Mitsubishi Electronics MSY-GE15NA, MSY-GE12NA, MSY18NA, MSY-GE09NA, MSZGE15NA User Manual

...
SPLIT-TYPE AIR CONDITIONERS
INDOOR UNIT
SERVICE MANUAL
Models
MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA
No. OBH548
MSZ-GE18NA MSY-GE09NA MSY-GE12NA MSY-GE15NA MSY-GE18NA
Outdoor unit service manual
MUZ-GENA MUY-GENA Series (OBH549)
MXZ-A·NA Series (OB444)
CONTENTS
1. TECHNICAL CHANGES
2. PART NAMES AND FUNCTIONS ·····················2
3. SPECIFICATION ················································ 3
4. OUTLINES AND DIMENSIONS ························5
6. REFRIGERANT SYSTEM DIAGRAM ···············7
7. SERVICE FUNCTIONS ·····································8
8. MICROPROCESSOR CONTROL ···················10
10. DISASSEMBLY INSTRUCTIONS ···················· 28
·······································
2
NOTE:
RoHS compliant products have <G> mark on the spec name plate.
PARTS CATALOG (OBB548)
1
TECHNICAL CHANGES
MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NA MSY-GE09NA MSY-GE12NA MSY-GE15NA MSY-GE18NA
1. New model
2
PART NAMES AND FUNCTIONS
MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NA MSY-GE09NA MSY-GE12NA MSY-GE15NA MSY-GE18NA
Air lter (Catechin air filter)
Air cleaning filter (Anti-Allergy Enzyme Filter)
Air inlet
Air outlet
Horizontal vane
Remote control receiving section
Front panel
Heat exchanger
Remote controller
ACCESSORIES
Installation plate 1 Installation plate fi xing screw 4 × 25 mm 5 Remote controller holder 1 Fixing screw for 3.5 × 1.6 mm (Black) 2 Battery (AAA) for remote controller 2 Wireless remote controller 1 Felt tape (Used for left or left-rear piping) 1
Operation indicator lamp
Emergency operation switch (E.O. SW)
2
3
SPECIFICATION
Indoor model MSZ-GE06NA
Power supply V, phase, Hz 208/230, 1, 60 Max. fuse size (time delay)/ Disconnect switch Min. circuit ampacity A 1.0 Fan motor F.L.A 0.76
Airfl ow Super High - High - Med. ­Low - Quiet
Moisture removal pt./h 1.5 2.5 Sound level
Super High - High - Med. ­Low - Quiet
Cond. drain connection O.D. in. 5/8
Dimensions
Weight Ib. 22 External fi nish Munsell 1.0Y 9.2/0.2 Control voltage (by built-in transformer) 12 - 24 VDC
Indoor model
Power supply V, phase, Hz 208/230, 1, 60 Max. fuse size (time delay)/ Disconnect switch Min. circuit ampacity A 1.0 Fan motor F.L.A 0.76
Airfl ow Super High - High - Med. ­Low - Quiet
Moisture removal pt./h 2.7 4.6 Sound level
Super High - High - Med. ­Low - Quiet
Cond. drain connection O.D. in. 5/8
Dimensions
Weight Ib. 22 External fi nish Munsell 1.0Y 9.2/0.2 Control voltage (by built-in transformer) 12 - 24 VDC
NOTE: Test conditions are based on ARI 210/240.
COOL Dry
HEAT Dry CFM 406-321-233-170-145 406-321-237-170-145
Cooling dB(A)
Heating dB(A) 43-37-30-22-19
W D 9-1/8 H 11-5/8
COOL Dry
HEAT Dry CFM 463-367-304-247-205 512-431-339-275-230
Cooling dB(A) 49-44-38-32-26 49-44-38-33-28
Heating dB(A) 46-40-35-30-26 48-43-38-33-28
W D 9-1/8 H 11-5/8
A15
CFM
(Wet)
43-37-30-22-19
in.
MSZ-GE15NA MSY-GE15NA
A15
(Wet)
CFM
in.
