Mitsubishi Electronics MSY-A15NA, MSZ-A15NA, MSZ-A09NA, MSY-A17NA, MSZ-A17NA User Manual

...
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
Revision B:
• MSZ-A•NA- and MSY-A•NA- have been added.
Please void OB450 REVISED EDITION-A.
INDOOR UNIT
No. OB450
SERVICE MANUAL
REVISED EDITION-B
Wireless type Models
MSZ-A09NA MSZ-A24NA MSZ-A09NA - MSZ-A24NA -
11
11
MSZ-A12NA MSY-A15NA MSZ-A12NA - MSY-A15NA ­MSZ-A15NA MSY-A17NA MSZ-A15NA - MSY-A17NA ­MSZ-A17NA MSY-A24NA MSZ-A17NA - MSY-A24NA -
Outdoor unit service manual
MUZ-A·NA Series (OB451) MXZ-A·NA Series (OB444)
CONTENTS
1. TECHNICAL CHANGES ····································2
2. PART NAMES AND FUNCTIONS······················3
3. SPECIFICATION·················································4
4. OUTLINES AND DIMENSIONS·························6
5. WIRING DIAGRAM ············································8
6. REFRIGERANT SYSTEM DIAGRAM················9
MSZ-A09NA MSY-A15NA MSZ-A12NA MSY-A17NA MSZ-A15NA MSZ-A17NA
7. SERVICE FUNCTIONS ····································10
8. TROUBLESHOOTING ······································11
10. PARTS LIST······················································30 10-1. PARTS LIST ·············································30 10-2. RoHS PARTS LIST··································36
11. MICROPROCESSOR CONTROL·····················42
11
11
11
NOTE:
RoHS compliant products have <G> mark on the spec name plate. For servicing of RoHS compliant products, refer to the PARTS LIST (RoHS compliant).
Remote controller
KM06A
KM07J KM06B KM07K KM06C KM07L KM06D
KM07M
Temperature indication
_F
_F/ _C
_F
_F/ _C
_F
_F/ _C
_F
_F/ _C
MSZ-A09/12/15/17NA MSZ-A09/12/15/17NA­MSZ-A24NA MSZ-A24NA­MSY-A15/17NA MSY-A15/17NA­MSY-A24NA MSY-A24NA-
Models
Revision A :
PARTS LIST has been revised. (10-1.8, 10-2.8)
Revision B :
MSZ-ANA- and MSY-A•NA- Remote controller has been changed.
1
TECHNICAL CHANGES
MSZ09UN MSZ-A09NA MSZ12UN MSZ-A12NA MSH15TN MSZ-A15NA MSH17TN MSZ-A17NA
1.Control method between indoor and outdoor has been changed.
2.Indoor fan motor has been changed.
3.Signal of remote controller has been changed. (It is not available for conventional models.)
MSZ-A09NAMSZ-A09NA- MSZ-A12NAMSZ-A12NA- MSZ-A15NAMSZ-A15NA- MSZ-A17NAMSZ-A17NA-
11
MSH24WN MSZ-A24NA MS15TN MSY-A15NA MS17TN MSY-A17NA MS24WN MSY-A24NA
1
MSZ-A24NAMSZ-A24NA
1
MSY-A15NAMSY-A15NA-
1
MSY-A17NAMSY-A17NA-
1
MSY-A24NAMSY-A24NA-
1
-
1
1
1
1.Remote controller has been changed.
• Temperature indication function (_F/_C) has been added. (Refer to 11-10.)
