NOTE: Test conditions are based on ISO 5151.
Cooling: Indoor Dry-bulb temperature 27°C Wet-bulb temperature 19°C
Outdoor Dry-bulb temperature 35°C
Heating: Indoor Dry-bulb temperature 20°C
Outdoor Dry-bulb temperature 7°C Wet-bulb temperature 6°C
Refrigerant piping length (one way): 5 m
SPECIFICATION
Outdoor model MUZ-FD25VA MUZ-FD25VAH MUZ-FD35VA MUZ-FD35VAH
Low580
Fan speed regulator2
Refrigerant fi lling capacity (R410A)kg1.55
NOTE: Test conditions are based on ISO 5151.
Cooling: Indoor Dry-bulb temperature 27°C Wet-bulb temperature 19°C
Outdoor Dry-bulb temperature 35°C
Heating: Indoor Dry-bulb temperature 20°C
Outdoor Dry-bulb temperature 7°C Wet-bulb temperature 6°C
Refrigerant piping length (one way): 5 m
1 Measured under rated operating frequency.
6
Specifi cations and rating conditions of main electric parts
Item
Current transformer
Smoothing capacitor(C61, C62, C63)620 F 420 V
Diode module
Fuse
Defrost heater(H)—230 V 130 W—230 V 130 W
Intelligent power module(IPM)20 A 600 V
Expansion valve coil(LEV)DC 12 V
Reactor(L61)23.0 mH
Current-detecting resistor
Current-limiting PTC thermistor (PTC64, PTC65)33
Terminal block(TB1, TB2)3 P
Relay
R.V.coil(21S4)AC 220 - 240 V
Heater protector(26H)—Open 45°C—Open 45°C
IGBT(TR821)30 A 600 V
(CT761, CT781)15 A
(F701, F801, F901)T3.15AL250V
(R937, R938, R939)430 m 2 W
Model
(DB61)15 A 600 V
(DB65)25 A 600 V
(F61)T20AL250V
(R61, R62)180 m 5 W (2 elements)
(R825)25 m 5 W
(X63)3 A 250 V
(X64)20 A 250 V
(X66)—3 A 250 V—3 A 250 V
MUZ-FD25VAMUZ-FD25VAHMUZ-FD35VAMUZ-FD35VAH
(CT)20 A
Model
Item
Current transformer
Smoothing capacitor(CB1, CB2, CB3)560 F 450 V
Fuse
Expansion valve coil(LEV)DC 12 V
Intelligent power module
High pressure switch(HPS)ACB-DB156
Reactor(L)600 H 20 A
Power factor correct module(PFC)20 A 600 V
Current-limiting PTC thermistor(PTC64, PTC65)33
Current-detecting resistor
Solenoid coil relay(SSR61)0.5 A 600 V
Terminal block(TB1, TB2)3 P
Relay(X64) 20 A 250 V
R.V. coil(21S4)AC 220 - 240 V
(RS1, RS2, RS3, RS4)
(CT1, CT2)20 A
(CT61)20 A
(F64)T2.0AL250V
(F801)T3.15AL250V
(IPM)15 A 600 V
(HC930)3 A 600 V
(R937A, R937B)1.1 2 W
MUZ-FD50VA
40 m 7 W (2 elements)
7
4
NOISE CRITERIA CURVES
MUZ-FD25VA MUZ-FD25VAH
FUNCTION
COOLING
HEATING
90
80
70
60
50
40
30
20
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB re 0.0002 MICRO BAR
10
63125250500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
SPL(dB(A))LINE
46
NC-10
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
MUZ-FD35VA MUZ-FD35VAH
FUNCTION
COOLING
HEATING
90
80
70
60
50
40
30
20
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
10
63125250500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
SPL(dB(A))
47
50
NC-10
LINE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
MUZ-FD50VA
FUNCTION
COOLING
HEATING
90
80
70
60
50
40
30
20
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB re 0.0002 MICRO BAR
10
63125250500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
SPL(dB(A))LINE
54
56
NC-10
Test conditions
Cooling : Dry-bulb temperature 35 °C
Heating : Dry-bulb temperature 7 °C Wet-bulb temperature 6 °C
The standard specifications apply only to the operation of the air conditioner under normal conditions. Since operating condi-
tions vary according to the areas where these units are installed, the following information has been provided to clarify the
operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198 ~ 264 V, 50 Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature:°C [WB]
(2) Indoor outlet air wet-bulb temperature:°C [WB]
(3) Outdoor intake air dry-bulb temperature:°C [DB]
(4) Total input:W
(5) Indoor intake air dry-bulb temperature:°C [DB]
(7) Total input:W
Indoor air wet/dry-bulb temperature difference on the left side of the following chart shows the difference between the
indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.
How to measure the indoor air wet-bulb / dry-bulb temperature difference
1. Attach at least 2 sets of wet and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets
of wet and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air
speed is high.
