Mitsubishi Electric MELSERVO MRJ2S-B, MELSERVO MRJ2S-B4 Instruction Manual

MITSUBISHI ELECTRIC
MELSERVO
Servo amplifier and motors
Instruction Manual
Art.-No.: 168353 07 06 2006 Ver s i on A
MR-J2S-B/B4
MITSUBISHI ELECTRIC
INDUSTRIAL AUTOMATION
Version Changes / Additions / Corrections
A 06/2006 pdp
Instruction Manual
Servo amplifier MR-J2S-B/B4
Art.-N0.: 168353
About this Manual
The text, illustrations, diagrams and examples in this manual
are solely for clarification purposes for the installation,
handling and operation of the servo motors and amplifiers of the
MELSERVO J2-Super-Series.
If you have any questions concerning the programming and operation of the equipment
described in this manual, please contact your relevant sales office
or department (refer to back of cover).
Current information and answers to frequently asked questions are also
available through the Internet (www.mitsubishi-automation.com).
MITSUBISHI ELECTRIC EUROPE B.V. reserves the right to make
changes both to this manual and to the specifications and design of the
hardware at any time without prior notice.
© 06/2006
Safety Instructions
General safety instructions
For qualified staff only
This manual is intended exclusively for acknowledged and qualified electricians who are totally conversant with the safety standards of electrical drive and automation technology. Project management, installation, setup, maintenance and testing of the equipment must be carried out by an acknowledged and qualified electrician who is totally conversant with the safety standards of electrical drive and automation technology.
Proper use of equipment
MELSERVO-Series equipment is only designed for use in the areas described in this manual. Be sure to comply with all the characteristics stated in this manual. Only additional or supplementary devices recommended by MITSUBISHI ELECTRIC EUROPE may be used.
Any other use or application of the products is deemed to be improper.
Relevant safety regulations
All safety and accident prevention regulations relevant to your specific application must be observed in the system design, installation, setup, maintenance, servicing and testing of these products.
The regulations listed below are particularly important. This list does not claim to be complete; however, you are responsible for knowing and applying the regulations applicable to you.
VDE/EN Standards
– VDE 0100
(Regulations for electrical installations with rated voltages up to 1,000V)
– VDE 0105
(Operation of electrical installations)
– VDE 0113
(Electrical systems with electronic equipment)
– VDE 0160
(Configuration of electrical systems and electrical equipment)
Fire prevention regulations
Accident prevention regulations
– VBG No. 4 (electrical systems and equipment)
Low-voltage regulation
MELSERVO J2-Super I
Special instructions for working with this manual
In this manual special warnings that are important for the proper and safe use of the products are clearly identified as follows:
DANGER:
Personnel health and injury warnings. Failure to observe the precautions described
m
b
NOTE means that incorrect handling may lead to erroneous operation of the servo
here can result in serious health and injury hazards.
CAUTION:
Equipment and property damage warnings. Failure to observe the precautions described here can result in serious damage to the equipment or other property.
amplifier or servo motor. However, there is no risk to the health of the operators or of damage to the equipment or other property.
This note is also used to indicate an other parameter setting, an other function, an other use or it provides information for the employment of additional or supplementary devices.
II
Compliance with EC Directives
EC directives are intended to allow the liberal sales of goods within the EU. With the establishment of “essential safety regulations” the EC directives ensure that technical barriers to trade between member states of the EU are excluded. In the member states of the EU the machine directive (in force since January 1995), the EMC directive (in force since January 1996) and the low-voltage directive (in force since January 1997) of the EC directives determine the guarantee of the presence of fundamental safety requirements and the display of the “CE” mark.
Conformity with EC directives is indicated by the submission of a Declaration of Conformity as well as the display of the “CE” mark on the product, its packaging or its operating instructions.
The above directives relate only to devices and systems and not to single components, unless the components have a direct function for the end user. As a servo amplifier together with a servo motor have to be installed with a controller and other mechanical parts in order to serve a useful purpose for the end user, servo amplifiers do not possess this function. Consequently they can be described as a complex component for which a conformity declaration or the “CE” mark is not required. This position is also supported by CEMEP, the European association of manufacturers of electronic drive technology and electrical machines.
The servo amplifiers do, however, comply with the relevant low-voltage directive, which is a prerequisite for the “CE” mark on machines or accessories in which the servo amplifier is used. To ensure conformity with the requirements of the EMC directive, MITSUBISHI ELECTRIC has produced the manual “EMC INSTALLATION GUIDELINES” (article number: 103944) in which the installation of the servo amplifier, the construction of a control cabinet and other installation tasks are described. Please contact the relevant sales partner who is responsible for you.
MELSERVO J2-Super III
m
Special safety instructions
The following notes on sources of danger should be interpreted as general guidelines for servo drives in association with other devices. These precautions must always be observed in the design, installation and operation of all control systems.
DANGER:
Observe all safety and accident prevention regulations applicable to your specific
application. Installation, wiring and opening of the assemblies, components and devices may only be performed with all power supplies disconnected.
Prior to carrying out any installation work, wiring and opening assemblies, components and devices you must disconnect the power supply to the units and wait for at least 10 minutes. Prior to touching anything measure the residual voltage in condensers, etc. with a voltmeter to ensure that the voltage has been sufficiently reduced.
Never touch the servo amplifier or servo motor or the optional brake resistor during or shortly after operation whilst they are still live. The components can get very hot – there is a risk of getting burned.
Assemblies, components and devices must always be installed in a shockproof housing fitted with a proper cover and protective equipment.
Devices with a permanent connection to the mains power supply must be integrated in the building installations with an all-pole disconnection switch and a suitable fuse.
Ground the servo amplifier and servo motor securely.
Check power cables and lines connected to the equipment regularly for breaks and insulation damage. If cable damage is found, immediately disconnect the equipment and the cables from the power supply and replace the defective cabling.
Before using the equipment for the first time check that the power supply rating matches that of the local mains power.
EMERGENCY OFF facilities in accordance with VDE 0113 must remain effective in all operating modes of the servo motor. The EMERGENCY OFF facility reset function must be designed so that it cannot cause an uncontrolled or undefined restart.
The EMERGENCY OFF facility must be wired so that the electromagnetic brake is also activated during an EMERGENCY OFF.
Residual current protective devices pursuant to DIN VDE Standard 0641 Parts 1–3 are not adequate on their own as protection against indirect contact for installations with servo amplifier. Additional and/or other protection facilities are essential for such installations.
IV
b
Special safety instructions for the devices
CAUTION:
During the installation of servo systems beware of the heat that builds up during
operation. Make sure that there is adequate clearance between the individual modules and enough ventilation to allow the heat to be dissipated.
Never install servo amplifiers or servo motors or the optional brake unit close to easily flammable materials.
When using a servo system always observe strict compliance with electrical characteristics and physical dimensions.
In the event of a defect arising in the servo amplifier, servo motor or optional brake resistor immediately switch the power off to the servo drive, as otherwise it may lead to overheating and self-ignition of the devices.
MELSERVO J2-Super V
Configuration
Control power
supply
Reinforced
insulating
transformer
No-fuse breaker
Magnetic contactor
NFB MC
Power supply
Servo
amplifier
Servo motor
M
S00500C
Environment
Operate the servo amplifier at or above the contamination level 2 set forth in IEC60664-1. For this purpose, install the servo amplifier in a control box which is protected against water, oil, carbon, dust, dirt, etc. (IP54).
Grounding
To prevent an electric shock, always connect the protective earth terminals of the servo amplifier to the protective earth of the control box. Do not connect two or more ground cables to the same protective earth terminal.
VI
Earth terminal
Earth terminal
S00501C
Wiring
The cables are connected via insulated tubular cable sockets to the terminal strip of the servo amplifier.
Crimping terminal
Insulating tube
Cable
S00502C
Use only the connectors designed for it to attach the servo motor to the servo amplifier. The connectors can be ordered as accessories.
MELSERVO J2-Super VII
VIII

Contents

1 Introduction
1.1 Features and configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
1.2 Function block diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
1.2.1 Servo amplifiers 200V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
1.2.2 Servo amplifiers 400V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
1.3 Model overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
1.3.1 Servo amplifiers 200V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
1.3.2 Servo amplifiers 400V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
1.3.3 Rating plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
1.3.4 Servo motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
1.4 Removal and reinstallation of the front cover. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10
1.5 Operating elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-13
1.5.1 Servo amplifier 200V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-13
1.5.2 Servo amplifier 400V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-17
1.5.3 Servo motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-21
1.6 Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-22
1.7 System configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-23
1.7.1 Servo amplifiers 200V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-23
1.7.2 Servo amplifier 400V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-27
Contents
2 Installation
2.1 General environmental conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
2.1.1 Installation of servo amplifiers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
2.1.2 Installation of servo motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
3 Connection
3.1 Connection of servo amplifier. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.1.1 No-fuse circuit breakers, fuses, magnetic contactors and cables . . . . . . . . . . 3-1
3.1.2 Control circuit and main circuit terminal block . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
3.1.3 Signal lines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
3.1.4 Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
3.2 Servo motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
3.2.1 Connection of servo motors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
3.2.2 Motor connector. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
3.3 Internal circuit and common. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14
3.4 Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15
3.5 Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16
3.5.1 Connection example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17
3.6 Alarm occurence timing chart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-20
3.7 Servo motor with electromagnetic brake . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-21
3.8 Examples of standard wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-24
3.9 Station number setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-27
MELSERVO J2-Super IX
Contents
4 Operation
4.1 Points to check prior to starting operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
4.2 Procedures before Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
4.2.1 Start up procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
4.3 Display and Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
4.3.1 Display sequence. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
4.3.2 Indication list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
4.4 Test operation mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
4.4.1 Test operation procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-10
4.5 Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11
4.5.1 Parameter write inhibit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11
4.5.2 Parameter overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
4.5.3 Parameter description:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14
4.6 Gain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-23
4.6.1 Gain adjustment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-23
4.6.2 Gain adjustment using setup-software. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-25
4.6.3 Auto tuning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-26
4.6.4 Manual gain setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-30
4.6.5 Interpolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-33
4.6.6 Differences in auto tuning between MR-J2 and MR-J2S. . . . . . . . . . . . . . . . 4-34
5 Special adjustment functions
5.1 Filter functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
5.1.1 Machine resonance suppression filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
5.1.2 Adaptive vibration suppression control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
5.1.3 Low-pass filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
6 Absolute position detection system
6.1 General description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
6.1.1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
6.1.2 System configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
6.1.3 Communication overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
6.1.4 Battery installation procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
6.1.5 Parameter setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
6.1.6 Absolute position detection data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
7 Accessories
7.1 Optional accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
7.1.1 Regenerative brake option. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
7.1.2 Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-8
7.1.3 Confection diagram of encoder cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-9
7.1.4 Bus cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-10
7.2 Special accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-11
7.2.1 Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-11
X
8 Maintenance and Inspection
8.1 Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8-1
8.2 Life . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
9 Troubleshooting
9.1 Alarms and Warnings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1
9.1.1 Alarms and warning list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1
9.1.2 Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-3
9.1.3 Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-10
10 Specifications
10.1 Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-1
10.1.1Load diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-1
10.1.2Heat loss of servo amplifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3
10.1.3Specifications of electromagnetic brake . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-4
10.1.4Dynamic braking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-6
10.2 Standard specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-9
10.2.1Servo amplifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-9
10.2.2Servo motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-10
10.2.3Torque characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-13
Contents
11 EMC Directives
11.1 Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-1
12 Dimensions
12.1 Servo amplifiers 200V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-1
12.2 Servo amplifiers 400V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-7
12.3 Servo motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-10
12.3.1HC-MFS and HC-KFS series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-10
12.3.2HC-SFS-Serie . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-13
12.3.3HC-RFS series. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-15
12.4 Regenerative brake resistor option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-17
12.5 Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-18
MELSERVO J2-Super XI
Contents
XII
Features and configuration Introduction

1 Introduction

1.1 Features and configuration

Apart from possessing the functions of the servo amplifiers MR-J2-Series, the servo amplifiers MR-J2-Super have additional features and functions.
The servo amplifiers MR-J2S-B and MR-J2S-B4 are designed for operation with a Mitsubishi­Motion-Controller via a serial bus (SSCNET). For this the servo amplifier reads in the position data directly so that it can then execute the positioning process.
Through the specification of speed and direction of rotation via the command unit, precise positioning is possible. To protect the power transistor against over-current resulting from great accelerations or delays or overload the servo amplifier is equipped with a speed limitation feature. The value for speed limitation can be varied and may be specified via an external analogue input or a parameter.
The RS232C or RS422 interface permits serial communications between the servo amplifier and a PC. Using the Windows-supported setup software, functions such as parameter setting, test runs, status display, amplifier setting, etc. can be carried out. By means of real-time auto­tuning it is possible to undertake an automatic adjustment of the amplifier settings to the machine.
The MR-J2-Super series servo motor is equipped with an absolute position encoder which has the resolution of 131072 pulses/rev to ensure more accurate control as compared to the MR-J2 series.
Simply adding a battery to the servo amplifier makes up an absolute position detection system. This makes home position return unnecessary at power-on or alarm occurrence by setting a home position once.
MELSERVO J2-Super 1 - 1
Introduction Function block diagram

