Mitsubishi MSZ-FA25VA - E1, MSZ-FA25VA - E2, MSZ-FA25VA - E3, MSZ-FA35VA - E1, MSZ-FA35VA - E2 Service Manual

...
Page 1
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
INDOOR UNIT
SERVICE MANUAL
Wireless type Models
Revision:B
E3
model has been added.
9-2. Failure mode recall function has been
changed.
RoHS PARTS LIST has been added. Please void OB371 REVISED EDITION-A.
No. OB371
REVISED EDITION-B
MSZ-FA25VA ­MSZ-FA25VA ­MSZ-FA25VA ­MSZ-FA35VA ­MSZ-FA35VA ­MSZ-FA35VA -
E1
E2
E3
E1
E2
E3
Outdoor unit service manual MUZ-FA·VA(H) Series (OB372) MXZ-A·VA Series (OB377) MXZ-8A140VA1 (OC316)
CONTENTS
1. TECHNICAL CHANGES ····································2
2. PART NAMES AND FUNCTIONS······················3
3. SPECIFICATION·················································5
4. NOISE CRITERIA CURVES·······························6
5. OUTLINES AND DIMENSIONS·························7
6. WIRING DIAGRAM ············································8
7. REFRIGERANT SYSTEM DIAGRAM················8
8. SERVICE FUNCTIONS ······································9
9. TROUBLESHOOTING ······································11
11. PARTS LIST······················································35
12. RoHS PARTS LIST···········································39
13. OPTIONAL PARTS ···········································42
NOTE:
This service manual describes technical data of the indoor units. RoHS compliant products have <G> mark on the spec name plate. For servicing of RoHS compliant products, refer to the RoHS Parts List.
Page 2
Revision:A
E2
model has been added. Color of BOX and CORNER BOX has been changed to white.
Revision:B
E3
model has been added.
•9-2. Failure mode recall function has been changed.
•RoHS PARTS LIST has been added.
1
MSZ-A09YV - MSZ-FA25VA ­MSZ-A12YV - MSZ-FA35VA -
1. Indication of capacity has been changed.(BTU base kW base)
2. Controller method between indoor and outdoor has been changed.
3. Power supply method has been changed (change to supply from outdoor unit).
4. Power supply cord has been removed.
5. Indoor electronic control P.C. board has been changed.
6. Position of terminal block has been changed.
7. Indoor fan motor has been changed. ( AC ➔ DC)
8. Indoor heat exchanger has been changed.
9. The horizontal vane motor unit has been changed. An external gear is added to the generalized stepping motor. The unit is structured so that the driving torque and stopping torque would increase.
10. The vertical vane motor unit has been added. An external gear is added to the generalized stepping motor. The unit is structured so that the driving torque and stopping torque would increase.
TECHNICAL CHANGES
E1E1 E1E1
NOTE: Do not remove the vane motor from the motor unit.
Do not disassemble the horizontal vane motor unit.
Generalized stepping motor
Generalized stepping motor
NOTE: Do not remove the vane motor from the motor unit.
Do not disassemble the vertical vane motor unit.
11. Front panel driving motor unit which opens and closes the front panel has been added.
Front panel opening/closing
output gear
NOTE: Do not disassemble the front panel driving motor unit.
12. PLASMA DEODORIZING/AIR PURIFYING filter units have been added.
13. i-see Sensor has been added.
(i-see control operation and AREAsetting have been added.)
14. Air cleaning filer has been removed.
15. Signal of remote controller has been changed. (It is not available for the conventional models.)
16. Symbol on terminal block has been changed (to S1/S2/S3).
2
Page 3
Line flow fan
Air outlet
Vertical vane
Air inlet
Display section
Front panel
PLASMA DEODORIZING filter
Panel
Heat exchanger
Horizontal vane
Operation section
(When the front panel is opened)
Remote controller
POWER lamp
Remote control receiving section
PLASMA AIR PURIFYING filter
Anti-mold air filter
Fan guard
i-see Sensor
PLASMA/WASH lamp
AREA lamp
Emergency operation switch
WASH reset switch
Auto front panel
When the unit starts operating, the front panel opens automatically to draw in air. When the unit stops operating, the front panel closes automatically.
AREA lamp indicate AREA setting
In AREA setting, the horizontal air flow direction changes automatically according to the detection of i-see Sensor which detects the floor/ wall temperature to air-condition the room evenly.
i-see control operation
i-see sensor constantly measure floor/wall temperature to automatically adjust to the set temperature by estimating the temperature actually perceived by a person inside the room ("sensible temperature").
<Open> <Closed>
Auto front panel
MSZ-FA25VA- MSZ-FA25VA­MSZ-FA35VA- MSZ-FA35VA-
1. Color of BOX and CORNER BOX has been changed to white.
E2E1 E2E1
MSZ-FA25VA- MSZ-FA25VA­MSZ-FA35VA- MSZ-FA35VA-
1. The operation of thermo-off-unit has been changed. (When 2 or more indoor units are connected with a multi type outdoor unit, and operated in heat mode.)
E2E1
< , > Indoor fan operates with very Low speed or stops.
E3
< > Indoor fan operates intermittently with very Low speed or stops.
2
PART NAMES AND FUNCTIONS
E3E2 E3E2
MSZ-FA25VA MSZ-FA35VA
3
Page 4
1 2 3 4 5 6 7
Installation plate Installation plate fixing screw 4 o 25 mm Remote controller holder Fixing screw for 3 3.5 o 1.6 mm (Black) Battery (AAA) for remote controller Wireless remote controller Felt tape (Used for left or left-rear piping)
1 5 1 2 2 1 1
ON-TIMER button
CLOCK SET button
TIME SET buttons FORWARD button BACKWARD button
VANE CONTROL button (Horizontal vane button)
OFF-TIMER button
i-see button
(This diagram shows an overall view.)
Open the front lid.
PLASMA button
AREA button
RESET button
WIDE VANE button (Vertical vane button)
Signal transmitting section
Operation display section
Temperature buttons
OPERATE/STOP (ON/OFF) button
FAN SPEED CONTROL button
OPERATION SELECT button
ECONO COOL button
Indication of remote controller model is on back
MSZ-FA25VA MSZ-FA35VA
ACCESSORIES
REMOTE CONTROLLER
4
Page 5
3
T3.15AL250V
NSEJ001DA1 12V DC 100" (at 25˚C)
MP20Z 12V DC 300" (at 25˚C)
MSBPC20M16 12V DC 250" (at 25˚C)
MSBPC20M11 12V DC 300" (at 25˚C)
ERZV14D471
A2TPMI334F0V50HSOBA060P5L1J4S 5V DC
3P
Item Fuse Front panel driving motor i-see Sensor motor Horizontal vane motor Vertical vane motor Varistor i-see Sensor Terminal block
(F11)
(MP)
(MT) (MV1) (MV2)
(NR11)
(RR)
(TB)
MSZ-FA25VA
MSZ-FA35VA
Indoor model
Function
Power supply
Single phase
230V,50Hz
10
0.25 33 57
0.25
RC0J40-EB or RC0J30-CC
780O298O198
10
4
42
36/29/21
4
KM05A
Cooling
594
474/354/252
1,220
1,010/800/610
Heating
612
498/384/264
1,250
1,050/850/640
Single phase
230V,50Hz
10
0.25 33 57
0.25
RC0J40-EB or RC0J30-CC
780O298O198
10
4
42
36/29/22
4
KM05A
Cooling
594
474/354/258
1,220
1,010/800/630
Heating
612
498/384/276
1,250
1,050/850/660
Air flow(Super High) Air flow(High/Med./Low) Power outlet Running current ✽1 Power input ✽1 Power factor ✽1 Fan motor current ✽1 Model Dimensions WOHOD Weight Air direction Sound level(Super High) Sound level(High/Med./Low) Fan speed(Super High) Fan speed(High/Med./Low) Fan speed regulator Remote controller model
K /h K /h
A
A W %
A
mm
kg
dB(A) dB(A)
rpm rpm
Electrical
data
Fan motor
Special
remarks
Capacity
MSZ-FA25VA
MSZ-FA35VA
Indoor model
Function
Cooling
546
450/348/252
1,130
960/790/610
Heating
540
420/372/264
1,120
910/830/640
Cooling
516/390/258
1,080/860/630
Heating
522/402/276
1,090/880/660
Air flow(Super High) Air flow(High/Med./Low) Sound level(Super High) Sound level(High/Med./Low) Fan speed(Super High) Fan speed(High/Med./Low)
K /h K /h
dB(A) dB(A)
rpm rpm
Special
remarks
Capacity
42
36/29/21
642
42
36/29/22
1,300
SPECIFICATION
When outdoor unit is MXZ-8A140VA
NOTE : Test conditions are based on ISO 5151
Specifications and rating conditions of main electric parts
1 type.
