7. System example ...................................................................91
What is ATW heat pump?1
1-1. Compare with conventional fossil fuel boiler
• Heat pumps produce water at 30°C – 60°C
• Ideal for underfl oor heating
• Average underfl oor heating circuit 35°C
• Fossil fuel boilers heat water to 80°C
• Flow temp in rads design temp approx 70°C
• Heat pumps can still be used with radiators
• Larger surface area to emit heat from lower temp water
1-2. Points to notice
1-2-1. Design (Radiator sizing)
• Careful consideration must be given to appropriate application of this technology to maximise its benefi ts – it will not suit all
properties, especially many retrofi ts
• Heat emitters may need to be larger
• Lower fl ow temperatures maximise COP
• Various regulations apply to the design and installation of such systems
• Because the fl ow temp. of heat pump is low compare to fossile fuel boiler, the temperature difference between the primary (fl ow
water) and secondary (room air) becomes little, it makes the heat emission little.
To emit the same amount of heat energy, it is needed to select the radiator that has a larger surface area.
Be especially careful of the surface area when you design the radiator.
1-2-2. Defrost
Note: Occasionally, vapor that is made by the defrost operation may seem as if smoke come up from the outdoor unit.
1-2-3. Water Pressure loss (for packaged type outdoor unit)
• Water pressure lose of the heat exchangers are as follows.
Be aware of the infl uence when you design total pipng system.
Hex for PUHZ-W50VHA (ACH30-30Plates)
Secondary (Water - side)
Flow rate (L/min)51015202530
Pressure Loss (kPa)1.76.012.420.931.443.8
Pressure loss (kPa)
50
45
40
35
30
25
20
15
10
5
0
51015202530
Flow rate (L/min)
2
Hex for PUHZ-W85VHA (ACH30-40Plates)
Secondary (Water - side)
Flow rate (L/min)51015202530
Pressure Loss (kPa)1.03.67.512.518.826.2
Pressure loss (kPa)
30.0
25.0
20.0
15.0
10.0
5.0
0.0
51015202530
Flow rate (L/min)
Hex for PUHZ-W112, 140VHA / YHA (ACH50-50Plates)
Secondary (Water - side)
Flow rate (L/min)153045607590
Pressure Loss (kPa)1.34.910.919.329.942.8
Pressure loss (kPa)
45.0
40.0
35.0
30.0
25.0
20.0
15.0
10.0
5.0
0.0
153045607590
Flow rate (L/min)
33
Heat pump unit_General information2
2-1. Line-up
2-1-1. Outdoor unit for Air to water
(1) Packaged type: The Air to Water outdoor unit with a plate HEX (refrigerant-water) inside
* Outdoor units (PUHZ-RP or PUHZ-P) other than the above-mentioned become possible by connecting TH5 ( 2-phase refrig-
erant temp. thermistor ) with the interface only for Air to Air use.
1-phase3-phase1-phase3-phase
Packaged modelsZUBADAN-Packaged models
Split Replace inverter modelsSplit ZUBADAN models
2-1-2. Air to Air application
INTER FACE MODEL NAMEPAC-IF011B-E / PAC-IF010-E
AUTO
STEP *1
MANUAL
STEP *2
MANUAL STEP MODE is New function of INTER FACE (Fixed capacity = Compressor frequency (Hz) fi xed mode) .
<Old models : The models that are not described in the table above.>
*1: With(Auto-mode)+(SW2-6 is OFF)+(2phase thermistor), all A-control outdoor units are able to connect to PAC-IF010/
*2: With(Manual-mode)+(SW2-6 is OFF)+(2phase thermistor), from following RP type outdoor units are able to connect to
CapacitykW8.00
COP3.24
Power input2.47
CapacitykW8.00
COP4.40
Power input1.82
CapacitykW8.00
COP3.24
Power input2.47
CapacitykW11.20
COP3.02
Power input3.71
CapacitykW11.20
COP4.26
Power input2.63
CapacitykW11.20
COP3.24
Power input3.46
CapacitykW11.20
COP2.40
Power input4.67
CapacitykW14.00
COP2.70
Power input5.19
CapacitykW14.00
COP4.22
Power input3.32
CapacitykW14.00
COP3.20
Power input4.38
1[, 230V, 50Hz
PUHZ-HRP100VHA2 /
PUHZ-HRP100YHA2
1[, 230V, 50Hz /
3[, 400V, 50Hz
3[, 400V, 50Hz
Guaranteed operating range (Outdoor)
Heating
Cooling
:
:
-25 ~ +35
-5 ~ +46
Plate heat exchanger
ALFA LAVAL
ACH50
A: 50 mm
B: 466 mm
Ref.IN
(Heating)
w
Water OUT
B
W: 112 mm
H: 526 mm
D: 130 mm
50 plates
Ref.OUT
(Heating)
A
H
Water IN
D
Refrigerant pipng length from outdoor unit to
heat exchanger (Water HEX): 5m
Maximum outlet water temperature
65
]
60
55
50
45
Maximum outlet water temptemperature [°C
40
-25-20
-15-10-50510
Ambient temperature [°C]
The performance might be decreased by the refrigerant
pipng length, insulation of refrigerant pipng and
heat exchanger (Water HEX).