533-420-335-272-205
(498-385-300-237-170)
MSZ-GE09NA MSY-GE09NA
399-321-237-170-145
(364-286-201-134-109)
31-7/16
533-420-339-275-230
( 498-385-304-240-194)
31-7/16
MSZ-GE12NA MSY-GE12NA
45-37-30-22-19
MSZ-GE18NA MSY-GE18NA
3
3-1. OPERATING RANGE
(1) POWER SUPPLY
Rated voltage Guaranteed voltage (V)
Min. 187
Indoor unit
208/230 V
1 phase
60 Hz
(2) OPERATION
Mode Condition
Standard temperature 80 67 95
Cooling
Heating
Maximum temperature 90 73 115 — Minimum temperature 67 57 14 — Maximum humidity 78% — Standard temperature 70 60 47 43 Maximum temperature 80 67 75 65 Minimum temperature 70 60 -4 -5
3-2. OUTLET AIR SPEED AND COVERAGE
Model Mode Function
HEAT Dry 406 20.6 29.5
MSZ-GE06NA
MSZ-GE09NA MSY-GE09NA
MSZ-GE12NA MSY-GE12NA
MSZ-GE15NA MSY-GE15NA
MSZ-GE18NA MSY-GE18NA
COOL
HEAT Dry 406 20.6 29.5
COOL
HEAT Dry 406 20.6 29.5
COOL
HEAT Dry 463 23.4 33.5
COOL
HEAT Dry 512 25.9 36.9
COOL
Dry 321 16.3 23.5
Wet 286 14.5 21.0
Dry 321 16.3 23.5
Wet 286 14.5 21.0
Dry 321 16.3 23.5
Wet 286 14.5 21.0
Dry 420 21.3 30.5
Wet 385 19.5 28.0
Dry 420 21.3 30.5
Wet 385 19.5 28.0
Airfl ow
(CFM)
208 230
Indoor Outdoor
DB WB DB WB
Air speed
(ft./s.)
Max. 253
Intake air temperature (°F)
Coverage
The air coverage is the figure up to the
(ft.)
position where the air speed is 1 ft./s., when air is blown out horizontally from the unit properly at the High speed posi­tion.
The coverage should be used only as a
general guideline since it varies accord­ing to the size of the room and furniture arranged inside the room.
4
4
OUTLINES AND DIMENSIONS
MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NA MSY-GE09NA MSY-GE12NA MSY-GE15NA MSY-GE18NA
3/16
2-3/4
1-3/4
2- 5/16
2-3/16
6 - 1/4
9-1/8
3/4
11-5/8
1-11/16
2-3/16
7/16×1 Oblong hole
Installation plate
31-7/16
30-15/16 1/4
Indoor unit
5-1/824-3/81-15/16
1-15/16
3-1/8
10
8-3/8
1-5/8
5/16
3-15/16
Air out
Insulation ø1 - 3/8 O.D
1-5/8
Liquid line ø1/4 19 - 11/16 (Flared connection ø1/4)
Gas line ø3/8 16 - 15/16
Piping
Drain hose Insulation ø1-1/8 O.D Connected part ø5/8 O.D
8-7/8 8-7/8
6-1/8 6-1/8
13-5/162-3/8
13-9/16 2-1/8
Air in
Installation plate
Piping
1-5/8
4/3/16
4-3/8
(Flared connection: ø3/8 (GE06/09/12NA), ø1/2 (GE15/18NA))
2-3/16
7/16×13/16 Oblong hole
3-1/8
Wall hole ø2-9/16
Drain hose
2-11/16
Unit: inch
7/8
9-15/16
9-1/8
8-5/16
1/8
1-5/8
5
5
MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NA MSY-GE09NA MSY-GE12NA MSY-GE15NA MSY-GE18NA
WIRING DIAGRAM
6
6
REFRIGERANT SYSTEM DIAGRAM
MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NA MSY-GE09NA MSY-GE12NA MSY-GE15NA MSY-GE18NA
Refrigerant pipe ø3/8 (MSZ-GE06/09/12NA, MSY-GE09/12NA) ø1/2 (MSZ-GE15/18NA, MSY-GE15/18NA) (with heat insulator)
Indoor heat exchanger
Room temperature thermistor RT11
Indoor coil thermistor RT12 (main)
Indoor coil thermistor RT13 (sub)
Flared connection
Flared connection
Refrigerant pipe ø1/4 (with heat insulator)
Unit: inch
Refrigerant flow in cooling Refrigerant flow in heating
7
7
SERVICE FUNCTIONS
MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NA MSY-GE09NA MSY-GE12NA MSY-GE15NA MSY-GE18NA
7-1. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS the indoor electronic control P.C. board. The time will be shortened as follows. (Refer to 9-7.) Set time: 1-minute 1-second Set time: 3-minute 3-second (It takes 3 minutes for the compressor to start operation. However, the starting time is shortened by short circuit of JPG and JPS.)
