Maximum temperature9073115—
Minimum temperature675714—
Maximum humidity78 %—
Standard temperature70604743
Maximum temperature80677565
Minimum temperature70601413
Rated voltage Guaranteed Voltage
208/230 V
1 phase
60 Hz
Min.187 V
DBWBDBWB
208 V 230 V Max.253 V
Intake air temperature (°F)
IndoorOutdoor
55
4
OUTLINES AND DIMENSIONS
MUZ-FD09NA MUZ-FD12NA
21-5/8
1-3/4
Air in
handle
11-1/32
7/8
13/32
15-3/4
Air in
11-29/32
5-15/16
Drain hole 1-5/8
Air out
2- 3/8 13/16 Oval hole
19-11/16
31-1/2
1-9/16
12 ~ 12-3/4
11/16
2
2-23/32
13-9/16
5-7/8
REQUIRED SPACE
4 in. or more
17/3229/3211-1/4
Open two sides of left,
right, or rear side.
Liquid pipe :1/4 (flared)
Gas pipe :3/8 (flared)
6-23/32
Unit: inch
Basically open 4 inch or more
without any obstruction in front
and on both sides of the unit.
4 in. or more
14 in. or more
8 in. or more
66
5
MUZ-FD09NA MUZ-FD12NA
WIRING DIAGRAM
77
6
REFRIGERANT SYSTEM DIAGRAM
MUZ-FD09NA MUZ-FD12NA
Refrigerant pipe ø3/8
(with heat insulator)
Stop valve
(with service port)
Flared connection
Flared connection
Stop valve
(with strainer)
Refrigerant pipe 1/4
(with heat insulator)
4-way valve
Muffler
Discharge
temperature
thermistor
RT62
Service
port
Capillary tube
O.D. 0.118 ×I.D. 0.079
× 9-7/16
(ø3.0 × ø2.0 × 240)
Muffler
Service
port
Compressor
Defrost
thermistor
RT61
Capillary tube
O.D. 0.118× I.D. 0.071
× 23-5/8
(ø
3.0
× ø
1.8×600
Expansion
valve
)
Refrigerant flow in cooling
Refrigerant flow in heating
Outdoor
heat
exchanger
Strainer
#100
R.V. coil
heating ON
cooling OFF
Outdoor heat
exchanger
temperature
thermistor
RT68
Ambient
temperature
thermistor
RT65
Unit:inch
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Refrigerant piping : ft. Piping size O.D : in.
Model
MUZ-FD09NA
MUZ-FD12NA
Max. Length
A
Max. Height difference
B
Gas Liquid
6540 3/8 1/4
Indoor
unit
Max. Height
difference
B
Max. Length
A
Outdoor unit
ADDITIONAL REFRIGERANT CHARGE (R410A : oz.)
NOTE : Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
Model Outdoor unit precharged
MUZ-FD09NA
MUZ-FD12NA
2 lb. 9 oz.01.624.868.1011.3412.96
253040506065
Refrigerant piping length (one way) : ft.
NOTE : Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
Calculation : X oz. = 1.62 / 5 oz. / ft. × (Refrigerant piping length (ft.) - 25)
2. Above data is for heating operation without any frost.
Btu/h)
How to operate with fixed operational frequency of the compressor.
1. Press the EMERGENCY OPERATION switch on the front of the indoor unit, and select either EMERGENCY COOL
mode or EMERGENCY HEAT mode before starting to operate the air conditioner.
2. The compressor starts with operational frequency.
3. The fan speed of the indoor unit is High.
4. This operation continues for 30 minutes.
5. In order to release this operation, press the EMERGENCY OPERATION switch twice or once, or press any button on
the remote controller.
9
7-2. PERFORMANCE CURVE
Cooling
MUZ-FD09NA
SHF at rating condition = 0.76
13
Indoor intake air WB te
12
11
Btu/h)
10
3
9
8
Total capacity
(10
7
0.7
Indoor intake air
(kW)
0.6
0.5
Total power consumption
65758595105115
Outdoor intake air DB temperature (°F)
Airflow
WB te
mperature (°F)
mpe
Heating
MUZ-FD09NA
= 381 CFM
Airflow
12
10
Btu/h)
8
3
Total capacity
(10
6
0.8
0.6
(kW)
0.4
Total power consumption
1525354555
e air DB temperature
Indoor intak
Indoor intake air DB temperat
Outdoor intake air WB temperature (°F)
= 307 CFM
rature (°F)
)
(°F
ure (°F)
MUZ-FD12NA
SHF at rating condition = 0.73
15
14
13
Btu/h)
12
3
71
67
63
71
67
63
11
10
Total capacity
(10
1.2
1.1
1.0
(kW)
0.9
0.8
0.7
Total power consumption
Indoor
intak
9
oor intake air WB temperature (°F)
Ind
65758595105115
Outdoor intake air DB temperature (°F)
= 350 CFM
Airflow
e air WB temperat
ure
(°F)
71
67
63
71
67
63
MUZ-FD12NA
65
70
75
20
18
16
Btu/h)
14
3
12
Total capacity
(10
Indoor intake air DB temperature (°F)
10
8
6
75
70
65
1.1
1.0
(kW)
0.9
Indoor intake air
0.8
Total power consumption
0.7
0.6
1525354555
Outdoor intake air WB temperature (°F)
Airflow
temperature (°F)
DB
= 420 CFM
65
70
75
75
70
65
This value of frequency is not the same as the actual frequency in operating. Refer to 7-5 and 7-6 for the relationships
between frequency and capacity.
1010
7-3. CONDENSING PRESSURE
Cooling
Data is based on the condition of indoor humidity 50 %.
Air flow should be set to High speed.