Cooling : Indoor Dry-bulb temperature 27:Wet-bulb temperature 19: Heating : Indoor Dry-bulb temperature 20:Wet-bulb temperature 15: Refrigerant piping length (one way): 5m
Outdoor Dry-bulb temperature 35:Wet-bulb temperature 24: Outdoor Dry-bulb temperature 7: Wet-bulb temperature 6:
1 Measured under rated operating frequency.
5
Page 6
4
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
COOLING
FUNCTION
42 42
SPL(dB(A))
LINE
Super High
FAN SPEED
HEATING
Test conditions, Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
Heating : Dry-bulb temperature 20: Wet-bulb temperature 15:
INDOORUNIT
WALL
MICROPHONE
0.8m
1m
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions, Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
COOLING
FUNCTION
42 42
SPL(dB(A))
LINE
Super High
FAN SPEED
HEATING
Heating : Dry-bulb temperature 20: Wet-bulb temperature 15:
NOISE CRITERIA CURVES
MSZ-FA25VA
MSZ-FA35VA
6
Page 7
5
780
155 155
335 320
41.5 215
42.5
214
3 287.5
7055
5555 225 225
298
90
106
or more7
100
198 5
53.5 102624.5 19
159
58
234
14273.5
Air in
Air out
Wall hole
[65
Indoor unit
Installation plate
Installation plate
11o20 Oblong hole
11o26 Oblong hole
10 or more
75 or more
55 or morew
75 or more
wIn case of left, left back, or
left under piping (using spacer),
113 or more
Insulation [28
Drain hose [16 (Connected part O.D)
Liquid line [6.35 - 0.5m Gas line [9.52 - 0.43m Insulation [35 O.D [19 I.D
{
Required space (Indoor unit)
Wireless remote controller
OUTLINES AND DIMENSIONS
MSZ-FA25VA MSZ-FA35VA
Unit : mm
7
Page 8
6
Indoor heat exchanger
Flared connection
Room temperature thermistor RT11
Indoor coil thermistor RT13(sub)
Flared connection
Refrigerant flow in cooling Refrigerant flow in heating
Refrigerant pipe [9.52 (with heat insulator)
Refrigerant pipe [6.35 (with heat insulator)
Indoor coil thermistor RT12(main)
Indoor heat exchanger
Flared connection
Room temperature thermistor RT11
Indoor coil thermistor RT13(sub)
Flared connection
Refrigerant pipe [9.52 (with heat insulator)
Refrigerant pipe [6.35 (with heat insulator)
Indoor coil thermistor RT12(main)
SYMBOL
DB111
F11
MF
MP MT
MV1
SYMBOL
MV2
NR11 PLASMA_A PLASMA_D
RR
RT11
SYMBOL
RT12 RT13
T111
TB
NAME DIODE STACK FUSE (T3.15AL250V) INDOOR FAN MOTOR FRONT PANEL DRIVING MOTOR i-see Sensor MOTOR VANE MOTOR (HORIZONTAL)
NAME VANE MOTOR (VERTICAL) VARISTOR PLASMA AIR PURIFYING FILTER UNIT PLASMA DEODORIZING FILTER UNIT i-see Sensor ROOM TEMPERATURE THERMIST OR
NAME INDOOR COIL THERMISTOR (MAIN) INDOOR COIL THERMISTOR (SUB) TRANSFORMER TERMINAL BLOCK
1
2
3
4
S2
8
230V~
BLU
INDOOR ELECTRONIC CONTROL P.C. BOARD
33
PLASMA_DPLASMA_A
SAFETY DEVICE (PLASMA UNIT)
MP
RR
5
4
MT
SW P.C. BOARD
POWER MONITOR RECEIVER P.C. BOARD
INTERLOCK SWITCH(FAN)
5
5
MV2
MV1
TO OUTDOOR UNIT CONNECTING
BLK
RED
S3
TB
TAB3
DB111
NR11
F11
5
6
4
2
5
CN
1U1
2
CN
1T2
CN
1T1
CN
110
3
LD
105(T)
LD
101(A)
12-24V
RT13
2
1R1
CN
GRN
LD104
CN201
2 1
151
CN
T111
RED
WHT
111
CN
CN
112
CN211
BLU
YLW
BLK
MF
RT11
RT12
1 3 5
S1
WIRING DIAGRAM
MSZ-FA25VA MSZ-FA35VA
NOTE:1. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate.
/: Terminal block, : Connector
7
MSZ-FA25VA
REFRIGERANT SYSTEM DIAGRAM
MSZ-FA35VA
8
Unit : mm
Page 9
8
No. 1 unit No. 2 unit No. 3 unit No. 4 unit
1 unit operation No modification
– – –
2 units operation
Same as at left
Solder J1
– –
3 units operation
Same as at left Same as at left
Solder J2
4 units operation
Same as at left
Same as at left
Same as at left
Solder both J1 and J2
SERVICE FUNCTIONS
MSZ-FA25VA MSZ-FA35VA
8-1. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS the electronic control P.C. board. The time will be shortened as follows. (Refer to 9-7.) Set time : 1-minute 1-second Set time : 3-minute 3-second (It takes 3 minutes for the compressor to start operation. However, the starting time is
shortened by short circuit of JPG and JPS.)
8-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room. In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be modified according to the number of the indoor unit.
How to modify the remote controller P.C. board
Remove batteries before modification. The board has a print as shown below :
NOTE : For remodelling, take out
the batteries and press the OPERATE/STOP(ON/OFF) button twice or 3 times at first. After finish remodelling, put back the batteries then press the RESET button.
J1
The P.C. board has the print “J1” and “J2”. Solder “J1” and “J2” according to the number of indoor unit as shown in Table 1. After modification, press the RESET button.
J2
Table 1
How to set the remote controller exclusively for particular indoor unit.
After you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as the remote controller for the indoor unit. The indoor unit only accepts the signal from the remote controller that has been assigned to the indoor unit once they are set. The setting will be cancelled if the breaker has turned OFF, or the power supply has shut down. Please conduct the above setting once again after the power has restored.
8-3. AUTO RESTART FUNCTION
When the indoor unit is controlled with the remote controller, the operation mode, the set temperature, and the fan speed are memorized by the indoor electronic control P.C. board. The “AUTO RESTART FUNCTION” sets to work the moment power has restored after power failure. Then, the unit will restart automatically.
Operation
1 If the main power has been cut, the operation settings remain. 2 After the power is restored, the unit restarts automatically according to the memory.
(However, it takes at least 3 minutes for the compressor to start running.)
9
Page 10
How to release “AUTO RESTART FUNCTION”
JR07
CN151 CN211CN112 CN1R1
CN212
CN1T1CN1T2
CN130
IC156
8-4. Remote controller
Be sure to set the slide switch inside the remote controller to an appropriate position in accordance with the installed position of the indoor unit. If the switch is not set correctly, the air conditioner may not function properly.
Area Left Center Right
Position of
the slide
switch
Display on
the remote
controller
Where is the indoor unit installed in your room?
Installed at left , if the distance is not more than 50 cm.
NOTE:If the indoor unit is installed more than 50 cm away from the side walls, cabinets or other nearby objects, set the slide
switch to the “center” position.
Installed at right, if the distance is not more than 50 cm.
Is the indoor unit in­stalled at right, left or center?
(Left) (Center) (Right)
Side swich
1Turn OFF the main power for the unit. 2Solder the Jumper wire to JR07 on the indoor electronic control P.C. board. (Refer to 9-7.)
NOTE:
The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the remote
controller.
If main power is turned OFF or a power failure occurs while AUTO START/STOP timer is active, the timer setting is
cancelled.
If the unit has been off with the remote controller before power failure, the auto restart function does not works as the
power button of the remote controller is off.
To prevent breaker off due to the rush of starting current, systematize other home appliance not to turn ON at the same
time.
When some air conditioners are connected to the same supply system, if they are operated before power failure, the
starting current of all the compressors may flow simultaneously at restart. Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting current by adding to the system that allows the units to start one by one.
10
Page 11
21
Stopper
Lock.
Left
Insert this end first.
9
RESET button
Housing point
TROUBLESHOOTING
MSZ-FA25VA MSZ-FA35VA
9-1. Cautions on troubleshooting
1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care the following during servicing.
1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, and then after confirming the horizontal vane is closed, turn OFF the breaker and / or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board.
3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components.
4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality. To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
2) Before servicing check that the connector and terminal are connected properly.
3) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
4) When troubleshooting, refer to 9-2., 9-3. and 9-4.
4. How to replace batteries
Weak batteries may cause the remote controller malfunction. In this case, replace the batteries to operate the remote controller normally.
1 Remove the front lid and insert batteries.
Then reattach the front lid.
Insert the negative pole of the batteries first. Check if the polarity of the batteries are correct.
NOTE : 1. If RESET button is not pressed, the remote controller may not operate correctly.
2. This remote controller has a circuit to automatically reset the microcomputer when batteries are replaced. This function is equipped to prevent the microcomputer from malfunctioning due to the voltage drop caused by the battery replacement.
5. How to install the horizontal vane
If horizontal vane is not installed correctly, All of the operation indicator lamps will blink. In this case, install the horizontal vane correctly by following the procedures 1 to 2.
Lead wiring
2 Press RESET button with tip end of ball point pen
or the like, and then use the remote controller.
NOTE: Before installation of the horizontal vane, turn OFF the power supply.
11
22
In procedure
stoppers until they click into place.
lock the
Page 12
WASH
reset
E.O. SW
Plasma element holder
6. How to remove and install PLASMA DEODORIZING / AIR PURIFYING filter units
If PLASMA/WASH lamp on the indoor unit blinks, clean the filters as soon as possible. The lamp will start blinking when accumulated operating time exceeds 330 hours.
<Remove>
Figure 1.
(1) Switch the indoor unit OFF with the remote controller and
disconnect the power supply plug and/ or turn OFF the breaker. NOTE: Otherwise, you may get injured since PLASMA
DEODORIZING/AIR PURIFYING filter units are charged with high voltage.
(2) Hold the knobs on both sides of the front panel and lift the
panel up until its level. (3) Remove the anti-mold air filter.(See Figure 1.) (4) Remove PLASMA DEODORIZING/AIR PURIFYING filter
units. (See Figure 2.)
Figure 2.
<Install>
Install PLASMA DEODORIZING/AIR PURIFYING filter units by following the removal procedure in reverse. (1) Insert the top of PLASMA DEODORIZING/AIR PURIFYING filter
units into the aperture in the plasma element holder.
Figure 3.
(See Figure 3.)
(2) Push in PLASMA DEODORIZING/AIR PURIFYING filter units
until they click into place.
•The front panel does not close if PLASMA DEODORIZING/AIR PURIFYING filter units are not installed properly.
(3) Install the anti-mold air filter. (4) Connect the power supply plug and/ or turn ON the breaker. (5) Press WASH reset switch. A short “beep” is heard and the blinks
of PLASMA/WASH lamp will be cancelled. Make sure PLASMA/ WASH lamp is not blinking at the start of operation next time. (See Figure 4.)
(6) Hold both sides of the front panel and close the front panel.
Figure 4.
(7) Press the 3 positions on the front panel as indicated by the
arrows.(See Figure 5.)
