Mitsubishi Electric Mr. Slim PED-2EJA1.UK, Mr. Slim PED-2.5EJA1.UK Service Manual

Page 1
SPLIT-TYPE, AIR CONDITIONERS
ADVANCE AND EVER ADVANCING
TECHNICAL & SERVICE MANUAL
<indoor unit> Service ref.
Models
PED-2EJA1.UK PED-2.5EJA
1
The Slim Line. From Mitsubishi Electric
TM
1. FEATURES ················································· 1
2. PART NAMES AND FUNCTIONS ·············· 2
3. SPECIFICATIONS ······································ 4
4. DATA ··························································· 5
5. REFRIGERANT SYSTEM DIAGRAM ······· 8
6. OUTLINES AND DIMENSIONS ················· 9
7. WIRING DIAGRAM ···································· 10
8. DISASSEMBLY INSTRUCTIONS ············· 11
9. PARTS LIST ·············································· 14 10
. MICROPROCESSOR CONTROL·············· 19
11
. TROUBLE SHOOTING ······························25
12
. OPTIONAL PARTS ···································· 27
CONTENTS
INDOOR UNIT
REMOTE CONTROLLER
This manual does not cover the following outdoor units. When servicing them, please refer to the service manual No.OC149B and this manual as a set.
PU-2VJA2.UK PU-2.5VJA
2.UK
2000
Page 2
Page 3
1
1. TOTALLY INVISIBLE INDOOR UNIT BEHIND THE CEILING
The totally hidden indoor unit that lies above the ceiling surface enables you to utilize full floor space while allowing for flexible interior design.This new feature is recommended for stores and offices where the user's own imagination is allowed to be incorporated.
2. MOST SUITABLE FOR SIMULTANEOUS TWO ROOM AIR CONDITIONING
Using air ducts for cooling airflow that matches the structure and purpose of the room, enables you to provide two air outlets for simultaneous cooling of two rooms.
3. HIGH EXTERNAL STATIC PRESSURE
The exceptional external static pressure of 70Pa allows long ducts to be used more extensively to achieve convenient location of indoor units. (The factory setting is 30Pa.)
4. DRAIN WATER LIFT-UP MECHANISM (OPTION KIT)
This allows more versatility when selecting drain piping layouts.
FEATURES
1
lndoor unit
Remote controller
Models
W Btu/h
Cooling capacity (240V)
PED-2EJA1.UK PED-2.5EJA
1
.UK
5,500 6,500
18,800 22,200
air outlet air outlet
Air outlet duct
Air intake duct
air intake
Page 4
2
5. ADVANCED MICROPROCESSOR CONTROL
(1) Ultra - thin 12mm(1/2" )remote controller. (2) Attractive LED display .
Every operation condition is indicated on the LED display. (3) Simultaneous display of set temperature and room temperature. (4) Convenient 12 - hour ON-OFF timer.
This convenient timer allows the unit to be switched on and off automatically,at the time you set.Once the
timer is set,the remaining time is shown on the LED display.. (5) Self - diagnostic function indicates problems instantly on remote controller. (6) The useful memory feature can store instructions.
The previous set value is memorized so that constant temperature control can be obtained.For example,if a
power failure occurs, this feature will conveniently memorize the previous temperature and reset accordingly. (7) There is a polar 12 core - conductor cable between the remote controller and indoor board.The cable can be
extended up to 50m.(option)
PART NAMES AND FUNCTIONS
2
Indoor Unit
Air intake (sucks the air from inside the room into the unit)
Air outlet
or
Page 5
3
Remote controller
Operation buttons
Settings remain in effect until changed. Air conditioner can
be operated by simply pushing ON/OFF button once settings have been made.
(Example display readings are for explanations only ;actual display readings will differ.)
Page 6
4
3
SPECIFICATION
Model
PED-2.5EJA
1
.UKPED-2EJA1.UK
Item Cooling capacity
4 Btu/h 22,200
W 6,500
Total input 4 kW 2.69
Power supply
~/N, 50Hz, 220-240V Input kW 0.17 Running current A 0.72 Starting current A 1.6 External finish
Galvanized sheets
Heat exchanger
Plate fin coil
Plate fin coil
Fan (drive) ~No.
