Mitsubishi MEE99K029G Service Manual

AIR CONDITIONERS CITY MULTI
Models PUHY-200YMF-C, 250YMF-C
PUHY-P200YMF-C, P250YMF-C PUY-200YMF-C, 250YMF-C PUY-P200YMF-C, P250YMF-C
PURY-200YMF-C, 250YMF-C PURY-P200YMF-C, P250YMF-C
CMB-P104, P105, P106, P108, P1010, P1013, P1016V-E
Service Handbook
Contents
1 PRECAUTIONS FOR DEVICES THAT USE R407C REFRIGERANT .... 3
[1] Storage of Piping Material................................................................. 4
[2] Piping Machining............................................................................... 5
[3] Necessary Apparatus and Materials and Notes on Their Handling .. 6
[4] Brazing.............................................................................................. 7
[5] Airtightness T est................................................................................ 8
[6] Vacuuming ........................................................................................ 8
[7] Charging of Refrigerant..................................................................... 9
[8] Dryer ................................................................................................. 9
2 COMPONENT OF EQUIPMENT ........................................................... 10
[1] Appearance of Components ........................................................... 10
[2] Refrigerant Circuit Diagram and Thermal Sensor........................... 18
[3] Electrical Wiring Diagram................................................................ 24
[4] Standard Operation Data ................................................................ 33
[5] Function of Dip SW and Rotary SW................................................ 41
3 TEST RUN ............................................................................................. 47
[1] Before Test Run .............................................................................. 47
[2] Test Run Method ............................................................................. 51
4 GROUPING REGISTRATION OF INDOOR UNITS WITH REMOTE
CONTROLLER....................................................................................... 52
5 CONTROL.............................................................................................. 58
[1] Control of Outdoor Unit ................................................................... 58
[2] Control of BC Controller.................................................................. 63
[3] Operation Flow Chart...................................................................... 64
[4] List of Major Component Functions ................................................ 70
[5] Resistance of Temperature Sensor................................................. 73
6 REFRIGERANT AMOUNT ADJUSTMENT ............................................ 74
[1] Refrigerant Amount and Operating Characteristics ........................ 74
[2] Adjustment and Judgement of Refrigerant Amount ........................ 74
7 TROUBLESHOOTING ........................................................................... 84
[1] Principal Parts................................................................................. 84
[2] BC Controller Disassembly Procedure ..........................................113
[3] Self-diagnosis and Countermeasures Depending on the Check
Code Displayed..............................................................................119
[4] LED Monitor Display ..................................................................... 142
8 PREPARATION, REPAIRS AND REFRIGERANT REFILLING WHEN
REPAIRING LEAKS .............................................................................161
[1] Location of leaks: Extension piping or indoor units (when cooling)161
[4] Location of leaks: Outdoor unit (when heating) ............................ 163
9 CHECK THE COMPOSITION OF THE REFRIGERANT
(PURY-P200·250YMF-C only) ................................................................164
Safety precautions
Before installation and electric work
Before installing the unit, make sure you read all the “Safety precautions”.
The “Safety precautions” provide very important points regarding safety. Make sure you follow them.
This equipment may not be applicable to EN61000-3-2: 1995 and EN61000-3-3: 1995.
This equipment may have an adverse effect on equipment on the same electrical supply system. Please report to or take consent by the supply
authority before connection to the system.
Symbols used in the text
Warning: Describes precautions that should be observed to prevent danger of injury or death to the user.
Caution: Describes precautions that should be observed to prevent damage to the unit.
Symbols used in the illustrations
: Indicates an action that must be avoided. : Indicates that important instructions must be followed. : Indicates a part which must be grounded. : Beware of electric shock (This symbol is displayed on the
main unit label.) <Color: Yellow>
Warning:
Carefully read the labels affixed to the main unit.
Warning:
• Use the specified cables for wiring. Make the connections
securely so that the outside force of the cable is not applied to the terminals.
- Inadequate connection and fastening may generate heat and cause a fire.
• Have all electric work done by a licensed electrician according to “Electric Facility Engineering Standard” and “Interior Wire Regulations”and the instructions given in this manual and always use a special circuit.
- If the power source capacity is inadequate or electric work is
performed improperly, electric shock and fire may result.
• Securely install the cover of control box and the panel.
- If the cover and panel are not installed properly, dust or water
may enter the outdoor unit and fire or electric shock may result.
• After completing service work, make sure that refrigerant gas is not leaking.
- If the refrigerant gas leaks and is exposed to a fan heater,
stove, oven, or other heat source, it may generate noxious gases.
• Do not reconstruct or change the settings of the protection devices.
- If the pressure switch, thermal switch, or other protection
device is shorted and operated forcibly, or parts other than those specified by Mitsubishi Electric are used, fire or
explosion may result.
–2–
11
1 PRECAUTIONS FOR DEVICES THAT USE R407C REFRIGERANT
11
Caution
Do not use the existing refrigerant piping.
• The old refrigerant and refrigerator oil in the existing piping contains a large amount of chlorine which may cause the refrigerator oil of the new unit to deterio­rate.
Use refrigerant piping made of phosphorus deoxi­dized copper and copper alloy seamless pipes and tubes”. In addition, be sure that the inner and outer surfaces of the pipes are clean and free of hazardous sulphur, oxides, dust/dirt, shaving particles, oils, moisture, or any other contaminant.
• Contaminants on the inside of the refrigerant piping may cause the refrigerant residual oil to deteriorate.
Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing. (Store elbows and other joints in a plastic bag.)
• If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor trouble may result.
Use a vacuum pump with a reverse flow check valve.
• The vacuum pump oil may flow back into the refriger­ant cycle and cause the refrigerator oil to deteriorate.
Do not use the following tools that have been used with conventional refrigerants. (Gauge manifold, c harge hose, gas leak detector, re­verse flow check valve, refrigerant charge base, vacuum gauge, refrigerant recovery equipment)
• If the conventional refrigerant and refrigerator oil are mixed in the R407C, the refrigerant may deterio­rated.
• If water is mixed in the R407C, the refrigerator oil may deteriorate.
• Since R407C does not contain any chlorine, gas leak detectors for conventional refrigerants will not react to it.
Do not use a charging cylinder.
• Using a charging cylinder may cause the refrigerant to deteriorate.
Be especially careful when managing the tools.
Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator oil to coat flares and flange connections.
• The refrigerator oil will degrade if it is mixed with a large amount of mineral oil.
Use liquid refrigerant to seal the system.
• If gas refrigerant is used to seal the system, the com­position of the refrigerant in the cylinder will change and performance may drop.
Do not use a refrigerant other than R407C.
• If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may cause the refrigerator oil to de­teriorate.
• If dust, dirt, or water gets in the refrigerant cycle, the refrigerant may deteriorate.
If the refrigerant leaks, recover the refrigerant in the refrigerant cycle, then recharge the cycle with the specified amount of the liquid refrigerant indicated on the air conditioner.
• Since R407C is a nonazeotropic refrigerant, if addi­tionally charged when the refrigerant leaked, the com­position of the refrigerant in the refrigerant cycle will change and result in a drop in performance or abnor­mal stopping.
[1] Storage of Piping Material
(1) Storage location
Store the pipes to be used indoors. (Warehouse at site or owner’s warehouse) Storing them outdoors may cause dirt, waste, or water to infiltrate.
(2) Pipe sealing before storage
Both ends of the pipes should be sealed until immediately before brazing. Wrap elbows and T’s in plastic bags for storage.
* The new refrigerator oil is 10 times more hygroscopic than the conventional refrigerator oil (such as Suniso). Water
infiltration in the refrigerant circuit may deteriorate the oil or cause a compressor failure. Piping materials must be stored with more care than with the conventional refrigerant pipes.
[2] Piping Machining
Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator oil to coat flares and flange connections.
Use only the necessary minimum quantity of oil !
Reason :
1. The refrigerator oil used for the equipment is highly hygroscopic and may introduce water inside.
Notes :
Introducing a great quantity of mineral oil into the refrigerant circuit may also cause a compressor failure.
Do not use oils other than ester oil, ether oil or alkylbenzene.
5
[3] Necessary Apparatus and Materials and Notes on Their Handling
The following tools should be marked as dedicated tools for R407C.
<<Comparison of apparatus and materials used for R407C and for R22>>
Apparatus Used Use R22 R407C
Gauge manifold Evacuating, refrigerant filling Current product Charging hose Operation check Current product Charging cylinder Refrigerant charging Current product Do not use. Gas leakage detector Gas leakage check Current product Shared with R134a Refrigerant collector Refrigerant collection R22 For R407C use only Refrigerant cylinder Refrigerant filling R22
Vacuum pump Vacuum drying Current product
Vacuum pump with a check valve Current product Flare tool Flaring of pipes Current product Bender Bending of pipes Current product Application oil Applied to flared parts Current product
Torque wrench Tightening of flare nuts Current product Pipe cutter Cutting of pipes Current product Welder and nitrogen cylinder Welding of pipes Current product Refrigerant charging meter Refrigerant charging Current product Vacuum gauge Checking the vacuum degree Current product
Identification of dedi­cated use for R407C :Record refrigerant
name and put brown belt on upper part of cylinder.