1.2 Function block diagram

1.2.1 Servo amplifiers 200V

Power supply 3-phase, 200-230VAC;
1-phase, 230VAC
>
I
>
I
>
I
Servo amplifier
L1 L2 L3
MR-J2S-200B or more
L11 L21
Posi tion
command
input
brake option
Control
+
circuit power
supply
Regenerative
brake
Model position
control
Model position
Actual position
control
Regenerative
PCD
Main circuit
Fan
Base
amplifier
Model speed
Actual speed
control
Model speed
control
Voltage
detection
Over-
current
protection
Virtual
motor
Model torque
Current
control
Virtual
encoder
Current
detection
Servo motor
UU
VV WW
24VDC
Electro-
EMG
magnetic brake
CN2
Encoder
M
MR-BAT
I/F Control
CN1A CN1B
Controller
or
servo amplifier
Servo amplifier
or
termination
connector
RS-232C
CN3
D/A
CON1
Optional battery
(for absolute position
detection system)
Analog monitor
(2 channels)
Personal computer
S001002C
Fig. 1-1: Block diagram for Servo amplifier MR-J2-Super
Up to 750 W a 1-phase power supply is possible. For details of connecting the power supply please see section 3.5.
The connection of terminals shown for the optional regenerative braking resistor applies exclusively to servo amplifiers MR-J2S-350B or smaller. For exact descriptions of the wiring of terminals for other performance classes, please see tab. 3-4.
1 - 2
Function block diagram Introduction

1.2.2 Servo amplifiers 400V

MR-J2S-200B4 or less
Regenerative
brake option
Power supply 3-phase, 380–480VAC
>
I
>
I
>
I
Powe r supply 24VDC
+
Servo amplifier
L1 L2 L3
24V • L
11
0V • L
21
Posi tion
command
input
Fan
Control
circuit power
supply
Regenerative
brake
Model position
control
Model position
Actual position
control
PCD
Main circuit
Base
amplifier
Model speed
control
Model speed
Actual speed
control
Voltage
detection
Over-
current
protection
Virtual
motor
Model torque
Current control
Virtual
encoder
Current
detection
Servo motor
UU
VV WW
24V DC
Electro-
EMG
magnetic brake
CN2CON1
M
Encoder
MR-BAT
I/F Control
Optional battery
(for absolute position
detection system)
Analog monitor
(2 channels)
Personal computer
S001250C
CN1A CN1B
Controller
or
servo amplifier
Servo amplifier
or
termination
connector
RS-232C
CN3
D/A
Fig. 1-2: Block diagram for Servo amplifier MR-J2-Super
When connecting an optional regeneration brake resistor, always remove the lead from across the terminals P and D.
MELSERVO J2-Super 1 - 3
Introduction Function block diagram
MR-J2S-350B4 to 700B4
Regenerative
brake option
Power supply 3-phase, 380–480VAC
>
I
>
I
>
I
Powe r supply 24VDC
+
Servoverstärker
L1 L2 L3
24V • L
11
0V • L
21
Regenerative
Position
command
input
Fan
Control
circuit power supply
brake
Model position
control
Model position
Actual position
control
PCN
Main circuit
Base
amplifier
detection
Model speed
control
Model speed
Actual speed
control
Voltage
Virtual motor
Model torque
Over-
current
protection
Current
control
Virtual
encoder
Current
detection
Servo motor
UU
VV WW
24VDC
Electro-
EMG
magnetic brake
CN2CON1
M
Encoder
MR-BAT
I/F Control
Optional battery
(for absolute position
detection system)
Analog monitor
(2 channels)
Personal computer
CN1A CN1B
Controller
or
servo amplifier
Servo amplifier
or
termination
connector
RS-232C
CN3
D/A
Fig. 1-3: Block diagram for Servo amplifier MR-J2-Super
When connecting an optional regeneration brake resistor, always remove the lead from across the terminals P and C.
1 - 4
Model overview Introduction
MELSERVO
MELSERVO
MELSERVO
MELSERVO

1.3 Model overview

1.3.1 Servo amplifiers 200V

MITSUBISHI
A
0
1
-
S
2
J
-
R
M
I
H
IS
B
U
S
IT
M
A
0
1
-
S
2
J
-
R
M
MR-J2S-100B or less
MR-J2S-500B
MR-J2-B
Series
I
H
IS
B
U
S
T
I
M
A 0
0
5
-
S
2
J
-
R
M
N
E
P
O
N
E
P
O
C
C
N
N
1
1
B
A
)
C N
C
2
N 3
E N C
(
Code
HC-KFS HC-MFS HC-SFS HC-RFS
10 035/13 053/13
MR-J2S-200B/350B
MR-J2S-700B
Compatible servo motors
I H
IS
B U S
IT
M
A 0 0
5
-
S 2 J
­R
M
N
E P O
C
C
N
N
1
1
B
A
)
C N
C
2
N 3
E N C
(
20 23 23 — 40 43 43 — 60 52
70 73 73 — 100 102 — 200 152/202 103/153 350 352 203 500 502 353/503 700 702
S000847T, S000955T, S000913T, S000914T
Fig. 1-4: Model designation of servo amplifiers 200V
MELSERVO J2-Super 1 - 5
Introduction Model overview

1.3.2 Servo amplifiers 400V

MR-J2S-200B4 or less MR-J2S-350B4 and MR-J2S-500B4
MR-J2S- B4
MR-J2S-700B4
Fig. 1-5: Model designation of servo amplifiers 400V

1.3.3 Rating plate

MITSUBISHI
MODEL
POWER : INP UT :
OUTPUT: SERIAL :
MITSUBISHI ELECTRIC CORPORATION
MR-J2S-60B
600 W 3,2 A 3PH + 1PH 200 – 230 V 50Hz
3PH + 1PH 200 – 230 V 60Hz 5,5 A 1PH 230 V 50/60 Hz 170 V 0 – 300 Hz 3,6 A TC3XXAAAAG52
Series
AC SERVO
MADE IN JAPAN
Code Power supply
4 380–480VAC
Compatible
Code
servo motors
HC-SFS
60 524 100 1024 200 1524/2024 350 3524 500 5024 700 7024
S001196C, S001060E, S001061E
Model Capacity
Applicable power supply
Rated output current Serial number
NB
1 - 6
S001001C
Fig. 1-6: Rating plate
Model overview Introduction

1.3.4 Servo motors

HC-MFS series
HC-SFS series
Fig. 1-7: Servo motors
Servo motors 200V
HC - MFS  
HC-KFS series
HC-RFS series
S000849C
Code
Motor series
HC-MFS HC-KFS HC-SFS HC-RFS
——
B
Code Rated speed [r/min]
2 2000 3 3000
Code
05 50 10 1000 31 100 15 1500
Rated speed
2 200 20 2000 4 400 35 3500 5 500 50 5000 7 750 70 7000
Fig. 1-8: Model designation of servo motors 200V
Electromagnetic
brake
[r/min]
Code
Rated
output [W]
MELSERVO J2-Super 1 - 7
Introduction Model overview
Servo motors 400V
HC - SFS 4
Motor series
HC-SFS
Code
——
B
Code Power supply
4400 V
Code
22000
Code
5 500 35 3500 10 1000 50 5000 15 1500 70 7000 20 2000
Fig. 1-9: Model designation of servo motors 400V
Electro-
magnetic
brake
Rated speed
[r/min]
Rated
output [W]
Code
Rated
output [W]
NOTE All motors conform to the following standards: EN, UL, cUL
1 - 8
Model overview Introduction
MITSUBISHI AC SERVO MOTOR
Model
Serial number
Production date
Fig. 1-10: Rating plate
HC-MFS23
SERIAL
DATE
MITSUBISHI ELECTRIC CORPORATION
S00805C
MELSERVO J2-Super 1 - 9
Introduction Removal and reinstallation of the front cover

1.4 Removal and reinstallation of the front cover

For models MR-J2S-200B or larger the front cover must be removed before the battery holder and terminal strips for connecting the power supply of the motor TE1) and control voltage (TE2) are accessible.
DANGER:
Prior to removing the front cover the power supply must be switched off and at least
m
10 minutes must then elapse. This time interval is required for the condensers to discharge to a harmless voltage level after turning off the mains power supply.
Removal the front cover for MR-J2S-200B and MR-J2S-350B
Hold down the removing knob.Pull the front cover toward you.
Abb. 1-11:
Reinstallation the front cover for MR-J2S-200B and MR-J2S-350B
Insert the front cover hooks into the front cover sockets of the servo amplifier.Press the front cover against the servo amplifier until the removing knob clicks.
Removal the front cover
Abb. 1-12:
Reinstallation the front cover
S000513C
1 - 10
S000514C
Removal and reinstallation of the front cover Introduction
Removal the front cover for MR-J2S-500B, MR-J2S-350B4 and MR-J2S-500B4
Hold down the removing knob.Pull the front cover toward you.
Abb. 1-13:
Removal the front cover
S000909C
Reinstallation the front cover for MR-J2S-500B, MR-J2S-350B4 and MR-J2S-500B4
Insert the front cover hooks into the front cover sockets of the servo amplifier.Press the front cover against the servo amplifier until the removing knob clicks.
Abb. 1-14:
Reinstallation the front cover
S000910C
MELSERVO J2-Super 1 - 11
Introduction Removal and reinstallation of the front cover
Removal the front cover for MR-J2S-700B and MR-J2S-700B4
Press the lock on the side of the front cover inwards. Put a finger in the recess in the middle of the front cover and pull it off to the front.
Abb. 1-15:
Removal the front cover
Reinstallation the front cover for MR-J2S-700B and MR-J2S-700B4
Insert the front cover hooks into the front cover sockets of the servo amplifier. Press the front cover against the servo amplifier until the removing knob clicks.
Abb. 1-16:
Reinstallation the front cover
S000911C
1 - 12
S000912C
Operating elements Introduction

1.5 Operating elements

1.5.1 Servo amplifier 200V

Servo amplifier MR-J2S-350B or less
9
8
A
7
B
6
C
5
4
3
E
2
F
1
0
MR-J2S-100B or less
D
MR-J2S-200B and MR-J2S-350B
Fig. 1-17: Servo amplifier MR-J2S-350B or less
No. Name Description Reference
Battery holder Contains the battery (optional) for absolute
Chap. 6
position data backup.
Battery connector (CON1) Used to connect the battery. Section 6.1.4
Display The two-digit, seven-segment LED shows the
Section 4.3
servo status and alarm number.
Station number (CS1) Switch to set the station number of the servo
9
8
A
7
B
6
C
5
D
4
3
E
2
F
1
0
amplifier.
Section 3.9
Tab. 1-1: Operating elements and their meaning
9
8
A
7
B
6
C
5
D
4
3
E
2
F
1
0
S000970C
MELSERVO J2-Super 1 - 13
Introduction Operating elements
 
MR-J2S-100B or less
MR-J2S-200B and MR-J2S-350B
Fig. 1-18: Servo amplifier MR-J2S-350B or less
No. Name Description Reference
Bus cable connector (CN1A) Used to connect the servo system controller or
Bus cable connector (CN1B) Used to connect the subsequent axis servo
Communication connector (CN3)
Name plate Section 1.3.3
Encoder connector (CN2) Used for connection of the servo motor
Charge lamp Lit to indicate that the main circuit is charged.
Main circuit terminal block (TE1)
Control circuit terminal block (TE2)
Protective earth terminal (PE) Module grounding Section 3.4
Fan
preceding axis servo amplifier.
amplifier or termination connector (MR-A-TM) Used to connect a personal computer or output
analog monitor data.
encoder.
While this lamp is lit, do not reconnect the cables.
Used to connect the input power supply and servo motor.
Used to connect the control circuit power supply and regenerative brake option.
Section 3.1.3
Section 3.1.3
Section 3.1.3
Section 3.1.3
Section 3.1.2
Section 3.1.2
S000512C
b
1 - 14
Tab. 1-2: Operating elements and their meaning
CAUTION:
Any mixing up of the connectors CN1A, CN1B, CN3 and CN2 can lead to a shortcircuit and damage to the inputs and outputs.
Operating elements Introduction
Servo amplifier MR-J2S-500B and MR-J2S-700B
9
8
A
7
B
6
C
5
D
4
3
E
2
F
1
0
S000971C
Fig. 1-19: Servo amplifier MR-J2S-500B and MR-J2S-700B
No. Name Description Reference
Battery holder Contains the battery (optional) for absolute
Chap. 6
position data backup. Battery connector (CON1) Used to connect the battery. Section 6.1.4 Display The two-digit, seven-segment LED shows the
Section 4.3
servo status and alarm number. Station number (CS1) Switch to set the station number of the servo
9
8
A
7
B
6
C
5
D
4
3
E
2
F
1
0
amplifier.
Section 3.9
Tab. 1-3: Operating elements and their meaning
MELSERVO J2-Super 1 - 15
Introduction Operating elements
 