Centrifugal (direct)x2 Fan motor output 1 kW 0.116 Airflow (Low-High) CMM,(CFM)
17-21 (600-740)
External static pressure 2 Pa(mmAq)
30(3)/70(7) at Hi-notch
Operation control & Thermostat
Remote control&Built-in
Noise level (Low-High)
3, 5 dB (A) 37-41
Cond. drain conn. O.D.
mm, (in)
32(1-1/4)
W mm, (in) 1175(46-1/8)
Dimensions
D mm, (in) 700(27-9/16) H mm, (in) 295(11-5/8)
Weight
kg, (lbs) 42(93) Model name Power supply
Input kW Running current A Starting current A
2.52
10.7 52
External finish
Munsell 5Y 7/1
Refrigerant control
Capillary tube
Compressor
Hermetic Model Motor output kW Starter type
Line Start Protection devices Inner thermostat,HP switch,LP switch Heat exchanger
Fan (drive) ~No. Fan motor output kW 0.085 Airflow CMM,( CFM) 50(1765) Noise level dB (A) 52
W mm, (in) 870(34-1/4)
Dimensions D mm, (in)
H mm, (in) 850(33-7/16) Weight kg, (lbs) 71(157) Refrigerant
R-22 Charge kg, (lbs) 2.4(5.29) Pipe size O.D. Liquid mm, (in)
9.52(3/8)
Gas mm, (in)
(m)
(m)
Connection method Indoor side
Flared
Outdoor side
Flared Between the indoor Height difference & outdoor unit Piping length
18,800
5,500
2.63
0.15
0.63
1.1
0.076
13.5- 17(476-600)
36-40
935(36-13/16)
700(27-9/16)
295(11-5/8)
33(73)
PU-2VJA.UK PU-2.5VJA.UK
~/N
50Hz
220-240V
2.48
10.8 52
~/N
50Hz
220-240V
NHJ41VMDT
1.9
Propeller(direct)X1
Propeller(direct)X1
0.065
45(1588)
49
870(34-1/4)
295+24(11-5/8 add 1) 295+24(11-5/8 add 1)
650(25-5/8)
60(132)
1.78(3.92)
15.88(5/8)
30 30
1. External static pressure at 70Pa. 4.Rating condition <JIS B 8615>
2. Ex-works at 30Pa. INDOOR : 27 ˚CDB, 19 ˚CWB
3. External static pressure at 30Pa. OUTDOOR : 35 ˚CDB
5.Noise level : Sound pressure level
INDOOR UNIT
OUTDOOR
UNIT
REFRIGERANT
PIPING
✻✻
✻ ✻
Page 7
5
4
DA T A
Service Ref.
Indoor
intake air
WB˚C
20 25 30 35 40 45
CA P.C. CA P.C. CA P.C. CA P.C. CA P.C. CA P.C.
1. PERFORMANCE DATA
1) COOLING CAPACITY
Note C A: Capacity(W)
P.C.: Power consumption(kW)
Service Ref.
Refrigerant piping length(one way)
5m 10m 15m 20m 25m 30m
2) COOLING CAPACITY CORRECTION FACTORS
16 18 20 22
PED-
2.5EJA1.UK
5,599 5,957 6,320 6,688 6,617 7,039 7,468 7,904
2.13
2.17
2.21
2.25
2.18
2.22
2.26
2.30
5,445 5,803 6,171 6,562 6,435 6,858 7,355 7,754
2.22
2.27
2.30
2.35
2.27
2.32
2.36
2.40
5,225 5,566 5,929 6,309 6,175 6,578 7,007 7,456
2.38
2.44
2.49
2.54
2.43
2.49
2.54
2.60
4,989 5,324 5,676 6,050 5,896 6,292 6,708 7,150
2.54
2.61
2.66
2.72
2.60
2.66
2.72
2.79
4,741 5,071 5,418 5,786 5,603 5,993 6,403 6,838
2.70
2.77
2.84
2.92
2.76
2.83
2.90
2.98
4,488 4,813 5,154 5,511 5,304 5,688 6,091 6,513
2.15
2.30
2.47
2.63
2.20
2.36
2.52
2.70
16 18 20 22
PED­2EJA1.UK
PED- 2.5EJA1.UK
1.00 0.983 0.972 0.961
0.951 0.940
PED- 2EJA1.UK
1.00 0.985 0.975 0.964
0.954 0.944
Outdoor intake air DB˚C
2. PERFORMANCE CURVE (CAPACITY RATIO & TOTAL INPUT RATIO) PED-2EJA
1.UK
PED-2.5EJA
1.UK
Cooling
1.4
1.2
1
0.8
0.6
1.4
1.2
1
0.8
0.6
0.4
22 20 18 16
22 20 18 16
INDOOR WB
(˚C)
INDOOR WB
(˚C)
CAPACITY(RATIO)
TOTAL INPUT(RATIO)
OUTDOOR DB
(˚C)
-5 5 15 25 35 46
Page 8
6
Fan Performance <30Pa>
