Mitsubishi MUZ-A18YV-E1, MUZ-A24YV-E1, MUZ-A26YV-E1 Service Manual

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS

Revision C:

● “Check of HPS” has been corrected.

Please void OB346 REVISED EDITION-B.

 

HFC

No. OB346

 

REVISED EDITION-C

SERVICE MANUAL

utilized

 

R410A

 

 

 

Wireless type

Models

MUZ-A18YV - E1

MUZ-A24YV - E1

MUZ-A26YV - E1

CONTENTS

Indication of model name

MUZ-A18YV - E1 MUZ-A24YV - E1 MUZ-A26YV - E1

1.TECHNICAL CHANGES ··············

2.PART NAMES AND FUNCTIONS··········

3.SPECIFICATION··················

4.NOISE CRITERIA CURVES ·············

5.OUTLINES AND DIMENSIONS···········

6.WIRING DIAGRAM ················

7.REFRIGERANT SYSTEM DIAGRAM ········

8.PERFORMANCE CURVES ·············

9.ACTUATOR CONTROL··············

10.TROUBLESHOOTING···············

11.DISASSEMBLY INSTRUCTIONS··········

12.PARTS LIST···················

NOTE:

This service manual describes technical data of the outdoor units.

•As for indoor units MSZ-A18YV - E1 , MSZ-A24YV - E1 and MSZ-A26YV - E1 , refer to the service manual OB345.

•As for indoor units MCFZ-A18WV - E1 and MCFZ-A24WV - E1 , refer to the service manual OB344.

Revision A:

MUZ-A18YV - E1 can be connected to MCFZ-A18WV - E1 .

MUZ-A24YV - E1 can be connected to MCFZ-A24WV - E1 .

Revision B:

• Part number of 4-WAY VALVE has been corrected.

Model

Revise point

Part Name

 

 

 

Part Number

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Incorrect

 

Correct

 

 

 

 

 

 

 

 

 

 

 

MUZ-A18YV - E1

12-1. No.18

4-WAY VALVE

E02

679

961

 

E02

891

961

 

 

 

 

 

 

 

 

 

 

MUZ-A24YV - E1

12-1. No.18

4-WAY VALVE

E02

679

961

 

E02

891

961

 

 

 

 

 

 

 

 

 

 

MUZ-A26YV - E1

12-1. No.18

4-WAY VALVE

E02

679

961

 

E02

891

961

 

 

 

 

 

 

 

 

 

 

 

 

Revision C:

• “Check of HPS ” has been corrected.

2

Refrigerant

1 TECHNICAL CHANGES

INFORMATION FOR THE AIR CONDITIONER WITH R410A REFRIGERANT

This room air conditioner adopts an HFC refrigerant (R410A) which never destroys the ozone layer.

Pay particular attention to the following points, though the basic installation procedure is same as that for R22 air conditioners.

1As R410A has working pressure approximate 1.6 times as high as that of R22, some special tools and piping parts/ materials are required. Refer to the table below.

2 Take sufficient care not to allow water and other contaminations to enter the R410A refrigerant during storage and installation, since it is more susceptible to contaminations than R22.

3For refrigerant piping, use clean, pressure-proof parts/materials specifically designed for R410A. (Refer to 2. Refrigerant piping.)

4Composition change may occur in R410A since it is a mixed refrigerant. When charging, charge liquid refrigerant to prevent composition change.

Refrigerant

Refrigerating

oil

 

New refrigerant

Previous refrigerant

Refrigerant

R410A

R22

 

 

 

Composition (Ratio)

HFC-32: HFC-125 (50%:50%)

R22 (100%)

 

 

 

Refrigerant handling

Pseudo-azeotropic refrigerant

Single refrigerant

 

 

 

Chlorine

Not included

Included

 

 

 

Safety group (ASHRAE)

A1/A1

A1

 

 

 

Molecular weight

72.6

86.5

 

 

 

Boiling point (:)

-51.4

-40.8

Steam pressure [25:](Mpa)

1.557

0.94

Saturated steam density [25:](Kg/K)

64

44.4

Combustibility

Non combustible

Non combustible

ODP w1

0

0.055

 

 

 

GWP w2

1730

1700

 

 

 

Refrigerant charge method

From liquid phase in cylinder

Gas phase

 

 

 

Additional charge on leakage

Possible

Possible

Kind

Incompatible oil

Compatible oil

 

 

 

Color

Non

Light yellow

 

 

 

Smell

Non

Non

 

 

 

w1 :Ozone Destruction Parameter

: based on CFC-11

w2 :Global Warmth Parameter

: based on CO2

Compressor

 

New Specification

Current Specification

The incompatible refrigerating oil easily separates from

Since refrigerant and refrigerating oil are compatible each,

refrigerant and is in the upper layer inside the suction muffler.

refrigerating oil backs to the compressor through the lower

Raising position of the oil back hole enables to back the

position oil back hole.

refrigerating oil of the upper layer to flow back to the

 

 

 

 

 

 

 

compressor.

