Mitsubishi MUZ-EF35VEH - E1, MUZ-EF42VE - E1, MUZ-EF25VE - E2, MUZ-EF25VEH - E1, MUZ-EF25VEH - E2 Service Manual

...
SERVICE MANUAL
CONTENTS
1. TECHNICAL CHANGES ··································· 3
2. PART NAMES AND FUNCTIONS ····················· 4
3. SPECIFICATION ················································ 5
4. NOISE CRITERIA CURVES ······························ 7
5. OUTLINES AND DIMENSIONS ························ 8
7. REFRIGERANT SYSTEM DIAGRAM ··············11
8. PERFORMANCE CURVES ····························· 13
9. ACTUATOR CONTROL ··································· 27
10. SERVICE FUNCTIONS ···································· 28
11. TROUBLESHOOTING ····································· 29
12. DISASSEMBLY INSTRUCTIONS ···················· 46
Models
SPLIT-TYPE AIR CONDITIONERS
NOTE: RoHS compliant products have <G> mark on the spec name plate.
HFC
utilized
R410A
No. OBH590
REVISED EDITION-B
OUTDOOR UNIT
Indoor unit service manual MSZ-EF•VE Series (OBH589)
PARTS CATALOG (OBB590)
MUZ-EF25VE MUZ-EF25VEH MUZ-EF35VE MUZ-EF35VEH MUZ-EF42VE
MUZ-EF25VE
-
E1
MUZ-EF35VEH
-
E1
MUZ-EF25VE
-
E2
MUZ-EF35VEH
-
E2
MUZ-EF25VEH
-
E1
MUZ-EF42VE
-
E1
MUZ-EF25VEH
-
E2
MUZ-EF42VE
-
E2
MUZ-EF35VE
-
E1
MUZ-EF50VE
-
E1
MUZ-EF35VE
-
E2
MUZ-EF50VE
-
E2
Please void OBH590 REVISED EDITION-A.
Revision B:
• MUZ-EF25/35/42/50VE - E2 and MUZ-EF25/35VEH - E2 have been added.
2
<Preparation before the repair service>
Prepare the proper tools. Prepare the proper protectors. Provide adequate ventilation. After stopping the operation of the air conditioner, turn off the power-supply breaker and remove the power plug. Discharge the capacitor before the work involving the electric parts.
<Precautions during the repair service>
Do not perform the work involving the electric parts with wet hands. Do not pour water into the electric parts. Do not touch the refrigerant. Do not touch the hot or cold areas in the refrigeration cycle. When the repair or the inspection of the circuit needs to be done without turning off the power, exercise great caution not to
touch the live parts.
Use the specifi ed refrigerant only
Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of. Correct refrigerant is specified in the manuals and on the spec labels provided with our products. We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions.
Revision A:
• "
TROUBLESHOOTING" has been corrected (11-2,11-5).
• "Specifi cations and rated conditions of main electric parts" has been corrected. (3)
Revision B:
•MUZ-EF25/35/42/50VE - E2 and MUZ-EF25/35VEH - E2 have been added.
OBH590B
3
MUZ-EF25VE -
E1
MUZ-EF25VEH -
E1
MUZ-EF35VE -
E1
MUZ-EF35VEH -
E1
MUZ-EF42VE -
E1
MUZ-EF50VE -
E1
1. New model
MUZ-EF25VE -
E1
MUZ-EF25VE -
E2
MUZ-EF25VEH -
E1
MUZ-EF25VEH -
E2
MUZ-EF35VE -
E1
MUZ-EF35VE -
E2
MUZ-EF35VEH -
E1
MUZ-EF35VEH -
E2
MUZ-EF42VE -
E1
MUZ-EF42VE -
E2
MUZ-EF50VE -
E1
MUZ-EF50VE -
E2
1. Inverter P.C. board has been changed.
TECHNICAL CHANGES
1
OBH590B
4
Air outlet
Drain outlet
Piping
Drain hose
Air inlet
(back and side)
MUZ-EF25VE MUZ-EF25VEH MUZ-EF35VE MUZ-EF35VEH MUZ-EF42VE
PART NAMES AND FUNCTIONS
2
ACCESSORIES
MODELS
MUZ-EF25VE MUZ-EF35VE MUZ-EF42VE MUZ-EF50VE
Drain socket 1
MUZ-EF50VE
Piping
Air outlet
Drain outlet
Air inlet
(back and side)
Drain hose
OBH590B
5
Outdoor model
MUZ-EF25VE
MUZ-EF25VEH
MUZ-EF35VE
MUZ-EF35VEH
MUZ-EF42VE MUZ-EF50VE
Power supply Single phase, 230 V, 50 Hz
Capacity Rated frequency (Min.-Max.)
Cooling
kW
2.5 (1.2 - 3.4) 3.5 (1.4 - 4.0) 4.2 (0.9 - 4.6) 5.0 (1.4 - 5.4)
Heating 3.2 (1.1 - 4.2) 4.0 (1.8 - 5.5) 5.4 (1.4 - 6.3) 5.8 (1.6 - 7.5)
Breaker Capacity A 10 16
Electrical data
Power input 1 (Total)
Cooling
W
545 910 1,280 1,560
Heating 700 955 1,460 1,565
Running current 1 (Total)
Cooling
A
2.9 4.2 5.7 6.9
Heating 3.5 4.4 6.5 7.0
Power factor 1 (Total)
Cooling
%
81 94 97 98
Heating 86 94 97 97
Starting current 1 (Total) A 3.5 4.4 6.5 7.0
Coeffi cient of performance (COP)
1 (Total)
Cooling 4.59 3.85 3.28 3.21 Heating 4.57 4.19 3.70 3.71
Compressor
Model KNB073FKFMC KNB092FFAMC SNB130FGAMT SNB130FGBMT Output W 550 650 900
Current 1
Cooling
A
2.76 4.06 5.56 5.58
Heating 3.24 4.09 6.19 5.75
Refrigeration oil (Model) L 0.31 (FV50S) 0.27(FV50S) 0.35 (FV50S)
Fan motor
Model RC0J50-FA RC0J60-BD
Current 1
Cooling
A
0.24 0.29 0.30 0.84
Heating 0.27 0.28 0.28 0.93 Dimensions W × H × D mm 800 × 550 × 285 840 × 880 × 330 Weight kg 30 35 54
Special remarks
Dehumidifi cation Cooling /h 0.3 1.0 1.7 2.1
Air fl ow 1
Cooling
High
m3/h
1,806 2,868
Low 1,170 1,038 1,602
Heating
High 2,106 2,016 2,778 Med. 1,806 1,710 2,778
Low 1,452 1,326 2,124
Sound level 1
Cooling
dB(A)
47 49 50 52
Heating 48 50 51 52
Fan speed
Cooling
High
rpm
740 810 840
Low 740 490 480
Heating
High 860 900 810 Med. 740 770 810
Low 600 610 620 Fan speed regulator 3 Refrigerant fi lling capacity (R410A) kg 0.80 1.15 1.45
NOTE: Test conditions are based on ISO 5151. Cooling: Indoor Dry-bulb temperature 27°C Wet-bulb temperature 19°C Outdoor Dry-bulb temperature 35°C Heating: Indoor Dry-bulb temperature 20°C Outdoor Dry-bulb temperature 7°C Wet-bulb temperature 6°C Refrigerant piping length (one way): 5 m 1 Measured under rated operating frequency.
SPECIFICATION
3
OBH590B
6
Specifi cations and rated conditions of main electric parts
Model
Item
MUZ-EF25VE MUZ-EF25VEH MUZ-EF35VE MUZ-EF35VEH MUZ-EF42VE MUZ-EF50VE
Smoothing capacitor
(C61, C62) 620 μF 420 V
(C63) — 620 μF 420 V
Diode module (DB61) 15 A 600 V 25 A 600 V
Fuse
(F61) T20AL250V
(F701, F801, F901)
T3.15AL250V
Defrost heater (H)
230 V
130 W
230 V
130 W
——
Intelligent power module
(IC700) 15 A 600 V 20 A 600 V (IC932) 8A600V
Expansion valve coil
(LEV) 12 V DC
Reactor (L61) 18 mH 23 mH Power factor
controller
(IC820) 20A 600V
Current-limiting PTC thermistor
(PTC64, PTC65) 33 Ω
Terminal block (TB) 5 P
Relay
(X63) 3 A 250 V (X64) 20 A 250 V (X66) 3 A 250 V 3 A 250 V
(X69) 10A 230V R.V.coil (21S4) 220 - 240 V AC Heater protector (26H) Open 45°C Open 45°C
OBH590B
7
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
COOLING
FUNCTION
SPL(dB(A)) LINE
HEATING
50
NC-10
51
MUZ-EF42VE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
COOLING
FUNCTION
SPL(dB(A)) LINE
HEATING
52
NC-10
52
MUZ-EF50VE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
COOLING
FUNCTION
SPL(dB(A)) LINE
HEATING
47
48
NC-10
MUZ-EF25VE MUZ-EF25VEH
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
COOLING
FUNCTION
SPL(dB(A))
LINE
HEATING
49
50
NC-10
MUZ-EF35VE MUZ-EF35VEH
NOISE CRITERIA CURVES
4
Test conditions Cooling: Dry-bulb temperature 35°C Heating: Dry-bulb temperature 7°C Wet-bulb temperature 6°C
OUTDOOR UNIT
MICROPHONE
1 m
OBH590B
8
Unit: mm
MUZ-EF25VE MUZ-EF25VEH MUZ-EF35VE MUZ-EF35VEH MUZ-EF42VE
10
69
800
302.5
500 Bolt pitch for installation
150
22.3
Handle
550
280
164.5
99.5
170.5
23
Service panel
Service port
285
344.5
44
400
Air in
Air out
Air in
17.5
Bolt pitch for
installation
304~325
40
Liquid refrigerant pipe joint Refrigerant pipe (flared) ø6.35
Gas refrigerant pipe joint Refrigerant pipe (flared) ø9.52
43
35
2 holes 10 X 21
REQUIRED SPACE
100 mm or more
350 mm or more
200 mm or more
100 mm or more
100 mm or more
Drain hole ø42 (MUZ-EF25/35/42VE) Drain hole ø33 (MUZ-EF25/35VEH)
MUZ-EF50VE
OUTLINES AND DIMENSIONS
5
417.5
40
42
Drain hole
175
500
330
50
Air in
Air out
2-holes 10 21
360
840
109
81
880
452
Service panel
99.5
164.5
195
35
44
Liquid refrigerant pipe joint Refrigerant pipe (flared) Ø 6.35
Gas refrigerant pipe joint Refrigerant pipe (flared)
Ø 12.7
350 mm or more
100 mm or more
REQUIRED SPACE
500 mm or more
100 mm or more
500 mm or more
OBH590B
9
WIRING DIAGRAM
6
MUZ-EF25VE MUZ-EF35VE
MUZ-EF25VEH MUZ-EF35VEH
OBH590B
10
MUZ-EF42VE MUZ-EF50VE
OBH590B
11
Unit: mm
MUZ-EF25VE MUZ-EF25VEH
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve (with strainar)
Stop valve
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe ø9.52 (with heat insulator)
Refrigerant pipe ø6.35 (with heat insulator)
R.V. coil heating ON cooling OFF
Strainer #100
LEV
Ambient temperature thermistor RT65
Muffler
Capillary tube ø3.0×ø2.0×240
Outdoor heat exchanger temperature thermistor RT68
Muffler
REFRIGERANT SYSTEM DIAGRAM
7
Unit: mm
MUZ-EF35VE MUZ-EF35VEH MUZ-EF42VE
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve (with strainar)
Stop valve
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe ø9.52 (with heat insulator)
Refrigerant pipe ø6.35 (with heat insulator)
R.V. coil heating ON cooling OFF
Strainer #100
Capillary tube ø3.0×ø1.8×600(×2)
LEV
Ambient temperature thermistor RT65
Muffler
Capillary tube ø3.0×ø2.0×240
Outdoor heat exchanger temperature thermistor RT68
Muffler
OBH590B
12
MUZ-EF50VE
Unit: mm
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve
Stop valve (with service port)
Capillary tube
ø
4.0
×
ø
2.4×100 Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe
ø
12.7
(with heat insulator)
Refrigerant pipe ø6.35 (with heat insulator)
LEV
R.V. coil heating ON cooling OFF
Muffler
#100
Strainer
#100
Outdoor heat exchanger temperature thermistor RT68
Ambient temperature thermistor RT65
Strainer
#100
Muffler
Max. Length A
Max. Height
difference
B
Indoor unit
Outdoor unit
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFEFRENCE
Refrigerant piping: m Piping size O.D: mm
Max. Length A Max. Height difference B Gas Liquid
MUZ-EF25/35/42 20 12 9.52
6.35
MUZ-EF50 30 15 12.7
ADDITIONAL REFRIGERANT CHARGE (R410A: g)
Model
Outdoor unit
precharged
7 m 8 m 9 m 10 m 11 m 12 m 13 m 14 m 15 m 20 m
MUZ-EF25 800
0 30 60 90 120 150 180 210 240 390
MUZ-EF35/42 1,150
Calculation: X g = 30 g/m × (Refrigerant piping length (m) - 7)
Model
Outdoor unit
precharged
Refrigerant piping length (one way)
7 m 10 m 15 m 20 m 25 m 30 m
MUZ-EF50 1,450 0 60 160 260 360 460
Calculation: X g = 20 g/m × (Refrigerant piping length (m) – 7) NOTE: Refrigerant piping exceeding 7 m requires additional refrigerant charge according to the calculation.
OBH590B
13
The standard specifications apply only to the operation of the air conditioner under normal conditions. Since operating condi­tions vary according to the areas where these units are installed, the following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198 ~ 264 V, 50 Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature: °C [WB]
}
Cooling
(2) Indoor outlet air wet-bulb temperature: °C [WB] (3) Outdoor intake air dry-bulb temperature: °C [DB] (4) Total input: W (5) Indoor intake air dry-bulb temperature: °C [DB]
}
Heating(6) Outdoor intake air wet-bulb temperature: °C [WB] (7) Total input: W Indoor air wet and dry bulb temperature difference on the left side of the following chart shows the difference between the indoor intake air wet and dry bulb temperature and the indoor outlet air wet and dry bulb temperature for your reference at service.
How to measure the indoor air wet and dry bulb temperature difference
1. Attach at least 2 sets of wet and dry bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet and dry bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.
2. Attach at least 2 sets of wet and dry bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once (twice) to start the EMERGENCY COOL (HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
MUZ-EF25VE MUZ-EF25VEH MUZ-EF35VE MUZ-EF35VEH MUZ-EF42VE MUZ-EF50VE
INDOOR UNIT OUTDOOR UNIT
Wet and dry bulb thermometers FRONT VIEW
Wet and dry bulb thermometers BACK VIEW
Cooling capacity (
at Rated frequency)
0.9
1.0
1.1
1.2
1.3
1.4
1.5
-10-5 0 5 1015202530354045
Outdoor intake air Dry-bulb temperature(°C)
Capacity correction factors
26
24
20 18
22
Indoor intake air Wet-bulb temperature( )
13.8
12.7
11.5
10.5
9.4
8.4
7.4
MUZ-EF50VE
MUZ-EF42VE
MUZ-EF35VE
MUZ-EF35VEH
MUZ-EF25VE
MUZ-EF25VEH
Indoor air Wet-bulb temperature
difference (°C)
7.2
6.7
6.1
5.6
5.1
4.6
4.1
10.7
9.9
9.0
8.2
7.4
6.7
5.9
15.8
14.4
13.1
11.8
10.6
9.5
8.4
8-1. CAPACITY AND INPUT CURVES
PERFORMANCE CURVES8
OBH590B
14
NOTE: The above broken lines are for the heating operation without any frost and defrost operation.
