SUBMITTAL DATA: MSZ-GL12NA-U1
M-SERIES
Job Name:
System Reference: Date:
12,000 BTU/H WALL-MOUNTED INDOOR UNIT FOR MXZ-C MULTI-ZONE HEAT-PUMP SYSTEMS
Indoor Unit: MSZ-GL12NA-U1
Wireless Remote Controller
ACCESSORIES:
Indoor Unit
□ Condensate Pump (BlueDiamond X87-711/721; 115/230V)
□ Condensate Pump (Sauermann SI30-115/230; 115/230V)
□ Anti-Allergy Enzyme Filter (MAC-408FT-E)
□ Platinum Catalyst Deodorizing Filter (MAC-308FT-E)
□ Drain Pan Level Sensor (DPLS2)
Controls
□ Wireless Controller (MHK1)
□ Wired Remote Controller PAR-31MAA (Requires MAC-333IF-E)
□ Wireless Interface for kumo cloud™ (PAC-WHS01WF-E)
□ Thermostat Interface (PAC-US444CN-1)
SPECIFICATIONS:
Rated Capacity*
Cooling
Heating at 47º F
Rating Conditions per AHRI Standard:
1
Cooling | Indoor: 80º F(27º C)DB / 67º F(19º C)WB; Outdoor: 95º F(35º C)DB / 75º F(24º C)WB
2
Heating at 47ºF | Indoor: 70º F (21º C)DB / 60º F (16º C)WB; Outdoor: 47º F (8º C)DB / 43º F (6º C)WB
For data on specic indoor units (all ducted, all non-ducted, and both ducted and non-ducted)
combinations, see the MXZ Technical and Service Manual.
Applications should be restricted to comfort cooling only; equipment cooling applications are not
recommended for low ambient temperature conditions.
Electrical Power
Requirements
Minimum Circuit
Ampacity (MCA)
Blower Motor (ECM)
Blower Motor Output
Field Drainpipe Size O.D.
Airow Rate (Quiet - Lo - Med - Hi - Super Hi)
Cooling
Heating DRY
1
Btu/h / W
2
Btu/h / W
12,000
14,400
208 / 230V, 1-Phase, 60 Hz
DRY
WET
A
F.L.A.
W
In.(mm)
CFM
1
0.76
30
5/8 (15)
145-170-237-321-399
109-134-201-286-364
145-170-237-321-406
Sound Pressure Level (Quiet - Lo - Med - Hi - Super Hi)
Cooling
Heating
External Dimensions
(H x W x D)
Net Weight
External Finish
dB(A)
In.(mm)
Lbs.(kg)
Munsell 1.0Y 9.2 / 0.2
19-22-30-37-45
19-22-30-37-43
11-5/8 x 31-7/16 x 9-1/8
(295 x 798 x 232)
22 (10)
Refrigerant Piping (Flared)
Liquid (High Pressure)
Gas (Low Pressure)
In.(mm)
1/4 (6.35)
3/8 (9.52)
Specications are subject to change without notice. © 2016 Mitsubishi Electric US, Inc.
DIMENSIONS: MSZ-GL12NA-U1
Unit: inch
4
OUTLINES AND DIMENSIONS
MSZ-GL06NA MSZ-GL09NA MSZ-GL12NA MSZ-GL15NA
MSY-GL09NA MSY-GL12NA MSY-GL15NA
MSZ-GL12NA-U1
Unit: in. (mm)
Insulation ø1 - 3/8 O.D
Liquid line ø1/4 19 - 11/16 (Flared connection ø1/4)
Gas line ø3/8 16 - 15/16
Piping
Drain hose Insulation ø1-1/8 O.D Connected part ø5/8 O.D
(Flared connection: ø3/8 (GL06/09/12NA), ø1/2 (GL15NA))
1340 Satellite Boulevard. Suwanee, GA 30024
Toll Free: 800-433-4822 www.mehvac.com
FORM# MSZ-GL12NA-U1 FOR MXZ-C MULTI-ZONE SYSTEMS - 201602
Specications are subject to change without notice. © 2016 Mitsubishi Electric US, Inc.