 

 

 

 

 

 

Suction muffler

 

 

 

 

 

 

Suction muffler

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Oil back hole

 

 

 

 

 

 

 

Compressor

 

 

 

 

 

 

Compressor

 

 

 

 

 

 

 

 

 

 

Refrigerating oil

 

 

 

 

 

 

Oil back hole

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refrigerating oil /Refrigerant

NOTE : The unit of pressure has been changed to MPa on the international system of units(SI unit system). The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/f [Gauge])

3

Conversion chart of refrigerant temperature and pressure

(MPa [Gauge])

 

 

 

 

 

 

 

 

 

 

 

 

 

4.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pressure

 

 

 

 

 

R410A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.0

 

 

 

 

 

R22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

liquid

2.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.0

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE : The unit of pressure has been changed to MPa on the

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

 

 

 

 

 

 

 

 

 

 

 

 

 

Saturated

 

 

 

 

 

 

 

 

 

 

 

 

 

1.0

 

 

 

 

 

 

 

 

 

 

 

 

 

international system of units(SI unit system).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/f [Gauge])

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-30 -20

-10 0 10 20 30 40 50 60 (:)

1.Tools dedicated for the air conditioner with R410A refrigerant

The following tools are required for R410A refrigerant. Some R22 tools can be substituted for R410A tools.

The diameter of the service port on the stop valve in outdoor unit has been changed to prevent any other refrigerant being charged into the unit. Cap size has been changed from 7/16 UNF with 20 threads to 1/2 UNF with 20 threads.

R410A tools

Can R22 tools be used?

Description

 

 

R410A has high pressures beyond the measurement range of existing

Gauge manifold

No

gauges. Port diameters have been changed to prevent any other refrigerant

 

 

from being charged into the unit.

 

 

 

Charge hose

No

Hose material and cap size have been changed to improve the pressure

resistance.

 

 

Gas leak detector

No

Dedicated for HFC refrigerant.

 

 

 

Torque wrench

Yes

6.35 mm and 9.52 mm

No

12.7 mm and 15.88mm

 

 

 

 

Flare tool

Yes

Clamp bar hole has been enlarged to reinforce the spring strength in the tool.

 

 

 

Flare gauge

New

Provided for flaring work (to be used with R22 flare tool).

Vacuum pump

New

Provided to prevent the back flow of oil. This adapter enables you to use

adapter

vacuum pumps.

 

Electronic scale for

New

It is difficult to measure R410A with a charging cylinder because the

refrigerant charging

refrigerant bubbles due to high pressure and high-speed vaporization

 

 

 

 

No : Not Substitutable for R410A Yes : Substitutable for R410A

2.Refrigerant piping

1Specifications

Use the refrigerant pipes that meet the following specifications.

Pipe

Outside diameter

Wall

Insulation material

mm

thickness

 

 

 

 

 

6.35

0.8 mm

 

For liquid

 

 

Heat resisting foam plastic

 

0.8 mm

9.52

12.7

0.8 mm

Specific gravity 0.045 Thickness 8 mm

For gas

15.881.0 mm

Use a copper pipe or a copper-alloy seamless pipe with a thickness of 0.8 mm (6.35, 9.52, 12.7), 1.0 mm (15.88). Never use any pipe with a thickness less than 0.8 mm (6.35, 9.52, 12.7), 1.0 mm (15.88), as the pressure resistance is insufficient.

4

2Flaring work and flare nut

Flaring work for R410A pipe differs from that for R22 pipe.

For details of flaring work, refer to Installation manual “FLARING WORK”.

Pipe diameter

Dimension of flare nut

 

 

 

 

 

mm

R410A

 

R22

6.35

17

 

17

9.52

22

 

22

 

 

 

 

12.7

26

 

24

 

 

 

 

15.88

29

 

27

3.Refrigerant oil

Apply the special refrigeration oil (accessories: packed with indoor unit) to the flare and the union seat surfaces.

4.Air purge

Do not discharge the refrigerant into the atmosphere.

Take care not to discharge refrigerant into the atmosphere during installation, reinstallation, or repairs to the refrigerant circuit.

Use the vacuum pump for air purging for the purpose of environmental protection.

5.Additional charge

For additional charging, charge the refrigerant from liquid phase of the gas cylinder.

If the refrigerant is charged from the gas phase, composition change may occur in the refrigerant inside the cylinder and the outdoor unit. In this case, ability of the refrigerating cycle decreases or normal operation can be impossible. However, charging the liquid refrigerant all at once may cause the compressor to be locked. Thus, charge the refrigerant slowly.