0.8
0.9
1.0
1.1
1.2
1.3
-10-5 0 5 1015202530354045
Outdoor intake air Dry-bulb temperature (°C)
Input correction factors
26
24
22 20 18
Indoor intake air Wet-bulb temperature( )
Indoor air Wet-bulb temperature
difference (°C)
6.1
5.6
5.1
4.6
4.1
3.6
9.0
8.2
7.4
6.7
5.9
5.2
11.5
10.5
9.4
8.4
7.4
6.5
13.1
11.8
10.6
9.5
8.4
7.3
MUZ-EF50VE
MUZ-EF42VE
MUZ-EF35VE
MUZ-EF35VEH
MUZ-EF25VE
MUZ-EF25VEH
Total input (Cooling :
at Rated frequency
)
Indoor air Dry-bulb temperature
difference (°C)
17.6
16.2
14.9
13.5
12.2
10.8
9.5
8.1
6.8
5.4
27.8
25.7
23.5
21.4
19.2
17.1
15.0
12.8
10.7
8.6
28.7
26.5
24.3
22.1
19.9
17.7
15.5
13.3
11.1
8.8
MUZ-EF50VE
MUZ-EF42VE
MUZ-EF25VEH
MUZ-EF35VE
20.6
19.0
17.4
15.8
14.3
12.7
11.1
9.5
7.9
6.3
MUZ-EF35VEH
MUZ-EF25VE
Outdoor intake air Wet-bulb temperature (°C)
-20 -15 -10 -5 0 5 10 15
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
Heating capacity (
at Rated frequency)
Capacity correction factor
15
20 26
Indoor intake air Dry-bulb temperature ( )
Indoor air Dry-bulb temperature
difference (°C)
17.6
16.2
14.9
13.5
12.2
10.8
9.5
8.1
6.8
5.4
MUZ-EF50VE
MUZ-EF42VE
MUZ-EF35VEH
MUZ-EF25VE
20.6
19.0
17.4
15.8
14.3
12.7
11.1
9.5
7.9
6.3
MUZ-EF35VEH
MUZ-EF35VE
27.8
25.7
23.5
21.4
19.2
17.1
15.0
12.8
10.7
8.6
28.7
26.5
24.3
22.1
19.9
17.7
15.5
13.3
11.1
8.8
Outdoor intake air Wet-bulb temperature (°C)
-20 -15 -10 -5 0 5 10 15
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
Total input (Heating :
at Rated frequency
)
Input correction factor
15
20
26
Indoor intake air Dry-bulb temperature ( )
Lower limit of guaranteed operating range in heating MUZ-EF25/35/42/50VE: -15°C MUZ-EF25/35VEH : -20°C
OBH590B
15
8-2. CAPACITY AND INPUT CORRECTION BY OPERATIONAL FREQUENCY OF COMPRESSOR
0 50 100
0.0
0.5
1.0
1.5
0 50 100
0.0
0.5
1.0
1.5
0 50 100
0.0
0.5
1.0
1.5
0 50 100
0.0
0.5
1.0
1.5
2.0
0 50 100
150
0.0
0.5
1.0
1.5
050100
150
0.0
0.5
1.0
1.5
050100
150
0.0
0.5
1.0
1.5
050100
150
0.0
0.5
1.0
1.5
2.0
0 50 100
0.0
0.5
1.0
1.5
0 50 100
0.0
0.5
1.0
1.5
2.0
0 50 100
0.0
0.5
1.0
1.5
0 50 100
0
1
2
3
050100
150
0.0
0.5
1.0
1.5
0 50 100
150
0.0
0.5
1.0
1.5
2.0
0 50 100
150
0.0
0.5
1.0
1.5
0 50 100
150
0.0
0.5
1.0
1.5
2.0
MUZ-EF25VE MUZ-EF25VEH
MUZ-EF35VE MUZ-EF35VEH
Correction of Cooling capacity
Capacity correction factors
Correction of Cooling input
Input correction factors
Correction of Heating capacity
Capacity correction factors
MUZ-EF42VE
Correction of Heating input
Capacity correction factors
Correction of Cooling capacity
Capacity correction factors
Correction of Cooling input
Input correction factors
Correction of Heating capacity
Capacity correction factors
MUZ-EF50VE
Correction of Heating input
Capacity correction factors
The o per ational fr equency of compressor (Hz)
The o per ational fr equency of compressor (Hz)
The o per ational fr equency of compressor (Hz)
The o per ational fr equency of compressor (Hz)
The o per ational fr equency of compressor (Hz)
The operational frequency of compressor (Hz)
The operational frequency of compressor ( Hz)
The operational frequency of compressor ( Hz)
Correction of Cooling capacity
The operational frequency of compressor (Hz)
Capacity cor rection f actors
Correction of Cooling input
The operational frequenc y of compressor (Hz )
Input corr ection factors
Correction of Heating capacity
The operational frequenc y of compressor ( Hz)
Capacity c orr ection factor s
Correction of Heating input
The operational frequency of compressor ( Hz)
Input corr ection factors
Corr ection of C ooling capacity
The o per ational fr equency of compressor (Hz)
Capacity cor rection f actors
Corr ection of C ooling input
The operational frequency of compressor (Hz)
Input correction factors
Correction of Heating capacity
The operational frequency of compressor ( Hz)
Capacity c orr ection factor s
Correction of Heating input
The operational frequency of compressor ( Hz)
Input corr ection factors
OBH590B
16
15 20 25 30 35
0.4
0.5
0.6
0.7
0.8
0.9
15 20 25 30 35
0.3
0.4
0.5
0.6
15 20 25 30 35
0.3
0.4
0.5
0.6
0.7
15 20 25 30 35
0.3
0.4
0.5
0.6
0.7
(kgf/cm2[Gauge])(MPa [Gauge])
6
5
4
7
8
9
(kgf/cm2[Gauge])(MPa [Gauge])
4
3
5
6
(kgf/cm2[Gauge])(MPa [Gauge])
3
5
4
6
7
(kgf/cm2[Gauge])(MPa [Gaug e])
4
3
5
6
7
50 60 70
Ambient temperature(°C) Ambient humidity(%)
50 60 70
Ambient temperature(°C) Ambient humidity(%)
50 60 70
Ambient temperature(°C) Ambient humidity(%)
50 60 70
Ambient temperature(°C) Ambient humidity(%)
Outdoor low pressure
MUZ-EF25VE MUZ-EF25VEH
MUZ-EF35VE MUZ-EF35VEH
MUZ-EF42VE
MUZ-EF50VE
COOL operation
Both indoor and outdoor unit are under the same temperature/
humidity condition.
Operation: TEST RUN OPERATION (Refer to 8-3.)
8-4. OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
Dry-bulb temperature (°C) Relative humidity (%)
20 50 25 60 30 70
8-3. HOW TO OPERATE FIXED-FREQUENCY OPERATION
<Test run operation>
1. Press EMERGENCY OPERATION switch to start COOL or HEAT mode (COOL: Press once, HEAT: Press twice).
2. Test run operation starts and continues to operate for 30 minutes.
3. Compressor operates at rated frequency in COOL mode or 58 Hz in HEAT mode.
4. Indoor fan operates at High speed.
5.
After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (operation frequency of compressor varies).
6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on remote controller.
NOTE: The unit of pressure has been changed to MPa on the international system of units (SI unit system) The conversion factor is: 1 (MPa [Gauge]) = 10.2 (kgf/cm
2
[Gauge])
OBH590B
17
15 20502560307035
1.5
2.0
2.5
3.0
15 20 25 30 35
4.5
5.0
5.5
6.0
6.5
7.0
15 20 25 30 35
2.5
3.0
3.5
4.0
4.5
15 20 25 30 35
3.5
4.0
4.5
5.0
5.5
6.0
Ambient temperature(°C) Ambient humidity(%)
Ambient temperature (°C) Ambient humidity(%)
Ambient temperature (°C) Ambient humidity(%)
Outdoor current (A)Outdoor current (A)
Ambient temperature (°C) Ambient humidity(%)
Outdoor current (A)
Outdoor current (A)
MUZ-EF35VE MUZ-EF35VEHMUZ-EF25VE MUZ-EF25VEH
Outdoor unit current
MUZ-EF42VE
MUZ-EF50VE
0510
15 20 25
1.5
2.0
2.5
3.0
0510
15
20 25
3.5
4.0
4.5
5.0
5.5
0510
15 20 25
2.5
3.0
3.5
4.0
0510
15
20
25
4.0
4.5
5.0
5.5
Ambient temperature (°C)
Outdoor current (A)
Ambient temperature (°C)
Outdoor current (A)
Ambient temperature (°C)
Outdoor current (A)
Ambient temperature (°C)
Outdoor current (A)
MUZ-EF35VE MUZ-EF35VEHMUZ-EF25VE MUZ-EF25VEH
Outdoor unit current
MUZ-EF42VE
MUZ-EF50VE
Condition:
Operation: Test run operation (Refer to 8-3.)
HEAT operation
Indoor Outdoor
Dry bulb temperature (°C) 20.0 2 7 15 20.0
Wet bulb temperature (°C) 14.5 1 6 12 14.5
OBH590B
18
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-EF25VE MUZ-EF25VEH
CAPACITY: 2.5 kW SHF: 0.92 INPUT: 545 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
21 25 27 30
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 2.94 2.17 0.74 436 2.81 2.08 0.74 458 2.70 2.00 0.74 480 2.60 1.92 0.74 501
21 20 3.06 1.90 0.62 458 2.94 1.82 0.62 485 2.85 1.77 0.62 496 2.75 1.71 0.62 518
22 18 2.94 2.29 0.78 436 2.81 2.19 0.78 458 2.70 2.11 0.78 480 2.60 2.03 0.78 501
22 20 3.06 2.02 0.66 458 2.94 1.94 0.66 485 2.85 1.88 0.66 496 2.75 1.82 0.66 518
22 22 3.19 1.72 0.54 474 3.08 1.66 0.54 504 3.00 1.62 0.54 518 2.88 1.55 0.54 540
23 18 2.94 2.41 0.82 436 2.81 2.31 0.82 458 2.70 2.21 0.82 480 2.60 2.13 0.82 501
23 20 3.06 2.14 0.70 458 2.94 2.06 0.70 485 2.85 2.00 0.70 496 2.75 1.93 0.70 518
23 22 3.19 1.85 0.58 474 3.08 1.78 0.58 504 3.00 1.74 0.58 518 2.88 1.67 0.58 540
24 18 2.94 2.53 0.86 436 2.81 2.42 0.86 458 2.70 2.32 0.86 480 2.60 2.24 0.86 501
24 20 3.06 2.27 0.74 458 2.94 2.17 0.74 485 2.85 2.11 0.74 496 2.75 2.04 0.74 518
24 22 3.19 1.98 0.62 474 3.08 1.91 0.62 504 3.00 1.86 0.62 518 2.88 1.78 0.62 540
24 24 3.35 1.68 0.50 496 3.23 1.61 0.50 523 3.15 1.58 0.50 540 3.05 1.53 0.50 567
25 18 2.94 2.64 0.90 436 2.81 2.53 0.90 458 2.70 2.43 0.90 480 2.60 2.34 0.90 501
25 20 3.06 2.39 0.78 458 2.94 2.29 0.78 485 2.85 2.22 0.78 496 2.75 2.15 0.78 518
25 22 3.19 2.10 0.66 474 3.08 2.03 0.66 504 3.00 1.98 0.66 518 2.88 1.90 0.66 540
25 24 3.35 1.81 0.54 496 3.23 1.74 0.54 523 3.15 1.70 0.54 540 3.05 1.65 0.54 567
26 18 2.94 2.76 0.94 436 2.81 2.64 0.94 458 2.70 2.54 0.94 480 2.60 2.44 0.94 501
26 20 3.06 2.51 0.82 458 2.94 2.41 0.82 485 2.85 2.34 0.82 496 2.75 2.26 0.82 518
26 22 3.19 2.23 0.70 474 3.08 2.15 0.70 504 3.00 2.10 0.70 518 2.88 2.01 0.70 540
26 24 3.35 1.94 0.58 496 3.23 1.87 0.58 523 3.15 1.83 0.58 540 3.05 1.77 0.58 567
26 26 3.45 1.59 0.46 523 3.35 1.54 0.46 550 3.30 1.52 0.46 567 3.20 1.47 0.46 583
27 18 2.94 2.88 0.98 436 2.81 2.76 0.98 458 2.70 2.65 0.98 480 2.60 2.55 0.98 501
27 20 3.06 2.63 0.86 458 2.94 2.53 0.86 485 2.85 2.45 0.86 496 2.75 2.37 0.86 518
27 22 3.19 2.36 0.74 474 3.08 2.28 0.74 504 3.00 2.22 0.74 518 2.88 2.13 0.74 540
27 24 3.35 2.08 0.62 496 3.23 2.00 0.62 523 3.15 1.95 0.62 540 3.05 1.89 0.62 567
27 26 3.45 1.73 0.50 523 3.35 1.68 0.50 550 3.30 1.65 0.50 567 3.20 1.60 0.50 583
28 18 2.94 2.94 1.00 436 2.81 2.81 1.00 458 2.70 2.70 1.00 480 2.60 2.60 1.00 501
28 20 3.06 2.76 0.90 458 2.94 2.64 0.90 485 2.85 2.57 0.90 496 2.75 2.48 0.90 518
28 22 3.19 2.49 0.78 474 3.08 2.40 0.78 504 3.00 2.34 0.78 518 2.88 2.24 0.78 540
28 24 3.35 2.21 0.66 496 3.23 2.13 0.66 523 3.15 2.08 0.66 540 3.05 2.01 0.66 567
28 26 3.45 1.86 0.54 523 3.35 1.81 0.54 550 3.30 1.78 0.54 567 3.20 1.73 0.54 583
29 18 2.94 2.94 1.00 436 2.81 2.81 1.00 458 2.70 2.70 1.00 480 2.60 2.60 1.00 501
29 20 3.06 2.88 0.94 458 2.94 2.76 0.94 485 2.85 2.68 0.94 496 2.75 2.59 0.94 518
29 22 3.19 2.61 0.82 474 3.08 2.52 0.82 504 3.00 2.46 0.82 518 2.88 2.36 0.82 540
29 24 3.35 2.35 0.70 496 3.23 2.26 0.70 523 3.15 2.21 0.70 540 3.05 2.14 0.70 567
29 26 3.45 2.00 0.58 523 3.35 1.94 0.58 550 3.30 1.91 0.58 567 3.20 1.86 0.58 583
30 18 2.94 2.94 1.00 436 2.81 2.81 1.00 458 2.70 2.70 1.00 480 2.60 2.60 1.00 501
30 20 3.06 3.00 0.98 458 2.94 2.88 0.98 485 2.85 2.79 0.98 496 2.75 2.70 0.98 518
30 22 3.19 2.74 0.86 474 3.08 2.64 0.86 504 3.00 2.58 0.86 518 2.88 2.47 0.86 540
30 24 3.35 2.48 0.74 496 3.23 2.39 0.74 523 3.15 2.33 0.74 540 3.05 2.26 0.74 567
30 26 3.45 2.14 0.62 523 3.35 2.08 0.62 550 3.30 2.05 0.62 567 3.20 1.98 0.62 583
31 18 2.94 2.94 1.00 436 2.81 2.81 1.00 458 2.70 2.70 1.00 480 2.60 2.60 1.00 501