NOTE: Install PLASMA DEODORIZING/AIR PURIFYING filter units only when they are completely dry. If the filter unit remains wet, PLASMA/WASH lamp may blink and the plasma function may be disabled.(When PLASMA DEODORIZING/AIR PURIFYING filter units are cleaned.)
12
Figure 5.
Page 13
INFORMATION FOR MULTI SYSTEM AIR CONDITIONER
Lighted Blinking Not lighted
OUTDOOR UNIT : MXZ series
Multi system air conditioner can connect two or more indoor units with one outdoor unit.
•Unit won’t operate in case the total capacity of indoor units exceeds the capacity of outdoor units. Do not connect indoor units beyond the outdoor unit capacity. Operation indicator lamp flashes as shown in the figure below.
•When you try to operate two or more indoor units with one outdoor unit simultaneously, one for the cooling and the other for heating, the operation mode of the indoor unit that operates earlier is selected. The other indoor units which start the operation later cannot operate, indicating as shown in the figure below. In this case, please set all the indoor units to the same operation mode.
•When indoor units start the operation while the defrosting of outdoor unit is being done, it takes a few minutes (max. 10 minutes) to blow out the warm air.
•In the heating operation, though indoor unit that does not operate may get warm or the sound of refrigerant flowing may be heard, they are not malfunction. The reason is that the refrigerant continuously flows into it.
13
Page 14
9-2. Failure mode recall function
Operational procedure
Yes
(Blinks)
No
(OFF)
Yes
No
Releasing the failure mode recall function
W1. Regardless of normal or abnormal, a short beep is emitted once as the signal is received.
Note1.Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.
2.If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
W2. Blinking pattern when the indoor unit is abnormal:
W3.Blinking pattern when the outdoor unit is abnormal:
ON
OFF
Beeps
Repeated cycle Repeated cycle
ON
OFF
No beep Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5-
second interval
2.5-second OFF 3-second ON
Blinking at 0.5-
second interval
Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5­second interval
No beep Beeps
Repeated cycle
2.5-second OFF 3-second ON
Blinking at 0.5­second interval
Repeated cycle
Beeps
Does POWER lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: Either indoor or outdoor unit is abnormal. Beep are emitted at the same timing as the blinking of POWER lamp. W2
The cause of abnormality cannot be found because the abnormality doesn't recur.
Setting up the failure mode recall function
Before blinking, does POWER lamp stay ON for 3 seconds? Stays ON for 3 seconds (without beep): The outdoor unit is abnormal.
The indoor unit is abnormal. Check the blinking pattern, and confirm the abnormal point with the indoor unit failure mode table (9-2.4.). Make sure to check at least two consecutive blinking cycles. W2
Turn ON the power supply. <
Preparation of the remote controller
> 1 While pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button. 2 First, release RESET button. And release the other two buttons after all LCD except the set temperature in operation display section of the remote controller is displayed after 3 seconds.
Deleting the abnormal memorized condition
1After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall function" mentioned above. 2Press OPERATE/STOP(ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit.
3Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. 4Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
Repair the defective parts.
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller.
Judgment of indoor/outdoor abnormality
Press OPERATE/STOP(ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. W1
The plasma or outdoor unit might be abnormal because there are some abnormalities that can't be recalled with this way. Confirm if plasma unit or outdoor unit is abnormal according to the flow chart of the plasma unit or detailed outdoor unit failure mode recall function.
The outdoor unit is abnormal. Check the blinking pattern, and confirm the abnormal point with the outdoor unit failure mode table (Refer to outdoor unit service manual.) Make sure to check at least two consecutive blinking cycles. W3
Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table disappears, the memorized failure details can be recalled. This mode is very useful when the unit needs to be repaired for the abnormality which doesn't recur.
1. Flow chart of failure mode recall function for the indoor/outdoor unit
14
Page 15
2. Flow chart of PLASMA DEODORIZING/PLASMA AIR PURIFYING power failure mode recall function
Operational procedure
Note1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized. W2.Blinking pattern when plasma unit is abnormal:
Yes
(Blinks)
No
(OFF)
W1. Regardless of normal or abnormal, a short beep is emitted as the signal is received.
Does POWER lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: The plasma unit is abnormal. Beep are emitted at the same timing as the blinking of POWER lamp. W2
Deleting the abnormal memorized condition
Repair the defective parts.
With the remote controller headed towards the indoor unit, press TOO COOL or TOO WARM button to adjust the set temperature to 23:. W1
The plasma unit is normal.
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller.
The plasma unit is abnormal. Check the blinking pattern, and refer to confirm the abnormal point with the PLASMA DEODORIZING/PLASMA AIR PURIFYING power failure mode table (9-2.5.). Make sure to check at least two consecutive blinking cycles. W2
Release the failure mode recall function according to the left mentioned procedure.
Confirm that the remote controller is in the failure mode recall function.
The plasma unit might be abnormal. Confirm if plasma unit is abnormal according to the following procedures.
ON
OFF
Beeps
Repeated cycle Repeated cycle
2.5-second OFF
Blinking at 0.5­second interval
Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5­second interval
Beeps
1After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall function" mentioned above. 2Press OPERATE/STOP(ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit.
3Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. 4Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
ActionPLASMA/WASH lamp
Continuously blinking
2-time flash
Follow "Check of
PLASMA DEODORIZING
power" or "Check of
PLASMA AIR PURIFYING
power"
to identify the error.(Refer to 9-6.F or G.) PLASMA DEODORIZING power and/or PLASMA AIR PURIFYING power
control circuit on the indoor
electronic control P.C. board is out of order.(Refer to 9-6.F or G.)
PLASMA DEODORIZING/PLASMA AIR PURIFYING power goes ON when PLASMA button on the remote contoller is pressed with any set temperature displayed during failure mode recall function. PLASMA button is pressed, the power of plasma is changed in sequence: PLASMA DEODORIZING power goes ON PLASMA AIR PURIFYING power goes ON Cancel Check the operation display section of the remote controller to confirm that PLASMA DEODORIZING power or PLASMA AIR PURIFYING power is activated. While PLASMA/WASH lamp stays OFF, it means normal. Flashing PLASMA/WASH lamp means abnormal, the plasma power is not conducted.
3. PLASMA DEODORIZING/PLASMA AIR PURIFYING power operation check
NOTE: Perform the above mentioned check with the front panel closed (Refer to 9-1.6 Figure5). The SAFETY DEVICE
(PLASMA UNIT) works by opening front panel and the plasma power is cut.
15
Page 16
4. Indoor unit failure mode table
5-time flash
When the voltage between CN1 3(+) and 2(GND) on the PLASMA POWER P.C. board (in the PLASMA DEODORIZING or PLASMA AIR PURIFYING unit) rises above the normal voltage value (3V).
4-time flash
PLASMA DEODORIZING/ PLASMA AIR PURIFYING power
When the voltage between CN1 3(+) and 2(GND) on the PLASMA POWER P.C. board (in the PLASMA DEODORIZING or PLASMA AIR PURIFYING unit) falls significantly. (0.4V / 0.5ms)
3-time flash
Refer to 9-6.F"Check of PLASMA DEODORIZING power" or 9-6.G"Check of PLASMA AIR PURIFYING power".
Abnormal electric discharge error 1
When the voltage between CN1 3(+) and 2(GND) on the PLASMA POWER P.C. board (in the PLASMA DEODORIZING or PLASMA AIR PURIFYING unit) falls by 0.9V below the normal voltage value (3V).
2-time flash
Spark discharge
1-time flash
PLASMA DEODORIZING/ PLASMA AIR PURIFYING power control
When the voltage between CN1 3(+) and 2(GND) on the PLASMA POWER P.C. board (in the PLASMA DEODORIZING or PLASMA AIR PURIFYING unit) falls below
1.6V(spark discharge judgment voltage).
When PLASMA DEODORIZING and/or PLASMA AIR PURIFYING power cannot be turned OFF even if the PLASMA operation is turned OFF with the remote controller.
POWER lamp
Correspondence
Abnormal point
(Failure mode)
Condition
Abnormal electric discharge error 2
12-time flash
2.5-second OFF
Replace the indoor electronic control P.C. board.
Indoor control system
When it cannot properly read data in the nonvolatile memory of the indoor electronic control P.C. board.
11-time flash
2.5-second OFF
Refer to 9-6.A "Check of indoor fan motor".
Indoor fan motor
When the rotational frequency feedback signal is not emitted during the 12-seconds indoor fan operation.
2-time flash
2.5-second OFF
Refer to the characteristics of the main indoor coil thermistor, the sub indoor coil thermistor (9-7.).
Indoor coil thermistor
When the indoor coil thermistor short or open circuit is detected every 8 seconds during operation.
3-time flash
2.5-second OFF
Refer to 9-6.D "How to check mis-wiring and serial signal error".
Serial signal
When the serial signal from the outdoor unit is not received for a maximum of 6 minutes.
1-time flash every 0.5-second
Refer to the characteristics of the room temperature thermistor (9-7.).
Room temperature thermistor
When the room temperature thermistor short or open circuit is detected every 8 seconds during operation.
Not lighted Normal
POWER lamp
Correspondence
Abnormal point
(Failure mode)
Condition
NOTE : Blinking patterns of this mode differ from the ones of Troubleshooting check table (9-4.).
5. PLASMA DEODORIZING/PLASMA AIR PURIFYING power failure mode table
NOTE1 :Blinking patterns of this mode differ from the ones of Troubleshooting check table (9-4.). NOTE2 :As soon as an abnormality is detected, PLASMA DEODORIZING power and/or PLASMAAIR PURIFYING
power goes OFF, therefore measuring instrument which records the voltage wave is required in order to perform the above mentioned voltage measurement.
16
Page 17
9-3. Instruction of troubleshooting
Start
Indoor unit operates. Outdoor unit doesn't operate.
Outdoor unit operates only in Test Run operation. w
Outdoor unit doesn't operate even in Test Run operation. w
Indoor unit operates. Outdoor unit doesn't operate normally.
Unit doesn't operate normal operation in COOL or
Indoor unit operates, when EMERGENCY OPERATION switch is pressed.
HEAT mode.
w"Test Run operation" means the operation within 30 minutes after EMERGENCY OPERATION switch is pressed.
