Mitsubishi Electric MELSERVO-J4, MELSERVO MR-J4-03A6-RJ Instruction Manual

Page 1
General-Purpose AC Servo
General-Purpose Interface AC Servo
MODEL
SERVO AMPLIFIER INSTRUCTION MANUAL (POSITIONING MODE)
C
Page 2
www.kavrammuhendislik.com.tr

Safety Instructions

Please read the instructions carefully before using the equipment.
To use the equipment correctly, do not attempt to install, operate, maintain, or inspect the equipment until you have read through this Instruction Manual, Installation guide, and appended documents carefully. Do not use the equipment until you have a full knowledge of the equipment, safety information and instructions. In this Instruction Manual, the safety instruction levels are classified into "WARNING" and "CAUTION".
WARNING
CAUTION
Note that the CAUTION level may lead to a serious consequence according to conditions. Please follow the instructions of both levels because they are important to personnel safety. What must not be done and what must be done are indicated by the following diagrammatic symbols.
Indicates that incorrect handling may cause hazardous conditions,
resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous conditions,
resulting in medium or slight injury to personnel or may cause physical damage.
Indicates what must not be done. For example, "No Fire" is indicated by .
Indicates what must be done. For example, grounding is indicated by .
In this Instruction Manual, instructions at a lower level than the above, instructions for other functions, and so on are classified into "POINT". After reading this Instruction Manual, keep it accessible to the operator.
A - 1
Page 3
www.kavrammuhendislik.com.tr
1. To prevent electric shock, note the following
WARNING
Before wiring or inspection, turn off the power and wait for 15 minutes or more until the charge lamp turns off. Then, confirm that the voltage between P+ and N- is safe with a voltage tester and others. Otherwise, an electric shock may occur. In addition, when confirming whether the charge lamp is off or not, always confirm it from the front of the servo amplifier. Ground the servo amplifier and servo motor securely. Any person who is involved in wiring and inspection should be fully competent to do the work. Do not attempt to wire the servo amplifier and servo motor until they have been installed. Otherwise, it may cause an electric shock. Do not operate switches with wet hands. Otherwise, it may cause an electric shock. The cables should not be damaged, stressed, loaded, or pinched. Otherwise, it may cause an electric shock. During power-on or operation, do not open the front cover of the servo amplifier. Otherwise, it may cause an electric shock. Do not operate the servo amplifier with the front cover removed. High-voltage terminals and charging area are exposed and you may get an electric shock. Except for wiring and periodic inspection, do not remove the front cover of the servo amplifier even if the power is off. The servo amplifier is charged and you may get an electric shock. To prevent an electric shock, always connect the protective earth (PE) terminal (marked ) of the servo amplifier to the protective earth (PE) of the cabinet. To avoid an electric shock, insulate the connections of the power supply terminals.
2. To prevent fire, note the following
CAUTION
Install the servo amplifier, servo motor, and regenerative resistor on incombustible material. Installing them directly or close to combustibles will lead to a fire or smoke generation. Always connect a magnetic contactor between the power supply and the main circuit power supply (L1/L2/L3) of the servo amplifier, in order to configure a circuit that shuts down the power supply on the side of the servo amplifier’s power supply. If a magnetic contactor is not connected, continuous flow of a large current may cause smoke or a fire when the servo amplifier malfunctions. In order to configure a circuit that shuts down the power supply on the side of the servo amplifier's power supply, always connect one molded-case circuit breaker or fuse per one servo amplifier between the power supply and the main circuit power supply (L1/L2/L3) of a servo amplifier. If a molded-case circuit breaker or fuse is not connected, continuous flow of a large current may cause smoke or a fire when the servo amplifier malfunctions. When using the regenerative resistor, switch power off with the alarm signal. Otherwise, a regenerative transistor malfunction or the like may overheat the regenerative resistor, causing smoke or a fire. Provide adequate protection to prevent screws and other conductive matter, oil and other combustible matter from entering the servo amplifier and servo motor.
A - 2
Page 4
www.kavrammuhendislik.com.tr
3. To prevent injury, note the following
CAUTION
Only the voltage specified in the Instruction Manual should be applied to each terminal. Otherwise, a burst, damage, etc. may occur. Connect cables to the correct terminals. Otherwise, a burst, damage, etc. may occur. Ensure that polarity (+/-) is correct. Otherwise, a burst, damage, etc. may occur. The servo amplifier heat sink, regenerative resistor, servo motor, etc., may be hot while the power is on and for some time after power-off. Take safety measures such as providing covers to avoid accidentally touching them by hands and parts such as cables.
4. Additional instructions
The following instructions should also be fully noted. Incorrect handling may cause a malfunction, injury, electric shock, fire, etc.
(1) Transportation and installation
CAUTION
Transport the products correctly according to their mass. Stacking in excess of the specified number of product packages is not allowed. Do not hold the front cover when transporting the servo amplifier. Otherwise, it may drop. Install the servo amplifier and the servo motor in a load-bearing place in accordance with the Instruction Manual. Do not get on or put heavy load on the equipment. The equipment must be installed in the specified direction. Leave specified clearances between the servo amplifier and the cabinet walls or other equipment. Do not install or operate the servo amplifier and servo motor which have been damaged or have any parts missing. Do not block the intake and exhaust areas of the servo amplifier. Otherwise, it may cause a malfunction. Do not drop or strike the servo amplifier and servo motor. Isolate them from all impact loads. When you keep or use the equipment, please fulfill the following environment.
Item Environment
Ambient
temperature
Storage -20 ˚C to 65 ˚C (non-freezing)
Ambient humidity
Storage
Ambience Indoors (no direct sunlight), free from corrosive gas, flammable gas, oil mist, dust, and dirt
Altitude 2000 m or less above sea level (Contact your local sales office for the altitude for options.)
Vibration resistance 5.9 m/s2, at 10 Hz to 55 Hz (directions of X, Y and Z axes)
When the product has been stored for an extended period of time, contact your local sales office. When handling the servo amplifier, be careful about the edged parts such as corners of the servo amplifier. The servo amplifier must be installed in a metal cabinet.
Operation 0 ˚C to 55 ˚C (non-freezing)
Operation
5 %RH to 90 %RH (non-condensing)
A - 3
Page 5
r
www.kavrammuhendislik.com.tr
CAUTION
When fumigants that contain halogen materials such as fluorine, chlorine, bromine, and iodine are used for disinfecting and protecting wooden packaging from insects, they cause malfunction when entering our products. Please take necessary precautions to ensure that remaining materials from fumigant do not enter our products, or treat packaging with methods other than fumigation (heat method). Additionally, disinfect and protect wood from insects before packing products.
(2) Wiring
CAUTION
Wire the equipment correctly and securely. Otherwise, the servo motor may operate unexpectedly. Do not install a power capacitor, surge killer, or radio noise filter (optional FR-BIF(-H)) on the servo amplifier output side. To avoid a malfunction, connect the wires to the correct phase terminals (U/V/W) of the servo amplifier and servo motor. Connect the servo amplifier power output (U/V/W) to the servo motor power input (U/V/W) directly. Do not let a magnetic contactor, etc. intervene. Otherwise, it may cause a malfunction.
Servo amplifier
U
V
W
Servo motor
U
V
W
Servo motorServo amplifier
U
M
V
W
U
V
W
M
The connection diagrams in this instruction manual are shown for sink interfaces, unless stated otherwise. The surge absorbing diode installed to the DC relay for control output should be fitted in the specified direction. Otherwise, the emergency stop and other protective circuits may not operate.
Servo amplifie
or MR-D01
DOCOM
(DOCOMD)
Control output signal
For sink output interface
24 V DC
RA
Servo amplifier
or MR-D01
DOCOM
(DOCOMD)
Control output signal
For source output interface
24 V DC
RA
When the cable is not tightened enough to the terminal block, the cable or terminal block may generate heat because of the poor contact. Be sure to tighten the cable with specified torque. Connecting a servo motor of the wrong axis to U, V, W, or CN2 of the servo amplifier may cause a malfunction. Configure a circuit to turn off EM2 or EM1 when the main circuit power is turned off to prevent an unexpected restart of the servo amplifier.
A - 4
Page 6
www.kavrammuhendislik.com.tr
(3) Test run and adjustment
CAUTION
Before operation, check the parameter settings. Improper settings may cause some machines to operate unexpectedly. Never make a drastic adjustment or change to the parameter values as doing so will make the operation unstable. Do not get close to moving parts during the servo-on status.
(4) Usage
CAUTION
When it is assumed that a hazardous condition may occur due to a power failure or product malfunction, use a servo motor with an external brake to prevent the condition. Do not disassemble, repair, or modify the equipment. Before resetting an alarm, make sure that the run signal of the servo amplifier is off in order to prevent a sudden restart. Otherwise, it may cause an accident. Use a noise filter, etc. to minimize the influence of electromagnetic interference. Electromagnetic interference may be given to the electronic equipment used near the servo amplifier. Burning or breaking a servo amplifier may cause a toxic gas. Do not burn or break it. Use the servo amplifier with the specified servo motor. The electromagnetic brake on the servo motor is designed to hold the motor shaft and should not be used for ordinary braking. For such reasons as service life and mechanical structure (e.g. where a ball screw and the servo motor are coupled via a timing belt), the electromagnetic brake may not hold the motor shaft. To ensure safety, install a stopper on the machine side.
(5) Corrective actions
CAUTION
Ensure safety by confirming the power off, etc. before performing corrective actions. Otherwise, it may cause an accident. When it is assumed that a hazardous condition may occur due to a power failure or product malfunction, use a servo motor with an electromagnetic brake or external brake to prevent the condition. Configure an electromagnetic brake circuit which is interlocked with an external emergency stop switch.
Contacts must be opened when ALM (Malfunction) or MBR (Electromagnetic brake interlock) turns off.
Servo motor
B
Electromagnetic brake
When any alarm has occurred, eliminate its cause, ensure safety, and deactivate the alarm before restarting operation. Provide an adequate protection to prevent unexpected restart after an instantaneous power failure.
RA
Contacts must be opened with the emergency stop switch.
24 V DC
A - 5
Page 7
www.kavrammuhendislik.com.tr
(6) Maintenance, inspection and parts replacement
CAUTION
Make sure that the emergency stop circuit operates properly such that an operation can be stopped immediately and a power is shut off by the emergency stop switch. It is recommended that the servo amplifier be replaced every 10 years when it is used in general environment. When using the servo amplifier that has not been energized for an extended period of time, contact your local sales office.
(7) General instruction
To illustrate details, the equipment in the diagrams of this Instruction Manual may have been drawn without covers and safety guards. When the equipment is operated, the covers and safety guards must be installed as specified. Operation must be performed in accordance with this Instruction Manual.

DISPOSAL OF WASTE

Please dispose a servo amplifier, battery (primary battery) and other options according to your local laws and regulations.
EEP-ROM life
The number of write times to the EEP-ROM, which stores parameter settings, etc., is limited to 100,000. If the total number of the following operations exceeds 100,000, the servo amplifier may malfunction when the EEP-ROM reaches the end of its useful life.
Write to the EEP-ROM due to parameter setting changes Write to the EEP-ROM due to device changes Write to the EEP-ROM due to point table changes Write to the EEP-ROM due to program changes

STO function of the servo amplifier

When using the STO function of the servo amplifier, refer to chapter 13 of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual". For the MR-J3-D05 safety logic unit, refer to app. 5 of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual".
A - 6
Page 8
www.kavrammuhendislik.com.tr

Compliance with global standards

For the compliance with global standards, refer to app. 4 of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual".
«About the manual»
You must have this Instruction Manual and the following manuals to use this servo. Ensure to prepare them to use the servo safely.
Relevant manuals
Manual name Manual No.
MELSERVO MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual SH(NA)030107ENG
MELSERVO MR-J4-_A_-RJ Servo Amplifier Instruction Manual (Modbus-RTU Protocol) (Note
5)
MELSERVO MR-J4-DU_(-RJ)/MR-CR55K_ Instruction Manual (Note 6) SH(NA)030153ENG
MELSERVO-J4 Servo Amplifier Instruction Manual (Troubleshooting) SH(NA)030109ENG
MELSERVO Servo Motor Instruction Manual (Vol. 3) (Note 1) SH(NA)030113ENG
MELSERVO Linear Servo Motor Instruction Manual (Note 2) SH(NA)030110ENG
MELSERVO Direct Drive Motor Instruction Manual (Note 3) SH(NA)030112ENG
MELSERVO Linear Encoder Instruction Manual (Note 2, 4) SH(NA)030111ENG
EMC Installation Guidelines IB(NA)67310ENG
Parameter Unit MR-PRU03 Instruction Manual (MR-J4) SH(NA)030186ENG
Note 1. It is necessary for using a rotary servo motor.
2. It is necessary for using a linear servo motor.
3. It is necessary for using a direct drive motor.
4. It is necessary for using a fully closed loop system.
5. It is necessary for using the Modbus-RTU communication function.
6. It is necessary for using the MR-J4-DU_A_(-RJ) drive unit or MR-CR55K_ converter unit.
This Instruction Manual does not describe the following items. The followings are the same as MR-J4­_A_-RJ Servo amplifiers. For details of the items, refer to each chapter/section of the detailed explanation field. "MR-J4-_A_" means "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual".
Item Detailed explanation
Installation MR-J4-_A_ chapter 2
Normal gain adjustment MR-J4-_A_ chapter 6
Special adjustment functions MR-J4-_A_ chapter 7
Dimensions MR-J4-_A_ chapter 9
Characteristics MR-J4-_A_ chapter 10
ABSOLUTE POSITION DETECTION SYSTEM (only 12.1 Summary and 12.2 Battery)
USING STO FUNCTION MR-J4-_A_ chapter 13
USING A LINEAR SERVO MOTOR (Note) MR-J4-_A_ chapter 15
USING A DIRECT DRIVE MOTOR MR-J4-_A_ chapter 16
FULLY CLOSED LOOP SYSTEM (Note) MR-J4-_A_ chapter 17
MR-J4-03A6-RJ SERVO AMPLIFIER MR-J4-_A_ chapter 18
Note. For the home position return, refer to each chapter indicated in the detailed
explanation field and chapter 4 in this Instruction Manual.
«Wiring»
SH(NA)030175ENG
MR-J4-_A_ chapter 12
Wires mentioned in this Instruction Manual are selected based on the ambient temperature of 40 ˚C.
A - 7
Page 9
www.kavrammuhendislik.com.tr
«U.S. customary units»
U.S. customary units are not shown in this manual. Convert the values if necessary according to the following table.
Quantity SI (metric) unit U.S. customary unit
Mass 1 [kg] 2.2046 [lb]
Length 1 [mm] 0.03937 [inch]
Torque 1 [N•m] 141.6 [oz•inch]
Moment of inertia 1 [(× 10-4 kg•m2)] 5.4675 [oz•inch2]
Load (thrust load/axial load) 1 [N] 0.2248 [lbf]
Temperature N [°C] × 9/5 + 32 N [°F]
A - 8
Page 10

CONTENTS

www.kavrammuhendislik.com.tr
1. FUNCTIONS AND CONFIGURATION 1- 1 to 1-12
1.1 For proper use of the positioning mode ............................................................................................ 1- 1
1.2 Positioning mode specification list .................................................................................................... 1- 2
1.3 Function list ....................................................................................................................................... 1- 5
1.4 Configuration including peripheral equipment ................................................................................. 1-10
2. SIGNALS AND WIRING 2- 1 to 2-46
2.1 I/O signal connection example .......................................................................................................... 2- 3
2.1.1 MR-J4-_A_-RJ 100 W or more .................................................................................................. 2- 3
2.1.2 MR-J4-03A6-RJ ......................................................................................................................... 2- 9
2.2 Connectors and pin assignment ...................................................................................................... 2-15
2.3 Signal (device) explanations ............................................................................................................ 2-22
2.4 Analog override ................................................................................................................................ 2-38
2.5 Internal connection diagram ............................................................................................................ 2-40
2.6 Power-on sequence ......................................................................................................................... 2-45
2.6.1 MR-J4-_A_-RJ 100 W or more ................................................................................................. 2-45
2.6.2 MR-J4-03A6-RJ ........................................................................................................................ 2-46
3. DISPLAY AND OPERATION SECTIONS 3- 1 to 3-54
3.1 MR-J4-_A_-RJ 100 W or more ......................................................................................................... 3- 1
3.1.1 Display sequence ....................................................................................................................... 3- 1
3.1.2 Status display ............................................................................................................................. 3- 3
3.1.3 Diagnostic mode ....................................................................................................................... 3-12
3.1.4 Alarm mode ............................................................................................................................... 3-15
3.1.5 Point table setting ...................................................................................................................... 3-17
3.1.6 Parameter mode ....................................................................................................................... 3-21
3.1.7 External I/O signal display ......................................................................................................... 3-23
3.1.8 Output signal (DO) forced output .............................................................................................. 3-24
3.1.9 Single-Step feed ........................................................................................................................ 3-25
3.1.10 Teaching function .................................................................................................................... 3-27
3.2 MR-J4-03A6-RJ ............................................................................................................................... 3-28
3.2.1 Display flowchart ....................................................................................................................... 3-28
3.2.2 Status display mode .................................................................................................................. 3-29
3.2.3 Diagnostic mode ....................................................................................................................... 3-34
3.2.4 Alarm mode ............................................................................................................................... 3-38
3.2.5 Point table setting ...................................................................................................................... 3-40
3.2.6 Parameter mode ....................................................................................................................... 3-44
3.2.7 External I/O signal display ......................................................................................................... 3-49
3.2.8 Output signal (DO) forced output .............................................................................................. 3-50
3.2.9 Step feed ................................................................................................................................... 3-51
3.2.10 Teaching function .................................................................................................................... 3-53
4. HOW TO USE THE POINT TABLE 4- 1 to 4-80
4.1 Startup .............................................................................................................................................. 4- 2
4.1.1 Power on and off procedures ..................................................................................................... 4- 2
1
Page 11
4.1.2 Stop ............................................................................................................................................ 4- 2
www.kavrammuhendislik.com.tr
4.1.3 Test operation ............................................................................................................................ 4- 3
4.1.4 Parameter setting ....................................................................................................................... 4- 4
4.1.5 Point table setting ....................................................................................................................... 4- 5
4.1.6 Actual operation ......................................................................................................................... 4- 5
4.1.7 Troubleshooting at start-up ........................................................................................................ 4- 5
4.2 Automatic operation mode ................................................................................................................ 4- 7
4.2.1 Automatic operation mode ......................................................................................................... 4- 7
4.2.2 Automatic operation using point table ....................................................................................... 4-12
4.3 Manual operation mode ................................................................................................................... 4-42
4.3.1 JOG operation ........................................................................................................................... 4-42
4.3.2 Manual pulse generator operation ............................................................................................ 4-44
4.4 Home position return mode ............................................................................................................. 4-46
4.4.1 Outline of home position return ................................................................................................. 4-46
4.4.2 Dog type home position return .................................................................................................. 4-49
4.4.3 Count type home position return ............................................................................................... 4-51
4.4.4 Data set type home position return ........................................................................................... 4-53
4.4.5 Stopper type home position return ............................................................................................ 4-54
4.4.6 Home position ignorance (servo-on position as home position) ............................................... 4-56
4.4.7 Dog type rear end reference home position return ................................................................... 4-57
4.4.8 Count type front end reference home position return ............................................................... 4-59
4.4.9 Dog cradle type home position return ....................................................................................... 4-60
4.4.10 Dog type last Z-phase reference home position return ......................................................... 4-62
4.4.11 Dog type front end reference home position return type ....................................................... 4-64
4.4.12 Dogless Z-phase reference home position return type .......................................................... 4-66
4.4.13 Automatic retract function used for the home position return ................................................ 4-67
4.4.14 Automatic positioning to home position function .................................................................... 4-68
4.4.15
4.4.16
Precautions for using linear servo motors .............................................................................. 4-69
Precautions for using the fully closed loop system ................................................................. 4-73
4.5 Roll feed mode using the roll feed display function ......................................................................... 4-76
4.6 Point table setting method ............................................................................................................... 4-78
4.6.1 Setting procedure ...................................................................................................................... 4-78
4.6.2 Detailed setting window ............................................................................................................ 4-80
5. HOW TO USE THE PROGRAM 5- 1 to 5-68
5.1 Startup .............................................................................................................................................. 5- 1
5.1.1 Power on and off procedures ..................................................................................................... 5- 1
5.1.2 Stop ............................................................................................................................................ 5- 2
5.1.3 Test operation ............................................................................................................................ 5- 3
5.1.4 Parameter setting ....................................................................................................................... 5- 4
5.1.5 Actual operation ......................................................................................................................... 5- 5
5.1.6 Troubleshooting at start-up ........................................................................................................ 5- 5
5.2 Program operation method ............................................................................................................... 5- 6
5.2.1 Program operation method ........................................................................................................ 5- 6
5.2.2 Program language ...................................................................................................................... 5- 7
5.2.3 Basic settings of signals and parameters ................................................................................. 5-30
5.2.4 Timing chart of the program operation ...................................................................................... 5-32
5.3 Manual operation mode ................................................................................................................... 5-34
5.3.1 JOG operation ........................................................................................................................... 5-34
5.3.2 Manual pulse generator operation ............................................................................................ 5-35
2
Page 12
5.4 Home position return mode ............................................................................................................. 5-37
www.kavrammuhendislik.com.tr
5.4.1 Summary of home position return ............................................................................................. 5-37
5.4.2 Dog type home position return .................................................................................................. 5-40
5.4.3 Count type home position return ............................................................................................... 5-42
5.4.4 Data set type home position return ........................................................................................... 5-44
5.4.5 Stopper type home position return ............................................................................................ 5-45
5.4.6 Home position ignorance (servo-on position as home position) ............................................... 5-46
5.4.7 Dog type rear end reference home position return ................................................................... 5-47
5.4.8 Count type front end reference home position return ............................................................... 5-49
5.4.9 Dog cradle type home position return ....................................................................................... 5-51
5.4.10 Dog type last Z-phase reference home position return ......................................................... 5-53
5.4.11 Dog type front end reference home position return type ....................................................... 5-55
5.4.12 Dogless Z-phase reference home position return type .......................................................... 5-57
5.4.13 Automatic retract function used for the home position return ................................................ 5-58
5.5 Serial communication operation ...................................................................................................... 5-59
5.5.1 Positioning operation using the program .................................................................................. 5-59
5.5.2 Multi-drop method (RS-422 communication) ............................................................................ 5-60
5.5.3 Group specification ................................................................................................................... 5-61
5.6 Incremental value command method .............................................................................................. 5-63
5.7 Roll feed mode using the roll feed display function ......................................................................... 5-64
5.8 Program setting method .................................................................................................................. 5-65
5.8.1 Setting procedure ...................................................................................................................... 5-65
5.8.2 Window for program edit ........................................................................................................... 5-66
5.8.3 Indirect addressing window ....................................................................................................... 5-67
6. HOW TO USE INDEXER 6- 1 to 6-30
6.1 Startup .............................................................................................................................................. 6- 2
6.1.1 Power on and off procedures ..................................................................................................... 6- 2
6.1.2 Stop ............................................................................................................................................ 6- 2
6.1.3 Test operation ............................................................................................................................ 6- 3
6.1.4 Parameter setting ....................................................................................................................... 6- 4
6.1.5 Actual operation ......................................................................................................................... 6- 5
6.1.6 Troubleshooting at start-up ........................................................................................................ 6- 5
6.2 Automatic operation mode ................................................................................................................ 6- 7
6.2.1 Automatic operation mode ......................................................................................................... 6- 7
6.2.2 Automatic operation mode 1 (rotation direction specifying indexer) .......................................... 6- 8
6.2.3 Automatic operation mode 2 (shortest rotating indexer) ........................................................... 6-12
6.3 Manual operation mode ................................................................................................................... 6-15
6.3.1 Station JOG operation ............................................................................................................... 6-15
6.3.2 JOG operation ........................................................................................................................... 6-18
6.4 Home position return mode ............................................................................................................. 6-20
6.4.1 Outline of home position return ................................................................................................. 6-20
6.4.2 Torque limit changing dog type home position return ............................................................... 6-22
6.4.3 Torque limit changing data set type .......................................................................................... 6-24
6.4.4 Backlash compensation and digital override ............................................................................ 6-26
6.4.5 Safety precautions .................................................................................................................... 6-29
7. PARAMETERS 7- 1 to 7-100
7.1 Parameter list .................................................................................................................................... 7- 2
3
Page 13
7.1.1 Basic setting parameters ([Pr. PA_ _ ]) ...................................................................................... 7- 3
www.kavrammuhendislik.com.tr
7.1.2 Gain/filter setting parameters ([Pr. PB_ _ ]) ............................................................................... 7- 4
7.1.3 Extension setting parameters ([Pr. PC_ _ ]) .............................................................................. 7- 6
7.1.4 I/O setting parameters ([Pr. PD_ _ ]) ......................................................................................... 7- 9
7.1.5 Extension setting 2 parameters ([Pr. PE_ _ ]) ........................................................................... 7-10
7.1.6 Extension setting 3 parameters ([Pr. PF_ _ ]) ........................................................................... 7-12
7.1.7 Linear servo motor/DD motor setting parameters ([Pr. PL_ _ ]) ............................................... 7-13
7.1.8 Option setting parameters ([Pr. Po_ _ ]) ................................................................................... 7-14
7.1.9 Positioning control parameters ([Pr. PT_ _ ]) ............................................................................ 7-15
7.2 Detailed list of parameters ............................................................................................................... 7-16
7.2.1 Basic setting parameters ([Pr. PA_ _ ]) ..................................................................................... 7-17
7.2.2 Gain/filter setting parameters ([Pr. PB_ _ ]) .............................................................................. 7-30
7.2.3 Extension setting parameters ([Pr. PC_ _ ]) ............................................................................. 7-42
7.2.4 I/O setting parameters ([Pr. PD_ _ ]) ........................................................................................ 7-56
7.2.5 Extension setting 2 parameters ([Pr. PE_ _ ]) ........................................................................... 7-68
7.2.6 Extension setting 3 parameters ([Pr. PF_ _ ]) ........................................................................... 7-71
7.2.7 Linear servo motor/DD motor setting parameters ([Pr. PL_ _ ]) ............................................... 7-73
7.2.8 Option setting parameters ([Pr. Po_ _ ]) ................................................................................... 7-75
7.2.9 Positioning control parameters ([Pr. PT_ _ ]) ............................................................................ 7-83
7.3 How to set the electronic gear ......................................................................................................... 7-93
7.3.1 Electronic gear settings in the point table method and program method ................................. 7-93
7.3.2 Electronic gear setting in the indexer method ........................................................................... 7-96
7.4 Software limit ................................................................................................................................... 7-97
7.5 Stop method for LSP (Forward rotation stroke end) off or LSN (Reverse rotation stroke end) off . 7-98
7.6 Stop method at software limit detection ........................................................................................... 7-99
8. TROUBLESHOOTING 8- 1 to 8-14
8.1 Explanation for the lists ..................................................................................................................... 8- 1
8.2 Alarm list ........................................................................................................................................... 8- 2
8.3 Warning list ...................................................................................................................................... 8-11
9. OPTIONS AND PERIPHERAL EQUIPMENT 9- 1 to 9- 4
9.1 MR-HDP01 manual pulse generator ................................................................................................ 9- 2
10. COMMUNICATION FUNCTION (MITSUBISHI GENERAL-PURPOSE AC SERVO PROTOCOL)
10- 1 to 10-40
10.1 Command and data No. list .......................................................................................................... 10- 1
10.1.1 Reading command ................................................................................................................. 10- 2
10.1.2 Writing commands ................................................................................................................ 10-12
10.2 Detailed explanations of commands ............................................................................................ 10-16
10.2.1 External I/O signal status (DIO diagnosis) ............................................................................ 10-16
10.2.2 Input device on/off ................................................................................................................. 10-21
10.2.3 Input device on/off (for test operation) .................................................................................. 10-22
10.2.4 Test operation mode ............................................................................................................. 10-23
10.2.5 Output signal pin on/off (output signal (DO) forced output) .................................................. 10-25
10.2.6 Point table ............................................................................................................................. 10-26
10.3 Settings equivalent to previous models ....................................................................................... 10-34
10.3.1 Relevant matters to monitor information ............................................................................... 10-34
10.3.2 Relevant matters to input/output ........................................................................................... 10-36
4
Page 14
11. MR-D01 EXTENSION I/O UNIT 11- 1 to 11-78
www.kavrammuhendislik.com.tr
11.1 Function block diagram ................................................................................................................. 11- 2
11.2 Structure ....................................................................................................................................... 11- 4
11.2.1 Parts identification .................................................................................................................. 11- 4
11.2.2 Installation and removal of the MR-D01 extension I/O unit ................................................... 11- 5
11.3 Configuration including peripheral equipment .............................................................................. 11- 9
11.4 Installation direction and clearances ........................................................................................... 11-11
11.5 Signals and wiring ........................................................................................................................ 11-13
11.5.1 I/O signal connection diagram .............................................................................................. 11-14
11.5.2 Connectors and pin assignment ........................................................................................... 11-40
11.5.3 Signal (device) explanations ................................................................................................. 11-42
11.5.4 Interfaces .............................................................................................................................. 11-56
11.6 Monitor display with MR Configurator2 ........................................................................................ 11-60
11.7 Operation ..................................................................................................................................... 11-62
11.7.1 Operation mode and selecting method ................................................................................. 11-62
11.7.2 When using MR-DS60 (6-digit digital switch) for automatic operation with BCD
(3-digit × 2) inputs ................................................................................................................. 11-62
11.7.3 When using a programmable controller for automatic operation with BCD
(3 digits × 2) inputs ................................................................................................................ 11-66
11.7.4 Home position return in the BCD (3 digits × 2) input operation ............................................ 11-69
11.8 Dimensions .................................................................................................................................. 11-70
11.8.1 MR-D01 extension I/O unit .................................................................................................... 11-70
11.8.2 When an MR-D01 extension IO unit is connected to a servo amplifier ................................ 11-70
11.9 Options and peripheral equipment .............................................................................................. 11-71
11.9.1 Combinations of cable/connector sets .................................................................................. 11-71
11.9.2 MR-DS60 (6-digit digital switch) ............................................................................................ 11-72
11.9.3 PS7DW-20V14B-F (Junction terminal block) (recommended) ............................................. 11-75
11.9.4 MR-TB50 (Junction terminal block)....................................................................................... 11-77
12. APPLICATION OF FUNCTIONS
12- 1 to 12-62
12.1 Simple cam function ..................................................................................................................... 12- 1
12.1.1 Outline of simple cam function ............................................................................................... 12- 1
12.1.2 Simple cam function block ..................................................................................................... 12- 2
12.1.3 Simple cam specification list .................................................................................................. 12- 3
12.1.4 Control of simple cam function ............................................................................................... 12- 4
12.1.5 Operation in combination with the simple cam ...................................................................... 12- 5
12.1.6 Setting list ............................................................................................................................... 12- 7
12.1.7 Data to be used with simple cam function ............................................................................. 12- 8
12.1.8 Function block diagram for displaying state of simple cam control ...................................... 12-28
12.1.9 Operation .............................................................................................................................. 12-28
12.1.10 Cam No. setting method ..................................................................................................... 12-38
12.1.11 Stop operation of cam control ............................................................................................. 12-39
12.1.12 Restart operation of cam control ......................................................................................... 12-41
12.1.13 Cam axis position at cam control switching ........................................................................ 12-42
12.1.14 Clutch .................................................................................................................................. 12-49
12.1.15 Cam position compensation target position ........................................................................ 12-51
12.1.16 Cam position compensation time constant ......................................................................... 12-52
12.2 Mark detection ............................................................................................................................. 12-53
12.2.1 Current position latch function .............................................................................................. 12-53
5
Page 15
12.2.2 Interrupt positioning function ................................................................................................. 12-59
www.kavrammuhendislik.com.tr
12.3 Infinite feed function (setting degree) .......................................................................................... 12-62
6
Page 16

