Please read the instructions carefully before using the equipment.
To use the equipment correctly, do not attempt to install, operate, maintain, or inspect the equipment until
you have read through this Instruction Manual, Installation guide, and appended documents carefully. Do not
use the equipment until you have a full knowledge of the equipment, safety information and instructions.
In this Instruction Manual, the safety instruction levels are classified into "WARNING" and "CAUTION".
WARNING
CAUTION
Note that the CAUTION level may lead to a serious consequence according to conditions.
Please follow the instructions of both levels because they are important to personnel safety.
What must not be done and what must be done are indicated by the following diagrammatic symbols.
Indicates that incorrect handling may cause hazardous conditions,
resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous conditions,
resulting in medium or slight injury to personnel or may cause physical
damage.
Indicates what must not be done. For example, "No Fire" is indicated by
Indicates what must be done. For example, grounding is indicated by
In this Instruction Manual, instructions at a lower level than the above, instructions for other functions, and so
on are classified into "POINT".
After reading this Instruction Manual, keep it accessible to the operator.
.
.
A - 1
Page 3
1. To prevent electric shock, note the following
WARNING
Before wiring and inspections, turn off the power and wait for 15 minutes or more until the charge lamp
turns off. Otherwise, an electric shock may occur. In addition, when confirming whether the charge lamp
is off or not, always confirm it from the front of the servo amplifier.
Ground the servo amplifier and servo motor securely.
Any person who is involved in wiring and inspection should be fully competent to do the work.
Do not attempt to wire the servo amplifier and servo motor until they have been installed. Otherwise, it
may cause an electric shock.
Do not operate switches with wet hands. Otherwise, it may cause an electric shock.
The cables should not be damaged, stressed, loaded, or pinched. Otherwise, it may cause an electric
shock.
To prevent an electric shock, always connect the protective earth (PE) terminal (marked ) of the servo
amplifier to the protective earth (PE) of the cabinet.
To avoid an electric shock, insulate the connections of the power supply terminals.
2. To prevent fire, note the following
CAUTION
Install the servo amplifier, servo motor, and regenerative resistor on incombustible material. Installing
them directly or close to combustibles will lead to smoke or a fire.
Always connect a magnetic contactor between the power supply and the power supply (L1/L2/L3) of the
servo amplifier, in order to configure a circuit that shuts down the power supply on the side of the servo
amplifier’s power supply. If a magnetic contactor is not connected, continuous flow of a large current may
cause smoke or a fire when the servo amplifier malfunctions.
Always connect a molded-case circuit breaker, or a fuse to each servo amplifier between the power
supply and the power supply (L1/L2/L3) of the servo amplifier, in order to configure a circuit that shuts
down the power supply on the side of the servo amplifier’s power supply. If a molded-case circuit breaker
or fuse is not connected, continuous flow of a large current may cause smoke or a fire when the servo
amplifier malfunctions.
When using the regenerative resistor, switch power off with the alarm signal. Otherwise, a regenerative
transistor malfunction or the like may overheat the regenerative resistor, causing smoke or a fire.
When you use a regenerative option with an MR-JE-40C to MR-JE-100C, remove the built-in
regenerative resistor and wiring from the servo amplifier.
Provide adequate protection to prevent screws and other conductive matter, oil and other combustible
matter from entering the servo amplifier and servo motor.
3. To prevent injury, note the following
CAUTION
Only the power/signal specified in the Instruction Manual must be supplied/applied to each terminal.
Otherwise, an electric shock, fire, injury, etc. may occur.
Connect cables to the correct terminals. Otherwise, a burst, damage, etc. may occur.
Ensure that polarity (+/-) is correct. Otherwise, a burst, damage, etc. may occur.
The servo amplifier heat sink, regenerative resistor, servo motor, etc., may be hot while the power is on
and for some time after power-off. Take safety measures such as providing covers to avoid accidentally
touching them by hands and parts such as cables.
A - 2
Page 4
4. Additional instructions
The following instructions should also be fully noted. Incorrect handling may cause a malfunction, injury,
electric shock, fire, etc.
(1) Transportation and installation
CAUTION
Transport the products correctly according to their mass.
Stacking in excess of the specified number of product packages is not allowed.
Do not hold the lead of the built-in regenerative resistor, cables, or connectors when carrying the servo
amplifier. Otherwise, it may drop.
Install the servo amplifier and the servo motor in a load-bearing place in accordance with the Instruction
Manual.
Do not get on or put heavy load on the equipment. Otherwise, it may cause injury.
The equipment must be installed in the specified direction.
Leave specified clearances between the servo amplifier and the cabinet walls or other equipment.
Do not install or operate the servo amplifier and servo motor which have been damaged or have any
parts missing.
Do not block the intake and exhaust areas of the servo amplifier. Otherwise, it may cause a malfunction.
Do not drop or apply heavy impact on the servo amplifiers and the servo motors. Otherwise, injury,
malfunction, etc. may occur.
Do not strike the connector. Otherwise, a connection failure, malfunction, etc. may occur.
When you keep or use the equipment, please fulfill the following environment.
Item Environment
Ambient
temperature
Storage -20 °C to 65 °C (non-freezing)
Ambient
humidity
Storage
Ambience Indoors (no direct sunlight), free from corrosive gas, flammable gas, oil mist, dust, and dirt
Altitude 2000 m or less above sea level (Contact your local sales office for the altitude for options.)
Vibration resistance 5.9 m/s2, at 10 Hz to 55 Hz (directions of X, Y and Z axes)
When the product has been stored for an extended period of time, contact your local sales office.
When handling the servo amplifier, be careful about the edged parts such as corners of the servo
amplifier.
The servo amplifier must be installed in a metal cabinet.
When fumigants that contain halogen materials such as fluorine, chlorine, bromine, and iodine are used
for disinfecting and protecting wooden packaging from insects, they cause malfunction when entering our
products. Please take necessary precautions to ensure that remaining materials from fumigant do not
enter our products, or treat packaging with methods other than fumigation (heat method). Additionally,
disinfect and protect wood from insects before packing products.
To prevent a fire or injury from occurring in case of an earthquake or other natural disasters, securely
install, mount, and wire the servo motor in accordance with the Instruction Manual.
Operation 0 °C to 55 °C (non-freezing)
Operation
5 %RH to 90 %RH (non-condensing)
A - 3
Page 5
r
(2) Wiring
CAUTION
Before removing the CNP1 connector of MR-JE-40C to MR-JE-100C, disconnect the lead wires of the
regenerative resistor from the CNP1 connector.
Wire the equipment correctly and securely. Otherwise, the servo motor may operate unexpectedly.
Make sure to connect the cables and connectors by using the fixing screws and the locking mechanism.
Otherwise, the cables and connectors may be disconnected during operation.
Do not install a power capacitor, surge killer, or radio noise filter (optional FR-BIF) on the servo amplifier
output side.
To avoid a malfunction, connect the wires to the correct phase terminals (U/V/W) of the servo amplifier
and servo motor.
Connect the servo amplifier power output (U/V/W) to the servo motor power input (U/V/W) directly. Do
not let a magnetic contactor, etc. intervene. Otherwise, it may cause a malfunction.
Servo amplifier
U
V
W
Servo motor
U
V
W
Servo motorServo amplifier
U
M
V
W
U
V
W
M
The connection diagrams in this instruction manual are shown for sink interfaces, unless stated
otherwise.
The surge absorbing diode installed to the DC relay for control output should be fitted in the specified
direction. Otherwise, the emergency stop and other protective circuits may not operate.
Servo amplifier
DOCOM
Control output
signal
For sink output interface
24 V DC
RA
Servo amplifie
DOCOM
Control output
signal
For source output interface
24 V DC
RA
When the cable is not tightened enough to the terminal block, the cable or terminal block may generate
heat because of the poor contact. Be sure to tighten the cable with specified torque.
Connecting a servo motor of the wrong axis to U, V, W, or CN2 of the servo amplifier may cause a
malfunction.
Configure a circuit to turn off EM2 or EM1 when the power supply is turned off to prevent an unexpected
restart of the servo amplifier.
To prevent malfunction, avoid bundling power lines (input/output) and signal cables together or running
them in parallel to each other. Separate the power lines from the signal cables.
(3) Test run and adjustment
CAUTION
When executing a test run, follow the notice and procedures in this instruction manual. Otherwise, it may
cause a malfunction, damage to the machine, or injury.
Before operation, check the parameter settings. Improper settings may cause some machines to operate
unexpectedly.
A - 4
Page 6
CAUTION
Never adjust or change the parameter values extremely as it will make operation unstable.
Do not get close to moving parts during the servo-on status.
(4) Usage
CAUTION
When it is assumed that a hazardous condition may occur due to a power failure or product malfunction,
use a servo motor with an external brake to prevent the condition.
For equipment in which the moving part of the machine may collide against the load side, install a limit
switch or stopper to the end of the moving part. The machine may be damaged due to a collision.
Do not disassemble, repair, or modify the product. Otherwise, an electric shock, fire, injury, etc. may
occur. Disassembled, repaired, and/or modified products are not covered under warranty.
Before resetting an alarm, make sure that the run signal of the servo amplifier is off in order to prevent a
sudden restart. Otherwise, it may cause an accident.
Use a noise filter, etc. to minimize the influence of electromagnetic interference. Electromagnetic
interference may be given to the electronic equipment used near the servo amplifier.
Burning or breaking a servo amplifier may cause a toxic gas. Do not burn or break it.
Use the servo amplifier with the specified servo motor.
Correctly wire options and peripheral equipment, etc. in the correct combination. Otherwise, an electric
shock, fire, injury, etc. may occur.
The electromagnetic brake on the servo motor is designed to hold the motor shaft and should not be
used for ordinary braking.
For such reasons as incorrect wiring, service life, and mechanical structure (e.g. where a ball screw and
the servo motor are coupled via a timing belt), the electromagnetic brake may not hold the motor shaft.
To ensure safety, install a stopper on the machine side.
If the dynamic brake is activated at power-off, alarm occurrence, etc., do not rotate the servo motor by an
external force. Otherwise, it may cause a fire.
(5) Corrective actions
CAUTION
Ensure safety by confirming the power off, etc. before performing corrective actions. Otherwise, it may
cause an accident.
If it is assumed that a power failure, machine stoppage, or product malfunction may result in a hazardous
situation, use a servo motor with an electromagnetic brake or provide an external brake system for
holding purpose to prevent such hazard.
When any alarm has occurred, eliminate its cause, ensure safety, and deactivate the alarm before
restarting operation.
If the molded-case circuit breaker or fuse is activated, be sure to remove the cause and secure safety
before switching the power on. If necessary, replace the servo amplifier and recheck the wiring.
Otherwise, it may cause smoke, fire, or an electric shock.
Provide an adequate protection to prevent unexpected restart after an instantaneous power failure.
A - 5
Page 7
CAUTION
Configure an electromagnetic brake circuit which is interlocked with an external emergency stop switch.
Contacts must be opened when ALM
(Malfunction) or MBR (Electromagnetic
brake interlock) turns off.
Contacts must be opened
with the emergency stop switch.
Servo motor
B
Electromagnetic brake
To prevent an electric shock, injury, or fire from occurring after an earthquake or other natural disasters,
ensure safety by checking conditions, such as the installation, mounting, wiring, and equipment before
switching the power on.
RA
U
24 V DC
(6) Maintenance, inspection and parts replacement
CAUTION
Make sure that the emergency stop circuit operates properly such that an operation can be stopped
immediately and a power is shut off by the emergency stop switch.
It is recommended that the servo amplifier be replaced every 10 years when it is used in general
environment.
When using a servo amplifier whose power has not been turned on for a long time, contact your local
sales office.
(7) General instruction
To illustrate details, the equipment in the diagrams of this Instruction Manual may have been drawn
without covers and safety guards. When the equipment is operated, the covers and safety guards must
be installed as specified. Operation must be performed in accordance with this Instruction Manual.
A - 6
Page 8
DISPOSAL OF WASTE
Please dispose a servo amplifier, battery (primary battery) and other options according to your local laws and
regulations.
EEP-ROM life
The number of write times to the EEP-ROM, which stores parameter settings, etc., is limited to 100,000. If
the total number of the following operations exceeds 100,000, the servo amplifier may malfunction when the
EEP-ROM reaches the end of its useful life.
Write to the EEP-ROM due to parameter setting changes
Write to the EEP-ROM due to device changes
Compliance with global standards
For the compliance with global standards, refer to app. 3 of "MR-JE-_C Servo Amplifier Instruction Manual".
«About the manual»
You must have this Instruction Manual and the following manuals to use this servo. Ensure to prepare
them to use the servo safely.
Wires mentioned in this Instruction Manual are selected based on the ambient temperature of 40 °C.
«U.S. customary units»
U.S. customary units are not shown in this manual. Convert the values if necessary according to the
following table.
Quantity SI (metric) unit U.S. customary unit
Mass 1 [kg] 2.2046 [lb]
Length 1 [mm] 0.03937 [inch]
Torque 1 [N•m] 141.6 [oz•inch]
Moment of inertia 1 [(× 10-4 kg•m2)] 5.4675 [oz•inch2]
Load (thrust load/axial load) 1 [N] 0.2248 [lbf]
Temperature N [°C] × 9/5 + 32 N [°F]
A - 7
Page 9
MEMO
A - 8
Page 10
CONTENTS
1. FUNCTIONS AND CONFIGURATION 1- 1 to 1- 4
1.1 Summary of Modbus-TCP ................................................................................................................ 1- 1
1.2 Function List ...................................................................................................................................... 1- 1
1.3 Communication specifications .......................................................................................................... 1- 4
5.3 Machine diagnosis function .............................................................................................................. 5- 4
5.4 Servo amplifier life diagnosis function .............................................................................................. 5- 4
6. MODBUS REGISTERS 6- 1 to 6-44
6.1 List of registers .................................................................................................................................. 6- 1
6.2 Object library details (objects in the 1000s) ..................................................................................... 6-17
6.2.1 Writing command to EEP-ROM (1010h) ................................................................................... 6-17
6.4.8 Touch probe (60B8h to 60BBh) ................................................................................................ 6-41
6.4.9 Touch probe function setting (60B8h) ....................................................................................... 6-42
6.4.10 Touch probe function status (60B9h) ...................................................................................... 6-43
6.4.11 Rising edge position of touch probe (60BAh) ......................................................................... 6-43
6.4.12 Falling edge position of touch probe (60BBh) ......................................................................... 6-43
6.4.13 Supported control mode (6502h) ............................................................................................ 6-44
2
Page 12
1. FUNCTIONS AND CONFIGURATION
1. FUNCTIONS AND CONFIGURATION
1.1 Summary of Modbus-TCP
The Modbus protocol, developed for programmable controllers by Modicon Inc., has evolved into the
Modbus/TCP protocol for use over TCP/IP.
The Modbus master acts as a TCP client, and the Modbus slave acts as a TCP server for client-server
communication. Using the functions in the message frames enables to read or write data from/to
parameters, write input commands, and check operation status of servo amplifiers.
For MR-JE-_C servo amplifier, Modbus registers are assigned like the address assignment of CiA 402 drive
profile.
A Modbus-compatible controller, the client, can communicate with the MR-JE-_C servo amplifiers that are
servers by accessing assigned holding registers.
1.2 Function List
The following table lists the functions of this servo. For details of the functions, refer to each section
indicated in the detailed explanation field.
Function Description
Position control mode (P)
(pulse train input)
Speed control mode (S)
(Analog input/DI input)
Torque control mode (T)
(Analog input)
Position/speed control
switching mode (P/S)
Speed/torque control switch
mode (S/T)
Torque/position control switch
mode (T/P)
Profile position mode (pp) The servo amplifier operates in the profile position mode.
Profile velocity mode (pv) The servo amplifier operates in the profile velocity mode.
Profile torque mode (tq) The servo amplifier operates in the profile torque mode.
Homing mode (hm) The servo amplifier operates in the home position return mode.
Absolute position detection
system
Model adaptive control
Touch probe function
Command pulse selection Command pulse train form can be selected from among three different types.
High-resolution encoder
This servo amplifier is used as a position control servo.
This servo amplifier is used as a speed control servo.
This servo amplifier is used as a torque control servo.
Using an input device, control can be switched between position control and speed
control.
Using an input device, control can be switched between speed control and torque
control.
Using an input device, control can be switched between torque control and position
control.
Setting a home position once makes home position return unnecessary at every
power-on.
This function achieves a high response and stable control following the ideal model.
The two-degrees-of-freedom model adaptive control enables you to set a response
to the command and a response to the disturbance separately.
Additionally, this function can be disabled. To disable this function, refer to section
7.4 of "MR-JE-C_ Servo Amplifier Instruction Manual".
The touch probe function is available only in the profile mode. When the touch probe
1 signal turns on, the current position latch function will latch the current position.
The latched data can be read with communication commands.
High-resolution encoder of 131072 pulses/rev is used for the encoder of the servo
motor compatible with the MELSERVO-JE series.