Indoor unit doesn't receive the signal from remote controller.
Indoor unit doesn't operate, when EMERGENCY OPERATION switch is pressed.
If blinking of OPERATION INDICATOR lamp cannot be checked, it can be checked with failure mode recall function.
OPERATION INDICATOR lamp on the indoor unit is flashing on and off.
PLASMA/WASH lamp 2-time flash cause: Indoor unit
• Trouble of PLASMA DEODORIZNG power control and/or PLASMA AIR PURIFYING power control
Check room temperature thermistor. Refer to 9-7. "Test point diagram and voltage".
All lamps Flash on and off at 0.5-second intervals Cause: Indoor unit
• The horizontal vane is not installed correctly.
Refer to 9-6. E "Check of installation of the horizontal vane".
Refer to "How to check inverter/ compressor".
POWER lamp Flash on and off at 0.5-second intervals Cause: Indoor/ Outdoor unit
• Mis-wiring or trouble of serial signal
Refer to 9-6. D "How to check of mis-wiring and serial signal error
.
Refer to "Check of R.V. coil".
POWER lamp 2-time flash Cause: Indoor unit
• Trouble of room temp­ erature/ indoor coil thermistor
Check room temperature thermistor and indoor coil thermis­tor. Refer to 9-7. "Test point diagram and voltage".
Refer to 9-6.B "Check of remote controller and receiver P.C. board".
POWER lamp 3-time flash Cause: Indoor unit
• Trouble of indoor fan motor
Refer to 9-6. A "Check of indoor fan motor".
1. Check indoor / outdoor connecting wire. (Check if the power is supplied to the indoor unit.)
2. Refer to 9-6.C "Check of indoor electronic control P.C. board and indoor fan motor".
Left lamp of AREA lamp 4-time flash Cause: Indoor unit
• Trouble of indoor unit control
POWER lamp 5-time flash Cause: Outdoor unit
• Outdoor power system abnormality
system
Replace the indoor electronic control
Refer to "How to check inverter/ compressor".
P.C. board.
Refer to outdoor unit service manual.
POWER lamp 6-time flash Cause: Outdoor unit
• Trouble of thermistor in outdoor unit
Refer to "Check of outdoor thermistors".
Refer to 9-6.F"Check of PLASMA DEODORIZING power" or 9-6.G"Check of PLASMA AIR PURIFYING power".
POWER lamp 7-time flash Cause: Outdoor unit
• Trouble of outdoor
POWER lamp 14-time flash Cause: Outdoor unit
• Other
abnormality control system
Replace the inverter P.C. board or the outdoor electronic control P.C.
Check
"Flow chart of
the detailed
outdoor unit
failure mode
recall function."
board.
17
Page 18
No.
1
3
5
6
SymptomOperation indicator lamp Condition
Correspondence
POWER lamp flashes.
0.5-second ON
0.5-second OFF
Mis-Wiring or serial signal
Outdoor power system
Outdoor thermistors
Outdoor control system
Indoor coil thermistor
When the serial signal form the outdoor unit is not received for a maximum of 6 minutes.
When it consecutively occurs 3 times that the compressor stops for overcurrent protection or start-up failure protection within 1 minute after start-up.
When the outdoor thermistors short or open circuit during the compressor operation.
When it cannot properly read data in the nonvolatile memory of the inverter P.C. board or the outdoor electronic control P.C. board.
• Refer to "Check of outdoor thermistor".
Refer to outdoor unit service manual.
• Refer to "How to check of
inverter/compressor". Refer to outdoor unit service manual.
• Check the stop valve.
• Replace the inverter P.C.
board or the outdoor electronic control P.C. board. Refer to outdoor unit service manual.
• Refer to 9-6.D "How to check mis-wiring and serial signal
error".
4
Indoor fan motor
7
Abnormal
point
Outdoor unit does not operate.
Room tempera­ture thermistor
POWER lamp flashes. 2-time flash
2.5-second OFF
When the indoor coil or the room temperature thermistor is short or open circuit.
• Refer to 9-7.the characteristics of indoor coil thermistor, and the room temperature thermistor.
POWER lamp flashes. 3-time flash
2.5-second OFF
When the rotational frequency feedback signal is not emit during the indoor fan operation.
• Refer to 9-6.A "Check of
indoor fan motor".
Indoor unit and outdoor unit do not operate.
POWER lamp flashes. 5-time flash
2.5-second OFF POWER lamp flashes.
6-time flash
2.5-second OFF
Indoor unit and outdoor unit do not operate.
Indoor unit and outdoor unit do not operate.
Indoor unit and outdoor unit do not operate.
Other abnonmality
An abnormality other than above mentioned is detected.
• Confirm the abnormality in detail using the failure mode recall function for outdoor unit.
Indoor unit and outdoor unit do not operate.
Indoor unit and outdoor unit do not operate.
8
Outdoor control system
When it cannot properly read data in the nonvolatile memory of the inverter P.C. board or the outdoor electronic control P.C. board.
• Check the blinking pattern of the LED on the inverter P.C. board or the outdoor electronic control P.C. board.
2
Outdoor unit does not operate.
POWER lamp flashes. 7-time flash
2.5-second OFF
POWER lamp flashes. 14-time flash
2.5-second OFF
POWER lamp lights up
9-4. Troubleshooting check table
Lighted Blinking Not lighted
Before taking measures, make sure that the symptom reappears for accurate troubleshooting. When the indoor unit has started operation and the following detection method has detected an abnormality (the first
detection after the power ON), the indoor electronic control P.C. board turns OFF the indoor fan motor with OPERATION INDICATOR lamp flashing.
· Flashing of POWER lamp indicates abnormalities.
18
Page 19
Lighted
No.
1
SymptomOperation indicator lamp Condition
Correspondence
Abnormal
point
Left lamp of AREA lamp flashes. 4-time flash
2.5-second OFF
Indoor control system
When it cannot properly read data in the nonvolatile memory of the indoor electronic control P.C. board.
Indoor unit and outdoor unit do not operate.
• Replace the indoor electronic control P.C. board.
No.
1
SymptomOperation indicator lamp Condition
Correspondence
Abnormal
point
0.5-second ON
0.5-second OFF
When the electricity is not conducted to the interlock switch (Fan) of the horizontal vane.
• Refer to 9-6.E "Check of installation of the horizontal vane".
Indoor unit and outdoor unit do not operate.
Attachment of the horizontal vane
All lamps flash at the same time.
No.
SymptomOperation indicator lamp Condition
Correspondence
Abnormal
point
1
MXZ type
Operation mode setting
Outdoor unit operates but indoor unit does not operate.
When the operation mode of the each indoor unit is differently set to COOL (includes DRY) and HEAT at the same time, the operation mode of the indoor unit that has operated at first has the priority.
• Unify the operation mode. Refer to outdoor unit service manual.
2.5-second OFF
Both lamps flash
Lighted Blinking Not lighted
No.
1
SymptomOperation indicator lamp Condition
Correspondence
Abnormal
point
PLASMA/WASH lamp flashes. 2-time flash
2.5-second OFF
When PLASMA DEODORIZING power and/or PLASMA AIR PURIFYING power can not be turned OFF even if the PLASMA operation is turned OFF with remote controller.
Indoor unit and outdoor unit do not operate.
PLASMA DEODORIZING/ PLASMA AIR PURIFYING power control
Refer to 9-6.F"Check of
PLASMA DEODORIZING power" or 9-6.G"Check of PLASMA AIR PURIFYING power".
Blinking Not lighted
· Flashing of AREAlamp(left-hand side lamp) indicates abnormality.
Lighted Blinking Not lighted
Lighted Blinking Not lighted
· Flashing of All lamps indicate abnormality.
· Flashing of AREAlamp(both lamps) indicates abnormality.
· POWER lamp is lighted.
· Flashing of PLASMA/WASH lamp indicates abnormality.
19
Page 20
9-5. Trouble criterion of main parts
Part name FigureCheck method and criterion
Measure the resistance with a tester. Refer to 9-7. "Test point diagram and voltage", "Indoor electronic control
P.C. board", the chart of thermistor.
Room temperature thermistor(RT11)
Indoor coil thermistor (RT12(MAIN), RT13(SUB))
Horizontal vane motor(MV1)
Normal
BRN-other one
Measure the resistance between the terminals with a tester. (Part temperature 10°C ~ 30°C)
235 " ~ 255 "
Color of the lead wire
Vertical vane motor(MV2)
i-see Sensor motor(MT)
Normal
Measure the resistance between the terminals with a tester. (Part temperature 10°C ~ 30°C)
Front panel driving motor (MP)
Normal
Measure the resistance between the terminals with a tester. (Part temperature 10°C ~ 30°C)
94 " ~ 102 "
i-see Sensor(RR)
Turn the power ON(i-see Sensor is energized) with the aluminum block part on the i-see Sensor P.C. board (upper part of i-see Sensor) covered with black vinyl tape, then measure the voltage between connector terminals of i-see Sensor using tester. (Part temperature 10 ~ 40°C)
282 " ~ 306 "
Normal range
2(-)
-
4(+)
1(+) - 2(-)
1.874 ~ 3.387V DC
1.010 ~ 1.420V DC
i-see Sensor connector terminals
NOTE: Pay attention to static electricity.
Indoor fan motor(MF)
Check 9-6. A.
PLASMA DEODORIZING/ PLASMA AIR PURIFYING power
Check 9-6. F or G.
Color of the lead wire
BRN-other one
Color of the lead wire
BRN-other one
RED
YLW
BRN
ORN
GRN
ROTOR
RED
YLW BRN
ORN
GRN
ROTOR
RED
YLW BRN
ORN
GRN
ROTOR
MSZ-FA25VA MSZ-FA35VA
Aluminum block
i-see Sensor
w The aluminum block
part is covered with black vinyl tape.
Connector
i-see Sensor P.C. board
Black vinyl tape
20
Page 21
wIf more than 12 seconds passes after EMERGENCY OPERATION switch
is pressed, the voltage mentioned above 2 goes 0V DC although the indoor electric control P.C. board is normal.
