Mitsubishi MS-C18TV-E1, MS-C24TV-E1, MU-C18TV-E1, MU-C24TV-E1 Service Manual

SPLIT-TYPE AIR CONDITIONERS
HFC
utilized
R407C
SERVICE MANUAL
Wireless type Models
No. OB273
MS-C18TV ­MS-C24TV -
MS-C18TV ­MS-C24TV -
E1 E1
(WH)
(WH)
· MU-C18TV -
· MU-C24TV -
CONTENTS
1. TECHNICAL CHANGES ····································3
2. PART NAMES AND FUNCTIONS······················5
3. SPECIFICATION·················································7
4. NOISE CRITERIA CURVES·······························8
5. OUTLINES AND DIMENSIONS·························9
6. WIRING DIAGRAM ··········································10
7. REFRIGERANT SYSTEM DIAGRAM··············12
8. PERFORMANCE CURVES······························14
9. MICROPROCESSOR CONTROL ····················20
11. TROUBLESHOOTING ······································29
13. PARTS LIST······················································43
14. OPTIONAL PARTS ···········································46
E1E1
E1E1
-30 -20 -10 0 10 20
30
40 50 60
-0.5
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
(MPa[Gauge])
R407C R22
Conversion chart of refrigerant temperature and pressure
Saturated liquid pressure
(:)
Lubricant
Refrigerant
New refrigerant
R407C
R32: R125: R134a (23%:25%:52%)
Non-azeotropic refrigerant
Not included
A1/A1
86.2
-43.6
0.9177
42.5
Non combustible
0
1530
From liquid phase in cylinder
Impossible
Incompatible oil
Non Non
Previous refrigerant
R22
HCFC22 (100%)
Single refrigerant
Included
A1
86.5
-40.8
0.94
44.4
Non combustible
0.055 1700
Gas phase
Possible
Compatible oil
Light yellow
Non
Refrigerant Composition (Ratio) Refrigerant handling Chlorine Safety group (ASHRAE) Molecular weight Boiling point (:) Steam pressure [25:](Mpa [Gauge]) Saturated steam density [25:](Kg/K) Combustibility ODP w1 GWP w2 Refrigerant charge method Additional charge on leakage Kind Color Smell
w1:Ozone Destruction Parameter : based on CFC11 w2 :Global Warmth Parameter : based on CO
2
1
TECHNICAL CHANGES
INFORMATION FOR THE AIR CONDITIONER WITH R-407C REFRIGERANT
This room air conditioner adopts HFC refrigerant (R407C) which will never destroy the ozone layer. Pay attention to following points.
1 Take sufficient care not to allow water and other contaminations to enter the R407C refrigerant during storage and
installation, since it is more susceptible to contaminations than HCFC (R22) refrigerant.
2 Clean refrigerant pipings should be used. 3 Composition change may occur in R407C since it is a mixed refrigerant. When charging, charge liquid refrigerant to
prevent composition change.
4 Be especially careful when managing the tools.
If dust, dirt, or water mixes in the refrigerant cycle, it may cause decrease of performance.
New Specification Previous Specification
The incompatible lubricant easily separates from refrigerant and makes the layer in the upper inside the suction muffler. The higher position of the returning oil hole enables to return the lubricant of the upper layer to the compressor.
Suction muffler
Compressor
Compressor
Returning oil hole
Lubricant
Refrigerant
NOTE : The unit of pressure has been changed to MPa on the
The conversion factor is: 1(MPa[Gauge]) =10.2(kgf/ff[Gauge])
3
Since refrigerant and lubricant are compatible each other, lubricant returns to the compressor through the lower position returning oil hole.
Suction muffler
Compressor
Returning oil hole
Lubricant and Refrigerant
international system of units(SI unit system).
Electronic scale for refrigerant charging
Refrigerant gas cylinder operating valve
Refrigerant gas cylinder for R407C with siphon
Refrigerant (liquid)
Gage manifold
Outdoor unit
Indoor unit
Union
Liquid pipe Gas pipe
Service port
Stop valve
Charge hose
1.Tools dedicated for the air conditioner with R407C refrigerant
R407C tools Can R22 tools be used?
Gas leak detector
A gauge manifold with a sight glass is recommended for charging the liquid refregerant.
Hose material have been changed to improve the pressure resistance.
Dedicated for HFC refrigerant.
Description
Provided to prevent the back flow of oil. This adapter enables you to use existing vacuum pumps.
No
No
No
Yes Yes
New
New
Gauge manifold
Charge hose
Torque wrench Flare tool
Vacuum pump adapter
Electronic scale for refrigerant charging
Use the electronic control scale for measuring the R407C.
The following tools are required for R407C refrigerant. Some R22 tools can be substituted for R407C tools. Do not use tools that are used with R22 refrigerant in order to avoid mixing oils.
2.Refrigerant piping
Do not use copper pipes which are broken, deformed or discoloured. In addition, be sure that the inner surfaces of the pipes are clean, free of hazardous sulfur and oxides, or have no dust/ dirt, shaving particles, oil, moisture or any other contamination.
•If there is a large amount of residual oil inside the piping and joints, deterioration of the refrigerant oil will result.
3.Refrigerant oil
Apply the specific refrigeration oil (accessories) to the flare and the union seat surfaces.
4.Air purge
Use the vacuum pump for air purge to protect environments, and to avoid changing the composition of refrigerant.
5.Additional charge
For additional charging, charge the refrigerant with liquid phase slowly using a gas cylinder. If the refrigerant is charged with gas phase, the composition of refrigerant will change. In this case, ability of the refrigerating cycle decreases or normal operation can be impossible. If liquid refrigerant is rapidly charged at once, the compressor may be locked.
NOTE: 1. The R407C is mixed refrigerant which consist of three different kinds of evaporative temperature. As a result, the
R407C occurs the change of composition.
2. Additional refrigerant charge has been changed by change of refrigerant.(R22 ➔ R407C) R22 : <MU-type> 15g/m R407C : <MU-C18/C24TV> 20g/m
4
2
Remote control receiving section
Air cleaning filter(option)
Deodorizing filter(option)
Front panel
Grille
(When the grille is open)
1 5 1 2 2 1 1 1
1
2
3
4
5
6
7
8
Installation plate Installation plate fixing screw 4 x 25 mm Remote controller mounting hardware Fixing screw for 3 3.5 x 16 mm (Black) Battery (AAA) for remote controller Wireless remote controller Felt tape (Used for left or left-rear piping) Refrigeration oil
PART NAMES AND FUNCTIONS
INDOOR UNIT
MS-C18TV ­MS-C24TV -
E1
E1
ACCESSORIES
MS-C18TV ­MS-C24TV -
E1
E1
OUTDOOR UNIT
MU-C18TV ­MU-C24TV -
5
E1
E1
REMOTE CONTROLLER
MS-C18TV ­MS-C24TV -
E1
E1
Signal transmitting section
Operation display section
OPERATE /STOP
(ON /OFF)button
Open the front lid.
ON/OFF
TOO
WARM
PM
AM
TOO
COOL
TEMPERATURE buttons
FAN SPEED CONTROL button
OPERATION SELECT button
ECONO COOL button
RESET button
TOO
ON/OFF
WARM
COOL
DRY
FAN
VANE
RESET
I FEEL
FAN
MODE
ECONO COOL
6
CLOCK
CLOCK
PM
AM
TOO
COOL
STOP
START
HR.
MIN.
OFF-TIMER button
ON-TIMER button
HR. button
MIN. button
(TIME SET button)
CLOCK SET button
VANE CONTROL button
3
Indoor model
Function
Power supply
Capacity Dehumidification Air flow(High) Power outlet Running current Power input Auxiliary heater Power factor Starting current Fan motor current
Model Winding resistance(at20:) Dimensions WOHOD Weight Air direction Sound level (High) Fan speed (High) Fan speed regulator Thermistor RT11(at25:) Thermistor RT12(at25:) Outdoor model Air flow Compressor motor current Fan motor current Model Output Winding resistance(at20:) Model Winding resistance(at20:) Dimensions WOHOD Weight Sound level(High) Fan speed(High) Fan speed regulator Refrigerant filling capacity(R407C) Refrigerating oil (Model)
kW
R/h
K /h
A A
W
A(kW)
%
A A
"
mm
kg
dB
rpm
k" k"
K /h
A A
W
"
"
mm
kg dB
rpm
kg
cc
Cooling
Single phase
230V, 50Hz
WHT-BLK 183.8 BLK-RED 250.5 1,015O320O190
14
5
3 10 10
850o605o290
1100 (NEO22)
MS-C24TV -
E1
6.4
3.1
816
25
12.7
2,840
97 84
0.29
2.25
RA4V27-EE
45
1,260
MU-C24TV -
E1
11.86
0.55
NE-47VMHHT
2,200 C-R 0.67 C-S 2.02
RA6V60-AC
WHT-BLK 81.1 BLK-RED 102.2
BLK-YLW 92.2
61 53
873
2
1.85
MS-C18TV -
E1
5.1
2.4
756
15
9.3
2,100
98 50
0.25
2.43
RA4V27-EF
42
1,180
MU-C18TV -
E1
2370
8.66
0.39
PE-33VPEHT
1,500 C-R 1.08 C-S 2.18
RA6V50-OG
WHT-BLK 116.4
BLK-RED 111.0
48 52
845
1
1.10
Electrical
data
Fan
motor
Special
remarks
Compressor
Electrical
data
Fan
motor
Special
remarks
Capacity
Coefficient of performance(C.O.P)
Capacity
Cooling
Single phase
230V, 50Hz
WHT-BLK 183.8 BLK-RED 250.5 1,015O320O190
14
5
3 10 10
2322
850o605o290
1400 (NEO22)
SPECIFICATION
NOTE: Test conditions are based on JIS C 9612.
