Mitsubishi MSZ-FA-VA, MSZ-GA-VA, MUZ-GA-VA, MFZ-KA-VA, MUZ-FA-VA Service Technical Manual

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS FLOOR TYPE, HEAT PUMP AIR CONDITIONERS
Revision A:
MSZ-GA80VA has been added.
MUZ-GA•VA - has been added.
MXZ-A•VA - has been added.
Please void OBT14.
SERVICE TECHNICAL GUIDE
Wireless type Models
A
A
No. OBT14
REVISED EDITION-A
A
A
A
Inverter-controlled multi system type Models
· MXZ-A•VA -
A
A
A
Downloaded from AC-Manual.com Manuals
CONTENTS
1. MSZ-FA MICROPROCESSOR CONTROL ··········4
2. MSZ-GA MICROPROCESSOR CONTROL ·······22
3. MFZ MICROPROCESSOR CONTROL··············50
4. MXZ MICROPROCESSOR CONTROL··············62
Revision A:
MSZ-GA80VA has been added.
MUZ-GA•VA - has been added.
MXZ-A•VA - has been added.
1. MSZ-FA MICROPROCESSOR CONTROL ···················································4
A
A
MSZ-FA·VA
Indoor unit models Outdoor unit models
MSZ-FA25VA MUZ-FA25VA MSZ-FA35VA MUZ-FA35VA
1-1. COOL OPERATION ··············································································5 1-2. DRY OPERATION ·················································································6 1-3. HEAT OPERATION ···············································································6 1-4. AUTO CHANGE OVER ··· AUTO MODE OPERATION························8 1-5. INDOOR FAN MOTOR CONTROL·······················································8 1-6. OUTDOOR FAN MOTOR CONTROL···················································8 1-7. AUTO VANE OPERATION ····································································9 1-8. i-see CONTROL OPERATION····························································11 1-9. AREA SETTING ··················································································12 1-10. PLASMA DUO OPERATION······························································14 1-11. AUTO FRONT PANEL ········································································15 1-12. TIMER OPERATION···········································································15 1-13. EMERGENCY / TEST OPERATION···················································16 1-
14.
INVERTER SYSTEM CONTROL ·······················································17
1-
15.
OPERATIONAL FREQUENCY CONTROL OF OUTDOOR UNIT ····19
1-
16.
EXPANSION VALVE CONTROL (LEV CONTROL) ···························20
As for outdoor unit MXZ-8A140VA, refer to service manual OC316.
( )
2. MSZ-GA MICROPROCESSOR CONTROL·················································22
MSZ-GA·VA
Indoor unit models Outdoor unit models
MSZ-GA22VA MSZ-GA25VA MUZ-GA25VA MXZ-A·VA (Refer to 4.) MSZ-GA35VA MUZ-GA35VA MXZ-8A140A
2-1. COOL OPERATION·············································································23 2-2. DRY OPERATION ···············································································24 2-3. HEAT OPERATION ·············································································24 2-4. AUTO CHANGE OVER ··· AUTO MODE OPERATION······················26 2-5. INDOOR FAN MOTOR CONTROL·····················································27 2-6. OUTDOOR FAN MOTOR CONTROL·················································27 2-7. AUTO VANE OPERATION ··································································27 2-8. TIMER OPERATION············································································29 2-9. EMERGENCY / TEST OPERATION ···················································30 2-10.
INVERTER SYSTEM CONTROL·······················································31
2-
11.
OPERATIONAL FREQUENCY CONTROL OF OUTDOOR UNIT·····33
2-
12.
EXPANSION VALVE CONTROL (LEV CONTROL) ···························34
1 (Refer to OC316)
MSZ-GA·VA
Indoor unit models Outdoor unit models
MSZ-GA50VA MUZ-GA50VA MXZ-A·VA (Refer to 4.) MSZ-GA60VA MUZ-GA60VA MXZ-8A140VA
1 (Refer to OC316)
MSZ-GA71VA MUZ-GA71VA MSZ-GA80VA MUZ-GA80VA
2-13. COOL OPERATION ············································································36 2-14. DRY OPERATION···············································································37 2-15. HEAT OPERATION·············································································38 2-16. AUTO CHANGE OVER ··· AUTO MODE OPERATION ·····················40 2-17. INDOOR FAN MOTOR CONTROL·····················································40 2-18. OUTDOOR FAN MOTOR CONTROL·················································41 2-19. AUTO VANE OPERATION··································································41 2-20. TIMER OPERATION ···········································································44 2-21. EMERGENCY/TEST OPERATION·····················································45 2-
22.
INVERTER SYSTEM CONTROL ·······················································45
2-
23.
OPERATIONAL FREQUENCY CONTROL OF OUTDOOR UNIT·····47
2-
24.
EXPANSION VALVE CONTROL (LEV CONTROL) ···························48
Downloaded from AC-Manual.com Manuals
2
3. MFZ MICROPROCESSOR CONTROL ·······················································50
MFZ-KA·VA
Indoor unit models
MFZ-KA25VA MFZ-KA35VA MFZ-KA50VA
3-1. COOL OPERATION·············································································51 3-2. DRY OPERATION ···············································································52 3-3. HEAT OPERATION ·············································································52 3-4. AUTO CHANGE OVER ··· AUTO MODE OPERATION······················54 3-5. INDOOR FAN MOTOR CONTROL·····················································55 3-6. OUTDOOR FAN MOTOR CONTROL·················································55 3-7. AUTO VANE OPERATION ··································································55 3-8. i-save OPERATION·············································································59 3-9. TIMER OPERATION············································································60 3-
10.
EMERGENCY / TEST OPERATION ···················································61
4. MXZ MICROPROCESSOR CONTROL·······················································62
As for outdoor units SUZ-KA25VA.TH, SUZ-KA35VA.TH and SUZ-KA50VA.TH,
(
refer to service manual OC323.
)
MXZ-A·VA
Outdoor unit models
MXZ-2A52VA MXZ-3A54VA MXZ-4A71VA MXZ-4A80VA
4-1. INVERTER SYSTEM CONTROL·························································62 4-2. EXPANSION VALVE CONTROL (LEV CONTROL) ····························66 4-3. OPERATIONAL FREQUENCY RANGE···············································71 4-4. HEAT DEFROSTING CONTROL·························································72 4-5. DISCHARGE TEMPERATURE PROTECTION CONTROL·················72 4-6. REFRIGERANT RECOVERY CONTROL ON HEATING·····················72 4-7. OUTDOOR FAN CONTROL·································································73
Downloaded from AC-Manual.com Manuals
3
1
ON-TIMER button
CLOCK SET button
TIME SET buttons FORWARD button BACKWARD button
VANE CONTROL button (Horizontal vane button)
OFF-TIMER button
i-see button
(This diagram shows an overall view.)