 
 
Fig. 1-20: Servo amplifier MR-J2S-500B and MR-J2S-700B
No. Name Description Reference
Bus cable connector (CN1A) Used to connect the servo system controller or
Bus cable connector (CN1B) Used to connect the subsequent axis servo
Communication connector (CN3)
Name plate Section 1.3.3
Encoder connector (CN2) Used for connection of the servo motor
Charge lamp Lit to indicate that the main circuit is charged.
Main circuit terminal block (TE1)
Control circuit terminal block (TE2)
Protective earth terminal (PE) Module grounding Section 3.4
Fan
preceding axis servo amplifier.
amplifier or termination connector (MR-A-TM)
Used to connect a personal computer or output
analog monitor data.
encoder.
While this lamp is lit, do not reconnect the
cables
Used to connect the input power supply and
servo motor.
Used to connect the control circuit power
supply and regenerative brake option.
Section 3.1.3
Section 3.1.3
Section 3.1.3
Section 3.1.3
Section 3.1.2
Section 3.1.2
S000916C
b
1 - 16
Tab. 1-4: Operating elements and their meaning
CAUTION:
Any mixing up of the connectors CN1A, CN1B, CN3 and CN2 can lead to a shortcircuit and damage to the inputs and outputs.
Operating elements Introduction

1.5.2 Servo amplifier 400V

Servo amplifier MR-J2S-60B4 to MR-J2S-200B4
9
8
A
7
B
6
CHARGE
LED1 LED2
Fig. 1-21: Servo amplifier MR-J2S-60B4 to MR-J2S-200B4
5
4
SW1
C
D
3
E
2
F
1
0
S001238C
No. Name Description Reference
Battery holder Contains the battery (optional) for absolute
Chap. 6
position data backup. Battery connector (CON1) Used to connect the battery. Section 6.1.4 Display The five-digit, seven-segment LED shows the
Section 4.3
servo status and alarm number. Charge lamp Lit to indicate that the main circuit is charged.
— While this lamp is lit, do not reconnect the cables
Station number (CS1)
9
8
A
7
B
6
C
5
D
4
3
E
2
F
1
0
Switch to set the station number of the servo amplifier.
Section 3.9
Tab. 1-5: Operating elements and their meaning
MELSERVO J2-Super 1 - 17
Introduction Operating elements
 
Fig. 1-22: Servo amplifier MR-J2S-60B4 to MR-J2S-200B4
No. Name Description Reference
Main circuit connector (CNP1) Used to connect the input power supply Section 3.1.3
Bus cable connector (CN1A) Used to connect the servo system controller
Bus cable connector (CN1B) Used to connect the subsequent axis servo
Encoder connector (CN2) Used for connection of the servo motor
Communication connector (CN3) Used to connect a personal computer or
Name plate Section 1.3.3
Regeneration connector Used to connect the regeneration brake
Control circuit terminal block (CN4) Used to connect the control circuit power
Motor power supply connector (CNP3)
Protective earth terminal (PE) Module grounding Section 3.4
Fan
or preceding axis servo amplifier.
amplifier or termination connector (MR-A-TM)
encoder.
output analog monitor data.
option.
supply. Used to connect the servo motor Section 3.1.2
Section 3.1.3
Section 3.1.3
Section 3.1.3
Section 3.1.3
Section 3.1.2
S001198C
b
1 - 18
Tab. 1-6: Operating elements and their meaning
CAUTION:
Any mixing up of the connectors CN1A, CN1B, CN2 and CN3 can lead to a shortcircuit and damage to the inputs and outputs.
Operating elements Introduction
Servo amplifier MR-J2S-350B4 to MR-J2S-700B4
9
8
A
7
B
6
C
5
D
4
3
E
2
F
1
0
S000971C
Fig. 1-23: Servo amplifier MR-J2S-350B4 to MR-J2S-700B4
No. Name Description Reference
Battery holder Contains the battery (optional) for absolute
Chap. 6 position data backup.
Battery connector (CON1) Used to connect the battery. Section 6.1.4 Display The five-digit, seven-segment LED shows the
Section 4.3 servo status and alarm number.
Station number (CS1) Switch to set the station number of the servo
9
8
A
7
B
6
C
5
D
4
3
E
2
F
1
0
amplifier.
Section 3.9
Tab. 1-7: Operating elements and their meaning
MELSERVO J2-Super 1 - 19
Introduction Operating elements
 
 
 
MR-J2S-350B4 and MR-J2S-500B4
MR-J2S-700B4
Fig. 1-24: Servo amplifier MR-J2S-350B4 to MR-J2S-700B4
No. Name Description Reference
Bus cable connector (CN1A) Used to connect the servo system controller
Bus cable connector (CN1B) Used to connect the subsequent axis servo
Communication connector (CN3) Used to connect a personal computer or
Name plate Section 1.3.3
Encoder connector (CN2) Used for connection of the servo motor
Charge lamp Lit to indicate that the main circuit is
Control circuit terminal block (TE2) Used to connect the control circuit power
Main circuit terminal block
Protective earth terminal (PE) Module grounding Section 3.4
Fan
(TE1)
or preceding axis servo amplifier.
amplifier or termination connector (MR-A-TM)
output analog monitor data.
encoder.
charged. While this lamp is lit, do not reconnect the cables
supply. Used to connect the input power supply,
regenerative brake option and servo motor.
Section 3.1.3
Section 3.1.3
Section 3.1.3
Section 3.1.3
Section 3.1.2
Section 3.1.2
S000916C
b
1 - 20
Tab. 1-8: Operating elements and their meaning
CAUTION:
Any mixing up of the connectors CN1A, CN1B, CN2 and CN3 can lead to a shortcircuit and damage to the inputs and outputs.
Operating elements Introduction

1.5.3 Servo motor

S000882C
Fig. 1-25: Servo motor
No. Name Description Reference
Encoder connector Cable for connection of encoders Section 7.1.3 Power supply connector, brake Power supply cable (U, V, W), Earth cable,
Brake (for motor with electromagnetic brake)
Servo motor shaft Shaft of servo motor Section 2.1.2
Section 3.2
Tab. 1-9: Operating elements and their meaning
MELSERVO J2-Super 1 - 21
Introduction Functions

1.6 Functions

Function Description Reference
High-resolution encoder Motor encoder has a resolution of 131072 pulses/rev. — Absolute position detection
system Adaptive vibration suppression
control
Vibration suppression control Vibrations with an amplitude of ±1 impulse on stopping
Low-pass filter Suppresses high-frequency resonance which occurs
Machine analyzer function By attaching the MR-J2-Super to a PC on which the
Machine simulation Can simulate machine motions on a personal computer
Gain search function Personal computer changes gains automatically and
Real-time auto tuning Automatically adjusts the gain to optimum value if load
Analog monitor output Servo status is output in terms of voltage in real time. Parameter 22 Torque limit Servo motor torque can be limited to any value. Parameter 10, 11 Forced stop The external EMERGENCY OFF signal (EM1) can be
Forced output signal Output signal can be forced on/off independently of the
Test operation mode The servo motor can be operated from the servo
Regenerative brake option Used when the built-in regenerative brake resistor of
Setup software Using a personal computer, parameter setting, test
Merely setting a home position once makes home position return unnecessary at every power-on.
Servo amplifier detects mechanical resonance and sets filter characteristics automatically to suppress mechanical vibration.
the servo motor are suppressed.
as servo system response is increased.
setup software is installed, the frequency characteristics of the mechanical system can be recorded.
screen on the basis of the machine analyser results.
searches for overshoot-free gains in a short time.
applied to the servo motor shaft varies. This function is more powerful on the MR-J2-Super
than on the MR-J2.
released internally.
servo status. Use this function for output signal wiring check, etc.
amplifier without a start signal.
the servo amplifier does not have sufficient regenerative capability for the regenerative power generated.
operation, status display, etc. can be performed.
Chap. 6
Section 5.1.2
Parameter 24
Section 5.1.3
Section 4.6.3
Parameter 23
Section 4.4
Section 4.4
Section 7.1.1
1 - 22
Tab. 1-10: Function description
System configuration Introduction

1.7 System configuration

CAUTION:
To prevent an electric shock, always connect the protective earth (PE) terminal of the
b

1.7.1 Servo amplifiers 200V

servo amplifier to the protective earth (PE) of the control box.
System configuration for MR-J2S-100B or less
Serco system
controller
Power supply
or preceding axis servo amplifier
No-fuse circuit breaker
Magnetic contactor
Servo amplifier
Subsequent
axis servo
amplifier
or
termination
connector
Personal computer (optional)
Protective earth terminal
Regenerative brake option
Encoder cable
Servo motor
power supply
Servo motor
S001003C
Fig. 1-26: Overview of the system configuration for MR-J2S-100B or less
NOTE A listing of options and auxillary equipment can be find in Tab. 1-11 on page 1-26.
MELSERVO J2-Super 1 - 23
Introduction System configuration
System configuration for MR-J2S-200B and MR-J2S-350B
Serco system
controller
Power supply
or
preceding axis
servo
amplifier
Magnetic contactor
No-fuse circuit breaker
Protective earth terminal
Servo amplifier
Subsequent
axis servo
amplifier
or
termination
connector
Personal computer (optional)
Regenerative brake option
Encoder cable
Servo motor
power supply
Servo motor
Fig. 1-27: Overview of the system configuration for MR-J2S-200B and MR-J2S-350B
NOTE A listing of options and auxillary equipment can be find in Tab. 1-11 on page 1-26.
S001004C
1 - 24
System configuration Introduction
System configuration for MR-J2S-500B
Power supply
L1, L2, L3
Regenerative
brake option
Protective earth terminal
L21, L11
No-fuse circuit breaker
Magnetic contactor
Serco system
controller
or preceding axis servo
amplifier
CN1A
P, C
CN1B
Subsequent
axis servo
amplifier
or
termination
connector
CN3
Personal computer (optional)
CN2
Servo motor
power supply
Encoder cable
Servo motor
Fig. 1-28: Overview of the system configuration for MR-J2S-500B
NOTE A listing of options and auxillary equipment can be find in Tab. 1-11 on page 1-26.
S001005C
MELSERVO J2-Super 1 - 25
Introduction System configuration
System configuration for MR-J2S-700B
Power supply
Serco system
controller No-fuse circuit breaker
Magnetic contactor
L21, L11
or preceding axis servo
amplifier
CN1A
CN1B
Subsequent
axis servo
amplifier
or
termination
connector
CN3
P, C
Protective earth terminal
L1, L2, L3
Regenerative
brake option
Servo motor
power supply
Encoder cable
Servo motor
Fig. 1-29: Overview of the system configuration for MR-J2S-700B
Personal computer (optional)
CN2
S001006C
1 - 26
Options and auxiliary equipment Reference
No-fuse circuit breaker Section 3.1.1 Magnetic contactor Section 3.1.1 Regenerative brake option Section 7.1.1 Cables Section 7.1.2 Power factor improving reactor (UE/UA = 400V/230V) Section 7.2.1
Tab. 1-11: Options and auxiliary equipment
System configuration Introduction