Cooling : Indoor DB 27°C / WB 19°C
Outdoor DB 35°C / WB 24°C
7
4
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions, Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
42
SPL(dB(A)) LINE
NOTCH
High
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
Test conditions, Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
45
SPL(dB(A)) LINE
NOTCH
High
NOISE CRITERIA CURVES
MS-C18TV -
E1
MU-C18TV -
E1
NOTCH
High
SPL(dB(A)) LINE
52
Test conditions, Cooling : Dry-bulb temperature 35: Wet-bulb temperature 24:
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
NOISE
10
63 125 250 500 1000 2000 4000 8000
NC-20
BAND CENTER FREQUENCIES, Hz
MS-C24TV -
E1
MU-C24TV -
E1
NOTCH
High
SPL(dB(A)) LINE
53
Test conditions, Cooling : Dry-bulb temperature 35: Wet-bulb temperature 24:
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
8
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
5
OUTLINES AND DIMENSIONS
MS-C18TV ­MS-C24TV -
E1
E1
INDOOR UNIT
320
Wireless remote controller
MU-C18TV ­MU-C24TV -
E1
E1
OUTDOOR UNIT
58
162
995
1015
19
19077550
Power supply cord Lead to right 2m Lead to left 1m
150 648 217
60
40
Installation plate
Air in
4holes 1120
450 450
Air out
100mm or more
Indoor unit
352438
5190
Installation plate
Liquid line [8-0.5m Gas line [12-0.43m
{
Insulation [50 O.D
[28 I.D
Drain hose [16 Insulation [28
100mm or more
Unit : mm
20
254
3 297
Wall hole [75
100mm or more
Drainage hole [16.2
35
90
248
Air in
605
Drainage 3holes [33
292
20
355
350
Air in
Air out
500 850
183
20
50
74
157
290
30
100
310
345
161
500mm or more
Service panel
Liquid refrigerant pipe joint
Refregerant pipe (flared) [6.35(MU-C18TV) [9.52(MU-C24TV)
35-
30-
Gas refregerant pipe joint
Refregerant pipe (flared) [15.88
350mm or more
9
6
SYMBOL
RT12
TB
52C
SYMBOL
IC141
MF
MV NR11 RT11
SYMBOL
C11
DSAR
F11 F12
HIC1
NAME
NAME NAME INDOOR FAN CAPACITOR SURGE ABSORBER FUSE(3.15A) THERMAL FUSE(93°C) DC / DC CONVERTER
HYBRID IC INDOOR FAN MOTOR(INNER FUSE) VANE MOTOR VARISTOR ROOM TEMPERATURE THERMIST OR
INDOOR COIL THERMISTOR TERMINAL BLOCK CONTACTOR
MF
BLK
WHT
RED ORN
N
230V~
BLU
4
BLU
WHT
BLK
RED
C1
TB
WHT
ORN
F
C2
RED
WHT
1 2 3
GRN/YLW
FROM
INDOOR UNIT
CONNECTING
C
S
R
MC
2
CIRCUIT BREAKER
50Hz
230V~
BRN
DSAR
GRN/YLW
LD1
REMOTE CONTROLLER
3 1
DISPLAY P.C. BOARD
101
CN
102
CN
151
CN
BLU
RECEIVER P.C. BOARD
MV
5
F11
33
BLU
~/N 230V
CORD
POWER SUPPLY
TO OUTDOOR UNIT
CONNECTING
BRN
L
N
GRN/YLW
TB
52C
BRN
2
4
3
CN201
1
2
F12
WHT
BLU
BLU BLU
TRANS
HIC1
111
CN
4 2 1
C11
CN211
BLK
WHT
GRY RED
RT11
MF
3
121
CN
CN
112
NR11
IC141
RT12
YLW
BRN
ELECTRONIC CONTROL P.C. BOARD
PE
WIRING DIAGRAM
MS-C18TV -
INDOOR UNIT
E1
MODEL WIRING DIAGRAM
NOTE:1. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate. /: Terminal block, : Connector
MU-C18TV -
OUTDOOR UNIT
SYMBOL
C1
NOTE:1. About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
C2
2.Use copper conductors only. (For field wiring)
3. Symbols below indicate. /: Terminal block, : Connector
E1
MODEL WIRING DIAGRAM
COMPRESSOR CAPACITOR OUTDOOR FAN CAPACITOR
NAME
SYMBOL
F
MC
FUSE(2A) COMPRESSOR(INNER PROTECTOR)
NAME NAME
10
SYMBOL
MF
TB
OUTDOOR FAN MOTOR(INNER PROTECTOR) TERMINAL BLOCK
VG79B066H01
SG79B965H01
MS-C24TV -
E1
INDOOR UNIT
TO OUTDOOR UNIT CONNECTING
230V
~
230V~
POWER SUPPLY CORD ~/N 230V 50Hz
PE
CIRCUIT BREAKER
SYMBOL
C11
DSAR
F11 F12
HIC1
NOTE:1. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
INDOOR FAN CAPACITOR SURGE ABSORBER FUSE(3.15A) THERMAL FUSE(93°C) DC / DC CONVERTER
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate. /: Terminal block, : Connector
MU-C24TV -
OUTDOOR UNIT
MODEL WIRING DIAGRAM
TB
BLU
BRN
NAME
RED
BLU
WHT
F12
DSAR
WHT
1
GRN/YLW
BLU
2
BLU
1
LD1
SYMBOL
3
N
2 L
GRN/YLW
IC141
MF MV
NR11
RT11
E1
MODEL WIRING DIAGRAM
TB
3
230V~
230V~
BLU
N
2
WHT WHT
WHT
CN
102
CN201
3
BLU
1
CN
151
3
MV
DISPLAY P.C. BOARD
5
4 3
CN
ELECTRONIC CONTROL P.C. BOARD
101
3
RECEIVER P.C. BOARD
NAME NAME HYBRID IC INDOOR FAN MOTOR(INNER FUSE) VANE MOTOR VARISTOR ROOM TEMPERATURE THERMIST OR
REDRED
A1/a
TB2
WHT
1
RED
RED
26F1
BLU
C1
F
A2/b
52C
52C
21
52C
REDBLU BLK
HIC1
TRANS
F11
CR
RED
GRY
78
X1
S
MC
R
IC141
NR11
C11
REMOTE CONTROLLER
SYMBOL
RT12
TB
52C
3
X1
5 6
1
BLU
BLK
YLW
YLW
BLK
C
CN
112
CN 111
CN
121
CN211
4 2 1
3
BRN YLW GRY WHT RED BLK
RT12
RT11
MF
INDOOR COIL THERMISTOR TERMINAL BLOCK CONTACTOR
VG79B067H01
C2
RED
ORN
WHT
123456
WHT
RED
ORN
MF
FROM INDOOR UNIT CONNECTING
SYMBOL
CR
NOTE:1. About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
CR SURGE ABSORBER COMPRESSOR CAPACITOR
C1
OUTDOOR FAN CAPACITOR
C2
FUSE(2A)
F
2.Use copper conductors only. (For field wiring)
3. Symbols below indicate. /: Terminal block, : Connector
NAME
GRN/YLW
SYMBOL
MC MF
TB
TB2
NAME NAME COMPRESSOR (INNER PROTECTOR) OUTDOOR FAN MOTOR (INNER PROTECTOR) TERMINAL BLOCK TERMINAL BLOCK
11
SYMBOL
X1
26F1
52C
FAN MOTOR RELAY THERMOSTAT (AIR FLOW CONTORL) COMPRESSOR CONTACTOR
SG79B964H01
7
REFRIGERANT SYSTEM DIAGRAM
MS-C18TV -
INDOOR UNIT
Indoor heat exchanger
Distributor
Room temperature thermistor RT11
E1
Indoor coil thermistor
Refrigerant pipe [15.88 (Option) (with heat insulator)
RT12
Flared connection
Refrigerant pipe [6.35 (Option)
(with heat insulator)
Stop valve (with service port)
Stop valve
Compressor
Capillary tube [3.0 X [2.0 X 850
Unit:mm
MU-C18TV -
E1
OUTDOOR UNIT
Outdoor heat
Strainer
Refrigerant flow in cooling
exchanger
MS-C24TV -
INDOOR UNIT
Indoor heat exchanger
Distributor
Room temperature thermistor RT11
E1
Indoor coil thermistor
RT12
Refrigerant pipe [15.88 (Option) (with heat insulator)
Stop valve (with service port)
Flared connection
Stop valve
Refrigerant pipe [9.52
(Option)
(with heat insulator)
Compressor
Capillary tube [3.0 X [2.0 X 550
Unit:mm
MU-C24TV -
E1
OUTDOOR UNIT
Outdoor heat exchanger
Strainer
12
Refrigerant flow in cooling
Model
Refrigerant piping
Max. length : m
A
15
Piping size O.D : mm
Length of connecting pipe : m
Indoor unit
Gas 0.43
Liquid 0.5
Gas
15.88
Liquid
6.35
9.52
Outdoor unit
Gas 0
Liquid 0
MS-C18TV -
E1
MU-C18TV - E1 MS-C24TV - E1
MU-C24TV - E1
MAX. REFRIGERANT PIPING LENGTH
MAX. HEIGHT DIFFERENCE
Indoor unit
Refrigerant Piping
w Max. Height difference 5m
w Height difference should be within 5m regardless of which unit, indoor or outdoor position is high.
ADDITIONAL REFRIGERANT CHARGE(R407C : g)
Max.length
A
Outdoor unit
Model
MS-C18TV - E1 MU-C18TV - E1 MS-C24TV - E1 MU-C24TV - E1
Outdoor unit precharged
1,100
1,850
Refrigerant piping length (one way)
7m
0
Calculation : Xg=20g/mx(Refrigerant piping length (m)-7)
10m
60
15m
160
13
Wet and dry-bulb thermometers
Dry-bulb thermometers
8
PERFORMANCE CURVES
MS-C18TV - MU-C18TV ­MS-C24TV - MU-C24TV -
The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions. Since operating conditions vary according to the areas where these units are installed. The following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
Rated voltage : 207 ~ 253V
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature :°CWB (2) Indoor outlet air wet-bulb temperature :°CWB (3) Outdoor intake air dry-bulb temperature :°CDB (4) Total input :W
Indoor air wet/dry-bulb temperature difference on the left side of the chart on next page shows the difference between the indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry -bulb temperature for your reference at ser­vice.
How to measure the indoor air wet-bulb/dry-bulb temperature difference
1. Attach at least 2 sets of wet-and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet-and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.
2. Attach at least 2 sets of dry-bulb thermometers to the outdoor air intake. Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once to start the EMERGENCY COOL MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
,50Hz
E1E1
E1E1
Cooling
}
INDOOR UNIT
OUTDOOR UNIT
14
12.2
15 20
50
25 60
30 70
35(:)
(%)
0.3
0.4
0.5
0.6
0.7
7.0
6.0
5.0
4.0
3.0
18 32
230V
15 20
50
25 60
30 70
35(:)
(%)
7.0
8.0
9.0
10.0
11.0
12.0
230V
18
32
7.0
6.0
5.0
4.0
3.0
230V
15 20
50
25 60
30 70
35(:)
(%)
0.3
0.4
0.5
0.6
0.7
18 32
230V
15 20
50
25 60
30 70
35(:) (%)
8.0
9.0
10.0
11.0
12.0
13.0
14.0
18
32
11.2
10.1
9.1
8.2
7.2
14.9
13.5
12.2
11.0
9.8
8.6
MS-C18TV - E1
MS-C24TV - E1
OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT COOL operation
11
Both indoor and outdoor unit are under the same temperature/humidity condition.
Dry-bulb temperature
20 25
Relative humidity(%)
50 60
30 70
22
Air flow should be set at MAX.
33
The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The conversion factor is : 1(MPa[Gauge]) =10.2(kgf/ff[Gauge])
(kgf/F[Gauge])(MPa[Gauge])
Outdoor low pressure
Ambient temperature(˚C)Ambient humidity(%)
MU-C18TV -
E1
MU-C18TV -
Outdoor unit current(A)
Ambient temperature(˚C)Ambient humidity(%)
E1
(kgf/F[Gauge])(MPa[Gauge])
Outdoor low pressure
E1
MU-C24TV -
Ambient temperature(˚C)Ambient humidity(%)
Outdoor unit current(A)
Ambient temperature(˚C)Ambient humidity(%)
15
MU-C24TV -
E1
PERFORMANCE DATA COOL operation