Indoor electronic control P.C. board
Pay careful attention to the high voltage on the fan motor connector CN211.
Yes
No
No
No (Changed)
Yes (Unchanged)
Is there any foreign matter that interferes the rotation of the line flow fan?
Turn OFF the power supply.
Remove the foreign matter and adjust the line flow fan.
Turn ON the power supply, wait 5 seconds or more, and then press EMERGENCY OPERATION switch. Measure the supply voltage as follows within 12 seconds after EMERGENCY OPERATION switch is pressed. If more than 12 seconds passes by, turn OFF the power supply and turn ON it again, then measure the voltage. w
1.Measure the voltage between CN211 1(+) and 3(-).
2.Measure the voltage between CN211 5(+) and 3(-).
Is there 325V DC between CN211 1 (+) and 3 (-), and does the voltage between CN211 5(+) and 3(-) rise to the range of 3 to 6V DC within 12 seconds after EMERGENCY OPERATION switch is pressed?
Yes
Replace the indoor fan motor.
CN211
Replace the indoor electronic control P.C. board.
The indoor fan motor error has occurred, and the indoor fan repeats "12-second ON and 30-second OFF" 3 times, and then stops.
Measure the voltage between CN211 6(+) and 3(-) while the fan motor is rotating.
Is it unchanged holding 0V DC or 15V DC?
Replace the indoor fan motor.
Replace the indoor electronic control P.C. board.
The indoor fan motor error has occurred, and the indoor fan doesn't operate.
9-6. Troubleshooting flow
When POWER lamp flashes 3-time. Indoor fan does not operate.
A
Check of indoor fan motor
21
Page 22
Indoor unit operates by pressing EMERGENCY OPERATION switch, but does not operate with the remote controller.
Check of remote controller and receiver P.C. board
B
wCheck if the remote controller is exclusive for this air conditioner.
Switch ON the remote controller.
Is LCD display on the the remote controller visible?
Yes
Remove the batteries, then set them back and press RESET button. (Refer to 9-1.4.) Check if the unit operates with the remote controller.
Does the unit operate with the remote controller?
Yes
OK
No (not clear)
No
Replace the batteries. (Refer to 9-1.4.)
Turn ON a radio to AM and press switch ON the remote controller.
Is noise heard from radio?
Yes
Are there any fluorescent lights of inverter or rapid-start type within the range of 1m?
No
Replace the indoor electronic control P.C. board.
No
Yes
Replace the remote controller.
Reinstall the unit away from lights.
Attach a filter on receiving part.
22
Page 23
The unit does not operate with the remote controller. Also, POWER lamp does not light up by pressing EMERGENCY OPERATION switch.
Check of indoor electronic control P.C. board and indoor fan motor
C
Turn OFF the power supply. Remove indoor fan motor connector CN211, vane motor connector CN151 front panel driving motor connector CN1U1 and the i-see Sensor motor connector CN110 from the indoor electronic control P.C. board and turn ON the power supply.
Does the unit operate with the remote controller? Does POWER lamp light up by pressing EMERGENCY OPERATION switch?
No
Turn OFF the power supply. Check both “parts side” and “pattern side” of the indoor electronic control P.C. board visually.
Yes
Measure the resistance of the front panel driving motor coil. Refer to 9-5.
Measure the resistance of the i-see Sensor motor coil. Refer to 9-5.
Measure the resistance between CN211 3 and 4 of the indoor fan motor connector.
Measure the resistance of the horizontal vane motor coil and the vertical vane motor coil. Refer to 9-5.
Replace the varistor(NR11) and fuse(F11).
Yes
Are the varistor(NR11) burnt and the fuse(F11) blown?
Be sure to check both the fuse and the varistor in any case.
Is the fuse(F11) blown only?
No
No
Short/open circuit: Replace the front panel driving motor and the indoor electronic control P.C. board.
Short/open circuit: Replace the i-see Sensor motor and the indoor electronic control P.C. board.
Short/open circuit: Replace the indoor fan motor.
Short/open circuit: Replace the horizontal vane motor, the vertical vane motor and the indoor electronic control P.C. board.
Indoor electronic control P.C.Board
CN201
Measure the resistance of cement resistance R111 on the indoor electronic control P.C. board.
CN211
Varistor(NR11)
Yes
Measure the resistance between 1(+) and 3(-) of the indoor fan motor connector (to CN211 on the indoor electronic control P.C. board) . w1,w2
Is the resistance 1M" or more?
Yes
Replace the fuse (F11).
Replace the indoor electronic control P.C. board.
No
Is the resistance approx. 4"?
w1. The fan motor connector's 1 lead wire is red, whereas 3 is black. w2. Connect "+" of the tester to fan motor connector's 1 lead
wire, and "-" to 3 lead wire, otherwise the resistance cannot be measured properly.
Replace the fuse (F11) and the indoor fan motor.
No
Replace the indoor electronic control P.C. board and the indoor fan motor.
Yes
Fuse(F11)
23
Page 24
• When unit cannot operate neither by the remote controller nor by EMERGENCY OPERATION switch. Indoor unit does not operate.
• When POWER lamp flashes ON and OFF in every 0.5-second. Outdoor unit does not operate.
D
How to check mis-wiring and serial signal error
Turn OFF the power supply.
Yes
A
· Reinstall either the unit or the light each other away.
No
· Attach a filter on remote control receiving section of the indoor unit.
· Turn OFF inverter-controlled lighting equipment.
· Turn OFF the power supply and then turn ON again.
· Press EMERGENCY OPERATION switch.
Is serial signal error indicated 6 minutes later?
B
Is there rated voltage in the power supply?
Yes
Turn ON the power supply.
Is there rated voltage between outdoor terminal block S1 and S2?
Yes
Press EMERGENCY OPERATION switch once.
Does POWER lamp light up? <Confirmation of the power to the indoor unit>
Yes
Is serial signal error indicated 6 minutes later?
Yes
A
Turn OFF the power supply. Check once more if the indoor/outdoor connecting wire is not mis-wiring.
B
Short-circuit outdoor terminal block S2 and S3. W1
Turn ON the power supply.
Does the LED on the inverter P.C. board or the outdoor electronic control P.C.board repeat "3.6-second-OFF and 0.8-second-ON quick blinking"?
Turn OFF the power supply. Remove the short-circuit between outdoor terminal block S2 and S3. Turn ON the power supply. Is there amplitude of 10 to 20V DC between outdoor terminal block S2 and S3? <Confirmation of serial signal>
Is there rated voltage between indoor terminal block S1 and S2? <Confirmation of power voltage>
Replace the indoor electronic control P.C. board.
Be sure to release the failure-mode recall function after checking.
W3
Yes
Yes
Yes
Refer to outdoor unit service manual.
No
No
24
Check the power supply.
Check the wiring.
No
Is there any mis-wiring, poor contact, or wire
No
disconnection of the indoor/outdoor connecting wire?
No
W1. Mis-wiring may damage indoor electronic control
P.C. board during the operation. Be sure to confirm the wiring is correct before the operation starts.
W3. Be sure to check this within 3 minutes after turning
ON. After 3 minutes, LED blinks 6 times. Even when the inverter P.C.board or the outdoor electronic control P.C.board is normal, LED blinks 6 times after 3 minutes. (Except for outdoor unit of multi system type)
No
(Lighted or not lighted)
No
No
Replace the inverter P.C. board or the outdoor electronic control P.C.board.
W2
W2 Be careful to the residual
voltage of smoothing capacitor.
Is there any error of the indoor/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
No
Is there any error of the indoor/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
No
Yes
Make them correct.
Yes
Yes
Replace the indoor/outdoor connecting wire.
Replace the indoor/outdoor connecting wire.
Page 25
Replace the indoor electronic control P.C. board.
Replace the interlock switch(Fan).
Is the stopper of the horizontal vane locked to the indoor unit correctly?
Yes
No
Is there resistance 0 "?
Relock the stopper of the horizontal vane to the indoor unit. Refer to 9-1.5.
Yes
Are all lamps flashing?
Yes
No()
No
OK
Turn ON the power supply.
To check the continuity of the interlock switch (Fan), measure the resistance of connector 1 - 2 connected to CN1R1 on the indoor electronic control P.C. board.
Turn OFF the power supply.
Turn OFF the power supply.
When All lamps flash ON and OFF every 0.5-second. Indoor unit and outdoor unit do not operate.
Check of installation of the horizontal vane
E
25
Page 26
When PLASMA/WASH lamp flashes 2-time.
After performing the check, make sure to release the failure mode recall function.
Make sure that the front panel is firmly closed. (Refer to 9-1.6 Figure 5)
1 While pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the
same time, press RESET button. 2 First, release RESET button. And release the other two buttons after all LCD except the set
temperature in operation display section of the remote
controller is displayed after 3 seconds. 3 Press OPERATE/STOP (ON/OFF) button (the set temperature
is displayed)
4 And press PLASMA button once with the remote controller
headed towards the indoor unit. w1 PLASMA DEODORIZING operation is selected. wThe plasma power operation check mode is set.(Refer to 9-2.5.)
PLASMA DEODORIZING power supply is normal. Working of SAFETY DEVICE (PLASMA UNIT) due to uncomplete close of the front panel could cause 2-time flash.
Abnormal discharge may occur due to much dirt on the PLASMA unit, clean the unit. After cleaning, make sure to attach the unit since it is completely dry. If PLASMA DEODORIZING power operation check is performed with the plasma unit wet, protection gets active and PLASMA/WASH lamp blinks continuously as well.
w2 Turn PLASMA DEODORIZING power OFF and ON again.
(For turning OFF PLASMA DEODORIZING power, refer to 9-2.3.) (If it goes normal without turning OFF and ON, PLASMA/WASH lamp doesn't go OFF.)
Yes
No
No
Yes
Yes
No
9.5V DC is generated.
Yes
No
Replace the indoor electronic control P.C. board, after check of the wiring of CN1T1 on the indoor electronic control P.C. board.
