Mitsubishi MUZ-AP42VG - ET1, MUZ-AP25VG - ET1, MUZ-AP50VG - E1, MUZ-AP50VG - ET1, MUZ-AP25VGH - E1 Service Manual

...
No. OBH789
Indoor unit service manual MSZ-AP•VG(K) Series (OBH788)
PARTS CATALOG (OBB789)
HFC
utilized
SERVICE MANUAL
OUTDOOR UNIT
NOTE:
RoHS compliant products have <G> mark on the spec name plate.
CONTENTS
1. TECHNICAL CHANGES ···································2
2. SERVICING PRECAUTIONS FOR UNITS USING REFRIGERANT R32 ····························· 3
3. PART NAMES AND FUNCTIONS ····················· 5
4. SPECIFICATION ················································ 6
5. NOISE CRITERIA CURVES ······························ 7
6. OUTLINES AND DIMENSIONS ························ 9
7. WIRING DIAGRAM ·········································· 10
8. REFRIGERANT SYSTEM DIAGRAM ············· 13
9. PERFORMANCE CURVES ····························· 15
10. ACTUA TOR CONTROL ··································· 29
11. SERVICE FUNCTIONS ···································· 30
12. TROUBLESHOOTING ····································· 31
13. DISASSEMBLY INSTRUCTIONS ···················· 51
Models MUZ-AP25VG
-
E1,
ET1
MUZ-AP25VGH
-
E1
MUZ-AP35VG
-
E1,
ET1
MUZ-AP35VGH
-
E1
MUZ-AP42VG
-
E1,
ET1
MUZ-AP42VGH
-
E1
MUZ-AP50VG
-
E1,
ET1
MUZ-AP50VGH
-
E1
MUZ-AP25VG MUZ-AP35VG MUZ-AP42VG
MUZ-AP25VGH MUZ-AP35VGH MUZ-AP42VGH
2
MUZ-AP25VG
-
E1, ET1
MUZ-AP35VG
-
E1, ET1
MUZ-AP42VG
-
E1, ET1
MUZ-AP50VG
-
E1, ET1
MUZ-AP25VGH
-
E1
MUZ-AP35VGH
-
E1
MUZ-AP42VGH
-
E1
MUZ-AP50VGH
-
E1
1. New model
<Preparation before the repair service>
Prepare the proper tools. Prepare the proper protectors. Provide adequate ventilation. After stopping the operation of the air conditioner, turn off the power-supply breaker and remove the power plug. Discharge the capacitor before the work involving the electric parts.
<Precautions during the repair service>
Do not perform the work involving the electric parts with wet hands. Do not pour water into the electric parts. Do not touch the refrigerant. Do not touch the hot or cold areas in the refrigeration cycle. When the repair or the inspection of the circuit needs to be done without turning off the power, exercise great caution not to
touch the live parts.
Use the specifi ed refrigerant only
Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of. Correct refrigerant is specified in the manuals and on the spec labels provided with our products. We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions.
TECHNICAL CHANGES
1
OBH789
3
2
SERVICING PRECAUTIONS FOR UNITS USING REFRIGERANT R32
Servicing precautions for units using refrigerant R32
WARNING
This unit uses a flammable refrigerant. If refrigerant leaks and comes in contact with fire or heating part, it will create harmful gas and there is risk of fire.
Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer. The appliance shall be stored in a room without continuously operating ignition sources (for example: open flames, an operating gas appliance or an operating
electric heater.)
Do not pierce or burn. Be aware that refrigerants may not contain an odor. Pipe-work shall be protected from physical damage. The installation of pipe-work shall be kept to a minimum. Compliance with national gas regulations shall be observed. Keep any required ventilation openings clear of obstruction. Servicing shall be performed only as recommended by the manufacturer. The appliance shall be stored so as to prevent mechanical damage from occurring.
Basic work procedures are the same as those for conventional units using refrigerant R410A. However, pay careful attention to the following points.
1. Information on servicing Checks on the Area
Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimized.
Work Procedure
Work shall be undertaken under a controlled procedure so as to minimize the risk of a flammable gas or vapor being present while the work is being performed.
General Work Area
All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out. Work in confined spaces shall be avoided. The area around the workspace shall be sectioned off. Ensure that the conditions within the area have been made safe by control of flammable material.
Checking for Presence of Refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially toxic or flammable atmospheres. Ensure that the leak detection equipment being used is suitable for use with all applicable refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe.
Presence of Fire Extinguisher
If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire extinguishing equipment shall be available to hand. Have a dry powder or CO2 fire extinguisher adjacent to the charging area.
No Ignition Sources
No person carrying out work in relation to a refrigeration system which involves exposing any pipe work shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition sources, including cigarette smoking, should be kept sufficiently far away from the site of installa­ tion, repairing, removing and disposal, during which refrigerant can possibly be released to the surrounding space. Prior to work taking place, the area around the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks. "No Smoking" signs shall be displayed.
Ventilated Area
Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. A degree of ventilation shall continue during the period that the work is carried out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere.
Checks on the Refrigeration Equipment
Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the manufacturer's maintenance and service guidelines shall be followed. If in doubt, consult the manufacturer's technical department for assistance. The following checks shall be applied to installations using flammable refrigerants:
• The charge size is in accordance with the room size within which the refrigerant containing parts are installed.
• The ventilation machinery and outlets are operating adequately and are not obstructed.
• If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant.
• Marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected.
• Refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing
components, unless the components are constructed of materials which are inherently resistant to being corroded or are suitably protected against being cor­ roded.
Checks on Electrical Devices
Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures. If a fault exists that could compro­ mise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is nec­ essary to continue operation, an adequate temporary solution shall be used. This shall be reported to the owner of the equipment so all parties are advised. Initial safety checks shall include that:
• capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking;
• no live electrical components and wiring are exposed while charging, recovering or purging the system;
• there is continuity of earth bonding
2. Repairs to Sealed Components During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers,
etc. If it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation.
Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not altered in such a way that the level of
protection is affected. This shall include damage to cables, excessive number of connections, terminals not made to original specification, damage to seals, incorrect fitting of glands, etc. Ensure that the apparatus is mounted securely. Ensure that seals or sealing materials have not degraded to the point that they no longer serve the purpose of preventing the ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer's specifications.
3. Repair to intrinsically Safe Components
Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted for the equipment in use. Intrinsically safe components are the only types that can be worked on while live in the presence of a flammable atmosphere. The test apparatus shall be at the correct rating. Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere from a leak.
4. Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans.
OBH789
4
5. Detection of Flammable Refrigerants Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.
6. Leak Detection Methods Electronic leak detectors may be used to detect refrigerant leaks but, in the case of flammable refrigerants, the sensitivity may not be adequate, or may need re-calibration. (Detection equipment shall be calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed, and the appropriate percentage of gas (25 % maximum) is confirmed. Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work. If a leak is suspected, all naked flames shall be removed/extinguished. If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by means of shut off valves) in a part of the system remote from the leak. For appliances containing flammable refrigerants, oxygen free nitrogen (OFN) shall then be purged through the sys­ tem both before and during the brazing process.
7. Removal and Evacuation When breaking into the refrigerant circuit to make repairs - or for any other purpose conventional procedures shall be used. However, for flammable refrigerants it is important that best practice is followed since flammability is a consideration. The following procedure shall be adhered to: ▪ remove refrigerant ▪ purge the circuit with inert gas ▪ evacuate ▪ purge again with inert gas ▪ open the circuit by cutting or brazing. The refrigerant charge shall be recovered into the correct recovery cylinders. For appliances containing flammable refrigerants, the system shall be "flushed" with OFN to render the unit safe. This process may need to be repeated several times. Compressed air or oxygen shall not be used for purging refrigerant sys­ tems. For appliances containing flammable refrigerants, flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system. When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take place. This operation is abso- lutely vital if brazing operations on the pipe-work are to take place. Ensure that the outlet for the vacuum pump is not close to any ignition sources and that ventilation is available.
8. Charging Procedures In addition to conventional charging procedures, the following requirements shall be followed: ▪ Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in them. ▪ Cylinders shall be kept upright. ▪ Ensure that the refrigeration system is earthed prior to charging the system with refrigerant. ▪ Label the system when charging is complete (if not already). ▪ Extreme care shall be taken not to overfill the refrigeration system. Prior to recharging the system, it shall be pressure-tested with the appropriate purging gas. The system shall be leak-tested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the site.
9. Decommissioning Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re­ use of reclaimed refrigerant. It is essential that electrical power is available before the task is commenced. a) Become familiar with the equipment and its operation. b) Isolate system electrically. c) Before attempting the procedure, ensure that:
- mechanical handling equipment is available, if required, for handling refrigerant cylinders;
- all personal protective equipment is available and being used correctly;
- the recovery process is supervised at all times by a competent person;
- recovery equipment and cylinders conform to the appropriate standards. d) Pump down refrigerant system, if possible. e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system. f) Make sure that cylinder is situated on the scales before recovery takes place. g) Start the recovery machine and operate in accordance with manufacturer's instructions. h) Do not overfill cylinders. (no more than 80 % volume liquid charge). i) Do not exceed the maximum working pressure of the cylinder, even temporarily. j) When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are removed from site promptly and all isolation valves on the equipment are closed off. k) Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked.
10. Labeling Equipment shall be labeled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated and signed. For appliances containing flammable refrigerants, ensure that there are labels on the equipment stating the equipment contains flammable refrigerant.
11. Recovery When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cyl­ inders for holding the total system charge are available. All cylinders to be used are designated for the recovered refrigerant and labeled for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure-relief valve and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs. The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recov­ ery of all appropriate refrigerants including, when applicable, flammable refrigerants. In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be complete with leak-free disconnect couplings and in good condition. Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refriger­ ant release. Consult manufacturer if in doubt. The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant waste transfer note arranged. Do not mix refrigerants in recovery units and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certa
in that flammable refriger­ ant does not remain within the lubricant. The evacuation process shall be carried out prior to returning the compressor to the suppliers. Only electric heating to the compressor body shall be employed to accelerate this process. When oil is drained from a system, it shall be carried out safely.
OBH789
5
Air outlet
Drain outlet
Piping
Drain hose
Air inlet
(back and side)
MUZ-AP25VG MUZ-AP35VG MUZ-AP42VG MUZ-AP25VGH MUZ-AP35VGH MUZ-AP42VGH
PART NAMES AND FUNCTIONS
3
ACCESSORIES
MODELS
MUZ-AP25VG MUZ-AP35VG MUZ-AP42VG MUZ-AP50VG
Drain socket 1
MUZ-AP50VG MUZ-AP50VGH
Air outlet
Drain outlet
Piping
Drain hose
Air inlet
(back and side)
OBH789
6
1 Measured under rated operating frequency.
Outdoor model
MUZ-AP25VG
MUZ-AP25VGH
MUZ-AP35VG
MUZ-AP35VGH
MUZ-AP42VG
MUZ-AP42VGH
MUZ-AP50VG
MUZ-AP50VGH
Power supply Single phase, 230 V, 50 Hz
Capacity Rated frequency (Min.-Max.)
Cooling
kW
2.5 (0.9 - 3.4) 3.5 (1.1 - 3.8) 4.2 (0.9 - 4.5) 5.0 (1.4 - 5.4)
Heating 3.2 (1.0 - 4.1) 4.0 (1.3 - 4.6) 5.4 (1.3 - 6.0) 5.8 (1.4 - 7.3)
Breaker Capacity A 10 16
Electrical data
Power input 1 (Set)
Cooling
W
600 990 1,300 1,550
Heating 780 1,030 1,490 1,600
Running current
1
(Set)
Cooling
A
2.9 4.5 5.8 6.9
Heating 3.6 4.7 6.6 7.0
Power factor
1 (Set)
Cooling
%
89 95 97 97
Heating 94 95 98 99
Starting current
1 (Set) A 3.6 4.7 6.6 7.0
Coeffi cient of performance (COP) 1 (Set)
Cooling 4.17 3.54 3.23 3.23 Heating 4.10 3.88 3.62 3.63
Compressor
Model KVB073FYXMC KVB073FYXMC SVB130FBBMC SVB130FBBMT Output W 470 470 900 900
Current
1
Cooling
A
2.50 4.10 5.42 6.39
Heating 3.14 4.20 6.05 6.41
Refrigeration oil (Model) L 0.27 (FW68S) 0.35 (FW68S)
Fan motor
Model RC0J50-NC RC0J50-RA Current
1
Cooling
A
0.22 0.22 0.20 0.27
Heating 0.20 0.24 0.23 0.27 Dimensions W × H × D mm 800 × 550 × 285 800 × 714 × 285 Weight kg 31 31 35 40
Special remarks
Dehumidifi cation Cooling L/h 0.3 0.6 1.4 1.9
Air fl ow
1
Cooling
High
m3/h
2,178 2,178 2,058 2,430
Low 1,038 1,038 906 1,320
Heating
High 2,076 2,076 1,962 2,430 Med. 1,788 1,788 1,686 2,238
Low 1,452 1,452 1,260 1,704
Sound level
1
Cooling
dB(A)
47 49 50 52
Heating 48 50 51 52
Fan speed
Cooling
High
rpm
940 940 940 840
Low 470 470 460 490
Heating
High 900 900 900 840 Med. 780 780 780 780
Low 640 640 600 610 Fan speed regulator 3 Refrigerant fi lling capacity (R32) kg 0.55 0.55 0.70 1.00
NOTE: Test conditions are based on ISO 5151. Cooling: Indoor Dry-bulb temperature 27°C Wet-bulb temperature 19°C Outdoor Dry-bulb temperature 35°C Wet-bulb temperature 24°C Heating: Indoor Dry-bulb temperature 20°C Wet-bulb temperature 15°C Outdoor Dry-bulb temperature 7°C Wet-bulb temperature 6°C Refrigerant piping length (one way): 5 m
SPECIFICATION
4
OBH789
7
Specifi cations and rated conditions of main electric parts
Model
Item
MUZ-
AP25VG
MUZ-
AP25VGH
MUZ-
AP35VG
MUZ-
AP35VGH
MUZ-
AP42VG
MUZ-
AP42VGH
MUZ-
AP50VG
MUZ-
AP50VGH
Smoothing capacitor
(C61) — 600 μF/ 620 μF 420 V
(C62, C63) 600 μF/ 620 μF 420 V Diode module (DB61) 15 A 600 V 25 A 600 V Diode module (DB65) 25 A 600 V
Fuse
(F61) 25A 250V (F62) 15A 250V
(F701, F801, F901)
T3.15AL250V
Defrost heater (H)
230 V
60W
230 V
60W
230 V
60W
230 V 130W
Power module
(IC700) 15 A 600 V 20 A 600 V (IC932) 5 A 600 V
Expansion valve coil
(LEV) 12 V DC
Reactor (L61) 18 mH 23 mH Switch power
transistor
(Q821) 30 A 600 V
Current-limiting PTC thermistor
(PTC64, PTC65)
33 Ω
Terminal block (TB1) 5 P
Relay
(X63) 3 A 250 V (X64) 20 A 250 V (X66) 3 A 250 V 3 A 250 V 3 A 250 V 3 A 250 V
(X69) 10 A 230 V R.V.coil (21S4) 220 - 240 V AC Heater protector (26H)
Open 45°C
Open 45°C
Open 45°C
Open 45°C
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
COOLING
FUNCTION
SPL(dB(A)) LINE
HEATING
47 48
NC-10
MUZ-AP25VG MUZ-AP25VGH
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
COOLING
FUNCTION
SPL(dB(A))
LINE
HEATING
49 50
NC-10
MUZ-AP35VG MUZ-AP35VGH
NOISE CRITERIA CURVES
5
OBH789
8
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
COOLING
FUNCTION
SPL(dB(A)) LINE
HEATING
50
NC-10
51
MUZ-AP42VG MUZ-AP42VGH
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
COOLING
FUNCTION
SPL(dB(A)) LINE
HEATING
52
NC-10
52
MUZ-AP50VG MUZ-AP50VGH
Test conditions Cooling: Dry-bulb temperature 35°C Wet-bulb temperature 24°C Heating: Dry-bulb temperature 7°C Wet-bulb temperature 6°C
OUTDOOR UNIT
MICROPHONE
1 m
OBH789
9
Unit: mm
MUZ-AP25VG MUZ-AP35VG MUZ-AP42VG MUZ-AP25VGH MUZ-AP35VGH MUZ-AP42VGH
(MUZ-AP25/35/42VG) (MUZ-AP25/35/42VGH)
MUZ-AP50VG MUZ-AP50VGH
OUTLINES AND DIMENSIONS
6
(MUZ-AP50VG) (MUZ-AP50VGH)
OBH789
10
WIRING DIAGRAM
7
MUZ-AP25VG -E1,
ET1
MUZ-AP35VG -E1,
ET1
MUZ-AP25VGH -
E1
MUZ-AP35VGH -
E1
OBH789
11
MUZ-AP42VG -E1,
ET1
MUZ-AP42VGH -
E1
OBH789
12
MUZ-AP50VG -E1,
ET1
MUZ-AP50VGH -
E1
OBH789
13
Unit: mm
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve (with strainar)
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe ø9.52 (with heat insulator)
Refrigerant pipe ø6.35 (with heat insulator)
R.V. coil heating ON cooling OFF
Strainer #100
LEV
Ambient temperature thermistor RT65
Muffler
Capillary tube ø4.0×ø2.4×240
Outdoor heat exchanger temperature thermistor RT68
Stop valve (with service port)
Muffler
REFRIGERANT SYSTEM DIAGRAM
8
Unit: mm
MUZ-AP42VG MUZ-AP42VGH
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve (with strainar)
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe ø9.52 (with heat insulator)
Refrigerant pipe ø6.35 (with heat insulator)
R.V. coil heating ON cooling OFF
Strainer #100
LEV
Ambient temperature thermistor RT65
Muffler
Capillary tube ø4.0×ø2.4×240
Outdoor heat exchanger temperature thermistor RT68
Stop valve (with service port)
Muffler
MUZ-AP25VG MUZ-AP35VG MUZ-AP25VGH MUZ-AP35VGH
OBH789
14
MUZ-AP50VG MUZ-AP50VGH
Unit: mm
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve (With strainer)
Stop valve (with service port)
Capillary tube ø
4.0×ø
2.4×240
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe
ø
9.52
(with heat insulator)
Refrigerant pipe ø6.35 (with heat insulator)
LEV
R.V. coil heating ON cooling OFF
Muffler
Outdoor heat exchanger temperature thermistor RT68
Ambient temperature thermistor RT65
Strainer
#100
Muffler
Capillary tube ø3.0×ø2.0×210(×2)
Max. Length A
Max. Height
difference
B
Indoor unit
Outdoor unit
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Model
Refrigerant piping: m Piping size O.D: mm
Max. Length A Max. Height difference B Gas Liquid
MUZ-AP25/35/42/50VG(H) 20 12 9.52 6.35
ADDITIONAL REFRIGERANT CHARGE (R32: g)
Model
Outdoor unit
precharged
Refrigerant piping length (one way)
7 m 8 m 9 m 10 m 11 m 12 m 13 m 14 m 15 m 20 m
MUZ-AP25VG(H)
550
0 20 40 60 80 100 120 140 160 260
MUZ-AP35VG(H) MUZ-AP42VG(H) 700 MUZ-AP50VG(H) 1,000
Calculation: X g = 20 g/m × (Refrigerant piping length (m) – 7) NOTE: Refrigerant piping exceeding 7 m requires additional refrigerant charge according to the calculation.
