Gas refrigerant
pipe joint
Refrigerant pipe (flared)
[15.88
If a front side
or both side is vacant,
an upper side of a
unit has only to be vacant 10cm.
7
Page 8
5
TRANS
NR11
HIC1
IC141
1
DSAR
GRN/YLW
WHT
WHT
LD1
REMOTE
CONTROLLER
3
3
BLU
BLU
BLU
DISPLAY
P.C.BOARD
CN
102
3
WHT
F12
2
1
CN201
1
3
3
4
F11
5
MV
151
CN
111
CN
RT11
BRN
YLW
RED
GRY
WHT
BLK
RECEIVER
P.C.BOARD
BLU
112
CN
121
CN
RT12
2
101
CN
52C
CN211
C11
1
2
4
ELECTRONIC CONTROL P.C BOARD
TB
GRN/YLW
N
3
RED
TO OUTDOOR
UNIT
CONNECTING
MF
POWER SUPPLY
CORD
1[220V
60Hz
SYMBOLNAMESYMBOLNAMESYMBOLNAME
C11INDOOR FANMFINDOOR FAN MOTORTBTERMINAL BLOCK
DSARSURGE ABSORBERMVVANE MOTORIC141HYBRID IC
F11 FUSE(3.15A)52CCOMPRESSOR CONTACTORNR11VARISTOR
F12 FUSE(93°C)RT11ROOM TEMPERATURE THERMISTOR
HIC1DC/DC CONVERTERRT12INDOOR COIL THERMISTOR
WIRING DIAGRAM
INDOOR UNIT
MS-18NN-
TO OUTDOOR
UNIT
CONNECTING
POWER SUPPLY
CORD
1[220V
60Hz
MS-24NN-
S1
TB
L
❈
BRN
2
❈
N
❈
BLU
GRN/YLW
S1
❈
MODEL MS-18NN -WIRING DIAGRAM
S1
BRN
❈
4
52C
❈
3
WHT
BLU
F12
BLU
BLU
2
1
BLU
CN201
3
1
BRN
LD1
CN
CN
CN
101
GRN/YLW
DSAR
3
RECEIVER
P.C.BOARD
REMOTE
CONTROLLER
MODEL MS-24NN -WIRING DIAGRAM
102
3
DISPLAY
P.C.BOARD
151
MV
S1
ELECTRONIC CONTROL P.C BOARD
5
HIC1
TRANS
F11
IC141
NR11
CN
112
3
CN
121
CN211
C11
4
2
1
CN
111
BRN
YLW
GRY
WHT
RED
BLK
RT11
RT12
MF
❈
❈
❈
❈
NOTES : 1.For the outdoor electric wiring refer to the outdoor unit electric wiring diagram for servicing.
8
2.Use copper conductors only. (For field wiring)
3.Symbols below indicate.
4.”❈”shows the terminals with a lock mechanism, so they cannot be removed when you pull the lead wire.
Be sure to pull the wire by pushing the locking lever (projected part) of the terminal with a finger.
/ : Terminal block : Connector
11
Side the sleeve.
22
Pull the wire while
pushing the locking lever.
Page 9
OUTDOOR UNIT
SYMBOLNAMESYMBOLNAMESYMBOLNAME
COMPRESSOROUTDOOR FAN MOTORTHERMAL REED
CAPACITOR(INNER THERMOSTAT)SWITCH
OUTDOOR FAN
CAPACITOR
COMPRESSORFAN MOTORSURGE
(INNER THERMOSTAT)RELAYABSORBER
C1MF26F1C2TB
52CMCX1
CR
TERMINAL BLOCK
CONTACTOR
SYMBOLNAMESYMBOLNAME
COMPRESSORFAN MOTOR
CAPACITOR(INNER THERMOSTAT)
FAN MOTOR
CAPACITOR
COMPRESSOR
(INNER THERMOSTAT)
C1MFC2TBMC
TERMINAL BLOCK
MU-18NN-
S1
MODEL MU-18NN -WIRING DIAGRAM
S1
TB
GRN/YLW
TO INDOOR
UNIT
CONNECTING
MU-24NN-
TO INDOOR
UNIT
CONNECTING
S1
TB
2
N
3
❈
2
N
❈
MODEL MU-24NN -WIRING DIAGRAM
WHT
2
S1
52C
1
BLK
WHT
52C
YLW
❈
YLW
4
6
3
52C
5
C2
❈
BLK
RED
❈
GRN/YLW
GRY
GRY
b
a
RED
52C
CR
5
GRY
78
X1
3
6
X1
1
26F1
BLK
RED
ORN
WHT
BLK
YLW
1
2
3
4
5
6
WHT
C1
C2
RED
ORN
WHT
BLK
YLW
RED
BLK
MF
S
BLK
WHT
ORN
RED
MC
BLK
4
WHT
3
ORN
2
RED
1
C
MC
RED
R
MF
C
RS
BLK
C1
NOTES : 1.Use copper conductors only. (For field wiring)
2.”❈”shows the terminals with a lock mechanism.so they cannot
be removed when you pull the lead wire.
