MITSUBISHI MGS SERIES
DIESEL GENERATOR SET
60Hz/1800 rpm/480V
POWER RATING (0.8 P.F.) MODEL CODE
STAND-BY 2012 kW 6S-7PF
PRIME 1820 kW 6P-7PF
MGS2500B with typical options
Voltage Variation
■ Standard Voltage 3Phase 4 Wires
480V
■ Volt ages A vailable 3Phase 4 Wires
480, 460, 450, 440 and 416V
Note: Outputs for optional voltages may differ from standard output mentioned above.
CONDITIONS & DEFINITIONS
Stand-by: Code: S
Applicable for supplying emergency power at varying load in the event of the normal utility power interruption.
Fuel stop power in accordance with ISO15550, IS O3046/1, JISB8002-1, DIN6271 and BS5514.
Overload: not allowed
Prime: Code: P
Applicable for supply ing em erg ency p ower at varying load in t he ev ent of normal utility power inter r upt ion. + 10% overload
in accordance with ISO3046/1. Overload power in accordance with ISO15550, ISO3046/1, JIS8002-1, DIN6271 and
BS5514.
Conditions:
Engine ratings are based on SAE J1349 standard conditions and also apply at ISO3046/1, DIN6271 & BS5514 standard
conditions.
Fuel rates: based on A ST M D975, BS2869 and on fuel oil of 35° API (16°C or 60° F) grav ity hav ing a LHV of 4 2,78 0 kJ /kg
(18,390 Btu/lb.) when used at 29°C (85° F) and weighing 838.9 g/liter (7.001lbs./U.S. gal.).
Note: * For conditions of pri me power (P.R.P.) and additional ra ting requirements, please con sult your nearest Mitsubish i
MGS dealer.
DIMENSION (Reference Data)
H : Height mm 3460
MITSUBISHI MGS SERIES
Lubricating oil capacity L 230
Coolant capacity without radiator
Coolant pump external resistance
Cooling fan air flow restriction
Allowable exhaust back pressure
Exhaust flange size (internal diameter)
Brake mean effective pressure
(excluding: intake, exhaust & fan)
Fuel consumption load 100%*
Fuel consumption load 75%*
Combustion air inlet flow rate
Heat rejection to coolant
Heat rejection to exhaust
Heat rejection to atmosphere from engine
Heat rejection to atmosphere from generator
STAND-BY
2012 kW
PRIME
1820 kW
MGS SERIES DIESEL ENGINE: MITSUBISHI S16R-PTAA2
DIESEL GENERATOR SET
MGS2500B
V-16, 4 stroke-cycle water-cooled, turbocharged and air-to-air cooling system
ENGINE SPECIFICATIONS & TECHNICAL DATA
Ambient air temperature
℃
ENGINE OPERATING DATA
Exhaust gas temperature
* WITH FAN basis.
Deration for engine
Note: Please consult with your nearest Mitsubishi MGS dealer
℃
ENGINE STANDARD EQUIPMENT
Aftercooler
Turbocharger filter
Structure ste el bas e
Crankcase breather
Charging alternator
Lubricating oil cooler
Fuel filters, full flow paper element
Fuel transfer pump, gear driven, plunger type
Electronic type governor
Jacket water heater
Jacket water pump, gear driven
Lubricating oil filter, full flow paper element
Lubricating oil pump, gear driven
Exhaust dry manifold
Radiator, blower fan, fan drive
Manual shutoff
24V DC electric starting mot or
40