1. FUNCTIONS AND CONFIGURATION

)
www.kavrammuhendislik.com.tr
1. FUNCTIONS AND CONFIGURATION
The following items are the same as MR-J4-_A_-RJ servo amplifiers. For details, refer to each section indicated in the detailed explanation field. "MR-J4-_A_" means "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual".
Item
Combinations of servo amplifiers and servo motors MR-J4-_A_ section 1.4 MR-J4-_A_ section 18.1.4
Model code definition MR-J4-_A_ section 1.6 MR-J4-_A_ section 18.1.6
Structure (parts identification) MR-J4-_A_ section 1.7 MR-J4-_A_ section 18.1.7
MR-J4-_A_-RJ 100 W
or more

1.1 For proper use of the positioning mode

(1) Servo amplifier/MR Configurator2
The positioning mode is used by the servo amplifier and MR Configurator2 with the following software versions.
Product name Model Software version
Servo amplifier
MR Configurator2 SW1DNC-MRC2-_ 1.34L or later
MR-J4-_A_-RJ 100 W or more B3 or later
MR-J4-03A6-RJ Does not depend on the software version.
(2) Parameter setting
(a) Selection of the positioning mode
Select a positioning mode with [Pr. PA01 Operation mode] to use.
[Pr. PA01]
Detailed explanation
MR-J4-03A6-RJ
(b) Positioning control parameters ([Pr. PT_ _ ])
To enable read/write the positioning control parameters ([Pr. PT_ _ ]), set [Pr. PA19 Parameter writing inhibit] to "0 0 A B".
(c) Assigning recommended input/output devices
Assign recommended input/output devices to the pins of CN1 in accordance with each chapter of point table/program/indexer method.
Control mode selection 6: Positioning mode (point table method 7: Positioning mode (program method) 8: Positioning mode (indexer method)
1 - 1
Page 17
1. FUNCTIONS AND CONFIGURATION
www.kavrammuhendislik.com.tr

1.2 Positioning mode specification list

The specifications only of the positioning mode are listed here. For other specifications, refer to section 1.3 and 18.1.3 of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual".
Positioning mode
Command method
Item Description
Servo amplifier model MR-J4-_A_-RJ 100 W or more/MR-J4-03A6-RJ
Operational specifications Positioning with specification of point table No. (255 points) (Note 6, 7)
Absolute value
Position
Point table
command input (Note 1)
command method
Incremental value command method
Speed command input
Setting range of feed length per point: -999999 to 999999 [×10
-99.9999 to 99.9999 [×10 Setting range of rotation angle: -360.000 to 360.000 [degree]
Setting range of feed length per point: 0 to 999999 [×10
0 to 99.9999 [×10
Setting range of rotation angle: 0 to 999.999 [degree]
Set the acceleration/deceleration time constants in the point table.
Set the S-pattern acceleration/deceleration time constants with [Pr. PC03].
Set in the point table.
STM
inch], -999999 to 999999 [pulse],
Set in the point table.
STM
inch], 0 to 999999 [pulse],
STM
STM
μm],
μm],
System Signed absolute value command method/incremental value command method
Analog override 0 V DC to ±10 V DC/0% to 200%
Torque limit Set with parameter or external analog input (0 V DC to +10 V DC/maximum torque)
Signed 6-digit BCD digital switch or contact input
Setting range of feed length: -999999 to 999999 [×10
-99.9999 to 99.9999 [×10
STM
inch], -999999 to 999999 [pulse],
STM
μm],
Setting range of rotation angle: -360.000 to 360.000 [degree]
Absolute value
command
method
BCD input
Signed 6-digit BCD digital switch or contact input
Setting range of feed length: 0 to 999999 [×10
0 to 99.9999 [×10
STM
inch], 0 to 999999 [pulse],
STM
μm],
Setting range of rotation angle: 0 to 999.999 [degree]
Position command input (Note 1)
Incremental
value command
method
command input
System Signed absolute value command method/incremental value command method
Speed
Selects the rotation speeds and acceleration/deceleration times of
the point table No. 1 to 15 by a contact input.
Set the S-pattern acceleration/deceleration time constants with [Pr. PC03].
Setting of position command data with RS-422/RS-485 communication Setting range of feed length per point: -999999 to 999999 [×10
-99.9999 to 99.9999 [×10
STM
inch], -999999 to 999999 [pulse],
STM
μm],
Setting range of rotation angle: -360.000 to 360.000 [degree]
Absolute value
command
method
Setting of position command data with RS-422/RS-485 communication
Setting range of feed length per point: 0 to 999999 [×10
0 to 99.9999 [×10
STM
inch], 0 to 999999 [pulse],
STM
μm],
Setting range of rotation angle: 0 to 999.999 [degree]
Position command input (Note 1)
Incremental
value command
method
command input
Speed
Position command data input
System Signed absolute value command method/incremental value command method
Operational specifications
Program
Position command input (Note 1)
RS-422/RS-485 communication (Note 5)
Absolute value command method
Incremental value command method
Speed command input
Selects the rotation speed and acceleration/deceleration time constant
through RS-422/RS-485 communication.
Set the S-pattern acceleration/deceleration time constants with [Pr. PC03].
Program language (program with MR Configurator2)
Program capacity: 640 steps (256 programs)
Setting range of feed length: -999999 to 999999 [×10
-99.9999 to 99.9999 [×10
STM
inch], -999999 to 999999 [pulse],
Set with program language.
STM
μm],
Setting range of rotation angle: -360.000 to 360.000 [degree]
Setting range of feed length: -999999 to 999999 [×10
-99.9999 to 99.9999 [×10
STM
inch], -999999 to 999999 [pulse],
Set with program language.
STM
μm],
Setting range of rotation angle: -999.999 to 999.999 [degree]
Set servo motor speed, acceleration/deceleration time constants,
and S-pattern acceleration/deceleration time constants with program language.
S-pattern acceleration/deceleration time constants are also settable with [Pr. PC03].
System Signed absolute value command method/signed incremental value command method
Analog override Set with external analog input (0 V DC to ±10 V DC/0% to 200%)
Torque limit Set with parameter or external analog input (0 V DC to +10 V DC/maximum torque)
1 - 2
Page 18
1. FUNCTIONS AND CONFIGURATION
www.kavrammuhendislik.com.tr
Item Description
Operational specifications
Indexer
Speed command input Selects the rotation speed and acceleration/deceleration time constant by a contact input.
System Rotation direction specifying indexer/shortest rotating indexer
Positioning mode
Other functions
Digital override Selects the override multiplying factor by a contact input.
Command method
Torque limit Set with parameter or external analog input (0 V DC to +10 V DC/maximum torque)
Point table
Operation mode
Program Depends on settings of program language.
Automatic operation mode
Indexer
Point table/
program
Indexer
Manual operation mode
Dog type
Count type
Point table/program
Data set type
Home position return mode
Stopper type
Home position ignorance (servo-on position as
home position)
Dog type rear end reference
Count type front end reference
Dog cradle type
Dog type last Z-phase reference (Note 4)
Dog type front end reference
Dogless Z-phase reference (Note 4)
Torque limit changing dog type
Indexer
Torque limit changing data set type
Automatic positioning to home position function (Note 2)
Each positioning operation
Automatic continuous positioning operation
Rotation direction specifying indexer
Shortest rotating indexer
JOG operation
Manual pulse generator operation
JOG operation Decelerates to a stop regardless of the station.
Station JOG operation
Varying-speed operation (2 to 255 speeds)/automatic continuous positioning operation (2 to 255 points)/
Executes a contact input or an inching operation with the RS-422/RS-485 communication function based on
Positions to the nearest station where the servo motor can decelerate to a stop when the start signal turns off.
home position address settable/home position shift amount settable/home position return direction selectable/
Home position return direction selectable/home position shift amount settable/home position address settable/
Sets any position as a home position using manual operation, etc./home position address settable
Home position return direction selectable/home position shift amount settable/home position address settable/
Home position return direction selectable/home position shift amount settable/home position address settable/
Returns to home position upon the first Z-phase pulse based on the front end of the proximity dog.
Home position return direction selectable/home position shift amount settable/home position address settable/
Returns to home position upon the Z-phase pulse right before the proximity dog based on the front end of the
Home position return direction selectable/home position shift amount settable/home position address settable/
Home position return direction selectable/home position shift amount settable/home position address settable/
Home position return direction selectable/home position shift amount settable/home position address settable
Home position return direction selectable/home position shift amount settable/home position address settable
Sets any position as home position/home position address settable/torque limit automatic changing function
Absolute position detection/backlash compensation/overtravel prevention with external limit switch
Operates each positioning based on position command and speed command.
Positions to the specified station. Rotates in the shorter direction from the current position.
Command pulse multiplication: select from ×1, ×10, and ×100 with a parameter.
Rotates in a direction specified by the rotation direction decision when the start signal turns on.
Returns to home position upon Z-phase pulse after passing through the proximity dog.
automatic retract on dog back to home position/automatic stroke retract function
Returns to home position upon the encoder pulse count after touching the proximity dog.
automatic retract on dog back to home position/automatic stroke retract function
Home position return direction selectable/home position address settable
automatic retract on dog back to home position/automatic stroke retract function
automatic retract on dog back to home position/automatic stroke retract function
automatic retract on dog back to home position/automatic stroke retract function
automatic retract on dog back to home position/automatic stroke retract function
Returns to home position to the front end of the dog based on the front end of the proximity dog.
automatic retract on dog back to home position/automatic stroke retract function
Returns to home position to the Z-phase pulse with respect to the first Z-phase pulse.
Returns to home position upon Z-phase pulse after an external limit is detected.
(LSP/LSN)/software stroke limit/mark detection function (Note 3)/override
Positioning by specifying the station position (Note 7)
The maximum number of divisions: 255
Point table No. input method/position data input method
automatic continuous operation to a point table selected at startup/
automatic continuous operation to the point table No. 1
Positions to the specified station. Rotation direction settable
Manual feeding is executed with a manual pulse generator.
Returns to home position upon hitting the stroke end.
Sets a home position where SON (Servo-on) signal turns on.
Returns to home position based on the rear end of the proximity dog.
Returns to home position based on the front end of the proximity dog.
Torque limit automatic changing function
Returns to home position without external limits.
High-speed automatic positioning to a defined home position
speed command set with parameters.
Returns to home position without dog.
Home position address settable
proximity dog.
1 - 3
Page 19
1. FUNCTIONS AND CONFIGURATION
www.kavrammuhendislik.com.tr
Note 1. STM is the ratio to the setting value of the position data. STM can be changed with [Pr. PT03 Feeding function selection].
2. The automatic positioning to home position function is not available with the program method and the indexer method.
3. Indexer method does not have the mark detection function.
4. Dog type last Z-phase reference home position return and dogless Z-phase reference home position return type are not
compatible with direct drive motors and incremental linear encoders.
5. For MR-J4-_A_-RJ servo amplifiers with a capacity of 100 W or more, the RS-485 communication is available with the servo
amplifiers manufactured in November, 2014 or later.
6. For MR-J4-03A6-RJ servo amplifiers, point table No. 1 to No. 99 can be set with the operation section (4 push buttons). Use
MR Configurator2 to set point table No. 100 to 255. (Refer to section 3.2.5.)
7. For MR-J4-03A6-RJ servo amplifiers, up to six points of DO are available; therefore, PT0 (Point table No. output 1) to PT7
(Point table No. output 8) or PS0 (Station output 1) to PS7 (Station output 8) cannot be outputted simultaneously.
1 - 4
Page 20
1. FUNCTIONS AND CONFIGURATION
www.kavrammuhendislik.com.tr