MUZ-FD09NA
(PSIG)
580
540
500
460
420
380
Condensing pressure
340
300
260
68 707580859095100 105(°F)
oor DB temperature (°F)
Ind
Outdoor ambient temperature
86
80
75
70
MUZ-FD12NA
(PSIG)
580
540
500
86
460
420
380
Condensing pressure
340
300
260
68 707580859095100 105(°F)
Indoor DB temperature (°F)
Outdoor ambient temperature
80
75
70
(PSIG)
180
175
170
165
160
155
150
145
140
Suction pressure
135
130
125
120
68 707580859095100 105(°F)
(PSIG)
180
175
170
165
160
155
150
145
140
Suction pressure
135
130
125
120
68 707580859095100 105(°F)
Indoor DB temperature (°F)
Outdoor ambient temperature
Indoor DB temperature (°F)
Outdoor ambient temperature
86
80
75
70
86
80
75
70
1111
Heating
Data is based on the condition of outdoor humidity 75%.
Air flow should be set to High speed.
Data is for heating operation without any frost.
MUZ-FD09NA
(PSIG)(PSIG)
400
380
360
340
320
300
280
260
240
220
Condensing pressure
200
180
160
140
oor DB tem
Ind
perat
ure(
°F)
58Hz
75
70
65
Suction pressure
14 20 25 30 35 40 45 50 55 60 6570(°F)
Outdoor ambient temperature
MUZ-FD12NA
170
160
150
140
130
120
110
100
90
80
70
60
14 20 25 30 35 40 45 50 55
DB temperature (°F)
oor
Ind
Outdoor ambient temperature
58Hz
60 65 70(°F)
75
70
65
(PSIG)(PSIG)
400
380
360
340
320
300
280
260
240
220
Condensing pressure
200
180
160
140
Indoor DB temperature(°F)
58Hz
75
70
65
170
160
150
140
130
120
110
Suction pressure
100
14 20 25 30 35 40 45 50 55 60 6570(°F)
Outdoor ambient temperature
Indoor DB temperature
90
80
70
60
14 20 25 30 35 40 45 50 55
Outdoor ambient temperature
(°F)
58Hz
60 65 70(°F)
75
70
65
12
7-4. STANDARD OPERATION DATA
ModelMSZ-FD09NAMSZ-FD12NA
ItemUnitCooling Heating Cooling Heating
CapacityBtu/h9,00010,90012,00013,600
SHF—0.76 — 0.73 —
Total
InputkW0.6500.7500.9600.980
Rated frequencyHz35435154
Indoor unitMSZ-FD09NAMSZ-FD12NA
Power supply
InputkW0.0180.0240.0240.030
Fan motor currentA0.19/0.170.25/0.230.25/0.230.32/0.29
7-5. CAPACITY AND INPUT CORRECTION BY INVERTER OUTPUT FREQUENCY
MUZ-FD09NA
Correction of Cooling capacity
1.5
1.0
Correction of Cooling total input
1.5
1.0
Correction of Heating capacity
2.0
1.5
1.0
Correction of Heating total input
3.0
2.0
0.5
Capacity correction factors
050100150
The operational frequency of compressor
0.5
Input correction factors
(Hz)
050100150
The operational frequency of compressor
0.5
Capacity correction factors
(Hz)
050100150
The operational frequency of compressor
1.0
Input correction factors
(Hz)
050100150
The operational frequency of compressor
MUZ-FD12NA
Correction of Cooling capacity
1.5
1.0
0.5
Capacity correction factors
050100150
The operational frequency of compressor
Correction of Cooling total input
1.5
1.0
0.5
Input correction factors
(Hz)
050100150
The operational frequency of compressor
Correction of Heating capacity
1.5
1.0
0.5
Capacity correction factors
(Hz)
050100150
The operational frequency of compressor
Correction of Heating total input
2.0
1.0
Input correction factors
(Hz)
050100150
The operational frequency of compressor
7-6. TEST RUN OPERATION (How to operate fixed-frequency operation)
1. Press EMERGENCY OPERATION switch to start COOL or HEAT mode (COOL : Press once, HEAT : Press twice).
2. Test run operation starts and continues to operate for 30 minutes.
3. Compressor operates at rated frequency in COOL mode or 58 Hz in HEAT mode.
4. Indoor fan operates at High speed.
5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (operation frequency of compressor varies).
6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on
remote controller.
(Hz)
(Hz)
14
8
ACTUATOR CONTROL
MUZ-FD09NA MUZ-FD12NA
8-1. OUTDOOR FAN MOTOR CONTROL
The fan motor turns ON/OFF, interlocking with the compressor.
[ON] The fan motor turns ON 5 seconds before the compressor starts up.
[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
5 seconds15 seconds
ON
Compressor
OFF
ON
Outdoor fan
motor
OFF
8-2. R.V. COIL CONTROL
Heating
Cooling
Dry
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
8-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR
Discharge temperature thermistor Protection
Indoor coil temperature thermistor
Defrost thermistor
Fin temperature thermistor Protection
Outdoor heat exchanger temperature thermistor
Ambient temperature thermistor
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
Compressor
R.V.coil
Outdoor fan
motor
Sensor Purpose
ON
OFF
OFF
<COOL>
5 seconds
ON
OFF
ON
OFF
ON
OFF
Cooling : Coil frost prevention
Heating : High pressure protection
Cooling : High pressure protection
Heating :
Defrosting
High pressure protection
Low ambient temperature operation
Compressor
<HEAT>
5 seconds
Actuator
LEV
Outdoor
fan motor
○○
○
○○
○○
○○○○○
○○
○○○
○○○
R.V. coil
Indoor fan
motor
1515
9
SERVICE FUNCTIONS
MUZ-FD09VA MUZ-FD12VA
9-1. CHANGE IN DEFROST SETTING
Changing defrost finish temperature
<JS> To change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P.C. board.
(Refer to 10-6-1.)
JumperDefrost fi nish temperature
(Initial setting)
JS
Soldered
None
(Cut)
41°F (5°C)
50°F (10°C)
9-2. PRE-HEAT CONTROL SETTING
PRE-HEAT CONTROL
When moisture gets into the refrigerant cycle, it may interfere the start-up of the compressor at low outside temperature. The pre-heat control prevents this interference. The pre-heat control turns ON when outside temperature is 68°F (20
°C) or below. When pre-heat control is turned ON, compressor is energized. (About 50 W)
<JK> To activate the pre-heat control, cut the JK wire of the inverter P.C. board. (Refer to 10-6.1)
NOTE: When the inverter P.C. board is replaced, check the Jumper wires, and cut/solder them if necessary.