• Timer indication has been changed. (AM/PM indication)
2.Conduit plate has been removed. (MSZ-A09/12/15/17,MSY-A15/17)
3.Conduit cover, terminal block cover and terminal block holder have been changed. (MSZ-A09/12/15/17,MSY-A15/17)
2
2
Line flow fan
Air outlet Vertical vane
Air inlet
Display section
Front panel
Panel
Heat exchanger
Horizontal vane
Operation section
(When the front panel is opened)
Remote controller
Remote control receiving section
Catechin air filter
Air cleaning filter (Anti-Allergy Enzyme Filter, Blue bellows type)
Emergency operation switch
Emergency operation switch
Operation indicator lamp
Remote control
receiving section
Operation Indicator lamp
1 2 3 4 5 6 7 8
Installation plate Installation plate fixing screw 4 o 25 mm Remote controller holder Fixing screw for 3 o 3.5 o 1.6 mm (Black) Battery (AAA) for remote controller Wireless remote controller Felt tape (Used for left or left-rear piping) Conduit plate
1 7 1 2 2 1 1
1 8 1 2 2 1 1 1
MSZ-A24NA MSY-A24NA
MSZ-A09/12/15/17NA
MSY-A15/17NA
1 5 1 2 2 1 1
MSZ-A09/12/15/17NA- 1
MSY-A15/17NA- 1
PART NAMES AND FUNCTIONS
MSZ-A09NA MSY-A15NA MSZ-A12NA MSY-A17NA MSZ-A15NA MSZ-A17NA
MSZ-A09NA MSZ-A12NA MSZ-A15NA MSZ-A17NA MSY-A15NA MSY-A17NA
MSZ-A24NA MSY-A24NA
MSZ-A24NA MSY-A24NA
ACCESSORIES
3
3
Item
Model
MSZ-A12NA
Indoor unit model External finish Power supply Max. fuse size (time delay)/ Disconnect switch Min. circuit ampacity Fan motor
Airflow LowMed.High Moisture removal
Sound level Low-Med.-High Cond. drain connection O.D.
Dimensions Weight
Remote controller Control voltage (by built-in transformer)
V, phase, Hz
A A
F.L.A
CFM CFM
pt./h
dB(A)
in. in. in. in. Ib.
MSZ-A12NA
1.0
0.76
353-240-159
353(318)-240(215)-152(134)
3.2
22-34-42
23
MSZ-A09NA
1.0
0.76
307-222-159
307(275)-229(205)-152(134)
2.3
22-33-38
23
White
208/230, 1, 60
15
5/8
30-11/16
8-1/4
11-3/4
Wireless type
12-24V DC
MSZ-A09NA
HEAT Dry COOL Dry (Wet)
W D H
Item
Model
MSZ-A17NA MSY-A17NA
Indoor unit model External finish Power supply Max. fuse size (time delay)/ Disconnect switch Min. circuit ampacity Fan motor
Airflow LowMed.High Moisture removal
Sound level Low-Med.-High Cond. drain connection O.D.
Dimensions Weight
Remote controller Control voltage (by built-in transformer)
V, phase, Hz
A A
F.L.A
CFM CFM
pt./h
dB(A)
in. in. in. in. Ib.
1.0
0.76
381(342)-328(293)-268(240)
5.1
23
1.0
0.76
381(342)-328(293)-268(240)
4.7
23
381-314-254
34-40-45/34-38-44—34-40-45/
381-314-254
34-40-46/34-38-44—34-40-46/
White
208/230, 1, 60
15
5/8
30-11/16
8-1/4
11-3/4
Wireless type
12-24V DC
MSZ-A15NA MSY-A15NA
HEAT Dry COOL Dry (Wet)
W D H
HEAT Dry COOL Dry (Wet)
W D H
Item
Model
MSY-A24NA
Indoor unit model External finish Power supply Max. fuse size (time delay)/ Disconnect switch Min. circuit ampacity Fan motor
Airflow LowMed.High Moisture removal
Sound level Low-Med.-High Cond. drain connection O.D.
Dimensions Weight
Remote controller Control voltage (by built-in transformer)
V, phase, Hz
A A
F.L.A
CFM CFM
pt./h
dB(A)
in. in. in. in. Ib.
MSY-A24NA
1.0
0.76
568(508)-431(385)-296(265)
7.3
34-40-49/
37
MSZ-A24NA
1.0
0.76
568-486-296
568(508)-431(385)-296(265)
7.3
34-40-49/34-40-48
37
White
208/230, 1, 60
15
5/8
43-5/16
10-1/4
12-13/16
Wireless type
12-24V DC
MSZ-A24NA
(Cooling/Heating)
(Cooling/Heating)
MSZ-A15NA MSY-A15NA MSZ-A17NA MSY-A17NA
-
-
-
SPECIFICATION
NOTE : Test conditions are based on ARI 210/240.