External static pressure (Pa)
(1Pa 0.1mmAg)
Air Flow (CMM)
6 8 10 12 14 16 18 20
8 101214161820 22
20
40
60
80
100
120
140
0.8
0.9
1.0
1.1
Corrected Air Flow
Capacity
input
Cooling
Air flow (CMM)
Correction factor
Fan Performance <70Pa>
External static pressure (Pa)
(1Pa 0.1mmAg)
Air Flow (CMM)
8 10121416182022
8 101214161820 22
20
40
60
80
100
120
140
160
0.8
0.9
1.0
1.1
1.2
1.3
Heating
Air flow (CMM)
Correction factor
3. FAN PERFORMANCE AND CORRECTED AIR FLOW PED-2EJA1.UK
Fan Performance <30Pa>
External static pressure (Pa)
(1Pa 0.1mmAg)
Air Flow (CMM)
8 1012141618202224
12 14 16 18 20 22 24 26
20
40
60
80
100
120
0.8
0.9
1.0
1.1
Corrected Air Flow
Capacity
input
Cooling
Air flow (CMM)
Correction factor
Fan Performance <70Pa>
External static pressure (Pa)
(1Pa 0.1mmAg)
Air Flow (CMM)
10 12 14 16 18 20 22 24 26
12 14 16 18 20 22 24 26
20
40
60
80
100
120
140
0.8
0.9
1.0
1.1
1.2
1.3
Heating
Air flow (CMM)
Correction factor
PED-2.5EJA1.UK
Page 9
7
Models
Indoor
Outdoor
Capacity(W) Total input(kW)
Input(kW) Current(A) Starting current(A) Input(kW) Current(A) Starting current(A)
IndoorOutdoor
Indoor ······220V 50Hz 1phase Outdoor ···220V 50Hz 1phase
Models
Indoor
Outdoor
Capacity(W) Total input(kW)
Input(kW) Current(A) Starting current(A) Input(kW) Current(A) Starting current(A)
IndoorOutdoor
Indoor ······230V 50Hz 1phase Outdoor···230V 50Hz 1phase
Models
Indoor
Outdoor
Capacity(W) Total input(kW)
Input(kW) Current(A) Starting current(A) Input(kW) Current(A) Starting current(A)
IndoorOutdoor
Indoor·······240V 50Hz 1phase Outdoor···240V 50Hz 1phase
PED-2.5EJA1.UKPED-2EJA1.UK
PU-2.5VJAPU-2VJA
PED-2.5EJA
1
.UKPED-2EJA1.UK
PU-2.5VJAPU-2VJA
PED-2.5EJA
1
.UKPED-2EJA1.UK
PU-2.5VJAPU-2VJA
5,400
2.57
0.13
0.60
1.05
2.44
11.3 48
6,300
2.61
0.15
0.69
1.53
2.46
11.4 48
5,450
2.60
0.14
0.61
1.07
2.46
11.0 50
6,400
2.65
0.16
0.70
1.56
2.49
11.0 50
5,500
2.63
0.15
0.63
1.10
2.48
10.8 52
6,500
2.69
0.17
0.72
1.60
2.52
10.7 52
4. ELECTRICAL DATA
Page 10
8
PED-2EJA1.UK PED-2.5EJA
1.UK
Strainer
Refrigerant pipe (option)
9.52mm(3/8) (With heat insulator)
Flexible tube
Flared connection
Thermistor RT2
Distributor
Refrigerant pipe (option)
15.88mm(5/8) (With heat insulator)
Indoor unit
5. STANDARD OPERATION DATA (COOLING)
Models
TotalElectrical circuitRefrigerant circuit
Indoor side
Outdoor
side
SHF
BF
Capacity Input Indoor unit model Phase Hz Volts Amperes Outdoor unit-model Phase,Hz Volts Amperes
W
kW
Discharge pressure Suction pressure Discharge temperature Condensing temperature Suction temperature Ref.Pipe length
Intake air temperature
Intake air temperature
Diischarge air temperature
MPa MPa
˚C ˚C ˚C
m
DB˚C
WB˚C
DB˚C DB˚C
WB˚C
PED-2EJA1.UK
5,500
2.63
PED-2EJA
1, 50
240
0.63
PU-2VJA
1, 50
240
10.8
1.98
0.46
77.3
52.5
15.3 5
27.0
19.0
14.8
35.0
24.0
0.74
0.32
PED-2.5EJA
1
.UK
6,500
2.69
PED-2.5EJA
1, 50
240
0.72
PU-2.5VJA
1, 50
240
10.7
2.00
0.51
78.6
53.1
8.5 5
27.0
19.0
16.0
35.0
24.0
0.71
0.27
REFRIGERANT SYSTEM DIAGRAM
5
Page 11
9
10
10
30
15
256
17640
A
81 C B 81
29
22761
81
A E 1313