Speed limit Servo motor speed can be limited to any value.
Automatic VC offset
Alarm code output If an alarm has occurred, the corresponding alarm number is outputted in 3-bit code.
Test operation mode
MR Configurator2
One-touch tuning
You can switch gains during rotation and during stop, and can use an
input device to switch gains during operation.
This function suppresses vibration or residual vibration at an arm end.
This filter function (notch filter) decreases the gain of the specific frequency to
suppress the resonance of the mechanical system.
When a load is mounted to the servo motor shaft, resonance by shaft torsion during
driving may generate a mechanical vibration of high frequency. The shaft resonance
suppression filter suppresses the vibration.
The servo amplifier detects mechanical resonance and sets filter characteristics
automatically to suppress mechanical vibration.
Suppresses high-frequency resonance which occurs as the servo system response is
increased.
Analyzes the frequency characteristic of the mechanical system by simply
connecting an MR Configurator2 installed personal computer and the servo
amplifier.
MR Configurator2 is necessary for this function.
Improves a disturbance response when a response performance cannot be
increased because of a large load to motor inertia ratio, such as a roll feed axis.
Suppresses vibration of ±1 pulse generated at a servo motor stop.
The position control is performed based on a value obtained by multiplying the
position command from the controller by the set electronic gear ratio.
When the position control mode is used, the input pulses can be multiplied by 1/10
to 4000.
When the profile position mode is used, the position commands can be multiplied by
1/27649 to 8484.
Enables smooth acceleration and deceleration.
Set S-pattern acceleration/deceleration time constants with [Pr. PC03].
As compared with linear acceleration/deceleration, the acceleration/deceleration
time will be longer for the S-pattern acceleration/deceleration time constants
regardless of command speed.
Automatically adjusts the gain to optimum value if load applied to the servo motor
shaft varies.
Use a regenerative option when the built-in regenerative resistor of the servo
amplifier does not have sufficient regenerative capacity for a large regenerative
power generated.
ST1 (Forward rotation start), ST2 (Reverse rotation start), and SON (Servo-on) and
other input device can be assigned to certain pins of the CN3 connector.
The output devices including MBR (Electromagnetic brake interlock) can be
assigned to certain pins of the CN3 connector.
Turns on/off the output signals forcibly independently of the servo status.
Use this function for checking output signal wiring, etc.
Voltage is automatically offset to stop the servo motor if it does not come to a stop
when VC (Analog speed command) is 0 V.
MR Configurator2 is necessary for this function.
Jog operation, positioning operation, motor-less operation, DO forced output, and
program operation
MR Configurator2 is necessary for this function.
Using a personal computer, you can perform the parameter setting, test operation,
monitoring, and others.
Gain adjustment is performed just by one click on MR Configurator2.
This function is available with MR Configurator2 or via a network.
Detailed
explanation
"MR-JE-_C
Servo Amplifier
Instruction
Manual"
"MR-JE-_C
Servo Amplifier
Instruction
Manual"
"MR-JE-_C
Servo Amplifier
Instruction
Manual"
Section 5.2
"MR-JE-_C
Servo Amplifier
Instruction
Manual"
1 - 2
Page 14
1. FUNCTIONS AND CONFIGURATION
Function Description
This function makes the equipment continue operating even under the condition that
Tough drive function
Drive recorder function
Servo amplifier life diagnosis
function
Power monitoring function
Machine diagnosis function
Modbus/TCP
CC-Link IE Field Network
Basic
SLMP
IP address filtering function
Operation specification IP
address function
Lost motion compensation
function
Limit switch
Software limit
an alarm occurs.
The tough drive function includes two types: the vibration tough drive and the
instantaneous power failure tough drive.
This function continuously monitors the servo status and records the status transition
before and after an alarm for a fixed period of time. You can check the recorded data
by clicking the Waveform-Display button in the drive recorder window of MR
Configurator2.
However, the drive recorder is not available when:
1. You are using the graph function of MR Configurator2.
2. You are using the machine analyzer function.
3. [Pr. PF21] is set to "-1".
You can check the cumulative energization time and the number of on/off times of the
inrush relay. This function gives an indication of the replacement time for parts of the
servo amplifier including a capacitor and a relay before they malfunction.
This function is available with MR Configurator2 or via a network. (Refer to section
6.4.)
This function calculates the power running energy and the regenerative power from
the data in the servo amplifier such as speed and current. Power consumption and
others are displayed on MR Configurator2.
From the data in the servo amplifier, this function estimates the friction and
vibrational component of the drive system in the equipment and recognizes an error
in the machine parts, including a ball screw and bearing.
This function is available with MR Configurator2 or via a network. (Refer to section
6.3.)
The Modbus/TCP uses dedicated message frames for the Ethernet communication
between a client (master) and servers (slaves). The dedicated message frames have
functions for reading and writing data, you can set the parameters of servo amplifiers
and monitor it by using this function. In the profile mode, driving the servo motor is
also possible.
CC-Link IE Field Network Basic enables fixed cycle communication between the
master and slave stations using a general-purpose Ethernet connector. The
parameters of servo amplifiers can be set (read/written) and monitored. In the profile
mode, driving the servo motor is also possible.
SLMP (SeamLess Message Protocol) is a protocol to access SLMP-compatible
devices from external devices (such as a personal computer and an HMI) or
programmable controller CPU via Ethernet. The parameters of servo amplifiers can
be set (read/written) and monitored. In the profile mode, driving the servo motor is
also possible.
Register the range of IP addresses in advance to limit the network devices allowed
to be connected to the servo amplifier.
In Ethernet communication (CC-Link IE Field Network Basic, SLMP, or
Modbus/TCP), to limit the network devices to which the operation right is given, set
the range of the device IP addresses.
Monitoring/parameter reading can be performed with the network devices having no
operation right.
This function improves the response delay generated when the machine moving
direction is reversed.
Limits travel intervals using LSP (Forward rotation stroke end) and LSN (Reverse
rotation stroke end).
Limits travel intervals by address using parameters.
Enables the same function with the limit switch by setting parameters.
Detailed
explanation
"MR-JE-_C
Servo Amplifier
Instruction
Manual"
Chapter 2
"MR-JE-_C
Servo Amplifier
Instruction
Manual (CCLink IE Field
Network
Basic)"
Chapter 4
"MR-JE-_C
Servo Amplifier
Instruction
Manual (CCLink IE Field
Network
Basic)"
"MR-JE-_C
Servo Amplifier
Instruction
Manual"
Section 6.4.5
1 - 3
Page 15
1. FUNCTIONS AND CONFIGURATION
1.3 Communication specifications
The following table lists the Modbus/TCP communication specifications.
Communication protocol Modbus/TCP protocol
Conformed standard OPEN Modbus/TCP SPECIFICATION
Port No. No. 502
IP address
Subnet mask Default value (recommended): 255.255.255.0
Message format Refer to section 2.
Physical layer 1000BASE-T
Communication connector RJ45, 1 port (CN1)
Communication cable CAT5e, shielded twisted pair (4 pair) straight cable
Network topology Star
Variable communication speed 100 Mbps
Transmission speed between stations Max. 100 m
Waiting time setting None
Maximum number of connections 3
Server function
Function Description
IPv4 range: 0.0.0.0 to 255.255.255.255
Use the same network address for both a client and servers.
Default value: 192.168.3.0
Number of request messages that are
receivable simultaneously
1
1 - 4
Page 16
2. MODBUS/TCP PROTOCOL
2. MODBUS/TCP PROTOCOL
POINT
If connection with a client disconnects during establishment, the connection may
not close and this may cause reconnection failure. In case you cannot
reconnect, cycle the power of the servo amplifier.
2.1 Summary
In Modbus/TCP communication, a command that a client (controller) sends to servers (servo amplifiers) is
called "Query Message", and a command that the servers return to the client is called "Response Message".
When a servo amplifier receives a Query Message, it returns a Response Message to the client after the
servo amplifier response time.
In Modbus/TCP communication, as in the case of TCP/IP, make sure to establish the connection before
sending and receiving commands. Check that the connection has been established, and then send a Query
Message.
Client (controller)
Server (servo amplifier)
Note. The servo amplifier response time differs depending on the command to send.
Query Message
Response Message
Servo amplifier response time (Note)
Query Message
Response Message
2.2 Modbus/TCP Communication Message Frame
Query Messages sent from the client (controller) and Response Messages sent from the servers (servo
amplifiers) are both sent in the following message frame format. Messages are sent by using TCP/IP.
Unit Identifier
Function
Data
Query Message
Client
(controller)
Response Message
Unit Identifier
Function
Data
Server
(servo amplifier)
A message frame is composed of six message fields.
When a server (servo amplifier) received a Query Message sent from the client (controller) without errors,
the function code in the Query Message is copied into the Function in a Response Message. When a server
(servo amplifier) received a Query Message with an error, the server returns a value obtained by adding
"80h" to the function code value in the Query Message to the client. Judge the occurrence of an error by
checking the function code in the Response Message on the controller side.
Length Field (Message length) 16 bits Set "0006h".
Unit Identifier (Unit identifier) 8 bits Set "FFh".
Function (Function field) 8 bits Set "03h".
Starting Address (Start address)
(Note 1)
No. of Points
(Number of read points)
16 bits Set any value.
16 bits Set "0000h".
16 bits Set a start address of the holding registers to read.
16 bits Set the number of points of data to read starting from the start address of the
holding registers from which data is read.
Set the number of read points described in the list of holding registers.
To read the data in continuous registers, set a value obtained by adding the
number of read points of the target registers to this number.
The following shows the information in each Response Message.
Message field Description
Transaction Identifier
(Transaction identifier)
Protocol Identifier
(Protocol identifier)
Length Field (Message length) The byte length from Unit Identifier to Data is returned.
Unit Identifier (Unit identifier) Unit Identifier received from the client (controller) is copied and returned.
Function (Function field) When the message was received without errors, "03h" is returned.
Byte Count (Byte count) The value "08h" is returned. This means that data of 8 frames is returned.
Data (Read data) Data starting from the start address is returned.
Transaction Identifier received from the client (controller) is copied and returned.
The value "0000h" is returned.
Lower-bit value of the register 2B05h: "5678h"
Higher-bit value of the register 2B05h: "1234h"
Value of the register 2B06h: "1000h"
Value of the register 2B07h: "2000h"
Starting Address No. of Points
H L H L
Data
H L H L H L H L
2 - 5
Page 21
2. MODBUS/TCP PROTOCOL
2.3.3 Diagnostics (Function diagnostics: 08h)
Use this register when performing the communication check from the client (controller). When a server
(servo amplifier) receives a Query Message, it sends the received data as a Response Message without any
changes to the client (controller).
(1) Message frame
Query Message
Transaction
Identifier
16 bits 0000h 0006h FFh 08h 00h 00h 8 bits 8 bits
Protocol
Identifier
Length Field
Unit
Identifier
Function
Message field Size Description
Transaction Identifier
(Transaction identifier)
Protocol Identifier
(Protocol identifier)
Length Field (Message length) 16 bits Set "0006h".
Unit Identifier (Unit identifier) 8 bits Set "FFh".
Function (Function field) 8 bits Set "08h".
Sub Function (Sub function) 16 bits Set "0000h".
Data (Data) 16 bits Set 2-byte length data.
16 bits Set any value.
16 bits Set "0000h".
When a value other than "0000h" is set, a communication error occurs.
Response Message
Transaction
Identifier
16 bits 0000h 0006h FFh 08h 00h 00h 8 bits 8 bits
Protocol
Identifier
Length Field
Unit
Identifier
Function
Message field Size Description
Transaction Identifier
(Transaction identifier)
Protocol Identifier
(Protocol identifier)
Length Field (Message length) 16 bits The byte length from Unit Identifier to Data is returned.
Unit Identifier (Unit identifier) 8 bits Unit Identifier received from the client (controller) is copied and returned.
Function (Function field) 8 bits When the message was received without errors, "08h" is returned.
Sub Function (Sub function) 16 bits The value "0000h" is returned.
Data (Data) 16 bits The data set in the Query Message is returned.
16 bits Transaction Identifier received from the client (controller) is copied and returned.
16 bits The value "0000h" is returned.
Sub Function Data
H L H L
Sub Function Data
H L H L
2 - 6
Page 22
2. MODBUS/TCP PROTOCOL
(2) Usage example
The following shows a setting example of when the diagnosis function is used.
Query Message
Transaction
Identifier
16 bits 0000h 0006h FFh 08h 00h 00h 12h 34h
Protocol
Identifier
Length Field
Unit
Identifier
Function
Set the following values to each Query Message.
Message field Description
Transaction Identifier
(Transaction identifier)
Protocol Identifier
(Protocol identifier)
Length Field (Message length) Set "0006h".
Unit Identifier (Unit identifier) Set "FFh".
Function (Function field) Set "08h".
Sub Function (Sub function) Set "0000h".
Data (Data) When setting 1234h, set values as follows:
Set any value.
Set "0000h".
H: "12h"
L: "34h"
Response Message
Transaction
Identifier
16 bits 0000h 0006h FFh 08h 00h 00h 12h 34h
Protocol
Identifier
Length Field
Unit
Identifier
Function
The following shows the information in each Response Message.
Message field Description
Transaction Identifier
(Transaction identifier)
Protocol Identifier
(Protocol identifier)
Length Field (Message length) The byte length from Unit Identifier to Data is returned.
Unit Identifier (Unit identifier) Unit Identifier received from the client (controller) is copied and returned.
Function (Function field) When the message was received without errors, "08h" is returned.
Sub Function (Sub function) The value "0000h" is returned.
Data (Data) The value "1234h" set in the Query Message is returned.
Transaction Identifier received from the client (controller) is copied and returned.
The value "0000h" is returned.
H: "12h"
L: "34h"
Sub Function Data
H L H L
Sub Function Data
H L H L
2 - 7
Page 23
2. MODBUS/TCP PROTOCOL
2.3.4 Preset Multiple Registers (Writing data in multiple holding registers: 10h)
Data is written to consecutive holding registers for the specified number of data points starting from the
specified register address.
(1) Message frame
Query Message
Transaction
Identifier
16 bits 0000h 16 bits FFh 10h 8
Protocol
Identifier
Length Field
Unit
Identifier
Function
Message field Size Description
Transaction Identifier
(Transaction identifier)
Protocol Identifier
(Protocol identifier)
Length Field (Message length) 16 bits Set the byte length from Unit Identifier to Data.
Unit Identifier (Unit identifier) 8 bits Set "FFh".
Function (Function field) 8 bits Set "10h".
Starting Address (Start address)
(Note)
No. of Registers
(Number of registers to write)
Byte Count (Byte count) 16 bits Set the size of the data to write.
Data (Writing data) (Note) 16 bits × n Set the data to write.
16 bits Set any value.
16 bits Set "0000h".
16 bits Set the start address of the holding registers to which data is written.
16 bits Set the number of points of data to write starting from the start address of the
holding registers to which data is written.
Set the number of write points described in the list of holding registers.
To write data in continuous registers, set a value obtained by adding the number
of write points of the target registers to this number.
Length Field (Message length) Set the byte length from Unit Identifier to Data.
Unit Identifier (Unit identifier) Set "FFh".
Function (Function field) Set "10h".
Starting Address (Start address) Set "2102h", the start address of the registers to which data is written.
No. of Registers
(Number of registers to write)
Byte Count (Byte count) Set "04h". This means that data of 4 frames is sent.
Data (Writing data) Set values in order starting from the start address.
Set any value.
Set "0000h".
Set "02h", because the total number of write points of the Modbus register 2102h is 2.
Lower-bit value of the register 2102h: "0100h"
Higher-bit value of the register 2102h: "0000h"
Response Message
Transaction
Identifier
2 × 8 bits 0000h 0006h FFh 10h 21h 02h 00h 02h
Protocol
Identifier
Length Field
Unit
Identifier
Function
Starting Address No. of Points
H L H L
The following shows the information in each Response Message.
Message field Size Description
Transaction Identifier
(Transaction identifier)
Protocol Identifier
(Protocol identifier)
Length Field (Message length) 16 bits The byte length from Unit Identifier to Data is returned.
Unit Identifier (Unit identifier) 8 bits Unit Identifier received from the client (controller) is copied and returned.
Function (Function field) 8 bits When the message was received without errors, "10h" is returned.
Starting Address (Start address) 16 bits The value "2102h", the start address of the holding registers to which the data
No. of Registers
(Number of registers to write)
16 bits Transaction Identifier received from the client (controller) is copied and returned.
16 bits The value "0000h" is returned.
was written is returned.
H: "21h"
L: "02h"
16 bits The number of registers to write "02h" is returned.
No. of
Registers
(Number of
registers to
write)
No. of
Registers
Byte
Count
Continuous
read/write
Data
Setting value
00000100h
2 - 9
Page 25
2. MODBUS/TCP PROTOCOL
2.3.5 Processing at occurrence of an error
In Modbus/TCP communication, when the Query Message sent from the client (controller) includes an
incorrect value, the server (servo amplifier) returns an exception response to the client (controller).