1 : Rating conditions (cooling) Indoor : 80˚FDB, 67˚FWB, Outdoor : 95˚FDB, (75˚FWB)2 : (heating) Indoor : 70˚FDB, 60˚FWB, Outdoor : 17˚FDB, 15˚FWB
(heating) Indoor : 70˚FDB, 60˚FWB, Outdoor : 47˚FDB, 43˚FWB
4
3-1. OPERATING RANGE
MSZ-A09NA MSY-A15NA MSZ-A12NA MSY-A17NA MSZ-A15NA MSY-A24NA MSZ-A17NA MSZ-A24NA
Rated voltage Guaranteed VoltageModel
Min. 198V Max. 253V
208V
230V
208/230V 1phase 60Hz
78%
Function
Cooling
Heating
Standard temperature
Maximum temperature
Minimum temperature
Maximum humidity
Standard temperature
Maximum temperature
Minimum temperature
DB (˚F)
80 95 67
70 80 70
WB (˚F)
67 71 57
60 67 60
Indoor
DB (˚F)
95
115
14
47 75 14
WB (˚F)
— — —
43 65 13
Outdoor
Condition
Intake air temperature
(1) POWER SUPPLY
(2) OPERATION
3-2. OUTLET AIR SPEED AND COVERAGE RANGE
Model
MSZ-A09NA
MSZ-A12NA
MSZ-A15NA MSZ-A15NA MSY-A15NA MSZ-A17NA MSZ-A17NA MSY-A17NA MSZ-A24NA MSZ-A24NA MSY-A24NA
Mode
HEAT COOL
HEAT COOL HEAT COOL HEAT COOL HEAT COOL
Function
Dry Dry
Wet
Dry Dry
Wet
Dry Dry
Wet
Dry Dry
Wet
Dry Dry
Wet
Air flow
(CFM)
Air speed
(ft./sec.)
307 307 275 353 353 318 381 381 342 381 381 342 568 568 508
16.8
16.8
15.1
19.3
19.3
17.4
20.9
20.9
18.8
20.9
20.9
18.8
20.2
20.2
18.1
5
Coverage range (ft.)
23.4
23.4
21.0
26.7
26.7
24.1
28.8
28.8
26.0
28.8
28.8
26.0
34.4
34.4
30.9
The air coverage range is the figure up to the position where the air speed is 1 ft./sec., when air is blown out horizon­tally from the unit properly at the High speed position. The coverage range should be used only as a general guideline since it varies according to the size of the room and furniture arranged inside the room.
4
11-3/4
424-9/16
30-11/16
8-1/4
3/16
2-1/8
3/4
6-1/4
2-5/16
Air in
Air out
Installation plate
Insulation [1-1/8
Drain hose [5/8 (Connected part O.D)
Liquid line [1/4 19-11/16 Gas line [3/8 16-15/16 Insulation [1-3/8 O.D [3/4 I.D
{
6-1/8 6-1/8
7/8
1-3/4
13-3/16 12-5/8
1-5/8 8-7/16
10-1/8
1-11/16
8-7/16
1/8
11-5/16
2-3/4
2-3/16
2-3/16 2-3/16
8-7/8 8-7/8
9/1610-3/4
9-3/16
Wall hole [2-9/16
Indoor unit
Installation plate
7/16x13/16
Oblong hole
7/16x1 Oblong hole
7/8
hole
Conduit plate(MSZ-ANA- and MSY-ANA- are excluded.)
OUTLINES AND DIMENSIONS
MSZ-A09NA MSY-A15NA MSZ-A12NA MSY-A17NA MSZ-A15NA MSZ-A17NA
Unit : inch
6
MSZ-A24NA MSY-A24NA
Unit : inch
12-13/16
2-3/16
2-5/16
42-1/16
43-5/16
31-1/8
3/4
9-15/16
Installation plate
3-7/8
1-7/8
3-7/8 6-13/16
Air in
16-5/16 16-5/16
Wall hole [3
10-1/4
Air out
3/16
Installation plate
Indoor unit
Liquid line [1/4 19-11/16 Gas line [5/8 16-15/16
{
Insulation [1-15/16 O.D
Drain hose [5/8 (Connected part O.D)
Insulation [1-1/8
6-13/16
[1-1/4 I.D
1/8
10-1/161-7/8
5/16
12-3/8
6-1/4
Wireless remote controller
7
5
MSZ-A09NA MSY-A15NA MSZ-A12NA MSY-A17NA MSZ-A15NA MSZ-A17NA
WIRING DIAGRAM
MSZ-A24NA MSY-A24NA
8
6
Indoor heat exchanger
Flared connection
Room temperature thermistor RT11
Indoor coil thermistor RT13(sub)
Flared connection
Refrigerant pipe [3/8 (with heat insulator)
Refrigerant pipe [1/4 (with heat insulator)
Indoor coil thermistor RT12(main)
REFRIGERANT SYSTEM DIAGRAM
MSZ-A09NA MSZ-A12NA
MSZ-A15NA MSY-A15NA MSZ-A17NA MSY-A17NA
Refrigerant pipe [1/2 (with heat insulator)
Indoor heat exchanger
Room temperature thermistor RT11
Indoor coil thermistor RT12(main)
Distributor
Flared connection
Indoor coil thermistor RT13(sub)
Flared connection
Unit:inch
MSZ-A24NA MSY-A24NA
Indoor heat exchanger
Room temperature thermistor RT11
Indoor coil thermistor RT12(main)
Distributor
Indoor coil thermistor RT13(sub)
Refrigerant pipe[1/4 (with heat insulator)
Refrigerant pipe [5/8 (with heat insulator)
Flared connection
Flared connection
Refrigerant pipe [1/4 (with heat insulator)
Refrigerant flow in cooling Refrigerant flow in heating
9
7
No. 1 unit No. 2 unit No. 3 unit No. 4 unit
1 unit operation No modification
– – –
2 units operation
Same as at left
Solder J1
– –
3 units operation