PLASMA button
AREA button
RESET button
WIDE VANE button (Vertical vane button)
Signal transmitting section
Operation display section
Temperature buttons
OPERATE/STOP (ON/OFF) button
FAN SPEED CONTROL button
OPERATION SELECT button
ECONO COOL button
(This diagram shows an overall view.)
Indication of remote controller model
MSZ-FA MICROPROCESSOR CONTROL
MSZ-FA25VA MUZ-FA25VA MSZ-FA35VA MUZ-FA35VA
WIRELESS REMOTE CONTROLLER
Once the operation mode is set, the same operation mode can be repeated by simply turning OPERATE/STOP (ON/OFF) button ON. Indoor unit receives the signal with a beep tone. When the system turns off, 3-minute time delay will operate to protect system from overload and compressor will not restart for 3 minutes.
Downloaded from AC-Manual.com Manuals
4
1-1. COOL ( ) OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.
POWER lamp of the indoor unit turns on with a beep tone. (2) Select COOL mode with OPERATION SELECT button. (3) Press TEMPERATURE buttons (TOO WARM or TOO COOL button)to select the desired temperature.
The setting range is 16 ~ 31°C
Difference between room
1. Thermostat control
Thermostat is ON or OFF by difference between room temperature and set temperature
Initial temperature difference Thermostat Room temperature minus set temperature : -1.0 : or more··············································ON Room temperature minus set temperature : less than -1.0 :············································OFF
2. Indoor fan speed control
Indoor fan operates continuously at the set speed by FAN SPEED CONTROLbutton regardless of the thermostat’s OFF-ON. In AUTO the fan speed is as follows.
Room temperature minus set temperature : 1.7
Room temperature minus set temperature : Between 1 and 1.7 :
Initial temperature difference
Fan speed
: or more ········································High
··································
Med.
Room temperature minus set temperature : less than 1 : ········································Low
3. Coil frost prevention
Temperature control When indoor coil thermistor detects following temperature for 90 seconds, operational frequency of compressor is controlled according to the following table.
temperature and set temper­ature during operation.
Difference between room temperature and set tempera-
ture during operation ( T)
Set temperature
-1.0 :
1 :
-0.7 :
3 :
1.7 :
Temperature of indoor coil thermistor
10°C or more
Operation frequency
Normal (variable)
8°C to 10°C Raise 6 Hz
6°C to 8°C 3°C to 6°C
Fixed
Lower 3Hz Lower 6Hz
3°C or less
when temperature of indoor coil thermistor continues 3°C or less
Compressor is turned OFF for 5 minutes
for 5 minutes or more.
The indoor fan maintains the actual speed of the moment.
4. Low outside temperature operation
If the outside temperature falls to 18°C or less during operation in COOL mode, the unit enters the low outside temperature operation mode.
<Operation> (1) If the unit enters the low outside temperature operation mode, the outside fan rotation speed gets slow down. (2) Even when the unit is in the "thermostat-off" status under the low outside temperature operation mode, the outside fan
rotation does not stop.
(3) In this mode to detect the exact outside temperature the compressor turns OFF with the outdoor fan ON for 3 minutes
once 1 hour; if the outside temperature rises over 18°C, the unit goes back to the normal COOL mode, and if the outside temperature is still 18°C or less, the unit stays in the low outside temperature operation mode.
(4) Dew drop prevention
When the ambient temperature thermistor RT65 reads -12: or less, as coil frost or dew drop from indoor unit may occur, the compressor turns OFF with the outdoor fan ON for prevention of them.
WOther protections work as well as in the normal COOL mode.
Downloaded from AC-Manual.com Manuals
5
1-2. DRY ( ) OPERATION
35
30
25
20
15
10
:
10 15 20 25 30 35
Set temperature
Initial room temperature
Set temperature and initial room temperature in dry mode
:
(1) Press OPERATE/STOP(ON/OFF) button.
POWER lamp of the indoor unit turns on with a beep tone. (2) Select DRY mode with OPERATION SELECT button. (3) The microprocessor reads the room temperature and determines
the set temperature. Set temperature is as shown on the right chart.
The system for dry operation uses the same refrigerant circuit as the cooling circuit. The compressor and the indoor fan are controlled by the room temperature. By such controls, indoor flow amounts will be reduced in order to lower humidity without much room temperature decrease.
Difference between room
1. Thermostat control
Thermostat is ON or OFF by difference between room temperature and set temperature.
Initial temperature difference Thermostat
temperature and set tem­perature during operation
Set temperature Room temperature minus set temperature : -1.0 : or more················································ON Room temperature minus set temperature : less than -1.0 :··············································OFF
2. Indoor fan speed control
-1.0 :
Indoor fan operates at the set speed by FAN SPEED CONTROLbutton. When thermostat OFF (compressor OFF) fan speed becomes Very Low.
In AUTO the fan speed is as follows.
Initial temperature difference
Fan speed
Difference between room temperature and set tempera­ture during operation ( T)
Room temperature minus set temperature : 1.7 : or more ········································High Room temperature minus set temperature : Between 1 and 1.7 :
··································
Room temperature minus set temperature : less than 1 : ········································Low
Med.
1 :
3. Coil frost prevention
Coil frost prevention is as same as COOL mode. (1-1.3.) The indoor fan maintains the actual speed of the moment.
4. Low outside temperature operation
Low outside temperature operation is as same as COOL mode. (1-1.4.)
1-3. HEAT ( ) OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.
POWER lamp of the indoor unit turns on with a beep tone. (2) Select HEAT mode with OPERATION SELECT button. (3) Press TEMPERATURE buttons (TOO WARM or TOO COOL button) to select the desired temperature.
The setting range is 16 ~ 31°C.
1. Thermostat control
Thermostat is ON or OFF by difference between room temperature and set temperature.
Initial temperature difference Thermostat Room temperature minus set temperature : less than 2.0 :···············································ON Room temperature minus set temperature : 2.0 : or more·················································OFF
2. Indoor fan speed control
(1) Indoor fan operates at the set speed by FAN SPEED CONTROLbutton.
In Auto the fan speed is as follows.
Initial temperature difference
Set temperature minus room temperature: 2 :or more Set temperature minus room temperature:
Between 0.2 and 2 : ·································
Set temperature minus room temperature: less than 0.2
··················································High :··············································
(2) Cold air prevention control
1 When the compressor is not operating,
(1) if the temperature of room temperature thermistor RT11 is less than 19°C, the fan stops. (2) if the temperature of room temperature thermistor RT11 is 19°C or more and
(1) if the temperature of RT12 is less than 0°C, the fan stops. (2) if the temperature of RT12 is 0°C or more, the fan operates at Very Low.
2 When the compressor is operating,
(1) if the temperature of RT12 is 40°C or more, the fan operates at set speed. (2) if the temperature of RT12 is less than 40°C and
(1) if heating operation starts after defrosting, the fan stops. (2) if the temperature of room temperature thermistor RT11 is 19°C or less, the fan stops.