31 20 3.06 3.06 1.00 458 2.94 2.94 1.00 485 2.85 2.85 1.00 496 2.75 2.75 1.00 518
31 22 3.19 2.87 0.90 474 3.08 2.77 0.90 504 3.00 2.70 0.90 518 2.88 2.59 0.90 540
31 24 3.35 2.61 0.78 496 3.23 2.52 0.78 523 3.15 2.46 0.78 540 3.05 2.38 0.78 567
31 26 3.45 2.28 0.66 523 3.35 2.21 0.66 550 3.30 2.18 0.66 567 3.20 2.11 0.66 583
32 18 2.94 2.94 1.00 436 2.81 2.81 1.00 458 2.70 2.70 1.00 480 2.60 2.60 1.00 501
32 20 3.06 3.06 1.00 458 2.94 2.94 1.00 485 2.85 2.85 1.00 496 2.75 2.75 1.00 518
32 22 3.19 3.00 0.94 474 3.08 2.89 0.94 504 3.00 2.82 0.94 518 2.88 2.70 0.94 540
32 24 3.35 2.75 0.82 496 3.23 2.64 0.82 523 3.15 2.58 0.82 540 3.05 2.50 0.82 567
32 26 3.45 2.42 0.70 523 3.35 2.35 0.70 550 3.30 2.31 0.70 567 3.20 2.24 0.70 583
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH590B
19
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-EF25VE MUZ-EF25VEH
CAPACITY: 2.5 kW SHF: 0.92 INPUT: 545 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
35 40 46
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 2.45 1.81 0.74 534 2.25 1.67 0.74 567 2.08 1.54 0.74 589
21 20 2.58 1.60 0.62 556 2.40 1.49 0.62 583 2.23 1.38 0.62 616
22 18 2.45 1.91 0.78 534 2.25 1.76 0.78 567 2.08 1.62 0.78 589
22 20 2.58 1.70 0.66 556 2.40 1.58 0.66 583 2.23 1.47 0.66 616
22 22 2.73 1.47 0.54 578 2.55 1.38 0.54 610 2.38 1.28 0.54 632
23 18 2.45 2.01 0.82 534 2.25 1.85 0.82 567 2.08 1.70 0.82 589
23 20 2.58 1.80 0.70 556 2.40 1.68 0.70 583 2.23 1.56 0.70 616
23 22 2.73 1.58 0.58 578 2.55 1.48 0.58 610 2.38 1.38 0.58 632
24 18 2.45 2.11 0.86 534 2.25 1.94 0.86 567 2.08 1.78 0.86 589
24 20 2.58 1.91 0.74 556 2.40 1.78 0.74 583 2.23 1.65 0.74 616
24 22 2.73 1.69 0.62 578 2.55 1.58 0.62 610 2.38 1.47 0.62 632
24 24 2.88 1.44 0.50 600 2.70 1.35 0.50 627 2.55 1.28 0.50 654
25 18 2.45 2.21 0.90 534 2.25 2.03 0.90 567 2.08 1.87 0.9 589
25 20 2.58 2.01 0.78 556 2.40 1.87 0.78 583 2.23 1.74 0.78 616
25 22 2.73 1.80 0.66 578 2.55 1.68 0.66 610 2.38 1.57 0.66 632
25 24 2.88 1.55 0.54 600 2.70 1.46 0.54 627 2.55 1.38 0.54 654
26 18 2.45 2.30 0.94 534 2.25 2.12 0.94 567 2.08 1.95 0.94 589
26 20 2.58 2.11 0.82 556 2.40 1.97 0.82 583 2.23 1.82 0.82 616
26 22 2.73 1.91 0.70 578 2.55 1.79 0.70 610 2.38 1.66 0.70 632
26 24 2.88 1.67 0.58 600 2.70 1.57 0.58 627 2.55 1.48 0.58 654
26 26 3.03 1.39 0.46 621 2.85 1.31 0.46 649 2.68 1.23 0.46 676
27 18 2.45 2.40 0.98 534 2.25 2.21 0.98 567 2.08 2.03 0.98 589
27 20 2.58 2.21 0.86 556 2.40 2.06 0.86 583 2.23 1.91 0.86 616
27 22 2.73 2.02 0.74 578 2.55 1.89 0.74 610 2.38 1.76 0.74 632
27 24 2.88 1.78 0.62 600 2.70 1.67 0.62 627 2.55 1.58 0.62 654
27 26 3.03 1.51 0.50 621 2.85 1.43 0.50 649 2.68 1.34 0.50 676
28 18 2.45 2.45 1.00 534 2.25 2.25 1.00 567 2.08 2.08 1.00 589
28 20 2.58 2.32 0.90 556 2.40 2.16 0.90 583 2.23 2.00 0.90 616
28 22 2.73 2.13 0.78 578 2.55 1.99 0.78 610 2.38 1.85 0.78 632
28 24 2.88 1.90 0.66 600 2.70 1.78 0.66 627 2.55 1.68 0.66 654
28 26 3.03 1.63 0.54 621 2.85 1.54 0.54 649 2.68 1.44 0.54 676
29 18 2.45 2.45 1.00 534 2.25 2.25 1.00 567 2.08 2.08 1.00 589
29 20 2.58 2.42 0.94 556 2.40 2.26 0.94 583 2.23 2.09 0.94 616
29 22 2.73 2.23 0.82 578 2.55 2.09 0.82 610 2.38 1.95 0.82 632
29 24 2.88 2.01 0.70 600 2.70 1.89 0.70 627 2.55 1.79 0.70 654
29 26 3.03 1.75 0.58 621 2.85 1.65 0.58 649 2.68 1.55 0.58 676
30 18 2.45 2.45 1.00 534 2.25 2.25 1.00 567 2.08 2.08 1.00 589
30 20 2.58 2.52 0.98 556 2.40 2.35 0.98 583 2.23 2.18 0.98 616
30 22 2.73 2.34 0.86 578 2.55 2.19 0.86 610 2.38 2.04 0.86 632
30 24 2.88 2.13 0.74 600 2.70 2.00 0.74 627 2.55 1.89 0.74 654
30 26 3.03 1.88 0.62 621 2.85 1.77 0.62 649 2.68 1.66 0.62 676
31 18 2.45 2.45 1.00 534 2.25 2.25 1.00 567 2.08 2.08 1.00 589
31 20 2.58 2.58 1.00 556 2.40 2.40 1.00 583 2.23 2.23 1.00 616
31 22 2.73 2.45 0.90 578 2.55 2.30 0.90 610 2.38 2.14 0.90 632
31 24 2.88 2.24 0.78 600 2.70 2.11 0.78 627 2.55 1.99 0.78 654
31 26 3.03 2.00 0.66 621 2.85 1.88 0.66 649 2.68 1.77 0.66 676
32 18 2.45 2.45 1.00 534 2.25 2.25 1.00 567 2.08 2.08 1.00 589
32 20 2.58 2.58 1.00 556 2.40 2.40 1.00 583 2.23 2.23 1.00 616
32 22 2.73 2.56 0.94 578 2.55 2.40 0.94 610 2.38 2.23 0.94 632
32 24 2.88 2.36 0.82 600 2.70 2.21 0.82 627 2.55 2.09 0.82 654
32 26 3.03 2.12 0.70 621 2.85 2.00 0.70 649 2.68 1.87 0.70 676
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH590B
20
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-EF35VE MUZ-EF35VEH
CAPACITY: 3.5 kW SHF: 0.80 INPUT: 910 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
21 25 27 30
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 4.11 2.55 0.62 728 3.94 2.44 0.62 764 3.78 2.34 0.62 801 3.64 2.26 0.62 837
21 20 4.29 2.14 0.50 764 4.11 2.06 0.50 810 3.99 2.00 0.50 828 3.85 1.93 0.50 865
22 18 4.11 2.71 0.66 728 3.94 2.60 0.66 764 3.78 2.49 0.66 801 3.64 2.40 0.66 837
22 20 4.29 2.32 0.54 764 4.11 2.22 0.54 810 3.99 2.15 0.54 828 3.85 2.08 0.54 865
22 22 4.46 1.87 0.42 792 4.31 1.81 0.42 842 4.20 1.76 0.42 865 4.03 1.69 0.42 901
23 18 4.11 2.88 0.70 728 3.94 2.76 0.70 764 3.78 2.65 0.70 801 3.64 2.55 0.70 837
23 20 4.29 2.49 0.58 764 4.11 2.39 0.58 810 3.99 2.31 0.58 828 3.85 2.23 0.58 865
23 22 4.46 2.05 0.46 792 4.31 1.98 0.46 842 4.20 1.93 0.46 865 4.03 1.85 0.46 901
24 18 4.11 3.04 0.74 728 3.94 2.91 0.74 764 3.78 2.80 0.74 801 3.64 2.69 0.74 837
24 20 4.29 2.66 0.62 764 4.11 2.55 0.62 810 3.99 2.47 0.62 828 3.85 2.39 0.62 865
24 22 4.46 2.23 0.50 792 4.31 2.15 0.50 842 4.20 2.10 0.50 865 4.03 2.01 0.50 901
24 24 4.69 1.78 0.38 828 4.52 1.72 0.38 874 4.41 1.68 0.38 901 4.27 1.62 0.38 946
25 18 4.11 3.21 0.78 728 3.94 3.07 0.78 764 3.78 2.95 0.78 801 3.64 2.84 0.78 837
25 20 4.29 2.83 0.66 764 4.11 2.71 0.66 810 3.99 2.63 0.66 828 3.85 2.54 0.66 865
25 22 4.46 2.41 0.54 792 4.31 2.32 0.54 842 4.20 2.27 0.54 865 4.03 2.17 0.54 901
25 24 4.69 1.97 0.42 828 4.52 1.90 0.42 874 4.41 1.85 0.42 901 4.27 1.79 0.42 946
26 18 4.11 3.37 0.82 728 3.94 3.23 0.82 764 3.78 3.10 0.82 801 3.64 2.98 0.82 837
26 20 4.29 3.00 0.70 764 4.11 2.88 0.70 810 3.99 2.79 0.70 828 3.85 2.70 0.70 865
26 22 4.46 2.59 0.58 792 4.31 2.50 0.58 842 4.20 2.44 0.58 865 4.03 2.33 0.58 901
26 24 4.69 2.16 0.46 828 4.52 2.08 0.46 874 4.41 2.03 0.46 901 4.27 1.96 0.46 946
26 26 4.83 1.64 0.34 874 4.69 1.59 0.34 919 4.62 1.57 0.34 946 4.48 1.52 0.34 974
27 18 4.11 3.54 0.86 728 3.94 3.39 0.86 764 3.78 3.25 0.86 801 3.64 3.13 0.86 837
27 20 4.29 3.17 0.74 764 4.11 3.04 0.74 810 3.99 2.95 0.74 828 3.85 2.85 0.74 865
27 22 4.46 2.77 0.62 792 4.31 2.67 0.62 842 4.20 2.60 0.62 865 4.03 2.50 0.62 901
27 24 4.69 2.35 0.50 828 4.52 2.26 0.50 874 4.41 2.21 0.50 901 4.27 2.14 0.50 946
27 26 4.83 1.84 0.38 874 4.69 1.78 0.38 919 4.62 1.76 0.38 946 4.48 1.70 0.38 974
28 18 4.11 3.70 0.90 728 3.94 3.54 0.90 764 3.78 3.40 0.90 801 3.64 3.28 0.90 837
28 20 4.29 3.34 0.78 764 4.11 3.21 0.78 810 3.99 3.11 0.78 828 3.85 3.00 0.78 865
28 22 4.46 2.95 0.66 792 4.31 2.84 0.66 842 4.20 2.77 0.66 865 4.03 2.66 0.66 901
28 24 4.69 2.53 0.54 828 4.52 2.44 0.54 874 4.41 2.38 0.54 901 4.27 2.31 0.54 946
28 26 4.83 2.03 0.42 874 4.69 1.97 0.42 919 4.62 1.94 0.42 946 4.48 1.88 0.42 974
29 18 4.11 3.87 0.94 728 3.94 3.70 0.94 764 3.78 3.55 0.94 801 3.64 3.42 0.94 837
29 20 4.29 3.52 0.82 764 4.11 3.37 0.82 810 3.99 3.27 0.82 828 3.85 3.16 0.82 865
29 22 4.46 3.12 0.70 792 4.31 3.01 0.70 842 4.20 2.94 0.70 865 4.03 2.82 0.70 901
29 24 4.69 2.72 0.58 828 4.52 2.62 0.58 874 4.41 2.56 0.58 901 4.27 2.48 0.58 946
29 26 4.83 2.22 0.46 874 4.69 2.16 0.46 919 4.62 2.13 0.46 946 4.48 2.06 0.46 974
30 18 4.11 4.03 0.98 728 3.94 3.86 0.98 764 3.78 3.70 0.98 801 3.64 3.57 0.98 837
30 20 4.29 3.69 0.86 764 4.11 3.54 0.86 810 3.99 3.43 0.86 828 3.85 3.31 0.86 865
30 22 4.46 3.30 0.74 792 4.31 3.19 0.74 842 4.20 3.11 0.74 865 4.03 2.98 0.74 901
30 24 4.69 2.91 0.62 828 4.52 2.80 0.62 874 4.41 2.73 0.62 901 4.27 2.65 0.62 946
30 26 4.83 2.42 0.50 874 4.69 2.35 0.50 919 4.62 2.31 0.50 946 4.48 2.24 0.50 974
31 18 4.11 4.11 1.00 728 3.94 3.94 1.00 764 3.78 3.78 1.00 801 3.64 3.64 1.00 837
31 20 4.29 3.86 0.90 764 4.11 3.70 0.90 810 3.99 3.59 0.90 828 3.85 3.47 0.90 865
31 22 4.46 3.48 0.78 792 4.31 3.36 0.78 842 4.20 3.28 0.78 865 4.03 3.14 0.78 901
31 24 4.69 3.10 0.66 828 4.52 2.98 0.66 874 4.41 2.91 0.66 901 4.27 2.82 0.66 946
31 26 4.83 2.61 0.54 874 4.69 2.53 0.54 919 4.62 2.49 0.54 946 4.48 2.42 0.54 974
32 18 4.11 4.11 1.00 728 3.94 3.94 1.00 764 3.78 3.78 1.00 801 3.64 3.64 1.00 837
32 20 4.29 4.03 0.94 764 4.11 3.87 0.94 810 3.99 3.75 0.94 828 3.85 3.62 0.94 865
32 22 4.46 3.66 0.82 792 4.31 3.53 0.82 842 4.20 3.44 0.82 865 4.03 3.30 0.82 901
32 24 4.69 3.28 0.70 828 4.52 3.16 0.70 874 4.41 3.09 0.70 901 4.27 2.99 0.70 946
32 26 4.83 2.80 0.58 874 4.69 2.72 0.58 919 4.62 2.68 0.58 946 4.48 2.60 0.58 974
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH590B
21
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-EF35VE MUZ-EF35VEH
CAPACITY: 3.5 kW SHF: 0.80 INPUT: 910 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
35 40 46
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 3.43 2.13 0.62 892 3.15 1.95 0.62 946 2.91 1.80 0.62 983
21 20 3.61 1.80 0.50 928 3.36 1.68 0.50 974 3.12 1.56 0.50 1028
22 18 3.43 2.26 0.66 892 3.15 2.08 0.66 946 2.91 1.92 0.66 983
22 20 3.61 1.95 0.54 928 3.36 1.81 0.54 974 3.12 1.68 0.54 1028
22 22 3.82 1.60 0.42 965 3.57 1.50 0.42 1019 3.33 1.40 0.42 1056
23 18 3.43 2.40 0.70 892 3.15 2.21 0.70 946 2.91 2.03 0.70 983
23 20 3.61 2.09 0.58 928 3.36 1.95 0.58 974 3.12 1.81 0.58 1028
23 22 3.82 1.75 0.46 965 3.57 1.64 0.46 1019 3.33 1.53 0.46 1056
24 18 3.43 2.54 0.74 892 3.15 2.33 0.74 946 2.91 2.15 0.74 983
24 20 3.61 2.24 0.62 928 3.36 2.08 0.62 974 3.12 1.93 0.62 1028
24 22 3.82 1.91 0.50 965 3.57 1.79 0.50 1019 3.33 1.66 0.50 1056
24 24 4.03 1.53 0.38 1001 3.78 1.44 0.38 1047 3.57 1.36 0.38 1092
25 18 3.43 2.68 0.78 892 3.15 2.46 0.78 946 2.91 2.27 0.78 983
25 20 3.61 2.38 0.66 928 3.36 2.22 0.66 974 3.12 2.06 0.66 1028
25 22 3.82 2.06 0.54 965 3.57 1.93 0.54 1019 3.33 1.80 0.54 1056
25 24 4.03 1.69 0.42 1001 3.78 1.59 0.42 1047 3.57 1.50 0.42 1092
26 18 3.43 2.81 0.82 892 3.15 2.58 0.82 946 2.91 2.38 0.82 983
26 20 3.61 2.52 0.70 928 3.36 2.35 0.70 974 3.12 2.18 0.70 1028
26 22 3.82 2.21 0.58 965 3.57 2.07 0.58 1019 3.33 1.93 0.58 1056
