 26 22 5.45 2.78 0.51 1463 5.10 2.60 0.51 1546 4.75 2.42 0.51 1601 26 24 5.75 2.24 0.39 1518 5.40 2.11 0.39 1587 5.10 1.99 0.39 1656 26 26 6.05 1.63 0.27 1573 5.70 1.54 0.27 1642 5.35 1.44 0.27 1711 27 18 4.90 3.87 0.79 1352 4.50 3.56 0.79 1435 4.15 3.28 0.79 1490 27 20 5.15 3.45 0.67 1408 4.80 3.22 0.67 1477 4.45 2.98 0.67 1559 27 22 5.45 3.00 0.55 1463 5.10 2.81 0.55 1546 4.75 2.61 0.55 1601 27 24 5.75 2.47 0.43 1518 5.40 2.32 0.43 1587 5.10 2.19 0.43 1656 27 26 6.05 1.88 0.31 1573 5.70 1.77 0.31 1642 5.35 1.66 0.31 1711 28 18 4.90 4.07 0.83 1352 4.50 3.74 0.83 1435 4.15 3.44 0.83 1490 28 20 5.15 3.66 0.71 1408 4.80 3.41 0.71 1477 4.45 3.16 0.71 1559 28 22 5.45 3.22 0.59 1463 5.10 3.01 0.59 1546 4.75 2.80 0.59 1601 28 24 5.75 2.70 0.47 1518 5.40 2.54 0.47 1587 5.10 2.40 0.47 1656 28 26 6.05 2.12 0.35 1573 5.70 2.00 0.35 1642 5.35 1.87 0.35 1711 29 18 4.90 4.26 0.87 1352 4.50 3.92 0.87 1435 4.15 3.61 0.87 1490 29 20 5.15 3.86 0.75 1408 4.80 3.60 0.75 1477 4.45 3.34 0.75 1559 29 22 5.45 3.43 0.63 1463 5.10 3.21 0.63 1546 4.75 2.99 0.63 1601 29 24 5.75 2.93 0.51 1518 5.40 2.75 0.51 1587 5.10 2.60 0.51 1656 29 26 6.05 2.36 0.39 1573 5.70 2.22 0.39 1642 5.35 2.09 0.39 1711 30 18 4.90 4.46 0.91 1352 4.50 4.10 0.91 1435 4.15 3.78 0.91 1490 30 20 5.15 4.07 0.79 1408 4.80 3.79 0.79 1477 4.45 3.52 0.79 1559 30 22 5.45 3.65 0.67 1463 5.10 3.42 0.67 1546 4.75 3.18 0.67 1601 30 24 5.75 3.16 0.55 1518 5.40 2.97 0.55 1587 5.10 2.81 0.55 1656 30 26 6.05 2.60 0.43 1573 5.70 2.45 0.43 1642 5.35 2.30 0.43 1711 31 18 4.90 4.66 0.95 1352 4.50 4.28 0.95 1435 4.15 3.94 0.95 1490 31 20 5.15 4.27 0.83 1408 4.80 3.98 0.83 1477 4.45 3.69 0.83 1559 31 22 5.45 3.87 0.71 1463 5.10 3.62 0.71 1546 4.75 3.37 0.71 1601 31 24 5.75 3.39 0.59 1518 5.40 3.19 0.59 1587 5.10 3.01 0.59 1656 31 26 6.05 2.84 0.47 1573 5.70 2.68 0.47 1642 5.35 2.51 0.47 1711 32 18 4.90 4.85 0.99 1352 4.50 4.46 0.99 1435 4.15 4.11 0.99 1490 32 20 5.15 4.48 0.87 1408 4.80 4.18 0.87 1477 4.45 3.87 0.87 1559 32 22 5.45 4.09 0.75 1463 5.10 3.83 0.75 1546 4.75 3.56 0.75 1601 32 24 5.75 3.62 0.63 1518 5.40 3.40 0.63 1587 5.10 3.21 0.63 1656 32 26 6.05 3.09 0.51 1573 5.70 2.91 0.51 1642 5.35 2.73 0.51 1711
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH624A
Page 23
23
PERFORMANCE DATA HEAT operation at Rated frequency
MUZ-FH25VE
CAPACITY: 3.2 kW INPUT: 580 W
INDOOR
DB (°C)
OUTDOOR WB (°C)
-10 -5 0 5 10 15 20
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT 15 2.02 377 2.43 452 2.85 510 3.26 551 3.68 586 4.06 603 4.48 615 21 1.92 406 2.30 481 2.72 534 3.10 574 3.52 603 3.90 621 4.30 644 26 1.73 435 2.14 510 2.53 563 2.94 603 3.36 632 3.74 650 4.16 667
MUZ-FH35VE
CAPACITY: 4.0 kW INPUT: 800 W
INDOOR
DB (°C)
OUTDOOR WB (°C)
-10 -5 0 5 10 15 20
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT 15 2.52 520 3.04 624 3.56 704 4.08 760 4.60 808 5.08 832 5.60 848 21 2.40 560 2.88 664 3.40 736 3.88 792 4.40 832 4.88 856 5.38 888 26 2.16 600 2.68 704 3.16 776 3.68 832 4.20 872 4.68 896 5.20 920
MUZ-FH50VE
CAPACITY: 6.0 kW INPUT: 1480 W
INDOOR
DB (°C)
OUTDOOR WB (°C)
-10 -5 0 5 10 15 20
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT 15 3.78 962 4.56 1154 5.34 1302 6.12 1406 6.90 1495 7.62 1539 8.40 1569 21 3.60 1036 4.32 1228 5.10 1362 5.82 1465 6.60 1539 7.32 1584 8.07 1643 26 3.24 1110 4.02 1302 4.74 1436 5.52 1539 6.30 1613 7.02 1658 7.80 1702
NOTE: Q : Total capacity (kW) INPUT : Total power input (W) DB: Dry-bulb temperature WB: Wet-bulb temperature
OBH624A
Page 24
24
MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE
9-2. R.V. COIL CONTROL
Heating
. . . . . . . . . . . . . . . . .
ON
Cooling
. . . . . . . . . . . . . . . . .
OFF
Dry
. . . . . . . . . . . . . . . . . . . .
OFF
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
ON
OFF
ON
OFF
Outdoor fan motor
Compressor
5 seconds 15 seconds
ON OFF
Compressor
Outdoor fan motor
R.V.coil
ON OFF
ON OFF
<COOL>
5 seconds
<HEAT>
5 seconds
9-1. OUTDOOR FAN MOTOR CONTROL
The fan motor turns ON/OFF, interlocking with the compressor. [ON] The fan motor turns ON 5 seconds before the compressor starts up. [OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
9-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR
Sensor Purpose
Actuator
Compressor
LEV
Outdoor fan
motor
R.V.coil
Indoor fan
motor
Defrost
heater
Discharge temperature thermistor
Protection
○○
Indoor coil temperature thermistor
Cooling: Coil frost prevention
Heating: High pressure protec­tion
○○
Defrost thermistor Heating: Defrosting
○○○○○
Fin temperature thermistor Protection
○○
Ambient temperature thermistor
Cooling: Low ambient tempera­ture operation
○○○
Heating: Defrosting (Heater)
Outdoor heat exchanger tem­perature thermistor
Cooling: Low ambient tempera­ture operation
○○○
Cooling: High pressure protec­tion
○○○
ACTUATOR CONTROL
9
OBH624A
Page 25
25
SERVICE FUNCTIONS
10
10-1. CHANGE IN DEFROST SETTING Changing defrost finish temperature
<JS> To change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P.C. board. (Refer to 11-6-1.)