NOTE : When 3 minutes have passed since the compressor started operation, this control is released regardless of the
Downloaded from AC-Manual.com Manuals
(3) if the temperature of room temperature thermistor RT11 is more than 19°C, the fan operates at Very Low.
temperature of RT11 and RT12.
Fan speed
Med. Low
6
Difference between room temperature and set tem­perature during operation
Set temperature
1.7 :
Difference between room temperature and set tem­perature during operation
0.2 :
1.7 :
1.7 :
-0.7 :
2.0 :
2 :
2.5 :
4 :
set position
set speed
set position
set speed
Indoor fan
Compressor normal
Outdoor fan
R.V. coil
(21S4)
OFF (COOL)
OFF
Maximum frequency
horizontal
Horizontal vane
Very Low (temperature of indoor coil thermistor > 18:)
30
seconds
30
seconds
30
seconds
40
seconds
5 seconds 5 seconds
40
seconds
OFF
OFF
OFF
ON (HEAT)
ON ON
ON (HEAT)
3. High pressure protection
In HEAT operation the indoor coil thermistor detects the temperature of the indoor heat exchanger. The compressor opera­tional frequency is controlled to prevent the condensing pressure from increasing excessively.
4. Overload starting
When the room temperature thermistor RT11 reads 18°C or more, the compressor runs with its maximum frequency regulat­ed for 10 minutes after the start-up.
5. Defrosting
(1) Starting conditions of defrosting
When the following conditions a) ~ c) are satisfied, the defrosting starts. a) The defrost thermistor reads -3°C or less. b) The cumulative operation time of the compressor has reached any of the set valuesw (30, 35, 40, 45, 55, 65, 75, 85,
95, 105, 115, 125, 150 minutes). c) More than 5 minutes have passed since the start-up of the compressor. w Set value of compressor operation time(hereinafter referred to as defrost interval)
This is decided by the temperature of defrost thermistor and ambient temperature thermistor, the previous defrosting
time. For example, the first defrost interval is 40 minutes long, and the second is 45 minutes long. The third and sub-
sequent intervals are set to be longer, and less frequent, depending on defrosting time.
The third and subsequent defrost intervals follow any of the three patterns …5 or 10 to 20 minutes longer, the same,
or 5 or 10 to 20 minutes shorter compared with the previous defrost interval … with the longest 150 minutes and the
shortest 30 minutes.
(2) Releasing conditions of defrosting
Defrosting is released when any of the following conditions is satisfied: a) The defrost thermistor continues to read 5°C or more (MUZ-FA25VA) / 10°C or more (MUZ-FA35VA) for 30 seconds. b) Defrosting time has exceeded 10 minutes. c) Any other mode than HEAT mode is set during defrosting.
Time chart of defrosting in HEAT mode (reverse type)
<indoor unit>
<outdoor unit>
Downloaded from AC-Manual.com Manuals
7
1-4. AUTO CHANGE OVER ··· AUTO MODE OPERATION
High
Med.
Low
Super High
Super High
time
Rotational frequency
COOL
Fan speed
Up
Down
Up
Down
Mode
HEAT
Compressor frequency
MUZ-FA25 MUZ-FA35
<Relation between compressor frequency and fan speed.>
43Hz 33Hz 43Hz 33Hz
54Hz 41Hz 54Hz 41Hz
Up
Down
Fan speed
High
Low
Compressor frequencyMin. Max.
Once desired temperature is set, unit operation is switched automatically between COOL and HEAT operation.
1. Mode selection
(1) Initial mode
At first indoor unit operates only indoor fan with outdoor unit OFF for 3 minutes to detect present room temperature. Following the conditions below, operation mode is selected.
1 If the room temperature thermistor RT11 reads more than set temperature, COOL mode is selected. 2 If the room temperature thermistor RT11 reads set temperature or less, HEAT mode is selected.
(2) Mode change
In case of the following conditions the operation mode is changed. 1 COOL mode changes to HEAT mode when 15 minutes have passed with the room temperature 2 degrees below the
set temperature.
2 HEAT mode changes to COOL mode when 15 minutes have passed with the room temperature 2 degrees above the
set temperature. In the other cases than the above conditions, the present operation mode is continued. NOTE1: Mode selection is performed when multi standby (refer to NOTE2) is released and the unit starts operation with
ON-timer.
NOTE2: If two or more indoor units are operating in multi system, there might be a case that the indoor unit, which is
operating in AUTO ( ), cannot change over the other operating mode (COOL HEAT) and becomes a state of standby.
(3) Indoor fan control/ Vane control
As the indoor fan speed and the horizontal vane position depend on the selected operation mode, when the operation mode changes over, they change to the exclusive ones.
1-5. INDOOR FAN MOTOR CONTROL
(1) Rotational frequency feedback control
The indoor fan motor is equipped with a rotational frequency sensor, and outputs signal to the microprocessor to feedback the rotational frequency. Comparing the current rotational frequency with the target rotational frequency (Super High, High, Med., Low), the microprocessor adjusts fan motor electric current to make the current rotational frequency close to the target rotational frequency. With this control, when the fan speed is switched, the rotational frequency changes smoothly.
(2) Fan motor lock-up protection
When the rotational frequency feedback signal has not output for 12 seconds, (or when the microprocessor cannot detect the signal for 12 seconds) energizing to the fan motor is stopped. Then the microprocessor retries detection 3 times every 30 seconds. If the microprocessor still cannot detect the signal, the fan motor is regarded locked-up. When the fan motor lock-up, POWER lamp flashes on and off to show the fan motor abnormality.
1-6. OUTDOOR FAN MOTOR CONTROL
Fan speed is switched according to the compressor frequency.
Downloaded from AC-Manual.com Manuals
8
Horizontal
position
1-7. AUTO VANE OPERATION
1. Horizontal vane
(1) Vane motor drive
These models are equipped with a stepping motor for the horizontal vane. The rotating direction, speed, and angle of the motor are controlled by pulse signals (approximate 12V) transmitted from indoor microprocessor.
(2) The horizontal vane angle and mode change as follows by pressing VANE CONTROL button.
(3) Positioning
The vane presses the vane stopper once to confirm the standard position and then moves to the set angle. Confirming of standard position is performed in case of follows. (a) When the operation starts or finishes (including timer operation). (b) When the test run starts. (c) When multi-standby starts or finishes.
(4) VANE AUTO ( ) mode
In VANE AUTO mode, the microprocessor automatically determines the vane angle and operation to make the optimum room-temperature distribution.
(1) In COOL and DRY operation
(2) In HEAT operation
(5) STOP (operation OFF) and ON-TIMER standby
When the following cases occur, the horizontal vane returns to the closed position. (a) When OPERATE/STOP (ON/OFF) button is pressed (POWER OFF). (b) When the operation is stopped by the emergency operation. (c) When ON-TIMER is ON standby.
