Mitsubishi Electronics MUZ-FD12NA, MUZ-FD12NA- U1, MUZ-FD09NA- U1 User Manual

OUTDOOR UNIT
Revision A:
• 3. SPECIFICATION has been corrected. Please void OBH498.
SERVICE MANUAL
Wireless type Models
MUZ-FD09NA MUZ-FD09NA­MUZ-FD12NA
MUZ-FD12NA-
U1
U1
HFC
utilized
R410A
No. OBH498
REVISED EDITION-A
Indoor unit service manual
MSZ-FD•NA Series (OBH497)
NOTE:
RoHS compliant products have <G> mark on the spec name plate.
CONTENTS
1. TECHNICAL CHANGES ··································· 3
2. PART NAMES AND FUNCTIONS ····················· 3
3. SPECIFICATION ················································ 4
4. OUTLINES AND DIMENSIONS ························ 6
5. WIRING DIAGRAM ············································ 7
6. REFRIGERANT SYSTEM DIAGRAM ··············· 8
8. ACTUA TOR CONTROL ··································· 15
9. SERVICE FUNCTIONS ··································· 16
10. TROUBLESHOOTING ····································· 16
11. DISASSEMBLY INSTRUCTIONS ···················· 32
PARTS CATALOG (OBB498)
TM
Revision A:
• 3. SPECIFICATION has been corrected.
2
1
TECHNICAL CHANGES
MUZ-FD09NA MUZ-FD09NA ­MUZ-FD12NA MUZ-FD12NA -
1. New model
2
MUZ-FD09NA MUZ-FD12NA
PART NAMES AND FUNCTIONS
U1
U1
Air inlet
Piping
Drain hose
Air outlet
Drain outlet
33
3
SPECIFICATION
Outdoor unit model MUZ-FD09NA MUZ-FD12NA
Capacity
Rated (Minimum~Maximum)
Capacity Rated
Power consumption
Rated (Minimum~Maximum)
Power consumption Rated
1
EER
[SEER] 3 Cooling 13.8 [23.0] 12.5 [22.0]
Cooling 1
Heating 47 1
Heating 17 2
Cooling 1
Heating 47 1
Heating 17 2
Btu/h 9,000 (2,800~9,000) 12,000 (2,800~12,000) Btu/h 10,900 (3,000~18,000) 13,600 (3,000~21,000) Btu/h 12,500 13,600 W W
650 (160~650) 960 (160~960)
750 (150~2,400)
980
(150~2,400)
W 1,730 1,780
HSPF IV (V) 4 Heating 10.55 (7.4) 10.55 (7.4) COP Heating
1 4.26 4.07 Power supply V , phase , Hz 208/230 , 1 , 60 Max. fuse size (time delay) A 15 Min. circuit ampacity A 12 Fan motor F.L.A 0.56
Model SNB130FQAH
Compressor
R.L.A 8.6 L.R.A 10.8
Refrigerant control Liner expansion valve
Sound level
1
Cooling dB(A) 48 48 Heating dB(A) 49 49
Defrost method Reverse cycle
W in. 31-1/2
Dimensions
D in. 11-1/4 H in. 21-5/8
Weight Ib. 80 External fi nish Munsell 3Y 7.8/1.1 Remote controller Wireless type Control voltage
(by built-in transformer)
VDC 12 - 24
Refrigerant piping Not supplied
Refrigerant pipe size (Min. wall thickness)
Connection method
Between the indoor & outdoor units
Liquid in. 1/4 (0.0315) Gas in. 3/8 (0.0315) Indoor Flared Outdoor Flared Height difference ft. 40
Piping length ft. 65 Refrigerant charge (R410A) 2 lb. 9 oz. Refrigeration oil (Model) NE022
NOTE : Test conditions are based on ARI 210/240.
1 : Rating conditions (Cooling) — Indoor : 80˚FDB, 67˚FWB, Outdoor : 95˚FDB, (75˚FWB) Rated frequency (Heating) — Indoor : 70˚FDB, 60˚FWB, Outdoor : 47˚FDB, 43˚FWB Rated frequency 2 : (Heating) — Indoor : 70˚FDB, 60˚FWB, Outdoor : 17˚FDB, 15˚FWB Maximum frequency
44
Test condition
3, 4
Mode Test
ARI
"A" Cooling Steady State at rated compressor Speed
"B-2" Cooling Steady State at rated compressor Speed
SEER
(Cooling)
HSPF
(Heating)
5
: At Intermediate compressor Speed
"B-1" Cooling Steady State at minimum compressor Speed
Low ambient Cooling Steady State at minimum compressor Speed
Intermediate Cooling Steady State at Intermediate compressor Speed
Standard Rating-Heating at rated compressor Speed
Low temperature Heating at rated compressor Speed
Max temperature Heating at minimum compressor Speed
High temperature Heating at minimum compressor Speed
Frost Accumulation at rated compressor Speed
Frost Accumulation at Intermediate compressor Speed
5
5
= ("Cooling rated compressor speed" - "minimum compressor speed") / 3 + "minimum compressor speed".
OPERATING RANGE
(1) POWER SUPPLY
Indoor air condition Outdoor air condition
Dry bulb (°F) Wet bulb (°F) Dry bulb (°F) Wet bulb (°F)
80 67 95 (75)
80 67 82 (65)
80 67 82 (65)
80 67 67 (53.5)
80 67 87 (69)
70 60 47 43
70 60 17 15
70 60 62 56.5
70 60 47 43
70 60 35 33
70 60 35 33
Outdoor unit
(2) OPERATION
Mode Condition
Standard temperature 80 67 95
Cooling
Heating
Maximum temperature 90 73 115 — Minimum temperature 67 57 14 — Maximum humidity 78 % — Standard temperature 70 60 47 43 Maximum temperature 80 67 75 65 Minimum temperature 70 60 14 13
Rated voltage Guaranteed Voltage
208/230 V
1 phase
60 Hz
Min.187 V
DB WB DB WB
208 V 230 V Max.253 V
Intake air temperature (°F)
Indoor Outdoor
55
4
OUTLINES AND DIMENSIONS
MUZ-FD09NA MUZ-FD12NA
21-5/8
1-3/4
Air in
handle
11-1/32
7/8
13/32
15-3/4
Air in
11-29/32
5-15/16
Drain hole 1-5/8
Air out
2- 3/8 13/16 Oval hole
19-11/16
31-1/2
1-9/16
12 ~ 12-3/4
11/16
2
2-23/32
13-9/16
5-7/8
REQUIRED SPACE
4 in. or more
17/3229/32 11-1/4
Open two sides of left, right, or rear side.
Liquid pipe :1/4 (flared) Gas pipe :3/8 (flared)
6-23/32
Unit: inch
Basically open 4 inch or more without any obstruction in front and on both sides of the unit.