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 5.99 3.18 0.53 1680 5.74 3.04 0.53 1764 5.51 2.92 0.53 1848 5.30 2.81 0.53 1932 21 20 6.25 2.56 0.41 1764 5.99 2.46 0.41 1869 5.81 2.38 0.41 1911 5.61 2.30 0.41 1995 22 18 5.99 3.42 0.57 1680 5.74 3.27 0.57 1764 5.51 3.14 0.57 1848 5.30 3.02 0.57 1932 22 20 6.25 2.81 0.45 1764 5.99 2.70 0.45 1869 5.81 2.62 0.45 1911 5.61 2.52 0.45 1995 22 22 6.50 2.15 0.33 1827 6.27 2.07 0.33 1943 6.12 2.02 0.33 1995 5.87 1.94 0.33 2079 23 18 5.99 3.66 0.61 1680 5.74 3.50 0.61 1764 5.51 3.36 0.61 1848 5.30 3.24 0.61 1932 23 20 6.25 3.06 0.49 1764 5.99 2.94 0.49 1869 5.81 2.85 0.49 1911 5.61 2.75 0.49 1995 23 22 6.50 2.41 0.37 1827 6.27 2.32 0.37 1943 6.12 2.26 0.37 1995 5.87 2.17 0.37 2079 24 18 5.99 3.90 0.65 1680 5.74 3.73 0.65 1764 5.51 3.58 0.65 1848 5.30 3.45 0.65 1932 24 20 6.25 3.31 0.53 1764 5.99 3.18 0.53 1869 5.81 3.08 0.53 1911 5.61 2.97 0.53 1995 24 22 6.50 2.67 0.41 1827 6.27 2.57 0.41 1943 6.12 2.51 0.41 1995 5.87 2.40 0.41 2079 24 24 6.83 1.98 0.29 1911 6.58 1.91 0.29 2016 6.43 1.86 0.29 2079 6.22 1.80 0.29 2184 25 18 5.99 4.13 0.69 1680 5.74 3.96 0.69 1764 5.51 3.80 0.69 1848 5.30 3.66 0.69 1932 25 20 6.25 3.56 0.57 1764 5.99 3.42 0.57 1869 5.81 3.31 0.57 1911 5.61 3.20 0.57 1995 25 22 6.50 2.93 0.45 1827 6.27 2.82 0.45 1943 6.12 2.75 0.45 1995 5.87 2.64 0.45 2079 25 24 6.83 2.26 0.33 1911 6.58 2.17 0.33 2016 6.43 2.12 0.33 2079 6.22 2.05 0.33 2184 26 18 5.99 4.37 0.73 1680 5.74 4.19 0.73 1764 5.51 4.02 0.73 1848 5.30 3.87 0.73 1932 26 20 6.25 3.81 0.61 1764 5.99 3.66 0.61 1869 5.81 3.55 0.61 1911 5.61 3.42 0.61 1995 26 22 6.50 3.19 0.49 1827 6.27 3.07 0.49 1943 6.12 3.00 0.49 1995 5.87 2.87 0.49 2079 26 24 6.83 2.53 0.37 1911 6.58 2.43 0.37 2016 6.43 2.38 0.37 2079 6.22 2.30 0.37 2184 26 26 7.04 1.76 0.25 2016 6.83 1.71 0.25 2121 6.73 1.68 0.25 2184 6.53 1.63 0.25 2247 27 18 5.99 4.61 0.77 1680 5.74 4.42 0.77 1764 5.51 4.24 0.77 1848 5.30 4.08 0.77 1932 27 20 6.25 4.06 0.65 1764 5.99 3.90 0.65 1869 5.81 3.78 0.65 1911 5.61 3.65 0.65 1995 27 22 6.50 3.45 0.53 1827 6.27 3.32 0.53 1943 6.12 3.24 0.53 1995 5.87 3.11 0.53 2079 27 24 6.83 2.80 0.41 1911 6.58 2.70 0.41 2016 6.43 2.63 0.41 2079 6.22 2.55 0.41 2184 27 26 7.04 2.04 0.29 2016 6.83 1.98 0.29 2121 6.73 1.95 0.29 2184 6.53 1.89 0.29 2247 28 18 5.99 4.85 0.81 1680 5.74 4.65 0.81 1764 5.51 4.46 0.81 1848 5.30 4.30 0.81 1932 28 20 6.25 4.31 0.69 1764 5.99 4.13 0.69 1869 5.81 4.01 0.69 1911 5.61 3.87 0.69 1995 28 22 6.50 3.71 0.57 1827 6.27 3.58 0.57 1943 6.12 3.49 0.57 1995 5.87 3.34 0.57 2079 28 24 6.83 3.08 0.45 1911 6.58 2.96 0.45 2016 6.43 2.89 0.45 2079 6.22 2.80 0.45 2184 28 26 7.04 2.32 0.33 2016 6.83 2.26 0.33 2121 6.73 2.22 0.33 2184 6.53 2.15 0.33 2247 29 18 5.99 5.09 0.85 1680 5.74 4.88 0.85 1764 5.51 4.68 0.85 1848 5.30 4.51 0.85 1932 29 20 6.25 4.56 0.73 1764 5.99 4.37 0.73 1869 5.81 4.24 0.73 1911 5.61 4.10 0.73 1995 29 22 6.50 3.97 0.61 1827 6.27 3.83 0.61 1943 6.12 3.73 0.61 1995 5.87 3.58 0.61 2079 29 24 6.83 3.35 0.49 1911 6.58 3.22 0.49 2016 6.43 3.15 0.49 2079 6.22 3.05 0.49 2184 29 26 7.04 2.60 0.37 2016 6.83 2.53 0.37 2121 6.73 2.49 0.37 2184 6.53 2.42 0.37 2247 30 18 5.99 5.33 0.89 1680 5.74 5.11 0.89 1764 5.51 4.90 0.89 1848 5.30 4.72 0.89 1932 30 20 6.25 4.81 0.77 1764 5.99 4.61 0.77 1869 5.81 4.48 0.77 1911 5.61 4.32 0.77 1995 30 22 6.50 4.23 0.65 1827 6.27 4.08 0.65 1943 6.12 3.98 0.65 1995 5.87 3.81 0.65 2079 30 24 6.83 3.62 0.53 1911 6.58 3.49 0.53 2016 6.43 3.41 0.53 2079 6.22 3.30 0.53 2184 30 26 7.04 2.89 0.41 2016 6.83 2.80 0.41 2121 6.73 2.76 0.41 2184 6.53 2.68 0.41 2247 31 18 5.99 5.57 0.93 1680 5.74 5.34 0.93 1764 5.51 5.12 0.93 1848 5.30 4.93 0.93 1932 31 20 6.25 5.06 0.81 1764 5.99 4.85 0.81 1869 5.81 4.71 0.81 1911 5.61 4.54 0.81 1995 31 22 6.50 4.49 0.69 1827 6.27 4.33 0.69 1943 6.12 4.22 0.69 1995 5.87 4.05 0.69 2079 31 24 6.83 3.90 0.57 1911 6.58 3.75 0.57 2016 6.43 3.66 0.57 2079 6.22 3.55 0.57 2184 31 26 7.04 3.17 0.45 2016 6.83 3.08 0.45 2121 6.73 3.03 0.45 2184 6.53 2.94 0.45 2247 32 18 5.99 5.81 0.97 1680 5.74 5.57 0.97 1764 5.51 5.34 0.97 1848 5.30 5.14 0.97 1932 32 20 6.25 5.31 0.85 1764 5.99 5.09 0.85 1869 5.81 4.94 0.85 1911 5.61 4.77 0.85 1995 32 22 6.50 4.75 0.73 1827 6.27 4.58 0.73 1943 6.12 4.47 0.73 1995 5.87 4.28 0.73 2079 32 24 6.83 4.17 0.61 1911 6.58 4.01 0.61 2016 6.43 3.92 0.61 2079 6.22 3.80 0.61 2184 32 26 7.04 3.45 0.49 2016 6.83 3.35 0.49 2121 6.73 3.30 0.49 2184 6.53 3.20 0.49 2247
OUTDOOR DB(:)
INDOOR INDOOR
DB(:) WB(:)
21 25 27 30
CAPACITY : 5.1(KW) SHF : 0.71 INPUT : 2100(W)
MS-C18TV - : MU-C18TV -
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB: Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB: Wet-bulb temperature
E1E1
16
PERFORMANCE DATA COOL operation
OUTDOOR DB(:)
INDOOR INDOOR
35 40 43 46
DB(:) WB(:)
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 5.00 2.65 0.53 2058 4.59 2.43 0.53 2184 4.41 2.34 0.53 2226 4.23 2.24 0.53 2268 21 20 5.25 2.15 0.41 2142 4.90 2.01 0.41 2247 4.72 1.93 0.41 2310 4.54 1.86 0.41 2373 22 18 5.00 2.85 0.57 2058 4.59 2.62 0.57 2184 4.41 2.51 0.57 2226 4.23 2.41 0.57 2268 22 20 5.25 2.36 0.45 2142 4.90 2.20 0.45 2247 4.72 2.12 0.45 2310 4.54 2.04 0.45 2373 22 22 5.56 1.83 0.33 2226 5.20 1.72 0.33 2352 5.02 1.66 0.33 2394 4.85 1.60 0.33 2436 23 18 5.00 3.05 0.61 2058 4.59 2.80 0.61 2184 4.41 2.69 0.61 2226 4.23 2.58 0.61 2268 23 20 5.25 2.57 0.49 2142 4.90 2.40 0.49 2247 4.72 2.31 0.49 2310 4.54 2.22 0.49 2373 23 22 5.56 2.06 0.37 2226 5.20 1.92 0.37 2352 5.02 1.86 0.37 2394 4.85 1.79 0.37 2436 24 18 5.00 3.25 0.65 2058 4.59 2.98 0.65 2184 4.41 2.87 0.65 2226 4.23 2.75 0.65 2268 24 20 5.25 2.78 0.53 2142 4.90 2.59 0.53 2247 4.72 2.50 0.53 2310 4.54 2.41 0.53 2373 24 22 5.56 2.28 0.41 2226 5.20 2.13 0.41 2352 5.02 2.06 0.41 2394 4.85 1.99 0.41 2436 24 24 5.87 1.70 0.29 2310 5.51 1.60 0.29 2415 5.36 1.55 0.29 2468 5.20 1.51 0.29 2520 25 18 5.00 3.45 0.69 2058 4.59 3.17 0.69 2184 4.41 3.04 0.69 2226 4.23 2.92 0.69 2268 25 20 5.25 2.99 0.57 2142 4.90 2.79 0.57 2247 4.72 2.69 0.57 2310 4.54 2.59 0.57 2373 25 22 5.56 2.50 0.45 2226 5.20 2.34 0.45 2352 5.02 2.26 0.45 2394 4.85 2.18 0.45 2436 25 24 5.87 1.94 0.33 2310 5.51 1.82 0.33 2415 5.36 1.77 0.33 2468 5.20 1.72 0.33 2520 26 18 5.00 3.65 0.73 2058 4.59 3.35 0.73 2184 4.41 3.22 0.73 2226 4.23 3.09 0.73 2268 26 20 5.25 3.20 0.61 2142 4.90 2.99 0.61 2247 4.72 2.88 0.61 2310 4.54 2.77 0.61 2373 26 22 5.56 2.72 0.49 2226 5.20 2.55 0.49 2352 5.02 2.46 0.49 2394 4.85 2.37 0.49 2436 26 24 5.87 2.17 0.37 2310 5.51 2.04 0.37 2415 5.36 1.98 0.37 2468 5.20 1.92 0.37 2520 26 26 6.17 1.54 0.25 2394 5.81 1.45 0.25 2499 5.64 1.41 0.25 2552 5.46 1.36 0.25 2604 27 18 5.00 3.85 0.77 2058 4.59 3.53 0.77 2184 4.41 3.40 0.77 2226 4.23 3.26 0.77 2268 27 20 5.25 3.41 0.65 2142 4.90 3.18 0.65 2247 4.72 3.07 0.65 2310 4.54 2.95 0.65 2373 27 22 5.56 2.95 0.53 2226 5.20 2.76 0.53 2352 5.02 2.66 0.53 2394 4.85 2.57 0.53 2436 27 24 5.87 2.40 0.41 2310 5.51 2.26 0.41 2415 5.36 2.20 0.41 2468 5.20 2.13 0.41 2520 27 26 6.17 1.79 0.29 2394 5.81 1.69 0.29 2499 5.64 1.63 0.29 2552 5.46 1.58 0.29 2604 28 18 5.00 4.05 0.81 2058 4.59 3.72 0.81 2184 4.41 3.57 0.81 2226 4.23 3.43 0.81 2268 28 20 5.25 3.62 0.69 2142 4.90 3.38 0.69 2247 4.72 3.26 0.69 2310 4.54 3.13 0.69 2373 28 22 5.56 3.17 0.57 2226 5.20 2.97 0.57 2352 5.02 2.86 0.57 2394 4.85 2.76 0.57 2436 28 24 5.87 2.64 0.45 2310 5.51 2.48 0.45 2415 5.36 2.41 0.45 2468 5.20 2.34 0.45 2520 28 26 6.17 2.04 0.33 2394 5.81 1.92 0.33 2499 5.64 1.86 0.33 2552 5.46 1.80 0.33 2604 29 18 5.00 4.25 0.85 2058 4.59 3.90 0.85 2184 4.41 3.75 0.85 2226 4.23 3.60 0.85 2268 29 20 5.25 3.83 0.73 2142 4.90 3.57 0.73 2247 4.72 3.44 0.73 2310 4.54 3.31 0.73 2373 29 22 5.56 3.39 0.61 2226 5.20 3.17 0.61 2352 5.02 3.06 0.61 2394 4.85 2.96 0.61 2436 29 24 5.87 2.87 0.49 2310 5.51 2.70 0.49 2415 5.36 2.62 0.49 2468 5.20 2.55 0.49 2520 29 26 6.17 2.28 0.37 2394 5.81 2.15 0.37 2499 5.64 2.09 0.37 2552 5.46 2.02 0.37 2604 30 18 5.00 4.45 0.89 2058 4.59 4.09 0.89 2184 4.41 3.93 0.89 2226 4.23 3.77 0.89 2268 30 20 5.25 4.04 0.77 2142 4.90 3.77 0.77 2247 4.72 3.63 0.77 2310 4.54 3.50 0.77 2373 30 22 5.56 3.61 0.65 2226 5.20 3.38 0.65 2352 5.02 3.27 0.65 2394 4.85 3.15 0.65 2436 30 24 5.87 3.11 0.53 2310 5.51 2.92 0.53 2415 5.36 2.84 0.53 2468 5.20 2.76 0.53 2520 30 26 6.17 2.53 0.41 2394 5.81 2.38 0.41 2499 5.64 2.31 0.41 2552 5.46 2.24 0.41 2604 31 18 5.00 4.65 0.93 2058 4.59 4.27 0.93 2184 4.41 4.10 0.93 2226 4.23 3.94 0.93 2268 31 20 5.25 4.25 0.81 2142 4.90 3.97 0.81 2247 4.72 3.82 0.81 2310 4.54 3.68 0.81 2373 31 22 5.56 3.84 0.69 2226 5.20 3.59 0.69 2352 5.02 3.47 0.69 2394 4.85 3.34 0.69 2436 31 24 5.87 3.34 0.57 2310 5.51 3.14 0.57 2415 5.36 3.05 0.57 2468 5.20 2.97 0.57 2520 31 26 6.17 2.78 0.45 2394 5.81 2.62 0.45 2499 5.64 2.54 0.45 2552 5.46 2.46 0.45 2604 32 18 5.00 4.85 0.97 2058 4.59 4.45 0.97 2184 4.41 4.28 0.97 2226 4.23 4.11 0.97 2268 32 20 5.25 4.47 0.85 2142 4.90 4.16 0.85 2247 4.72 4.01 0.85 2310 4.54 3.86 0.85 2373 32 22 5.56 4.06 0.73 2226 5.20 3.80 0.73 2352 5.02 3.67 0.73 2394 4.85 3.54 0.73 2436 32 24 5.87 3.58 0.61 2310 5.51 3.36 0.61 2415 5.36 3.27 0.61 2468 5.20 3.17 0.61 2520 32 26 6.17 3.02 0.49 2394 5.81 2.85 0.49 2499 5.64 2.76 0.49 2552 5.46 2.67 0.49 2604