(6) Dew prevention
During COOL or DRY operation with the vane angle at Angle 2 ~ 4 when the compressor cumulative operation time exceeds 1 hour, the vane angle automatically changes to Angle 1 for dew prevention.
(7) SWING MODE ( )
By selecting SWING mode with VANE CONTROL button, the horizontal vane swings vertically. The remote controller displays “”. SWING mode is cancelled when VANE CONTROL button is pressed once again.
(8) Cold air prevention in HEAT operation.
When any of the following conditions occurs in HEAT operation, the vane angle changes to Horizontal position automati­cally to prevent cold air blowing on users.
Compressor is not operating.Defrosting is performed.Indoor coil thermistor RT12 reads 24: or below.Indoor coil thermistor RT12 temperature is raising from 24°C or below, but it does not exceed 39:.For about 3 minutes after compressor starts.
Vane angle is fixed to Horizontal position.
Vane angle is fixed to Angle 4.
NOTE : When 2 or more indoor units are operated with multi outdoor unit, even if any indoor unit turns thermostat off,
this control doesn’t work in the indoor unit.
Downloaded from AC-Manual.com Manuals
9
The air conditioner starts heat­ing operation approx. 3 minutes after the vane has moved to the horizontal position.
• Sometimes the area around your feet may not war m. To warn the area around the feet, set the horizontal vane to (AUTO) or the downward­blowing position.
• When VANE CONTROL button is pressed again, the vane returns to the previously-set position and the air conditioner starts the heating operation in approx. 3minutes.
To change the air
flow direction
When to use this function?
Use this function if you don’t want the air from the indoor unit to blow directly onto your body.
• Depending on the shape of the room,the air may blow directly onto your body.
• Press VANE CONTROL button again to return the
vane to the previously-set position.
The air conditioner starts the cooling or drying operation approx. 3 minutes after the vane has moved to the hori­zontal position.
Pressing and holding VANE CONTROL
button for 2 seconds
or more causes the horizontal vane to reverse and move to horizontal position.
COOL/DRY
HEAT
NOTE:
• If you make the air flow not to blow directly onto your body by pressing VANE CONTROL button, the compressor stops for 3 minutes even during the operation of the air conditioner.
• The air conditioner operates with decreased air flow until the compressor turns on again.
(9) To change the air flow direction not to blow directly onto your body.
Horizontal
position
When VANE CONTROL button is pressed again, the vane returns to the previously-set position and the air conditioner starts the cooling or drying operation in approx. 3minutes.
(10) ECONO COOL ( ) operation (ECONOmical operation)
When ECONO COOL button is pressed in COOL mode, set temperature is automatically set 2°C higher than that in COOL mode. Also the horizontal vane swings in various cycle according to the temperature of indoor heat exchanger(RT12). SWING operation makes you feel cooler than set temperature. So, even though the set temperature is higher than that in COOL mode, the air conditioner can keep comfort. As a result, energy can be saved.
ECONO COOL operation is cancelled when ECONO COOL button is pressed once again or VANE CONTROL
button is pressed or change to other operation mode.
<SWING operation> In swing operation of ECONO COOL operation mode, the initial air flow direction is adjusted to “Horizontal”. According to the temperature of indoor coil thermistor RT12 at starting of this operation, next downward blow time is decided. Then when the downward blow has been finished, next horizontal blow time is decided. For initial 10 minutes the swing operation is performed in table G~H for quick cooling. Also, after 10 minutes when the difference of set temperature and room temperature is more than 2:, the swing oper­ation is performed in table D~H for more cooling. The air conditioner repeats the swing operation in various cycle as follows.
Temperature of indoor
coil thermistor RT12
A
B C D E
F G H
15°C or less 15°C to 17°C 17°C to 18°C
18°C to 20°C
20°C to 21°C 21°C to 22°C 22°C to 24°C
more than 24°C
Downward blow time
(second)
2 5
8 11 14 17 20 23
Horizontal blow time
(second)
23 20 17 14 11
8 5 2
Downloaded from AC-Manual.com Manuals
10
2. Vertical vane
(1) Vane motor drive
These models are equipped with a stepping motor for the vertical vane. The rotating direction, speed, and angle of the motor are controlled by pulse signals (approximate 12V) transmitted from microprocessor.
(2) The vertical vane angle and mode change as follows by pressing WIDE VANE button.
1
2 3
4 5
(SWING)
(3) Positioning
The vane is once pressed to the vane stopper to confirm the standard position and then set to the desired angle. Confirming of standard position is performed in case of follows. (a) When OPERATE/STOP(ON/OFF) button is pressed (POWER ON). (b) When SWING is started.
(4) SWING MODE ( )
By selecting SWING mode with WIDE VANE button, the vertical vane swings horizontally. The remote controller displays “ ”. Swing mode is cancelled when WIDE MODE button is pressed once again.
1-8. i-see CONTROL OPERATION
The sensors constantly measure the room and floor/wall temperatures to automatically adjust to the set temperature by estimating the temperature actually perceived by a person inside the room (“sensory temperature”).
Advantages
· The air inside the room is conditioned quickly to a comfortable condition.
· The room will not become too cold or hot even when the air conditioner is kept on for a long period.
· The air conditioner will not overcool or overheat, which means you can save on electricity. i-see control operation is activated when i-see button is pressed with a thin stick in manual COOL or manual HEAT mode.
NOTE :
i-see control operation is activated when the remote controller is first used following replacement of the batteries or resetting of the remote controller.
i-see control operation is cancelled when i-see button is pressed with a thin stick once again.
NOTE :
If the conditioner is turned OFF without cancelling i-see control operation, i-see control operation is activated the next time the air conditioner is turned ON.
i-see Sensor
i-see Sensor, which is installed on the right side of the air outlet of the indoor unit, is moved with the stepping motor and it
detects the floor/ wall temperature.
i-see Sensor is installed here.
i-see Sensor
When AREA setting is not activated, the sensing range of i-see Sensor differs depending on the installation
·
location of the air conditioner.
Installation
position
Image of sensing
range
Direction of sensor
Refer to the description on service manual OB371 (8-4. Remote controller) for slide switch settinng.
Installed at left Installed at center Installed at right
Right Center Left
· Install the front panel correctly after being removed for maintenance or service so that the
floor/wall temperatures can be measured correctly.
Downloaded from AC-Manual.com Manuals
Enlarged view of i-see Sensor
11
1-9. AREA ( ) SETTING
(1) Press OPERATE / STOP (ON/ OFF)button to start the air conditioner. (2) Press i-see button. (NOTE 1) (3) Press AREA button.