Indoor unit

Refrigerant gas cylinder operating valve

Union

 

Stop valve

Liquid pipe

 

Gas pipe

Outdoor unit

Service port

Gauge manifold valve (for R410A)

Charge hose (for R410A)

Refrigerant gas cylinder for R410A with siphon

Refrigerant (liquid)

Electronic scale for refrigerant charging

5

2 PART NAMES AND FUNCTIONS

MUZ-A18YV - E1

MUZ-A24YV - E1

MUZ-A26YV - E1

OUTDOOR UNIT

Air inlet (back and side)

Piping

Drain hose

Air outlet

Drain outlet

ACCESSORIES

 

 

MUZ-A18YV - E1

 

 

MUZ-A24YV - E1

 

 

MUZ-A26YV - E1

1

Drain socket

1

 

 

 

2

Drain cap [33

2

6

3

 

SPECIFICATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor model

 

 

MUZ-A18YV -

E1

MUZ-A18YV - E1

 

 

 

 

 

Indoor model

Indoor model

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MSZ-A18YV -

E1

MCFZ-A18WV - E1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Function

 

 

Cooling

 

 

Heating

Cooling

 

Heating

 

 

 

Power supply

 

 

Single phase

 

Single phase

 

 

 

 

 

230V,50Hz

 

230V,50Hz

 

 

 

 

 

 

 

 

Capacity

Capacity Rated frequency(Min.~Max.)

kW

 

5.0(0.9~5.9)

 

5.9(0.9~7.8)

4.8(10.9~5.5)

 

6.0(0.9~7.5)

Dehumidification

 

r/h

 

2.5

 

 

2.4

 

Air flow(High/LowW)

K /h

 

2,940/1,650W

 

2,940/2,210W

2,940/1,650W

 

2,940/2,210W

 

 

Power outlet

 

A

 

 

20

 

 

20

Electrical

 

Running current

 

A

 

6.62

 

 

7.38

7.76

 

8.87

data

Starting current

1

A

 

1,500

7.38

1,670

1,750

8.87

 

 

Power input

 

W

 

 

 

2,000

 

 

Power factor

 

%

 

98.5

 

 

98.4

 

98

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor motor current 1

A

 

6.32

 

 

7.08

7.46

 

8.57

 

 

Fan motor current

A

 

 

0.30

 

 

0.30

Coefficient of performance(C.O.P) 1

 

3.21

 

 

3.41

2.62

 

2.88

Compressor

resistance(at 20:)

 

 

V-W 0.45

 

V-W 0.45

 

 

Model

 

 

 

SNB130FLDH

SNB130FLDH

 

 

Output

 

W

 

 

850

 

 

850

 

 

Winding

 

"

 

U-V 0.45 W-U 0.45

U-V 0.45 W-U 0.45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

motor

Model

 

 

 

PM8H60-UB

 

PM8H60-UB

Fan

Winding

 

"

 

BLK-WHT 15.2

 

BLK-WHT 15.2

 

 

 

 

 

 

 

 

resistance(at 20:)

 

 

WHT-RED 15.2 RED-BLK15.2

WHT-RED 15.2 RED-BLK15.2

 

 

Dimensions WOHOD

mm

 

840o850o330

840o850o330

 

 

Weight

 

kg

 

 

53

 

 

53

 

 

Sound level(High/LowW)

dB

 

53/51W

 

 

55/53W

53/51W

 

55/53W

 

 

Fan speed(High/LowW)

rpm

 

800/480W

 

800/620W

800/480W

 

800/620W

 

 

Fan speed regulator

 

 

 

2

 

 

2

Special

remarks

Refrigerant filling

 

kg

 

 

1.8

 

 

1.8

capacity(R410A)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refrigerating oil(Model)

cc

 

450

(NEO22)

450

(NEO22)

 

 

Thermistor RT61(at 100:)

k"

 

 

13.4

 

 

13.4

 

 

Thermistor RT62(at 25:)

k"

 

 

10.0

 

 

10.0

 

 

Thermistor RT65(at 50:)

k"

 

 

17.0

 

 

17.0

 

 

Thermistor RT68(at 25:)

k"

 

 

10.0

 

 

10.0

NOTE : Test conditions are based on ISO 5151.

 

 

 

 

 

 

 

 

Cooling : Indoor

DB 27: WB

19:

 

 

 

 

 

 

 

 

 

Outdoor DB 35: WB (24:)

 

 

 

 

 

 

 

 

Heating : Indoor

DB 20: WB

15:

 

 

 

 

 

 

 

 

 

Outdoor DB 7: WB

6:

 

 

 

 

 

 

 

 

Refrigerant piping length (one way): 5m

 

 

 

 

 

 

 

 

1 Measured under rated operating frequency.

 

 

 

 

 

 

 

 

w Reference value

 

 

 

 

 

 

 

 

 

7

Outdoor model

Function

Power supply

Capacity

Air flow(High/LowW)

K /h

 

Capacity Rated frequency(Min.~Max.)

kW

 

Dehumidification

r/h

 

Power outlet

A

Electrical data

Running current

A

Starting current 1

A

 

Power input

W

 

Power factor

%

 

Compressor motor current 1

A

 

Fan motor current

A

 

 

 

Coefficient of performance(C.O.P) 1

Compressor

resistance(at 20:)

 

 

 

 

Model

 

 

 

 

Output

 

W

 

 

Winding

 

"

 

 

 

 

Fan

motor

Model

 

"

Winding

 

 

 

 

 

 

 

resistance(at 20:)

 

 

 

 

Dimensions WOHOD

 

mm

 

 

Weight

 

kg

 

 

Sound level(High/LowW)

 

dB

 

 

Fan speed(High/LowW)

 

rpm

 

 

Fan speed regulator

 

 

Special

remarks

Refrigerant filling

 

kg

 

capacity(R410A)

 

