Power supply
CapacitykW2.3-2.3-2.32.75-2.75-2.753.5-3.5-3.5
Electrical
data
Coeffi cient of performance (C.O.P) (Total)
Fan
Dimensions W
Weightkg2225
Special
NOTE: Test conditions are based on ISO 5151.
Cooling: Indoor Dry-bulb temperature 27°C Wet-bulb temperature 19°C
Outdoor Dry-bulb temperature 35°C Wet-bulb temperature 24°C
Indoor-Outdoor piping length: 5 m
The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions.
Since operating conditions vary according to the areas where these units are installed. The following information has been
provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198 ~ 264 V, 50 Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature : °CWB
(2) Indoor outlet air wet-bulb temperature : °CWB
(3) Outdoor intake air dry-bulb temperature : °CDB
(4) Total input: W
Indoor air wet/dry-bulb temperature difference on the left side of the chart on next page shows the difference between the
indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.
How to measure the indoor air wet/dry-bulb temperature difference
1. Attach at least 2 sets of wet and-dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets
of wet and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air
speed is high.
2. Attach at least 2 sets of wet and dry-bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of the room.
5. Press the EMERGENCY OPERATION switch once to start the EMERGENCY COOL MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
INDOOR UNITOUTDOOR UNIT
Wet and dry-bulb
thermometers
7.6
7.0
6.4
5.8
5.3
4.8
4.3
7.0
6.4
5.8
5.2
4.6
10.0
9.2
8.4
7.5
6.8
6.0
Indoor intake air WB temperature (°C)
Indoor intake air WB temperature (°C)
Wet and dry-bulb
thermometers
MS-C10VC
MS-C08VC
MU-C10VC
MU-C08VC
MS-C13VC
MU-C13VC
Outdoor intake air DB temperature (°C)
8
Outdoor intake air DB temperature (°C)
Page 9
OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
COOL operation
Both indoor and outdoor units are under the same temperature/humidity condition.
Dry-bulb temperature (°C)
20
25
Relative humidity (%)
50
60
3070
Air flow should be set at MAX.
The unit of pressure has been changed to MPa on the international system of units (SI unit system).
The conversion factor is : 1(MPa [Gauge]) =10.2(kgf/cm² [Gauge])
(kgf/cm² [Gauge])(MPa [Gauge])
0.9
9.0
0.8
8.0
0.7
7.0
0.6
6.0
Outdoor low pressure
5.0
0.5
MU-C08VCMU-C08VC
4.0
3.5
3.0
Outdoor unit current (A)
2.5
0.4
4.0
1520
50
25
60
Ambient temperature (˚C)/Ambient humidity (%)
(kgf/cm² [Gauge])(MPa [Gauge])
0.8
8.0
0.7
7.0
0.6
6.0
0.5
5.0
Outdoor low pressure
4.0
3.0
0.4
0.3
1520
MU-C10VC
50
25
60
3070 35(°C)
(%)
3070 35(°C)
(%)
2.0
1520
50
25
60
30
70
Ambient temperature (˚C)/Ambient humidity (%)
MU-C10VC
5.0
4.5
4.0
Outdoor unit current (A)
3.5
3.0
1520
50
25
60
30
70
°C
35(
(%)
35(
(%)
)
°C
)
Ambient temperature (˚C)/Ambient humidity (%)
Ambient temperature (˚C)/Ambient humidity (%)
9
Page 10
(kgf/cm² [Gauge])(MPa [Gauge])
0.8
8.0
0.7
7.0
0.6
6.0
0.5
5.0
Outdoor low pressure
0.4
4.0
MU-C13VC
6.0
5.5
5.0
Outdoor unit current (A)
4.5
MU-C13VC
0.3
3.0
1520
50
25
60
3070 35(°C)
(%)
Ambient temperature (˚C)/Ambient humidity (%)
4.0
1520
50
25
60
30
70
Ambient temperature (˚C)/Ambient humidity (%)
°C
35(
(%)
)
10
Page 11
TROUBLESHOOTING8
MU-C08VC MU-C10VC MU-C13VC
8-1. CAUTIONS ON TROUBLESHOOTING
1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, and then after
confirming the horizontal vane is closed, turn OFF the breaker and/or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the
cabinet, the top panel and the electronic control P.C. board.
3) When removing the electronic control P.C. board, hold the edge of the
board with care NOT to apply stress on the components.
4) When connecting or disconnecting the connectors, hold the housing of the
connector. DO NOT pull the lead wires.
Lead wiring
8-2. TROUBLE CRITERION OF MAIN PARTS
MU-C08VC
MU-C10VC
MU-C13VC
Housing point
Part name
Compressor (MC)
INNER
PROTECTOR
MU-C08VC
155 ± 5°C OPEN
90 ± 10°C CLOSE
MU-C10VC
160 ± 5°C OPEN
90 ± 10°C CLOSE
COMPRESSOR
THERMAL
PROTECTOR
MU-C13VC
160 ± 7°C OPEN
69 ± 10°C CLOSE
Outdoor fan
motor (MF)
INNER FUSE
126 ± 2°C OPEN
Check method and criterion
Measure the resistance between the terminals with a tester.