10
TROUBLESHOOTING
MUZ-FD09NA MUZ-FD12NA
10-1. CAUTIONS ON TROUBLESHOOTING
1. Before troubleshooting, check the following
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for miswiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, then after confirming the horizontal vane is closed, turn off the breaker and/or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic
control P.C. board.
3) When removing the electrical parts, be careful to the residual voltage of smoothing capacitor.
4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.
5) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
Lead wiring
3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.
To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
2) Before servicing check that the connector and terminal are connected properly.
3) When the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
4) Refer to 10-2. and 10-3.
Housing point
16
10-2. FAILURE MODE RECALL FUNCTION
Outline of the function
This air conditioner can memorize the abnormal condition which has occurred once.
Even though LED indication listed on the troubleshooting check table (10-3.) disappears, the memorized failure details
can be recalled.
This mode is very useful when the unit needs to be repaired for the abnormality which doesn't recur.
1. Flow chart of failure mode recall function for the indoor/outdoor unit
Operational procedure
The cause of abnormality cannot be found because the abnormality doesn't recur.
Setting up the failure mode recall function
Turn ON the power supply.
<Preparation of the remote controller>
While pressing both OPERATION SELECT button and TOO COOL button on the
remote controller at the same time, press RESET button.
First, release RESET button.
And release the other two buttons after all LCD in operation display section of the
remote controller is displayed after 3 seconds.
1. Regardless of normal or abnormal condition, a short beep
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is
displayed) with the remote controller headed towards the indoor unit.
1
is emitted once the signal is
received.
Does POWER lamp on the indoor unit blink at the interval of
0.5 seconds?
Blinks: Either indoor or outdoor unit is abnormal. Beep is emit-
ted at the same timing as the blinking of POWER lamp.
2
Yes
Judgment of indoor/outdoor abnormality
Before blinking, does POWER lamp stay ON for 3 seconds?
Stays ON for 3 seconds (without beep):
The outdoor unit is abnormal.
The indoor unit is abnormal.
Check the blinking pattern, and confi rm the abnormal point with the indoor unit
failure mode table. (Refer to indoor unit service manual.)
Make sure to check at least two consecutive blinking cycles.
Releasing the failure mode recall function
Deleting the memorized abnormal condition
Release the failure mode recall function by the following procedures.
Turn OFF the power supply and turn it ON again.
Press RESET button of the remote controller.
Repair the defective parts.
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" mentioned above.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed)
with the remote controller headed towards the indoor unit.
Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.
Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
NOTE: 1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
(Blinks)
No
No
(OFF)
Yes
2
Indoor unit is normal.
But the outdoor unit might be abnormal because there are some abnormalities that can't be recalled with this way.
Confi rm if outdoor unit is abnormal according to the detailed outdoor
unit failure mode recall function. (Refer to 10-2.2)
The outdoor unit is abnormal.
Check the blinking pattern, and confi rm the abnormal point with the
outdoor unit failure mode table. (Refer to 10-2.3)
Make sure to check at least two consecutive blinking cycles.
2. Blinking pattern when the indoor unit is abnormal:
2.5-second OFF
Blinking at 0.5second interval
2.5-second OFF
Blinking at 0.5-
second interval
ON
OFF
Repeated cycleRepeated cycle
Beeps
Beeps
Repeated cycle
3
Beeps
3.Blinking pattern when the outdoor unit is abnormal:
2.5-second OFF3-second ON
ON
OFF
No beepBeeps
Repeated cycle
Blinking at 0.5second interval
2.5-second OFF3-second ON
No beepBeeps
Repeated cycle
17
Blinking at 0.5second interval
Repeated cycle
2. Flow chart of the detailed outdoor unit failure mode recall function
Operational procedure
The outdoor unit might be abnormal.
Confi rm if outdoor unit is abnormal according to the following procedures.
Confi rm that the remote controller is in the failure mode recall function.
With the remote controller headed towards the indoor unit, press TOO
COOL or TOO WARM button to adjust the set temperature to 77˚F (25˚C).
1
Does POWER lamp on the indoor unit blink at the
interval of 0.5 seconds?
Blinks: The outdoor unit is abnormal. Beep is emitted
at the same timing as the blinking of POWER
lamp. 2
Yes
)
(Blinks
The outdoor unit is abnormal.
Check the blinking pattern, and confi rm the abnormal point with the out-
door unit failure mode table (10-2.3.).
Make sure to check at least two consecutive blinking cycles.
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures.
Turn OFF the power supply and turn it ON again.
Press RESET button of the remote controller.
Repair the defective parts.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" (10-2.1.).
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with
the remote controller headed towards the indoor unit.
Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.
Release the failure mode recall function according to "Releasing the failure mode recall function" men-
tioned above.
NOTE: 1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
No
(OFF)
2
1. Regardless of normal or abnormal condition, 2 short
beeps are emitted as the signal is received.
The outdoor unit is normal.
Release the failure mode recall function according to the left mentioned procedure.
Overcurrent protection stop is
continuously performed 3 times within
—
—
1 minute after the compressor gets
started.
Thermistor shorts or opens during
compressor running.
Large current fl ows into intelligent
power module.
Waveform of compressor current is
distorted.
Temperature of discharge temperature
thermistor exceeds 241°F (116°C),
compressor stops.
Compressor can restart if discharge
temperature thermistor reads 212°F
(100°C) or less 3 minutes later.
Condition Correspondence
Reconnect connectors.
•
Refer to 10-5. "How
•
to check inverter/
compressor".
Check stop valve.
•
Refer to 10-5. "Check
•
of outdoor thermistors".
Defective outdoor
thermistors can be
identifi ed by checking
the blinking pattern of
LED.
Reconnect compressor
•
connector.
Refer to 10-5. "How
•
to check inverter/
compressor".
Check stop valve.
•
Reconnect compressor
•
connector.
Refer to 10-5. "How
•
to check inverter/
compressor".
Check refrigerant circuit
•
and refrigerant amount.
Refer to 10-5. "Check
•
of LEV".