If an error is detected in the TCP/IP layer, the server (servo amplifier) returns no message to the client
(controller).
When an exception response occurs, a value obtained by adding "80h" to the function code sent in the
Query Message is returned with an exception code.
However, no exception response occurs in the following cases.
Function code "03h" (Read Holding Registers)
When data can be read from even one of consecutive registers, no exception response occurs. In this
case, "0" is returned to the register data that cannot be read.
Function code "10h" (Preset Multiple Registers)
When data can be written into even one of consecutive registers, no exception response occurs.
Response Message
Transaction
Identifier
16 bits 0000h 0003h FFh 8 bits 8 bits
Transaction Identifier
(Transaction identifier)
Protocol Identifier
(Protocol identifier)
Length Field (Message length) 16 bits The byte length from Unit Identifier to Data is returned.
Unit Identifier (Unit identifier) 8 bits Unit Identifier received from the client (controller) is copied and returned.
Function (Function field) 8 bits A value obtained by adding "80h" to the function code of the Query Message is
Exception Code (Exception code) 8 bits An exception code is set. For details of exception codes, refer to the following
List of exception codes
Code Error name Description
01h ILLEGAL FUNCTION
02h ILLEGAL DATA ADDRESS
03h ILLEGAL DATA VALUE
Protocol
Identifier
Message field Size Description
Length Field
(Illegal function code)
(Illegal address)
(Illegal data)
Unit
Identifier
16 bits Transaction Identifier received from the client (controller) is copied and returned.
16 bits The value "0000h" is returned.
Function
returned.
When Function is "03h": "83h"
When Function is "08h": "88h"
When Function is "10h": "90h"
When an unsupported Function (example: "01h") is used, "Function + 80h"
(example: "81h") is returned.
"List of exception codes".
The Query Message sent from the client set a function code that the server does not
support.
The Query Message sent from the client set a register address that the server does not
support. (Ex: No register address is set, or reading or writing data from/to registers is
not available.)
The Query Message sent from the client set data that the register cannot handle. (Ex: A
value out of the setting range is set, or "0" is set to No. of Registers.)
Exception
Code
2 - 10
Page 26
3. STARTUP
3. STARTUP
POINT
When using Modbus/TCP communication, set [Pr. PN10 Ethernet
communication time-out selection] before driving the servo motor. The servo
motor may continue to operate after the communication is disabled due to a
communication shut-off or other causes.
Setting [Pr. PN10 Ethernet communication time-out selection] to several
milliseconds may trigger [AL. 86.4] in the following condition. The power of the
servo amplifier is cycled, or an instantaneous power failure occurs during
Modbus/TCP communication.
This chapter describes the network setting of the MR-JE-_C servo amplifier. Refer to "MR-JE-_C Servo
Amplifier Instruction Manual" and "MR-JE-_C Servo Amplifier Instruction Manual (Profile Mode)" for other
startup settings.
3.1 Modbus/TCP initial communication setting
Make the initial communication settings in the following procedure.
IP address setting
Network setting
Subnet mask setting
Default gateway setting
Server (servo amplifier)
power cycling
Client (controller)
Modbus/TCP communication start
[IP address setting]
The initial value is 192.168.3.0. To change the initial value, set it with either of the
following (1) or (2). (Refer to section 3.2.)
(1) Identification number setting rotary switch (SW1/SW2)
(2) Parameter ([Pr. PN11] to [Pr. PN14])
[Subnet mask setting]
The initial value is 255.255.255.0. Set it with the parameters ([Pr. PN15] to [Pr. PN18]).
(Refer to chapter 4.)
[Default gateway setting]
The initial value is 192.168.3.1. Set it with the parameters ([Pr. PN19] to [Pr. PN22]).
(Refer to chapter 4.)
[Server (servo amplifier) power cycling]
The settings of the IP address, subnet mask, and default gateway are reflected.
[Modbus/TCP communication start]
Start Modbus/TCP communication of the client (controller).
Communication
start
3 - 1
Page 27
3. STARTUP
3.2 IP address setting
POINT
Use a twisted pair cable with Ethernet Category 5e (1000BASE-T) or higher as
an Ethernet cable. The maximum cable length between nodes is 100 m.
Use a hub with a transmission speed of 100 Mbps or faster when branching the
Ethernet communication using a switching hub.
For the switching hub without the auto-negotiation function, set it to the
transmission speed 100 Mbps and half duplex.
The initial value of the IP address is 192.168.3.0.
The 4th octet can be set to 1 to 255 by using the identification number setting
rotary switch (SW1/SW2).
Cycle the power of the servo amplifier after changing the parameter setting of
the IP address or identification number setting rotary switch (SW1/SW2).
The IP address range for Modbus/TCP communication is between 0.0.0.0 and
255.255.255.255. Set the IP address within the range.
Set the IP address with the identification number setting rotary switch (SW1/SW2) on the display of the servo
amplifier or MR Configurator2.
When the IP address is changed with the identification number setting rotary switch (SW1/SW2), change it
before powering on the servo amplifier.
The IP address you set can be checked in the system configuration window of MR Configurator 2.
The IP address can be set as follows.
Identification number setting
rotary switch (SW1/SW2)
00h
01h to FFh
IP address
1st octet The setting value of [Pr. PN11] is used.
2nd octet The setting value of [Pr. PN12] is used.
3rd octet The setting value of [Pr. PN13] is used.
4th octet The setting value of [Pr. PN14] is used.
1st octet The setting value of [Pr. PN11] is used.
2nd octet The setting value of [Pr. PN12] is used.
3rd octet The setting value of [Pr. PN13] is used.
4th octet
The setting value of the identification number setting rotary switch
(SW1/SW2) is used.
3 - 2
Page 28
4. PARAMETERS
4. PARAMETERS
Never make a drastic adjustment or change to the parameter values as doing so
will make the operation unstable.
Do not change the parameter settings as described below. Doing so may cause
an unexpected condition, such as failing to start up the servo amplifier.
Changing the values of the parameters for manufacturer setting
CAUTION
4.1 List of communication-related parameters
Setting a value out of the range
Changing the fixed values in the digits of a parameter
When you write parameters with the controller, make sure that the identification
No. of the servo amplifier is set correctly. Otherwise, the parameter settings of
another identification No. may be written, possibly causing the servo amplifier to
be an unexpected condition.
POINT
To enable a parameter whose symbol is preceded by *, cycle the power after
setting it. However, the time will be longer depending on a setting value of [Pr.
PF25 Instantaneous power failure tough drive - Detection time] when
"instantaneous power failure tough drive selection" is enabled in [Pr. PA20].
In Modbus/TCP communication, the following parameter cannot be used.
[Pr. PN02 Communication error detection time]
No. Symbol Name
PN01 For manufacturer setting 0h
PN02 CERT Communication error detection time 1000 ms [ms]
PN03 For manufacturer setting 0000h
PN04 0000h
PN05 0000h
PN06 0000h
PN07 0000h
PN08 0000h
PN09 1
PN10 EIC Ethernet communication time-out selection 0 [s]
PN11 *IPAD1 IP address setting 1 192
PN12 *IPAD2 IP address setting 2 168
PN13 *IPAD3 IP address setting 3 3
PN14 *IPAD4 IP address setting 4 0
PN15 *SNMK1 Subnet mask setting 1 255
PN16 *SNMK2 Subnet mask setting 2 255
PN17 *SNMK3 Subnet mask setting 3 255
PN18 *SNMK4 Subnet mask setting 4 0
PN19 *DGW1 Default gateway setting 1 192
PN20 *DGW2 Default gateway setting 2 168
PN21 *DGW3 Default gateway setting 3 3
PN22 *DGW4 Default gateway setting 4 1
PN23 *KAA KeepAlive time 3600 [s]
PN24 *IPAF1 IP address filter 1 0
PN25 *IPAF2 IP address filter 2 0
PN26 *IPAF3 IP address filter 3 0
Initial
value
Unit
4 - 1
Page 29
4. PARAMETERS
No. Symbol Name
PN27 *IPAF4 IP address filter 4 0
PN28 *IPFR2 IP address filter 2 range setting 256
PN29 *IPFR3 IP address filter 3 range setting 256
PN30 *IPFR4 IP address filter 4 range setting 256
PN31 *IPOA1 Operation specification IP address 1 0
PN32 *IPOA2 Operation specification IP address 2 0
PN33 *IPOA3 Operation specification IP address 3 0
PN34 *IPOA4 Operation specification IP address 4 0
PN35 *IPOR3 Operation specification IP address 3 range specification 256
PN36 *IPOR4 Operation specification IP address 4 range specification 256
PN37 For manufacturer setting 0000h
PN38 0000h
PN39 0000h
PN40 0000h
PN41 0000h
PN42 0000h
PN43 0000h
PN44 0000h
PN45 0000h
PN46 0000h
PN47 0000h
PN48 0000h
Initial
value
Unit
4 - 2
Page 30
4. PARAMETERS
4.2 Detailed list of communication-related parameters
POINT
Set a value to each "x" in the "Setting digit" columns.
No./symbol/
name
PN10
*CONN
Ethernet
communication time-out
selection
PN11
*IPAD1
IP address
setting 1
Setting
digit
Set the network number of the servo amplifier.
Set the time until [AL. 86.4 Network communication error 4] is detected.
Setting "0" will disable the detection of [AL. 86.4 Network communication error 4].
This parameter is enabled with SLMP.
Setting range: 0 to 60
Set the 1st octet of the IP address in decimal.
Set the IP address assigned by the network administrator.
When SLMP command (IPAdressSet) is received, the setting of the first octet will be
written to this parameter.
Refer to table 5.1 for the relation between the setting value of the identification
number setting rotary switch and the parameter setting value.
Setting range: 0 to 255
Table 4.1 Relation between IP address setting and identification number setting rotary switch
Identification number
setting rotary switch
(SW1/SW2)
2nd octet The setting value of [Pr. PN12] is used.
3rd octet The setting value of [Pr. PN13] is used.
4th octet The setting value of [Pr. PN14] is used.
2nd octet The setting value of [Pr. PN12] is used.
3rd octet The setting value of [Pr. PN13] is used.
PN12
*IPAD2
IP address
setting 2
PN13
*IPAD3
IP address
setting 3
00h
01h to FFh
Set the 2nd octet of the IP address in decimal.
Set the IP address assigned by the network administrator.
When SLMP command (IPAdressSet) is received, the setting of the second octet will
be written to this parameter.
Refer to table 5.1 for the relation between the setting value of the identification
number setting rotary switch and the parameter setting value.
Setting range: 0 to 255
Set the 3rd octet of the IP address in decimal.
Set the IP address assigned by the network administrator.
When SLMP command (IPAdressSet) is received, the setting of the third octet will
be written to this parameter.
Refer to table 5.1 for the relation between the setting value of the identification
number setting rotary switch and the parameter setting value.
Setting range: 0 to 255
1st octet The setting value of [Pr. PN11] is used.
1st octet The setting value of [Pr. PN11] is used.
4th octet
Function
IP address
The setting value of the identification number setting
rotary switch (SW1/SW2) is used.
Initial
value
[unit]
0
[s]
192
168
3
4 - 3
Page 31
4. PARAMETERS
No./symbol/
name
PN14
*IPAD4
IP address
setting 4
PN15
*SNMK1
Subnet mask
setting 1
PN16
*SNMK2
Subnet mask
setting 2
PN17
*SNMK3
Subnet mask
setting 3
PN18
*SNMK4
Subnet mask
setting 4
PN19
*DGW1
Default
gateway
setting 1
PN20
*DGW2
Default
gateway
setting 2
PN21
*DGW3
Default
gateway
setting 3
PN22
*DGW4
Default
gateway
setting 4
PN23
*KAA
KeepAlive
time
PN24
*IPAF1
IP address
filter 1
Setting
digit
Set the 4th octet of the IP address in decimal.
Set the IP address assigned by the network administrator.
When SLMP command (IPAdressSet) is received, the setting of the fourth octet will
be written to this parameter.
Refer to table 5.1 for the relation between the setting value of the identification
number setting rotary switch and the parameter setting value.
Setting range: 0 to 255
Set the 1st octet of the subnet mask in decimal.
Set the subnet mask assigned by the network administrator.
Setting range: 0 to 255
Set the 2nd octet of the subnet mask in decimal.
Set the subnet mask assigned by the network administrator.
Setting range: 0 to 255
Set the 3rd octet of the subnet mask in decimal.
Set the subnet mask assigned by the network administrator.
Setting range: 0 to 255
Set the 4th octet of the subnet mask in decimal.
Set the subnet mask assigned by the network administrator.
Setting range: 0 to 255
Set the 1st octet of the default gateway in decimal.
Set the default gateway assigned by the network administrator.
Setting range: 0 to 255
Set the 2nd octet of the default gateway in decimal.
Set the default gateway assigned by the network administrator.
Setting range: 0 to 255
Set the 3rd octet of the default gateway in decimal.
Set the default gateway assigned by the network administrator.
The default gateway can also be changed simultaneously by the SLMP command
(IPAdressSet).
Setting range: 0 to 255
Set the 4th octet of the default gateway in decimal.
Set the default gateway assigned by the network administrator.
The default gateway can also be changed simultaneously by the SLMP command
(IPAdressSet).
Setting range: 0 to 255
Set the time interval between the transmissions of the alive check message (Keep
Alive ACK) for TCP communication.
If no response to the alive check message is received, the connection is forcibly
closed after the time (setting value × 8 times) has elapsed. In the initial setting, the
connection is closed after 8 hours (3600 [s] × 8 times = 28800 [s]) have elapsed.
Setting range: 1 to 7200
Set the 1st octet of the IP address of the network device allowed to be connected in
decimal.
When [Pr. PN24] to [Pr. PN27] are all set to "0", the function is disabled.
Setting range: 0 to 255
Function
Initial
value
[unit]
0
255
255
255
0
192
168
3
1
3600
[s]
0
4 - 4
Page 32
4. PARAMETERS
No./symbol/
name
PN25
*IPAF2
IP address
filter 2
PN26
*IPAF3
IP address
filter 3
PN27
*IPAF4
IP address
filter 4
PN28
*IPAF2
IP address
filter 2 range
specification
PN29
*IPAF3
IP address
filter 3 range
specification
PN30
*IPAF4
IP address
filter 4 range
specification
PN31
*IPOA1
Operation
specification
IP address 1
Setting
digit
Set the 2nd octet of the IP address of the network device allowed to be connected in
decimal.
When [Pr. PN24] to [Pr. PN27] are all set to "0", the function is disabled.
Setting range: 0 to 255
Set the 3rd octet of the IP address of the network device allowed to be connected in
decimal.
When [Pr. PN24] to [Pr. PN27] are all set to "0", the function is disabled.
Setting range: 0 to 255
Set the 4th octet of the IP address of the network device allowed to be connected in
decimal.
When [Pr. PN24] to [Pr. PN27] are all set to "0", the function is disabled.
Setting range: 0 to 255
Set a value for the 2nd octet range of the IP address of the network device allowed
to be connected. The range for the IP address of the network device allowed to be
connected is between [Pr. PN25] and [Pr. PN28].
Set a value in decimal.
Setting "256" will disable the function.
Setting range: 0 to 256
Set a value for the 3rd octet range of the IP address of the network device allowed to
be connected. The range for the IP address of the network device allowed to be
connected is between [Pr. PN26] and [Pr. PN29].
Set a value in decimal.
Setting "256" will disable the function.
Setting range: 0 to 256
Set a value for the 4th octet range of the IP address of the network device allowed to
be connected. The range for the IP address of the network device allowed to be
connected is between [Pr. PN27] and [Pr. PN30].
Set a value in decimal.
Setting "256" will disable the function.
Setting range: 0 to 256
Set the 1st octet of the IP address of the network device allowed to be connected in
decimal.
When [Pr. PN31] to [Pr. PN34] are set to all "0", the function is disabled.
When the function is enabled, the servo amplifier allows the following data 1) to be
imported only if the IP address of the client (external device) matches with the
operation specification IP address. If they are mismatched, the data is discarded.
1) Modbus/TCP function code 10h
Monitoring, parameter setting, and test operation can be executed via Ethernet when
the IP addresses of a personal computer (MR Configurator2) and GOT are within the
range of the operation specification IP address. When out of the range,
communication to the servo amplifier cannot be established.
Setting range: 0 to 255
Function
Initial
value
[unit]
0
0
0
256
256
256
0
4 - 5
Page 33
4. PARAMETERS
No./symbol/
name
PN32
*IPOA2
Operation
specification
IP address 2
PN33
*IPOA3
Operation
specification
IP address 3
PN34
*IPOA4
Operation
specification
IP address 4
PN35
*IPOR3
Operation
specification
IP address 3
range
specification
PN36
*IPOA4
Operation
specification
IP address 4
range
specification
Setting
digit
Set the 2nd octet of the IP address of the network device allowed to be connected in
decimal.
