Mitsubishi Electric Mr. SLIM SUZ-SA100VA, Mr. SLIM SUZ-SA71VA2 Installation Manual

TIL INSTALLATØREN
FÖR INSTALLATÖREN
PARA O INSTALADOR
ΓΙΑ ΑΥΤΟΝ ΠΟΥ ΚΑΝΕΙ ΤΗΝ ΕΓΚΑΤΑΣΤΑΣΗ
PER L’INSTALLATORE
PARA EL INSTALADOR
VOOR DE INSTALLATEUR
FÜR INSTALLATEURE
FOR INSTALLER
Air-Conditioner
SUZ-SA71VA2, SA100VA
INSTALLATION MANUAL
For safe and correct use, read this manual and the indoor unit installation manual thoroughly before installing the air-conditioner unit.
INSTALLATIONSHANDBUCH
Aus Sicherheitsgründen und zur richtigen Verwendung vor der Installation die vorliegende Bedienungsanleitung und die Installationsanleitung der Innenanlage gründlich durchlesen die Klimaanlage.
MANUEL D’INSTALLATION
Avant d’installer le climatiseur, lire attentivement ce manuel, ainsi que le manuel d’installation de l’appareil intérieur pour une utilisation sûre et correcte.
INSTALLATIEHANDLEIDING
Lees deze handleiding en de installatiehandleiding van het binnenapparaat zorgvuldig door voordat u met het installeren van de airconditioner begint.
MANUAL DE INSTALACIÓN
Para un uso correcto y seguro, lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado.
MANUALE DI INSTALLAZIONE
Per un uso sicuro e corretto, leggere attentamente il presente manuale ed il manuale d’installazione dell’unità interna prima di installare il condizionatore d’aria.
EΓΧEIPIΔIO OΔHΓIΩN EΓKATAΣTAΣHΣ
Για σωστή και ασφαλή χρήση, διαβάστε προσεκτικά αυτό το εγχειρίδιο καθώς και το εγχειρίδιο εγκατάστασης της εσωτερικής μονάδας, προτού εγκαταστήσετε τη μονάδα του κλιματιστικού.
MANUAL DE INSTALAÇÃO
Para uma utilização segura e correcta, leia atentamente este manual e o manual de instalação da unidade interior antes de instalar o aparelho de ar condicionado.
INSTALLATIONSMANUAL
Læs af sikkerhedshensyn denne manual samt manualen til installation af indendørsenheden grundigt, før du installerer klimaanlægget.
INSTALLATIONSMANUAL
Läs bruksanvisningen och inomhusenhetens installationshandbok noga innan luftkonditioneringen installeras så att den används på ett säkert och korrekt sätt.
English
Deutsch
Français
Nederlands
Español
Italiano
Eλληνικά
Português
Dansk
Svenska
2
Contents
1. The following should always be observed for safety . . . . . . . . . . . . . . . . . . . . . . 2
2. Selecting the installation location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
3. Installation diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
4. Refrigerant piping work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1. The following should always be observed for safety
After reading this manual, be sure to keep it together with the instruction manual in a handy place on the customer’s site.
: Indicates a part which must be grounded.
Warning:
Carefully read the labels affi xed to the main unit.
Warning:
• Do not install it by yourself (customer). Incomplete installation could cause injury due to fi re, electric shock, the unit falling or leakage of water. Consult the dealer from whom you pur­chased the unit or special installer.
• This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial use by lay persons.
• Install the unit securely in a place which can bear the weight of the unit. When installed in an insuffi cient strong place, the unit could fall causing injured.
• Use the specifi ed wires to connect the indoor and outdoor units securely and attach the wires fi rmly to the terminal board connecting sections so the stress of the wires is not applied to the sections. Incomplete connecting and fi xing could cause fi re.
• Do not use intermediate connection of the power cord or the extension cord and do not connect many devices to one AC outlet. It could cause a fi re or an electric shock due to defective contact, defective insulation, exceeding the permissible current, etc.
Check that the refrigerant gas does not leak after installation has completed.
• Perform the installation securely referring to the installation manual. Incomplete installation could cause a personal injury due to fi re, electric shock, the unit falling or leakage of water.
• Use only specifi ed cables for wiring. The wiring connections must be made securely with no tension applied on the terminal connections. Also, never splice the cables for wiring (unless otherwise indicated in this document).
Failure to observe these instructions may result in overheating or a fi re.
• Perform electrical work according to the installation manual and be sure to use an exclusive circuit.
If the capacity of the power circuit is insuffi cient or there is incomplete elec- trical work, it could result in a fi re or an electric shock.
• Attach the electrical part cover to the indoor unit and the service panel to the outdoor unit securely. If the electrical part cover in the indoor unit and/or the service panel in the outdoor unit are not attached securely, it could result in a fi re or an electric shock due to dust, water, etc.
• Be sure to use the part provided or specifi ed parts for the installation work. The use of defective parts could cause an injury or leakage of water due to a fi re, an electric shock, the unit falling, etc.
• Ventilate the room if refrigerant leaks during operation. If the refrigerant comes in contact with a fl ame, poisonous gases will be released.
When pumping down the refrigerant, stop the compressor before disconnect­ing the refrigerant pipes. The compressor may burst if air etc. get into it.
• When installing or relocating, or servicing the air conditioner, use only the specifi ed refrigerant (R410A) to charge the refrigerant lines. Do not mix it with any other refrigerant and do not allow air to remain in the lines.
If air is mixed with the refrigerant, then it can be the cause of abnormal high
pressure in the refrigerant line, and may result in an explosion and other hazards.