High voltage (approx. -3.9kV) is generated during PLASMA DEODORIZING power operation. Pay careful attention and never touch PLASMA unit and the high-voltage lead part (red wire).
Yes
No
OFF
PLASMA DEODORIZING operation
Continuously blinking.
OFF
Continuously blinking.
Does PLASMA/WASH lamp flash 2-time with unit stopping?
Turn ON the power supply.
Replace the indoor electronic control P.C. board.
Remove PLASMA DEODORIZING filter, firmly close the front panel, and then perform PLASMA DEODORIZING power operation check (w2). Does PLASMA/WASH lamp stay OFF, or continuously blink?
Does PLASMA/WASH lamp stay OFF, or continuously blink?
Turn OFF the power supply, and check the SAFETY DEVICE(PLASMA UNIT). Is it firmly fixed?
Work and Not-work the SAFETY DEVICE (PLASMA UNIT) using something like a screw driver, and measure the resistance between CN1T2 1 and 3 on the indoor electronic control P.C. board. Does the SAFETY DEVICE function?
Keep the SAFETY DEVICE(PLASMA UNIT) Not-work (close) using something like a screw driver. Turn ON the power supply. Is the voltage between CN1 1(+) and 2(GND) on the PLASMA POWER P.C. board (PLASMA DEODORIZING) 0V with the unit stopping? (Refer to 9-7.)
Set the plasma power failure mode recall function. (Refer to 9-2.2)
Replace the PLASMA POWER P.C. board (PLASMA DEODORIZING).
Replace the indoor electronic control P.C. board.
When PLASMA DEODORIZING power turns ON by pressing PLASMA button once, is there
12.5V DC between CN1 1(+) and 2(GND)?
Replace the SAFETY DEVICE(PLASMA UNIT).
Firmly fix the SAFETY DEVICE(PLASMA UNIT).
w1 Regardless of normal or abnormal, a short beep is emitted once as the signal is received.
When POWER lamp flashes 1 to 5 times while PLASMA DEODORIZING / PLASMA AIR PURIFYING power failure mode is recalled.
F
Check of PLASMA DEODORIZING power
26
Page 27
When PLASMA/WASH lamp flashes 2-time.
After performing the check, make sure to release the failure mode recall function.
Make sure that the front panel is firmly closed. (Refer to 9-1.6 Figure 5)
1 While pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the
same time, press RESET button. 2 First, release RESET button. And release the other two buttons after all LCD except the set
temperature in operation display section of the remote
controller is displayed after 3 seconds. 3 Press OPERATE/STOP (ON/OFF) button (the set temperature
is displayed)
4 And press PLASMA button twice with the remote controller
headed towards the indoor unit. w1 PLASMA AIR PURIFYING operation is selected. wThe plasma power operation check mode is set.(Refer to 9-2.5.)
PLASMA AIR PURIFYING power supply is normal. Working of SAFETY DEVICE (PLASMA UNIT) due to uncomplete close of the front panel could cause 2-time flash.
Abnormal discharge may occur due to much dirt on the PLASMA unit, clean the unit. After cleaning, make sure to attach the unit since it is completely dry. If PLASMA AIR PURIFYING power operation check is performed with the plasma unit wet, protection gets active and PLASMA/WASH lamp blinks continuously as well.
w2 Turn PLASMA AIR PURIFYING power OFF and ON again.
(For turning OFF PLASMA AIR PURIFYING power, refer to 9-2.3.) (If it goes normal without turning OFF and ON, PLASMA/WASH lamp doesn't go OFF.)
Yes
No
No
Yes
Yes
No
9.5V DC is generated.
Yes
No
Replace the indoor electronic control P.C. board, after check of the wiring of CN1T1 on the indoor electronic control P.C. board.
High voltage (approx. -3.9kV) is generated during PLASMA AIR PURIFYING power operation. Pay careful attention and never touch PLASMA unit and the high-voltage lead part (red wire).
Yes
No
OFF
Continuously blinking.
OFF
Continuously blinking.
Does PLASMA/WASH lamp flash 2-time with unit stopping?
Turn ON the power supply.
Replace the indoor electronic control P.C. board.
Remove PLASMA AIR PURIFYING filter, firmly close the front panel, and then perform PLASMA AIR PURIFYING power operation check (w2). Does PLASMA/WASH lamp stay OFF, or continuously blink?
Does PLASMA/WASH lamp stay OFF, or continuously blink?
Turn OFF the power supply, and check the SAFETY DEVICE(PLASMA UNIT). Is it firmly fixed?
Work and Not-work the SAFETY DEVICE (PLASMA UNIT) using something like a screw driver, and measure the resistance between CN1T2 1 and 3 on the indoor electronic control P.C. board. Does the SAFETY DEVICE function?
Keep the SAFETY DEVICE(PLASMA UNIT) Not-work (close) using something like a screw driver. Turn ON the power supply. Is the voltage between CN1 1(+) and 2(GND) on the PLASMA POWER P.C. board (PLASMA AIR PURIFYING) 0V with the unit stopping? (Refer to 9-7.)
Set the plasma power failure mode recall function. (Refer to 9-2.2)
Replace the PLASMA POWER P.C. board (PLASMA AIR PURIFYING).
Replace the indoor electronic control P.C. board.
When PLASMA AIR PURIFYING power turns ON by pressing PLASMA button twice, is there
12.5V DC between CN11(+) and 2(GND)?
Replace the SAFETY DEVICE(PLASMA UNIT).
Firmly fix the SAFETY DEVICE(PLASMA UNIT).
PLASMA AIR PURIFYING operation
w1 Regardless of normal or abnormal, a short beep is emitted once as the signal is received.
When POWER lamp flashes 1 to 5 times while PLASMA DEODORIZING / PLASMA AIR PURIFYING power failure mode is recalled.
G
Check of PLASMA AIR PURIFYING power
27
Page 28
Is the connectors for the front panel driving motor unit connected? (Motor side or P.C. board side)
Front panel is normal.
Replace the front panel driving motor unit.
Does the front panel automatically open? (Does it start to move?)
Yes
Is the front panel held 10mm or more upper than the level line of the nozzle top?
Yes
No
Turn the remote controller ON.
Connect the connector and check from the start again.
Is the resistance between terminals of the front panel driving motor unit normal? (Refer to 9-5.)
Replace the indoor electric control P.C. board.
Replace the front panel driving motor unit.
Yes
No
No
Yes
No
Indoor unit and outdoor unit do not operate.
Check of auto front panel
H
10 mm or more
Z-Z side view
28
Page 29
Electromagnetic noise enters into TV sets or radios
Replace or repair the antenna. Replace or repair the coaxial cable.
No
No
No
Yes
Yes
No
No
Yes
Yes
Yes
Is the distance between the antennas and the indoor unit within 3m, or is the distance between the antennas and the outdoor unit within 3m?
Is the distance between the TV sets or radios and the indoor unit within 1m, or is the distance between the TV sets or radios and the outdoor unit within 3m?
Are the antennas damaged? Is the coaxial cable damaged? Is there any poor contact in the antenna wiring?
Is the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas close?
Even if all of the above conditions is fulfilled, the electromagnetic noise may enter, depending on the electric field strength or the installation condition (combination of specific conditions such as antennas or wiring). Check the followings before asking for service.
1.Devices affected by the electromagnetic noise TV sets, radios (FM/AM broadcast, shortwave)
2.Channel, frequency, broadcast station affected by the electromagnetic noise
3.Channel, frequency, broadcast station unaffected by the electromagnetic noise
4.Layout of ; indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, grounding wire, antennas, wiring from antennas, receiver
5.Electric field intensity of the broadcast station affected by the electromagnetic noise
6.Presence or absence of amplifier such as booster
7.Operation condition of air conditioner when the electromagnetic noise enters in.
1)Turn OFF the power supply once, and then turn ON the power supply. In this situation check for the electromagnetic noise.
2)Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button on the remote controller for power ON, and check for the electromagnetic noise.
3)After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the electromagnetic noise.
4)Press OPERATE/STOP (ON/OFF) button on the remote controller for power OFF, when the outdoor unit stops but the indoor/outdoor communication still runs on. In this situation check for the electromagnetic noise.
After checking the above, consult the service representative.
Is the unit earthed?
Earth the unit.
Extend the distance between the antennas and the indoor unit, and/or the antennas and the outdoor unit.
Extend the distance between the TV sets and/or radios and the indoor unit, or the TV sets or radios and the outdoor unit.
Extend the distance between the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas.
I
29
Page 30
Indoor coil thermistor [RT12 (MAIN), RT13 (SUB)] Room temperature thermistor (RT11)
Temperature (:)
Resistance (k")
9-7. Test point diagram and voltage
MSZ-FA25VA MSZ-FA35VA
Indoor electronic control P.C. board
Power supply input
SW P.C. Board
WASH reset switch(SW2)
Emergency operation switch(SW1)
230V AC
{
5V DC
12V DC
Cement resistance
(R111)
Indoor fan motor (CN211)
1311V DC
3(-) Fiducial terminal of
cathode side on measur­ing high-voltage DC
415
V DC
5(+)3-6V DC 6(+)0V DC or 15V DC
Interlock switch(Fan) (CN1R1)
Room temperature thermistor (CN111)
Varistor (NR11)
CN2011 (Used for check of con­ducting of thermal fuse)
Indoor coil thermistor RT12(MAIN) RT13(SUB) (CN112)
Plasma deodorizing/air purifying filter units (CN1T1)
12
34
Power monitor receiver P.C. board.
Plasma power P.C. board
High-voltage lead wire (Red)
i-see Sensor (CN110)
Release of Auto restart function Solder the Jumper wire to JR07.
(Refer to 8-3.)
1DC 2.5V during PLASMA
CN1
AIR PURIFYING/PLASMA DEODORIZING operation
2GND 3DC 12.5V during PLASMA
AIR PURIFYING/PLASMA DEODORIZING operation
Standard lead wire (Green)
Fuse (F11)
Front panel driving motor (CN1U1)
Safety device(Plasma unit) (CN1T2)
Horizontal and Vertical vane motor(CN151)
Timer short mode point JPG, JPS
}
(Refer to 8-1.)