4 in. or more
14 in. or more
8 in. or more
66
5
MUZ-FD09NA MUZ-FD12NA
WIRING DIAGRAM
77
6
REFRIGERANT SYSTEM DIAGRAM
MUZ-FD09NA MUZ-FD12NA
Refrigerant pipe ø3/8 (with heat insulator)
Stop valve (with service port)
Flared connection
Flared connection
Stop valve (with strainer)
Refrigerant pipe 1/4 (with heat insulator)
4-way valve
Muffler
Discharge temperature thermistor RT62
Service port
Capillary tube
O.D. 0.118 ×I.D. 0.079
× 9-7/16
(ø3.0 × ø2.0 × 240)
Muffler
Service port
Compressor
Defrost thermistor RT61
Capillary tube
O.D. 0.118× I.D. 0.071
× 23-5/8
3.0
× ø
1.8×600
Expansion valve
)
Refrigerant flow in cooling Refrigerant flow in heating
Outdoor heat exchanger
Strainer #100
R.V. coil heating ON cooling OFF
Outdoor heat exchanger temperature thermistor RT68
Ambient temperature thermistor RT65
Unit:inch
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Refrigerant piping : ft. Piping size O.D : in.
Model
MUZ-FD09NA MUZ-FD12NA
Max. Length
A
Max. Height difference
B
Gas Liquid
65 40 3/8 1/4
Indoor unit
Max. Height
difference
B
Max. Length A
Outdoor unit
ADDITIONAL REFRIGERANT CHARGE (R410A : oz.)
NOTE : Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
Model Outdoor unit precharged
MUZ-FD09NA MUZ-FD12NA
2 lb. 9 oz. 0 1.62 4.86 8.10 11.34 12.96
25 30 40 50 60 65
Refrigerant piping length (one way) : ft.
NOTE : Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
Calculation : X oz. = 1.62 / 5 oz. / ft. × (Refrigerant piping length (ft.) - 25)
8
DATA7
MUZ-FD09NA MUZ-FD12NA
7-1. PERFORMANCE DATA
1) COOLING CAPACITY
Indoor air Outdoor intake air DB temperature (˚F)
Model
MUZ-FD09NA
MUZ-FD12NA
IWB 75 85 95 105 115
(˚F) TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC
71 11.0 6.9 0.58 10.3 6.5 0.63 9.7 6.1 0.68 9.0 5.6 0.72 8.3 5.2 0.75 67 10.4 7.9 0.55 9.7 7.4 0.60 9.0 6.8 0.65 8.4 6.4 0.69 7.7 5.8 0.72 63 9.8 8.8 0.52 9.1 8.1 0.58 8.5 7.6 0.62 7.7 6.9 0.66 7.0 6.3 0.69 71 14.7 8.8 0.85 13.7 8.2 0.94 12.9 7.7 1.01 12.0 7.2 1.06 11.0 6.6 1.10 67 13.9 10.2 0.81 13.0 9.5 0.89 12.0 8.8 0.96 11.2 8.1 1.02 10.3 7.5 1.07
63 13.1 11.3 0.77 12.1 10.5 0.85 11.3 9.7 0.92 10.3 8.9 0.98 9.4 8.1 1.02
NOTE : 1. IWB : Intake air wet-bulb temperature
TC : Total Capacity (x10 SHC : Sensible Heat Capacity (x10
3
Btu/h)
3
TPC : Total Power Consumption (kW)
2. SHC is based on 80˚F of indoor Intake air DB temperature.
2) COOLING CAPACITY CORRECTIONS
Refrigerant piping length (one way : ft.)
25 (std.) 40 65
MUZ-FD09NA MUY-FD12NA
1.0 0.954 0.878
3) HEATING CAPACITY
Indoor air Outdoor intake air WB temperature (˚F)
Model
IDB 15 25 35 43 45 55 (˚F) TC TPC TC TPC TC TPC TC TPC TC TPC TC TPC
75 6.3 0.56 7.9 0.66 9.4 0.73 10.6 0.77 11.0 0.78 12.4 0.81
MUZ-FD09NA
70 6.7 0.54 8.2 0.64 9.6 0.71 10.9 0.75 11.2 0.77 12.7 0.80 65 6.9 0.52 8.6 0.62 10.0 0.69 11.2 0.73 11.6 0.74 13.0 0.78 75 7.9 0.73 9.9 0.86 11.8 0.96 13.3 1.00 13.7 1.02 15.5 1.06
MUZ-FD12NA
70 8.4 0.71 10.2 0.84 12.0 0.93 13.6 0.98 14.0 1.00 15.8 1.04 65 8.6 0.68 10.7 0.81 12.4 0.91 14.0 0.96 14.4 0.97 16.2 1.02
NOTE : 1. IDB : Intake air dry-bulb temperature
TC : Total Capacity (x10
3
Btu/h)
TPC : Total Power Consumption (kW)
2. Above data is for heating operation without any frost.
Btu/h)
How to operate with fixed operational frequency of the compressor.
1. Press the EMERGENCY OPERATION switch on the front of the indoor unit, and select either EMERGENCY COOL mode or EMERGENCY HEAT mode before starting to operate the air conditioner.
2. The compressor starts with operational frequency.
3. The fan speed of the indoor unit is High.
4. This operation continues for 30 minutes.
5. In order to release this operation, press the EMERGENCY OPERATION switch twice or once, or press any button on the remote controller.
9
7-2. PERFORMANCE CURVE Cooling
MUZ-FD09NA
SHF at rating condition = 0.76
13
Indoor intake air WB te
12 11
Btu/h)
10
3
9 8
Total capacity
(10
7
0.7
Indoor intake air
(kW)
0.6
0.5
Total power consumption
65 75 85 95 105 115
Outdoor intake air DB temperature (°F)
Airflow
WB te
mperature (°F)
mpe
Heating
MUZ-FD09NA
= 381 CFM
Airflow
12
10
Btu/h)
8
3
Total capacity
(10
6
0.8
0.6
(kW)
0.4
Total power consumption
15 25 35 45 55
e air DB temperature
Indoor intak
Indoor intake air DB temperat
Outdoor intake air WB temperature (°F)
= 307 CFM
rature (°F)
)
(°F
ure (°F)
MUZ-FD12NA
SHF at rating condition = 0.73
15 14 13
Btu/h)
12
3
71 67 63
71 67 63
11
10
Total capacity
(10
1.2
1.1
1.0
(kW)
0.9
0.8
0.7
Total power consumption
Indoor
intak
9
oor intake air WB temperature (°F)
Ind
65 75 85 95 105 115
Outdoor intake air DB temperature (°F)
= 350 CFM
Airflow
e air WB temperat
ure
(°F)
71 67 63
71 67 63
MUZ-FD12NA
65
70
75
20 18 16
Btu/h)
14
3
12
Total capacity
(10
Indoor intake air DB temperature (°F)
10
8 6
75 70 65
1.1
1.0
(kW)
0.9
Indoor intake air
0.8
Total power consumption
0.7
0.6 15 25 35 45 55
Outdoor intake air WB temperature (°F)
Airflow
temperature (°F)
DB
= 420 CFM
65 70 75
75 70 65
This value of frequency is not the same as the actual frequency in operating. Refer to 7-5 and 7-6 for the relationships between frequency and capacity.
1010
7-3. CONDENSING PRESSURE Cooling
Data is based on the condition of indoor humidity 50 %. Air flow should be set to High speed.
MUZ-FD09NA
(PSIG)
580 540 500 460 420 380
Condensing pressure
340 300 260
68 70 75 80 85 90 95 100 105(°F)
oor DB temperature (°F)
Ind
Outdoor ambient temperature
86 80 75 70
MUZ-FD12NA
(PSIG)
580 540 500
86
460 420 380
Condensing pressure
340 300 260
68 70 75 80 85 90 95 100 105(°F)
Indoor DB temperature (°F)
Outdoor ambient temperature
80 75 70
(PSIG)
180 175 170 165 160 155 150 145 140
Suction pressure
135 130 125 120
68 70 75 80 85 90 95 100 105(°F)
(PSIG)
180 175 170 165 160 155 150 145 140
Suction pressure
135 130 125 120
68 70 75 80 85 90 95 100 105(°F)
Indoor DB temperature (°F)
Outdoor ambient temperature
Indoor DB temperature (°F)
Outdoor ambient temperature
86
80
75 70
86
80
75 70
1111
Heating
Data is based on the condition of outdoor humidity 75%. Air flow should be set to High speed. Data is for heating operation without any frost.