Be sure to pull the wire by pushing the locking
lever (projected part) of the terminal with a finger.
ModelOutdoor unit prechargedRefrigerant piping length (one way)
(up to 7m)7m10m15m
MS-18NN -1650
MS-24NN -2150
0
45
120
S1
S1
Additional piping
ModelMax. length : m
AGasLiquidIndoor unitOutdoor unit
MS-18NN -15
[6.35
MS-24NN -
[9.52
15
[15.88
0.43
0
S1
S1
Piping size O.D : mm
Length of connecting pipe : m
MAX. REFRIGERANT PIPING LENGTH
MAX. HEIGHT DIFFERENCE
ADDITIONAL REFRIGERANT CHARGE(R-22 : g)
Note : Calculation : Xg=15g/m✕(A-7)m
11
Page 12
EVACUATION PROCEDURES
Connect the refrigerant pipes (both the liquid and gas pipes)
between the indoor and the outdoor units.
Remove the service port cap of the stop valve on the side of the outdoor unit gas pipe (The stop valve will not
work in it initial state fresh out of the factory (totally closed with cap on).)
Connect the gage manifold valve and the vacuum pump to
the service port of the stop valve on the gas pipe side of the
outdoor unit.
Run the vacuum pump(Vacuumize for more than 15 minutes.)
and at this time confirm that the pressure gage shows -0.1
Mpa ( -76cm Hg).
Check the vacuum with the gage manifold valve, then close
the gage manifold valve, and stop the vacuum pump.
Leave it as is for one or two minutes. Make sure the pointer
gage manifold valve remains in the same position.
Remove the gage manifold valve quickly from the service port of the stop valve.
After refrigerant pipes are connected and evacuated, fully open all stop valves on gas and liquid pipe sides.
Operating without fully opening lowers the performance and causes trouble.
12
Pipe length :
7m maximum
No gas charge
is needed
Tighten the cap to the service port to obtain the initial status
Retighten the cap
Leak test
Pipe length
exceeding 7m
Charge the prescribed
amount of gas
Page 13
7
PERFORMANCE CURVES
MS-18NN- MS-24NN-
The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions.
Since operating conditions vary according to the areas where these units are installed. The following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
S1S1
(1) GUARANTEED VOLTAGE
Rated voltage : ±10% (198 ~ 242V ) 60Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature :°CWB
(2) Indoor discharge air wet-bulb temperature :°CWB
(3) Outdoor intake air dry-bulb temperature :°CDB
(4) Total input:W
Indoor air wet-bulb temperature difference on the left side of the chart on next page shows the difference between the
indoor intake air wet-bulb temperature and the indoor discharge air wet-bulb temperature for your reference at service.
How to measure the indoor air wet-bulb temperature difference
1. Attach at least 2 sets of wet-and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets
of wet-and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air
speed is high.
2. Attach at least 2 sets of dry-bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY ON/OFF button to start the EMERGENCY operation.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
}
Cooling
INDOOR UNIT
OUTDOOR UNIT
13
Page 14
OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
COOL operation
① Both indoor and outdoor unit are under the same temperature/humidity condition.
Dry-bulb temperature(;)
20
25
3070
➁ Air flow should be set at MAX.
Relative humidity(%)
MU-18NN -
Outdoor low pressure(kg/cm2)Outdoor unit current(A)
Ambient temperature(˚C)
Ambient humidity(%)
MU-18NN -
50
60
S1
Outdoor low pressure(kg/cm2)
S1
MU-24NN -
Ambient temperature(˚C)
Ambient humidity(%)
MU-24NN -
S1
S1
Ambient temperature(˚C)
Ambient humidity(%)
14
Outdoor unit current(A)
Ambient temperature(˚C)
Ambient humidity(%)
Page 15
8
Operation Indicator
Initial room temperaturemode
COOL mode of
I FEEL CONTROL
DRY mode of
"I FEEL CONTROL"
more than 25°C
13°C to 25°C
MICROPROCESSOR CONTROL
Wireless remote controller
INDOOR UNIT DISPLAY SECTION
MS-18NN MS-24NN -
Once the controls are set, the same operation mode can be
repeated by simply turning the OPERATE/STOP button ON.