Same as at left Same as at left
Solder J2
4 units operation
Same as at left Same as at left Same as at left
Solder both J1 and J2
SERVICE FUNCTIONS
MSZ-A09NA MSZ-A12NA MSZ-A15NA MSZ-A17NA MSZ-A24NA MSY-A15NA MSY-A17NA MSY-A24NA
7-1. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS the indoor electronic control P.C. board. The time will be shortened as follows. (Refer to 8-7.) Set time : 1-minute 1-second Set time : 3-minute 3-second (It takes 3 minutes for the compressor to start operation. However, the starting time is
shortened by short circuit of JPG and JPS.)
7-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room. In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be modified according to the number of the indoor unit.
How to modify the remote controller P.C. board
Remove batteries before modification. The board has a print as shown below :
NOTE : For modification, take out
the batteries and press the OPERATE/STOP(ON/OFF) button twice or 3 times at first. After finish modification, put back the batteries then
J1
J2
press the RESET button.
The P.C. board has the print J1 and J2. Solder J1 and J2 according to the number of indoor unit as shown in Table 1. After modification, press the RESET button.
Table 1
How to set the remote controller exclusively for particular indoor unit
After you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as the remote controller for the indoor unit. The indoor unit will only accept the signal from the remote controller that has been assigned to the indoor unit once they are set. The setting will be cancelled if the breaker has turned off, or the power supply has shut down. Please conduct the above setting once again after the power has restored.
10
JR07
CN151 CN211CN112
BZ
7-3. AUTO RESTART FUNCTION
JR07
CN151
CN152
CN101
CN211CN112
BZ
Housing point
When the indoor unit is controlled with the remote controller, the operation mode, the set temperature, and the fan speed are memorized by the indoor electronic control P.C. board. The AUTO RESTART FUNCTION sets to work the moment power has restored after power failure. Then, the unit will restart automatically.
Operation
1 If the main power has been cut, the operation settings remain. 2 After the power is restored, the unit restarts automatically according to the memory.
(However, it takes at least 3 minutes for the compressor to start running.)
How to release AUTO RESTART FUNCTION
1Turn off the main power of the unit. 2Solder the Jumper wire JR07 on the indoor electronic control P.C. board. (Refer to 8-7.)
MSZ-A09/12/15/17NA MSY-A15/17NA
MSZ-A24NA MSY-A24NA
NOTE:
The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the
remote controller.
If main power is turned OFF or a power failure occurs while AUTO START/STOP timer is active, the timer setting is
cancelled.
If the unit has been off with the remote controller before power failure, the auto restart function does not work as the
power button of the remote controller is off.
To prevent breaker off due to the rush of starting current, systematize other home appliance not to turn on at the
same time.
When some air conditioners are connected to the same supply system, if they are operated before power failure,
the starting current of all the compressors may flow simultaneously at restart. Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting current by adding to the system that allows the units to start one by one.
8
TROUBLESHOOTING
MSZ-A09NA MSZ-A12NA MSZ-A15NA MSZ-A17NA MSZ-A24NA MSY-A15NA MSY-A17NA MSY-A24NA
8-1. Cautions on troubleshooting
1. Before troubleshooting, check the following
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to turn off the unit first with the remote controller, and then after confirming the horizontal vane is closed, turn off the breaker and / or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board.