MS-C18TV - : MU-C18TV -
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB: Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB: Wet-bulb temperature
E1E1
17
PERFORMANCE DATA COOL operation
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 7.52 3.61 0.48 2272 7.20 3.46 0.48 2386 6.91 3.32 0.48 2499 6.66 3.19 0.48 2613 21 20 7.84 2.82 0.36 2386 7.52 2.71 0.36 2528 7.30 2.63 0.36 2584 7.04 2.53 0.36 2698 22 18 7.52 3.91 0.52 2272 7.20 3.74 0.52 2386 6.91 3.59 0.52 2499 6.66 3.46 0.52 2613 22 20 7.84 3.14 0.40 2386 7.52 3.01 0.40 2528 7.30 2.92 0.40 2584 7.04 2.82 0.40 2698 22 22 8.16 2.28 0.28 2471 7.87 2.20 0.28 2627 7.68 2.15 0.28 2698 7.36 2.06 0.28 2812 23 18 7.52 4.21 0.56 2272 7.20 4.03 0.56 2386 6.91 3.87 0.56 2499 6.66 3.73 0.56 2613 23 20 7.84 3.45 0.44 2386 7.52 3.31 0.44 2528 7.30 3.21 0.44 2584 7.04 3.10 0.44 2698 23 22 8.16 2.61 0.32 2471 7.87 2.52 0.32 2627 7.68 2.46 0.32 2698 7.36 2.36 0.32 2812 24 18 7.52 4.51 0.60 2272 7.20 4.32 0.60 2386 6.91 4.15 0.60 2499 6.66 3.99 0.60 2613 24 20 7.84 3.76 0.48 2386 7.52 3.61 0.48 2528 7.30 3.50 0.48 2584 7.04 3.38 0.48 2698 24 22 8.16 2.94 0.36 2471 7.87 2.83 0.36 2627 7.68 2.76 0.36 2698 7.36 2.65 0.36 2812 24 24 8.58 2.06 0.24 2584 8.26 1.98 0.24 2726 8.06 1.94 0.24 2812 7.81 1.87 0.24 2954 25 18 7.52 4.81 0.64 2272 7.20 4.61 0.64 2386 6.91 4.42 0.64 2499 6.66 4.26 0.64 2613 25 20 7.84 4.08 0.52 2386 7.52 3.91 0.52 2528 7.30 3.79 0.52 2584 7.04 3.66 0.52 2698 25 22 8.16 3.26 0.40 2471 7.87 3.15 0.40 2627 7.68 3.07 0.40 2698 7.36 2.94 0.40 2812 25 24 8.58 2.40 0.28 2584 8.26 2.31 0.28 2726 8.06 2.26 0.28 2812 7.81 2.19 0.28 2954 26 18 7.52 5.11 0.68 2272 7.20 4.90 0.68 2386 6.91 4.70 0.68 2499 6.66 4.53 0.68 2613 26 20 7.84 4.39 0.56 2386 7.52 4.21 0.56 2528 7.30 4.09 0.56 2584 7.04 3.94 0.56 2698 26 22 8.16 3.59 0.44 2471 7.87 3.46 0.44 2627 7.68 3.38 0.44 2698 7.36 3.24 0.44 2812 26 24 8.58 2.74 0.32 2584 8.26 2.64 0.32 2726 8.06 2.58 0.32 2812 7.81 2.50 0.32 2954 26 26 8.83 1.77 0.20 2726 8.58 1.72 0.20 2868 8.45 1.69 0.20 2954 8.19 1.64 0.20 3039 27 18 7.52 5.41 0.72 2272 7.20 5.18 0.72 2386 6.91 4.98 0.72 2499 6.66 4.79 0.72 2613 27 20 7.84 4.70 0.60 2386 7.52 4.51 0.60 2528 7.30 4.38 0.60 2584 7.04 4.22 0.60 2698 27 22 8.16 3.92 0.48 2471 7.87 3.78 0.48 2627 7.68 3.69 0.48 2698 7.36 3.53 0.48 2812 27 24 8.58 3.09 0.36 2584 8.26 2.97 0.36 2726 8.06 2.90 0.36 2812 7.81 2.81 0.36 2954 27 26 8.83 2.12 0.24 2726 8.58 2.06 0.24 2868 8.45 2.03 0.24 2954 8.19 1.97 0.24 3039 28 18 7.52 5.72 0.76 2272 7.20 5.47 0.76 2386 6.91 5.25 0.76 2499 6.66 5.06 0.76 2613 28 20 7.84 5.02 0.64 2386 7.52 4.81 0.64 2528 7.30 4.67 0.64 2584 7.04 4.51 0.64 2698 28 22 8.16 4.24 0.52 2471 7.87 4.09 0.52 2627 7.68 3.99 0.52 2698 7.36 3.83 0.52 2812 28 24 8.58 3.43 0.40 2584 8.26 3.30 0.40 2726 8.06 3.23 0.40 2812 7.81 3.12 0.40 2954 28 26 8.83 2.47 0.28 2726 8.58 2.40 0.28 2868 8.45 2.37 0.28 2954 8.19 2.29 0.28 3039 29 18 7.52 6.02 0.80 2272 7.20 5.76 0.80 2386 6.91 5.53 0.80 2499 6.66 5.32 0.80 2613 29 20 7.84 5.33 0.68 2386 7.52 5.11 0.68 2528 7.30 4.96 0.68 2584 7.04 4.79 0.68 2698 29 22 8.16 4.57 0.56 2471 7.87 4.41 0.56 2627 7.68 4.30 0.56 2698 7.36 4.12 0.56 2812 29 24 8.58 3.77 0.44 2584 8.26 3.63 0.44 2726 8.06 3.55 0.44 2812 7.81 3.44 0.44 2954 29 26 8.83 2.83 0.32 2726 8.58 2.74 0.32 2868 8.45 2.70 0.32 2954 8.19 2.62 0.32 3039 30 18 7.52 6.32 0.84 2272 7.20 6.05 0.84 2386 6.91 5.81 0.84 2499 6.66 5.59 0.84 2613 30 20 7.84 5.64 0.72 2386 7.52 5.41 0.72 2528 7.30 5.25 0.72 2584 7.04 5.07 0.72 2698 30 22 8.16 4.90 0.60 2471 7.87 4.72 0.60 2627 7.68 4.61 0.60 2698 7.36 4.42 0.60 2812 30 24 8.58 4.12 0.48 2584 8.26 3.96 0.48 2726 8.06 3.87 0.48 2812 7.81 3.75 0.48 2954 30 26 8.83 3.18 0.36 2726 8.58 3.09 0.36 2868 8.45 3.04 0.36 2954 8.19 2.95 0.36 3039 31 18 7.52 6.62 0.88 2272 7.20 6.34 0.88 2386 6.91 6.08 0.88 2499 6.66 5.86 0.88 2613 31 20 7.84 5.96 0.76 2386 7.52 5.72 0.76 2528 7.30 5.54 0.76 2584 7.04 5.35 0.76 2698 31 22 8.16 5.22 0.64 2471 7.87 5.04 0.64 2627 7.68 4.92 0.64 2698 7.36 4.71 0.64 2812 31 24 8.58 4.46 0.52 2584 8.26 4.29 0.52 2726 8.06 4.19 0.52 2812 7.81 4.06 0.52 2954 31 26 8.83 3.53 0.40 2726 8.58 3.43 0.40 2868 8.45 3.38 0.40 2954 8.19 3.28 0.40 3039 32 18 7.52 6.92 0.92 2272 7.20 6.62 0.92 2386 6.91 6.36 0.92 2499 6.66 6.12 0.92 2613 32 20 7.84 6.27 0.80 2386 7.52 6.02 0.80 2528 7.30 5.84 0.80 2584 7.04 5.63 0.80 2698 32 22 8.16 5.55 0.68 2471 7.87 5.35 0.68 2627 7.68 5.22 0.68 2698 7.36 5.00 0.68 2812 32 24 8.58 4.80 0.56 2584 8.26 4.62 0.56 2726 8.06 4.52 0.56 2812 7.81 4.37 0.56 2954 32 26 8.83 3.89 0.44 2726 8.58 3.77 0.44 2868 8.45 3.72 0.44 2954 8.19 3.60 0.44 3039
OUTDOOR DB(:)
INDOOR INDOOR
DB(:) WB(:)
21 25 27 30
CAPACITY : 6.4(KW) SHF : 0.66 INPUT : 2840(W)
MS-C24TV - : MU-C24TV -
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB: Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB: Wet-bulb temperature
E1E1
18
PERFORMANCE DATA COOL operation
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 6.27 3.01 0.48 2783 5.76 2.76 0.48 2954 5.54 2.66 0.48 3010 5.31 2.55 0.48 3067 21 20 6.59 2.37 0.36 2897 6.14 2.21 0.36 3039 5.92 2.13 0.36 3124 5.70 2.05 0.36 3209 22 18 6.27 3.26 0.52 2783 5.76 3.00 0.52 2954 5.54 2.88 0.52 3010 5.31 2.76 0.52 3067 22 20 6.59 2.64 0.40 2897 6.14 2.46 0.40 3039 5.92 2.37 0.40 3124 5.70 2.28 0.40 3209 22 22 6.98 1.95 0.28 3010 6.53 1.83 0.28 3181 6.30 1.77 0.28 3238 6.08 1.70 0.28 3294 23 18 6.27 3.51 0.56 2783 5.76 3.23 0.56 2954 5.54 3.10 0.56 3010 5.31 2.97 0.56 3067 23 20 6.59 2.90 0.44 2897 6.14 2.70 0.44 3039 5.92 2.60 0.44 3124 5.70 2.51 0.44 3209 23 22 6.98 2.23 0.32 3010 6.53 2.09 0.32 3181 6.30 2.02 0.32 3238 6.08 1.95 0.32 3294 24 18 6.27 3.76 0.60 2783 5.76 3.46 0.60 2954 5.54 3.32 0.60 3010 5.31 3.19 0.60 3067 24 20 6.59 3.16 0.48 2897 6.14 2.95 0.48 3039 5.92 2.84 0.48 3124 5.70 2.73 0.48 3209 24 22 6.98 2.51 0.36 3010 6.53 2.35 0.36 3181 6.30 2.27 0.36 3238 6.08 2.19 0.36 3294 24 24 7.36 1.77 0.24 3124 6.91 1.66 0.24 3266 6.72 1.61 0.24 3337 6.53 1.57 0.24 3408 25 18 6.27 4.01 0.64 2783 5.76 3.69 0.64 2954 5.54 3.54 0.64 3010 5.31 3.40 0.64 3067 25 20 6.59 3.43 0.52 2897 6.14 3.19 0.52 3039 5.92 3.08 0.52 3124 5.70 2.96 0.52 3209 25 22 6.98 2.79 0.40 3010 6.53 2.61 0.40 3181 6.30 2.52 0.40 3238 6.08 2.43 0.40 3294 25 24 7.36 2.06 0.28 3124 6.91 1.94 0.28 3266 6.72 1.88 0.28 3337 6.53 1.83 0.28 3408 26 18 6.27 4.26 0.68 2783 5.76 3.92 0.68 2954 5.54 3.76 0.68 3010 5.31 3.61 0.68 3067 26 20 6.59 3.69 0.56 2897 6.14 3.44 0.56 3039 5.92 3.32 0.56 3124 5.70 3.19 0.56 3209 26 22 6.98 3.07 0.44 3010 6.53 2.87 0.44 3181 6.30 2.77 0.44 3238 6.08 2.68 0.44 3294 26 24 7.36 2.36 0.32 3124 6.91 2.21 0.32 3266 6.72 2.15 0.32 3337 6.53 2.09 0.32 3408 26 26 7.74 1.55 0.20 3238 7.30 1.46 0.20 3380 7.07 1.41 0.20 3451 6.85 1.37 0.20 3522 27 18 6.27 4.52 0.72 2783 5.76 4.15 0.72 2954 5.54 3.99 0.72 3010 5.31 3.82 0.72 3067 27 20 6.59 3.96 0.60 2897 6.14 3.69 0.60 3039 5.92 3.55 0.60 3124 5.70 3.42 0.60 3209 27 22 6.98 3.35 0.48 3010 6.53 3.13 0.48 3181 6.30 3.03 0.48 3238 6.08 2.92 0.48 3294 27 24 7.36 2.65 0.36 3124 6.91 2.49 0.36 3266 6.72 2.42 0.36 3337 6.53 2.35 0.36 3408 27 26 7.74 1.86 0.24 3238 7.30 1.75 0.24 3380 7.07 1.70 0.24 3451 6.85 1.64 0.24 3522 28 18 6.27 4.77 0.76 2783 5.76 4.38 0.76 2954 5.54 4.21 0.76 3010 5.31 4.04 0.76 3067 28 20 6.59 4.22 0.64 2897 6.14 3.93 0.64 3039 5.92 3.79 0.64 3124 5.70 3.65 0.64 3209 28 22 6.98 3.63 0.52 3010 6.53 3.39 0.52 3181 6.30 3.28 0.52 3238 6.08 3.16 0.52 3294 28 24 7.36 2.94 0.40 3124 6.91 2.76 0.40 3266 6.72 2.69 0.40 3337 6.53 2.61 0.40 3408 28 26 7.74 2.17 0.28 3238 7.30 2.04 0.28 3380 7.07 1.98 0.28 3451 6.85 1.92 0.28 3522 29 18 6.27 5.02 0.80 2783 5.76 4.61 0.80 2954 5.54 4.43 0.80 3010 5.31 4.25 0.80 3067 29 20 6.59 4.48 0.68 2897 6.14 4.18 0.68 3039 5.92 4.03 0.68 3124 5.70 3.87 0.68 3209 29 22 6.98 3.91 0.56 3010 6.53 3.66 0.56 3181 6.30 3.53 0.56 3238 6.08 3.40 0.56 3294 29 24 7.36 3.24 0.44 3124 6.91 3.04 0.44 3266 6.72 2.96 0.44 3337 6.53 2.87 0.44 3408 29 26 7.74 2.48 0.32 3238 7.30 2.33 0.32 3380 7.07 2.26 0.32 3451 6.85 2.19 0.32 3522 30 18 6.27 5.27 0.84 2783 5.76 4.84 0.84 2954 5.54 4.65 0.84 3010 5.31 4.46 0.84 3067 30 20 6.59 4.75 0.72 2897 6.14 4.42 0.72 3039 5.92 4.26 0.72 3124 5.70 4.10 0.72 3209 30 22 6.98 4.19 0.60 3010 6.53 3.92 0.60 3181 6.30 3.78 0.60 3238 6.08 3.65 0.60 3294 30 24 7.36 3.53 0.48 3124 6.91 3.32 0.48 3266 6.72 3.23 0.48 3337 6.53 3.13 0.48 3408 30 26 7.74 2.79 0.36 3238 7.30 2.63 0.36 3380 7.07 2.55 0.36 3451 6.85 2.47 0.36 3522 31 18 6.27 5.52 0.88 2783 5.76 5.07 0.88 2954 5.54 4.87 0.88 3010 5.31 4.67 0.88 3067 31 20 6.59 5.01 0.76 2897 6.14 4.67 0.76 3039 5.92 4.50 0.76 3124 5.70 4.33 0.76 3209 31 22 6.98 4.46 0.64 3010 6.53 4.18 0.64 3181 6.30 4.03 0.64 3238 6.08 3.89 0.64 3294 31 24 7.36 3.83 0.52 3124 6.91 3.59 0.52 3266 6.72 3.49 0.52 3337 6.53 3.39 0.52 3408 31 26 7.74 3.10 0.40 3238 7.30 2.92 0.40 3380 7.07 2.83 0.40 3451 6.85 2.74 0.40 3522 32 18 6.27 5.77 0.92 2783 5.76 5.30 0.92 2954 5.54 5.09 0.92 3010 5.31 4.89 0.92 3067 32 20 6.59 5.27 0.80 2897 6.14 4.92 0.80 3039 5.92 4.74 0.80 3124 5.70 4.56 0.80 3209 32 22 6.98 4.74 0.68 3010 6.53 4.44 0.68 3181 6.30 4.29 0.68 3238 6.08 4.13 0.68 3294 32 24 7.36 4.12 0.56 3124 6.91 3.87 0.56 3266 6.72 3.76 0.56 3337 6.53 3.66 0.56 3408 32 26 7.74 3.41 0.44 3238 7.30 3.21 0.44 3380 7.07 3.11 0.44 3451 6.85 3.01 0.44 3522