Indoor/
outdoor unit
failure mode
recall function
○○
○○
—
—
—
Outdoor unit
failure mode
recall function
○
○
○
6-time fl ash
2.5 seconds
OFF
7-time fl ash
2.5 seconds
OFF
8-time fl ash
2.5 seconds
OFF
9-time fl ash
2.5 seconds
OFF
10-time fl ash
2.5 seconds
OFF
11-time fl ash
2.5 seconds
OFF
12-time fl ash
2.5 seconds
OFF
14-time fl ash
2.5 seconds
OFF
High pressure
—
Fin temperature/ P.C. board
temperature
Outdoor fan motor
Nonvolatile memory data 5-time fl ash
Discharge temperature
DC voltage 8-time fl ash
Each phase current of
compressor
Overcurrent Compressor openphase
Stop valve (Closed valve) 14-time fl ash
7-time fl ash
2.5 seconds OFF
—
2.5 seconds OFF
—
2.5 seconds OFF
9-time fl ash
2.5 seconds OFF
10-time fl ash
2.5 seconds OFF
2.5 seconds OFF
Temperature of indoor coil thermistor
exceeds 158°F (70°C) in HEAT mode.
Temperature of defrost thermistor
exceeds 158°F (70°C) in COOL mode.
Temperature of fi n temperature
thermistor on the inverter P.C. board
exceeds 167 ~ 176°F (75 ~ 80°C), or
temperature of P.C. board temperature
thermistor on the inverter P.C. board
exceeds 158 ~ 167°F (70 ~ 75°C).
Outdoor fan has stopped 3 times in a
row within 30 seconds after outdoor fan
start-up.
Nonvolatile memory data cannot be
read properly.
Temperature of discharge temperature
thermistor has been 122°F (50°C) or
less for 20 minutes.
DC voltage of inverter cannot be
detected normally.
Each phase current of compressor
cannot be detected normally.
Large current fl ows into intelligent
power module (IPM).
The open-phase operation of
compressor is detected.
The interphase short out occurs in the
output of the intelligent power module
(IPM).
The compressor winding shorts out.
Closed valve is detected by compressor
current.
Check refrigerant circuit
•
and refrigerant amount.
Check stop valve.
•
Check around outdoor
•
unit.
Check outdoor unit air
•
passage.
Refer to 10-5. "Check
•
of outdoor fan motor".
Refer to 10-5. "Check
•
of outdoor fan motor".
Refer to 10-5. "Check
of inverter P.C. board".
Replace the inverter
•
P.C. board.
Refer to 10-5. "Check
•
of LEV".
Check refrigerant circuit
•—
and refrigerant amount.
Refer to 10-5. "How
•
to check inverter/
compressor".
Reconnect compressor
•
connector.
Refer to 10-5. "How
•
to check inverter/
compressor".
Check stop valve •
NOTE: Blinking patterns of this mode differ from the ones of Troubleshooting check table (10-3.).
19
—
—
—
○
○
○
○○
○
—
—
○
○
○○
10-3. TROUBLESHOOTING CHECK TABLE
No. Symptom LED indication
Outdoor unit
does not oper-
1
ate.
2
3
4
5
6
'Outdoor unit
stops and
7
restarts 3 minutes later' is
repeated.
8
9
1-time fl ash every
2.5 seconds
6-time fl ash
2.5 seconds OFF
11-time fl ash
2.5 seconds OFF
14-time fl ash
2.5 seconds OFF
2-time fl ash
2.5 seconds OFF
3-time fl ash
2.5 seconds OFF
4-time fl ash
2.5 seconds OFF
Abnormal point/
Condition
Outdoor power system
Outdoor thermistors Discharge temperature thermistor, fi n temperature thermistor,
Outdoor control system
Serial signal The communication fails between the indoor and outdoor unit
Stop valve/
Closed valve
Outdoor unit
(Other abnormality)
Overcurrent protection
Discharge temperature overheat protection
Fin temperature
/P.C. board temperature thermistor
overheat protection
Condition Correspondence
Overcurrent protection stop is continuously performed 3 times
within 1 minute after the compressor gets started, or failure of
restart of compressor has repeated 24 times.
defrost thermistor, P.C. board temperature thermistor or ambient temperature thermistor shorts or opens during compressor
running.
Nonvolatile memory data cannot be read properly.
(POWER lamp of the indoor unit lights up or fl ashes 7 times.)
for 3 minutes.
Closed valve is detected by compressor current. Check stop valve. •
Outdoor unit is defective.Refer to 10-2.2. "Flow chart of the
Large current fl ows into intelligent power module.
When overcurrent protection occurs within 10 seconds after
compressor starts, compressor restarts after 15 seconds.
Temperature of discharge temperature thermistor exceeds 241
°F (116°C), compressor stops. Compressor can restart if discharge temperature thermistor reads 212°F (100°C) or less 3
minutes later.
Temperature of fi n temperature thermistor on the heat sink
exceeds 167 ~ 176°F (75 ~ 80°C) or temperature of P.C. board
temperature thermistor on the inverter P.C. board exceeds 158
~ 167°F (70 ~ 75°C).
Reconnect connector of compres-
•
sor.
Refer to 10-5. "How to check in-
•
verter/compressor".
Check stop valve.
•
Refer to 10-5. "Check of outdoor
•
thermistors".
Replace inverter P.C. board. •
Refer to 10-5. "How to check
•
miswiring and serial signal error.
•
detailed outdoor unit failure mode
recall function".
Reconnect connector of compres-
•
sor.
Refer to 10-5. "How to check in-
•
verter/compressor".
Check stop valve.
•
Check refrigerant circuit and refrig-
•
erant amount.
Refer to 10-5. "Check of LEV".
•
Check around outdoor unit.
•
Check outdoor unit air passage.
•
Refer to 10-5. "Check of outdoor
•
fan motor".
10
11
12
13
14
Outdoor unit
15
operates.
16
17
NOTE: 1. The location of LED is illustrated at the right fi gure. Refer to 10-6.1.
2. LED is lighted during normal operation.
The fl ashing frequency shows the number of times the LED blinks after every 2.5-second OFF. Flashing
(Example) When the fl ashing frequency is “2”.