Each time the button is pressed, the area is changed in sequence:
NOTE1: AREA setting is only available during i-see control operation. NOTE2: If AREA setting is canceled, the vertical vane returns to the previously set position before AREA setting. NOTE3: The horizontal air flow direction (WIDE VANE button), including horizontal SWING, can not be set during AREA setting.
(AUTO) (LEFT) (RIGHT) Cancel
The indoor unit delivers warm air detecting the cold area in the room.
· If AREA setting is set to AUTO in heating operation, the indoor unit automatically delivers warm air to the area where the floor/wall temperature is the lowest in the room.
· If AREA setting is set to AUTO in cooling operation, the indoor unit automatically delivers cool air to the area where the floor/wall temperature is the highest in the room.
Ex.) In heating operation
Moving of horizontal air flow direction
Indoor unit
display
NOTE
· The horizontal air flow direction changes if i-see Sensor detects approx. 3; temperature difference.
· In AUTO of AREA setting, both right and left lamps are lighted when the room is evenly air-conditioned.
Indication of AREA setting
Day
Night
Warm area Cold area
Lighted Not lighted
i-see Sensor moves intermittenly, measuring the floor and wall temperature.
Downloaded from AC-Manual.com Manuals
12
(4) AREA setting is cancelled when the "cancel" is sellected by pressing AREA button, or when WIDE VANE button is pressed.
Indoor unit installation location and air-conditioning area
Installed at left Installed at center Installed at right
LEFT RIGHT LEFT RIGHT LEFT RIGHT
· Be sure to set the slide switch inside the remote controller to an appropriate position in accordance with the installed position of the indoor unit. If the switch is not set correctly, the air conditioner may not function properly.
(Refer to Service manual OB371 8-4.)
To air-condition mainly the left area of the room
Remote controller button
Remote controller display
i-see Sensor operation
Control range of horizontal air flow direction. The vertical air flow direction conforms to the setting on the remote controller. (The horizontal air flow direction is controlled in this range.)
Indoor unit display
NOTE: If the AREA setting is activated (AUTO), i-see Sensor moves in a range of 150 degrees detecting
floor/wall temperature of 3 area (left, right, center). Therefore, the detected temperatures may be different from the temperatures measured on commercial thermometers depending on the condition or temperature distribution on the floor and/or wall.
Installed at center
Installed at left
Installed at right
AREA
Press AREA button to select LEFT.
T o air-condition the entire room The horizontal air flow direction and in­door unit display are switched accord­ing to the room temperature (floor/wall).
Press AREA button to select AUTO.
or
or
Operation and operating range
i-see sensor moves 30 degrees from the center in both right and left side.
To air-condition mainly the right area of the room
Press AREA button to select RIGHT.
Approx. 150 degrees
i-see Sensor turning to the left
i-see Sensor turning to the center
i-see Sensor turning to the right i-see Sensor operates as follows in accordance with AREAsetting made with the remote controller.
“AUTO” in AREAsetting; first turning to the LEFT for adjusting the position then.....
CENTER RIGHT CENTER LEFT CENTER......
(The sensor turns to the right, left and center.)
“RIGHT” in AREAsetting; first turning to the LEFT for adjusting the position then....
CENTER RIGHT CENTER RIGHT CENTER......
(The sensor turns to the right and center.)
“LEFT” in AREAsetting; first turning to the LEFT for adjusting the position then....
CENTER LEFT CENTER LEFT CENTER......
(The sensor turns to the left and center.)
The sensor finishes turning to one area to another for 3 seconds and it operates one area for 5 seconds.
13
Downloaded from AC-Manual.com Manuals
PLASMA/WASH lamp
Blinking Not lighted
Lighted
WASH reset switch
WASH
reset
E.O.
SW
Each time this b utton is pressed, the oper ation mode of PLASMA is changed in sequence:
Cancel (The sign of PLASMA oper ation disappears .)
PLASMA/WASH lamp tur ns on in the displa y section of the indoor unit and PLASMA DEODORIZING and/or PLASMA AIR PURIFYING unit is energyz ed. Adjust the air flow to your desired speed.
(1) Press OPERATE/STOP (ON/OFF) button to start the air conditioner. (2) Press PLASMA button to set PLASMA DUO operation.
(3) PLASMA operation is cancelled when the "cancel" is selected by pressing PLASMA button. Once PLASMA operation is selected, PLASMA operation will be performed every time the air conditioner is turned on until the "Cancel" is selected with PLASMA button.
1-10. PLASMA DUO ( ) OPERATION
Never touch the PLASMA DEODORIZING/AIR PURIFYING filter units during the operation of the air conditioner. Although the filter units are safety-conscious design, touching the units could be the cause of trouble as they discharge high voltage electricity.
PLASMA/WASH lamp
Not lighted
Lighted
Description of PLASMA DUO operation:
< function>
Both PLASMA DEODORIZING and PLASMA AIR PURIFYING operation work.
<
function>
PLASMA DEODORIZING operation cleans the air inside the room by adsorbing and decomposing the particles of odor-releasing substances and gases such as formaldehyde.
<
function>
PLASMA AIR PURIFYING operation cleans the air inside the room by absorbing the particles of cigarette smoke or allergens such as pollens and house dust.
NOTE1: Carbon monoxide released from cigarettes cannot be removed by PLASMA operation. Open the windows to let the outside air in from time to time. NOTE2: During PLASMA operation, you may smell ozone that is generated in small quantities from PLASMA DEODORIZING/AIR PURIFYING filter units. This is not a malfunction. NOTE3: You may hear a small "hissing" sound during PLASMA operation. This is the sound of plasma discharge, and not a malfunction.
<Cleaning>
When PLASMA/WASH lamp is blinking, please clean PLASMA DEODORIZING/AIR PURIFYING filter units. After cleaning of PLASMA DEODORIZING/AIR PURIFYING filter units, press WASH reset switch. A short “beep” is heard and the blinks of PLASMA/WASH lamp will be cancelled.
Downloaded from AC-Manual.com Manuals
14
START
STOP
START
STOP
1-11. AUTO FRONT PANEL
When the unit starts operating, the front panel opens automatically to draw in air. When the unit stops operating, the front panel closes automatically.
Open
Closed
Operation and operating range of the auto front panel
The front panel fully opens 10 mm or more upper than the level line of the top end of the nozzle assembly. It takes about 13 seconds to open the front panel completely.
10 mm or more
Z-Z Side view
1-12. TIMER OPERATION
1. How to set the timer
(1) Press OPERATE/STOP (ON/OFF) button to start the air conditioner. (2) Check that the current time is set correctly. NOTE : Timer operation will not work without setting the current time. Initially “AM0:00” blinks at the current time display of
TIME MONITOR, so set the current time correctly with CLOCK SET button.
ON timer setting
(1) Press ON-TIMER button( ) to set ON timer.
Each time the button is pressed, ON timer mode alternates between ON and OFF.
(2) Set the time of the timer using TIME SET buttons ( and ).