6
(2) PUHZ-RP • VHA3/YHA3(2)
Outdoor unit
Model namePUHZ-RP60VHA3#1
Power supply
(Phase, Voltage, Frequency)
Breaker sizeA25
Nominal water fl owL/min20.1
Heating
(A2/W35)
Heating
(A7/W35)
Heating
(A7/W45)
Outdoor unit
Model namePUHZ-RP71VHA3#1
Power supply
(Phase, Voltage, Frequency)
Breaker sizeA25
Nominal water fl owL/min22.9
Heating
(A2/W35)
Heating
(A7/W35)
Heating
(A7/W45)
CapacitykW6.80
COP2.94
Power inputkW2.31
CapacitykW7.00
COP4.29
Power inputkW1.63
CapacitykW7.00
COP3.27
Power inputkW2.14
CapacitykW7.50
COP2.92
Power inputkW2.57
CapacitykW8.00
COP4.21
Power inputkW1.90
CapacitykW8.00
COP3.20
Power inputkW2.50
1[, 230V, 50Hz
1[, 230V, 50Hz
Guaranteed operating range (Outdoor)
Heating
Cooling:-5 ~ +46
:
-11 ~ +35
Plate heat exchanger
ALFA LAVAL
ACH50
A: 50 mm
B: 466 mm
Ref.IN
(Heating)
w
Water OUT
B
W:112 mm
H: 526 mm
D: 82 mm
30 plates
Ref.OUT
(Heating)
A
H
Water IN
D
Refrigerant pipng length from outdoor unit to
heat exchanger (Water HEX): 5m
Maximum outlet water temperature
65
]
60
55
50
Maximum outlet water temptemperature [°C
45
-10-50510
Ambient temperature [°C]
The performance might be decreased by the refrigerant
pipng length, insulation of refrigerant pipng and
heat exchanger (Water HEX).
7
Outdoor unit
Model name
Power supply
(Phase, Voltage, Frequency)
Breaker sizeA32 / 16
Nominal water fl owL/min32.1
Heating
(A2/W35)
Heating
(A7/W35)
Heating
(A7/W45)
Outdoor unit
Model name
Power supply
(Phase, Voltage, Frequency)
Breaker sizeA32/16
Nominal water fl owL/min40.1
Heating
(A2/W35)
Heating
(A7/W35)
Heating
(A7/W45)
Outdoor unit
Model name
Power supply
(Phase, Voltage, Frequency)
Breaker sizeA40/16
Nominal water fl owL/min45.9
Heating
(A2/W35)
Heating
(A7/W35)
Heating
(A7/W45)
CapacitykW10.50
COP2.90
Power inputkW3.62
CapacitykW11.20
COP4.21
Power inputkW2.66
CapacitykW11.20
COP3.20
Power inputkW3.50
CapacitykW11.50
COP2.70
Power inputkW4.26
CapacitykW14.00
COP4.15
Power inputkW3.37
CapacitykW14.00
COP3.10
Power inputkW4.51
CapacitykW11.70
COP2.69
Power inputkW4.35
CapacitykW16.00
COP3.90
Power inputkW4.10
CapacitykW16.00
COP3.00
Power inputkW5.34
PUHZ-RP100VHA3#1 /
PUHZ-RP100YHA3#1
1[, 230V, 50Hz /
3[, 400V, 50Hz
PUHZ-RP125VHA2#2 /
PUHZ-RP125YHA2#2
1[, 230V, 50Hz /
3[, 400V, 50Hz
PUHZ-RP140VHA2#2 /
PUHZ-RP140YHA2#2
1[, 230V, 50Hz /
3[, 400V, 50Hz
Guaranteed operating range (Outdoor)
Heating
Cooling
:
:
-20 ~ +35
-5 ~ +46
Plate heat exchanger
ALFA LAVAL
ACH50
A: 50 mm
B: 466 mm
Ref.IN
(Heating)
w
Water OUT
B
W:112 mm
H: 526 mm
D: 130 mm
50 plates
Ref.OUT
(Heating)
A
H
Water IN
D
Refrigerant pipng length from outdoor unit to
heat exchanger (Water HEX): 5m
Maximum outlet water temperature
65
]
60
55
50
45
Maximum outlet water temptemperature [°C
40
-20-15
-10-50510
Ambient temperature [°C]
The performance might be decreased by the refrigerant
pipng length, insulation of refrigerant pipng and
heat exchanger (Water HEX).