Jumper wire
Defrost fi nish temperature (°C)
MUZ-FH25/35VE MUZ-FH50VE
JS
Soldered (Initial setting) 5 10
None (Cut) 10 18
10-2. PRE-HEAT CONTROL SETTING
PRE-HEAT CONTROL MUZ-FH25/35
When moisture gets into the refrigerant cycle, it may interfere the start-up of the compressor at low discharge tempera­ture. The pre-heat control prevents this interference. The pre-heat control turns ON when the discharge temperature is 20°C or below. When the pre-heat control turns ON, the compressor is energized. (About 50 W)
MUZ-FH50
Prolonged low load operation, in which the thermostat is OFF for a long time, at low outside temperature (0°C or less) may cause the following troubles. To prevent those troubles, activate the pre-heat control.
1) If moisture gets into the refrigerant cycle and freezes, it may interfer the start-up of the compressor.
2) If liquid refrigerant collects in the compressor, a failure in the compressor may occur. The pre-heat control turns ON when the compressor temperature is 20°C or below. When the pre-heat control turns ON,
the compressor is energized. (About 70 W)
Pre-heat control setting
<JK> ON: To activate the pre-heat control, cut JK wire of the inverter P.C. board. OFF: To deactivate the pre-heat control, solder JK wire of the inverter P.C. board. (Refer to 11-6.1)
NOTE: When the inverter P.C. board is replaced, check JK wire, and cut/solder it if necessary.
MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE
OBH624A
Page 26
26
11-1. CAUTIONS ON TROUBLESHOOTING
1. Before troubleshooting, check the following
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for miswiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, and then after confirming the horizontal vane is closed, turn OFF the breaker and/or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board.
3) When removing the electrical parts, be careful of the residual voltage of smoothing capacitor.
4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components.
5) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
TROUBLESHOOTING
11
3. Troubleshooting procedure
1) Check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.
To make sure, check how many times the OPERATION INDICATOR lamp is flashing on and off before starting serv-
ice work.
2) Before servicing, check that the connector and terminal are connected properly.
3) When the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the components for bursting and discoloration.
4) Refer to 11-2 and 11-3.
Lead wiring
Housing point
<Incorrect>
<Correct>
MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE
OBH624A
Page 27
27
Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (11-3.) disappears, the memorized failure details can be recalled.
11-2. FAILURE MODE RECALL FUNCTION
1. Flow chart of failure mode recall function for the indoor/outdoor unit
NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
Does POWER lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: Either indoor or outdoor unit is abnormal. Beep is emit-
ted at the same timing as the blinking of POWER lamp.
2
Indoor unit is normal. But the outdoor unit might be abnormal because there are some abnor­malities that can not be recalled with this way. Confi rm if outdoor unit is abnormal according to the detailed outdoor unit failure mode recall function. (Refer to 11-2.2)
No
Yes
The cause of abnormality cannot be found because the abnormality does not recur.
Setting up the failure mode recall function
Turn ON the power supply. <Preparation of the remote controller>
While pressing OPERATION SELECT button and TEMP button on the remote
controller at the same time, press RESET button.
First, release RESET button.
Hold down the other two buttons for another 3 seconds. Make sure that the indicators
on the LCD screen shown in the right fi gure are all displayed. Then release the but- tons.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1
Judgment of indoor/outdoor abnormality
Before blinking, does POWER lamp stay ON for 3 seconds? Stays ON for 3 seconds (without beep): The outdoor unit is abnormal.
The indoor unit is abnormal. Check the blinking pattern, and identify the abnormal point with the indoor unit failure mode table. (Refer to indoor unit service manual.) Make sure to check at least two consecutive blinking cycles. 2
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller.
The outdoor unit is abnormal. Check the blinking pattern, and confi rm the abnormal point with the outdoor unit failure mode table. (Refer to 11-2.3) Make sure to check at least two consecutive blinking cycles.
3
Repair the failure parts.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" mentioned above.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed)
with the remote controller headed towards the indoor unit. Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
Operational procedure
Yes (Blinks)
No (OFF)
1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received.
2. Blinking pattern when the indoor unit is abnormal:
3.Blinking pattern when the outdoor unit is abnormal:
ON
OFF
Beeps
Repeated cycle Repeated cycle
ON
OFF
No beep Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5-
second interval
2.5-second OFF 3-second ON
Blinking at 0.5­second interval
Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5-
second interval
No beep Beeps
Repeated cycle
2.5-second OFF
3-second ON
Blinking at 0.5­second interval
Repeated cycle
Beeps
OBH624A
Page 28
28
2. Flow chart of the detailed outdoor unit failure mode recall function
2.Blinking pattern when outdoor unit is abnormal:
ON
OFF
No beep
Beeps
Repeated cycle
2.5-second OFF 3-second ON
Blinking at 0.5­second interval
No beep Beeps
Repeated cycle
2.5-second OFF 3-second ON
Blinking at 0.5-
second interval
Repeated cycle
Does POWER lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: The outdoor unit is abnormal. Beep is emitted
at the same timing as the blinking of POWER lamp. 2
Yes (Blinks
)
No (OFF)
The outdoor unit might be abnormal. Confi rm if outdoor unit is abnormal according to the following procedures.
Operational procedure
Confi rm that the remote controller is in the failure mode recall function.
With the remote controller headed towards the indoor unit, press TEMP
button to adjust the set temperature to 25°C. 1
1. Regardless of normal or abnormal condition, 2 short beeps are emitted as the signal is received.
The outdoor unit is abnormal. Check the blinking pattern, and identify the abnormal point with the out­door unit failure mode table (11-2.3.). Make sure to check at least two consecutive blinking cycles.
2
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller.
Repair the failure parts.
The outdoor unit is normal.
Release the failure mode recall function accord­ing to the left mentioned procedure.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" (11-2.1.).
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with
the remote controller headed towards the indoor unit.
Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.
4
Release the failure mode recall function according to "Releasing the failure mode recall function" men-
tioned above.
NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
4
The information regarding whether the
connected outdoor unit is a low-standby-
power model or a non-low-standby-power model will also be initialized.
(Default= compatible with a low-standby-
power model)
NOTE: It takes up to 1 minute to indicate the outdoor unit
abnormality.
Even if POWER lamp is not lighting, keep check-
ing at least 1 minute or longer.
OBH624A
Page 29
29
3. Outdoor unit failure mode table
POWER lamp
(Indoor unit)
Abnormal point
(Failure mode/protection)
LED indication
(Outdoor P.C. board)
Condition Remedy
Indoor/outdoor
unit failure
mode recall
function
Outdoor unit failure mode
recall function
OFF None (Normal)
—— —
1-time fl ash
2.5 seconds OFF
Indoor/outdoor communication, receiving error
Any signals from the inverter P.C. board cannot be received normally for 3 minutes.
•Refer to 11-5. How to check miswiring and serial signal error.
○○
Indoor/outdoor communication, receiving error
Although the inverter P.C. board sends signal "0", signal "1" has been received 30 consecutive times.
•Refer to 11-5.
How to check miswiring and serial signal error.