1.3 Function list

POINT
The symbols in the control mode column mean as follows. CP: Positioning mode (point table method) CL: Positioning mode (program method) PS: Positioning mode (indexer method)
The following table lists the functions of this servo. For details of the functions, refer to each section indicated in the detailed explanation field. "MR-J4-_A_" means "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual".
Function Description
This function achieves a high response and stable control following the ideal model. The two-degrees-of-freedom model adaptive control enables you to set a response to the command and response to the disturbance separately.
Model adaptive control
Positioning mode (point table method)
Positioning mode (program method)
Positioning mode (indexer method)
Roll feed display function
Current position latch
Mark detection
Infinite feed function (setting degree)
Simple cam function
function
Interrupt positioning function
Additionally, this function can be disabled. To disable this function, refer to section 7.5 of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual". This is available with servo amplifiers with software version B4 or later. Check the software version using MR Configurator2.
Set 1 to 255 point tables in advance, and select any point table to perform operation in accordance with the set values. To select point tables, use external input signals or communication function.
Set 1 to 256 programs in advance and select any program to perform operation in accordance with the programs. To select programs, use external input signals or communication function.
Set 2 to 255 divided stations in advance to perform operation to the station positions. To select station positions, use external input signals or communication function.
Positions based on specified travel distance from a status display "0" of current/command positions at start.
When the mark detection signal turns on, the current position is latched. The latched data can be read with communication commands.
When MSD (Mark detection) turns on, this function converts the remaining distance to the travel amount set in [Pr. PT30] and [Pr. PT31] (Mark sensor stop travel distance).
This is available with servo amplifiers with software version B7 or later.
When the unit of position data of the automatic operation or manual operation is set to degree, the detection of [AL. E3.1 Multi-revolution counter travel distance excess warning] is disabled and the home position is retained even if the servo motor rotates 32768 revolutions or more are in the same direction. Thus, the current position is restored after the power is cycled.
This function can be used with the absolute position detection system. This is available with servo amplifiers with software version B7 or later.
This function enables the encoder following function, mark sensor input compensation function, synchronous operation using positioning data, and synchronous interpolation operation.
This function is not available with the servo amplifier to which the MR-D30 unit has been connected. This is available with servo amplifiers with software version B7 or later.
This function will be available with MR-J4-03A6-RJ servo amplifiers in the future.
Control mode
Detailed
explanation
CL
CP/BCD
PS
Chapter 4
Chapter 5
Chapter 6
Section 4.5
Section
12.2.1
Section
12.2.2
Section
12.3
Section
12.1
1 - 5
Page 21
1. FUNCTIONS AND CONFIGURATION
www.kavrammuhendislik.com.tr
Control mode
Function Description
Dog type/count type/data setting type/stopper type/home position ignorance/dog type rear end reference/count type front end reference/dog
home position return
High-resolution encoder
Absolute position detection system
Gain switching function
Advanced vibration suppression control II
Machine resonance suppression filter
Shaft resonance suppression filter
Adaptive filter II
Low-pass filter
Machine analyzer function
Robust filter
Slight vibration suppression control
Electronic gear
Auto tuning
Brake unit
Power regeneration converter
Regenerative option
Alarm history clear Alarm history is cleared.
Input signal selection (device settings)
cradle type/dog type last Z-phase reference/dog type Z-phase reference/dogless Z-phase reference
Torque limit changing dog type/torque limit changing data set type High-resolution encoder of 4194304 pulses/rev is used as the encoder of the
rotary servo motor compatible with the MELSERVO-J4 series. However, the encoder resolution of the rotary servo motor compatible with MR-J4-03A6­RJ servo amplifiers will be 262144 pulses/rev.
Home position return is required only once, and not required at every power­on. Only "12.1 Summary" and "12.2 Battery" will be appropriate references for the positioning mode.
You can switch gains during rotation/stop, and can use input devices to switch gains during operation.
This function suppresses vibration at the arm end or residual vibration.
This is a filter function (notch filter) which decreases the gain of the specific frequency to suppress the resonance of the mechanical system.
When a load is mounted to the servo motor shaft, resonance by shaft torsion during driving may generate a mechanical vibration at high frequency. The shaft resonance suppression filter suppresses the vibration.
Servo amplifier detects mechanical resonance and sets filter characteristics automatically to suppress mechanical vibration.
Suppresses high-frequency resonance which occurs as servo system response is increased.
Analyzes the frequency characteristic of the mechanical system by simply connecting an MR Configurator2 installed personal computer and servo amplifier.
MR Configurator2 is necessary for this function. This function provides better disturbance response in case low response
level that load to motor inertia ratio is high for such as roll send axes.
Suppresses vibration of ±1 pulse generated at a servo motor stop.
Position commands can be multiplied by 1/864 to 33935. Position commands can be multiplied by 1/9999 to 9999. Automatically adjusts the gain to optimum value if load applied to the servo
motor shaft varies. Used when the regenerative option cannot provide enough regenerative
power. Can be used for the 5 kW or more servo amplifier. This is not available with MR-J4-03A6-RJ servo amplifiers. Used when the regenerative option cannot provide enough regenerative
power. Can be used for the 5 kW or more servo amplifier. This is not available with MR-J4-03A6-RJ servo amplifiers. Used when the built-in regenerative resistor of the servo amplifier does not
have sufficient regenerative capability for the regenerative power generated. This is not available with MR-J4-03A6-RJ servo amplifiers.
ST1 (Forward rotation start), ST2 (Reverse rotation start), and SON (Servo­on) and other input device can be assigned to any pins.
CL
CP/BCD
Detailed
explanation
PS
Section 4.4 Section 5.4
Section 6.4
MR-J4-_A_ chapter 12
MR-J4-_A_ section 7.2
MR-J4-_A_ section 7.1.5
MR-J4-_A_ section 7.1.1
MR-J4-_A_ section 7.1.3
MR-J4-_A_ section 7.1.2
MR-J4-_A_ section 7.1.4
[Pr. PE41]
[Pr. PB24]
[Pr. PA06] [Pr. PA07]
MR-J4-_A_ section 6.3
MR-J4-_A_ section 11.3
MR-J4-_A_ section 11.4
MR-J4-_A_ section 11.2
[Pr. PC18] [Pr. PD04] [Pr. PD06] [Pr. PD08] [Pr. PD10] [Pr. PD12] [Pr. PD14] [Pr. PD18] [Pr. PD20] [Pr. PD22] [Pr. PD44] [Pr. PD46]
1 - 6
Page 22
1. FUNCTIONS AND CONFIGURATION
www.kavrammuhendislik.com.tr
Function Description
Output signal selection (device settings)
Output signal (DO) forced output
Command pulse selection Supports only A-axis/B-axis pulse trains.
Torque limit Servo motor torque can be limited to any value.
Status display
External I/O signal display On/off statuses of external I/O signals are shown on the display.
Alarm code output
Test operation mode
Analog monitor output Servo status is outputted in terms of voltage in real time.
MR Configurator2
Linear servo system
Direct drive servo system
Fully closed loop system
One-touch tuning
The output devices including MBR (Electromagnetic brake interlock) can be assigned to certain pins of the CN1 connector.
However, [Pr. PD47] is not available with MR-J4-03A6-RJ servo amplifiers.
Output signal can be forced on/off independently of the servo status. Use this function for checking output signal wiring, etc.
Servo status is shown on the 5-digit, 7-segment LED display. For MR-J4-03A6-RJ servo amplifiers, the servo status is shown on the 3-
digit, 7-segment LED display.
If an alarm has occurred, the corresponding alarm number is outputted in 3­bit code.
Jog operation/positioning operation/motor-less operation/DO forced output/program operation/single-step feed
However, MR Configurator2 is necessary for positioning operation, program operation, and single-step feed.
Using a personal computer, you can perform the parameter setting, test operation, monitoring, and others.
Linear servo system can be configured using a linear servo motor and linear encoder.
For the home position return, refer to the chapter indicated in the detailed explanation field and section 4.4.15.
This is not available with MR-J4-03A6-RJ servo amplifiers. The direct drive servo system can be configured to drive a direct drive
motor. This is not available with MR-J4-03A6-RJ servo amplifiers. Fully closed loop system can be configured using the load-side encoder. For the home position return, refer to the chapter indicated in the detailed
explanation field and section 4.4.16. This is not available with MR-J4-03A6-RJ servo amplifiers.
Gain adjustment is performed just by one click on a certain button on MR Configurator2 or operation section.
Control mode
CL
CP/BCD
[Pr. PA13]
Detailed
explanation
PS
[Pr. PD23] to [Pr. PD26] [Pr. PD28] [Pr. PD47] Section 3.1.8 Section 3.2.8 MR-J4-_A_
section 4.5.8 section
18.5.9
[Pr. PA11] [Pr. PA12] Section
3.1.2 Section
3.2.2 Section
3.1.7 Section
3.2.7
Chapter 8
Section
3.1.8 Section
3.1.9 Section
3.2.8 Section
3.2.9 MR-J4-_A_
section 4.5.8 section 4.5.9 section
18.5.9 section
18.5.10 [Pr. PC14] [Pr. PC15] MR-J4-_A_
section 11.7
MR-J4-_A_ chapter 15
MR-J4-_A_ chapter 16
MR-J4-_A_ chapter 17
MR-J4-_A_ section 6.2
section
18.5.4
1 - 7
Page 23
1. FUNCTIONS AND CONFIGURATION
www.kavrammuhendislik.com.tr
Function Description
This function which complies with the SEMI-F47 standard enables to avoid triggering [AL. 10 Undervoltage] using the electrical energy charged in the
SEMI-F47 function
Tough drive function
Drive recorder function
STO function
Servo amplifier life diagnosis function
Power monitoring function
Machine diagnosis function
Lost motion compensation function
Super trace control
Limit switch
S-pattern acceleration/deceleration
Software limit
Analog override
Digital override
capacitor in case that an instantaneous power failure occurs during operation.
This is not available with MR-J4-03A6-RJ servo amplifiers. This function makes the equipment continue operating even under the
condition that an alarm occurs. The tough drive function includes two types: the vibration tough drive and
the instantaneous power failure tough drive. MR-J4-03A6-RJ servo amplifiers are not compatible with the instantaneous
power failure tough drive.
This function continuously monitors the servo status and records the status transition before and after an alarm for a fixed period of time. You can check the recorded data on the drive recorder window on MR Configurator2 by clicking the "Graph" button.
However, the drive recorder will not operate on the following conditions.
1. You are using the graph function of MR Configurator2.
2. You are using the machine analyzer function.
3. [Pr. PF21] is set to "-1".
This amplifier complies with the STO function as functional safety of IEC/EN 61800-5-2. You can create a safety system for the equipment easily.
This is not available with MR-J4-03A6-RJ servo amplifiers.
You can check the cumulative energization time and the number of on/off times of the inrush relay. This function gives an indication of the replacement time for parts of the servo amplifier including a capacitor and a relay before they malfunction.
MR Configurator2 is necessary for this function.
This function calculates the power running energy and the regenerative power from the data in the servo amplifier such as speed and current. Power consumption and others are displayed on MR Configurator2.
From the data in the servo amplifier, this function estimates the friction and vibrational component of the drive system in the equipment and recognizes an error in the machine parts, including a ball screw and bearing.
MR Configurator2 is necessary for this function.
This function improves the response delay occurred when the machine moving direction is reversed. This is used with servo amplifiers with software version B4 or later. Check the software version of the servo amplifier with MR Configurator2.
This function sets constant and uniform acceleration/deceleration droop pulses to almost 0. This is used with servo amplifiers with software version B4 or later. Check the software version of the servo amplifier with MR Configurator2.
Limits travel intervals using LSP (Forward rotation stroke end) and LSN (Reverse rotation stroke end).
Enables smooth acceleration and deceleration. Set S-pattern acceleration/deceleration time constants with [Pr. PC03]. Compared with linear acceleration/deceleration, the
acceleration/deceleration time will be longer for the S-pattern acceleration/deceleration time constants regardless of command speed.
Limits travel intervals by address using parameters. Enables the same function with the limit switch by setting parameters.
Limits a servo motor speed with analog inputs. A value can be changed from 0% to 200% for a set speed.
A commanded speed multiplied by an override value selected with OVR (Override selection) will be an actual servo motor speed.
A value can be changed from 0% to 360% for a set speed.
Control mode
CL
CP/BCD
Section 7.4
Section 2.4
Detailed
explanation
PS
MR-J4-_A_ section 7.4
[Pr. PA20] [Pr. PF25]
MR-J4-_A_ section 7.3
[Pr. PA23]
MR-J4-_A_ chapter 13
MR-J4-_A_ section 7.6
MR-J4-_A_ section 7.7
[Pr. PC03] section 5.2.2
[Pr. PT42] [Pr. PT43] section
6.4.4 (2)
1 - 8
Page 24
1. FUNCTIONS AND CONFIGURATION
www.kavrammuhendislik.com.tr
Function Description
After an operation travels to a target position with a JOG operation or
Teaching function
MR-D01 extension I/O unit
Modbus-RTU communication function
High-resolution analog input (VC)
manual pulse generator operation, pushing the SET button of the operation part or turning on TCH (Teach) will import position data.
MR-D01 is an extension I/O unit that can extend the input/output signals of MR-J4-_A_-RJ servo amplifiers.
MR-D01 extension I/O unit is available with servo amplifiers with software version B7 or later.
The Modbus protocol uses dedicated message frames for the serial communication between a master and slaves. Using the functions in the message frames enables to read or write data from/to parameters, write input commands, and check operation status of servo amplifiers. When the indexer method is used, there are functional restrictions.
This function is supported by MR-J4-_A_-RJ servo amplifiers with a capacity of 100 W or more manufactured in November, 2014 or later.
This function will be available with MR-J4-03A6-RJ servo amplifiers in the future.
The analog input resolution can be increased to 16 bits. This function is available with servo amplifiers manufactured in November 2014 or later.
This is not available with MR-J4-03A6-RJ servo amplifiers.
Control mode
CL
CP/BCD
[Pr. PC60]
Detailed
explanation
PS
Section
3.1.10 Section
3.2.10
Chapter 11
MR-J4-_A_­RJ Servo Amplifier Instruction Manual (Modbus­RTU Protocol)
1 - 9
Page 25
1. FUNCTIONS AND CONFIGURATION
www.kavrammuhendislik.com.tr

1.4 Configuration including peripheral equipment

CAUTION
(1) MR-J4-_A_-RJ 100 W or more
The following illustration is an example of MR-J4-20A-RJ.
(Note 2) Power supply
Molded-case circuit breaker (MCCB)
RS T
Connecting a servo motor of the wrong axis to U, V, W, or CN2 of the servo amplifier may cause a malfunction.
POINT
Equipment other than the servo amplifier and servo motor are optional or recommended products.
Personal computer
MR Configurator2
CN5
(Note 3) Magnetic contactor (MC)
(Note 1)
Line noise filter (FR-BSF01)
Power factor improving DC reactor (FR-HEL)
Regenerative option
L1 L2 L3
P+
C
P3
P4
L11
L21
D (Note 5)
CN6
To RS-422/RS-485 communication
CN3
controller, parameter unit, etc.
CN8
Analog monitor
To safety relay or MR-J3-D05 safety logic unit
U
V
W
CN1
CN2
CN2L (Note 4)
CN4
Battery
Manual pulse generator
Junction terminal block
Servo motor
1 - 10
Page 26
1. FUNCTIONS AND CONFIGURATION
A
A
y
www.kavrammuhendislik.com.tr
Note 1. The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used.
2.
3. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop
4. When using MR-J4-_A_-RJ servo amplifiers with a capacity of 100 W or more in the linear servo system or in the fully closed
5.
(2) MR-J4-03A6-RJ
48 V DC main circuit power suppl
When not using the power factor improving DC reactor, short P3 and P4.
1-phase 200 V AC to 240 V AC power supply may be used with the servo amplifier of MR-J4-200A-RJ or less. For 1-phase 200 V AC to 240 V AC, connect the power supply to L1 and L3. Leave L2 open. For power supply specifications, refer to section 1.3 of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual".
deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn off the magnetic contactor.
loop system, connect an external encoder to this connector. Refer to Table 1.1 of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual" and "Linear Encoder Instruction Manual" for the connectible external encoders.
lways connect between P+ and D terminals. When using the regenerative option, refer to section 11.2 of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual".
48 V DC
power
supply
+-
24 V DC
power supply
-+
Circuit
protector
MR Configurator2
Personal computer
CN3
CN4
CNP1 (Note)
24
0
PM
Relay
24 V DC main circuit power supply
24 V DC
power supply
-+
Circuit
protector
PM 0 24
Note. For details, refer to section 18.3.2 of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual".
CN1
CN2
CNP1
MR-BAT6V1SET-A
Manual pulse generator
Junction terminal block
Servo motor
1 - 11
Page 27
1. FUNCTIONS AND CONFIGURATION
www.kavrammuhendislik.com.tr
MEMO
1 - 12
Page 28

2. SIGNALS AND WIRING

r
www.kavrammuhendislik.com.tr
2. SIGNALS AND WIRING
Any person who is involved in wiring should be fully competent to do the work. Before wiring, turn off the power and wait for 15 minutes or more until the charge lamp turns off. Then, confirm that the voltage between P+ and N- is safe with a voltage tester and others. Otherwise, an electric shock may occur. In addition, when confirming whether the charge lamp is off or not, always confirm it from the front of the servo amplifier.
WARNING
Ground the servo amplifier and servo motor securely. Do not attempt to wire the servo amplifier and servo motor until they have been installed. Otherwise, it may cause an electric shock. The cables should not be damaged, stressed, loaded, or pinched. Otherwise, it may cause an electric shock. To avoid an electric shock, insulate the connections of the power supply terminals.
Wire the equipment correctly and securely. Otherwise, the servo motor may operate unexpectedly, resulting in injury. Connect cables to the correct terminals. Otherwise, a burst, damage, etc. may occur. Ensure that polarity (+/-) is correct. Otherwise, a burst, damage, etc. may occur. The surge absorbing diode installed to the DC relay for control output should be fitted in the specified direction. Otherwise, the emergency stop and other protective circuits may not operate.
Servo amplifie
or MR-D01
DOCOM
(DOCOMD)
Control output signal
For sink output interface
24 V DC
RA
Servo amplifier
or MR-D01
For source output interface
(DOCOMD)
Control output signal
DOCOM
24 V DC
RA
CAUTION
Use a noise filter, etc. to minimize the influence of electromagnetic interference. Electromagnetic interference may be given to the electronic equipment used near the servo amplifier. Do not install a power capacitor, surge killer or radio noise filter (optional FR-BIF(­H)) with the power line of the servo motor. When using the regenerative resistor, switch power off with the alarm signal. Otherwise, a transistor fault or the like may overheat the regenerative resistor, causing a fire. Do not modify the equipment. Connect the servo amplifier power output (U/V/W) to the servo motor power input (U/V/W) directly. Do not let a magnetic contactor, etc. intervene. Otherwise, it may cause a malfunction.
Servo amplifier
U
V
W
Servo motor
U
V
W
Servo motorServo amplifier
U
M
V
W
U
V
W
Connecting a servo motor of the wrong axis to U, V, W, or CN2 of the servo amplifier may cause a malfunction.
M
2 - 1
Page 29
2. SIGNALS AND WIRING
www.kavrammuhendislik.com.tr
The following items are the same as MR-J4-_A_-RJ servo amplifiers. For details, refer to each section indicated in the detailed explanation field. "MR-J4-_A_" means "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual".
Item
Input power supply circuit MR-J4-_A_ section 3.1 MR-J4-_A_ section 18.3.1
Explanation of power supply system (except section 2.6 Power-on sequence)
Detailed explanation of signals MR-J4-_A_ section 3.6
Forced stop deceleration function MR-J4-_A_ section 3.7
Alarm occurrence timing chart MR-J4-_A_ section 3.8 MR-J4-_A_ section 18.3.8
Interface (except for section 2.5 Internal connection diagram)
Servo motor with an electromagnetic brake MR-J4-_A_ section 3.10
Grounding MR-J4-_A_ section 3.11 MR-J4-_A_ section 18.3.10
MR-J4-_A_-RJ 100 W
or more
MR-J4-_A_ section 3.3 MR-J4-_A_ section 18.3.2
Detailed explanation
MR-J4-03A6-RJ
MR-J4-_A_ section 3.9
2 - 2
Page 30
2. SIGNALS AND WIRING
r
www.kavrammuhendislik.com.tr

2.1 I/O signal connection example

2.1.1 MR-J4-_A_-RJ 100 W or more

(1) Point table method
POINT
Assign the following output devices to CN1-22, CN1-23, and CN1-25 pins with [Pr. PD23], [Pr. PD24], and [Pr. PD26]. CN1-22: CPO (Rough match) CN1-23: ZP (Home position return completion) CN1-25: MEND (Travel completion)
(Note 3, 5)
(Note 15)
(Note 5)
(Note 18, 19)
(Note 11) Analog override
(Note 8) Analog torque limit
(Note 9) MR Configurator2
Forced stop 2 Servo-on Operation mode selection 1 Forward rotation start Reverse rotation start Proximity dog Forward rotation stroke end Reverse rotation stroke end Point table No. selection 1 Point table No. selection 2 Point table No. selection 3 Point table No. selection 4
±10 V/0% to 200%
+10 V/maximum torque
Personal computer
+
24 V DC (Note 4, 14)
Upper limit setting
Upper limit setting
(Note 12) Short-circuit connector (Packed with the servo amplifier)
10 m or shorter
(Note 13)
Main circuit
power supply
2 m or shorter
(Note 10) USB cable (option)
EM2 SON MD0
ST1
ST2 DOG LSP LSN
DI0
DI1
DI2
DI3
DICOM
DICOM
OPC
P15R
VC
LG
TLA
SD
Servo amplifie
(Note 7)
CN1
(Note 7) CN1
42 15 16 17 18 45 43 44 19
41
10
35 20 21
12
1 2
28
Plate
27
Plate
(Note 7)
CN6
CN5
CN8
DOCOM
46
47 DOCOM
ALM
48
22 CPO
23 ZP
25 MEND
24 INP
49
RD
13
(Note 16)
14
(Note 16)
8LZ 9 LZR 4LA 5 LAR 6LB 7 LBR
34 LG 33 OP
SD
2 m or shorter
3 MO1 1LG 2 MO2
2 m or shorter
(Note 1)
24 V DC (Note 4, 14)
(Note 2)
RA1
RA2
RA3
RA4
RA5
RA6
10 m or shorter
Malfunction (Note 6)
Rough match
Home position return completion
Travel completion
In-position
Ready
Encoder Z-phase pulse (differential line driver)
Encoder A-phase pulse (differential line driver)
Encoder B-phase pulse (differential line driver)
Control common
Control common
Encoder Z-phase pulse (open-collector)
± 10 V DC ± 10 V DC
(Note 17)
Analog monitor 1
Analog monitor 2
2 - 3
Page 31
2. SIGNALS AND WIRING
A
_
r
www.kavrammuhendislik.com.tr
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal (marked ) of the servo amplifier to the
protective earth (PE) of the cabinet.
2. Connect the diode in the correct direction. If it is connected reversely, the servo amplifier will malfunction and will not output
signals, disabling EM2 (Forced stop 2) and other protective circuits.
3. The forced stop switch (normally closed contact) must be installed.
4. Supply 24 V DC ± 10% to interfaces from outside. The total current capacity is up to 500 mA. 500 mA is the value applicable
when all I/O signals are used. The current capacity can be decreased by reducing the number of I/O points. Refer to section
3.9.2 (1) of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual" that gives the current value necessary for the interface. A 24
V DC power supply can be used for both input signal and output signal.
5. When starting operation, always turn on EM2 (Forced stop 2), LSP (Forward rotation stroke end) and LSN (Reverse rotation
stroke end) (normally closed contact).
6.
7. The pins with the same signal name are connected in the servo amplifier.
8. TLA will be available when TL (External torque limit selection) is enabled with [Pr. PD04], [Pr. PD06], [Pr. PD08], [Pr. PD10],
9. Use SW1DNC-MRC2-_. (Refer to section 11.7 of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual".)
10. Controllers or parameter units can also be connected via the CN3 connector with the RS-422/RS-485 communication. Note
LM (Malfunction) turns on in normal alarm-free condition (normally closed contact).
[Pr. PD12], [Pr. PD14], [Pr. PD18], [Pr. PD20], [Pr. PD22], [Pr. PD44], and [Pr. PD46]. (Refer to section 3.6.1 (5) of "MR-J4-
A_(-RJ) Servo Amplifier Instruction Manual".)
that using the USB communication function (CN5 connector) prevents the RS-422/RS-485 communication function (CN3
connector) from being used, and vice versa. They cannot be used together.
RS-422/RS-485
compatible controller
Servo amplifie
MR-PRU03
or
parameter unit
PRU03
10BASE-T cable, etc. (EIA568-compliant)
11. Use an external power supply when inputting a negative voltage.
12. When not using the STO function, attach the short-circuit connector came with a servo amplifier.
13. Configure a circuit to turn off EM2 when the main circuit power is turned off to prevent an unexpected restart of the servo
amplifier.
14. This diagram shows sink I/O interface.
15. The device can be changed with [Pr. PD04], [Pr. PD06], [Pr. PD08], [Pr. PD10], [Pr. PD12], [Pr. PD14], [Pr. PD18], [Pr. PD20],
[Pr. PD22], [Pr. PD44], and [Pr. PD46].
16. These output devices are not assigned by default. Assign the output device with [Pr. PD47] as necessary.
17. These devices are recommended assignments. The device can be changed by [Pr. PD23] to [Pr. PD26], and [Pr. PD28].
18. DI2 and DI3 are assigned to the CN1-10 and CN1-35 pins by default. When connecting a manual pulse generator, change
them with [Pr. PD44] and [Pr. PD46]. Refer to section 9.1 for details of the manual pulse generator.
19. Supply + of 24 V DC to OPC (Power input for open-collector sink interface) when input devices are assigned to the CN1-10 pin
and the CN1-35 pin. They are not used with source input interface. For the positioning mode, input devices (DI2 and DI3) are
assigned by default.
CN3
2 - 4
Page 32
2. SIGNALS AND WIRING
r
www.kavrammuhendislik.com.tr
(2) Program method
POINT
Assign the following output devices to CN1-22, CN1-23, and CN1-25 pins with [Pr. PD23], [Pr. PD24], and [Pr. PD26]. CN1-22: CPO (Rough match) CN1-23: ZP (Home position return completion) CN1-25: MEND (Travel completion)
(Note 3, 5)
(Note 15)
(Note 5)
(Note 18, 19)
(Note 11) Analog override
(Note 8) Analog torque limit
(Note 9) MR Configurator2
Forced stop 2 Servo-on Operation mode selection 1 Forward rotation start Reverse rotation start Proximity dog Forward rotation stroke end Reverse rotation stroke end Program No. selection 1 Program No. selection 2 Program No. selection 3 Program No. selection 4
±10 V/0% to 200%
+10 V/maximum torque
Personal computer
+
24 V DC (Note 4, 14)
Upper limit setting
Upper limit setting
(Note 12) Short-circuit connector (Packed with the servo amplifier)
10 m or shorter
(Note 13)
Main circuit
power supply
2 m or shorter
(Note 10) USB cable (option)
EM2 SON MD0
ST1 ST2
DOG
LSP LSN
DI0
DI1
DI2
DI3
DICOM
DICOM
OPC
P15R
VC
LG
TLA
SD
Servo amplifie
(Note 7)
CN1
46
47 DOCOM
1 2
48
22 CPO
23 ZP
25 MEND
24 INP
49
13 14
34 LG 33 OP
Plate
(Note 7)
CN6
(Note 7) CN1
42 15 16 17 18 45 43 44 19
41
10
35 20 21
12
28
27
Plate
CN5
CN8
24 V DC (Note 4, 14)
DOCOM
ALM
RD
(Note 16)
(Note 16)
8LZ 9 LZR 4LA 5 LAR 6LB 7 LBR
SD
2 m or shorter
3 MO1 1LG 2 MO2
2 m or shorter
(Note 1)
(Note 2)
RA1
RA2
RA3
RA4
RA5
RA6
10 m or shorter
Control common
Encoder Z-phase pulse (open-collector)
Malfunction (Note 6)
Rough match
Home position return completion
Travel completion
In-position
Ready
Encoder Z-phase pulse (differential line driver)
Encoder A-phase pulse (differential line driver)
Encoder B-phase pulse (differential line driver)
Control common
Analog monitor 1
± 10 V DC ± 10 V DC
Analog monitor 2
(Note 17)
2 - 5
Page 33
2. SIGNALS AND WIRING
A
_
r
www.kavrammuhendislik.com.tr
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal (marked ) of the servo amplifier to the
protective earth (PE) of the cabinet.
2. Connect the diode in the correct direction. If it is connected reversely, the servo amplifier will malfunction and will not output
signals, disabling EM2 (Forced stop 2) and other protective circuits.
3. The forced stop switch (normally closed contact) must be installed.
4. Supply 24 V DC ± 10% to interfaces from outside. The total current capacity is up to 500 mA. 500 mA is the value applicable
when all I/O signals are used. The current capacity can be decreased by reducing the number of I/O points. Refer to section
3.9.2 (1) of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual" that gives the current value necessary for the interface. A 24
V DC power supply can be used for both input signal and output signal.
5. When starting operation, always turn on EM2 (Forced stop 2), LSP (Forward rotation stroke end) and LSN (Reverse rotation
stroke end) (normally closed contact).
6.
7. The pins with the same signal name are connected in the servo amplifier.
8. TLA will be available when TL (External torque limit selection) is enabled with [Pr. PD04], [Pr. PD06], [Pr. PD08], [Pr. PD10],
9. Use SW1DNC-MRC2-_. (Refer to section 11.7 of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual".)
10. Controllers or parameter units can also be connected via the CN3 connector with the RS-422/RS-485 communication. Note
LM (Malfunction) turns on in normal alarm-free condition (normally closed contact).
[Pr. PD12], [Pr. PD14], [Pr. PD18], [Pr. PD20], [Pr. PD22], [Pr. PD44], and [Pr. PD46]. (Refer to section 3.6.1 (5) of "MR-J4-
A_(-RJ) Servo Amplifier Instruction Manual".)
that using the USB communication function (CN5 connector) prevents the RS-422/RS-485 communication function (CN3
connector) from being used, and vice versa. They cannot be used together.
RS-422/RS-485
compatible controller
Servo amplifie
MR-PRU03
or
parameter unit
PRU03
10BASE-T cable, etc. (EIA568-compliant)
11. Use an external power supply when inputting a negative voltage.
12. When not using the STO function, attach the short-circuit connector came with a servo amplifier.
13. Configure a circuit to turn off EM2 when the main circuit power is turned off to prevent an unexpected restart of the servo
amplifier.
14. This diagram shows sink I/O interface.
15. The device can be changed with [Pr. PD04], [Pr. PD06], [Pr. PD08], [Pr. PD10], [Pr. PD12], [Pr. PD14], [Pr. PD18], [Pr. PD20],
[Pr. PD22], [Pr. PD44], and [Pr. PD46].
16. These output devices are not assigned by default. Assign the output device with [Pr. PD47] as necessary.
17. These devices are recommended assignments. The device can be changed by [Pr. PD23] to [Pr. PD26], and [Pr. PD28].
18. DI2 and DI3 are assigned to the CN1-10 and CN1-35 pins by default. When connecting a manual pulse generator, change
them with [Pr. PD44] and [Pr. PD46]. Refer to section 9.1 for details of the manual pulse generator.
19. Supply + of 24 V DC to OPC (Power input for open-collector sink interface) when input devices are assigned to the CN1-10 pin
and the CN1-35 pin. They are not used with source input interface. For the positioning mode, input devices (DI2 and DI3) are
assigned by default.
CN3
2 - 6
Page 34
2. SIGNALS AND WIRING
www.kavrammuhendislik.com.tr
(3) Indexer method
POINT
In the indexer method, assign the following input device to CN1-18 pin with [Pr. PD10]. CN1-18: MD1 (Operation mode selection 2) Assign the following output devices to CN1-22, CN1-23, and CN1-25 pins with [Pr. PD23], [Pr. PD24], and [Pr. PD26]. CN1-22: CPO (Rough match) CN1-23: ZP (Home position return completion) CN1-25: MEND (Travel completion)
(Note 3, 5)
(Note 14)
(Note 5)
(Note 17, 18)
Forced stop 2 Servo-on
Operation mode selection 1 Forward rotation start Operation mode selection 2
External limit/Rotation direction decision/ Automatic speed selection Forward rotation stroke end
Reverse rotation stroke end
Next station No. selection 1 Next station No. selection 2 Next station No. selection 3 Next station No. selection 4
(Note 8) Analog torque limit
+10 V/maximum torque
(Note 9) MR Configurator2
Personal computer
+
10 m or shorter
(Note 12)
Main circuit
power supply
24 V DC (Note 4, 13)
Upper limit setting
2 m or shorter
(Note 10) USB cable (option)
(Note 11) Short-circuit connector (Packed with the servo amplifier)
EM2 SON MD0
ST1
MD1
SIG LSP LSN
DI0
DI1
DI2
DI3
DICOM
DICOM
OPC
P15R
LG
TLA
SD
Servo amplifier
(Note 7)
CN1
46
47 DOCOM
42 15 16 17 18 45 43 44 19
41
10
35 20 21
12
1
28
27
48
22 CPO
23 ZP
25 MEND
24 INP
49
13 14
8LZ 9 LZR 4LA 5 LAR 6LB 7 LBR
34 LG 33 OP
Plate
(Note 7)
CN6
3 MO1 1LG 2 MO2
(Note 7) CN1
Plate
CN5
CN8
24 V DC (Note 4, 13)
DOCOM
ALM
RD
(Note 15)
(Note 15)
10 m or shorter
SD
2 m or shorter
2 m or shorter
(Note 1)
(Note 2)
RA1
RA2
RA3
RA4
RA5
RA6
Control common Encoder Z-phase pulse (open-collector)
± 10 V DC ± 10 V DC
Malfunction (Note 6)
Rough match
Home position return completion
Travel completion
In-position
Ready
Encoder Z-phase pulse (
(differential line driver)
Encoder A-phase pulse (
(differential line driver)
Encoder B-phase pulse (differential line driver)
Control common
Analog monitor 1
Analog monitor 2
(Note 16)
2 - 7
Page 35
2. SIGNALS AND WIRING
A
_
r
www.kavrammuhendislik.com.tr
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal (marked ) of the servo amplifier to the
protective earth (PE) of the cabinet.
2. Connect the diode in the correct direction. If it is connected reversely, the servo amplifier will malfunction and will not output
signals, disabling EM2 (Forced stop 2) and other protective circuits.
3. The forced stop switch (normally closed contact) must be installed.
4. Supply 24 V DC ± 10% to interfaces from outside. The total current capacity is up to 500 mA. 500 mA is the value applicable
when all I/O signals are used. The current capacity can be decreased by reducing the number of I/O points. Refer to section
3.9.2 (1) of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual" that gives the current value necessary for the interface. A 24
V DC power supply can be used for both input signal and output signal.
5. When starting operation, always turn on EM2 (Forced stop 2), LSP (Forward rotation stroke end) and LSN (Reverse rotation
stroke end) (normally closed contact).
6.
7. The pins with the same signal name are connected in the servo amplifier.
8. TLA will be available when TL (External torque limit selection) is enabled with [Pr. PD04], [Pr. PD06], [Pr. PD08], [Pr. PD10],
9. Use SW1DNC-MRC2-_. (Refer to section 11.7 of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual".)
10. Controllers or parameter units can also be connected via the CN3 connector with the RS-422/RS-485 communication.
LM (Malfunction) turns on in normal alarm-free condition (normally closed contact).
[Pr. PD12], [Pr. PD14], [Pr. PD18], [Pr. PD20], [Pr. PD22], [Pr. PD44], and [Pr. PD46]. (Refer to section 3.6.1 (5) of "MR-J4-
A_(-RJ) Servo Amplifier Instruction Manual".)
Note that using the USB communication function (CN5 connector) prevents the RS-422/RS-485 communication function (CN3
connector) from being used, and vice versa. They cannot be used together.
RS-422/RS-485
compatible controller
Servo amplifie
MR-PRU03
or
parameter unit
PRU03
10BASE-T cable, etc. (EIA568-compliant)
11. When not using the STO function, attach the short-circuit connector came with a servo amplifier.
12. Configure a circuit to turn off EM2 when the main circuit power is turned off to prevent an unexpected restart of the servo
amplifier.
13. This diagram shows sink I/O interface.
14. The signals can be changed with [Pr. PD04], [Pr. PD06], [Pr. PD08], [Pr. PD10], [Pr. PD12], [Pr. PD14], [Pr. PD18], [Pr. PD20],
[Pr. PD22], [Pr. PD44], and [Pr. PD46].
15. These output devices are not assigned by default. Assign the output device with [Pr. PD47] as necessary.
16. These devices are recommended assignments. The device can be changed by [Pr. PD23] to [Pr. PD26], and [Pr. PD28].
17. DI2 and DI3 are assigned to the CN1-10 and CN1-35 pins by default. When connecting a manual pulse generator, change
them with [Pr. PD44] and [Pr. PD46]. Refer to section 9.1 for details of the manual pulse generator.
18. Supply + of 24 V DC to OPC (Power input for open-collector sink interface) when input devices are assigned to the CN1-10 pin
and the CN1-35 pin. They are not used with source input interface. For the positioning mode, input devices (DI2 and DI3) are
assigned by default.
CN3
2 - 8
Page 36
2. SIGNALS AND WIRING
r
www.kavrammuhendislik.com.tr