26 24 4.03 1.85 0.46 1001 3.78 1.74 0.46 1047 3.57 1.64 0.46 1092
26 26 4.24 1.44 0.34 1037 3.99 1.36 0.34 1083 3.75 1.27 0.34 1128
27 18 3.43 2.95 0.86 892 3.15 2.71 0.86 946 2.91 2.50 0.86 983
27 20 3.61 2.67 0.74 928 3.36 2.49 0.74 974 3.12 2.31 0.74 1028
27 22 3.82 2.37 0.62 965 3.57 2.21 0.62 1019 3.33 2.06 0.62 1056
27 24 4.03 2.01 0.50 1001 3.78 1.89 0.50 1047 3.57 1.79 0.50 1092
27 26 4.24 1.61 0.38 1037 3.99 1.52 0.38 1083 3.75 1.42 0.38 1128
28 18 3.43 3.09 0.90 892 3.15 2.84 0.90 946 2.91 2.61 0.90 983
28 20 3.61 2.81 0.78 928 3.36 2.62 0.78 974 3.12 2.43 0.78 1028
28 22 3.82 2.52 0.66 965 3.57 2.36 0.66 1019 3.33 2.19 0.66 1056
28 24 4.03 2.17 0.54 1001 3.78 2.04 0.54 1047 3.57 1.93 0.54 1092
28 26 4.24 1.78 0.42 1037 3.99 1.68 0.42 1083 3.75 1.57 0.42 1128
29 18 3.43 3.22 0.94 892 3.15 2.96 0.94 946 2.91 2.73 0.94 983
29 20 3.61 2.96 0.82 928 3.36 2.76 0.82 974 3.12 2.55 0.82 1028
29 22 3.82 2.67 0.70 965 3.57 2.50 0.70 1019 3.33 2.33 0.70 1056
29 24 4.03 2.33 0.58 1001 3.78 2.19 0.58 1047 3.57 2.07 0.58 1092
29 26 4.24 1.95 0.46 1037 3.99 1.84 0.46 1083 3.75 1.72 0.46 1128
30 18 3.43 3.36 0.98 892 3.15 3.09 0.98 946 2.91 2.85 0.98 983
30 20 3.61 3.10 0.86 928 3.36 2.89 0.86 974 3.12 2.68 0.86 1028
30 22 3.82 2.82 0.74 965 3.57 2.64 0.74 1019 3.33 2.46 0.74 1056
30 24 4.03 2.50 0.62 1001 3.78 2.34 0.62 1047 3.57 2.21 0.62 1092
30 26 4.24 2.12 0.50 1037 3.99 2.00 0.50 1083 3.75 1.87 0.50 1128
31 18 3.43 3.43 1.00 892 3.15 3.15 1.00 946 2.91 2.91 1.00 983
31 20 3.61 3.24 0.90 928 3.36 3.02 0.90 974 3.12 2.80 0.90 1028
31 22 3.82 2.98 0.78 965 3.57 2.78 0.78 1019 3.33 2.59 0.78 1056
31 24 4.03 2.66 0.66 1001 3.78 2.49 0.66 1047 3.57 2.36 0.66 1092
31 26 4.24 2.29 0.54 1037 3.99 2.15 0.54 1083 3.75 2.02 0.54 1128
32 18 3.43 3.43 1.00 892 3.15 3.15 1.00 946 2.91 2.91 1.00 983
32 20 3.61 3.39 0.94 928 3.36 3.16 0.94 974 3.12 2.93 0.94 1028
32 22 3.82 3.13 0.82 965 3.57 2.93 0.82 1019 3.33 2.73 0.82 1056
32 24 4.03 2.82 0.70 1001 3.78 2.65 0.70 1047 3.57 2.50 0.70 1092
32 26 4.24 2.46 0.58 1037 3.99 2.31 0.58 1083 3.75 2.17 0.58 1128
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH590B
22
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-EF42VE
CAPACITY: 4.2 kW SHF: 0.72 INPUT: 1280 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
21 25 27 30
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 4.94 2.66 0.54 1024 4.73 2.55 0.54 1075 4.54 2.45 0.54 1126 4.37 2.36 0.54 1178
21 20 5.15 2.16 0.42 1075 4.94 2.07 0.42 1139 4.79 2.01 0.42 1165 4.62 1.94 0.42 1216
22 18 4.94 2.86 0.58 1024 4.73 2.74 0.58 1075 4.54 2.63 0.58 1126 4.37 2.53 0.58 1178
22 20 5.15 2.37 0.46 1075 4.94 2.27 0.46 1139 4.79 2.20 0.46 1165 4.62 2.13 0.46 1216
22 22 5.36 1.82 0.34 1114 5.17 1.76 0.34 1184 5.04 1.71 0.34 1216 4.83 1.64 0.34 1267
23 18 4.94 3.06 0.62 1024 4.73 2.93 0.62 1075 4.54 2.81 0.62 1126 4.37 2.71 0.62 1178
23 20 5.15 2.57 0.50 1075 4.94 2.47 0.50 1139 4.79 2.39 0.50 1165 4.62 2.31 0.50 1216
23 22 5.36 2.03 0.38 1114 5.17 1.96 0.38 1184 5.04 1.92 0.38 1216 4.83 1.84 0.38 1267
24 18 4.94 3.26 0.66 1024 4.73 3.12 0.66 1075 4.54 2.99 0.66 1126 4.37 2.88 0.66 1178
24 20 5.15 2.78 0.54 1075 4.94 2.66 0.54 1139 4.79 2.59 0.54 1165 4.62 2.49 0.54 1216
24 22 5.36 2.25 0.42 1114 5.17 2.17 0.42 1184 5.04 2.12 0.42 1216 4.83 2.03 0.42 1267
24 24 5.63 1.69 0.30 1165 5.42 1.63 0.30 1229 5.29 1.59 0.30 1267 5.12 1.54 0.30 1331
25 18 4.94 3.45 0.70 1024 4.73 3.31 0.70 1075 4.54 3.18 0.70 1126 4.37 3.06 0.70 1178
25 20 5.15 2.98 0.58 1075 4.94 2.86 0.58 1139 4.79 2.78 0.58 1165 4.62 2.68 0.58 1216
25 22 5.36 2.46 0.46 1114 5.17 2.38 0.46 1184 5.04 2.32 0.46 1216 4.83 2.22 0.46 1267
25 24 5.63 1.91 0.34 1165 5.42 1.84 0.34 1229 5.29 1.80 0.34 1267 5.12 1.74 0.34 1331
26 18 4.94 3.65 0.74 1024 4.73 3.50 0.74 1075 4.54 3.36 0.74 1126 4.37 3.23 0.74 1178
26 20 5.15 3.19 0.62 1075 4.94 3.06 0.62 1139 4.79 2.97 0.62 1165 4.62 2.86 0.62 1216
26 22 5.36 2.68 0.50 1114 5.17 2.58 0.50 1184 5.04 2.52 0.50 1216 4.83 2.42 0.50 1267
26 24 5.63 2.14 0.38 1165 5.42 2.06 0.38 1229 5.29 2.01 0.38 1267 5.12 1.95 0.38 1331
26 26 5.80 1.51 0.26 1229 5.63 1.46 0.26 1293 5.54 1.44 0.26 1331 5.38 1.40 0.26 1370
27 18 4.94 3.85 0.78 1024 4.73 3.69 0.78 1075 4.54 3.54 0.78 1126 4.37 3.41 0.78 1178
27 20 5.15 3.40 0.66 1075 4.94 3.26 0.66 1139 4.79 3.16 0.66 1165 4.62 3.05 0.66 1216
27 22 5.36 2.89 0.54 1114 5.17 2.79 0.54 1184 5.04 2.72 0.54 1216 4.83 2.61 0.54 1267
27 24 5.63 2.36 0.42 1165 5.42 2.28 0.42 1229 5.29 2.22 0.42 1267 5.12 2.15 0.42 1331
27 26 5.80 1.74 0.30 1229 5.63 1.69 0.30 1293 5.54 1.66 0.30 1331 5.38 1.61 0.30 1370
28 18 4.94 4.05 0.82 1024 4.73 3.87 0.82 1075 4.54 3.72 0.82 1126 4.37 3.58 0.82 1178
28 20 5.15 3.60 0.70 1075 4.94 3.45 0.70 1139 4.79 3.35 0.70 1165 4.62 3.23 0.70 1216
28 22 5.36 3.11 0.58 1114 5.17 3.00 0.58 1184 5.04 2.92 0.58 1216 4.83 2.80 0.58 1267
28 24 5.63 2.59 0.46 1165 5.42 2.49 0.46 1229 5.29 2.43 0.46 1267 5.12 2.36 0.46 1331
28 26 5.80 1.97 0.34 1229 5.63 1.91 0.34 1293 5.54 1.88 0.34 1331 5.38 1.83 0.34 1370
29 18 4.94 4.24 0.86 1024 4.73 4.06 0.86 1075 4.54 3.90 0.86 1126 4.37 3.76 0.86 1178
29 20 5.15 3.81 0.74 1075 4.94 3.65 0.74 1139 4.79 3.54 0.74 1165 4.62 3.42 0.74 1216
29 22 5.36 3.32 0.62 1114 5.17 3.20 0.62 1184 5.04 3.12 0.62 1216 4.83 2.99 0.62 1267
29 24 5.63 2.81 0.50 1165 5.42 2.71 0.50 1229 5.29 2.65 0.50 1267 5.12 2.56 0.50 1331
29 26 5.80 2.20 0.38 1229 5.63 2.14 0.38 1293 5.54 2.11 0.38 1331 5.38 2.04 0.38 1370
30 18 4.94 4.44 0.90 1024 4.73 4.25 0.90 1075 4.54 4.08 0.90 1126 4.37 3.93 0.90 1178
30 20 5.15 4.01 0.78 1075 4.94 3.85 0.78 1139 4.79 3.73 0.78 1165 4.62 3.60 0.78 1216
30 22 5.36 3.53 0.66 1114 5.17 3.41 0.66 1184 5.04 3.33 0.66 1216 4.83 3.19 0.66 1267
30 24 5.63 3.04 0.54 1165 5.42 2.93 0.54 1229 5.29 2.86 0.54 1267 5.12 2.77 0.54 1331
30 26 5.80 2.43 0.42 1229 5.63 2.36 0.42 1293 5.54 2.33 0.42 1331 5.38 2.26 0.42 1370
31 18 4.94 4.64 0.94 1024 4.73 4.44 0.94 1075 4.54 4.26 0.94 1126 4.37 4.11 0.94 1178
31 20 5.15 4.22 0.82 1075 4.94 4.05 0.82 1139 4.79 3.93 0.82 1165 4.62 3.79 0.82 1216
31 22 5.36 3.75 0.70 1114 5.17 3.62 0.70 1184 5.04 3.53 0.70 1216 4.83 3.38 0.70 1267
31 24 5.63 3.26 0.58 1165 5.42 3.14 0.58 1229 5.29 3.07 0.58 1267 5.12 2.97 0.58 1331
31 26 5.80 2.67 0.46 1229 5.63 2.59 0.46 1293 5.54 2.55 0.46 1331 5.38 2.47 0.46 1370
32 18 4.94 4.84 0.98 1024 4.73 4.63 0.98 1075 4.54 4.45 0.98 1126 4.37 4.28 0.98 1178
32 20 5.15 4.42 0.86 1075 4.94 4.24 0.86 1139 4.79 4.12 0.86 1165 4.62 3.97 0.86 1216
32 22 5.36 3.96 0.74 1114 5.17 3.82 0.74 1184 5.04 3.73 0.74 1216 4.83 3.57 0.74 1267
32 24 5.63 3.49 0.62 1165 5.42 3.36 0.62 1229 5.29 3.28 0.62 1267 5.12 3.18 0.62 1331
32 26 5.80 2.90 0.50 1229 5.63 2.81 0.50 1293 5.54 2.77 0.50 1331 5.38 2.69 0.50 1370
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH590B
23
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-EF42VE
CAPACITY: 4.2 kW SHF: 0.72 INPUT: 1280 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
35 40 46
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 4.12 2.22 0.54 1254 3.78 2.04 0.54 1331 3.49 1.88 0.54 1382
21 20 4.33 1.82 0.42 1306 4.03 1.69 0.42 1370 3.74 1.57 0.42 1446
22 18 4.12 2.39 0.58 1254 3.78 2.19 0.58 1331 3.49 2.02 0.58 1382
22 20 4.33 1.99 0.46 1306 4.03 1.85 0.46 1370 3.74 1.72 0.46 1446
22 22 4.58 1.56 0.34 1357 4.28 1.46 0.34 1434 3.99 1.36 0.34 1485
23 18 4.12 2.55 0.62 1254 3.78 2.34 0.62 1331 3.49 2.16 0.62 1382
23 20 4.33 2.16 0.50 1306 4.03 2.02 0.50 1370 3.74 1.87 0.50 1446
23 22 4.58 1.74 0.38 1357 4.28 1.63 0.38 1434 3.99 1.52 0.38 1485
24 18 4.12 2.72 0.66 1254 3.78 2.49 0.66 1331 3.49 2.30 0.66 1382
24 20 4.33 2.34 0.54 1306 4.03 2.18 0.54 1370 3.74 2.02 0.54 1446
24 22 4.58 1.92 0.42 1357 4.28 1.80 0.42 1434 3.99 1.68 0.42 1485
24 24 4.83 1.45 0.30 1408 4.54 1.36 0.30 1472 4.28 1.29 0.30 1536
25 18 4.12 2.88 0.70 1254 3.78 2.65 0.70 1331 3.49 2.44 0.7 1382
25 20 4.33 2.51 0.58 1306 4.03 2.34 0.58 1370 3.74 2.17 0.58 1446
25 22 4.58 2.11 0.46 1357 4.28 1.97 0.46 1434 3.99 1.84 0.46 1485
25 24 4.83 1.64 0.34 1408 4.54 1.54 0.34 1472 4.28 1.46 0.34 1536
26 18 4.12 3.05 0.74 1254 3.78 2.80 0.74 1331 3.49 2.58 0.74 1382
26 20 4.33 2.68 0.62 1306 4.03 2.50 0.62 1370 3.74 2.32 0.62 1446
26 22 4.58 2.29 0.50 1357 4.28 2.14 0.50 1434 3.99 2.00 0.50 1485
26 24 4.83 1.84 0.38 1408 4.54 1.72 0.38 1472 4.28 1.63 0.38 1536
26 26 5.08 1.32 0.26 1459 4.79 1.24 0.26 1523 4.49 1.17 0.26 1587
27 18 4.12 3.21 0.78 1254 3.78 2.95 0.78 1331 3.49 2.72 0.78 1382
27 20 4.33 2.86 0.66 1306 4.03 2.66 0.66 1370 3.74 2.47 0.66 1446
27 22 4.58 2.47 0.54 1357 4.28 2.31 0.54 1434 3.99 2.15 0.54 1485
27 24 4.83 2.03 0.42 1408 4.54 1.91 0.42 1472 4.28 1.80 0.42 1536
27 26 5.08 1.52 0.30 1459 4.79 1.44 0.30 1523 4.49 1.35 0.30 1587
28 18 4.12 3.38 0.82 1254 3.78 3.10 0.82 1331 3.49 2.86 0.82 1382
28 20 4.33 3.03 0.70 1306 4.03 2.82 0.70 1370 3.74 2.62 0.70 1446
28 22 4.58 2.66 0.58 1357 4.28 2.48 0.58 1434 3.99 2.31 0.58 1485
28 24 4.83 2.22 0.46 1408 4.54 2.09 0.46 1472 4.28 1.97 0.46 1536
28 26 5.08 1.73 0.34 1459 4.79 1.63 0.34 1523 4.49 1.53 0.34 1587
29 18 4.12 3.54 0.86 1254 3.78 3.25 0.86 1331 3.49 3.00 0.86 1382
29 20 4.33 3.20 0.74 1306 4.03 2.98 0.74 1370 3.74 2.77 0.74 1446
29 22 4.58 2.84 0.62 1357 4.28 2.66 0.62 1434 3.99 2.47 0.62 1485
29 24 4.83 2.42 0.50 1408 4.54 2.27 0.50 1472 4.28 2.14 0.50 1536
29 26 5.08 1.93 0.38 1459 4.79 1.82 0.38 1523 4.49 1.71 0.38 1587
30 18 4.12 3.70 0.90 1254 3.78 3.40 0.90 1331 3.49 3.14 0.90 1382
30 20 4.33 3.37 0.78 1306 4.03 3.14 0.78 1370 3.74 2.92 0.78 1446
30 22 4.58 3.02 0.66 1357 4.28 2.83 0.66 1434 3.99 2.63 0.66 1485
30 24 4.83 2.61 0.54 1408 4.54 2.45 0.54 1472 4.28 2.31 0.54 1536
30 26 5.08 2.13 0.42 1459 4.79 2.01 0.42 1523 4.49 1.89 0.42 1587
31 18 4.12 3.87 0.94 1254 3.78 3.55 0.94 1331 3.49 3.28 0.94 1382
31 20 4.33 3.55 0.82 1306 4.03 3.31 0.82 1370 3.74 3.07 0.82 1446
31 22 4.58 3.20 0.70 1357 4.28 3.00 0.70 1434 3.99 2.79 0.70 1485
31 24 4.83 2.80 0.58 1408 4.54 2.63 0.58 1472 4.28 2.48 0.58 1536
31 26 5.08 2.34 0.46 1459 4.79 2.20 0.46 1523 4.49 2.07 0.46 1587
32 18 4.12 4.03 0.98 1254 3.78 3.70 0.98 1331 3.49 3.42 0.98 1382
32 20 4.33 3.72 0.86 1306 4.03 3.47 0.86 1370 3.74 3.21 0.86 1446
32 22 4.58 3.39 0.74 1357 4.28 3.17 0.74 1434 3.99 2.95 0.74 1485