2-time fl ash
2.5 seconds OFF
Outdoor power system
Overcurrent protection cut-out operates 3 consecutive times within 1 minute after the compressor gets started.
Reconnect connectors. Refer to 11-5. "How to check inverter/ compressor". Check stop valve.
○○
3-time fl ash
2.5 seconds OFF
Discharge temperature thermistor
1-time fl ash every
2.5 seconds
Thermistor shorts or opens during compressor running.
Refer to 11-5. "Check of outdoor thermistors". Defective outdoor thermistors can be identifi ed by checking the blinking pattern of LED.
○○
Defrost thermistor Fin temperature thermistor 3-time fl ash
2.5 seconds OFF
P.C. board temperature thermistor
4-time fl ash
2.5 seconds OFF
Ambient temperature thermistor
2-time fl ash
2.5 seconds OFF
Outdoor heat exchanger temperature thermistor
4-time fl ash
2.5 seconds OFF
Overcurrent 11-time fl ash
2.5 seconds OFF
Large current fl ows into power module (IC700) (FH25/35)/ IGBT module (IC700) (FH50).
Reconnect compressor connector. Refer to 11-5. "How to check inverter/ compressor". Check stop valve.
Compressor synchronous abnormality (Compressor start-up failure protection)
12-time fl ash
2.5 seconds OFF
Waveform of compressor current is distorted.
Reconnect compressor connector. Refer to 11-5. "How to check inverter/ compressor".
5-time fl ash
2.5 seconds OFF
Discharge temperature
Temperature of discharge temperature thermistor exceeds 116°C, compressor stops. Compressor can restart if discharge temperature thermistor reads 100°C or less 3 minutes later.
Check refrigerant circuit and refrigerant amount. Refer to 11-5. "Check of LEV".
6-time fl ash
2.5 seconds OFF
High pressure
Temperature indoor coil thermistor exceeds 70°C in HEAT mode. Temperature defrost thermistor exceeds 70°C in COOL mode.
Check refrigerant circuit and refrigerant amount. Check stop valve.
7-time fl ash
2.5 seconds OFF
Fin temperature/ P.C. board temperature
7-time fl ash
2.5 seconds OFF
Temperature of fi n temperature thermistor on the inverter P.C. board exceeds 75 ~ 86°C (FH25/35)/75 ~ 80°C (FH50), or temperature of P.C. board temperature thermistor on the inverter P.C. board exceeds 72 ~ 85°C (FH25/35)/70 ~ 75°C (FH50).
Check around outdoor unit. Check outdoor unit air passage. Refer to 11-5. "Check of outdoor fan motor".
8-time fl ash
2.5 seconds OFF
Outdoor fan motor
Outdoor fan has stopped 3 times in a row within 30 seconds after outdoor fan start-up.
Refer to 11-5. "Check of outdoor fan motor". Refer to 11-5.
"Check
of inverter P.C. board".
• —
9-time fl ash
2.5 seconds OFF
Nonvolatile memory data 5-time fl ash
2.5 seconds OFF
Nonvolatile memory data cannot be read properly.
Replace the inverter P.C. board.
○○
Power module (IC700) (FH25/35) IGBT module (IC700) (FH50)
6-time fl ash
2.5 seconds OFF
The interface short circuit occurs in the output of the power module (IC700) (FH25/35)/IGBT module (IC700) (FH50). The compressor winding shorts circuit.
Refer to 11-5. "How to check inverter/ compressor".
10-time fl ash
2.5 seconds OFF
Discharge temperature
Temperature of discharge temperature thermistor has been 50°C or less for 20 minutes.
Refer to 11-5. "Check of LEV". Check refrigerant circuit and refrigerant amount.
•—
11-time fl ash
2.5 seconds OFF
Bus-bar voltage (DC) 8-time fl ash
2.5 seconds OFF
Bus-bar voltage of inverter cannot be detected normally.
Refer to 11-5. "How to check inverter/ compressor".
• —
Each phase current of compressor
9-time fl ash
2.5 seconds OFF
Each phase current of compressor cannot be detected normally.
14-time fl ash
2.5 seconds OFF
Stop valve (Closed valve) 14-time fl ash
2.5 seconds OFF
Closed valve is detected by compressor current.
Check stop valve.
○○
NOTE: Blinking patterns of this mode differ from the ones of TROUBLESHOOTING CHECK TABLE (11-3.).
OBH624A
Page 30
30
11-3. TROUBLESHOOTING CHECK TABLE
No. Symptom LED indication
Abnormal point/
Condition
Condition Remedy
1
Outdoor unit does not op­erate.
1-time fl ash every
2.5 seconds
Outdoor power sys­tem
Overcurrent protection cut-out operates 3 consecutive times within 1 minute after the compressor gets started.
Reconnect connector of compres­sor. Refer to 11-5.
"How to check in­verter/compressor". Check stop valve.
2
Outdoor thermistors Discharge temperature thermistor, fi n temperature thermistor,
defrost thermistor, P.C. board temperature thermistor, outdoor heat exchanger temperature thermistor or ambient tempera­ture thermistor shorts or opens during compressor running.
Refer to 11-5. "Check of outdoor thermistors".
3
Outdoor control sys­tem
Nonvolatile memory data cannot be read properly. (POWER lamp of the indoor unit lights up or fl ashes 7-time.)
Replace inverter P.C. board.
4
6-time fl ash
2.5 seconds OFF
Serial signal The communication fails between the indoor and outdoor unit
for 3 minutes.
Check connection between the in­verter P.C. board and the relay P.C. board. (FH50) Refer to 11-5. "How to check miswiring and serial signal error.
5
11-time fl ash
2.5 seconds OFF
Stop valve/ Closed valve
Closed valve is detected by compressor current. Check stop valve.
6
14-time fl ash
2.5 seconds OFF
Outdoor unit (Other abnormality)
Outdoor unit is defective. Refer to 11-2.2. "Flow chart of the
detailed outdoor unit failure mode recall function".
7
'Outdoor unit stops and restarts 3 minutes later' is repeated.
2-time fl ash
2.5 seconds OFF
Overcurrent protec­tion
Large current fl ows into power module (IC700) (FH25/35)/ IGBT module (IC700) (FH50).
Reconnect connector of compressor. Refer to 11-5. "How to check in­verter/compressor". Check stop valve.
8
3-time fl ash
2.5 seconds OFF
Discharge tempera­ture overheat pro­tection
Temperature of discharge temperature thermistor exceeds 116°C, compressor stops. Compressor can restart if discharge temperature thermistor reads 100°C or less 3 minutes later.
Check refrigerant circuit and refrig­erant amount. Refer to 11-5. "Check of LEV".
9
4-time fl ash
2.5 seconds OFF
Fin temperature /P.C. board tem­perature thermistor overheat protection
Temperature of fi n temperature thermistor on the heat sink ex- ceeds 75 ~ 86°C (FH25/35)/75 ~ 80°C (FH50) or temperature of P.C. board temperature thermistor on the inverter P.C.board exceeds 72 ~ 85°C (FH25/35)/70 ~ 75°C (FH50).
Check around outdoor unit. Check outdoor unit air passage. Refer to 11-5. "Check of outdoor fan motor".
10
5-time fl ash
2.5 seconds OFF
High pressure pro­tection
Indoor coil thermistor exceeds 70°C in HEAT mode. Defrost thermistor exceeds 70°C in COOL mode.