2.1.2 MR-J4-03A6-RJ

(1) Point table method
POINT
Assign the following output devices to CN1-22, CN1-23, and CN1-25 pins with [Pr. PD23], [Pr. PD24], and [Pr. PD26]. CN1-22: CPO (Rough match) CN1-23: ZP (Home position return completion) CN1-25: MEND (Travel completion)
(Note 3, 5)
(Note 14)
(Note 5)
(Note 16, 17)
(Note 11) Analog override
±10 V/0% to 200%
(Note 8) Analog torque limit
+10 V/maximum torque
(Note 9) MR Configurator2
Forced stop 2 Servo-on Operation mode selection 1 Forward rotation start Reverse rotation start Proximity dog Forward rotation stroke end Reverse rotation stroke end Point table No. selection 1 Point table No. selection 2 Point table No. selection 3 Point table No. selection 4
24 V DC (Note 4, 13)
Upper limit setting
Upper limit setting
Personal computer
+
10 m or less
(Note 12) Main circuit power supply
DICOM
DICOM
P15R
2 m or less
(Note 10)
USB cable
(option)
EM2 SON MD0
ST1 ST2
DOG
LSP
LSN
DI0
DI1
DI2
DI3
OPC
VC
LG
TLA
SD
Servo amplifie
(Note 7)
CN1
46
47 DOCOM
(Note 7)
CN1
Plate
CN3
48
22 CPO
42 15
23 ZP
16
25 MEND
17 18
24 INP
45
49
43 44 19
41
10
35 20 21
12
1 2
34 LG
28
33 OP
Plate
27
(Note 7)
CN1 26 MO1 28 LG 29 MO2
CNP1
DOCOM
ALM
RD
8LZ 9 LZR 4LA 5 LAR 6LB 7 LBR
SD
2 m or less
2 m or less
6
24 V DC (Note 4, 13)
(Note 2)
RA1
RA2
RA3
RA4
RA5
RA6
10 m or less
Control common
Encoder Z-phase pulse (open-collector)
5 V DC ± 4 V DC 5 V DC ± 4 V DC
(Note 1)
Malfunction (Note 6)
Rough match
Home position return completion
Travel completion
In-position
Ready
Encoder Z-phase pulse (differential line driver)
Encoder A-phase pulse (differential line driver)
Encoder B-phase pulse (differential line driver)
Control common
Analog monitor 1
Analog monitor 2
(Note 15)
2 - 9
Page 37
2. SIGNALS AND WIRING
A
_
www.kavrammuhendislik.com.tr
Note 1. To prevent an electric shock, always connect the CNP1 noiseless grounding terminal ( marked) of the servo amplifier to the
grounding terminal of the cabinet.
2. Connect the diode in the correct direction. If it is connected reversely, the servo amplifier will malfunction and will not output
signals, disabling EM2 (Forced stop 2) and other protective circuits.
3. The forced stop switch (normally closed contact) must be installed.
4. Supply 24 V DC ± 10% to interfaces from outside. The total current capacity of these power supplies must be 300 mA or lower.
300 mA is the value applicable when all I/O signals are used. The current capacity can be decreased by reducing the number
of I/O points. Refer to section 3.9.2 (1) of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual" that gives the current value
necessary for the interface. A 24 V DC power supply can be used for both input signal and output signal. For 24 V DC power
for I/O signal, use power other than 24 V DC power of servo amplifier control circuit power supply.
5. When starting operation, always turn on EM2 (Forced stop 2), LSP (Forward rotation stroke end) and LSN (Reverse rotation
stroke end). (Normally closed contact)
6.
7. The pins with the same signal name are connected in the servo amplifier.
8. TLA will be available when TL (External torque limit selection) is enabled with [Pr. PD04], [Pr. PD06], [Pr. PD08], [Pr. PD10],
9. Use SW1DNC MRC2-_. (Refer to "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual" section 11.7.)
10. The USB communication function and RS-422 communication function are mutually exclusive. They cannot be used together.
11. Use an external power supply when inputting a negative voltage.
12. Configure a circuit to turn off EM2 when the main circuit power is turned off to prevent an unexpected restart of the servo
13. This diagram shows sink I/O interface.
14. The devices can be changed with [Pr. PD04], [Pr. PD06], [Pr. PD08], [Pr. PD10], [Pr. PD12], [Pr. PD14], [Pr. PD18], [Pr.
15. Recommended device assignments are shown. The device can be changed by [Pr. PD23] to [Pr. PD26], and [Pr. PD28].
16. DI2 and DI3 are assigned to the CN1-10 and CN1-35 pins by default. When connecting a manual pulse generator, change
17. Supply + of 24 DC V to OPC (Power input for open-collector sink interface) when input devices are assigned to the CN1-10 pin
LM (Malfunction) turns on in normal alarm-free condition. (Normally closed contact)
[Pr. PD12], [Pr. PD14], [Pr. PD18], [Pr. PD20], [Pr. PD22], [Pr. PD44], and [Pr. PD46]. (Refer to section 3.6.1 (5) of "MR-J4-
A_(-RJ) Servo Amplifier Instruction Manual".)
amplifier.
PD20], [Pr. PD22], [Pr. PD44], and [Pr. PD46].
them with [Pr. PD44] and [Pr. PD46]. Refer to section 9.1 for details of the manual pulse generator.
and the CN1-35 pin. They cannot be used with source input interface. For the positioning mode, input devices (DI2 and DI3)
are assigned by default.
2 - 10
Page 38
2. SIGNALS AND WIRING
r
www.kavrammuhendislik.com.tr
(2) Program method
POINT
Assign the following output devices to CN1-22, CN1-23, and CN1-25 pins with [Pr. PD23], [Pr. PD24], and [Pr. PD26]. CN1-22: CPO (Rough match) CN1-23: ZP (Home position return completion) CN1-25: MEND (Travel completion)
(Note 3, 5)
(Note 14)
(Note 5)
(Note 16, 17)
(Note 11) Analog override
(Note 8) Analog torque limit
(Note 9) MR Configurator2
Forced stop 2 Servo-on Operation mode selection 1 Forward rotation start Reverse rotation start Proximity dog Forward rotation stroke end Reverse rotation stroke end Program No. selection 1 Program No. selection 2 Program No. selection 3 Program No. selection 4
±10 V/0% to 200%
+10 V/maximum torque
Personal computer
+
24 V DC (Note 4, 13)
Upper limit setting
Upper limit setting
10 m or less
(Note 12) Main circuit power supply
DICOM
DICOM
P15R
2 m or less
(Note 10)
USB cable
(option)
EM2 SON MD0
ST1 ST2
DOG
LSP LSN
DI0
DI1
DI2
DI3
OPC
VC
LG
TLA
SD
Servo amplifie
(Note 7)
CN1
46
47 DOCOM
42 15 16 17 18 45 43 44 19
41
10
35 20 21
12
28
27
1 2
48
22 CPO
23 ZP
25 MEND
24 INP
49
8LZ 9 LZR 4LA 5 LAR 6LB 7 LBR
34 LG 33 OP
Plate
(Note 7)
CN1
26 MO1 28 LG 29 MO2
CNP1
6
(Note 7) CN1
Plate
CN3
DOCOM
ALM
RD
SD
2 m or less
2 m or less
(Note 1)
24 V DC (Note 4, 13)
(Note 2)
RA1
RA2
RA3
RA4
RA5
RA6
10 m or less
Malfunction (Note 6)
Rough match
Home position return completion
Travel completion
In-position
Ready
Encoder Z-phase pulse (differential line driver)
Encoder A-phase pulse (differential line driver)
Encoder B-phase pulse (differential line driver)
Control common
Control common
Encoder Z-phase pulse (open-collector)
5 V DC ± 4 V DC 5 V DC ± 4 V DC
(Note 15)
Analog monitor 1
Analog monitor 2
2 - 11
Page 39
2. SIGNALS AND WIRING
A
_
www.kavrammuhendislik.com.tr
Note 1. To prevent an electric shock, always connect the CNP1 noiseless grounding terminal ( marked) to the grounding terminal of
the cabinet.
2. Connect the diode in the correct direction. If it is connected reversely, the servo amplifier will malfunction and will not output
signals, disabling EM2 (Forced stop 2) and other protective circuits.
3. The forced stop switch (normally closed contact) must be installed.
4. Supply 24 V DC ± 10% to interfaces from outside. The total current capacity of these power supplies must be 300 mA or lower.
300 mA is the value applicable when all I/O signals are used. The current capacity can be decreased by reducing the number
of I/O points. Refer to section 3.9.2 (1) of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual" that gives the current value
necessary for the interface. A 24 V DC power supply can be used for both input signal and output signal. For 24 V DC power
for I/O signal, use power other than 24 V DC power of servo amplifier control circuit power supply.
5. When starting operation, always turn on EM2 (Forced stop 2), LSP (Forward rotation stroke end) and LSN (Reverse rotation
stroke end). (Normally closed contact)
6.
7. The pins with the same signal name are connected in the servo amplifier.
8. TLA will be available when TL (External torque limit selection) is enabled with [Pr. PD04], [Pr. PD06], [Pr. PD08], [Pr. PD10],
9. Use SW1DNC MRC2-_. (Refer to "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual" section 11.7.)
10. The USB communication function and RS-422 communication function are mutually exclusive. They cannot be used together.
11. Use an external power supply when inputting a negative voltage.
12. Configure a circuit to turn off EM2 when the main circuit power is turned off to prevent an unexpected restart of the servo
13. This diagram shows sink I/O interface.
14. The devices can be changed with [Pr. PD04], [Pr. PD06], [Pr. PD08], [Pr. PD10], [Pr. PD12], [Pr. PD14], [Pr. PD18], [Pr.
15. Recommended device assignments are shown. The device can be changed by [Pr. PD23] to [Pr. PD26], and [Pr. PD28].
16. DI2 and DI3 are assigned to the CN1-10 and CN1-35 pins by default. When connecting a manual pulse generator, change
17. Supply + of 24 DC V to OPC (Power input for open-collector sink interface) when input devices are assigned to the CN1-10 pin
LM (Malfunction) turns on in normal alarm-free condition. (Normally closed contact)
[Pr. PD12], [Pr. PD14], [Pr. PD18], [Pr. PD20], [Pr. PD22], [Pr. PD44], and [Pr. PD46]. (Refer to section 3.6.1 (5) of "MR-J4-
A_(-RJ) Servo Amplifier Instruction Manual".)
amplifier.
PD20], [Pr. PD22], [Pr. PD44], and [Pr. PD46].
them with [Pr. PD44] and [Pr. PD46]. Refer to section 9.1 for details of the manual pulse generator.
and the CN1-35 pin. They cannot be used with source input interface. For the positioning mode, input devices (DI2 and DI3)
are assigned by default.
2 - 12
Page 40
2. SIGNALS AND WIRING
r
www.kavrammuhendislik.com.tr
(3) Indexer method
POINT
In the indexer method, assign the following input device to CN1-18 pin with [Pr. PD10]. CN1-18: MD1 (Operation mode selection 2) Assign the following output devices to CN1-22, CN1-23, and CN1-25 pins with [Pr. PD23], [Pr. PD24], and [Pr. PD26]. CN1-22: CPO (Rough match) CN1-23: ZP (Home position return completion) CN1-25: MEND (Travel completion)
(Note 3, 5)
(Note 13)
(Note 5)
(Note 15, 16)
Forced stop 2 Servo-on Operation mode selection 1 Forward rotation start
Operation mode selection 2 External limit/Rotation direction decision/ Automatic speed selection Forward rotation stroke end
Reverse rotation stroke end Next station No. selection 1
Next station No. selection 2 Next station No. selection 3 Next station No. selection 4
(Note 8) Analog torque limit
+10 V/maximum torque
(Note 9) MR Configurator2
+
Upper limit setting
Personal computer
10 m or less
(Note 11) Main circuit power supply
24 V DC (Note 4, 12)
2 m or less
(Note 10)
USB cable
(option)
EM2 SON MD0 ST1 MD1
SIG LSP LSN
DI0
DI1
DI2
DI3
DICOM
DICOM
OPC
P15R
LG
TLA
SD
Servo amplifie
(Note 7)
CN1
46
47 DOCOM
42 15 16 17 18 45 43 44 19
41
10
35 20 21
12
28
27
1
48
22 CPO
23 ZP
25 MEND
24 INP
49
34 LG 33 OP
Plate
(Note 7)
CN1
26 MO1 28 LG 29 MO2
CNP1
(Note 7) CN1
Plate
CN3
DOCOM
ALM
RD
8LZ 9 LZR 4LA 5 LAR 6LB 7 LBR
SD
2 m or less
2 m or less
6
24 V DC (Note 4, 12)
(Note 2)
RA1
RA2
RA3
RA4
RA5
RA6
10 m or less
Control common Encoder Z-phase pulse (open-collector)
5 V DC ± 4 V DC 5 V DC ± 4 V DC
(Note 1)
Malfunction (Note 6)
Rough match
Home position return completion
Travel completion
In-position
Ready
Encoder Z-phase pulse (differential line driver)
Encoder A-phase pulse (differential line driver)
Encoder B-phase pulse (differential line driver)
Control common
Analog monitor 1
Analog monitor 2
(Note 14)
2 - 13
Page 41
2. SIGNALS AND WIRING
A
_
www.kavrammuhendislik.com.tr
Note 1. To prevent an electric shock, always connect the CNP1 noiseless grounding terminal ( marked) to the grounding terminal of
the cabinet.
2. Connect the diode in the correct direction. If it is connected reversely, the servo amplifier will malfunction and will not output
signals, disabling EM2 (Forced stop 2) and other protective circuits.
3. The forced stop switch (normally closed contact) must be installed.
4. Supply 24 V DC ± 10% to interfaces from outside. The total current capacity of these power supplies must be 300 mA or lower.
300 mA is the value applicable when all I/O signals are used. The current capacity can be decreased by reducing the number
of I/O points. Refer to section 3.9.2 (1) of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual" that gives the current value
necessary for the interface. A 24 V DC power supply can be used for both input signal and output signal. For 24 V DC power
for I/O signal, use power other than 24 V DC power of servo amplifier control circuit power supply.
5. When starting operation, always turn on EM2 (Forced stop 2), LSP (Forward rotation stroke end) and LSN (Reverse rotation
stroke end). (Normally closed contact)
6.
7. The pins with the same signal name are connected in the servo amplifier.
8. TLA will be available when TL (External torque limit selection) is enabled with [Pr. PD04], [Pr. PD06], [Pr. PD08], [Pr. PD10],
9. Use SW1DNC MRC2-_. (Refer to "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual" section 11.7.)
10. The USB communication function and RS-422 communication function are mutually exclusive. They cannot be used together.
11. Configure a circuit to turn off EM2 when the main circuit power is turned off to prevent an unexpected restart of the servo
12. This diagram shows sink I/O interface.
13. The devices can be changed with [Pr. PD04], [Pr. PD06], [Pr. PD08], [Pr. PD10], [Pr. PD12], [Pr. PD14], [Pr. PD18], [Pr.
14. Recommended device assignments are shown. The device can be changed by [Pr. PD23] to [Pr. PD26], and [Pr. PD28].
15. DI2 and DI3 are assigned to the CN1-10 and CN1-35 pins by default. When connecting a manual pulse generator, change
16. Supply + of 24 DC V to OPC (Power input for open-collector sink interface) when input devices are assigned to the CN1-10 pin
LM (Malfunction) turns on in normal alarm-free condition. (Normally closed contact)
[Pr. PD12], [Pr. PD14], [Pr. PD18], [Pr. PD20], [Pr. PD22], [Pr. PD44], and [Pr. PD46]. (Refer to section 3.6.1 (5) of "MR-J4-
A_(-RJ) Servo Amplifier Instruction Manual".)
amplifier.
PD20], [Pr. PD22], [Pr. PD44], and [Pr. PD46].
them with [Pr. PD44] and [Pr. PD46]. Refer to section 9.1 for details of the manual pulse generator.
and the CN1-35 pin. They cannot be used with source input interface. For the positioning mode, input devices (DI2 and DI3)
are assigned by default.
2 - 14
Page 42
2. SIGNALS AND WIRING
www.kavrammuhendislik.com.tr