163
282
85
45 80
277
21
30 640 30
24
35
10
179
109
10
3.53.5
256
288
40176
Set
10-ø3 (1.6, 2HP) 12-ø3 (2.5HP)
10-ø3 (1.6, 2HP) 12-ø3 (2.5HP)
450
450
A C B 81
10
C
30D
In case of bottom inlet
In case of rear inlet
10-ø3 (1.6, 2HP) 12-ø3 (2.5HP)
(1422)
Lifting bolt hole
8
8
Air inlet
35556
10
81B
365~465
159
18
44 75
7
6
7
5
6
5
4
3
2
1
Refrigerant piping flare connection (liquid ø9.52 copper tube):HP Refrigerant piping flare connection (gas ø15.88 copper tube):LP Drain R1(External thread) Electrical parts box Electric Heater···Only PEHD-EKHA Type Drain Pump (Option) Drain Pipe (Option)···Use VP25(O.D.ø32 PVC TUBE) Filter
Keep duct-work length 850mm or more. Be sure to apply the air filter (field supply) near the air inlet grille.
Service space:500 or more
197
81
50~150
55
Access door
Air outlet
Air inlet
4
3
1
2
PED-2 PED-2.5
Model
1012
772 305
280 290
830
1070
804
1044
-
ABCDE
6
OUTLINES & DIMENSIONS
1. INDOOR UNIT PED-2EJA
1.UK
PED-2.5EJA1.UK
2. REMOTE CONTROLLER
Page 12
10
7
WIRING DIAGRAM
3
1
312
3124321
3 2 1
321
1
3
1
3
7
*
*
Drain sensor
Drain pump
Drain sensor connector
Drain pump connector
DS
DP
CN50
CNP
*
fig: *1
220V
230V
220 RED
230 ORANGE
240 YELLOW
NOTES
1.Since the indoor transfomer(T) is connected with 240V power. if 220,230V power is used, Change the wiring connection shown at fig: 1
When power supply is
(indoor/outdoor connecting line)
Terminal block
NAME NAME NAME
SYMBOL EXPLANATION(*·····Option parts)
LD3<R.B>
F1, 2<I.B>
CNR120<R.B>
CN51<I.B>
Connector (remote controller)
Capacitor (fan motor) C
SYMBOL
LD5<R.B>
Auxiliary relay (fan motor)
X5,X6(I.B)
Thermistor (pipe temperature sensor 0˚C/15k, 25˚C/5.4k)
Terminal block (power)
TB1
SYMBOL
SYMBOL
LD4<R.B>
CN120<I.B>
I.B
TB2
ZNR<I.B>
T
RT1 RT2
Indoor controller board
Fuse <6.3A>
Varistor
Transformer
Thermistor (room temperature sensor 0˚C/15k, 25˚C/5.4k)
LD7<R.B> LD8<R.B>
LD1<R.B>
Run indicator LED
Connector (centrally control) Connector (remote controller)
Cooling indicator LED Fan mode indicator LED
Fan high indicator LED Indicator mode temperature LED Indicator mode timer LED
LD12<R.B>
LD11<R.B>
LD10<R.B>
LD9<R.B>
Dry indicator LED
Fan low indicator LED
Off timer indicator LED On timer indicator LED
LD13-24<R.B>
Temperature/Timer remaining time indicator LED
MF
Indoor Fan motor
Function switch
SW1(I.B) SW2(I.B)
Unit switch
SW3(I.B)
Emergency operation switch
SW1(R.B)
ON/OFF switch
SW2(R.B)
Operation mode switch
SW3(R.B)
Fan hige/low switch
SW5(R.B)
Indicator switch
SW6(R.B)
Temperature and timer setting up switch
SW7(R.B)
Temperature and timer setting down switch
SW8(R.B)
Timer continuous ON/OFF switch
R.B Remote controller board
GRN/YLW
BRN
BRN
BLU
BLK
BLK
GRY
GRY
YLW
GRN/YLW
BLU
RED
ORN YLW
GRN/YLW
BLU
BLK
RED
WHT
WHT
ORN
YLW
WHT
RED
AC10.6V
AC14.5V
BRN
RED
TRANSMISSION WIRES 12VDC 12CORE CONNECTOR
TO OUTDOOR UNIT CONNECTING WIRES 12VDC(non-polar)
CN31
HEA TER
CN51 MUL TIPLE
BLU
2
1
4
3
2
1
DS
4
3
1
OFF ON
SW5
SW8
SW3
SW2
ON
OFF
SW1
R.B
SW3
I.B
CN50 DRAIN
CN21 PIPE
CN20
INTAKE
1
1
2
2
2
5
RT2
RT1