When [Pr. PN31] to [Pr. PN34] are all set to "0", the function is disabled.
When the function is enabled, the servo amplifier allows the following data 1) to be
imported only if the IP address of the client (external device) matches with the
operation specification IP address. If they are mismatched, the data is discarded.
1) Modbus/TCP function code 10h
Monitoring, parameter setting, and test operation can be executed via Ethernet when
the IP addresses of a personal computer (MR Configurator2) and GOT are within the
range of the operation specification IP address. When out of the range,
communication to the servo amplifier cannot be established.
Setting range: 0 to 255
Set the 3rd octet of the IP address of the network device allowed to be connected in
decimal.
When [Pr. PN31] to [Pr. PN34] are all set to "0", the function is disabled.
When the function is enabled, the servo amplifier allows the following data 1) to be
imported only if the IP address of the client (external device) matches with the
operation specification IP address. If they are mismatched, the data is discarded.
1) Modbus/TCP function code 10h
Monitoring, parameter setting, and test operation can be executed via Ethernet when
the IP addresses of a personal computer (MR Configurator2) and GOT are within the
range of the operation specification IP address. When out of the range,
communication to the servo amplifier cannot be established.
Setting range: 0 to 255
Set the 4th octet of the IP address of the network device allowed to be connected in
decimal.
When [Pr. PN31] to [Pr. PN34] are all set to "0", the function is disabled.
When the function is enabled, the servo amplifier allows the following data 1) to be
imported only if the IP address of the client (external device) matches with the
operation specification IP address. If they are mismatched, the data is discarded.
1) Modbus/TCP function code 10h
Monitoring, parameter setting, and test operation can be executed via Ethernet when
the IP addresses of a personal computer (MR Configurator2) and GOT are within the
range of the operation specification IP address. When out of the range,
communication to the servo amplifier cannot be established.
Setting range: 0 to 255
Set a value for the 3rd octet range of the IP address of the network device allowed to
be connected.
The range for the IP address of the network device allowed to be connected is
between [Pr. PN33] and [Pr. PN35]. Set a value in decimal.
Setting "256" will disable the function.
Setting range: 0 to 256
Set a value for the 4th octet range of the IP address of the network device allowed to
be connected.
The range for the IP address of the network device allowed to be connected is
between [Pr. PN34] and [Pr. PN36]. Set a value in decimal.
Setting "256" will disable the function.
Setting range: 0 to 256
Function
Initial
value
[unit]
0
0
0
256
256
4 - 6
Page 34
5. MANUFACTURER FUNCTIONS
5. MANUFACTURER FUNCTIONS
5.1 Stroke end
When LSP (Forward rotation stroke end) or LSN (Reverse rotation stroke end) is turned off, a slow stop is
performed by either of the following stop methods.
During rotation at constant speed During deceleration to a stop
No S-pattern acceleration/
deceleration
With S-pattern acceleration/
deceleration
Servo motor speed
0 r/min
LSP
or
LSN
ON
OFF
Perform a return as follows when the stroke end is detected.
Mode Return method
Profile position mode (pp) Input the position command of the direction opposite to the limit to Target position (607Ah).
Profile velocity mode (pv) Input the speed command of the direction opposite to the limit to Target velocity (60FFh).
Operation status
Part of droop
pulses
No S-pattern acceleration/
deceleration
With S-pattern acceleration/
deceleration
Servo motor speed
LSP
or
LSN
0 r/min
ON
OFF
Remark
Travels for the droop pulses
portion and stops the servo
motor.
A difference will be
Part of
droop
generated between the
pulses
command position and the
current position.
Perform a home position
return again.
5 - 1
Page 35
5. MANUFACTURER FUNCTIONS
5.2 One-touch tuning
Refer to "MR-JE-_C Servo Amplifier Instruction Manual" for one-touch tuning. Using One-touch tuning mode
(2D50h) allows one-touch tuning from the client (controller).
Setting a value of "1" to "3" starts onetouch tuning. After one-touch tuning is
completed, the setting value automatically
changes to "0".
0: During one-touch tuning stop
1: Basic mode
2: High mode
3: Low mode
Regardless of whether one-touch tuning is
properly completed or not, the setting
value changes to 100% at the completion.
Unit: %
Writing "1EA5h" stops one-touch tuning.
Writing a value other than "1EA5h" sets
0609 0030h Value range of parameter
exceeded in SDO Abort Code.
The parameter changed in one-touch
tuning can be returned to the value before
the change.
0000h: Restores the initial value.
0001h: Restores the value before one-
touch tuning.
The setting value of the restored
parameter is stored to the EEP-ROM.
The following shows the details of the onetouch tuning error codes.
0000h: Finished normally
C000h: Tuning canceled
C001h: Overshoot exceeded
C002h: Servo-off during tuning
C003h: Control mode error
C004h: Time-out
C005h: Load to motor inertia ratio
misestimated
C00Fh: One-touch tuning disabled
5 - 2
Page 36
5. MANUFACTURER FUNCTIONS
(2) Procedure of one-touch tuning via a network
Perform one-touch tuning via a network in the following procedure.
Start
Startup of the system
Operation
One-touch tuning execution
One-touch tuning in progress
One-touch tuning completion
Tuning result check
End
Refer to "MR-JE-_C Servo Amplifier Instruction Manual" and "MR-JE-_C
Servo Amplifier Instruction Manual (Profile Mode)" to start the system.
Rotate the servo motor by a controller. (One-touch tuning cannot be
performed if the servo motor is not operating.)
Write a value corresponding to the response mode (High mode, basic mode,
or Low mode) to perform in One-touch tuning mode (2D50h) during servo
motor driving to perform one-touch tuning.
Gains and filters will be adjusted automatically. During one-touch tuning, the
progress can be checked with One-touch tuning status (2D51h).
Check whether one-touch tuning is completed normally with One-touch tuning
Error Code (2D54h). When the one-touch tuning is completed normally, the
parameters will be set automatically. Refer to "MR-JE-_C Servo Amplifier
Instruction Manual" for the parameters that are set automatically.
After a tuning error is returned, take the appropriate action according to "MRJE-_C Servo Amplifier Instruction Manual".
Check the tuning result.
If the tuning result is not satisfactory, you can return the parameter to the
value before the one-touch tuning or the initial value using One-touch tuning
Clear (2D53h).
5 - 3
Page 37
5. MANUFACTURER FUNCTIONS
2
2
2
2
5.3 Machine diagnosis function
This function estimates the friction and vibrational component of the drive system in the equipment based on
the data in the servo amplifier, and recognizes an error in the machine parts, including a ball screw and
bearing. The information of the machine diagnosis function can be obtained with the following resisters.
C20h
Bit 0 to Bit 3
Friction estimation status at forward rotation
Bit 4 to Bit 7
Friction estimation status at reverse rotation
Bit 8 to Bit 11
Vibration estimation status
During estimation
During estimationEstimation completed
During estimation
Estimation completed
Estimation completed
C21h/2C22h
C23h/2C24h
C25h to 2C28h
Address Read/write Name
2C20h Reading Machine diagnostic status 2 bytes Refer to section 6.1.
2C21h Reading
2C22h Reading
2C23h Reading
2C24h Reading
2C25h Reading
2C26h Reading
2C27h Reading
2C28h Reading
Static friction torque at
forward rotation
Dynamic friction torque at
forward rotation
(at rated speed)
Static friction torque at
reverse rotation
Dynamic friction torque at
reverse rotation
(at rated speed)
Oscillation frequency during
motor stop
Vibration level during motor
stop
Oscillation frequency during
motor operating
Vibration level during motor
operating
5.4 Servo amplifier life diagnosis function
Undefined valueEstimated value
Undefined valueEstimated value
Undefined valueEstimated value
Data
type
2 bytes
2 bytes
2 bytes
2 bytes
2 bytes
2 bytes
2 bytes
2 bytes
Initial
value
Description
Static friction at forward rotation torque is
displayed in increments of 0.1%.
Kinetic friction at forward rotation torque at
the rated speed is displayed in increments
of 0.1%.
Static friction at reverse rotation torque is
displayed in increments of 0.1%.
Kinetic friction at reverse rotation torque at
the rated speed is displayed in increments
of 0.1%.
Vibration frequency during stop/servo-lock
is displayed in increments of 1 Hz.
Vibration level during stop/servo-lock is
displayed in increments of 0.1%.
Vibration frequency during operation is
displayed in increments of 1 Hz.
Vibration level during operation is
displayed in increments of 0.1%.
You can check the cumulative energization time and the number of on/off times of the inrush relay based on
the data in the servo amplifier. This function gives an indication of the replacement time for parts of the servo
amplifier including a capacitor and a relay before they malfunction. The information of the servo amplifier life
diagnosis function can be obtained with the following resisters.
Address Read/write Name
2C18h Reading Power ON cumulative time 4 bytes
2C19h Reading Inrush relay ON/OFF number 4 bytes
Data
type
Initial
value
Description
The cumulative energization time of the
servo amplifier is returned.
The number of on/off times of the inrush
relay of the servo amplifier is returned.
5 - 4
Page 38
6. MODBUS REGISTERS
6. MODBUS REGISTERS
Each data such as control parameters, command values, and feedback values is handled as an object
composed of an address, object name, data type, access rule, and other elements. The object data can be
exchanged between the client (controller) and the servers (servo amplifiers).
6.1 List of registers
No. of
Continuous
Points/
No. of
Registers
read/
continuous
write
Impossible
Impossible
Impossible
Impossible
Impossible
2 Possible
Address Name and function
1000 Supported profile information (Device Type)
The servo drive defined with the CiA 402
profile is indicated.
1001 Alarm information (Error Register)
The error occurrence is returned.
Bit 0: Turns on when an alarm has occurred.
Bit 1 to Bit 7: Unused
1010 Writing command to EEP-ROM (Store
parameters)
The number of entries is returned.
Saving all parameters (Save all parameters)
[Writing]
Writing "save" (= 65766173h) saves all the
objects which can be stored in the EEP-ROM.
[Reading]
Bit 0: 0: The parameter cannot be saved with
the command. (A parameter is being
saved.)
1: The parameter can be saved with the
command. (No parameter is being
saved.)
Bit 1: 0: The parameter is not automatically
saved.
1011 Restoring default EEP-ROM parameters
(Restore default parameters)
The number of entries is returned.
Restoring all default parameters (Restore all
default parameters)
The parameter of the servo amplifier can be
rewritten with the factory setting.
When "64616F6Ch" (= reverse order of ASCII
code of "load") is written to Restore all default
parameters (1011h: 1) and the power is cycled,
the parameter is initialized.
1018 Device information (Identity Object)
The number of entries is returned.
Vendor ID (Vendor ID)
The vendor ID of a servo amplifier is returned.
Product number (Product Code)
The servo amplifier serial number is returned.
Revision number (Revision Number)
The revision number of a servo amplifier is
returned.
Serial number (Serial Number)
The serial number of the network module is
returned.
2001
PA01 to PA32
to
The values of the basic setting parameters
2021
([Pr. PA_ _ ]) can be obtained and set.
For details, refer to "MR-JE-_C Servo Amplifier
Instruction Manual".
Data
Read/
type
4
Reading 00020192h 00020192h
bytes
1
Reading 00h
bytes
1
Reading 1 01h 3
bytes
4
bytes
bytes
bytes
bytes
bytes
bytes
bytes
bytes
bytes
Read/
1
Reading 1 01h (fixed) 3
4
Read/
1
Reading 4 04h (fixed) 9
4
Reading 00000002h 00000002h
4
Reading 00001003h 00001003h
4
Reading 00000000h
4
Reading 00000000h 00000000h
4
Read/
Initial value Range Unit
write
(fixed)
to
01h
00000001h
write
00000001h
write
(fixed)
(fixed)
to
FFFFFFFFh
to
FFFFFFFFh
write
Saved
ROM
Parameter
PA01
PA32
to EEP-
2
1
to
6 - 1
Page 39
6. MODBUS REGISTERS
Address Name and function
2081
PB01 to PB64
to
The values of the gain/filter setting parameters
20C0
([Pr. PB_ _ ]) can be obtained and set.
For details, refer to "MR-JE-_C Servo Amplifier
Instruction Manual".
2101
PC01 to PC80
to
The values of the extension setting parameters
2150
([Pr. PC_ _ ]) can be obtained and set.
For details, refer to "MR-JE-_C Servo Amplifier
Instruction Manual".
2181
PD01 to PD48
to
The values of the I/O setting parameters ([Pr.
21B0
PD_ _ ]) can be obtained and set.
For details, refer to "MR-JE-_C Servo Amplifier
Instruction Manual".
2201
PE01 to PE64
to
The values of the extension setting 2
2240
parameters ([Pr. PE_ _ ]) can be obtained and
set.
For details, refer to "MR-JE-_C Servo Amplifier
Instruction Manual".
2281
PF01 to PF48
to
The values of the extension setting 3
22B0
parameters ([Pr. PF_ _ ]) can be obtained and
set.
For details, refer to "MR-JE-_C Servo Amplifier
Instruction Manual".
2481
PT01 to PT80
to
The values of the positioning control
24D0
parameters ([Pr. PT_ _ ]) can be obtained and
set.
For details, refer to "MR-JE-_C Servo Amplifier
Instruction Manual (Profile Mode)."
2581
PN01 to PN48
to
The values of the network setting parameters
25B0
([Pr. PN_ _ ]) can be obtained and set.
Refer to chapter 5 for details.
2A00
Alarm history 0 to Alarm history 15 (Alarm
to
history newest)
2A0F
The number of entries in the latest alarm of the
alarm history is returned.
Alarm No. (Alarm No.)
The number of the alarm that has occurred is
returned.
The description is as follows.
Bit 0 to Bit 15: Alarm detail number
Bit 16 to Bit 31: Alarm number
When no history exists, "0" is returned.
Alarm occurrence time (Alarm time (Hour))
Alarm occurrence time is returned.
When no history exists, "0" is returned.
Alarm 2 No. (Alarm2 No.)
The number of the alarm that has occurred is
returned.
The description is as follows.
Bit 0 to Bit 7: Alarm detail number
Bit 8 to Bit 15: Alarm number
When no history exists, "0" is returned.
2A40 Alarm history clear (Clear alarm history)
Writing "1EA5h" clears the alarm history.
2A41 Current alarm (Current alarm)
The number of the current alarm is returned.
When no alarm has occurred, "00000000h" is
returned.
Bit 0 to Bit 15: Alarm detail number
Bit 16 to Bit 31: Alarm number
Data
type
4
bytes
Read/
write
Read/
write
Initial value Range Unit
Saved
to EEP-
ROM
Parameter
PB01
PB64
4
bytes
Read/
write
PC01
PC80
4
bytes
4
bytes
Read/
write
Read/
write
PD01
PD48
PE01
PE64
4
bytes
Read/
write
PF01
PF48
4
bytes
Read/
write
PT01
PT80
4
bytes
Read/
write
PN01
PN48
1
Read 3 03h (fixed)
bytes
4
Reading 0 00000000h
bytes
to
FFFFFFFFh
4
Reading 0 00000000h
bytes
to
hour
FFFFFFFFh
2
Reading 0 0000h to
bytes
2
Writing 1
FFFFh
bytes
4
Reading 00000000h
bytes
to
2
FFFFFFFFh
No. of
Continuous
Points/
No. of
Registers
read/
continuous
write
2 Possible
to
2 Possible
to
2 Possible
to
2 Possible
to
2 Possible
to
2 Possible
to
2 Possible
to
Impossible
6
Impossible
Impossible
6 - 2
Page 40
6. MODBUS REGISTERS
Address Name and function
2A42 Current alarm 2 (Current alarm 2)
The number of the current alarm is returned.
When no alarm has occurred, "0000h" is
returned.
Bit 0 to Bit 7: Alarm detail number
Bit 8 to Bit 15: Alarm number
2A44 Number of parameter errors (Parameter error
number)
When [AL. 37 Parameter error] has occurred,
the number of the parameters which cause the
error is returned. Refer to Parameter error list
(2A45h) for the number of each parameter
which causes the error.
2A45 Parameter error No. (Parameter error list)
When [AL. 37 Parameter error] has occurred,
the number of entries of the parameter which
causes the error is returned.
Parameter error No. 1 to 32 (Parameter error
list 1 to 32)
When [AL. 37 Parameter error] has occurred,
the 1st to 32nd numbers of the parameter which
causes the alarm is returned.
Bit 0 to Bit 7: Parameter number
Bit 8 to Bit 15: Parameter group number
00: [Pr. PA _ _ ]
01: [Pr. PB _ _ ]
02: [Pr. PC _ _ ]
03: [Pr. PD _ _ ]
04: [Pr. PE _ _ ]
05: [Pr. PF _ _ ]
06: Parameter for manufacturer setting
07: Parameter for manufacturer setting
08: Parameter for manufacturer setting
09: Parameter for manufacturer setting
0A: Parameter for manufacturer setting
0B: Parameter for manufacturer setting
0C: [Pr. PT _ _ ]
0E: [Pr. PN _ _ ]
2A46 Alarm reset (Reset alarm)
Writing the value "1EA5h" resets an alarm.