2. Attach at least 2 sets of wet and dry-bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once (twice) to start the EMERGENCY COOL (HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
}
}
Cooling
Heating(6) Outdoor intake air wet-bulb temperature:°C [WB]
INDOOR UNIT
Wet and dry-bulb
thermometers
FRONT VIEW
8-1. CAPACITY AND INPUT CURVES
6.5
6.0
5.5
5.1
4.6
difference (°C)
4.1
3.7
Indoor air Wet-bulb temperature
9.1
8.4
7.7
7.0
6.3
5.7
5.1
10.1
9.3
8.5
7.7
7.0
6.3
5.6
1.5
1.4
1.3
1.2
1.1
1.0
Capacity correction factors
0.9
-10-5 0 5 1015202530354045
OUTDOOR UNIT
Wet and dry-bulb
thermometers
BACK VIEW
Cooling capacity
Outdoor intake air Dry-bulb temperature(°C)
(
at Rated frequency)
Indoor intake air Wet-bulb
temperature( )
26
24
22
20
18
MUZ-FD25VAH
MUZ-FD35VA
MUZ-FD35VAH
MUZ-FD50VA
MUZ-FD25VA
15
9.3
8.0
6.7
5.3
MUZ-FD25VAH
7.7
7.0
6.3
5.7
5.1
4.5
MUZ-FD35VA
8.5
7.7
7.0
6.3
5.6
4.9
MUZ-FD35VAH
20.9
19.3
17.7
16.1
14.5
12.9
11.3
9.7
8.0
6.4
5.5
5.1
4.6
4.1
difference (°C)
3.7
3.3
Indoor air Wet-bulb temperature
MUZ-FD25VA
17.3
16.0
14.6
13.3
12.0
10.6
difference (°C)
Indoor air Dry-bulb temperature
1.3
1.2
1.1
1.0
0.9
Input correction factors
0.8
-10-5 0 5 1015202530354045
MUZ-FD50VA
25.6
23.7
21.7
19.7
17.7
15.8
13.8
11.8
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
9.9
0.5
Capacity correction factor
7.9
0.4
-20-15-10-5051015
Total input (Cooling :
at Rated frequency
)
Indoor intake air Wet-bulb
temperature(°C)
Outdoor intake air Dry-bulb temperature (°C)
Heating capacity (
Indoor intake air Dry-bulb te
at Rated frequency)
mperature ( )
Outdoor intake air Wet-bulb temperature (°C)
22
26
24
20
18
15
20
26
MUZ-FD35VA
MUZ-FD25VAH
MUZ-FD25VA
17.3
16.0
14.6
13.3
12.0
10.6
9.3
8.0
difference (°C)
6.7
5.3
Indoor air Dry-bulb temperature
20.9
19.3
17.7
16.1
14.5
12.9
11.3
9.7
8.0
6.4
MUZ-FD35VAH
MUZ-FD50VA
25.6
23.7
21.7
19.7
17.7
15.8
13.8
11.8
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
Input correction factor
9.9
0.5
7.9
0.4
Total input (Heating :
r Dry-
ke ai
inta
Indoor
at Rated frequency
bulb te
)
mperature (
26
)
°C
20
15
-20-15-10-5051015
Outdoor intake air Wet-bulb temperature (°C)
MUZ-FD25VA
MUZ-FD25VAH
MUZ-FD35VAH
MUZ-FD35VA
MUZ-FD50VA
NOTE: The above broken lines are for the heating operation without any frost and defrost operation.
16
8-2. CAPACITY AND INPUT CORRECTION BY OPERATIONAL FREQUENCY OF COMPRESSOR
MUZ-FD25VA MUZ-FD25VAH
Correction of Cooling capacity
1.5
1.0
0.5
Capacity correction factors
0.0
050100150(Hz)
The operational frequency of compressor
MUZ-FD35VA
Correction of Cooling capacity
1.5
1.0
0.5
Capacity correction factors
0.0
050100150(Hz)
The operational frequency of compressor
Correction of Cooling input
2.5
2.0
1.5
1.0
0.5
Input correction factors
0.0
050100150(Hz)
The operational frequency of compressor
Correction of Cooling input
1.5
1.0
0.5
Input correction factors
0.0
050100150(Hz)
The operational frequency of compressor
Correction of Heating capacity
2.0
1.5
1.0
0.5
Capacity correction factors
0.0
050100150(Hz)
The operational frequency of compressor
Correction of Heating capacity
2.0
1.5
1.0
0.5
Capacity correction factors
0.0
050100150(Hz)
The operational frequency of compressor
Correction of Heating input
4
3
2
1
Input correction factors
0
050100150(Hz)
The operational frequency of compressor
Correction of Heating input
3
2
1
Capacity correction factors
0
050100150(Hz)
The operational frequency of compressor
MUZ-FD35VAH
Correction of Cooling capacity
1.5
1.0
0.5
Capacity correction factors
0.0
050100150(Hz)
The operational frequency of compressor
MUZ-FD50VA
Correction of Cooling capacity
1.5
1.0
0.5
Capacity correction factors
0.0
050100
The operational frequency of
compressor (Hz)
Correction of Cooling input
1.5
1.0
0.5
Input correction factors
0.0
050100150(Hz)
The operational frequency of compressor
Correction of Cooling input
2.0
1.5
1.0
0.5
Input correction factors
0.0
050100
The operational frequency of
compressor (Hz)
Correction of Heating capacity
2.0
1.5
1.0
0.5
Capacity correction factors
0.0
050100150(Hz)
The operational frequency of compressor
Correction of Heating capacity
1.5
1.0
0.5
Capacity correction factors
0.0
050100150
The operational frequency of
compressor (Hz)
Correction of Heating input
3
2
1
Capacity correction factors
0
050100150(Hz)
The operational frequency of compressor
Correction of Heating input
2.0
1.5
1.0
0.5
Capacity correction factors
0.0
050100150
The operational frequency of
compressor (Hz)
17
8-3. TEST RUN OPERATION (How to operate fixed-frequency operation)