SW2
SW1
3
1
CND POWER
OFF ON
LD8 LD7
LD13 LD14 LD15 LD16 LD17 LD18 LD19 LD20 LD21 LD22 LD23 LD24
LD1 LD3 LD9 LD4 LD5
LD10
LD11 LD12
SW6
SW7
1
MODELS:PED-2,2.5EJA
WIRING DIAGRAM
NOTES
1. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
2. Symbols used in circuit diagram above are, :Terminal block, :connector.
3. Emergency operation If a trouble occurs with either the remote controller or the indoor microcomputer and no other trouble exists,emer­ gency operation for cooling can be performed by changing the setting of dip switch (SW3<I.B>) on the indoor controller board (emergency dry operation is not possible).
<Check items> (1) Make sure that no other trouble exists with the outdoor unit. Trouble with the outdoor unit prevents emergency operation. (If any trouble exists with the outdoor unit,the trouble location will be displayed on the remote controller and the trouble position will be shown on the outdoor contro­ ller board LED.See electric circuit diagram of the outdoor unit for details.) (2) Make sure that there is no trouble with the indoor fan. Emergency operation will be a continuous run with the power ON/OFF(ON/OFFwith the remote controller is not possible).
<Emergency operation procedure> (1) Set the dip switch(SW3<I.B>)on the indoor controller board to 1 - 2 on and 3 off for cooling. (2) Turn on the outdoor unit side circuit breaker. (3) During emergency operation indoor fan runs at High speed. (4) Thermostat will not function.Cold air blows out for defro­ sting during heating thus do not operate de frosting for a long time. (5) Emergency cooling should be limited to 10 hours maximum(the indoor unit heat exchanger may freeze).
X6 X5
ZNR
F2
T
CN4T TRANS
CNT TRANS
FAN1
F1
:OPTION PARTS
pressure 70Pa
External static
pressure 30Pa
External static
WHITE
RED
2
4
2
3
53
6
1
DP
PE
BREAKER
TO DUCT
TB2
CN30 OUTDOOR
CN120 TO RC
TB1
N
L
POWER SUPPLY ~(1phase) 220-240VAC 50Hz
C
5
4
6
1
MF
CNR120
Page 13
11
8
DISASSEMBLY INSTRUCTIONS
Figure1.
Disconnect the fan motor connecter (and the booster heater connector)
Drain pan catches (Hidden)
Drain pan catches (Hidden)
Filter
Bottom plate
Drain pan
Heat exchanger
Bottom plate assembly
1
2
A
11
. Removing the fan motor
1. Removing the 9 screws that fix the bottom plate A, and remove it.
2. Removing the drain pan as follows: (1) Remove the screw that fixes the drain pan. (2) Slide the drain pan in the direction 1, Figure1 and
unhook the drain pan catch near the drain pipe.
(3) Slide the drain pan in the direction 2, Figure1 and
unhook the 2 catches on the other side of the drain pipe.
3. Remove the 8 screws that fix the bottom plate assembly, and remove it.
4. Disconnect the fan motor connector from the controller box.
5. Remove the fan plate as follow:
Figure2.
(1)Remove the 4 screws1 (2)Slide down the fan plate to remove.
6. Remove the sirocco fan setting screw and the motor fixture setting screw to remove the motor fixture. Remove the other motor fixture as well, and then remove the fan motor.
1
1
Fan base
Page 14
12
Figure3.