MUZ-FD09NA
(PSIG) (PSIG)
400 380 360 340 320 300 280 260 240 220
Condensing pressure
200 180 160 140
oor DB tem
Ind
perat
ure(
°F)
58Hz
75 70
65
Suction pressure
14 20 25 30 35 40 45 50 55 60 6570(°F)
Outdoor ambient temperature
MUZ-FD12NA
170 160 150 140 130 120 110 100
90 80 70 60
14 20 25 30 35 40 45 50 55
DB temperature (°F)
oor
Ind
Outdoor ambient temperature
58Hz
60 65 70(°F)
75 70 65
(PSIG) (PSIG)
400 380 360 340 320 300 280 260 240 220
Condensing pressure
200 180 160 140
Indoor DB temperature(°F)
58Hz
75 70
65
170 160 150 140 130 120 110
Suction pressure
100
14 20 25 30 35 40 45 50 55 60 6570(°F)
Outdoor ambient temperature
Indoor DB temperature
90 80 70 60
14 20 25 30 35 40 45 50 55
Outdoor ambient temperature
(°F)
58Hz
60 65 70(°F)
75 70 65
12
7-4. STANDARD OPERATION DATA
Model MSZ-FD09NA MSZ-FD12NA
Item Unit Cooling Heating Cooling Heating
Capacity Btu/h 9,000 10,900 12,000 13,600
SHF 0.76 — 0.73 —
Total
Input kW 0.650 0.750 0.960 0.980
Rated frequency Hz 35 43 51 54
Indoor unit MSZ-FD09NA MSZ-FD12NA
Power supply
Input kW 0.018 0.024 0.024 0.030
Fan motor current A 0.19/0.17 0.25/0.23 0.25/0.23 0.32/0.29
Outdoor unit MUZ-FD09NA MUZ-FD12NA
Power supply
Electrical circuit
Input kW 0.632 0.726 0.936 0.950
Comp. current A 2.96/2.68 3.39/3.06 4.40/3.97 4.43/4.01
Fan motor current A 0.35/0.32
Condensing pressure PSIG 376 355 402 392
Suction pressure PSIG 154 108 148 104
Discharge temperature ˚F 143 144 161 159
Condensing temperature ˚F 112 108 117 115
Suction temperature ˚F51465145
Comp. shell bottom temperature ˚F 144 128 146 129
Refrigerant circuit
Ref. pipe length ft. 25
Refrigerant charge (R410A) 2 lb. 9 oz.
Intake air temperature
Discharge air temperature
Indoor unit
Fan speed (High) rpm 1,020 1,120 1,120 1,220
Airfl ow (High) CFM 307 (Wet) 381 350 (Wet) 420
Intake air temperature
Fan speed rpm 810 870 810 870
Airfl ow CFM 1,102 1,187 1,102 1,187
Outdoor unit
DB ˚F80708070
WB ˚F67606760
DB ˚F 59 100 56 105
WB ˚F 56 54
DB ˚F95479547
WB ˚F — 43 — 43
V,
phase,
Hz
V,
phase,
Hz
208/230 , 1 , 60
208/230 , 1 , 60
1313
7-5. CAPACITY AND INPUT CORRECTION BY INVERTER OUTPUT FREQUENCY
MUZ-FD09NA
Correction of Cooling capacity
1.5
1.0
Correction of Cooling total input
1.5
1.0
Correction of Heating capacity
2.0
1.5
1.0
Correction of Heating total input
3.0
2.0
0.5
Capacity correction factors
0 50 100 150
The operational frequency of compressor
0.5
Input correction factors
(Hz)
0 50 100 150
The operational frequency of compressor
0.5
Capacity correction factors
(Hz)
0 50 100 150
The operational frequency of compressor
1.0
Input correction factors
(Hz)
0 50 100 150
The operational frequency of compressor
MUZ-FD12NA
Correction of Cooling capacity
1.5
1.0
0.5
Capacity correction factors
0 50 100 150
The operational frequency of compressor
Correction of Cooling total input
1.5
1.0
0.5
Input correction factors
(Hz)
0 50 100 150
The operational frequency of compressor
Correction of Heating capacity
1.5
1.0
0.5
Capacity correction factors
(Hz)
0 50 100 150
The operational frequency of compressor
Correction of Heating total input
2.0
1.0
Input correction factors
(Hz)
0 50 100 150
The operational frequency of compressor
7-6. TEST RUN OPERATION (How to operate fixed-frequency operation)
1. Press EMERGENCY OPERATION switch to start COOL or HEAT mode (COOL : Press once, HEAT : Press twice).
2. Test run operation starts and continues to operate for 30 minutes.
3. Compressor operates at rated frequency in COOL mode or 58 Hz in HEAT mode.
4. Indoor fan operates at High speed.
5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (operation frequency of compressor var­ies).
6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on remote controller.
(Hz)
(Hz)
14
8
ACTUATOR CONTROL
MUZ-FD09NA MUZ-FD12NA
8-1. OUTDOOR FAN MOTOR CONTROL
The fan motor turns ON/OFF, interlocking with the compressor. [ON] The fan motor turns ON 5 seconds before the compressor starts up. [OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
5 seconds 15 seconds
ON
Compressor
OFF
ON
Outdoor fan motor
OFF
8-2. R.V. COIL CONTROL
Heating Cooling
Dry
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
8-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR
Discharge temperature thermistor Protection
Indoor coil temperature thermistor
Defrost thermistor
Fin temperature thermistor Protection
Outdoor heat exchanger temperature thermistor
Ambient temperature thermistor
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
Compressor
R.V.coil
Outdoor fan motor
Sensor Purpose
ON OFF OFF
<COOL>
5 seconds
ON OFF
ON OFF
ON OFF
Cooling : Coil frost prevention
Heating : High pressure protection
Cooling : High pressure protection
Heating :
Defrosting
High pressure protection
Low ambient temperature operation
Compressor
<HEAT>
5 seconds
Actuator
LEV
Outdoor
fan motor
○○ ○ ○○ ○○ ○○○○○ ○○ ○○○ ○○○
R.V. coil
Indoor fan
motor
1515
9
SERVICE FUNCTIONS
MUZ-FD09VA MUZ-FD12VA
9-1. CHANGE IN DEFROST SETTING Changing defrost finish temperature
<JS> To change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P.C. board. (Refer to 10-6-1.)
Jumper Defrost fi nish temperature
(Initial setting)
JS
Soldered
None
(Cut)
41°F (5°C)
50°F (10°C)
9-2. PRE-HEAT CONTROL SETTING
PRE-HEAT CONTROL
When moisture gets into the refrigerant cycle, it may interfere the start-up of the compressor at low outside tempera­ture. The pre-heat control prevents this interference. The pre-heat control turns ON when outside temperature is 68°F (20 °C) or below. When pre-heat control is turned ON, compressor is energized. (About 50 W)
<JK> To activate the pre-heat control, cut the JK wire of the inverter P.C. board. (Refer to 10-6.1)
NOTE: When the inverter P.C. board is replaced, check the Jumper wires, and cut/solder them if necessary.