OBH789
15
The standard specifications apply only to the operation of the air conditioner under normal conditions. Since operating condi­tions vary according to the areas where these units are installed, the following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198 ~ 264 V, 50 Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature: °C [WB]
}
Cooling
(2) Indoor outlet air wet-bulb temperature: °C [WB] (3) Outdoor intake air dry-bulb temperature: °C [DB] (4) Total input: W (5) Indoor intake air dry-bulb temperature: °C [DB]
}
Heating(6) Outdoor intake air wet-bulb temperature: °C [WB]
(7) Total input: W
Indoor air wet and dry bulb temperature difference on the left side of the following chart shows the difference between the
indoor intake air wet and dry bulb temperature and the indoor outlet air wet and dry bulb temperature for your reference at service.
How to measure the indoor air wet and dry bulb temperature difference
1. Attach at least 2 sets of wet and dry bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet and dry bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.
2. Attach at least 2 sets of wet and dry bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once (twice) to start the EMERGENCY COOL (HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
MUZ-AP25VG MUZ-AP35VG MUZ-AP42VG MUZ-AP50VG MUZ-AP25VGH MUZ-AP35VGH MUZ-AP42VGH MUZ-AP50VGH
INDOOR UNIT
OUTDOOR UNIT
Wet and dry bulb thermometers FRONT VIEW
Wet and dry bulb thermometers BACK VIEW
Cooling capacity (
at Rated frequency)
0.9
1.0
1.1
1.2
1.3
1.4
1.5
-10-5 0 5 1015202530354045 Outdoor intake air Dry-bulb temperature(°C)
Capacity correction factors
26
24
20 18
22
Indoor intake air Wet-bulb temperature( )
10.7
9.9
9.0
8.2
7.4
6.7
5.9
MUZ-AP50VG
MUZ-AP42VG
MUZ-AP35VG
MUZ-AP25VG
Indoor air Wet-bulb temperature
difference (°C)
5.9
5.4
5.0
4.6
4.2
3.8
3.4
8.6
7.9
7.3
6.7
6.0
5.4
4.8
11.7
10.8
9.9
9.0
8.1
7.2
6.4
MUZ-AP25VGH
MUZ-AP50VGH
MUZ-AP42VGH
MUZ-AP35VGH
9-1. CAPACITY AND INPUT CURVES
PERFORMANCE CURVES
9
OBH789
16
NOTE: The above broken lines are for the heating operation without any frost and defrost operation.
0.8
0.9
1.0
1.1
1.2
1.3
-10-5 0 5 1015202530354045 Outdoor intake air Dry-bulb temperature (°C)
Input correction factors
26
24
22 20 18
Indoor intake air Wet-bulb temperature( )
Indoor air Wet-bulb temperature
difference (°C)
5.0
4.6
4.2
3.8
3.4
3.0
7.3
6.7
6.0
5.4
4.8
4.2
9.0
8.2
7.4
6.7
5.9
5.2
9.9
9.0
8.1
7.2
6.4
5.6
MUZ-AP50VG
MUZ-AP42VG
MUZ-AP35VG
MUZ-AP25VG
MUZ-AP25VGH
MUZ-AP50VGH
MUZ-AP42VGH
MUZ-AP35VGH
Total input (Cooling :
at Rated frequency
)
Indoor air Dry-bulb temperature
difference (°C)
16.2
15.0
13.7
12.5
11.2
10.0
8.7
7.5
6.2
5.0
25.2
23.3
21.3
19.4
17.5
15.5
13.6
11.6
9.7
7.8
27.1
25.0
22.9
20.8
18.8
16.7
14.6
12.5
10.4
8.3
20.3
18.7
17.2
15.6
14.0
12.5
10.9
9.4
7.8
6.2
MUZ-AP50VG
MUZ-AP42VG
MUZ-AP35VG
MUZ-AP25VG
MUZ-AP25VGH
MUZ-AP50VGH
MUZ-AP42VGH
MUZ-AP35VGH
Outdoor intake air Wet-bulb temperature (°C)
-20 -15 -10 -5 0 5 10 15
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
Heating capacity (
at Rated frequency)
Capacity correction factor
15
20
26
Indoor intake air Dry-bulb temperature ( )
Indoor air Dry-bulb temperature
difference (°C)
16.2
15.0
13.7
12.5
11.2
10.0
8.7
7.5
6.2
5.0
20.3
18.7
17.2
15.6
14.0
12.5
10.9
9.4
7.8
6.2
25.2
23.3
21.3
19.4
17.5
15.5
13.6
11.6
9.7
7.8
27.1
25.0
22.9
20.8
18.8
16.7
14.6
12.5
10.4
8.3
MUZ-AP50VG
MUZ-AP42VG
MUZ-AP35VG
MUZ-AP25VG
MUZ-AP25VGH
MUZ-AP50VGH
MUZ-AP42VGH
MUZ-AP35VGH
Outdoor intake air Wet-bulb temperature (°C)
-20 -15 -10 -5 0 5 10 15
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
Total input (Heating :
at Rated frequency
)
Input correction factor
15
20
26
Indoor intake air Dry-bulb temperature ( )
Lower limit of guaranteed operating range in heating MUZ-AP25/35/42/50VG: -15°C MUZ-AP25/35/42/50VGH: -20°C
OBH789
17
9-2. CAPACITY AND INPUT CORRECTION BY OPERATIONAL FREQUENCY OF COMPRESSOR
0 50 100
150
0.5
1.0
1.5
0 50 100
150
0.5
1.0
1.5
0 50 100
0.5
1.0
1.5
0 50 100
0.5
1.0
1.5
2.0
0 50 100
150
0.5
1.0
1.5
050100
150
0.5
1.0
1.5
0 50 100
150
0.5
1.0
1.5
0 50 100
150
0.5
1.0
1.5
2.0
0 50 100
0.5
1.0
1.5
0 50 100
0.5
1.0
1.5
2.0
0 50 100
0.5
1.0
1.5
0 50 100
0.5
1.0
1.5
2.0
0 50 100
150
0.5
1.0
1.5
050100
150
0.5
1.0
1.5
2.0
0 50 100
150
0.5
1.0
1.5
050100
150
0.5
1.0
1.5
2.0
MUZ-AP25VG MUZ-AP25VGH
MUZ-AP35VG MUZ-AP35VGH
Correction of Cooling capacity
Capacity correction factors
Correction of Cooling input
Input correction factors
Correction of Heating capacity
Capacity correction factors
MUZ-AP42VG MUZ-AP42VGH
Correction of Heating input
Capacity correction factors
Correction of Cooling capacity
Capacity correction factors
Correction of Cooling input
Input correction factors
Correction of Heating capacity
Capacity correction factors
MUZ-AP50VG MUZ-AP50VGH
Correction of Heating input
Capacity correction factors
The operatio na l freq uency of compressor (Hz)
The operatio na l freq uency of compressor (Hz)
The operatio na l freq uency of compressor (Hz)
The operatio na l freq uency of compressor (Hz)
The op erat i o na l frequency of compressor (Hz)
The op erat i o na l frequency of compressor (Hz)
The operational frequency of compressor (Hz)
The operational frequency of compressor (Hz)
Correction of Cooling ca pa ci ty
The operatio na l freq uency of compressor (Hz)
Ca pacity correct io n f a ct o rs
Correction of Cooling input
The operational frequency of compressor (Hz)
In put correction factors
Correction of Heati ng capacity
The operational frequency of compressor (Hz)
Capacity correction factors
Correction of Heati ng input
The operational frequency of compressor (Hz)
Input correction factors
Co rrect io n o f C o o ling capacity
The op erat i o na l frequency of compressor (Hz)
Ca pacity correct io n f a ct o rs
Cor rection of Cooling input
The op erat i o na l frequency of compressor (Hz)
Inp ut correcti o n f a ct o rs
Correction of Heati ng capacity
The operational frequency of compressor (Hz)
Capacity correction factors
Correction of Heati ng input
The operational frequency of compressor (Hz)
Input correction factors
OBH789
18
15 20 25 30 35
0.5
0.7
0.9
1.1
1.3
1.5
15 20 25 30 35
0.5
0.6
0.7
0.8
0.9
1.0
15 20 25 30 35
0.5
0.7
0.9
1.1
1.3
1.5
15 20 25 30 35
0.5
0.7
0.9
1.1
1.3
1.5
(kgf/cm2 [Gauge])(MPa [Gauge])
9
7
5
11
13
15
(kgf/cm2 [Gauge])(MPa [Gauge])
7
6
5
8
9
10
(kgf/cm2 [Gauge])(MPa [Gauge])
5
9
11
7
13
15
(kgf/cm2 [Gauge])(MPa [Gauge])
7
9
3
11
13
15
50 60 70
Ambient temperature(°C) Ambient humi di ty ( %)
50 60 70
Ambient temperature(°C) Ambient humi di ty( %)
50 60 70
Ambient temperature(°C) Ambient humi dity(%)
50 60 70
Ambient temperature(°C) Ambient humi di ty( %)
Outdoor low pressure
MUZ-AP25VG MUZ-AP35VG
MUZ-AP42VG
MUZ-AP50VG
MUZ-AP25VGH
MUZ-AP35VGH MUZ-AP42VGH
MUZ-AP50VGH
COOL operation
Both indoor and outdoor unit are under the same temperature/
humidity condition.
Operation: TEST RUN OPERATION (Refer to 9-3.)
9-4. OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
Dry-bulb temperature (°C) Relative humidity (%)
20 50 25 60 30 70
9-3. HOW TO OPERATE FIXED-FREQUENCY OPERATION
<Test run operation>
1. Press EMERGENCY OPERATION switch to start COOL or HEAT mode (COOL: Press once, HEAT: Press twice).
2. Test run operation starts and continues to operate for 30 minutes.
3. Compressor operates at rated frequency in COOL mode or 58 Hz in HEAT mode.
4. Indoor fan operates at High speed.
5.
After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (operation frequency of compressor varies).
6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on remote controller.
NOTE: The unit of pressure has been changed to MPa on the international system of units (SI unit system) The conversion factor is: 1 (MPa [Gauge]) = 10.2 (kgf/cm
2
[Gauge])
OBH789
19
15 20 25 30 35
1.5
2.0
2.5
3.0
15 20 25 30 35
4
5
6
7
8
15 20 25 30 35
2.5
3.0
3.5
4.0
4.5
15 20 25 30 35
3.5
4.0
4.5
5.0
5.5
6.0
Ambient temperature(°C) Ambient humidity(%)
Ambient temperature (°C) Ambient humidity(%)
Ambient temperature (°C) Ambient humidity(%)
Outdoor current (A)Outdoor current (A)
Ambient temperature (°C) Ambient humidity(%)
Outdoor current (A)
Outdoor current (A)
MUZ-AP35VG MUZ-AP35VGH
MUZ-AP25VG MUZ-AP25VGH
Outdoor unit current
MUZ-AP42VG MUZ-AP42VGH
MUZ-AP50VG MUZ-AP50VGH
0510
15 20 25
2.0
2.5
3.0
3.5
4.0
0510
15
20 25
5.5
6.0
6.5
7.0
0510
15 20 25
2.0
2.5
3.0
3.5
4.0
0510
15
20
25
4.5
5.0
5.5
6.0
6.5
Ambient temperature (°C)
Outdoo r cu rren t ( A)
Ambient temperature (°C)
Outdoo r cu rren t ( A)
Ambient temperature (°C)
Outdoo r cu rren t ( A)
Ambient temperature (°C)
Outdoo r cu rren t ( A)
MUZ-AP35VG MUZ-AP35VGH
MUZ-AP25VG MUZ-AP25VGH
Outdoor unit current
MUZ-AP42VG MUZ-AP42VGH
MUZ-AP50VG MUZ-AP50VGH
Condition:
Operation: Test run operation (Refer to 9-3.)