32 24 4.83 2.99 0.62 1408 4.54 2.81 0.62 1472 4.28 2.66 0.62 1536
32 26 5.08 2.54 0.50 1459 4.79 2.39 0.50 1523 4.49 2.25 0.50 1587
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH590B
24
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-EF50VE
CAPACITY: 5.0 kW SHF: 0.71 INPUT: 1560 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
21 25 27 30
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 5.88 3.11 0.53 1248 5.63 2.98 0.53 1310 5.40 2.86 0.53 1373 5.20 2.76 0.53 1435
21 20 6.13 2.51 0.41 1310 5.88 2.41 0.41 1388 5.70 2.34 0.41 1420 5.50 2.26 0.41 1482
22 18 5.88 3.35 0.57 1248 5.63 3.21 0.57 1310 5.40 3.08 0.57 1373 5.20 2.96 0.57 1435
22 20 6.13 2.76 0.45 1310 5.88 2.64 0.45 1388 5.70 2.57 0.45 1420 5.50 2.48 0.45 1482
22 22 6.38 2.10 0.33 1357 6.15 2.03 0.33 1443 6.00 1.98 0.33 1482 5.75 1.90 0.33 1544
23 18 5.88 3.58 0.61 1248 5.63 3.43 0.61 1310 5.40 3.29 0.61 1373 5.20 3.17 0.61 1435
23 20 6.13 3.00 0.49 1310 5.88 2.88 0.49 1388 5.70 2.79 0.49 1420 5.50 2.70 0.49 1482
23 22 6.38 2.36 0.37 1357 6.15 2.28 0.37 1443 6.00 2.22 0.37 1482 5.75 2.13 0.37 1544
24 18 5.88 3.82 0.65 1248 5.63 3.66 0.65 1310 5.40 3.51 0.65 1373 5.20 3.38 0.65 1435
24 20 6.13 3.25 0.53 1310 5.88 3.11 0.53 1388 5.70 3.02 0.53 1420 5.50 2.92 0.53 1482
24 22 6.38 2.61 0.41 1357 6.15 2.52 0.41 1443 6.00 2.46 0.41 1482 5.75 2.36 0.41 1544
24 24 6.70 1.94 0.29 1420 6.45 1.87 0.29 1498 6.30 1.83 0.29 1544 6.10 1.77 0.29 1622
25 18 5.88 4.05 0.69 1248 5.63 3.88 0.69 1310 5.40 3.73 0.69 1373 5.20 3.59 0.69 1435
25 20 6.13 3.49 0.57 1310 5.88 3.35 0.57 1388 5.70 3.25 0.57 1420 5.50 3.14 0.57 1482
25 22 6.38 2.87 0.45 1357 6.15 2.77 0.45 1443 6.00 2.70 0.45 1482 5.75 2.59 0.45 1544
25 24 6.70 2.21 0.33 1420 6.45 2.13 0.33 1498 6.30 2.08 0.33 1544 6.10 2.01 0.33 1622
26 18 5.88 4.29 0.73 1248 5.63 4.11 0.73 1310 5.40 3.94 0.73 1373 5.20 3.80 0.73 1435
26 20 6.13 3.74 0.61 1310 5.88 3.58 0.61 1388 5.70 3.48 0.61 1420 5.50 3.36 0.61 1482
26 22 6.38 3.12 0.49 1357 6.15 3.01 0.49 1443 6.00 2.94 0.49 1482 5.75 2.82 0.49 1544
26 24 6.70 2.48 0.37 1420 6.45 2.39 0.37 1498 6.30 2.33 0.37 1544 6.10 2.26 0.37 1622
26 26 6.90 1.73 0.25 1498 6.70 1.68 0.25 1576 6.60 1.65 0.25 1622 6.40 1.60 0.25 1669
27 18 5.88 4.52 0.77 1248 5.63 4.33 0.77 1310 5.40 4.16 0.77 1373 5.20 4.00 0.77 1435
27 20 6.13 3.98 0.65 1310 5.88 3.82 0.65 1388 5.70 3.71 0.65 1420 5.50 3.58 0.65 1482
27 22 6.38 3.38 0.53 1357 6.15 3.26 0.53 1443 6.00 3.18 0.53 1482 5.75 3.05 0.53 1544
27 24 6.70 2.75 0.41 1420 6.45 2.64 0.41 1498 6.30 2.58 0.41 1544 6.10 2.50 0.41 1622
27 26 6.90 2.00 0.29 1498 6.70 1.94 0.29 1576 6.60 1.91 0.29 1622 6.40 1.86 0.29 1669
28 18 5.88 4.76 0.81 1248 5.63 4.56 0.81 1310 5.40 4.37 0.81 1373 5.20 4.21 0.81 1435
28 20 6.13 4.23 0.69 1310 5.88 4.05 0.69 1388 5.70 3.93 0.69 1420 5.50 3.80 0.69 1482
28 22 6.38 3.63 0.57 1357 6.15 3.51 0.57 1443 6.00 3.42 0.57 1482 5.75 3.28 0.57 1544
28 24 6.70 3.02 0.45 1420 6.45 2.90 0.45 1498 6.30 2.84 0.45 1544 6.10 2.75 0.45 1622
28 26 6.90 2.28 0.33 1498 6.70 2.21 0.33 1576 6.60 2.18 0.33 1622 6.40 2.11 0.33 1669
29 18 5.88 4.99 0.85 1248 5.63 4.78 0.85 1310 5.40 4.59 0.85 1373 5.20 4.42 0.85 1435
29 20 6.13 4.47 0.73 1310 5.88 4.29 0.73 1388 5.70 4.16 0.73 1420 5.50 4.02 0.73 1482
29 22 6.38 3.89 0.61 1357 6.15 3.75 0.61 1443 6.00 3.66 0.61 1482 5.75 3.51 0.61 1544
29 24 6.70 3.28 0.49 1420 6.45 3.16 0.49 1498 6.30 3.09 0.49 1544 6.10 2.99 0.49 1622
29 26 6.90 2.55 0.37 1498 6.70 2.48 0.37 1576 6.60 2.44 0.37 1622 6.40 2.37 0.37 1669
30 18 5.88 5.23 0.89 1248 5.63 5.01 0.89 1310 5.40 4.81 0.89 1373 5.20 4.63 0.89 1435
30 20 6.13 4.72 0.77 1310 5.88 4.52 0.77 1388 5.70 4.39 0.77 1420 5.50 4.24 0.77 1482
30 22 6.38 4.14 0.65 1357 6.15 4.00 0.65 1443 6.00 3.90 0.65 1482 5.75 3.74 0.65 1544
30 24 6.70 3.55 0.53 1420 6.45 3.42 0.53 1498 6.30 3.34 0.53 1544 6.10 3.23 0.53 1622
30 26 6.90 2.83 0.41 1498 6.70 2.75 0.41 1576 6.60 2.71 0.41 1622 6.40 2.62 0.41 1669
31 18 5.88 5.46 0.93 1248 5.63 5.23 0.93 1310 5.40 5.02 0.93 1373 5.20 4.84 0.93 1435
31 20 6.13 4.96 0.81 1310 5.88 4.76 0.81 1388 5.70 4.62 0.81 1420 5.50 4.46 0.81 1482
31 22 6.38 4.40 0.69 1357 6.15 4.24 0.69 1443 6.00 4.14 0.69 1482 5.75 3.97 0.69 1544
31 24 6.70 3.82 0.57 1420 6.45 3.68 0.57 1498 6.30 3.59 0.57 1544 6.10 3.48 0.57 1622
31 26 6.90 3.11 0.45 1498 6.70 3.02 0.45 1576 6.60 2.97 0.45 1622 6.40 2.88 0.45 1669
32 18 5.88 5.70 0.97 1248 5.63 5.46 0.97 1310 5.40 5.24 0.97 1373 5.20 5.04 0.97 1435
32 20 6.13 5.21 0.85 1310 5.88 4.99 0.85 1388 5.70 4.85 0.85 1420 5.50 4.68 0.85 1482
32 22 6.38 4.65 0.73 1357 6.15 4.49 0.73 1443 6.00 4.38 0.73 1482 5.75 4.20 0.73 1544
32 24 6.70 4.09 0.61 1420 6.45 3.93 0.61 1498 6.30 3.84 0.61 1544 6.10 3.72 0.61 1622
32 26 6.90 3.38 0.49 1498 6.70 3.28 0.49 1576 6.60 3.23 0.49 1622 6.40 3.14 0.49 1669
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH590B
25
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-EF50VE
CAPACITY: 5.0 kW SHF: 0.71 INPUT: 1560 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
35 40 46
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 4.90 2.60 0.53 1529 4.50 2.39 0.53 1622 4.15 2.20 0.53 1685
21 20 5.15 2.11 0.41 1591 4.80 1.97 0.41 1669 4.45 1.82 0.41 1763
22 18 4.90 2.79 0.57 1529 4.50 2.57 0.57 1622 4.15 2.37 0.57 1685
22 20 5.15 2.32 0.45 1591 4.80 2.16 0.45 1669 4.45 2.00 0.45 1763
22 22 5.45 1.80 0.33 1654 5.10 1.68 0.33 1747 4.75 1.57 0.33 1810
23 18 4.90 2.99 0.61 1529 4.50 2.75 0.61 1622 4.15 2.53 0.61 1685
23 20 5.15 2.52 0.49 1591 4.80 2.35 0.49 1669 4.45 2.18 0.49 1763
23 22 5.45 2.02 0.37 1654 5.10 1.89 0.37 1747 4.75 1.76 0.37 1810
24 18 4.90 3.19 0.65 1529 4.50 2.93 0.65 1622 4.15 2.70 0.65 1685
24 20 5.15 2.73 0.53 1591 4.80 2.54 0.53 1669 4.45 2.36 0.53 1763
24 22 5.45 2.23 0.41 1654 5.10 2.09 0.41 1747 4.75 1.95 0.41 1810
24 24 5.75 1.67 0.29 1716 5.40 1.57 0.29 1794 5.10 1.48 0.29 1872
25 18 4.90 3.38 0.69 1529 4.50 3.11 0.69 1622 4.15 2.86 0.69 1685
25 20 5.15 2.94 0.57 1591 4.80 2.74 0.57 1669 4.45 2.54 0.57 1763
25 22 5.45 2.45 0.45 1654 5.10 2.30 0.45 1747 4.75 2.14 0.45 1810
25 24 5.75 1.90 0.33 1716 5.40 1.78 0.33 1794 5.10 1.68 0.33 1872
26 18 4.90 3.58 0.73 1529 4.50 3.29 0.73 1622 4.15 3.03 0.73 1685
26 20 5.15 3.14 0.61 1591 4.80 2.93 0.61 1669 4.45 2.71 0.61 1763
26 22 5.45 2.67 0.49 1654 5.10 2.50 0.49 1747 4.75 2.33 0.49 1810
26 24 5.75 2.13 0.37 1716 5.40 2.00 0.37 1794 5.10 1.89 0.37 1872
26 26 6.05 1.51 0.25 1778 5.70 1.43 0.25 1856 5.35 1.34 0.25 1934
27 18 4.90 3.77 0.77 1529 4.50 3.47 0.77 1622 4.15 3.20 0.77 1685
27 20 5.15 3.35 0.65 1591 4.80 3.12 0.65 1669 4.45 2.89 0.65 1763
27 22 5.45 2.89 0.53 1654 5.10 2.70 0.53 1747 4.75 2.52 0.53 1810
27 24 5.75 2.36 0.41 1716 5.40 2.21 0.41 1794 5.10 2.09 0.41 1872
27 26 6.05 1.75 0.29 1778 5.70 1.65 0.29 1856 5.35 1.55 0.29 1934
28 18 4.90 3.97 0.81 1529 4.50 3.65 0.81 1622 4.15 3.36 0.81 1685
28 20 5.15 3.55 0.69 1591 4.80 3.31 0.69 1669 4.45 3.07 0.69 1763
28 22 5.45 3.11 0.57 1654 5.10 2.91 0.57 1747 4.75 2.71 0.57 1810
28 24 5.75 2.59 0.45 1716 5.40 2.43 0.45 1794 5.10 2.30 0.45 1872
28 26 6.05 2.00 0.33 1778 5.70 1.88 0.33 1856 5.35 1.77 0.33 1934
29 18 4.90 4.17 0.85 1529 4.50 3.83 0.85 1622 4.15 3.53 0.85 1685
29 20 5.15 3.76 0.73 1591 4.80 3.50 0.73 1669 4.45 3.25 0.73 1763
29 22 5.45 3.32 0.61 1654 5.10 3.11 0.61 1747 4.75 2.90 0.61 1810
29 24 5.75 2.82 0.49 1716 5.40 2.65 0.49 1794 5.10 2.50 0.49 1872
29 26 6.05 2.24 0.37 1778 5.70 2.11 0.37 1856 5.35 1.98 0.37 1934
30 18 4.90 4.36 0.89 1529 4.50 4.01 0.89 1622 4.15 3.69 0.89 1685
30 20 5.15 3.97 0.77 1591 4.80 3.70 0.77 1669 4.45 3.43 0.77 1763
30 22 5.45 3.54 0.65 1654 5.10 3.32 0.65 1747 4.75 3.09 0.65 1810
30 24 5.75 3.05 0.53 1716 5.40 2.86 0.53 1794 5.10 2.70 0.53 1872
30 26 6.05 2.48 0.41 1778 5.70 2.34 0.41 1856 5.35 2.19 0.41 1934
31 18 4.90 4.56 0.93 1529 4.50 4.19 0.93 1622 4.15 3.86 0.93 1685
31 20 5.15 4.17 0.81 1591 4.80 3.89 0.81 1669 4.45 3.60 0.81 1763
31 22 5.45 3.76 0.69 1654 5.10 3.52 0.69 1747 4.75 3.28 0.69 1810
31 24 5.75 3.28 0.57 1716 5.40 3.08 0.57 1794 5.10 2.91 0.57 1872
31 26 6.05 2.72 0.45 1778 5.70 2.57 0.45 1856 5.35 2.41 0.45 1934
32 18 4.90 4.75 0.97 1529 4.50 4.37 0.97 1622 4.15 4.03 0.97 1685
32 20 5.15 4.38 0.85 1591 4.80 4.08 0.85 1669 4.45 3.78 0.85 1763
32 22 5.45 3.98 0.73 1654 5.10 3.72 0.73 1747 4.75 3.47 0.73 1810
32 24 5.75 3.51 0.61 1716 5.40 3.29 0.61 1794 5.10 3.11 0.61 1872
32 26 6.05 2.96 0.49 1778 5.70 2.79 0.49 1856 5.35 2.62 0.49 1934
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH590B
26
PERFORMANCE DATA HEAT operation at Rated frequency
MUZ-EF25VE MUZ-EF25VEH
CAPACITY: 3.2 kW INPUT: 700 W
INDOOR
DB (°C)
OUTDOOR WB (°C)
-10 -5 0 5 10 15 20
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
15 2.02 455 2.43 546 2.85 616 3.26 665 3.68 707 4.06 728 4.48 742
21 1.92 490 2.30 581 2.72 644 3.10 693 3.52 728 3.90 749 4.30 777
26 1.73 525 2.14 616 2.53 679 2.94 728 3.36 763 3.74 784 4.16 805
MUZ-EF35VE MUZ-EF35VEH
CAPACITY: 4.0 kW INPUT: 955 W
INDOOR
DB (°C)
OUTDOOR WB (°C)
-10 -5 0 5 10 15 20
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
15 2.52 621 3.04 745 3.56 840 4.08 907 4.60 965 5.08 993 5.60 1012
21 2.40 669 2.88 793 3.40 879 3.88 945 4.40 993 4.88 1022 5.38 1060
26 2.16 716 2.68 840 3.16 926 3.68 993 4.20 1041 4.68 1070 5.20
1098
MUZ-EF42VE
CAPACITY: 5.4 kW INPUT: 1460 W
INDOOR
DB (°C)
OUTDOOR WB (°C)
-10 -5 0 5 10 15 20
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
15 3.40 949 4.10 1139 4.81 1285 5.51 1387 6.21 1475 6.86 1518 7.56 1548
21 3.24 1022 3.89 1212 4.59 1343 5.24 1445 5.94 1518 6.59 1562 7.26 1621
26 2.92 1095 3.62 1285 4.27 1416 4.97 1518 5.67 1591 6.32 1635 7.02 1679
MUZ-EF50VE
CAPACITY: 5.8 kW INPUT: 1565 W
INDOOR
DB (°C)
OUTDOOR WB (°C)
-10 -5 0 5 10 15 20
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
15 3.65 1017 4.41 1221 5.16 1377 5.92 1487 6.67 1581 7.37 1628 8.12 1659
21 3.48 1096 4.18 1299 4.93 1440 5.63 1549 6.38 1628 7.08 1675 7.80 1737
26 3.13 1174 3.89 1377 4.58 1518 5.34 1628 6.09 1706 6.79 1753 7.54 1800
NOTE: Q : Total capacity (kW) INPUT : Total power input (W) DB: Dry-bulb temperature WB: Wet-bulb temperature
OBH590B
27
MUZ-EF25VE MUZ-EF25VEH MUZ-EF35VE MUZ-EF35VEH MUZ-EF42VE MUZ-EF50VE
9-2. R.V. COIL CONTROL
Heating
. . . . . . . . . . . . . . . . .