Can be used by attaching an adapter with a check valve.
Ester oil or Ether oil or Alkybenzene (Small amount)
Symbols :
Tools for R407C must be handled with more care than those for conventional refrigerants. They must not come into contact with any water or dirt.
To be used for R407C only. Can also be used for conventional refrigerants.
–6–
[4] Brazing
No changes from the conventional method, but special care is required so that foreign matter (ie. oxide scale, water, dirt, etc.) does not enter the refrigerant circuit.
Example : Inner state of brazed section
When non-oxide brazing was not used When non-oxide brazing was used
Items to be strictly observed :
1. Do not conduct refrigerant piping work outdoors on a rainy day.
2. Apply non-oxide brazing.
3. Use a br azing material (Bcup-3) which requires no flux when brazing between copper pipes or between a copper pipe and copper coupling.
4. If installed refrigerant pipes are not immediately connected to the equipment, then br aze and seal both ends of them.
Reasons :
1. The new refrigerant oil is 10 times more hygroscopic than the conv entional oil. The probability of a machine failure if water infiltrates is higher than with conventional refrigerant oil.
2. A flux generally contains chlorine. A residual flux in the refrigerant circuit may generate sludge.
Note :
Commercially available antioxidants may have adverse effects on the equipment due to its residue, etc. When applying non-oxide brazing, use nitrogen.
–7–
[5] Airtightness Test
No changes from the conventional method. Note that a refrigerant leakage detector for R22 cannot detect R407C leakage.
Halide torch R22 leakage detector
Items to be strictly observed :
1. Pressuriz e the equipment with nitrogen up to the design pressure and then judge the equipments airtightness, taking temperature variations into account.
2. When investigating leakage locations using a refrigerant, be sure to use R407C.
3. Ensure that R407C is in a liquid state when charging.
Reasons :
1. Use of oxygen as the pressurized gas may cause an explosion.
2. Charging with R407C gas will lead the composition of the remaining refrigerant in the cylinder to change and this refrigerant can then not be used.
Note :
A leakage detector for R407C is sold commercially and it should be purchased.
[6] Vacuuming
1. Vacuum pump with check valve A vacuum pump with a check valve is required to prevent the vacuum pump oil from flowing back into the refrigerant circuit when the vacuum pump power is turned off (power failure). It is also possible to attach a check valve to the actual vacuum pump afterwards.
2. Standard degree of vacuum for the vacuum pump Use a pump which reaches 0.5 Torr (500 MICRON) or below after 5 minutes of operation. In addition, be sure to use a vacuum pump that has been properly maintained and oiled using the specified oil. If the vacuum pump is not properly maintained, the degree of vacuum may be too low.
3. Required accuracy of the vacuum gauge Use a vacuum gauge that can measure up to 5 Torr. Do not use a general gauge manifold since it cannot measure a vacuum of 5 Torr.
4. Evacuating time
Evacuate the equipment for 1 hour after 755 mmHg (5 Torr) has been reached.
After envacuating, leave the equipment for 1 hour and make sure the that vacuum is not lost.
5. Operating procedure when the vacuum pump is stopped In order to prevent a bac kflo w of the vacuum pump oil, open the relief valv e on the v acuum pump side or loosen the charge hose to drawn in air before stopping operation. The same operating procedure should be used when using a vacuum pump with a check valve.
–8–
[7] Charging of Refrigerant
R407C must be in a liquid state when charging, because it is a non-azeotropic refrigerant.
For a cylinder with a syphon attached For a cylinder without a syphon attached
Cylin-
Cylin-
der
Cylinder color identification R407C-Gray Charged with liquid refrigerant
R410A-Pink
Valve
der
Valve
Liquid
Liquid
Reasons :
1. R407C is a mixture of 3 refrigerants, each with a different evaporation temperature. Therefore, if the equipment is charged with R407C gas, then the refrigerant whose evapor ation temperature is closest to the outside temperature is charged first while the rest of refrigerants remain in the cylinder.
Note :
In the case of a cylinder with a syphon, liquid R407C is charged without turning the cylinder up side down. Chec k the type of cylinder before charging.
[8] Dryer
1. Replace the dryer when the refrigerant circuit is opened (Ex. Change the compressor, full gas leakage). Be sure to replace the dryer with a CITY MULTI Series Y (For use with R407C).
If any other product is used, the unit will be damaged.
2. Opening the refrigerant circuit after changing to a ne w dryer is less than 1 hour . The replacement of the dryer should be the last operation performed.
–9–
22
2 COMPONENT OF EQUIPMENT
22
[1] Appearance of Components
Outdoor unit
PU(H)Y-(P)200, 250YMF-C
Fan motor
Heatexchanger(rear)
Propeller fan
Heatexchanger(front)
Control Box
Compressor
PUHY-YMF-C PUY-P-YMF-C
4–way valve
SCC
Accumulator
Drier
SCC
Accumulator
Compressor
Compressor
10
PURY-P200·250YMF-C
Propeller fan
Fan motor
Heat exchanger(rear)
Heat exchanger(front)
Control box
Compressor
PURY-YMF-C PURY-P-YMF-C
4–way valve
SV block
SV6
SV5
SV4
SV3
Accumulator
4–way valve
CV block
Drier
SV block
CS circuit
SV6
SV5
SV4 SV3
Accumulator
CV block
Compressor
Compressor
–11–
Controller Box
FANCON board
INV board
MAIN board
Noise filter
Choke coil (L2)
Terminal block TB1A Power Source
Terminal block TB3 Transmission
Terminal block TB7 Transmission (Centralized control)
Inteligent Power Module (IPM)
G/A board
Capacitor (C2, C3) (Smoothing capacitor)
Diode stack (DS)
Magnetic contactor (52C)
–12–
MAIN board
PUHY / PURY
CNTR CNFC1
CNVCC4 Power source for control(5V)
CNS1 CNS2 CN40 CN41 CNVCC3
Power Source for control
1-2 30V 1-3 30V 4-6 12V 5-6 5V
CN51 Indication distance 3-4 Compressor ON/OFF 3-5 T roub le
CNRS3 Serial transmission to INV board
CN3D
CN20 Power supply
3 L1 1 N
SW4
SW3
SW2 SWU2
SWU1
CN3S
CN3N
LD1 Service LED
SW1
–13–
INV board
CNVDC 1-4 DC-560V
CN15V2 Power supply for IPM control
CNR
CN52C Control for 52C
CNFAN Control for MF1
CNAC2 Power source
1 L2 3 N 5 G
SW1
CNRS2 Serial transmission to MAIN board
CNVCC4 Power supply (5V)
CNL2 Choke coil
CNVCC2 Power supply
1-2 30V, 1-3 30V 4-6 12V, 5-6 5V
CNDR2 Out put to G/A board
CNTH
CNACCT
–14–
FANCON board
CNFAN
G/A board
CNPOW
CNFC2
CNE CNDC1
CN15V1
CNDR1
CNIPM1
–15–
BC controller