10
TROUBLESHOOTING
MUZ-FD09NA MUZ-FD12NA
10-1. CAUTIONS ON TROUBLESHOOTING
1. Before troubleshooting, check the following
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for miswiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, then after con­firming the horizontal vane is closed, turn off the breaker and/or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board.
3) When removing the electrical parts, be careful to the residual voltage of smoothing capacitor.
4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components.
5) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
Lead wiring
3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.
To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
2) Before servicing check that the connector and terminal are connected properly.
3) When the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
4) Refer to 10-2. and 10-3.
Housing point
16
10-2. FAILURE MODE RECALL FUNCTION
Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (10-3.) disappears, the memorized failure details can be recalled. This mode is very useful when the unit needs to be repaired for the abnormality which doesn't recur.
1. Flow chart of failure mode recall function for the indoor/outdoor unit
Operational procedure
The cause of abnormality cannot be found because the abnormality doesn't recur.
Setting up the failure mode recall function
Turn ON the power supply. <Preparation of the remote controller>
While pressing both OPERATION SELECT button and TOO COOL button on the
remote controller at the same time, press RESET button.
First, release RESET button.
And release the other two buttons after all LCD in operation display section of the
remote controller is displayed after 3 seconds.
1. Regardless of normal or ab­normal condition, a short beep
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit.
1
is emitted once the signal is received.
Does POWER lamp on the indoor unit blink at the interval of
0.5 seconds? Blinks: Either indoor or outdoor unit is abnormal. Beep is emit-
ted at the same timing as the blinking of POWER lamp.
2
Yes
Judgment of indoor/outdoor abnormality
Before blinking, does POWER lamp stay ON for 3 seconds? Stays ON for 3 seconds (without beep): The outdoor unit is abnormal.
The indoor unit is abnormal. Check the blinking pattern, and confi rm the abnormal point with the indoor unit failure mode table. (Refer to indoor unit service manual.) Make sure to check at least two consecutive blinking cycles.
Releasing the failure mode recall function
Deleting the memorized abnormal condition
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller.
Repair the defective parts.
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" mentioned above.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed)
with the remote controller headed towards the indoor unit. Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
NOTE: 1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
(Blinks)
No
No (OFF)
Yes
2
Indoor unit is normal. But the outdoor unit might be abnormal because there are some abnor­malities that can't be recalled with this way. Confi rm if outdoor unit is abnormal according to the detailed outdoor unit failure mode recall function. (Refer to 10-2.2)
The outdoor unit is abnormal. Check the blinking pattern, and confi rm the abnormal point with the outdoor unit failure mode table. (Refer to 10-2.3) Make sure to check at least two consecutive blinking cycles.
2. Blinking pattern when the indoor unit is abnormal:
2.5-second OFF
Blinking at 0.5­second interval
2.5-second OFF
Blinking at 0.5-
second interval
ON
OFF
Repeated cycle Repeated cycle
Beeps
Beeps
Repeated cycle
3
Beeps
3.Blinking pattern when the outdoor unit is abnormal:
2.5-second OFF 3-second ON
ON
OFF
No beep Beeps
Repeated cycle
Blinking at 0.5­second interval
2.5-second OFF 3-second ON
No beep Beeps
Repeated cycle
17
Blinking at 0.5­second interval
Repeated cycle
2. Flow chart of the detailed outdoor unit failure mode recall function
Operational procedure
The outdoor unit might be abnormal. Confi rm if outdoor unit is abnormal according to the following procedures.
Confi rm that the remote controller is in the failure mode recall function.
With the remote controller headed towards the indoor unit, press TOO COOL or TOO WARM button to adjust the set temperature to 77˚F (25˚C).
1
Does POWER lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: The outdoor unit is abnormal. Beep is emitted
at the same timing as the blinking of POWER lamp. 2
Yes
)
(Blinks
The outdoor unit is abnormal. Check the blinking pattern, and confi rm the abnormal point with the out- door unit failure mode table (10-2.3.). Make sure to check at least two consecutive blinking cycles.
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller.
Repair the defective parts.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" (10-2.1.).
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with
the remote controller headed towards the indoor unit. Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. Release the failure mode recall function according to "Releasing the failure mode recall function" men-
tioned above.
NOTE: 1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
No (OFF)
2
1. Regardless of normal or abnormal condition, 2 short beeps are emitted as the signal is received.
The outdoor unit is normal.
Release the failure mode recall function accord­ing to the left mentioned procedure.
2.Blinking pattern when outdoor unit is abnormal:
2.5-second OFF 3-second ON
ON
OFF
No beep
Repeated cycle
Blinking at 0.5­second interval
Beeps
2.5-second OFF 3-second ON
No beep Beeps
Repeated cycle
18
Blinking at 0.5-
second interval
Repeated cycle
3. Outdoor unit failure mode table
POWER lamp
(Indoor unit)
OFF None (Normal)
2-time fl ash
2.5 seconds OFF
3-time fl ash
2.5 seconds OFF
4-time fl ash
2.5 seconds OFF
5-time fl ash
2.5 seconds OFF
Abnormal point
(Failure mode / protection)
Outdoor power system
Discharge temperature thermistor
Defrost thermistor
Fin temperature thermistor 3-time fl ash
P.C. board temperature thermistor
Ambient temperature thermistor
Overcurrent 11-time fl ash
Compressor synchronous abnormality (Compressor start­up failure protection)
Discharge temperature
(Outdoor P.C. board)
1-time fl ash every
2.5 seconds
2.5 seconds OFF
4-time fl ash
2.5 seconds OFF
2-time fl ash
2.5 seconds OFF
2.5 seconds OFF
12-time fl ash
2.5 seconds OFF
LED indication
—— —
Overcurrent protection stop is continuously performed 3 times within
1 minute after the compressor gets started.
Thermistor shorts or opens during compressor running.
Large current fl ows into intelligent power module.
Waveform of compressor current is distorted.
Temperature of discharge temperature thermistor exceeds 241°F (116°C), compressor stops. Compressor can restart if discharge temperature thermistor reads 212°F (100°C) or less 3 minutes later.
Condition Correspondence
Reconnect connectors.
• Refer to 10-5. "How
• to check inverter/ compressor". Check stop valve.
Refer to 10-5. "Check
• of outdoor thermistors". Defective outdoor thermistors can be identifi ed by checking the blinking pattern of LED.
Reconnect compressor
• connector. Refer to 10-5. "How
• to check inverter/ compressor". Check stop valve.
Reconnect compressor
• connector. Refer to 10-5. "How
• to check inverter/ compressor".
Check refrigerant circuit
• and refrigerant amount. Refer to 10-5. "Check
• of LEV".