2.2 Connectors and pin assignment

POINT
The pin assignment of the connectors is as viewed from the cable connector wiring section. For the STO I/O signal connector (CN8), refer to chapter 13 of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual". For the CN1 connector, securely connect the external conductor of the shielded cable to the ground plate and fix it to the connector shell.
Screw
Cable
Screw
Ground plate
PP (CN1-10 pin) /NP (CN1-35 pin) and PP2 (CN1-37 pin) /NP2 (CN1-38 pin) are exclusive. They cannot be used together.
2 - 15
Page 43
2. SIGNALS AND WIRING
www.kavrammuhendislik.com.tr
(1) MR-J4-_A_-RJ 100 W or more
The servo amplifier front view shown is that of the MR-J4-20A-RJ or less. For other views of servo amplifiers, connector arrangements, and details, refer to chapter 9 of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual".
CN5 (USB connector) Refer to "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual" section 11.7.
CN6
3
MO1
2
MO2
1
LG
CN8 For the STO I/O signal connector, refer to chapter 13.2 of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual".
(Note 2) CN2
2
LG 8
1
P5
4
MRR
3
MR
6
THM2
5
THM1
MXR
7
MX
10
BAT
9
This is a connector of 3M.
(Note 1, 2) CN2L
(using serial encoder)
2
LG 8
1
P5
4
MRR2
3
MR2
6
5
MXR2
7
MX2
10
BAT
9
(Note 1, 2) CN2L
(using A/B/Z-phase pulse encoder)
2
LG 8
1
P5
4
PAR
3
6
PBR
5
PB
PA
PZR
PZ
10
PSEL
9
7
CN3 (RS-422/RS485 connector) Refer to "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual" chapter 14.
CN4 (battery connector) Refer to "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual" section 11.8.
The frame of the CN1 connector is connected to the PE (grounding) terminal in the servo amplifier.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25 50
CN1
27
29
31
33
35
37
39
41
43
45
47
49
26
28
30
32
34
36
38
40
42
44
46
48
Note 1. This CN2L is a connector of 3M.
2. For the connection with external encoders, refer to table 1.1 of "MR-J4-_A_(-RJ) Servo Amplifier Instruction
The device assignment of CN1 connector pins changes depending on the control mode. For the pins which are given parameters in the related parameter column, their devices will be changed using those parameters.
When using any other connector, refer to each servo motor instruction manual.
Manual".
2 - 16
Page 44
2. SIGNALS AND WIRING
www.kavrammuhendislik.com.tr
Pin No.
1 P15R P15R P15R 2 I VC VC 3 LG LG LG 4 O LA LA LA 5 O LAR LAR LAR 6 O LB LB LB 7 O LBR LBR LBR 8 O LZ LZ LZ
9 O LZR LZR LZR 10 (Note 8) I (Note 10) (Note 10) (Note 10) PD44 (Note 9) 11 I PG PG PG 12 OPC OPC OPC 13 O (Note 4) (Note 4) (Note 4) PD47 14 O (Note 4) (Note 4) (Note 4) PD47 15 I SON SON SON PD04 16 I MD0 MD0 MD0 PD06 17 I ST1 ST1 ST1 PD08
18 I ST2 ST2
19 I DI0 DI0 DI0 PD12 20 DICOM DICOM DICOM 21 DICOM DICOM DICOM
22 O
23 O (Note 6) ZP (Note 6) ZP (Note 6) ZP PD24
24 or
less
25 O
26
27 I
28 LG LG LG 29 30 LG LG LG 31 32 33 O OP OP OP 34 LG LG LG 35 (Note 8) I (Note 10) (Note 10) (Note 10) PD46 (Note 9) 36 I NG NG NG 37
(Note 12)
38
(Note 12)
39 40 41 I DI1 DI1 DI1 PD14 42 I EM2 EM2 EM2 43 I LSP LSP LSP PD18 44 I LSN LSN LSN PD20 45 I DOG DOG SIG PD22 46 DOCOM DOCOM DOCOM 47 DOCOM DOCOM DOCOM 48 O ALM ALM ALM 49 O RD RD RD PD28 50
(Note 1)
I/O
O INP INP INP PD25
I (Note 11) (Note 11) (Note 11) PD44 (Note 9)
I (Note 11) (Note 11) (Note 11) PD46 (Note 9)
(Note 2) I/O signals in control modes
CP/BCD
(Note 7)
(Note 6)
CPO
(Note 6)
MEND
(Note 3)
TLA
CL PS
(Note 5)
MD1
(Note 6)
CPO
(Note 6)
MEND
(Note 3)
TLA
(Note 6)
CPO
(Note 6)
MEND
(Note 3)
TLA
Related parameter
PD10
PD23
PD26
2 - 17
Page 45
2. SIGNALS AND WIRING
A
A
A
www.kavrammuhendislik.com.tr
Note 1. I: input signal, O: output signal
2. CP: Positioning mode (point table method)
3. TLA will be available when TL (External torque limit selection) is enabled with [Pr.
4.
5. In the indexer method, assign the following input device to CN1-18 pin with [Pr. PD10].
6.
7. For BCD input, refer to chapter 12.
8. Supply + of 24 V DC to OPC (power input for open-collector sink interface) when using
9. This parameter is available with servo amplifiers with software version B7 or later.
10. This signal is used with sink interface. Input devices are not assigned by default. Assign
11. This signal is used with source interface. Input devices are not assigned by default.
12. These pins are available with servo amplifiers having software version B7 or later, and
BCD: Positioning mode (point table method in the BCD input positioning operation)
This method is available only when the MR-D01 unit is connected. Refer to
chapter 12 for details.
CL: Positioning mode (program method)
PS: Positioning mode (indexer method)
PD04], [Pr. PD06], [Pr. PD08], [Pr. PD10], [Pr. PD12], [Pr. PD14], [Pr. PD18], [Pr.
PD20], [Pr. PD22], [Pr. PD44], and [Pr. PD46].
ssign any device with [Pr. PD47].
CN1-18: MD1 (Operation mode selection 2)
ssign the following output devices to CN1-22, CN1-23, and CN1-25 pins with [Pr.
PD23], [Pr. PD24], and [Pr. PD26].
CN1-22: CPO (Rough match)
CN1-23: ZP (Home position return completion)
CN1-25: MEND (Travel completion)
the CN1-10 pin and CN1-35 pin for DI.
the input devices with [Pr. PD44] and [Pr. PD46] as necessary. In addition, supply + of
24 DC V to the CN1-12 pin of OPC (Power input for open-collector sink interface). This
is available with servo amplifiers with software version B7 or later.
ssign the input devices with [Pr. PD44] and [Pr. PD46] as necessary.
manufactured in January 2015 or later.
2 - 18
Page 46
2. SIGNALS AND WIRING
www.kavrammuhendislik.com.tr
(2) MR-J4-03A6-RJ
For the views of servo amplifiers, connector arrangements, and details, refer to section 18.6 of "MR-J4­_A_(-RJ) Servo Amplifier Instruction Manual".
CN1
CN3 (USB connector)
1A
MR
2A
3A
4A P5 5A
SHD
CN2
Refer to "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual" section 11.7.
1B
MRR
2B
3B
4B LG 5B
BAT
CN4 (Battery connector) Refer to "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual" section 11.8.
The frame of the CN1 connector is connected to the noiseless grounding terminal in the servo amplifier.
50
48
46
44
42
40
38
36
34
32
30
28
26
49
47
45
43
41
39
37
35
33
31
29
27
25
23
21
19
17
15
13
11
24
22
20
18
16
14
12
10
9
8
7
6
5
4
3
2
1
2 - 19
Page 47
2. SIGNALS AND WIRING
www.kavrammuhendislik.com.tr
The device assignment of the CN1 connector pins changes depending on the control mode. For the pins which are given parameters in the related parameter column, their devices can be changed using those parameters.
Pin No.
(Note 1)
I/O
1 P15R P15R P15R
2 I VC VC
3 LG LG LG
4 O LA LA LA
5 O LAR LAR LAR
6 O LB LB LB
7 O LBR LBR LBR
8 O LZ LZ LZ
9 O LZR LZR LZR
10 (Note 6) I (Note 8) (Note 8) (Note 8) PD44 (Note 7)
11 I PG PG PG
12 OPC OPC OPC
13 O SDP SDP SDP
14 O SDN SDN SDN
15 I SON SON SON PD04
16 I MD0 MD0 MD0 PD06
17 I ST1 ST1 ST1 PD08
18 I ST2 ST2 (Note 4) MD1 PD10
19 I DI0 DI0 DI0 PD12
20 DICOM DICOM DICOM
21 DICOM DICOM DICOM
22 O
23 O (Note 5) ZP (Note 5) ZP (Note 5) ZP PD24
24 O INP INP INP PD25
25 O
26 O MO1 MO1 MO1 PC14
27 I (Note 3) TLA (Note 3) TLA (Note 3) TLA
28 LG LG LG
29 O MO2 MO2 MO2 PC15
30 LG LG LG
31 I TRE TRE TRE
32
33 O OP OP OP
34 LG LG LG
35 (Note 6) I (Note 8) (Note 8) (Note 8) PD46 (Note 7)
36 I NG NG NG
37 I (Note 9) (Note 9) (Note 9) PD44 (Note 7)
38 I (Note 9) (Note 9) (Note 9) PD46 (Note 7)
39 I RDP RDP RDP
40 I RDN RDN RDN
41 I DI1 DI1 DI1 PD14
42 I EM2 EM2 EM2
43 I LSP LSP LSP PD18
44 I LSN LSN LSN PD20
45 I DOG DOG SIG PD22
46 DOCOM DOCOM DOCOM
47 DOCOM DOCOM DOCOM
48 O ALM ALM ALM
49 O RD RD RD PD28
50
(Note 2) I/O signals in control modes
CP CL PS
(Note 5)
CPO
(Note 5)
MEND
(Note 5)
CPO
(Note 5)
MEND
(Note 5)
CPO
(Note 5)
MEND
Related parameter
PD23
PD26
2 - 20
Page 48
2. SIGNALS AND WIRING
A
www.kavrammuhendislik.com.tr
Note 1. I: input signal, O: output signal
2. CP: Positioning mode (point table method)
3. TLA will be available when TL (External torque limit selection) is enabled with [Pr.
4. In the indexer method, assign the following input device to CN1-18 pin with [Pr. PD10].
5.
6. Supply + of 24 V DC to OPC (power input for open-collector sink interface) when using
7. This is available with servo amplifiers with software version B7 or later.
8. This is used with sink interface. Input devices are not assigned by default. Assign the
9. This is used with source interface. Input devices are not assigned by default. Assign the
CL: Positioning mode (program method)
PS: Positioning mode (indexer method)
PD04], [Pr. PD06], [Pr. PD08], [Pr. PD10], [Pr. PD12], [Pr. PD14], [Pr. PD18], [Pr.
PD20], [Pr. PD22], [Pr. PD44], and [Pr. PD46].
CN1-18: MD1 (Operation mode selection 2)
ssign the following output devices to CN1-22, CN1-23, and CN1-25 pins with [Pr.
PD23], [Pr. PD24], and [Pr. PD26].
CN1-22: CPO (Rough match)
CN1-23: ZP (Home position return completion)
CN1-25: MEND (Travel completion)
the CN1-10 and CN1-35 pins for DI.
input devices with [Pr. PD44] and [Pr. PD46] as necessary. In addition, supply + of 24
DC V to the CN1-12 pin of OPC (Power input for open-collector sink interface).
input devices with [Pr. PD44] and [Pr. PD46] as necessary.
2 - 21
Page 49
2. SIGNALS AND WIRING
www.kavrammuhendislik.com.tr