CNTR
CN02 M-NET transmission
CN03
CN12 Power supply
1 EARTH 3 N 5 L
SW4 SW2 SW1
–16–
RELAY 10 board
RELAY 4 board
–17–
[2] Refrigerant Circuit Diagram and Thermal Sensor
1PUHY-200YMF-C, 250YMF-C
: Solenoid valve : Orifice : Capillary : Check valve : Thermal sensor
: Strainer SP : Service port ACC : Accumulator
BV1ST1
CJ1
63HS
CJ2
CP1
Indoor unit
TH2
SV1
SV2
BV2
ST2
CP2
SA
SLEV
MA
TH7
ST4
LEV1
HEX2
HEX1
O/S
ST3
TH1
TH6
–18–
CV1
Comp
63H
SCC
TH8
TH5
2PUY-200YMF-C, 250YMF-C
: Solenoid valve : Orifice : Capillary : Check valve : Thermal sensor
: Strainer SP : Service port ACC : Accumulator
BV1ST1
CJ1
63HS
CJ2
CP1
SV1
TH2
SV2
BV2ST2
CP2
SA
SLEV
MA
TH7
ST4
LEV1
HEX2HEX1
O/S
TH6
ST3
–19–
Comp
63H
SCC
TH8
TH5
3PUHY-P200YMF-C, P250YMF-C
: Solenoid valve : Orifice : Capillary : Check valve : Thermal sensor
: Strainer SP : Service port ACC : Accumulator
ST1 BV1
CJ1
63HS
ST5
CJ2
CP1
O/S
Indoor units
63LS
ST3
SV1
SV2
TH1
CV1
Comp
SA
MA
TH10
63H
TH9
Drier
CP4
TH2
SLEV
CP3
ST2 BV2
TH8
TH7
ST4
LEV1
SCC
SV3
HEX 1 HEX 2
TH6
–20–
ST8
SV4
ST9
TH5
4PUY-P200YMF-C, 250YMF-C
ST1 BV1
: Solenoid valve : Orifice : Capillary : Check valve : Thermal sensor
: Strainer SP : Service port ACC : Accumulator
Indoor units
ST2 BV2
CJ1
SV3
63HS
ST5
CJ2
HEX2 HEX1
CP
O/S
63LS
ST3
SV1
TH1
SV2
CV1
Comp
MA SA
TH10
63H
TH9
Drier
TH2
CP3
CV2
SLEV
TH8
TH5
TH7
ST4
LEV1
SCC
TH6
–21–
5PURY-200YMF-C, 250YMF-C
CJ1
Solenoid Valves Block
: Solenoid valve
: Orifice
: Capillary
: Check valve
: Thermal sensor
: Strainer SP : Service port ACC : Accumulator
Distributor
63H
CV1
O/S
TH1
Comp
TH10
TH10
ST6
63HS
SV1
CP1
SV2
63LS
MA
CJ2
ACC
SA
SLEV
TH6
HEXb
SVC
SVA SVB
SV3
SV4
HEXf3
SV6
SV5
TH7
CV7
HEXf2
HEXf1
CV2
CV3
CV10
CV9CV8
CV4
CV5
CV6
TH5
ST1
BV1
BV2
Check Valves Block
Gas/liquid separator
TH12
TH15
LEV3
TH16
TH11
LEV1
63HS1
63HS3
BC controller CMB-P104V-E
–22–
TH21
TH22
TH23
LEV
Indoor units
6PURY-P200YMF-C, P250YMF-C
: Solenoid valve : Orifice : Capillary : Check valve : Thermal sensor
: Strainer SP : Service port ACC : Accumulator
ST5
SJ1
63HS
O/S
ST6
SV1
CV1
63H
TH1
Comp
TH10
TH2
TH9
Drier
CP2
CS(Composition Sensing) circuit
CP1
SV2
63LS
MA
CJ2
ACC
SA
SLEV
Solenoid Valves Block
HEXb
TH6
CV9CV8
CV10
SV3
SV4
Distributor
SV6
SV5
TH7
HEXf3
HEXf2
HEXf1
CV4
Check Valves Block
CV6
CV7
BV1
ST1
CV3CV2CV5
TH5
BV2
Gas/liquid separator
TH12
TH15
LEV3
TH11
LEV1
63HS1
63HS3
SVC
SVA SVB
TH21
TH23
TH22
LEV
Indoor units
TH16
BC controller CMB-P104V-E
–23–
SV4
*
1,
*
2
(Heat exchanger capacity control)
Solenoid valve
*
1
FB4
X1~10
Motor
(Compressor)
MC1
W
U
Inverter
*
2
TH6
TH9TH10
SLEV
63LS
321
63HS
TH2
TH1
321
LEV1
TH7TH8TH5
*
2
LD
ACCT
-W
BOX BODY
CNE
(2P)
21
N
*
2
SV3
SV4
X07
X06
12345
6
(6P)
CN36
342
1
31245
BOX BODY
BOX BODY
High pressure
switch
Crank case heater
(Compressor)
Diode
stack
Noise
Filter
Terminal
Block
Terminal
Block
CNFC2
(6P)
12345
6
circuit
detection
12345
6
N
L3
L2
L1
N
L3
L2
L1
Blue
Black
White
Red
NF
Blue
Black
Red
White
L1
TB1B
BOX BODY
N
L3
L2
12 1234
CN06
(2P)
CN34
(6P)
65432
1
123
CN38
(3P)
X10
X04
X05
21S4
SV2
63H
CN05
(4P)
(2P)
21
(6P)
CNFC1
CN09
Control circuit board
Blue
Red
White
Black
Brown
Red
Controller Box
BOX BODY
(INV board)
Power circuit board
L2
R7
MF1
(2P)
CN30V
(2P)
CNL2
(14P)
CN15V2
(5P)
CNLV2
(3P)
CNTR
(5P)
CNLV1
(3P)
CN32
(3P)
CNL
(3P)
CNH
(2P)
CN01
THHS
(8P)
CN02
(3P)
CN03
(3P)
CNFAN
(7P)
CNRS3
(6P)
CNVCC2
(6P)
CNVCC3
(2P)
CNVCC4
(7P)
CNRS2
X10
X01
X02
52C
32165
1234567
1234567
12143
2
23 12 123 1
43
2
21
12
12
3
Black
Red
V
White
CNTR1
1A F
250VAC
F3
T01
R3
R2
C3
C2
DCL
+
+
52C
R1
R5
C1
ZNR4
+
~
–~
DS
~
TB7
M2
M1
TB3
controller
remote
Indoor and
Connect to
Yellow
Green/
Blue
Black
Red
White
PE
L1
Red White Black
Red White Black
2A F
250VAC
F1
L2
TB1A
CH1
SV1
(MAIN board)
50/60Hz
380/400/415V
3N~
Power source
L3
N
4:Compressor ON/OFF
5:Trouble
N
12V
X01
X02
(2P)
CNTH
(4P)
CNVDC
3
(3P)
CN52C
2
(3P)
CNR
(3P)
CNX10
1
(3P)
CNS2
2
(5P)
CNAC2
(5P)
CN51
(2P)
CNS1
13
(2P)
CNVCC4
1
122
322
(3P)
CN20
3
(3P)
CN3D
1
1
(3P)
CN33
3
2A F
250VAC
F01
1
5322413
625
543215432132132
1122
1
3
8
1
763211
4
2
1
3
3
4
2
5
R6
PE
L3
1
L1
M1
M2
S
L2
Refer to the service handbook
about the switch operations.
CNDC1
(4P)
1234
CNDR2
(9P)
1210 11 13 14
543216789 54321
6789
1210 11 13 14543216789 54321 6789
Yellow Orange
Purple Black
White Gray
5
123
4
Fan motor
(Heat exchanger)
V
W
N
U
MF
UVW
P
N
Gate amp board
(G/A board)
132
CN3S
(3P)
FB1
FB2
FB3
IPM
CNDR1
(9P)
CN15V1
(14P)
Orange Brown
4
CNACCT
(4P)
(5P)
CNFAN
CN04
no fuse breaker
50A
30APU(H)Y-(P)200YMF-C
PU(H)Y-(P)250YMF-C
*
1
ACCT
-U
(3P)
CN3N
231
DEMAND
NIGHT MODE
OFF
ON
1-2
CN3D
OFF
ON
1-3
ON
OFF
Mode
Auto
Normal
changeover
HEAT
COOL
*
1
Green
Red White Black
N
L3
L2
L1
L1 L2 L3
32451
CNPOW
(5P)
(Fancon board)
Fan control board
F01 250VAC 6.3AF
F02 250VAC 6.3AF
F03 250VAC 6.3AF
MF1
52C
ZNR4
ACCT-U, W
<Symbol explanation>
DCL
Symbol Name
21S4
*
1
SV1, SV2
(Sub-cool coil bypass)
LEV1 Electronic expansion valve
IPM
SLEV
63HS
63LS
*
2
SV3
*
2
TH9
*
2
at Sub-cool coil
bypass outlet temp. detectTH8
TH7
TH6
TH5
TH1
TH2
L2
LD
TH10
*
2
THHS
FB1~4
*
2 are not existed
PUY - 200/250YMF-C
PUHY- 200/250YMF-C
*
1 and
*
2 are not existed
*
1 are not existed
PUHY-P200/250YMF-C
PUY -P200/250YMF-C
All exists
Appliance Name
<Difference of appliance>
Solenoid valve(Discharge-suction bypass)
4-way valve
Electronic expansion valve(Oil return)
High pressure sensor
Low pressure sensor
(Heat exchanger capacity control)
Solenoid valve
Varistor
(Power factor improvement)
DC reactor
Current Sensor
Ferrite core
Fan motor(Radiator panel)
(Inverter main circuit)
Magnetic contactor
Choke coil(Transmission)
Intelligent power module
Discharge pipe temp. detect
Radiator panel temp. detect
Compressor shell temp.
High pressure liquid temp.
OA temp. detect
Pipe temp. detect
Saturation evapo. temp. detect
Thermistor
Earth terminal
Aux. relay
liquid outlet temp. detect
at Sub-cool coil
Accumulator liquid level detect
[3] Electrical Wiring Diagram
1 PU(H)Y-(P)200·250YMF-C
24
2 PURY-(P)200·250YMF-C
FB4
MC1
LD
Black
White
Red
Green
no fuse breaker
30A
PURY-(P)250YMF-C
PURY-(P)200YMF-C
50A
NIGHT MODE
*
1
TH5
TH7
CN04
CNFAN
(5P)
(4P)
CNACCT
4
Brown
Orange
(14P)
CN15V1
(9P)
CNDR1
IPM
FB3
FB2
FB1
L3L2L1
(Fancon board)
Fan control board
(G/A board)
Gate amp board
N
P
WVU
43215
432
1
54321
MF
U
N
W
V
Fan motor
(Heat exchanger)
432
1
5
Gray
White
Black
Purple
Orange
Yellow
9876
12345987612345
14131110 12
1210 11 1314
(9P)
CNDR2
54321 6789 54321
4321
(4P)
CNDC1
Refer to the service handbook
about the switch operations.