HEAT operation
Indoor Outdoor
Dry bulb temperature (°C) 20.0 2 7 15 20.0
Wet bulb temperature (°C) 14.5 1 6 12 14.5
OBH789
20
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-AP25VG MUZ-AP25VGH
CAPACITY: 2.5 kW SHF: 0.92 INPUT: 600 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
21 25 27 30
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 2.94 2.17 0.74 480 2.81 2.08 0.74 504 2.70 2.00 0.74 528 2.60 1.92 0.74 552 21 20 3.06 1.90 0.62 504 2.94 1.82 0.62 534 2.85 1.77 0.62 546 2.75 1.71 0.62 570 22 18 2.94 2.29 0.78 480 2.81 2.19 0.78 504 2.70 2.11 0.78 528 2.60 2.03 0.78 552 22 20 3.06 2.02 0.66 504 2.94 1.94 0.66 534 2.85 1.88 0.66 546 2.75 1.82 0.66 570 22 22 3.19 1.72 0.54 522 3.08 1.66 0.54 555 3.00 1.62 0.54 570 2.88 1.55 0.54 594 23 18 2.94 2.41 0.82 480 2.81 2.31 0.82 504 2.70 2.21 0.82 528 2.60 2.13 0.82 552 23 20 3.06 2.14 0.70 504 2.94 2.06 0.70 534 2.85 2.00 0.70 546 2.75 1.93 0.70 570 23 22 3.19 1.85 0.58 522 3.08 1.78 0.58 555 3.00 1.74 0.58 570 2.88 1.67 0.58 594 24 18 2.94 2.53 0.86 480 2.81 2.42 0.86 504 2.70 2.32 0.86 528 2.60 2.24 0.86 552 24 20 3.06 2.27 0.74 504 2.94 2.17 0.74 534 2.85 2.11 0.74 546 2.75 2.04 0.74 570 24 22 3.19 1.98 0.62 522 3.08 1.91 0.62 555 3.00 1.86 0.62 570 2.88 1.78 0.62 594 24 24 3.35 1.68 0.50 546 3.23 1.61 0.50 576 3.15 1.58 0.50 594 3.05 1.53 0.50 624 25 18 2.94 2.64 0.90 480 2.81 2.53 0.90 504 2.70 2.43 0.90 528 2.60 2.34 0.90 552 25 20 3.06 2.39 0.78 504 2.94 2.29 0.78 534 2.85 2.22 0.78 546 2.75 2.15 0.78 570 25 22 3.19 2.10 0.66 522 3.08 2.03 0.66 555 3.00 1.98 0.66 570 2.88 1.90 0.66 594 25 24 3.35 1.81 0.54 546 3.23 1.74 0.54 576 3.15 1.70 0.54 594 3.05 1.65 0.54 624 26 18 2.94 2.76 0.94 480 2.81 2.64 0.94 504 2.70 2.54 0.94 528 2.60 2.44 0.94 552 26 20 3.06 2.51 0.82 504 2.94 2.41 0.82 534 2.85 2.34 0.82 546 2.75 2.26 0.82 570 26 22 3.19 2.23 0.70 522 3.08 2.15 0.70 555 3.00 2.10 0.70 570 2.88 2.01 0.70 594 26 24 3.35 1.94 0.58 546 3.23 1.87 0.58 576 3.15 1.83 0.58 594 3.05 1.77 0.58 624 26 26 3.45 1.59 0.46 576 3.35 1.54 0.46 606 3.30 1.52 0.46 624 3.20 1.47 0.46 642 27 18 2.94 2.88 0.98 480 2.81 2.76 0.98 504 2.70 2.65 0.98 528 2.60 2.55 0.98 552 27 20 3.06 2.63 0.86 504 2.94 2.53 0.86 534 2.85 2.45 0.86 546 2.75 2.37 0.86 570 27 22 3.19 2.36 0.74 522 3.08 2.28 0.74 555 3.00 2.22 0.74 570 2.88 2.13 0.74 594 27 24 3.35 2.08 0.62 546 3.23 2.00 0.62 576 3.15 1.95 0.62 594 3.05 1.89 0.62 624 27 26 3.45 1.73 0.50 576 3.35 1.68 0.50 606 3.30 1.65 0.50 624 3.20 1.60 0.50 642 28 18 2.94 2.94 1.00 480 2.81 2.81 1.00 504 2.70 2.70 1.00 528 2.60 2.60 1.00 552 28 20 3.06 2.76 0.90 504 2.94 2.64 0.90 534 2.85 2.57 0.90 546 2.75 2.48 0.90 570 28 22 3.19 2.49 0.78 522 3.08 2.40 0.78 555 3.00 2.34 0.78 570 2.88 2.24 0.78 594 28 24 3.35 2.21 0.66 546 3.23 2.13 0.66 576 3.15 2.08 0.66 594 3.05 2.01 0.66 624 28 26 3.45 1.86 0.54 576 3.35 1.81 0.54 606 3.30 1.78 0.54 624 3.20 1.73 0.54 642 29 18 2.94 2.94 1.00 480 2.81 2.81 1.00 504 2.70 2.70 1.00 528 2.60 2.60 1.00 552 29 20 3.06 2.88 0.94 504 2.94 2.76 0.94 534 2.85 2.68 0.94 546 2.75 2.59 0.94 570 29 22 3.19 2.61 0.82 522 3.08 2.52 0.82 555 3.00 2.46 0.82 570 2.88 2.36 0.82 594 29 24 3.35 2.35 0.70 546 3.23 2.26 0.70 576 3.15 2.21 0.70 594 3.05 2.14 0.70 624 29 26 3.45 2.00 0.58 576 3.35 1.94 0.58 606 3.30 1.91 0.58 624 3.20 1.86 0.58 642 30 18 2.94 2.94 1.00 480 2.81 2.81 1.00 504 2.70 2.70 1.00 528 2.60 2.60 1.00 552 30 20 3.06 3.00 0.98 504 2.94 2.88 0.98 534 2.85 2.79 0.98 546 2.75 2.70 0.98 570 30 22 3.19 2.74 0.86 522 3.08 2.64 0.86 555 3.00 2.58 0.86 570 2.88 2.47 0.86 594 30 24 3.35 2.48 0.74 546 3.23 2.39 0.74 576 3.15 2.33 0.74 594 3.05 2.26 0.74 624 30 26 3.45 2.14 0.62 576 3.35 2.08 0.62 606 3.30 2.05 0.62 624 3.20 1.98 0.62 642 31 18 2.94 2.94 1.00 480 2.81 2.81 1.00 504 2.70 2.70 1.00 528 2.60 2.60 1.00 552 31 20 3.06 3.06 1.00 504 2.94 2.94 1.00 534 2.85 2.85 1.00 546 2.75 2.75 1.00 570 31 22 3.19 2.87 0.90 522 3.08 2.77 0.90 555 3.00 2.70 0.90 570 2.88 2.59 0.90 594 31 24 3.35 2.61 0.78 546 3.23 2.52 0.78 576 3.15 2.46 0.78 594 3.05 2.38 0.78 624 31 26 3.45 2.28 0.66 576 3.35 2.21 0.66 606 3.30 2.18 0.66 624 3.20 2.11 0.66 642 32 18 2.94 2.94 1.00 480 2.81 2.81 1.00 504 2.70 2.70 1.00 528 2.60 2.60 1.00 552 32 20 3.06 3.06 1.00 504 2.94 2.94 1.00 534 2.85 2.85 1.00 546 2.75 2.75 1.00 570 32 22 3.19 3.00 0.94 522 3.08 2.89 0.94 555 3.00 2.82 0.94 570 2.88 2.70 0.94 594 32 24 3.35 2.75 0.82 546 3.23 2.64 0.82 576 3.15 2.58 0.82 594 3.05 2.50 0.82 624 32 26 3.45 2.42 0.70 576 3.35 2.35 0.70 606 3.30 2.31 0.70 624 3.20 2.24 0.70 642
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH789
21
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-AP25VG MUZ-AP25VGH
CAPACITY: 2.5 kW SHF: 0.92 INPUT: 600 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
35 40 46
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 2.45 1.81 0.74 588 2.25 1.67 0.74 624 2.08 1.54 0.74 648 21 20 2.58 1.60 0.62 612 2.40 1.49 0.62 642 2.23 1.38 0.62 678 22 18 2.45 1.91 0.78 588 2.25 1.76 0.78 624 2.08 1.62 0.78 648 22 20 2.58 1.70 0.66 612 2.40 1.58 0.66 642 2.23 1.47 0.66 678 22 22 2.73 1.47 0.54 636 2.55 1.38 0.54 672 2.38 1.28 0.54 696 23 18 2.45 2.01 0.82 588 2.25 1.85 0.82 624 2.08 1.70 0.82 648 23 20 2.58 1.80 0.70 612 2.40 1.68 0.70 642 2.23 1.56 0.70 678 23 22 2.73 1.58 0.58 636 2.55 1.48 0.58 672 2.38 1.38 0.58 696 24 18 2.45 2.11 0.86 588 2.25 1.94 0.86 624 2.08 1.78 0.86 648 24 20 2.58 1.91 0.74 612 2.40 1.78 0.74 642 2.23 1.65 0.74 678 24 22 2.73 1.69 0.62 636 2.55 1.58 0.62 672 2.38 1.47 0.62 696 24 24 2.88 1.44 0.50 660 2.70 1.35 0.50 690 2.55 1.28 0.50 720 25 18 2.45 2.21 0.90 588 2.25 2.03 0.90 624 2.08 1.87 0.9 648 25 20 2.58 2.01 0.78 612 2.40 1.87 0.78 642 2.23 1.74 0.78 678 25 22 2.73 1.80 0.66 636 2.55 1.68 0.66 672 2.38 1.57 0.66 696 25 24 2.88 1.55 0.54 660 2.70 1.46 0.54 690 2.55 1.38 0.54 720 26 18 2.45 2.30 0.94 588 2.25 2.12 0.94 624 2.08 1.95 0.94 648 26 20 2.58 2.11 0.82 612 2.40 1.97 0.82 642 2.23 1.82 0.82 678 26 22 2.73 1.91 0.70 636 2.55 1.79 0.70 672 2.38 1.66 0.70 696 26 24 2.88 1.67 0.58 660 2.70 1.57 0.58 690 2.55 1.48 0.58 720 26 26 3.03 1.39 0.46 684 2.85 1.31 0.46 714 2.68 1.23 0.46 744 27 18 2.45 2.40 0.98 588 2.25 2.21 0.98 624 2.08 2.03 0.98 648 27 20 2.58 2.21 0.86 612 2.40 2.06 0.86 642 2.23 1.91 0.86 678 27 22 2.73 2.02 0.74 636 2.55 1.89 0.74 672 2.38 1.76 0.74 696 27 24 2.88 1.78 0.62 660 2.70 1.67 0.62 690 2.55 1.58 0.62 720 27 26 3.03 1.51 0.50 684 2.85 1.43 0.50 714 2.68 1.34 0.50 744 28 18 2.45 2.45 1.00 588 2.25 2.25 1.00 624 2.08 2.08 1.00 648 28 20 2.58 2.32 0.90 612 2.40 2.16 0.90 642 2.23 2.00 0.90 678 28 22 2.73 2.13 0.78 636 2.55 1.99 0.78 672 2.38 1.85 0.78 696 28 24 2.88 1.90 0.66 660 2.70 1.78 0.66 690 2.55 1.68 0.66 720 28 26 3.03 1.63 0.54 684 2.85 1.54 0.54 714 2.68 1.44 0.54 744 29 18 2.45 2.45 1.00 588 2.25 2.25 1.00 624 2.08 2.08 1.00 648 29 20 2.58 2.42 0.94 612 2.40 2.26 0.94 642 2.23 2.09 0.94 678 29 22 2.73 2.23 0.82 636 2.55 2.09 0.82 672 2.38 1.95 0.82 696 29 24 2.88 2.01 0.70 660 2.70 1.89 0.70 690 2.55 1.79 0.70 720 29 26 3.03 1.75 0.58 684 2.85 1.65 0.58 714 2.68 1.55 0.58 744 30 18 2.45 2.45 1.00 588 2.25 2.25 1.00 624 2.08 2.08 1.00 648 30 20 2.58 2.52 0.98 612 2.40 2.35 0.98 642 2.23 2.18 0.98 678 30 22 2.73 2.34 0.86 636 2.55 2.19 0.86 672 2.38 2.04 0.86 696 30 24 2.88 2.13 0.74 660 2.70 2.00 0.74 690 2.55 1.89 0.74 720 30 26 3.03 1.88 0.62 684 2.85 1.77 0.62 714 2.68 1.66 0.62 744 31 18 2.45 2.45 1.00 588 2.25 2.25 1.00 624 2.08 2.08 1.00 648 31 20 2.58 2.58 1.00 612 2.40 2.40 1.00 642 2.23 2.23 1.00 678 31 22 2.73 2.45 0.90 636 2.55 2.30 0.90 672 2.38 2.14 0.90 696 31 24 2.88 2.24 0.78 660 2.70 2.11 0.78 690 2.55 1.99 0.78 720 31 26 3.03 2.00 0.66 684 2.85 1.88 0.66 714 2.68 1.77 0.66 744 32 18 2.45 2.45 1.00 588 2.25 2.25 1.00 624 2.08 2.08 1.00 648 32 20 2.58 2.58 1.00 612 2.40 2.40 1.00 642 2.23 2.23 1.00 678 32 22 2.73 2.56 0.94 636 2.55 2.40 0.94 672 2.38 2.23 0.94 696 32 24 2.88 2.36 0.82 660 2.70 2.21 0.82 690 2.55 2.09 0.82 720 32 26 3.03 2.12 0.70 684 2.85 2.00 0.70 714 2.68 1.87 0.70 744
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH789
22
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-AP35VG MUZ-AP35VGH
CAPACITY: 3.5 kW SHF: 0.88 INPUT: 990 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
21 25 27 30
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 4.11 2.88 0.70 792 3.94 2.76 0.70 832 3.78 2.65 0.70 871 3.64 2.55 0.70 911 21 20 4.29 2.49 0.58 832 4.11 2.39 0.58 881 3.99 2.31 0.58 901 3.85 2.23 0.58 941 22 18 4.11 3.04 0.74 792 3.94 2.91 0.74 832 3.78 2.80 0.74 871 3.64 2.69 0.74 911 22 20 4.29 2.66 0.62 832 4.11 2.55 0.62 881 3.99 2.47 0.62 901 3.85 2.39 0.62 941 22 22 4.46 2.23 0.50 861 4.31 2.15 0.50 916 4.20 2.10 0.50 941 4.03 2.01 0.50 980 23 18 4.11 3.21 0.78 792 3.94 3.07 0.78 832 3.78 2.95 0.78 871 3.64 2.84 0.78 911 23 20 4.29 2.83 0.66 832 4.11 2.71 0.66 881 3.99 2.63 0.66 901 3.85 2.54 0.66 941 23 22 4.46 2.41 0.54 861 4.31 2.32 0.54 916 4.20 2.27 0.54 941 4.03 2.17 0.54 980 24 18 4.11 3.37 0.82 792 3.94 3.23 0.82 832 3.78 3.10 0.82 871 3.64 2.98 0.82 911 24 20 4.29 3.00 0.70 832 4.11 2.88 0.70 881 3.99 2.79 0.70 901 3.85 2.70 0.70 941 24 22 4.46 2.59 0.58 861 4.31 2.50 0.58 916 4.20 2.44 0.58 941 4.03 2.33 0.58 980 24 24 4.69 2.16 0.46 901 4.52 2.08 0.46 950 4.41 2.03 0.46 980 4.27 1.96 0.46 1030 25 18 4.11 3.54 0.86 792 3.94 3.39 0.86 832 3.78 3.25 0.86 871 3.64 3.13 0.86 911 25 20 4.29 3.17 0.74 832 4.11 3.04 0.74 881 3.99 2.95 0.74 901 3.85 2.85 0.74 941 25 22 4.46 2.77 0.62 861 4.31 2.67 0.62 916 4.20 2.60 0.62 941 4.03 2.50 0.62 980 25 24 4.69 2.35 0.50 901 4.52 2.26 0.50 950 4.41 2.21 0.50 980 4.27 2.14 0.50 1030 26 18 4.11 3.70 0.90 792 3.94 3.54 0.90 832 3.78 3.40 0.90 871 3.64 3.28 0.90 911 26 20 4.29 3.34 0.78 832 4.11 3.21 0.78 881 3.99 3.11 0.78 901 3.85 3.00 0.78 941 26 22 4.46 2.95 0.66 861 4.31 2.84 0.66 916 4.20 2.77 0.66 941 4.03 2.66 0.66 980 26 24 4.69 2.53 0.54 901 4.52 2.44 0.54 950 4.41 2.38 0.54 980 4.27 2.31 0.54 1030 26 26 4.83 2.03 0.42 950 4.69 1.97 0.42 1000 4.62 1.94 0.42 1030 4.48 1.88 0.42 1059 27 18 4.11 3.87 0.94 792 3.94 3.70 0.94 832 3.78 3.55 0.94 871 3.64 3.42 0.94 911 27 20 4.29 3.52 0.82 832 4.11 3.37 0.82 881 3.99 3.27 0.82 901 3.85 3.16 0.82 941 27 22 4.46 3.12 0.70 861 4.31 3.01 0.70 916 4.20 2.94 0.70 941 4.03 2.82 0.70 980 27 24 4.69 2.72 0.58 901 4.52 2.62 0.58 950 4.41 2.56 0.58 980 4.27 2.48 0.58 1030 27 26 4.83 2.22 0.46 950 4.69 2.16 0.46 1000 4.62 2.13 0.46 1030 4.48 2.06 0.46 1059 28 18 4.11 4.03 0.98 792 3.94 3.86 0.98 832 3.78 3.70 0.98 871 3.64 3.57 0.98 911 28 20 4.29 3.69 0.86 832 4.11 3.54 0.86 881 3.99 3.43 0.86 901 3.85 3.31 0.86 941 28 22 4.46 3.30 0.74 861 4.31 3.19 0.74 916 4.20 3.11 0.74 941 4.03 2.98 0.74 980 28 24 4.69 2.91 0.62 901 4.52 2.80 0.62 950 4.41 2.73 0.62 980 4.27 2.65 0.62 1030 28 26 4.83 2.42 0.50 950 4.69 2.35 0.50 1000 4.62 2.31 0.50 1030 4.48 2.24 0.50 1059 29 18 4.11 4.11 1.00 792 3.94 3.94 1.00 832 3.78 3.78 1.00 871 3.64 3.64 1.00 911 29 20 4.29 3.86 0.90 832 4.11 3.70 0.90 881 3.99 3.59 0.90 901 3.85 3.47 0.90 941 29 22 4.46 3.48 0.78 861 4.31 3.36 0.78 916 4.20 3.28 0.78 941 4.03 3.14 0.78 980 29 24 4.69 3.10 0.66 901 4.52 2.98 0.66 950 4.41 2.91 0.66 980 4.27 2.82 0.66 1030 29 26 4.83 2.61 0.54 950 4.69 2.53 0.54 1000 4.62 2.49 0.54 1030 4.48 2.42 0.54 1059 30 18 4.11 4.11 1.00 792 3.94 3.94 1.00 832 3.78 3.78 1.00 871 3.64 3.64 1.00 911 30 20 4.29 4.03 0.94 832 4.11 3.87 0.94 881 3.99 3.75 0.94 901 3.85 3.62 0.94 941 30 22 4.46 3.66 0.82 861 4.31 3.53 0.82 916 4.20 3.44 0.82 941 4.03 3.30 0.82 980 30 24 4.69 3.28 0.70 901 4.52 3.16 0.70 950 4.41 3.09 0.70 980 4.27 2.99 0.70 1030 30 26 4.83 2.80 0.58 950 4.69 2.72 0.58 1000 4.62 2.68 0.58 1030 4.48 2.60 0.58 1059 31 18 4.11 4.11 1.00 792 3.94 3.94 1.00 832 3.78 3.78 1.00 871 3.64 3.64 1.00 911 31 20 4.29 4.20 0.98 832 4.11 4.03 0.98 881 3.99 3.91 0.98 901 3.85 3.77 0.98 941 31 22 4.46 3.84 0.86 861 4.31 3.70 0.86 916 4.20 3.61 0.86 941 4.03 3.46 0.86 980 31 24 4.69 3.47 0.74 901 4.52 3.34 0.74 950 4.41 3.26 0.74 980 4.27 3.16 0.74 1030 31 26 4.83 2.99 0.62 950 4.69 2.91 0.62 1000 4.62 2.86 0.62 1030 4.48 2.78 0.62 1059 32 18 4.11 4.11 1.00 792 3.94 3.94 1.00 832 3.78 3.78 1.00 871 3.64 3.64 1.00 911 32 20 4.29 4.29 1.00 832 4.11 4.11 1.00 881 3.99 3.99 1.00 901 3.85 3.85 1.00 941 32 22 4.46 4.02 0.90 861 4.31 3.87 0.90 916 4.20 3.78 0.90 941 4.03 3.62 0.90 980 32 24 4.69 3.66 0.78 901 4.52 3.52 0.78 950 4.41 3.44 0.78 980 4.27 3.33 0.78 1030 32 26 4.83 3.19 0.66 950 4.69 3.10 0.66 1000 4.62 3.05 0.66 1030 4.48 2.96 0.66 1059