30
Page 31
10
(1) Slide the sleeve and check if there is a locking lever or not.
(2) The terminal with this connector has the locking mechanism.
1Slide the sleeve. 2Pull the terminal while
pushing the locking lever.
1Hold the sleeve, and pull out the terminal slowly.
The terminal which has the locking mechanism can be detached as shown below. There are two types ( Refer to (1) and (2)) of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching.
<"Terminal with locking mechanism" Detaching points>
Connector
Sleeve
Locking lever
DISASSEMBLY INSTRUCTIONS
MSZ-FA25VA MSZ-FA35VA
OPERATING PROCEDURE
1. Removing the panel
(1) Press and unlock the knobs on both sides of the front
panel and lift the front panel until it is level, and then pull
the hinges forward to remove the front panel. (2) Remove the horizontal vane. (3) Remove the screw caps of the panel.
Remove the screws. (See Photo 1.) (4) Remove the screw of the front panel driving motor.
(See Photo 2.) (5) Hold the lower part of both ends on the panel and pull it
slightly toward you, and then remove the panel by pushing
it upward.
PHOTOS
Photo 1
Front panel
Screws of the panel
Horizontal vane
Photo 2
31
Screw of the front panel driving motor
Page 32
OPERATING PROCEDURE PHOTOS
2. Removing the electronic control P.C. board, the power monitor receiver P.C. board, i-see Sensor, SW P.C. board and the terminal block
(1) Remove the horizontal vane, the panel (Refer to 1.) and
the corner box.
(2) Remove the screw of the V.A. clamp, and then the
indoor/outdoor connecting wire.(See Photo 3.)
(3) Remove the switch holder from the electrical cover.
(See Photo 4.)
(4) Remove the screw of the electrical cover, and then the
electrical cover. (See Photo 4.)
(5) Remove the earth wire connected to the indoor electronic
control P.C. board from the electrical box. (See Photo 5.)
(6) Unhook the power monitor receiver P.C. board holder from
the catch. (See Photo 5.)
(7) Open the rear cover of the power monitor receiver P.C.
board holder and pull out the power monitor receiver P.C. board.
(8) Remove the screws of the i-see Sensor cover and the i-see
Sensor motor, and then the i-see Sensor motor. (9) Open the i-see Sensor holder and pull out the i-see Sensor. (10)
Open the switch holder and pull out SW P.C. board. (11)
Pull the electronic control P.C. board slightly toward you
from the electrical box, and disconnect TAB3 and all the
connectors on the electronic control P.C. board.
(LD101 and LD105 are direct-mounted to the electronic
control P.C. board.)
(12)
Pull out the electronic control P.C. board from the electrical
box.
(13)
Remove the earth wire connected to the heat exchanger
from the electrical box. (See Photo 5.)
(14)
Unhook the catches of the electrical box, and pull out the
electrical box.
(15)
Remove the screws of the terminal block cover, and then the terminal block cover and the terminal block holder. (See Photo 3.)
(16)
Remove the terminal block by sliding it.
3. Removing the electrical box
(1) Remove the horizontal vane, the panel (Refer to 1.) and the
corner box.
(2) Remove the screw of the V.A. clamp, and then the indoor/
outdoor connecting wire.(See Photo 3.)
(3) Remove the switch holder and the electrical cover.
(See Photo 4.)
(4) Remove the earth wire connected to the heat exchanger
from the electrical box.(See Photo 5.)
(5) Disconnect the following connectors on the electronic
control P.C. board; the fan motor connector <CN211>, the
indoor coil thermistor connector <CN112>, the vane motor
connector <CN151>, the connector of the interlock switch
(Fan) of the horizontal vane <CN1R1>, the connector of
the safety device (plasma unit) <CN1T2>, the connector of
the plasma power P.C. board <CN1T1>, the connector of
the front panel driving motor <CN1U1>.
(6) Unhook the catches of the electrical box, and pull out the
electrical box. (See Photo3.)
Photo 3
Screws of the terminal block cover
Drain hose
Photo 4
Photo 5
Power monitor receiver P.C. board holder
Earth wires
i-see Sensor
Screw of the V.A. clamp
Switch holder
Screw of the electrical cover.
Fan motor connector (CN211)
Connector of the interlock switch(Fan) (CN1R1)
Indoor coil thermistor connector (CN112)
Connector of the plasma power P.C.board(CN1T1)
Connector of the safety device(Plasma unit) (CN1T2)
Vane motor connector (CN151)
Connector of the front panel driving motor (CN1U1)
i-see Sensor cover
32
Page 33
OPERATING PROCEDURE PHOTOS
4. Removing the horizontal vane motor unit
(1) Remove the horizontal vane and the panel. (Refer to 1.) (2) Remove the screws of the horizontal vane motor unit,
and pull out the horizontal vane motor unit. (See Photo 6.)
(3) Disconnect the connector from the horizontal vane motor
unit.
5. Removing the vertical vane motor unit
(1) Remove the horizontal vane, the panel (Refer to 1.) and
the corner box.
(2) Pull out the drain hose from the nozzle assembly, and
remove the nozzle assembly. (See Photo 5.)
(3) Remove the crank of the vertical vane motor unit from the
arm of the vertical vane.(See Photo 7.)
(4) Remove the screws of the vertical vane motor unit, and pull
the vertical vane motor unit. (See Photo 7.)
Photo 6
Screw of the horizontal vane motor unit
Photo 7
Arm
Crank of the vertical vane motor unit
Screws of the vertical vane motor unit
6. Removing the indoor fan motor and the line flow fan
(1) Remove the horizontal vane, the panel (Refer to 1.) and
the corner box.
(2)
Remove the switch holder and the electrical box. (Refer to 3.)
(3) Pull out the drain hose from the nozzle assembly, and
remove the nozzle assembly. (4) Remove the screws fixing the motor bed. (5) Loosen the screw fixing the line flow fan. (6) Remove the motor bed together with fan motor and motor
band. (7) Release the hooks of the motor band, and remove the
motor band then pull out the indoor fan motor. (8) Remove the screws fixing the left side of the heat
exchanger. (9) Lift the heat exchanger, and pull out the line flow fan to the
lower-left.
(See Photo 10.)
(See Photo 8.)
(See Photo 9.)
Photo 9
Screw of the line flow fan
Photo 8
Screws of the motor bed
Photo 10
Screws of the left side of the heat exchanger
Motor band
33
Page 34
OPERATING PROCEDURE PHOTOS
7. Removing the plasma power P.C. board
(1) Remove the horizontal vane, the panel (Refer to 1.) and
the corner box.
(2) Remove the switch holder and the electrical cover.
(Refer to 3.)
(3) Disconnect the connector of the front panel driving motor
<CN1U1> from the electronic control P.C. board. (4) Remove the front panel driving motor. (5) Remove the screw of the plasma element holder, and remove
the plasma element holder from the heat exchanger.
(See Photo 11.) (6) Unhook all the catches of plasma unit cover and remove
the plasma unit cover. (See Photo 12.) (7) Remove the terminals with locking mechanism connected
to the plasma power P.C. board and the safety device
(Plasma unit). (See Photo 13.) (8) Remove the plasma electrical box from the plasma element
holder. (9) Remove the screw fixing the plasma electrical box, and
open the plasma electrical box then pull out the plasma
power P.C. board from the plasma electrical box.
(See Photo 13.)
Photo 11
Photo 12
Screw of the plasma element holder
Plasma unit cover
Front panel driving motor
Photo 13
Terminal
Safety device (Plasma unit)
Terminal
Screw of the plasma electrical box
Plasma power P.C. board
Terminal
Terminal
34
Page 35
PARTS LIST (non-RoHS compliant)11
No.
Part No.
Part name
Remarks
Symbol
in Wiring
Diagram
Q'ty/unit
1 2
3 4 5 6
7 8
MSZ-FA25VA-
E1
9
10
REMOTE CONTROLLER REMOTE CONTROLLER HOLDER
KM05A
BOX BOX PANEL ASSEMBLY SCREW CAP FRONT PANEL AIR FILTER (LEFT) AIR FILTER (RIGHT) CORNER BOX (RIGHT) CORNER BOX (RIGHT) INSTALLATION PLATE
Including No.3,4 2PCS/SET
E2
MSZ-FA35VA-
E1 E2
1
1 2 1 1 1 1
1
1 1 2 1 1 1
1 1
1 1 2 1 1 1
1 1
1
1 2 1 1 1 1
1
E02 897 234 E02 A32 234 E02 913 000 E02 913 067 E02 913 010 E02 914 100 E02 913 100 E02 913 975 E02 A32 975 E02 913 970
1 1
1 1
1 1
1 1
E02 913 426 E02 527 083
MSZ-FA25VA MSZ-FA35VA 11-1. INDOOR UNIT STRUCTURAL PARTS
11-2. ACCESSORY AND REMOTE
CONTROLLER
1
2
3
4
5
11-1. INDOOR UNIT STRUCTURAL PARTS
8
9
10
7
6
11-2. ACCESSORY AND REMOTE CONTROLLER
35
Page 36
PARTS LIST (non-RoHS compliant)
MSZ-FA25VA MSZ-FA35VA
11-3. INDOOR UNIT ELECTRICAL PARTS
AND FUNCTIONAL PARTS
30
1
29
27
26
25
24
20
32
7
28
22
21
23
18
17
16
15
14
2
3 4
5
6
8
31
18
11
12
11-4. INDOOR UNIT HEAT EXCHANGER
34
35
13
33
36
10
9
18
19
Page 37
BEARING MOUNT SLEEVE BEARING DRAIN HOSE NOZZLE ASSEMBL Y VANE MOTOR UNIT (HORIZONTAL) INTERLOCK SWITCH(FAN) VANE MOTOR UNIT (VERTICAL) HORIZONTAL VANE FUSE VARISTOR POWER MONITOR RECEIVER P.C. BOARD HOLDER i-see Sensor i-see Sensor MOTOR VA CLAMP TERMINAL BLOCK COVER TERMINAL BLOCK HOLDER TERMINAL BLOCK ELECTRONIC CONTROL P.C. BOARD W1 ELECTRONIC CONTROL P.C. BOARD W1 ROOM TEMPERATURE THERMISTOR INDOOR COIL THERMISTOR INDOOR COIL THERMISTOR SWITCH HOLDER INDOOR FAN MOTOR W2 MOTOR BAND FRONT PANEL DRIVING MOTOR LINE FLOW FAN PLASMA ELEMENT HOLDER PLASMA UNIT COVER PLASMA ELECTRICAL BOX PLASMA POWER P.C. BOARD SAFETY DEVICE (PLASMA UNIT) PLASMA AIR PURIFYING FILTER UNIT PLASMA DEODORIZING FILTER UNIT
UP & DOWN
RIGHT & LEFT
T3.15AL250V
AUTO RESTART AUTO RESTART
RC0J40- or RC0J30-
MV1
MV2
F11
NR11
RR MT
TB
RT11 RT12, RT13 RT12, RT13
MF
MP
PLASMA_A PLASMA_D
No. Part No.