Indoor/ outdoor unit failure mode
recall function
○○
○○
Outdoor unit failure mode
recall function
6-time fl ash
2.5 seconds OFF
7-time fl ash
2.5 seconds OFF
8-time fl ash
2.5 seconds OFF
9-time fl ash
2.5 seconds OFF
10-time fl ash
2.5 seconds OFF
11-time fl ash
2.5 seconds OFF
12-time fl ash
2.5 seconds OFF
14-time fl ash
2.5 seconds OFF
High pressure
Fin temperature/ P.C. board temperature
Outdoor fan motor
Nonvolatile memory data 5-time fl ash
Discharge temperature
DC voltage 8-time fl ash
Each phase current of compressor
Overcurrent Compressor open­phase
Stop valve (Closed valve) 14-time fl ash
7-time fl ash
2.5 seconds OFF
2.5 seconds OFF
2.5 seconds OFF
9-time fl ash
2.5 seconds OFF
10-time fl ash
2.5 seconds OFF
2.5 seconds OFF
Temperature of indoor coil thermistor exceeds 158°F (70°C) in HEAT mode. Temperature of defrost thermistor exceeds 158°F (70°C) in COOL mode.
Temperature of fi n temperature thermistor on the inverter P.C. board exceeds 167 ~ 176°F (75 ~ 80°C), or temperature of P.C. board temperature thermistor on the inverter P.C. board exceeds 158 ~ 167°F (70 ~ 75°C).
Outdoor fan has stopped 3 times in a row within 30 seconds after outdoor fan start-up.
Nonvolatile memory data cannot be read properly.
Temperature of discharge temperature thermistor has been 122°F (50°C) or less for 20 minutes.
DC voltage of inverter cannot be detected normally.
Each phase current of compressor cannot be detected normally.
Large current fl ows into intelligent power module (IPM). The open-phase operation of compressor is detected. The interphase short out occurs in the output of the intelligent power module (IPM). The compressor winding shorts out.
Closed valve is detected by compressor current.
Check refrigerant circuit
• and refrigerant amount. Check stop valve.
Check around outdoor
• unit. Check outdoor unit air
• passage. Refer to 10-5. "Check
• of outdoor fan motor".
Refer to 10-5. "Check
• of outdoor fan motor". Refer to 10-5. "Check of inverter P.C. board".
Replace the inverter
• P.C. board.
Refer to 10-5. "Check
• of LEV". Check refrigerant circuit
— and refrigerant amount.
Refer to 10-5. "How
• to check inverter/ compressor".
Reconnect compressor
• connector. Refer to 10-5. "How
• to check inverter/ compressor".
Check stop valve
NOTE: Blinking patterns of this mode differ from the ones of Troubleshooting check table (10-3.).
19
○○
○○
10-3. TROUBLESHOOTING CHECK TABLE
No. Symptom LED indication
Outdoor unit does not oper-
1
ate.
2
3
4
5
6
'Outdoor unit stops and
7
restarts 3 min­utes later' is repeated.
8
9
1-time fl ash every
2.5 seconds
6-time fl ash
2.5 seconds OFF 11-time fl ash
2.5 seconds OFF 14-time fl ash
2.5 seconds OFF
2-time fl ash
2.5 seconds OFF
3-time fl ash
2.5 seconds OFF
4-time fl ash
2.5 seconds OFF
Abnormal point/
Condition
Outdoor power sys­tem
Outdoor thermistors Discharge temperature thermistor, fi n temperature thermistor,
Outdoor control sys­tem
Serial signal The communication fails between the indoor and outdoor unit
Stop valve/ Closed valve
Outdoor unit (Other abnormality)
Overcurrent protec­tion
Discharge tempera­ture overheat protec­tion
Fin temperature /P.C. board tem­perature thermistor overheat protection
Condition Correspondence
Overcurrent protection stop is continuously performed 3 times within 1 minute after the compressor gets started, or failure of restart of compressor has repeated 24 times.
defrost thermistor, P.C. board temperature thermistor or ambi­ent temperature thermistor shorts or opens during compressor running.
Nonvolatile memory data cannot be read properly.
(POWER lamp of the indoor unit lights up or fl ashes 7 times.)
for 3 minutes. Closed valve is detected by compressor current. Check stop valve.
Outdoor unit is defective. Refer to 10-2.2. "Flow chart of the
Large current fl ows into intelligent power module.
When overcurrent protection occurs within 10 seconds after
compressor starts, compressor restarts after 15 seconds.
Temperature of discharge temperature thermistor exceeds 241 °F (116°C), compressor stops. Compressor can restart if dis­charge temperature thermistor reads 212°F (100°C) or less 3 minutes later.
Temperature of fi n temperature thermistor on the heat sink exceeds 167 ~ 176°F (75 ~ 80°C) or temperature of P.C. board temperature thermistor on the inverter P.C. board exceeds 158 ~ 167°F (70 ~ 75°C).
Reconnect connector of compres-
• sor. Refer to 10-5. "How to check in-
• verter/compressor". Check stop valve.
• Refer to 10-5. "Check of outdoor
• thermistors".
Replace inverter P.C. board.
Refer to 10-5. "How to check
• miswiring and serial signal error.
• detailed outdoor unit failure mode recall function".
Reconnect connector of compres-
• sor. Refer to 10-5. "How to check in-
• verter/compressor". Check stop valve.
• Check refrigerant circuit and refrig-
• erant amount. Refer to 10-5. "Check of LEV".
Check around outdoor unit.
• Check outdoor unit air passage.
• Refer to 10-5. "Check of outdoor
• fan motor".
10
11
12
13
14
Outdoor unit
15
operates.
16
17
NOTE: 1. The location of LED is illustrated at the right fi gure. Refer to 10-6.1.
2. LED is lighted during normal operation.
The fl ashing frequency shows the number of times the LED blinks after every 2.5-second OFF. Flashing (Example) When the fl ashing frequency is “2”.
5-time fl ash
2.5 seconds OFF
8-time fl ash
2.5 seconds OFF
10-time fl ash
2.5 seconds OFF
12-time fl ash
2.5 seconds OFF 13-time fl ash
2.5 seconds OFF 1-time fl ash
2.5 seconds OFF 3-time fl ash
2.5 seconds OFF
4-time fl ash
2.5 seconds OFF
High pressure pro­tection
Compressor syn­chronous abnormal­ity
Outdoor fan motor Outdoor fan has stopped 3 times in a row within 30 seconds
Each phase current of compressor
DC voltage DC voltage of inverter cannot be detected normally. Refer to 10-5. "How to check in-
Frequency drop by current protection
Frequency drop by high pressure pro­tection
Frequency drop by defrosting in COOL mode
Frequency drop by discharge tempera­ture protection
Indoor coil thermistor exceeds 158°F (70°C) in HEAT mode. Defrost thermistor exceeds 158°F (70°C) in COOL mode.
The waveform of compressor current is distorted. Reconnect connector of compres-
after outdoor fan start-up.
Each phase current of compressor cannot be detected nor­mally.
Current from power outlet is nearing Max. fuse size. The unit is normal, but check the
Temperature of indoor coil thermistor exceeds 131°F (55°C) in HEAT mode, compressor frequency lowers.
Indoor coil thermistor reads 46°F (8°C) or less in COOL mode, compressor frequency lowers.
Temperature of discharge temperature thermistor exceeds 232 °F (111°C), compressor frequency lowers.
Check refrigerant circuit and refrig-
• erant amount. Check stop valve.
• sor. Refer to 10-5. "How to check in-
• verter/compressor".
Refer to 10-5. "Check of outdoor
• fan motor. Refer to 10-5. "Check of inverter
• P.C. board.
Refer to 10-5. "How to check in-
• verter/compressor".
• verter/compressor".
following. Check if indoor fi lters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air cir-
• culation is short cycled.
Check refrigerant circuit and refrig-
• erant amount. Refer to 10-5.