Fan base
Sirocco fan
Sirocco fan
Housing assembly
Housing assembly
Piece
Piece
Leg
Bush
Bush
Motor
Page 15
13
Pump cover assembly
Drain socket
Drain pan cover
Drain pump assembly
Drain hose
Rubber plug
Drain pan
1
2
2. Removing the drain water lift-up pump
1. Remove the drain pan.(Refer 1- 2.)
2. Disconnect the drain pump connector and drain sensor connector from the controller box.
3. Remove the two screws of the pump cover assembly.
4. Remove the drain hose from drain socket.
5. Remove the three screws of the drain pump assembly.
6. Remove the earth screw and four nuts of the drain pump assembly.
7. Remove the drain pump from drain pump assembly.
Figure4.
Page 16
14
9
PARTS LIST
PED-2EJA1.UK PED-2.5EJA1.UK
EXTERNAL PARTS
9, 10
1.2
7, 8
3, 4
5, 6
No.
1 2 3 4 5 6 7 8
9 10 11
Part No. Part Name Drawing No.
Qt’y/set
Spec.
1
1
PED-
2.5EJA
1
PED-
2EJA
1
W638918G02Bottom plate 2 ass’y
W638940G02Bottom plate 2 ass’y
W638917Z03Bottom plate 1
W638939Z03Bottom plate 1
W268511G03H.EX.General ass’y
W268511G02H.EX.General ass’y
W638920G01Drain pan ass’y
W638942G01Drain pan ass’y
W638181G02
Filter
W638181G01
Filter
S70 091 669
S70 081 669
S70 011 669
S70 031 669
S70 021 480
S70 020 480
S70 021 529
S70 011 529
S70 031 500
S70 021 500
1
1
1
1
1
1
1
1
Page 17
15
PED-2EJA1.UK PED-2.5EJA1.UK
BLOWER PARTS
5, 6
7, 8
1
1
4
4
9, 10
11
7, 8
5, 6
2, 3
No.
1
2
3
4
5
6
7
8
9 10 11 12 13 14
Part No. Part Name Drawing No.
Qt'y/set
W353715H01 22
22
2
2
1
1
1
11
1
W122296G01
W638949G03
W241060H03
P714774X01
<MF>
<MF>
Attachment
W638905G02Fan base ass'y
W638932G02Fan base ass'y
Sirocco fan
2
W122297G01Sirocco fan
Housing ass'y
2
W638949G04Housing ass'y
Motor Motor support
P714316X02Motor
W818836H01Bush
S07 652 131
S70 061 677
S70 051 677
S70 A88 114 S70 A89 114
S70 989 110 S70 985 110
S70 Y56 221 S70 652 130
S70 Y58 220
S70 922 105
PED-
2.5EJA
1
PED­2EJA
1
Page 18
16
PED-2EJA1.UK PED-2.5EJA1.UK
CONTROL BOX PARTS
6
5
3
4
7
2
1
7
No.
1
2
3
4
5
6
7
8
9 10
Part No. Part Name Drawing No.
P436109X01
P436110X01 BG00L760G22 BG65T178H03 BG71V161H04 BG71V162H08
P419114X01
Qt’y/set
Spec.
<TB2> <TB1> <I.B.> <T> <RT1> <RT2>
PED-
2.5EJA
1
PED­2EJA
1
11 11 11 11 11 11 22
Terminalbed Terminalbed Controller Transformer Thermistor S Thermistor H Ferrite core
S70 918 717 S70 979 717 S70 010 310 S70 11K 799 S70 010 202 S70 020 202 S70 010 292
Page 19
17
PED-2EJA1.UK PED-2.5EJA1.UK
ELECTRICAL PARTS
No.
1 2 3 4 5
Part No. Part Name Drawing No.
BC00C006G34 BG00K507G02 BG78R190G10
Qt’y/set
Spec.
J controller 10m
0.5m
11 11 11
PED-
2.5EJA
1
PED­2EJA
1
Remote controller Remote controller cable Cable ( for board )
S70 010 713 S70 A00 305 S70 010 304
1
3
2
Page 20
18
PED-2EJA1.UK PED-2.5EJA1.UK
DRAIN WATER LIFT-UP PUMP PARTS (OPTIONAL PARTS)
3
4
1.2
5
No.
1 2 3 4 5
Part No. Part Name Drawing No.
BG56J144G13 DB26F111H03 BB00P145G17 DE00H343G21 P312040X01
Qt’y/set
Spec.