ON
Cooling
. . . . . . . . . . . . . . . . .
OFF
Dry
. . . . . . . . . . . . . . . . . . . .
OFF
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
ON
OFF
ON
OFF
Outdoor fan motor
Compressor
5 seconds 15 seconds
ON
OFF
Compressor
Outdoor fan
motor
R.V.coil
ON
OFF
ON
OFF
<COOL>
5 seconds
<HEAT>
5 seconds
9-1. OUTDOOR FAN MOTOR CONTROL
The fan motor turns ON/OFF, interlocking with the compressor. [ON] The fan motor turns ON 5 seconds before the compressor starts up. [OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
9-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR
Sensor Purpose
Actuator
Compressor
LEV
Outdoor fan
motor
R.V.coil
Indoor fan
motor
Defrost
heater
Discharge temperature thermistor
Protection
○○
Indoor coil temperature thermistor
Cooling: Coil frost prevention
Heating: High pressure protec­tion
○○
Defrost thermistor Heating: Defrosting
○○○○○
Fin temperature thermistor Protection
○○
Ambient temperature thermistor
Cooling: Low ambient tempera­ture operation
○○○
Heating: Defrosting (Heater)
Outdoor heat exchanger tem­perature thermistor
Cooling: Low ambient tempera­ture operation
○○○
Cooling: High pressure protec­tion
○○○
ACTUATOR CONTROL
9
OBH590B
28
10-1. CHANGE IN DEFROST SETTING Changing defrost finish temperature
<JS> To change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P.C. board. (Refer to
11-6-1.)
Jumper wire
Defrost fi nish temperature (°C)
MUZ-EF25VE -
E1
MUZ-EF25VE -
E2
MUZ-EF25VEH
MUF-EF35VE MUZ-EF35VEH MUF-EF42VE MUZ-EF50VE
JS
Soldered (Initial setting)
5°C 8°C 10°C 10°C 5°C 9°C
None (Cut) 8°C 15°C 13°C 15°C 10°C 18°C
10-2. PRE-HEAT CONTROL SETTING
PRE-HEAT CONTROL
When moisture gets into the refrigerant cycle, it may interfere the start-up of the compressor at low outside temperature. The pre-heat control prevents this interference. The pre-heat control turns ON when the defrost thermistor reads 20°C or below. When pre-heat control is turned ON, compressor is energized. (About 50 W)
<JK> To activate the pre-heat control, cut the JK wire of the inverter P.C. board. (Refer to 11-6.1.)
NOTE: When the inverter P.C. board is replaced, check the Jumper wires, and cut/solder them if necessary.
MUZ-EF25VE MUZ-EF25VEH MUZ-EF35VE MUZ-EF35VEH MUZ-EF42VE MUZ-EF50VE
SERVICE FUNCTIONS
10
OBH590B
29
11-1. CAUTIONS ON TROUBLESHOOTING
1. Before troubleshooting, check the following
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for miswiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, and then after confirming the horizontal vane is closed, turn OFF the breaker and/or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board.
3) When removing the electrical parts, be careful of the residual voltage of smoothing capacitor.
4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components.
5) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
MUZ-EF25VE MUZ-EF25VEH MUZ-EF35VE MUZ-EF35VEH MUZ-EF42VE MUZ-EF50VE
TROUBLESHOOTING
11
3. Troubleshooting procedure
1) Check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality. To
make sure, check how many times the OPERATION INDICATOR lamp is flashing on and off before starting service work.
2) Before servicing, check that the connector and terminal are connected properly.
3) When the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
4) Refer to 11-2 and 11-3.
Lead wiring
Housing point
<Incorrect>
<Correct>
OBH590B
30
Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (11-3.) disappears, the memorized failure details can be recalled.
11-2. FAILURE MODE RECALL FUNCTION
1. Flow chart of failure mode recall function for the indoor/outdoor unit
NOTE: 1. Make sure to release the failure mode recall function once it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
Does the left lamp of OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: Either indoor or outdoor unit is abnormal. Beep is emit-
ted at the same timing as the blinking of the left lamp of OPERATION INDICATOR lamp. 2
Indoor unit is normal. But the outdoor unit might be abnormal because there are some abnor­malities that can not be recalled with this way. Confi rm if outdoor unit is abnormal according to the detailed outdoor unit failure mode recall function. (Refer to 11-2.2.)
No
Yes
The cause of abnormality cannot be found because the abnormality does not recur.
Setting up the failure mode recall function
Turn ON the power supply. <Preparation of the remote controller>
While pressing OPERATION SELECT button and TEMP button on the remote
controller at the same time, press RESET button.
First, release RESET button. Hold down the other two buttons for another 3 seconds. Confi rm that the indicators on the LCD screen shown in the right fi gure are all displayed. Then release the buttons.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1
Judgment of indoor/outdoor abnormality
Before blinking, does the left lamp of OPERATION INDICA­TOR lamp stay ON for 3 seconds? Stays ON for 3 seconds (without beep): The outdoor unit is abnormal.
The indoor unit is abnormal. Check the blinking pattern, and confi rm the abnormal point with the indoor unit failure mode table. (Refer to indoor unit service manual.) Make sure to check at least two consecutive blinking cycles. 2
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller.
The outdoor unit is abnormal. Check the blinking pattern, and confi rm the abnormal point with the outdoor unit failure mode table. (Refer to 11-2.3.) Make sure to check at least two consecutive blinking cycles.
3
Repair the defective parts.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" mentioned above.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed)
with the remote controller headed towards the indoor unit. Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
Operational procedure
Yes (Blinks)
No (OFF)
1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received.
2. Blinking pattern when the indoor unit is abnormal:
3.Blinking pattern when the outdoor unit is abnormal:
ON
OFF
Beeps
Repeated cycle Repeated cycle
ON
OFF
No beep Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5­second interval
2.5-second OFF 3-second ON
Blinking at 0.5­second interval
Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5­second interval
No beep Beeps
Repeated cycle
2.5-second OFF
3-second ON
Blinking at 0.5­second interval
Repeated cycle
Beeps
OBH590B
31
2. Flow chart of the detailed outdoor unit failure mode recall function
2.Blinking pattern when outdoor unit is abnormal:
ON
OFF
No beep
Beeps
Repeated cycle
2.5-second OFF 3-second ON
Blinking at 0.5­second interval
No beep Beeps
Repeated cycle
2.5-second OFF 3-second ON
Blinking at 0.5-
second interval
Repeated cycle
Does the left lamp of OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: The outdoor unit is abnormal. Beep is emitted
at the same timing as the blinking of the left lamp of OPERATION INDICATOR lamp. 2
Yes (Blinks
)
No (OFF)
The outdoor unit might be abnormal. Confi rm if outdoor unit is abnormal according to the following procedures.
Operational procedure
Confi rm that the remote controller is in the failure mode recall function.
With the remote controller headed towards the indoor unit, press TEMP
button to adjust the set temperature to 25°C. 1
1. Regardless of normal or abnormal condition, 2 short beeps are emitted as the signal is received.
The outdoor unit is abnormal. Check the blinking pattern, and confi rm the abnormal point with the out- door unit failure mode table (11-2.3.). Make sure to check at least two consecutive blinking cycles. 2
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller.
Repair the defective parts.
The outdoor unit is normal.
Release the failure mode recall function accord­ing to the left mentioned procedure.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" (11-2.1.).
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with
the remote controller headed towards the indoor unit.
Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.
4
Release the failure mode recall function according to "Releasing the failure mode recall function" men-
tioned above.
NOTE: 1. Make sure to release the failure mode recall function once it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
4
The information regarding whether the
connected outdoor unit is a low-standby-
power model or a non-low-standby-power model will also be initialized.
(Default= compatible with a low-standby-
power model)
NOTE: It takes up to 1 minute to indicate the outdoor unit
abnormality.
Even if the OPERATION INDICATOR lamp is not
lighting, keep checking at least 1 minute or longer.
OBH590B
32
3. Outdoor unit failure mode table
The left lamp of
OPERATION
INDICATOR
lamp
(Indoor unit)
Abnormal point
(Failure mode/protection)
LED indication
(Outdoor P.C. board)
Condition Remedy
Indoor/outdoor
unit failure
mode recall
function
Outdoor unit failure mode
recall function
OFF None (Normal)
1-time fl ash
2.5 seconds OFF
Indoor/outdoor communication, receiving error
Any signals from the inverter P.C. board cannot be received normally for 3 minutes.
•Refer to 11-5. How to check miswiring and serial signal error.
○○
Indoor/outdoor communication, receiving error
Although the inverter P.C. board sends signal "0", signal "1" has been received 30 consecutive times.
•Refer to 11-5. How to check miswiring and serial signal error.
2-time fl ash
2.5 seconds OFF
Outdoor power system
Overcurrent protection cut-out operates 3 consecutive times within 1 minute after the compressor gets started.
Reconnect connectors. Refer to 11-5. "How to check inverter/ compressor". Check stop valve.
○○
3-time fl ash
2.5 seconds OFF
Discharge temperature thermistor
1-time fl ash every
2.5 seconds
Thermistor shorts or opens during compressor running.
Refer to 11-5. "Check of outdoor thermistors". Defective outdoor thermistors can be identifi ed by checking the blinking pattern of LED.
○○
Defrost thermistor
Fin temperature thermistor 3-time fl ash
2.5 seconds OFF
P.C. board temperature thermistor
4-time fl ash
2.5 seconds OFF
Ambient temperature thermistor
2-time fl ash
2.5 seconds OFF
Outdoor heat exchanger temperature thermistor
4-time fl ash
2.5 seconds OFF
Overcurrent 11-time fl ash
2.5 seconds OFF
Large current fl ows into intelligent power module.
Reconnect compressor connector. Refer to 11-5.
"How to check inverter/ compressor". Check stop valve.
Compressor synchronous abnormality (Compressor start-up failure protection)
12-time fl ash
2.5 seconds OFF
Waveform of compressor current is distorted.
Reconnect compressor connector. Refer to 11-5. "How to check inverter/ compressor".
5-time fl ash
2.5 seconds OFF
Discharge temperature
Temperature of discharge temperature thermistor exceeds 116°C, compressor stops. Compressor can restart if discharge temperature thermistor reads 100°C or less 3 minutes later.
Check refrigerant circuit and refrigerant amount. Refer to 11-5. "Check of LEV".
6-time fl ash
2.5 seconds OFF
High pressure
Temperature indoor coil thermistor exceeds 70°C in HEAT mode. Temperature defrost thermistor exceeds 70°C in COOL mode.
Check refrigerant circuit and refrigerant amount. Check stop valve.
7-time fl ash
2.5 seconds OFF
Fin temperature/ P.C. board temperature
7-time fl ash
2.5 seconds OFF
Temperature of fi n temperature thermistor on the inverter P.C. board exceeds 75 ~ 86°C, or temperature of P.C. board temperature thermistor on the inverter P.C. board exceeds 72 ~ 85°C.
Check around outdoor unit. Check outdoor unit air passage. Refer to 11-5.
"Check of outdoor fan motor".
8-time fl ash
2.5 seconds OFF
Outdoor fan motor
Outdoor fan has stopped 3 times in a row within 30 seconds after outdoor fan start-up.
Refer to 11-5.
"Check of outdoor fan motor". Refer to 11-5. "Check of inverter P.C. board".
9-time fl ash
2.5 seconds OFF
Nonvolatile memory data 5-time fl ash
2.5 seconds OFF
Nonvolatile memory data cannot be read properly.
Replace the inverter P.C. board.
○○
Power module 6-time fl ash
2.5 seconds OFF
The interface short circuit occurs in the output of the intelligent power module (IC700). The compressor winding shorts circuit.
Refer to 11-5. "How to check inverter/ compressor".
10-time fl ash
2.5 seconds OFF
Discharge temperature
Temperature of discharge temperature thermistor has been 50°C or less for 20 minutes.
Refer to 11-5. "Check of LEV". Check refrigerant circuit and refrigerant amount.
11-time fl ash
2.5 seconds OFF
DC voltage 8-time fl ash
2.5 seconds OFF
DC voltage of inverter cannot be detected normally.
Refer to 11-5. "How to check inverter/ compressor".
Each phase current of compressor
9-time fl ash
2.5 seconds OFF
Each phase current of compressor cannot be detected normally.
14-time fl ash
2.5 seconds OFF
Stop valve (Closed valve) 14-time fl ash
2.5 seconds OFF
Closed valve is detected by compressor current.
Check stop valve
○○
4-way valve/ Pipe temperature
16-time fl ash
2.5 seconds OFF
The 4-way valve does not work properly. The indoor coil thermistor detects an abnormal temperature.
Check 4-way valve. Replace inverter P.C. board.
NOTE: Blinking patterns of this mode differ from the ones of Troubleshooting check table (11-3.).
OBH590B
33
11-3. TROUBLESHOOTING CHECK TABLE
No. Symptom LED indication
Abnormal point/
Condition
Condition Remedy
1
Outdoor unit does not op­erate.
1-time fl ash every
2.5 seconds
Outdoor power sys­tem
Overcurrent protection cut-out operates 3 consecutive times within 1 minute after the compressor gets started.
Reconnect connector of compres­sor. Refer to 11-5.
"How to check in­verter/compressor". Check stop valve.
2
Outdoor thermistors Discharge temperature thermistor, fi n temperature thermistor,
defrost thermistor, P.C. board temperature thermistor, outdoor heat exchanger temperature thermistor or ambient tempera­ture thermistor shorts or opens during compressor running.
Refer to 11-5. "Check of outdoor thermistors".
3
Outdoor control sys­tem
Nonvolatile memory data cannot be read properly.
(The left lamp of OPERATION INDICATOR lamp of the indoor unit lights up or fl ashes 7-time.)
Replace inverter P.C. board.
4
6-time fl ash
2.5 seconds OFF
Serial signal The communication fails between the indoor and outdoor unit
for 3 minutes.
Refer to 11-5. "How to check miswiring and serial signal error.
5
11-time fl ash
2.5 seconds OFF
Stop valve/ Closed valve
Closed valve is detected by compressor current. Check stop valve.