OUTDOOR DB(:)
INDOOR INDOOR
35 40 43 46
DB(:) WB(:)
MS-C24TV - : MU-C24TV -
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB: Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB: Wet-bulb temperature
E1E1
19
9
lighting not lighting
Approx. 2 : or more
Difference between set temperature and room temperature
Approx. 2 : or less
This shows that the air conditioner is operating to reach the target temperature. Please wait until the target temperature is obtained.
This shows that the room temperature is approaching the target temperature.
Operation stateIndication
Operation Indicator
Operation Indicator lamp
The operation indicator at the right side of the indoor unit indicates the operation state.
INDOOR UNIT DISPLAY SECTION
MICROPROCESSOR CONTROL
WIRELESS REMOTE CONTROLLER
Signal transmitting section
Operation display section
OPERATE /STOP
(ON /OFF)button
FAN SPEED CONTROL button
OPERATION SELECT button
ECONO COOL button
RESET button
I FEEL
FAN
MODE
ECONO COOL
ON/OFF
ON/OFF
COOL
DRY
WARM
WARM
FAN
VANE
RESET
PM
AM
TOO
TOO
COOL
TEMPERATURE buttons
CLOCK
PM
AM
TOO
TOO
COOL
STOP
START
HR.
MIN.
CLOCK
OFF-TIMER button
ON-TIMER button
HR. button
MIN. button
(TIME SET button)
CLOCK SET button
VANE CONTROL button
MS-C18TV ­MS-C24TV -
E1
E1
Once the operation mode are set, the same operation mode can be repeated by simply turning the OPERATE/STOP(ON/OFF) button ON. Indoor unit receives the signal with a beep tone. When the system turns off, 3-minute time delay will operate to protect system from overload and compressor will not restart for 3 minutes.
9-1. “I FEEL CONTROL” ( ) OPERATION
(1) Press OPERATE/STOP(ON/OFF) button on the remote
controller. OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select “I FEEL CONTROL”( ) mode with the OPERA-
TION SELECT button.
(3) The operation mode is determined by the room tempera-
ture at start-up of the operation.
Initial room temperature
25: or more more than 13:,
less than 25:
Once the mode is fixed, the mode does not change by room temperature afterwards.
Under the ON-TIMER ( ) operation, the mode is determined according to the room temperature at the set time the operation starts.
When the system is stopped on the remote controller, and restarted within 2 hours in “I FEEL CONTROL” ( )
mode, the system operates in previous mode automati­cally regardless of the room temperature.
mode
COOL mode of
“I FEEL CONTROL“
DRY mode of
“I FEEL CONTROL”
Example
Previous operation
COOL mode of “I FEEL CONTROL” or COOL mode
When the system is restarted after 2 hours and more, the operation mode is determined by the room tempera­ture at start-up of the operation.
Operation timer chart Example
Previous operation
COOL mode of “I FEEL CONTROL” or COOL mode
20
Restart
COOL mode of “I FEEL CONTROL”
Restart
COOL or DRY mode of “I FEEL CONTROL” that determined by room temperature at start-up of the operation.
Mode
COOL mode of
"I FEEL CONTROL"
DRY mode of
"I FEEL CONTROL"
Initial room temperature Initial set temperature
26: or more
25: to 26:
more than13:, less than 25:
24:
Initial room temperature minus 2: Initial room temperature minus 2:
w1
(4) The initial set temperature is decided by the initial room temperature.
TOO
COOL
TOO
WARM
w 1 When the system is restarted with the remote controller, the system operates with the previous set temperature regard-
less of the room temperature at restart. The set temperature is calculated by the previous set temperature.
(5) TEMPERATURE buttons
In “I FEEL CONTROL” ( ) mode, set temperature is decided by the microprocessor based on the room temperature.
In addition, set temperature can be controlled by TOO WARM or TOO COOL buttons when you feel too cool or too warm. Each time the TOO WARM or TOO COOL button is pressed the indoor unit receives the signal and emits a beep tone.
Fuzzy control
When the TOO COOL or TOO WARM button is pressed the microprocessor changes the set temperature, considering the room temperature, the frequency of pressing TOO COOL or TOO WARM button and the user’s preference to heat or cool. So this is called “Fuzzy control”, and works only in “I FEEL CONTROL” mode. In DRY mode of “I FEEL CONTROL”, the set temperature doesn’t change.
To raise the set temperature 1~2 degrees(°C)
To lower the set temperature 1~2 degrees(°C)
— COOL mode of “I FEEL CONTROL” —
1. Indoor fan speed control
Indoor fan operates at the set speed by FAN SPEED CONTROL button. In AUTO the fan speed is as follows.
Initial temperature difference
Fan speed
Room temperature minus set temperature : 2 degrees or more······································High Room temperature minus set temperature : Between 1 and 2 degrees··························Med. Room temperature minus set temperature : less than 1 degree······································Low
2. Coil frost prevention
1 Temperature control
When the indoor coil thermistor RT12 reads -1°C or below, the coil frost prevention mode starts immediately. However, the coil frost prevention doesn’t work for 5 minutes since the compressor has started. The indoor fan operates at the set speed and the compressor stops for 5 minutes. After that, if RT12still reads below -1°C this mode is prolonged until the RT12 reads over -1°C.
2 Time control
When the three conditions as follows have been satisfied for 1 hour and 45 minutes, compressor stops for 3 minutes. a. Compressor has been continuously operating. b. Indoor fan speed is Low or Med.. c. Room temperature is below 26°C. When compressor stops, the accumulated time is cancelled and when compressor restarts, time counting starts from the beginning. Time counting also stops temporarily when the indoor fan speed becomes High or the room temperature exceeds 26°C. However, when two of the above conditions (b.and c.) are satisfied again.Time accumulation is resumed.
Difference between room temperature and set tem­perature during operation
1 deg.
2 deg.
1.7 deg.
4 deg.
21
Operation chart
Example
ON
ON
Compressor Outdoor fan
Indoor fan
—DRY mode of “I FEEL CONTROL”—
The system for dry operation uses the same refrigerant circuit as the cooling circuit. The compressor and the indoor fan are controlled by the room temperature. By such controls, indoor flow amounts will be reduced in order to lower humidity without much room temperature
decrease.
1. Indoor fan speed control
Indoor fan operates at the set speed by FAN SPEED CONTROL button. However, in AUTO fan operation, fan speed becomes Low.
2. The operation of the compressor and indoor / outdoor fan
Compressor operates by room temperature control and time control.
Set temperature is controlled to fall 2°C from initial room temperature.
Indoor fan and outdoor fan operate in the same cycle as the compressor.
• When the room temperature is 23°C or over: When the thermostat is ON, the compressor repeats 8 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
• When the room temperature is under 23°C. When the thermostat is ON, the compressor repeats 2 minutes ON and 3 minutes OFF. When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
OFF
(continuously at set speed)
ON
OFF
Operation time chart
Example
Thermostat
Indoor fan
Outdoor fan Compressor
3. Coil frost prevention
The operation is as same as coil frost prevention during COOL mode of “I FEEL CONTROL”. Indoor fan operates at the set speed and the compressor stops for 5minutes, because protection (Coil frost prevention)has the priority. However when coil frost prevention works while the compressor is not operating, it’s speed becomes Low.
OFF
ON
OFF
OFF
8 min.
ON
ON
OFF
OFF
ON
ON
3 min.
ON
OFF
ON
OFF
ON
OFF
1 min.
22
9-2. COOL ( ) OPERATION
High
High
Med.
Low
AUTO
Horizontal Middle
Downward
Swing
(1) Press OPERATE/STOP(ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select COOL mode with the OPERATION
SELECT button.
(3) Press the TEMPERATURE buttons.
(TOO WARM or TOO COOL button) to select the desired temperature. The setting range is 16 ~ 31°C. w Indoor fan continues to operate regardless
of thermostat’s OFF-ON at set speed.
w Coil frost prevention is as same as COOL
mode of “I FEEL CONTROL”.
9-3. DRY ( ) OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select DRY mode with the OPERATION
SELECT button.
(3) The microprocessor reads the room temper-
ature and determines the set temperature. Set temperature is as shown on the right chart. Thermostat (SET TEMP.) does not work. The other operations are same as DRY mode of “I FEEL CONTROL”.
(4) DRY operation will not function when the room temperature is 13°C or below.
9-4.FAN( d )OPERATION
(1) Press OPERATE/STOP(ON/OFF) button. OPERATION INDICATOR lamp of the indoor unit turns ON with a beep tone. (2) Select FAN mode with the OPERATION SELECT button. (3) Select the desired fan speed. When AUTO, it becomes Low.