PED-
2.5EJA
1
PED­2EJA
1
11 44 11 11 11
Drain pump-94 Cushion Drain socket ass’y Drain sensor ass’y Rubber plug
S70 11K 355 S70 010 533 S70 K01 523 S70 W28 266 S70 E69 558
Page 21
19
10
MICROPROCESSOR CONTROL
Page 22
20
l
Page 23
21
l
Page 24
22
l
l
after
Page 25
23
Page 26
24
Page 27
25
11
TROUBLE SHOOTING
Page 28
26
Page 29
27
12
OPTIONAL PARTS
1. REFRIGERANT PIPES
28˚C
26˚C
8:00
Normai operation
8:00 Normai operation
23:00 Setback operation
3. TIMER
When using a program timer, a program timer adapter (PAC-825AD)is also needed.
3-1 Program timer specifications
3-2 Feature of program timer
(1) Daily timer function
Daily timer can be set in 30 minute units for up to 24 hours. Each unit can be set for unit ON, unit OFF, or setback operation.
(2) Setback operation(PAC-SK65PT)
Set back operation is useful for reducing running costs. e.g.AT a hotel with a 24-hour system
8:00~23:00 Cooling operation with set temperature at 26 ˚C
23:00~8:00 Setback operation with 2 degrees of setback As shown in the chart on the right, the set temperature rises 2 degrees automatically during the setback operation.When the set­back operation ends, normal operation will begin.
(3) Weekly timer function
Daily timer function can apply to each day of the week.
Part No. PAC-05FFS-E PAC-07FFS-E PAC-10FFS-E PAC-15FFS-E
5m 7m 10m 15mPipe length Pipe size OD Connection method
Liquid:/ø9.52 Gas:/ø15.88
Indoor unit:Flared Outdoor unit:Flared
Note 1.How to connect refrigerant pipes.
Factory supplied optional piping contains refrigerant at above atmospheric pressure. As long as the connection takes no more than 5 minutes, no air will enter, and there will be no need for air purging. Remove the blind caps and make the connections within 5 minutes. After the connections for the indoor and outdoor units are made, open the stop valve on the outdoor unit to allow refrigerant gas to flow.
If piping length exceeds 5m, an additional charge of refrigerant is needed. Note 2.The following main parts are contained in the optional refrigerant piping kit. Heat insulating cover, vinyl tapes, nipples, sleeve and flange(for wall hole), connecting cables.
Part No.
Model Name
PAC-SK65PT(with set back function)
Program timer
Part name Part No.
Program timer PAC-SK65PT
Exterior dimensions(mm)
120X120X15 (mm) Installation Wall mount Type of clock Quartz Clock accuracy
±
50second/month
Display-Time Liquid crystal display
Liquid crystal display Liquid crystal display
Program cycle
-Timer
-Week
24 hours Timer setting unit 30 minutes No. of set points 48/day Power rating
5V DC
Set back function
Provided
2. REMOTE CONTROLLER EXTENSION CABLE
When installing the remote controller at a distance from the air conditioner, use the designated extension cable with connector.
Part No. PAC-905EC PAC-906EC PAC-918EC PAC-919EC
12m 20m 30m 50mLength
Page 30
28
3-3 HOW to connect program timer
(1) Install the program timer next to the remote controller the same way as the remote controller is installed. (2) Connect the program timer and the remote controller with a 6-wire cable as shown in the figure below.
NOTE:While the program timer is connected to the remote controller,
the 24 hour ON/OFF timer on the remote controller will not operate.
3-4 Names and functions <PAC-SK65PTA>
Page 31
29
117
117
12
113
113
56.5
23.5 11
8
"ENGAGED" indicator When this indicator is lit, transmisson is in progress and all swiches are inoperative.
switch This change-over switch governs the opera­tion of the accessory remote controller.
"DUAL" Instructions from both the accessory remote controller and the centralized remote controller are valid. (Priority given to the last instruction received.)
"CENTRAL" ON / OFF switching by the accessory remote controller is invalidate. Operation is controlled by the centralized remote con­troller only. Inital setting is "DUAL"
LCD Matrix display This display indicates the operational sta­tus of all connected units either by steady lighting or by flashing.
switch Operation ON / OFF switch.
buttons These buttons are used to designate the attached unit (s). (They designate the unit to be centrally controlled.)
•When group "00" is designated ; collec­tive ON/OFF instruction is sent to all units.