Any value other than "1EA5h" is ignored.
2A60 SDO abort code (SDO abort code)
The latest SDO Abort Code is returned.
2A64 Access log 1 (Access log 1)
The latest address that was accessed
successfully in the Modbus communication is
returned.
Bit 0 to Bit15: Address
Bit 16 to Bit 31: For manufacturer setting
2A65 Access log 2 (Access log 2)
The numbers of the addresses that were
accessed successfully in the Modbus
communication before a disconnection are
returned. In addition, when an address
containing multiple elements is accessed, the
number of the elements is returned.
2B01 Cumulative feedback pulses (Cumulative
feedback pulses)
The cumulative feedback pulses are returned.
Writing "00001EA5h" clears the cumulative
feedback pulses.
2B02 Servo motor speed (Servo motor speed)
The servo motor speed is returned.
2B03 Droop pulses (Droop pulses)
The droop pulses (encoder unit) are returned.
Data
Read/
type
2
Reading 0000h to
bytes
2
Reading 0000h to
bytes
1
Reading 20h
bytes
2
Reading 0 0000h to
bytes
2
Writing 0 0000h to
bytes
4
bytes
4
bytes
2
bytes
4
bytes
bytes
bytes
Read/
4
Reading 80000000h
4
Reading 80000000h
Initial value Range Unit
write
(32)
Read
Read
Read
write
80000000h
FFFFFFFFh
FFFFFFFFh
7FFFFFFFh
7FFFFFFFh
7FFFFFFFh
FFFFh
01F4h
(500)
20h (32)
(fixed)
FFFFh
FFFFh
00000000h
to
00000000h
to
0000h
to
FFFFh
to
to
to
No. of
Saved
ROM
Parameter
to EEP-
1
1
1 +
1
pulse 2 Possible
r/min 2 Possible
pulse 2 Possible
Points/
No. of
Registers
number
of read
points
2
2
1
Continuous
read/
continuous
write
Impossible
Impossible
Impossible
Impossible
Impossible
Impossible
Impossible
6 - 3
Page 41
6. MODBUS REGISTERS
Address Name and function
2B04 Cumulative command pulses (Cumulative
command pulses)
The cumulative command pulses are returned.
2B05 Command pulse frequency (Command pulse
frequency)
The command pulse frequency is returned.
2B06 Analog speed command voltage (Analog
speed command voltage)
The analog speed command voltage is
returned.
2B07 Analog torque limit voltage/Analog torque
command voltage (Analog torque limit
voltage/Analog torque command voltage)
The analog torque limit voltage/analog torque
command voltage is returned.
2B08 Regenerative load ratio (Regenerative load
ratio)
The regenerative load ratio is returned.
2B09 Effective load ratio (Effective load ratio)
The effective load ratio is returned.
2B0A Peak load ratio (Peak load ratio)
The peak load ratio is returned.
2B0B Instantaneous torque (Instantaneous torque)
The instantaneous torque is returned.
2B0C Position within one-revolution (Within one-
revolution position)
The position within one-revolution is returned.
2B0D Multi-revolution counter (ABS counter)
Returns the multi-revolution counter.
2B0E Load to motor inertia ratio (Load to motor inertia
ratio)
The load to motor inertia ratio is returned.
2B0F Bus voltage (Bus voltage)
The bus voltage is returned.
2B16 F/B cumulative value of A/B-phase output
pulse (Cumulative encoder out pulses)
The feedback cumulative value of A/B-phase
output pulse is returned.
2B25 Internal temperature of encoder (Internal
temperature of encoder)
The internal temperature of encoder is
returned.
2B26 Settling time (Settling time)
The settling time is returned.
2B27 Oscillation detection frequency (Oscillation
detection frequency)
The oscillation detection frequency is returned.
2B28 Number of tough drive operations (Number of
tough drive operations)
The number of tough drive operations is
returned.
2B2A Internal temperature of amplifier (Internal
temperature of amplifier)
The internal temperature of amplifier is
returned.
2B2D Unit power consumption (Unit power
consumption)
The unit power consumption is returned.
2B2E Unit total power consumption (Unit total power
consumption)
The unit total power consumption is returned.
2B2F Current position (Current position)
The current position is returned.
Data
Read/
type
4
Reading 80000000h
bytes
4
Reading 80000000h
bytes
2
bytes
2
Reading 8000h to
bytes
2
Reading 0000h to
bytes
2
Reading 0000h to
bytes
2
Reading 0000h to
bytes
2
Reading 8000h to
bytes
4
Reading 80000000h
bytes
4
Reading 80000000h
bytes
2
Reading 0000h to
bytes
2
Reading 0000h to
bytes
4
bytes
2
Reading 8000h to
bytes
2
Reading 8000h to
1
bytes
2
Reading 8000h to
bytes
2
Reading 0000h to
bytes
2
Reading 8000h to
bytes
2
Reading 8000h to
bytes
4
Reading 80000000h
bytes
4
Reading 80000000h
bytes
Initial value Range Unit
write
7FFFFFFFh
7FFFFFFFh
Read 8000h to
7FFFFFFFh
7FFFFFFFh
Read 80000000h
7FFFFFFFh
7FFFFFFFh
7FFFFFFFh
to
to
7FFFh
7FFFh
FFFFh
FFFFh
FFFFh
7FFFh
to
to
FFFFh
FFFFh
to
7FFFh
7FFFh
7FFFh
FFFFh
7FFFh
7FFFh
to
to
No. of
Saved
to EEP-
pulse 2 Possible
kpulse/s 2 Possible
V 1 Possible
V 1 Possible
% 1 Possible
% 1 Possible
% 1 Possible
% 1 Possible
pulse 2 Possible
rev 2 Possible
0.01
times
V 1 Possible
pulse 2
°C 1
ms 1
Hz 1
times 1
°C 1
W 1 Possible
Wh 2 Possible
2 Possible
Parameter
ROM
1 Possible
Points/
No. of
Registers
Continuous
read/
continuous
write
Impossible
Impossible
Impossible
Impossible
Impossible
Impossible
6 - 4
Page 42
6. MODBUS REGISTERS
Address Name and function
2B30 Command position (Command position)
The command position is returned.
2B31 Command remaining distance (Command
remaining distance)
The command remaining distance is returned.
Error Code)
An error code of the one-touch tuning is
returned. The description of the error codes is
as follows.
0000: Finished normally
C000: Tuning canceled
C001: Overshoot exceeded
C002: Servo-off during tuning
C003: Control mode error
C004: Time-out
C005: Load to motor inertia ratio misestimated
C00F: One-touch tuning disabled
603F Latest error No. display (Error code)
The latest error No. that occurred after the
power on is returned. The error number is as
follows.
1000h: Generic error
6040 Control command (Controlword)
Set control commands to control the servo
amplifier.
Bit 0: switch on
Bit 1: enable voltage
Bit 2: quick stop
Bit 3: enable operation
Bit 4 to Bit 6: operation mode specific
Bit 7: fault reset
Bit 8: halt
Bit 9: operation mode specific
Bit 10 to Bit 14: reserved
Bit 15: operation mode specific
6041 Control status (Statusword)
The current control status can be checked.
Bit 0: ready to switch on
Bit 1: switched on
Bit 2: operation enabled
Bit 3: fault
Bit 4: voltage enabled
Bit 5: quick stop
Bit 6: switch disabled
Bit 7: warning
Bit 8: reserved
Bit 9: remote
Bit 10: target reached
Bit 11: internal limit active
Bit 12 to Bit 13: operation mode specific
Bit 14 to Bit 15: reserved
605A Quick stop option code
The operation method of deceleration to a stop
can be specified.
605D Halt option code
Set how to decelerate the servo motor to a
stop at Halt reception.
Data
Read/
type
2
Writing 0 0000h/
Initial value Range Unit
write
bytes
2
Writing 0 0000h to
bytes
2
Reading 0 0000h to
bytes
2
Reading 0 0000h to
bytes
2
bytes
write
2
Reading 0000h to
Read/
0 0000h to
bytes
2
bytes
2
bytes
Read/
write
Read/
write
2 0002h
1 0001h
1EA5h
0001h
C00Fh
FFFFh
FFFFh
FFFFh
(fixed)
(fixed)
No. of
Saved
ROM
Parameter
to EEP-
1
1
1
1
1
1
PT69 1
PT69 1
Points/
No. of
Registers
Continuous
read/
continuous
write
Impossible
Impossible
Impossible
Impossible
Impossible
Impossible
Impossible
Impossible
6 - 10
Page 48
6. MODBUS REGISTERS
Address Name and function
6060 Control mode (Modes of operation)
Set the control mode.
0: No mode assigned
1: Profile position mode (pp)
3: Profile velocity mode (pv)
4: Profile torque mode (tq)
6: Homing mode (hm)
-20: Position control mode
-21: Speed control mode
-22: Torque control mode
6061 Control mode display (Modes of operation
display)
The current control mode is returned.
0: No mode assigned
1: Profile position mode (pp)
3: Profile velocity mode (pv)
4: Profile torque mode (tq)
6: Homing mode (hm)
-20: Position control mode
-21: Speed control mode
-22: Torque control mode
6063 Current position (absolute position) [ENC unit]
(Position actual internal value)
The current position is returned.
6064 Current position (Position actual value)
The current position in the command unit on
the basis of the home position is returned.
When the home position is not set, the current
position in the command unit on the basis of
the zero point of the encoder is returned.
In the profile position mode (pp), when the
time set with Following error time out (6066h)
has elapsed with the number of droop pulses
exceeding the setting value of this object, bit
13 of Statusword (6041h) is turned on. When
"FFFFFFFFh" is set, Bit 13 of Statusword
(6041h) is always off.
6066 Error excessive detection time (Following error
time out)
Refer to Following error window (6065h).
6067 Permissible error range (Position window)
In the profile position mode (pp), when the
time set with Position windows time (6068h)
has elapsed with the number of droop pulses
equal to or lower than the setting value of this
object, Bit 10 of Statusword (6041h) is turned
on.
[Setting range] This setting value is limited to
the range of 00000000h to 0000FFFEh. When
"FFFFFFFFh" is set, Position window is
disabled as an exception.
6068 Permissible error judgment time (Position
window time)
Refer to Position window (6067h).
606B Command speed (Velocity demand value)
The speed command is returned.
606C Current speed (Velocity actual value)
The current speed is returned.
Data
Read/
type
1
Read/
bytes
1
Reading -20 80h to 7Fh 1
Initial value Range Unit
write
0 80h to 7Fh 1
write
Saved
to EEP-
ROM
bytes
4
Reading 80000000h
bytes
to
pulse 2
7FFFFFFFh
4
Reading 80000000h
bytes
to
pos
units
7FFFFFFFh
4
bytes
Read/
12582912 00000000h
write
to
units
pos
FFFFFFFFh
2
bytes
4
bytes
Read/
write
Read/
write
10 0000h to
FFFFh
100 00000000h
to
ms
pos
units
0000FFFEh/
FFFFFFFFh
2
bytes
write
4
Reading 0 80000000h
bytes
Read/
10 0000h to
FFFFh
to
r/min
ms
0.01
7FFFFFFFh
4
Reading 80000000h
bytes
7FFFFFFFh
to
0.01
r/min
No. of
Points/
No. of
Registers
2
Continuous
continuous
Impossible
Impossible
Impossible
Impossible
Impossible
Parameter
2
PC75/
PC76
PC77 1
PT65 2
PT66 1
2
2
Impossible
Impossible
Impossible
Impossible
Impossible
read/
write
6 - 11
Page 49
6. MODBUS REGISTERS
Address Name and function
606D Speed reached judgment width (Velocity
window)
In the profile velocity mode (pv), when the time
set with Velocity window time (606Eh) has
elapsed with the current speed equal to or
lower than the setting value of this object, Bit
10 of Statusword (6041h) is turned on.
606E Speed reached judgment time (Velocity
window time)
Refer to Velocity window (606Dh).
606F Zero speed (Velocity threshold)
In the profile velocity mode (pv), when the time
set with Velocity threshold time (6070h) has
elapsed with the current speed exceeding the
setting value of this object, Bit 12 of
Statusword (6041h) is turned off.
6070 Zero speed judgment time (Velocity threshold
time)
Refer to Velocity threshold (606Fh).
6071 Command torque (Target torque)
Set the torque command used in the profile
torque mode (tq).
6072 Maximum torque (nominal value) (Max torque)
The maximum torque of the servo motor is
returned. The value matches with the
maximum torque listed in "HG-KN_/HG-SN_
Servo Motor Instruction Manual".
6074 Internal torque command (Torque demand
value)
The torque command is returned.
6077 Current torque (Torque actual value)
The current torque is returned. The read data
is in the unit of 0.1%.
607A Position command (absolute/incremental)
(Target position)
In the profile position mode (pp), the range is
limited depending on the unit.
[Setting range]
degree: -360000 to 360000
Other than degree: -999999 to 999999
607B Command value limit (Position range limit)
The number of entries is returned.
Command value limit (lower limit) (Min position
range limit)
Set the range for limiting the command
position (lower limit value). The settable values
vary depending on the setting of [Pr. PT01].
[Pr. PT01] = _ 2 _ _ (degree): 00000000h to
00057E3Fh (0 to 359999)
[Pr. PT01] = _ 3 _ _ (pulse): 80000000h to
7FFFFFFFh (-2147483648 to 2147483647)
Command value limit (upper limit) (Max
position range limit)
Set the range for limiting the command
position (upper limit value). The settable
values vary depending on the setting of [Pr.
PT01].
[Pr. PT01] = _ 2 _ _ (degree): 00000000h to
00057E3Fh (0 to 359999)
[Pr. PT01] = _ 3 _ _ (pulse): 80000000h to
7FFFFFFFh (-2147483648 to 2147483647)
607C Home position (Home offset)
The home position is returned. Only reading
the value is available.
Do not perform writing because doing so
causes an error.
Data
type
2
bytes
2
bytes
2
bytes
2
bytes
2
bytes
2
bytes
2
Read/
Read/
Read/
Read/
Read/
Read/
Read/
Initial value Range Unit
write
2000 0000h to
write
10 0000h to
write
5000 0000h to
write
10 0000h to
write
0 8000h to
write
0000h to
write
Read 0 8000h to
bytes
2
Reading 8000h to
bytes
4
bytes
Read/
write
0 80000000h
FFFFh
FFFFh
FFFFh
FFFFh
7FFFh
FFFFh
7FFFh
7FFFh
to
Saved
to EEP-
ROM
0.01
r/min
ms
0.01
r/min
ms
0.1
%
0.1
%
0.1
%
0.1
%
pos
units
7FFFFFFFh
1
Reading 2 00h to 02h 5
bytes
4
Read/
bytes
write
00000000h
(degree)
80000000h
80000000h
to
7FFFFFFFh
pos
units
(pulse)
4
Read/
bytes
write
00057E3Fh
(degree)
7FFFFFFFh
80000000h
to
7FFFFFFFh
pos
units
(pulse)
4
bytes
Read/
write
0 80000000h
to
units
pos
7FFFFFFFh
No. of
Points/
No. of
Registers
Continuous
read/
continuous
write
Impossible
Impossible
Impossible
Impossible
Impossible
Impossible
Impossible
Impossible
Impossible
Impossible
Parameter
PT67 1
PT68 1
PT63 1
PT64 1
1
1
1
1
2
2
Impossible
6 - 12
Page 50
6. MODBUS REGISTERS
Address Name and function
607D Software limit (Software position limit)
Set the range for limiting the command
position. Target position (607Ah) is limited
within the range between Min position limit
(607Dh: 1) and Max position limit (607Dh: 2).
When the set value of Min position limit
(607Dh: 1) is equal to or greater than the set
value of Max position limit (607Dh: 2), the
function of Software position limit (607Dh) is
disabled.
Stroke limit - (Min position limit)
The stroke limit value in the reverse direction is
returned in units of commands.
Stroke limit + (Max position limit)
The stroke limit value in the forward direction is
returned in units of commands.
607E Rotation direction selection (Polarity)
The rotation direction selection can be set.
Bit 7: position polarity
Bit 6: velocity polarity
Bit 5: torque polarity
Turn on or off both bit 6 and bit 7 to set the
rotation direction to position commands and
speed commands. Turn on or off all of bit 5 to
bit 7 to set the rotation direction to torque
commands.
607F Maximum speed command (Max profile
velocity)
Set the maximum speed command for the
profile position mode (pp) and profile velocity
mode (pv). When a value exceeding this object
is set to Target velocity (60FFh) or Profile
velocity (6081h), the speed is limited with the
value of this object.
6080 Servo motor maximum speed (Max motor
speed)
The maximum speed of the servo motor is
returned. Operation cannot be performed at a
speed exceeding the speed set with this
object.
6081 Command speed (Profile velocity)
The current speed command value can be
read.
The speed command value can also be set.
Set a value in units of 0.01 r/min.