8
[2]
Standard operation data <Split> Reference data (connect to Plate HEX)
CurrentA9.98.216.5/5.611.7/4.07.35.3
Discharge pressureMPa2.42.02.62.12.82.3
Suction pressureMPa0.80.70.80.70.80.7
Discharge temperature
Condensing temperature
Suction temperature
Evaporating temperature
Evaporator inlet temperature
Refrigerant circuit
Evaporator outlet temperature
Condenser inlet temperature
Condenser outlet temperature
Cooling
(A35/W7)
:
:
:
:
:
:
:
:
706078638470
423546364739
126114103
525251
5—5—5—
5—5—5—
—55—60—65
—33—31—30
Heating
(A7/W35)
ACH50-50 plates
Cooling
(A35/W7)
PUHZ-HRP100VHA2/
PUHZ-HRP100YHA2
Heating
(A7/W35)
Cooling
(A35/W7)
PUHZ-HRP125YHA2
Heating
(A7/W35)
Flow volumeL/min20.422.928.734.435.840.1
Water
Outlet water temperature
conditions
D.B.
Intake air temperature
Outdoor
conditions
The unit of pressure has been changed to MPa based on international SI system.
The conversion factor is : 1(MPa)=10.2(kgf/F)
Discharge pressureMPa2.72.12.72.22.62.1
Suction pressureMPa0.80.70.80.70.80.7
Discharge temperature
Condensing temperature
Suction temperature
Evaporating temperature
Evaporator inlet temperature
Refrigerant circuit
Evaporator outlet temperature
Condenser inlet temperature
Condenser outlet temperature
:
:
:
:
:
:
:
:
ACH50-30 platesACH50-50 plates
Cooling
(A35/W7)
706570667465
453645364436
454265
515151
6—6—5—
5—5—5—
—56—57—58
—34—33—35
Heating
(A7/W35)
Cooling
(A35/W7)
Heating
(A7/W35)
Cooling
(A35/W7)
PUHZ-RP100VHA3#1/
PUHZ-RP100YHA3#1
Heating
(A7/W35)
Flow volumeL/min17.220.118.922.926.132.1
Water
Outlet water temperature
conditions
D.B.
Intake air temperature
Outdoor
conditions
The unit of pressure has been changed to MPa based on international SI system.
The conversion factor is : 1(MPa)=10.2(kgf/F)
CurrentA22.4 / 7.615.0 / 5.223.6 / 8.118.2 / 6.2
Discharge pressureMPa2.82.12.82.2
Suction pressureMPa0.70.70.70.7
Discharge temperature
Condensing temperature
Suction temperature
Evaporating temperature
Evaporator inlet temperature
Evaporator outlet temperature
Refrigerant circuit
Condenser inlet temperature
Condenser outlet temperature
Flow volumeL/min34.440.135.845.9
:
:
:
:
:
:
:
:
Cooling
(A35/W7)
PUHZ-RP125VHA2#2/
PUHZ-RP125YHA2#2
80698167
46364636
3431
5-15-1
6—6—
5—5—
—63—61
—35—34
Heating
(A7/W35)
Cooling
(A35/W7)
PUHZ-RP140VHA2#2/
PUHZ-RP140YHA2#2
Heating
(A7/W35)
Water
Outlet water temperature
conditions
D.B.
Intake air temperature
Outdoor
conditions
The unit of pressure has been changed to MPa based on international SI system.
The conversion factor is : 1(MPa)=10.2(kgf/F)
Refrigerant flow in cooling
Refrigerant flow in heating
(Outdoor pipe)
Restrictor
valve
Bypass
valve
Replace
filter
Strainer
#100
12
[6]
Notifi cation to design/select HEX (Refrigerant - Water)
• Specifi cations of AHU and compatibility with regulations must be confi rmed by your company.
• Selection of an apporopriate AHU (with appropriate specifi cations to match those of units
connected to the AHU such as confi guration, dimension, life-span, vibration, noise level,
or features) must be made by your company.
• Mitsubishi Electric shall not be liable for any damage to the entire system or the AHU main
body caused by connected AHU with wrong specifi cation or wrong usage of AHU.
• Mitsubishi Electric shall not be liable for any damage to the outdoor units caused by AHU damage.