Each time FORWARD button( ) is pressed, the set time increases by 10 minutes; each time BACKWARD button ( ) is pressed, the set time decreases by 10 minutes.
OFF timer setting
(1) Press OFF-TIMER button ( ) to set OFF timer.
Each time the button is pressed, OFF timer mode alternates between ON and OFF.
(2) Set the time of the timer using TIME SET buttons ( and ).
Each time FORWARD button ( ) is pressed, the set time increases by 10 minutes; each time BACKWARD ( ) button is pressed, the set time decreases by 10 minutes.
2. Cancel
TIMER setting can be cancelled with ON/OFF TIMER buttons. To cancel ON timer, press ON-TIMER button ( ). To cancel OFF timer, press OFF-TIMER button( ). TIMER is cancelled and the display of set time disappears.
Downloaded from AC-Manual.com Manuals
15
EMERGENCY OPERATION switch
WASH
reset
E.O.
SW
Operation mode COOL HEAT Set temperature
24:
24: Fan speed Medium Medium Horizontal vane Auto Auto Vertical vane Straight Straight
The operation mode is indicated by the Operation In­dicator lamp on the indoor unit as following figure.
Operation Indicator lamp
NOTE: This is the indication of EMERGENCY OPERATION mode. AREA setting is not available during EMER­GENCY OPERATION.
Press again <Heat>
Press once <Cool>
Lighted Not lighted
Press once again <Stop>
PROGRAM TIMER
• The OFF timer and ON timer can be used in combination. The timer of the set time that is reached first will operate first.
• “ ” and “ ” display shows the order of the OFF timer and the ON timer operation.
(Example 1) The current time is 8:00 PM.
The unit turns off at 11:00 PM, and on at 6:00 AM.
(Example 2) The current time is 11:00 AM.
The unit turns on at 5:00 PM, and off at 9:00 PM.
NOTE : If the main power is turned off or a power failure occurs while AUTO START/STOP timer is active, the timer setting is
cancelled. As these models are equipped with an auto restart function, the air conditioner starts operating with timer cancelled when power is restored.
1-13. EMERGENCY / TEST OPERATION
In case of test run operation or emergency operation, use EMERGENCY OPERATION switch on the front of the indoor unit. Emergency operation is available when the remote controller is missing, has failed or the batteries of the remote controller run down. The unit will start and AREA lamp will light. The first 30 minutes of operation is the test run operation. This operation is for servicing. The Indoor fan speed runs at High speed and the system is in continuous operation (The thermostat in ON). After 30 minutes of test run operation the system shifts to EMERGENCY COOL / HEAT MODE with a set temperature of 24°C. The fan speed shifts to Med.. The coil frost prevention works even in emergency operation, and defrosting too.
In the test run or emergency operation, the horizontal vane operates in VANE AUTO ( ) mode. Emergency operation continues until EMERGENCY OPERATION switch is pressed once or twice or the unit receives any signal from the remote controller. In case of latter normal operation will start.
NOTE1 : Do not press EMERGENCY OPERATION switch during normal operation. NOTE2 : 3 seconds after EMERGENCY OPERATION switch is pressed, the front panel starts moving forward
automatically.
16
Downloaded from AC-Manual.com Manuals
1-14. INVERTER SYSTEM CONTROL
POWER P.C. BOARD
Power supply
INVERTER P.C. BOARD
R64A R64B
CT
TR821
DB65
X64
L62 L63
C63A C63B C63C
DB61
L61
P
W
V
U
N
CT761
CT781
IPM
U
W
MC
V
+
Booster chopper circucuit
SYMBOL IPM C63A/C63B/C63C CT761/CT781
CT DB61 R64A, R64B
X64 DB65
TR821 L61
NAME INTELLIGENT POWER MODULE SMOOTHING CAPACITOR CURRENT TRANSFORMER
CURRENT TRANSFORMER DIODE MODULE CURRENT-LIMITING RESISTOR
RELAY DIODE MODULE
SWITCHING POWER TRANSISTOR REACTOR
FUNCTION
It supplies three-phase AC power to compressor. It stabilizes the DC voltage. It measures the current of the compressor motor. It measures the value of current which is supplied to the main power supply circuit. It converts the AC voltage to DC voltage. It absorbs the rush current not to run into the main power supply circuit when the electricity turns ON. It short-circuits the resistance which restricts rush current during the normal operation after the compressor startup.
Booster chopper circuit
Function of main parts
It improves power factor. It rectifies AC and controls its voltage.
1-14-2. Outline of main power supply circuit
1. At the start of operation
Main power supply circuit is formed when X64 (Relay) is turned ON at compressor startup. To prevent rush current from running into the circuit when power supply is turned ON, R64A and R64B (Current-limitting resistor) are placed in sub circuit.
2. At normal operation
1 When AC runs into POWER P.C. board, its external noise is eliminated in the noise filter circuit. 2 After noise is eliminated from AC, it is rectified to DC by DB61 (Diode module). 3 DC voltage, to which AC has been rectified by process 2, is stabilized by C63A, C63B and C63C (Smoothing capacitor) and supplied to IPM (Intelligent power module). 4 DC voltage, which has been stabilized in process 3, is converted to three-phase AC by IPM and supplied to compressor. 5 CT761 and CT781 (Current Transformer), which are placed in the power supply circuit to compressor, are used to measure the value of phase current and locate the polar direction of rotor with algorithm. PWM (Pulse width modulation) controls impressed voltage and frequency with those information.
1-14-1. Inverter main power supply circuit
Downloaded from AC-Manual.com Manuals
17
4. Intelligent power module
IPM consists of the following components
· IGBT (x6) : Converts DC waveform to three-phase AC waveform and outputs it.
· Drive Circuit : Drives transistors.
· Protection circuit : Protects transistors from overcurrent. Since the above components are all integrated in IPM, IPM has a merit to make the control circuit simplify and miniaturize.
5. Smoothing capacitor
C63A, C63B and C63C stabilize the DC voltage and supply it to IPM.
6. Elimination of electrical noice
Noise filter circuit, which is formed by *CMC COILS capacitors placed on the POWER P.C. board, eliminates electrical
noise of AC power that is supplied to main power supply circuit. And this circuit prevents the electrical noise generated in the inverter circuit from leaking out. *CMC COILS; Common mode choke coils
Outline of simple partial switching method
In conventional inverter models, diode module rectifies AC voltage to DC voltage, smoothing capacitor makes its DC waveform
smooth, and IPM converts its DC voltage to imitated AC voltage again in order to drive the compressor motor.