6083 Acceleration time constant (Profile
acceleration)
The current acceleration time constant can be
read.
The acceleration time constant can also be
set.
Set the length of time until the servo motor
accelerates to the rated speed in units of ms.
6084 Deceleration time constant (Profile
deceleration)
The current deceleration time constant can be
read.
The deceleration time constant can also be
set.
Set the length of time until the servo motor
decelerates from the rated speed to a stop in
units of ms.
Data
Read/
type
1
Reading 2 02h (fixed) 5
Initial value Range Unit
write
Saved
to EEP-
ROM
Parameter
bytes
4
bytes
Read/
write
0 80000000h
to
units
pos
PT17/
7FFFFFFFh
4
bytes
Read/
write
0 80000000h
to
units
pos
PT15/
7FFFFFFFh
1
bytes
4
bytes
Read/
write
Read/
write
00h 00h to FFh
2000000 00000000h
to
0.01
r/min
PA14/
PC29
PT51 2
001E8480h
(2000000)
4
bytes
Read/
write
00000000h
r/min 2
to
FFFFFFFFh
4
bytes
Read/
write
10000 00000000h
to
0.01
r/min
PT50 2
permissible
instantane-
ous speed
4
bytes
Read/
write
0 00000000h
to
ms
PC01 2
FFFFFFFFh
4
bytes
Read/
write
0 00000000h
to
FFFFFFFFh
ms
PC02 2
PT18
PT16
No. of
Points/
No. of
Registers
1
Continuous
read/
continuous
write
Impossible
Impossible
Impossible
Impossible
Impossible
Impossible
Impossible
6 - 13
Page 51
6. MODBUS REGISTERS
Address Name and function
6085 Deceleration time constant at Quick stop
command (Quick stop deceleration)
Set a deceleration time constant for the Quick
stop function. Set a time for the servo motor to
stop from the rated speed. When "0" is set, the
operation is performed with 100 ms.
[Range] Limited within the range of 0 to 20000.
When "0" is set, the operation is performed
with 100 ms. The operation depends on the
specification of [Pr. PC51].
6086 Acceleration/deceleration pattern (Motion
profile type)
Set the acceleration/deceleration pattern in the
profile position mode (pp). The description is
as follows.
-1: S-pattern
For this object, "-1" is always returned.
Values other than "-1" cannot be set.
6087 Torque slope
Set the variation per second of the torque
command used in the profile torque mode.
When "0" is set, the setting value is invalid and
the torque command is input with step input.
[Range] Limited within the range of 0 to
10000000.
When "0" is set, the setting value is invalid
(step input).
6088 Torque command pattern (Torque profile type)
Set the torque command pattern.
0: Linear interpolation method
Values other than 0 cannot be set.
608F Encoder information (Position encoder
resolution)
The number of entries is returned.
Encoder resolution (Encoder increments)
The encoder resolution is returned.
Number of revolutions of the servo motor (fixed
to 1 rev) (Motor revolutions)
The fixed value "1" is returned.
6091 Servo motor shaft gear ratio (Gear ratio)
The number of entries is returned.
Number of revolutions of the servo motor axis
(electronic gear numerator) (Motor revolutions)
Set the numerator of the electronic gear. Refer
to [Pr. PA06] for the settable values.
Number of revolutions of the drive axis
(electronic gear denominator) (Shaft
revolutions)
Set the numerator of the electronic gear. Refer
to [Pr. PA07] for the settable values.
6092 Travel distance per revolution of the drive axis
(Feed constant)
The number of entries is returned.
Electronic gear expression: Travel
distance/Number of revolutions of the drive
axis
Travel distance (Feed)
The value is set automatically according to the
[Pr. PT01] setting.
to 1 rev) (Shaft revolutions)
No value can be written as it is automatically
set with [Pr. PT01]. If a value is written, this
setting is disabled.
ms
Saved
to EEP-
ROM
Parameter
PC51 2
Data
type
4
bytes
Read/
write
Read/
write
Initial value Range Unit
100 00000000h
to
FFFFFFFFh
2
bytes
4
bytes
Read/
write
Read/
write
-1 FFFFh (-1)
(fixed)
0 00000000h
0.1%
to
1
PT49 2
00989680h
2
bytes
write
1
Reading 2 02h (fixed) pulse/
bytes
4
Read/
bytes
Read/
write
0 0000h
(fixed)
00000000h
pulse
to
1
5
rev
FFFFFFFFh
4
bytes
Read/
write
1 00000001h
to
rev
00000001h
1
Reading 2 02h (fixed) 5
bytes
4
bytes
Read/
write
1 00000001h
to
rev
PA06
00FFFFFFh
(16777215)
4
bytes
Read/
write
1 00000001h
to
rev
PA07
00FFFFFFh
(16777215)
1
Reading 2 02h (fixed) 5
bytes
4
bytes
Read/
write
360000
(degree)/
Encoder
00000001h
to
FFFFFFFFh
pos
units
resolution
(pulse)
4
bytes
Read/
write
1 00000001h
to
rev
PT01
00000001h
No. of
Points/
No. of
Registers
Continuous
read/
continuous
write
Impossible
Impossible
Impossible
Impossible
Impossible
Impossible
Impossible
6 - 14
Page 52
6. MODBUS REGISTERS
Address Name and function
6098 Home position return types (Homing method)
Set a home position return type.
6099 Home position return speed (Homing speeds)
The number of entries is returned.
Home position return speed (Speed during
search for switch)
Set the servo motor speed at home position
return.
Creep speed (Speed during search for zero)
Set a creep speed after proximity dog at home
position return.
609A Set acceleration/deceleration time constant at
home position return. (Homing acceleration)
Set the acceleration/deceleration time
constants at home position return. Set a time
for the servo motor to reach the rated speed.
60A8 SI unit position
SI unit position (60A8h) is set automatically
with [Pr. PT01].
The following shows the data structure.
[Bit 0 to Bit 7: Reserved]
[Bit 8 to Bit 15: Denominator]
"00" means "Dimensionless".
[Bit 16 to Bit 23: Numerator]
"41" means "degree", and "00" means
"Dimensionless".
[Bit 24 to Bit 31: Prefix]
"FD" means "milli", and "00" means "none".
60A9 SI unit velocity (SI unit velocity)
The SI unit velocity is returned.
FEB44700h: 0.01 r/min
60B8 Touch probe function setting (Touch probe
function)
Set the command for the touch probe function.
60B9 Status of the touch probe function (Touch
probe status)
The status of the touch probe function is
returned.
60BA Rising edge position of touch probe (Touch
probe pos1 pos value)
The position latched at the rising edge of touch
probe 1 is returned.
60BB Falling edge position of touch probe (Touch
probe pos1 neg value)
The position latched at the falling edge of
limit value)
The reverse rotation torque limit can be read.
The reverse rotation torque limit can also be
set.
Set a reverse torque limit value in units of
0.1%.
Data
Read/
type
1
Read/
bytes
1
Reading 2 02h (fixed) 5
Initial value Range Unit
write
37 D5h (-43)
write
to 27h (39)
Saved
ROM
Parameter
PT45 1
to EEP-
bytes
4
bytes
Read/
write
10000 0 to
permissible
0.01
r/min
PT05
instantane-
ous speed
4
bytes
Read/
write
1000 0 to
permissible
0.01
r/min
PT06
instantane-
ous speed
4
bytes
Read/
write
0 00000000h
to
ms
PT61/
PT62
00004E20h
(20000)
4
Read/
bytes
write
FD410000h
(degree)
00000000h
00000000h
to
FFFFFFFFh
2
(pulse)
4
Read/
bytes
bytes
write
2
Read/
0 0000h to
write
2
Reading 0 0000h to
bytes
FEB44700h FEB44700h
4
Reading 0 80000000h
bytes
4
Reading 0 80000000h
bytes
2
bytes
Read/
write
10000 0000h to
(0.01 r/min)
FFFFh
FFFFh
to
7FFFFFFFh
to
7FFFFFFFh
2710h
2
1 Possible
1 Possible
pos
2 Possible
units
pos
2 Possible
units
0.1%
PA11/
(PA12)
(10000)
2
bytes
Read/
write
10000 0000h to
2710h
0.1%
PA12/
(PA11)
(10000)
No. of
Points/
No. of
Registers
2
1
1
Continuous
read/
continuous
write
Impossible
Impossible
Impossible
Impossible
Impossible
Impossible
Impossible
6 - 15
Page 53
6. MODBUS REGISTERS
Address Name and function
60E3 Supported homing method (Supported homing
method)
The number of supported homing methods is
returned.
Number specification of supported homing
methods (1st to 39th) (1st supported homing
method)
Set the number of the supported home
position return type.
60F2 Profile position mode setting (Positioning
option code)
Set the profile position mode.
Bit 1 to Bit 3 always notify "0". Setting a value
other than "0" will cause an error.
[Bit 1/Bit 0: relative option]
How to handle the relative position command
during pp is specified.
00: The positioning is performed with the
relative position from the internal absolute
target position.
[Bit 3/Bit 2: change immediately option]
The operation of when change set immediately
(control word Bit 5) is 1 during pp is specified.
00: Normal pp mode operation (New Target
position, profile velocity, acceleration, and
others are reflected immediately.)
[Bit 7/Bit 6: rotary axis direction option]
Specify the operation of the rotation axis
during pp and pt.
00: The servo motor rotates to the target
position in a direction specified with a sign
of the position data.
01: The servo motor rotates in the address
decreasing direction regardless of the sign
of the position data.
10: The servo motor rotates in the address
increasing direction regardless of the sign
of the position data.
11: The servo motor rotates from the current
position to the target position in the shorter
direction. If the distances from the current
position to the target position are the same
for CCW and CW, the servo motor rotates
in the CCW direction.
60F4 Droop pulses [command unit] (Following error
actual value)
The droop pulses are returned.
60FA Speed command (Control effort)
The speed command is returned.
60FF Command speed (Target velocity)
Set the speed command used in the profile
velocity mode (pv).
6502 Supported control mode (Supported drive
modes)
The supported control mode is returned.
Bit 0: Profile position mode (pp)
Bit 2: Profile velocity mode (pv)
Bit 3: Profile torque mode (tq)
Bit 5: Homing mode (hm)
Data
Read/
type
1
Reading 39 00h to FFh 1 +
bytes
1
Reading 37 80h to 7Fh
bytes
2
bytes
bytes
bytes
bytes
bytes
Read/
4
4
4
Read/
4
Reading 0000002Dh 0000002Dh
Initial value Range Unit
write
write
Read 80000000h
Read 0 80000000h
write
0000h 0000h to
00C0h
to
7FFFFFFFh
to
7FFFFFFFh
0 80000000h
to
7FFFFFFFh
to
0000002Dh
Saved
to EEP-
ROM
1
pos
units
0.01
r/min
0.01
r/min
2
2
2
2
Parameter
No. of
Points/
No. of
Registers
number
of read
points
Continuous
read/
continuous
write
Impossible
Impossible
Impossible
Impossible
Impossible
Impossible
6 - 16
Page 54
6. MODBUS REGISTERS
6.2 Object library details (objects in the 1000s)
POINT
This section describes the objects in the 1000s. Refer to section 6.1 for details
on the objects not listed here.
6.2.1 Writing command to EEP-ROM (1010h)
POINT
Before shutting off the power after executing the writing command to EEP-ROM
(Store Parameters), always check that parameters are not being saved (Bit 0 is
on).
For the objects that can be saved, write "65766173h" (= reverse order of the ASCII code of "save") to the
corresponding sub object of the writing command to EEP-ROM (Store Parameters) (1010h) to store the
object in the EEP-ROM of the servo amplifier.
The value saved in the EEP-ROM is set to the object at the next power-on. Servo parameters can also be
modified through the object library. However, the new setting is not automatically written to the EEP-ROM.
To write the new setting, use the writing command to EEP-ROM (Store Parameters) (1010h).
Executing the writing command to EEP-ROM (Store Parameters) (1010h) takes about a maximum of 10 s
because all parameters are written at the same time. Be careful not to shut off the power during writing.
Address Name
1010h
Writing command to EEPROM (Store parameters)
Parameter setting values can be saved in EEP-ROM.
Number of entries
(Number of entries)
Restoring all default parameters
(Restore all default parameters)
Data
type
1 bytes Reading
4 bytes
Read/
write
Read/
write
No. of Points/
No. of Registers
3 Impossible
Continuous read/
continuous write
6 - 17
Page 55
6. MODBUS REGISTERS
(1) Usage
This object can read the availability of each Sub Index. The following table shows the returned values of
each item.
Number of entries
(Number of entries)
Saving all parameters
(Save all parameters)
Select the items to be saved in EEP-ROM using this object. At this time, set "00h" or "01h" for Number of
entries.
To save servo amplifier parameters in EEP-ROM, configure required settings following the table below.
When bit 1 (EEP-ROM write completed) of the control output (2D11h) is "1", saving data in EEP-ROM
has been completed.
Writing a value other than "65766173h" and "00000000h" to each item results in an error.
Number of entries
(Number of entries)
Saving all parameters
(Save all parameters)
6.2.2 Restore default EEP-ROM parameters (1011h)
Item Saved parameter Returned value
01h
Index: 2001h to 27FFh 00000001h (available)
Item Setting value
01h
00000000h Disabled
65766173h ("save") Enabled
Other than above Error
Write to EEP-ROM
Parameter
Address Name
Number of entries
(Number of entries)
Restoring all default parameters
(Restore all default parameters)
The parameter of the servo amplifier can be rewritten with the factory setting.
When "64616F6Ch" (= reverse order of ASCII code of "load") is written to Restore all default parameters
(1011h: 1) and the power in cycled, the parameter is initialized.
6 - 18
Page 56
6. MODBUS REGISTERS
6.3 Object library details (objects in the 2000s)
POINT
This section describes the objects in the 2000s. Refer to section 6.1 for details
on the objects not listed here.
6.3.1 External input pin status (2C10h)
Address Name
Number of entries
2C10h
External input pin status
(External Input pin display)
(Number of entries)
External input pin status 1
(External Input pin display1)
Data
type
1 bytes Reading
4 bytes Reading
Read/
write
No. of Points/
No. of Registers
3 Impossible
Continuous read/
continuous write
The ON/OFF state of the external input pins input to the servo amplifier can be read.
(1) Usage
Read the ON/OFF state of external input pins using this object. At this time, "02h" is returned to Number
of entries.
External Input pin display1 displays the input pin status of the MR-JE-_C servo amplifier. The following
table shows the details. When the input of the target pin is on, "1" is returned. When the input of the
target pin is off, "0" is returned. The values in the areas marked with diagonal lines are indefinite.
Bit CN3 connector pin Bit CN3 connector pin Bit CN3 connector pin Bit CN3 connector pin
0 3 8 16 24
1 4 9 17 25
2 1 10 18 26
3 2 11 19 27
4 8 12 20 28
5 21 13 21 29
6 6 14 22 30
7 19 15 23 31
6 - 19
Page 57
6. MODBUS REGISTERS
6.3.2 External output pin status (2C11h)
Address Name
Number of entries
2C11h
External output pin status
(External Output pin display)
(Number of entries)
External output pin status 1
(External Output pin display1)
Data
type
1 bytes Reading
4 bytes Reading
Read/
write
No. of Points/
No. of Registers
3 Impossible
Continuous read/
continuous write
The ON/OFF state of external output pins output from the servo amplifier can be read.
(1) Usage
Read the ON/OFF state of external output pins using this object. At this time, "02h" is returned to
Number of entries.
External Output pin display1 displays the output pin status of the MR-JE-_C servo amplifier. The
following table shows the details. When the output of the target pin is on, "1" is returned. When the
output of the target pin is off, "0" is returned. The values in the areas marked with diagonal lines are
indefinite.
Bit CN3 connector pin Bit CN3 connector pin Bit CN3 connector pin Bit CN3 connector pin
0 14 8 16 24
1 22 9 17 25
2 16 10 18 26
3 11 19 27
4 12 20 28
5 15 13 21 29
6 14 22 30
7 15 23 31
6.3.3 Input device status (2C12h)
Address Name
Number of entries
(Number of entries)
Input device status 1
(External Input signal display1)
2C12h
Input device status (External
Input signal display)
Input device status 2
(External Input signal display2)
Input device status 3
(External Input signal display3)
Input device status 4
(External Input signal display4)
The current input device status can be read.
Data
type
1 bytes
4 bytes
4 bytes
4 bytes
4 bytes
Read/
write
Reading 9 Impossible
No. of Points/
No. of Registers
Continuous read/
continuous write
6 - 20
Page 58
6. MODBUS REGISTERS
(1) Usage
External Input signal display1 (Input device status 1) to External Input signal display4 (Input device
status 4) display the ON/OFF state of each input device of the MR-JE-_C servo amplifier. The following
table shows the details. When the input of the target device is on, "1" is returned. When the input of the
target device is off, "0" is returned. The values in the areas marked with diagonal lines are indefinite.
