Mitsubishi M-P0398 TECHNICAL MANUAL

June 2008
Air to Water (ATW) Heat pump, Interface (I/F) and Flow temp. controller (FTC) Technical manual
CONTENTS
1. What is ATW heat pump? .......................................................2
2. Heat pump unit_General information ...................................4
3. System design ......................................................................15
4. Interface (I/F) ........................................................................23
5. Flow temp. controller (FTC) .................................................55
6. Requirements........................................................................90
What is ATW heat pump?1
1-1. Compare with conventional fossil fuel boiler
• Heat pumps produce water at 30°C – 60°C
• Ideal for underfl oor heating
• Average underfl oor heating circuit 35°C
• Fossil fuel boilers heat water to 80°C
• Flow temp in rads design temp approx 70°C
• Heat pumps can still be used with radiators
• Larger surface area to emit heat from lower temp water
1-2. Points to notice
1-2-1. Design (Radiator sizing)
• Careful consideration must be given to appropriate application of this technology to maximise its benefi ts – it will not suit all properties, especially many retrofi ts
• Heat emitters may need to be larger
• Lower fl ow temperatures maximise COP
• Various regulations apply to the design and installation of such systems
• Because the fl ow temp. of heat pump is low compare to fossile fuel boiler, the temperature difference between the primary (fl ow water) and secondary (room air) becomes little, it makes the heat emission little. To emit the same amount of heat energy, it is needed to select the radiator that has a larger surface area. Be especially careful of the surface area when you design the radiator.
1-2-2. Defrost
Note: Occasionally, vapor that is made by the defrost operation may seem as if smoke come up from the outdoor unit.
1-2-3. Water Pressure loss (for packaged type outdoor unit)
• Water pressure lose of the heat exchangers are as follows.
Be aware of the infl uence when you design total pipng system.
Hex for PUHZ-W50VHA (ACH30-30Plates)
Secondary (Water - side) Flow rate (L/min) 5 10 15 20 25 30 Pressure Loss (kPa) 1.7 6.0 12.4 20.9 31.4 43.8
Pressure loss (kPa)
50 45 40 35 30 25 20 15 10
5 0
51015202530
Flow rate (L/min)
2
Hex for PUHZ-W85VHA (ACH30-40Plates)
Secondary (Water - side) Flow rate (L/min) 5 10 15 20 25 30 Pressure Loss (kPa) 1.0 3.6 7.5 12.5 18.8 26.2
Pressure loss (kPa)
30.0
25.0
20.0
15.0
10.0
5.0
0.0 51015202530
Flow rate (L/min)
Hex for PUHZ-W112, 140VHA / YHA (ACH50-50Plates)
Secondary (Water - side) Flow rate (L/min) 15 30 45 60 75 90 Pressure Loss (kPa) 1.3 4.9 10.9 19.3 29.9 42.8
Pressure loss (kPa)
45.0
40.0
35.0
30.0
25.0
20.0
15.0
10.0
5.0
0.0 15 30 45 60 75 90
Flow rate (L/min)
33
Heat pump unit_General information2
2-1. Line-up
2-1-1. Outdoor unit for Air to water (1) Packaged type: The Air to Water outdoor unit with a plate HEX (refrigerant-water) inside
Connectable models
Capacity
( HP )
2 PUHZ-W50VHA — 3 PUHZ-W85VHA — 4 PUHZ-HW112YHA 5 PUHZ-HW140VHA PUHZ-HW140YHA
1-phase 3-phase 1-phase 3-phase
(2) Split type: The standard outdoor unit without a plate HEX (refrigerant-water) inside
Connectable models
Capacity
( HP )
2.5 PUHZ-RP60VHA3#1 — 3 PUHZ-RP71VHA3#1 PUHZ-HRP71VHA(2) — 4 PUHZ-RP100VHA3#1 PUHZ-RP100YHA3#1 PUHZ-HRP100VHA(2) PUHZ-HRP100YHA(2) 5 PUHZ-RP125VHA2#2 PUHZ-RP125YHA2#2 PUHZ-HRP125YHA(2) 6 PUHZ-RP140VHA2#2 PUHZ-RP140YHA2#2
* Outdoor units (PUHZ-RP or PUHZ-P) other than the above-mentioned become possible by connecting TH5 ( 2-phase refrig-
erant temp. thermistor ) with the interface only for Air to Air use.
1-phase 3-phase 1-phase 3-phase
Packaged models ZUBADAN-Packaged models
Split Replace inverter models Split ZUBADAN models
2-1-2. Air to Air application
INTER FACE MODEL NAME PAC-IF011B-E / PAC-IF010-E
AUTO STEP *1
MANUAL STEP *2
MANUAL STEP MODE is New function of INTER FACE (Fixed capacity = Compressor frequency (Hz) fi xed mode) .
<Old models : The models that are not described in the table above.>
*1: With(Auto-mode)+(SW2-6 is OFF)+(2phase thermistor), all A-control outdoor units are able to connect to PAC-IF010/ *2: With(Manual-mode)+(SW2-6 is OFF)+(2phase thermistor), from following RP type outdoor units are able to connect to
OUTDOOR UNIT 35 50 60 71 100 125 140 200 250
PUHZ-HRP VHA(2) V/YHA(2) YHA(2) — PUHZ-RP VHA3 VHA3 VHA3 VHA3 V/YHA3 V/YHA2 V/YHA2 YHA2 YHA2 PUHZ-P VHA2 VHA2 VHA2 YHA YHA SUZ-KA VA VA VA VA — PUH-P V/YHA V/YHA YHA YHA MYA MYA
OUTDOOR UNIT 35 50 60 71 100 125 140 200 250
PUHZ-HRP VHA V(Y)HA YHA — PUHZ-RP VHA3 VHA3 VHA3 VHA3 V/YHA3 V/YHA2 V/YHA2 YHA2 YHA2
2 Phase (Gas/Liquid) pipe thermistor is required (TH5). Also, Interface P.C.B. SW2-6 need to be set "OFF (No LEV self control mode)" .
011B-E only for Air to Air use. PAC-IF010/011B-E only for Air to Air use.
PUHZ-RP35V, 50V, 60V, 71V,100V/Y,125V/Y,140V/YHA2 PUHZ-RP200Y, 250YHA
²
¹
4
2-1-3. Reference manual
Outdoor unit Service
PUHZ-W50VHA PUHZ-W85VHA PUHZ-HW112YHA PUHZ-HW140VHA PUHZ-HW140YHA PUHZ-RP60VHA3#1 PUHZ-RP71VHA3#1 PUHZ-RP100VHA3#1 PUHZ-RP125VHA2#2 PUHZ-RP140VHA2#2 PUHZ-RP100YHA3#1 PUHZ-RP125YHA2#2 PUHZ-RP140YHA2#2 PUHZ-HRP71VHA(2) PUHZ-HRP100VHA(2) PUHZ-HRP100YHA(2) PUHZ-HRP125YHA(2)
manual
OCH439 OCB439
OC374 OC374
OCH425 OCB425
Parts catalog
I/F
FTC
2-2. Data
2-2-1. Packaged type Refer to each model's service manual.