1.7.2 Servo amplifier 400V

System configuration for MR-J2S-200B4 or less
Power supply
Serco system
No-fuse circuit breaker
Magnetic contactor
controller
or preceding axis servo
amplifier
CN1A
Servo amplifier
CN1B
CN3
Subsequent
axis servo
amplifier
or
termination
connector
L1, L2, L3
Regenerative
brake option
P, C
Protective earth terminal
Servo motor
power supply
CN4
Encoder cable
Servo motor
Personal computer
Circuit protector
CN2
+
-
Powe r supply 24VDC
S001252C
Fig. 1-30: Overview of the system configuration for MR-J2S-200B4 or less
NOTE A listing of options and auxillary equipment can be find in Tab. 1-12 on page 1-29.
MELSERVO J2-Super 1 - 27
Introduction System configuration
System configuration for MR-J2S-350B4 and MR-J2S-500B4
Power supply
Serco system
controller
or
preceding
No-fuse circuit breaker
Magnetic contactor
L1, L2, L3
Regenerative
brake option
Servo amplifier
P, C
axis servo
amplifier
CN1A
CN1B
CN3
Subsequent
axis servo
amplifier
or
termination
connector
Personal computer
Circuit protector
+
-
Powe r supply 24VDC
Protective earth terminal
CN2
Servo motor
power supply
Encoder cable
Servo motor
S001253C
Fig. 1-31: Overview of the system configuration for MR-J2S-350B4 and MR-J2S-500B4
NOTE A listing of options and auxillary equipment can be find in Tab. 1-12 on page 1-29.
1 - 28
System configuration Introduction
System configuration for MR-J2S-700B4
Power supply
Magnetic
contactor
No-fuse circuit breaker
Servo amplifier
Serco system
controller
or
preceding
axis servo
amplifier
CN1A
CN1B
CN3
Subsequent
axis servo
amplifier
or
termination
connector
Circuit protector
Personal computer
Powe r
+
supply
-
24VDC
L1, L2, L3
Protective earth terminal
Regenerative
P, C
brake option
Servo motor
power supply
CN2
Encoder cable
Servo motor
Fig. 1-32: Overview of the system configuration for MR-J2S-700B4
Options and auxiliary equipment Reference
No-fuse circuit breaker Section 3.1.1 Magnetic contacto Section 3.1.1 Regenerative brake option Section 7.1.1 Cables Section 7.1.2
S001254C
Tab. 1-12: Options and auxiliary equipment
MELSERVO J2-Super 1 - 29
Introduction System configuration
1 - 30
General environmental conditions Installation

2 Installation

2.1 General environmental conditions

CAUTION:
The equipment must be installed in the specified direction. Otherwise, a fault may
b
occur.
Leave specified clearances between the servo amplifier and control box inside walls or other equipment.
Environmental conditions
Ambient temperature during operation 0 to +55°C (non-freezing) 0 to +40°C (non-freezing) Ambient humidity during operation Max. 90% (no condensation) Max. 80% (no condensation) Ambient temperature in storage 20 to +65°C 15 to +70°C Ambient humidity in storage Max. 90% (no condensation) Max. 90% (no condensation) Ambience Indoors (no direct sunlight); no corrosive gas, no inflammable gas, no oil
Altitude above sea level Max. 1000m Protective structure IP00 HC-KFS/MFS: IP55,
Vibration Max. 5.9m/s² (0,6 g) Section 2.1.2
Tab. 2-1: Environmental condition overview
Servo amplifier Servo motor
mist, no dust)
Data
HC-SFS/RFS: IP65
MELSERVO J2-Super 2 - 1
Installation General environmental conditions

2.1.1 Installation of servo amplifiers

CAUTION:
When installing the unit in a control box, prevent drill chips and wire fragments
b
from entering the servo amplifier.
Prevent oil, water, metallic dust, etc. from entering the servo amplifier through openings in the control box or a fan installed on the ceiling.
Installation of one servo amplifier
The servo amplifier must be installed as shown in the following diagram, upright on a vertical and smooth wall.
Control box
A
Fig. 2-1: Installation direction and clearances
Servo amplifier
Servo amplifiers 200V
Servo amplifiers 400V
Control box
C
MITSUBISHI
Top
Bottom
OPEN
L1UL2
D
C N 1 A
C N 2
E N C
()
V
C N 1 B
BB
C N 3
L3
W
Minimal installation clearance [mm]
A B C D
75
70
10 40
S000520C
40
120
2 - 2
Tab. 2-2: Minimal installation clearance
The distance A for the servo amplifier MR-J2S-700B4 is 70mm.
General environmental conditions Installation
Installation of two or more servo amplifiers and other equipment
Leave a large clearance between the top of the servo amplifier and the internal surface of the control box. Due to the power loss of the units it must be ensured that the internal temperature of the control cabinet does not exceed the ambient temperature of +55 °C allowed for the servo amplifier. If necessary, the control cabinet will have to be ventilated. In this case, however, the servo amplifier must not be installed in the flow of coolant of some other operating agent. The fan(s) in the forced-cooling housing must be installed taking into account the provision of an optimum supply of cool air.
For details of the heat dissipation of control cabinets and housings please see the manufacturer’s specifications.
When using heat generating equipment such as the regenerative brake option, install them with full consideration of heat generation so that the servo amplifier is not affected.
C
MITSUBISHI
MITSUBISHI
OPEN
C
C
N
N
1
1
A
B
A AB
C N 2
E N C
()
L1UL2
D
VL3W
C N
3
Fig. 2-2: Installation of two or more servo amplifiers
Servo amplifier
Servo amplifiers 200V
Servo amplifiers 400V
A B C D
30 10 100
Tab. 2-3: Minimal installation clearance
OPEN
()
L1UL2
VL3W
S000521C
Minimal installation clearance [mm]
40
120
MELSERVO J2-Super 2 - 3
Installation General environmental conditions

2.1.2 Installation of servo motors

Safety instructions
CAUTION:
Do not hold the cable, shaft or encoder to carry the servo motor. Otherwise, a fault
b
or injury may occur.
Securely fix the servo motor to the machine. If fixed insecurely, the servo motor will come off during operation, leading to injury.
When coupling the shaft end of the servo motor, do not subject the shaft end to impact, such as hammering. The encoder may become faulty.
Secure the motor shaft and rotating parts against access through appropriate covers.
Do not subject the servo motor shaft to more than the permissible load. Otherwise, the shaft may break, leading to injury.
Instructions for the protection of the servo motor shaft
When mounting a pulley to the servo motor shaft provided with a keyway, use the screw hole in the shaft end (refer fig. 2-3). To fit the pulley, first insert a double-end stud into the screw hole of the shaft, put a washer against the end face of the coupling, and insert and tighten a nut to force the pulley in. Under no circumstances must you use a hammer for installation work on the servo motor shaft.
Servo motor
Nut
Double-end stud
Pulley
Fig. 2-3: Installing a pulley
For servo motors with the shaft without a keyway, use a friction coupling or the like.
When removing the pulley, use a pulley remover to protect the shaft or the motor from impact.
The orientation of the encoder on the servo motor cannot be changed.
Washer
S000522C
2 - 4
General environmental conditions Installation
For installation of the servo motor, use spring washers, etc. and fully tighten the bolts so that they do not become loose due to vibration.
When using a pulley, a chain wheel or synchronising pulley select a diameter that will not exceed the permissible radial load (see table below).
Do not use any inelastic, rigid connections that may lead to excessive bending moments to the shaft and thus cause the shaft to break.
HC-MFS
HC-KFS
HC-SFS
HC-RFS
Servo motor
053/13 25 88 59
23/43 30 245 98
73 40 392 147
053/13 25 88 59 23/43/73 30 245 98 52 to 152
524 to 1524
202 to 702
2024 to 7024
103 to 203 45 686 196
353/503 63 980 392
L [mm] Permissible radial load [N] Permissible thrust load
55 980 490
79 2058 980
Tab. 2-4: Permitted radial load and axial load of servo motor
[N]
L
Radial load
L: Distance from flange mounting surface to load center
Fig. 2-4: Directions of action of forces on the servo motor
Thrust load
S000523C
MELSERVO J2-Super 2 - 5
Installation General environmental conditions
Vibration
Servo motor Vibration
fig. 2-6
2
(5g)
2
(5g)
)
2
(2.5g)
2
(2.5g)
2
(3g)
HC-KFS HC-MFS
HC-SFS52 to 152 HC-SFS524 to 1524 HC-RFS
HC-SFS202, 352 HC-SFS2024, 3524
HC-SFS502, 702 HC-SFS5024, 7024
X, Y: 49m/s (refer fig. 2-6)
X, Y: 24.5m/s2 (2.5g) (refer
X: 24.5m/s Y: 49m/s
(refer fig. 2-6)
X: 24.5m/s Y: 29.4m/s
(refer fig. 2-6)
Fig. 2-5: Vibration resistance of the servo motors
Servo motor
X
Fig. 2-6: Vibration directions on the servo motor
200
100
80
60 50 40
30
Y
S000518C
2 - 6
20
Vibration amplitude in X and Y direction [mm]
350030002500200015001000500
Speed [r/min]
S000519C
Fig. 2-7: Graphic representation of the vibration amplitudes of the servo motor
General environmental conditions Installation
Protection from oil and water
When the gear box is mounted horizontally, the oil level in the gear box should always be lower than the oil seal lip on the servo motor shaft. If it is higher than the oil seal lip, oil will enter the servo motor, leading to a fault. Make sure there is a ventilation hole in the gear box to prevent any pressure build up in the gear box.
The following table presents an overview of the minimum clearances between the oil level and the servo motor shaft centre:
Servo motor Height above oil level [mm]
52 to 152
HC-SFS
HC-RFS 103 to 503 20
524 to 1524
202 to 702
2024 to 7024
20
25
Tab. 2-5: Minimum clearances between the oil level and the servo motor shaft centre
b
Gear
Servo motor
Height above oil level
h
Lip
V ring
S000525C
Fig. 2-8: Arrangement
CAUTION:
The servo motors in the HC-MFS- and KC-KFS-Series do not have any oil seal on the shaft. Here the sealing must occur on the gear side.
MELSERVO J2-Super 2 - 7
Installation General environmental conditions
When installing the servo motor horizontally, face the power cable and encoder cable downward. When installing the servo motor vertically, lay the cables with an adequate cable trap to avoid mechanical load on the cable and motor.
Cable trap
S000526C
Fig. 2-9: Installing the servo motor horizontally and vertically showing cable trap
Make sure that the cables leading to the servo motor does not pass through oil or water. Due to the effects of capillarity, oil or water could get into the motor via the cables.
Box
Servo motor
Oil-/water pool
Incorrect! Cable trap
S000527C
Fig. 2-10: Do not lay the cables to the motor in oil or water
When the servo motor is to be installed with the shaft end at top, provide measures so that it is not exposed to oil and water entering from the machine side, gear box, etc.
2 - 8
General environmental conditions Installation
Gear
Lubricating oil
Servo motor
S000528C
Fig. 2-11: Installation of the motor with the shaft at the top
In general the installation of the servo motor can be in any desired location or position. When the servo motor with electromagnetic brake is installed with the shaft end at top, the brake plate may generate sliding sound but it is not a fault.
Laying the cables
The way of clamping the cable must be fully examined so that flexing stress and the cable's own weight stress are not applied to the cable connection.
In situations where the servo motor moves, the cable must not be under tension. If the cables are laid in a cable duct, there must be a sufficient amount of play in the cable lengths of the motor and encoder cables.
The flexing service life of encoder cables is presented in fig. 2-12. The useful service life of the encoder cable MR-JCCBLmM-L will be at an end after flexing 5000 times with a flexing radius of 60 mm. In practice you should plan to have a certain safety margin. For installation on a machine where the servo motor will move, the flexing radius should be made as large as possible.
8
1 × 10
Number of flexings
5 × 10
1 × 10 5 × 10
1 × 10 5 × 10
1 × 10 5 × 10
1 × 10 5 × 10
7
7
6
6
5
5
4
4
3
High-flexible
encoder cable
MR-JCCBLM-H MR-JHSCBLM-H MR-ENCBLM-H
Standard encoder cable
MR-JCCBLM-L MR-JHSCBLM-L
3
1 × 10
4 7 10 20 40 70 100 200
Flexing radius [mm]
S000529C
Fig. 2-12: Number of flexings depending on the flexing radius
MELSERVO J2-Super 2 - 9
Installation General environmental conditions
2 - 10
Connection of servo amplifier Connection

3 Connection

3.1 Connection of servo amplifier

CAUTION:
Only the voltage stated may be connected to the relevant terminals. An incorrect
b