 

 

 

 

 

 

 

 

 

Refrigerating oil(Model)

 

cc

 

 

Thermistor RT61(at 100:)

 

k"

 

 

Thermistor RT62(at 25:)

 

k"

 

 

Thermistor RT65(at 50:)

 

k"

 

 

Thermistor RT68(at 25:)

 

k"

MUZ-A24YV - E1

MUZ-A24YV - E1

MUZ-A26YV - E1

Indoor model

Indoor model

Indoor model

MSZ-A24YV - E1

MCFZ-A24WV - E1

MSZ-A26YV - E1

Cooling

 

Heating

Cooling

 

Heating

Cooling

 

Heating

 

 

 

Single phase

Single phase

Single phase

230V,50Hz

230V,50Hz

230V,50Hz

6.0(0.9~6.7)

6.8(0.9~8.1)

5.5(0.9~6.1)

6.4(0.9~7.9)

7.1(0.9~8.3)

8.1(0.9~9.6)

3.0

 

3.1

 

3.8

 

2,940/1,650W 2,940/2,210W 2,940/1,650W 2,940/2,210W 2,940/1,650W 2,940/2,210W

 

20

 

20

 

20

8.49

 

8.75

10.38

 

10.47

10.75

 

11.42

1,921

 

1,981

2,340

 

2,360

2,431

 

2,581

 

98.4

 

98

 

98.3

 

8.75

10.47

11.42

8.19

 

 

10.08

 

 

10.45

 

11.12

 

8.45

 

10.17

 

 

0.30

 

0.30

 

0.30

3.02

 

3.32

2.27

 

 

2.84

 

3.06

 

 

2.62

 

SNB130FLDH

SNB130FLDH

TNB220FMCH

 

850

 

850

1,300

U-V 0.45 W-U 0.45

U-V 0.45 W-U 0.45

U-V 1.41

 

W-U 1.41

V-W 0.45

V-W 0.45

V-W 1.41

PM8H60-UB

PM8H60-UB

PM8H60-UB

BLK-WHT 15.2

BLK-WHT 15.2

BLK-WHT 15.2

WHT-RED 15.2 RED-BLK15.2 WHT-RED 15.2 RED-BLK15.2 WHT-RED 15.2 RED-BLK15.2

840o850o330

840o850o330

840o850o330

 

53

 

53

 

58

53/51W

 

55/53W

53/51W

 

55/53W

53/51W

 

55/53W

 

 

 

800/480W

 

800/620W

800/480W

 

800/620W

800/480W

 

800/620W

 

2

 

2

 

2

 

1.8

 

1.8

 

2.0

450 (NEO22)

450 (NEO22)

870 (NEO22)

 

13.4

 

13.4

 

13.4

 

10.0

 

10.0

 

10.0

 

17.0

 

17.0

 

17.0

 

10.0

 

10.0

 

10.0

NOTE : Test conditions are based on ISO 5151.

Cooling : Indoor

DB 27: WB

19:

Outdoor DB 35: WB (24:)

Heating : Indoor

DB

20: WB

15:

Outdoor DB

7: WB

6:

Refrigerant piping length (one way): 5m

1 Measured under rated operating frequency. w Reference value

8

Specifications and rating conditions of main electric parts

OUTDOOR UNIT

Item

 

Model

MUZ-A18YV - E1

 

MUZ-A24YV - E1

MUZ-A26YV - E1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Smoothing capacitor

 

(CB1,2,3)

 

 

560+ 450V

 

Current transformer

 

(CT1,2)

 

 

ETQ19Z68AY

 

 

 

 

 

 

 

 

Current transformer

 

(CT61)

 

 

ETQ19Z53AY

 

 

 

 

 

 

 

Fuse

(F801, F912)

 

 

250V 3.15A

 

 

 

 

 

 

 

 

Fuse

 

(F911)

 

 

250V 1A

 

 

 

 

 

 

 

 

Fet array

 

(HC932)

 

 

SLA5075

 

 

 

 

 

 

 

 

High pressure switch

 

(HPS)

 

ACB-DB156

 

 

 

 

 

 

Power transistor module

(IPM)

 

 

PS21244-A

 

 

 

 

 

 

 

 

Reactor

 

(L)

 

 

340 H 20A

 

 

 

 

 

 

 

Expansion valve

 

(LEV)

CAM-30YGME 12VDC

CAM-40YGME 12VDC

 

 

 

 

 

 

 

Power factor controller

 

(PFC)

 

 

PS51259-A

 

 

 

 

 

 

 

 

Resistor

 

(R64)

 

 

10" 20W

 

Resistor

 

(R934A,B)

 

 

1.1" 2W 2%

 

Resistor

 

(RS1~4)

 

 

0.04" 7W

 

Solenoid coil relay

 

(SSR61)

 

 

TLP3506

 

 

 

 

 

 

 

 

Terminal block

 

(TB1)

 

 

3P

 

 

 

 

 

 

 

 

Terminal block

 

(TB2)

 

 

2P

 

 

 

 

 

 

 

 

Relay

 

(X64)

 

 

G4A

 

 

 

 

 

 

 

 

R.V. coil

 