Indoor unit receives the signal with a beep tone.
When the system turns off, 3-minute time delay will operate to
protect system from overload and compressor will not restart
for 3 minutes.
1. “I FEEL CONTROL”OPERATION
S1
S1
(1) Press OPERATE/STOP button on the remote con-
troller. OPERATION INDICATOR LAMP of the
indoor unit will turn on with a beep tone.
(2) Press OPERATION SELECT button to set “I FEEL
CONTROL” Then a beep tone is heard.
(3) The operation mode is determined by the initial
room temperature at start-up of the operation.
● Once the mode is fixed, the mode will not change
by room temperature afterwards.
● Under the ON-TIMER operation, the mode is determined
according to the room temperature as the operation
starts.
● When the system is stopped with the
OPERATE/STOP button on the remote controller,
and restarted within 2 hours in “I FEEL CONTROL”
mode, the system operates in previous mode
automatically regardless of the room temperature.
Example
Previous operation
COOL mode of
“I FEEL CONTROL”
or COOL mode.
● When the system is restarted after 2 hours, the operation
mode is determined by the initial room temperature at
start-up of the operation.
Example
Previous operation
COOL mode of “I
FEEL CONTROL”
or COOL mode.
Restart
COOL mode of “I
FEEL CONTROL”
Restart
COOL or DRY mode of
“I FEEL CONTROL” that
determined by initial
room temperature startup of the operation.
15
Page 16
ModelInitial room temperatureInitial set temperature
26°C or more24°C
Initial room temperature
minus 2°C
DRY mode ofInitial room temperature
"I FELL CONTROL"minus 2°C
COOL mode of
"I FEEL CONTROL"
26°C or less
13°C to 25°C
(4) The initial set temperature is decided by the initial room temperature.
❈ 1
❈1 After the system restarts by the remote controller, the system operates with the previous set temperature regardless of
the initial set temperature.
The set temperature is calculated by the previous set temperature.
(5) TEMPERATURES buttons
In “I FEEL CONTROL” mode, set temperature is decided by the microprocessor based on the room temperature.
In addition, set temperature is controlled by TOO WARM or TOO COOL buttons when you feel too cool or too warm.
Pressing the TOO WARM or TOO COOL button emits a beep tone.
● Fuzzy control
When the TOO COOL or TOO WARM button is pressed, the microprocessor changes the set temperature, considering
the room temperature, the frequency of pressing TOO COOL or TOO WARM button and the user’s preference to heat or
cold. So this is called “Fuzzy control”, and works only in “I FEEL CONTROL” mode.
In DRY mode of “I FEEL CONTROL”, the set temperature doesn’t change.
▲ TOO
COOL… To raise the set temperature 1~2 degrees(°C)
▼ TOO
WARM … To lower the set temperature 1~2 degrees(°C)
16
Page 17
— COOL mode of “I FEEL CONTROL” —
ON
Compressor and
OFF
ON
OFF
outdoor fan motor
Indoor fan motor
ON
Run continuously in cooling mode
NOTE : Coil frost prevention during COOL mode of “I FEEL CONTROL”
There are two types of controls in coil frost prevention.
① Temperature control
When the indoor coil thermistor RT12 reads -1°C or below, the coil frost prevention mode starts immediately.
However the coil frost prevention will not work for 5 minutes after the compressor starts.
The compressor stops and the indoor fan operates at the set speed for 5 minutes.
After that, if RT12 still reads below -1°C this mode prolonged until the RT12 reads over -1°C .
② Time control
When the three conditions below have been satisfied for 1 hour and 45 minutes, compressor stops for 3 minutes.
a. Compressor has been continuously operating.
b. Indoor fan speed is Lo or Me.
c. Room temperature is below 26°C.
When compressor turns off half way, the accumulated time is cancelled.
When compressor turns on again, time counting starts from the beginning.
When the indoor fan speed becomes Hi or the room temperature exceeds 26°C, time counting stops temporarily.
After, when the above conditions are satisfied again, time counting restarts.
The indoor fan operates at set speed.
● Indoor fan operates at the set speed by FAN CONTROL
Followings are the fan speed in AUTO.