2-2-2. Split [1]
Specifi cations(Reference data(connect to plate heat exchanger))
Rating conditions
Nominal operating condition
Heating (A2/W35)
Outside air temperature (Dry-bulb) +2 Outside air temperature (Wet-bulb) +1 Water temperature (inlet/outlet) +30/+35
Heating (A7/W35)
Outside air temperature (Dry-bulb) +7 Outside air temperature (Wet-bulb) +6 Water temperature (inlet/outlet) +30/+35
Heating (A7/W45)
Outside air temperature (Dry-bulb) +7 Outside air temperature (Wet-bulb) +6 Water temperature (inlet/outlet) +40/+45
: :
:
: :
:
: :
:
Type Model name Parts catalog cased PAC-IF011B-E OCB427 PCB only PAC-IF010-E — cased PAC-IF021B-E OCB427 PCB only PAC-IF020-E
55
(1) PUHZ-HRP • V/YHA2
Outdoor unit
Model name PUHZ-HRP71VHA2
Power supply (Phase, Voltage, Frequency)
Breaker size A 32
Nominal water fl ow L/min 22.9
Heating (A2/W35)
Heating (A7/W35)
Heating (A7/W45)
Outdoor unit
Model name
Power supply (Phase, Voltage, Frequency)
Breaker size A 40 / 16
Nominal water fl ow L/min 32.1 Heating (A2/W35)
Heating (A7/W35)
Heating (A7/W45)
Heating (A7/W55)
Outdoor unit
Model name PUHZ-HRP125YHA2
Power supply (Phase, Voltage, Frequency)
Breaker size A 16
Nominal water fl ow L/min 40.1 Heating (A2/W35)
Heating (A7/W35)
Heating (A7/W45)
Capacity kW 8.00 COP 3.24 Power input 2.47 Capacity kW 8.00 COP 4.40 Power input 1.82 Capacity kW 8.00 COP 3.24 Power input 2.47
Capacity kW 11.20 COP 3.02 Power input 3.71 Capacity kW 11.20 COP 4.26 Power input 2.63 Capacity kW 11.20 COP 3.24 Power input 3.46 Capacity kW 11.20 COP 2.40 Power input 4.67
Capacity kW 14.00 COP 2.70 Power input 5.19 Capacity kW 14.00 COP 4.22 Power input 3.32 Capacity kW 14.00 COP 3.20 Power input 4.38
1[, 230V, 50Hz
PUHZ-HRP100VHA2 / PUHZ-HRP100YHA2
1[, 230V, 50Hz /
3[, 400V, 50Hz
3[, 400V, 50Hz
Guaranteed operating range (Outdoor)
Heating Cooling
: :
-25 ~ +35
-5 ~ +46
Plate heat exchanger
ALFA LAVAL
ACH50
A: 50 mm B: 466 mm
Ref.IN
(Heating)
w
Water OUT
B
W: 112 mm H: 526 mm D: 130 mm 50 plates
Ref.OUT (Heating)
A
H
Water IN
D
Refrigerant pipng length from outdoor unit to heat exchanger (Water HEX): 5m
Maximum outlet water temperature
65
]
60
55
50
45
Maximum outlet water temptemperature [°C
40
-25 -20
-15 -10 -5 0 5 10
Ambient temperature [°C]
The performance might be decreased by the refrigerant pipng length, insulation of refrigerant pipng and heat exchanger (Water HEX).
6
(2) PUHZ-RP • VHA3/YHA3(2)
Outdoor unit
Model name PUHZ-RP60VHA3#1
Power supply (Phase, Voltage, Frequency)
Breaker size A 25
Nominal water fl ow L/min 20.1 Heating
(A2/W35)
Heating (A7/W35)
Heating (A7/W45)
Outdoor unit
Model name PUHZ-RP71VHA3#1
Power supply (Phase, Voltage, Frequency)
Breaker size A 25
Nominal water fl ow L/min 22.9 Heating
(A2/W35)
Heating (A7/W35)
Heating (A7/W45)
Capacity kW 6.80 COP 2.94 Power input kW 2.31 Capacity kW 7.00 COP 4.29 Power input kW 1.63 Capacity kW 7.00 COP 3.27 Power input kW 2.14
Capacity kW 7.50 COP 2.92 Power input kW 2.57 Capacity kW 8.00 COP 4.21 Power input kW 1.90 Capacity kW 8.00 COP 3.20 Power input kW 2.50
1[, 230V, 50Hz
1[, 230V, 50Hz
Guaranteed operating range (Outdoor)
Heating Cooling : -5 ~ +46
:
-11 ~ +35
Plate heat exchanger
ALFA LAVAL
ACH50
A: 50 mm B: 466 mm
Ref.IN
(Heating)
w
Water OUT
B
W:112 mm H: 526 mm D: 82 mm 30 plates
Ref.OUT (Heating)
A
H
Water IN
D
Refrigerant pipng length from outdoor unit to heat exchanger (Water HEX): 5m
Maximum outlet water temperature
65
]
60
55
50
Maximum outlet water temptemperature [°C
45
-10 -5 0 5 10
Ambient temperature [°C]
The performance might be decreased by the refrigerant pipng length, insulation of refrigerant pipng and heat exchanger (Water HEX).
7
Outdoor unit
Model name
Power supply (Phase, Voltage, Frequency)
Breaker size A 32 / 16
Nominal water fl ow L/min 32.1 Heating
(A2/W35)
Heating (A7/W35)
Heating (A7/W45)
Outdoor unit
Model name
Power supply (Phase, Voltage, Frequency)
Breaker size A 32/16
Nominal water fl ow L/min 40.1 Heating
(A2/W35)
Heating (A7/W35)
Heating (A7/W45)
Outdoor unit
Model name
Power supply (Phase, Voltage, Frequency)
Breaker size A 40/16
Nominal water fl ow L/min 45.9 Heating
(A2/W35)
Heating (A7/W35)
Heating (A7/W45)
Capacity kW 10.50 COP 2.90 Power input kW 3.62 Capacity kW 11.20 COP 4.21 Power input kW 2.66 Capacity kW 11.20 COP 3.20 Power input kW 3.50
Capacity kW 11.50 COP 2.70 Power input kW 4.26 Capacity kW 14.00 COP 4.15 Power input kW 3.37 Capacity kW 14.00 COP 3.10 Power input kW 4.51
Capacity kW 11.70 COP 2.69 Power input kW 4.35 Capacity kW 16.00 COP 3.90 Power input kW 4.10 Capacity kW 16.00 COP 3.00 Power input kW 5.34
PUHZ-RP100VHA3#1 / PUHZ-RP100YHA3#1
1[, 230V, 50Hz /
3[, 400V, 50Hz
PUHZ-RP125VHA2#2 / PUHZ-RP125YHA2#2
1[, 230V, 50Hz /
3[, 400V, 50Hz
PUHZ-RP140VHA2#2 / PUHZ-RP140YHA2#2
1[, 230V, 50Hz /
3[, 400V, 50Hz
Guaranteed operating range (Outdoor)
Heating Cooling
: :
-20 ~ +35
-5 ~ +46
Plate heat exchanger
ALFA LAVAL
ACH50
A: 50 mm B: 466 mm
Ref.IN
(Heating)
w
Water OUT
B
W:112 mm H: 526 mm D: 130 mm 50 plates
Ref.OUT (Heating)
A
H
Water IN
D
Refrigerant pipng length from outdoor unit to heat exchanger (Water HEX): 5m
Maximum outlet water temperature
65
]
60
55
50
45
Maximum outlet water temptemperature [°C
40
-20 -15
-10 -5 0 5 10
Ambient temperature [°C]
The performance might be decreased by the refrigerant pipng length, insulation of refrigerant pipng and heat exchanger (Water HEX).
8
[2]
Standard operation data <Split> Reference data (connect to Plate HEX)
(1) PUHZ-HRP • V/YHA2
Mode
Capacity W 7,100 8,000 10,000 11,200 12,500 14,000
Total
Input kW 2.20 1.82 3.67 2.61 4.80 3.50 Outdoor unit PUHZ-HRP71VHA2 Phase, Hz 1, 50 1/3, 50 3, 50
Voltage V 230 230 / 400 400
Electrical circuit
Current A 9.9 8.2 16.5/5.6 11.7/4.0 7.3 5.3 Discharge pressure MPa 2.4 2.0 2.6 2.1 2.8 2.3 Suction pressure MPa 0.8 0.7 0.8 0.7 0.8 0.7 Discharge temperature Condensing temperature Suction temperature Evaporating temperature Evaporator inlet temperature
Refrigerant circuit
Evaporator outlet temperature Condenser inlet temperature Condenser outlet temperature
Cooling
(A35/W7)
: : : : : : : :
70 60 78 63 84 70 42 35 46 36 47 39 12 6 11 4 10 3
525251 5—5—5—
5—5—5— —55—60—65 —33—31—30
Heating
(A7/W35)
ACH50-50 plates
Cooling
(A35/W7)
PUHZ-HRP100VHA2/ PUHZ-HRP100YHA2
Heating
(A7/W35)
Cooling
(A35/W7)
PUHZ-HRP125YHA2
Heating
(A7/W35)
Flow volume L/min 20.4 22.9 28.7 34.4 35.8 40.1
Water
Outlet water temperature
conditions
D.B.
Intake air temperature
Outdoor
conditions
The unit of pressure has been changed to MPa based on international SI system. The conversion factor is : 1(MPa)=10.2(kgf/F)
W.B.