( AHU : hydro box or refrigerant - water HEX )
Heat exchanger
(1) Withstanding pressure
Designed pressure of outdoor unit is 4.15 MPa. Following must be satisfi ed for burst pressure of connecting application.
Burst pressure : More than 12.45 MPa (3 times more than designed pressure)
(2) Performance
Secure the heat exchanger capacity which meets the following conditions. If the conditions are not met, it may result in
malfunction caused by the protection operation or the outdoor unit may be turned off due to the operation of protection
system.
1. Evaporate temperature is more than 4: in max. frequency operation under *1 the cooling rated conditions.
2. In case of hot water supply, condense temperature is less than 58: in max. frequency operation with the outside temperature 7:D.B./6:W.B.
*1. Outdoor: 35:D.B./24:W.B.
(3) Heat exchanger internal capacity
Heat exchanger internal capacity must be within the capacity range shown below. If the heat exchanger below the minimum capacity is connected, it may result in the back fl ow of liquid or the failure of the compressor.
If the heat exchanger above the maximum capacity is connected, it may result in the defi ciency in performance due to lack
of refrigerant or overheating of the compressor.
Minimum capacity : 10 х Model capacity [J] / Maximum capacity : 30 х Model capacity [J]
e.g. When connecting to PUHZ-HRP100 VHA2
Minimum capacity : 10 х100 =1000
Maximum capacity : 30 х100 =3000
Model capacity60(2.5HP)71(3HP)100(4HP)125(5HP)140(6HP)
Maximum capacity [J]18002130300037504200
Minimum capacity [J]600710100012501400
J
J
Warranty for SPILIT solution
(4) Contamination maintenance
1. Wash the inside of heat exchanger to keep it clean. Be sure to rince not to leave fl ux. Do not use chlorine detergent for
wash.
2. Be sure that the amount of contamination per unit cubic content of heat transfer pipe is less than the following amount.
Example) In case of [ 9.52mm
Residual water : 0.6M/C, Residual oil : 0.5M/C, Solid foreign object : 1.8M/
Note:
• Install the hydraulic fi lter at the water intake.
• Use the inlet water of higher than 5 ˚C and lower than 55 ˚C.
• The water in a system should be clean and with pH value of 6.5-8.0.
• The followings are the maximum values;
Calcium : 100mg/L
Chlorine : 100mg/L
Iron/manganese : 0.5mg/L
• Refrigerant pipe diameter from outdoor unit to refrigerant-water HEX (Only for SPLIT type)
Use the pipe with same diameter size as the refrigerant pipe connection diameter of outdoor unit.(Refer to outdoor
unit installation manual.)
• Make sure to perform the frozen prevention measure for water pipe system.(Water piping insulation, back-up pump
system, using of a certain % ethylene glycol instead of normal water)
[Reference]
TB142 has for “Forced Comp. OFF” function as the EXTERNAL INPUT(Contact signal).
To input the abnormal signal of water pump or the abnormal lowering of water fl ow amount with non-voltage contact
signal makes the outdoor unit stop forcibly. For details, refer to each part of I/F or FTC on this manual.
C
13
• The water velocity in pipes should be kept within certain limits of material to avoid erosion,corrosion and excessive
noise generation.
Be aware, and take care of , that local velocities in small pipes, bends and similar obstructions can exceed the values
of previous page.
e.g.) Copper : 1.5m/s
Warning
• Use clean enough water which meets water quality standards. The deterioration of water quality may result in the system breakdown or the water leakage.
• Never use anything other than water as a medium. It may cause a fi re or an explosion.
• Do not use heated or cooled water that is produced by the air to water heat pump directly for drinking or cooking.
There is a risk to damage your health. There is also a risk that installing the water heat exchanger may corrode if the
necessary water quality for air to water heat pump system cannot be maintained. If you wish to use the heated or
cooled water from the heated pump for these purposes, take measure such as to the second heat exchanger within
the water piping system.
Reference data
Required specifi cation and performance of Plate Heat Exchanger.
Required specifi cation
Refrigerant typeR410A
Refrigerant side
Water side
Burst pressure12.45MPa (4.15MPa ×3) or more
Frozen performanceSatisfy an initial performance since 5 times or more of deep freezing.
Heat cycle70,000 times or more…Temperature difference: about 50K
Endurance pressure72,000 times or more…Pressure difference: 3.3MPa (0 ↔ 3.3MPa)
Normal (designed) pressure4.15MPa
Operating temperature-20~100
Refrigerant typeClean water
Normal (designed) pressure1.5MPa
Operating temperature-20~90: (No freezing)
:
Required performance
< For 2.5~3 HP >
Required performance of Plate Heat ExchangerkW9.09.0
Inlet temperaturedegC75100Gas pipe: [12.7mm
Refrigerant side
(R410A)
Water side
* For heating mode, used at counter fl ow direction between refrigerant fl ow and water one.