Room temperature minus set temperature : more than 2 ~ 4 degrees (°C)··············Hi
Room temperature minus set temperature : 1 ~ 4 degrees (°C) ·····························Me
Room temperature minus set temperature : less than 1 ~1.5 degrees (°C)·············Lo
—DRY mode of “I FEEL CONTROL”—
The system for dry operation uses the same refrigerant circuit as the cooling circuit.
The compressor and the indoor fan are controlled by the temperature and the microprocessor.
By such controls, indoor flow amounts will be reduced in order to lower humidity without much room temperature
decrease.
The operation of the compressor and indoor fan is as follows.
1. When the room temperature is 23°C or over:
Compressor operates by temperature control and time control.
① Set temperature is controlled to fall 2°C as initial set temperature.
② When the thermostat is ON, the compressor repeats 8 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
Indoor fan and outdoor fan operate in the same cycle as the compressor.
1 deg.
1.5 deg.
2 deg.
4 deg.
2. When the room temperature is under 23°C.
When the thermostat is ON, the compressor repeats 2 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
17
Page 18
Operation time chart
Example
Thermostat
OFF
1st ON
ON
OFF
ON
Indoor fan
Outdoor fan
compressor
NOTE ● Coil frost prevention during DRY mode of “I FEEL CONTROL”
OFF
ON
OFF
8 min.
The operation is same as coil frost prevention during COOL mode of “I FEEL CONTROL” excepting the
indoor fan is OFF.
● Coil frost becomes the fan speed Lo during the indoor fan is OFF.
(Because the coil frost prevention is priority.)
2. COOL OPERATION
(1) Press OPERATE/STOP button.
OPERATION INDICATOR of the indoor unit
turns on with a beep tone.
(2) Select COOL mode.
(3) Set the TEMPERATURES button.
(TOO WARM or TOO COOL button)
The setting range is 16 ~ 31°C
✻ Indoor fan continues to operate regardless
of thermostat’s OFF-ON
✻ Coil frost prevention is same as COOL
mode of “I FEEL CONTROL”
3. DRY OPERATION
(1) Press OPERATE/STOP button.
OPERATION INDICATOR of the indoor unit
turns on with a beep tone.
(2) Select DRY mode.
(3) The microprocessor reads the room temper-
ature and determines the set temperature.
Set temperature is as shown in the right
chart.
Thermostat (SET TEMP.)is not work.
The other operations are same as DRY
mode of “I FEEL CONTROL”.
(4) DRY operation will not work when the room
temperature is 13°C or below.
(5) When DRY operation works, the fan speed is
lower than cool operation.
OFF
OFF
ON
ON
3 min.
OFF
OFF
4 min.
ON
ON
1 min.
18
Page 19
4.FAN OPERATION
(1)Press OPERATE/STOP button.
(2)Select FAN mode.
(3)Select the desired fan speed.When AUTO,it becomes LO.(Only DRY operation)
Only indoor fan operates.Outdoor unit does not operate.
5. FAN MOTOR CONTROL
(1) Rotational frequency feedback control
The indoor fan motor is equipped with a rotational frequency sensor, and outputs signal to the microprocessor to feedback
the rotational frequency. Comparing the current rotational frequency with the target rotational frequency (Hi,Me,Lo) the
microprocessor controls IC141 and adjusts fan motor electric current to make the current rotational frequency close to the
target rotational frequency. With this control, when the fan speed is switched, the rotational frequency changes more
smoothly than before.
(2) Fan motor lock-up protection
When the rotational frequency feedback signal is not output for 12 seconds, (or when the microprocessor cannot detect the
signal for 12 seconds) the fan motor is regarded locked-up. Then the electric current to the fan motor is shut off. 3 minutes
later, the electric current is applied to the fan motor again. During the fan motor lock-up, the operation indicator flashes to
show the fan motor abnormality. (See page 25.)
6. AUTO VANE OPERATION
(1) Vane motor drive
MS series is equipped with a stepping motor for the vane. The rotating direction, speed, and angle of the motor are controlled by plus signals (approx. 12V) transmitted from indoor microprocessor.
(2) The auto vane angle changes as follows by pressing the VANE CONTROL button.
19
Page 20
(3) Positioning
The vane is once pressed to the vane stopper below to confirm the standard position and then set to the desired angle.
The positioning is decided as follows.
(a) When the operate button is pushed. (POWER ON)
(b) When th stop button is pushed. (POWER OFF)
(c) When the vane control change AUTO to MANUAL.
(d) When the SWING is finished.
(e) When the test run starts.
(f ) When the power supply is ON.
(4) VANE AUTO mode
In VANE AUTO mode, the microprocessor automatically determines the vane angle and operation to make the optimum
room-temperature distribution.