:
:
:
735735735
35 7 35 7 35 7
24 6 24 6 24 6
9
(2) PUHZ-RP • VHA3/YHA3(2)
Mode
Capacity W 6,000 7,000 6,600 8,000 9,100 11,200
Total
Input kW 2.31 1.63 2.59 1.90 3.31 2.66 Outdoor unit PUHZ-RP60VHA3#1 PUHZ-RP71VHA3#1 Phase, Hz 1, 50 1, 50 1/3, 50
Voltage V 230 230 230 / 400 Current A 10.3 7.2 11.4 8.4 14.5 / 5.1 11.8 / 4.1
Electrical circuit
Discharge pressure MPa 2.7 2.1 2.7 2.2 2.6 2.1 Suction pressure MPa 0.8 0.7 0.8 0.7 0.8 0.7 Discharge temperature Condensing temperature Suction temperature Evaporating temperature Evaporator inlet temperature
Refrigerant circuit
Evaporator outlet temperature Condenser inlet temperature Condenser outlet temperature
: : : : : : : :
ACH50-30 plates ACH50-50 plates
Cooling
(A35/W7)
70 65 70 66 74 65 45 36 45 36 44 36
454265 515151 6—6—5—
5—5—5— —56—57—58 —34—33—35
Heating
(A7/W35)
Cooling
(A35/W7)
Heating
(A7/W35)
Cooling
(A35/W7)
PUHZ-RP100VHA3#1/ PUHZ-RP100YHA3#1
Heating
(A7/W35)
Flow volume L/min 17.2 20.1 18.9 22.9 26.1 32.1
Water
Outlet water temperature
conditions
D.B.
Intake air temperature
Outdoor
conditions
The unit of pressure has been changed to MPa based on international SI system. The conversion factor is : 1(MPa)=10.2(kgf/F)
W.B.
:
:
:
7 35 7 35 7 35
357357357
246246246
10
ACH50-50 plates
Mode
Capacity W 12,000 14,000 12,500 16,000 Input kW 5.10 3.37 5.38 4.10
Total
Outdoor unit Phase, Hz 1 / 3, 50 1 / 3, 50
circuit
Voltage V 230 / 400 230 / 400
Electrical
Current A 22.4 / 7.6 15.0 / 5.2 23.6 / 8.1 18.2 / 6.2 Discharge pressure MPa 2.8 2.1 2.8 2.2 Suction pressure MPa 0.7 0.7 0.7 0.7 Discharge temperature Condensing temperature Suction temperature Evaporating temperature Evaporator inlet temperature
Evaporator outlet temperature
Refrigerant circuit
Condenser inlet temperature Condenser outlet temperature
Flow volume L/min 34.4 40.1 35.8 45.9
: : : : : : : :
Cooling
(A35/W7)
PUHZ-RP125VHA2#2/ PUHZ-RP125YHA2#2
80 69 81 67 46 36 46 36
3431 5-15-1 6—6—
5—5— —63—61 —35—34
Heating
(A7/W35)
Cooling
(A35/W7)
PUHZ-RP140VHA2#2/ PUHZ-RP140YHA2#2
Heating
(A7/W35)
Water
Outlet water temperature
conditions
D.B.
Intake air temperature
Outdoor
conditions
The unit of pressure has been changed to MPa based on international SI system. The conversion factor is : 1(MPa)=10.2(kgf/F)
W.B.
:
:
:
735735
357357
246246
11
[4]
Capacity correction curves (Refrigerant pipng length)
Cooling and heating capacity is lowered according to pipe length. Capacity can be obtained by referring to the capacity curves below.
Cooling
100
Heating
95
90
85
80
Capacity ratio [%]
75
Note: The permitted pipe length is up to 55m for RP 60, 71 model. The permitted pipe length is up to 80m for HRP71 and 100~ 140 model.
70
5 101520253035404550556065707580
Corrected pipe length [m]
[5]
Refrigerant circuit diagram (Representative pattern)
PUHZ-HRP
Water OUT
Plate HEX
Water IN
Thermistor TH1 (Outlet water)
Thermistor TH2 (Liquid pipe)
V/YHA2 + Plate HEX (ACH50) + FTC (TH1/2)
Ball valve
Refrigerant GAS pipe connection (5/8 inch)
Linear expansion valve B
Refrigerant LIQUID pipe connection (3/8 inch)
Stop valve (with service port)
Strainer #50
Charge plug (Low pressure)
Strainer #100
Strainer #100
Solenoid valve (Four-way valve)
Power receiver
Linear expansion valve C
Low pressure switch 63L
Strainer #100
Cooling 60 models
P-sensor
Charge plug (High pressure)
Muffler
Strainer #100
Compressor
Heat exchanger
High pressure switch 63H
Thermistor TH32 (Outdoor pipe)
Thermistor TH4 (Discharge)
Linear expansion valve A
Injection port
Heat interchange circuit
Heating
Cooling 71 model
Cooling 100 model
Cooling 125 model
Cooling 140 model
Thermistor TH7 (Outdoor)
Thermistor TH6 (Outdoor 2-phase pipe)
Thermistor TH3 (Outdoor pipe)
Distributor
Thermistor TH33
Strainer #100
Refrigerant flow in cooling Refrigerant flow in heating
(Outdoor pipe)
Restrictor valve
Bypass valve
Replace filter
Strainer #100
12
[6]
Notifi cation to design/select HEX (Refrigerant - Water)
• Specifi cations of AHU and compatibility with regulations must be confi rmed by your company.
• Selection of an apporopriate AHU (with appropriate specifi cations to match those of units connected to the AHU such as confi guration, dimension, life-span, vibration, noise level, or features) must be made by your company.
• Mitsubishi Electric shall not be liable for any damage to the entire system or the AHU main body caused by connected AHU with wrong specifi cation or wrong usage of AHU.
• Mitsubishi Electric shall not be liable for any damage to the outdoor units caused by AHU damage.
( AHU : hydro box or refrigerant - water HEX )
Heat exchanger
(1) Withstanding pressure
Designed pressure of outdoor unit is 4.15 MPa. Following must be satisfi ed for burst pressure of connecting application. Burst pressure : More than 12.45 MPa (3 times more than designed pressure)
(2) Performance
Secure the heat exchanger capacity which meets the following conditions. If the conditions are not met, it may result in malfunction caused by the protection operation or the outdoor unit may be turned off due to the operation of protection system.
1. Evaporate temperature is more than 4: in max. frequency operation under *1 the cooling rated conditions.
2. In case of hot water supply, condense temperature is less than 58: in max. frequency operation with the outside tem­perature 7:D.B./6:W.B. *1. Outdoor: 35:D.B./24:W.B.
(3) Heat exchanger internal capacity
Heat exchanger internal capacity must be within the capacity range shown below. If the heat exchanger below the mini­mum capacity is connected, it may result in the back fl ow of liquid or the failure of the compressor. If the heat exchanger above the maximum capacity is connected, it may result in the defi ciency in performance due to lack of refrigerant or overheating of the compressor. Minimum capacity : 10 х Model capacity [J] / Maximum capacity : 30 х Model capacity [J] e.g. When connecting to PUHZ-HRP100 VHA2
Minimum capacity : 10 х 100 =1000
Maximum capacity : 30 х 100 =3000 Model capacity 60(2.5HP) 71(3HP) 100(4HP) 125(5HP) 140(6HP) Maximum capacity [J] 1800 2130 3000 3750 4200 Minimum capacity [J] 600 710 1000 1250 1400
J J
Warranty for SPILIT solution
(4) Contamination maintenance
1. Wash the inside of heat exchanger to keep it clean. Be sure to rince not to leave fl ux. Do not use chlorine detergent for wash.
2. Be sure that the amount of contamination per unit cubic content of heat transfer pipe is less than the following amount. Example) In case of [ 9.52mm Residual water : 0.6M/C, Residual oil : 0.5M/C, Solid foreign object : 1.8M/
Note:
• Install the hydraulic fi lter at the water intake.
• Use the inlet water of higher than 5 ˚C and lower than 55 ˚C.
• The water in a system should be clean and with pH value of 6.5-8.0.
• The followings are the maximum values; Calcium : 100mg/L Chlorine : 100mg/L Iron/manganese : 0.5mg/L
• Refrigerant pipe diameter from outdoor unit to refrigerant-water HEX (Only for SPLIT type) Use the pipe with same diameter size as the refrigerant pipe connection diameter of outdoor unit.(Refer to outdoor unit installation manual.)
• Make sure to perform the frozen prevention measure for water pipe system.(Water piping insulation, back-up pump system, using of a certain % ethylene glycol instead of normal water)
[Reference]
TB142 has for “Forced Comp. OFF” function as the EXTERNAL INPUT(Contact signal). To input the abnormal signal of water pump or the abnormal lowering of water fl ow amount with non-voltage contact signal makes the outdoor unit stop forcibly. For details, refer to each part of I/F or FTC on this manual.
C
13
• The water velocity in pipes should be kept within certain limits of material to avoid erosion,corrosion and excessive noise generation. Be aware, and take care of , that local velocities in small pipes, bends and similar obstructions can exceed the values of previous page.
e.g.) Copper : 1.5m/s
Warning
• Use clean enough water which meets water quality standards. The deterioration of water quality may result in the sys­tem breakdown or the water leakage.