(21S4)

 

 

LD30013

 

 

 

 

 

 

 

 

9

4 NOISE CRITERIA CURVES

MUZ-A18YV - E1

MUZ-A24YV - E1

MUZ-A26YV - E1

SPEED FUNCTION SPL(dB(A)) LINE

 

 

 

 

High

COOLING

53

 

 

 

 

 

 

 

HEATING

55

 

 

 

 

 

 

 

 

 

 

 

 

Test conditions,

 

 

 

 

 

 

 

 

 

 

Cooling : Dry-bulb temperature 35: Wet-bulb temperature (24:)

 

 

90

Heating : Dry-bulb temperature

7: Wet-bulb temperature 6:

 

BAR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MICRO

80

 

 

 

 

 

 

 

 

 

0.0002

70

 

 

 

 

 

 

 

NC-70

OUTDOOR UNIT

 

 

 

 

 

 

 

 

 

 

dB re

60

 

 

 

 

 

 

 

 

1m

LEVEL,

 

 

 

 

 

 

 

NC-60

 

 

 

 

 

 

 

 

MICROPHONE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PRESSURE

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-50

 

 

40

 

 

 

 

 

 

 

 

 

SOUND

 

 

 

 

 

 

 

 

NC-40

 

30

 

 

 

 

 

 

 

 

 

BAND

 

 

 

 

 

 

 

 

NC-30

 

OCTAVE

20

APPROXIMATE

 

 

 

 

 

 

 

NOISE

 

 

 

 

 

 

 

 

 

 

THRESHOLD OF

 

 

 

 

 

 

 

 

HEARING FOR

 

 

 

 

 

NC-20

 

 

 

CONTINUOUS

 

 

 

 

 

 

 

 

10

63

125

250

500

1000

2000

4000

8000

 

 

 

 

 

 

 

 

BAND CENTER FREQUENCIES, Hz

 

 

10

5 OUTLINES AND DIMENSIONS

MUZ-A18YV - E1

MUZ-A24YV - E1

MUZ-A26YV - E1

OUTDOOR UNIT

REQUIRED SPACE

 

 

515

 

 

299

 

66

40

51

34

 

330

100mm or more

360

Unit: mm

Open as a rule 500mm or more if the front and both sides are open

100mm or more 200mm or more if there are obstacles to both sides

500

 

 

840

80 Open as a rule

 

121

500mm or more if the back,

350mm or more

 

both sides and top are open

 

 

 

 

Service panel

 

 

Liquid refrigerant

850

 

pipe joint

 

Refrigerant pipe

 

 

(flared) [6.35 (MUZ-A18/A24YV)

430

 

[9.52 (MUZ-A26YV)

 

-

 

 

30

 

 

-

155

 

35

90

Gas refrigerant

 

 

pipe joint

 

198

Refrigerant pipe

 

(flared) [12.7 (MUZ-A18YV)

 

 

[15.88 (MUZ-A24/A26YV)

11

12

POWER SUPPLY ~/N 230V 50Hz

CIRCUIT BRN BREAKER

TB1

L BLU

N

PE GRN/YLW

TAB1

 

 

 

 

 

 

 

 

 

 

F912

X64

 

4

 

NF

 

R64

 

TAB4

 

 

 

 

 

 

 

 

 

 

 

 

F911

 

NR63

 

CN902CN903 12 2 1

TAB2

 

 

SSR61

 

 

CT61

 

 

 

 

 

LDE1

LDE2

CN912

 

CN901

 

 

 

 

 

1

3

1

2

3

5

NOISE FILTER

GRN

BLU

BLU

 

 

P.C. BOARD

GRN

 

 

BLK BLK BLK

BLK

 

 

 

 

 

 

 

 

 

21S4

 

 

TO INDOOR UNIT CONNECTING 12V

TB2 RED

3

BLU

N

ELECTRONIC CONTROL P.C. BOARD

3 1

CN601

1

2

3

5

CN781

CN661

1 2 3 4

RT62 RT61

 

L

 

 

 

PFC

 

 

 

 

 

 

CT2 W

 

2

 

1

 

R

 

 

 

 

 

 

RED

RED

 

 

RED

S

 

 

 

CB1

CB2

CB3

 

 

 

3

 

4 YLW

 

 

 

 

 

 

W

 

 

 

 

 

 

 

 

 

 

YLW

 

 

BLK

 

 

 

 

 

 

 

 

V

V MC

 

 

 

2 1

CN5

 

 

 

 

 

IPM

 

 

 

BLK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U

 

 

 

BLK

1

 

 

 

 

 

 

 

CT1 U

WHT

 

 

 

2

 

 

 

RS1

 

RS3

 

BLK

 

 

 

 

3

CN2

CN4

RS2

 

RS4

 

CN3 21

 

 

 

 

 

456

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

1

2

LD2

 

LD1

LD9

POWER

RT65

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BOARD

 

BLK

BLK

BLK

BLK

 

BLK

BLK

RED

 

WHT

 

GRN

 

 

 

 

 

 

 

 

 

 

 

 

1 5 6 7

CN702

7

8

CN795

6

LEV RT68

1

2

1

3

CN801

 