•When group "01" - "16" is designated; ON/OFF instruction is sent only to
the designated units. switch
This change-over switch is for the pro­gram timer. (It selects the timer operation on the program timer.) Use "BYPASS" when a program timer is not connected. "ACTIVE" The switch turns ON/OFF commands given from the program timer automatically. "BYPASS" ON/OFF Operation is controlled by the centralized remote controller only. Initial setting is "BYPASS".
Independent "DUAL / CENTRAL" and "ACTIVE / BYPASS" setting of all the groups is prossible. When the power supply to the centralized remote controller is cut due to power failure, all settings will return to the original "DUAL" and "BYPASS".
DUAL/CENTRAL
POWER ON/OFF
BACK AHEAD
ACTIVE/BYPASS
4. CENTRALIZED REMOTE CONTROLLER
Allows individual or combined control of up to 16 units.
4-1 Dimensions
Part No. PAC-805RC
4-2 Functions
Unit:mm
Page 32
30
4-3 Connection method
(1) Connection in the power supply cord.
1. Connect the power supply cord to the power supply terminal-block and fix in-place with a tie-wrap. Connect a single phase 200V AC(220, 230, 240V)to AN .
As E is the GND terminal,be sure to ground the earth wire.
2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-wrap. Use a ø1.6
(AWG14)or above two-wire cable for the transmission line.
CAUTION:Ne
ver connect the power supply cord to the transmission terminal-block.
TERMINAL-BLOCK FOR TRANSMISSION
TERMINAL-BLOCK OF POWER SUPPLY
Fuse(5A)
TRANSFORMER
Tie-wrap
Tie-wrap
Transmission
POWER SUPPLY
Wiring has to be changed when a 200,230 or 240V power is used.
TO adaptor's terminal-block
TO adaptor's terminal-block
Non-polar two-wire cable
Power supply board box
Centralized remote controller
Power supply board
Dip swirch SW17
(2) Connection method of centralized remote controller and power supply board.
1. Connect the centralized remote controller and power supply board with a non-polar, two-wire cable.
2.Wiring diagram
3. Be sure to set the maximum address number with the dipswitch SW17 on the centralized remote controller.
Page 33
31
5. PROGRAM TIMER ADAPTER
This adapter is needed when a program timer(PAC-815PT)or a centralised remote controller(PAC-805RC)is used.
Part No. PAC-825AD
5-1 Parts included
1 ADAPTER ···································x1 2 3-core cable ·································· x1 2 3-core cable ·································· x1
2 4-core cable ·································· x1 2 5-core cable ·································· x1
Length:2m(6' 7")
Length:2m(6' 7")
Length:2m(6' 7" )
Length:2m(6' 7")
5-2 Connection method
Connection and wiring methods differ with the type of the indoor unit used. Confir m the type before carrying out the work.
(1) Connections in the adapter box
1. Connect the power supply cord to the terminal-block and fix in-place with a tie-wrap. Connect a single phase 200V AC(220, 230, 240V) to LN. As
; is the GND ter minal, be sure to ground the ear th wire.
2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-wrap, when a central­ized remote controller is being used.
CAUTION:Never connect the power supply cord to the transmission terminal-block.
Page 34
32
Part No. PAC-559AD
7. REMOTE INDICATION ADAPTER
This adapter is used for remote indication(operation/check.)
1
5
Power supply
BRN RED
ORN YRW
GRN
BRN RED ORN
YRW GRN
5
2 5
±
JST XHP3
<Wiring>
CN51
connector(5P)
Optional multiple display adaptor
The maximum distance between indoor board and relay is 10m.
Wiring at the actual place
X1 X2
RL GL
Electrical insulation is needed.
BROWN
RED
ORANGE
YELLOW
GREEN
X1 X2
6. TIMER ADAPTER
This adapter is needed for system control and for operation via external contacts.
Part No. PAC-SA89TA-E
1 2
3
ORN BRN
RED
8. DRAIN WATER LIFT-UP MECHANISM
This allows more versatility when selecting drain piping layouts.
Part No. PAC-SK001DM-F
PED-2EJA
1
.UK, PED-2.5EJA1.UK
Applied model
Page 35
Page 36
HEAD OFFICE MITSUBISHI DENKI BLDG. MARUNOUCHI TOKYO100 TELEX J24532 CABLE MELCO TOKYO
MEE00K028 Issued in Nov. 2000 Printed in Japan
New publication, effective Nov. 2000 Specifications subject to change without notice.
TM
Loading...