Check refrigerant circuit and refrig­erant amount. Check stop valve.
11
8-time fl ash
2.5 seconds OFF
Compressor syn­chronous abnormal­ity
The waveform of compressor current is distorted.
Reconnect connector of compressor. Refer to 11-5. "How to check in­verter/compressor".
12
10-time fl ash
2.5 seconds OFF
Outdoor fan motor Outdoor fan has stopped 3 times in a row within 30 seconds
after outdoor fan start-up.
Refer to 11-5.
"Check of outdoor fan motor. Refer to 11-5. "Check of inverter P.C. board.
13
12-time fl ash
2.5 seconds OFF
Each phase current of compressor
Each phase current of compressor cannot be detected nor­mally.
Refer to 11-5.
"How to check in­verter/compressor".
14
13-time fl ash
2.5 seconds OFF
Bus-bar voltage (DC)
Bus-bar voltage of inverter cannot be detected normally. It occurs with following case.
Instantaneous power voltage drop. (Short time power failure) (FH50) Refer to 11-5.
"Check of power supply". (FH50) Refer to 11-5. "How to check in­verter/compressor".
15
Outdoor unit operates.
1-time fl ash
2.5 seconds OFF
Frequency drop by current protection
FH25/35 When the input current exceeds approximately
10A (FH25)/10.5A (FH35), compressor frequency lowers.
The unit is normal, but check the following. Check if indoor fi lters are clogged. Check if refrigerant is short. Check if indoor/outdoor unit air circulation is short cycled.
FH50 Current from power outlet is nearing breaker ca-
pacity.
16
3-time fl ash
2.5 seconds OFF
Frequency drop by high pressure pro­tection
Temperature of indoor coil thermistor exceeds 55°C in HEAT mode, compressor frequency lowers.
Frequency drop by defrosting in COOL mode
Indoor coil thermistor reads 8°C or less in COOL mode, com­pressor frequency lowers.
17
4-time fl ash
2.5 seconds OFF
Frequency drop by discharge tempera­ture protection
Temperature of discharge temperature thermistor exceeds 111°C, compressor frequency lowers.
Check refrigerant circuit and refrig­erant amount. Refer to 11-5.
"Check of LEV". Refer to 11-5. "Check of outdoor thermistors".
18
MUZ-FH25/35
5-time fl ash
2.5 seconds OFF
Outside temperature thermistor protec­tion
When the outside temperature thermistor shorts or opens, protective operation without that thermistor is performed.
Refer to 11-5. Check of outdoor thermistors.
OBH624A
Page 31
31
No. Symptom LED indication
Abnormal point/
Condition
Condition Remedy
19
Outdoor unit operates.
7-time fl ash
2.5 seconds OFF
Low discharge tem­perature protection
Temperature of discharge temperature thermistor has been 50°C or less for 20 minutes.
Refer to 11-5. "Check of LEV". Check refrigerant circuit and refrig­erant amount.
20
8-time fl ash
2.5 seconds OFF
MUZ-FH25/35
PAM protection PAM: Pulse Ampli­tude Modulation
The overcurrent fl ows into PFC (Power factor correction : IC820) or the bus-bar voltage reaches 394 V or more, PAM stops and restarts.
This is not malfunction. PAM pro­tection will be activated in the fol­lowing cases: 1 Instantaneous power voltage
drop. (Short time power failure)
2 When the power supply voltage
is high.
MUZ-FH50
Zero cross detecting circuit
Zero cross signal cannot be detected. It occurs with following cases.
1 Instantaneous power voltage
drop. (Short time power failure) 2 Distortion of primary voltage Refer to 11-5.
"Check of power
supply".
21
9-time fl ash
2.5 seconds OFF
Inverter check mode The connector of compressor is disconnected, inverter check
mode starts.
Check if the connector of the com­pressor is correctly connected. Refer to 11-5. "How to check inverter/compressor".
NOTE: 1. The location of LED is illustrated at the right fi gure. Refer to 11-6.1.
2. LED is lighted during normal operation. The fl ashing frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the fl ashing frequency is “2”.
ON OFF
2.5-second OFF
2.5-second OFF
0.5-second ON
0.5-second ON LED
Flashing
MUZ-FH25/35VE
Inverter P.C. board
MUZ-FH50VE
LED
Flashing
OBH624A
Page 32
32
11-4. TROUBLE CRITERION OF MAIN PARTS
MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE
Part name Check method and criterion Figure
Defrost thermistor (RT61) Fin temperature
thermistor (RT64) Ambient temperature
thermistor (RT65) Outdoor heat exchanger
temperature thermistor (RT68)
Measure the resistance with a tester. Refer to 11-6. “Test point diagram and voltage”, 1. “Inverter P.C.
board”, for the chart of thermistor.
Discharge temperature thermistor (RT62)
Measure the resistance with a tester. Before measurement, hold the thermistor with your hands to warm it up.
Refer to 11-6. “Test point diagram and voltage”, 1. “Inverter P.C. board”, for the chart of thermistor.
Compressor
Measure the resistance between terminals using a tester. (Temperature: -10 ~ 40°C)
Normal (Ω)
MUZ-FH25/35VE MUZ-FH50VE
U-V
U-W
V-W
1.66 ~ 2.26 0.87 ~ 1.18
Outdoor fan motor
Measure the resistance between lead wires using a tester. (Temperature: -10 ~ 40°C)
Color of lead wire
Normal (Ω)
MUZ-FH25/35VE MUZ-FH50VE
RED – BLK
BLK – WHT
WHT – RED
12 ~ 16 12 ~ 17
R. V. coil (21S4)
Measure the resistance using a tester. (Temperature: -10 ~ 40°C)
Normal (kΩ)
MUZ-FH25/35VE MUZ-FH50VE
1.41 ~ 2.00 1.19 ~ 1.78
Expansion valve coil (LEV)
Measure the resistance using a tester. (Temperature: -10 ~ 40°C)
Color of lead wire Normal (Ω)
RED – ORN
37 ~ 54
RED – WHT
RED – BLU RED – YLW
RED
(+12V)
YLW
BLU
WHT ORN
LEV
W
U
V
WHT
RED BLK
W
U
V
WHT
RED BLK
OBH624A
Page 33
33
11-5. TROUBLESHOOTING FLOW
A How to check inverter/compressor
Refer to 11-5. “Check of compressor operation time”. Does the compressor operate continuously?
Refer to 11-5. “Check of compressor start failure”.
OK.
No
Yes
Refer to 11-5. “Check of compressor winding”. Is the compressor normal?
Replace the compressor.
No
Yes
B Check of open phase
C Check of compressor
With the connector between the compressor and the power module (IC700) (MUZ-FH25/35)/IGBT module (IC700) (MUZ-FH50) disconnected, activate the inverter and check if the inverter is normal by measuring the voltage balance between the termi­nals.
Output voltage is 50 - 130 V. (The voltage may differ according to the tester.) << Operation method>>
Start cooling or heating operation by pressing EMERGENCY OPERATION switch on the indoor unit. (TEST RUN OPERA-
TION: Refer to 8-3.) <<Measurement point>> At 3 points BLK (U)-WHT (V) BLK (U)-RED (W) WHT(V)-RED (W)
NOTE: 1. Output voltage varies according to power supply voltage.
2. Measure the voltage by analog type tester.
3. During this check, LED of the inverter P.C. board fl ashes 9 times. (Refer to 11-6.1.)
Measure AC voltage between the lead wires at 3 points.