CN701

 

 

 

 

F801

 

 

 

T801

HC932

R934A

 

R934B

 

 

5

CN931

2 3 4

 

1

 

3

 

2

 

1

CN932

GRY

PNK

ORN

BLU

YLW MF

RED

WHT

BLK

OUTDOOR

A24YV-MUZ

A18YV-MUZ

UNIT

E1 -

E1 -

DIAGRAM WIRING MODELS

SYMBOL

NAME

SYMBOL

NAME

SYMBOL

NAME

NOTES: 1.About the indoor side electric wiring

CB1~3

SMOOTHING CAPACITOR

MC

COMPRESSOR

RT65

FIN TEMPERATURE THERMISTOR

refer to the indoor unit electric wiring

CT1, 2

CURRENT TRANSFORMER

MF

OUTDOOR FAN MOTOR (INNER FUSE)

RT68

OUTDOOR HEAT EXCHANGER

diagram for servicing.

 

CT61

CURRENT TRANSFORMER

NF

NOISE FILTER

 

TEMPERATURE THERMISTOR

2.Use copper conductors only (for field wiring).

F801

FUSE (250V 3.15A)

NR63

VARISTOR

SSR61

SOLENOID COIL RELAY

3.Symbols below indicate.

F911

FUSE (250V 1A)

PFC

POWER FACTOR CONTROLLER

T801

TRANSFORMER

:Terminal block

 

 

 

:Connector

 

 

 

F912

FUSE (250V 3.15A)

R64

RESISTOR

TB1

TERMINAL BLOCK

 

 

 

 

 

HC932

FET ARRAY

R934A, B

RESISTOR

TB2

TERMINAL BLOCK

 

 

 

 

 

IPM

POWER TRANSISTOR MODULE

RS1~4

RESISTOR

X64

RELAY

 

 

 

 

 

L

REACTOR

RT61

DISCHARGE TEMPERATURE THERMISTOR

21S4

R.V. COIL

 

 

 

 

 

LEV

EXPANSION VALVE COIL

RT62

DEFROST THERMISTOR

 

 

 

 

 

 

 

DIAGRAM WIRING 6

Mitsubishi MUZ-A18YV-E1, MUZ-A24YV-E1, MUZ-A26YV-E1 Service Manual

 

 

TAB1

 

 

 

 

 

 

 

 

 

 

 

L

 

 

 

POWER SUPPLY

 

 

 

 

 

 

 

 

 

 

2

 

1

 

 

 

 

 

 

 

 

 

X64

 

4

 

 

 

 

~/N 230V 50Hz

BRN

 

 

NF

 

 

F912

 

RED

 

 

 

RED

BREAKER

 

 

 

 

R64

 

TAB4

 

 

 

CIRCUIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TB1

 

 

 

 

 

 

 

 

 

 

 

 

YLW

3

 

4 YLW

 

 

 

 

 

 

 

 

 

NR63

 

CN903

 

 

 

 

BLK

N

PE

TAB2

 

CT61

 

 

12

 

 

 

 

L

BLU

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLK

 

GRN/YLW

 

 

LDE1

 

LDE2

F911

 

SSR61

 

 

CN902

21

 

 

 

 

BLK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CN912

 

CN901

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

3

1

2

3

 

5

 

 

 

 

 

 

NOISE FILTER

GRN

GRN

 

 

BLU BLU

 

 

 

 

 

 

 

 

 

 

 

 

P.C. BOARD

 

 

 

 

 

BLK

BLK

BLK

 

BLK

BLK

 

BLK

BLK

BLK

 

 

 

 

 

 

21S4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ELECTRONIC

1

2

3

 

5

1

 

 

5

6

7

13

 

 

 

CONTROL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TB2 RED

P.C. BOARD

 

 

CN781

 

 

CN702

 

 

TO INDOOR

3

 

 

31

CN601

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT

 

 

 

 

 

CN681

 

 

 

CN661

 

 

 

 

 

 

 

BLU

 

 

 

 

 

 

 

 

 

 

 

 

CONNECTING

 

 

 

 

1

2

1

2

3

4

 

7

8

CN795

 

12V

N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RED

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

HPS RED

RT62 RT61

RT68

 

LEV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R

S

7 6 5 4 3 2 1 2 1

PFC

 

 

 

 

 

CT2 W RED

 

 

CB1

CB2

CB3

 

 

W

 

 

 

 

 

 

 

CN5

 

 

 

IPM

V

V MC

 

 

 

 

 

 

 

 

 

 

U

 

 

 

 

 

 

 

 

 

 

 

 

 

CT1 U

WHT

 

 

RS1

 

RS3

 

BLK

CN2

 

 

 

 

 

CN3 21

 

RS2

 

RS4

 

 

 

 

 

 

 

 

CN4

 

 

 

POWER

RT65

1

2

LD2

 

LD1 LD9

 

 

BOARD

 

 

 

 

 

 

BLK BLK

 

RED

WHT

CN801

1

2

1

3

 

CN701

 

 

 

 

F801

 

 

 

T801

HC932

R934A

 

R934B

 

 

 

GRN

 

5

GRY

 