• Refer to 10-5. "Check of outdoor
• thermistors".
Inverter P.C. board (Parts side)
Flashing
"Check of LEV".
LED
ON
OFF
2.5-second OFF
0.5-second ON
2.5-second OFF
0.5-second ON
20
No. Symptom LED indication
Outdoor unit operates.
18
19
20
7-time fl ash
2.5 seconds OFF
8-time fl ash
2.5 seconds OFF
9-time fl ash
2.5 seconds OFF
Abnormal point/
Condition
Low discharge tem­perature protection
PAM protection PAM: Pulse Ampli­tude Modulation
Inverter check mode The connector of compressor is disconnected, inverter check
Temperature of discharge temperature thermistor has been 122°F (50°C) or less for 20 minutes.
The overcurrent fl ows into IGBT (Insulated Gate Bipolar tran- sistor : TR821) or the bus-bar voltage reaches 320 V or more, PAM stops and restarts.
mode starts.
Condition Correspondence
Refer to 10-5. "Check of LEV".
• Check refrigerant circuit and refrig-
• erant amount.
This is not malfunction. PAM protec­tion will be activated in the following cases; 1 Instantaneous power voltage drop
(Short time power failure)
2 When the power supply voltage is
high.
Check if the connector of the com-
• pressor is correctly connected. Refer to 10-5. "How to check in­verter/compressor".
21
10-4. TROUBLE CRITERION OF MAIN PARTS
MUZ-FD09NA MUZ-FD12NA
Part name Check method and criterion Figure
Defrost thermistor (RT61)
Ambient temperature thermistor (RT65)
Outdoor heat ex­changer temperature thermistor (RT68)
Discharge tem­perature thermistor (RT62)
Fin temperature thermistor (RT64)
Measure the resistance with a tester.
Refer to 10-6. “Test point diagram and voltage”, 1. “Inverter P.C. board”, the chart of thermistor.
Measure the resistance with a tester. Before measurement, hold the thermistor with your hands to warm it up.
Refer to 10-6. “Test point diagram and voltage”, 1. “Inverter P.C. board”, the chart of thermistor.
Compressor
Outdoor fan motor
R. V. coil (21S4)
Expansion valve coil (LEV)
Measure the resistance between terminals using a tester. (Winding temperature : -4 ~ 104°F (-20 ~ 40°C))
Normal
U-V
U-W
1.52 ~ 2.17 Ω
V-W
Measure the resistance between lead wires using a tester. (Part temperature : 14 ~ 104°F (-10 ~ 40°C))
Color of lead wire Normal
RED – BLK BLK – WHT
11 ~ 16 Ω
WHT – RED
Measure the resistance using a tester. (Part temperature : 14 ~ 104°F (-10 ~ 40°C))
Normal
970 ~ 1380 Ω
Measure the resistance using a tester. (Part temperature : 14 ~ 104°F (-10 ~ 40°C))
Color of lead wire Normal
WHT – RED RED – ORN
YLW – BRN
37 ~ 54 Ω
BRN – BLU
WHT
WHT
WHT
RED
ORN
RED BLK
23
V
23
V
W
U
RED BLK
1
W
U
LEV
YLW
BRN
1
BLU
22
10-5. TROUBLESHOOTING FLOW
A How to check inverter/compressor
Disconnect the connector (CN61) between compressor and the intelligent power module (IPM).
Check the voltage between terminals.
Are the voltages balanced?
Yes
Check the compressor.
No
See 10-5. “Check of open phase”.
Replace the inverter P.C. board.
See 10-5. “Check of compressor”.
B Check of open phase
With the connector between the compressor and the intelligent power module disconnected,
activate the inverter and check if the inverter is normal by measuring the balance of voltage between the terminals.
Output voltage 115 V
<< Operation method>> Start cooling or heating operation by pressing EMERGENCY OPERATION switch on the
indoor unit. (TEST RUN OPERATION : Refer to 7-6.) <<Measurement point>> at 3 points BLK (U) - WHT (V) BLK (U) - RED (W) WHT(V) - RED (W)
NOTE: 1. Output voltage varies according to power supply voltage.
2. Measure the voltage by analog type tester.
3. During this check, LED of the inverter P.C. board fl ashes 9 times. (Refer to 10-6.1.)
Measure AC voltage between the lead wires at 3 points.
9-time flash
2.5-second OFF
C Check of compressor
Refer to 10-5. “Check of compressor winding”. Is the compressor normal?
Yes
Refer to 10-5. “Check of compressor operation time”. Does the compressor operate continuously?
Yes
OK.
No
No
Replace the compressor.
Refer to 10-5. “Check of compressor start failure”.
23
D Check of compressor winding
Disconnect the connector (CN61) between the compressor and intelligent power module, and measure the resistance between
the compressor terminals. <<Measurement point>> at 3 points BLK-WHT BLK-RED
Measure the resistance between the lead wires at 3 points. WHT-RED <<Judgement>> Refer to 10-4. 0[Ω] ················Abnormal [short] Infinite[Ω] ·······Abnormal [open]
NOTE: Be sure to zero the ohmmeter before measurement.
E Check of compressor operation time
<<Judgement>>
Connect the compressor and activate the inverter. Then measure
the time until the inverter stops due to over current. <<Operation method>> Start heating or cooling operation by pressing EMERGENCY
OPERATION switch on the indoor unit. (TEST RUN OPERATION : Refer to 7-6.) <<Measurement>> Measure the time from the start of compressor to the stop of
compressor due to overcurrent.
0 second
1 second
2 seconds
10 seconds
Compressor starts
Abnormal (IPM failure) (Compressor winding short)
Abnormal (Compressor lock out) (Starting defect)
Abnormal (Poor contact,) (Outdoor P.C. board defect) (Disconnected connector)
F Check of compressor start failure
Confi rm that 1~4 is normal.
• Electrical circuit check Contact of the compressor connector (including CN61)
1. Output voltage of inverter P.C. board and balance of them (See 10-5. )
2. Direct current voltage between DB61(+) and (-) on the inverter P.C. board
3. Voltage between outdoor terminal block S1-S2
4
.
Does the compressor run for 10 seconds or more after it starts?
No
After the compressor is heated with a drier, does the compressor start? 1
Yes
Compressor start failure. Activate pre-heat control. (Refer to 9-2. "PRE-HEAT CONTROL SETTING")
Yes
No
Check the refrigerant circuit. Check the stop valve.
Replace the compressor.
Abnormal (Refrigerant circuit defect) (Closed valve)
10 minutes
Normal
1 Heat the compressor with a drier for about 20 minutes. Do not recover refrigerant gas while heating.
24
Heating part
G Check of outdoor thermistors
Disconnect the connector of thermistor in the outdoor P.C. board (see below table), and measure the resistance of thermistor.
Is the thermistor normal? (Refer to 10-6.1.)
Yes
Reconnect the connector of thermistor. Turn ON the power supply and press EMERGENCY OPERATION switch.
Does the unit operate for 10 minutes or more without showing thermistor abnormality?
Yes
OK. (Cause is poor contact.)
Thermistor Symbol Connector, Pin No. Board Defrost RT61 Between CN641 pin1 and pin2 Discharge temperature RT62 Between CN641 pin3 and pin4 Fin temperature RT64 Between CN642 pin1 and pin2 Ambient temperature RT65 Between CN643 pin1 and pin2 Outdoor heat exchanger temperature RT68 Between CN644 pin1 and pin3
No
No
Replace the thermistor except RT64. When RT64 is abnormal, replace the inverter P.C. board.