L2
S
M2
M1
L1
1
L3
PE
R6
5
243
3
1
2
4
1123 67
1
8
3
1
221123712631523445321
526314223
5
1
F01
250VAC
2A F
3
CN33
(3P)
1
1
CN3D
(3P)
3
CN20
(3P)
223
221
1
CNVCC4
(2P)
31
CNS1
(2P)
CN51
(5P)
CNAC2
(5P)
2
CNS2
(3P)
1
CNX10
(3P)
CNR
(3P)
2
CN52C
(3P)
3
CNVDC
(4P)
CNTH
(2P)
X02
X01
12V
N
5 : Trouble
4 : Compressor ON/OFF
N
L3
Power source
3N~
380/400/415V
50/60Hz
(MAIN board)
SV1
CH1
TB1A
L2
F1
250VAC
2A F
123
TH1
TH2
Black
White
Red
63HS
123
Black
White
Red
63LS
L1
SLEV
PE
White
Red
Black
Blue
Green/
Yellow
Connect to
Indoor and
remote
controller
TB3
M1
M2
TB7
~
DS
~ –
~
+
ZNR4
C1
R5
R1
52C
+
+
DCL
C2
C3
R2
R3
T01
F3
250VAC
1A F
CNTR1
White
U
W
V
Motor
(Compressor)
Red
Black
3
21
21
12
2
34
13212
6
1
78
3
9
2
2341217654321
56123
X02
X01
X10
CNRS2
(7P)
CNVCC4
(2P)
CNVCC3
(6P)
CNVCC2
(6P)
CNRS3
(7P)
CNFAN
(3P)
CN03
(3P)
CN02
(8P)
THHS
CN01
(2P)
CNH
(3P)
CNL
(3P)
CN32
(3P)
CNLV1
(5P)
CNTR
(3P)
CN15V2
(14P)
CNL2
(2P)
CN30V
(2P)
MF1
R7
L2
Power circuit board
(INV board)
BOX BODY
Inverter
Controller Box
Red Brown
Black
White
Red
Blue
Control circuit board
TH10
CN09
CNFC1
(6P)
TH9
12
(2P)
CN37
(6P)
65432
1
X08
X09
CN36
(6P)
65432
1
X06
X07
(4P)
CN05
TH6
63H
SV2
21S4
X05
X04
X10
(3P)
CN38
321
12345
6
(6P)
CN34
(2P)
CN06
432121
L2
L3
N
BOX BODY
TB1B
L1
White
Red
Black
Blue
NF
Red
White
Black
Blue
L1L2L3
N
L1L2L3
N
65432
1
detection
circuit
SV4
SV3
SV6
SV5
*
1
65432
1
(6P)
CNFC2
(5P)
CNPOW
Terminal
Block
Terminal
Block
Noise
Filter
Diode
stack
Crank case heater
(Compressor)
High pressure
switch
BOX BODY
DEMAND
BOX BODY
N
(2P)
CNE
12
BOX BODY
ACCT
-W
ACCT
-U
52C
F02 250VAC 6.3AF
F03 250VAC 6.3AF
F01 250VAC 6.3AF
L1 L2
L3
N
*
1 are not existed
PURY-P200/250YMF-C
PURY- 200/250YMF-C
All exists
Appliance Name
<Difference of appliance>
SV1, SV2 Solenoid valve(Discharge-suction bypass)
4-way valve21S4
Electronic expansion valve(Oil return)
High pressure sensor
Low pressure sensor63LS
63HS
SLEV
(Heat exchanger capacity control)
Solenoid valve
SV3~6
Varistor
NameSymbol
DCL
(Power factor improvement)
<Symbol explanation>
DC reactor
ACCT-U, W
Current Sensor
ZNR4
FB1~4 Ferrite core
Fan motor(Radiator panel)
(Inverter main circuit)
52C
MF1
Magnetic contactor
Choke coil(Transmission)
Intelligent power moduleIPM
L2
Discharge pipe temp. detect
Radiator panel temp. detect
Compressor shell temp.
High pressure liquid temp.
OA temp. detect
Pipe temp. detect
Saturation evapo. temp. detect
Thermistor
THHS
TH10
*
1
TH9
*
1
TH6
TH5
TH2
*
1
TH1
Earth terminal
X1, 2, 4~10 Aux. relay
TH7
liquid outlet temp. detect
at Sub-cool coil
LD Accumulator liquid level detect
–25–
Symbol explanation
PE
1
2
3
1
2
3
EARTH
Terminal block
(for Transmission)
TB02
Terminal block
(for power source)
TB01
NameSymbol
Solenoid valve
Solenoid valve
Solenoid valve
Solenoid valve
Expansion valve
Thermister sensor
Transformer
NameSymbol
SV1 4A
SV1 4B
SV1 4C
SVM
TR
TH11 16
LEV1,3
PS1,3 Pressure sensor
Transmission line
Shield wire
/N 220V 240V 50Hz
Power source
BC Board
LEV1
TB01
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
SVM
SV4B
SV4A
SV4C
SV3B
SV3A
SV3C
SV2B
SV2A
SV2C
SV1C
SV1A
SV1B
}
3
1
CNTR
CN02
CN12
153
31
7
5
3
1
7
5
3
1
7
5
3
1
7
5
3
1
TR
X2
X1
X30
X4
X3
X31
X6
X5
X32
X8
X7
X33
X21
}
DC 30V
654321654321
LEV3
1
2
3
CNP1
1
2
3
CNP3
2
1
1
2
3
4
5
6
7
8
4
3
2
1
12321
CN03
CN13
CN10
CN11
CN07 CN05
L
N
TH11
TH12
TH15
TH16
PS1
PS3
20 22V
TB02
M2
M1
CN26
CN27
CN28
CN29
TB01
220 240V
CN36
1
1
1
1
Note:1.TB02 is terminal block for transmission.
Never connect power line to it.
2.
1
:SVM is not built in depending on models.
3 CMB-P104V-E
–26–
Symbol explanation
PE
1
2
3
1
2
3
EARTH
Terminal block
(for Transmission)
TB02
Terminal block
(for power source)
TB01
NameSymbol
Solenoid valve
Solenoid valve
Solenoid valve
Solenoid valve
Expansion valve
Thermister sensor
Transformer
NameSymbol
SV1 5A
SV1 5B
SV1 5C
SVM
TR
TH11 16
LEV1,3
PS1,3 Pressure sensor
Transmission line
Shield wire
/N 220V 240V 50Hz
Power source
BC Board
LEV1
TB01
16
15
2
1
2
1
14
13
12
11
10
9
8
7
6
5
4
3
2
1
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
SV4B
SV4A
SV4C
SV3B
SV3A
SV3C
SV2B
SV2A
SV2C
SV1C
SV1A
SV1B
}
3
1
CNTR
CN02
CN12
153
31
7
5
3
1
7
5
3
1
7
5
3
1
7
5
3
1
TR
X2
X1
X30
X4
X3
X31
X6
X5
X32
X8
X7
X33
X21
}
DC 30V
654321654321
LEV3
1
2
3
CNP1
1
2
3
CNP3
2
1
1
2
3
4
5
6
7
8
4
3
2
1
12321
CN03
CN13
CN10
CN11
CN07 CN05
L
N
TH11
TH12
TH15
TH16
PS1
PS3
20 22V
TB02
M2
M1
CN26
CN27
CN28
CN29
TB01
220 240V
SV5C
SV5A
SV5B
7
5
3
1
X10
X9
X34
CN30
SVM
CN36
1
1
1
1
Note:1.TB02 is terminal block for transmission.
Never connect power line to it.
2.
1
:SVM is not built in depending on models.
4 CMB-P105V-E
–27–
PE
1
2
3
1
2
3
EARTH
Transmission line
Shield wire
/N 220V 240V 50Hz
Power source
BC Board
31
LEV1
TB01
SV6B SV6A SV6C
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
SV5C
SV5A
SV5B
SV4B
SV4A
SV4C
SV3B
SV3A
SV3C
SV2B
SV2A
SV2C
SVM
SV1C
SV1A
SV1B
}
4321
1234
CN38
3
1
CNTR
CN02
CN12
153
31
7
5
3
1
7
5
3
1
7
5
3
1
7
5
3
1
7
5
3
1
7
5
3
1
TR
3
CNVCC1
12
X2
X1
X30
X4
X3
X31
X6
X5
X32
X8
X7
X33
X10
X9
X34
X12
X11
X35
X21
}
DC 30V
654321654321
LEV3
1
2
3
CNP1
1
2
3
CNP3
2
1
1
2
3
4
5
6
7
8
4
3
2
1
12321
CN51 CN50
CNOUT 1
CNOUT 3
CN03
CN13
CN10
CN11
CN07 CN05
L
N
TH11
TH12
TH15
TH16
PS1
PS3
20 22V
TB02
M2
M1
CN26
CN27
CN28
CN29
CN30
CN31
TB01
220 240V
CN36
Symbol explanation
Terminal block
(for Transmission)
TB02
Terminal block
(for power source)
TB01
NameSymbol
Solenoid valve
Solenoid valve
Solenoid valve
Solenoid valve
Expansion valve
Thermister sensor
Transformer
NameSymbol
SV1 6A
SV1 6B
SV1 6C
SVM
TR
TH11 16
LEV1,3
PS1,3 Pressure sensor
1
1
1
1
7654321123456
Note:1.TB02 is terminal block for transmission.