Are the voltages balanced?
Disconnect the connector between the compressor and the power module (IC700) (MUZ-FH25/35)/IGBT module (IC700) (MUZ-FH50).
Replace the inverter P.C. board.
Check the voltage between terminals.
Check the compressor.
See 11-5. “Check of compressor”.
No
Yes
See 11-5. “Check of open phase”.
OBH624A
Page 34
34
F Check of compressor start failure
D Check of compressor winding
E Check of compressor operation time
● Disconnect the connector between the compressor and the power module (IC700) (MUZ-FH25/35)/IGBT module (IC700) (MUZ-FH50), and measure the resistance between the compressor terminals.
<<Measurement point>> at 3 points BLK-WHT BLK-RED WHT-RED <<Judgement>> Refer to 11-4. 0 [Ω] ················Abnormal [short] Infinite [Ω] ·······Abnormal [open] NOTE: Be sure to zero the ohmmeter before measurement.
Measure the resistance between the lead wires at 3 points.
1 Heat the compressor with a drier for about 20 minutes. Do not recover refrigerant gas while heating.
Heating part
Connect the compressor and activate the inverter. Then measure the time until the inverter stops due to over current. <<Operation method>> Start heating or cooling operation by pressing EMERGENCY OPERATION switch on the indoor unit. (TEST RUN OPERATION: Refer to 8-3.) <<Measurement>> Measure the time from the start of compressor to the stop of compressor due to overcurrent.
Compressor starts
Abnormal (IPM failure) (Compressor winding short)
Abnormal (Compressor lock out) (Starting defect)
Abnormal (Poor contact,) (Outdoor P.C. board defect) (Disconnected connector)
Abnormal (Refrigerant circuit defect) (Closed valve)
Normal
0 second 1 second
2 seconds
10 seconds
10 minutes
<<Judgement>>
After the compressor is heated with a drier, does the compressor start? 1
Replace the compressor.
Compressor start failure. Activate pre-heat control. (Refer to 10-2. "PRE-HEAT CONTROL SETTING")
No
Yes
Does the compressor run for 10 seconds or more after it starts?
Check the refrigerant circuit. Check the stop valve.
Yes
No
Confi rm that ~ is normal.
•Electrical circuit check . Contact of the compressor connector . Output voltage of inverter P.C. board and balance of them (See 11-5. ) . Direct current voltage between DB61(+) and (-) (MUZ-FH25/35)/JP715(+)
and JP30(-) (MUZ-FH50) on the inverter P.C. board
. Voltage between outdoor terminal block S1-S2
OBH624A
Page 35
35
G Check of outdoor thermistors
Replace the thermistor except RT64. When RT64 is abnormal, replace the inverter P.C. board.
Replace the inverter P.C. board.
No
No
Is the resistance of thermistor normal? (Refer to 11-6.1.)
Reconnect the connector of thermistor. Turn ON the power supply and press EMERGENCY OPERATION switch.
Does the unit operate for 10 minutes or more without showing thermistor abnormality?
OK. (Cause is poor contact.)
Yes
Yes
Disconnect the connector of thermistor in the outdoor P.C. board (see below table), and measure the resistance of thermistor.
MUZ-FH25/35
Thermistor Symbol Connector, Pin No. Board
Defrost RT61 Between CN641 pin1 and pin2
Inverter P.C. board
Discharge temperature RT62 Between CN641 pin3 and pin4 Fin temperature RT64 Between CN642 pin1 and pin2 Ambient temperature RT65 Between CN643 pin1 and pin2 Outdoor heat exchanger temperature RT68 Between CN644 pin1 and pin3
MUZ-FH50
Thermistor Symbol Connector, Pin No. Board
Defrost RT61 Between CN671 pin1 and pin2
Inverter P.C. board
Discharge temperature RT62 Between CN671 pin3 and pin4 Fin temperature RT64 Between CN673 pin1 and pin2 Ambient temperature RT65 Between CN672 pin1 and pin2 Outdoor heat exchanger temperature RT68 Between CN671 pin5 and pin6
OBH624A
Page 36
36
H Check of R.V. coil
First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 11-4. In case CN721 is disconnected or R.V. coil is open, voltage is generated between the terminal pins of the connector
although no signal is being transmitted to R.V. coil.
Check if CN721 is connected.
Is there 230 VAC between CN721 and
on the inverter P.C. board 3 minutes
after the power supply is turned ON?
No
Yes
Replace the inverter P.C. board.
Replace the 4-way valve.
Unit operates COOL mode even if it is set to HEAT mode.
Is there 230 VAC between CN721 and
on the inverter P.C. board 3 minutes
after the power supply is turned ON?
Yes
No
Replace the inverter P.C. board.
Replace the 4-way valve.
Unit operates HEAT mode even if it is set to COOL mode.
Disconnect connector between the compressor and the power module (IC700). Turn ON the power supply and press EMERGENCY OPERATION switch twice (HEAT mode).
Disconnect connector between the compressor and the power module (IC700). Turn ON the power supply and press EMERGENCY OPERATION switch once (COOL mode).
First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 11-4. In case CN602 is disconnected or R.V. coil is open, voltage is generated between the terminal pins of the connector
although no signal is being transmitted to R.V. coil.
Check if CN602 is connected.
Is there 230 VAC between CN602 and
on the inverter P.C. board 3 minutes
after the power supply is turned ON?
No
Yes
Replace the inverter P.C. board.
Replace the 4-way valve.
Unit operates COOL mode even if it is set to HEAT mode.
Is there 230 VAC between CN602 and
on the inverter P.C. board 3 minutes
after the power supply is turned ON?
Yes
No
Replace the inverter P.C. board.
Replace the 4-way valve.
Unit operates HEAT mode even if it is set to COOL mode.
Disconnect connector between the compressor and the IGBT module (IC700). Turn ON the power supply and press EMERGENCY OPERATION switch twice (HEAT mode).
Disconnect connector between the compressor and the IGBT module (IC700). Turn ON the power supply and press EMERGENCY OPERATION switch once (COOL mode).
MUZ-FH25/35
MUZ-FH50
OBH624A
Page 37
37
I Check of outdoor fan motor
Is the resistance between each ter­minal of outdoor fan motor normal? (Refer to 11-4.)
Disconnect CN932 from the inverter P.C. board, and turn on the power supply.
Rotate the outdoor fan motor manually and measure the voltage of CN931. Between 1(+) and 5(-) Between 2(+) and 5(-) Between 3(+) and 5(-)
Does the voltage between each terminal become 5 and 0 VDC repeatedly?
Does the outdoor fan motor rotate smoothly?
Replace the outdoor fan motor.
Replace the inverter P.C. board.
Yes
Yes
No
(Fixed to either 5 or 0 VDC)
No
No
Yes
Disconnect the connectors CN931 and CN932 from the inverter P.C. board. Check the connection between the connector CN931 and CN932.
OBH624A
Page 38
38
J Check of power supply
Is there voltage 230 VAC between the indoor terminal block S1 and S2?
No
Yes
Replace the indoor electronic control P.C. board.
Rectify indoor/outdoor connecting wire.
Yes
If light up, OK. If fl ash, refer to 11-3.
Does POWER lamp on the indoor unit light up?
Does LED on the inverter P.C. board light up or fl ash? (Refer to 11-6.1.)