(Coil wiring temperature -10°C ~ 40°C)
Color of
lead wire
C-R
C-S
MU-C08VC
4.24 ~ 5.19 Ω
6.76 ~ 8.28 Ω
Normal
MU-C10VC
3.19 ~ 3.91 Ω
4.76 ~ 5.83 Ω
MU-C13VC
2.55 ~ 3.13 Ω
4.23 ~ 5.18 Ω
Measure the resistance between the terminals with a tester.
(Coil wiring temperature -10°C ~ 40°C)
Color of
lead wire
WHT-BLK
BLK-RED
MU-C08VC
222 ~ 272 Ω
245 ~ 300 Ω
Normal
MU-C10VC
222 ~ 272 Ω
245 ~ 300 Ω
MU-C13VC
150 ~ 185 Ω
199 ~ 244 Ω
Figure
MU-C08/C10VC
WHT
C
P
SR
RED
MU-C13VC
SR
RED
BLK
C
FUSE
WHT
MAIN
AUX.
BLK
P
BLK
RED
WHT
11
P
: PROTECTOR
Page 12
9
DISASSEMBLY INSTRUCTIONS
<"Terminal with locking mechanism" Detaching points>
The terminal which has the locking mechanism can be detached as shown below.
There are two types ( Refer to (1) and (2)) of the terminal with locking mechanism.
The terminal without locking mechanism can be detached by pulling it out.
Check the shape of the terminal before detaching.
(1) Slide the sleeve and check if there is a locking lever or not.
Sleeve
Slide the sleeve.
Pull the terminal while
Locking lever
pushing the locking
lever.
MU-C08VC MU-C10VC MU-C13VC
OPERATING PROCEDURE
1. Removing the cabinet
(1) Remove the screws fixing the top panel. (See Photo 1.)
(2) Remove the top panel. (See Photo 1.)
(3) Remove the screw fixing the service panel. (See Photo 2.)
(4) Pull down the service panel and remove it. (See Photo 2.)
(5) Remove the screws fixing the cabinet.
(6) Remove the cabinet.
(7)
Disconnect the power supply and indoor/outdoor connecting wire.
(8) Remove the screws fixing the back panel.
(9) Remove the back panel.
(2) The terminal with this connector has the
locking mechanism.
Hold the sleeve, and
pull out the terminal
slowly.
Connector
PHOTOS
Photo 1
Screws
of the
top panel
Screws of
the top panel
Photo 2
Screw of the
service panel
Direction to
remove
Hooks
12
Screws of
the cabinet
Service
panel
Page 13
OPERATING PROCEDUREPHOTOS
2. Removing the electrical parts
(1) Remove the service panel and the cabinet.(Refer to 1.)
(2) Remove the following parts.
•Compressor capacitor (C1)
•Outdoor fan capacitor (C2)
•Terminal block (TB)
•Compressor contactor (52C)
NOTE : When attaching compressor contactor (52C)
to relay panel, make sure that the side with
printed letters is facing upward.
Model and type name
OMRON
G7L-1A-TUB-07
xxxxxxxxxxxxx
xxxxxxxxxxxx
xxxxxxxxxxxxx
xxxxxxxxxxxxx
xxxxxxxxxxxxx
xxxxxxxxxxxxx
0
2
0
1
8
6
1
4
Photo 3
Compressor
capacitor
(C1)
Terminal
block (TB2)
Earth screw of
indoor/ outdoor
connecting wire
Outdoor fan
capacitor
(C2)
Terminal
block(TB1)
Lead clamp
Connector
Compressor
contactor
(52C)
Earth screw of
power supply
3. Removing the propeller and the outdoor fan motor
(1) Remove the cabinet. (Refer to 1.)
(2) Remove the propeller nut and the propeller.
NOTE : Loosen the propeller in the rotating direction for
removal.
When attaching the propeller, align the mark on the
propeller and the motor shaft cut section.
Set the propeller in position by using the cut on the
shaft and the mark on the propeller.
(3) Remove the lead clamps and outdoor fan motor lead wires.
(4) Remove the screws fixing the outdoor fan motor.
(5) Remove the outdoor fan motor.
Photo 4
Set screws of the
outdoor fan motor
Propeller
Propeller
nut
Set screws of the
outdoor fan motor
Outdoor fan motor lead wires
Hook
Relay panel
Outdoor
fan motor
13
Page 14
OPERATING PROCEDUREPHOTOS
4. Removing the compressor
(1) Remove the cabinet. (Refer to 1.)
(2) Remove the soundproof felt.
(3) Remove the screws fixing the relay panel.
(4) Remove the terminal cover.
(5) Pull out the lead wires from the glass terminal of the com-
pressor.
(6) Recover gas from the refrigerant circuit.
NOTE :Recover gas from the pipes until the pressure gauge
shows 0 kg/cm² (0MPa).
(7) Disconnect the welded part of the suction pipe and
discharge pipe.
(8) Remove the nuts fixing the compressor.
(9) Remove the compressor.
Photo 5
MU-C08/10VC
Discharge
pipe
Terminal
cover
Suction
pipe
Compressor
Compressor set nuts
(3 places)
Photo 6
MU-C13VC
Discharge
pipe
Terminal
cover
Suction
pipe
Compressor
14
Compressor set nuts
(3 places)
Page 15
15
Page 16
TM
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Copyright 2008 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD.
Distributed in Dec. 2008. No.OBH537 5
Made in Japan
New publication, effective Dec. 2008
Specifications subject to change without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.