① In COOL and DRY operation
Vane angle is fixed to Horizontal.
➁ In FAN operation
Vane angle is fixed to Downward.
(5) Dew prevention
During COOL or DRY operation with the vane angle at Downward when the compressor cumulative operation the exceeds
1 hour, the vane angle automatically changes to Horizontal for dew prevention.
(6) SWING MODE
By pressing the SWING button, vane swings vertically. The remote controller displays SWING mode is cancelled when the
SWING button is pressed again or the operation stops or changes to other mode or VANE button is pressed.
7. SLEEP MODE
• When the SLEEP button is pressed, the indoor fan speed drops and the air flow sound from the indoor unit is decrecsed.
• The indications of the remote controller are “” and “
• When the FAN SPEED CONTROLbutton is pressed during the SLEEP mode operation, the SLEEP made is released.
AUTO
”.
20
Page 21
STARTSTOP
STARTSTOP
8. TIMER OPERATION
1. How to set the timer.
(1) Press OPERATE/STOP (ON/OFF) button to start the air conditioner.
(2) Check that the current time is set correctly.
NOTE : Timer operation will not work without setting the current time. Initially “AM0:00” blinks at the current time display
of TIME MONITOR so set the current time, correctly with CLOCK SET button.
(3) Press ON or OFF TIMER button to select the operation.
(4) Press HR. and MIN. button to set the timer. Time setting is in 10-minute units.
HR. and MIN, button will work when ON or OFF TIMER button is flashing.
These marks disappear in 1minute.
When setting the ON timer, check that OPERATION INDICATOR of the indoor unit lights.
NOTE1 : Be sure to place the remote controller at the position where its signal can reach the air conditioner even during
TIMER operation, or the set time may deviate within the range of about 10 minutes.
NOTE2 : Reset the timer in the following cases, or the set time may deviate and other malfunctions may occur.
● A power failure occurs.
● The circuit breaker functions.
2. CANCEL
Timer setting can be cancelled with the ON or OFF TIMER button.
To cancel the ON timer, press the ON-TIMER button.
To cancel the OFF timer, press the OFF-TIMER button.
Timer is cancelled and the display of set time disappears.
PROGRAM TIMER
● The OFF timer and ON timer can be used in combination.
● ”” display shows the order of the OFF timer and ON timer operation order.
(Example 1) The current time is 8:00 PM.
The unit turns off at 11:00 PM, and on at 6:00 AM.
(Example 2) The current time is 11:00 AM.
The unit turns on at 5:00 PM, and off at 9:00 PM.
21
Page 22
9. EMERGENCY-TEST OPERATION
When the remote controller is missing, has failed or the batteries run down, press the Emergency operation switch button
on the front of the indoor unit. The unit will start and the Operation lamp will light.
The first 30 minutes of operation will be the test run operation. This operation is for servicing. The indoor fan runs at high
speed and the system is in continuous operation. The thermostat is ON and the timer is reset to normal.
After 30 minutes of test run operation the system shifts to emergency run operation with a set temperature of 24°C in
cooling.
The fan shifts to MED speed.
This operation continues until the Emergency operation switch is pressed or a button on the remote controller is pressed,
then normal operation will start.
The coil frost prevention circuit operates in this mode.
In the test run or emergency operation, auto vane operates in AUTO mode with the set temperature 24°C.
NOTE : Do not press the Emergency operation switch during normal operation.
22
Page 23
9
SERVICE FUNCTIONS
9-1. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS on the electronic control P.C. board.
The time will be shortened as follows.
3-minute time delay : 3-minute → 3-second.
AUTO START : 1 hour → 1-minute
AUTO STOP : 1 hour → 1-minute
Short the connector during the timer mode.
}
9-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room. In this case, to operate
each indoor unit individually by each remote controller, P.C. boards of remote controller must be modified
according to the indoor unit number.
(1) How to modify the remote controller P.C. board
Remove batteries before modification.
The board has a print as shown below;
NOTE : Fore remodeling, take out the batteries at first.
After finish remodeling, put back the batteries then push the RESET-button.
The P.C. board has the print “J1” and “J2”. Jumper wires are mounted to each “J1” and “J2”.Cut “J1” and “J2”
according to the number of indoor unit as shown in Table 1.
After modification, push the RESET. button near the MIN-button on the remote controller.
Table1.
1 unit operation
No.1 unit
No.2 unit
No.3 unit
No.4 unit
NOTE : At power supply failure or installation, indoor unit deletes the memory about remote controller. When
the power supply is turned on and indoor unit receives the first signals from the remote controller, the
remote controller number is designated as the indoor unit number. Therefore at and after the second
time indoor unit accepts the remote controller of the initial setting number.