Only indoor fan operates. Outdoor unit does not operate.
9-5. FAN MOTOR CONTROL
(1) Rotational frequency feedback control
The indoor fan motor is equipped with a rotational frequency sensor, and outputs signal to the microprocessor to feedback the rotational frequency. Comparing the current rotational frequency with the target rotational frequency
(High,Med.,Low), the microprocessor controls IC141 and adjusts fan motor electric current to make the current rotational frequency close to the target rotational frequency. With this control, when the fan speed is switched, the rotational frequency changes smoothly.
(2) Fan motor lock-up protection
When the rotational frequency feedback signal has not output for 12 seconds, (or when the microprocessor cannot
detect the signal for 12 seconds) the fan motor is regarded locked-up. Then the electric current to the fan motor is shut
off. 3 minutes later, the electric current is applied to the fan motor again. During the fan motor lock-up, the OPERATION
INDICATOR lamp flashes on and off to show the fan motor abnormality. (Refer to page 30.)
9-6. AUTO VANE OPERATION
(1) Vane motor drive
These models are equipped with a stepping motor for the horizontal vane. The rotating direction, speed, and angle of
the motor are controlled by pulse signals (approx. 12V) transmitted from microprocessor.
(2) The horizontal vane angle and mode change as follows by pressing the VANE CONTROL button.
23
(3) Positioning
The vane is once pressed to the vane stopper below to confirm the standard position and then set to the desired angle. Confirming of standard position is performed in case of follows. (a) When the OPERATE/STOP(ON/OFF) button is pressed(POWER ON/OFF). (b) When the vane control is changed from AUTO to MANUAL. (c) When the SWING is finished. (d) When the test run starts. (e) When the power supply turns ON.
(4) VANE AUTO ( ) mode
In VANE AUTO mode, the microprocessor automatically determines the horizontal vane angle and operation to make the optimum room-temperature distribution.
1 In COOL and DRY operation
Vane angle is fixed to Angle 1.
2 In FAN operation
Vane angle is fixed to Angle 4.
(5) STOP (operation OFF) and ON-TIMER standby.
When the following cases occur, the horizontal vane returns to the closed position. (a) When the OPERATE/STOP(ON/OFF) button is pressed (POWER OFF). (b) When the operation is stopped by the emergency operation. (c) When the ON-TIMER is on standby.
(6) Dew prevention
During COOL or DRY operation at Vane Angle 4 or 5 when the compressor cumulative operation time exceeds 1 hour, the vane angle automatically changes to Angle 1 for dew prevention.
(7) SWING MODE ( )
By selecting SWING mode with the VANE CONTROLbutton, the horizontal vane swings vertically. The remote controller displays “ ”.
(8) ECONO COOL ( ) operation (ECONOmical operation)
When the ECONO COOL button is pressed in COOL mode, set temperature is automatically set 2°C higher than that in COOL mode. Also the horizontal vane swings in various cycle according to the temperature of indoor heat exchanger(RT12). SWING operation makes you feel cooler than set temperature. So, even though the set temperature is higher than that in COOL mode, the air conditioner can keep comfort. As a result, energy can be saved. ECONO COOL operation is cancelled when the ECONO COOL button is pressed once again or VANE CONTROLbut­ton is pressed or change to other operation mode. NOTE : ECONO COOL operation not work in COOL mode of “I FEEL CONTROL”.
SWING operation
In swing operation of ECONO COOL operation air flow is initially blew out upward(levelly). According to the temperature of indoor coil thermistor RT12 at starting of this operation, next downward blow time is decided. Then when the downward blow has been finished, next upward blow time is decided. For initial 10 minutes the swing operation is performed in table G~H for quick cooling(but G : RT 12 is 24: or less). Also, after 10 minutes when the difference of set temperature and room temperature is more than 2:, the swing oper­ation is performed in table D~H for more cooling(but D: RT12 is 20: or less). The air conditioner repeats the swing operation in various cycle as follows.
Temperature of indoor
coil thermistor RT12
A
B C D E
F
G
H
15°C or less 15°C to 17°C
17°C to 18°C
18°C to 20°C
20°C to 21°C 21°C to 22°C 22°C to 24°C
more than 24°C
Downward blow time
(sec.)
2 5 8
11 14 17 20 23
24
Upward(level) blow time
(sec.)
23 20 17 14 11
8 5 2
9-7. TIMER OPERATION
PM
AM
PM
PM
1. How to set the timer
(1) Press OPERATE/STOP(ON/OFF) button to start the air conditioner. (2) Check that the current time is set correctly. NOTE : Timer operation will not work without setting the current time. Initially “AM0:00” blinks at the current time display of
TIMER MONITOR, so set the current time correctly with CLOCK SET button.
(3) Press ON/OFF TIMER buttons to select the operation.
“ON-TIMER” button... AUTO START operation (ON timer) “OFF-TIMER” button... AUTO STOP operation (OFF timer)
(4) Press HR. and MIN. button (TIME set button) to set the timer. Time setting is 10-minute units.
HR. and MIN. button will work when “ ” or “
mark is flashing.
These marks disappear in 1 minute. After setting the ON timer, check that OPERATION INDICATOR lamp of the indoor unit lights.
NOTE1 :Be sure to place the remote controller at the position where its signal can reach the air conditioner even during
TIMER operation, or the set time may deviate within the range of about 10 minutes.
NOTE2 :Reset the timer in the following cases, or the set time may deviate and other malfunctions may occur.
A power failure occurs.
The circuit breaker functions.
2. Cancel
TIMER setting can be cancelled with the ON/OFF TIMER buttons. To cancel the ON timer, press the “ To cancel the OFF timer, press the “
ON-TIMER
OFF-TIMER
” button.
” button.
TIMER is cancelled and the display of set time disappears.
PROGRAM TIMER
The OFF timer and ON timer can be used in combination.
”and “ ” display shows the order of the OFF timer and ON timer operation.
(Example 1) The current time is 8:00 PM.
The unit turns off at 11:00 PM, and on at 6:00 AM.
(Example 2) The current time is 11:00 AM.
The unit turns on at 5:00 PM, and off at 9:00 PM.
NOTE : TIMER setting will be cancelled by power failure or breaker functioning.
25
9-8. EMERGENCY-TEST OPERATION
EMERGENCY OPERATION switch
In case of test run operation or emergency operation, use the EMERGENCY OPERATION switch on the front of the indoor unit. Emergency operation is available when the remote controller is missing, has failed or the batteries of remote controller run down. The unit will start and the OPERATION INDICATOR lamp will light. The first 30 minutes of operation is the test run operation. This operation is for servicing. The indoor fan speed runs at High speed and the system is in continuous operation. (The thermostat is ON.) After 30 minutes of test run operation the system shifts to EMERGENCY COOL MODE with a set temperature of 24°C. The fan speed shifts to Med. speed. The coil frost prevention works even in emergency operation.
In the test run or emergency operation, the horizontal vane operates in VANE AUTO ( ) mode. Emergency operation continues until the EMERGENCY OPERATION switch is pressed again or the unit receives any sig­nal from the remote controller. In case of latter normal operation will start.
NOTE : Do not press the EMERGENCY OPERATION switch during normal operation.
OPERATION INDICATOR lamp
Press once <Cool> Press once again
<Stop>
26
10
SERVICE FUNCTIONS
MS-C18TV ­MS-C24TV -
E1
E1
10-1. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS the electronic control P.C. board. The time will be shortened as follows. (Refer to page 36.) Set time : 1 minute 1-second Set time : 3 minute 3-second (It takes 3 minutes for the compressor to start operation. However, the starting time is
shortened by short circuit of JPG and JPS.)
10-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room. In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be modified according to the number of the indoor unit.
How to modify the remote controller P.C. board
Remove batteries before modification. The board has a print as shown below :
NOTE : For remodelling, take out the bat-
teries and push the OPERATE/STOP(ON/OFF) button twice or 3 times at first. After finish remodelling, put back the batteries then push the RESET button.
The P.C. board has the print “J1” and “J2”. Solder “J1” and “J2” according to the number of indoor unit as shown in Table 1. After modification, push the RESET button.
Table 1
1 unit operation No. 1 unit No. 2 unit No. 3 unit No. 4 unit
NOTE :
At power supply failure or installation, indoor unit deletes the memory about remote controller. When the power supply is turned on and indoor unit receives the first signals from the remote controller, the remote controller number is desig­nated as the indoor unit number. Therefore at and after the second time indoor unit accepts the remote controller of the initial setting number. At setting-error, turn the power supply off to cancel the individual operation and then turn the power supply on to restart the setting.
No modification
– – –
2 units operation
Same as at left
Solder J1
– –
3 units operation
Same as at left Same as at left
Solder J2
4 units operation
Same as at left Same as at left Same as at left
Solder both J1 and J2
27
10-3. AUTO RESTART FUNCTION
JR06
CN102
CN151
CN112 CN111 CN121
CN101
BZ
SW
52C
IC101 RA102
IC141
CN211
C11CN201
When the indoor unit is controlled with the remote controller, the operation mode, set temperature, and the fan speed are memorized by the indoor electronic control P.C.board. The “AUTO RESTART FUNCTION” sets to work the moment power has restored after power failure. Then, the unit will restart automatically. However if the unit is operated in “I FEEL CONTROL.” mode before power failure, the operation is not memorized. In “I FEEL CONTROL.” mode, the operation is decided by the initial room temperature.
How to set “AUTO RESTART FUNCTION”
1Turn off the main power for the unit. 2Pull out the electronic control P.C. board and the display P.C.board. (Refer to page 37.) 3Cut the RESISTOR JR06 on the indoor electronic control P.C.board. (Refer to page 36.)
Operation
1If the main power (230V AC) has been cut, the operation settings remain. 2After the power is restored, the unit restarts automatically according to the memory.(However, it takes at least 3 minutes
for the compressor to start running.)
NOTE:
The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the remote
controller.
If main power is turned off or a power failure occurs while AUTO START/STOP timer is active, the timer setting is
cancelled.
If the unit has been off with the remote controller before power failure, the auto restart function does not work as the
power button of the remote controller is off.
To prevent breaker off due to the rush of starting current, systematize other home appliances not to turn on at the same
time.
When some air conditioners are connected to the same supply system, if they are operated before power failure, the
starting current of all the compressors may flow simultaneously at restart. Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting current by adding to the system that allows the units to start one by one.
28
11
Insert the minus pole of the batteries first. Check if the polarity of the battereis is correct.
RESET button
TROUBLESHOOTING
MS-C18TV - MU-C18TV ­MS-C24TV - MU-C24TV -
E1E1
E1E1
11-1. Cautions on troubleshooting
1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care the following during servicing.
1) Before servicing the air conditioner, be sure to first turn off the remote controller to stop the unit, and then after confirming the horizontal vane is closed, turn off the breaker and / or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel and the electronic control P.C. board.
3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.
4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.
To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
2) Before servicing that the connector and terminal are connected properly.
3) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and
the components for bursting and discoloration.
4) When troubleshooting, refer to the flow chart and the check table on page 30.
4. How to replace batteries
Weak batteries may cause the remote controller malfunction. In this case, replace the batteries to operate the remote controller normally. 1 Remove the front lid and insert batteries.
Then reattach the front lid.
2 Press the RESET button with tip end of ball point
pen or the like, and then use the remote controller.
NOTE : If the RESET button is not pressed, the remote controller may not operate correctly.
29
11-2. Instruction of troubleshooting
Start
Indoor unit operates. Outdoor unit doesn't operate.
Indoor unit doesn't receive the signal from remote controller.
OPERATION INDICATOR lamp on the indoor unit is flashing on and off.
Outdoor unit operates in only Test Run operation.
Outdoor unit doesn't operate even in Test Run operation.
Indoor unit operates, when the EMERGENCY OPERATION switch is pressed.
Indoor unit doesn't operate, when the EMERGENCY OPERATION switch is pressed.
Check room temperature thermistor. Refer to "Test point diagram and voltage" on page 36.
Refer to D "Check of outdoor unit" on page 33 or 34.
Refer to B "Check of remote controller and receiver P.C. board" on page 32.
1. Check indoor / outdoor connecting wire.
2. Refer to C "Check of indoor electronic control P.C. board" on page 33.
2-time flash Cause: Indoor unit
• Trouble of room temp­ erature/ indoor coil thermistor
3-time flash Cause: Indoor unit
• Trouble of indoor fan motor
Check room temperature thermistor and indoor coil thermistor. Refer to "Test point diagram and voltage" on page 36.
Refer to A "Check of indoor fan motor" on page 32.
Outdoor unit doesn't stop even if indoor unit stop.