However, it has been difficult to meet IEC harmonic current emission standard by above circuit because harmonic gets generated in the input current waveform and power factor gets down. The simple partial switching method with PAM, which has been adopted this time, places and utilizes the booster chopper circuit (L61, DB65 and TR821) before rectifying AC voltage in the general passive-method converter circuit. As harmonic gets suppressed and the peak of waveform gets lower by adding booster chopper circuit as mentioned above and by synchronizing the timing of one-time switching with the zero-cross point of waveform, the input current waveform can be improved and the requirement of IEC harmonic current emission standard can be
satisfied. Since the switching times is just once by synchronizing with the zero cross point, this simple partial switching method has the feature of lower energy loss compared to active filter method. In addition, output and efficiency is enhanced by
combining with vector-controlled inverter in order to boost the voltage of power supplied to IPM.
Input current waveform without PAM Input current waveform with PAM
Due to the time of no electricity;
· Power factor gets worse.
· Harmonic gets increased. Input voltage
Release of energy stored in L
Energized time is extended by optimization of L inductance.
Peak gets down.
Energized time is short in case L inductance is small.
No electricity runs into diode module because the voltage at both sides of smoothing capacitor is higher than input voltage.
Compulsory energizing by switching.
Input current
Owing to the increase of energized time;
· Power factor gets better.
· Harmonic gets suppressed.
3. Purpose of PAM adoption
PAM : Pulse Amplitude Modulation PAM has been adopted for the efficiency improvement and the adaptation to IEC harmonic current emission standard.
Sine wave control
In these air conditioners, compressor equips brushless DC motor which doesn't have Hall element. In short, the motor is sensorless. However, it's necessary to locate the polar direction of rotor in order to drive brushless DC
motor efficiently. The general detection method of the polar direction for such a DC motor is to locate it from the voltage induced by unenergized stator.
Therefore, It is necessary to have a certain period of time in which the stator is being unenergized for the rotor position detection when the voltage of supplied power is impressed. So the motor has been driven by square wave control (the conventional motor drive system) which energizes the motor only
when the range of electrical angle is within 120_ because it is forced to be unenergized within 30_ at start & end of one heap in one waveform cycle (180_) when the voltage is impressed.
However, torque pulsation occurs at rotation in this method when the current-carrying phases are switched over to other phases in sequence. Therefore, sine wave control system is adopted for these air conditioners because it can make the phase-to-phase current waveform smoother (sine wave) in order to drive the motor more efficiently and smoothly.
Downloaded from AC-Manual.com Manuals
18
1 hour
Time
Maximum frequency
Upper limit frequency
Rated frequency or less
1-15. OPERATIONAL FREQUENCY CONTROL OF OUTDOOR UNIT
Rotor Rotor Position Signal
Permanent magnet is embedded. Necessary
DC Motor
Excited by magnetic field of stator Unnecessary
AC Motor
1-14-3. Characteristics of sine wave control in case of brushless DC motor
Although ordinary three-phase induction motor requires energy to excite the magnetic field of rotor, brushless DC motor
doesn't need it. So, higher efficiency and torque are provided.
This control provides the most efficient waveform corresponding to the rotation times of compressor motor.
The rotation can be set to higher compared to the conventional motor drive system. So, the time in which air conditioner
can be operated with energy saved is longer than conventional models. This can save annual electric consumption.
Compared to square wave control, the torque pulsation is reduced at rotation so that the motor operates more quietly.
Since response and efficiency of motor are enhanced in sine wave control, finer adjustment can be provided.
w In brushless DC motor, permanent magnet is embedded in the rotor. Therefore, it doesn't require energy to excite the rotor
like AC motor does. However, it's necessary to control the frequency of three-phase AC current supplied to the stator according to the polar direction of magnet embedded in the rotor so as to drive the motor efficiently. Controlling three-phase AC current frequency also means controlling the timing to switch the polarity of stator. Therefore, the polar direction of rotor needs to be detected.
1-14-4. Control Method of Rotation Times
Sine wave control makes the current transformers conduct real time detection of the value of the current running into the motor, locates the rotor position from the detected value, and decides if voltage should be impressed and if frequency should be chan­ ged. Compared to the conventional control and rotor position detection method, sine wave control can provide finer adjustment of the voltage of supplied power. The value of the current running into the motor is determined by each motor characteristic.
1. Outline The operational frequency is as following: First, the target operational frequency is set based on the difference between the room temperature and the set tem­perature. Second, the target operational frequency is regulated by discharge temperature protection, high pressure protection, electric current protection and overload protection and also by the maximum/minimum frequency.
2. Maximum/minimum frequency in each operation mode.
COOL
Applied
model
MUZ-FA25VA
MUZ-FA35VA
Minimum frequency
28
28 70
Rated frequency
57
Maximum frequency
98
86
Minimum frequency
45
35
HEAT
Rated frequency
77 105
73 98 28
Maximum frequency
Minimum frequency
DRY
28
w The operation frequency in COOL mode is restricted the upper limit frequency after 1 hour as shown below for
dew prevention. It is rated frequency or less.
Downloaded from AC-Manual.com Manuals
19
Maximum frequency
58
57
1-16. EXPANSION VALVE CONTROL (LEV CONTROL)
(1) Outline of LEV control The LEV basic control is comprised of setting LEV opening degree to the standard opening degrees set for each opera-
tional frequency of the compressor. However, when any change in indoor/outdoor temperatures or other factors cause air conditioning load fluctuation, the LEV control also works to correct LEV opening degree based on discharge temper­ature (Shell temperature) of the compressor, developing the unit’s performance.
Control range from minimum 33 pulse to maximum 500 pulse. Actuating speed LEV opens 40 pulse/second and close 90 pulse/second Opening degree adjustment LEV opening degree is always adjusted in opening direction.
standard
specification
Unit OFF LEV remains at maximum opening degree (reaches maxi-
Remote controller ON LEV is positioned. (first full-closed at zero pulse and then
(When reducing the opening degree, LEV is once over­closed, and then adjusted to the proper degree by opening.
mum opening degree approximate in 15 minutes after com­pressor stops)
positioned.)
COOL · DRY MODE During 1 to 5 minutes after compressor starts
HEAT MODE During 1 to 15 minutes after compressor starts
More than COOL, DRY: 5/ HEAT: 15 minutes have passed since compressor start-up
general operation
Thermostat OFF LEV is adjusted to exclusive opening degree for thermostat
Thermostat ON
Defrosting in HEAT mode LEV is adjusted to open 500 pulse.
LEV is fixed to standard opening degree according to opera­tional frequency of compressor.
LEV opening degree is corrected to get target discharge temperature of compressor. (For discharge temperature lower than target temperature, LEV is corrected in closing direction.) (For discharge temperature higher than target temperature, LEV is corrected in opening direction.) wIt may take more than 30 minutes to reach target tempera­ture, depending on operating conditions.
OFF.
LEV is controlled in the same way as that after the compres­sor has started up.
Downloaded from AC-Manual.com Manuals
20
(2) Time chart
OFF Time
Time
ON
Operational frequency
of the compressor
Commanded to open
Standard opening degree
Opening degree is corrected according to discharge temperature.