< For 4~6 HP >
Required performance of Plate Heat ExchangerkW14.014.0
Refrigerant side
(R410A)
Water side
* For heating mode, used at counter fl ow direction between refrigerant fl ow and water one.
PAR-W21MAA(Only for FTC)I/FNG (Continue to indicate “PLEASE WAIT”)
PAR-20MAA(Standard)I/FNG (Continue to indicate “PLEASE WAIT”)
(Old )FTCNG (Continue to indicate “PLEASE WAIT”)
ManufacturerPAC-IF010-E *
Individual installerPAC-IF011B-ECased
ManufacturerPAC-IF010-E *PCB only
Individual installerPAC-IF011B-ECased
STEP I/F
ManufacturerPAC-IF010-E *PCB only
Individual installerPAC-IF011B-ECased
ManufacturerPAC-IF020-E *
Individual installerPAC-IF021B-ECased with R/C
FTC
OK
FTCNG (Continue to indicate “PLEASE WAIT”)
FTCOK
PCB only
PCB only
3-3. Flow chart to check system type
ATW
application
IF
start
Variable capacity
request signals for
Heat Pump is
calculated...
DIGITAL STEP
SYSTEM
IF PCBSystem controller
By local
controller
(your side)
By Non-voltage
Contact signals
ON/OF
Operation
mode
-Heating
-Cooling
capacity
signals
protocol is...
digital step
(non-voltage contact)
Your system is
DIGITAL STEP
SYSTEM
(IF)
(locally supplied)
End user interface
Analog
(0-10v/4-20mA…)
Your system is
ANALOG STEP
SYSTEM
(IF)
ANALOG STEP
SYSTEM
By Non-voltage
IF PCBSystem
Contact signals
ON/OF
Operation
mode
-Heating
-Cooling
controller
(locally supplied)
End user interface
By our FTC
Remote
for maintenance
- to check error code
Capacity
steps
By Non-voltage
Contact signals
1515
Capacity
Remote
For maintenance purpose
- analog signal parameters
steps
By Analog signal
4-20mA / 1-5V / 0-10V
Continued to next page.
FTC
By our FTC
Heat Pump switch ON/OFF
and the operation mode
change is done…
By remote controller
Your system is
SIMPLE SYSTEM.
(FTC)
By external signals from local controller
(non-voltage contact signals)
Your system is
‘Target flow temperature’ is set…
By remote controller
BASIC SYSTEM.
(FTC)
By external signals from local controller
(Analog signal:4-20mA/ 1-5V/ 0-10V)
Your system is ANALOG TEMP. SYSTEM.
(FTC)
SIMPLE SYSTEMBASIC SYSTEM
By Non-voltage
Contact signals
FTC PCB BOXFT C PCB BOXFTC PCB BOX
ON/OFF
Operation mode
Target flow temp.
Remote controller
End user interface
Target flow temp.
Remote controller
Topreset
- target temp. for eachmode
- target temp. parameters
ON/OFF
Operation mode
- Heating
- Heating ECO
- Hot water
- Anti freeze
- Cooling
System controller
(locally supplied)
End user interface
ANALOG TEMP. SYSTEM
Remote controller
Topreset
- analog signal parameters
By Non-voltage
Contact signals
ON/OFF
Operation mode
- Heating +
- Cooling
Target flow temp.
Analog signal
4-20mA/1-5V/0-10V
+In this system,
• Heating ECO mode of FTC is
not available.
• It is NOT necessary to switch
operation mode to realize
Hot water mode, Anti freeze
mode and Heating ECO mode.
Simply change the target temp.
by Analog signal.
System controller
(locally supplied)
End user interface
16
ATA
application
IF
start
Variable capacity
request signals for
Heat Pump is
calculated...
By local
controller
(your side)
capacity
signals
protocol is...
Analog
(0-10v/4-20mA…)
AUTO STEP SYSTEM
IF PCB
ON/OFF
Operation mode
Target retern air temp.