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH789
23
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-AP35VG MUZ-AP35VGH
CAPACITY: 3.5 kW SHF: 0.88 INPUT: 990 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
35 40 46
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 3.43 2.40 0.70 970 3.15 2.21 0.70 1030 2.91 2.03 0.70 1069 21 20 3.61 2.09 0.58 1010 3.36 1.95 0.58 1059 3.12 1.81 0.58 1119 22 18 3.43 2.54 0.74 970 3.15 2.33 0.74 1030 2.91 2.15 0.74 1069 22 20 3.61 2.24 0.62 1010 3.36 2.08 0.62 1059 3.12 1.93 0.62 1119 22 22 3.82 1.91 0.50 1049 3.57 1.79 0.50 1109 3.33 1.66 0.50 1148 23 18 3.43 2.68 0.78 970 3.15 2.46 0.78 1030 2.91 2.27 0.78 1069 23 20 3.61 2.38 0.66 1010 3.36 2.22 0.66 1059 3.12 2.06 0.66 1119 23 22 3.82 2.06 0.54 1049 3.57 1.93 0.54 1109 3.33 1.80 0.54 1148 24 18 3.43 2.81 0.82 970 3.15 2.58 0.82 1030 2.91 2.38 0.82 1069 24 20 3.61 2.52 0.70 1010 3.36 2.35 0.70 1059 3.12 2.18 0.70 1119 24 22 3.82 2.21 0.58 1049 3.57 2.07 0.58 1109 3.33 1.93 0.58 1148 24 24 4.03 1.85 0.46 1089 3.78 1.74 0.46 1139 3.57 1.64 0.46 1188 25 18 3.43 2.95 0.86 970 3.15 2.71 0.86 1030 2.91 2.50 0.86 1069 25 20 3.61 2.67 0.74 1010 3.36 2.49 0.74 1059 3.12 2.31 0.74 1119 25 22 3.82 2.37 0.62 1049 3.57 2.21 0.62 1109 3.33 2.06 0.62 1148 25 24 4.03 2.01 0.50 1089 3.78 1.89 0.50 1139 3.57 1.79 0.50 1188 26 18 3.43 3.09 0.90 970 3.15 2.84 0.90 1030 2.91 2.61 0.90 1069 26 20 3.61 2.81 0.78 1010 3.36 2.62 0.78 1059 3.12 2.43 0.78 1119 26 22 3.82 2.52 0.66 1049 3.57 2.36 0.66 1109 3.33 2.19 0.66 1148 26 24 4.03 2.17 0.54 1089 3.78 2.04 0.54 1139 3.57 1.93 0.54 1188 26 26 4.24 1.78 0.42 1129 3.99 1.68 0.42 1178 3.75 1.57 0.42 1228 27 18 3.43 3.22 0.94 970 3.15 2.96 0.94 1030 2.91 2.73 0.94 1069 27 20 3.61 2.96 0.82 1010 3.36 2.76 0.82 1059 3.12 2.55 0.82 1119 27 22 3.82 2.67 0.70 1049 3.57 2.50 0.70 1109 3.33 2.33 0.70 1148 27 24 4.03 2.33 0.58 1089 3.78 2.19 0.58 1139 3.57 2.07 0.58 1188 27 26 4.24 1.95 0.46 1129 3.99 1.84 0.46 1178 3.75 1.72 0.46 1228 28 18 3.43 3.36 0.98 970 3.15 3.09 0.98 1030 2.91 2.85 0.98 1069 28 20 3.61 3.10 0.86 1010 3.36 2.89 0.86 1059 3.12 2.68 0.86 1119 28 22 3.82 2.82 0.74 1049 3.57 2.64 0.74 1109 3.33 2.46 0.74 1148 28 24 4.03 2.50 0.62 1089 3.78 2.34 0.62 1139 3.57 2.21 0.62 1188 28 26 4.24 2.12 0.50 1129 3.99 2.00 0.50 1178 3.75 1.87 0.50 1228 29 18 3.43 3.43 1.00 970 3.15 3.15 1.00 1030 2.91 2.91 1.00 1069 29 20 3.61 3.24 0.90 1010 3.36 3.02 0.90 1059 3.12 2.80 0.90 1119 29 22 3.82 2.98 0.78 1049 3.57 2.78 0.78 1109 3.33 2.59 0.78 1148 29 24 4.03 2.66 0.66 1089 3.78 2.49 0.66 1139 3.57 2.36 0.66 1188 29 26 4.24 2.29 0.54 1129 3.99 2.15 0.54 1178 3.75 2.02 0.54 1228 30 18 3.43 3.43 1.00 970 3.15 3.15 1.00 1030 2.91 2.91 1.00 1069 30 20 3.61 3.39 0.94 1010 3.36 3.16 0.94 1059 3.12 2.93 0.94 1119 30 22 3.82 3.13 0.82 1049 3.57 2.93 0.82 1109 3.33 2.73 0.82 1148 30 24 4.03 2.82 0.70 1089 3.78 2.65 0.70 1139 3.57 2.50 0.70 1188 30 26 4.24 2.46 0.58 1129 3.99 2.31 0.58 1178 3.75 2.17 0.58 1228 31 18 3.43 3.43 1.00 970 3.15 3.15 1.00 1030 2.91 2.91 1.00 1069 31 20 3.61 3.53 0.98 1010 3.36 3.29 0.98 1059 3.12 3.05 0.98 1119 31 22 3.82 3.28 0.86 1049 3.57 3.07 0.86 1109 3.33 2.86 0.86 1148 31 24 4.03 2.98 0.74 1089 3.78 2.80 0.74 1139 3.57 2.64 0.74 1188 31 26 4.24 2.63 0.62 1129 3.99 2.47 0.62 1178 3.75 2.32 0.62 1228 32 18 3.43 3.43 1.00 970 3.15 3.15 1.00 1030 2.91 2.91 1.00 1069 32 20 3.61 3.61 1.00 1010 3.36 3.36 1.00 1059 3.12 3.12 1.00 1119 32 22 3.82 3.43 0.90 1049 3.57 3.21 0.90 1109 3.33 2.99 0.90 1148 32 24 4.03 3.14 0.78 1089 3.78 2.95 0.78 1139 3.57 2.78 0.78 1188 32 26 4.24 2.80 0.66 1129 3.99 2.63 0.66 1178 3.75 2.47 0.66 1228
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH789
24
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-AP42VG MUZ-AP42VGH
CAPACITY: 4.2 kW SHF: 0.77 INPUT: 1300 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
21 25 27 30
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 4.94 2.91 0.59 1040 4.73 2.79 0.59 1092 4.54 2.68 0.59 1144 4.37 2.58 0.59 1196 21 20 5.15 2.42 0.47 1092 4.94 2.32 0.47 1157 4.79 2.25 0.47 1183 4.62 2.17 0.47 1235 22 18 4.94 3.11 0.63 1040 4.73 2.98 0.63 1092 4.54 2.86 0.63 1144 4.37 2.75 0.63 1196 22 20 5.15 2.62 0.51 1092 4.94 2.52 0.51 1157 4.79 2.44 0.51 1183 4.62 2.36 0.51 1235 22 22 5.36 2.09 0.39 1131 5.17 2.01 0.39 1203 5.04 1.97 0.39 1235 4.83 1.88 0.39 1287 23 18 4.94 3.31 0.67 1040 4.73 3.17 0.67 1092 4.54 3.04 0.67 1144 4.37 2.93 0.67 1196 23 20 5.15 2.83 0.55 1092 4.94 2.71 0.55 1157 4.79 2.63 0.55 1183 4.62 2.54 0.55 1235 23 22 5.36 2.30 0.43 1131 5.17 2.22 0.43 1203 5.04 2.17 0.43 1235 4.83 2.08 0.43 1287 24 18 4.94 3.50 0.71 1040 4.73 3.35 0.71 1092 4.54 3.22 0.71 1144 4.37 3.10 0.71 1196 24 20 5.15 3.04 0.59 1092 4.94 2.91 0.59 1157 4.79 2.82 0.59 1183 4.62 2.73 0.59 1235 24 22 5.36 2.52 0.47 1131 5.17 2.43 0.47 1203 5.04 2.37 0.47 1235 4.83 2.27 0.47 1287 24 24 5.63 1.97 0.35 1183 5.42 1.90 0.35 1248 5.29 1.85 0.35 1287 5.12 1.79 0.35 1352 25 18 4.94 3.70 0.75 1040 4.73 3.54 0.75 1092 4.54 3.40 0.75 1144 4.37 3.28 0.75 1196 25 20 5.15 3.24 0.63 1092 4.94 3.11 0.63 1157 4.79 3.02 0.63 1183 4.62 2.91 0.63 1235 25 22 5.36 2.73 0.51 1131 5.17 2.63 0.51 1203 5.04 2.57 0.51 1235 4.83 2.46 0.51 1287 25 24 5.63 2.19 0.39 1183 5.42 2.11 0.39 1248 5.29 2.06 0.39 1287 5.12 2.00 0.39 1352 26 18 4.94 3.90 0.79 1040 4.73 3.73 0.79 1092 4.54 3.58 0.79 1144 4.37 3.45 0.79 1196 26 20 5.15 3.45 0.67 1092 4.94 3.31 0.67 1157 4.79 3.21 0.67 1183 4.62 3.10 0.67 1235 26 22 5.36 2.95 0.55 1131 5.17 2.84 0.55 1203 5.04 2.77 0.55 1235 4.83 2.66 0.55 1287 26 24 5.63 2.42 0.43 1183 5.42 2.33 0.43 1248 5.29 2.28 0.43 1287 5.12 2.20 0.43 1352 26 26 5.80 1.80 0.31 1248 5.63 1.74 0.31 1313 5.54 1.72 0.31 1352 5.38 1.67 0.31 1391 27 18 4.94 4.10 0.83 1040 4.73 3.92 0.83 1092 4.54 3.76 0.83 1144 4.37 3.63 0.83 1196 27 20 5.15 3.65 0.71 1092 4.94 3.50 0.71 1157 4.79 3.40 0.71 1183 4.62 3.28 0.71 1235 27 22 5.36 3.16 0.59 1131 5.17 3.05 0.59 1203 5.04 2.97 0.59 1235 4.83 2.85 0.59 1287 27 24 5.63 2.65 0.47 1183 5.42 2.55 0.47 1248 5.29 2.49 0.47 1287 5.12 2.41 0.47 1352 27 26 5.80 2.03 0.35 1248 5.63 1.97 0.35 1313 5.54 1.94 0.35 1352 5.38 1.88 0.35 1391 28 18 4.94 4.29 0.87 1040 4.73 4.11 0.87 1092 4.54 3.95 0.87 1144 4.37 3.80 0.87 1196 28 20 5.15 3.86 0.75 1092 4.94 3.70 0.75 1157 4.79 3.59 0.75 1183 4.62 3.47 0.75 1235 28 22 5.36 3.37 0.63 1131 5.17 3.25 0.63 1203 5.04 3.18 0.63 1235 4.83 3.04 0.63 1287 28 24 5.63 2.87 0.51 1183 5.42 2.76 0.51 1248 5.29 2.70 0.51 1287 5.12 2.61 0.51 1352 28 26 5.80 2.26 0.39 1248 5.63 2.19 0.39 1313 5.54 2.16 0.39 1352 5.38 2.10 0.39 1391 29 18 4.94 4.49 0.91 1040 4.73 4.30 0.91 1092 4.54 4.13 0.91 1144 4.37 3.97 0.91 1196 29 20 5.15 4.06 0.79 1092 4.94 3.90 0.79 1157 4.79 3.78 0.79 1183 4.62 3.65 0.79 1235 29 22 5.36 3.59 0.67 1131 5.17 3.46 0.67 1203 5.04 3.38 0.67 1235 4.83 3.24 0.67 1287 29 24 5.63 3.10 0.55 1183 5.42 2.98 0.55 1248 5.29 2.91 0.55 1287 5.12 2.82 0.55 1352 29 26 5.80 2.49 0.43 1248 5.63 2.42 0.43 1313 5.54 2.38 0.43 1352 5.38 2.31 0.43 1391 30 18 4.94 4.69 0.95 1040 4.73 4.49 0.95 1092 4.54 4.31 0.95 1144 4.37 4.15 0.95 1196 30 20 5.15 4.27 0.83 1092 4.94 4.10 0.83 1157 4.79 3.97 0.83 1183 4.62 3.83 0.83 1235 30 22 5.36 3.80 0.71 1131 5.17 3.67 0.71 1203 5.04 3.58 0.71 1235 4.83 3.43 0.71 1287 30 24 5.63 3.32 0.59 1183 5.42 3.20 0.59 1248 5.29 3.12 0.59 1287 5.12 3.02 0.59 1352 30 26 5.80 2.72 0.47 1248 5.63 2.65 0.47 1313 5.54 2.61 0.47 1352 5.38 2.53 0.47 1391 31 18 4.94 4.89 0.99 1040 4.73 4.68 0.99 1092 4.54 4.49 0.99 1144 4.37 4.32 0.99 1196 31 20 5.15 4.48 0.87 1092 4.94 4.29 0.87 1157 4.79 4.17 0.87 1183 4.62 4.02 0.87 1235 31 22 5.36 4.02 0.75 1131 5.17 3.87 0.75 1203 5.04 3.78 0.75 1235 4.83 3.62 0.75 1287 31 24 5.63 3.55 0.63 1183 5.42 3.41 0.63 1248 5.29 3.33 0.63 1287 5.12 3.23 0.63 1352 31 26 5.80 2.96 0.51 1248 5.63 2.87 0.51 1313 5.54 2.83 0.51 1352 5.38 2.74 0.51 1391 32 18 4.94 4.94 1.00 1040 4.73 4.73 1.00 1092 4.54 4.54 1.00 1144 4.37 4.37 1.00 1196 32 20 5.15 4.68 0.91 1092 4.94 4.49 0.91 1157 4.79 4.36 0.91 1183 4.62 4.20 0.91 1235 32 22 5.36 4.23 0.79 1131 5.17 4.08 0.79 1203 5.04 3.98 0.79 1235 4.83 3.82 0.79 1287 32 24 5.63 3.77 0.67 1183 5.42 3.63 0.67 1248 5.29 3.55 0.67 1287 5.12 3.43 0.67 1352 32 26 5.80 3.19 0.55 1248 5.63 3.10 0.55 1313 5.54 3.05 0.55 1352 5.38 2.96 0.55 1391
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH789
25
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-AP42VG MUZ-AP42VGH
CAPACITY: 4.2 kW SHF: 0.77 INPUT: 1300 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
35 40 46
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 4.12 2.43 0.59 1274 3.78 2.23 0.59 1352 3.49 2.06 0.59 1404 21 20 4.33 2.03 0.47 1326 4.03 1.90 0.47 1391 3.74 1.76 0.47 1469 22 18 4.12 2.59 0.63 1274 3.78 2.38 0.63 1352 3.49 2.20 0.63 1404 22 20 4.33 2.21 0.51 1326 4.03 2.06 0.51 1391 3.74 1.91 0.51 1469 22 22 4.58 1.79 0.39 1378 4.28 1.67 0.39 1456 3.99 1.56 0.39 1508 23 18 4.12 2.76 0.67 1274 3.78 2.53 0.67 1352 3.49 2.34 0.67 1404 23 20 4.33 2.38 0.55 1326 4.03 2.22 0.55 1391 3.74 2.06 0.55 1469 23 22 4.58 1.97 0.43 1378 4.28 1.84 0.43 1456 3.99 1.72 0.43 1508 24 18 4.12 2.92 0.71 1274 3.78 2.68 0.71 1352 3.49 2.48 0.71 1404 24 20 4.33 2.55 0.59 1326 4.03 2.38 0.59 1391 3.74 2.21 0.59 1469 24 22 4.58 2.15 0.47 1378 4.28 2.01 0.47 1456 3.99 1.88 0.47 1508 24 24 4.83 1.69 0.35 1430 4.54 1.59 0.35 1495 4.28 1.50 0.35 1560 25 18 4.12 3.09 0.75 1274 3.78 2.84 0.75 1352 3.49 2.61 0.75 1404 25 20 4.33 2.73 0.63 1326 4.03 2.54 0.63 1391 3.74 2.35 0.63 1469 25 22 4.58 2.33 0.51 1378 4.28 2.18 0.51 1456 3.99 2.03 0.51 1508 25 24 4.83 1.88 0.39 1430 4.54 1.77 0.39 1495 4.28 1.67 0.39 1560 26 18 4.12 3.25 0.79 1274 3.78 2.99 0.79 1352 3.49 2.75 0.79 1404 26 20 4.33 2.90 0.67 1326 4.03 2.70 0.67 1391 3.74 2.50 0.67 1469 26 22 4.58 2.52 0.55 1378 4.28 2.36 0.55 1456 3.99 2.19 0.55 1508 26 24 4.83 2.08 0.43 1430 4.54 1.95 0.43 1495 4.28 1.84 0.43 1560 26 26 5.08 1.58 0.31 1482 4.79 1.48 0.31 1547 4.49 1.39 0.31 1612 27 18 4.12 3.42 0.83 1274 3.78 3.14 0.83 1352 3.49 2.89 0.83 1404 27 20 4.33 3.07 0.71 1326 4.03 2.86 0.71 1391 3.74 2.65 0.71 1469 27 22 4.58 2.70 0.59 1378 4.28 2.53 0.59 1456 3.99 2.35 0.59 1508 27 24 4.83 2.27 0.47 1430 4.54 2.13 0.47 1495 4.28 2.01 0.47 1560 27 26 5.08 1.78 0.35 1482 4.79 1.68 0.35 1547 4.49 1.57 0.35 1612 28 18 4.12 3.58 0.87 1274 3.78 3.29 0.87 1352 3.49 3.03 0.87 1404 28 20 4.33 3.24 0.75 1326 4.03 3.02 0.75 1391 3.74 2.80 0.75 1469 28 22 4.58 2.88 0.63 1378 4.28 2.70 0.63 1456 3.99 2.51 0.63 1508 28 24 4.83 2.46 0.51 1430 4.54 2.31 0.51 1495 4.28 2.18 0.51 1560 28 26 5.08 1.98 0.39 1482 4.79 1.87 0.39 1547 4.49 1.75 0.39 1612 29 18 4.12 3.75 0.91 1274 3.78 3.44 0.91 1352 3.49 3.17 0.91 1404 29 20 4.33 3.42 0.79 1326 4.03 3.19 0.79 1391 3.74 2.95 0.79 1469 29 22 4.58 3.07 0.67 1378 4.28 2.87 0.67 1456 3.99 2.67 0.67 1508 29 24 4.83 2.66 0.55 1430 4.54 2.49 0.55 1495 4.28 2.36 0.55 1560 29 26 5.08 2.19 0.43 1482 4.79 2.06 0.43 1547 4.49 1.93 0.43 1612 30 18 4.12 3.91 0.95 1274 3.78 3.59 0.95 1352 3.49 3.31 0.95 1404 30 20 4.33 3.59 0.83 1326 4.03 3.35 0.83 1391 3.74 3.10 0.83 1469 30 22 4.58 3.25 0.71 1378 4.28 3.04 0.71 1456 3.99 2.83 0.71 1508 30 24 4.83 2.85 0.59 1430 4.54 2.68 0.59 1495 4.28 2.53 0.59 1560 30 26 5.08 2.39 0.47 1482 4.79 2.25 0.47 1547 4.49 2.11 0.47 1612 31 18 4.12 4.07 0.99 1274 3.78 3.74 0.99 1352 3.49 3.45 0.99 1404 31 20 4.33 3.76 0.87 1326 4.03 3.51 0.87 1391 3.74 3.25 0.87 1469 31 22 4.58 3.43 0.75 1378 4.28 3.21 0.75 1456 3.99 2.99 0.75 1508 31 24 4.83 3.04 0.63 1430 4.54 2.86 0.63 1495 4.28 2.70 0.63 1560 31 26 5.08 2.59 0.51 1482 4.79 2.44 0.51 1547 4.49 2.29 0.51 1612 32 18 4.12 4.12 1.00 1274 3.78 3.78 1.00 1352 3.49 3.49 1.00 1404 32 20 4.33 3.94 0.91 1326 4.03 3.67 0.91 1391 3.74 3.40 0.91 1469 32 22 4.58 3.62 0.79 1378 4.28 3.38 0.79 1456 3.99 3.15 0.79 1508 32 24 4.83 3.24 0.67 1430 4.54 3.04 0.67 1495 4.28 2.87 0.67 1560 32 26 5.08 2.80 0.55 1482 4.79 2.63 0.55 1547 4.49 2.47 0.55 1612