No
Replace the inverter P.C. board.
Is there bus-bar voltage 260 - 370 VDC between DB61 (+) and DB61 (–) (MUZ-FH25/35)/325 - 370 VDC between JP715 (+) and JP30 (–) (MUZ-FH50) on the inverter P.C. board? (Refer to 11-6.1.)
No
Check the electric parts in main circuit.
Yes
Yes
No
Disconnect the connector between the compressor and the power module (IC700) (MUZ-FH25/35)/IGBT module (IC700) (MUZ-FH50). Turn ON power supply and press EMERGENCY OPERATION switch.
Inverter P.C. board (Solder side)
DB61
260 - 370 VDC
MUZ-FH25/35
325 -370 VDC
JP30
JP715
MUZ-FH50
OBH624A
Page 39
39
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1
Expansion valve operates in full-opening direction.
OK
NOTE: After check of LEV, do the undermentioned operations.
1. Turn OFF the power supply and turn it ON again.
2. Press RESET button on the remote controller.
1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received.
Measure each voltage between connector pins of CN724 on the inverter P.C. board.
1. Pin (-) — Pin (+)
2. Pin (-) — Pin (+)
3. Pin (-) — Pin (+)
4. Pin (-) — Pin (+) Is there about 3 - 5 VAC between each?
NOTE: Measure the voltage by an analog
tester.
Properly fi x the LEV coil to the expansion valve.
Replace the inverter P.C. board.
Replace the LEV coil.
Replace the expansion valve.
Is LEV coil properly fi xed to the expansion valve?
Does the resistance of LEV coil have the characteristics? (Refer to 11-4.)
Do you hear the expansion valve "click, click·······"? Do you feel the expansion valve vibrate on touching it ?
Turn ON the power supply. <Preparation of the remote controller>
While pressing both OPERATION SELECT button and TEMP button on the remote controller at the same time, press RESET button. First, release RESET button.
Hold down the other two buttons for another 3 sec-
onds. Make sure that the indicators on the LCD screen shown in the right fi gure are all displayed. Then re- lease the buttons.
Yes
No
No
Yes
No
Yes
No
Yes
K Check of LEV (Expansion valve)
OBH624A
Page 40
40
Check the outdoor fan motor. (Refer to 11-5. .)
Is the fuse (F901) blown on the in­verter P.C. board?
Check the connection of the connectors (CN931, CN932) of the outdoor fan motor. If the connection is poor, make it correct.
Operate the outdoor unit by starting EMERGENCY OPERATION.
Check the LED indication on the in­verter P.C. board. Does the LED fl ash 10 times?
Replace the inverter P.C. board.
Check the corresponding parts following LED indication. (Refer to 11-3.)
Yes
No
Yes (10-time fl ash)
No
L Check of inverter P.C. board
OBH624A
Page 41
41
M How to check miswiring and serial signal error
Turn OFF inverter-controlled lighting equipment. Turn OFF the power supply and then turn ON again. Press EMERGENCY OPERATION switch.
A
Is serial signal error indicated 6 minutes later?
B
Yes
Reinstall either the unit or the light away from each other. Attach a fi lter on remote control receiving section of the indoor unit.
No
Turn the power supply OFF.
Is there rated voltage in the power supply?
Yes
No
Check for incorrect indoor-outdoor connecting wiring.
Check the power supply.
A
Is there rated voltage between outdoor terminal block S1 and S2?
No
Yes
Check for miswiring, broken wires, and loose wire connection between the power supply and outdoor terminal block S1 and between the power supply and outdoor terminal block S2.
Wait for 2 or more minutes after the power supply is turned on. Touch S2 and S3 with tester probes and start the emergency operation.
When the emergency operation starts, does the rated voltage occur for 2 seconds between indoor terminal block S2 and S3?
Yes
Turn the power supply OFF.
Turn the power supply ON.
Wait for 2 or more minutes after the power supply is turned ON. Touch CN202 and JPG with tester probes and start the emergency operation.
During the emergency operation, does DC (2V or more) occur for 2 seconds between CN202
and JPG on the indoor electronic control P.C. board?
No
Does the indoor POWER lamp blink continuously 6 minutes after the emergency operation starts?
No
Does the outdoor LED light up?
Replace the indoor electronic control P.C. board.
Replace the indoor power P.C. board.
Yes
Yes
Does the outdoor LED blink 6 times?
Yes
Confi rm that the thermostat is OFF and wiring is not loose.
No
Does DC (6V or more) occur between indoor terminal block S2 and S3?
Yes
Replace the outdoor inverter P.C. board. 1
No
Turn the power supply OFF. Replace the indoor power P.C. board.
Start the emergency operation.
No
Yes
Repair completed.
Does DC (20V or more) occur between indoor terminal block S2 and S3 ?
No
Yes
Replace the outdoor inverter P.C. board. 1
Replace the indoor electronic control P.C. board.
1. Electric charge may remain immediately after the power supply is turned OFF. Perform the procedure after 3 minutes.
Replace the outdoor inverter P.C. board. 1
Turn the power supply ON.
Does the indoor POWER lamp blink continuously 6 minutes after the emergency operation starts?
Yes
No
Turn the power supply ON.
B
No
No
Was the indoor unit ever connected to the Multi (MXZ) series and operated (turned on)?
The connection information to the Multi series is stored in the indoor unit. Refer to “Deleting the memorized abnormal condition” described in 11-2.1 to clear the error history. When the error history is being cleared, the con­nection information also will be initialized. The indoor unit will be compatible with a low-standby-power model after initialization.
OK
Yes
MUZ-FH25/35
OBH624A
Page 42
42
MUZ-FH50
Turn the power supply OFF.
Is there rated voltage in the power supply?
Yes
No
Check for incorrect indoor-outdoor connecting wiring.
Check the power supply.
A
Is there rated voltage between outdoor terminal block S1 and S2?
Check for miswiring, broken wires, and loose wire connection between the power supply and outdoor terminal block S1 and between the power supply and
outdoor terminal block S2. Wait for 2 or more minutes after the power supply is turned on. Touch S2 and S3 with tester probes and start the emergency operation.
When the emergency operation starts, does the rated voltage occur for 2 sec­onds between indoor terminal block S2 and S3?
No
No
No
Was the indoor unit ever connected to the Multi (MXZ) series and operated (turned on)?
The connection information to the Multi series is stored in the indoor unit. Refer to “Deleting the memorized abnormal condition” described in 11-2.1 to clear the error history. When the error history is being cleared, the connection information also will be initialized. The indoor unit will be compatible with a low-standby-power model after initialization.
OK
Yes
B Turn the power supply ON.
Yes
Turn OFF inverter-controlled lighting equipment. Turn OFF the power supply and then turn ON again. Press EMERGENCY OPERATION switch.
A
Is serial signal error indicated 6 minutes later?
B
Yes
Reinstall either the unit or the light away from each other. Attach a fi lter on remote control receiving section of the indoor unit.
No
NOTE: Refer to the indoor unit service manual.
Replace the indoor electronic control P.C. board.
Does the indoor POWER lamp blink continuously 6 minutes after the emergency operation starts?
No
Does DC (10 V or more) occur between L68A and L68B on the relay P.C. board?
Yes
Does the outdoor LED blink 6 times?
Yes
Replace the relay P.C. board.