2.3 Signal (device) explanations

The pin numbers in the connector pin No. column are those in the initial status. For the I/O interfaces (symbols in I/O division column in the table), refer to section 3.9.2 of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual". The symbols in the control mode field of the table show the followings. CP: Positioning mode (point table method) BCD: Positioning mode (point table method in the BCD input positioning operation)
This method is available only when the MR-D01 unit is connected. Refer to chapter 12 for details. CL: Positioning mode (program method) PS: Positioning mode (indexer method) "
" and " " of the table show the followings. : Usable device by default. : Usable device by setting the following parameters.
[Pr. PD04], [Pr. PD06], [Pr. PD08], [Pr. PD10], [Pr. PD12], [Pr. PD14], [Pr. PD18], [Pr. PD20], [Pr. PD22] to [Pr. PD26], [Pr. PD28], [Pr. PD44], [Pr. PD46], and [Pr. PD47]
(1) I/O device
(a) Input device
Device Symbol
Connector
pin No.
Function and application
division
I/O
Control
mode
CL
PS
Forced stop 2 EM2 CN1-42 Turn off EM2 (open between commons) to decelerate the servo motor to a
stop with commands. Turn EM2 on (short between commons) in the forced stop state to reset
that state. The following shows the setting of [Pr. PA04].
[Pr. PA04]
setting
EM2 or EM1 is off Alarm occurred
0 _ _ _ EM1
2 _ _ _ EM2
EM2 and EM1 are mutually exclusive.
Forced stop 1 EM1 (CN1-42) When using EM1, set [Pr. PA04] to "0 _ _ _" to enable EM1.
When EM1 is turned off (open between commons), the base circuit shuts off, and the dynamic brake operates to decelerate the servo motor to a stop.
Turn EM1 on (short between commons) in the forced stop state to reset that state.
Servo-on SON CN1-15 Turn SON on to power on the base circuit and make the servo amplifier
ready to operate. (servo-on status) Turn it off to shut off the base circuit and coast the servo motor. Set "_ _ _ 4" in [Pr. PD01] to switch this signal on (keep terminals
connected) automatically in the servo amplifier.
Reset RES Turn on RES for more than 50 ms to reset the alarm.
Some alarms cannot be deactivated by RES (Reset). Refer to chapter 8. Turning RES on in an alarm-free status shuts off the base circuit. The base
circuit is not shut off when " _ _ 1 _ " is set in [Pr. PD30]. This device is not designed to make a stop. Do not turn it on during
operation.
EM2/EM1
MBR (Electromagnetic brake interlock) turns off without the forced stop deceleration.
MBR (Electromagnetic brake interlock) turns off after the forced stop deceleration.
Deceleration method
MBR (Electromagnetic brake interlock) turns off without the forced stop deceleration.
MBR (Electromagnetic brake interlock) turns off after the forced stop deceleration.
CP/BCD
DI-1
DI-1
DI-1
DI-1
2 - 22
Page 50
2. SIGNALS AND WIRING
www.kavrammuhendislik.com.tr
Device Symbol
Forward rotation stroke end
Reverse rotation stroke end
External torque limit selection
Internal torque limit selection
Connector
pin No.
LSP CN1-43 To start operation, turn on LSP and LSN. Turn it off to bring the motor to a
sudden stop and make it servo-locked. Setting [Pr. PD30] to " _ _ _ 1" will enable "Slow stop (home position
erased)".
LSN CN1-44 (Note) Input device Operation
1 1
0 1
1 0
0 0
Note. 0: Off
The stop method can be changed with [Pr. PD30]. Set [Pr. PD01] as indicated below to switch on the signals (keep terminals
connected) automatically in the servo amplifier.
LSP LSN
When LSP or LSN is turned off, [AL. 99 Stroke limit warning] occurs, and WNG (Warning) turns on. When using WNG, enable it by setting [Pr. PD23] to [Pr. PD26], [Pr. PD28], and [Pr. PD47].
However, [Pr. PD47] is not available with MR-J4-03A6-RJ servo amplifiers.
TL Turning off TL will enable [Pr. PA11 Forward torque limit] and [Pr. PA12
Reverse torque limit], and turning on it will enable TLA (Analog torque limit). For details, refer to section 3.6.1 (5) of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual".
For the indexer method, [Pr. PC35 Internal torque limit 2] will be enabled automatically depending on operation status. Refer to each timing chart in section 6.2 and section 6.4.5.
TL1 To select [Pr. PC35 Internal torque limit 2/internal thrust limit 2], enable
TL1 with [Pr. PD04], [Pr. PD06], [Pr. PD08], [Pr. PD10], [Pr. PD12], [Pr. PD14], [Pr. PD18], [Pr. PD20], [Pr. PD22], [Pr. PD44], and [Pr. PD46]. For details, refer to section 3.6.1 (5) of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual".
For the indexer method, [Pr. PC35 Internal torque limit 2] will be enabled automatically depending on operation status. Refer to each timing chart in section 6.2 and section 6.4.5.
Function and application
LSP LSN
1: On
[Pr. PD01]
_ 4 _ _
_ 8 _ _
_ C _ _
Automatic
Automatic
CCW
direction
Positive
direction
on
on
CW
direction
Negative
direction
Status
Automatic
on
Automatic
on
Control
mode
I/O
division
DI-1
DI-1
DI-1
CL
CP/BCD
PS
2 - 23
Page 51
2. SIGNALS AND WIRING
www.kavrammuhendislik.com.tr
Device Symbol
Operation mode selection 1
Operation mode selection 2
Connector
pin No.
MD0 CN1-16 Point table method/program method
Turning on MD0 will be automatic operation mode, off will be manual
MD1 DI-1
operation mode. Changing an operation mode during operation will clear the command remaining distance and the motor will decelerate to stop.
MD1 cannot be used.
Indexer method Select an operation mode with combinations of MD0 and MD1. Refer to the
following table for combinations. Changing an operation mode during operation will clear the command
remaining distance and the motor will decelerate to stop.
Device (Note)
MD1 MD0
0 0 Home position return mode
0 1 Manual operation mode
Note. 0: Off
Function and application
Automatic operation mode 1
1 0
1 1
1: On
Automatic operation mode 2
Operation mode
(rotation direction specifying
indexer)
(shortest rotating indexer)
Control
mode
I/O
division
DI-1
CL
CP/BCD
PS
2 - 24
Page 52
2. SIGNALS AND WIRING
www.kavrammuhendislik.com.tr
Device Symbol
Forward rotation start
Reverse rotation start
Connector
pin No.
ST1 CN1-17 Point table method
1. Absolute value command method Turning on ST1 during automatic operation will execute one positioning
based on position data set in point tables. Turning on ST1 during home position return will also start home
position return. Turning on ST1 during JOG operation will rotate the motor in the
forward rotation direction while it is on. The forward rotation means address increasing direction. Turning on both ST1 and ST2 during JOG operation will stop the servo
motor.
2. Incremental value command method Turning on ST1 during automatic operation will execute one positioning
in the forward rotation direction based on position data set in point tables.
Turning on ST1 during home position return will also start home position return.
Turning on ST1 during JOG operation will rotate the motor in the forward rotation direction while it is on.
The forward rotation means address increasing direction. Turning on both ST1 and ST2 during JOG operation will stop the servo
motor.
Program method
1. Automatic operation mode Turning on ST1 will execute a program operation selected with DI0 to
DI7. The forward rotation means address increasing direction. Turning on both ST1 and ST2 during manual operation mode will stop
the servo motor.
2. Manual operation mode Turning on ST1 will rotate the motor in the forward rotation direction
while it is on. The forward rotation means address increasing direction. Turning on both ST1 and ST2 during manual operation mode will stop
the servo motor.
Indexer method
1. Automatic operation mode 1 or automatic operation mode 2 Turning on ST1 will execute one positioning to the specified station No.
2. Manual operation mode Turning on ST1 with the station JOG operation will rotate the motor in
the specified direction with SIG only while it is on. Turning off ST1 will execute a positioning to a station which can be decelerated to a stop.
Turning on ST1 with JOG operation will rotate the motor in the direction specified with SIG only while it is on. Turning off will decelerate the motor to a stop regardless of stations.
3. Home position return mode Turning on ST1 will also start home position return.
ST2 CN1-18 Point table method
Use this device with the incremental value command method. Turning on ST2 during automatic operation will execute one positioning in the reverse rotation direction based on position data set in point tables. Turning on ST2 during JOG operation will rotate the motor in the reverse rotation direction while it is on. Turning on both ST1 and ST2 will stop the servo motor.
Turning on ST2 during in the home position return mode will execute an automatic positioning to the home position.
The reverse rotation means address decreasing direction. Turning on both ST1 and ST2 during JOG operation will stop the servo
motor. Program method Turning on ST2 with JOG operation in the manual operation mode will
rotate the motor in the reverse rotation direction while it is on. Turning on both ST1 and ST2 will stop the servo motor.
The reverse rotation means address decreasing direction. Turning on both ST1 and ST2 during manual operation mode will stop the
servo motor. ST2 will be disabled in the automatic operation mode. Indexer method This device is not used.
Function and application
Control
mode
I/O
division
DI-1
DI-1
CL
CP/BCD
PS
2 - 25
Page 53
2. SIGNALS AND WIRING
www.kavrammuhendislik.com.tr
Device Symbol
Temporary stop/restart
Proximity dog DOG CN1-45 Turning off DOG will detect a proximity dog. The polarity for dog detection
External limit/ Rotation direction decision/ Automatic speed selection
Manual pulse generator multiplication 1
Manual pulse generator multiplication 2
TSTP Turning on TSTP during automatic operation will temporarily stop the
Connector
pin No.
motor. Turning on TSTP again will restart. Turning on ST1 (Forward rotation start)/ST2 (Reverse rotation start) during
a temporary stop will not rotate the motor. Changing the automatic operation mode to manual operation mode during
a temporary stop will erase a travel remaining distance. The temporary stop/restart input will not function during home position
return/JOG operation.
can be changed with [Pr. PT29].
_ _ _ 0 Detection with off
_ _ _ 1 Detection with on
SIG CN1-45 The function varies depending on the operation mode.
1. Home position return mode (MD1 = 0, MD0 = 0)
You can use SIG as an input device of external limit. This operation mode is enabled when the home position return type of the torque limit changing dog type is selected.
2. Manual operation mode (MD1 = 0, MD0 = 1)
You can use this as an input device for specifying a rotation direction of the servo motor. The rotation direction varies depending on the setting of [Pr. PA14 Rotation direction selection]. (Refer to section 2.1.)
3. Automatic operation mode 1 (rotation direction specifying indexer) (MD1
= 1, MD0 = 0)
You can use this as an input device for specifying a rotation direction of the servo motor. The rotation direction varies depending on the setting of [Pr. PA14 Rotation direction selection]. (Refer to section 2.1.)
4. Automatic operation mode 2 (shortest rotating indexer) (MD1 = 1, MD0 =
1)
You can use SIG as an input device for selecting a speed of the servo motor.
[Pr. PT29]
Function and application
Polarity for proximity dog
detection
Table 2.1 Rotation direction selection
0 0 CCW direction 0 1 CW direction 1 0 CW direction 1 1 CCW direction
TP0 Select a multiplication of the manual pulse generator.
When a multiplication is not selected, the setting of [Pr. PT03] will be enabled.
[Pr. PA14] SIG (Note)
Note. 0: Off
1: On
Servo motor
rotation direction
TP1
Device (Note)
TP1 TP0
0 0 [Pr. PT03] setting
0 1 × 1
1 0 × 10
1 1 × 100
Note. 0: Off
1: On
Manual pulse
generator multiplication
DI-1
Control
mode
I/O
division
DI-1
DI-1
DI-1
DI-1
CL
CP/BCD
PS
2 - 26
Page 54
2. SIGNALS AND WIRING
www.kavrammuhendislik.com.tr
Device Symbol
Analog override selection
Teach TCH Use this for teaching. Turning on TCH in the point table method will rewrite
Program input 1 PI1 Turning on PI1 will restart a step which was suspended with the SYNC (1)
Program input 2 PI2 Turning on PI2 will restart a step which was suspended with the SYNC (2)
Program input 3 PI3 Turning on PI3 will restart a step which was suspended with the SYNC (3)
Current position latch input
Point table No./program No. selection 1
Point table No./program No. selection 2
Point table No./program No. selection 3
Point table No./program No. selection 4
Point table No./program No. selection 5
Point table No./program No. selection 6
Point table No./program No. selection 7
Point table No./program No. selection 8
Connector
pin No.
OVR
LPS Turning on LPS during execution of the LPOS command will latch a current
DI0 CN1-19 Point table method
Turning on OVR will enable VC (Analog override). DI-1
a position data of the selected point table No. to the current position.
command during programming.
command during programming.
command during programming.
position with its rising edge. The latched current position can be read with communication commands.
Select point tables and home position return mode with DI0 to DI7.
Function and application
DI1 CN1-41 Device (Note)
DI7 DI6 DI5 DI4 DI3 DI2 DI1 DI0
0 0 0 0 0 0 0 0 Home position
DI2 CN1-10 0 0 0 0 0 0 0 1 Point table No. 1
0 0 0 0 0 0 1 0 Point table No. 2
DI3 CN1-35
0 0 0 0 0 0 1 1 Point table No. 3
DI4
DI5
DI6
DI7
1 1 1 1 1 1 1 0 Point table No. 254
1 1 1 1 1 1 1 1 Point table No. 255
Note. 0: Off
1: On
Program method Select program Nos. with DI0 to DI7.
Device (Note)
DI7 DI6 DI5 DI4 DI3 DI2 DI1 DI0
0 0 0 0 0 0 0 0 Program No. 1
0 0 0 0 0 0 0 1 Program No. 2
0 0 0 0 0 0 1 0 Program No. 3
0 0 0 0 0 0 1 1 Program No. 4
1 1 1 1 1 1 1 0 Program No. 255
1 1 1 1 1 1 1 1 Program No. 256
Note. 0: Off
1: On
Selection contents
return mode
Selection contents
I/O
division
DI-1
DI-1
DI-1
DI-1
DI-1
DI-1
Control
mode
CL
CP/BCD
PS
2 - 27
Page 55
2. SIGNALS AND WIRING
www.kavrammuhendislik.com.tr
Device Symbol
Next station No. selection 1
Next station No. selection 2
Next station No. selection 3
Next station No. selection 4
Next station No. selection 5
Next station No. selection 6
Next station No. selection 7
Next station No. selection 8
Second acceleration/dec eleration selection
Second acceleration/dec eleration gain selection
RTCDP This has two functions of CDP (Gain switching) and RT (Second
Connector
pin No.
DI0 CN1-19 Indexer method
Select next station Nos. with DI0 to DI7. A setting value at ST1 on will be enabled.
DI1 CN1-41 Device (Note 1)
DI7 DI6 DI5 DI4 DI3 DI2 DI1 DI0
DI2 CN1-10 0 0 0 0 0 0 0 0 Next station No. 0
DI3 CN1-35 0 0 0 0 0 0 0 1 Next station No. 1
DI4 0 0 0 0 0 0 1 0 Next station No. 2
DI5 0 0 0 0 0 0 1 1 Next station No. 3
DI6
DI7
1 1 1 1 1 1 1 0 Next station No. 254
1 1 1 1 1 1 1 1 Setting inhibited
Note 1. 0: Off
2. [AL. 97.2 Next station position warning] will occur.
RT
Turning on ST1 with RT-off will select acceleration/deceleration time constants set with [Pr. PC01 Acceleration time constant 1] and [Pr. PC02 Deceleration time constant 1].
Turning on ST1 with RT-on will select acceleration/deceleration time constants set with [Pr. PC30 Acceleration time constant 2] and [Pr. PC31 Deceleration time constant 2].
RT will not be accepted during operation.
Device (Note) Description
0 [Pr. PC01] [Pr. PC02]
1 [Pr. PC30] [Pr. PC31]
acceleration/deceleration selection). When RTCDP is off, the servo control gain set with [Pr. PB06], [Pr. PB08]
to [Pr. PB10] will be selected. Turning on ST1 (Forward rotation start) will select acceleration/deceleration time constants set with [Pr. PC01 Acceleration time constant 1] and [Pr. PC02 Deceleration time constant 1].
When RTCDP is on, the servo control gain set with [Pr. PB29] to [Pr. PB32] will be selected. Turning on ST1 (Forward rotation start) will select acceleration/deceleration time constants set with [Pr. PC30 Acceleration time constant 2] and [Pr. PC31 Deceleration time constant 2].
Function and application
Selection contents
(Note 2)
1: On
RT
Note. 0: Off
1: On
Acceleration time
constant
Deceleration time
constant
division
DI-1
DI-1
DI-1
I/O
Control
mode
CL
CP/BCD
PS
2 - 28
Page 56
2. SIGNALS AND WIRING
www.kavrammuhendislik.com.tr
Device Symbol
Digital override selection 1
Digital override selection 2
Digital override selection 3
Digital override selection 4
Connector
pin No.
OV0 To enable the digital override function, set [Pr. PT38] to "_ _ 1 _".
This signal is for multiplying a command speed by the digital override
OV1
OV2
OV3
(multiplying factor). A command speed multiplied by the digital override value selected with this
signal will be an actual servo motor speed. If the servo motor speed multiplied by the digital override value exceeds
the servo motor maximum speed, the speed will be limited at the maximum speed.
The following table shows an example of setting "50" to [Pr. PT42] and "5" to [Pr. PT43].
Device (Note)
OV3 OV2 OV1 OV0
0 0 0 0 100 [%] of
0 0 0 1 50 [%] of command
0 0 1 0 55 [%] of command
0 0 1 1 60 [%] of command
0 1 0 0 65 [%] of command
0 1 0 1 70 [%] of command
0 1 1 0 75 [%] of command
0 1 1 1 80 [%] of command
1 0 0 0 85 [%] of command
1 0 0 1 90 [%] of command
1 0 1 0 95 [%] of command
1 0 1 1 100 [%] of
1 1 0 0 105 [%] of
1 1 0 1 110 [%] of
1 1 1 0 115 [%] of
1 1 1 1 0 [%] of command
Note. 0: Off
1: On
Mark detection MSD The current position latch function by sensor input can be used. For the
current position latch function, refer to section 12.2.1. For the current position latch function, refer to section 12.2.2.
Function and application
Description
command speed
speed
speed
speed
speed
speed
speed
speed
speed
speed
speed
command speed
command speed
command speed
command speed
speed
Control
I/O
division
DI-1
DI-1
mode
CL
CP/BCD
PS
2 - 29
Page 57
2. SIGNALS AND WIRING
www.kavrammuhendislik.com.tr
Device Symbol
Proportion control
Clear
Gain switching CDP Turn on CDP to use the values of [Pr. PB29] to [Pr. PB36] and [Pr. PB56]
Fully closed loop selection
Motor-side/load­side deviation counter clear
Cam control command
Cam position compensation request
Clutch command CLTC
Cam No. selection 0
Cam No. selection 1
Cam No. selection 2
Cam No. selection 3
MECR Turn on MECR to clear the motor-side/load-side position deviation counter
CAMC
CPCD
Connector
pin No.
PC Turn PC on to switch the speed amplifier from the proportional integral type
CR Turn CR on to clear the position control counter droop pulse on its leading
CLD Not used with the positioning mode. DI-1
CI0
to the proportional type. If the servo motor at a stop is rotated even one pulse due to any external
factor, it generates torque to compensate for a position shift. When the servo motor shaft is to be locked mechanically after positioning completion (stop), switching on the PC (Proportion control) upon positioning completion will suppress the unnecessary torque generated to compensate for a position shift.
When the shaft is to be locked for a long time, switch on the PC (Proportion control) and TL (External torque limit selection) at the same time to make the torque less than the rated by TLA (Analog torque limit).
edge. The pulse width should be 10 ms or longer. The delay amount set in [Pr. PB03 Position command
acceleration/deceleration time constant] is also cleared. When " _ _ _1 " is set to [Pr. PD32], the pulses are always cleared while CR is on.
to [Pr. PB60] as the load to motor inertia ratio and gain values.
to zero.
It operates during the fully closed loop control. It does not affect the position control droop pulses. Turning on this device during the semi closed loop control does not
affect the operation. Turning on this device while the fully closed loop control error detection
function is disabled in [Pr. PE03] does not affect the operation. This device is not available with MR-J4-03A6-RJ servo amplifiers. When using CAMC, set [Pr. PT35] to "_ 1 _ _" to enable it. Turning CAMC on switches the control from the normal positioning control to the cam control.
Turning CPCD on compensates the cam axis one cycle current value to be in the position set in [Cam control data No. 60 - Cam position compensation target position].
This is used to turning on/off the main shaft clutch command. This is used when [Cam control data No. 36 - Main shaft clutch control
setting] is set to "_ _ _ 1". Select cam No. This is enabled when [Cam control data No. 49 - Cam No.] is set to "0". Set
the cam control data on the cam setting window of MR Configurator2.
Function and application
CI1
CI2
CI3
Device (Note 1)
CI3 CI2 CI1 CI0
0 0 0 0 Linear cam
0 0 0 1 Cam No. 1 0 0 1 0 Cam No. 2
0 0 1 1 Cam No. 3
1 0 0 0 Cam No. 8
1 0 0 1
1 1 1 1
Note 1. 0: Off
1: On
2. [AL. F6.5 Cam No. external error] occurs.
Selection contents
Setting inhibited
(Note 2)
I/O
division
DI-1
DI-1
DI-1
DI-1
DI-1
DI-1
DI-1
DI-1
Control
mode
CL
CP/BCD
PS
2 - 30
Page 58
2. SIGNALS AND WIRING
www.kavrammuhendislik.com.tr
(b) Output device
Device Symbol
Malfunction ALM CN1-48 When an alarm occurs, ALM will turn off.
Malfunction/War ning
Warning WNG When warning has occurred, WNG turns on. When a warning is not
Battery warning BWNG BWNG turns on when [AL. 92 Battery cable disconnection warning] or [AL.
AL9F warning BW9F When [AL. 9F Battery warning] occurs, BW9F will turn on. DO-1 Dynamic brake
interlock
Ready RD CN1-49 Enabling servo-on to make the servo amplifier ready to operate will turn on
In-position INP CN1-24 When the number of droop pulses is in the preset in-position range, INP
Limiting torque TLC CN1-25 TLC turns on when a generated torque reaches a value set with any of [Pr.
Zero speed detection
WNG
Connector
pin No.
When an alarm does not occur, ALM will turn on after 4 s to 5 s after power-on.
When [Pr. PD34] is "_ _ 1 _", an alarming or warning will turn off ALM.
ALM
DB When using the signal, enable it by setting [Pr. PD23] to [Pr. PD26], [Pr.
ZSP CN1-23
When an alarm occurs, ALMWNG will turn off.
When a warning (except [AL. 9F Battery warning]) occurs on and off will be repeated every 1 s.
When an alarm/warning is not occurring, turning on the power will turn on ALMWNG after 4 s to 5 s.
occurring, turning on the power will turn off WNG after 4 s to 5 s.
9F Battery warning] has occurred. When the battery warning is not occurring, turning on the power will turn off BWNG after 4 s to 5 s.
PD28], and [Pr. PD47]. DB turns off when the dynamic brake needs to operate. When using an external dynamic brake with the servo amplifier of 11 kW or more, this device is required. (Refer to "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual" section 11.17.)
For the servo amplifier of 7 kW or less, it is not necessary to use this device.
RD.
will turn on. The in-position range can be changed using [Pr. PA10]. When the in-position range is increased, INP may be on during low-speed rotation.
INP turns on when servo-on turns on.
PA11 Forward torque limit], [Pr. PA12 Reverse torque limit], or TLA (Analog torque limit).
ZSP turns on when the servo motor speed is zero speed (50 r/min) or less. Zero speed can be changed with [Pr. PC17].
Function and application
I/O
division
DO-1
DO-1
DO-1
DO-1
DO-1
DO-1
DO-1
DO-1
DO-1
Control
mode
CL
CP/BCD
PS
Forward rotation direction
Servo motor speed
Reverse rotation direction
ZSP (Zero speed detection)
ZSP will turn on when the servo motor is decelerated to 50 r/min (at 1)), and will turn off when the servo motor is accelerated to 70 r/min again (at
2)). ZSP will turn on when the servo motor is decelerated again to 50 r/min (at
3)), and will turn off when the servo motor speed has reached -70 r/min (at
4)). The range from the point when the servo motor speed has reached on
level, and ZSP turns on, to the point when it is accelerated again and has reached off level is called hysteresis width.
Hysteresis width is 20 r/min for this servo amplifier.
OFF level 70 r/min
ON level 50 r/min
0 r/min
ON level
-50 r/min OFF level
-70 r/min
ON OFF
1)
3)
2)
20 r/min (Hysteresis width)
[Pr. PC17]
[Pr. PC17]
20 r/min (Hysteresis width)
4)
2 - 31
Page 59
2. SIGNALS AND WIRING
www.kavrammuhendislik.com.tr
Device Symbol
Electromagnetic brake interlock
Speed command reached
Home position return completion
Rough match CPO When a command remaining distance is lower than the rough match output
Position range output
Temporary stop PUS When a deceleration begins for a stop, PUS will be on by TSTP
Travel completion
Position end PED When the droop pulses are within the position end output range set with
SYNC synchronous output
MEND When the droop pulses are within the in-position output range set with [Pr.
SOUT When the status is waiting for input of the program SYNC (1 to 3), SOUT
Connector
pin No.
MBR When using the device, set operation delay time of the electromagnetic
brake in [Pr. PC16]. When a servo-off status or alarm occurs, MBR will turn off.
SA When a command speed is within a target speed at servo-on status, SA
will be on. When the command speed is 0 r/min (mm/s), this will be continuously on. When the command speed is in acceleration/deceleration or at servo-off
status, SA will be off.
ZP When a home position return completes normally, ZP (Home position
return completion) will be on. This will be off with the following conditions in the incremental system.
1) SON (Servo-on) is off.
2) EM2 (Forced stop 2) is off.
3) RES (Reset) is on.
4) At alarm occurrence
5) LSP (Forward rotation stroke end) or LSN (Reverse rotation stroke end) is off.
6) Home position return is not being executed.
7) Software limit is being detected.
8) Home position return is in progress.
If once home position return is completed in the absolute position detection system, ZP (Home position return completion) will be the same output status as RD (Ready).
However, it will be off with the above 1) to 8) and the following 9) to 14).
9) The home position return is not performed after [AL. 25 Absolute position erased] or [AL. E3 Absolute position counter warning] occurred.
10) The home position return is not performed after the electronic gear
([Pr. PA06] and [Pr. PA07]) was changed.
11) The home position return is not performed after the setting of [Pr.
PA03 Absolute position detection system selection] was changed from "Disabled" to "Enabled".
12) [Pr. PA14 Rotation direction selection/travel direction selection] was
changed.
13) [Pr. PA01 Operation mode] was changed.
14) [Pr. PT08 Home position return position data] or [Pr. PT28 Number of
stations per rotation] was changed.
range set with [Pr. PT12], CPO will be on. This is not outputted during base circuit shut-off. CPO turns on with servo-on.
POT When an actual current position is within the range set with [Pr. PT21] and
[Pr. PT22], POT will be on. This will be off when a home position return does not complete or base circuit shut-off is in progress.
(Temporary stop/restart). When you enable TSTP (Temporary stop/restart) again and start operation, PUS will be off.
PA10] and the command remaining distance is "0", MEND will be on. MEND turns on with servo-on. MEND is off at servo-off status. However, MEND will not be off in the
indexer method.
[Pr. PA10] and the command remaining distance is "0", PED will be on. When MEND (Travel completion) is on and ZP (Home position return
completion) is on, PED (Position end) will be on. When ZP (Home position return completion) is on with servo-on status,
PED will be on. PED is off at servo-off status.
will be on. When PI1 (Program input 1) to PI3 (Program input 3) turn on, SOUT will be off.
Function and application
I/O
division
DO-1
DO-1
DO-1
DO-1
DO-1
DO-1
DO-1
DO-1
DO-1
Control
mode
CL
CP/BCD
PS
2 - 32
Page 60
2. SIGNALS AND WIRING
www.kavrammuhendislik.com.tr
Device Symbol
Program output 1 OUT1 OUT1 will turn on with the OUTON (1) command during programming.
Program output 2 OUT2 OUT2 will turn on with the OUTON (2) command during programming.
Program output 3 OUT3 OUT3 will turn on with the OUTON (3) command during programming.
Point table No. output 1
Point table No. output 2
Point table No. output 3
Point table No. output 4
Point table No. output 5
Point table No. output 6
Point table No. output 7
Point table No. output 8
Connector
pin No.
The OUTOF (1) command will turn off OUT1. You can also set time to off with [Pr. PT23].
The OUTOF (2) command will turn off OUT2. You can also set time to off with [Pr. PT24].
The OUTOF (3) command will turn off OUT3. You can also set time to off with [Pr. PT25].
PT0 The signals output point table Nos. in 8 bit code simultaneously with MEND
(Travel completion) on.
Function and application
PT1 Device (Note 1, 2) Description
PT7 PT6 PT5 PT4 PT3 PT2 PT1 PT0
PT2 0 0 0 0 0 0 0 1 Point table No. 1
PT3 0 0 0 0 0 0 1 0 Point table No. 2
PT4 0 0 0 0 0 0 1 1 Point table No. 3
PT5
PT6
PT7
1 1 1 1 1 1 1 0 Point table No. 254
1 1 1 1 1 1 1 1 Point table No. 255
I/O
division
DO-1
DO-1
DO-1
DO-1
Control
mode
CL
CP/BCD
PS
Note 1. 0: Off
2. For MR-J4-03A6-RJ servo amplifiers, up to six points of DO are
Station output 1 PS0 The signals output station Nos. simultaneously with MEND on while an
alarm is not occurring.
1: On
available; therefore, PT0 to PT7 cannot be outputted
simultaneously.
DO-1
Station output 2 PS1 Device (Note 1, 2)
PS7 PS6 PS5 PS4 PS3 PS2 PS1 PS0
Station output 3 PS2 0 0 0 0 0 0 0 0 In-position out of
Station output 4 PS3 1 1 1 1 1 1 1 1 Next station No. 0
Station output 5 PS4 1 1 1 1 1 1 1 0 Next station No. 1
Station output 6 PS5 1 1 1 1 1 1 0 1 Next station No. 2
Station output 7 PS6 1 1 1 1 1 1 0 0 Next station No. 3
Station output 8 PS7
0 0 0 0 0 0 1 0 Next station No. 253
0 0 0 0 0 0 0 1 Next station No. 254
Note 1. 0: Off
2. For MR-J4-03A6-RJ servo amplifiers, up to six points of DO are
1: On
available; therefore, PS0 to PS7 cannot be outputted
simultaneously.
Description
range
2 - 33
Page 61
2. SIGNALS AND WIRING
www.kavrammuhendislik.com.tr
Control
Device Symbol
M code 1 (bit 0) MCD00 This device can be used in the point table method.
M code 2 (bit 1) MCD01 DO-1
M code 3 (bit 2) MCD02 DO-1
M code 4 (bit 3) MCD03 DO-1
M code 5 (bit 4) MCD10 DO-1
M code 6 (bit 5) MCD11 DO-1
M code 7 (bit 6) MCD12 DO-1
M code 8 (bit 7) MCD13 DO-1
Connector
pin No.
Function and application
These signals can be checked with output devices of the communication function. (Refer to section 10.2 (1).)
To use these signals, set " _ _ 1 _" in [Pr. Po12]. The signals output M code simultaneously with CPO (Rough match) on. Set M code with point tables.
The code represents one digit of decimal using four digits of binary. The following shows correspondence of each digit and device.
Second digit First digit
bit3 bit2 bit1 bit0 bit3 bit2 bit1 bit0
MCD00
MCD01
MCD02
MCD03
division
DO-1
I/O
mode
CL
CP/BCD
PS
MCD10
MCD11
MCD12
MCD13
M code Device (Note)
First/second
digit
0 0 0 0 0
1 0 0 0 1
2 0 0 1 0
3 0 0 1 1
4 0 1 0 0
5 0 1 0 1
6 0 1 1 0
7 0 1 1 1
8 1 0 0 0
9 1 0 0 1
Note. 0: Off
1: On
MCD00 to MCD03 and MCD10 to MCD13 will turn off with the following status.
Power on Servo-off Manual operation mode At alarm occurrence
MCD03/
MCD13
MCD02/
MCD12
MCD01/
MCD11
MCD00/
MCD10
2 - 34
Page 62
2. SIGNALS AND WIRING
www.kavrammuhendislik.com.tr
Device Symbol
Mark detection rising latch completed
Mark detection falling latch completed
Alarm code ACD0 (CN1-24) To use these signals, set " _ _ _ 1" in [Pr. PD34].
Variable gain selection
Absolute position undetermined
During tough drive
During fully closed loop control
Under cam control
Cam position compensation execution completed
Clutch on/off status
Clutch smoothing status
MSDH Turning on MSD (Mark detection) will turn on MSDH. DO-1
MSDL After MSD (Mark detection) is turned on, turning off MSD will turn on
ACD1 (CN1-23)
ACD2 (CN1-22)
CDPS CDPS turns on during gain switching. DO-1
ABSV ABSV turns on when the absolute position is undetermined. DO-1
MTTR When a tough drive is "Enabled" in [Pr. PA20], activating the instantaneous
CLDS CLDS turns on during fully closed loop control.
CAMS It turns on when the control switches to the cam control.
CPCC It turns on when the cam compensation execution is enabled.
CLTS It turns on with clutch-on.
CLTSM It outputs clutch smoothing status.
(2) Input signal
Device Symbol
Connector
pin No.
Connector
pin No.
Function and application
MSDL.
This signal is outputted when an alarm occurs. When an alarm is not occurring, respective ordinary signals are outputted. For details of the alarm codes, refer to chapter 8. When [Pr. PD34] is set to "_ _ _ 1", setting the following will trigger [AL. 37
Parameter error].
"_ _ _ 1" is set in [Pr. PA03] and the absolute position detection system
by DIO is selected.
MBR, DB, or ALM is assigned to the CN1-22 pin, CN1-23 pin, or CN1-24
pin.
power failure tough drive will turn on MTTR. This device is not available with MR-J4-03A6-RJ servo amplifiers.
This device is not available with MR-J4-03A6-RJ servo amplifiers.
It turns off when the control switches to the normal positioning control.
It turns on when the position compensation is not being executed during the cam control.
It is always off when [Cam control data No. 36 - Main shaft clutch control setting] is set to "_ _ _ 0".
The output depends on the setting in [Cam control data No. 42 - Main shaft clutch smoothing system] as follows:
0: Direct
Always off
1: Time constant method (index)
Always on in clutch-on status It turns off when the clutch is off and the smoothing is complete.
Function and application
I/O
division
DO-1
DO-1
DO-1
DO-1
DO-1
DO-1
DO-1
DO-1
I/O
division
Control
mode
CL
CP/BCD
Control
mode
CL
PS
PS
Manual pulse generator
PP (CN1-10) Connect the manual pulse generator (MR-HDP01).
NP (CN1-35)
When using the signal, enable PP and NP with [Pr. PD44] and [Pr. PD46].
2 - 35
DI-2
CP/BCD
Page 63
2. SIGNALS AND WIRING
www.kavrammuhendislik.com.tr
Device Symbol
Analog torque limit
Analog override VC CN1-2 The signal controls the servo motor setting speed by applying -10 V to +10
(3) Output signal
(a) MR-J4-_A_-RJ 100 W or more
Device Symbol
Connector
pin No.
TLA CN1-27 When using the signal, enable TL (External torque limit selection) with [Pr.
PD04], [Pr. PD06], [Pr. PD08], [Pr. PD10], [Pr. PD12], [Pr. PD14], [Pr. PD18], [Pr. PD20], [Pr. PD22], [Pr. PD44], and [Pr. PD46].
When TLA is enabled, torque is limited in the full servo motor output torque range. Apply 0 V to +10 V DC between TLA and LG. Connect the positive terminal of the power supply to TLA. The maximum torque is generated at +10 V. (Refer to section 3.6.1 (5) of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual".)
If a value equal to or larger than the maximum torque is inputted to TLA, the value is clamped at the maximum torque.
Resolution: 10 bits
V to between VC and LG. The percentage will be 0% with -10 V, 100% with 0 V, and 200% with +10 V to the setting speed of the servo motor.
Resolution: 14 bits or equivalent
For MR-J4-_A_-RJ 100 W or more servo amplifiers, setting [Pr. PC60] to "_ _ 1 _" increases the analog input resolution to 16 bits. This function is available with servo amplifiers manufactured in November 2014 or later.
Connector
pin No.
Function and application
Function and application
I/O
division
Analog
input
Analog
input
I/O
division
Control
mode
CL
CP/BCD
Control
mode
CL
PS
PS
Encoder A­phase pulse
(differential line driver)
Encoder B­phase pulse
(differential line driver)
Encoder Z­phase pulse
(differential line driver)
Encoder Z­phase pulse
(open-collector)
Analog monitor 1 MO1 CN6-3 This is used to output the data set in [Pr. PC14] to between MO1 and LG in
Analog monitor 2 MO2 CN6-2 This signal outputs the data set in [Pr. PC15] to between MO2 and LG in
LA
LAR
LB
LBR
LZ
LZR
OP CN1-33 The encoder zero-point signal is outputted in the open-collector type. DO-2
CN1-4 CN1-5
CN1-6 CN1-7
CN1-8 CN1-9
These devices output pulses of encoder output pulse set in [Pr. PA15] in the differential line driver type.
In CCW rotation of the servo motor, the encoder B-phase pulse lags the encoder A-phase pulse by a phase angle of π/2.
The relation between rotation direction and phase difference of the A­phase and B-phase pulses can be changed with [Pr. PC19].
The encoder zero-point signal is outputted in the differential line driver type. One pulse is outputted per servo motor revolution. This turns on when the zero-point position is reached. (negative logic)
The minimum pulse width is about 400 μs. For home position return using this pulse, set the creep speed to 100 r/min or less.
terms of voltage. Output voltage: ±10 V Resolution: 10 bits or equivalent
terms of voltage. Output voltage: ±10 V Resolution: 10 bits or equivalent
CP/BCD
DO-2
DO-2
Analog
output
Analog
output
2 - 36
Page 64
2. SIGNALS AND WIRING
www.kavrammuhendislik.com.tr
(b) MR-J4-03A6-RJ
Device Symbol
Encoder A­phase pulse
(differential line driver)
Encoder B­phase pulse
(differential line driver)
Encoder Z­phase pulse
(differential line driver)
Encoder Z­phase pulse
(open-collector)
Analog monitor 1 MO1 CN1-26 This is used to output the data set in [Pr. PC14] to between MO1 and LG in
Analog monitor 2 MO2 CN1-29 This signal outputs the data set in [Pr. PC15] to between MO2 and LG in
(4) Communication
(a) MR-J4-_A_-RJ 100 W or more
Device Symbol
Connector
pin No.
LA
LAR
LB
LBR
LZ
LZR
OP CN1-33 The encoder zero-point signal is outputted in the open-collector type. DO-2
CN1-4 CN1-5
CN1-6 CN1-7
CN1-8 CN1-9
Connector
pin No.
These devices output pulses of encoder output pulse set in [Pr. PA15] in the differential line driver type.
In CCW rotation of the servo motor, the encoder B-phase pulse lags the encoder A-phase pulse by a phase angle of π/2.
The relation between rotation direction and phase difference of the A­phase and B-phase pulses can be changed with [Pr. PC19].
The encoder zero-point signal is outputted in the differential line driver type. One pulse is outputted per servo motor revolution. This turns on when the zero-point position is reached. (negative logic)
The minimum pulse width is about 400 μs. For home position return using this pulse, set the creep speed to 100 r/min or less.
terms of voltage. Output voltage: 5 V ± 4 V Resolution: 10 bits or equivalent
terms of voltage. Output voltage: 5 V ± 4 V Resolution: 10 bits or equivalent
Function and application
Function and application
Control
I/O
division
DO-2
DO-2
Analog
output
Analog
output
division
mode
CP
Control
mode
I/O
CL
CL
PS
PS
CP/BCD
RS-422/RS-485 I/F
RDP CN3-3
RDN CN3-6
SDP CN3-5 These are terminals for RS-422/RS-485 communication.
SDN CN3-4
(b) MR-J4-03A6-RJ
Device Symbol
RS-422 I/F SDP CN1-13 These are terminals for RS-422 communication.
SDN CN1-14
RDP CN1-39
RDN CN1-40
TRE CN1-31
Connector
pin No.
Function and application
division
I/O
Control
mode
CL
CP
PS
2 - 37
Page 65
2. SIGNALS AND WIRING
www.kavrammuhendislik.com.tr

2.4 Analog override

POINT
The override function has two types. One is analog override by using analog voltage input and another is digital override by using parameter settings.
Target method of analog override: Point table method/Program method
Target method of digital override: Indexer method OVR (Analog override selection) is for the analog override. The digital override does not depend on OVR (Analog override selection). Refer to [Pr. PT38], [Pr. PT42], and [Pr. PT43] for the digital override. When using the analog override in the point table method or program method, enable OVR (Analog override selection). The following shows functions whether usable or not with the analog override. (1) Analog override usable
Automatic operation mode (point table method/program method) JOG operation in the manual operation mode Automatic positioning to home position function in the point table method
(2) Analog override unusable
Manual pulse generator operation in the manual operation mode Home position return mode Test operation mode using MR Configurator2 (positioning operation/JOG
operation)
You can change the servo motor speed by using VC (Analog override). The following table shows signals and parameters related to the analog override.
Item Name Remark
Analog input signal VC (Analog override)
Contact input signal OVR (Analog override selection)
Parameter [Pr. PC37 Analog override offset] -9999 to 9999 [mV]
Turning on OVR will enable VC (Analog override) setting value.
(1) VC (Analog override)
You can continuously set changed values from outside by applying voltage (-10 V to +10 V) to VC (Analog override). The following shows percentage of the actual speed to input voltage and set speed.
[%] 200
100
Percentage of the actual
speed to set speed.
0
-10 0 10 [V]
VC (Analog override voltage) applied voltage
OVR (Analog override selection)
24 V DC
VC (Analog override)
-10 V to +10 V
Servo amplifier
OVR
DICOM
VC
(Note) LG SD
Note. This diagram shows sink input interface.
2 - 38
Page 66
2. SIGNALS AND WIRING
r
www.kavrammuhendislik.com.tr
(2) OVR (Analog override selection)
Select enabled/disabled of VC (Analog override).
Servo amplifie
Analog
override
Speed control
OVR (Analog override selection)
VC (Analog override)
-10 V to +10 V
Position
control
Select a changed value using OVR (Analog override selection).
(Note) External input
signal
0 No change
1
Setting of VC (Analog override) is enabled.
Speed change value
Note. 0: Off
1: On
(3) Analog override offset ([Pr. PC37])
You can set an offset voltage to the input voltage of VC (Analog override) with [Pr. PC37]. The setting value is from -9999 to +9999 [mV].
Servo motor
2 - 39
Page 67
2. SIGNALS AND WIRING
www.kavrammuhendislik.com.tr