Never connect power line to it.
2.
1
:SVM is not built in depending on models.
5 CMB-P106V-E
–28–
PE
1
2
3
1
2
3
EARTH
}
Power source
}}
L
N
Power source
/N 220V 240V 50Hz
Transmission line
Shield wire
SVM
BC Board
CN38
1
3
1
CNTR
CN50
CN51
7654321123456
CN02
CN12
153
31
7
5
3
1
7
5
3
1
7
5
3
1
7
5
3
1
7
5
3
1
7
5
3
1
3
TR
3
CNVCC1
12
X2
X1
X30
X4
X3
X31
X6
X5
X32
X8
X7
X33
X10
X9
X34
X12
X11
X35
X21
}
DC 30V
654321654321
LEV3 LEV1
1
2
3
CNP1
1
2
3
CNP3
2
1
1
2
3
4
5
6
7
8
4
3
2
1
123
21
CN03
CN13
CN10
CN11
CN07 CN05
CN36
TH11
TH12
TH15
TH16
PS1
PS3
20 22V
TB02
M2
M1
CN26
CN27
CN28
CN29
CN30
CN31
TB01
220 240V
LEV1
7654321
TB01
SV6B SV6A SV6C
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
RELAY4 Board
SV5C
SV5A
SV5B
SV4B
SV4A
SV4C
SV3B
SV3A
SV3C
SV2B
SV2A
SV2C
CN32
CN33
CN39
3
1
SV7C
SV7A
SV7B
SV8C
SV8A
SV8B
SV1C
SV1A
SV1B
X14
X13
X36
X37 X15 X16
98765432116 15 1011121314
12345678910111213141516
CN52
75317531
Symbol explanation
Terminal block
(for Transmission)
TB02
Terminal block
(for power source)
TB01
NameSymbol
Solenoid valve
Solenoid valve
Solenoid valve
Solenoid valve
Expansion valve
Thermister sensor
Transformer
NameSymbol
SV1 8A
SV1 8B
SV1 8C
SVM
TR
TH11 16
LEV1,3
PS1,3 Pressure sensor
CNOUT 1
CNOUT 3
1
Note:1.TB02 is terminal block for transmission.
1
1
1
Never connect power line to it.
2.
1
:SVM is not built in depending on models.
6 CMB-P108V-E
–29–
PE
1
2
3
1
2
3
EARTH
}
Power source
}}
L
N
Power source
/N 220V 240V 50Hz
Transmission line
Shield wire
SV10B SV10A SV10C
SV9B SV9A SV9C
BC Board
CN38
1
3
1
CNTR
CN50
CN51
7654321123456
CN02
CN12
153
31
7
5
3
1
7
5
3
1
7
5
3
1
7
5
3
1
7
5
3
1
7
5
3
1
3
TR
3
CNVCC1
12
X2
X1
X30
X4
X3
X31
X6
X5
X32
X8
X7
X33
X10
X9
X34
X12
X11
X35
X21
}
DC 30V
654321654321
LEV3 LEV1
1
2
3
CNP1
1
2
3
CNP3
2
1
1
2
3
4
5
6
7
8
4
3
2
1
123
21
CN03
CN13
CN10
CN11
CN07 CN05
CN36
TH11
TH12
TH15
TH16
PS1
PS3
20 22V
TB02
M2
M1
CN26
CN27
CN28
CN29
CN30
CN31
TB01
220 240V
LEV1
7654321123456
CN35
TB01
SV6B SV6A SV6C
SVM
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
RELAY4 Board
SV5C
SV5A
SV5B
SV4B
SV4A
SV4C
SV3B
SV3A
SV3C
SV2B
SV2A
SV2C
CN32
CN33
CN34
CN39
3
1
SV7C
SV7A
SV7B
SV8C
SV8A
SV8B
SV1C
SV1A
SV1B
X14
X13
X36
X37 X15 X16
98765432116 15 1011121314
12345678910111213141516
X18
X17
X38
X39 X19 X20
CN52CN53
5731753175317533 31
Symbol explanation
Terminal block
(for Transmission)
TB02
Terminal block
(for power source)
TB01
NameSymbol
Solenoid valve
Solenoid valve
Solenoid valve
Solenoid valve
Expansion valve
Thermister sensor
Transformer
NameSymbol
SV1 10A
SV1 10B
SV1 10C
SVM
TR
TH11 16
LEV1,3
PS1,3 Pressure sensor
CNOUT 1
CNOUT 3
1
1
1
1
Note:1.TB02 is terminal block for transmission.
Never connect power line to it.
2.
1
:SVM is not built in depending on models.
7 CMB-P1010V-E
–30–
PE
EARTH
3
2
1
3
2
1
TB02
TB01
Name
Symbol
Terminal block
(for Transmission)
Solenoid valve
Solenoid valve
Solenoid valve
Solenoid valve
Terminal block
(for power source)
Pressure sensor
Expansion valve
Thermister sensor
Transformer
Name
SV1~13A
SV1~13B
SV1~13C
SVM
Symbol
TR
TH11~16
LEV1,3
PS1,3
M1
M2
DC 30V
}
Shield wire
Transmission line
Power source
}
L
N
Power source
~/N 220V~240V 50Hz
RELAY10
Board
BC Board
CN39
13
654321 1234567
CN51
CN50
135
CN12
13
CNOUT3
CNOUT1
1
3
5
7
1
3
5
7
1
3
5
7
1
3
5
7
1
3
5
7
1
3
5
7
1
3
5
7
1
3
5
7
7
5
3
1
1571571357
13
21
CNVCC2
3
CN42
X46
X47
X48
1
2
3
8
7
6
5
4
3
2
1
4
CNOUT2
CNOUT4
CN41
CN40
X41
X44
X40
X43
X42
X45
X20
X18
X19
X17
X39
X38
3
CNVCC1
12
X16
X15
X37
X36 X13 X14
X2
X1
X30
X4
X3
X31
X6
X5
X32
X8
X7
X33
X10
X9
X34
X12
X11
X35
X21
6
5432
1
6
5432
1
LEV3 LEV1
1
2
3
CNP1
1
2
3
CNP3
2
1
1
2
3
4
5
6
7
8
4
3
2
1
12321
CN03
CN02
CN13
CN10
CN11
CN07 CN05
33
CN34
CN33
1357
CN32
TH11
TH12
TH15
TH16
TR
TB02
CN38
CN26
CN27
CN28
CN29
CN30
CN31
TB01
CN35
3
1
CNTR
4
1
2
3
4
5
6
7
8
3
2
1
SV1B
SV1A
SV1C
SV2C
SV2A
SV2B
SV3C
SV3A
SV3B
SV4C
SV4A
SV4B
SV5B
SV5A
SV5C
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
SV9C
SV9A
SV9B
SV10C
SV10A
SV10B
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
14 13 12 11 101516 123456789
SV8B SV8A SV8C
SV7B SV7A SV7C
SVM
SV6C
SV6A
SV6B
SV11C
SV11A
SV11B
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
9
8
7
6
5
4
3
2
1
16
15
14
13
12
11
10
SV12C
SV12A
SV12B
SV13C
SV13A
SV13B
PS1
PS3
Note : 1. TB02 is transmission terminal block.
Never connect power line to it.
2.
1
:SVM is not built in depending on models.
20 22V 220 240V
CN36
1
1
1
1
8 CMB-P1013V-E
–31–
PE
EARTH
3
2
1
3
2
1
TB02
TB01
Name
Symbol
Terminal block
(for Transmission)
Solenoid valve
Solenoid valve
Solenoid valve
Solenoid valve
Terminal block
(for power source)
Pressure sensor
Expansion valve
Thermister sensor
Transformer
Name
SV1~16A
SV1~16B
SV1~16C
SVM
Symbol
TR
TH11~16
LEV1,3
PS1,3
M1
M2
DC 30V
}
Shield wire
Transmission line
Power source
}
L
N
Power source
~/N 220V~240V 50Hz
CN39
13
654321 1234567
CN51
CN50
135
CN12
13
CNOUT3
CNOUT1
1
3
5
7
1
3
5
7
1
3
5
7
1
3
5
7
1
3
5
7
1
3
5
7
1
3
5
7
1
3
5
7
7
5
3
1
1571571357
13
21
CNVCC2
3
CN42
X46
X47
X48
1
2
3
8
7
6
5
4
3
2
1
4
CNOUT2
CNOUT4
CN41
CN40
X41
X44
X40
X43
X42
X45
X20
X18
X19
X17
X39
X38
3
CNVCC1
12
X16
X15
X37
X36 X13 X14
X2
X1
X30
X4
X3
X31
X6
X5
X32
X8
X7
X33
X10
X9
X34
X12
X11
X35
X21
6
5432
1
6
5432
1
LEV3 LEV1
1
2
3
CNP1
1
2
3
CNP3
2
1
1
2
3
4
5
6
7
8
4
3
2
1
12321
CN03
CN02
CN13
CN10
CN11
CN07 CN05
33
CN34
CN33
1357
CN32
TH11
TH12
TH15
TH16
TR
TB02
CN38
CN26
CN27
CN28
CN29
CN30
CN31
TB01
CN35
3
1
CNTR
4
1
2
3
4
5
6
7
8
3
2
1
SV1B
SV1A
SV1C
SV2C
SV2A
SV2B
SV3C
SV3A
SV3B
SV4C
SV4A
SV4B
SV5B
SV5A
SV5C
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
SV9C
SV9A
SV9B
SV10C
SV10A
SV10B
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
14 13 12 11 101516 123456789
SV8B SV8A SV8C
SV7B SV7A SV7C
SVM
SV6C
SV6A
SV6B
SV11C
SV11A
SV11B
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
9
8
7
6
5
4
3
2
1
16
15
14
13
12
11
10
SV12C
SV12A
SV12B
SV13C
SV13A
SV13B
PS1
PS3
1
1
1
1
Note : 1. TB02 is transmission terminal block.