Remote controller
End user interface
By our IF
Your system is
AUTO STEP
SYSTEM
(IF)
DIGITAL STEP SYSTEM
By Non-voltage
Contact signals
IF
PCB
Remote
controller
for
maintenance
- to check
error code
ON/OF
Operation
mode
-Heating
-Cooling
Capacity
steps
By Non-voltage
Contact signals
System
controller
(locally
suppliied)
End user
interface
digital step
(non-voltage contact)
Your system is
DIGITAL STEP
SYSTEM
(IF)
ANALOG STEP SYSTEM
By Non-voltage
Contact signals
IF
PCB
Remote
controller
For
maintenance
purpose
- analog signal
Your systemis
ANALOG STEP
SYSTEM
(IF)
System
controller
ON/OF
Operation
mode
-Heating
-Cooling
Capacity
steps
By Analog
signal
4-20mA / 1-5V / 0-10V
(locally
suppliied)
End user
interface
17
6
5
2
1
1
8
1
2
1
8
1
8
4
3
TH1
OFF/ONOFF/ON
OFF/ON
OFF/ON
TB61
TH2
6
5
214
3
+
TB62
Adjustable resistor
4-20mA/1-5V/0-10V
Wired Remote Controller
(For Maintenance)
6
5
2
1
4
3
8
7
10
9
11
13
12
14
6
5
2
1
4
3
8
7
10
9
11 13
12 14
TB142TB141
(External Output)
(External Input)
L
N
S1 S2 S3
L
N
S1 S2 S3
TB6
DC311~
339V
FUSE
SW6
LED1
RECTIFICATION
LED2
LED3
LED4
LED5
CNS2
(RED)
Interface controller
TO OUTDOOR UNIT
U
U
DSA
21
SYMBOL
INTERFACE CONTROLLER
TB6
TB141
TB142
TB62
TB61
LED1
LED2~5
FUSE
SW1
SW2
SW3
SW6
ZNR01,02
DSA
X1
~
X6
TH1
TH2
TH5
NAME
TERMINAL BLOCK(INTERFACE/OUTDOOR CONNECTING LINE)
TERMINAL BLOCK (External Output)
TERMINAL BLOCK (External Input REMOTE SWITCH)
TERMINAL BLOCK (External Input)
THERMISTOR(TARGET, PIPE)
POWER SUPPLY(I/F)
OPERATION INDICATION
FUSE(T3.15AL250V)
SWITCH(Input selection of inverter capacity setting) *See table 4.
Notes on system controller side in I/F connection system
(1)Please do not transmit “STEP 0” during defrost operation.
Defrost operation might be interrupted, and frost remain.
(Please demand the planned capacity step even when the system controller receives defrost signal from the heat
pump (outdoor unit)).
(2)Please do not transmit “STEP 0” when the outdoor unit(H/P) is abnormal.
Abnormal detection data is reset, and an Abnormal point cannot be confi rmed.
2323
1. System outline
With PAC-IF011B-E, local units can be connected with the outdoor units manufactured by MITSUBISHI ELECTRIC.
The commands, such as Remote switch, Varistor, 4-20mA/1-5V/0-10V and etc., allow the inverter outdoor unit to operate, to
stop and to switch capacity.
By outputting the operation state, the interface can be connected with the local unit.Also, the interface can be connected with
wired remote controller for maintenance so that the maintenance information is obtained.
Only the outdoor units with self-controlled S/W are connectable.
2. System structure
System structure(1)
Outdoor unit capacity switch
Remote switch
Capacity switch of outdoor
unit according to the remote
switch
When auto stop being set,
the difference between room
temperature and set
temperature of interface,
and the pipe temperature
switch the capacity of
outdoor unit automatically.
Wired remote controller
(Auto step mode only)
The difference between
room temperature and set
temperature of wired remote
controller, and the pipe
temperature switch the
capacity of outdoor unit
automatically.
As with the remote controller
for air conditioner, the
interface performs ON/OFF
operation, and changes
operation mode (cooling,
heating ,fan) and set
temperature.
Adjustable resistor(0-10k)
Capacity switch of outdoor
unit according to the
adjustable resistor
System diagramPower supply specifications
Intake temp.
Liquid pipe temp.
Local unit
Local controller
Intake temp.
Liquid pipe temp.
Local unit
Local controller
Intake temp.
Liquid pipe temp.
Local unit
Wired
remote controller
Intake temp.
Liquid pipe temp.
Local unit
Wired
remote controller
Intake temp.
Liquid pipe temp.
Local unit
Local controllerAdjustable resistor
Interface controller
Remote switch
Power line
Interface controller
Remote switch
Interface controller
PAR-21MAA
Power line
Interface controller
PAR-21MAA
Interface controller
A transmission line/Power line
Power line
Outdoor unit
A transmission line/Power line
Power line
Outdoor unit
A transmission line/Power line
Power line
Outdoor unit
A transmission line/Power line
Power line
Outdoor unit
A transmission line/Power line
Power line
Outdoor unit
Power supplied from outdoor unit
Power supply for interface
controller is supplied from the
outdoor unit.
Refer to 3.1.
Separate interface/outdoor unit
power supplies
Power supply for interface
controller and power supply for
outdoor unit are supplied from the
different source.(Common power
source for local unit and interface
controller)
Refer to 3.2.