3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components.
4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
Lead wiring
11
3. Troubleshooting procedure
RESET button
Insert the negative pole of the batteries first. Check if the polarity of the batteries is correct.
OPERATION INDICATOR
Not lighted
Blinking
Lighted
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality. To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
2) Before servicing check that the connector and terminal are connected properly.
3) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
4) When troubleshooting, refer to 8-2., 8-3. and 8-4.
4. How to replace batteries
Weak batteries may cause the remote controller malfunction. In this case, replace the batteries to operate the remote controller normally.
1 Remove the front lid and insert batteries.
Then reattach the front lid.
2 Press RESET button with tip end of ball point pen
or the like, and then use the remote controller.
NOTE : 1. If RESET button is not pressed, the remote controller may not operate correctly.
2. This remote controller has a circuit to automatically reset the microcomputer when batteries are replaced. This function is equipped to prevent the microcomputer from malfunctioning due to the voltage drop caused by the battery replacement.
INFORMATION FOR MULTI SYSTEM AIR CONDITIONER OUTDOOR UNIT : MXZ series
Multi system air conditioner can connect two or more indoor units with one outdoor unit.
Unit wont operate in case the total capacity of indoor units exceeds the capacity of outdoor units. Do not connect indoor units beyond the outdoor unit capacity. Operation indicator lamp flashes as shown in the figure below.
When you try to operate two or more indoor units with one outdoor unit simultaneously, one for the cooling and the other for heating, the operation mode of the indoor unit that operates earlier is selected. The other indoor units cannot operate, indicating as shown in the figure below. In this case, please set all the indoor units to the same operation mode.
When indoor unit starts the operation while the defrosting of outdoor unit is being done, it takes a few minutes (max. 10 minutes) to blow out the warm air.
In the heating operation, though indoor unit that does not operate may get warm or the sound of refrigerant flowing may be heard, they are not malfunction. The reason is that the refrigerant continuously flows into it.
12
8-2. Failure mode recall function
Operational procedure
Yes
(Blinks)
No
(OFF)
Yes
No
Releasing the failure mode recall function
Note1.Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.
2.If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
W2. Blinking pattern when the indoor unit is abnormal:
W3.Blinking pattern when the outdoor unit is abnormal:
ON
OFF
Beeps
Repeated cycle Repeated cycle
ON
OFF
No beep Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5­second interval
2.5-second OFF 3-second ON
Blinking at 0.5­second interval
Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5­second interval
No beep Beeps
Repeated cycle
2.5-second OFF 3-second ON
Blinking at 0.5-
second interval
Repeated cycle
Beeps
Does the left lamp of OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: Either indoor or outdoor unit is abnormal. Beep is emitted at the same timing as the blinking of the left lamp of OPERATION INDICATOR lamp. W2
The cause of abnormality cannot be found because the abnormality doesn't recur.
Setting up the failure mode recall function
Before blinking, does the left lamp of OPERATION INDICATOR lamp stay ON for 3 seconds? Stays ON for 3 seconds (without beep): The outdoor unit is abnormal.
The indoor unit is abnormal. Check the blinking pattern, and confirm the abnormal point with the indoor unit failure mode table(8-2.2.). Make sure to check at least two consecutive blinking cycles. W2
Turn ON the power supply. <
Preparation of the remote controller
>
1 While pressing both OPERATION SELECT
button and TOO COOL button on the remote controller at the same time, press RESET button.
2 First, release RESET button.
And release the other two buttons after all LCD in operation display section of the remote controller is displayed after 3 seconds.
Deleting the memorized abnormal condition
1After repairing the unit, recall the failure mode again according to
"Setting up the failure mode recall function" mentioned above.
2Press OPERATE/STOP(ON/OFF) button of the remote controller (the set temperature is displayed)
with the remote controller headed towards the indoor unit.
3Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. 4Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
Repair the defective parts.
Release the failure mode recall function by the following procedures.
Turn OFF the power supply and turn it ON again.
Press RESET button of the remote controller.
Judgment of indoor/outdoor abnormality
Press OPERATE/STOP(ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. W1
Indoor unit is normal. But the outdoor unit might be abnormal because there are some abnormalities that can't be recalled with this way. Confirm if outdoor unit is abnormal according to the detailed outdoor unit failure mode recall function.