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH789
26
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-AP50VG MUZ-AP50VGH
CAPACITY: 5.0 kW SHF: 0.74 INPUT: 1550 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
21 25 27 30
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 5.88 3.29 0.56 1240 5.63 3.15 0.56 1302 5.40 3.02 0.56 1364 5.20 2.91 0.56 1426 21 20 6.13 2.70 0.44 1302 5.88 2.59 0.44 1380 5.70 2.51 0.44 1411 5.50 2.42 0.44 1473 22 18 5.88 3.53 0.60 1240 5.63 3.38 0.60 1302 5.40 3.24 0.60 1364 5.20 3.12 0.60 1426 22 20 6.13 2.94 0.48 1302 5.88 2.82 0.48 1380 5.70 2.74 0.48 1411 5.50 2.64 0.48 1473 22 22 6.38 2.30 0.36 1349 6.15 2.21 0.36 1434 6.00 2.16 0.36 1473 5.75 2.07 0.36 1535 23 18 5.88 3.76 0.64 1240 5.63 3.60 0.64 1302 5.40 3.46 0.64 1364 5.20 3.33 0.64 1426 23 20 6.13 3.19 0.52 1302 5.88 3.06 0.52 1380 5.70 2.96 0.52 1411 5.50 2.86 0.52 1473 23 22 6.38 2.55 0.40 1349 6.15 2.46 0.40 1434 6.00 2.40 0.40 1473 5.75 2.30 0.40 1535 24 18 5.88 4.00 0.68 1240 5.63 3.83 0.68 1302 5.40 3.67 0.68 1364 5.20 3.54 0.68 1426 24 20 6.13 3.43 0.56 1302 5.88 3.29 0.56 1380 5.70 3.19 0.56 1411 5.50 3.08 0.56 1473 24 22 6.38 2.81 0.44 1349 6.15 2.71 0.44 1434 6.00 2.64 0.44 1473 5.75 2.53 0.44 1535 24 24 6.70 2.14 0.32 1411 6.45 2.06 0.32 1488 6.30 2.02 0.32 1535 6.10 1.95 0.32 1612 25 18 5.88 4.23 0.72 1240 5.63 4.05 0.72 1302 5.40 3.89 0.72 1364 5.20 3.74 0.72 1426 25 20 6.13 3.68 0.60 1302 5.88 3.53 0.60 1380 5.70 3.42 0.60 1411 5.50 3.30 0.60 1473 25 22 6.38 3.06 0.48 1349 6.15 2.95 0.48 1434 6.00 2.88 0.48 1473 5.75 2.76 0.48 1535 25 24 6.70 2.41 0.36 1411 6.45 2.32 0.36 1488 6.30 2.27 0.36 1535 6.10 2.20 0.36 1612 26 18 5.88 4.47 0.76 1240 5.63 4.28 0.76 1302 5.40 4.10 0.76 1364 5.20 3.95 0.76 1426 26 20 6.13 3.92 0.64 1302 5.88 3.76 0.64 1380 5.70 3.65 0.64 1411 5.50 3.52 0.64 1473 26 22 6.38 3.32 0.52 1349 6.15 3.20 0.52 1434 6.00 3.12 0.52 1473 5.75 2.99 0.52 1535 26 24 6.70 2.68 0.40 1411 6.45 2.58 0.40 1488 6.30 2.52 0.40 1535 6.10 2.44 0.40 1612 26 26 6.90 1.93 0.28 1488 6.70 1.88 0.28 1566 6.60 1.85 0.28 1612 6.40 1.79 0.28 1659 27 18 5.88 4.70 0.80 1240 5.63 4.50 0.80 1302 5.40 4.32 0.80 1364 5.20 4.16 0.80 1426 27 20 6.13 4.17 0.68 1302 5.88 4.00 0.68 1380 5.70 3.88 0.68 1411 5.50 3.74 0.68 1473 27 22 6.38 3.57 0.56 1349 6.15 3.44 0.56 1434 6.00 3.36 0.56 1473 5.75 3.22 0.56 1535 27 24 6.70 2.95 0.44 1411 6.45 2.84 0.44 1488 6.30 2.77 0.44 1535 6.10 2.68 0.44 1612 27 26 6.90 2.21 0.32 1488 6.70 2.14 0.32 1566 6.60 2.11 0.32 1612 6.40 2.05 0.32 1659 28 18 5.88 4.94 0.84 1240 5.63 4.73 0.84 1302 5.40 4.54 0.84 1364 5.20 4.37 0.84 1426 28 20 6.13 4.41 0.72 1302 5.88 4.23 0.72 1380 5.70 4.10 0.72 1411 5.50 3.96 0.72 1473 28 22 6.38 3.83 0.60 1349 6.15 3.69 0.60 1434 6.00 3.60 0.60 1473 5.75 3.45 0.60 1535 28 24 6.70 3.22 0.48 1411 6.45 3.10 0.48 1488 6.30 3.02 0.48 1535 6.10 2.93 0.48 1612 28 26 6.90 2.48 0.36 1488 6.70 2.41 0.36 1566 6.60 2.38 0.36 1612 6.40 2.30 0.36 1659 29 18 5.88 5.17 0.88 1240 5.63 4.95 0.88 1302 5.40 4.75 0.88 1364 5.20 4.58 0.88 1426 29 20 6.13 4.66 0.76 1302 5.88 4.47 0.76 1380 5.70 4.33 0.76 1411 5.50 4.18 0.76 1473 29 22 6.38 4.08 0.64 1349 6.15 3.94 0.64 1434 6.00 3.84 0.64 1473 5.75 3.68 0.64 1535 29 24 6.70 3.48 0.52 1411 6.45 3.35 0.52 1488 6.30 3.28 0.52 1535 6.10 3.17 0.52 1612 29 26 6.90 2.76 0.40 1488 6.70 2.68 0.40 1566 6.60 2.64 0.40 1612 6.40 2.56 0.40 1659 30 18 5.88 5.41 0.92 1240 5.63 5.18 0.92 1302 5.40 4.97 0.92 1364 5.20 4.78 0.92 1426 30 20 6.13 4.90 0.80 1302 5.88 4.70 0.80 1380 5.70 4.56 0.80 1411 5.50 4.40 0.80 1473 30 22 6.38 4.34 0.68 1349 6.15 4.18 0.68 1434 6.00 4.08 0.68 1473 5.75 3.91 0.68 1535 30 24 6.70 3.75 0.56 1411 6.45 3.61 0.56 1488 6.30 3.53 0.56 1535 6.10 3.42 0.56 1612 30 26 6.90 3.04 0.44 1488 6.70 2.95 0.44 1566 6.60 2.90 0.44 1612 6.40 2.82 0.44 1659 31 18 5.88 5.64 0.96 1240 5.63 5.40 0.96 1302 5.40 5.18 0.96 1364 5.20 4.99 0.96 1426 31 20 6.13 5.15 0.84 1302 5.88 4.94 0.84 1380 5.70 4.79 0.84 1411 5.50 4.62 0.84 1473 31 22 6.38 4.59 0.72 1349 6.15 4.43 0.72 1434 6.00 4.32 0.72 1473 5.75 4.14 0.72 1535 31 24 6.70 4.02 0.60 1411 6.45 3.87 0.60 1488 6.30 3.78 0.60 1535 6.10 3.66 0.60 1612 31 26 6.90 3.31 0.48 1488 6.70 3.22 0.48 1566 6.60 3.17 0.48 1612 6.40 3.07 0.48 1659 32 18 5.88 5.88 1.00 1240 5.63 5.63 1.00 1302 5.40 5.40 1.00 1364 5.20 5.20 1.00 1426 32 20 6.13 5.39 0.88 1302 5.88 5.17 0.88 1380 5.70 5.02 0.88 1411 5.50 4.84 0.88 1473 32 22 6.38 4.85 0.76 1349 6.15 4.67 0.76 1434 6.00 4.56 0.76 1473 5.75 4.37 0.76 1535 32 24 6.70 4.29 0.64 1411 6.45 4.13 0.64 1488 6.30 4.03 0.64 1535 6.10 3.90 0.64 1612 32 26 6.90 3.59 0.52 1488 6.70 3.48 0.52 1566 6.60 3.43 0.52 1612 6.40 3.33 0.52 1659
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH789
27
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-AP50VG MUZ-AP50VGH
CAPACITY: 5.0 kW SHF: 0.74 INPUT: 1550 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
35 40 46
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 4.90 2.74 0.56 1519 4.50 2.52 0.56 1612 4.15 2.32 0.56 1674 21 20 5.15 2.27 0.44 1581 4.80 2.11 0.44 1659 4.45 1.96 0.44 1752 22 18 4.90 2.94 0.60 1519 4.50 2.70 0.60 1612 4.15 2.49 0.60 1674 22 20 5.15 2.47 0.48 1581 4.80 2.30 0.48 1659 4.45 2.14 0.48 1752 22 22 5.45 1.96 0.36 1643 5.10 1.84 0.36 1736 4.75 1.71 0.36 1798 23 18 4.90 3.14 0.64 1519 4.50 2.88 0.64 1612 4.15 2.66 0.64 1674 23 20 5.15 2.68 0.52 1581 4.80 2.50 0.52 1659 4.45 2.31 0.52 1752 23 22 5.45 2.18 0.40 1643 5.10 2.04 0.40 1736 4.75 1.90 0.40 1798 24 18 4.90 3.33 0.68 1519 4.50 3.06 0.68 1612 4.15 2.82 0.68 1674 24 20 5.15 2.88 0.56 1581 4.80 2.69 0.56 1659 4.45 2.49 0.56 1752 24 22 5.45 2.40 0.44 1643 5.10 2.24 0.44 1736 4.75 2.09 0.44 1798 24 24 5.75 1.84 0.32 1705 5.40 1.73 0.32 1783 5.10 1.63 0.32 1860 25 18 4.90 3.53 0.72 1519 4.50 3.24 0.72 1612 4.15 2.99 0.72 1674 25 20 5.15 3.09 0.60 1581 4.80 2.88 0.60 1659 4.45 2.67 0.60 1752 25 22 5.45 2.62 0.48 1643 5.10 2.45 0.48 1736 4.75 2.28 0.48 1798 25 24 5.75 2.07 0.36 1705 5.40 1.94 0.36 1783 5.10 1.84 0.36 1860 26 18 4.90 3.72 0.76 1519 4.50 3.42 0.76 1612 4.15 3.15 0.76 1674 26 20 5.15 3.30 0.64 1581 4.80 3.07 0.64 1659 4.45 2.85 0.64 1752 26 22 5.45 2.83 0.52 1643 5.10 2.65 0.52 1736 4.75 2.47 0.52 1798 26 24 5.75 2.30 0.40 1705 5.40 2.16 0.40 1783 5.10 2.04 0.40 1860 26 26 6.05 1.69 0.28 1767 5.70 1.60 0.28 1845 5.35 1.50 0.28 1922 27 18 4.90 3.92 0.80 1519 4.50 3.60 0.80 1612 4.15 3.32 0.80 1674 27 20 5.15 3.50 0.68 1581 4.80 3.26 0.68 1659 4.45 3.03 0.68 1752 27 22 5.45 3.05 0.56 1643 5.10 2.86 0.56 1736 4.75 2.66 0.56 1798 27 24 5.75 2.53 0.44 1705 5.40 2.38 0.44 1783 5.10 2.24 0.44 1860 27 26 6.05 1.94 0.32 1767 5.70 1.82 0.32 1845 5.35 1.71 0.32 1922 28 18 4.90 4.12 0.84 1519 4.50 3.78 0.84 1612 4.15 3.49 0.84 1674 28 20 5.15 3.71 0.72 1581 4.80 3.46 0.72 1659 4.45 3.20 0.72 1752 28 22 5.45 3.27 0.60 1643 5.10 3.06 0.60 1736 4.75 2.85 0.60 1798 28 24 5.75 2.76 0.48 1705 5.40 2.59 0.48 1783 5.10 2.45 0.48 1860 28 26 6.05 2.18 0.36 1767 5.70 2.05 0.36 1845 5.35 1.93 0.36 1922 29 18 4.90 4.31 0.88 1519 4.50 3.96 0.88 1612 4.15 3.65 0.88 1674 29 20 5.15 3.91 0.76 1581 4.80 3.65 0.76 1659 4.45 3.38 0.76 1752 29 22 5.45 3.49 0.64 1643 5.10 3.26 0.64 1736 4.75 3.04 0.64 1798 29 24 5.75 2.99 0.52 1705 5.40 2.81 0.52 1783 5.10 2.65 0.52 1860 29 26 6.05 2.42 0.40 1767 5.70 2.28 0.40 1845 5.35 2.14 0.40 1922 30 18 4.90 4.51 0.92 1519 4.50 4.14 0.92 1612 4.15 3.82 0.92 1674 30 20 5.15 4.12 0.80 1581 4.80 3.84 0.80 1659 4.45 3.56 0.80 1752 30 22 5.45 3.71 0.68 1643 5.10 3.47 0.68 1736 4.75 3.23 0.68 1798 30 24 5.75 3.22 0.56 1705 5.40 3.02 0.56 1783 5.10 2.86 0.56 1860 30 26 6.05 2.66 0.44 1767 5.70 2.51 0.44 1845 5.35 2.35 0.44 1922 31 18 4.90 4.70 0.96 1519 4.50 4.32 0.96 1612 4.15 3.98 0.96 1674 31 20 5.15 4.33 0.84 1581 4.80 4.03 0.84 1659 4.45 3.74 0.84 1752 31 22 5.45 3.92 0.72 1643 5.10 3.67 0.72 1736 4.75 3.42 0.72 1798 31 24 5.75 3.45 0.60 1705 5.40 3.24 0.60 1783 5.10 3.06 0.60 1860 31 26 6.05 2.90 0.48 1767 5.70 2.74 0.48 1845 5.35 2.57 0.48 1922 32 18 4.90 4.90 1.00 1519 4.50 4.50 1.00 1612 4.15 4.15 1.00 1674 32 20 5.15 4.53 0.88 1581 4.80 4.22 0.88 1659 4.45 3.92 0.88 1752 32 22 5.45 4.14 0.76 1643 5.10 3.88 0.76 1736 4.75 3.61 0.76 1798 32 24 5.75 3.68 0.64 1705 5.40 3.46 0.64 1783 5.10 3.26 0.64 1860 32 26 6.05 3.15 0.52 1767 5.70 2.96 0.52 1845 5.35 2.78 0.52 1922
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH789
28
PERFORMANCE DATA HEAT operation at Rated frequency
MUZ-AP25VG MUZ-AP25VGH
CAPACITY: 3.2 kW INPUT: 780 W
INDOOR
DB (°C)
OUTDOOR WB (°C)
-10 -5 0 5 10 15 20
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT 15 2.02 507 2.43 608 2.85 686 3.26 741 3.68 788 4.06 811 4.48 827 21 1.92 546 2.30 647 2.72 718 3.10 772 3.52 811 3.90 835 4.30 866 26 1.73 585 2.14 686 2.53 757 2.94 811 3.36 850 3.74 874 4.16 897
MUZ-AP35VG MUZ-AP35VGH
CAPACITY: 4.0 kW INPUT: 1030 W
INDOOR
DB (°C)
OUTDOOR WB (°C)
-10 -5 0 5 10 15 20
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT 15 2.52 670 3.04 803 3.56 906 4.08 979 4.60 1040 5.08 1071 5.60 1092 21 2.40 721 2.88 855 3.40 948 3.88 1020 4.40 1071 4.88 1102 5.38 1143 26 2.16 773 2.68 906 3.16 999 3.68 1071 4.20 1123 4.68 1154 5.20 1185
MUZ-AP42VG MUZ-AP42VGH
CAPACITY: 5.4 kW INPUT: 1490 W
INDOOR
DB (°C)
OUTDOOR WB (°C)
-10 -5 0 5 10 15 20
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT 15 3.40 969 4.10 1162 4.81 1311 5.51 1416 6.21 1505 6.86 1550 7.56 1579 21 3.24 1043 3.89 1237 4.59 1371 5.24 1475 5.94 1550 6.59 1594 7.26 1654 26 2.92 1118 3.62 1311 4.27 1445 4.97 1550 5.67 1624 6.32 1669 7.02 1714
MUZ-AP50VG MUZ-AP50VGH
CAPACITY: 5.8 kW INPUT: 1600 W
INDOOR
DB (°C)
OUTDOOR WB (°C)
-10 -5 0 5 10 15 20
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT 15 3.65 1040 4.41 1248 5.16 1408 5.92 1520 6.67 1616 7.37 1664 8.12 1696 21 3.48 1120 4.18 1328 4.93 1472 5.63 1584 6.38 1664 7.08 1712 7.80 1776 26 3.13 1200 3.89 1408 4.58 1552 5.34 1664 6.09 1744 6.79 1792 7.54 1840
NOTE: Q : Total capacity (kW) INPUT : Total power input (W) DB: Dry-bulb temperature WB: Wet-bulb temperature
OBH789
29
10-2. R.V. COIL CONTROL
Heating
. . . . . . . . . . . . . . . . .
