Maximum temperature9073115—
Minimum temperature675714—
Maximum humidity78 %—
Standard temperature70604743
Maximum temperature80677565
Minimum temperature70601413
Rated voltage Guaranteed Voltage
208/230 V
1 phase
60 Hz
Min.187 V
DBWBDBWB
208 V 230 V Max.253 V
Intake air temperature (°F)
lndoorOutdoor
55
4
OUTLINES AND DIMENSIONS
MUZ-FD09NA
MUZ-FD12NA
1-3/4
Air in
7/8
handle
21-5/8
11- 1/3 2
5-15/16
13/32
15-3/4
11-29/32
Air in
19-11/16
Air out
31-1/2
Drain hole 1-5/8
1-9/16
2- 3/8 13/16 Oval hole
12 ~ 12-3/4
11/16
2
2-23/32
13-9/16
5-7/8
REQUIRED SPACE
4 in. or more
17/3229/3211-1/4
Open two sides of left,
right, or rear side.
Liquid pipe :1/4 (flared)
Gas pipe :3/8 (flared)
6-23/32
Unit: inch
Basically open 4 inch or more
without any obstruction in front
and on both sides of the unit.
4 in. or more
14 in. or more
8 in. or more
66
5
MUZ-FD09NA MUZ-FD12NA
WIRING DIAGRAM
77
6
REFRIGERANT SYSTEM DIAGRAM
MUZ-FD09NA
MUZ-FD12NA
Refrigerant pipe ø3/8
(with heat insulator)
Flared connection
Flared connection
Refrigerant pipe 1/4
(with heat insulator)
Muffler
Stop valve
(with service port)
Stop valve
(with strainer)
Capillary tube
O.D. 0.118 × I.D. 0.079
× 9-7/16
(ø3.0 × ø2.0 × 240)
4-way valve
Discharge
temperature
thermistor
RT62
Service
port
Muffler
Service
port
Compressor
Defrost
thermistor
RT61
Capillary tube
O.D. 0.118 × I.D. 0.071
× 23-5/8
3.0
× ø
(ø
Expansion
valve
1.8×600
)
Refrigerant flow in cooling
Refrigerant flow in heating
Outdoor
heat
exchanger
Strainer
#100
R.V. coil
heating ON
cooling OFF
Outdoor heat
exchanger
temperature
thermistor
RT68
Ambient
temperature
thermistor
RT65
Unit:inch
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Refrigerant piping : ft Piping size O.D : in
Model
MUZ-FD09NA
MUZ-FD12NA
Max. Length
A
Max. Height difference
B
Gas Liquid
6540 3/8 1/4
Indoor
unit
Max. Height
difference
B
Max. length
A
Outdoor unit
ADDITIONAL REFRIGERANT CHARGE (R410A:oz.)
NOTE : Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
Model Outdoor unit precharged
MUZ-FD09NA
MUZ-FD12NA
2 lb. 9 oz.01.624.868.1011.3412.96
253040506065
Refrigerant piping length (one way) : ft
NOTE : Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
Calculation : X oz. = 1.62/ 5 oz./ ft x (Refrigerant piping length (ft) - 25)
2. Above data is for heating operation without any frost.
Btu/h)
How to operate with fixed operational frequency of the compressor.
1. Press the EMERGENCY OPERATION switch on the front of the indoor unit, and select either EMERGENCY COOL
mode or EMERGENCY HEAT mode before starting to operate the air conditioner.
2. The compressor starts with operational frequency.
3. The fan speed of the indoor unit is High.
4. This operation continues for 30 minutes.
5. In order to release this operation, press the EMERGENCY OPERATION switch twice or once, or press any button on
the remote controller.
9
7-2. PERFORMANCE CURVE
Cooling
MUZ-FD09NA
SHF at rating condition = 0.76
13
Indoor intake air WB temperature (°F)
12
11
Btu/h)
10
3
9
8
Total capacity
(10
7
0.7
Indoor intake air WB temperature (°F)
(kW)
0.6
0.5
Total power consumption
65758595105115
Outdoor intake air DB temperature (°F)
Airflow
Heating
MUZ-FD09NA
= 381 CFM
Airflow
12
10
Btu/h)
8
3
Indoor intake air DB temperature (°F)
Total capacity
(10
6
0.8
Indoor intake air DB temperature (°F)
0.6
(kW)
0.4
Total power consumption
1525354555
Outdoor intake air WB temperature (°F)
= 307 CFM
MUZ-FD12NA
SHF at rating condition = 0.73
15
14
13
Btu/h)
12
3
71
67
63
71
67
63
11
10
Total capacity
(10
1.2
1.1
1.0
(kW)
0.9
0.8
0.7
Total power consumption
Indoor intake air WB temperature (°F)
9
Indoor intake air WB temperature (°F)
65758595105115
Outdoor intake air DB temperature (°F)
Airflow
= 350 CFM
71
67
63
71
67
63
MUZ-FD12NA
65
70
75
20
18
16
Btu/h)
14
3
12
Total capacity
(10
Indoor intake air DB temperature (°F)
10
8
6
75
70
65
1.1
1.0
(kW)
0.9
Indoor intake air DB temperature (°F)
0.8
Total power consumption
0.7
0.6
1525354555
Outdoor intake air WB temperature (°F)
Airflow
= 420 CFM
65
70
75
75
70
65
This value of frequency is not the same as the actual frequency in operating. Refer to 7-5 and 7-6 for the relationships
between frequency and capacity.
1010
7-3. CONDENSING PRESSURE
Cooling
Data is based on the condition of indoor humidity 50 %.
Air flow should be set to High speed.
MUZ-FD09NA
(PSIG)
580
540
500
460
420
380
Condensing pressure
340
300
260
68 707580859095100 105(°F)
Indoor DB temperature (°F)
Outdoor ambient temperature
86
80
75
70
MUZ-FD12NA
(PSIG)
580
540
500
86
460
420
380
Condensing pressure
340
300
260
68 707580859095100 105(°F)
Indoor DB temperature (°F)
Outdoor ambient temperature
80
75
70
(PSIG)
180
175
170
165
160
155
150
145
140
Suction pressure
135
130
125
120
68 707580859095100 105(°F)
(PSIG)
180
175
170
165
160
155
150
145
140
Suction pressure
135
130
125
120
68 707580859095100 105(°F)
Indoor DB temperature (°F)
Outdoor ambient temperature
Indoor DB temperature (°F)
Outdoor ambient temperature
86
80
75
70
86
80
75
70
1111