Part name
Remarks
Symbol
in Wiring
Diagram
Q'ty/unit
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17
18 19 20 21
22 23 24 25 26 27 28 29 30 31 32
MSZ-FA25VA-
E1 E2
MSZ-FA35VA-
E1 E2
33 34
35
INDOOR HEAT EXCHANGER INDOOR HEAT EXCHANGER UNION (GAS) UNION (LIQUID)
{9.52 {6.35
E02 751 509 E02 001 504 E02 897 702 E02 913 235 E02 897 303 E02 897 316 E02 913 303 E02 913 040 E02 A49 382 E02 661 385 E02 913 095 E02 913 391 E02 914 303 E02 897 784 E02 897 780 E02 897 779 E02 913 375 E02 913 452 E02 914 452 E02 897 308 E02 913 307 E02 914 307 E02 913 782 E02 915 300 E02 897 333 E02 898 303 E02 897 302 E02 913 775 E02 913 776 E02 913 777 E02 897 440 E02 898 316 E02 913 774 E02 914 774
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1
1 1 1 1 1 1 1 1 2 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1
1 1 1 1 1 1 1 1 2 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1
1 1 1 1 1 1 1 1 1 2 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1
1 1 1 1 1 1 1 1 1 2 1 1 1
E02 913 620 E02 914 620 E02 815 666 E02 151 667
1
1 1
1
1 1
1 1 1
1 1 1
W1 Including SW P.C. BOARD and POWER MONITOR RECEIVER P.C. BOARD W2 Including FAN MOTOR RUBBER MOUNT (2 PCS/SET)
PARTS LIST (non-RoHS compliant)
11-3. INDOOR UNIT ELECTRICAL PARTS AND FUNCTIONAL PARTS
11-4. INDOOR UNIT HEAT EXCHANGER
37
Page 38
38
Page 39
RoHS PARTS LIST (RoHS compliant)12
No.
Part No.
Part name
Remarks
Symbol
in Wiring
Diagram
Q'ty/unit
1 2 3 4 5 6 7 8
G G G G G G G G
MSZ-FA25VA-
E2
910G
G
REMOTE CONTROLLER REMOTE CONTROLLER HOLDER
KM05A
BOX PANEL ASSEMBLY SCREW CAP FRONT PANEL AIR FILTER (LEFT) AIR FILTER (RIGHT) CORNER BOX (RIGHT) INSTALLATION PLATE
Including No.3,4 2PCS/SET
E3
MSZ-FA35VA-
E2 E3
1 1 2 1 1 1 1 1
1 1 2 1 1 1 1 1
1 1 2 1 1 1 1 1
1 1 2 1 1 1 1 1
E12 A32 234 E12 913 000 E12 913 067 E12 913 010 E12 914 100 E12 913 100 E12 A32 975 E12 913 970
1 1
1 1
1 1
1 1
E12 913 426 E12 527 083
RoHS
MSZ-FA25VA MSZ-FA35VA 12-1. INDOOR UNIT STRUCTURAL PARTS
12-2. ACCESSORY AND REMOTE
CONTROLLER
1
2
3
4
5
12-1. INDOOR UNIT STRUCTURAL PARTS
8
9
10
7
6
12-2. ACCESSORY AND REMOTE CONTROLLER
39
Page 40
RoHS PARTS LIST (RoHS compliant)
MSZ-FA25VA MSZ-FA35VA
12-3. INDOOR UNIT ELECTRICAL PARTS
AND FUNCTIONAL PARTS
30
1
29
27
26
25
24
20
32
7
28
22
21
23
18
17
16 15
14
2
3 4
5
6
8
31
18
11
12
12-4. INDOOR UNIT HEAT EXCHANGER
34
35
13
33
40
10
9
18
19
Page 41
RoHS PARTS LIST (RoHS compliant)
12-3. INDOOR UNIT ELECTRICAL PARTS AND FUNCTIONAL PARTS
Symbol
No. Part No.
RoHS
G
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17
18
19 20 21
22 23 24 25 26 27 28 29 30 31 32
W1 Including SW P.C. BOARD and POWER MONITOR RECEIVER P.C. BOARD W2 Including FAN MOTOR RUBBER MOUNT (2 PCS/SET)
E12 751 509
G
E12 001 504
G
E12 897 702
G
E12 913 235
G
E12 897 303
G
E12 897 316
G
E12 913 303
G
E12 913 040
G
E12 A49 382
G
E12 661 385
G
E12 913 095
G
E12 913 391
G
E12 914 303
G
E12 897 784
G
E12 897 780
G
E12 897 779
G
E12 913 375
G
E12 913 452
G
E12 914 452
G
E12 B42 452
G
E12 B43 452
G
E12 897 308
G
E12 913 307
G
E12 914 307
G
E12 913 782
G
E12 915 300
G
E12 897 333
G
E12 898 303
G
E12 897 302
G
E12 913 775
G
E12 913 776
G
E12 913 777
G
E12 897 440
G
E12 898 316
G
E12 913 774
G
E12 914 774
BEARING MOUNT SLEEVE BEARING DRAIN HOSE NOZZLE ASSEMBL Y VANE MOTOR UNIT (HORIZONTAL) INTERLOCK SWITCH(FAN) VANE MOTOR UNIT (VERTICAL) HORIZONTAL VANE FUSE VARISTOR POWER MONITOR RECEIVER P.C. BOARD HOLDER i-see Sensor i-see Sensor MOTOR VA CLAMP TERMINAL BLOCK COVER TERMINAL BLOCK HOLDER TERMINAL BLOCK ELECTRONIC CONTROL P.C. BOARD W1 ELECTRONIC CONTROL P.C. BOARD W1 ELECTRONIC CONTROL P.C. BOARD W1 ELECTRONIC CONTROL P.C. BOARD W1 ROOM TEMPERATURE THERMISTOR INDOOR COIL THERMISTOR INDOOR COIL THERMISTOR SWITCH HOLDER INDOOR FAN MOTOR W2 MOTOR BAND FRONT PANEL DRIVING MOTOR LINE FLOW FAN PLASMA ELEMENT HOLDER PLASMA UNIT COVER PLASMA ELECTRICAL BOX PLASMA POWER P.C. BOARD SAFETY DEVICE (PLASMA UNIT) PLASMA AIR PURIFYING FILTER UNIT PLASMA DEODORIZING FILTER UNIT
Part name
in Wiring
Diagram
MV1
MV2
F11
NR11
RR MT
TB
RT11 RT12, RT13 RT12, RT13
MF
MP
PLASMA_A PLASMA_D
MSZ-FA25VA-
E2 E3
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1
1 1 1 1 1 1 1 1 2 1 1 1
Q'ty/unit
MSZ-FA35VA-
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1
1 1
1 1 1 1 1 1 1 1 2 1 1 1
E2 E3
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1
1
1 1 1 1 1 1 1 1 1 2 1 1 1
Remarks
1 1 1 1
UP & DOWN
1 1
RIGHT & LEFT
1 1
T3.15AL250V
1 1 1 1 1 1 1 1 1
AUTO RESTART AUTO RESTART AUTO RESTART AUTO RESTART
1 1
1 1
RC0J40- or RC0J30-
1 1 1 1 1 1 1 2 1 1 1
12-4. INDOOR UNIT HEAT EXCHANGER
33 34
35
G
E12 913 620
G
E12 914 620
G
E12 815 666
G
E12 151 667
INDOOR HEAT EXCHANGER INDOOR HEAT EXCHANGER UNION (GAS) UNION (LIQUID)
41
1
1 1
1
1 1 1
1
1
1
{9.52
1
{6.35
1
Page 42
13 OPTIONAL PARTS
(1)
(2)
Deodorizing ceramic filter
MAC-305FT-E
Model Part No.
MSZ-FA25VA MSZ-FA35VA
MAC-093SS-E
Model Part No.
MSZ-FA25VA MSZ-FA35VA
Heat exchanger
13-1. DEODORIZING CERAMIC FILTER
Replacement of the deodorizing ceramic filter(about once every 6 years)
Deodorizing ceramic filter is installed inside PLASMA DEODORIZING filter unit. The filter is fragile. Handle it with care. NOTE: PLASMA DEODORIZING filter unit may not operate properly if the deodorizing ceramic filter is not installed.
Be sure to install the deodorizing ceramic filter.
(1) Release the two knobs to open the filter unit. (2) Pull the side knobs to outward and then
forward to remove, as illustrated below.
(3) Pull out the deodorizing ceramic filter from the side of
the filter unit.
(4) Install the deodorizing ceramic filter by following the
removal procedure in reverse.
13-2. QUICK CLEAN KIT
You can sweep the surface of heat exchanger if you install the special-made brush to your vacuum cleaner.
42
Page 43
43
Page 44
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
CC
Copyright 2005 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD Distributed in May 2006. No. OB371 REVISED EDITION-B 6 Distributed in Jan. 2006. No. OB371 REVISED EDITION-A 6 Distributed in Jan. 2005. No. OB371 6 Made in Japan
New publication, effective May 2006 Specifications subject to change without notice.
Loading...