5-time fl ash
2.5 seconds OFF
8-time fl ash
2.5 seconds OFF
10-time fl ash
2.5 seconds OFF
12-time fl ash
2.5 seconds OFF
13-time fl ash
2.5 seconds OFF
1-time fl ash
2.5 seconds OFF
3-time fl ash
2.5 seconds OFF
4-time fl ash
2.5 seconds OFF
High pressure protection
Compressor synchronous abnormality
Outdoor fan motor Outdoor fan has stopped 3 times in a row within 30 seconds
Each phase current
of compressor
DC voltage DC voltage of inverter cannot be detected normally. Refer to 10-5. "How to check in-
Frequency drop by
current protection
Frequency drop by
high pressure protection
Frequency drop by
defrosting in COOL
mode
Frequency drop by
discharge temperature protection
Indoor coil thermistor exceeds 158°F (70°C) in HEAT mode.
Defrost thermistor exceeds 158°F (70°C) in COOL mode.
The waveform of compressor current is distorted. Reconnect connector of compres-
after outdoor fan start-up.
Each phase current of compressor cannot be detected normally.
Current from power outlet is nearing Max. fuse size.The unit is normal, but check the
Temperature of indoor coil thermistor exceeds 131°F (55°C) in
HEAT mode, compressor frequency lowers.
Indoor coil thermistor reads 46°F (8°C) or less in COOL mode,
compressor frequency lowers.
Temperature of discharge temperature thermistor exceeds 232
°F (111°C), compressor frequency lowers.
Check refrigerant circuit and refrig-
•
erant amount.
Check stop valve.
•
•
sor.
Refer to 10-5. "How to check in-
•
verter/compressor".
Refer to 10-5. "Check of outdoor
•
fan motor.
Refer to 10-5. "Check of inverter
•
P.C. board.
Refer to 10-5. "How to check in-
•
verter/compressor".
•
verter/compressor".
following.
Check if indoor fi lters are clogged.
•
Check if refrigerant is short.
•
Check if indoor/outdoor unit air cir-
•
culation is short cycled.
Check refrigerant circuit and refrig-
•
erant amount.
Refer to 10-5.
•
Refer to 10-5. "Check of outdoor
•
thermistors".
Inverter P.C. board (Parts side)
Flashing →
"Check of LEV".
LED
ON
OFF
2.5-second OFF
0.5-second ON
2.5-second OFF
0.5-second ON
20
No. Symptom LED indication
Outdoor unit
operates.
18
19
20
7-time fl ash
2.5 seconds OFF
8-time fl ash
2.5 seconds OFF
9-time fl ash
2.5 seconds OFF
Abnormal point/
Condition
Low discharge temperature protection
PAM protection
PAM: Pulse Amplitude Modulation
Inverter check mode The connector of compressor is disconnected, inverter check
Temperature of discharge temperature thermistor has been
122°F (50°C) or less for 20 minutes.
The overcurrent fl ows into IGBT (Insulated Gate Bipolar tran-
sistor : TR821) or the bus-bar voltage reaches 320 V or more,
PAM stops and restarts.
mode starts.
Condition Correspondence
Refer to 10-5. "Check of LEV".
•
Check refrigerant circuit and refrig-
•
erant amount.
This is not malfunction. PAM protection will be activated in the following
cases;
1 Instantaneous power voltage drop
(Short time power failure)
2 When the power supply voltage is
high.
Check if the connector of the com-
•
pressor is correctly connected.
Refer to 10-5. "How to check inverter/compressor".
21
10-4. TROUBLE CRITERION OF MAIN PARTS
MUZ-FD09NA MUZ-FD12NA
Part name Check method and criterion Figure
Defrost thermistor
(RT61)
Ambient temperature
thermistor (RT65)
Outdoor heat exchanger temperature
thermistor (RT68)
Discharge temperature thermistor
(RT62)
Fin temperature
thermistor (RT64)
Measure the resistance with a tester.
Refer to 10-6. “Test point diagram and voltage”, 1. “Inverter P.C.
board”, the chart of thermistor.
Measure the resistance with a tester. Before measurement, hold the
thermistor with your hands to warm it up.
Refer to 10-6. “Test point diagram and voltage”, 1. “Inverter P.C.
board”, the chart of thermistor.
Compressor
Outdoor fan motor
R. V. coil (21S4)
Expansion valve coil
(LEV)
Measure the resistance between terminals using a tester.
(Winding temperature : -4 ~ 104°F (-20 ~ 40°C))
Normal
U-V
U-W
1.52 ~ 2.17 Ω
V-W
Measure the resistance between lead wires using a tester.
(Part temperature : 14 ~ 104°F (-10 ~ 40°C))
Color of lead wire Normal
RED – BLK
BLK – WHT
11 ~ 16 Ω
WHT – RED
Measure the resistance using a tester.
(Part temperature : 14 ~ 104°F (-10 ~ 40°C))
Normal
970 ~ 1380 Ω
Measure the resistance using a tester.
(Part temperature : 14 ~ 104°F (-10 ~ 40°C))
Color of lead wire Normal
WHT – RED
RED – ORN
YLW – BRN
37 ~ 54 Ω
BRN – BLU
WHT
WHT
WHT
RED
ORN
RED BLK
23
V
23
V
W
U
RED BLK
1
W
U
LEV
YLW
BRN
1
BLU
22
10-5. TROUBLESHOOTING FLOW
A How to check inverter/compressor
Disconnect the connector (CN61) between
compressor and the intelligent power module
(IPM).
Check the voltage between terminals.
Are the voltages balanced?
Yes
Check the compressor.
No
See 10-5. “Check of open phase”.
Replace the inverter P.C. board.
See 10-5. “Check of compressor”.
B Check of open phase
●With the connector between the compressor and the intelligent power module disconnected,
activate the inverter and check if the inverter is normal by measuring the balance of voltage
between the terminals.
Output voltage 115 V
<< Operation method>>
Start cooling or heating operation by pressing EMERGENCY OPERATION switch on the
indoor unit. (TEST RUN OPERATION : Refer to 7-6.)