1
No
Does DC (more than 0 V) occur between indoor terminal block S2 and S3?
Yes
Replace the inverter P.C. board. 1
No
Turn the power supply OFF.
Start the emergency operation.
No
Repair has been completed.
Replace the inverter P.C. board and the relay P.C. board.
1
1. Electric charge may remain immediately after the power supply is turned OFF. Perform the procedure after 3 minutes.
Replace the inverter P.C. board and the relay P.C. board. 1
Turn the power supply ON.
Does the indoor POWER lamp blink continuously 6 minutes after the emergency operation starts?
Yes
No
Replace the indoor electronic control P.C. board.
Yes
Replace the inverter P.C. board and the relay P.C. board. 1
Yes
OBH624A
Page 43
43
N Electromagnetic noise enters into TV sets or radios
Yes
Is the unit earthed?
No
Earth the unit.
Yes
Is the distance between the antennas and the indoor unit within 3 m, or is the distance between the antennas and the outdoor unit within 3 m?
No
Extend the distance between the antennas and the indoor unit, and/or the antennas and the outdoor unit.
Is the distance between the TV sets or radios and the indoor unit within 1 m, or is the distance between the TV sets or radios and the outdoor unit within 3 m?
Yes
Extend the distance between the TV sets and/or radios and the indoor unit, or the TV sets or radios and the outdoor unit.
Are the antennas damaged? Is the coaxial cable damaged? Is there any poor contact in the anten­na wiring?
Yes
No
No
Replace or repair the antenna. Replace or repair the coaxial cable.
Is the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas close?
Yes
Extend the distance between the indoor/outdoor connecting wire of the air conditioner and the wir­ing of the antennas.
No
Even if all of the above conditions are fulfi lled, the electromagnetic noise may enter, depending on the electric fi eld strength or the installation condition (combination of specifi c conditions such as antennas or wiring). Check the following before asking for service.
1. Devices affected by the electromagnetic noise TV sets, radios (FM/AM broadcast, shortwave)
2. Channel, frequency, broadcast station affected by the electromagnetic noise
3. Channel, frequency, broadcast station unaffected by the electromagnetic noise
4. Layout of: indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, earth wire, antennas, wiring from antennas, receiver
5. Electric fi eld intensity of the broadcast station affected by the electromagnetic noise
6. Presence or absence of amplifi er such as booster
7. Operation condition of air conditioner when the electromagnetic noise enters in
1) Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic noise.
2) Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button on the remote controller for power ON, and check for the electromagnetic noise.
3) After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the electromagnetic noise.
4) Press OPERATE/STOP (ON/OFF) button on the remote controller for power OFF, when the outdoor unit stops but the indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise.
OBH624A
Page 44
44
-20 -10 0 10 20 30 40
0
10
20
30
40
50
60
70
80
90
100
Temperature( )
Defrost thermistor(RT61) Ambient temperature thermistor(RT65) Outdoor heat exchanger temperature thermistor(RT68)
Temperature( )
Discharge temperature thermistor(RT62)
0 102030405060708090100110120
0
100
200
300
400
500
600
700
0 1020304050607080
0
20
40
60
80
100
120
140
160
180
200
Temperature( )
Fin temperature thermistor(RT64)
Resistance(k )
Resistance(k )
Resistance(k )
1. Inverter P.C. board
MUZ-FH25VE MUZ-FH35VE
11-6. TEST POINT DIAGRAM AND VOLTAGE
Fin temperature
thermistor/RT64
(CN642)
Ambient temperature
thermistor/RT65
(CN643)
Discharge temperature
thermistor/RT62
(CN641)
Defrost thermistor
/RT61(CN641)
DB61 260 - 370 VDC
Front side of unit
230 VAC
Smoothing capacitor (C62)
Output to drive compressor (LDU, LDV, LDW)
(+)
(-)
Fuse (F701) T3.15AL250V
Smoothing capacitor (C61)
Fuse (F901) T3.15AL250V
R.V.coil (CN721) 230 VAC
Jumper wire for changing defrost setting (JS)
Signal of outdoor
fan motor (CN931)
230 VAC
Outdoor heat exchanger
temperature thermistor
/RT68 (CN644)
Jumper wire for pre-heat control setting (JK)
Fuse (F801) T3.15AL250V
Back side of unit
LEV connector
(CN724)
Output to drive outdoor fan motor (CN932)
LED
OBH624A
Page 45
45
MUZ-FH50VE
-20 -10 0 10 20 30 40
0
10
20
30
40
50
60
70
80
90
100
Temperature( )
Defrost thermistor(RT61) Ambient temperature thermistor(RT65) Outdoor heat exchanger temperature thermistor(RT68)
Temperature( )
Discharge temperature thermistor(RT62)
0 102030405060708090100110120
0
100
200
300
400
500
600
700
0 1020304050607080
0
20
40
60
80
100
120
140
160
180
200
Temperature( )
Fin temperature thermistor(RT64)
Resistance(k )
Resistance(k )
Resistance(k )
Fin temperature thermistor/RT64 (CN673)
Ambient temperature thermistor/RT65 (CN672)
Discharge temperature thermistor/RT62 (CN671)
Defrost thermistor /RT61 (CN671)
Output to drive outdoor fan motor (CN932)
Outdoor heat exchanger temperature thermistor /RT68 (CN671)
Fuse (F901) T3.15AL250V
Fuse (F880) T3.15AL250V
LEV connector (CN724)
Jumper wire for changing defrost setting (JS)
Jumper wire for pre-heat control setting (JK)
Fuse (F601) T3.15AL250V
Signal of out­door fan motor (CN931)
R.V. coil (CN602) 230VAC
325 - 370 VDC
JP715 (+)
JP30 (-)
LED
Heater (CN601) 230VAC
To relay P.C. board CN680 (CN681)
OBH624A
Page 46
46
2. Relay P.C. board
MUZ-FH50VE
To inverter P.C. board CN681 (CN680)
CN60
L68B(-)
L68A(+)
10 VDC
OBH624A
Page 47
47
12-1. MUZ-FH25VE MUZ-FH35VE
NOTE: Turn OFF power supply before disassembly.
OPERATING PROCEDURE PHOTOS
1. Removing the cabinet
(1) Remove the screw fixing the service panel. (2) Pull down the service panel and remove it. (3) Disconnect the power supply and indoor/outdoor con-
necting wire. (4) Remove the screws fixing the top panel. (5) Remove the top panel. (6) Remove the screws fixing the cabinet. (7) Remove the cabinet. (8) Remove the screws fixing the back panel. (9) Remove the back panel.
Photo 1
Photo 2
(1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector has the
locking mechanism.
Slide the sleeve. Pull the terminal while pushing the locking lever.
Hold the sleeve, and pull out the terminal slowly.
Connector
Sleeve
Locking lever
Back panel
Service
panel
Screws of the
top panel
Screws of the cabinet
Screws of the top panel
Screw of the service panel
Direction to remove
Screws of
the cabinet
Hooks
<"Terminal with locking mechanism" Detaching points>
The terminal which has the locking mechanism can be detached as shown below. There are two types (refer to (1) and (2)) of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching.