Replace the inverter P.C. board.
Inverter P.C. board
H Check of R.V. coil
First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 10-4. In case CN721 is not connected or R.V. coil is open, voltage is generated between the terminal pins of the connector
although any signal is not being transmitted to R.V. coil.
Check if CN721 is connected.
Unit operates COOL mode even if it is set to HEAT mode.
Disconnect connector (CN61) between the compressor and the intelligent power module. Turn ON the power supply and press EMERGENCY OPERATION switch twice (HEAT mode).
Is there 230 VAC between CN721 and
on the inverter P.C. board 3 minutes
after the power supply is turned ON?
Replace the 4-way valve.
Unit operates HEAT mode even if it is set to COOL mode.
Disconnect connector (CN61) between the compressor and the intelligent power module. Turn ON the power supply and press EMERGENCY OPERATION switch once (COOL mode).
Is there 230 VAC between CN721 and
on the inverter P.C. board 3 minutes
after the power supply is turned ON?
Replace the 4-way valve.
25
Yes
No
Replace the inverter
No
P.C. board.
Replace the inverter
Yes
P.C. board.
I Check of outdoor fan motor
Disconnect CN932 from the inverter P.C. board, and measure the resistance of the outdoor fan motor.
Is the outdoor fan motor normal? (Refer to 10-4.)
Yes
Replace the inverter P.C. board.
J Check of power supply
Disconnect the connector (CN61) between compressor and intelligent power module. Turn ON power supply and press EMERGENCY OPERATION switch.
Does POWER lamp on the indoor unit light up?
Yes
No
No
Rectify indoor/outdoor connecting wire.
Is there voltage 208/230 VAC between the indoor terminal block S1 and S2?
Replace the outdoor fan motor.
Yes
Replace the indoor electronic control P.C.
No
board.
Is there voltage 280 ~ 370 VDC between DB61 (+) and DB61 (–) on the inverter P.C. board? (Refer to 10-6.1.)
No
Check the electric parts in main circuit.
Yes
Dose LED on the inverter P.C. board light up or fl ash? (Refer to 10-6.1.)
Yes
If light up, OK. If fl ash, refer to 10-3.
26
Replace the inverter
No
P.C. board.
DB61
Inverter P.C. board (Solder side)
280 ~ 370 VDC
K Check of LEV (Expansion valve)
Turn ON the power supply. <Preparation of the remote controller>
While pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button.
First, release RESET button.
And release the other two buttons after all LCD except
the set temperature in operation display section of the remote controller is displayed after 3 seconds.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1
Expansion valve operates in full-opening direction.
Do you hear the expansion valve "click, click·······"? Do you feel the expansion valve vibrate on touching it ?
No
Yes
OK.
1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received.
Is LEV coil properly fi xed to the expansion valve?
Yes
Does the resistance of LEV coil have the characteristics? (Refer to 10-4.)
No
Replace the LEV coil.
NOTE : After check of LEV, do the undermentioned operations.
1. Turn OFF the power supply and turn ON it again.
2. Press RESET button on the remote controller.
No
Yes
Properly fi x the LEV coil to the expansion valve.
Measure each voltage between connector pins of CN724 on the inverter P.C. board.
1.Pin (-) — Pin (+)
2.Pin (-) — Pin (+)
3.Pin (-) — Pin (+)
4.Pin (-) — Pin (+) Is there about 3 ~ 5 VAC between each?
NOTE: Measure the voltage by an analog
tester.
Replace the expansion valve.
Yes
Replace the inverter P.C.
No
board.
27
L Check of inverter P.C. board
Check the outdoor fan motor. (Refer to10-5. .)
Is the fuse (F901) blown on the in­verter P.C. board?
No
Check the connection of the connectors (CN932) of the outdoor fan motor. If the connection is poor, make it correct.
Operate the outdoor unit by starting EMERGENCY OPERATION.
Check the LED indication on the in­verter P.C. board. Does the LED fl ash 10 times?
Yes (10-time fl ash)
Replace the inverter P.C. board.
Yes
No
Inverter P.C. board (Solder side)
CN932
Check the corresponding parts following LED indication. (Refer to 10-3.)
28
M How to check miswiring and serial signal error
Turn OFF the power supply.
Is there rated voltage in the power supply?
Yes
Turn ON the power supply.
Is there rated voltage between outdoor terminal block S1 and S2?
Press EMERGENCY OPERATION switch once.
Does AREA-L lamp light up? <Confi rmation of the power to the indoor unit>
Is serial signal error indicated 6 minutes later?
Turn OFF the power supply. Check once more if the indoor/outdoor
B
connecting wire is not miswiring. Short-circuit outdoor terminal block S2 and S3.
Turn ON the power supply.
Yes
Yes
Yes
A
1
No
No
Check the power supply.
Check the wiring.
No
Is there any miswiring, poor contact, or wire disconnection of the
No
indoor/outdoor connect­ing wire?
1. Miswiring may damage indoor electronic control P.C. board during the operation.
Be sure to confi rm the wiring is correct before the opera-
tion starts.
3. Be sure to check this within 3 minutes after turning ON. After 3 minutes, LED blinks 6 times. Even when the inverter P.C. board or the outdoor electronic control P.C. board is normal, LED blinks 6 times after 3 minutes.
No
Yes
Correct them.
A
Turn OFF inverter-controlled lighting
• equipment. Turn OFF the power supply and then
• turn ON again. Press EMERGENCY OPERATION
• switch.
Reinstall
• either the unit or the light each other
No
away. Attach a fi lter on remote control receiv­ing section of the indoor unit.
Is serial signal error indicated 6 minutes later?
Yes
B
Does the LED on the inverter P.C. board or the outdoor electronic control P.C. board repeat "3.6-second-OFF and 0.8-second­ON quick blinking"? 3
Yes
Turn OFF the power supply. Remove the short-circuit between outdoor terminal block S2 and S3. Turn ON the power supply. Is there amplitude of 10 to 20 VDC between outdoor terminal block S2 and S3? <Confi rmation of serial signal>
Yes
Is there rated voltage between indoor terminal block S1 and S2? <Confi rmation of power voltage>
Yes
Replace the indoor electronic control P.C. board.
Be sure to release the failure-mode recall function after checking.
No (Lighted or not lighted)
No
No
29
Replace the inverter P.C. board or the out­door electronic control P.C. board.
2
2. Be careful to the residual voltage of smoothing capacitor.
Is there any error of the in­door/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
Is there any error of the in­door/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
No
No
Replace the indoor/ outdoor connecting
Yes
wire.
Replace the indoor/ outdoor connecting
Yes
wire.
N Electromagnetic noise enters into TV sets or radios
Is the unit grounded?
Yes
Is the distance between the antennas and the indoor unit within 9.91 ft., or is the distance between the antennas and the outdoor unit within 9.91 ft.?
No
Is the distance between the TV sets or radios and the indoor unit within 3.28 ft., or is the distance between the TV sets or radios and the outdoor unit within 9.91 ft.?
No
Are the antennas damaged? Is the coaxial cable damaged? Is there any poor contact in the anten­na wiring?
No
Is the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas close?
No
No
Yes
Yes
Yes
Yes
Ground the unit.