3.1.1 No-fuse circuit breakers, fuses, magnetic contactors and cables

voltage can lead to damage to the servo amplifier.
The terminal strips for mains and motor connections become visible after opening the flap on the front cover (MR-J2S-100B or less) or after removing the front cover (MR-J2S-200B or larger and MR-J2S-350B4 or larger). Mains power is connected via terminals L1, L2 and L3. In the case of 200V models up to 750W a 1-phase connection is possible.
Connect the motor to the output terminals U, V and W. For a description of the terminals for the power connections see Tab. 3-4 and Tab. 3-5 on page
3-4. The following accessories in this section are to be used for the operation of the servo amplifier
and servo motor:
Injection Dimensions [mm²]
Servo amplifier
MR-J2S-10B NF30, 5 A 16 A MR-J2S-20B NF30, 5 A 16 A MR-J2S-40B NF30, 10 A 16 A MR-J2S-60B NF30, 15 A 16 A MR-J2S-70B NF30, 15 A 16 A MR-J2S-100B NF30, 15 A 16 A MR-J2S-200B NF30, 20 A 20 A
Servo amplifier 200V
MR-J2S-350B NF30, 20 A 25 A MR-J2S-500B NF50, 50 A 50 A MR-J2S-700B NF100, 75 A 50 A MR-J2S-60B4 NF30, 5 A 16 A MR-J2S-100B4 NF30, 10 A 16 A MR-J2S-200B4 NF30, 15 A 16 A MR-J2S-350B4 NF30, 20 A 20 A MR-J2S-500B4 NF30, 20 A 25 A
Servo amplifier 400V
MR-J2S-700B4 NF50, 50 A 50 A
No-fuse ciruit breaker
Fuse
Magnetic
contactor
S-N10 S-N10 S-N10 S-N10 S-N10 S-N10 S-N18 S-N20 S-N35 S-N50 S-N10 S-N10 S-N10 S-N18 S-N20 S-N35
L1-L2-L3 L11-L21 U-V-W
1.5 1.5 1.5 1.5
1.5 1.5 1.5 1.5
1.5 1.5 1.5 1.5
1.5 1.5 1.5 1.5
1.5 1.5 1.5 1.5
1.5 1.5 2.5 1.5
2.5–4 1.5 4 1.5 4–6 1.5 6 1.5 4–6 1.5 6 1.5
10 1.5 10 1.5
1.5 1.5 1.5 1.5
1.5 1.5 1.5 1.5
1.5 1.5 1.5 1.5
2.5–4 1.5 4 1.5 4–6 1.5 6 1.5 4–6 1.5 6 1.5
Electro-
magnetic
brake
Tab. 3-1: Required equipment
MELSERVO J2-Super 3 - 1
Connection Connection of servo amplifier
L
L
P
C
D
L
L
P
C
D
L
N
L
P
C
D
N
W
a
C
PNUVW

3.1.2 Control circuit and main circuit terminal block

Connectors
Servo amplifier
MR-J2S-10B to MR-J2S-60B
Main circuit/control circuit/
brake restistor/brake unit
Front of
L1UL2VL3
W
device
Back of
device
Protective earth PE
TE2TE1
S001222C S000539C
TE2TE1
MR-J2S-70B MR-J2S-100B
MR-J2S-200B MR-J2S-350B
Servo amplifier 200V
MR-J2S-500B
MR-J2S-700B
TE1
TE1
TE2
PE
S000919C
L1UL2VL3
Front of
device
W
Back of
device
S001223C S000540C
TE2TE1
TE2
TE1
L1 L2 L3 U V
PE
S000920C S001224C S000541C
L1 L2 L3
PE
PE
TE2
S000921C S001225C S000925C
TE2
TE1
S000922C S001226C S000927C
L1 L2 L3
C P N U V
W
L11L21 DPC
TE2TE1
L11 L21
TE2TE1
L11 L21
Mounting screw for intern brake resistor cable in the event it is not used
Mounting screw for internal brake resistor cable in the event it is not used
Tab. 3-2: Terminals of servo amplifier 200V
3 - 2
Connection of servo amplifier Connection
a
C
PNUVW
Connectors
Servo amplifier
Main circuit/control circuit/
brake restistor/brake unit
Protective earth PE
MR-J2S-60B4 to MR-J2S-200B4
MR-J2S-350B4 to MR-J2S-500B4
Servo amplifier 400V
MR-J2S-700B4
TE1
PE
CNP1
CNP2
CNP3
24V L11
L21
C N 1 B
C N 3
0V
TE2
L1
L2
L3
CNP1 CNP3 CN4CNP2
P
C
D
N
L1 L2 L3
C P N U V
U
24 V/L11
V
0 V/L21
W
TE2TE1
24 V/L11 0 V/L21
Mounting screw for intern brake resistor cable in the event it is not used
CHARGE
OPEN
C N 1 A
L1
L2
L3
C
P
N 2
(
E
C
N C
D
(
N
U
V
W
PE
S001204C S001227C S001208C
W
S000921C S001228C S000925C
Mounting screw for internal brake resistor cable in the event it is not used
TE2
TE2TE1
24 V/L11 0 V/L21
TE1
PE
L1 L2 L3
S000922C S001229C S000927C
Tab. 3-3: Terminals of servo amplifier 400V
MELSERVO J2-Super 3 - 3
Connection Connection of servo amplifier
Main circuit terminal overview for MR-J2S-60B to MR-J2S-700B
Termin al Signal Description
L1, L2, L3
L11, L21 Control circuit power
N Brake unit option When using the optional brake unit, connect it across the terminals P and N.
P, C, D Regenerative brake
U, V, W Servo motor output Connect to the servo motor power supply terminals U, V, W. PE Protective earth Connect this terminal to the protective earth (PE) terminals of the servo
Main circuit power supply
supply
option/brake unit
The rated voltage range is 3-phase 200 to 230V AC, 50/60 Hz. Up to 750 W a 1-phase power supply is possible.
The rated voltage range is 1-phase 200 to 230V AC, 50/60 Hz. Here L11 must be equal in phase to L1 and L21 equal in phase to L2.
Before connecting the optional brake unit, you must disconnect the internal brake resistor across the terminals P and C. Do not connect a optional brake unit to the servo amplifier of MR-J2S-350B or less.
MR-J2S-350B or less
The terminals P and D are factory-connected. When connecting an optional regenerative brake, always disconnect the cable connection across P and D. Connect the optional regenerative brake across the terminals P and C. Do not connect a optional brake unit to the servo amplifier of MR-J2S-350B or less.
MR-J2S-500B or more
When connecting an optional regenerative brake or brake unit, always disconnect the cable connection across P and C of the internal brake resistor. Connect the optional regenerative brake across the terminals P and C. When using the optional brake unit, connect it across the terminals P and N.
motor and control box for grounding.
Tab. 3-4: Signal overview (MR-J2S-60B to MR-J2S-700B)
Main circuit terminal overview for MR-J2S-60B4 to MR-J2S-700B4
Termin al Signal Description
L1, L2, L3 24V/L11,
0V/L21
N Brake unit option When using the optional brake unit, connect it across the terminals P and N.
P, C, D Regenerative brake
U, V, W Servo motor output Connect to the servo motor power supply terminals U, V, W. PE Protective earth Connect this terminal to the protective earth (PE) terminals of the servo
Main circuit power supply Control circuit power
supply
option/brake unit
The rated voltage range is 3-phase 380 to 480V AC, 50/60Hz. Connect a 24VDC source here. Make sure that the plus pole of the DC
source is connected to terminal 24V/L11 and the minus pole of the DC source to terminal 0V/L21.
Before connecting the optional brake unit, you must disconnect the internal brake resistor across the terminals P and C. Do not connect a optional brake unit to the servo amplifier of MR-J2S-200B4 or less.
MR-J2S-200B4 or less
The terminals P and D are factory-connected. When connecting an optional regenerative brake, always disconnect the cable connection across P and D. Connect the optional regenerative brake across the terminals P and C. Do not connect a optional brake unit to the servo amplifier of MR-J2S-200B4 or less.
MR-J2S-350B4 or more
When connecting an optional regenerative brake or brake unit, always disconnect the cable connection across P and C of the internal brake resistor. Connect the optional regenerative brake across the terminals P and C. When using the optional brake unit, connect it across the terminals P and N.
motor and control box for grounding.
3 - 4
Tab. 3-5: Signal overview (MR-J2S-60B4 to MR-J2S-700B4)
Connection of servo amplifier Connection

3.1.3 Signal lines

The servo amplifier has four signal connectors. You will find the pin configuration of the connectors on the next page.
CN1A
1
2
RD
4
TD
6
8
EMG EMG*
10
11
12
LG LG LG
RD*
3
13
14
TD*
5
15
16
LGBTLG
7
17
18
9
19
20
2
RDLGRD*
4
TD
6
8
10
CN2
1
12
LG LG
3
14
5
16
7
18
MR MRR
P5
9
20
BAT
P5
11
13
15
17
19
P5
2
RXD
4
MO1
6
LA
8 LZLBLZR 10
VDD
The connector frames are connected with the PE (earth) terminal inside the servo amplifier.
2
LG
4
6
MDLGMDR
8
10
CN1B
1
11
12
3
13
14
TD*
5
15
16
LG
LG
7
17
18
EMG EMG*
9
19
20
BT
CN3
1
11
12
LG
LG
TXD
3
13
14
MBRSG
MO2
5
15
16
COM
LAR
7
17
18
LBR
9
19
20
EM1
S000974C
Fig. 3-1: Signal connector
NOTE The display of the pin configuration in fig. 3-1 shows the view from the soldering tag side.
MELSERVO J2-Super 3 - 5
Connection Connection of servo amplifier
Interface explanations
Connector Name Description
CN1A
CN1B
CN2
CN3
Connector for bus cable from preceding axis.
Connector for bus cable to next axis
Encoder connector Used for connection with the servo motor encoder.
Communication connector
Used for connection with the controller or preceding-axis servo amplifier.
Used for connection with the next-axis servo amplifier or for connection of the termination connector.
Used for connection with the personal computer. Serves as an I/O signal connector when the personal computer is not used.
Tab. 3-6: Description of interfaces CN1A, CN1B CN2 and CN3
Input signal
Signal Symbol Pin-No. Description I/O
Turning off EM1 puts the servo motor in a forced
Forced stop
EM1 CN3-20
stop status, in which the servo is switched off and the dynamic brake is operated to stop the servo motor. Turn on EM1 in the forced stop status to reset this status.
DI-1
Tab. 3-7: Input signal
Output signals
Signal Symbol Pin-No. Description I/O
Electromagnetic brake interlock
Encoder A-phase pulse (Differential outputs)
Encoder B-phase pulse (Differential outputs)
Encoder Z-phase pulse (Differential outputs)
Analog monitor 1
Analog monitor 2
MBR CN3-13
LA
LAR
LB
LBR
LZ
LZR
MO1 CN3-4
MO2 CN3-14
CN3-6
CN3-16
CN3-7
CN3-17
CN3-8
CN3-18
With switched off signal “Servo ON” MBR-SG is opened.
Outputs pulses per servo motor revolution set in parameter No. 38. In forward rotation of the servo motor, the encoder B-phase pulse lags the encoder A-phase pulse by a phase angle of π/2.
The zero-phase signal of the encoder is output.
The data set for CH1 in parameter 22 are output as analog via MO1-LG.
The data set for CH2 in parameter 22 are output as analog via MO1-LG.
Analog
output
Analog
output
Tab. 3-8: Output signals
Power supply
Signal Symbol Pin-No. Description
24VDC output
Common for digital inputs
Common for control signals
Shield
VDD CN3-10
SG CN3-3
COM CN3-5
LG
SD Plate
CN3-1
CN3-11
Internal voltage source output voltage at the terminals VDD R SG: +24VDC ± 10 %. Output current: max. 80mA
Common reference point for the digital inputs, voltaically separated from terminal LG
Common for analog outputs MO1 and MO2
Connect the shield of signal cable here.
DO1
DO2
DO2
3 - 6
Tab. 3-9: Power supply
Connection of servo amplifier Connection

3.1.4 Interfaces

The connection of external periphery to the interface described in section 3.1.3 is covered in the following.
Digital input interface DI-1
Give a signal with a relay or open collector transistor.
Servo amplifier
approx. 5mA
Tr
U
≤≤ 1V
CES
I 100µA
CEO
Fig. 3-2: External device connection
VDD
COM
EM1
SG
24VDC
4.7k
S001007C
MELSERVO J2-Super 3 - 7
Connection Connection of servo amplifier
Digital output interface DO-1
Via this interface a control lamp, a relay or an photocoupler may be addressed, for example. Provide a diode (D) for an inductive load, or an inrush current suppressing resistor (R) for a lamp load. (Permissable current: 40mA, inrush current: 100mA).
Inductive Load
Servo amplifier
b
24 V DC
VDD
MBR
Tr
D
SG
S001008C
Fig. 3-3: Inductive load connection
CAUTION:
When connecting an inductive load be sure to observe the correct polarity of the recovery diode D. Connecting it backwards could cause the servo amplifier to be damaged.
Lamp connection
Fig. 3-4: Lamp connection
Servo amplifier
24 V DC
VDD
R
MBR
Tr
SG
S001009C
3 - 8
Connection of servo amplifier Connection
Emulated encoder output
Differential output max. output current: 35mA
Servo amplifier
LA
(LB, LZ)
LAR
(LBR, LZR)
LG
SD SD
Fig. 3-5: Example
AM26LS32 or equivalent
150
T
π
/2
>400 s
µ
Servo amplifier
LA
(LB, LZ)
LAR
(LBR, LZR)
LZ/LZR signal varies ±3/8T on its leading edge.
1,2k
High-speed
photocoupler
&
S000553C
Fig. 3-6: Time response of the output signals
Analog output
Servo amplifier
MO1
(MO2)
LG
SD
Fig. 3-7: Example for an interface
Output ±10V/1mA
10k
A
S000554C
S000556C
MELSERVO J2-Super 3 - 9
Connection Servo motor