• Never use anything other than water as a medium. It may cause a fi re or an explosion.
• Do not use heated or cooled water that is produced by the air to water heat pump directly for drinking or cooking. There is a risk to damage your health. There is also a risk that installing the water heat exchanger may corrode if the necessary water quality for air to water heat pump system cannot be maintained. If you wish to use the heated or cooled water from the heated pump for these purposes, take measure such as to the second heat exchanger within the water piping system.
Reference data
Required specifi cation and performance of Plate Heat Exchanger.
Required specifi cation
Refrigerant type R410A
Refrigerant side
Water side
Burst pressure 12.45MPa (4.15MPa ×3) or more Frozen performance Satisfy an initial performance since 5 times or more of deep freezing. Heat cycle 70,000 times or more…Temperature difference: about 50K Endurance pressure 72,000 times or more…Pressure difference: 3.3MPa (0 3.3MPa)
Normal (designed) pressure 4.15MPa Operating temperature -20~100 Refrigerant type Clean water Normal (designed) pressure 1.5MPa Operating temperature -20~90: (No freezing)
:
Required performance
< For 2.5~3 HP >
Required performance of Plate Heat Exchanger kW 9.0 9.0
Inlet temperature degC 75 100 Gas pipe: [12.7mm
Refrigerant side (R410A)
Water side
* For heating mode, used at counter fl ow direction between refrigerant fl ow and water one. < For 4~6 HP >
Required performance of Plate Heat Exchanger kW 14.0 14.0
Refrigerant side (R410A)
Water side
* For heating mode, used at counter fl ow direction between refrigerant fl ow and water one.
Condensing temperature degC 39.5 63.5 Liquid pipe: [9.52mm Subcool degC 2 2 Max. pressure loss kPa 50 50 Inlet temperature degC 30 55 Inlet / outlet pipe: [28.6mm Outlet temperature degC 35 60 Water fl ow volume L/min 25.8 25.8 Max. pressure loss kPa 50 50
Inlet temperature degC 75 100 Gas pipe: [15.88mm Condensing temperature degC 39.5 63.5 Liquid pipe: [9.52mm Subcool degC 2 2 Max. pressure loss kPa 50 50 Inlet temperature degC 30 55 Inlet / outlet pipe: over [28.6mm Outlet temperature degC 35 60 Water fl ow volume L/min 40.1 40.1 Max. pressure loss kPa 50 50
14
System design3
3-1. System type
* with step I/F by digital/analog signals * with FTC simple/basic/analog temp.
Application Capacity control For Model name Type
Local controller
Air to Air
I/F
Local controller
Air to Water
FTC
* PAC-IF010-E, PAC-IF020-E : PCB 10pcs/set
3-2. Combination of remote controller
Remote controller model Connected object Connectability PAR-21MAA (Standard) I/F
PAR-W21MAA (Only for FTC) I/F NG (Continue to indicate “PLEASE WAIT”)
PAR-20MAA (Standard) I/F NG (Continue to indicate “PLEASE WAIT”) (Old ) FTC NG (Continue to indicate “PLEASE WAIT”)
Manufacturer PAC-IF010-E * Individual installer PAC-IF011B-E Cased Manufacturer PAC-IF010-E * PCB only Individual installer PAC-IF011B-E Cased
STEP I/F
Manufacturer PAC-IF010-E * PCB only Individual installer PAC-IF011B-E Cased Manufacturer PAC-IF020-E * Individual installer PAC-IF021B-E Cased with R/C
FTC
OK
FTC NG (Continue to indicate “PLEASE WAIT”)
FTC OK
PCB only
PCB only
3-3. Flow chart to check system type
ATW
application
IF
start
Variable capacity request signals for Heat Pump is calculated...
DIGITAL STEP SYSTEM
IF PCB System controller
By local controller (your side)
By Non-voltage Contact signals
ON/OF
Operation mode
-Heating
-Cooling
capacity signals protocol is...
digital step (non-voltage contact)
Your system is DIGITAL STEP SYSTEM (IF)
(locally supplied)
End user interface
Analog (0-10v/4-20mA…)
Your system is ANALOG STEP SYSTEM (IF)
ANALOG STEP SYSTEM
By Non-voltage
IF PCB System
Contact signals
ON/OF
Operation mode
-Heating
-Cooling
controller (locally supplied)
End user interface
By our FTC
Remote
for maintenance
- to check error code
Capacity steps
By Non-voltage Contact signals
1515
Capacity
Remote
For maintenance purpose
- analog signal parameters
steps By Analog signal
4-20mA / 1-5V / 0-10V
Continued to next page.
FTC
By our FTC
Heat Pump switch ON/OFF and the operation mode change is done…
By remote controller
Your system is
SIMPLE SYSTEM.
(FTC)
By external signals from local controller (non-voltage contact signals)
Your system is
‘Target flow temperature’ is set…
By remote controller
BASIC SYSTEM.
(FTC)
By external signals from local controller (Analog signal:4-20mA/ 1-5V/ 0-10V)
Your system is ANALOG TEMP. SYSTEM.
(FTC)
SIMPLE SYSTEM BASIC SYSTEM
By Non-voltage Contact signals
FTC PCB BOX FT C PCB BOX FTC PCB BOX
ON/OFF
Operation mode
Target flow temp.
Remote controller
End user interface
Target flow temp.
Remote controller
Topreset
- target temp. for eachmode
- target temp. parameters
ON/OFF
Operation mode
- Heating
- Heating ECO
- Hot water
- Anti freeze
- Cooling
System controller (locally supplied)
End user interface
ANALOG TEMP. SYSTEM
Remote controller
Topreset
- analog signal parameters
By Non-voltage Contact signals
ON/OFF
Operation mode
- Heating +
- Cooling
Target flow temp. Analog signal
4-20mA/1-5V/0-10V
+In this system,
• Heating ECO mode of FTC is not available.
• It is NOT necessary to switch operation mode to realize Hot water mode, Anti freeze mode and Heating ECO mode. Simply change the target temp. by Analog signal.
System controller
(locally supplied)
End user interface
16
ATA
application
IF
start
Variable capacity request signals for Heat Pump is calculated...
By local controller (your side)
capacity signals protocol is...
Analog (0-10v/4-20mA…)
AUTO STEP SYSTEM
IF PCB
ON/OFF
Operation mode
Target retern air temp.
Remote controller
End user interface
By our IF
Your system is AUTO STEP SYSTEM (IF)
DIGITAL STEP SYSTEM
By Non-voltage Contact signals
IF PCB
Remote
controller
for maintenance
- to check error code
ON/OF
Operation mode
-Heating
-Cooling
Capacity steps
By Non-voltage Contact signals
System controller (locally suppliied)
End user interface
digital step (non-voltage contact)
Your system is DIGITAL STEP SYSTEM (IF)
ANALOG STEP SYSTEM
By Non-voltage Contact signals
IF PCB
Remote controller
For maintenance purpose
- analog signal
Your systemis ANALOG STEP SYSTEM (IF)
System controller
ON/OF
Operation mode
-Heating
-Cooling
Capacity steps
By Analog signal 4-20mA / 1-5V / 0-10V
(locally suppliied)
End user interface
17
6
5
2
1
1
8
1
2
1
8
1
8
4
3
TH1
OFF/ONOFF/ON
OFF/ON
OFF/ON
TB61
TH2
6
5
214
3
+
TB62
Adjustable resistor
4-20mA/1-5V/0-10V
Wired Remote Controller
(For Maintenance)
6
5
2
1
4
3
8
7
10
9
11
13
12
14
6
5
2
1
4
3
8
7
10
9
11 13
12 14
TB142 TB141
(External Output)
(External Input)
L
N
S1 S2 S3
L
N
S1 S2 S3
TB6
DC311~
339V
FUSE
SW6
LED1
RECTIFICATION
LED2
LED3
LED4
LED5
CNS2
(RED)
Interface controller
TO OUTDOOR UNIT
U
U
DSA
21
SYMBOL
INTERFACE CONTROLLER
TB6
TB141
TB142
TB62
TB61
LED1
LED2~5
FUSE
SW1
SW2
SW3
SW6
ZNR01,02
DSA
X1
~
X6
TH1
TH2
TH5
NAME
TERMINAL BLOCK(INTERFACE/OUTDOOR CONNECTING LINE)
TERMINAL BLOCK (External Output)
TERMINAL BLOCK (External Input REMOTE SWITCH)
TERMINAL BLOCK (External Input)
THERMISTOR(TARGET, PIPE)
POWER SUPPLY(I/F)
OPERATION INDICATION
FUSE(T3.15AL250V)
SWITCH(Input selection of inverter capacity setting) *See table 4.