DISASSEMBLY INSTRUCTIONS
12
Screw of the cabinet
Screw of the back panel
Screws of the terminal block support and the back panel
OBH624A
Page 48
OPERATING PROCEDURE
PHOTOS
2. Removing the inverter assembly, inverter P.C. board
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following con-
nectors:
<Inverter P.C. board>
CN721 (R.V. coil) CN931, CN932 (Fan motor) CN641 (Defrost thermistor and discharge temperature ther-
mistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor) CN724 (LEV)
(3) Remove the compressor connector (CN61). (4) Remove the screws fixing the heat sink support and the sep-
arator.
(5) Remove the fixing screws of the terminal block support and
the back panel. (6) Remove the inverter assembly. (7) Remove the screw of the earth wire and screw of the termi-
nal block support. (8) Remove the heat sink support from the P.C. board support. (9) Remove the screw of the inverter P.C. board and remove the
inverter P.C. board from the P.C. board support.
Photo 3
Photo 4 (Inverter assembly)
Photo 5
3. Removing R.V. coil
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the following connectors: <Inverter P.C. board>
CN721 (R.V. coil)
(3) Remove the R.V. coil.
4. Removing the discharge temperature thermistor, defrost thermistor, outdoor heat exchanger tempera­ture thermistor and ambient temperature thermistor
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following con-
nectors: <Inverter P.C. board>
CN641 (Defrost thermistor and discharge temperature ther-
mistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor)
(3) Pull out the discharge temperature thermistor from its holder. (4) Pull out the defrost thermistor from its holder. (Photo 6) (5) Pull out the outdoor heat exchanger temperature thermistor
from its holder. (Photo 6)
(6) Pull out the ambient temperature thermistor from its holder.
Discharge temperature thermistor
Screw of the R.V. coil
Screws of the heat sink support and the separator
Heat sink
Screw of the earth wire
Screw of the Terminal block support
48
Screw of the inverter P.C. board
Screws of the terminal block support and the back panel
Heat sink support
P.C. board support
Terminal block support
Ambient temperature thermistor
OBH624A
Page 49
OPERATING PROCEDURE
PHOTOS
5. Removing outdoor fan motor
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the following connectors: <Inverter P.C. board>
CN931, CN932 (Fan motor) (3) Remove the propeller nut. (4) Remove the propeller. (5) Remove the screws fixing the fan motor. (6) Remove the fan motor.
Photo 6
Photo 7
6. Removing the compressor and 4-way valve
(1) Remove the cabinet and panels. (Refer to 1.) (2) Remove the inverter assembly. (Refer to 2.) (3) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure gauge
shows 0 kg/cm
2
(0 MPa).
(4) Detach the brazed part of the suction and the discharge pipe
connected with compressor. (5) Remove the nuts of compressor legs. (6) Remove the compressor. (7) Detach the brazed part of pipes connected with 4-way valve.
49
Propeller nut
Screws of the outdoor fan motor
Propeller
Photo 8
Defrost thermistor
Outdoor heat exchanger tempera­ture thermistor
Brazed parts of 4-way valve
Suction pipe brazed part
Discharge pipe brazed part
OBH624A
Page 50
12-2. MUZ-FH50VE
NOTE: Turn OFF power supply before disassembly.
OPERATING PROCEDURE
PHOTOS
1. Removing the cabinet
(1) Remove the screws of the service panel. (2) Remove the screws of the top panel. (3) Remove the screw of the valve cover. (4) Remove the service panel. (5) Remove the top panel. (6) Remove the valve cover. (7) Disconnect the power supply and indoor/outdoor connect-
ing wire. (8) Remove the screws of the cabinet. (9) Remove the cabinet. (10)
Remove the screws of the back panel.
(11)
Remove the back panel.
Photo 2
Photo 1
50
Screws of the cabinet
Screws of the top panel
Screws of the cabinet
Screws of the top panel
Screw of the back panel
Screws of the cabinet
Screws of the service panel
Screw of the valve cover
Screws of the cabinet
Screws of the back panel
OBH624A
Page 51
OPERATING PROCEDURE
PHOTOS
2. Removing the inverter assembly, inverter P.C. board and relay P.C. board
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following con-
nectors: <Inverter P.C. board> CN602 (R.V. coil) CN931, CN932 (Fan motor) CN671 (Defrost thermistor, discharge temperature thermistor
and outdoor heat exchanger temperature thermistor) CN672 (Ambient temperature thermistor) CN724 (LEV)
(3) Remove the compressor connector. (4) Remove the screws fixing the relay panel. (5) Remove the relay panel. (6) Remove the earth wires and the lead wires of the inverter P.C.
board.
(7) Remove the screws of the P.B. support. (8) Remove the inverter P.C. board from the relay panel. (9) Disconnect the following connectors:
<Relay P.C. board> CN60 (Terminal block) CN680 (Inverter P.C. board) TAB65 (Inverter P.C. board) TB71
(10)
Remove the screws fixing the P.B. holder.
(11)
Remove the relay P.C. board from the P.B. holder.
Photo 3
Photo 4
3. Removing R.V. coil
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the following connector: <Inverter P.C. board>
CN602 (R.V. coil)
(3) Remove the R.V. coil.
51
Screws of the P.B. support
Screws of the relay panel
Inverter P.C. board
Earth wires
Screw of the P.B. holder
Screws of the P.B. support
Brazed parts of 4-way valve
Screw of the R.V. coil
Screw of the relay panel
Relay P.C board
OBH624A
Page 52
OPERATING PROCEDURE PHOTOS
4. Removing the discharge temperature thermistor, defrost thermistor, outdoor heat exchanger tempera­ture thermistor and ambient temperature thermistor
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following
connectors: <Inverter P.C. board> CN671 (Defrost thermistor, discharge temperature thermis-
tor and outdoor heart exchanger temperature ther­mistor)
CN672 (Ambient temperature thermistor)
(3) Pull out the discharge temperature thermistor from its hold-
er. (Photo 7) (4) Pull out the defrost thermistor from its holder. (5) Pull out the outdoor heat exchanger temperature thermistor
from its holder. (6) Pull out the ambient temperature thermistor from its holder.
Photo 5
Photo 6
Photo 7
5. Removing outdoor fan motor
(1)
Remove the top panel, cabinet and service panel. (Refer to 1.)
(2) Disconnect the following connectors:
<Inverter P.C. board>
CN931 and CN932 (Fan motor)
(3) Remove the propeller. (4) Remove the screws fixing the fan motor. (5) Remove the fan motor.
6. Removing the compressor and 4-way valve
(1)
Remove the top panel, cabinet and service panel. (Refer to 1.) (2) Remove the back panel. (Refer to 1.) (3) Remove the inverter assembly. (Refer to 2.) (4) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure gauge
shows 0 kg/cm2 (0 MPa).
(5) Detach the brazed part of the suction and the discharge
pipe connected with compressor. (6) Remove the compressor nuts. (7) Remove the compressor. (8) Detach the brazed parts of 4-way valve and pipe. (Photo 4)
52
Screws of the outdoor fan motor
Brazed part of the discharge pipe
Brazed part of the suction pipe
Discharge temperature thermistor
Outdoor heat exchanger temperature thermistor
Ambient temperature thermistor
Defrost thermistor
OBH624A
Page 53
53
OBH624A
Page 54
© Copyright 2012 MITSUBISHI ELECTRIC CORPORATION Distributed in Mar. 2013. No. OBH624 REVISED EDITION-A Distributed in Oct. 2012. No. OBH624 Made in Japan
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
New publication, effective Mar. 2013 Specifications are subject to change without notice.
Loading...