Extend the distance between the antennas and the indoor unit, and/or the antennas and the outdoor unit.
Extend the distance between the TV sets and/or radios and the indoor unit, or the TV sets or radios and the outdoor unit.
Replace or repair the antenna. Replace or repair the coaxial cable.
Extend the distance between the indoor/outdoor connecting wire of the air conditioner and the wir­ing of the antennas.
Even if all of the above conditions are fulfi lled, the electromagnetic noise may enter, depending on the electric fi eld strength or the installation condition (combination of specifi c conditions such as antennas or wiring). Check the followings before asking for service.
1. Devices affected by the electromagnetic noise TV sets, radios (FM/AM broadcast, shortwave)
2. Channel, frequency, broadcast station affected by the electromagnetic noise
3. Channel, frequency, broadcast station unaffected by the electromagnetic noise
4. Layout of ; indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, grounding wire, antennas, wiring from antennas, receiver
5. Electric fi eld intensity of the broadcast station affected by the electromagnetic noise
6. Presence or absence of amplifi er such as booster
7. Operation condition of air conditioner when the electromagnetic noise enters in
1) Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic noise.
2) Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button on the remote controller for power ON, and check for the electromagnetic noise.
3) After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the elec­tromagnetic noise.
4) Press OPERATE/STOP (ON/OFF) button on the remote controller for power OFF, when the outdoor unit stops but the indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise.
30
10-6. TEST POINT DIAGRAM AND VOLTAGE
1. Inverter P.C. board
MUZ-FD09NA MUZ-FD12NA
Back side of unit
AC 208/230 V
Fuse (F901) 250 V 3.15 A
Output to drive com­pressor (LDU, LDV, LDW)
DB61 DC260 ~300 V
(-)
(+)
Smoothing capacitor (C63)
Smoothing capacitor (C62)
Fuse (F801) 250 V 3.15 A
Smoothing capacitor (C61)
Fuse (F701) 250 V 3.15 A
R.V. coil (CN721) 208/230 VAC
AC208/230 V
Front side of unit
Defrost thermistor(RT61) Ambient temperature thermistor(RT65) Outdoor heat exchanger temperature thermistor(RT68)
100
90
80
70
60
50
40
30
Resistance(kΩ)
20
10
0
-4 14 32 50 68 86 104
Output to drive outdoor
fan motor (CN932)
Temperature(°F)
Fin temperature
thermistor /RT64
(CN642)
Outdoor heat exchanger
temperature thermistor
/RT68(CN644)
Discharge temperature thermistor(RT62)
700
600
500
400
300
200
Resistance(kΩ)
100
0
32 50 68 86 104 122 140 158 176 194 212 230 248
Defrost thermistor
/RT61(CN641)
Ambient temperature
thermistor /RT65
(CN643)
Temperature(°F)
Discharge temperature
thermistor /RT62
LEV connector (CN724)
(CN641)
Jumper wire for changing defrost setting (JS)
Fin temperature thermistor(RT64)
200
180
160
140
120
100
80
60
Resistance(kΩ)
40
20
0
32 50 68 86 104 122 140 158 176
Temperature(°F)
Jumper wire for pre-heat control setting (JK)
31
11
DISASSEMBLY INSTRUCTIONS
<"Terminal with locking mechanism" Detaching points>
The terminal which has the locking mechanism can be detached as shown below. There are two types (refer to (1) and (2)) of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching.
(1) Slide the sleeve and check if there is a locking lever or not.
Sleeve
Slide the sleeve. Pull the terminal while
Locking lever
pushing the locking lever.
11-1. MUZ-FD09NA MUZ-FD12NA
OPERATING PROCEDURE PHOTOS
1. Removing the cabinet
(1) Remove the screw fixing the service panel. (See
Photo 1.)
(2) Pull down the service panel and remove it. (See Photo
1.)
(3) Remove the screws fixing the conduit cover. (See
Photo 2.) (4) Remove the conduit cover. (See Photo 2.) (5) Disconnect the power supply wire and indoor/outdoor
connecting wire. (6) Remove the screws fixing the top panel. (See Photo 1.) (7) Remove the top panel. (See Photo 1.) (8) Remove the screws fixing the cabinet. (9) Remove the cabinet. (10)
Remove the screws fixing the back panel.
(11)
Remove the back panel.
Photo 2
(2) The terminal with this connector has the locking mechanism.
Hold the sleeve, and pull out the terminal slowly.
Connector
NOTE : Turn OFF power supply before disassembling.
Photo 1
Screws
of the top panel
Screw of the cabinet
Screws of the top panel
Screw of the service panel
Back panel
Hooks
Conduit cover
Screw of the
conduit cover
Conduit plate
32
32
Screws of the cabinet
Service
panel
OPERATING PROCEDURE
PHOTOS
2. Removing the inverter assembly, inverter P.C. board
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following
connectors; <Inverter P.C. board> CN721 (R.V.coil) CN932 (Fan motor) CN641 (Defrost thermistor and discharge temperature ther-
mistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor) CN724 (LEV)
(3) Remove the compressor connector (CN61). (4) Remove the screws fixing the relay panel. (See Photo 3.) (5) Remove the inverter assembly. (See Photo 4.) (6) Remove the screw of the ground wire and screw of the
T.B.support. (See Photo 4.)
(7) Remove the inverter P.C. board from the inverter assembly.
3. Removing R.V. coil
(1) Remove the cabinet and panels. (Refer to 1.) (2) Remove the R.V. coil. (See Photo 5.)
Photo 3
Screws of the relay panel
Photo 4 (Inverter assembly)
Heat sink
Inverter P.C. board
Screw of the T.B.support
T.B.support
4. Removing the discharge temperature thermistor, defrost thermistor and outdoor heat exchanger tem­perature thermistor.
(1) Remove the cabinet and panels. (Refer to 1.) (2) Pull out the discharge temperature thermistor from its hold-
er. (See Photo 5.) (3) Pull out the defrost thermistor from its holder. (See Photo 6.) (4) Pull out the outdoor heat exchanger temperature thermistor
from its holder. (See Photo 6.)
33
Photo 5
Screw of the ground wire
R.V. coil
Discharge temperature thermistor
OPERATING PROCEDURE
PHOTOS
5. Removing outdoor fan motor
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the connectors for outdoor fan motor. (3) Remove the propeller nut. (See Photo 7.) (4) Remove the propeller. (See Photo 7.) (5) Remove the screws fixing the fan motor. (See Photo 7.) (6) Remove the fan motor.
6. Removing the compressor and 4-way valve
(1) Remove the cabinet and panels. (Refer to 1.) (2) Remove the inverter assembly. (Refer to 2.) (3) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure
gauge shows 0 PSIG.
(4) Detach the welded part of the suction and the discharge
pipe connected with compressor. (5) Remove the nuts of compressor legs. (6) Remove the compressor. (7) Detach the welded part of pipes connected with 4-way
valve. (See Photo 8.)
Photo 6
Photo 7
Outdoor heat exchanger tempera­ture thermistor
Defrost thermistor
Screws of the outdoor fan motor
34
Propeller
Photo 8
Propeller nut
Welded parts of 4-way valve
35
TM
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Copyright 2008 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD Distributed in Mar. 2008. No. OBH498 REVISED EDITION-A 7 Distributed in Jan. 2008. No. OBH498 7 Made in Japan
New publication, effective Mar. 2008 Specifications subject to change without notice.
Loading...