Never connect power line to it.
2.
1
:SVM is not built in depending on models.
1
2
2
1
1
3
5
7
1
3
5
7
1
3
5
7
X57
X53
X52
X56
X55
CN45
CN44
CN43
X50
SV14C
SV14A
SV14B
SV15A
SV15B
SV16C
SV16A
SV16B
SV15C
X54
X51
X49
RELAY10
Board
BC Board
20 22V 220 240V
CN36
9 CMB-P1016V-E
–32–
[4] Standard Operation Data
(1) Cooling operation 1 PU(H)Y-200·250YMF-C
Items
Ambient temp.
Indoor unit
Condition
Piping
Indoor unit fan notch Refrigerant volume Total current
Volts/Frequency
Outdoor unit
Indoor unit
Outdoor unit
Indoor Outdoor Quantity Quantity in operation Model Main pipe Branch pipe Total piping length
DB/WB
Set
m
kg
A V
V/Hz
PUHY-200YMF-C
PUY-200YMF-C
PUHY-250YMF-C
PUY-250YMF-C
27.0/19.0 27.0/19.0
35.0/24.0 35.0/24.0 44 44
63 63 50 25 125 40 63 25
55
10 10 10 10 10 10 10 10
45 45
Hi Hi Hi Hi Hi Hi Hi Hi
11.2 12.7
14.5 13.3 18.3 16.8 380 415 380 415
270/75 270/75 340/95 340/95
440 440 380 280 430 350 440 280
SC (LEV1) Oil return (SLEV)
LEV opening
High pressure/Low pressure (after O/S) (before MA)
Pressure
Discharge (TH1) Heat exchanger outlet (TH5)
Inlet
Accumulator
Outlet
Outdoor unit
Suction (Comp) TH2 Shell bottom (Comp)
Sectional temperature
SCC outlet (TH7) Bypass outlet (TH8)
Indoor unit
LEV inlet Heat exchanger outlet
Pulse
kg/cm
(MPa)
˚C
130 140 235 235
2
G
22.0/4.80 20.3/4.7
(2.16/0.47) (1.99/0.46)
93 95 40 42
75 97 710
64 69 60 27 27
86 26 26 10 10
–33–
PU(H)Y-P200·250YMF-C
Items
Ambient temp.
Indoor unit
Condition
Piping
Indoor unit fan notch Refrigerant volume Total current
Volts/Frequency
Outdoor unit
Indoor unit
Outdoor unit
Indoor Outdoor Quantity Quantity in operation Model Main pipe Branch pipe Total piping length
DB/WB
Set
m
kg
A V
V/Hz
PUHY-P200YMF-C
PUY-P200YMF-C
PUHY-P250YMF-C
PUY-P250YMF-C
27.0/19.0 27.0/19.0
35.0/24.0 35.0/24.0 44 44
63 63 50 25 125 40 63 25
55
10 10 10 10 10 10 10 10
45 45
Hi Hi Hi Hi Hi Hi Hi Hi
11.7 13.2
14.5 13.3 18.3 16.8 380 415 380 415
270/75 270/75 340/95 340/95
440 440 380 280 430 350 440 280 SC (LEV1) Oil return (SLEV)
LEV opening
High pressure/Low pressure (after O/S) (before MA)
Pressure
Discharge (TH1) Heat exchanger outlet (TH5)
Inlet
Accumulator
Outlet
Outdoor unit
Suction (Comp) CS circuit (TH2) CS circuit (TH9) Shell bottom (Comp)
Sectional temperature
SCC outlet (TH7) Bypass outlet (TH8)
Indoor unit
LEV inlet Heat exchanger outlet
Pulse
kg/cm
(MPa)
˚C
130 140 235 235
2
G
20.5/4.0 21.9/3.9
(2.01/0.39) (2.15/0.38)
96 96 40 42
77 10 10 12 15 –1 –1 11 11 80 85 27 27
86 26 26 10 10
αOC
0.23 0.23
–34–
PURY-200·250YMF-C
Items
Ambient temp.
Indoor Outdoor Quantity
Indoor unit
Quantity in operation Model Main pipe
Piping
Condition
Branch pipe
Total piping length Indoor unit fan notch Refrigerant volume
Compressor volts / Frequency
Outdoor unit Indoor unit
Outdoor unit
DB/WB
Qty
m
kg
V
V/Hz
A
PURY-P200YMF-C PURY-P250YMF-C
27.0/19.0 27.0/19.0
35.0/24.0 35.0/24.0 44 44
63 63 50 25 125 40 63 25
55
55555555
25 25
Hi Hi Hi Hi Hi Hi Hi Hi
13.9 14.4
380 415 380 415
270/75 270/75 340/95 340/95
14.5 13.3 18.3 16.8
330 460 430 300 410 330 460 300 BC controller (1, 3) Oil return
LEV opening
High pressure/Low pressure
BC controller liquid/Intermediate
Pressure
Discharge (TH1) Heat exchanger outlet (TH5)
Outdoor unit
Accumulator
Suction (Comp) Shell bottom (Comp)
Sectional temperature
Indoor unit
LEV inlet Heat exchanger outlet
Inlet Outlet
Pulse
kg/cm
(MPa)
˚C
2000 140 2000 150
235 235
20.7/5.0 19.4/4.0
2
G
(2.03/0.49) (1.90/0.39)
19.6/19.6 18.3/18.3
(1.92/1.92) (1.79/1.79)
107 110
50 47
77 10 10 12 12 75 70 26 30 15 15
–35–
PURY-P200·250YMF-C
Items
Indoor
Ambient temp.
Outdoor Quantity
Indoor unit
Quantity in operation Model Main pipe
Piping
Condition
Branch pipe
Total piping length Indoor unit fan notch Refrigerant volume
Compressor volts / Frequency
Outdoor unit Indoor unit
Outdoor unit
DB/WB
Qty
m
kg
V
V/Hz
A
PURY-P200YMF-C PURY-P250YMF-C
27.0/19.0 27.0/19.0
35.0/24.0 35.0/24.0 44 44
63 63 50 25 125 40 63 25
55
55555555
25 25
Hi Hi Hi Hi Hi Hi Hi Hi
14.4 14.9
380 415 380 415
270/75 270/75 340/95 340/95
14.5 13.3 18.3 16.8
330 460 430 300 410 330 460 300
BC controller (1, 3) Oil return
LEV opening
High pressure/Low pressure
BC controller liquid/Intermediate
Pressure
Discharge (TH1) Heat exchanger outlet (TH5)
Outdoor
Accumulator
unit
Suction (Comp) CS circuit (TH2)
Sectional temperature
Indoor unit
Shell bottom (Comp) LEV inlet Heat exchanger outlet
αOC
Inlet Outlet
Pulse
kg/cm
(MPa)
˚C
2000 140 2000 150
235 235
23.5/5.3 23.0/5.1
2
G
(2.30/0.52) (2.25/0.50)
22.4/22.4 21.9/21.9
(2.20/2.20) (2.15/2.15)
97 105 50 47
77
10 10 12 12
75
75 70 26 30 15 15
0.23 0.23
–36–
2 Heating operation PUHY-200·250YMF-C
Items
Ambient temp.
Indoor unit
Condition
Piping
Indoor unit fan notch Refrigerant volume Total current
Volts/Frequency
Outdoor unit
Indoor unit
Outdoor unit
Indoor Outdoor Quantity Quantity in operation Model Main pipe Branch pipe Total piping length
DB/WB
Set
m
kg
A V
V/Hz
PUHY-200YMF-C PUHY-250YMF-C
20.0/– 20.0/–
7.0/6.0 7.0/6.0 44 44
63 63 50 25 125 40 63 25
55
10 10 10 10 10 10 10 10
45 45
Hi Hi Hi Hi Hi Hi Hi Hi
11.2 12.7
13.4 12.3 17.1 15.6 380 415 380 415
280/83 280/83 355/102 355/102
510 510 450 280 440 420 510 280 SC (LEV1) Oil return (SLEV)
LEV opening
High pressure/Low pressure (after O/S) (before MA)
Pressure
Discharge (TH1) Heat exchanger outlet (TH5)
Inlet
Outdoor unit
Accumulator
Outlet Suction (Comp) TH2
Sectional temperature
Indoor unit
Shell bottom (Comp) Heat exchanger outlet LEV inlet
Pulse
kg/cm
(MPa)
˚C
00
150 235
2
G
17.5/3.7 17.5/3.7
(1.72/0.36) (1.72/0.36)
80 85
68
1 21 21 22 2
50 60 71 71 33 33
–37–
PUHY-P200·250YMF-C
Items
Ambient temp.