At setting - error, turn the power supply off to cancel the individual operation and then turn the power
supply on to restart the setting.
No modification
2 unit operation
Same as at left
Cut J1
3 unit operation
Same as at left
Same as at left
Cut J2
4 unit operation
Same as at left
Same as at left
Same as at left
Cut both J1 and J2
23
Page 24
10TROUBLESHOOTING
MS-18NN MS-24NN -
S1
S1
10-1 Cautions on troubleshooting
10-1-1 Before troubleshooting, check the followings:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
10-1-2 Take care the followings during servicing.
1) Be sure to unplug the power cord before removing the front panel, the cabinet, the top panel, and the P.C. boards.
2) When removing the P.C. board, hold the edge of the board with care NOT to apply stress on the components.
3) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
10-1-3 Troubleshooting procedure
1) First, check if the OPERATION INDICATION LAMP on the indoor unit is flashing to indicate an abnormality. To make
sure, check the abnormality indication for 2 or 3 times before starting service work.
2) If the P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the components for
bursting and discoloration.
3) When troubleshooting, refer to the flow chart and the check table on page 25.
10-14 How to replace batteries
Weak batteries may cause the remote controller malfunction.
In this case, the remote controller can not be repaired only by the battery replacement. To operate the remote con-
troller normally, discharge the remote controller in the following order.
This remote controller has the reset button. After refilling new batteries, press the reset button with tip end of ball point
pen or the like, and then use the remote controller.
24
Page 25
10-2 Instruction of troubleshooting
Operation Indicator
Start
Indoor unit operates. Outdoor unit
doesn’t operate.
Outdoor unit
operates in
only Test
Run mode.
Check room
temperature
thermistor.
Outdoor unit
doesn’t operate even in
Test Run
mode.
Refer to
D
“Check of
outdoor unit”
on page 28.
Indoor unit
dosen’t receive
the signal from
remote
controller.
Refer to
B
”Check of
receiver P.C.
board” on page
27.
Indoor unit operation
monitor lamp is flashing
Indoor unit doesn’t
receive the signal from
remote controller.
Also, operation monitor
lamp doesn’t flash, when
the emergency operation
2-time flash
switch is pressed.
2.5-second OFF
3-time flash
Refer to “Check of
indoor electric control
P.C. board” on page 28.
2.5-second OFF
Cause:Indoor unit
2-time-Room temperature/Indoor coil thermistor trouble.
3-times-Indoor fan motor trouble
Check indoor coil
thermistor. Refer
to“Test point dia-
Refer to
A
“Check of indoor
fan motor” on
page 27.
Check room temperature.
Refer to“Test point diagram and voltage” on
page 29.
gram and voltage”
on page 29.
C
10-2-1 troubleshooting check table
❈ Before taking measures make sure that the symptom reappears, for accurate troubleshooting.
Self check table
Abnormal
NO.
point
Indoor coil
thermistor
1
Room
temperature thermistor
Indoor fan
2
motor
2-time flash
2.5-second OFF
3-time flash
Indication
2.5-second OFF
Symptom
Outdoor unit
does not run.
Indoor fan
repeats 12 seconds ON and 3
minutes OFF.
When the indoor
fan breaks, the
fan keeps stopping.
Detect method
Detects Indoor coil/room temperature thermistor short or
open circuit every 2 seconds
during operation.
When rotational frequency
feedback pulse signal is not
emit during 12-second indoor
fan operation
Repair
● Check thermistor calibration
● Reconnect connector
● Check indoor borad
● Disconnect connector CN211 and then
check connector CN121 - to make
sure rotational frequency feedback signal
of on 1.5V or over exists.
● Check indoor electronic control P.C.
board.
● Check indoor fan motor
● Reconnect conector
2
3
25
Page 26
P
P
MS-18NN-
MS-24NN-
,
S1S1
10-2-2 Trouble criterion of main parts
Part name
Check method and criterion
Figure
Room
temperature
thermistor
Indoor coil
thermistor
Compressor
Indoor fan
motor
Measure the resistance with a tester.
(Part temperature 10°C ~ 30°C)
Normal
8kΩ ~ 20kΩ
Opened or short-circuited
Abnormal
Measure the resistance between the terminals with a tester.
(Coil wiring temperature-10°C ~ 40°C)
Normal
C-R
C-S
18NN
0.88~1.08Ω
1.73~2.12Ω
24NN
0.73~0.90Ω
1.61~1.97Ω
Measure the resistance between the terminals with a tester.