Refer to E "Check of outdoor unit" on page 35.
MS-C24TV only
Indoor unit operates. Outdoor unit doesn't operate normally.
Operation Indicator
· Flashing of the OPERATION INDICATOR lamp (on the left-hand side) indicates possible abnormalities.
· The OPERATION INDICATOR lamp (on the left-hand side) is lighting during normal operation.
flashing
1. troubleshooting check table
Before taking measures, make sure that the symptom reappears for accurate troubleshooting. Self check table
Abnormal
NO.
point
Indoor coil thermistor
1
Room tempera­ture ther­mistor
Indoor fan
2
motor
2-time flash
2.5-second OFF
3-time flash
Indication
2.5-second OFF
Symptom
Outdoor unit does not run.
Indoor fan motor repeats 12 sec­onds ON and 3 minutes OFF. When the indoor fan motor breaks, the fan keeps stopping.
30
Detect method
Detect Indoor coil/room tem­perature thermistor short or open circuit every 8 seconds during operation.
When rotational frequency
feedback signal is not emit during 12-second indoor fan operation
Check thermistor calibration.
Reconnect connector.
Check indoor electronic control P.C.
board.
Disconnect connector CN211 and then check connector CN121 2 - 3 to make
sure rotational frequency feedback signal of 1.5V or over exists.
Check indoor electronic control P.C. board.
Check indoor fan motor.
Reconnect connector.
Check point
P
~
BLK
R
MAIN
AUX
RED
S
C
WHT
MAIN
AUX
FUSE
BLK
RED
WHT
GRY
YLW
BRN
MAIN
AUX
BLK
RED
WHTORN
P
YLW
RED
BLU
ORN
PNK
ROTOR
INNER PROTECTOR
P
MS-C18TV - MU-C18TV -
MAIN
AUX
BLKYLW RED WHTORN
P
MAIN
MS-C24TV - MU-C24TV -
2. Trouble criterion of main parts
Part name
Room temperature thermistor(RT11)
Indoor coil thermistor(RT12)
Measure the resistance with a tester. (Part temperature 10°C ~ 30°C)
Normal
8k~ 20k
Measure the resistance between the terminals with a tester. (Coil wiring temperature –10°C ~ 40°C)
E1E1
E1E1
Check method and criterion
Abnormal
Open or short-circuit
Figure
Compressor (MC)
Indoor fan motor (MF)
C-R C-S
Normal
C18TV C24TV
0.95 ~ 1.17
1.92 ~ 2.36
0.59 ~ 0.73
1.78 ~ 2.18
Abnormal
short-circuit
Measure the resistance between the terminals with a tester. (Coil wiring temperature10°C ~ 30°C)
Abnormal
short-circuit
WHT-BLK
Motor partSensor part
BLK-RED
Normal 176 ~ 192 240 ~ 261
Measure the voltage Power ON.
BRN-YLW YLW-GRY
Normal
4.5 ~ 5.5V
(When fan revolved one time)
0V➔5V➔0V
(Approx.)
Abnormal
Remain 0V or 5V
Measure the resistance between the terminals with a tester. (Coil wiring temperature –10°C ~ 40°C)
Open or
Open or
MS-C18TV
Outdoor fan motor (MF)
Vane motor (MV)
WHT-BLK BLK-RED
BLK-YLW
Normal
C18TV C24TV
102 ~ 126
97 ~ 120
71 ~ 88
90 ~ 111
81 ~ 100
Abnormal
Open or
short-circuit
Measure the resistance between the terminals with a tester. (Part temperature10°C ~ 30°C)
Normal
358 ~ 388
Abnormal
Open or
short-circuit
31
MS-C24TV
A
Check of indoor fan motor
Indoor fan motor doesn’t operate.
No
Reconnect the lead wires.
Disconnect lead wires from connector CN211 on the indoor electronic control P.C. board. Measure resistance between lead wires No.1 and No.4 and then No.1 and No.2.
Check of remote controller and receiver P.C. board
B
Are lead wires connected?
Is resistance 0 (short circuit) or (open circuit)?
Turn OFF the power supply. Check connector CN211 visually.
Yes
Yes ( 0 or ∞ )
Repair or replace the indoor fan motor.
Is soldering point of the connector
correctly soldered?
Yes
Insert screwdriver into air outlet to rotate indoor fan motor slowly for 1 revolution or over, and measure voltage No.2(+) and No.3(-) on CN121.
No
(others)
No
Does voltage repeat 0V DC and 5V DC?
Replace the indoor electronic control P.C. board.
No
Resolder it.
Yes
Indoor unit operates by pressing the EMERGENCY OPERATION switch, but doesn’t operate with the remote controller.
wCheck if the remote controller is exclusive for this air conditioner.
Switch on the remote controller.
Is LCD display on the remote controller displayed?
Yes
Remove the batteries, then set them back and press the RESET button. Check if the unit operates with the remote controller.
Does the unit operate with the remote controller?
Yes
OK
No (not clear)
No
Replace the batteries.(Refer to page 29.)
Turn on a radio to AM and press switch on the remote controller.
Is noise heard from radio?
Yes
Are there any fluorescent lights of inverter or rapid-start type within the range of 1m?
No
Measure the voltage between receiver P.C. board connector No.2 pressed.
No
Yes
Replace the remote controller.
Re-install the unit away from lights.
Attach a filter on receiving part.
(+)
and No.1 when remote controller button is
Is the voltage approx. 4V DC?
No(5V or 0V DC)
Replace the receiver P.C. board.
32
Yes
Replace the indoor electronic control P.C. board.
Check of indoor electronic control P.C. board
Check the both “parts side”and “pattern side” of indoor electronic control P.C. board visually.
Replace the fuse.
Is fuse(F11) blown?
Be sure to check both fuse and varistor in any case.
Replace the fan motor.
Replace the indoor electronic control P.C. board.
Is winding resistance of fan motor 0 "?
Is winding resistance of vane motor 0 "?
No
Yes
Replace the vane motor.
Turn OFF the power supply.
Turn OFF the power supply.
No
Yes
Yes
Is varistor(NR11) burnt?
Replace the varistor.
Yes
Turn OFF the power supply. Remove indoor fan motor connector CN211 and vane motor connector CN151 from the indoor electronic control P.C. board and turn ON the power supply.
No
No
Does the unit operate with the remote controller? Does the OPERATION INDICATORE lamp light up by pressing the EMERGENCY OPERATION switch?
No
Yes
1.Pull out the power supply cord.
2.
Measure the resistance between CN201 1 on the indoor electronic control P.C. board and
N on the terminal
block with a tester.
Is resistance approx. 0"?
Replace the fuse (F12)
CN201
2
1
N
F12
1
3
Terminal block
Be sure to check both fresistance.
Yes
No ()
C
The unit doesn’t operate with the remote controller. Also, the OPERATION INDICATOR lamp doesn’t light up by pressing the EMERGENCY OPERATION switch.
D
Check of outdoor unit
Compressor and / or outdoor fan motor doesn’t operate.
MS-C18TV
Check the outdoor wiring, the outdoor fan motor and compressor.
Check the conti­nuity of indoor and outdoor unit connection.
Press the EMERGENCY OPERA­TION switch. 3-minute time delay works. Test run operation operates for 30 minutes.
Yes
Yes
Check the voltage to terminal block of outdoor unit. Is there 230V AC to terminal block between 2 - N ?
Check the voltage to terminal block of indoor unit. Is there 230V AC to terminal block between 2 - N ?
Replace the indoor electronic con­trol P.C. board.
Turn ON the power supply.
No
No
33
Turn ON the power supply.
Pess the EMERGENCY OPERATION switch. 3-minute time delay works. Test run operation operates for 30 minutes.
Is there 230V AC between 2-N on the outdoor terminal block ?
Yes
Compressor doesn't operate.
Yes
No
Is there 230V AC between 3-N on the outdoor terminal block?
Replace the indoor electronic control P.C. board.
Check the compressor. (Refer to page 31.)
Outdoor fan motor doesn't operate.
Yes
Is there 230V AC between 3-N on the outdoor terminal block?
Check the outdoor fan motor. (Refer to page 31.)
No
Make the connection of wiring correct.
Is there 230V AC between 3-N on the indoor terminal block?
Yes
Reconnect the continuity of indoor and outdoor unit connection.
Yes
Is there 230V AC between 1 on the compressor contactor(52C) and N on the outdoor terminal block?
Replace the compressor contactor(52C).
No
No
No
Replace the indoor electronic control P.C. board.
Is there 230V AC between 3-N on the indoor terminal block?
Yes
Reconnect the continuity of indoor and outdoor unit connection.
No
MS-C24TV
34
E
Check of outdoor unit
<MS-C24TV only>
Compressor and / or outdoor fan motor doesn’t stop.
1 Turn OFF the power supply. 2 After 30 seconds, turn ON the power supply again. 3 Operate the unit in COOL mode by pressing the
EMERGENCY OPERATION switch. 4 Operate the unit for 1 minute or more and stop it by pressing the EMERGENCY OPERATION switch again.
After 30 seconds, does compressor stop ?
Yes
OK
After 30 seconds, does outdoor fan motor stop ?
Yes
OK
Is there 230V AC between
No
3-N on the outdoor terminal block?
Is there 230V AC between 3-N on the indoor terminal block?
Replace the indoor electronic control P.C. board.
Is there 230V AC between
No
3-N on the indoor terminal block?
Replace the indoor electronic control P.C. board.
Yes
Yes
Yes
Is there 230V AC between
No
1 on the compressor contactor(52C) and N on the outdoor terminal block?
Replace the compressor contactor(52C).
No
No
Reconnect the continuity of indoor and outdoor unit connection.
Reconnect the continuity of indoor and outdoor unit connection.
Yes
No
Make the connection of wiring correct.
35
TEST POINT DIAGRAM AND VOLTAGE MS-C18TV - MS-C24TV ­Indoor electronic control P.C. board
E1E1
Varistor(NR11)
Fan motor power supply
}
Fuse 250V AC 3.15A
Power supply input
}
230V AC
Auto restart function Cut the Resistor JR06. (Refer to page 28.)
+
C144
C144
--
Room temperature thermistor(RT11)
Indoor coil thermistor(RT12)
Timer short mode point(JPG, JPS) (Refer to page 27.)
Emergency operation switch
JPG
--
JP45
+
Room temperature thermistor (RT11) Indoor coil thermistor (RT12)
}
}
12V DC
5V DC
36
12
(1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector is a terminal
with lock mechanism.
1Slide the sleeve. 2Pull the terminal while
pushing the locking lever.
1Hold the sleeve, and pull out the terminal slowly.
In case of terminal with lock mechanism, detach the terminal as shown below. There are two types ( Refer to (1) and (2)) of the terminal with lock mechanism. The terminal with no lock mechanism can be removed by pulling it out. Check the shape of the terminal and work.
<"Terminal with lock mechanism" Detaching points>
Connector
Sleeve
Locking lever
DISASSEMBLY INSTRUCTIONS
12-1. MS-C18TV - MS-C24TV -
E1E1
INDOOR UNIT
OPERATING PROCEDURE PHOTOS
1. Removing the front panel
(1) Remove the screw caps at the down of the front panel.
Remove the screws.
(2) Pull the panel down to your side slightly and unhook the
catches at the top.
2. Removing the electronic control P.C. board, the receiver P.C. board and the display P.C. board
(1) Remove the front panel. (Refer to 1) (2) Remove the electrical cover. (3) Remove the screw of the terminal cover. (4) Remove the screw of the terminal block. (5) Unhook the catch of the lamp holder. (6) Remove the receiver holder and the receiver P.C. board. (7) Remove the screw of the ground wire. (8) Disconnect all the connectors and all the lead wires on the
electronic control P.C. board.
(9) Remove the electronic control P.C. board and display P.C.
board.
37
Photo 1
Photo 2
Screw of the ground wire
Lamp holder
Front panel
Screws
Indoor coil thermistor
Display P.C. board
Receiver P.C. board
Screw of the termi­nal block
Indoor electronic control P.C. board
Receiver holder
OPERATING PROCEDURE PHOTOS
3. Removing the electrical box
(1) Remove the front panel. (Refer to 1) (2) Remove the electrical cover. (3) Disconnect the connector of the indoor coil thermistor. (4) Disconnect the motor connector (CN211 and CN121) and
the vane motor connector (CN151) on the electronic con­trol P.C. board.
(5) Remove the screw of the electrical box, remove the electri-
cal box.
4. Removing the vane motor
(1) Remove the front panel. (Refer to 1) (2) Remove the electrical box. (Refer to 3) (3) Pull out the drain hose from the nozzle assembly, remove
the nozzle assembly.
(4) Remove the screws (both upper and lower) of the vane
motor, disconnect the connector.