The outdoor unit is abnormal. Check the blinking pattern, and confirm the abnormal point with the outdoor unit failure mode table (Refer to outdoor unit service manual.) Make sure to check at least two consecutive blinking cycles. W3
W1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received.
Those figures show about MSZ-A09/12/15/17.
Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (8-4.) disappears, the memorized failure details can be recalled. This mode is very useful when the unit needs to be repaired for the abnormality which doesn't recur.
1. Flow chart of failure mode recall function for the indoor/outdoor unit
13
2. Indoor unit failure mode table
12-time flash
2.5-second OFF
Replace the indoor electronic control P.C. board.
Indoor control system
It cannot properly read data in the nonvolatile memory of the indoor electronic control P.C. board.
11-time flash
2.5-second OFF
Refer to 8-6.A "Check of indoor fan motor".
Indoor fan motor
The rotational frequency feedback signal is not emit during the 12 seconds the indoor fan operation.
2-time flash
2.5-second OFF
Refer to the characteristics of the main indoor coil thermistor, the sub indoor coil thermistor (8-7.).
Indoor coil thermistor
The indoor coil thermistor short or open circuit is detected every 8 seconds during operation.
3-time flash
2.5-second OFF
Refer to 8-6.D "How to check mis-wiring and serial signal error".
Serial signal
The serial signal from outdoor unit is not received for a maximum of 6 minutes.
1-time flash every 0.5-second
Refer to the characteristics of the room temperature thermistor (8-7.).
Room temperature thermistor
The room temperature thermistor short or open circuit is detected every 8 seconds during operation.
Not lighted Normal
Left lamp of OPERATION
INDICATOR lamp
Correspondence
Abnormal point (Failure mode)
Condition
NOTE : Blinking patterns of this mode differ from the ones of Troubleshooting check table (8-4.).
14
8-3. Instruction of troubleshooting
Start
Indoor unit operates. Outdoor unit doesn't operate.
Outdoor unit operates only in Test Run operation.
w
Check room temperature thermistor. Refer to 8-7. "Test point diagram and voltage".
Outdoor unit doesn't operate even in Test Run operation.
w
Refer to "How to check inverter/ compressor".
Indoor unit operates. Outdoor unit doesn't operate normally.
Unit doesn't operate normal operation in COOL or HEAT mode.
Refer to "Check of R.V. coil".
Indoor unit doesn't receive the signal from remote controller.
Indoor unit operates, when EMERGENCY OPERATION switch is pressed.
Refer to 8-6.B "Check of remote controller and receiver P.C. board".
OPERATION INDICATOR lamp on the indoor unit is flashing on and off.
Indoor unit doesn't operate, when EMERGENCY OPERATION switch is pressed.
1. Check indoor / outdoor connecting wire. (Check if the power is supplied to the indoor unit.)
2. Refer to 8-6.C "Check of indoor electronic control P.C. board and indoor fan motor".
If blinking of OPERATION INDICATOR lamp cannot be checked, it can be checked with failure mode recall function.
w
"Test Run operation" means the operation within 30 minutes after EMERGENCY OPERATION switch is pressed.
Refer to outdoor unit service manual.
Left lamp Flash on and off at 0.5-second intervals Cause: Indoor/ Outdoor unit
Mis-wiring or trouble of serial signal
Refer to 8-6. D "How to check of mis-wiring and serial signal error
".
Left
lamp 2-time flash Cause: Indoor unit
Trouble of room temp­ erature/ indoor coil thermistor
Check room temperature thermistor and indoor coil thermis­tor. Refer to 8-7. "Test point diagram and voltage".
Left
lamp 3-time flash Cause: Indoor unit
Trouble of indoor fan motor
Refer to 8-6. A "Check of indoor fan motor".
Left lamp 4-time flash Cause: Indoor unit
Trouble of indoor unit control system
Replace the indoor electronic control P.C. board.
Left lamp 5-time flash Cause: Outdoor unit
Outdoor power system abnormality
Refer to "How to check inverter/ compressor".
15
Left lamp 6-time flash Cause: Outdoor unit
Trouble of thermistor in outdoor unit
Refer to "Check of outdoor thermistors".
Left lamp 7-time flash Cause: Outdoor unit
Trouble of outdoor control system
Replace the inverter P.C. board or the outdoor electronic control P.C. board.
Left lamp 14-time flash Cause: Outdoor unit
Other abnormality
Check "Flow chart of the detailed outdoor unit failure mode recall function."