3.2 Servo motor

3.2.1 Connection of servo motors

CAUTION:
b
Ground the servo amplifier and servo motor securely.
To prevent an electric shock, always connect the protective earth terminal (PE) of the servo amplifier marked with , with the protective earth of the control box.
Connect the cables to the servo amplifier and servo motor with the right terminals and the correct phases (U, V, W) . Otherwise the servo motor will not work correctly.
Do not connect AC power supply directly to the servo motor. Otherwise, a fault may occure.
Connect the servo motors via corresponding power supply connector.For grounding, connect the earth cable of the servo motor to the protective earth (PE)
terminal of the servo amplifier. Simultaneouse connect the ground cable of the servo amplifier to the earth via the protective earth of the control box. Refer fig. 3-8.
When using a servo motor with brake then it must be connected via an external voltage
source of 24VDC.
Control box
Servo amplifier
Servo motor
PE terminal
S000557C
Fig. 3-8: Protective earth connection
3 - 10
Servo motor Connection

3.2.2 Motor connector

Servo motor series HC-KFS (B)/HC-MFS (B)
Encoder connector
Brake connector
Fig. 3-9: Servo motor series HC-KFS (B) and HC-MFS (B)
Without
electromagnetic
brake
13
42
Power supply connector
MR-PWCNK1
Pin Signal
1U Red 2VWhite 3WBlack
Protective
4
earth
Cable
color
Green/
Yellow
Power supply connector
Pin Signal
1U Red 2V White 3W Black
4
5B1 6B2
With
electromagnetic
brake
14
562
3
MR-PWCNK2
Protective
earth
Cable
color
Green/
Yellow
— —
Power supply connector Red: Phase U White: Phase V Black: Phase W Green/yellow: Protective earth
S000883C
1
2
3
MRR
5
MDR
8
LG
BAT
6
9
SHD
MR
4
MD
7
P5
Encoder connector
View on the crimp terminals
S000981C
Fig. 3-10: Connections of power supply, encoder and electromagnetic brake
24VDC no polarity
MELSERVO J2-Super 3 - 11
Connection Servo motor
Servo motor series HC-SFS/HC-RFS
Power supply connectors Brake connector Encoder connector
S000562C
Fig. 3-11: Servo motor series HC-SFS/HC-RFS
Servo motor
HC-SFS52
HC-SFS102
HC-SFS152
HC-SFS202
HC-SFS352
HC-SFS502
HC-SFS702 MR-PWCNS3
HC-RFS103
Servo motor 200V
HC-RFS153
HC-RFS203
HC-RFS353
HC-RFS503
HC-SFS524
HC-SFS1024
HC-SFS1524
HC-SFS2024
HC-SFS3524
HC-SFS5024
Servo motor 400V
HC-SFS7024 MR-PWCNS3
Power supply Encoder Electromagnetic brake
MR-PWCNS1
MR-PWCNS2
MR-PWCNS1
MR-PWCNS2
MR-PWCNS1
MR-PWCNS2
Connectors
In the power supply connector
MR-BKCN
MR-J2CNS (Set)
In the power supply connector
In the power supply connector
MR-J2CNS (Set)
MR-BKCN
3 - 12
Tab. 3-10: Power supply and encoder interfaces
Servo motor Connection
A
BM
G
F
E
A
B
H
C
D
FA
G
BE
D
C
D
A
BC
CL
N
DK T P
EJ S R
FH
G
AB
Power supply
connector
MR-PWCNS1
Pin Signal
AU BV
CW
Protective
D
earth E— F—
GB1 HB2
Power supply
connector
MR-PWCNS2
Pin Signal
AU BV CW
Protective
D
earth EB1 FB2 G—
Power supply
connector
MR-PWCNS3
Pin Signal
AU BV CW
Protective
D
earth
Pin Signal Pin Signal
AMDK — BMDRL — CMRM — DMRRN SD E—P— FBATR LG
GLGSP5
H—T— J—
Encoder
MR-J2CNS (Set)
Electro-
megnetic
brake
MR-BKCN
Pin Signal
AB1 BB2
S000898C
Fig. 3-12: Connections of power supply, encoder and electromagnetic brake
24VDC no polarity For the motors HC-SFS52B/102B/152B and motors HC-RFS103B/153B/203B/353B/503B the attachment for the electromagnetic brake is integrated into the power supply connector.
MELSERVO J2-Super 3 - 13
Connection Internal circuit and common

3.3 Internal circuit and common

Servo amplifier
24 V DC
VDD
Digital input
interface
COM
EM1
SG
MBR
LA, etc.
LAR,
etc.
LG SD
MO1 MO2
LG
TXD
RXD
MR
MRR
LG
SD
Differential output 35mA max.
Analog output
RS232C
CN2
Input encoder
3 - 14
S000976C
Fig. 3-13: Internal circuit and common
Grounding Connection

3.4 Grounding

DANGER:
Ground the servo amplifier and servo motor securely.
m
To prevent an electric shock, always connect the protective earth terminal (PE) of the servo amplifier marked with , with the protective earth of the control box.
Power
supply
200-230V
50Hz
Line filter
Control box
MC
Protective earth
Servo amplifier
L1
L2
L3 L11 L21
CN1A
U V
W
Controller
CN2
Servo motor
Encoder
U V
M
W
Connect to PE terminal!
S000983C
Fig. 3-14: Grounding
Ground the bus cable near the controller! That way you reduce the influence of external noise. Another possibility to reduce noise interference is to build in filters.
MELSERVO J2-Super 3 - 15
Connection Power supply

3.5 Power supply

DANGER:
When the servo amplifier has become faulty, switch power off on the amplifier power
m
side.
Power-on procedure
Always wire the power supply using the magnetic contactor with the main circuit power supply L1, L2 and L3 or L1 and L2 for 1-phase connection.
Switch on the control circuit power supply L11, L21 simultaneously with the main circuit power supply or before switching on the main circuit power supply. If the main circuit power supply is not on, the display shows the corresponding warning. However, by switching on the main circuit power supply, the warning disappears and the servo amplifier will operate properly.
The servo amplifier can accept the "servo ON" command within 3s the 3-phase power supply is switched on.
3 - 16
Power supply Connection

3.5.1 Connection example

Connection for servo amplifier 200V
Connection examples for 1-phase and 3-phase power supplies are illustrated in the following diagrams:
RA
Power
supply
230V 50Hz
Emergency stop
Controller
emergency stop
MC
Fig. 3-15: 1-phase connection of servo amplifier
Emergency stop
Servo amplifier
L1 L2 L3 L11 L21
VDD
COM
EM1
SG
MC
ON
MC
SK
S000977C
Power
supply
400V 50Hz
Tr an s fo r m e r
UE/UA = 400V/230V
Emergency stop
RA
Emergency stop
Controller
emergency stop
MC
Servo amplifier
L1 L2 L3 L11 L21
VDD
COM
EM1
SG
ON
MC
MC
SK
S000978C
Fig. 3-16: 3-phase connection of servo amplifier
Configure up the power supply circuit which switches off the magnetic contactor after detection of alarm occurrence on the controller side.
MELSERVO J2-Super 3 - 17
Connection Power supply
Connection for servo amplifier 400V
Emergency stop OFF ON
RA
Power
supply
Tr an s fo r m e r
Servo amplifier
400V 50Hz
L1 L2 L3
Power
+
supply
24VDC
-
Emergency stop
Circuit protector
MC
L1 L2 L3
P C D
24 V/L11 0 V/L21
EM1
SG VDD COM
Fig. 3-17: Servo amplifier MR-J2S-60B4 to MR-J2S-200B4
MC
MC
SK
S001239C
Emergency stop OFF ON
RA
Power
supply
400V 50Hz
L1 L2 L3
Tr an s fo r m e r
MC
Servo amplifier
L1 L2 L3
Circuit protector
Power
+
supply
24VDC
-
Emergency stop
24 V/L11 0 V/L21
EM1
SG
VDD COM
Fig. 3-18: Servo amplifier MR-J2S-350B4 to MR-J2S-700B4
MC
MC
SK
S001240C
3 - 18
Power supply Connection
Timing chart
"Servo ON" command accepted
(3s)
Main circuit and
control circuit
Base circuit
Servo ON command
(from controller)
ON
OFF
ON
OFF
ON
OFF
60ms 60ms10ms
S000979C
Fig. 3-19: Timing chart for switching on the power supply
Emergency stop
For safety’s sake an EMERGENCY OFF switch must always be installed between the terminals EM1 and SG. When the contact is interrupted, the servo motor is switched to a resistance brake (dynamic brake) integrated into the unit and brought to a stop as soon as possible. Simultaneously the EMERGENCY OFF message (E6) appears on the display.
During ordinary operation, do not use emergency stop circuit to alternate stop and run.
Servo amplifier
VDD
COM
Emergency stop
Fig. 3-20: Emergency stop circuit
EM1
SG
S000980C
MELSERVO J2-Super 3 - 19
Connection Alarm occurence timing chart

3.6 Alarm occurence timing chart

CAUTION:
When an alarm has occurred, remove its cause, make sure that the operation signal
b
is not being input, ensure safety, and reset the alarm before restarting operation.
Main circuit and
control circuit
Base circuit
Dynamic brake
Servo ON command
(from controller)
Alarm
Reset command
(from controller)
ON
OFF
ON
OFF
Val id
Invalid
ON
OFF
ON
OFF
OFF
1 s
ALARM
Fig. 3-21: Alarm occurence timing chart
Brake operation
ON
Remove cause of trouble
50 ms
OFF
Power OFF
Brake operation
ON
60 ms
Power ON
OFF
S000975C
3 - 20
Servo motor with electromagnetic brake Connection

3.7 Servo motor with electromagnetic brake

CAUTION:
Configure the electromagnetic brake circuit so that it is activated not only by the
b
interface unit signals but also by a emergency stop.
b
EM1 RA
Emergency stop signal
Contacts must be open when servo ON,
when an alarm occurence and when an
electromagnetic brake interlock
Connection diagram
Please observe closely the following instructions for the use of a servo motor with electromagnetic brake.
CAUTION:
The electromagnetic brake is only intended for holding a static load, e.g. from vertical lifting axes. The braking effect and frequent switching of the EMERGENCY OFF function will result in the destruction of the brake after only a few cycles.
Provide a separate power source of 24VDC for the electromagnetic brake.The brake will operate when the power switches off.
Servo motor
M
Electro-
magnetic brake
Switch off the SON command after the servo motor has stopped.
Servo amplifier
EM1
VDD COM MBR
Fig. 3-22: Connection diagram
RA
RA
24VDC
B1
B2
Servo motor
M
S000982C
MELSERVO J2-Super 3 - 21
Connection Servo motor with electromagnetic brake
Setting procedure
The setting for the electromacnetic brake is as follows:
In Parameter 21 set the time delay (T
b) from electromagnetic brake operation to base circuit
shut-off, shown in fig. 3-23. Use parameter 30 to set the rotation speed at which the electromagnetic brake is to be
activated when there is an alarm or an EMERGENCY OFF.
Timing charts
Coasting
Servo motor speed
Base circuit
Electromagnetic
brake (MBR)
Servo ON command
(from controller)
0r/min
ON
OFF
Invalid (ON)
Valid (OFF )
ON
OFF
Electromagnetic brake operation delay time
Fig. 3-23: Servo ON command (from controller) ON/OFF
S000801E
Dynamic brake
Servo motor speed
Base circuit
Electromagnetic
brake (MBR)
Emergency stop
command
(from controller)
or external
emergency stop (EM1)
ON
OFF
Invalid (ON)
Valid (OFF)
Invalid (ON)
Valid (OFF)
Dynamic brake, electromagnetic brake Electromagnetic brake
Electromagnetic
brake release
Electromagnetic brake operation delay time
S000802E
Fig. 3-24: Emergency stop command from controller or external emergency stop (EM1)
ON/OFF
3 - 22
Servo motor with electromagnetic brake Connection
Dynamic brake
Servo motor speed
Dynamic brake, electromagnetic brake Electromagnetic brake
Base circuit
Electromagnetic
brake (MBR)
Alarm
Invalid (ON)
Valid (OFF)
Invalid (ON)
Valid (OFF)
Fig. 3-25: Alarm occurence
Servo motor speed
Base circuit
Electromagnetic
brake (MBR)
Alarm
Invalid (ON)
Valid (OFF )
Yes ( OF F)
ON
OFF
ON
OFF
No (ON)
10 to 100 ms
Electromagnetic brake operation delay time
S000803E
Dynamic brake Dynamic brake, electromagnetic brake Electromagnetic brake
This time depends on the operation status of servo amplifier.
Electromagnetic brake operation delay time
When the main circuit power supply is off in a motor stop status and the control circuit power supply is on, the main circuit off warning (E9) occurs and the alarm (ALM) does not turn off.
Main circuit power
supply and control
circuit power supply
ON
OFF
Fig. 3-26: Main and control circuit power supplies OFF
Dynamic brake
Servo motor speed
Base circuit
Electromagnetic
brake (MBR)
Alarm
Main circuit power
supply
15 ms or more
ON
OFF
Invalid (ON)
Valid (OFF )
No (ON)
Yes ( OF F)
ON
OFF
Dynamic brake, electromagnetic brake Electromagnetic brake
Electromagnetic brake operation delay time
When the main circuit power supply is off in a motor stop status and the control circuit power supply is on, the main circuit off warning (E9) occurs and the alarm (ALM) does not turn off.
S000804E
This time depends on the operation status of servo amplifier.
S000899E
Fig. 3-27: Main circuit power supply OFF (control circuit power supply remains ON.)
MELSERVO J2-Super 3 - 23
Connection Examples of standard wiring diagrams