SWITCH(Function switch)*See table 5 and 6.
SWITCH(LED2~5 Display setting)
SWITCH(4-20mA/1-5V/0-10V switch)*See table 4.
VARISTOR
SURGE ABSORBER
RELAY
TARGET TEMP. THERMISTOR
(0
/15k, 25/5.2k DETECT)
PIPE TEMP . THERMIST OR/LIQUID
(0
/15k, 25/5.2k DETECT)
PIPE TEMP . THERMIST OR/2-PHASE
(0
/15k, 25/5.2k DETECT)
TB6
TO OUTDOOR UNIT
POWER SUPPLY
~/N
21354678
TB141
11 10
9
121314
ZNR01
ZNR02
21354678
TB142
I/F
9
X1 X2 X3 X4 X5 X6
Item
Operation Output
Error Output
Comp. Output
Defrost Output
Mode(Cool) Output
Mode(Heat) Output
(OUT1)
(OUT2)
(OUT3)
(OUT4)
(OUT5)
(OUT6)
(OUT7)
X1X2X3X4X5
X6
ON
ErrorONONONON
OFF
Normal
OFF(Comp. OFF)
OFF
OFF
OFF
(Comp. ON)
(Defrosting)
(Cooling)
(Heating)
TB141
1-2
3-4
5-6
7-8
9-10
11-12
13-14
Refer to table 1.
table 1
*1(Fig.1)
Refer to table 2, 3.
Remark
SW2-1, SW2-2: ON is valid.
ON
Forced Comp. OFF
Heating
OFF
Normal
Cooling
Item
Forced Comp. OFF
Fixed operation mode
TB142
1-2 (IN1)
3-4 (IN2)
table 2
Step for capacity setting
TB142
10-11
(COM-IN5)
TB142
10-12
(COM-IN6)
TB142
10-13
(COM-IN7)
TB142
10-14
(COM-IN8)
Remark
Auto mode
OFF
Fixed capacity
(Hz fixed)
mode
table 3
TB142
I/F
1110121314
1110121314
At site
4bit8 switch
OFF
~AUTO
TB142
I/F
At site
Step1
Step4
Step7
AUTO
SW1-1
OFFONONONOFFONOFF
SW2-3
OFFONOFFONOFFONOFF
ON
OFFONOFFONOFFONOFFONOFF
OFF
OFFONON
OFF
OFFONON
OFF
OFF
OFF
OFF
OFFONONONON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF 0%
Step1 10%
Step2 20%
Step3 30%
Step4 50%
Step5 70%
Step6 80%
Step7 100%
Auto
OFF 0%
Step1 10%
Step4 50%
Step7 100%
Auto
[OFF]
[ON]
[OFF]
[ON]
SW2-4
OFF
OFFONON
OFF
OFFONON
SW2-5
OFF
OFF
OFF
OFFONONONON
Details
Not fixed (Remote controller setting)
Cooling 19 ˚C/Heating 17 ˚C FIX
20 ˚C FIX
22 ˚C FIX
24 ˚C FIX
26 ˚C FIX
28 ˚C FIX
Cooling 30 ˚C / Heating 28 ˚C FIX
SW1-2
OFF
OFFONON
OFF
OFF
ON
SW2-1
OFFONOFF
ON
SW2-2
OFF
OFFONON
SW1-3
OFF
OFF
OFF
OFFONON
ON
SW6-1
OFF
OFFONOFF
OFF
OFF
OFF
SW6-2
OFF
OFFONON
OFF
OFF
OFF
Input
TypeA
(4bit-8 setting)
TypeB
(1bit-1 setting)
4-20mA
1-5V
0-10V
0-10k
No input(Auto mode)
Step for capacity setting
OFF/Step 1/Step 2/
...
/Step 7/Auto
OFF/Step 1/Step 4/Step 7/Auto
OFF/Step 1/Step 2/
...
/Step 7
OFF/Step 1/Step 2/
...
/Step 7
OFF/Step 1/Step 2/
...
/Step 7
OFF/Step 1/Step 2/
...
/Step 7/Auto
Only Auto mode
table 4 SW1, SW6 : Input selection of inverter capacity setting
table 5 SW2-1/2-2 : Fixed operation mode
Details
Not FIX
(Depending on Remote controller setting)
[Cooling]FIX
[Heating]FIX
External input(Depending on TB142-3,4)
1. SymboIs used in wiring diagram are, : Connector, : Terminal block.
2. Interface controller and outdoor connecting wires have poIarities, make sure to match
terminal numbers(S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit
electric wiring diagram for servicing.
4. This diagram shows the wiring of Interface controller and outdoor connecting wires.(specification of 230V),
adopting superimposed system of power and signal.
*1 : When work to supply power separately to Interface controller and outdoor units was applied, refer to Fig 1.
*2 : Remove the short-circuited connector CNS2 when work to supply power separately to
Interface controller and outdoor units was applied.
ONOFF
TypeA TypeB
At site
*2 Remove the
short-circuited connector
CNS2.
table 6 SW2-3/2-4/2-5 : Fixed set temperature [For Auto mode]
SW3SW2SW1
1110
12
13
14
{
{
{
{
SW2-6
OFF
ON
table 7 SW2-6 : setting TH5
Details
Connect TH5
Not connect TH5 (Initial setting)
TH5
(
(
(
3-4. Wiring diagram
(1) PAC-IF011B-E(I/F)
18
6
5
2
1
1
8
1
2
1
8
1
8
4
3
TH1
OFF/ONOFF/ON
OFF/ON
OFF/ON
TB61
*6TH2
6
5
214
3+
TB62
4-20mA/1-5V/0-10V
WiredRemoteController
6
5
2
1
4
3
8
7
10
9
11
13
12
14
6
5
2
1
4
3
8
7
10 
9
1113
12 14
TB142 TB141
(ExternalOutput)
(ExternalInput)
LN
S1 S2 S3
LN
S1 S2 S3
TB6
DC311〜
339V
FUSE
SW6
LED1
RECTIFICATION
LED2
LED3
LED4
LED5
CNS2
(RED)
FLOWTEMP.CONTROLLER(FTC)
TOOUTDOORUNIT
U
U
DSA
21
SYMBOL
FLOWTEMP.CONTROLLER(FTC)
TB6
TB141
TB142
TB62
TB61
LED1
LED2
LED3
LED4,5
FUSE
SW1
SW2
SW3
SW6
ZNR01,02
DSA
X1〜X7
TH1
TH2
NAME
TERMINALBLOCK(FTC/OUTDOORUNITCONNECTINGLINE)
TERMINALBLOCK(ExternalOutput)
TERMINALBLOCK(ExternalInputContactsignal)
TERMINALBLOCK(ExternalInputAnalogsignal)
TERMINALBLOCK(Thermistor)
POWERSUPPLY(FTC)
POWERSUPPLY(WIREDREMOTECONTROLLER)
TRANSMISSION(FTC-OUTDOORUNIT)
NOTINUSE
FUSE(T3.15AL250V)
SWITCH*SeeTable3,4and6.
SWITCH
SWITCH*SeeTable5.
SWITCH(4-20mA/1-5V/0-10Vswitch)*SeeTable3.
VARISTOR
SURGEABSORBER
RELAY
ACTUALFLOWWATERTEMP.THERMISTOR(Waterpiping)
(0℃/15kΩ,25℃/5.2kΩDETECT)
PIPETEMP.THERMISTOR/LIQUID(Refrigerantpiping)
(0℃/15kΩ,25℃/5.2kΩDETECT)
TB6
TOOUTDOORUNIT
POWERSUPPLY
〜/N
21354678
TB141
11 10
9
12 13 14
ZNR01
ZNR02
X1X2X3X4X5X X76
OFF
Normal
ForcedComp.OFF
OFF
OFF
OFF
OFF
OFF
(IN1)
(IN2)
(IN3)
(IN4)
(COM-IN5)
(COM-IN6)
(COM-IN7)
(COM-IN8)
Remark
Notinuse
Notinuse
SW3-6=OFF
SW3-6=ON
ON
ForcedComp.OFF
Normal
Cooling
Heating
HeatingECO
HotWater
Anti-Freeze
TB142
1-2
3-4
5-6
7-8
10-11
10-12
10-13
10-14
X1X2X3X4X5X6X7
(OUT1)
(OUT2)
(OUT3)
(OUT4)
(OUT5)
(OUT6)
(OUT7)
OFF
OFF
Normal
OFF
OFF
OFF
OFF
ONONErrorONONONON
Item
OperationOutput
ErrorOutput
Comp.Output
DefrostOutput
Mode(Cooling)Output
Mode(Heating/HeatingECO/
HotWater/Anti-Freeze)Output
TB141
1-2
3-4
5-6
7-8
9-10
11-12
13-14
RefertoTable2.