<<Measurement point>>
at 3 points
BLK (U) - WHT (V)
BLK (U) - RED (W)
WHT(V) - RED (W)
NOTE: 1. Output voltage varies according to power supply voltage.
2. Measure the voltage by analog type tester.
3. During this check, LED of the inverter P.C. board fl ashes 9 times. (Refer to 10-6.1.)
Measure AC voltage between the
lead wires at 3 points.
9-time flash
2.5-second OFF
C Check of compressor
Refer to 10-5. “Check of compressor
winding”.
Is the compressor normal?
Yes
Refer to 10-5. “Check of compressor
operation time”.
Does the compressor operate continuously?
Yes
OK.
No
No
Replace the compressor.
Refer to 10-5. “Check of compressor start failure”.
23
D Check of compressor winding
●Disconnect the connector (CN61) between the compressor and intelligent power module, and measure the resistance between
the compressor terminals.
<<Measurement point>>
at 3 points
BLK-WHT
BLK-RED
Measure the resistance between the lead wires at 3 points.
WHT-RED
<<Judgement>>
Refer to 10-4.
0[Ω] ················Abnormal [short]
Infinite[Ω] ·······Abnormal [open]
NOTE: Be sure to zero the ohmmeter before measurement.
E Check of compressor operation time
<<Judgement>>
●Connect the compressor and activate the inverter. Then measure
the time until the inverter stops due to over current.
<<Operation method>>
Start heating or cooling operation by pressing EMERGENCY
OPERATION switch on the indoor unit.
(TEST RUN OPERATION : Refer to 7-6.)
<<Measurement>>
Measure the time from the start of compressor to the stop of
1
Heat the compressor with
a drier for about 20 minutes.
Do not recover refrigerant
gas while heating.
24
Heating part
G Check of outdoor thermistors
Disconnect the connector of thermistor in the outdoor P.C. board (see
below table), and measure the resistance of thermistor.
Is the thermistor normal? (Refer to 10-6.1.)
Yes
Reconnect the connector of thermistor.
Turn ON the power supply and press EMERGENCY OPERATION switch.
Does the unit operate for 10 minutes or more
without showing thermistor abnormality?
Yes
OK.
(Cause is poor contact.)
Thermistor Symbol Connector, Pin No. Board
DefrostRT61Between CN641 pin1 and pin2
Discharge temperature RT62Between CN641 pin3 and pin4
Fin temperature RT64Between CN642 pin1 and pin2
Ambient temperature RT65Between CN643 pin1 and pin2
Outdoor heat exchanger temperature RT68Between CN644 pin1 and pin3
No
No
Replace the thermistor except RT64. When RT64 is
abnormal, replace the inverter P.C. board.
Replace the inverter P.C. board.
Inverter P.C. board
H Check of R.V. coil
First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 10-4.
In case CN721 is not connected or R.V. coil is open, voltage is generated between the terminal pins of the connector
although any signal is not being transmitted to R.V. coil.
Check if CN721 is connected.
Unit operates COOL mode even if it is set to HEAT mode.
Disconnect connector (CN61)
between the compressor and the
intelligent power module.
Turn ON the power supply and
press EMERGENCY OPERATION
switch twice (HEAT mode).
Is there 230 VAC between CN721 and
on the inverter P.C. board 3 minutes
after the power supply is turned ON?
Replace the 4-way valve.
Unit operates HEAT mode even if it is set to COOL mode.
Disconnect connector (CN61)
between the compressor and the
intelligent power module.
Turn ON the power supply and
press EMERGENCY OPERATION
switch once (COOL mode).
Is there 230 VAC between CN721 and
on the inverter P.C. board 3 minutes
after the power supply is turned ON?
Replace the 4-way valve.
25
Yes
No
Replace the inverter
No
P.C. board.
Replace the inverter
Yes
P.C. board.
I Check of outdoor fan motor
Disconnect CN932 from the inverter P.C. board, and
measure the resistance of the outdoor fan motor.
Is the outdoor fan motor normal?
(Refer to 10-4.)
Yes
Replace the inverter P.C. board.
J Check of power supply
Disconnect the connector (CN61)
between compressor and intelligent
power module.
Turn ON power supply and press
EMERGENCY OPERATION switch.
Does POWER lamp on the indoor
unit light up?
Yes
No
No
Rectify indoor/outdoor
connecting wire.
Is there voltage 208/230 VAC
between the indoor terminal
block S1 and S2?
Replace the outdoor fan motor.
Yes
Replace the indoor
electronic control P.C.
No
board.
Is there voltage 280 ~ 370 VDC
between DB61 (+) and DB61 (–) on
the inverter P.C. board?
(Refer to 10-6.1.)
No
Check the electric parts in main circuit.
Yes
Dose LED on the inverter P.C.
board light up or fl ash? (Refer
to 10-6.1.)
Yes
If light up, OK.
If fl ash, refer to 10-3.
26
Replace the inverter
No
P.C. board.
DB61
Inverter P.C. board
(Solder side)
280 ~ 370 VDC
K Check of LEV (Expansion valve)
Turn ON the power supply.
<Preparation of the remote controller>
While pressing both OPERATION SELECT button
and TOO COOL button on the remote controller at the
same time, press RESET button.
First, release RESET button.
And release the other two buttons after all LCD except
the set temperature in operation display section of the
remote controller is displayed after 3 seconds.
Press OPERATE/STOP (ON/OFF) button of the remote
controller (the set temperature is displayed) with the
remote controller headed towards the indoor unit. 1
Expansion valve operates in full-opening direction.
Do you hear the expansion valve "click,
click·······"?
Do you feel the expansion valve vibrate
on touching it ?
No
Yes
OK.
1. Regardless of normal or abnormal condition, a short beep
is emitted once the signal is received.
Is LEV coil properly fi xed to
the expansion valve?
Yes
Does the resistance of LEV
coil have the characteristics?
(Refer to 10-4.)
No
Replace the LEV coil.
NOTE : After check of LEV, do the undermentioned operations.
1. Turn OFF the power supply and turn ON it again.
2. Press RESET button on the remote controller.
No
Yes
Properly fi x the LEV coil to the expansion valve.