Positioning
Air conditioner ON
Air conditioner OFF (thermostat off)
LEV opening degree
about 5 minutes <COOL, DRY> about 15 minutes <HEAT>
06 05 04 03 02
01
LEV opening degree
A(target discharge temperature)
B
C
D
E
F
30 50 70
Operational frequency of the compressor
90 110 130
(Hz)
(3) Control data
(a) Reference value of target discharge temperature
(COOL/HEAT :)
Applied model
MUZ-FA25VA
MUZ-FA35VA
A
47/41B53/48C58/55
50/45
53/52 60/59
In COOL operation, the two indoor coil thermistors (one main and one sub) sense temperature ununiformity (super heat) at the heat exchanger, and when temperature difference have developed, the indoor coil thermistors adjust LEV opening degree to get approximate 10 degrees lower temperature than the target temperature in the table above, thus diminishing super heat.
(b) Reference value of LEV standard opening degree
(COOL/ HEAT pulse)
Applied model
MUZ-FA25VA
MUZ-FA35VA
150/110
130/100
01
02
190/11003240/15004280/17005310/20006340/230
190/130 240/170
Downloaded from AC-Manual.com Manuals
D
63/60
66/68
260/210
E
67/65F67/65
70/76 70/76
260/230
260/230
21
2
Approximate 2 : or more
Difference between target temperature and room temperature
Approximate 2 : or less
This shows that the air conditioner is operating to reach the target temperature. Please wait until the target temperature is obtained.
This shows that the room temperature is approaching the target temperature.
Operation stateIndication
Lighted
Not lighted
•The following indication applies regardless of shape of the indicator.
Operation Indicator
MSZ-GA MICROPROCESSOR CONTROL
MSZ-GA22VA MSZ-GA25VA MUZ-GA25VA MSZ-GA35VA MUZ-GA35VA
WIRELESS REMOTE CONTROLLER
Signal transmitting section
Operation display section
OPERATE/STOP (ON/OFF) button
(This diagram shows an overall view.)
Temperature buttons
Indication of remote controller model is on back
FAN SPEED CONTROL button
OPERATION SELECT button
ECONO COOL button
RESET button
OFF-TIMER button
ON-TIMER button
TIME SET buttons FORWARD button BACKWARD button
CLOCK SET button
VANE CONTROL button
Once the operation mode is set, the same operation mode can be repeated by simply turning OPERATE/STOP (ON/OFF) button ON. Indoor unit receives the signal with a beep tone. When the system turns off, 3-minute time delay will operate to protect system from overload and compressor will not restart for 3 minutes.
INDOOR UNIT DISPLAY SECTION
Operation Indicator lamp
The operation indicator at the right side of the indoor unit indicates the operation state.
Downloaded from AC-Manual.com Manuals
22
2-1. COOL ( ) OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone. (2) Select COOL mode with OPERATION SELECT button. (3) Press TEMPERATURE buttons (TOO WARM or TOO COOL button)to select the desired temperature.
The setting range is 16 ~ 31°C
1. Thermostat control
Thermostat is ON or OFF by difference between room temperature and set temperature
Initial temperature difference Thermostat
Room temperature minus set temperature : -1.0 : or more··············································ON Room temperature minus set temperature : less than -1.0 :············································OFF
2. Indoor fan speed control
Indoor fan operates continuously at the set speed by FAN SPEED CONTROLbutton regardless of the thermostat’s OFF-ON. In AUTO the fan speed is as follows.
Initial temperature difference
Fan speed
Room temperature minus set temperature : 1.7 : or more ········································High Room temperature minus set temperature : Between 1 and 1.7 :
··································
Med.
Room temperature minus set temperature : less than 1 : ········································Low
3. Coil frost prevention
Temperature control When indoor coil thermistor detects following temperature for 90 seconds, operational frequency of compressor is controlled according to the following table.
Temperature of indoor coil thermistor
10°C or more
Operation frequency
Normal (variable)
8°C to 10°C Raise 6Hz
6°C to 8°C 3°C to 6°C
Fixed Lower 3Hz Lower 6Hz
3°C or less
Compressor is turned OFF for 5 minutes when temperature of indoor coil thermistor continues 3°C or less for 5 minutes or more.
The indoor fan maintains the actual speed of the moment.
4. Low outside temperature operation MSZ-GA25
When the ambient temperature thermistor RT65 reads 17: or less, the operation mode moves to cool operation in low out­side temperature from normal cool operation. Each outdoor actuators (compressor/ fan/ solenoid valve) are operated in the exclusive control, which is different from one of normal cool operation. Especially fan motor doesn’t operates continuously to maintain sufficient cooling capacity. (1) Outdoor fan control
Outdoor unit (compressor) operates with outdoor fan OFF basically. But any of following conditions is satisfied, the outdoor fan turns ON for about 5 seconds. a). the defrost thermistor RT61 reads 50: or more. b). the fin temperature thermistor RT64 reads 60: or more.
(2) Solenoid valve control
In low outside temperature operation solenoid valve coil is energized and solenoid valve is open.
(3) Dew drop prevention
When the ambient temperature thermistor RT65 reads -12: or less, as coil frost or dew drop from indoor unit may
occur, the compressor turns OFF with the outdoor fan ON for prevention of them.
NOTE: This control can be released by cut of the jumper line JG on the outdoor inverter P.C. board.
Be sure to cut it since user accepts that maker can’t be responsible for coil frost or dew drop from indoor unit.
(4) Outside temperature detecting control
In this mode to detect the exact outside temperature the compressor turns OFF with the outdoor fan ON for 3 minutes once 1 hour.
MSZ-GA35
If the outside temperature falls to 18°C or less during operation in COOL mode, the unit enters the low outside temperature operation mode.
<Operation> (1) If the unit enters the low outside temperature operation mode, the outside fan rotation speed gets slow down. (2) Even when the unit is in the "thermostat-off" status under the low outside temperature operation mode, the outside fan
rotation does not stop.
(3) In this mode to detect the exact outside temperature the compressor turns OFF with the outdoor fan ON for 3 minutes
once 1 hour; if the outside temperature rises over 18°C, the unit goes back to the normal COOL mode, and if the outside temperature is still 18°C or less, the unit stays in the low outside temperature operation mode.
(4) Dew drop prevention
When the ambient temperature thermistor RT65 reads -12: or less, as coil frost or dew drop from indoor unit may
occur, the compressor turns OFF with the outdoor fan ON for prevention of them.
Difference between room temperature and set temper­ature during operation.
Set temperature
-0.7 :
-1.0 :
Difference between room temperature and set tempera-
ture during operation ( T)
3 :
1.7 :
1 :
WOther protections work as well as in the normal COOL mode.
Downloaded from AC-Manual.com Manuals
23
Loading...
+ 51 hidden pages