(Coil wiring temperature10°C ~ 30°C)
Normal
Motor part
BLK-RED
116 ~ 126
159 ~ 172Ω
ΩWHT-BLK
Measure the voltage Power ON.
Abnormal
Opened or
short-circuited
Abnormal
Opened or
short-circuited
Outdoor fan
motor
Vane motor
Normal
Sensor part
BRN-YLW
YLW-GRY
4.5 ~ 5.5V
(When fan revolved one time)
0V➔5V➔0V
(Approx.)
Remain 0V or 5V
Measure the resistance between the terminals with a tester.
(Coil wiring temperature-10°C ~ 40°C)
Normal
WHT-BLK
BLK-RED
BLK-YLW
18NN
102 ~ 126Ω
98 ~ 120Ω
-
24NN
71.5 ~ 87.5Ω
90.1 ~ 110.2Ω
80.8 ~ 99.4Ω
Measure the resistance between the terminals with a tester.
(Part temperature10°C ~ 30°C)
Normal
358 ~ 387Ω
Abnormal
Opened or short-circuited
Abnormal
18NN
Abnormal
24NN
Opened or
short-circuited
26
Page 27
A
Check of indoor fan motor
Inodoor fan does not operate.
NO
Are lead wires connected?
Reconnect lead wires
Disconnect lead wires from connector CN211 on indoor control P.C. board.
Measure resistance between lead wires No.1 and No.4 and then No.3 and No.4.
Check of receiver P.C. board
B
Turn OFF power supply.
Check connector CN211 visually.
Yes
Is resistance 0 (short circuit) or ∞ (open circuit)?
Yes ( 0 or ∞ )
Repair indoor fan motor.
Is soldered point normal?
Yes
Replace indoor electronic control
P.C. board.
No
(others)
NO
Resolder it.
Indoor unit operates by pressing the emergency ON/OFF switch, but does not operate with the remote controller.
Check the model name of remote
controller.
Is.LCD display on remote controller visible?
Yes
Remove batteries and then set them back.
Check if the unit operates with remote
controller.
Does the unit operate with remote
controller?
Yes
OK
No
(not clear)
No
Replace batteries.(see page 24.)
Turn a radio to AM and press switch on
remote controller.
Is noise heard from radio?
Yes
Are there any fluorescent lights of
inverter or rapid-start type within
the range of 1m?
No
Measure the voltage between receiver board connector No.2
when remote controller button is pressed.
No
Yes
Replace remote controller
● Re-install the unit away from lights.
● Attach a filter on receiving part.
(+)
and No.1
Is the voltage approx. 4V DC?
No(5V or OV DC)
Replace the receiver
Yes
Replace indoor electronic control
P.C. board.
27
Page 28
Check of indoor electronic control P.C. board
C
The unit doesn’t operate with
the remote controller.
Replace fuse.
Also, the operation indicator
doesn’t light up by pressing the
emergency ON/OFF switch.
Is fuse(F11)blown?
Check both “parts side”and “pattern
side ✻ of indoor electronic control P.C.
board visually
Yes
No
1.Pull out power supply
cord.
2.Measure resistance
between CN201
1
on electronic control P.C. board and
on the terminal block
with a tester.
Trouble of indoor electronic control P.C. board.
Yes
Is there resistance?
(Approx.0Ω)
N
No
Trouble of fuse(F12)
Check of outdoor unit
D
Is varistor(NR11)burnt?
Yes
Replace varistor.
No
Compressor and outdoor fan do not operate.(Only indoor fan operates.)
Yes
<MS-18NN>
Start
Press EMERGENCY ON/OFF
button. 3-minute time delay
works. Test mode operates
for 30 minutes.
Check voltage to terminal
block of outdoor unit. Is there
AC220V to terminal block
2
between - ?
N
<MS-24NN>
Start
Press EMERGENCY ON/OFF
button. 3-minute time delay
works. Test mode operates
for 30 minutes.
Check voltage to terminal
block of outdoor unit. Is there
AC220V to terminal block
2
between - ?
N
No
①
➂
CN201
Check the outdoor wiring.
L
N
Terminal
block
Check outdoor unit fan motor
and compressor.
Yes
Check continuity of indoor
and outdoor unit connection.
Check voltage to terminal
block of indoor unit. Is there
AC220V to terminal block
between - ?
Replace indoor electronic
control P.C. board.