1. Press EMERGENCY OPERATION switch to start COOL or HEAT mode (COOL: Press once, HEAT: Press twice).
2. Test run operation starts and continues to operate for 30 minutes.
3. Compressor operates at rated frequency in COOL mode or 58 Hz in HEAT mode.
4. Indoor fan operates at High speed.
5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (operation frequency of compressor varies).
6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on
remote controller.
8-4. OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
COOL operation
Both indoor and outdoor unit are under the same temperature/
humidity condition.
Operation: TEST RUN OPERATION (Refer to 8-3.)
Dry-bulb temperature (°C) Relative humidity (%)
2050
2560
3070
Outdoor low pressure
MUZ-FD25VA MUZ-FD25VAH
1.4
1.2
1.0
MPa [Gauge]
0.8
0.6
0.4
0.2
1520253035
506070
Ambient temperature(°C)
Ambient humidity(%)
MUZ-FD50VA
1.4
1.2
1.0
MPa [Gauge]
0.8
0.6
0.4
0.2
1520253035
506070
Ambient temperature(°C)
Ambient humidity(%)
14
12
10
8
6
4
14
12
10
8
6
4
[Gauge]
2
kgf/cm
[Gauge]
2
kgf/cm
MUZ-FD35VA
1.4
1.2
1.0
MPa [Gauge]
0.8
0.6
0.4
0.2
1520253035
506070
Ambient temperature(°C)
Ambient humidity(%)
14
12
10
8
6
4
[Gauge]
2
kgf/cm
MUZ-FD35VAH
1.4
1.2
1.0
MPa [Gauge]
0.8
0.6
0.4
0.2
1520253035
506070
Ambient temperature(°C)
Ambient humidity(%)
14
12
10
8
6
4
[Gauge]
2
kgf/cm
NOTE:
The unit of pressure has been changed to MPa on the international system of units (SI unit system)
The conversion factor is: 1 (MPa [Gauge]) = 10.2 (kgf/cm
2
[Gauge])
18
Outdoor unit current
MUZ-FD25VA MUZ-FD25VAH
(A)(A)
2.4
2.2
2.0
1.8
15205025
18
MUZ-FD50VA
(A)
6.5
6.0
5.5
5.0
4.5
1520253035
60
Ambient temperature(°C)
Ambient humidity(%)
506070
Ambient temperature (°C)
Ambient humidity (%)
3230
35(°C)
70 (%)
MUZ-FD35VA
4.0
3.5
3.0
2.5
15205025
18
Ambient temperature(°C)
Ambient humidity(%)
60
3230
35(°C)
70 (%)
MUZ-FD35VAH
(A)
4.0
3.5
3.0
2.5
15205025
18
Ambient temperature(°C)
Ambient humidity(%)
60
3230
35(°C)
70 (%)
HEAT operation
Condition:
Dry bulb temperature (°C) 20.0271520.0
Wet bulb temperature (°C) 14.5161214.5
Operation: Test run operation (Refer to 8-3.)
Outdoor unit current
MUZ-FD25VA MUZ-FD25VAH
6.0
(A)(A)
5.5
5.0
4.5
4.0
MUZ-FD50VA
(A)
5 10152025
Ambient temperature(°C)
8.5
8.0
7.5
IndoorOutdoor
MUZ-FD35VA
6.0
5.5
5.0
4.5
4.0
2
510152025
Ambient temperature(°C)
MUZ-FD35VAH
(A)
6.0
5.5
5.0
4.5
4.0
2
5 10152025
Ambient temperature(°C)
7.0
6.5
6.0
02 510 15 20 25
Ambient temperature (°C)
19
PERFORMANCE DATA COOL operation at Rated frequency