Power supplied from outdoor unit
Power supply for interface
controller is supplied from the
outdoor unit.
Refer to 3.1.
Separate interface/outdoor unit
power supplies
Power supply for interface
controller and power supply for
outdoor unit are supplied from the
different source.(Common power
source for local unit and interface
controller)
Refer to 3.2.
Power supplied from outdoor unit
Power supply for interface
controller is supplied from the
outdoor unit.
Refer to 3.1.
Intake temp.
Liquid pipe temp.
Local unit
Local controller
Power line
Interface controller
Adjustable resistor
A transmission line/Power line
Power line
Outdoor unit
24
Separate interface/outdoor unit
power supplies
Power supply for interface
controller and power supply for
outdoor unit are supplied from the
different source.(Common power
source for local unit and interface
controller)
Refer to 3.2.
Note:
• REMOTE SWITCH Type A (4bit - 8 setting) / Type B (1bit -1 setting)
Circuit rating
DC12V
The figure is NOT
always against the
ground.
Only the operation
with remote
controller is valid.
(External signal is
invalid)
Refer to 6.
Refer to 6.
2
)
Refer to 7.
Refer to 7.
Refer to 7.
Refer to 7.
Refer to 8, 9.
Refer to 8, 9.
Refer to 8, 9.
Refer to 8, 9.
Available
Refer to 10.
Connect adaptor to
outdoor unit.
M-NET converter
PAC-SF80MA-E
A-Control sub
Interface
PAC-SK82SI-E
Available
Refer to 10.
Connect adaptor to
outdoor unit.
M-NET converter
PAC-SF80MA-E
A-Control sub
Interface
PAC-SK82SI-E
Not available
Not available
25
System structure(2)
Outdoor unit capacity switch
4-20mA
Capacity switch of outdoor
unit according to the signal
of 4-20mA
1-5V
Capacity switch of outdoor
unit according to the signal
of 1-5V
Intake temp.
Liquid pipe temp.
Local unit
Local controller
Intake temp.
Liquid pipe temp.
Local unit
Local controller
Intake temp.
Liquid pipe temp.
Local unit
Local controller
System diagramPower supply specifications
Power supplied from outdoor unit
A transmission line/Power line
Power supply for interface
controller is supplied from the
outdoor unit.
Refer to 3.1.
Interface controller
4-20mA
Power line
Outdoor unit
Separate interface/outdoor unit
Power line
A transmission line/Power line
power supplies
Power supply for interface
controller and power supply for
Interface controller
4-20mA
Power line
Outdoor unit
outdoor unit are supplied from the
different source.
(Common power source for local
unit and interface controller)
Refer to 3.2.
Power supplied from outdoor unit
A transmission line/Power line
Power supply for interface
controller is supplied from the
outdoor unit.
Interface controller
1-5V
Power line
Outdoor unit
Refer to 3.1.
0-10V
Capacity switch of outdoor
unit according to the signal
of 0-10V
Intake temp.
Liquid pipe temp.
Local unit
Local controller
Intake temp.
Liquid pipe temp.
Local unit
Local controller
Intake temp.
Liquid pipe temp.
Local unit
Local controller
Power line
Interface controller
1-5V
Interface controller
0-10V
Power line
Interface controller
0-10V
A transmission line/Power line
Power line
Outdoor unit
A transmission line/Power line
Power line
Outdoor unit
A transmission line/Power line
Power line
Outdoor unit
Separate interface/outdoor unit
power supplies
Power supply for interface
controller and power supply for
outdoor unit are supplied from the
different source.
(Common power source for local
unit and interface controller)
Refer to 3.2.
Power supplied from outdoor unit
Power supply for interface
controller is supplied from the
outdoor unit.
Refer to 3.1.
Separate interface/outdoor unit
power supplies
Power supply for interface
controller and power supply for
outdoor unit are supplied from the
different source.
(Common power source for local
unit and interface controller)
Refer to 3.2.
26
Attachment of sensor
Refer to 4.
Pipe-thermistor/
2-phase might be
neccessary
depending on the
type of the outdoor
unit.
Refer to 4.
Pipe-thermistor/
2-phase might be
neccessary
depending on the
type of the outdoor
unit.
Interface controller
switch setting
SW1-1:ON
SW1-2:ON
SW1-3:OFF
SW6-1:ON
SW6-2:ON
Other switches are
to be set according
to the site.
Refer to 5 for details.
Interface controller specifications
Input and wiringOutput and wiring
Refer to 6.
Refer to 6.
Refer to 7.
Refer to 7.
Other functions/setting
Maintenance
Refer to 8, 9.