(5) Remove the vane motor.
5. Removing the indoor fan motor and the line flow fan
(1) Remove the front panel. (2) Remove the electrical box. (3) Unhook the catches on the both sides of the nozzle
assembly. (4) Remove the nozzle assembly. (5) Remove the screws of the bearing support. (6) Remove the screw of the heat exchanger unhook the catch. (7) Lifting the heat exchanger, remove the bearing support. (8) Loose the screw fixing the line flow fan, remove the line flow
fan. (9) Remove the screws of the motor band, remove the fan
motor.
Photo 3
Photo 4
Catch
Heat exchanger
screw
Bearing support screws
Vane motor
Screws of the vane motor
Screw of the electrical cover
Heat exchanger
38
Photo 5
Indoor fan motor
Screws of the motor band
Line flow fan Screws of the
motor band
12-2. MU-C18TV -
E1
OUTDOOR UNIT
OPERATING PROCEDURE PHOTOS
1. Removing the cabinet
(1) Remove the screws of the cabinet. (2) Hold the bottom of the cabinet on the both side to remove
the cabinet.
Photo 1
Screws of the cabinet
Service panel
Photo 2
2. Removing the electrical parts
(1) Remove the service panel and the cabinet. (2) Remove the following parts.
•Compressor capacitor (C1)
•Outdoor fan capacitor (C2)
•Terminal block (TB)
Screws of the cabinet
Photo 3
Outdoor fan capacitor(C2)
39
Compressor capacitor(C1) Terminal block(TB)
OPERATING PROCEDURE
3. Removing the outdoor fan motor
(1) Remove the cabinet. (Refer to 1) (2) Disconnect the connector remove the hooked lead wire
from the fan motor.
(3) Remove the propeller fan nut and remove the propeller fan. (4) Remove screws fixing the fan motor.
Photo 4
PHOTOS
Hook
Connector
4. Removing the compressor
(1) Remove the cabinet. (Refer to 1) (2) Remove the soundproof felt. (3) Remove the terminal cover on the compressor (4) Disconnect lead wires from the glass terminal of the com-
pressor. (5) Recover gas from the refrigerant circuit. (6) Disconnect the welded part of the discharge pipe. (7) Disconnect the welded part of the suction pipe. (8) Remove nuts fixing the compressor. (9) Remove the compressor.
NOTE
Before using a burner, reclaim gas from the pipes until the pressure gauge shows 0 kg/cm
Use the burner under the condition that gas can be recovered even when the inner pressure rises by heat.
2
(MPa).
Propeller fan
Photo 5
Compressor
Soundproof felt
Propeller fan nut
Discharge pipe
Suction pipe
40
Compressor set nuts
12-3. MU-C24TV -
E1
OUTDOOR UNIT
OPERATING PROCEDURE PHOTOS
1. Removing the cabinet
(1) Remove the screws of the cabinet. (2) Hold the bottom of the cabinet on the both side to remove
the cabinet.
Photo 1
Screws of the cabinet
Service panel
Photo 2
2. Removing the electrical parts
(1) Remove the service panel and cabinet. (2) Remove the following parts.
•Compressor capacitor (C1)
•Outdoor fan capacitor (C2)
•Compressor contactor (52C)
•Fan motor relay (X1)
•Terminal block (TB)
Screws of the cabinet
Photo 3
Outdoor fan capacitor (C2)
Contactor (52C)
Terminal block (TB)
41
Compressor capacitor (C1)
Fan motor relay (X1)
OPERATING PROCEDURE
PHOTOS
3. Removing the outdoor fan motor
(1) Remove the cabinet. (Refer to 1) (2) Disconnect the connector and remove the lead wire from
the fan motor. (3) Remove the propeller fan nut and remove the propeller fan. (4) Remove the screws fixing the fan motor. (5) Remove the fan motor.
4. Removing the compressor
(1) Remove the cabinet. (Refer to 1) (2) Remove the soundproof felt. (3) Remove the terminal cover on the compressor. (4) Disconnect lead wires from the glass terminal of the com-
pressor. (5) Recover gas from the refrigerant circuit. (6) Disconnect the welded part of the discharge pipe. (7) Disconnect the welded part of the suction pipe. (7) Remove the nuts fixing the compressor. (8) Remove the compressor.
Photo 4
Propeller fan
Photo 5
Glass terminal
Lead clamp
Hook
Propeller fan nut
Connector
NOTE
Before using a burner, reclaim gas from the pipes until the pressure gauge shows 0 kg/cm
Use the burner under the condition that gas can be recovered even when the inner pressure rises by heat.
2
(MPa).
Suction
pipe Discharge pipe
Compressor
Compressor set nuts
42
13
E02 141 970 E02 143 234 E02 138 000 E02 138 010 E02 143 067 E02 141 100 E02 516 007
1 2 3 4 5 6 7
INSTALLATION PLATE BOX (WH) FRONT PANEL ASSEMBLY(WH) GRILLE (WH) SCREW CAP (WH) AIR FILTER LAMP PANEL (WH)
Symbol
in Wiring
Diagram
Q'ty/unit
Including 4,5,7
3PCS/SET
RemarksPart No.
NO.
Part Name
1 1 1 1 3 2 1
1 1 1 1 3 2 1
MS-C18TV -
E1
(WH)
MS-C24TV -
E1
(WH)
E02 141 620 E02 138 667 E02 176 667 E02 138 666
8 9
10
INDOOR HEAT EXCHANGER UNION(LIQUID) UNION(LIQUID) UNION(GAS)
{6.35 {9.52 {15.88
1 1
1
1
1 1
PARTS LIST
MS-C18TV - (WH) MS-C24TV - (WH)
E1
E1
13-1. INDOOR UNIT
STRUCTURAL PARTS
1 2
3
4
5
SCREW CAP
13-2. INDOOR UNIT
HEAT EXCHANGER
8
Optional parts (See page 46.)
910
6
13-1. INDOOR UNIT STRUCTURAL PARTS
Part number that is circled is not shown in the illustration.
13-2. INDOOR UNIT HEAT EXCHANGER
43
MS-C18TV - (WH)
E02 141 302 E02 001 504 E02 141 509 E02 408 702 E02 143 235 E02 143 040 E02 138 307 E02 141 303 E02 138 395 E02 320 395 E02 611 375 E02 612 375 E02 138 308 E02 141 468 E02 611 452 E02 612 452 E02 141 300 E02 213 300 E02 001 505 E02 138 329 E02 336 385 E02 127 382 E02 205 381 E02 209 381 E02 138 383 E02 147 383
1 2 3 4 5 6 7 8
9
10 11
12 13
14 15
16 17 18
19
20
LINE FLOW FAN SLEEVE BEARING BEARING MOUNT DRAIN HOSE NOZZLE (WH) VANE (WH) INDOOR COIL THERMISTOR VANE MOTOR POWER SUPPLY CORD POWER SUPPLY CORD TERMINAL BLOCK TERMINAL BLOCK ROOM TEMPERATURE THERMISTOR RECEIVER P. C. BOARD ELECTRONIC CONTROL P.C. BOARD ELECTRONIC CONTROL P.C. BOARD INDOOR FAN MOTOR INDOOR FAN MOTOR FAN MOTOR RUBBER MOUNT DISPLAY P.C. BOARD VARISTOR FUSE THERMAL FUSE THERMAL FUSE SURGE ABSORBER SURGE ABSORBER
Symbol
in Wiring
Diagram
Q'ty/unit
1 1 1 1 1 1 1 1
1
1 1 1
1
1 2 1 1 1
1
1
AUTO RESTART AUTO RESTART RA4V27 ­RA4V27 ­2PCS/SET
3.15A 93: 93:
Remarks
Part No.
NO.
Part Name
RT12
MV
TB TB
RT11
MF MF
NR11
F11 F12
F12 DSAR DSAR
(WH)
MS-C24TV -
E1
1 1 1 1 1 1 1 1 1
1
1 1 1
1
2 1 1 1 1
1
(WH)
MS-C18TV -
E1
E02 611 426 E02 527 083
21 22
REMOTE CONTROLLER REMOTE CONTROLLER HOLDER
1 1
1 1
MS-C24TV - (WH)
E1
E1
13-3. INDOOR UNIT
ELECTRICAL PARTS AND FUNCTIONAL PARTS
1 2
SLEEVE BEARING
16
13
13-4. ACCESSORY P ART
AND REMOTE CONTROLLER
21 22
7
10
15
ROOM TEMPERATURE
11
THERMISTOR
12
3
4
14
5
6
INDOOR COIL THERMISTOR
9
8
13-3. INDOOR UNIT ELECTRICAL PARTS AND FUNCTIONAL PARTS
13-4. ACCESSORY PART AND REMOTE CONTROLLER
44
MU-C18TV ­MU-C24TV -
E1
E1
13-5. OUTDOOR UNIT
STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS
16
1
17
15 14
13
2
3
Part numbers that are circled are not shown in the illustration.
Part No.
NO.
E02 140 233
1
E02 141 232
2
E02 141 521
3
E02 141 501
4
E02 140 515
5
E02 139 515 E02 138 506
6
E02 624 900
7
E02 517 900 E02 217 290
8
E02 176 290 E02 624 661
9
E02 627 662
10
E02 625 662 E02 141 245
11
E02 144 301
12
E02 147 301 E02 217 630
13
E02 147 630 E02 197 374
14
E02 601 374 E02 056 374
15
E02 138 351
16
E02 082 353
17
E02 624 936
18
E02 625 936 E02 095 382
19
E02 010 342
20
E02 288 343
21
E02 229 381
22
E02 326 384
23
BACK PANEL CABINET GRILLE PROPELLER FAN MOTOR SUPPORT MOTOR SUPPORT COMPRESSOR RUBBER SET COMPRESSOR COMPRESSOR BASE BASE STOP VALVE(GAS) STOP VALVE(LIQUID) STOP VALVE(LIQUID) SERVICE PANEL OUTDOOR FAN MOTOR OUTDOOR FAN MOTOR OUTDOOR HEAT EXCHANGER OUTDOOR HEAT EXCHANGER TERMINAL BLOCK TERMINAL BLOCK TERMINAL BLOCK OUTDOOR FAN CAPACITOR COMPRESSOR CAPACITOR CAPILLARY TUBE CAPILLARY TUBE FUSE COMPRESSOR CONTACTOR FAN MOTOR RELAY THERMOSTAT CR SURGE ABSORBER
Part Name
Symbol
in Wiring
Diagram
MC MC
MF MF
TB TB
TB2
C2 C1
F
52C
X1
26F1
CR
45
4
MU-C18TV -
1 1 1 1 1
4 1
1
1 1
1 1
1
1
1 1 1
1
5
Q'ty/unit
E1
6
MU-C24TV -
7
1 1 1 1
1 4
1
1 1
1 1
1
1
1 1 1 1
1 1 1 1 1 1
8
E1
Remarks
4RUBBERS/SET PE-33VPEHT NE-47VMHHT
{15.88 { 6.35 { 9.52
RA6V50 ­RA6V60 -
3P 4P
3.0+/440V 50+/440V
{3.0o{2.0o850 {3.0o{2.0o550
250V/2A
12
11
10 9
14
Part No.
Model
MAC-1100FT
MS-C18TV -
E1
MS-C24TV -
E1
Part No.
Model
MAC-1600DF
MS-C18TV -
E1
MS-C24TV -
E1
Deodorizing filter (Gray sponge type)
Air cleaning filter (White bellows type)
OPTIONAL PARTS
14-1. AIR CLEANING FILTER
AIR CLEANING FILTER removes fine dust of 0.01 micron from air by means of static electricity.
Normal life of AIR CLEANING FILTER is 4 months. However, when it becomes dirty, replace it as soon as possible.
Clogged AIR CLEANING FILTER may reduce the air conditioner capacity or cause frost on the air outlet.
DO NOT reuse AIR CLEANING FILTER even if it is washed.
DO NOT remove or attach AIR CLEANING FILTER during unit operation.
14-2. DEODORIZING FILTER
DEODORIZING FILTER removes ammonia and hydrogen sulphide emitted from tobacco, and odor of pets.
Clean DEODORIZING FILTER every two weeks. If the filter is particularly dirty, clean the filter more often.
For cleaning, soak the filter in warm water for a while, and then wash and rinse it. Dry the filter in the shade thor-
oughly.
When the filter color is still dark even after cleaning, replace the filter with a new one. Replace the filter at least once a year.
DEODORIZING FILTER and AIR CLEANING FILTER can be attached on either side.
46
HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO100-8310, JAPAN
CC
Copyright 2000 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD. Issued in Dec. 2000. No.OB273 223 Made in Japan
New publication, effective Dec. 2000 Specifications subject to change without notice.
Loading...