Table1Externalinput(Contactsignal)
Table2Externaloutput
*1(Fig.1)
Referto
Table1.
SW1-6
OFF
OFF
OFF
OFFONONONON
SW1-7
OFFONOFFONOFFONOFF
ON
SW1-8
OFF
OFFONON
OFF
OFFONON
Heating/HeatingECO/HotWater
Upper55℃/lower20℃
Upper60℃/lower20℃*7
Upper50℃/lower20℃

Anti-Freeze
Upper45℃/lower5℃
Upper45℃/lower5℃
Upper45℃/lower5℃

Cooling
Upper25℃/lower5℃
Upper25℃/lower5℃
Upper25℃/lower5℃

Temperaturetable
SW2-1〜8,SW3-1〜3
Table*8Table*8
SW3-6
OFF
ON
TB142No.5-6input
OFF(open)
ON(short)
OFF(open)
ON(short)
Table3SW1,SW6:Inputselection
Table5SW3-6LogicofForcedcomp.OFFexternalsignal(TB1425-6)
*7.DontusethissettingwhenusingtheSPLITtypeoutdoorunit.
*8.Refertoinstallationmanual.
Item
Normal
ForcedComp.OFF
ForcedComp.OFF
Normal
SW1-3
OFF
ON
Operationmode
Heating/HeatingECO/Hotwater/Anti-freeze/Cooling
Heating/HeatingECO/Hotwater/Anti-freeze
Table4SW1-3ProhibitionofCoolingmode
*3.0〜2mA:STOP
*4.0〜0.5V:STOP
*5.Thesignalofexternalinputispriortothesignalofwiredremotecontroller.
*6.SPLITtype:thestandardoutdoorunitwithoutaplateHEX(refrigerant-waterHEX)inside.
 PACKAGEDtype:theAirtowateroutdoorunitwithaplateHEX(refrigerant-waterHEX)inside.
(ItisnotnecessarytoconnecttoTH2.)
1.SymboIsusedinwiringdiagramare, :Connector, :Terminalblock.
2.FTCandoutdoorunitconnectingwireshavepoIarities,makesuretomatchterminalnumbers(S1,
S2,S3)forcorrectwirings.
3.Sincetheoutdoorunitsideelectricwiringmaychange,besuretochecktheoutdoorunitelectric
wiringdiagramforservicing.
4.ThisdiagramshowsthewiringofFTCandoutdoorunitconnectingwires(specificationof230V),
adoptingsuperimposedsystemofpowerandsignal.
*1:WhenworktosupplypowerseparatelytoFTCandoutdoorunitwasapplied,refertoFig1.
*2:Removetheshort-circuitedconnectorCNS2whenworktosupplypowerseparatelytoFTC
andoutdoorunitwasapplied.
*2Removethe
short-circuited
connectorCNS2.
Table6SW1-6,7,8 Settemperaturerange
 SW1-6=OFF Settemperaturerangewithwiredremotecontroller
 SW1-6=ON SettemperaturetablewithDIPswitchofFTC
BH79L347H01
t。t
SW3SW2SW1
{
{
{
TB142
FTC
FTC
11
10
12
13
14
Atsite
Atsite
HeatingECO
→
Anti-Freeze
→
HotWater
→
Heating
→
65789
213
4
ForcedComp.OFF→
Cooling→
ON/OFFInput
Externalinput
(non-voltagecontact)
Externalinput
(non-voltagecontact)
Externalinputor
4-20mA*3
Externalinputor
1-5V*4
Externalinput
Externalinputand
Wiredremotecontroller
Externalinputand
Wiredremotecontroller
Wiredremotecontroller
ChangemodeInput
Externalinput
(non-voltagecontact)
Externalinput
(non-voltagecontact)
Externalinput
(non-voltagecontact)
Externalinput
(non-voltagecontact)
Externalinput
(non-voltagecontact)
Externalinputand
Wiredremotecontroller
Externalinputand
Wiredremotecontroller
Wiredremotecontroller
ChangeTEMP. Input
DIPswitchonPCB
SW2-1〜8,SW3-1〜3
Wiredremotecontroller
4-20mA
1-5V
0-10V
DIPswitchonPCB
SW2-1〜8,SW3-1〜3
Wiredremotecontroller
Wiredremotecontroller
Outdoorunit*6
SPLITtype
PACKAGEDtype
SPLITtype
PACKAGEDtype
SPLITtype
PACKAGEDtype
SPLITtype
PACKAGEDtype
SPLITtype
PACKAGEDtype
SPLITtype
PACKAGEDtype
SPLITtype
PACKAGEDtype
SPLITtype
PACKAGEDtype
SW1-1ONONONON
OFF
OFF
OFF
OFFONON
OFF
OFF
OFF
OFF
OFF
OFF
SW1-2
OFF
OFF
OFF
OFFONONONONONON
OFF
OFF
OFF
OFF
OFF
OFF
SW1-5
OFFONOFFONOFFONOFFONOFFONOFFONOFFONOFF
ON
SW1-6ONON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFFONON
OFF
OFF
OFF
OFF
SW6-1
OFF
OFF
OFF
OFFONON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
SW6-2
OFF
OFF
OFF
OFFONONONON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Temperaturerangewithwiredremotecontroller
*5
*5
(
(
(2) PAC-IF021B-E(FTC)
19
3-5. PCB diagram(Test point )
(1) PAC-IF011B-E, PAC-IF010-E
TB61 1-2
Thermistor (TH1)
TB61 3-4
Thermistor (TH2)
CN21
Thermistor (TH2)
TB61 5-6
Thermistor (TH5)
CN29
Thermistor (TH5)
CN2P
Adjustable resistor
TB62 1-2
Adjustable resistor
CN2A
4-20mA/1-5V/0-10V
TB62 3-4
4-20mA/1-5V/0-10V
CN22
Wired remote controller
TB62 5-6
Wired remote controller
CN20
Thermistor (TH1)
LED2~5 LED1
Power supply
CN82
External input Remote switch
TB142
External input Remote switch
CN53
External input Remote switch
PAC-IF011B-E PAC-IF010-E
TB6 TB141 TB142 TB61 TB62 CNX1~CNX6 — CN20 CN21 CN29 CN2P CN2A CN22
: mounting
Ο
: unmounting
CNX2
Error Output
CNX1
Operation Output
TB141
External output
CNX4
Defrost Output
CNX3
Comp.Output
CNX5
Mode(Cool)Output
ΟΟ Ο
ΟΟ ΟΟ ΟΟ
Ο ΟΟ ΟΟ ΟΟ ΟΟ ΟΟ ΟΟ
CNX6
Mode(Heat)Output
TB6
Interface/outdoor connecting
FUSE
T3,15AL250V
20
(2) PAC-IF021B-E(FTC), PAC-IF020-E
CN20
Thermistor (TH1)
TB61 1-2
Thermistor (TH1)
TB61 3-4
Thermistor (TH2)
CN21
Thermistor (TH2)
TB62 3-4
4-20mA/1-5V/0-10V
CN2A
4-20mA/1-5V/0-10V
TB62 5-6
Wired remote controller
CN22
Wired remote controller
LED2,3
TB6
FTC/outdoor unit connecting
CN82
External input
TB142
External input
CN53
External input
PAC-IF021B-E PAC-IF020-E
TB6 TB141 TB142 TB61 TB62 CNX1~CNX6 — CN20 CN21 CN29 CN2P CN2A CN22
: mounting
Ο
: unmounting
CNX2
Error Output
CNX1
Operation Output
CNX4
Defrost Output
CNX3
Comp.Output
TB141
External output
CNX5
Mode(Cooling)Output
ΟΟ Ο
ΟΟ ΟΟ ΟΟ
Ο ΟΟ ΟΟ ΟΟ ΟΟ ΟΟ ΟΟ
CNX6
Mode(Heating/Heating ECO/Hot Water/Anti-Freeze)Output
FUSE
T3,15AL250V
21
3-6. Specifi cation of connectors
Please connect wiring with either of the terminal bed or the connector. Parts on the PCB are different depending on the model.