2.5 Internal connection diagram

POINT
For details of interface and source I/O interface, refer to section 3.9 of "MR-J4­_A_(-RJ) Servo Amplifier Instruction Manual". For the CN8 connector, refer to section 13.3.1 of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual".
The following shows an example of internal connection diagram of the point table method.
2 - 40
Page 68
2. SIGNALS AND WIRING
www.kavrammuhendislik.com.tr
(1) MR-J4-_A_-RJ 100 W or more
CN1
SON
15
MD0
16 ST1 17 ST2
18
DI0
(Note 3)
(Note 2)
(
Note
24 V DC
4)
19
DI1 41
EM2
42 LSP
43 LSN 44
DOG
45
OPC 12
DICOM
20
DICOM
21
DI2 10
DI3 35
CN1
TLA
27
P15R
LG
28LG
30LG
Case
SD
2VC
1
3
Approx.
6.2 kΩ
Approx.
6.2 kΩ
Approx.
100
Ω
Approx.
100
Ω
15 V DC
Servo amplifier
Approx.
1.2 k
Ω
Approx.
1.2 k
Ω
Insulated
CN1
46
47
22
23
24
25
48
49
13
14
CN1
4 5 6 7 8
9 33 34
CN3
5
4
3
6
7
CN6
3
DOCOM
DOCOM
CPO
ZP
INP
MEND
ALM
RD
(Note 1)
(Note 1)
LA
LAR
LB
LBR
LZ
LZR
OP LG
RS-422/RS-485
SDP SDN RDP RDN
LG
Analog monitor
MO1
(Note 4)
24 V DC
RA
(Note 3)
RA
Differential line driver output (35 mA or lower)
Open-collector output
D-
USB D+
GND
CN5
2 3 5
2 - 41
2
1
CN2
7
8
3
4
2
(Note 5) CN2L
7
8
3
4
2
MO2
LG
MX
MXR
MR
MRR
LG
E
MX2
MXR2
MR2
MRR2
LG
± 10 V DC
± 10 V DC
Servo motor
Encoder
M
External encoder
Encoder
Page 69
2. SIGNALS AND WIRING
www.kavrammuhendislik.com.tr
Note 1. Output signals are not assigned by default. Assign the output signals with [Pr. PD47] as necessary.
2. Refer to section 9.1 for the connection of manual pulse generator.
3. This diagram shows sink I/O interface. For source I/O interface, refer to section 3.9.3 of "MR-J4-_A_(-RJ) Servo Amplifier
Instruction Manual".
4. The illustration of the 24 V DC power supply is divided between input signal and output signal for convenience. However, they
can be configured by one.
5. For the connection with external encoders, refer to table 1.1 of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual".
2 - 42
Page 70
2. SIGNALS AND WIRING
r
www.kavrammuhendislik.com.tr
(2) MR-J4-03A6-RJ
CN1
SON
15 16
MD0
ST1 17 ST2
18
DI0
(Note 2)
(Note 1)
(Note 3) 24 V DC
USB D+
19
DI1 41
EM2
42
LSP
43 LSN 44 DOG
45 OPC 12
DICOM
20
DICOM
21
DI2 10
DI3 35
CN1
TLA
27
P15R
LG
CaseSD
CN3
D-
GND
2VC
1
3
2 3 5
Approx.
6.2 kΩ
Approx.
6.2 k
Ω
Approx.
100 Ω
Approx.
100
Ω
15 V DC
Servo amplifie
Approx.
1.2 kΩ
Approx.
1.2 k
Ω
Insulated
CN1
46
47
22
23
24
25
48
49
CN1
4 5 6 7 8
9 33 34
CN1
13 14 39 40 30 31
CN1
26
29
28
CN2
1A 1BMRMRR 4B
CNP1
8
6
DOCOM
DOCOM
CPO
ZP
INP
MEND
ALM
RD
LA
LAR
LB
LBR
LZ
LZR
OP LG
SDP SDN RDP RDN
LG
TRE
MO1
MO2
LG
LG
E
(Note 3)
24 V DC
RA
RA
Differential line driver output (35 mA or lower)
Open-collector output
RS-422
(Note 4)
Analog monitor
5 V DC ± 4 V DC
Servo motor
Encoder
M
(Note 2)
5 V DC ± 4 V DC
2 - 43
Page 71
2. SIGNALS AND WIRING
_
www.kavrammuhendislik.com.tr
Note 1. Refer to section 9.1 for the connection of a manual pulse generator.
2. This diagram shows sink I/O interface. For source I/O interface, refer to section 3.9.3 of "MR-J4-_A_(-RJ) Servo Amplifier
Instruction Manual".
3. The illustration of the 24 V DC power supply is divided between input signal and output signal for convenience. However, they
can be configured by one. For 24 V DC power for I/O signal, use power other than 24 V DC power of servo amplifier control
circuit power supply.
4. To use the RS-422 communication function, connect between TRE and RDN of the final axis servo amplifier. (Refer to "MR-J4-
A_(-RJ) Servo Amplifier Instruction Manual" section 18.9.)
2 - 44
Page 72
2. SIGNALS AND WIRING
A
www.kavrammuhendislik.com.tr

2.6 Power-on sequence

POINT
The voltage of analog monitor output, output signal, etc. may be unstable at power-on.

2.6.1 MR-J4-_A_-RJ 100 W or more

(1) Power-on procedure
1) Always use a magnetic contactor for the main circuit power supply wiring (L1/L2/L3) as shown in section 3.1 of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual". Configure an external
(2) Timing chart
sequence to switch off the magnetic contactor as soon as an alarm occurs.
2) Switch on the control circuit power supply (L11 and L21) simultaneously with the main circuit power supply or before switching on the main circuit power supply. If the main circuit power supply is not on, the display shows the corresponding warning. However, by switching on the main circuit power supply, the warning disappears and the servo amplifier will operate properly.
3) The servo amplifier receives the SON (Servo-on) 4 s to 5 s after the main circuit power supply is switched on. Therefore, when SON (Servo-on) is switched on simultaneously with the main circuit power supply, the base circuit will switch on in about 4 s to 5 s, and the RD (Ready) will switch on in further about 5 ms, making the servo amplifier ready to operate. (Refer to (2) of this section.)
4) When RES (Reset) is switched on, the base circuit is shut off and the servo motor shaft coasts.
Main circuit
power supply
Control circuit
Base circuit
SON (Servo-on)
RES (Reset)
RD (Ready)
LM (Malfunction)
No alarming (ON) Alarming (OFF)
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
SON (Servo-on) accepted
(Note)
(4 s to 5 s)
4 s to 5 s
10 ms
10 ms5 ms
95 ms
95 ms
10 ms
10 ms5 ms
5 ms 10 ms
Note. The time will be longer during the magnetic pole detection of a linear servo motor and direct drive motor.
2 - 45
Page 73
2. SIGNALS AND WIRING
www.kavrammuhendislik.com.tr

2.6.2 MR-J4-03A6-RJ

(1) Power-on procedure
1) When wiring the power supply, always use a circuit protector for the power supply (24/PM).
Configure up an external sequence so that the relay connected to PM turns off when an alarm occurs.
2) Switch on the control circuit power supply (24/0) simultaneously with the main circuit power
supply (PM/0) or before switching on the main circuit power supply. If the main circuit power supply is not on, the display shows the corresponding warning. However, by switching on the main circuit power supply, the warning disappears and the servo amplifier will operate properly.
3) The servo amplifier receives the SON (Servo-on) within 4 s to 5 s after the main circuit power
supply is switched on. Therefore, when SON (Servo-on) is switched on simultaneously with the main circuit power supply, the base circuit will switch on in about 4 s to 5 s, and the RD (Ready) will switch on in further about 5 ms, making the servo amplifier ready to operate. (Refer to (2) of this section.)
4) When RES (Reset) is switched on, the base circuit is shut off and the servo motor shaft coasts.
(2) Timing chart
SON (Servo-on) accepted
(4 s to 5 s)
Main circuit Control circuit
Base circuit
SON (Servo-on)
RES (Reset)
RD (Ready)
ALM (Malfunction)
Power supply
No alarming (ON)
Alarming (OFF)
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
4 s to 5 s
10 ms
10 ms5 ms
95 ms
95 ms
10 ms
10 ms5 ms
5 ms 10 ms
2 - 46
Page 74

3. DISPLAY AND OPERATION SECTIONS

www.kavrammuhendislik.com.tr
3. DISPLAY AND OPERATION SECTIONS
The following items are the same as MR-J4-_A_-RJ servo amplifiers. For details, refer to each section indicated in the detailed explanation field. "MR-J4-_A_" means "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual".
Item
Test operation mode MR-J4-_A_ section 4.5.9 MR-J4-_A_ section 18.5.10
MR-J4-_A_-RJ 100 W
or more

3.1 MR-J4-_A_-RJ 100 W or more

3.1.1 Display sequence

Press the "MODE" button once to shift to the next display mode. Refer to section 3.1.2 and later for the description of the corresponding display mode.
Detailed explanation
MR-J4-03A6-RJ
3 - 1
Page 75
3. DISPLAY AND OPERATION SECTIONS
www.kavrammuhendislik.com.tr
Display mode transition Initial screen Function Reference
Servo status display. For the point table method and program
method, "PoS" is displayed at power-on.
Status display
One-touch tuning
Diagnosis
Alarm
For the indexer method, "C" is displayed. (Note) One-touch tuning Select this when performing the one-touch
tuning.
Sequence display, drive recorder enabled/disabled display, external I/O signal display, output signal (DO) forced output, test operation, software version display, VC automatic offset, servo motor series ID display, servo motor type ID display, servo motor encoder ID display, teaching function
Current alarm display, alarm history display and parameter error No./point table error No. display
Section 3.1.2
MR-J4-_A_ (-RJ) Servo
Amplifier
Instruction
Manual
section 6.2
Section 3.1.3
Section 3.1.4
MODE
button
Point table setting
Basic setting
parameters
Gain/filter
parameters
Extension setting
parameters
I/O setting
parameters
Extension setting 2
parameters
Extension setting 3
parameters
Linear/DD motor
setting parameter
Option setting
parameters
Positioning control
parameters
Display and setting of point table data. The screen is displayed only in the point table
method, and is not displayed in other control mode.
Display and setting of basic setting parameters.
Display and setting of gain/filter parameters.
Display and setting of extension setting parameters.
Display and setting of I/O setting parameters.
Section 3.1.5
Section 3.1.6
Display and setting of extension setting 2 parameters.
Display and setting of extension setting 3 parameters.
Display and setting of linear/DD motor setting parameters.
Display and setting of option setting parameters.
Display and setting of positioning control parameters.
Note. When the axis name is set to the servo amplifier using MR Configurator2, the axis name is displayed and the servo status is then
displayed.
3 - 2
Page 76
3. DISPLAY AND OPERATION SECTIONS
www.kavrammuhendislik.com.tr

3.1.2 Status display

The servo status during operation is shown on the 5-digit, 7-segment LED display. Press the "UP" or "DOWN" button to change display data as desired. When the required data is selected, the corresponding symbol is displayed. Press the "SET" button to display that data. At only power-on, however, data appears after the symbol of the status display selected in [Pr. PC36] has been shown for 2 s.
(1) Display transition
After selecting the status display mode with the "MODE" button, pressing the "UP" or "DOWN" button changes the display as shown below.
3 - 3
Page 77
3. DISPLAY AND OPERATION SECTIONS
www.kavrammuhendislik.com.tr
(a) Standard control mode (rotary servo motor)/DD motor control mode
Main axis one cycle current position
Cumulative feedback pulses
Servo motor speed/ linear servo motor speed
Droop pulses
Cumulative command pulses
Command pulse frequency
Analog speed command voltage Analog speed limit voltage
Analog torque limit voltage Analog torque command voltage
Regenerative load ratio
Effective load ratio
Number of tough drive operations
Unit power consumption 1 (1 W unit)
Unit power consumption 2 (1 kW unit)
Unit total power consumption 1 (1 Wh unit)
Unit total power consumption 2 (100 kWh unit)
Current position
Command position
Command remaining distance
Point table/program No./ command station position
Peak load ratio
Instantaneous torque
Position within one-revolution (1 pulse unit)
Position within one-revolution (1000 pulses unit)
ABS counter
Load to motor inertia ratio
Bus voltage
Internal temperature of encoder
Settling time
Oscillation detection frequency
UP
DOWN
Step No.
Analog override voltage
Override level
Cam axis one cycle current value
Cam standard position
Cam axis feed current value
Cam No. in execution
Cam stroke amount in execution
Main axis current value
Main axis one cycle current value
(Note)
Note. Supported by servo amplifiers with software version B7 or later.
Cumulative feedback pulses
3 - 4
Page 78
3. DISPLAY AND OPERATION SECTIONS
www.kavrammuhendislik.com.tr
(b) Fully closed loop control mode
Main axis one cycle current value
(Note 1)
Cumulative feedback pulses
Unit total power consumption 2 (100 kWh unit)
Load-side encoder cumulative feedback pulses
Load-side encoder droop pulses
Load-side encoder information 1 (1 pulse unit)
Load-side encoder information 1 (100000 pulses unit)
Load-side encoder information 2
(Note 2)
Current position
Override level
Main axis one cycle current value
Cumulative feedback pulses
Note 1. The displays in the frames are from the cumulative feedback pulses of positioning
mode to unit total power consumption 2 (100 kWh unit) with some displays
omitted.
2. The displays in the frames are from the current position of positioning mode to
override level with some displays omitted.
3 - 5
Page 79
3. DISPLAY AND OPERATION SECTIONS
www.kavrammuhendislik.com.tr
(c) Linear servo motor control mode
Main axis one cycle current value
(Note 1)
Cumulative feedback pulses
Unit total power consumption 2 (100 kWh unit)
Z-phase counter low
Z-phase counter high
Cumulative feedback pulses
Electrical angle low
Electrical angle high
(Note 2)
Current position
Override level
Main axis one cycle current value
Note 1. The displays in the frames are from the cumulative feedback pulses of positioning
mode to unit total power consumption 2 (100 kWh unit) with some displays
omitted.
2. The displays in the frames are from the current position of positioning mode to
override level with some displays omitted.
3 - 6
Page 80
3. DISPLAY AND OPERATION SECTIONS
www.kavrammuhendislik.com.tr
(2) Status display list
The following table lists the servo statuses that may be shown.
Status display Symbol Unit Description
Feedback pulses from the servo motor encoder are counted and displayed.
The values in excess of ±99999 can be counted. However, the counter Cumulative feedback pulses
Servo motor speed/ linear servo motor speed
Droop pulses E pulse
Cumulative command pulses
Command pulse frequency
Analog speed command voltage
Analog speed limit voltage
Analog torque command voltage
Analog torque limit voltage
Regenerative load ratio L %
Effective load ratio J %
Peak load ratio b %
Instantaneous torque T %
Position within one-revolution
(1 pulse unit)
Position within one-revolution
(1000 pulses unit)
ABS counter LS rev
Load to motor inertia ratio
Bus voltage Pn V The voltage of main circuit converter (between P+ and N-) is displayed.
Encoder inside temperature
C pulse
r r/min
P pulse Not used with the positioning mode. "0" is always displayed.
n kpulse/s Not used with the positioning mode. "0" is always displayed.
F V
U V
Cy1 pulse
Cy2
dC Multiplier
ETh °C Inside temperature of encoder detected by the encoder is displayed.
1000
pulses
shows only the lower five digits of the actual value since the servo
amplifier display is five digits.
Press the "SET" button to reset the display value to zero.
The value of minus is indicated by the lit decimal points in the upper
four digits.
The servo motor speed or linear servo motor speed is displayed.
It is displayed rounding off 0.1 r/min (0.1 mm/s) unit.
The number of droop pulses in the deviation counter are displayed.
The decimal points in the upper four digits are lit for reverse rotation
pulses.
The values in excess of ±99999 can be counted. However, the counter
shows only the lower five digits of the actual value since the servo
amplifier display is five digits.
The number of pulses displayed is in the encoder pulse unit.
Not used with the positioning mode. An applied voltage to the CN1
connector is displayed.
Not used with the positioning mode. An applied voltage to the CN1
connector is displayed.
Voltage of TLA (Analog torque limit) voltage is displayed.
The ratio of regenerative power to permissible regenerative power is
displayed in %.
The continuous effective load current is displayed.
The effective value in the past 15 s is displayed relative to the rated
current of 100 %.
The maximum occurrence torque is displayed.
The highest value in the past 15 s is displayed relative to the rated
torque of 100 %.
The instantaneous torque is displayed.
The value of torque being occurred is displayed in real time considering
a rated torque as 100%.
Position within one revolution is displayed in encoder pulses.
The values in excess of ±99999 can be counted. However, the counter
shows only the lower five digits of the actual value since the servo
amplifier display is five digits.
When the servo motor rotates in the CCW direction, the value is added.
The within one-revolution position is displayed in 1000 pulse
increments of the encoder.
When the servo motor rotates in the CCW direction, the value is added.
The travel distance from the home position is displayed as multi-
revolution counter value of the absolution position encoder in the
absolution position detection system.
The travel distance from the home position is displayed as load side
multi-revolution counter value in the absolution position detection
system.
The estimated ratio of the load inertia moment to the servo motor shaft
inertia moment is displayed.
Control
mode
(Note 1)
CL
CP/BCD
Operation
mode (Note 3)
PS
Lin.
Full.
Standard
DD
3 - 7
Page 81
3. DISPLAY AND OPERATION SECTIONS
www.kavrammuhendislik.com.tr
Status display Symbol Unit Description
Settling time ST ms
Oscillation detection frequency
Number of tough drive operations
Unit power consumption 1 (1 W unit)
Unit power consumption 2 (1 kW unit)
Unit total power consumption 1 (1 Wh unit)
Unit total power consumption 2
(100 kWh unit)
Load-side encoder Cumulative feedback
pulses
Load-side encoder Droop pulses
Load-side encoder information 1
(1 pulse unit)
Load-side encoder information 1
(100000 pulses unit)
Load-side encoder information 2
Z-phase counter low FCy1 pulse
oF Hz Frequency at the time of oscillation detection is displayed.
Td times The number of tough drive functions activated is displayed.
PC1 W
PC2 kW
TPC1 Wh
TPC2 100 kWh
FC pulse
FE pulse
FCy1 pulse
FCy2 100000 pulses
FL5 rev
Settling time is displayed. When it exceeds 1000 ms, "1000" will be displayed.
Unit power consumption is displayed by increment of 1 W. Positive value indicates power running, and negative value indicates regeneration. The values in excess of ±99999 can be counted. However, the counter shows only the lower five digits of the actual value since the servo amplifier display is five digits.
Unit power consumption is displayed by increment of 1 kW. Positive value indicates power running, and negative value indicates regeneration.
Unit total power consumption is displayed by increment of 1 Wh. Positive value is cumulated during power running and negative value during regeneration. The values in excess of ±99999 can be counted. However, the counter shows only the lower five digits of the actual value since the servo amplifier display is five digits.
Unit total power consumption is displayed by increment of 100 kWh. Positive value is cumulated during power running and negative value during regeneration.
Feedback pulses from the load-side encoder are counted and displayed.
The values in excess of ±99999 can be counted. However, the counter shows only the lower five digits of the actual value since the servo amplifier display is five digits.
Press the "SET" button to reset the display value to zero. The value of minus is indicated by the lit decimal points in the
upper four digits.
Droop pulses of the deviation counter between a load-side encoder and a command are displayed. When the count exceeds ±99999, it starts from 0.
Negative value is indicated by the lit decimal points in the upper four digits.
The display shows the average droop pulse value of 128-time sampling at the rate of 444 [μs].
The Z-phase counter of a load-side encoder is displayed in the encoder pulse unit.
For an incremental linear encoder, the Z-phase counter is displayed. The value is counted up from 0 based on the home position (reference mark). For an absolute position linear encoder, the encoder absolute position is displayed.
When the count exceeds 99999, it starts from 0.
The Z-phase counter of a load-side encoder is displayed by increments of 100000 pulses.
For an incremental linear encoder, the Z-phase counter is displayed. The value is counted up from 0 based on the home position (reference mark). For an absolute position linear encoder, the encoder absolute position is displayed.
When the count exceeds 99999, it starts from 0.
When an incremental linear encoder is used as the load-side encoder, the display shows 0.
When an absolute position linear encoder is used as the load­side encoder, the display shows 0.
When a rotary encoder is used as the load-side encoder, the display shows the multi-revolution counter value of the encoder.
The Z-phase counter is displayed in the encoder pulse unit. For an incremental linear encoder, the Z-phase counter is
displayed. The value is counted up from 0 based on the home position (reference mark). For an absolute position linear encoder, the encoder absolute position is displayed.
When the count exceeds 99999, it starts from 0.
Control
mode
(Note 1)
CL
CP/BCD
Operation
mode (Note 3)
PS
Full.
Standard
Lin.
DD
3 - 8
Page 82
3. DISPLAY AND OPERATION SECTIONS
www.kavrammuhendislik.com.tr
Status display Symbol Unit Description
The Z-phase counter is displayed by increments of 100000 pulses.
Z-phase counter high FCy2 100000 pulses
Electrical angle low ECy1 pulse The servo motor electrical angle is displayed.
Electrical angle high ECy2 100000 pulses
STM
μm
10
(STM-4)
10
-3
Current position PoS
10
degree
pulse
(Note 2)
STM
μm
10
(STM-4)
10
-3
Command position CPoS
10
degree
pulse
(Note 2)
STM
μm
10
(STM-4)
Command remaining distance
rn
10
10
-3
degree
pulse
(Note 2)
Point table No./program No./command station
Pno
position
Step No. Sno
Analog override voltage oru V The analog override voltage is displayed.
Override level or %
STM
10
μm
(STM-4)
Cam axis one cycle current value
CCyC
10
10
-3
degree
pulse
(Note 4)
STM
μm
10
(STM-4)
10
-3
10
Cam standard position CbAS
degree
pulse
(Note 2)
For an incremental linear encoder, the Z-phase counter is displayed. The value is counted up from 0 based on the home position (reference mark). For an absolute position linear encoder, the encoder absolute position is displayed.
When the count exceeds 99999, it starts from 0.
The servo motor electrical angle is displayed by increments of 100000 pulses.
When "_ _ 0 _" (positioning display) is set in [Pr. PT26], the current position is displayed as machine home position is 0.
When "_ _ 1 _" (roll feed display) is set in [Pr. PT26], the actual
inch
current position is displayed as start position is 0. The values in excess of ±99999 can be counted. However, the
counter shows only the lower five digits of the actual value since the servo amplifier display is five digits.
When "_ _ 0 _" (positioning display) is set in [Pr. PT26], the command current position is displayed as machine home position is 0.
When "_ _ 1 _" (roll feed display) is set in [Pr. PT26], turning on the start signal starts counting from 0 and a command current position to the target position is displayed in the automatic
inch
mode. The command positions of the selected point table are
displayed at a stop. At the manual mode, the command positions of the selected point table are displayed.
The values in excess of ±99999 can be counted. However, the counter shows only the lower five digits of the actual value since the servo amplifier display is five digits.
Indicates the remaining distance to the command position of the currently selected point table, program and station.
inch
The values in excess of ±99999 can be counted. However, the counter shows only the lower five digits of the actual value since the servo amplifier display is five digits.
For the point table method and program method, the point table and program No. currently being executed are displayed. The selected number is displayed during a temporary stop or manual operation.
For the indexer method, the command next station position is displayed.
The step No. of the program currently being executed is displayed. At a stop, 0 is displayed.
The setting value of the override is displayed. When the override is disabled, 100% is displayed.
The current position in one cycle of CAM axis is displayed with the range of "0 to (cam axis one cycle length - 1)", the cam axis one cycle current value which is calculated from the travel distance inputted to the cam axis. When the simple cam
inch
function is disabled, 0 is always displayed. The values in excess of ±99999 can be counted. However, the
counter shows only the lower five digits of the actual value since the servo amplifier display is five digits.
Refer to section 12.1.8 for detecting point.
A feed current value which is the standard position of the cam operation is displayed. When the simple cam function is disabled, 0 is always displayed.
inch
The values in excess of ±99999 can be counted. However, the counter shows only the lower five digits of the actual value since the servo amplifier display is five digits.
Refer to section 12.1.8 for detecting point.
Control
mode
(Note 1)
CL
CP/BCD
Operation
mode (Note 3)
PS
Full.
Lin.
Standard
DD
3 - 9
Page 83
3. DISPLAY AND OPERATION SECTIONS
www.kavrammuhendislik.com.tr
Control
mode
Status display Symbol Unit Description
STM
10
(STM-4)
Cam axis feed current value
Cam No. in execution Cno
Cam stroke amount in execution
Main axis current value MCMd
Main axis one cycle current value
CCMd
CSTK
MCyC
10
-3
10
degree
pulse
(Note 2)
STM
10
(STM-4)
10
-3
10
degree
pulse
(Note 2)
STM
10
(STM-4)
10
-3
10
degree
pulse
(Note 4)
STM
10
(STM-4)
10
-3
10
degree
pulse
(Note 4)
μm
μm
μm
μm
A feed current value during the cam axis control is displayed. When the simple cam function is disabled, 0 is always displayed.
inch
The values in excess of ±99999 can be counted. However, the counter shows only the lower five digits of the actual value since the servo amplifier display is five digits.
Refer to section 12.1.8 for detecting point.
Cam No. in execution is displayed. When the simple cam function is disabled, 0 is always
displayed. Refer to section 12.1.8 for detecting point.
Cam stroke amount in execution is displayed. When the simple cam function is disabled, 0 is always displayed.
inch
The values in excess of ±99999 can be counted. However, the counter shows only the lower five digits of the actual value since the servo amplifier display is five digits.
Refer to section 12.1.8 for detecting point.
A current value of the input axis (synchronous encoder axis or servo input axis) is displayed. Unit is increment of input axis position. When the simple cam function is disabled, 0 is always
inch
displayed. The values in excess of ±99999 can be counted. However, the
counter shows only the lower five digits of the actual value since the servo amplifier display is five digits.
Refer to section 12.1.8 for detecting point.
The input travel amount of the input axis is displayed within the range of "0 and (cam axis one cycle length setting - 1)". Unit is an increment of cam axis one cycle. When the simple cam
inch
function is disabled, 0 is always displayed. The values in excess of ±99999 can be counted. However, the
counter shows only the lower five digits of the actual value since the servo amplifier display is five digits.
Refer to section 12.1.8 for detecting point.
(Note 1)
CL
CP/BCD
Note 1. CP: Positioning mode (point table method)
BCD: Positioning mode (point table method in the BCD input positioning operation)
This method is available only when the MR-D01 unit is connected. Refer to chapter 12 for details.
CL: Positioning mode (program method)
PS: Positioning mode (indexer method)
2. The unit can be selected from μm/inch/degree/pulse with [Pr. PT01].
3. Standard: Standard (semi closed loop system) use of the rotary servo motor
Full.: Fully closed loop system use of the rotary servo motor
Lin.: Linear servo motor use
DD: Direct drive (DD) motor use
4. Depending on the setting of [Cam control data No. 30 Main shaft input axis selection], the parameters used to set the unit and
feed length multiplication will change as follows. For details of each parameter, refer to section 7.2.9 and 12.1.7 (3).
Setting of [Cam control data No. 30] Parameter for the unit setting
"0" or "1" [Pr. PT01] [Pr. PT03]
"2" [Cam control data No. 14] [Cam control data No. 14]
Parameter for the feed length
multiplication setting
Operation
mode (Note 3)
PS
Standard
Full.
Lin.
DD
3 - 10
Page 84
3. DISPLAY AND OPERATION SECTIONS
www.kavrammuhendislik.com.tr
(3) Changing the status display screen
The status display item of the servo amplifier display shown at power-on can be changed by changing [Pr. PC36] settings. The item displayed in the initial status changes with the control mode as follows.
Positioning (point table method/program
Control mode Status display
Position Cumulative feedback pulses
Position/speed Cumulative feedback pulses/servo motor speed
Speed Servo motor speed
Speed/torque Servo motor speed/analog torque command voltage
Torque Analog torque command voltage
Torque/position
method)
Positioning (indexer method) Cumulative feedback pulses
Analog torque command voltage/cumulative feedback
pulses
Current position
3 - 11
Page 85
3. DISPLAY AND OPERATION SECTIONS
www.kavrammuhendislik.com.tr