PNK

CN931

32 4

ORN

 

 

 

 

BLU

 

1

YLW MF

 

3

RED

 

WHT

 

2

 

BLK

 

1

 

 

CN932

 

OUTDOOR

A26YV-MUZ

UNIT

E1 -

DIAGRAM WIRING MODEL

SYMBOL

 

NAME

SYMBOL

NAME

SYMBOL

NAME

NOTES: 1.About the indoor side electric wiring

CB1~3

SMOOTHING CAPACITOR

MC

COMPRESSOR

RT68

OUTDOOR HEAT EXCHANGER

refer to the indoor unit electric wiring

CT1, 2

CURRENT TRANSFORMER

MF

OUTDOOR FAN MOTOR (INNER FUSE)

TEMPERATURE THERMISTOR

diagram for servicing.

 

CT61

CURRENT TRANSFORMER

NF

NOISE FILTER

SSR61

SOLENOID COIL RELAY

2.Use copper conductors only (for field wiring).

F801

FUSE (250V 3.15A)

NR63

VARISTOR

T801

TRANSFORMER

3.Symbols below indicate.

F911

FUSE (250V

1A)

PFC

POWER FACTOR CONTROLLER

TB1

TERMINAL BLOCK

:Terminal block

 

 

 

:Connector

 

 

 

F912

FUSE (250V

3.15A)

R64

RESISTOR

TB2

TERMINAL BLOCK

 

 

 

 

 

HC932

FET ARRAY

 

R934A, B

RESISTOR

X64

RELAY

 

 

 

 

 

HPS

HIGH PRESSURE SWITCH

RS1~4

RESISTOR

21S4

R.V. COIL

 

 

 

 

 

IPM

POWER TRANSISTOR MODULE

RT61

DISCHARGE TEMPERATURE THERMISTOR

 

 

 

 

 

 

 

L

REACTOR

 

RT62

DEFROST THERMISTOR

 

 

 

 

 

 

 

LEV

EXPANSION VALVE COIL

RT65

FIN TEMPERATURE THERMISTOR

 

 

 

 

 

 

 

7 REFRIGERANT SYSTEM DIAGRAM

MUZ-A18YV

- E1

 

 

 

 

 

Unit:mm

MUZ-A24YV

- E1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR UNIT

 

 

 

 

 

 

Refrigerant pipe [12.7 (MUZ-A18YV)

 

Muffler

(with heat insulator) [15.88 (MUZ-A24YV)

4-way valve

#100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stop valve

 

 

 

 

(with service port)

 

 

Outdoor

Flared connection

Discharge

 

 

 

 

heat

 

temperature

 

exchanger

 

thermistor

 

Defrost

 

 

RT61

 

thermistor

 

 

 

 

RT62

 

 

Compressor

 

 

 

 

 

Outdoor heat

 

 

 

 

exchanger

 

 

 

 

temperature

 

 

 

 

thermistor

Flared connection

 

 

 

RT68

Strainer

LEV

 

 

 

Strainer

 

 

 

R.V. coil

Receiver #100

 

#100

 

 

 

 

heating ON

Stop valve

Capillary tube

 

 

cooling OFF

 

 

 

 

[3.6 [2.4 50

 

 

Refrigerant pipe [6.35

Refrigerant flow in cooling

(with heat insulator)

Refrigerant flow in heating

MUZ-A26YV - E1

Capillary tube

 

 

 

 

 

 

 

Unit:mm

OUTDOOR UNIT

 

[1.8 [0.6 1000

Refrigerant pipe [15.88

4-way valve

Oil separator High-pressure

(with heat insulator)

 

 

 

switch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stop valve

 

 

 

 

 

(with service port)

Strainer

Defrost

Outdoor

Flared connection

 

 

heat

 

 

 

#100

thermistor

exchanger

 

 

 

 

RT62

 

 

 

 

Discharge

 

 

 

 

temperature

 

 

 

 

thermistor

 

 

 

 

RT61

 

 

 

 

Compressor

 

Outdoor

 

 

 

 

 

 

 

 

 

 

heat

 

 

 

 

 

exchanger

 

 

 

 

 

temperature

 

 

 

 

 

thermistor

Flared connection

 

 

 

 

RT68

 

LEV

 

 

 

 

Strainer

Strainer

 

Receiver

 

R.V. coil

#100

 

#100

 

 

 

 

 

 

heating ON

Stop valve

Capillary tube

 

 

cooling OFF

 

 

 

Refrigerant pipe [9.52

[3.6 [2.4 50

 

Refrigerant flow in cooling

 

 

 

(with heat insulator)

 

 

 

Refrigerant flow in heating

 

 

 

 

 

14

 

 

 

 

MAX. REFRIGERANT PIPING LENGTH

 

 

Refrigerant piping

Piping size O.D : mm

Length of connecting pipe : m

Model

 

Max. length : m

 

 

 

 

 

 

 

A

Gas

Liquid

Indoor unit

Outdoor unit

MUZ-A18YV -

E1

 

12.7

6.35

Gas 0.43

Gas 0

 

 

 

 

MUZ-A24YV -

 

30

 

E1

15.88

 

Liquid 0.5

Liquid 0

 

 

 

 

 

 

MUZ-A26YV -

E1

 

9.52

 

 

 

 

 

 

 

 

 

 

 

 

 

MAX. HEIGHT DIFFERENCE

Indoor unit

wMax. Height difference 15m

Refrigerant Piping

Max. length

A

Outdoor unit

w Height difference should be within 15m regardless of which unit, indoor or outdoor position is high.