3.8 Examples of standard wiring diagrams

In the following illustrations there is presented a wiring diagram for a 200V and a 400V servo amplifier.
NOTE Please take all notes given in this chapter into account.
Servo amplifier 200V
Make up a sequence which switches off the MC at alarm occurence or emergency stop.
Servo motors
HC-KFS, HC-MFS
1 2 3 4
B1
5 6
B2
Servo motors
HC-SFS, HC-RFS
24 V DC
EMG
A B C D
B1
G
H
B2
S R C D A B F
G
N
M
S001011C
M
ENCODER
M
ENCODER
L1 I
Powe r
supply
Controller
MR-J2HBUS M cable
is connected between
N
Optional brake
resistor
(connection of a
brake unit to servo
P
amplifiers with
500A or more is
shown on the left)
MR-J2HBUSM-A cable
is connected to CN1A
A171SH A172SH A173UH
2 amplifiers
>
>
I
>
I
Te r mi n a t or
MR-A-TM
MC
MR-J2S- B
TE1
L1
L2L2
L3L3
L11 L21 C
D P
MR-BAT
CON1
CN1A
CN1BCN1ACN1BCN1ACN1B
U
V
W
24 V DC
CN2
19
P5
TE2
11
LG
20
P5
12
PLATE
PLATE
LG
18
P5
2
LG
7
MR
17
MRR
6
MD
16
MDR
9
BAT
1
LG SD
CN3
TxD
12
LG
11
2
RxD
1
LG
15m max.
20
EM1
3
SG
10m max.
13
MBR
5
COM
10
VDD
4
MO1
1
LG
14
MO2
11
LG
5
LA
LAR
16
LB
7
LBR
17
LZ
8
LZR
18
SD
CS1
2m max.
GND
GND

/
RA

/
Monitor output 1
A
10k Monitor output 2
A
10k
Encoder A-phase pulse
Encoder B-phase pulse
Encoder Z-phase pulse
RD
SD
77
88
11
22
44
55
33
99 66
EMG
P5 P5
LG LG
MR MR
MRR MRR
MD MD
MDR MDR
BAT BAT
SD SD
CNT CNT
PC
19
P5
11
LG
20
P5
12
LG
18
P5
2
LG
7
MR
17
MRR
6
MD
16
MDR
9
BAT
1
LG SD
MR-J2S- B
CS1
MR-J2S- B
CS1
/

3 - 24
Fig. 3-28: Standard wiring diagram for amplifier 200V
Examples of standard wiring diagrams Connection
Servo amplifier 400V
Make up a sequence which switches off the MC at alarm occurence or emergency stop.
B1
B2
Servo motors
HC-SFS
A B C D
G H
S R C D A B
F G N
M
M
ENCODER
L1 I
Powe r
supply
Controller
MR-J2HBUS M cable
is connected between
N
Optional brake
resistor
(connection of a
brake unit to servo
P
amplifiers with
350B4 or more is
shown on the left)
MR-J2HBUS M-A cable
is connected to CN1A
A171SH A172SH A173UH
2 amplifiers
>
>
I
>
I
Te r mi n a t or
MR-A-TM
MC
MR-J2S- B4
TE1
L1
L2L2
L3L3
L11 L21 C
TE2
D P
MR-BAT
CON1
CN1A
CN1BCN1ACN1BCN1ACN1B
MR-J2S- B4
MR-J2S- B4
PLATE
12 11
20
13
10
14 11
16
17
18
PLATE
CS1
CS1
W
CS1
U V
24 V DC
CN2
19
P5
11
LG
20
P5
12
LG
18
P5
2
LG
7
MR
17
MRR
6
MD
16
MDR
9
BAT
1
LG SD
CN3
TxD
LG
2
RxD
LG
1
3
5
4 1
5
7
8
EM1
SG
MBR
COM
VDD
MO1
LG
MO2
LG
LA
LAR
LB
LBR
LZ
LZR
SD
15m max.
10m max.
2m max.
RD
GND
SD
GND

/
RA

/
A
Monitor output 1 10kΩ Monitor output 2
A
10k
Encoder A-phase pulse
Encoder B-phase pulse
Encoder Z-phase pulse
EMG
PC

/
S001255C
Fig. 3-29: Standard wiring diagram for amplifier 400V
MELSERVO J2-Super 3 - 25
Connection Examples of standard wiring diagrams
DANGER:
Ground the servo amplifier and servo motor securely.
m
b
To prevent an electric shock, always connect the protective earth terminal (PE) of the servo amplifier marked with , with the protective earth of the control box.
CAUTION:
Do not reverse the diode’s direction. Connecting it backwards could cause the
amplifier to malfunction so that signals are not output, and emergency stop and other safety circuits are inoperable.
If the controller is not equipped with an EMERGENCY OFF function, then an external EMERGENCY OFF switch must be installed.
Notes to fig. 3-28 and fig. 3-29:
The connection of terminals shown for the optional regenerative braking resistor applies exclusively
to servo amplifiers MR-J2S-350B or less and MR-J2S-200B4 or less. For exact descriptions of the wiring of terminals for other performance classes, please see Tab. 3-4 and Tab. 3-5.
CN1A, CN1B, CN2 and CN3 have the same shape. Wrong connection of the connectors will lead to
a fault or may lead to a destruction of the inputs/outputs.
The sum of currents that flow in the external relays should be 80mA max. If it exceeds 80mA, supply
interface power from external.
Prior to starting up operations the external EMERGENCY OFF signal (EM1) must be switched on
(opener). By setting parameter 23 to “0001” the external EMERGENCY OFF switch may be deactivated.
Total length of the MR-J2HBUSM-A and MR-J2HBUSM cables = max. 30m. Use of a cable clamp or
data line filters (3–4 in a row) near the connector pull to enhance noise resistence is recommended.
Motor-side wiring after the second axis has been omitted.
Up to 8 axes (n = 0–7) can be connected. MR-H-B series servo amplifiers can be connected to the
same bus (however, it requires a different cable).
For termination the connector CN1B of the last servo amplifier must be fitted with the terminating
resistance MR-A-TM.
Only for motors with electromagnetic brake.
A 1-phase 230VAC power supply can be used with servo amplifiers rated at MR-J2S-70A or less.
Please connect the power supply using only terminals L1 and L2. Do not connect anything to L3.
3 - 26
Station number setting Connection

3.9 Station number setting

Use the coding switch (CS1) to set the station number for the servo amplifier. If the same numbers are set to different servo amplifier in a single communication system, the system will not operate properly. Set the switch to "F" when executing the test operation mode using the setup-software.
NOTE
The station number set to CS1 should be the same as the one set to the servo system controller.
CS1
9
8
A
7
B
6
C
5
D
4
3
E
2
F
1
0
Setting Description
0 Station 1
Abb. 3-30:
Station number setting switch
Abb. 3-31:
Station number setting
1 Station 2 2 Station 3 3 Station 4 4 Station 5 5 Station 6 6 Station 7 7 Station 8 8— 9— A—
B— C— D—
E—
Test operation mode or when
F
machine analyzer is used (refer
section 4.6.2)
S000972C
MELSERVO J2-Super 3 - 27
Connection Station number setting
3 - 28
Points to check prior to starting operation Operation

4 Operation

4.1 Points to check prior to starting operation

Wiring
Before starting operation, check the following:
A correct power supply is connected to the power input terminals (3-phase: L1, L2, L3,
1-phase: L11, L21) of the servo amplifier.
The servo motor power supply terminals (U, V, W) of the servo amplifier match in phase with the power input terminals (U, V, W) of the servo motor.
Servo amplifier 200V Servo amplifier 400VServo amplifier 200V
MR-J2S- B
MR-J2S- B MR-J2S- B4
L1
L2
L3
L11
L21
U
U
V
V
W
M
W
L1
L2
L3
L11
L21
U
U
V
V
W
M
W
24 V DC
L1
L2
L3
+
L11
L21
U
U
V
V
W
M
W
1-phase connector 3-phase connector3-phase connector
S001257C
Fig. 4-1: Wiring
The servo motor power supply terminals (U, V, W) of the servo amplifier are not shorted to the power input terminals (L1, L2, L3) of the servo motor.
L1
L2
L3
Servo amplifier
W
U
V
M
S000582C
Fig. 4-2: Short circuit
Ground the servo amplifier and servo motor securely.
When using a regenerative brake option or brake unit:
– always remove the lead across the terminals D and P for the servo amplifier MR-J2S-
350B or less and MR-J2S-200B4 or less.
– disconnect the cable connections to the internal brake resistor between the terminals P
and C for the servo amplifier MR-J2S-500B or more and MR-J2S-350B4 or more.
MELSERVO J2-Super 4 - 1
Operation Points to check prior to starting operation
24VDC or higher voltages are not applied to the pins of connector CN3.
SD and SG of connector CN3 are not shorted.
SD SG
Servo amplifier
S000583C
Fig. 4-3: Short-circuit of SD and SG
The connection cable are not under a mechanical load (tension or excessive bend etc.).
CN1A should be connected with the bus cable connected to the servo system controller or
preceding axis servo amplifier, and CN1B should connected with the bus cable connected to the subsequent axis servo amplifier or with the termination connector (MR-A-TM.)
Station number
The station number setting of CS1 should be the same as that of the servo system controller. (refer section 3.9).
Parameter
Check the parameter setting on the servo system controller screen or using the setup-software.
Environment
Before starting operation, check the following:
Signal cables and power cables are not shorted by wire offcuts, metallic dust or the like.
4 - 2
Procedures before Operation Operation

4.2 Procedures before Operation

DANGER:
Do not operate the switches with wet hands. You may get an electric shock.
m