3.1.3 Diagnostic mode

The display can show diagnosis contents. Press the "UP" or "DOWN" button to change display data as desired.
(1) Display transition
Sequence
Drive recorder enabled/ disabled display
External I/O signal display
Output signal (DO) forced output
JOG operation
Positioning operation
Motor-less operation
Automatic VC offset
Servo motor series ID
Servo motor type ID
Servo motor encoder ID
For manufacturer adjustment
For manufacturer adjustment
UP
DOWN
Teaching function
Machine analyzer operation
For manufacturer adjustment
Single-step feed
Software version: lower
Software version: upper
3 - 12
Page 86
3. DISPLAY AND OPERATION SECTIONS
www.kavrammuhendislik.com.tr
(2) Diagnosis display list
Name Display Description
Not ready Indicates that the servo amplifier is being initialized
or an alarm has occurred.
Sequence
Drive recorder enabled/disabled display
External I/O signal display Refer to section 3.1.7.
Output signal (DO) forced output
JOG operation
Ready Indicates that the servo was switched on after
completion of initialization and the servo amplifier is ready to operate.
Drive recorder enabled When an alarm occurs in the status, the drive
recorder will operate and write the status of occurrence.
Drive recorder disabled The drive recorder will not operate on the following
conditions.
1.You are using the graph function of MR Configurator2.
2.You are using the machine analyzer function.
3.[Pr. PF21] is set to "-1".
This Indicates the on/off status of external I/O signal.
The upper segments correspond to the input signals and the lower segments to the output signals.
This allows digital output signal to be switched on/off forcibly.
Refer to section 3.1.8 for details.
JOG operation can be performed when there is no command from an external controller.
For details, refer to section 4.5.9 (2) of "MR-J4­_A_(-RJ) Servo Amplifier Instruction Manual".
Test operation mode
Positioning operation
Motor-less operation
Machine analyzer operation
For manufacturer adjustment
Single-step feed
Positioning operation can be performed when there is no command from an external controller.
MR Configurator2 is required to perform positioning operation.
For details, refer to section 4.5.9 (3) of "MR-J4­_A_(-RJ) Servo Amplifier Instruction Manual".
Without connecting the servo motor, output signals or status display can be provided in response to the input device as if the servo motor is actually running.
For details, refer to section 4.5.9 (4) of "MR-J4­_A_(-RJ) Servo Amplifier Instruction Manual".
Merely connecting the servo amplifier allows the resonance point of the mechanical system to be measured.
MR Configurator2 is required to perform machine analyzer operation.
For details, refer to section 11.7 of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual".
This is for manufacturer adjustment.
This function is available only in the point table method and program method. When the positioning operation is executed in accordance with the point table or program set by MR Configurator2, the diagnosis display changes to "d-06" during single­step feed. For other control mode, the display does not change to "d-06". Refer to section 3.1.9 for details.
The status will be displayed with the "MODE" button. The "UP" and "DOWN" buttons are disabled.
3 - 13
Page 87
3. DISPLAY AND OPERATION SECTIONS
www.kavrammuhendislik.com.tr
Name Display Description
Indicates the version of the software.
Software version - Lower
Software version - Upper
Automatic VC offset (Note)
Servo motor series ID
Indicates the system number of the software.
If offset voltages in the analog circuits inside and outside the servo amplifier cause the servo motor setting speed not to be the designated value at VC or OVC of 0 V, a zero-adjustment of offset voltages will be automatically performed. When using the VC automatic offset, enable it in the following procedures.
1) Press the "SET" once.
2) Set the number in the first digit to 1 with "UP"/"DOWN".
3) Press the "SET".
This function cannot be used if the input voltage of VC or OVC is -0.4 V or less, or +0.4 V or more.
When the VC automatic offset is enabled, the following automatic offset voltage is applied according to the setting of [Pr. Po11].
Pr. Po11
_ _ 0 _
_ _ 1 _
Offset voltage to be
automatically adjusted
Offset voltage set with [Pr. PC37] (Servo amplifier side)
Offset voltage set with [Pr. Po21] (MR-D01 side)
Push the "SET" button to show the series ID of the servo motor currently connected.
For indication details, refer to app. 1 of "Servo Motor Instruction Manual (Vol. 3)".
Push the "SET" button to show the type ID of the
Servo motor type ID
Servo motor encoder ID
For manufacturer adjustment
For manufacturer adjustment
Teaching function Refer to section 3.1.10.
servo motor currently connected. For indication details, refer to app. 1 of "Servo Motor
Instruction Manual (Vol. 3)".
Push the "SET" button to show the encoder ID of the servo motor currently connected.
For indication details, refer to app. 1 of "Servo Motor Instruction Manual (Vol. 3)".
This is for manufacturer adjustment.
This is for manufacturer adjustment.
After an operation travels to a target position (MEND (Travel completion) is turned on) with a JOG operation or manual pulse generator operation, pushing the "SET" button of the operation part or turning on TCH (Teach) will import position data. This function is available only in the point table method. For other control mode, the display remains the same.
Note. Even if VC automatic offset is performed and 0 V is inputted, the speed may not completely be the set value.
3 - 14
Page 88
3. DISPLAY AND OPERATION SECTIONS
www.kavrammuhendislik.com.tr

3.1.4 Alarm mode

The current alarm, past alarm history and parameter error are displayed. The lower 2 digits on the display indicate the alarm number that has occurred or the parameter number in error.
Name Display (Note 1) Description
Indicates no occurrence of an alarm.
Current alarm
Alarm history
Indicates the occurrence of [AL. 33.1 Main circuit voltage error]. Flickers at alarm occurrence.
Indicates that the last alarm is [AL. 50.1 Thermal overload error 1 during operation].
Indicates the second last alarm is [AL. 33.1 Main circuit voltage error].
Indicates the third last alarm is [AL. 10.1 Voltage drop in the control circuit power].
Indicates that there is no tenth alarm in the past.
Indicates that there is no eleventh alarm in the past.
Indicates that there is no twelfth alarm in the past.
Indicates that there is no sixteenth alarm in the past.
This indicates no occurrence of [AL. 37 Parameter error].
The data content error of [Pr. PA12 Reverse rotation torque limit].
Parameter error No./point table error No.
(Note 2)
The value of the point table is over the setting range. The error point table No. (intermediate digit "2") and item (lower digit
"d") are displayed. The following shows the items. P: position data, d: motor speed, A: acceleration time constant, b:
deceleration time constant, n: dwell, H: auxiliary function, M: M code
Note 1. If a parameter error and point table error occur simultaneously, the display shows the parameter error.
2. The display shows only when the current alarm is [AL. 37 Parameter error].
3 - 15
Page 89
3. DISPLAY AND OPERATION SECTIONS
www.kavrammuhendislik.com.tr
The following is additional information of alarm occurrence. (1) Any mode screen displays the current alarm.
(2) Even during alarm occurrence, the other screen can be viewed by pressing the button in the operation
area. At this time, the decimal point in the fourth digit remains flickering.
(3) For any alarm, remove its cause and clear it in any of the following methods. (Refer to chapter 8 for the
alarms that can be cleared.)
(a) Switch power off, then on.
(b) Push the "SET" button on the current alarm screen.
(c) Turn on RES (Reset).
(4) Use [Pr. PC18] to clear the alarm history.
(5) Push "UP" or "DOWN" to move to the next history.
3 - 16
Page 90
3. DISPLAY AND OPERATION SECTIONS
www.kavrammuhendislik.com.tr

3.1.5 Point table setting

You can set the target position, servo motor speed, acceleration time constant, deceleration time constant, dwell, auxiliary function and M code.
(1) Display transition
Point table transition
Setting item transition
Point table No. 1
Point table No. 2
Point table No. 3
Point table No. 253
Point table No. 254
Point table No. 255
UP
DOWN
SET button
MODE button
Target position
Servo motor speed
Acceleration time constant
Deceleration time constant
Dwell
Auxiliary function
M code
UP
DOWN
3 - 17
Page 91
3. DISPLAY AND OPERATION SECTIONS
www.kavrammuhendislik.com.tr
(2) Setting list
The following table indicates the point table settings that may be displayed.
Status display Symbol Unit Description
Point table No. Po001
STM
10
(STM-4)
10
-3
Target position PoS
10
degree
pulse
(Note 1)
r/min
Servo motor speed SPd
Acceleration time constant STA ms Set a time until the servo motor rotates at the rated speed. 0 to 20000
Deceleration time constant STb ms
Dwell TLn ms
Auxiliary function H
M code MCd
mm/s
(Note 2)
Specify the point table to set the target position, servo motor speed, acceleration time constant, deceleration time constant, dwell, auxiliary function and M code.
μm
inch
Set the travel distance.
Set the command speed of the servo motor for execution of positioning. The setting value must be within the permissible speed of the servo motor used. If a value equal to or larger than the permissible speed is set, the value is clamped at the permissible speed.
Set a time from when the servo motor rotates at the rated speed until when the motor stops.
This function is enabled when you select the point table by input signal. To disable the dwell, set "0" or "2" to the auxiliary function. To perform
varying-speed operation, set "1", "3", "8", "9", "10", or "11" to the auxiliary function and 0 to the dwell. When the dwell is set, the position command of the selected point table is completed. After the set dwell has elapsed, start the position command of the next point table.
This function is enabled when you select the point table by input signal. (1) When using this point table under the absolute value command method 0: Automatic operation is performed in accordance with a single point table
selected. 1: Executes automatic continuous operation without stopping for the next
point table. 8: Automatic continuous operation is performed to the point table selected at
start-up. 9: Automatic continuous operation is performed to point table No. 1. (2) When using this point table under the incremental value command method 2: Automatic operation is performed in accordance with a single point table
selected. 3: Executes automatic continuous operation without stopping for the next
point table. 10: Automatic continuous operation is performed to the point table selected at
start-up. 11: Automatic continuous operation is performed to point table No. 1. When a different rotation direction is set, smoothing zero (command output) is
confirmed and then the rotation direction is reversed. When "1" or "3" is set to the point table No. 255, [AL. 61] will occur at the time
of point table execution.
This is the code output at the completion of positioning. Outputs the first digit and the second digit of the M code in 4-bit binary
respectively.
Note 1. The unit can be selected from μm/inch/degree/pulse with [Pr. PT01].
2. The unit will be "mm/s" for the linear servo motor control mode.
Indication
range
1 to 255
-999999 to
999999
0
to
Permissible
speed
0 to 20000
0 to 20000
0 to 3, 8 to 11
0 to 99
3 - 18
Page 92
3. DISPLAY AND OPERATION SECTIONS
www.kavrammuhendislik.com.tr
(3) Operation method
POINT
After changing and defining the setting values of the specified point table, the defined setting values of the point table are displayed. After defining the values, pressing the "MODE" button for 2 s or more to discard the changed setting values, and the previous setting values are displayed. Keep pressing the "UP" or "DOWN" button to continuously change the most significant digit of the setting values.
(a) Setting of 5 or less digits
The following example is the operation method at power-on to set "1" to the auxiliary function of the point table No. 1.
Press the "MODE" button four times.
To the next item setting
A point table No. is displayed.
Press the "UP" or "DOWN" button to select point table No. 1.
Press the "SET" button once.
Press the "UP" button five times.
Press the "SET" button twice.
The setting value of auxiliary function of specified point table No. flickers.
Press the "UP" button once.
During flickering, the set value can be changed.
Set using the "UP" or "DOWN" button.
Press "SET" to enter.
Press the "UP" or "DOWN" button to switch to other item of the same point table No. Press the "MODE" button to switch to the next point table No.
3 - 19
Page 93
3. DISPLAY AND OPERATION SECTIONS
www.kavrammuhendislik.com.tr
(b) Setting of 6 or more digits
The following example is the operation method to change the position data of the point table No. 1 to "123456".
Press the "MODE" button four times.
A point table No. is displayed.
Press the "UP" or "DOWN" button to select point table No. 1.
Press the "SET" button once.
Press the "SET" button once.
Setting of upper 1 digit
Press the "MODE" button once.
Setting of lower 4 digits
Press the "SET" button once.
The screen flickers.
Change the setting with the "UP" or "DOWN" button.
Press the "SET" button once.
Enter the setting.
Press the "MODE" button once.
3 - 20
Page 94
3. DISPLAY AND OPERATION SECTIONS
www.kavrammuhendislik.com.tr

3.1.6 Parameter mode

(1) Parameter mode transition
After selecting the corresponding parameter mode with the "MODE" button, pressing the "UP" or "DOWN" button changes the display as shown below.
From alarm mode
Basic setting
parameters
To status display mode
Gain/filter
parameters
Extension setting
parameters
MODE
I/O setting
parameters
Extension setting 2
parameters
Extension setting 3
parameters
Linear/DD motor
setting parameter
Option setting
parameters
Positioning
control parameters
[Pr. PA01]
[Pr. PA02]
[Pr. PA31]
[Pr. PA32]
[Pr. PB01]
[Pr. PB02]
[Pr. PB63]
[Pr. PB64]
[Pr. PC01]
[Pr. PC02]
[Pr. PC79]
[Pr. PC80]
(2) Operation method
(a) Parameters of 5 or less digits
The following example shows the operation procedure performed after power-on to change the control mode to the positioning mode (point table method) with [Pr. PA01 Operation mode]. Press "MODE" to switch to the basic setting parameter screen.
[Pr. PD01]
[Pr. PD02]
[Pr. PD47]
[Pr. PD48]
[Pr. PE01]
[Pr. PE02]
[Pr. PE63]
[Pr. PE64]
[Pr. PF01]
[Pr. PF02]
[Pr. PF47]
[Pr. PF48]
The parameter number is displayed. Press "UP" or "DOWN" to change the number.
[Pr. PL01]
[Pr. PL02]
[Pr. PL47]
[Pr. PL48]
[Pr. Po01]
[Pr. Po02]
[Pr. Po31]
[Pr. Po32]
[Pr. PT01]
[Pr. PT02]
[Pr. PT47]
[Pr. PT48]
Press "SET" twice.
The set value of the specified parameter number flickers.
Press the "UP" button six times.
UP
DOWN
To shift to the next parameter, press the "UP" or "DOWN" button. When changing the [Pr. PA01] setting, change its setting value, then switch power off once and switch it on again to enable the new value.
3 - 21
During flickering, the set value can be changed. Use "UP" or "DOWN". ( _ _ _ 6: Positioning mode (point table method))
Press "SET" to enter.
Page 95
3. DISPLAY AND OPERATION SECTIONS
www.kavrammuhendislik.com.tr
(b) Parameters of 6 or more digits
The following example gives the operation procedure to change the electronic gear numerator to "123456" with [Pr. PA06 Electronic gear numerator].
Press the "MODE" button to switch to the basic setting parameter screen. Press the "UP" or "DOWN" button to select [Pr. PA06].
Press the "SET" button once.
Setting of upper 1 digit
Press the "MODE" button once.
Press the "SET" button once.
…… ……
The screen flickers.
Setting of lower 4 digits
Change the setting with the "UP" or "DOWN" button.
Press the "SET" button once.
Enter the setting.
……
Press the "MODE" button once.
3 - 22
Page 96
3. DISPLAY AND OPERATION SECTIONS
n
A
t
www.kavrammuhendislik.com.tr

3.1.7 External I/O signal display

POINT
The I/O signal settings can be changed using the I/O setting parameters [Pr. PD04] to [Pr. PD28].
The on/off states of the digital I/O signals connected to the servo amplifier can be confirmed.
(1) Operation
The display screen at power-on. Using the "MODE" button, display the diagnostic screen.
Press the "UP" button twice.
……External I/O signal display scree
(2) Display definition
The 7-segment LED segments and CN1 connector pins correspond as shown below.
CN1-10 (Note 1)/
CN1-37 (Note 2)
CN1-45CN1-42
Input signals
lways li
Output signals
CN1-13CN1-14
Note 1. This pin is available with servo amplifiers having software version B3 or later, and manufactured in
November 2014 or later.
2. This pin is available with servo amplifiers having software version B7 or later, and manufactured in
January 2015 or later.
CN1-35 (Note 1)/ CN1-38 (Note 2)
CN1-18 CN1-17
CN1-33
CN1-16 CN1-41
CN1-22CN1-48
CN1-19 CN1-15 CN1-44 CN1-43
CN1-23CN1-25 CN1-49CN1-24
The LED segment corresponding to the pin is lit to indicate on, and is extinguished to indicate off. For each pin signal in control modes, refer to section 2.2 (1).
Light on: on Light off: off
3 - 23
Page 97
3. DISPLAY AND OPERATION SECTIONS
www.kavrammuhendislik.com.tr

3.1.8 Output signal (DO) forced output

POINT
When the servo system is used in a vertical lift application, turning on MBR (Electromagnetic brake interlock) by the DO forced output after assigning it to connector CN1 will release the electromagnetic brake, causing a drop. Take drop preventive measures on the machine side.
Output signals can be switched on/off forcibly independently of the servo status. This function can be used for output signal wiring check, etc. This operation must be performed in the servo off state by turning off SON (Servo-on).
The display screen at power-on. Using the "MODE" button, display the diagnostic screen.
Press the "UP" button three times.
CN1-14
CN1-13
CN1-33
CN1-48
CN1-22
CN1-23
CN1-25
CN1-24
CN1-49
Press the "SET" button for 2 s or more.
……
Switch on/off the signal below the lit segment.
Always lit
……
Indicates on/off of output signal. Definitions of on/off are the same as those for the external I/O signals. (Light on: on, light off: off)
Press the "MODE" button once.
The lit LED moves to the upper LED of CN1-24.
……
Press the "UP" button once.
CN1-24 switches on.
……
(Between CN1-24 and DOCOM are connected.)
Press the "DOWN" button once.
CN1-24 switches off.
……
Press the "SET" button for 2 s or more.
3 - 24
Page 98
3. DISPLAY AND OPERATION SECTIONS
www.kavrammuhendislik.com.tr

3.1.9 Single-Step feed

The test operation mode is designed for checking servo operation. Do not use it
CAUTION
The positioning operation can be performed in accordance with the point table No. or program No. set by MR Configurator2. Select the test operation/single-step feed by the menu of MR Configurator2. When the single-step feed window is displayed, input the following items and operate.
for actual operation. If the servo motor operates unexpectedly, use EM2 (Forced stop 2) to stop it.
POINT
MR Configurator2 is required to perform single-step feed. Test operation cannot be performed if SON (Servo-on) is not turned off.
(a)
(b)
(c) (d) (e) (f)
(c) (d) (e) (f)
Point table operation Program operation
(1) Point table No. or program No. setting
Input a point table No. into the input box (a) "Point table No.", or a program No. into the input box (b) "Program No.".
(2) Forward/reverse the servo motor
Click "Operation Start" (c) to rotate the servo motor.
(3) Pause the servo motor
Click "Pause" (d) to temporarily stop the servo motor. While the servo motor is temporarily stopped, click "Operation Start" (c) to restart the rotation by the amount of the remaining travel distance. While the servo motor is temporarily stopped, click "Stop" (e) to clear the remaining travel distance.
(4) Stop the servo motor
Click "Stop" (e) to stop the servo motor. At this time, the remaining travel distance is cleared. Click "Operation Start" (c) to restart the rotation.
3 - 25
Page 99
3. DISPLAY AND OPERATION SECTIONS
www.kavrammuhendislik.com.tr
(5) Forced stop of the servo motor software
Click "Forced Stop" (f) to make an instantaneous stop. When "Forced Stop" is enabled, the servo motor does not drive even if "Operation Start" is clicked. Click "Forced Stop" again to enable "Operation Start" to be clicked.
(6) Switch to the normal operation mode
Before switching from the test operation mode to the normal operation mode, turn off the servo amplifier.
3 - 26
Page 100
3. DISPLAY AND OPERATION SECTIONS
www.kavrammuhendislik.com.tr

3.1.10 Teaching function

After an operation travels to a target position (MEND (Travel completion) is turned on) with a JOG operation or manual pulse generator operation, pushing the "SET" button of the operation part or turning on TCH (Teach) will import position data. This function is available only in the point table method. For other control mode, the display remains the same.
(1) Teaching preparation
(2) Position data setting method
After an operation travels to a target position (MEND (Travel completion) is turned on) with a JOG operation or manual pulse generator operation, pushing the "SET" button of the operation part or turning on TCH (Teach) will set the positioning address as position data.
Teaching setting initial screen Press the "SET" button for approximately 2 s to switch to the teaching setting mode.
When the lower three digits flicker, press the "UP" or "DOWN" button to select the point table.
When the lower three digits flicker, press the "SET" button to complete the teaching setting preparation. The upper two digits on the display will flicker on completion of proper preparation
When the upper two digits flicker, the current position is written to the selected point table by pressing the "SET" button.
When the upper two digits or the lower two digits flicker, the display returns to the teaching setting initial screen by pressing the "MODE" button. The following shows the conditions for when the teaching function operates.
(a) When the "positioning command method" of [Pr. PT01] is set to absolute value command method (_
_ _ 0)
(b) Home position return completion (ZP (Home position return completion) is turned on)
(c) While the servo motor is stopped (command output = 0, MEND (Travel completion) is turned on)
3 - 27
Loading...