ON
Cooling
. . . . . . . . . . . . . . . . .
OFF
Dry
. . . . . . . . . . . . . . . . . . . .
OFF
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
ON
OFF
ON
OFF
Outdoor fan motor
Compressor
5 seconds 15 seconds
ON OFF
Compressor
Outdoor fan motor
R.V.coil
ON OFF
ON OFF
<COOL>
5 seconds
<HEAT>
5 seconds
10-1. OUTDOOR FAN MOTOR CONTROL
The fan motor turns ON/OFF, interlocking with the compressor. [ON] The fan motor turns ON 5 seconds before the compressor starts up. [OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
10-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR
Sensor Purpose
Actuator
Compressor
LEV
Outdoor fan
motor
R.V. coil
Indoor fan
motor
Defrost
heater
Discharge temperature thermistor
Protection
○○
Indoor coil temperature thermistor
Cooling: Coil frost prevention
Heating: High pressure protec­tion
○○
Defrost thermistor Heating: Defrosting
○○○○○
Fin temperature thermistor Protection
○○
Ambient temperature thermistor
Cooling: Low ambient tempera­ture operation
○○○
Heating: Defrosting (Heater)
Outdoor heat exchanger tem­perature thermistor
Cooling: Low ambient tempera­ture operation
○○○
Cooling: High pressure protec­tion
○○○
ACTUATOR CONTROL
10
MUZ-AP25VG MUZ-AP35VG MUZ-AP42VG MUZ-AP50VG MUZ-AP25VGH MUZ-AP35VGH MUZ-AP42VGH MUZ-AP50VGH
OBH789
30
SERVICE FUNCTIONS
11
11-1. CHANGE IN DEFROST SETTING Changing defrost finish temperature
<JS> To change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P.C. board. (Refer to 12-6-1.)
Jumper wire Defrost nish temperature (°C)
JS
Soldered (Initial setting) 5
None (Cut) 10
11-2. PRE-HEAT CONTROL SETTING
PRE-HEAT CONTROL
When moisture gets into the refrigerant cycle, it may interfere the start-up of the compressor at low outside temperature. The pre-heat control prevents this interference. The pre-heat control turns ON when the discharge temperature thermis­tor is 20°C or below. When the pre-heat control turns ON, the compressor is energized. (About 50 W)
Pre-heat control setting
<JK> ON: To activate the pre-heat control, cut the JK wire of the inverter P.C. board. OFF: To deactivate the pre-heat control, solder the JK wire of the inverter P.C. board. (Refer to 12-6.1)
NOTE: When the inverter P.C. board is replaced, check the jumper wires, and cut/solder them if necessary.
MUZ-AP25VG MUZ-AP35VG MUZ-AP42VG MUZ-AP50VG MUZ-AP25VGH MUZ-AP35VGH MUZ-AP42VGH MUZ-AP50VGH
OBH789
31
12-1. CAUTIONS ON TROUBLESHOOTING
1. Before troubleshooting, check the following
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for miswiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, and then after confirming the horizontal vane is closed, turn OFF the breaker and/or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board.
3) When removing the electrical parts, be careful of the residual voltage of smoothing capacitor.
4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components.
5) When connecting or disconnecting the connectors, hold the connector housing. DO NOT pull the lead wires.
TROUBLESHOOTING
12
3. Troubleshooting procedure
1) Check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality. To make sure, check how many times the OPERATION INDICATOR lamp is flashing on and off before starting ser-
vice work.
2) Before servicing, check that the connector and terminal are connected properly.
3) When the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the components for bursting and discoloration.
4) Refer to 12-2 and 12-3.
Lead wiring
Connector housing
<Incorrect>
<Correct>
MUZ-AP25VG MUZ-AP35VG MUZ-AP42VG MUZ-AP50VG MUZ-AP25VGH MUZ-AP35VGH MUZ-AP42VGH MUZ-AP50VGH
OBH789
32
Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (12-3.) disappears, the memorized failure details can be recalled.
12-2. FAILURE MODE RECALL FUNCTION
1. Flow chart of failure mode recall function for the indoor/outdoor unit
NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
Does the upper lamp of OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: Either indoor or outdoor unit is abnormal. Beep is
emitted at the same timing as the blinking of the up­per lamp on the indoor unit.
2
Indoor unit is normal. But the outdoor unit might be abnormal because there are some abnor­malities that cannot be recalled with this way. Check if outdoor unit is abnormal according to the detailed outdoor unit failure mode recall function. (Refer to 12-2.2)
No
Yes
The cause of abnormality cannot be found because the abnormality does not recur.
Setting up the failure mode recall function
Turn ON the power supply. <Preparation of the remote controller>
While pressing OPERATION SELECT button and TEMP
button on the remote
controller at the same time, press RESET button.
First, release RESET button.
Hold down the other 2 buttons for another 3 seconds. Make sure that the indicators on
the LCD screen shown in the right fi gure are all displayed. Then release the buttons.
Press STOP/OPERATE (OFF/ON) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit.
1
Judgment of indoor/outdoor abnormality
Before blinking, does the upper lamp on the indoor unit stay ON for 3 seconds? When it stays ON for 3 seconds (without beep):The outdoor unit is abnormal.
The indoor unit is abnormal. Check the blinking pattern, and identify the abnormal point by referring to the table of indoor unit failure mode recall function. (Refer to indoor unit service manual.) Make sure to check at least 2 consecutive blinking cycles.
2
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller.
The outdoor unit is abnormal. Check the blinking pattern, and identify the abnormal point by referring to the table of outdoor unit failure mode recall function. (Refer to 12-2.3) Make sure to check at least 2 consecutive blinking cycles.
3
Repair the failure parts.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" mentioned above.
Press STOP/OPERATE (OFF/ON) button of the remote controller (the set temperature is displayed)
with the remote controller headed towards the indoor unit. Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
Operational procedure
Yes (Blinks)
No (OFF)
1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received.
2. Blinking pattern when the indoor unit is abnormal:
3.Blinking pattern when the outdoor unit is abnormal:
ON
OFF
Beeps
Repeated cycle Repeated cycle
ON
OFF
No beep Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5-
second interval
2.5-second OFF 3-second ON
Blinking at 0.5­second interval
Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5­second interval
No beep Beeps
Repeated cycle
2.5-second OFF 3-second ON
Blinking at 0.5­second interval
Repeated cycle
Beeps
WEEKLY TIMER
MSZ-AP·VG(K)
OBH789
33
2. Flow chart of the detailed outdoor unit failure mode recall function
2.Blinking pattern when outdoor unit is abnormal:
ON
OFF
No beep
Beeps
Repeated cycle
2.5-second OFF 3-second ON
Blinking at 0.5­second interval
No beep Beeps
Repeated cycle
2.5-second OFF 3-second ON
Blinking at 0.5-
second interval
Repeated cycle
Does the upper lamp of OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: The outdoor unit is abnormal. Beep is emitted
at the same timing as the blinking of the upper lamp on the indoor unit.
2
Yes (Blinks
)
No (OFF)
The outdoor unit might be abnormal. Check if outdoor unit is abnormal according to the following procedures.
Operational procedure
Make sure that the remote controller is set to the failure mode recall function.
With the remote controller headed towards the indoor unit, press TEMP
button to adjust the set temperature to 25°C. 1
1. Regardless of normal or abnormal condition, 2 short beeps are emitted as the signal is received.
The outdoor unit is abnormal. Check the blinking pattern, and identify the abnormal point by referring to the table of outdoor unit failure mode recall function (12-2.3.). Make sure to check at least 2 consecutive blinking cycles.
2
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller.
Repair the failure parts.
The outdoor unit is normal.
Release the failure mode recall function accord­ing to the left mentioned procedure.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" (12-2.1.).
Press STOP/OPERATE (OFF/ON) button of the remote controller (the set temperature is displayed) with
the remote controller headed towards the indoor unit.
Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.
4
Release the failure mode recall function according to "Releasing the failure mode recall function" men-
tioned above.
NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
4
The information regarding whether the
connected outdoor unit is a low-standby-
power model or a non-low-standby-power model will also be initialized.
(Default= compatible with a low-standby-
power model)
NOTE: It takes up to 1 minute to indicate the outdoor unit abnor-
mality.
Even if the upper lamp on the indoor unit is not lighting,
keep checking at least 1 minute or longer.
OBH789
34
3. Table of outdoor unit failure mode recall function
NOTE: Blinking patterns of this mode differ from the ones of TROUBLESHOOTING CHECK TABLE (12-3.).
Upper lamp
(Indoor unit)
Abnormal point
(Failure mode/protection)
LED indication
(Outdoor P.C. board)
Condition Remedy
Indoor/outdoor
unit failure
mode recall
function
Outdoor unit failure mode
recall function
OFF None (Normal) — 1-time fl ash
2.5 seconds OFF
Indoor/outdoor communication, receiving error
Any signals from the inverter P.C. board cannot be received normally for 3 minutes.
•Refer to 12-5.
How to check miswiring and serial signal error.
○○
Indoor/outdoor communication, receiving error
Although the inverter P.C. board sends signal "0", signal "1" has been received 30 consecutive times.
•Refer to 12-5.
How to check miswiring and serial signal error.
2-time fl ash
2.5 seconds OFF
Outdoor power system
Overcurrent protection cut-out operates 3 consecutive times within 1 minute after the compressor gets started.
Reconnect connectors.
Refer to 12-5.
"How to check inverter/ compressor".
Check stop valve.
○○
3-time fl ash
2.5 seconds OFF
Discharge temperature thermistor
1-time fl ash every
2.5 seconds
Thermistor shorts or opens during compressor running.
Refer to 12-5. "Check of outdoor thermistors". Defective outdoor thermistors can be identifi ed by checking the blinking pattern of LED.
○○
Defrost thermistor Fin temperature thermistor 3-time fl ash
2.5 seconds OFF P.C. board temperature thermistor
4-time fl ash
2.5 seconds OFF Ambient temperature thermistor
2-time fl ash
2.5 seconds OFF Outdoor heat exchanger temperature thermistor
4-time fl ash
2.5 seconds OFF
Overcurrent 11-time fl ash
2.5 seconds OFF
Large current fl ows into power module (IC700).
Reconnect compressor connector.
Refer to 12-5.
"How to check inverter/ compressor".
Check stop valve.
Compressor synchronous abnormality (Compressor start-up failure protection)
12-time fl ash
2.5 seconds OFF
Waveform of compressor current is distorted.
Reconnect compressor connector.
Refer to 12-5.
"How to check inverter/ compressor".
5-time fl ash
2.5 seconds OFF
Discharge temperature
Temperature of discharge temperature thermistor exceeds 116°C, compressor stops. Compressor can restart if discharge temperature thermistor reads 100°C or less 3 minutes later.
Check refrigerant circuit and refrigerant amount.
Refer to 12-5.
"Check of LEV".
6-time fl ash
2.5 seconds OFF
High pressure
Temperature of indoor coil thermistor exceeds 70°C in HEAT mode. Temperature of defrost thermistor exceeds 70°C in COOL mode.
Check refrigerant circuit and refrigerant amount.
Check stop valve.
7-time fl ash
2.5 seconds OFF
Fin temperature/P.C. board temperature
7-time fl ash
2.5 seconds OFF
Temperature of fi n temperature thermistor on the inverter P.C. board exceeds 75 ~ 86°C, or temperature of P.C. board temperature thermistor on the inverter P.C. board exceeds 72 ~ 85°C.
Check around outdoor unit.
Check outdoor unit air passage.
Refer to 12-5.
"Check of outdoor fan motor".
8-time fl ash
2.5 seconds OFF
Outdoor fan motor
Outdoor fan has stopped 3 times in a row within 30 seconds after outdoor fan startup.
Refer to 12-5. "Check of outdoor fan motor". Refer to 12-5.
"Check of inverter P.C. board".
9-time fl ash
2.5 seconds OFF
Nonvolatile memory data 5-time fl ash
2.5 seconds OFF
Nonvolatile memory data cannot be read properly.
Replace the inverter P.C. board.
○○
Power module (IC700) 6-time fl ash
2.5 seconds OFF
The interface short circuit occurs in the output of the power module (IC700). The compressor winding shorts circuit.
Refer to 12-5. "How to check inverter/ compressor".
OBH789
35
NOTE: Blinking patterns of this mode differ from the ones of TROUBLESHOOTING CHECK TABLE (12-3.).
Upper lamp (Indoor unit)
Abnormal point
(Failure mode/protection)
LED indication
(Outdoor P.C. board)
Condition Remedy
Indoor/outdoor
unit failure
mode recall
function
Outdoor unit failure mode
recall function
10-time fl ash
2.5 seconds OFF
Discharge temperature
Temperature of discharge temperature thermistor has been 50°C or less for 20 minutes.
Refer to 12-5.
"Check
of LEV".
Check refrigerant circuit and refrigerant amount.
11-time fl ash
2.5 seconds OFF
Bus-bar voltage (DC) 8-time fl ash
2.5 seconds OFF
Bus-bar voltage of inverter cannot be detected normally.
Refer to 12-5. "How to check inverter/ compressor".
Each phase current of compressor
9-time fl ash
2.5 seconds OFF
Each phase current of compressor
cannot be detected normally. 14-time fl ash or more
2.5 seconds OFF
Stop valve (Closed valve) 14-time fl ash
2.5 seconds OFF
Closed valve is detected by
compressor current.
Check stop valve.
○○
4-way valve/ Pipe temperature
16-time fl ash
2.5 seconds OFF
The 4-way valve does not work
properly.
The indoor coil thermistor detects an
abnormal temperature.
Check the 4-way valve.
Replace the inverter
P.C. board. Outdoor refrigerant system abnormality
1-time fl ash
2.5 seconds OFF
A closed valve and air trapped in the refrigerant circuit are detected based on the temperature sensed by the indoor and outdoor thermistors and the current of the compressor.
Check for a gas leak
in a connecting piping
etc.
Check the stop valve.
Refer to 12-5.
“Check of outdoor
refrigerant circuit”.
○○
OBH789
36
12-3. TROUBLESHOOTING CHECK TABLE
No. Symptom LED indication
Abnormal point/ Con-
dition
Condition Remedy
1
Outdoor unit does not op­erate.
1-time fl ash every
2.5 seconds
Outdoor power sys­tem
Overcurrent protection cut-out operates 3 consecutive times within 1 minute after the compressor gets started.