Bit
0 SON (Servo-on)
1
2
3
4
5 PC (Proportional control)
6 RES (Reset)
7 CR (Clear)
8 SP1 (Speed selection 1)
9 SP2 (Speed selection 2) DOG (Proximity dog)
10 SP3 (Speed selection 3)
11
12
13
14
15 LOP (Control switching)
16
17
18 EM2/EM1 (Forced stop 2/1)
19
20
21
22
23
24
25
26
27 CDP (Gain switching)
28
29
30
31
Input device status 1 Input device status 2 Input device status 3 Input device status 4
Note. For details on the symbols, refer to section 3.5 in "MR-JE-_C Servo Amplifier Instruction Manual".
Input device abbreviation (Note)
6 - 21
Page 59
6. MODBUS REGISTERS
6.3.4 Control input (2D01h to 2D0Ah)
Address Name
2D01h
to
Control input (Control DI1 to Control DI10) 2 bytes
2D0Ah
Data
type
The on/off status of input device can be read.
The on/off status of input device can also be set.
The following table lists readable and writable input devices.
(1) Bit definition of control DI1
Bit Symbol Description
This device can be used by setting "2 _ _ _" (initial value) in [Pr. PA04].
C_EM2
0
C_EM1
1
2
3
4 C_CDP
5
6
7
8 C_TL1
9
10
11
12
13
14
15
When C_EM2 is turned on, the command decelerates the servo motor to a stop.
Turn C_EM2 off in the forced stop state to reset that state.
In the torque control mode, C_EM2 functions the same as C_EM1.
This device can be used by setting "0 _ _ _" in [Pr. PA04].
When C_EM1 is turned on, the base circuit shuts off, and the dynamic brake operates to decelerate the
servo motor to a stop.
Turn C_EM1 off in the forced stop state to reset that state.
The value at reading is undefined. Set "0" when writing.
Gain switching
Turn on C_CDP to use the values of [Pr. PB29] to [Pr. PB36] and [Pr. PB56] to [Pr. PB60] as the load to
motor inertia ratio and gain values.
The value at reading is undefined. Set "0" when writing.
When C_TL1 is turned on, [Pr. PC35 Internal torque limit 2] can be selected.
However, if the value of [Pr. PA11] (60E0h) or [Pr. PA12] (60E1h) is less than the limit value selected by
[Pr. PC35], the value of [Pr. PA11] (60E0h) or [Pr. PA12] (60E1h) will be enabled.
The value at reading is undefined. Set "0" when writing.
Read/
write
Read/
write
No. of Points/
No. of Registers
1 Possible
Continuous read/
continuous write
6 - 22
Page 60
6. MODBUS REGISTERS
(2) Bit definition of control DI2
Bit Symbol Description
0
1
2
3
4
5
6
7
8 C_PC
9
10
11
12
13
14
15 C_ORST
(3) Bit definition of control DI3
Bit Symbol Description
0
1
2
3
4
5
6
7
8
9
10
11
12
13 C_STAB2
14
15
The value at reading is undefined. Set "0" when writing.
Proportional control
Turn C_PC on to switch the speed amplifier from the proportional integral type to the proportional type.
If the servo motor is stopped and then rotated by even one pulse due to any external factor, it generates
torque to compensate for the droop pulses and returns to the original position. When the servo motor shaft
is to be locked mechanically after positioning completion (stop), switching on the C_PC upon positioning
completion will suppress the unnecessary torque generated to compensate for a position mismatch.
When the shaft is to be locked for a long time, switch on the C_PC and TL (External torque limit selection)
at the same time to make the torque less than the rated by TLA (Analog torque limit).
Do not use C_PC in the torque control. When C_PC is used in the torque control, operation may be
performed at a speed exceeding the speed limit value.
The value at reading is undefined. Set "0" when writing.
Operation alarm reset
Turn on C_ORST from off to reset [AL. F4 Positioning warning].
The value at reading is undefined. Set "0" when writing.
Second acceleration/deceleration selection
The device allows selection of the acceleration/deceleration time constant at servo motor rotation in the
speed control mode or torque control mode. The S-pattern acceleration/deceleration time constant is
always uniform.
Bit 13 Acceleration time constant Deceleration time constant
0 Pr. PC01 Pr. PC02
1 Pr. PC30 Pr. PC31
The value at reading is undefined. Set "0" when writing.
6 - 23
Page 61
6. MODBUS REGISTERS
(4) Bit definition of control DI4
Bit Symbol Description
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
(5) Bit definition of control DI5
Bit Symbol Description
0
1
2
3
4
5
6
7
8
9
10
11 C_DOG
12
13
14
15
The value at reading is undefined. Set "0" when writing.
The value at reading is undefined. Set "0" when writing.
Proximity dog input
When C_DOG is turned on, a proximity dog will be detected. The polarity for dog detection can be changed
with [Pr. PT29].
The value at reading is undefined. Set "0" when writing.
6 - 24
Page 62
6. MODBUS REGISTERS
(6) Bit definition of control DI6
Bit Symbol Description
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
(7) Bit definition of control DI7
Bit Symbol Description
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
(8) Bit definition of control DI8
Bit Symbol Description
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
The value at reading is undefined. Set "0" when writing.
The value at reading is undefined. Set "0" when writing.
The value at reading is undefined. Set "0" when writing.
6 - 25
Page 63
6. MODBUS REGISTERS
(9) Bit definition of control DI9
Bit Symbol Description
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
(10) Bit definition of control DI10
Bit Symbol Description
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
The value at reading is undefined. Set "0" when writing.
The value at reading is undefined. Set "0" when writing.
6 - 26
Page 64
6. MODBUS REGISTERS
6.3.5 Control output (2D11h to 2D1Ah)
Address Name
2D11h
to
Control output (Status DO1 to Status DO10) 2 bytes Reading 1 Possible
2D1Ah
Data
type
Read/
write
No. of Points/
No. of Registers
Continuous read/
continuous write
The on/off status of output device can be read. The following table lists readable output devices.
(1) Bit definition of Status DO 1
Bit Symbol Description
0 The value at reading is undefined.
EEP-ROM write completed
1 S_ERF
2 S_SA
3 S_MBR
4 S_CDPS
5
6
7 S_TL
8 S_TL1
9
10
11
12 S_INP
13 S_TLC
14 S_ABSV
15 S_BWNG
When a value is not written to EEP-ROM, S_ERF turns on. While a value is being written to EEP-ROM,
S_ERF turns off.
Speed reached
When the servo motor speed reaches the following range, S_SA turns on.
Set speed ± ((Set speed × 0.05) + 20) r/min
When the preset speed is 20 r/min or less, SA always turns on.
SA does not turn on even when the SON (Servo-on) is turned off or the servo motor speed by the external
force reaches the preset speed while both ST1 (Forward rotation start) and ST2 (reverse rotation start) are
off.
Electromagnetic brake interlock
When a servo-off status or alarm occurs, S_MBR will turn off.
Variable gain selection
S_CDPS turns on during gain switching.
The value at reading is undefined.
Analog torque limit selection
When TL (External torque limit selection) is turned on, S_TL turns on.
Torque limit selection
When C_TL1 or TL1 (Internal torque limit selection) is turned on, S_TL1 turns on.
The value at reading is undefined.
In-position
When the number of droop pulses is in the in-position range, S_INP will turn on. The in-position range can
be changed with [Pr. PA10]. When the in-position range is increased, INP may be always on during lowspeed rotation.
Limiting torque
S_TLC turns on when a generated torque reaches a value set with any of [Pr. PA11 Forward torque limit],
[Pr. PA12 Reverse torque limit], or TLA (Analog torque limit).
Absolute position undetermined
S_ABSV turns on when the absolute position is undetermined.
Battery warning
When [AL. 92 Battery cable disconnection warning] or [AL. 9F Battery warning] has occurred, S_BWNG
turns on. When the battery warning is not occurring, S_BWNG will turn off in 2.5 s to 3.5 s after power-on.
6 - 27
Page 65
6. MODBUS REGISTERS
(2) Bit definition of Status DO 2
Bit Symbol Description
Z-phase already passed
0 S_ZPASS
1
2
3 S_ZSP
4 S_VLC
5
6
7
8 S_PC
9
10
11
12
13
14
15 S_ZP2
0: Z-phase unpassed after start-up
1: Z-phase passed once or more after start-up
The value at reading is undefined.
Zero speed state
S_ZSP turns on when the servo motor speed is zero speed or less. Zero speed can be changed with [Pr.
PC17].
Limiting speed
S_VLC turns on when speed reaches a value limited with any of [Pr. PC05 Internal speed limit 1] to [Pr.
PC11 Internal speed limit 7].
This turns off when SON (Servo-on) turns off.
The value at reading is undefined.
Under proportional control
S_PC turns on under proportional control.
The value at reading is undefined.
Home position return completion 2
When a home position return completes normally, S_ZP2 turns on. S_ZP2 is always on unless the home
position is erased.
In the incremental system, it turns off with one of the following conditions.
1) [AL. 69 Command error] occurs.
2) Home position return is not being executed.
3) Home position return is in progress.
If a home position return completes once in the absolute position detection system, S_ZP2 is always on.
However, it will be off with one of the conditions 1) to 3) or the following.
4) The home position return is not performed after [AL. 25 Absolute position erased] or [AL. E3 Absolute
position counter warning] occurred.
5) The home position return is not performed after the electronic gear ([Pr. PA06] or [Pr. PA07]) was
changed.
6) The home position return is not performed after the setting of [Pr. PA03 Absolute position detection
system selection] was changed from "Disabled" to "Enabled".
7) [Pr. PA14 Rotation direction selection/travel direction selection] was changed.
8) [Pr. PA01 Operation mode] was changed.
This bit will be enabled in the profile mode.
6 - 28
Page 66
6. MODBUS REGISTERS
(3) Bit definition of Status DO 3
Bit Symbol Description
0
1
2
3
4
5
6
7
8
9 S_RSTP
10 The value at reading is undefined.
11 S_MTTR
12
13
14
15
(4) Bit definition of Status DO 4
Bit Symbol Description
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
The value at reading is undefined.
Forced stop deceleration
S_RSTP turns on during a forced stop deceleration.
Transition to tough drive mode in process
When a tough drive is "Enabled" in [Pr. PA20], activating the instantaneous power failure tough drive will
The latest SDO Abort Code generated in Modbus communication can be read.
The access to registers can be checked by reading the latest SDO Abort Code.
When an error is found by reading SDO Abort Codes, change the method to access registers.
(2) Usage
Read SDO Abort Codes using this register.
The following table lists the SDO Abort Codes.
SDO Abort Code Description
0000 0000h No problem found.
0504 0001h Client/server command specifier not valid or unknown.
0601 0000h Unsupported access to a register.
0601 0001h Attempt to read a write only register.
0601 0002h Attempt to write a read only register.
0602 0000h Register does not exist in the Modbus resisters.
0604 0041h Resister cannot be mapped to the PDO
0604 0042h The number and length of the resisters to be mapped would exceed PDO length
0607 0010h Data type does not match, length of service parameter does not match
0609 0011h Element of resister does not exist.
0609 0030h Value range of parameter exceeded (only for write access).
0609 0031h Value of parameter written too high.
0609 0032h Value of parameter written too low.
0800 0000h Generic error.
0800 0020h Data cannot be transferred or stored to the application
0800 0021h Data cannot be transferred or stored to the application because of local control.
0800 0022h Data cannot be transferred or stored to the application because of the present device state.
Read the access log 2 using this register.
The access log 2 displays the number of addresses that were accessed successfully in Modbus
communication.
Use this register when an access error has occurred in the continuous read/write.
For example, when an error has occurred while the registers for monitoring (address: 2B01h to 2B0Ah)
are continuously read, the error has occurred at the address 2B07h because the read value of the
access log 2 is "0006h".
6 - 34
Page 72
6. MODBUS REGISTERS
6.4 Object library details (objects in the 6000s)
POINT
This section describes the objects in the 6000s. Refer to section 6.1 for details
on the objects not listed here.
6.4.1 Control status (6041h)
Address Name
6041h Control status (Statusword) 2 bytes Reading 1 Impossible
Data
type
Read/
write
No. of Points/
No. of Registers
Continuous read/
continuous write
The current control status can be checked.
The following table lists the bits of this object. The status can be checked with bit 0 to bit 7.
Bit Description
0 Ready To Switch On
1 Switched On
2 Operation Enabled
3 Fault
4 Voltage Enabled
5 Quick Stop
6 Switch On Disabled
7 Warning
8 Reserved (Note 2)
9 Reserved (Note 2)
10 Target reached (Note 1)
11 Internal Limit Active
12 to 13 Operation Mode Specific (Note 1)
14 to 15 Reserved (Note 2)
Note 1. The description changes depending on the control mode.
2. The value at reading is undefined.
The following table lists the servo amplifier statuses that can be read with bit 0 to bit 7.
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Status
0 0 0 0 0 Not ready to switch on
1 0 0 0 0 Switch on disable
0 1 0 0 0 1 Ready to switch on
0 1 0 0 1 1 Switch on
0 1 0 1 1 1 Operation enabled
0 0 0 1 1 1 Quick stop active (Note)
0 1 1 1 1 Fault reaction active
0 1 0 0 0 Fault
1 Main power on (power input on)
1 Warning (warning occurrence)
Note. Not supported in the position control mode, speed control mode, and torque control mode.
Bit 11 turns on when the stroke limit, software limit, or positioning command is outside the range.
The operation method of deceleration to a stop can be specified. The following table shows the supported
methods and the operations.
Setting
value
1 For manufacturer setting
In the profile mode (pp/pv) and homing mode (hm), the servo motor decelerates to a stop with Quick stop deceleration
(6085h) and the state shifts to the Switch On Disabled state. The new setting of Quick stop deceleration is reflected at all
times.
2
In the profile torque mode (tq), the state immediately shifts to the Switch On Disabled state and the servo motor stops with
the dynamic brake.
3 For manufacturer setting
4
5
6
7
8
Description
6 - 36
Page 74
6. MODBUS REGISTERS
6.4.3 Halt option code (605Dh)
(1) Object list
Address Name
605Dh Halt option code (Halt option code) 2 bytes
The following table shows descriptions of Halt option code (605Dh).
Setting
value
The description varies depending on the control mode.
1
Refer to the following table.
2 For manufacturer setting
3
4
Description
The following shows the meaning of Halt Bit (Bit 8 of Controlword (6040h)) and the reflecting timing of
the deceleration time setting.
Control mode Halt Bit is set to "1" Halt Bit is set to "0"
Profile position mode (pp)
Profile velocity mode (pv)
Profile torque mode (tq)
Homing mode (hm)
The servo motor decelerates
to a stop according to Profile
deceleration (6084h).
The servo motor decelerates
to a stop according to Profile
deceleration (6084h).
Torque demand value
(6074h) becomes "0" with the
amount of torque change set
in Torque slope (6087h)
regardless of the setting of
Halt option code (605Dh).
When Halt Bit is set to "1", the servo motor decelerates to a
stop with Homing acceleration (609Ah) and the state does not
change from Operation Enabled (servo-on). After that, when
Halt Bit is set to "0" and Homing Operation Start (Bit 4 of
Controlword (6040h)) is set to "0" and then "1", home position
return is performed again.
The operation restarts after
the servo motor decelerates
to a stop.
The operation restarts after
the servo motor decelerates
to a stop.
The operation restarts after
Torque demand value
(6074h) becomes "0".
Data
type
Read/
write
Read/
write
No. of Points/
No. of Registers
1 Impossible
Reflecting timing of deceleration time
The new setting of Profile
deceleration (6084h) is reflected
when New set-point (Bit 4 of
Controlword (6040h)) is set to "1".
The new setting of Profile
deceleration (6084h) is reflected at all
times.
The new setting of Torque slope
(6087h) is reflected at all times.
The new setting of Homing
acceleration (609Ah) is reflected
when Homing Operation Start (Bit 4 of
Controlword (6040h)) is set to "1".
Continuous read/
continuous write
setting
6 - 37
Page 75
6. MODBUS REGISTERS
6.4.4 Control mode display (6061h)
Address Name
6061h Control mode display (Modes of operation Display) 1 bytes Reading 1 Impossible
Data
type
Read/
write
No. of Points/
No. of Registers
Continuous read/
continuous write
The current control mode can be read.
The following table shows the correspondence between control modes and setting values.
Control mode
Position control mode -20
Speed control mode -21
Torque control mode -22
Profile position mode (pp) 1
Profile velocity mode (pv) 3
Profile torque mode (tq) 4
Homing mode (hm) 6
Test mode: JOG operation -1
Test mode: Positioning operation -2
Test mode: DO forced output -4
Test mode: Machine analyzer -6
Setting
value
6.4.5 Software limit (607Dh)
Address Name
Number of entries
(Number of entries)
607Dh
Software limit (Software
Position Limit)
Min Position Limit
(Stroke limit -)
Max Position Limit
(Stroke limit +)
Data
type
1 bytes Reading
4 bytes
4 bytes
Read/
write
Read/
write
No. of Points/
No. of Registers
5 Impossible
Continuous read/
continuous write
The current software limit setting can be read.