Indoor unit
Condition
Piping
Indoor unit fan notch Refrigerant volume Total current
Volts/Frequency
Outdoor unit
Indoor unit
Outdoor unit
Indoor Outdoor Quantity Quantity in operation Model Main pipe Branch pipe Total piping length
DB/WB
Set
m
kg
A V
V/Hz
PUHY-P200YMF-C PUHY-P250YMF-C
20.0/– 20.0/–
7.0/6.0 7.0/6.0 44 44
63 63 50 25 125 40 63 25
55
10 10 10 10 10 10 10 10
45 45
Hi Hi Hi Hi Hi Hi Hi Hi
11.7 13.2
13.4 12.3 17.1 15.6 380 415 380 415
270/75 270/75 340/95 340/95
510 510 450 280 440 420 510 280 SC (LEV1) Oil return (SLEV)
LEV opening
High pressure/Low pressure (after O/S) (before MA)
Pressure
Discharge (TH1) Heat exchanger inlet (TH5)
Inlet
Accumulator Outdoor unit
Suction (Comp)
Outlet
CS circuit (TH2)
CS circuit (TH9)
Sectional temperature
Shell bottom (Comp)
Indoor unit
Heat exchanger outlet
LEV inlet αOC
Pulse
kg/cm
(MPa)
˚C
00
150 150
2
G
18.5/3.7 21.4/3.7
(1.81/0.36) (2.10/0.36)
75 78
1 12 22 23 33 3
00 60 70 80 80 39 39
0.28 0.28
–38–
PURY-200·250YMF-C
Items
Indoor
Ambient temp.
Outdoor Quantity
Indoor unit
Quantity in operation Model Main pipe
Piping
Condition
Branch pipe
Total piping length Indoor unit fan notch Refrigerant volume
Compressor volts / Frequency
Outdoor unit total current Indoor unit
Outdoor unit
DB/WB
Qty
m
kg
V
V/Hz
A
PURY-200YMF-C PURY-250YMF-C
20.0/– 20.0/–
7.0/6.0 7.0/6.0 44 44
63 63 50 25 125 40 63 25
55
55555555
25 25
Hi Hi Hi Hi Hi Hi Hi Hi
13.9 14.4
380 415 380 415
285/85 285/85 360/105 360/105
13.4 12.3 17.1 15.6
600 950 750 400 750 600 950 400
BC controller (1, 3) Oil return
LEV opening
High pressure/Low pressure
BC controller liquid/Intermediate
Pressure
Discharge (TH1) Heat exchanger outlet (TH5)
Outdoor unit
Accumulator
Suction (Comp) Shell bottom (Comp)
Sectional temperature
Indoor unit
LEV inlet Heat exchanger outlet
Inlet Outlet
Pulse
kg/cm
(MPa)
˚C
60 700 60 800
150 235
18.5/3.6 18.0/3.7
2
G
(1.81/0.35) (1.76/0.36)
17.5/14.0 17.0/14.0
(1.72/1.37) (1.67/1.37)
100 95
2 11 14 21 1
45 40 38 40 80 85
–39–
PURY-P200·250YMF-C
Items
Indoor
Ambient temp.
Outdoor Quantity
Indoor unit
Quantity in operation Model Main pipe
Piping
Condition
Branch pipe
Total piping length Indoor unit fan notch Refrigerant volume
Compressor volts/Frequency
Outdoor unit total current Indoor unit
Outdoor unit
DB/WB
Qty
m
kg
V
V/Hz
A
PURY-P200YMF-C PURY-P250YMF-C
20.0/– 20.0/–
7.0/6.0 7.0/6.0 44 44
63 63 50 25 125 40 63 25
55
55555555
25 25
Hi Hi Hi Hi Hi Hi Hi Hi
14.4 14.9
380 415 380 415
280/80 280/80 340/95 340/95
13.4 12.3 17.1 15.6
600 950 750 400 750 600 950 400
BC controller (1, 3) Oil return
LEV opening
High pressure/Low pressure
BC controller liquid/Intermediate
Pressure
Discharge (TH1) Heat exchanger outlet (TH5)
Outdoor
Accumulator
unit
Suction (Comp) CS circuit
Sectional temperature
Indoor unit
Shell bottom (Comp) LEV inlet Heat exchanger outlet
αOC
Inlet Outlet
(TH2)
Pulse
kg/cm
(MPa)
˚C
60 700 60 800
150 235
18.5/3.6 18.0/3.7
2
G
(1.96/0.38) (1.86/0.34)
17.5/14.0 17.0/14.0
(1.86/1.57) (1.76/1.47)
100 95
2 11 14 21 1
75
45 40 38 40 80 85
0.28 0.28
–40–
[5] Function of Dip SW and Rotary SW
(1) Outdoor unit 1 PU(H)Y-200·250YMF-C
Switch Function
SWU
1~2
Unit address setting
SW1
1~8
For self diagnosis/ operation monitoring
9~10
SW2
SW3
1
Centralized control switch
2
Deletion of connection information.
3
Deletion of error history.
4 5 6
Disregard ambient air sensor errors, liquid overflow errors.
7
Forced defrosting
8
Defrost prohibited timer
9
10
1
SW3-2 Function valid/ invalid
2
Indoor unit test operation
3
Defrosting start tempera­ture of TH5.
4
Defrosting end tempera­ture of TH5. Opening angle of IC except when heater thermostat is ON during defrosting.
Function according to switch operation Switch set timing
When off When on When off When on
Set on 51~100 with the dial switch.
LED monitering display
Centralized control not connected. Storing of refrigeration system connection information.
– –
Errors valid.
Ordinary control
-
­SW3-2 Function invalid
Stop all indoor units.
– –
43 min.
– –
-2°C
8°C
(no operation)
Centralized control connected. Deletion of refrigeration system connection information. Deletion
– –
Disregard errors.
Start forced defrosting.
90 min.
– –
SW3-2 Function valid
All indoor units test operation ON.
0°C
15°C
2000
Before power is turned on. During normal operation when power is on. Should be set on OFF. Before power is turned on.
Before power is turned on.
During normal operation when power is on.
During normal operation when power is on.
During normal operation when power is on.
During normal operation when power is on. (Except during defrosting)
During normal operation when power is on. When SW3-1 is ON after power is turned on. During normal operation when power is on. During normal operation when power is on. (Except during defrosting)
– –
10 minutes or more after compressor starts.
– –
5 6
Models
7
Target Pd (High pressure)
8 9
10
SW4
Note:
SWU1~2=00 when shipped from the factory. Other factory settings are indicated by shaded portions.
If the address is set from 01 to 50, it automatically becomes 100.
Models 1 2 3
– –
– – –
PUHY-YMF-C
18kg/cm2G
(1.76MPa)
– –
Model 200
– – –
PUY-YMF-C
20kg/cm2G
(1.96MPa)
– –
Model 250
– – –
When switching on the power.
During normal operation when power is on.
– –
When switching on the power.
– – –
41
2 PUHY-P200·250YMF-C
Switch Function
SWU
1~2
Unit address setting
SW1
1~8
For self diagnosis/ operation monitoring
9~10
SW2
SW3
1
Centralized control switch
2
Deletion of connection information.
3
Deletion of error history .
4 5 6
Disregard ambient air sensor errors, liquid overflow errors.
7
Forced defrosting
8
Defrost prohibited timer
9
10
1
SW3-2 Function valid/ invalid
2
Indoor unit test operation
3
Defrosting start tempera­ture of TH5.
4
Defrosting end tempera­ture of TH5. Opening angle of IC except when heater thermostat is ON during defrosting.
Function according to switch operation Switch set timing
When off When on When off When on
Set on 51~100 with the dial switch.
LED Monitering Display
Centralized control not connected. Storing of refrigeration system connection information.
– –
Errors valid.
Ordinary control
– –
SW3-2 Function invalid
Stop all indoor units.
– –
39 min.
– –
4°C
8°C
(no operation)
Centralized control connected. Deletion of refrigeration system connection information. Deletion
– –
Disregard errors.
Start forced defrosting.
90 min.
– –
SW3-2 Function valid
All indoor units test operation ON.
–1°C
15°C
2000
Before power is turned on. During normal operation when power is on. Should be set on OFF. Before power is turned on.
Before power is turned on.
During normal operation when power is on.
During normal operation when power is on.
During normal operation when power is on.
During normal operation when power is on. (Except during defrosting)
During normal operation when power is on. When SW3-1 is ON after power is turned on. During normal operation when power is on. During normal operation when power is on. (Except during defrosting)
– –
10 minutes or more after compressor starts.