7-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room. In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be modified according to the number of the indoor unit.
How to modify the remote controller P.C. board
Remove batteries before modification. The board has a print as shown below:
NOTE: For modification, take out the batteries and
press the OPERATE/STOP (ON/OFF) button twice or 3 times at first.
After finish modification, put back the batteries
then press the RESET button.
J1
J2
The P.C. board has the print “J1” and “J2”. Solder “J1” and “J2” according to the number of indoor unit as shown in Table 1. After modification, press the RESET button.
Table 1
1 unit operation 2 units operation 3 units operation 4 units operation
No. 1 unit No modifi cation Same as at left Same as at left Same as at left
No. 2 unit Solder J1 Same as at left Same as at left
No. 3 unit Solder J2 Same as at left
No. 4 unit Solder both J1 and J2
How to set the remote controller exclusively for particular indoor unit
After you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as the remote controller for the indoor unit. The indoor unit will only accept the signal from the remote controller that has been assigned to the indoor unit once they are set. The setting will be cancelled if the breaker has turned OFF, or the power supply has shut down. Please conduct the above setting once again after the power has restored.
8
7-3. AUTO RESTART FUNCTION
When the indoor unit is controlled with the remote controller, the operation mode, the set temperature, and the fan speed are memorized by the indoor electronic control P.C. board. “AUTO RESTART FUNCTION” automatically starts operation in the same mode just before the shut-off of the main power.
Operation
If the main power has been cut, the operation settings remain. After the power is restored, the unit restarts automatically according to the memory.
(However, it takes at least 3 minutes for the compressor to start running.)
How to release “AUTO RESTART FUNCTION”
Turn OFF the main power of the unit. Solder the Jumper wire JR07 on the indoor electronic control P.C. board. (Refer to 9-7.)
Indoor electronic control P.C. board
JR07
CN 111CN112CN151CN10A
NOTE:
The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the
remote controller.
If main power is turned OFF or a power failure occurs while AUTO START/STOP timer is active, the timer setting is
cancelled.
If the unit has been OFF with the remote controller before power failure, the auto restart function does not work as
the power button of the remote controller is OFF.
To prevent breaker OFF due to the rush of starting current, systematize other home appliance not to turn ON at the
same time.
When some air conditioners are connected to the same supply system, if they are operated before power failure, the
starting current of all the compressors may flow simultaneously at restart.
Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting
current by adding to the system that allows the units to start one by one.
9
8
MICROPROCESSOR CONTROL
MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NA MSY-GE09NA MSY-GE12NA MSY-GE15NA MSY-GE18NA
WIRELESS REMOTE CONTROLLER
Signal transmitting section
Operation display section
OPERATE/STOP (ON/OFF) button
Temperature buttons
E.g.: MSZ type
FAN SPEED CONTROL button
OPERATION SELECT button
ECONO COOL button
VANE CONTROL button
SMART SET button
RESET button
Indication of remote controller model is on back
OFF TIMER button
ON TIMER button
TIME SET buttons FORWARD button BACKWARD button
CLOCK SET button
NOTE: Last setting will be stored after the unit is turned OFF with the remote controller. Indoor unit receives the signal of the
remote controller with beeps.
INDOOR UNIT DISPLAY SECTION
Operation Indicator lamp
The operation indicator at the right side of the indoor unit indicates the operation state.
• The following indication applies regardless of shape of the indication.
Indication Operation state Room temperature
The unit is operating to reach the set temperature
The room temperature is approaching the set tem­perature
Standby mode (Only during multi system operation)
About 4°F(2°C) or more away from set tempera­ture
About 2 to 4°F(1 to 2°C) from set temperature
-
Lighted
Blinking
Not lighted
10