6
14-time fl ash
2.5 seconds OFF
Outdoor unit (Other abnormality)
Outdoor unit is defective. Refer to 11-2.2. "Flow chart of the
detailed outdoor unit failure mode recall function".
7
16-time fl ash
2.5 seconds OFF
4-way valve/
Pipe temperature
The 4-way valve does not work properly. The indoor coil thermistor detects an abnormal temperature.
Refer to 11-5.
"Check of R.V. coil". Replace inverter P.C. board.
8
'Outdoor unit stops and restarts 3 minutes later' is repeated.
2-time fl ash
2.5 seconds OFF
Overcurrent protec­tion
Large current fl ows into intelligent power module.
Reconnect connector of compressor. Refer to 11-5. "How to check in­verter/compressor". Check stop valve.
9
3-time fl ash
2.5 seconds OFF
Discharge tempera­ture overheat pro­tection
Temperature of discharge temperature thermistor exceeds 116°C, compressor stops. Compressor can restart if discharge temperature thermistor reads 100°C or less 3 minutes later.
Check refrigerant circuit and refrig­erant amount. Refer to 11-5.
"Check of LEV".
10
4-time fl ash
2.5 seconds OFF
Fin temperature /P.C. board tem­perature thermistor overheat protection
Temperature of fi n temperature thermistor on the heat sink exceeds 75 ~ 86°C or temperature of P.C. board temperature thermistor on the inverter P.C.board exceeds 72 ~ 85°C.
Check around outdoor unit. Check outdoor unit air passage. Refer to 11-5. "Check of outdoor fan motor".
11
5-time fl ash
2.5 seconds OFF
High pressure pro­tection
Indoor coil thermistor exceeds 70°C in HEAT mode. Defrost thermistor exceeds 70°C in COOL mode.
Check refrigerant circuit and refrig­erant amount. Check stop valve.
12
8-time fl ash
2.5 seconds OFF
Compressor syn­chronous abnormal­ity
The waveform of compressor current is distorted.
Reconnect connector of compressor. Refer to 11-5. "How to check in­verter/compressor".
13
10-time fl ash
2.5 seconds OFF
Outdoor fan motor Outdoor fan has stopped 3 times in a row within 30 seconds
after outdoor fan start-up.
Refer to 11-5.
"Check of outdoor fan motor. Refer to 11-5. "Check of inverter P.C. board.
14
12-time fl ash
2.5 seconds OFF
Each phase current of compressor
Each phase current of compressor cannot be detected nor­mally.
Refer to 11-5. "How to check in­verter/compressor".
15
13-time fl ash
2.5 seconds OFF
DC voltage DC voltage of inverter cannot be detected normally. Refer to 11-5. "How to check in-
verter/compressor".
16
Outdoor unit operates.
1-time fl ash
2.5 seconds OFF
Frequency drop by current protection
When the input current exceeds approximately 7A(EF25)/ 8A(EF35)/9A(EF42)/12A(EF50), compressor frequency lowers.
The unit is normal, but check the following. Check if indoor fi lters are clogged. Check if refrigerant is short. Check if indoor/outdoor unit air circulation is short cycled.
17
3-time fl ash
2.5 seconds OFF
Frequency drop by high pressure pro­tection
Temperature of indoor coil thermistor exceeds 55°C in HEAT mode, compressor frequency lowers.
Frequency drop by defrosting in COOL mode
Indoor coil thermistor reads 8°C or less in COOL mode, com­pressor frequency lowers.
18
4-time fl ash
2.5 seconds OFF
Frequency drop by discharge tempera­ture protection
Temperature of discharge temperature thermistor exceeds 111°C, compressor frequency lowers.
Check refrigerant circuit and refrig­erant amount. Refer to 11-5.
"Check of LEV". Refer to 11-5. "Check of outdoor thermistors".
19
5-time fl ash
2.5 seconds OFF
Outside temperature thermistor protec­tion
When the outside temperature thermistor shorts or opens, protective operation without that thermistor is performed.
Refer to 11-5.
Check of outdoor
thermistors.
20
Outdoor unit operates.
7-time fl ash
2.5 seconds OFF
Low discharge tem­perature protection
Temperature of discharge temperature thermistor has been 50°C or less for 20 minutes.
Refer to 11-5. "Check of LEV". Check refrigerant circuit and refrig­erant amount.
21
8-time fl ash
2.5 seconds OFF
PAM protection PAM: Pulse Ampli­tude Modulation
The overcurrent fl ows into PFC (Power factor correction : IC820) or the bus-bar voltage reaches 394 V or more, PAM stops and restarts.
This is not malfunction. PAM pro­tection will be activated in the fol­lowing cases: 1 Instantaneous power voltage
drop. (Short time power failure)
2 When the power supply voltage
is high.
22
9-time fl ash
2.5 seconds OFF
Inverter check mode The connector of compressor is disconnected, inverter check
mode starts.
Check if the connector of the com­pressor is correctly connected. Refer to 11-5. "How to check inverter/compressor".
NOTE: 1. The location of LED is illustrated at the right fi gure. Refer to 11-6.1.
2. LED is lighted during normal operation.
The fl ashing frequency shows the number of times the LED blinks after every 2.5-second OFF. (Example) When the fl ashing frequency is “2”.
ON
OFF
2.5-second OFF
2.5-second OFF
0.5-second ON 0.5-second ON
LED
Flashing
Inverter P.C. board
OBH590B
34
11-4. TROUBLE CRITERION OF MAIN PARTS
MUZ-EF25VE MUZ-EF25VEH MUZ-EF35VE MUZ-EF35VEH MUZ-EF42VE MUZ-EF50VE
Part name Check method and criterion Figure
Defrost thermistor (RT61)
Fin temperature thermistor (RT64)
Ambient temperature thermistor (RT65)
Outdoor heat exchanger temperature thermistor (RT68)
Measure the resistance with a tester.
Refer to 11-6. “Test point diagram and voltage”, 1. “Inverter P.C. board”, for the chart of thermistor.
Discharge temperature thermistor (RT62)
Measure the resistance with a tester. Before measurement, hold the thermistor with your hands to warm it up.
Refer to 11-6. “Test point diagram and voltage”, 1. “Inverter P.C. board”, for the chart of thermistor.
Compressor
Measure the resistance between terminals using a tester. (Temperature: -10 ~ 40°C)
Normal (Ω)
MUZ-EF25 MUZ-EF35/42 MUZ-EF50
U-V U-W V-W
1.36 ~ 1.93 1.52 ~ 2.17 0.78 ~ 1.11
Outdoor fan motor
Measure the resistance between lead wires using a tester. (Temperature: -10 ~ 40°C)
Color of lead wire
Normal (Ω)
MUZ-EF25/35/42 MUZ-EF50
RED – BLK BLK – WHT WHT – RED
29 ~ 42 12 ~ 17
R. V. coil (21S4)
Measure the resistance using a tester. (Temperature: -10 ~ 40°C)
Normal (kΩ)
1.19 ~ 1.78
Expansion valve coil (LEV)
Measure the resistance using a tester. (Temperature: -10 ~ 40°C)
MUZ-EF25/35/42
Color of lead wire Normal (Ω)
WHT – RED
37 ~ 54
RED – ORN YLW – BRN
BRN – BLU
Measure the resistance using a tester. (Temperature: -10 ~ 40°C)
MUZ-EF50
Color of lead wire Normal (Ω)
RED – ORN
37 ~ 54
RED – WHT
RED – BLU
RED – YLW
Defrost heater
MUZ-EF•VEH
Measure the resistance using a tester. (Temperature: -10 ~ 40°C)
Normal (Ω)
349 ~ 428
W
U
V
WHT
RED BLK
W
U
V
WHT
RED BLK
LEV
WHT
RED
ORN
YLW
BRN
BLU
RED
(+12V)
YLW
BLU
WHT
ORN
LEV
OBH590B
35
11-5. TROUBLESHOOTING FLOW
Are the voltages balanced?
Disconnect the connector between compressor and the intelligent power module (IC700).
Replace the inverter P.C. board.
Check the voltage between terminals.
Check the compressor.
See 11-5. “Check of compressor”.
No
Yes
See 11-5. “Check of open phase”.
A How to check inverter/compressor
Refer to 11-5. “Check of compressor operation time”. Does the compressor operate continuously?
Refer to 11-5. “Check of compressor start failure”.
OK.
No
Yes
Refer to 11-5. “Check of compressor winding”. Is the compressor normal?
Replace the compressor.
No
Yes
B Check of open phase
C Check of compressor
With the connector between the compressor and the intelligent power module disconnected, activate the inverter and check if the inverter is normal by measuring the voltage balance between the terminals.
Output voltage is 50 - 130 V. (The voltage may differ according to the tester.)
<< Operation method>> Start cooling or heating operation by pressing EMERGENCY OPERATION switch on the indoor unit. (TEST RUN OPERA-
TION: Refer to 8-3.) <<Measurement point>> At 3 points BLK (U)-WHT (V) BLK (U)-RED (W) WHT(V)-RED (W)
NOTE: 1. Output voltage varies according to power supply voltage.
2. Measure the voltage by analog type tester.
3. During this check, LED of the inverter P.C. board fl ashes 9 times. (Refer to 11-6.1.)
Measure AC voltage between the lead wires at 3 points.
OBH590B
36
F Check of compressor start failure
D Check of compressor winding
E Check of compressor operation time
Disconnect the connector between the compressor and intelligent power module, and measure the resistance between the compressor terminals.
<<Measurement point>> at 3 points BLK-WHT BLK-RED WHT-RED <<Judgement>> Refer to 11-4. 0 [Ω] ················Abnormal [short] Infinite [Ω] ·······Abnormal [open] NOTE: Be sure to zero the ohmmeter before measurement.
Measure the resistance between the lead wires at 3 points.
After the compressor is heated with a drier, does the compressor start?
1
Replace the compressor.
Compressor start failure. Activate pre-heat control. (Refer to 10-2. "PRE-HEAT CONTROL SETTING")
No
Yes
Does the compressor run for 10 seconds or more after it starts?
Check the refrigerant circuit. Check the stop valve.
Yes
No
1 Heat the compressor with a drier for about 20 minutes. Do not recover refrigerant gas while heating.
Heating part
Connect the compressor and activate the inverter. Then measure the time until the inverter stops due to over current. <<Operation method>> Start heating or cooling operation by pressing EMERGENCY OPERATION switch on the indoor unit. (TEST RUN OPERATION: Refer to 8-3.) <<Measurement>> Measure the time from the start of compressor to the stop of compressor due to overcurrent.
Compressor starts
Abnormal (IPM failure) (Compressor winding short)
Abnormal (Compressor lock out) (Starting defect)
Abnormal (Poor contact,) (Outdoor P.C. board defect) (Disconnected connector)
Abnormal (Refrigerant circuit defect) (Closed valve)
Normal
0 second
1 second
2 seconds
10 seconds
10 minutes
<<Judgement>>
Confi rm that
~ is normal.
•Electrical circuit check . Contact of the compressor connector . Output voltage of inverter P.C. board and balance of them (See 11-5. ) . Direct current voltage between DB61(+) and (-) on the inverter P.C. board . Voltage between outdoor terminal block S1-S2
OBH590B
37
G Check of outdoor thermistors
H Check of R.V. coil
Thermistor Symbol Connector, Pin No. Board
Defrost RT61 Between CN641 pin1 and pin2
Inverter P.C. board
Discharge temperature RT62 Between CN641 pin3 and pin4 Fin temperature RT64 Between CN642 pin1 and pin2 Ambient temperature RT65 Between CN643 pin1 and pin2 Outdoor heat exchanger temperature RT68 Between CN644 pin1 and pin3
Replace the thermistor except RT64. When RT64 is abnormal, replace the inverter P.C. board.
Replace the inverter P.C. board.
No
No
Is the resistance of thermistor normal? (Refer to 11-6.1.)
Reconnect the connector of thermistor. Turn ON the power supply and press EMERGENCY OPERATION switch.
Does the unit operate for 10 minutes or more without showing thermistor abnormality?
OK. (Cause is poor contact.)
Yes
Yes
Disconnect the connector of thermistor in the outdoor P.C. board (see below table), and measure the resistance of thermistor.
First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 11-4. In case CN721 is disconnected or R.V. coil is open, voltage is generated between the terminal pins of the connector
although no signal is being transmitted to R.V. coil.
Check if CN721 is connected.
Is there 230 VAC between CN721 and
on the inverter P.C. board 3 minutes
after the power supply is turned ON?
No
Yes
Replace the inverter P.C. board.
Replace the 4-way valve.
Unit operates COOL mode even if it is set to HEAT mode.
Is there 230 VAC between CN721 and
on the inverter P.C. board 3 minutes
after the power supply is turned ON?
Yes
No
Replace the inverter P.C. board.
Replace the 4-way valve.
Unit operates HEAT mode even if it is set to COOL mode.
Disconnect connector between the compressor and the intelligent power module. Turn ON the power supply and press EMERGENCY OPERATION switch twice (HEAT mode).
Disconnect connector between the compressor and the intelligent power module. Turn ON the power supply and press EMERGENCY OPERATION switch once (COOL mode).
OBH590B
38
I Check of outdoor fan motor
Is the resistance between each ter­minal of outdoor fan motor normal? (Refer to 11-4.)
Disconnect CN932 from the inverter P.C. board, and turn on the power supply.
Rotate the outdoor fan motor manually and measure the voltage of CN931. Between 1(+) and 5(-) Between 2(+) and 5(-) Between 3(+) and 5(-)
Does the voltage between each terminal become 5 and 0 VDC repeatedly?
Does the outdoor fan motor rotate smoothly?
Replace the outdoor fan motor.
Replace the inverter P.C. board.
Yes
Yes
No
(Fixed to either 5 or 0 VDC)
No
No
Yes
Disconnect the connectors CN931 and CN932 from the inverter P.C. board. Check the connection between the connector CN931 and CN932.
OBH590B
39
J Check of power supply
Is there voltage 230 VAC between the indoor terminal block S1 and S2?
No
Yes
Replace the indoor electronic control P.C. board.
Rectify indoor/outdoor connecting wire.
Yes
If light up, OK. If fl ash, refer to 11-3.
Does The left lamp of OPERATION INDICATOR lamp on the indoor unit light up?
Dose LED on the inverter P.C. board light up or fl ash? (Refer to 11-6.1.)
No
Replace the inverter P.C. board.
Is there voltage 260 - 370 VDC between DB61 (+) and DB61 (–) on the inverter P.C. board? (Refer to 11-6.1.)
No
Check the electric parts in main circuit.
Yes
Yes
No
Disconnect the connector between compressor and intelligent power module. Turn ON power supply and press EMERGENCY OPERATION switch.
Inverter P.C. board (Solder side)
DB61
260 - 370 VDC
OBH590B
40
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1
Expansion valve operates in full-opening direction.
OK
NOTE: After check of LEV, do the undermentioned operations.
1. Turn OFF the power supply and turn it ON again.
2. Press RESET button on the remote controller.
1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received.
Measure each voltage between connector pins of CN724 on the inverter P.C. board.
1. Pin (-) — Pin (+)
2. Pin (-) — Pin (+)
3. Pin (-) — Pin (+)
4. Pin (-) — Pin (+) Is there about 3 - 5 VAC between each?
NOTE: Measure the voltage by an analog
tester.
Properly fi x the LEV coil to the expansion valve.
Replace the inverter P.C. board.
Replace the LEV coil.
Replace the expansion valve.
Is LEV coil properly fi xed to the expansion valve?
Does the resistance of LEV coil have the characteristics? (Refer to 11-4.)
Do you hear the expansion valve "click, click·······"? Do you feel the expansion valve vibrate on touching it ?
Turn ON the power supply. <Preparation of the remote controller>
While pressing both OPERATION SELECT button and TEMP button on the remote controller at the same time, press RESET button.
First, release RESET button.
Hold down the other two buttons for another 3 seconds. Confi rm that the indicators on the LCD
screen shown in the right fi gure are all displayed. Then release the buttons.
Yes
No
No
Yes
No
Yes
No
Yes
K Check of LEV (Expansion valve)
OBH590B
41
Check the outdoor fan motor. (Refer to 11-5. .)
Is the fuse (F901) blown on the in­verter P.C. board?