PCB ONLY Cased PAC-IF010-E PAC-IF020-E Parts on PCB Parts on PCB
TERMINAL BED CONNECTOR TERMINAL BED CONNECTOR TB6 TB6
CNX1 CNX2 CNX3 CNX4 CNX5 CNX6
TB142 CN82
CN53
TB61 CN20
CN21 CN29
TB62 CN2P
CN2A CN22
The following terminal bed and the connector is the same signals, meaning.
PAC-IF011B-E PAC-IF021B-E
TB141
TB142
TB61 CN20
CN21 CN29
TB62 CN2P
CN2A CN22
TB6
TERMINAL BED TB6-L
TB6-N — TB6-PE — TB6-S1 — TB6-S2 — TB6-S3
Specifi cation of connectors (Manufacture: J.S.T. Mfg. Co., Ltd.)
CONNECTOR NAME HOUSING CNX1 ~ 6 VHR-3N CN82 XAP-08V-1
CN53 XAP-05V-1 CN20,21,29,2P,2A,22 XAP-02V-1
Contact pin : According to the wiring size select the correct
contact pin by yourself.
CONNECTOR NAME PIN No.
TB141, TB142, TB61
TERMINAL BED TB141-1,2 CNX1 1,3pin
TB141-3,4 CNX2 1,3pin TB141-5,6 CNX3 1,3pin TB141-7,8 CNX4 1,3pin TB141-9,10 CNX5 1,3pin TB141-11,12 CNX6 1,3pin TB142-1 CN82 1pin TB142-2 CN82 2pin TB142-3 CN82 3pin TB142-4 CN82 4pin TB142-5 CN82 5pin TB142-6 CN82 6pin TB142-7 CN82 7pin TB142-8 CN82 8pin TB142-9 CN53 5pin TB142-10 CN53 5pin TB142-11 CN53 1pin TB142-12 CN53 2pin TB142-13 CN53 3pin TB142-14 CN53 4pin TB61-1,2 CN20 1,2pin TB61-3,4 CN21 1,2pin TB61-5,6 CN29 1,2pin TB62-1,2 CN2P 1,2pin TB62-3,4 CN2A 1,2pin TB62-5,6 CN22 1,2pin
CONNECTOR NAME PIN No.
22
Interface (I/F)4
CONTENTS
1. System outline ..................................................................................24
2. System structure ...............................................................................24
3. Power supply ....................................................................................28
4. Connecting thermistor.......................................................................30
5. Interface controller switch setting .....................................................31
6. Input specifi cations ...........................................................................32
7. Output specifi cations ........................................................................33
8. LED display detail .............................................................................34
9. Maintenance information ..................................................................35
10. Central control ..................................................................................52
11. Outlines and dimensions ..................................................................53
12. Troubleshooting ................................................................................ 54
Notes on system controller side in I/F connection system (1)Please do not transmit “STEP 0” during defrost operation.
Defrost operation might be interrupted, and frost remain. (Please demand the planned capacity step even when the system controller receives defrost signal from the heat pump (outdoor unit)).
(2)Please do not transmit “STEP 0” when the outdoor unit(H/P) is abnormal.
Abnormal detection data is reset, and an Abnormal point cannot be confi rmed.
2323
1. System outline
With PAC-IF011B-E, local units can be connected with the outdoor units manufactured by MITSUBISHI ELECTRIC. The commands, such as Remote switch, Varistor, 4-20mA/1-5V/0-10V and etc., allow the inverter outdoor unit to operate, to stop and to switch capacity. By outputting the operation state, the interface can be connected with the local unit.Also, the interface can be connected with wired remote controller for maintenance so that the maintenance information is obtained. Only the outdoor units with self-controlled S/W are connectable.
2. System structure
System structure(1)
Outdoor unit capacity switch
Remote switch
Capacity switch of outdoor unit according to the remote switch
When auto stop being set, the difference between room temperature and set temperature of interface, and the pipe temperature switch the capacity of outdoor unit automatically.
Wired remote controller (Auto step mode only)
The difference between room temperature and set temperature of wired remote controller, and the pipe temperature switch the capacity of outdoor unit automatically.
As with the remote controller for air conditioner, the interface performs ON/OFF operation, and changes operation mode (cooling, heating ,fan) and set temperature.
Adjustable resistor(0-10k)
Capacity switch of outdoor unit according to the adjustable resistor
System diagram Power supply specifications
Intake temp. Liquid pipe temp.
Local unit
Local controller
Intake temp. Liquid pipe temp.
Local unit
Local controller
Intake temp. Liquid pipe temp.
Local unit
Wired remote controller
Intake temp. Liquid pipe temp.
Local unit
Wired remote controller
Intake temp. Liquid pipe temp.
Local unit
Local controller Adjustable resistor
Interface controller
Remote switch
Power line
Interface controller
Remote switch
Interface controller
PAR-21MAA
Power line
Interface controller
PAR-21MAA
Interface controller
A transmission line/Power line
Power line
Outdoor unit
A transmission line/Power line
Power line
Outdoor unit
A transmission line/Power line
Power line
Outdoor unit
A transmission line/Power line
Power line
Outdoor unit
A transmission line/Power line
Power line
Outdoor unit
Power supplied from outdoor unit Power supply for interface
controller is supplied from the outdoor unit. Refer to 3.1.
Separate interface/outdoor unit power supplies
Power supply for interface controller and power supply for outdoor unit are supplied from the different source.(Common power source for local unit and interface controller) Refer to 3.2.
Power supplied from outdoor unit
Power supply for interface controller is supplied from the outdoor unit. Refer to 3.1.
Separate interface/outdoor unit power supplies
Power supply for interface controller and power supply for outdoor unit are supplied from the different source.(Common power source for local unit and interface controller) Refer to 3.2.
Power supplied from outdoor unit
Power supply for interface controller is supplied from the outdoor unit. Refer to 3.1.
Intake temp. Liquid pipe temp.
Local unit
Local controller
Power line
Interface controller
Adjustable resistor
A transmission line/Power line
Power line
Outdoor unit
24
Separate interface/outdoor unit power supplies
Power supply for interface controller and power supply for outdoor unit are supplied from the different source.(Common power source for local unit and interface controller) Refer to 3.2.
Note:
• REMOTE SWITCH Type A (4bit - 8 setting) / Type B (1bit -1 setting)
TB142 10-11 (COM-IN5)
OFF ON OFF ON OFF ON OFF ON OFF
TB142 10-12 (COM-IN6)
OFF OFF ON ON OFF OFF ON ON OFF
TB142 10-13 (COM-IN7)
OFF OFF OFF OFF ON ON ON ON OFF
TB142 10-14 (COM-IN8)
OFF OFF OFF OFF OFF OFF OFF OFF ON
Step for capacity setting *
TypeA TypeB
OFF 0%
[OFF] [ON]
Step1 10% Step2 20% Step3 30% Step4 50% Step5 70% Step6 80% Step7 100% Auto step
[OFF] [ON]
OFF 0% Step1 10% Step4 50%
Step7 100%
Auto step
Remark
OFF
Fixed capacity
(Hz fixed)
mode
Auto step mode
Type A Type B
I/F
At site
4 bit 8 switch
OFF~AUTO
step
{
10 11 12 13 14
TB142
At site
Step1 Step4 Step7
AUTO
step
I/F
10 11 12 13 14
TB142
* The actual capacity will be slightly different from the numerial data in this table depending on conditions such as the ambient
temperature.
Attachment of sensor
Refer to 4.
Pipe-thermistor/ 2-phase might be neccessary depending on the type of the outdoor unit.
Refer to 4.
Pipe-thermistor/ 2-phase might be neccessary depending on the type of the outdoor unit.
Interface controller
switch setting
2 patterns can be set. (Refer to NOTE 1.)
Type A SW1-1:OFF SW1-2:OFF SW1-3:OFF SW6-1:OFF SW6-2:OFF
Type B SW1-1:ON SW1-2:OFF SW1-3:OFF SW6-1:OFF SW6-2:OFF Other switches are to be set according to the site. Refer to 5 for details.
Interface controller specifications
Input and wiring Output and wiring
Type A
Refer to 7.
OFF/Step1/Step2/
···Step7/Auto step Type B
OFF/Step1/Step4/ Step7/Auto step
Refer to 6 for details.
Refer to 7.
Other functions/setting
Maintenance
Refer to 8, 9.
Refer to 8, 9.
Connection with
BMS/MELANS
Not available
Not available
Refer to 4.
Pipe-thermistor/ 2-phase might be neccessary depending on the type of the outdoor unit.
Refer to 4.
Pipe-thermistor/ 2-phase might be neccessary depending on the type of the outdoor unit.
Refer to 4.