No
2
N
No
28
Yes
Check voltage to terminal
block of outdoor unit. Is there
AC220V to terminal block
3
between - ?
Check the outdoor wiring and
N
YesYes
conductor relay.
Check voltage to terminal
No
block of indoor unit. Is there
AC220V to terminal block
3
between - ?
Check the indoor/outdoor
wirining.
Replace the
No
indoor
electronic
N
P.C.board
Page 29
TEST POINT DIAGRAM AND VOLTAGE
MS-18NN MS-24NN Indoor electronic control P.C. board
S1
S1
Fan motor power supply
}
Fuse AC250V 3.15A
Power supply input AC220V
}
Room temperature thermistor (RT11)
Indoor coil thermistor (RT12)
+
DC5V
}
--
Indoor coil thermistor (RT12)
Room temperaure thermistor (RT11)
Time short mode point
Emergency switch
--
DC12V
}
+
29
Page 30
11
DISASSEMBLY INSTRUCTIONS
NOTE:
❈ On the wiring diagram shows the terminals with a lock
mechanism, so it cannot be removed when you pull the
lead wire. Be sure to pull the wire by pushing the locking
lever (projected part) of the terminal with a finger.
11-1 MS-18NN -, MS-24NN -INDOOR UNIT
S1S1
OPERATING PROCEDUREPHOTOS
1. Removing the front panel
(1) Remove the screw caps at the bottom of the front panel.
(2) Remove the screws.
(3) Pull the bottom of the front panel to your side slightly and
unhook the catches at the top of the front panel.
(4) Remove the front panel.
2. Removing the electronic control P.C. board
(1) Remove the front panel. (Refer to 1)
(2) Remove the screw, remove the terminal cover.
(3) Remove the elect cover.
(4) Remove the screw of terminal block.
(5) Unhook the catch of the lamp holder.
(6) Remove the receiver holder.
(7) Disconnect the connector and remove the earth and the
indoor coil thermistor.
(8) Remove the electronic P.C. board.
Photo 1
Photo 2
Earth
Front panel
Screws
Indoor coil thermistor
30
Screw
Terminal
block
screw
Electrical
P.C. board
Page 31
OPERATING PROCEDUREPHOTOS
3. Removing the indoor fan motor and the line flow fan
(1) Remove the front panel.
(2) Remove the electrical box.
(3) Unhook the catch on the both sides of the nozzle assem-
bly.
(4) Remove the nozzle assembly.
(5) Remove the screws of the bearing support.
(6) Remove the screw of the heat exchanger unhook the
catch.
(7) Lifting the heat exchanger, remove the bearing support.
(8) Remove the motor support.
(9) Loose the screw fixing the line flow fan, remove the line
flow fan.
(10) Remove the screws of the side cover, remove the fan
motor.
Photo 3
Catch
Heat exchanger
screw
Bearing support
screws
Photo 4
Heat exchanger
Indoor fan motor
Line flow fanMotor band
Fan
motor
screws
31
Page 32
11-2 MU-18NN -,MU-24NN -OUTDOOR UNIT
S1S1
OPERATING PROCEDUREPHOTOS
1. Removing the cabinet
(1) Remove the screws of the cabinet.
(2) Hold the bottom of the cabinet on the both side to remove
the cabinet.
Photo 1
Photo 2
Screws
2. Removing the electrical parts
(1) Remove the cabinet.(Refer to 1)
(2) Remove the following parts.
•Compressor capacitor (C1)
•Outdoor fan capacitor (C2)
•Terminal block
•Compressor contactor(52C)(MU-24)
•Surege absorber (CR)(MU-24)
•Fan motor relay (X1)(MU-24)
•Thermal reed switch (26F1)(MU-24)
Screws
Service
panel
Photo 3
32
Compressor capacitor
Page 33
OPERATING PROCEDURE
3. Removing the outdoor fan motor
(1) Remove the cabinet. (Refer to 1)
(2) Unconnect the connector remove the hooked lead wire
from the fan motor.
(3) Remove the propeller nut and remove the propeller.
(4) Remove screws fixing the fan motor.
Photo 4
PHOTOS
Hook
Connector
4. Removing the compressor
(1) Remove the cabinet. (Refer to 1)
(2) Remove the soundproof felt.
(3) Remove the terminal cover on the compressor
(4) Remove the electrical assembly.(Refer to 2)
(5) Release gas from the refrigerant circuit.
(6) Disconnect the welded part of the discharge pipe
(7) Disconnect the welded part of the suction pipe.
(8) Remove nuts fixing the compressor.
(9) Remove the compressor.