4.2.1 Start up procedure

Do not operate the controller with the front cover removed. There is the risk of getting an electric shock from live parts.
During power-on or operation, do not open the front cover. You may get an electric shock.
Before starting operation, check the parameters. Through the incorrect setting of parameters some machines may execute unexpected movements.
Never touch the cooling fins of the servo amplifier, the brake resistor, servo motor or other components while the power supply is still on or shortly after switching it off. They can become very hot and touching them could result in serious burns.
Power on
When the main and control circuit power supplies are switched on, "d1" (for the first axis) appears on the servo amplifier display.
In the absolute position detection system, first power-on results in the absolute position lost (25) alarm and the servo system cannot be switched on. This is not a failure and takes place due to the uncharged capacitor in the encoder.The alarm can be deactivated by keeping power on for a few minutes in the alarm status and then switching power off once and on again.
Also in the absolute position detection system, if power is switched on at the servo motor speed of 500r/min or higher, position mismatch may occur due to external force or the like. Power must therefore be switched on when the servo motor is at a stop.
Parameter setting
Set the parameters according to the structure and specifications of the machine.
Pr.-No. Name Setting Description
Rotation direction setting
7
Auto tuning
8
Servo response
9
Tab. 4-1: Setting value and control function
After setting the above parameters, switch power off once. Then switch power on again to make the set parameter values valid.
0
1
Increase in positioning address rotates the motor in the forward direction
Used Slow response (initial value)
5
MELSERVO J2-Super 4 - 3
Operation Procedures before Operation
Servo on
Switch the servo-on in the following procedure:
Switch on main circuit and control circuit power supply.The controller transmits the "servo ON" command.
When placed in the "servo ON" status, the servo amplifier is ready to operate and the servo motor is locked.
Home position return
Always perform home position return before starting positioning operation.
Stop
If any of the following situations occurs, the servo amplifier suspends the running of the servo motor and brings it to a stop. When the servo motor is equipped with an electromagnetic brake, refer to section 3.7.
Operation Stopping condition
"Servo OFF" command
Servo system controller
Emergency stop command
Alarm occurrence
Servo amplifier
External EMERGENCY OFF switch (EM1) is pressed.
The base circuit is shut off and the servo motor coasts.
The base circuit is shut off and the dynamic brake operates to bring the servo motor to stop. The controller emergency stop warning (E7) occurs.
The base circuit is shut off and the dynamic brake operates to bring the servo motor to stop.
The base circuit is shut off and the dynamic brake operates to bring the servo motor to stop. The servo forced stop warning (E6) occurs.
Tab. 4-2: Stopping condition
4 - 4
Display and Operation Operation

4.3 Display and Operation

4.3.1 Display sequence

On the servo amplifier display (two-digit, seven-segment display), check the status of communication with the servo system controller at power-on, check the station number, and diagnose a fault at occurrence of an alarm.
Servo amplifier power ON
Waiting for servo system controller power to switch ON
Servo system controller power ON
When alarm
occurs, alarm
code appears.
Ready OFF/
Refer
note
Ready ON
Refer
note
Servo ON
Refer
note
Ordinary operation
Servo system controller power OFF
servo OFF
Ready ON/ servo OFF
Ready ON/ servo ON
Initial data communication
During emergency stop and forced stop
or
Emergency stop and forced stop reset
The segments of b1, c1 and d1
Servo system controller power ON
NOTE:
indicate the station number. (station 1 in this example)
S000984C
Fig. 4-4: Display sequence
MELSERVO J2-Super 4 - 5
Operation Display and Operation

4.3.2 Indication list

Display Status Description
AA Initializing
Ab Initializing
AC Initializing
Ad Initializing
AE Initialize completion
b#
d#
C#
** 88 CPU error
b0.
b#. d#. c#.
Ready OFF
Servo ON
Servo OFF
Alarm/Warning The alarm No./warning No. that occurred is displayed.
Test operation mode 
The servo amplifier was switched on when power to the servo system controller is off.
Power to the servo system controller was switched off
during power-on of the servo amplifier. The station number set to the servo system controller
does not match the station number set with the coding switch (CS1) of the servo amplifier.
A servo amplifier fault occurred or an error took place in communication with the servo system controller. In this case, the indication changes: Ab AC Ad Ab.
The servo system controller is faulty.
Communication started between the servo system controller and servo amplifier
The initial parameters from the servo system controller were received.
Initial data communication with the serco system controller was completed.
The ready off signal from the servo system controller was received.
The servo on signal from the servo system controller was received.
The servo off signal from the servo system controller was received
JOG operation, positioning operation, programmed operation, forced output signal
Motor-less operation
Tab. 4-3: Indication list
The character "#" denotes any of numerals 0 to 8 and what it means is listed in Tab. 4-4.
The character "**" indicates the warning/alarm number.
To execute this functions the setup-software is required.
# Description
0 Test operation mode
1 Station 1
2 Station 2
3 Station 3
4 Station 4
5 Station 5
6 Station 6
7 Station 7
8 Station 8
Tab. 4-4:
Meaning of character "#"
4 - 6
Test operation mode Operation

4.4 Test operation mode

CAUTION:
The test operation mode is designed for servo operation confirmation and not for
b
NOTE For full information of this functions, refer to the setup-software manual.
machine operation confirmation. Do not use this mode with the machine. Always use the servo motor alone.
If an operation fault occurred, use the forced stop (EM1) to make a stop.
By using a personal computer and the setup-software, you can execute jog operation, positioning operation, motor-less operation and forced output without connecting the motion controller.
Use the system setup according to fig. 3-28 and fig. 3-29.
JOG operation
Jog operation can be performed without using the servo system controller. This operation may be used independently of whether the servo is on or off and whether the servo system controller is connected or not.
Exercise control on the jog operation screen of the setup-software.
Initial value Setting range
Speed [r/min] Acceleration/deceleration time constant [ms]
Tab. 4-5: JOG operation settings
Function Button
Forward rotation start Forward Reverse rotation start Reverse Stop Stop
Tab. 4-6: Operation method
200 0 to 5175
1000 0 to 20000
MELSERVO J2-Super 4 - 7
Operation Test operation mode
Positioning operation Positioning operation can be performed without using the servo system controller. This
operation may be used independently of whether the servo is on or off and whether the servo system controller is connected or not.
Exercise control on the positioning operation screen of the setup-software.
Name Initial value Setting range
Travel [pulse] 131072 0 to 9999999 Speed [r/min] 200 0 to 5175 Acceleration/deceleration time constant [ms] 1000 0 to 20000
Tab. 4-7: Positioning operation settings
Function Button
Forward rotation start Forward Reverse rotation start Reverse Pause Pause
Tab. 4-8: Operation method
Program operation Program operation can be performed in two or more operation patterns combined, without using
the servo system controller. This operation may be used independently of whether the servo is on or off and whether the servo system controller is connected or not.
Exercise control on the programmed operation screen of the setup-software..
Function Button
Start Start Stop Reset
Tab. 4-9: Operation method
4 - 8
Test operation mode Operation
Motor-less operation
Without connecting the servo motor, output signals or status displays can be provided in response to the servo system controller commands as if the servo motor is actually running. This operation may be used to check the servo system controller sequence. Use this operation with the servo amplifier connected to the servo system controller.
NOTE
Motor-less operation may be used with the setup-software. However, use motor-less operation which is available by making the servo system controller parameter setting.
Exercise control on the motor-less operation screen of the setup-software.
Load Setting
Load torque 0 Load inertia moment ratio Same as servo motor inertia moment
Tab. 4-10: Load settings
The following alarms and warning do not occur for operation without servo motor: – Encoder error 1 (16) – Encoder error 2 (20) – Absolute position erasure (25) – Battery cable breakage warning (92) All other alarms and warnings occur as when the servo motor is connected
Forced output signal
Output signals can be switched on/off forcibly independently of the servo status. Use this function for output signal wiring check, etc.
Exercise control on the forced output screen of the setup-software.
MELSERVO J2-Super 4 - 9
Operation Test operation mode

4.4.1 Test operation procedure

JOG operation, positioning operation, program operation, forced output
Switch power off. Set the coding switch CS1 to „F“.
When CS1 is set to the station number and operation is performed by the servo system controller, the test operation mode screen is displayed on the personal computer, but no function is performed.
Switch servo amplifier power on. When initialization is over, the display shows the following
screen:
Decimal point flickers
Perform operation with the personal computer.
Motor-less operation
Switch off the servo amplifier. Perform motor-less operation with the personal computer. The display shows the following
screen:
Decimal point flickers
4 - 10
Parameter Operation

4.5 Parameter

When the servo amplifier is connected with the servo system controller, the parameters are set to the values of the servo system controller. Switching power off, then on makes the values set on the setup-software invalid and the servo system controller values valid.
NOTES In the maker setting parameters, do not set any values other than the initial values.
Setting may not be made to some parameters and ranges depending on the model or version of the servo system controller. For details, refer to the servo system controller user's manual.

4.5.1 Parameter write inhibit

The release of access to the parameters is established via parameter 40 (parameter write protection). Parameter No. 40 is made valid by switching power off, then on after setting its value.
The following table provides an overview over the settings of parameter No. 40:
Setting Function Operation from controller Operation from setup-software
0000 (Initial value)
000A
000C
000E
100E
Read Write Read Write Read Write Parameter No. 1 to No. 11 and No. 40 Read Write Read Write Parameter No. 40
Parameter No. 1 to No. 39 Parameter No. 1 to No. 11 and No. 40
Parameter No. 1 to No. 39 Parameter No. 40
Parameter No. 1 to No. 39
Parameter No. 1 to No. 39 Parameter No. 1 to No. 40
Parameter No. 1 to No. 39
Parameter No. 1 to No. 40
Parameter No. 1 to No. 40
Tab. 4-11: Parameter settings
MELSERVO J2-Super 4 - 11
Operation Parameter

4.5.2 Parameter overview

Function No. Symbol Name Initial value Unit
Basic parameters
Adjustment parameters
1
AMS
2
REG 3— 4— 000 — 5— 1
6
FPB 7
POL 8 ATU Auto tuning 0001 — 9 RSP Response auto tuning 0005
10 TLP 11 TLN
12 GD2
13 PG1 Position control gain 1 35 rad/s 14 VG1 Speed control gain 1 177 rad/s 15 PG2 Position control gain 2 35 rad/s 16 VG2 Speed control gains 2 817 rad/s 17 VIC Speed integral compensation 48 ms 18 NCH Machine resonance suppression filter 0000 — 19 FFC Feed forward gain 0 % 20 INP In-position range 100 Pulse
21 MBR
22 MOD Analog monitor output 0001 — 23
OP1 24
OP2
25 LPF
26 — Reserved 0
Amplifier setting 0000 — Regenerative brake resistor 0000
0080
Reserved
Feedback pulse number 0 — Rotation direction selection 0
Forward rotation torque limit Reverse rotation torque limit
Ratio of load inertia moment to servo motor inertia moment
Electromagnetic brake sequence output
Function selection1 0000 — Function selection 2 0000
Low-pass filter for adaptive vibration suppression control
300 % 300 %
7.0 Times
0ms
0000
Customer setting
Tab. 4-12: Parameter overview (1)
4 - 12
Parameter Operation
Function No. Symbol Name Initial value Unit
27 MO1 Analog output 1 offset 0 mV 28 MO2 Analog output 2 offset 0 mV 29 — Reserved 0001 — 30 ZSP Zero speed 50 r/min 31 ERZ Error excessive alarm level 80 0.1 × r 32 OP5 Function selection 5 0000
Expansion parameters
33
OP6
34 VPI
35 — Reserved 0 — 36 VDC Speed differential compensation 980 — 37 — Reserved 0010
38
ENR
39 — Reserved 0 — 40
BLK
Function selection 6 0000 — PI-/PID control switch-over position
droop
Encoder output pulses 4000 Pulse/r
Parameter entry prohibition 0000
0Pulse
Customer setting
Tab. 4-12: Parameter overview (2)
Set the parameter value and switch power off once, then switch it on again to make that parameter setting valid.
The values corresponds with the factory settings of the servo amplifier. Connecting it with the servo system controller and switching power on changes them to the settings of the servo system controller.
Setting and changing cannot be made from the peripheral software of the motion controller.
MELSERVO J2-Super 4 - 13
Operation Parameter

4.5.3 Parameter description:

Number Symbol Initial value Unit Setting range
1 AMS 0000 Refer description
Amplifier setting Used to select the absolute position detection.
0 00
Positioning 0: Standard (incremental) 1: Absolute position detection system
2 REG 0000 Refer description
Regenerative brake resistor
Servo amplifier 200V
00
Regenerative selection brake option 00: No brake resistor 01: FR-RC, FR-BU 05: MR-RFH220-40 08: MR-RFH400-13 09: MR-RFH400-13 0B: MR-RFH400-6.7 0C: MR-RFH400-6.7 10: MR-RFH75-40 11: MR-RFH75-40
CAUTION: Wrong setting may cause the regenerative brake option to burn. NOTE: If the regenerative brake option selected is not for use with the servo amplifier, parameter error (37) occurs.
3 0080
Reserved Do not change this parameter.
4 0000
Reserved Do not change this parameter.
Servo amplifier 400V
00
Regenerative selection brake option 00: No brake resistor 01: FR-RC-H , FR-BU-H 80: MR-RB3H-4 81: MR-RB5H-4/MR-PWR-T-600-80 82: MR-RB3G-4 83: MR-RB5G-4/MR-PWR-T-600-47 84: MR-RB34-4 85: MR-RB54-4/MR-PWR-T-600-26 86: MR-RB1L-4/MR-PWR-T-150-270 87: MR-RB3M-4/MR-PWR-T-400-120
4 - 14
5 1
Reserved Do not change this parameter.
Tab. 4-13: Parameter list details (1)
Loading...