Check the connection of the connectors (CN931, CN932) of the outdoor fan motor. If the connection is poor, make it correct.
Operate the outdoor unit by starting EMERGENCY OPERATION.
Check the LED indication on the in­verter P.C. board. Does the LED fl ash 10 times?
Replace the inverter P.C. board.
Check the corresponding parts following LED indication. (Refer to 11-3.)
Yes
No
Yes (10-time fl ash)
No
L Check of inverter P.C. board
OBH590B
42
M How to check miswiring and serial signal error
Turn OFF inverter-controlled lighting equipment. Turn OFF the power supply and then turn ON again. Press EMERGENCY OPERATION switch.
A
Is serial signal error indicated 6 minutes later?
B
Yes
Reinstall either the unit or the light away from each other. Attach a fi lter on remote control receiving section of the indoor unit.
No
Turn the main power supply OFF.
Is there rated voltage in the power supply?
Yes
No
Check for incorrect indoor-outdoor connecting wiring.
Check the power supply.
A
Is there rated voltage between outdoor terminal block S1 and S2?
No
Yes
Check for miswiring, broken wires, and loose wire connection between the main power supply and outdoor terminal block S1 and between the main power supply and outdoor terminal block S2.
Wait for 2 or more minutes after the main power supply is turned on. Touch S2 and S3 with tester probes and start the emergency operation.
When the emergency operation starts, does the rated voltage occur for 2 seconds between indoor terminal block S2 and S3?
Yes
Turn the main power supply OFF.
Turn the main power supply ON.
Wait for 2 or more minutes after the main power sup­ply is turned ON. Touch CN202 and JPG with tester probes and start the emergency operation.
During the emergency operation, does DC (2V or more) occur for 2 seconds between CN202
and JPG on the indoor electronic control P.C. board?
No
Does the indoor OPERATION INDICATOR lamp (left) blink continuously 6 minutes after the emergency operation starts?
No
Does the outdoor LED light up?
Replace the indoor electronic control P.C. board.
Replace the indoor power P.C. board.
Yes
Yes
Does the outdoor LED blink 6 times?
Yes
Confi rm that the thermostat is OFF and wiring is not loose.
No
Does DC (6V or more) occur between indoor terminal block S2 and S3?
Yes
Replace the outdoor inverter P.C. board. 1
No
Turn the main power supply OFF. Replace the indoor power P.C. board.
Start the emergency operation.
No
Yes
Repair completed.
Does DC (20V or more) occur between indoor terminal block S2 and S3 ?
No
Yes
Replace the outdoor inverter P.C. board.
1
Replace the indoor electronic control P.C. board.
1. Electric charge may remain immediately after the main power supply is turned OFF. Perform the procedure after 3 minutes.
Replace the outdoor inverter P.C. board. 1
Turn the main power supply ON.
Does the indoor OPERATION INDICATOR lamp (left) blink continuously 6 minutes after the emergency operation starts?
Yes
No
Turn the main power supply ON.
B
No
No
Was the indoor unit ever connected to the Multi (MXZ) series and operated (turned on)?
The connection information to the Multi series is stored in the indoor unit. Refer to “Deleting the memorized abnormal condition” described in 11-2.1 to clear the error history. When the error history is being cleared, the con­nection information also will be initialized. The indoor unit will be compatible with a low-standby-power model after initialization.
OK
Yes
OBH590B
43
N Electromagnetic noise enters into TV sets or radios
Yes
Is the unit earthed?
No
Earth the unit.
Yes
Is the distance between the antennas and the indoor unit within 3 m, or is the distance between the antennas and the outdoor unit within 3 m?
No
Extend the distance between the antennas and the indoor unit, and/or the antennas and the outdoor unit.
Is the distance between the TV sets or radios and the indoor unit within 1 m, or is the distance between the TV sets or radios and the outdoor unit within 3 m?
Yes
Extend the distance between the TV sets and/or radios and the indoor unit, or the TV sets or radios and the outdoor unit.
Are the antennas damaged? Is the coaxial cable damaged? Is there any poor contact in the anten­na wiring?
Yes
No
No
Replace or repair the antenna. Replace or repair the coaxial cable.
Is the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas close?
Yes
Extend the distance between the indoor/outdoor connecting wire of the air conditioner and the wir­ing of the antennas.
No
Even if all of the above conditions are fulfi lled, the electromagnetic noise may enter, depending on the electric fi eld strength or the installation condition (combination of specifi c conditions such as antennas or wiring). Check the following before asking for service.
1. Devices affected by the electromagnetic noise TV sets, radios (FM/AM broadcast, shortwave)
2. Channel, frequency, broadcast station affected by the electromagnetic noise
3. Channel, frequency, broadcast station unaffected by the electromagnetic noise
4. Layout of: indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, earth wire, antennas, wiring from antennas, receiver
5. Electric fi eld intensity of the broadcast station affected by the electromagnetic noise
6. Presence or absence of amplifi er such as booster
7. Operation condition of air conditioner when the electromagnetic noise enters in
1) Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic noise.
2) Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button on the remote controller for power ON, and check for the electromagnetic noise.
3) After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the electromagnetic noise.
4) Press OPERATE/STOP (ON/OFF) button on the remote controller for power OFF, when the outdoor unit stops but the indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise.
OBH590B
44
O Check of defrost heater
Check the following points before checking electric continuity.
1. Does the resistance of ambient temperature thermistor have the characteristics? Refer to 11-6.1.
2. Is the resistance of defrost heater normal? Refer to 11-4.
3. Does the heater protector remain conducted (not open)?
4. Are both ambient temperature thermistor and circuit of defrost heater securely connected to connectors?
Is there 230 VAC between CN722
and on
the inverter P.C. board? Refer to 11-6.1.
Not the problem of the inverter P.C. board.
Replace the inverter P.C. board.
No
Yes
In HEAT mode, for more than 5 minutes, let the ambient temperature thermistor continue to read 5°C or below, and let the defrost thermistor continue to read -1°C or below.
NOTE: In case both thermistors are more than the above temperature, cool them with cold
water etc...
MUZ-EF•VEH
OBH590B
45
-20 -10 0 10 20 30 40
0
10
20
30
40
50
60
70
80
90
100
Temperature( )
Defrost thermistor(RT61) Ambient temperature thermistor(RT65) Outdoor heat exchanger temperature thermistor(RT68)
Temperature( )
Discharge temperature thermistor(RT62)
0 10 20 30 40 50 60 70 80 90 100 110 120
0
100
200
300
400
500
600
700
0 1020304050607080
0
20
40
60
80
100
120
140
160
180
200
Temperature( )
Fin temperature thermistor(RT64)
Resistance(k )
Resistance(k )
Resistance(k )
1. Inverter P.C. board
MUZ-EF25VE MUZ-EF25VEH MUZ-EF35VE MUZ-EF35VEH MUZ-EF42VE MUZ-EF50VE
11-6. TEST POINT DIAGRAM AND VOLTAGE
Fin temperature
thermistor/RT64
(CN642)
Ambient temperature
thermistor/RT65
(CN643)
Discharge temperature
thermistor/RT62
(CN641)
Defrost thermistor
/RT61(CN641)
DB61 260 - 370 VDC
Front side of unit
230 VAC
Smoothing capacitor (C62)
Output to drive compressor (LDU, LDV, LDW)
(+)
(-)
Fuse (F701) T3.15AL250V
Smoothing capacitor (C61)
Smoothing capacitor (C63)
MUZ-EF42/50VE
Fuse (F901) T3.15AL250V
R.V.coil (CN721) 230 VAC
Jumper wire for changing defrost setting (JS)
Signal of outdoor
fan motor (CN931)
230 VAC
Outdoor heat exchanger
temperature thermistor
/RT68 (CN644)
Jumper wire for pre-heat control setting (JK)
Heater connector (CN722)
MUZ-EF25/35VEH MUZ-EF42/50VE
Fuse (F801) T3.15AL250V
Back side of unit
LEV connector
(CN724)
Output to drive outdoor fan motor (CN932)
LED
OBH590B
46
12-1. MUZ-EF25VE MUZ-EF25VEH MUZ-EF35VE MUZ-EF35VEH MUZ-EF42VE
NOTE: Turn OFF power supply before disassembly.
OPERATING PROCEDURE PHOTOS
1. Removing the cabinet
(1) Remove the screw fixing the service panel. (2) Pull down the service panel and remove it. (3) Disconnect the power supply and indoor/outdoor con-
necting wire. (4) Remove the screws fixing the top panel. (5) Remove the top panel. (6) Remove the screws fixing the cabinet. (7) Remove the cabinet. (8) Remove the screws fixing the back panel. (9) Remove the back panel.
Photo 1
Photo 2
(1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector has the
locking mechanism.
Slide the sleeve. Pull the terminal while pushing the locking lever.
Hold the sleeve, and pull out the terminal slowly.
Connector
Sleeve
Locking lever
Back panel
Service
panel
Screws of the top panel
Screws of the cabinet
Screws of the top panel
Screw of the service panel
Direction to remove
Screws of
the cabinet
Hooks
<"Terminal with locking mechanism" Detaching points>
The terminal which has the locking mechanism can be detached as shown below. There are two types (refer to (1) and (2)) of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching.
DISASSEMBLY INSTRUCTIONS
12
Screw of the cabinet
Screw of the back panel
Screws of the terminal block support and the back panel
OBH590B
47
OPERATING PROCEDURE
PHOTOS
2. Removing the inverter assembly, inverter P.C. board
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following con-
nectors:
<Inverter P.C. board>
CN721 (R.V. coil) CN722 (Defrost heater) CN931, CN932 (Fan motor) CN641 (Defrost thermistor and discharge temperature ther-
mistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor) CN724 (LEV)
(3) Remove the compressor connector (CN61). (4) Remove the screws fixing the heat sink support and the sep-
arator.
(5) Remove the fixing screws of the terminal block support and
the back panel.
(6) Remove the inverter assembly. (7) Remove the screw of the earth wire and screw of the termi-
nal block support.
(8) Remove the heat sink support from the P.C. board support. (9) Remove the screw of the inverter P.C. board and remove the
inverter P.C. board from the P.C. board support.
Photo 3
Photo 4 (Inverter assembly)
Photo 5
3. Removing R.V. coil
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the following connectors: <Inverter P.C. board>
CN721 (R.V. coil)
(3) Remove the R.V. coil.
4. Removing the discharge temperature thermistor, defrost thermistor, outdoor heat exchanger tempera­ture thermistor and ambient temperature thermistor
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following con-
nectors: <Inverter P.C. board> CN641 (Defrost thermistor and discharge temperature ther-
mistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor)
(3) Pull out the discharge temperature thermistor from its holder. (4) Pull out the defrost thermistor from its holder. (Photo 6) (5) Pull out the outdoor heat exchanger temperature thermistor
from its holder. (Photo 6)
(6) Pull out the ambient temperature thermistor from its holder.
Discharge temperature thermistor
Screw of the R.V. coil
Screws of the heat sink support and the separator
Heat sink
Screw of the earth wire
Screw of the Terminal block support
47
Screw of the inverter P.C. board
Screws of the terminal block support and the back panel
Heat sink support
P.C. board support
Terminal block support
OBH590B
48
OPERATING PROCEDURE
PHOTOS
5. Removing outdoor fan motor
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the following connectors: <Inverter P.C. board>
CN931, CN932 (Fan motor) (3) Remove the propeller nut. (4) Remove the propeller. (5) Remove the screws fixing the fan motor. (6) Remove the fan motor.
Photo 6
Photo 7
Photo 8
6. Removing the compressor and 4-way valve
(1) Remove the cabinet and panels. (Refer to 1.) (2) Remove the inverter assembly. (Refer to 2.) (3) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure gauge
shows 0 kg/cm2 (0 MPa).
(4) Detach the brazed part of the suction and the discharge pipe
connected with compressor. (5) Remove the nuts of compressor legs. (6) Remove the compressor. (7) Detach the brazed part of pipes connected with 4-way valve.
Defrost thermistor
Outdoor heat exchanger tempera­ture thermistor
Propeller nut
Screws of the outdoor fan motor
Propeller
Brazed parts of 4-way valve
Ambient temperature thermistor
OBH590B
49
12-2. MUZ-EF50VE
NOTE: Turn OFF power supply before disassembly.
OPERATING PROCEDURE
PHOTOS
1. Removing the cabinet
(1) Remove the screws of the service panel. (2) Remove the screws of the top panel. (3) Remove the screw of the valve cover. (4) Remove the service panel. (5) Remove the top panel. (6) Remove the valve cover. (7) Disconnect the power supply and indoor/outdoor connect-
ing wire. (8) Remove the screws of the cabinet. (9) Remove the cabinet. (10)
Remove the screws of the back panel.
(11)
Remove the back panel.
Photo 1
Photo 2
Screws of the cabinet
Screws of the top panel
Screws of the top panel
Screw of the back panel
Screws of the cabinet
Screws of the cabinet
Screws of the service panel
Screw of the valve cover
Screws of the cabinet
Screws of the back panel
Screws of the cabinet
OBH590B
50
OPERATING PROCEDURE
PHOTOS
2. Removing the inverter assembly, inverter P.C. board
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following con-
nectors: <Inverter P.C. board> CN721 (R.V. coil) CN931, CN932 (Fan motor) CN641 (Defrost thermistor and discharge temperature ther-
mistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor) CN724 (LEV)
(3) Remove the compressor connector. (4) Remove the screws fixing the heat sink support and the sep-
arator.
(5) Remove the fixing screws of the terminal block support and
the back panel.
(6) Remove the inverter assembly. (7) Remove the screw of the earth wire, screw of the P.C. board
cover and screws of the terminal block support.
(8) Remove the heat sink support from the P.C. board support. (9) Remove the screw of the inverter P.C. board and the inverter
P.C. board from the P.C. board support.
Photo 3
Photo 4
Photo 5
3. Removing R.V. coil
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the following connector: <Inverter P.C. board>
CN721 (R.V. coil)
(3) Remove the R.V. coil.
Screw of the heat sink support and the separator
Brazed parts of 4-way valve
Screw of the R.V. coil
Heat sink
Screw of the inverter P.C. board
Screw of the earth wire
Screws of the terminal block support
Screw of the P.C. board cover
Screw of the terminal block support and the back panel
P.C. board support
Heat sink support
OBH590B
51
OPERATING PROCEDURE PHOTOS
4. Removing the discharge temperature thermistor, defrost thermistor, outdoor heat exchanger tempera­ture thermistor and ambient temperature thermistor
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following
connectors: <Inverter P.C. board> CN641 (Defrost thermistor and discharge temperature ther-
mistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor)
(3) Pull out the discharge temperature thermistor from its hold-
er. (4) Pull out the defrost thermistor from its holder. (5) Pull out the outdoor heat exchanger temperature thermistor
from its holder. (6) Pull out the ambient temperature thermistor from its holder.
Photo 6
Photo 7
Photo 8
5. Removing outdoor fan motor
(1)
Remove the top panel, cabinet and service panel. (Refer to 1.)
(2) Disconnect the following connectors:
<Inverter P.C. board>
CN931 and CN932 (Fan motor)
(3) Remove the propeller nut. (4) Remove the propeller. (5) Remove the screws fixing the fan motor. (6) Remove the fan motor.
6. Removing the compressor and 4-way valve
(1)
Remove the top panel, cabinet and service panel. (Refer to 1.) (2) Remove the back panel. (Refer to 1.) (3) Remove the inverter assembly. (Refer to 2.) (4) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure gauge
shows 0 kg/cm2 (0 MPa).
(5) Detach the brazed part of the suction and the discharge
pipe connected with compressor. (6) Remove the compressor nuts. (7) Remove the compressor. (8) Detach the brazed part of 4-way valve and pipe. (Photo 5)
Screws of the outdoor fan motor
Brazed part of the discharge pipe
Brazed part of the suction pipe
Discharge temperature thermistor
Outdoor heat exchanger tempera­ture thermistor
Ambient tem­perature thermistor
Defrost thermistor
Propeller nut
51
OBH590B
© Copyright 2010 MITSUBISHI ELECTRIC CORPORATION Distributed in Nov. 2012. No. OBH590 REVISED EDITION-B Distributed in Mar. 2011. No. OBH590 REVISED EDITION-A Distributed in Nov. 2010. No. OBH590 Made in Japan