Pipe-thermistor/ 2-phase might be neccessary depending on the type of the outdoor unit.
Refer to 4.
Pipe-thermistor/ 2-phase might be neccessary depending on the type of the outdoor unit.
SW1-1:OFF SW1-2:ON SW1-3:ON SW6-1:OFF SW6-2:OFF
Other switches are to be set according to the site. Refer to 5 for details.
SW1-1:OFF SW1-2:OFF SW1-3:ON SW6-1:OFF SW6-2:OFF
Other switches are to be set according to the site. Refer to 5 for details.
TB62 Connect the wired remote controller wire to No.5-6
Wiring Wire NO.×size(mm 2×0.3(Non-polar) Max. 500m
Circuit rating DC12V The figure is NOT always against the ground.
Only the operation with remote controller is valid. (External signal is invalid)
Refer to 6.
Refer to 6.
2
)
Refer to 7.
Refer to 7.
Refer to 7.
Refer to 7.
Refer to 8, 9.
Refer to 8, 9.
Refer to 8, 9.
Refer to 8, 9.
Available Refer to 10.
Connect adaptor to outdoor unit. M-NET converter PAC-SF80MA-E A-Control sub Interface PAC-SK82SI-E
Available Refer to 10.
Connect adaptor to outdoor unit. M-NET converter PAC-SF80MA-E A-Control sub Interface PAC-SK82SI-E
Not available
Not available
25
System structure(2)
Outdoor unit capacity switch
4-20mA
Capacity switch of outdoor unit according to the signal of 4-20mA
1-5V Capacity switch of outdoor unit according to the signal of 1-5V
Intake temp. Liquid pipe temp.
Local unit
Local controller
Intake temp. Liquid pipe temp.
Local unit
Local controller
Intake temp. Liquid pipe temp.
Local unit
Local controller
System diagram Power supply specifications
Power supplied from outdoor unit
A transmission line/Power line
Power supply for interface controller is supplied from the outdoor unit. Refer to 3.1.
Interface controller
4-20mA
Power line
Outdoor unit
Separate interface/outdoor unit
Power line
A transmission line/Power line
power supplies Power supply for interface
controller and power supply for
Interface controller
4-20mA
Power line
Outdoor unit
outdoor unit are supplied from the different source. (Common power source for local unit and interface controller) Refer to 3.2.
Power supplied from outdoor unit
A transmission line/Power line
Power supply for interface controller is supplied from the outdoor unit.
Interface controller
1-5V
Power line
Outdoor unit
Refer to 3.1.
0-10V
Capacity switch of outdoor unit according to the signal of 0-10V
Intake temp. Liquid pipe temp.
Local unit
Local controller
Intake temp. Liquid pipe temp.
Local unit
Local controller
Intake temp. Liquid pipe temp.
Local unit
Local controller
Power line
Interface controller
1-5V
Interface controller
0-10V
Power line
Interface controller
0-10V
A transmission line/Power line
Power line
Outdoor unit
A transmission line/Power line
Power line
Outdoor unit
A transmission line/Power line
Power line
Outdoor unit
Separate interface/outdoor unit power supplies
Power supply for interface controller and power supply for outdoor unit are supplied from the different source. (Common power source for local unit and interface controller) Refer to 3.2.
Power supplied from outdoor unit Power supply for interface
controller is supplied from the outdoor unit. Refer to 3.1.
Separate interface/outdoor unit power supplies
Power supply for interface controller and power supply for outdoor unit are supplied from the different source. (Common power source for local unit and interface controller) Refer to 3.2.
26
Attachment of sensor
Refer to 4.
Pipe-thermistor/ 2-phase might be neccessary depending on the type of the outdoor unit.
Refer to 4.
Pipe-thermistor/ 2-phase might be neccessary depending on the type of the outdoor unit.
Interface controller
switch setting
SW1-1:ON SW1-2:ON SW1-3:OFF SW6-1:ON SW6-2:ON
Other switches are to be set according to the site. Refer to 5 for details.
Interface controller specifications
Input and wiring Output and wiring
Refer to 6.
Refer to 6.
Refer to 7.
Refer to 7.
Other functions/setting
Maintenance
Refer to 8, 9.
Refer to 8, 9.
Connection with
BMS/MELANS
Not available
Not available
Refer to 4.
Pipe-thermistor/ 2-phase might be neccessary depending on the type of the outdoor unit.
Refer to 4.
Pipe-thermistor/ 2-phase might be neccessary depending on the type of the outdoor unit.
Refer to 4.
Pipe-thermistor/ 2-phase might be neccessary depending on the type of the outdoor unit.
SW1-1:ON SW1-2:ON SW1-3:OFF SW6-1:OFF SW6-2:ON
Other switches are to be set according to the site. Refer to 5 for details.
SW1-1:OFF SW1-2:OFF SW1-3:ON SW6-1:OFF SW6-2:OFF
Other switches are to be set according to the site. Refer to 5 for details.
Refer to 6.
Refer to 6.
Refer to 6.
Refer to 7.
Refer to 7.
Refer to 7.
Refer to 8, 9.
Refer to 8, 9.
Refer to 8, 9.
Not available
Not available
Not available
Refer to 4.
Pipe-thermistor/ 2-phase might be neccessary depending on the type of the outdoor unit.
Refer to 6.
27
Refer to 7.
Refer to 8, 9.
Not available
3. Power Supply
Interface controller is applicable to both methods of interface unit power supplied from outdoor unit, and of separate interface unit/outdoor unit power supplies. Choose one according to the site.
(Photo. 3-1)
Inlet for control cable
A
Inlet for power
B
Clamp
C
Interface / Outdoor unit connecting terminals
D
Earth terminal
E
D
A
3.1. Interface unit power supplied from outdoor unit (Photo 3-2)
The following connection patterns are available. The outdoor unit power supply patterns vary on models.
D
L
ABC
N
S1 S2 S3
E
A Outdoor unit power supply B Earth leakage breaker C Wiring circuit breaker or isolating switch D Outdoor unit E Interface unit/outdoor unit connecting cables F Interface unit
F
S1 S2 S3
C
Photo.3-1
C
E
B
Photo.3-2
Interface unit model PAC-IF011B-E
)
2
Interface unit-Outdoor unit *1 3× 1.5 (polar)
size
Interface unit-Outdoor unit earth *1 1 × Min.1.5
Wiring
(mm
Wire No.×
Interface unit-Outdoor unit S1-S2 *2 AC 230 V
rating
Circuit
*1. Max. 80 m *2. The fi gures are NOT always against the ground.
S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are not electrically insulated by the transformer or other device.
Interface unit-Outdoor unit S2-S3 *2 DC24 V
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Power supply cables and interface unit/outdoor unit connecting cables shall not be lighter than polychloro­prene sheathed fl exible cable. (Design 60245 IEC 57)
3. Install an earth longer than other cables.
28
3.2. Separate interface unit/outdoor unit power supplies
The following connection patterns are available. The outdoor unit power supply patterns vary on models.
D
L
N
A
CB
GEB
S1 S2 S3
C
F
L N
S1 S2 S3
A Outdoor unit power supply B Earth leakage breaker C Wiring circuit breaker or isolating switch D Outdoor unit E Interface unit/outdoor unit connecting cables F Interface unit G Interface unit power supply
If the interface and outdoor units have separate power supplies, refer to the table below.
Separate power supply specifi cations
Interface unit controller con­nector (CNS2) connection change
Disconnected
Photo. 3-3
CNS2
Outdoor unit DIP switch set­tings (when using separate in­terface unit/outdoor unit power supplies only)
ON OFF
Set the SW8-3 to ON.
12
3
(SW8)
Interface unit model PAC-IF011B-E Interface unit power supply ~/N (Single Phase), 50 Hz, 230 V Interface unit input capacity Main switch (Breaker)
)
Interface unit power supply & earth 3 × Min. 1.5
2
Interface unit-Outdoor unit *2 2 × Min. 0.3
size
Wire
No.×
Wiring
(mm
Interface unit-Outdoor unit earth
*1 16 A
Interface unit L-N *3 AC230V Interface unit-Outdoor unit S1-S2 *3
rating
Circuit
*1. A breaker with at least 3.0mm contact separation in each pole shall be provided. Use earth leakage breaker (NV). *2. Max. 120 m *3. The fi gures are NOT always against the ground.
Interface unit-Outdoor unit S2-S3 *3 DC24V
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Power supply cables and interface unit/outdoor unit connecting cables shall not be lighter than polychloro­prene sheathed fl exible cable. (Design 60245 IEC 57)
3. Install an earth longer than other cables.
29
Loading...
+ 67 hidden pages