The use of any refrigerant other than that specifi ed for the system will cause
mechanical failure or system malfunction or unit breakdown. In the worst case, this could lead to a serious impediment to securing product safety.
Caution:
• Perform grounding. Do not connect the ground wire to a gas pipe, water pipe arrester or tel­ephone ground wire. Defective grounding could cause an electric shock.
• Do not install the unit in a place where an infl ammable gas leaks. If gas leaks and accumulates in the area surrounding the unit, it could cause an explosion.
• Install a ground leakage breaker depending on the installation place (where it is humid). If a ground leakage breaker is not installed, it could cause an electric shock.
• Please provide an exclusive circuit for the air conditioner and do not con­nect other electrical appliances to it.
• Be sure to read “The following should always be observed for safety” be­fore installing the air conditioner.
• Be sure to observe the cautions specifi ed here as they include important items related to safety.
The indications and meanings are as follows.
Warning:
Could lead to death, serious injury, etc.
Caution: Could lead to serious injury in particular environments when operated incor­rectly.
• Perform the drainage/piping work securely according to the installation manual. If there is a defect in the drainage/piping work, water could drop from the unit and household goods could be wet and damaged.
• Fasten a fl are nut with a torque wrench as specifi ed in this manual. When fastened too tight, a fl are nut may broken after a long period and cause a leakage of refrigerant.
2.1. Outdoor unit
• Where it is not exposed to strong wind.
• Where airfl ow is good and dustless.
• Where it is not exposed to rain and direct sunshine.
• Where neighbours are not annoyed by operation sound or hot air.
• Where rigid wall or support is available to prevent the increase of operation sound or vibration.
• Where there is no risk of combustible gas leakage.
• When installing the unit at a high level, be sure to fi x the unit legs.
• Where it is at least 3 m away from the antenna of TV set or radio. (Otherwise, images would be disturbed or noise would be generated.)
• Please install it in an area not affected by snowfall or blowing snow. In areas with heavy snow, please install a canopy, a pedestal and/or some baffl e boards.
• Install the unit horizontally.
Caution: Avoid the following places for installation where air conditioner trouble is li­able to occur.
• Where there is too much machine oil.
• Salty environment as seaside areas.
• Hot-spring areas.
• Where sulfi de gas exists.
• Other special atmospheric areas. The outdoor unit produces condensate during the heating operation. Select the installation place to ensure to prevent the outdoor unit and/or the grounds from being wet by drain water or damaged by frozen drain water.
2. Selecting the installation location
5. Electrical work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
6. Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
7. Pumping down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
8. Specifi cations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3
3. Installation diagram
Fig. 3-1
3.1. Outdoor unit (Fig. 3-1)
Ventilation and service space
SUZ-SA71VA2, SUZ-SA100VA
A
100 mm or more
B 350 mm or more C 500 mm or more
When the piping is to be attached to a wall containing metals (tin plated) or metal netting, use a chemically treated wooden piece 20 mm or thicker between the wall and the piping or wrap 7 to 8 turns of insulation vinyl tape around the piping.
Units should be installed by licensed contractor accordingly to local code re­quirement.
Note: When operating the air conditioner in low outside temperature, be sure to fol­low the instructions described below.
• Never install the outdoor unit in a place where its air inlet/outlet side may be ex­posed directly to wind.
• To prevent exposure to wind, install the outdoor unit with its air inlet side facing the wall.
• To prevent exposure to wind, it is recommended to install a baffl e board on the air outlet side of the outdoor unit.
SUZ-SA71VA2
SUZ-SA100VA
A
C
A
C
B
Drainage hole (W42)
Air inlet
Air outlet
417.5
50
360
500175
Air inlet
330
40
2-10 mm × 21 mm slot
81
840
4. Refrigerant piping work
Fig. 4-2
Fig. 4-1
(C)
(B)
(A)
A Indoor unit B Outdoor unit
A Indoor unit B Outdoor unit
ø9.52
ø15.88
4.1. Refrigerant pipe (Fig. 4-1)
Check that the difference between the heights of the indoor and outdoor
units, the length of refrigerant pipe, and the number of bends in the pipe are within the limits shown below.
Model
(A) Pipe length
(one way)
(B) Height difference
(C) Number of
bends (one way)
SUZ-SA71/SA100 Max. 30 m Max. 30 m Max. of 10
• Height difference limitations are binding regardless of which unit, indoor or out­door, is positioned higher.
• Refrigerant adjustment ... If pipe length exceeds 7 m, additional refrigerant (R410A) charge is required. (The outdoor unit is charged with refrigerant for pipe length up to 7 m.)
Pipe length
Up to 7 m No additional charge is required.
Exceeding 7 m
Additional charge is required.
(Refer to the table below.) Refrigerant to be added
SUZ-SA71 50 g × (refrigerant piping length (m) -7)
SUZ-SA100 50 g × (refrigerant piping length (m) -7)
(1) Table below shows the specifi cations of pipes commercially available.
Model Pipe
Outside diameter
Min. wall
thickness
Insulation thickness
Insulation
material
mm inch
SUZ-SA71
SUZ-SA100
For liquid 9.52 3/8 0.8 mm 8 mm
Heat resisting
foam plastic
0.045 specifi c gravity
For gas 15.88 5/8 1.0 mm 8 mm
(2) Ensure that the 2 refrigerant pipes are well insulated to prevent condensation. (3) Refrigerant pipe bending radius must be 100 mm or more.
Caution: Using careful insulation of specifi ed thickness. Excessive thickness prevents storage behind the indoor unit and smaller thickness causes dew drippage.
(mm)