Reconnect connector of compres­sor.
Refer to 12-5.
"How to check
inverter/compressor".
Check stop valve.
2
Outdoor thermistors Discharge temperature thermistor, fi n temperature thermistor,
defrost thermistor, P.C. board temperature thermistor, outdoor heat exchanger temperature thermistor or ambient tempera­ture thermistor shorts or opens during compressor running.
Refer to 12-5.
"Check of outdoor
thermistors".
3
Outdoor control sys­tem
Nonvolatile memory data cannot be read properly. (Upper lamp of OPERATION INDICATOR lamp on the indoor unit lights up or fl ashes 7-time.)
Replace inverter P.C. board.
4
6-time fl ash
2.5 seconds OFF
Serial signal The communication fails between the indoor and outdoor unit
for 3 minutes.
Refer to 12-5.
"How to check
miswiring and serial signal error.
5
11-time fl ash
2.5 seconds OFF
Stop valve/ Closed valve
Closed valve is detected by compressor current.
Check stop valve.
6
14-time fl ash
2.5 seconds OFF
Outdoor unit (Other abnormality)
Outdoor unit is defective.
Refer to 12-2.2. "Flow chart of the detailed outdoor unit failure mode recall function".
7
16-time fl ash
2.5 seconds OFF
4-way valve/
Pipe temperature
The 4-way valve does not work properly. The indoor coil thermistor detects an abnormal temperature.
Refer to 12-5.
"Check of R.V.
coil".
Replace the inverter P.C. board.
8
17-time fl ash
2.5 seconds OFF
Outdoor refrigerant system abnormality
A closed valve and air trapped in the refrigerant circuit are detected based on the temperature sensed by the indoor and outdoor thermistors and the current of the compressor.
Check for a gas leak in a connecting piping etc.
Check the stop valve.
Refer to 12-5.
“Check of outdoor
refrigerant circuit”.
9
'Outdoor unit stops and restarts 3 minutes later' is repeated.
2-time fl ash
2.5 seconds OFF
Overcurrent protec­tion
Large current fl ows into power module (IC700).
Reconnect connector of compressor.
Refer to 12-5. "How to check inverter/compressor".
Check stop valve.
10
3-time fl ash
2.5 seconds OFF
Discharge tem­perature overheat protection
Temperature of discharge temperature thermistor exceeds 116°C, compressor stops. Compressor can restart if discharge temperature thermistor reads 100°C or less 3 minutes later.
Check refrigerant circuit and refrig­erant amount.
Refer to 12-5.
"Check of LEV".
11
4-time fl ash
2.5 seconds OFF
Fin temperature / P.C. board tem­perature thermistor overheat protection
Temperature of fi n temperature thermistor on the heat sink exceeds 75 ~ 86°C or temperature of P.C. board temperature thermistor on the inverter P.C. board exceeds 72 ~ 85°C.
Check around outdoor unit.
Check outdoor unit air passage.
Refer to 12-5.
"Check of outdoor
fan motor".
12
5-time fl ash
2.5 seconds OFF
High pressure pro­tection
Indoor coil thermistor exceeds 70°C in HEAT mode. Defrost thermistor exceeds 70°C in COOL mode.
Check refrigerant circuit and refrig­erant amount.
Check stop valve.
13
8-time fl ash
2.5 seconds OFF
Compressor syn­chronous abnormal­ity
The waveform of compressor current is distorted.
Reconnect connector of compressor.
Refer to 12-5. "How to check inverter/compressor".
14
10-time fl ash
2.5 seconds OFF
Outdoor fan motor Outdoor fan has stopped 3 times in a row within 30 seconds
after outdoor fan start-up.
Refer to 12-5.
"Check of outdoor
fan motor.
Refer to 12-5.
"Check of inverter
P.C. board.
15
12-time fl ash
2.5 seconds OFF
Each phase current of compressor
Each phase current of compressor cannot be detected nor­mally.
Refer to 12-5.
"How to check
inverter/compressor".
16
13-time fl ash
2.5 seconds OFF
Bus-bar voltage (DC)
Bus-bar voltage of inverter cannot be detected normally.
It occurs with following case. Instantaneous power voltage drop. (Short time power failure) (AP50)
Refer to 12-5.
"Check of power
supply". (AP50)
Refer to 12-5.
"How to check in-
verter/compressor".
17
Outdoor unit operates.
1-time fl ash
2.5 seconds OFF
Frequency drop by current protection
When the input current exceeds approximately 10A, compres­sor frequency lowers.
The unit is normal, but check the following.
Check if indoor fi lters are clogged.
Check if refrigerant is short.
Check if indoor/outdoor unit air circulation is short cycled.
18
3-time fl ash
2.5 seconds OFF
Frequency drop by high pressure pro­tection
Temperature of indoor coil thermistor exceeds 55°C in HEAT mode, compressor frequency lowers.
19
Frequency drop by defrosting in COOL mode
Indoor coil thermistor reads 8°C or less in COOL mode, com­pressor frequency lowers.
4-time fl ash
2.5 seconds OFF
Frequency drop by discharge tempera­ture protection
Temperature of discharge temperature thermistor exceeds 111°C, compressor frequency lowers.
Check refrigerant circuit and refrig­erant amount.
Refer to 12-5.
"Check of LEV".
Refer to 12-5.
"Check of outdoor
thermistors".
20
MUZ-
AP25/35/42
5-time fl ash
2.5 seconds OFF
Outside temperature thermistor protec­tion
When the outside temperature thermistor shorts or opens, protective operation without that thermistor is performed.
Refer to 12-5.
Check of outdoor
thermistors.
OBH789
37
No. Symptom LED indication
Abnormal point/ Con-
dition
Condition Remedy
21
Outdoor unit operates.
7-time fl ash
2.5 seconds OFF
Low discharge tem­perature protection
Temperature of discharge temperature thermistor has been 50°C or less for 20 minutes.
Refer to 12-5.
"Check of LEV".
Check refrigerant circuit and refrig­erant amount.
22
8-time fl ash
2.5 seconds OFF
PAM protection PAM: Pulse Ampli­tude Modulation
The overcurrent fl ows into PFC (Power factor correction: IC820) or the bus-bar voltage reaches 394 V or more, PAM stops and restarts.
This is not malfunction. PAM pro­tection will be activated in the fol­lowing cases:
1 Instantaneous power voltage
drop. (Short time power failure)
2 When the power supply voltage
is high.
23
9-time fl ash
2.5 seconds OFF
Inverter check mode The connector of compressor is disconnected, inverter check
mode starts.
Check if the connector of the com­pressor is correctly connected. Refer to 12-5.
"How to check
inverter/compressor".
NOTE: 1. The location of LED is illustrated at the right fi gure. Refer to 12-6.1.
2. LED is lighted during normal operation. The fl ashing frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the fl ashing frequency is “2”.
ON OFF
2.5-second OFF
2.5-second OFF
0.5-second ON
0.5-second ON
LED
Flashing
Inverter P.C. board
OBH789
38
12-4. TROUBLE CRITERION OF MAIN PARTS
Part name Check method and criterion Figure
Defrost thermistor (RT61) Fin temperature
thermistor (RT64) Ambient temperature
thermistor (RT65) Outdoor heat exchanger
temperature thermistor (RT68)
Measure the resistance with a tester. Refer to 12-6. “Test point diagram and voltage”, 1. “Inverter P.C.
board”, for the chart of thermistor.
Discharge temperature thermistor (RT62)
Measure the resistance with a tester. Before measurement, hold the thermistor with your hands to warm it up.
Refer to 12-6. “Test point diagram and voltage”, 1. “Inverter P.C. board”, for the chart of thermistor.
Compressor
Measure the resistance between terminals using a tester. (Temperature: -10 ~ 40°C)
Normal (Ω)
MUZ-AP25/35VG(H) MUZ-AP42/50VG(H)
U-V U-W V-W
1.59 ~ 2.16 0.82 ~ 1.11
W
U
V
WHT
RED BLK
Outdoor fan motor
Measure the resistance between lead wires using a tester. (Temperature: -10 ~ 40°C)
Color of lead wire
Normal (Ω)
MUZ-AP25/35/42VG(H) MUZ-AP50VG(H)
RED – BLK BLK – WHT
WHT – RED
32 ~ 43 15 ~ 20
W
U
V
WHT
RED BLK
R. V. coil (21S4)
Measure the resistance using a tester. (Temperature: -10 ~ 40°C)
Normal (kΩ)
1.41 ~ 2.00
Expansion valve coil (LEV)
Measure the resistance using a tester. (Temperature: -10 ~ 40°C)
Color of lead wire Normal (Ω)
RED – ORN
37 ~ 54
RED – WHT
RED – BLU
RED – YLW
RED
(+12V)
YLW
BLU
WHT
ORN
LEV
Defrost heater
MUZ-AP•VGH
Normal (Ω)
MUZ-AP25/35/42VGH MUZ-AP50VGH
802 ~ 980 370 ~ 428
OBH789
39
12-5. TROUBLESHOOTING FLOW
A How to check inverter/compressor
Refer to 12-5. “Check of compressor operation time”. Does the compressor operate continuously?
Refer to 12-5. “Check of compressor start failure”.
OK
No
Yes
Refer to 12-5. “Check of compressor winding”. Is the compressor normal?
Replace the compressor.
No
Yes
B Check of open phase
C Check of compressor
With the connector between the compressor and the power module (IC700) disconnected, activate the inverter and check if the inverter is normal by measuring the voltage balance between the terminals.
Output voltage is 50 - 130 V. (The voltage may differ according to the tester.) << Operation method>>
Start cooling or heating operation by pressing EMERGENCY OPERATION switch on the indoor unit. (TEST RUN OPERA-
TION: Refer to 9-3.) <<Measurement point>> At 3 points BLK (U)-WHT (V) BLK (U)-RED (W) WHT(V)-RED (W)
NOTE: 1. Output voltage varies according to power supply voltage.
2. Measure the voltage by analog type tester.
3. During this check, LED of the inverter P.C. board fl ashes 9 times. (Refer to 12-6.1.)
Measure AC voltage between the lead wires at 3 points.
Are the voltages balanced?
Disconnect the connector between the compressor and the power module (IC700).
Replace the inverter P.C. board.
Check the voltage between terminals.
Check the compressor.
See 12-5. “Check of compressor”.
No
Yes
See 12-5. “Check of open phase”.
OBH789
40
F Check of compressor start failure
D Check of compressor winding
E Check of compressor operation time
Disconnect the connector between the compressor and the power module (IC700), and measure the resistance between the compressor terminals.
<<Measurement point>> At 3 points BLK-WHT BLK-RED WHT-RED <<Judgement>> Refer to 12-4. 0 [Ω] ················Abnormal [short] Infinite [Ω] ·······Abnormal [open] NOTE: Be sure to zero the ohmmeter before measurement.
Measure the resistance between the lead wires at 3 points.
1 Heat the compressor with a drier for about 20 minutes. Do not recover refrigerant gas while heating.
Heating part
Connect the compressor and activate the inverter. Then measure the time until the inverter stops due to overcurrent. <<Operation method>> Start heating or cooling operation by pressing EMERGENCY OPERATION switch on the indoor unit. (TEST RUN OPERATION: Refer to 9-3.) <<Measurement>> Measure the time from the start of compressor to the stop of compressor due to overcurrent.
Compressor starts Abnormal
(IC700 failure) (Compressor winding short)
Abnormal (Compressor lock out) (Starting defect)
Abnormal (Poor contact) (Inverter P.C. board defect) (Disconnected connector)
Abnormal (Refrigerant circuit defect) (Closed valve)
Normal
0 second 1 second
2 seconds
10 seconds
10 minutes
<<Judgement>>
After the compressor is heated with a drier, does the compressor start?
1
Replace the compressor.
Compressor start failure. Activate pre-heat control. (Refer to 11-2. "PRE-HEAT CONTROL SETTING")
No
Yes
Does the compressor run for 10 seconds or more after it starts?
Check the refrigerant circuit. Check the stop valve.
Yes
No
Confi rm that ~ is normal.
•Electrical circuit check . Contact of the compressor connector . Output voltage of inverter P.C. board and balance of them (See 12-5. ) . Direct current voltage between DB61(+) and (-) on the inverter P.C. board . Voltage between outdoor terminal block S1-S2
OBH789
41
G Check of outdoor thermistors
Replace the thermistor except RT64. When RT64 is abnormal, replace the inverter P.C. board.
Replace the inverter P.C. board.
No
No
Is the resistance of thermistor normal? (Refer to 12-6.1.)
Reconnect the connector of thermistor. Turn ON the power supply and press EMERGENCY OPERATION switch.
Does the unit operate for 10 minutes or more without showing thermistor abnormality?
OK (Cause is poor contact.)
Yes
Yes
Disconnect the connector of thermistor in the inverter P.C. board (see below table), and measure the resistance of thermistor.
Thermistor Symbol Connector, Pin No. Board
Defrost RT61 Between CN641 pin1 and pin2
Inverter P.C. board
Discharge temperature RT62 Between CN641 pin3 and pin4 Fin temperature RT64 Between CN642 pin1 and pin2 Ambient temperature RT65 Between CN643 pin1 and pin2 Outdoor heat exchanger temperature RT68 Between CN644 pin1 and pin3
OBH789
42
H Check of R.V. coil
First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 12-4. In case CN721 is disconnected or R.V. coil is open, voltage is generated between the terminal pins of the connector
although no signal is being transmitted to R.V. coil.
Check if CN721 is connected.
Is there 230 V AC between CN721 and
on the inverter P.C. board 3 minutes
after the power supply is turned ON?
No
Yes
Replace the inverter P.C. board.
Replace the 4-way valve.
Unit operates COOL mode even if it is set to HEAT mode.
Is there 230 V AC between CN721 and
on the inverter P.C. board 3 minutes
after the power supply is turned ON?
Yes
No
Replace the inverter P.C. board.
Replace the 4-way valve.
Unit operates HEAT mode even if it is set to COOL mode.
Disconnect connector between the compressor and the IGBT module (IC700). Turn ON the power supply and press EMERGENCY OPERATION switch twice (HEAT mode).
Disconnect connector between the compressor and the IGBT module (IC700). Turn ON the power supply and press EMERGENCY OPERATION switch once (COOL mode).
OBH789
43
I Check of outdoor fan motor
Is the resistance between each ter­minal of outdoor fan motor normal? (Refer to 12-4.)
Disconnect CN932 from the inverter P.C. board, and turn on the power supply.
Rotate the outdoor fan motor manually and measure the voltage of CN931. Between 1(+) and 5(-) Between 2(+) and 5(-) Between 3(+) and 5(-)
Does the voltage between each terminal become 5 and 0 V DC repeatedly?
Does the outdoor fan motor rotate smoothly?
Replace the outdoor fan motor.
Replace the inverter P.C. board.
Yes
Yes
No
(Fixed to either 5 or 0 V DC)
No
No
Yes
Disconnect the connectors CN931 and CN932 from the inverter P.C. board. Check the connection between the connector CN931 and CN932.
OBH789
44
J Check of power supply
Is there voltage 230 V AC between the indoor terminal block S1 and S2?
No
Yes
Replace the indoor electronic control P.C. board.
Rectify indoor/outdoor connecting wire.
Yes
If lights up, OK. If fl ashes, refer to 12-3.
Does the upper lamp of OPERATION INDICATOR lamp on the indoor unit light up?
Does LED on the inverter P.C. board light up or fl ash? (Refer to 12-6.1.)
No
Replace the inverter P.C. board.
Is there bus-bar voltage 260 - 370 V DC between DB61 (+) and DB61 (–) on the inverter P.C. board? (Refer to 12-6.1.)
No
Check the electric parts in main circuit.
Yes
Yes
No
Disconnect the connector between the compressor and the
power module (IC700). Turn ON power supply and press EMERGENCY OPERATION switch.
Inverter P.C. board (Solder side)
DB61
260 - 370 V DC
OBH789
45
Press STOP/OPERATE (OFF/ON) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1
Expansion valve operates in full-opening direction.
OK
NOTE: After check of LEV, do the undermentioned operations.
1. Turn OFF the power supply and turn it ON again.
2. Press RESET button on the remote controller.
1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received.
Measure each voltage between connector pins of CN724 on the inverter P.C. board.
1. Pin (-) — Pin (+)
2. Pin (-) — Pin (+)
3. Pin (-) — Pin (+)
4. Pin (-) — Pin (+) Is there about 3 - 5 V AC between each?
NOTE: Measure the voltage by an analog
tester.
Properly fi x the LEV coil to the expansion valve.
Replace the inverter P.C. board.
Replace the LEV coil.
Replace the expansion valve.
Is LEV coil properly fi xed to the expansion valve?
Does the resistance of LEV coil have the characteristics? (Refer to 12-4.)
Do you hear the expansion valve "click, click·······"? Do you feel the expansion valve vibrate when touching it ?
Turn ON the power supply. <Preparation of the remote controller>
While pressing both OPERATION SELECT button and TEMP button on the remote controller at the same time, press RESET button. First, release RESET button.
Hold down the other 2 buttons for another 3 seconds.
Make sure that the indicators on the LCD screen shown in the right fi gure are all displayed. Then re- lease the buttons.
Yes
No
No
Yes
No
Yes
No
Yes
K Check of LEV (Expansion valve)
WEEKLY TIMER
MSZ-AP·VG(K)
OBH789
46
Check the outdoor fan motor. (Refer to 12-5. .)