Measure each voltage between connector
pins of CN724 on the inverter P.C. board.
1.Pin (-) — Pin (+)
2.Pin (-) — Pin (+)
3.Pin (-) — Pin (+)
4.Pin (-) — Pin (+)
Is there about 3 ~ 5 VAC between each?
NOTE: Measure the voltage by an analog
tester.
Replace the expansion valve.
Yes
Replace the inverter P.C.
No
board.
27
L Check of inverter P.C. board
Check the outdoor fan motor.
(Refer to10-5. .)
Is the fuse (F901) blown on the inverter P.C. board?
No
Check the connection of the connectors
(CN932) of the outdoor fan motor.
If the connection is poor, make it correct.
Operate the outdoor unit by starting
EMERGENCY OPERATION.
Check the LED indication on the inverter P.C. board.
Does the LED fl ash 10 times?
Yes
(10-time fl ash)
Replace the inverter P.C. board.
Yes
No
Inverter P.C. board
(Solder side)
CN932
Check the corresponding parts
following LED indication.
(Refer to 10-3.)
28
M How to check miswiring and serial signal error
Turn OFF the power supply.
Is there rated voltage in the
power supply?
Yes
Turn ON the power supply.
Is there rated voltage between
outdoor terminal block S1 and
S2?
Press EMERGENCY OPERATION switch once.
Does AREA-L lamp light up? <Confi rmation of
the power to the indoor unit>
Is serial signal error indicated 6 minutes later?
Turn OFF the power supply.
Check once more if the indoor/outdoor
B
connecting wire is not miswiring.
Short-circuit outdoor terminal block S2
and S3.
Turn ON the power supply.
Yes
Yes
Yes
A
1
No
No
Check the power supply.
Check the wiring.
No
Is there any miswiring,
poor contact, or wire
disconnection of the
No
indoor/outdoor connecting wire?
1. Miswiring may damage indoor electronic control P.C.
board during the operation.
Be sure to confi rm the wiring is correct before the opera-
tion starts.
3. Be sure to check this within 3 minutes after turning ON.
After 3 minutes, LED blinks 6 times. Even when the
inverter P.C. board or the outdoor electronic control P.C.
board is normal, LED blinks 6 times after 3 minutes.
No
Yes
Correct them.
A
Turn OFF inverter-controlled lighting
•
equipment.
Turn OFF the power supply and then
•
turn ON again.
Press EMERGENCY OPERATION
•
switch.
Reinstall
•
either the unit
or the light
each other
No
•
away.
Attach a fi lter
on remote
control receiving section
of the indoor
unit.
Is serial signal
error indicated 6
minutes later?
Yes
B
Does the LED on the inverter P.C. board or
the outdoor electronic control P.C. board
repeat "3.6-second-OFF and 0.8-secondON quick blinking"? 3
Yes
Turn OFF the power supply.
Remove the short-circuit between
outdoor terminal block S2 and S3.
Turn ON the power supply.
Is there amplitude of 10 to 20 VDC
between outdoor terminal block S2 and
S3? <Confi rmation of serial signal>
Yes
Is there rated voltage between
indoor terminal block S1 and S2?
<Confi rmation of power voltage>
Yes
Replace the indoor electronic control P.C. board.
Be sure to release the failure-mode recall function
after checking.
No
(Lighted
or not
lighted)
No
No
29
Replace the inverter P.C. board or the outdoor electronic control P.C. board.
2
2. Be careful to the residual
voltage of smoothing capacitor.
Is there any error of the indoor/outdoor connecting wire,
such as the damage of the wire,
intermediate connection, poor
contact to the terminal block?
Is there any error of the indoor/outdoor connecting wire,
such as the damage of the wire,
intermediate connection, poor
contact to the terminal block?
No
No
Replace the indoor/
outdoor connecting
Yes
wire.
Replace the indoor/
outdoor connecting
Yes
wire.
N Electromagnetic noise enters into TV sets or radios
Is the unit grounded?
Yes
Is the distance between the antennas
and the indoor unit within 9.91 ft., or is
the distance between the antennas and
the outdoor unit within 9.91 ft.?
No
Is the distance between the TV sets or
radios and the indoor unit within 3.28
ft., or is the distance between the TV
sets or radios and the outdoor unit
within 9.91 ft.?
No
Are the antennas damaged?
Is the coaxial cable damaged?
Is there any poor contact in the antenna wiring?
No
Is the indoor/outdoor connecting wire
of the air conditioner and the wiring of
the antennas close?
No
No
Yes
Yes
Yes
Yes
Ground the unit.
Extend the distance between the antennas and
the indoor unit, and/or the antennas and the
outdoor unit.
Extend the distance between the TV sets and/or
radios and the indoor unit, or the TV sets or
radios and the outdoor unit.
Replace or repair the antenna.
Replace or repair the coaxial cable.
Extend the distance between the indoor/outdoor
connecting wire of the air conditioner and the wiring of the antennas.
Even if all of the above conditions are fulfi lled, the electromagnetic noise may enter, depending on the electric fi eld strength
or the installation condition (combination of specifi c conditions such as antennas or wiring).
Check the followings before asking for service.
1. Devices affected by the electromagnetic noise
TV sets, radios (FM/AM broadcast, shortwave)
2. Channel, frequency, broadcast station affected by the electromagnetic noise
3. Channel, frequency, broadcast station unaffected by the electromagnetic noise
4. Layout of ;
indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, grounding wire, antennas, wiring from antennas, receiver
5. Electric fi eld intensity of the broadcast station affected by the electromagnetic noise
6. Presence or absence of amplifi er such as booster
7. Operation condition of air conditioner when the electromagnetic noise enters in
1) Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic
noise.
2) Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button on the remote controller
for power ON, and check for the electromagnetic noise.
3) After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the electromagnetic noise.
4) Press OPERATE/STOP (ON/OFF) button on the remote controller for power OFF, when the outdoor unit stops but the
indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise.