At this time, "02h" is returned to Number of entries.
The stroke limit value in the reverse direction is returned to Min Position Limit (stroke limit -) in units of
commands.
The stroke limit value in the forward direction is returned to Max Position Limit (stroke limit +) in units of
commands.
The current software limit setting can also be written.
At this time, set "02h" for Number of entries.
Set the stroke limit value in the reverse direction in Min Position Limit (stroke limit -) in units of commands.
Set the stroke limit value in the forward direction in Max Position Limit (stroke limit +) in units of commands.
If Min Position Limit (stroke limit -) and Max Position Limit (stroke limit +) are set to the same value, the
software limit function is disabled.
6 - 38
Page 76
6. MODBUS REGISTERS
6.4.6 Polarity (607Eh)
Address Name
607Eh Rotation direction selection (Polarity) 1 bytes
Data
type
Read/
write
Read/
write
No. of Points/
No. of Registers
1 Impossible
Continuous read/
continuous write
The rotation direction selection can be set.
To set the rotation direction to position commands and speed commands, turn on or off both bit 6 and bit 7 of
Polarity (607Eh) or use [Pr. PA14]. To set the rotation direction to torque commands, turn on or off all of bit 5
to bit 7 of Polarity (607Eh) or use [Pr. PA14] and "POL reflection selection at torque mode" of [Pr. PC29].
The following table shows the descriptions of Polarity (607Eh).
Bit Description
0 Reserved
1 The value at reading is undefined. Set "0" when writing.
2
3
4
Torque POL
5
The polarity is reversed when this bit is turned on. Select a rotation direction by setting bit 5 to bit 7 in combination.
Velocity POL
6
The polarity is reversed when this bit is turned on. Select a rotation direction by setting bit 5 to bit 7 in combination.
Position POL
7
The polarity is reversed when this bit is turned on. Select a rotation direction by setting bit 5 to bit 7 in combination.
6.4.7 Degree (60F2h)
Address Name
60F2h Profile position mode setting (Positioning option code) 2 bytes
Data
type
Read/
write
Read/
write
No. of Points/
No. of Registers
1 Impossible
Continuous read/
continuous write
Selecting "degree (_ 2 _ _)" in "Position data unit" of [Pr. PT01] allows for positioning with module
coordinates (axis of rotation). The following shows the differences when "degree" is selected.
Item (Index, Sub Index) Description
Target position (607Ah, 0) The range will be between -360.000° and 360.000°.
Position actual value (6064h, 0) The range will be between 0° and 359.999°.
Software position limit (607Dh, 0) The range will be between 0° and 359.999°. A value outside the range is
clamped within the range 0° to 359.999°.
Position range limit (607Bh, 0) The range will be between 0° and 359.999°.
Touch probe pos1 pos value (60BAh, 0) The range will be between 0° and 359.999°.
Touch probe pos1 neg value (60BBh, 0) The range will be between 0° and 359.999°.
Touch probe pos2 pos value (60BCh, 0) The range will be between 0° and 359.999°.
Touch probe pos2 neg value (60BDh, 0) The range will be between 0° and 359.999°.
Home offset (607Ch, 0) The range will be between 0° and 359.999°.
6 - 39
Page 77
6. MODBUS REGISTERS
Positioning operation patterns can be changed with Positioning option code (60F2h). Change the setting
while the servo motor is stopped (Target reached is on). If the setting is changed while the servo motor is
rotating (Target reached is off), the setting value is not applied immediately. The new value is applied at a
positioning start (Bit 4 of Controlword is turned on) after Target reached is once turned on. The following
table shows the bits and settings of Positioning option code (60F2h).
Bit 7 Bit 6 [Pr. PT03] Rotation direction definition for the axis of rotation
0 0 _ 0 _ _
0 1 _ 2 _ _
1 0 _ 3 _ _
1 1 _ 1 _ _
The following shows the operation patterns corresponding to the settings of Positioning option code (60F2h).
(a) When POL is disabled ([Pr. PA14] = 0)
360 = 0
50
330
The servo motor rotates to the target position in a direction specified with a sign of the position
data.
The servo motor rotates in the address decreasing direction regardless of the sign of the
position data.
The servo motor rotates in the address increasing direction regardless of the sign of the
position data.
The servo motor rotates from the current position to the target position in the shorter direction. If
the distances from the current position to the target position are the same for CCW and CW, the
servo motor rotates in the CCW direction.
50
360 = 0
330
50
360 = 0
330
50
360 = 0
330
150210
Bit 7: 0
Bit 6: 0
The servo motor rotates in a
direction specified with a sign
of the position data.
The servo motor rotates only
in the address decreasing
direction.
150210
(b) When POL is enabled ([Pr. PA14] = 1)
360 = 0
330
50
330
210150
Bit 7: 0
Bit 6: 0
The servo motor rotates in a
direction specified with a sign
of the position data.
The servo motor rotates only
in the address decreasing
direction.
Bit 7: 0
Bit 6: 1
360 = 0
210150
Bit 7: 0
Bit 6: 1
150210
Bit 7: 1
Bit 6: 0
The servo motor rotates only
in the address increasing
direction.
360 = 0
330
50
210150
Bit 7: 1
Bit 6: 0
The servo motor rotates only
in the address increasing
direction.
150210
Bit 7: 1
Bit 6: 1
The servo motor rotates in the
shorter direction.
360 = 0
330
50
210150
Bit 7: 1
Bit 6: 1
The servo motor rotates in the
shorter direction.
50
6 - 40
Page 78
6. MODBUS REGISTERS
6.4.8 Touch probe (60B8h to 60BBh)
The current position latch data at the time of TPR1 (Touch probe 1) input can be read.
(1) Object list
Address Name
60B8h Touch probe function setting (Touch probe function) 2 bytes
60B9h Status of the touch probe function (Touch probe status) 2 bytes Reading 1 Possible
60BAh
60BBh
Rising edge position of touch probe (Touch probe position
positive value)
Falling edge position of touch probe (Touch probe position
negative value)
When the touch probe function (60B8h) is set, and TPR1 (touch probe1), an external signal, is turned
on/off, the current position of the rising and falling edges are latched.
The latch status of the current position data can be checked with the touch probe status (60B9h). The
latched current data can be read with the touch probe position positive value (60BAh) and the touch
probe position negative value (60BBh). For details of each object, refer to sections 6.4.9 to 6.4.12.
(2) Usage
The following explains for latching the current position at the rising edge of TPR1 (Touch probe 1).
(a) Set "0013h" to the touch probe function setting (Touch probe function: 60B8h) to store data at rising
edge of TPR1 (Touch probe 1).
(b) At this time, the touch probe status (Touch probe status: 60B9h) is set to "0001h", and the latched
data has not been stored yet.
(c) Use an external signal to turn on TPR1 (Touch probe 1).
(d) The touch probe status (Touch probe status: 60B9h) changes to "0003h", and the current position at
the time of TPR1 (touch probe1) on will be stored to the rising edge position of touch probe (Touch
probe position positive value: 60BAh).
(e) Use an external signal to turn off TPR1 (Touch probe 1).
(f) The touch probe status (Touch probe status: 60B9h) remains "0003h", and the current position at
the time that TPR1 (Touch probe 1) turns off will not be stored as the touch probe falling edge
position (Touch probe position negative value: 60BBh).
(g) Latching can be continued from (c).
Data
type
4 bytes Reading 2 Possible
4 bytes Reading 2 Possible
Read/
write
Read/
write
No. of Points/
No. of Registers
1 Possible
Continuous read/
continuous write
6 - 41
Page 79
6. MODBUS REGISTERS
The following shows a timing chart.
60B8h Bit 0
60B8h Bit 1
60B8h Bit 4
60B8h Bit 5
60B9h Bit 0
60B9h Bit 1
60B9h Bit 2
TPR1 (Touch Probe 1)
(Touch probe signal)
1
0
1
0
1
0
1
0
1
0
1
0
1
0
ON
OFF
(a) 60B8h = 0013h
(d) 60B9h = 0003h
(b) 60B9h = 0001h
(f) 60B9h = 0003h(g) Latches continuously
60BAh
60BBh
A0
(c) TPR1 on(e) TPR1 off
0
BC
6.4.9 Touch probe function setting (60B8h)
Address Name
60B8h Touch probe function setting (Touch probe function) 2 bytes
Data
type
Read/
write
Read/
write
No. of Points/
No. of Registers
1 Possible
Continuous read/
continuous write
The current setting of the touch probe function can be checked.
Each setting of the touch probe function can also be set. The settings of this object are as follows.
Bit Description
0: Latch function disabled
0
1: Latch function enabled
0: Latch with the first trigger
1
1: Continuously latch with trigger inputs
2 The value at reading is undefined. Set "0" when writing.
3
0: Stop sampling at the rising edge of touch probe
4
1: Start sampling at the rising edge of touch probe
0: Stop sampling at the falling edge of touch probe
5
1: Start sampling at the falling edge of touch probe
6 to 15 The value at reading is undefined. Set "0" when writing.
Select enable/disable for the latch function with bit 0. Select "1" when using the touch probe function.
Select a trigger condition for the touch probe function with bit 1. Set "0" to latch just once when TPR1 (Touch
probe 1) is inputted. Set "1" to latch every time TPR1 (Touch probe 1) is inputted.
Set a condition for the rising edge of TPR1 (Touch probe 1) with bit 4. Set "1" to latch at the rising edge.
Set a condition for the falling edge of TPR1 (Touch probe 1) with bit 5. Set "1" to latch at the falling edge.
6 - 42
Page 80
6. MODBUS REGISTERS
6.4.10 Touch probe function status (60B9h)
Address Name
60B9h Status of the touch probe function (Touch probe status) 2 bytes Reading 1 Possible
Data
type
Read/
write
No. of Points/
No. of Registers
Continuous read/
continuous write
The current status of the touch probe function can be checked. The description of this object is as follows.
Bit Description
0: Latch function of touch probe is disabled
0
1: Latch function of touch probe is enabled.
0: Latch is incomplete at the rising edge with the latch function of the touch probe.
1
1: Latch is complete at the rising edge with the latch function of the touch probe.
0: Latch is incomplete at the falling edge with the latch function of the touch probe.
2
1: Latch is complete at the falling edge with the latch function of the touch probe.
3 to 15 The value at reading is undefined.
Bit 0 indicates the status of the touch probe function. 0 indicates disabled, and 1 enabled.
With bit 1, if the data is latched at the rising edge of the touch probe can be checked. Latched data can be
read when this bit is set to "1". When this bit turns on, it remains on until bit 4 of the touch probe setting
(60B8h) is set to "0".
With bit 2, if the data is latched at the falling edge of the touch probe can be checked. Latched data can be
read when this bit is set to "1". When this bit turns on, it remains on until bit 5 of the touch probe setting
(60B8h) is set to "0".
6.4.11 Rising edge position of touch probe (60BAh)
Address Name
60BAh
Rising edge position of touch probe (Touch probe position
positive value)
4 bytes Reading 2 Possible
The current rising edge position of touch probe can be checked.
6.4.12 Falling edge position of touch probe (60BBh)
Address Name
60BBh
Falling edge position of touch probe (Touch probe position
negative value)
4 bytes Reading 2 Possible
The current falling edge position of touch probe can be checked.
The supported control mode can be read.
The returned value is "0000002Dh". The following table shows the details.
Bit Supported Modes Defined value
0 Profile position mode (pp) 1: Supported
2 Profile velocity mode (pv) 1: Supported
3 Profile torque mode (tq) 1: Supported
5 Homing mode (hm) 1: Supported
6 - 44
Page 82
REVISIONS
*The manual number is given on the bottom left of the back cover.
Revision Date *Manual Number Revision
Aug. 2017 SH(NA)030269ENG-A First edition
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses.
Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which
may occur as a result of using the contents noted in this manual.
2017 MITSUBISHI ELECTRIC CORPORATION
Page 83
MEMO
Page 84
MELSERVO is a trademark or registered trademark of Mitsubishi Electric Corporation in Japan and/or other countries.
Microsoft, Windows, Internet Explorer, and Windows Vista are registered trademarks or trademarks of Microsoft Corporation in the
United States, Japan, and/or other countries.
Intel, Pentium, and Celeron are trademarks of Intel Corporation in the United States and/or other countries.
Ethernet is a registered trademark of Fuji Xerox Co., Ltd. in Japan.
All other product names and company names are trademarks or registered trademarks of their respective companies.
Page 85
Warranty
1. Warranty period and coverage
We will repair any failure or defect hereinafter referred to as "failure" in our FA equipment hereinafter referred to as the "Product"
arisen during warranty period at no charge due to causes for which we are responsible through the distributor from which you
purchased the Product or our service provider. However, we will charge the actual cost of dispatching our engineer for an on-site
repair work on request by customer in Japan or overseas countries. We are not responsible for any on-site readjustment and/or trial
run that may be required after a defective unit are repaired or replaced.
[Term]
The term of warranty for Product is twelve (12) months after your purchase or delivery of the Product to a place designated by you or
eighteen (18) months from the date of manufacture whichever comes first (“Warranty Period”). Warranty period for repaired Product
cannot exceed beyond the original warranty period before any repair work.
[Limitations]
(1) You are requested to conduct an initial failure diagnosis by yourself, as a general rule.
It can also be carried out by us or our service company upon your request and the actual cost will be charged. However, it will not
be charged if we are responsible for the cause of the failure.
(2) This limited warranty applies only when the condition, method, environment, etc. of use are in compliance with the terms and
conditions and instructions that are set forth in the instruction manual and user manual for the Product and the caution label
affixed to the Product.
(3) Even during the term of warranty, the repair cost will be charged on you in the following cases;
(i) a failure caused by your improper storing or handling, carelessness or negligence, etc., and a failure caused by your
2. Term of warranty after the stop of production
(1) We may accept the repair at charge for another seven (7) years after the production of the product is discontinued. The
(2) Please note that the Product (including its spare parts) cannot be ordered after its stop of production.
3. Service in overseas countries
4. Exclusion of loss in opportunity and secondary loss from warranty liability
(1) Damages caused by any cause found not to be the responsibility of Mitsubishi.
(2) Loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products.
(3) Special damages and secondary damages whether foreseeable or not, compensation for accidents, and compensation for
(4) Replacement by the user, maintenance of on-site equipment, start-up test run and other tasks.
5. Change of Product specifications
6. Application and use of the Product
(1) For the use of our General-Purpose AC Servo, its applications should be those that may not result in a serious damage even if any
(2) Our General-Purpose AC Servo is designed and manufactured as a general purpose product for use at general industries.
SH(NA)030269ENG-A
hardware or software problem
(ii) a failure caused by any alteration, etc. to the Product made on your side without our approval
(iii) a failure which may be regarded as avoidable, if your equipment in which the Product is incorporated is equipped with a
safety device required by applicable laws and has any function or structure considered to be indispensable according to a
common sense in the industry
(iv) a failure which may be regarded as avoidable if consumable parts designated in the instruction manual, etc. are duly
maintained and replaced
(v) any replacement of consumable parts (battery, fan, smoothing capacitor, etc.)
(vi) a failure caused by external factors such as inevitable accidents, including without limitation fire and abnormal fluctuation of
voltage, and acts of God, including without limitation earthquake, lightning and natural disasters
(vii) a failure generated by an unforeseeable cause with a scientific technology that was not available at the time of the shipment
of the Product from our company
(viii) any other failures which we are not responsible for or which you acknowledge we are not responsible for
announcement of the stop of production for each model can be seen in our Sales and Service, etc.
Our regional FA Center in overseas countries will accept the repair work of the Product. However, the terms and conditions of the
repair work may differ depending on each FA Center. Please ask your local FA center for details.
Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation to:
damages to products other than Mitsubishi products.
Specifications listed in our catalogs, manuals or technical documents may be changed without notice.
failure or malfunction occurs in General-Purpose AC Servo, and a backup or fail-safe function should operate on an external
system to General-Purpose AC Servo when any failure or malfunction occurs.
Therefore, applications substantially influential on the public interest for such as atomic power plants and other power plants of
electric power companies, and also which require a special quality assurance system, including applications for railway companies
and government or public offices are not recommended, and we assume no responsibility for any failure caused by these
applications when used
In addition, applications which may be substantially influential to human lives or properties for such as airlines, medical treatments,
railway service, incineration and fuel systems, man-operated material handling equipment, entertainment machines, safety
machines, etc. are not recommended, and we assume no responsibility for any failure caused by these applications when used.
We will review the acceptability of the abovementioned applications, if you agree not to require a specific quality for a specific
application. Please contact us for consultation.
Page 86
MODEL
MODEL
CODE
HEAD OFFICE: TOKYO BLDG MARUNOUCHI TOKYO 100-8310
This Instruction Manual uses recycled paper.
SH(NA)030269ENG-A(1708)MEE Printed in Japan Specifications are subject to change without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.