Is the fuse (F901) blown on the in­verter P.C. board?
Check the connection of the connectors (CN931, CN932) of the outdoor fan motor. If the connection is poor, make it correct.
Operate the outdoor unit by starting EMERGENCY OPERATION.
Check the LED indication on the in­verter P.C. board. Does the LED fl ash 10 times?
Replace the inverter P.C. board.
Check the corresponding parts following LED indication. (Refer to 12-3.)
Yes
No
Yes (10-time fl ash)
No
L Check of inverter P.C. board
OBH789
47
M How to check miswiring and serial signal error
• Turn OFF inverter-controlled lighting equipment.
• Turn OFF the power supply and then turn ON again.
• Press EMERGENCY OPERATION switch.
A
Is serial signal error indicated 6 minutes later?
B
Yes
• Reinstall either the unit or the light away from each other.
• Attach a fi lter on remote control receiving section of the indoor unit.
No
Turn the main power supply OFF.
Is there rated voltage in the power supply?
Yes
No
Check for incorrect indoor-outdoor connecting wiring.
Check the power supply.
A
Is there rated voltage between outdoor terminal block S1 and S2?
Yes
Check for miswiring, broken wires, and loose wire connection between the main power supply and outdoor terminal block S1 and between the main power supply and outdoor terminal block S2.
Wait for 2 or more minutes after the main power supply is turned on. Touch S2 and S3 with tester probes and start the emergency operation.
When the emergency operation starts, does the rated voltage occur for 2 seconds between indoor terminal block S2 and S3?
Yes
No
Does the upper lamp of OPERA­TION INDICATOR lamp on the indoor unit blink continuously 6 minutes after the emergency operation starts?
No
Does the outdoor LED light up?
Replace the indoor electronic control P.C. board.
Yes
Does the outdoor LED blink 6 times?
Yes
Confi rm that the thermostat is OFF and wiring is not loose.
No
Does DC (6V or more) occur between indoor terminal block S2 and S3?
Yes
Replace the outdoor inverter P.C. board. 1
No
Replace the indoor elec­tronic control P.C. board.
1
1. Electric charge may remain immediately after the main power supply is turned OFF. Perform the procedure after 3 minutes.
Replace the outdoor inverter P.C. board. 1
Yes
Turn the main power supply ON.
B
No
No
Was the indoor unit ever connected to the Multi (MXZ) series and operated (turned on)?
The connection information to the Multi series is stored in the indoor unit. Refer to “Deleting the memorized abnormal condition” described in 12-2.1 to clear the error history. When the error history is being cleared, the con­nection information also will be initialized. The indoor unit will be compatible with a low-standby-power model after initialization.
OK
Yes
No
OBH789
48
N Check of the outdoor refrigerant circuit
Has the operation stopped during pump down?
Was the operation started with the stop valve closed, and was it opened during operation?
No
Yes
The operation has stopped to pre­vent the diesel explosion caused by air trapped in the refrigerant circuit. Close the stop valve, and disconnect the power plug or turn the breaker OFF.
The unit occasionally stops when the stop valve is opened or closed during operation. Open the stop valve and start the cooling operation again.
Yes
No
The refrigerant gas amount may be 60% or less than the normal amount. Identify where the gas is leaking from, and fi x the leak.
CAUTION : Do not start the operation again to prevent hazards.
OBH789
49
O Electromagnetic noise enters into TV sets or radios
Yes
Is the unit earthed?
No
Earth the unit.
Yes
Is the distance between the antennas and the indoor unit within 3 m, or is the distance between the antennas and the outdoor unit within 3 m?
No
Extend the distance between the antennas and the indoor unit, and/or the antennas and the outdoor unit.
Is the distance between the TV sets or radios and the indoor unit within 1 m, or is the distance between the TV sets or radios and the outdoor unit within 3 m?
Yes
Extend the distance between the TV sets and/ or radios and the indoor unit, or the TV sets or radios and the outdoor unit.
Are the antennas damaged? Is the coaxial cable damaged? Is there any poor contact in the anten­na wiring?
Yes
No
No
Replace or repair the antenna. Replace or repair the coaxial cable.
Is the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas close?
Yes
Extend the distance between the indoor/outdoor connecting wire of the air conditioner and the wir­ing of the antennas.
No
Even if all of the above conditions are fulfi lled, the electromagnetic noise may enter, depending on the electric fi eld strength or the installation condition (combination of specifi c conditions such as antennas or wiring). Check the following before asking for service.
1. Devices affected by the electromagnetic noise TV sets, radios (FM/AM broadcast, shortwave)
2. Channel, frequency, broadcast station affected by the electromagnetic noise
3. Channel, frequency, broadcast station unaffected by the electromagnetic noise
4. Layout of: indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, earth wire, antennas, wiring from antennas, receiver
5. Electric fi eld intensity of the broadcast station affected by the electromagnetic noise
6. Presence or absence of amplifi er such as booster
7. Operation condition of air conditioner when the electromagnetic noise enters in
1) Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic noise.
2) Within 3 minutes after turning ON the power supply, press STOP/OPERATE (OFF/ON) button on the remote controller for power ON, and check for the electromagnetic noise.
3) After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the electromagnetic noise.
4) Press STOP/OPERATE (OFF/ON) button on the remote controller for power OFF, when the outdoor unit stops but the indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise.
OBH789
50
-20 -10 0 10 20 30 40
0
10
20
30
40
50
60
70
80
90
100
Temperature( )
Defrost thermistor(RT61) Ambient temperature thermistor(RT65) Outdoor heat exchanger temperature thermistor(RT68)
0 1020304050607080
0
20
40
60
80
100
120
140
160
180
200
Temperature( )
Fin temperature thermistor(RT64)
Resistance(k )
Resistance(k )
Temperature (°C)
Discharge temperature thermistor (RT62)
5HVLVWDQFHN
0
100
200
300
400
500
600
700
800
0 102030405060708090100110120
1. Inverter P.C. board
12-6. TEST POINT DIAGRAM AND VOLTAGE
Fin temperature
thermistor/RT64
(CN642)
Ambient temperature
thermistor/RT65
(CN643)
Discharge temperature
thermistor/RT62
(CN641)
Defrost thermistor
/RT61(CN641)
DB61 260 - 370 V DC
Front side of unit
230 V AC
Output to drive compressor (LDU, LDV, LDW)
(+)
(-)
Fuse (F701) T3.15AL250V
R.V.coil (CN721) 230 V AC
Jumper wire for changing defrost setting (JS)
Signal of outdoor
fan motor (CN931)
230 V AC
Outdoor heat exchanger
temperature thermistor
/RT68 (CN644)
Jumper wire for pre-heat control setting (JK)
Fuse (F801) T3.15AL250V
Back side of unit
LEV (CN724)
Output to drive outdoor fan motor (CN932)
LED
MUZ-AP25VG MUZ-AP35VG MUZ-AP42VG MUZ-AP50VG MUZ-AP25VGH MUZ-AP35VGH MUZ-AP42VGH MUZ-AP50VGH
Defrost heater (CN722) (MUZ-AP•VGH)
Fuse (F62) 15 A 250 V
Fuse (F901) T3.15AL250V
Smoothing capacitor (C63)
Smoothing capacitor (C62)
Smoothing capacitor (C61)
(MUZ-AP42/50)
Fuse (F61) 25 A 250V
OBH789
13-1. MUZ-AP25VG MUZ-AP35VG MUZ-AP42VG MUZ-AP25VGH MUZ-AP35VGH MUZ-AP42VGH
NOTE: Turn OFF the power supply before disassembly.
Photos: MUZ-AP42VGH
OPERATING PROCEDURE PHOTOS
1. Removing the cabinet
(1) Remove the screw fixing the service panel. (2) Pull down the service panel and remove it. (3) Disconnect the power supply cord and indoor/outdoor
connecting wire. (4) Remove the screws fixing the top panel. (5) Remove the top panel. (6) Remove the screws fixing the cabinet. (7) Remove the cabinet. (8) Remove the screws fixing the back panel. (9) Remove the back panel.
Photo 1
Photo 2
51
(1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector shown below has the
locking mechanism.
Slide the sleeve. Pull the terminal while pushing the locking lever.
Hold the sleeve, and pull out the terminal slowly.
Connector
Sleeve
Locking lever
Back panel
Service
panel
Screws of the cabinet
Screws of the
top panel
<Detaching method of the terminal with locking mechanism >
The terminal which has the locking mechanism can be detached as shown below. There are following 2 types of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching.
DISASSEMBLY INSTRUCTIONS
13
Screw of the cabinet
Screws of the back panel
Screws of the terminal block support and the back panel
Screws of the service panel
Direction to remove
Hooks
Screws of the top panel
Screws of the cabinet
OBH789
52
OPERATING PROCEDURE
PHOTOS
2. Removing the inverter assembly, inverter P.C. board
(1) Remove the cabinet and panels. (Refer to section 1.) (2) Disconnect the lead wire to the reactor and the following con-
nectors:
<Inverter P.C. board>
CN721 (R.V. coil) CN722 (Defrost heater)(MUZ-AP•VGH) CN931, CN932 (Fan motor) CN641 (Defrost thermistor and discharge temperature ther-
mistor)
CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor)
CN724 (LEV) (3) Remove the compressor connector (CN61). (4) Remove the screws fixing the heat sink support and the sep-
arator. (5) Remove the fixing screws of the terminal block support and
the back panel. (6) Remove the inverter assembly. (7) Remove the screw of the earth wire and screw of the termi-
nal block support. (8) Remove the heat sink support from the P.C. board support. (9) Remove the screw of the inverter P.C. board and remove the
inverter P.C. board from the P.C. board support.
Photo 3
Photo 4 (Inverter assembly)
Photo 5
3. Removing R.V. coil
(1) Remove the cabinet and panels. (Refer to section 1.) (2) Disconnect the following connectors: <Inverter P.C. board>
CN721 (R.V. coil) (3) Remove the R.V. coil.
4. Removing the discharge temperature thermistor, defrost thermistor, outdoor heat exchanger tempera­ture thermistor and ambient temperature thermistor
(1) Remove the cabinet and panels. (Refer to section 1.) (2) Disconnect the lead wire to the reactor and the following con-
nectors: <Inverter P.C. board> CN641 (Defrost thermistor and discharge temperature ther-
mistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor)
(3) Pull out the discharge temperature thermistor from its holder. (4) Pull out the defrost thermistor from its holder. (Photo 6) (5) Pull out the outdoor heat exchanger temperature thermistor
from its holder. (Photo 6)
(6) Pull out the ambient temperature thermistor from its holder.
Discharge temperature thermistor
Screw of the R.V. coil
Screws of the heat sink support and the separator
Screws of the terminal block support and the back panel
Heat sink
Screw of the earth wire
Screw of the Terminal block support
Screw of the inverter P.C. board
Heat sink support
P.C. board support
Terminal block support
OBH789
53
OPERATING PROCEDURE
PHOTOS
5. Removing outdoor fan motor
(1) Remove the cabinet and panels. (Refer to section 1.) (2) Disconnect the following connectors: <Inverter P.C. board>
CN931, CN932 (Fan motor) (3) Remove the propeller fan nut. (4) Remove the propeller fan. (5) Remove the screws fixing the fan motor. (6) Remove the fan motor.
Photo 6
NOTE: MUZ-AP25/35VG/H are different in the installa-
tion position of thermistors.
Photo 7
6. Removing the compressor and 4-way valve
(1) Remove the cabinet and panels. (Refer to section 1.) (2) Remove the inverter assembly. (Refer to section 2.) (3) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure gauge
shows 0 kg/cm2 (0 MPa).
(4) Detach the brazed part of the suction and the discharge pipe
connected with compressor. (5) Remove the nuts of compressor legs. (6) Remove the compressor. (7) Detach the brazed part of pipes connected with 4-way valve.
7. Removing the LEV assembly
(1) Detaching the brazed part of pipes connected with LEV
valve.
Photo 8
Defrost thermistor
Outdoor heat exchanger tempera­ture thermistor
Brazed parts of 4-way valve
Ambient temperature thermistor
Brazed parts of LEV valve
Propeller fan nut
Screws of the outdoor fan motor
Propeller fan
OBH789
54
13-2. MUZ-AP50VG MUZ-AP50VGH
NOTE: Turn OFF the power supply before disassembly.
OPERATING PROCEDURE
PHOTOS
1. Removing the cabinet
(1) Remove the screws of the service panel. (2) Remove the screws of the top panel. (3) Remove the screw of the valve cover. (4) Remove the service panel. (5) Remove the top panel. (6) Remove the valve cover. (7) Disconnect the power supply and indoor/outdoor connect-
ing wire. (8) Remove the screws of the cabinet. (9) Remove the cabinet. (10)
Remove the screws of the back panel.
(11)
Remove the back panel.
Photo 2
Photo 1
Screws of the cabinet
Screws of the top panel
Screws of the cabinet
Screws of the top panel
Screw of the back panel
Screws of the service panel
Screw of the valve cover
Screws of the cabinet
Screws of the back panel
OBH789
55
OPERATING PROCEDURE PHOTOS
2. Removing the inverter assembly and inverter P.C. board
(1) Remove the cabinet and panels. (Refer to section 1.) (2) Disconnect the lead wire to the reactor and the following con-
nectors:
<Inverter P.C. board>
CN721 (R.V. coil) CN722 (Defrost heater)(MUZ-AP50VGH) CN931, CN932 (Fan motor) CN641 (Defrost thermistor and discharge temperature ther-
mistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor) CN724 (LEV)
(3) Remove the compressor connector (CN61). (4) Remove the screws fixing the heat sink support and the sep-
arator.
(5)
Remove the fixing screw of the P.B. support and the separator.
(6) Remove the fixing screws of the terminal block support and
the back panel.
(7) Remove the inverter assembly. (8) Remove the heat sink support from the P.C. board support. (9) Remove the screw of the inverter P.C. board and remove the
inverter P.C. board from the P.C. board support.
*
Connection procedure when attaching the inverter P.C.
board (Photo 4)
1. Connect the lead wires of the heat exchanger temperature thermistor, the defrost thermistor and discharge tempera­ture thermistor to the connector on the inverter P.C. board. Pull the lead wires toward you and put them on the right hook on the P.C. board support.
2. Connect the lead wires of the LEV to the connector on the inverter P.C. board. Pull the lead wires toward you and put them on the right hook on the P.C. board support.
3. Connect the lead wires of the ambient temperature ther­mistor to the connector on the inverter P.C. board. Pull the lead wires toward you and put them on the left hook on the P.C. board support so that the fan motor lead wires are bundled up as shown in Photo 4.
Photo 3
Photo 4
Photo 5 (Inverter assembly)
Screw of the heat sink
support and the separator
Screws of the terminal block support and the back panel
Screw of the P.B. support and the separator
Heat sink
Screws of the earth wire
Screw of the inverter P.C. board
Heat sink support
P.C. board support
Inverter P.C. board
Lead wires of the LEV
Lead wires of the heat exchanger temperature and discharge temperature thermistor
Inverter P.C. board support
Lead wires of the ambient temperature thermistor
OBH789
56
OPERATING PROCEDURE
PHOTOS
3. Removing R. V. coil
(1) Remove the cabinet and panels. (Refer to section 1.) (2) Disconnect the following connectors: <Inverter P.C. board>
CN721 (R.V. coil)
(3) Remove the R.V. coil.
Photo 6
Photo 7
4. Removing the discharge temperature thermistor, defrost thermistor, outdoor heat exchanger tempera­ture thermistor and ambient temperature thermistor
(1) Remove the cabinet and panels. (Refer to section 1.) (2) Disconnect the lead wire to the reactor and the following con-
nectors: <Inverter P.C. board> CN641 (Defrost thermistor and discharge temperature ther-
mistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor)
(3) Pull out the discharge temperature thermistor from its holder. (4) Pull out the defrost thermistor from its holder. (5) Pull out the outdoor heat exchanger temperature thermistor
from its holder.
(6) Pull out the ambient temperature thermistor from its holder.
5. Removing outdoor fan motor
(1) Remove the cabinet and panels. (Refer to section 1.) (2) Disconnect the following connectors: <Inverter P.C. board>
CN931, CN932 (Fan motor)
(3) Remove the propeller fan nut. (4) Remove the propeller fan. (5) Remove the screws fixing the fan motor. (6) Remove the fan motor.
Photo 8
Discharge temperature thermistor
Screw of the R.V. coil
Defrost thermistor
Outdoor heat exchanger tempera­ture thermistor
Ambient temperature thermistor
Screws of the outdoor fan motor
Propeller fan
Propeller fan nut
OBH789
57
OPERATING PROCEDURE
PHOTOS
6. Removing the compressor and 4-way valve
(1) Remove the cabinet and panels. (Refer to section 1.) (2) Remove the inverter assembly. (Refer to section 2.) (3) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure gauge
shows 0 kg/cm2 (0 MPa).
(4) Detach the brazed part of the suction and the discharge pipe
connected with compressor. (5) Remove the compressor nuts. (6) Remove the compressor. (7) Detach the brazed part of pipes connected with 4-way valve.
Photo 9
Brazed parts of 4-way valve
Suction pipe brazed part
Discharge pipe brazed part
OBH789
HEAD OFFICE: TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
© Copyright 2017 MITSUBISHI ELECTRIC CORPORATION
Published: Dec. 2017. No. OBH789 Made in Japan Specifications are subject to change without notice.
Loading...