30
10-6. TEST POINT DIAGRAM AND VOLTAGE
1. Inverter P.C. board
MUZ-FD09NA MUZ-FD12NA
Back side of unit
AC 208/230 V
Fuse (F901)
250 V 3.15 A
Output to
drive compressor
(LDU,
LDV,
LDW)
DB61
DC260 ~300 V
(-)
(+)
Smoothing
capacitor
(C63)
Smoothing
capacitor
(C62)
Fuse (F801)
250 V 3.15 A
Smoothing
capacitor
(C61)
Fuse (F701)
250 V 3.15 A
R.V. coil
(CN721)
208/230 VAC
AC208/230 V
Front side of unit
Defrost thermistor(RT61)
Ambient temperature thermistor(RT65)
Outdoor heat exchanger temperature thermistor(RT68)
100
90
80
70
60
50
40
30
Resistance(kΩ)
20
10
0
-41432506886 104
Output to drive outdoor
fan motor (CN932)
Temperature(°F)
Fin temperature
thermistor /RT64
(CN642)
Outdoor heat exchanger
temperature thermistor
/RT68(CN644)
Discharge temperature thermistor(RT62)
700
600
500
400
300
200
Resistance(kΩ)
100
0
32 50 68 86 104 122 140 158 176 194 212 230 248
Defrost thermistor
/RT61(CN641)
Ambient temperature
thermistor /RT65
(CN643)
Temperature(°F)
Discharge temperature
thermistor /RT62
LEV
connector
(CN724)
(CN641)
Jumper wire for
changing defrost
setting (JS)
Fin temperature thermistor(RT64)
200
180
160
140
120
100
80
60
Resistance(kΩ)
40
20
0
32 50 68 86 104 122 140 158 176
Temperature(°F)
Jumper wire
for pre-heat
control setting
(JK)
31
11
DISASSEMBLY INSTRUCTIONS
<"Terminal with locking mechanism" Detaching points>
The terminal which has the locking mechanism can be detached as shown below.
There are two types (refer to (1) and (2)) of the terminal with locking mechanism.
The terminal without locking mechanism can be detached by pulling it out.
Check the shape of the terminal before detaching.
(1) Slide the sleeve and check if there is a locking lever or not.
Sleeve
Slide the sleeve.
Pull the terminal while
Locking lever
pushing the locking
lever.
11-1. MUZ-FD09NA MUZ-FD12NA
OPERATING PROCEDUREPHOTOS
1. Removing the cabinet
(1) Remove the screw fixing the service panel. (See
Photo 1.)
(2) Pull down the service panel and remove it. (See Photo
1.)
(3) Remove the screws fixing the conduit cover. (See
Photo 2.)
(4) Remove the conduit cover. (See Photo 2.)
(5) Disconnect the power supply wire and indoor/outdoor
connecting wire.
(6) Remove the screws fixing the top panel. (See Photo 1.)
(7) Remove the top panel. (See Photo 1.)
(8) Remove the screws fixing the cabinet.
(9) Remove the cabinet.
(10)
Remove the screws fixing the back panel.
(11)
Remove the back panel.
Photo 2
(2) The terminal with this connector has the
locking mechanism.
Hold the sleeve, and
pull out the terminal
slowly.
Connector
NOTE : Turn OFF power supply before disassembling.
Photo 1
Screws
of the top
panel
Screw of the
cabinet
Screws of
the top panel
Screw of
the service
panel
Back
panel
Hooks
Conduit cover
Screw of the
conduit cover
Conduit plate
32
32
Screws of
the cabinet
Service
panel
OPERATING PROCEDURE
PHOTOS
2. Removing the inverter assembly, inverter P.C. board
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the lead wire to the reactor and the following
connectors;
<Inverter P.C. board>
CN721 (R.V.coil)
CN932 (Fan motor)
CN641 (Defrost thermistor and discharge temperature ther-
mistor)
CN643 (Ambient temperature thermistor)
CN644 (Outdoor heat exchanger temperature thermistor)
CN724 (LEV)
(3) Remove the compressor connector (CN61).
(4) Remove the screws fixing the relay panel. (See Photo 3.)
(5) Remove the inverter assembly. (See Photo 4.)
(6) Remove the screw of the ground wire and screw of the
T.B.support. (See Photo 4.)
(7) Remove the inverter P.C. board from the inverter assembly.
3. Removing R.V. coil
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Remove the R.V. coil. (See Photo 5.)
Photo 3
Screws of the
relay panel
Photo 4 (Inverter assembly)
Heat sink
Inverter
P.C. board
Screw of the
T.B.support
T.B.support
4. Removing the discharge temperature thermistor,
defrost thermistor and outdoor heat exchanger temperature thermistor.
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Pull out the discharge temperature thermistor from its hold-
er. (See Photo 5.)
(3) Pull out the defrost thermistor from its holder. (See Photo 6.)
(4) Pull out the outdoor heat exchanger temperature thermistor
from its holder. (See Photo 6.)
33
Photo 5
Screw of the
ground wire
R.V. coil
Discharge temperature thermistor
OPERATING PROCEDURE
PHOTOS
5. Removing outdoor fan motor
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the connectors for outdoor fan motor.
(3) Remove the propeller nut. (See Photo 7.)
(4) Remove the propeller. (See Photo 7.)
(5) Remove the screws fixing the fan motor. (See Photo 7.)
(6) Remove the fan motor.
6. Removing the compressor and 4-way valve
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Remove the inverter assembly. (Refer to 2.)
(3) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure
gauge shows 0 PSIG.
(4) Detach the welded part of the suction and the discharge
pipe connected with compressor.
(5) Remove the nuts of compressor legs.
(6) Remove the compressor.
(7) Detach the welded part of pipes connected with 4-way
valve. (See Photo 8.)
Photo 6
Photo 7
Outdoor heat
exchanger temperature thermistor
Defrost thermistor
Screws of the outdoor fan motor
34
Propeller
Photo 8
Propeller nut
Welded parts of 4-way valve
35
TM
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Copyright 2008 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD
Distributed in Mar. 2008. No. OBH498 REVISED EDITION-A 7
Distributed in Jan. 2008. No. OBH498 7
Made in Japan
New publication, effective Mar. 2008
Specifications subject to change without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.