ADDITIONAL REFRIGERANT CHARGE(R410A : g)

Model

Outdoor unit

 

 

Refrigerant piping length (one way)

 

 

 

 

 

 

 

 

 

 

precharged

7m

10m

 

15m

20m

 

25m

30m

 

 

 

MUZ-A18YV - E1

1,800

0

60

 

160

260

 

360

460

 

 

 

 

 

 

 

 

 

 

Calculation : Xg=20g/m (Refrigerant piping length (m)–7)

Model

Outdoor unit

 

 

 

Refrigerant piping length (one way)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

precharged

 

7m

10m

 

 

15m

 

20m

 

25m

 

30m

 

 

 

 

 

 

 

MUZ-A24YV - E1

1,800

0

60

 

160

260

 

360

460

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Calculation : Xg=20g/m (Refrigerant piping length (m)–7)

 

 

 

 

 

 

 

 

 

 

 

 

Model

Outdoor unit

 

 

 

Refrigerant piping length (one way)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

precharged

 

7m

10m

 

 

15m

 

20m

 

25m

 

30m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MUZ-A26YV - E1

2,000

 

0

165

 

440

 

715

 

990

 

1,265

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Calculation : Xg=55g/mo(Refrigerant piping length(m)-7)

15

8 PERFORMANCE CURVES

MUZ-A18YV - E1

MUZ-A24YV - E1

MUZ-A26YV - E1

The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions. Since operating conditions vary according to the areas where these units are installed. The following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.

(1)GUARANTEED VOLTAGE

207 ~ 253V, 50Hz

(2)AIR FLOW

Air flow should be set at MAX.

 

 

 

(3) MAIN READINGS

 

}

 

(1)

Indoor intake air wet-bulb temperature :

°C WB

 

(2)

Indoor outlet air wet-bulb temperature :

°C WB

Cooling

(3)

Outdoor intake air dry-bulb temperature :

°C DB

 

(4) Total input :

W

 

(5)

Indoor intake air dry-bulb temperature :

°C DB

}

 

(6)

Outdoor intake air wet-bulb temperature :

°C WB

Heating

(7) Total input :

W

 

Indoor air wet/dry-bulb temperature difference on the left side of the chart on this page and next page shows the difference between the indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.

How to measure the indoor air wet-bulb / dry-bulb temperature difference

1.Attach at least 2 sets of wet and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.

2.Attach at least 2 sets of wet and dry-bulb thermometers to the outdoor air intake.

Cover the thermometers to prevent direct rays of the sun.

3.Check that the air filter is cleaned.

4.Open windows and doors of room.

5.Press the EMERGENCY OPERATION switch once (twice) to start the EMERGENCY COOL (HEAT) MODE.

6.When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.

7.10 minutes later, measure temperature again and check that the temperature does not change.

INDOOR UNIT

OUTDOOR UNIT

Wet and dry-bulb

Wet and dry-bulb

thermometers

thermometers

Indoor air Wet-bulb temperature difference (degree)

11.4

 

 

 

11.1

 

 

 

 

11.3

 

 

 

12.9

 

 

 

13.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10.5

 

 

 

10.2

 

 

 

 

10.3

 

 

 

11.7

 

 

 

12.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9.5

 

 

 

9.2

 

 

 

 

9.3

 

 

 

10.6

 

 

 

11.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8.6

 

 

 

8.3

 

 

 

 

8.4

 

 

 

9.6

 

 

 

10.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7.7

 

 

 

7.5

 

 

 

 

7.5

 

 

 

8.6

 

 

 

9.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6.8

 

 

 

6.6

 

 

 

 

6.7

 

 

 

7.6

 

 

 

8.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated frequency 102Hz

 

 

 

 

 

 

 

 

 

Rated frequency 73Hz

 

E1

 

 

Rated frequency 84Hz

 

 

 

 

Rated frequency 88Hz

 

E1

 

 

 

 

 

 

Rated frequency 63Hz

E1

E1

 

 

E1

E1

E1

E1

E1

E1

MCFZ-A18WV -

MCFZ-A24WV -

MSZ-A18YV -

MUZ-A18YV -

 

 

MUZ-A18YV -

 

MSZ-A24YV -

MUZ-A24YV -

MUZ-A24YV -

MSZ-A26YV -

MUZ-A26YV -

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor

intake

 

 

air

 

Wet-

 

bulb

 

temperature (

 

:)

Outdoor intake air Dry-bulb temperature (:)

 

 

 

)

 

 

 

(:

 

 

 

ulb temperature

 

 

-b

 

et

 

air

W

 

 

intake

 

 

 

Indoor

 

 

 

Outdoor intake air Dry-bulb temperature (:)

16

Loading...
+ 36 hidden pages