Refer to 8, 9.
Connection with
BMS/MELANS
Not available
Not available
Refer to 4.
Pipe-thermistor/
2-phase might be
neccessary
depending on the
type of the outdoor
unit.
Refer to 4.
Pipe-thermistor/
2-phase might be
neccessary
depending on the
type of the outdoor
unit.
Refer to 4.
Pipe-thermistor/
2-phase might be
neccessary
depending on the
type of the outdoor
unit.
SW1-1:ON
SW1-2:ON
SW1-3:OFF
SW6-1:OFF
SW6-2:ON
Other switches are
to be set according
to the site.
Refer to 5 for details.
SW1-1:OFF
SW1-2:OFF
SW1-3:ON
SW6-1:OFF
SW6-2:OFF
Other switches are
to be set according
to the site.
Refer to 5 for details.
Refer to 6.
Refer to 6.
Refer to 6.
Refer to 7.
Refer to 7.
Refer to 7.
Refer to 8, 9.
Refer to 8, 9.
Refer to 8, 9.
Not available
Not available
Not available
Refer to 4.
Pipe-thermistor/
2-phase might be
neccessary
depending on the
type of the outdoor
unit.
Refer to 6.
27
Refer to 7.
Refer to 8, 9.
Not available
3. Power Supply
Interface controller is applicable to both methods of interface unit power supplied from outdoor unit, and of separate interface
unit/outdoor unit power supplies. Choose one according to the site.
(Photo. 3-1)
Inlet for control cable
A
Inlet for power
B
Clamp
C
Interface / Outdoor unit connecting terminals
D
Earth terminal
E
D
A
3.1. Interface unit power supplied from outdoor unit (Photo 3-2)
The following connection patterns are available.
The outdoor unit power supply patterns vary on models.
D
L
ABC
N
S1
S2
S3
E
A Outdoor unit power supply
B Earth leakage breaker
C Wiring circuit breaker or isolating switch
D Outdoor unit
E Interface unit/outdoor unit connecting cables
F Interface unit
F
S1
S2
S3
C
Photo.3-1
C
E
B
Photo.3-2
Interface unit modelPAC-IF011B-E
)
2
Interface unit-Outdoor unit *13× 1.5 (polar)
size
Interface unit-Outdoor unit earth*11 × Min.1.5
Wiring
(mm
Wire No.×
Interface unit-Outdoor unit S1-S2*2AC 230 V
rating
Circuit
*1. Max. 80 m
*2. The fi gures are NOT always against the ground.
S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are not electrically insulated by the transformer or other device.
Interface unit-Outdoor unit S2-S3*2DC24 V
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Power supply cables and interface unit/outdoor unit connecting cables shall not be lighter than polychloroprene sheathed fl exible cable. (Design 60245 IEC 57)
3. Install an earth longer than other cables.
28
3.2. Separate interface unit/outdoor unit power supplies
The following connection patterns are available.
The outdoor unit power supply patterns vary on models.
D
L
N
A
CB
GEB
S1
S2
S3
C
F
L
N
S1
S2
S3
A Outdoor unit power supply
B Earth leakage breaker
C Wiring circuit breaker or isolating switch
D Outdoor unit
E Interface unit/outdoor unit connecting cables
F Interface unit
G Interface unit power supply
If the interface and outdoor units have separate power supplies, refer to the table below.
Separate power supply
specifi cations
Interface unit controller connector (CNS2) connection
change
Disconnected
Photo. 3-3
CNS2
Outdoor unit DIP switch settings (when using separate interface unit/outdoor unit power
supplies only)
ON
OFF
Set the SW8-3 to ON.
12
3
(SW8)
Interface unit modelPAC-IF011B-E
Interface unit power supply ~/N (Single Phase), 50 Hz, 230 V
Interface unit input capacity
Main switch (Breaker)
)
Interface unit power supply & earth3 × Min. 1.5
2
Interface unit-Outdoor unit*2 2 × Min. 0.3
size
Wire
No.×
Wiring
(mm
Interface unit-Outdoor unit earth –
*1 16 A
Interface unit L-N*3AC230V
Interface unit-Outdoor unit S1-S2*3 –
rating
Circuit
*1. A breaker with at least 3.0mm contact separation in each pole shall be provided. Use earth leakage breaker (NV).
*2. Max. 120 m
*3. The fi gures are NOT always against the ground.
Interface unit-Outdoor unit S2-S3*3DC24V
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Power supply cables and interface unit/outdoor unit connecting cables shall not be lighter than polychloroprene sheathed fl exible cable. (Design 60245 IEC 57)
3. Install an earth longer than other cables.
29
Loading...
+ 67 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.