– –
5 6
Models
7
Target Tc (High pressure)
at Heating 8 9
10
Models
SW4
Note:
1
SW4-2 Function valid/
invalid 2
Configuration compensa-
tion value 3
SWU1~2=00 when shipped from the factory. Other factory settings are indicated by shaded portions.
If the address is set from 01 to 50, it automatically becomes 100.
– –
Changes as shown below by on off change 0% 3% 6% 9% 12% –6% –3% 0%
PUHY-P-YMF-C
49˚C
– –
Model P200
Invalid
PUY-P-YMF-C
53˚C
– –
Model P250
Valid
When switching on the power. During normal operation when power is on.
– –
When switching on the power. During normal operation when power is on. when SW4-1 in ON.
42
3 PURY-200·250YMF-C
Switch Function
SWU
1~2
SW1
SW2
SW3
SW4
Unit address setting
1~8
For self diagnosis/ operation monitoring
9~10
1
Centralized control switch
2
Deletion of connection information.
3
Deletion of error history.
4 5 6
Disregard ambient air sensor errors, liquid overflow errors.
7
Forced defrosting
8
Defrost prohibited timer
9
10
1
SW3-2 Function valid/ invalid
2
Indoor unit test operation
3
Defrosting start tempera­ture of TH7.
4
Defrosting end tempera-
ture of TH5. 5 6
Pump down operation
7
Target Td (High pressure)
at Heating 8 9
10
Models 1 2 3
Function according to switch operation Switch set timing
When off When on When off When on
Set on 51~100 with the dial switch.
LED monitering display
Centralized control not connected. Storing of refrigeration system connection information.
– –
Errors valid.
Ordinary control
– –
SW3-2 Function invalid
Stop all indoor units.
– –
– – –
– –
43 min.
– –
6°C
8°C
Invalid
49˚C
– –
Model 200
– – –
Centralized control
connected. Deletion of refrigeration system connection information. Deletion
– –
Disregard errors.
Start forced defrosting.
90 min.
– –
SW3-2 Function valid
All indoor units test operation ON.
–3°C
15°C
Valid
53˚C
– –
Model 250
– – –
Before power is turned on. During normal operation when power is on. Should be set on OFF. Before power is turned on.
Before power is turned on.
During normal operation when power is on.
During normal operation when power is on.
During normal operation when power is on.
During normal operation when power is on. (Except during defrosting)
During normal operation when power is on. When SW3-1 is ON after power is turned on. During normal operation when power is on. During normal operation when power is on. (Except during defrosting)
During compressor stop when power is on. During normal operation when power is on.
When switching on the power.
– –
10 minutes or more after compressor starts.
– –
– –
– – –
Note:
SWU1~2=00 when shipped from the factory. Other factory settings are indicated by shaded portions.
If the address is set from 01 to 50, it automatically becomes 100.
43
4 PURY-P200·250YMF-C
Switch Function
SWU
1~2
Unit address setting
SW1
1~8
For self diagnosis/ operation monitoring
9~10
SW2
SW3
SW4
1
Centralized control switch
2
Deletion of connection information.
3
Deletion of error history .
4 5 6
Disregard ambient air sensor errors, liquid overflow errors.
7
Forced defrosting
8
Defrost prohibited timer
9
10
1
SW3-2 Function valid/ invalid
2
Indoor Unit Test operation
3
Defrosting start tempera­ture of TH7.
4
Defrosting end tempera-
ture of TH5. 5 6
Pomp down operation
7
Target Tc (High pressure)
at Heating 8 9
10
1
SW4-2 function valid/
Invalid 2
Configuration compensa-
tion value 3
Models
Function according to switch operation Switch set timing
When off When on When off When on
Set on 51~100 with the dial switch.
LED monitering display
Centralized control not connected. Storing of refrigeration system connection information.
– –
Errors valid.
Ordinary control
– –
SW3-2 Function invalid
Stop all indoor units.
– –
Changes as shown below by on off change 0% 3% 6% 9% 12% –6% –3% 0%
– –
43 min.
– –
8°C
8°C
Invalid
49˚C
– –
Model P200
Invalid
Centralized control connected. Deletion of refrigeration system connection information. Deletion
– –
Disregard errors.
Start forced defrosting.
90 min.
– –
SW3-2 Function valid
All indoor units test operation ON.
–5°C
15°C
Valid
53˚C
– –
Model P250
Valid
Before power is turned on. During normal operation when power is on. Should be set on OFF. Before power is turned on.
Before power is turned on.
During normal operation when power is on.
During normal operation when power is on.
During normal operation when power is on.
During normal operation when power is on. (Except during defrosting)
During normal operation when power is on. When SW3-1 is ON after power is turned on. During normal operation when power is on. During normal operation when power is on. (Except during defrosting)
During compressor stop when power is on. During normal operation when power is on.
When switching on the power. During normal operation when power is on. when SW4-1 in ON.
– –
10 minutes or more after compressor starts.
– –
– –
Note:
SWU1~2=00 when shipped from the factory. Other factory settings are indicated by shaded portions.
If the address is set from 01 to 50, it automatically becomes 100.
44
(2) Indoor unit
DIP SW1, 3
Switch SW name
Room temp. sensor position
1
Clogged filter detect.
2
Filter duration
3
OA intake
4
Remote display select.
5
SW1
SW3
Humidifier control
6
Heating thermo. OFF airflow
7
Heating thermo. OFF airflow
8
Power failure automatic
9
return Power source start/stop
10
Model selection
1
2
3 4 5 6
Cooling capacity saving
Louver
for PKFY-P. VAM, effective/ineffective
Vane Vane swing function Vane horizontal angle
Vane angle set for cooling 7 8
Heating 4deg up 9
10
Operation by SW
OFF ON OFF ON
Indoor unit inlet
None 100h
Ineffective
Fan output display
At stationary heating
Very low speed
SW1-7 setting
Ineffective
Ineffective
Heat pump
None
None None
1st setting
Down blow B, C
Effective
– –
– –
Built in remote controller
Provided
2500h
Effective
Thermo. ON signal display
Always at heat.
Low speed Set airflow
Effective
Effective
Cool.only
Provided
Provided Provided
2nd setting
Horizontal
Ineffective
– –
Switch set timing
At unit stopping
(at remote
controller OFF)
Remarks
Always ineffective for PKFY-P.VAM
Not provided for PKFY-P.VAM Provided for PLFY-P.VGM (ON) setting
Always down blow B,C for PKFY-P.VAM Horizontal (ON) setting for PLFY-P.VLMD
Ineffective (ON) setting for floor standing
Note 1: The shaded part indicates the setting at factory shipment. (For the SW not being shaded, refer to the
table below.)
Switch
SW1
SW3
Model
3 6 7 3 4 6 8
VBM-A
OFF OFF
ON
OFF
PLFY-P VLMD-A
ON
OFF
ON
OFFONON
VKM-A
VML-A VMH-A
OFF ON
ON
OFF
PEFY-P 20~80VMM-A
OFF
ON
OFF ON
PDFY-P
100~140VMM-A
OFF OFF
OFF
VM-A
ON
PFFY-P PCFY-P
VLRM-A, VLEM-A
OFF
OFF
ON OFF
PKFY-P
VGM-AONVAM-A VGM-A
OFF
OFF
ON
ON OFF ON
Note 2: The DipSW setting is only effective during unit stopping (remote controller OFF) for SW1, 2, 3 and 4 commonly
and the power source is not required to reset.)
3: When both SW1-7 and SW1-8 are being set to ON, the fan stops at the heating thermostat of OFF.
Setting of DIP SW2
Model P20 P25 P32 P40 P50 P63 Capacity (model name) code
SW2 setting
45 681013
OFF
ON
OFF
ON
ON
OFF
OFF
ON
OFF
ON
OFF
ON
Model P71 P80 P100 P125 P140 P200 P250 Capacity (model name) code
SW2 setting
14 16 20 25 28 40 50
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
–45–
Setting of DIP SW4 Setting of DIP SW5
Model Circuit board used
PMFY-P-VBM-A PLFY-P-VLMD-A PDFY-P20 ~ 80VM-A PLFY-P40 ~ 63VKM-A PLFY-P80 ~ 125VKM-A PCFY-P-VGM-A PKFY-P-VGM-A PKFY-P-VAM-A PEFY-P20 ~ 80VMM-A PFFY-P-VLEM-A, P-VLRM-A PEFY-P20 ~ 32VML-A PEFY-P40 ~ 140VMH-A PEHY-P200·250VMH-A PDFY-P100·125VM-A PEFY-P100 ~ 140VMM-A
Phase control
Relay selection
1234
ON OFF ON OFF
––––
ON OFF ON OFF
OFF OFF OFF ON
ON OFF OFF ON OFF ON OFF ON OFF OFF ON ON
––––
ON ON OFF OFF OFF OFF OFF
ON ON ON – OFF OFF OFF
ON OFF OFF – OFF OFF ON
ON ON ON OFF
SW4
220V 240V
Switch Function Operation by switch Switch set timing
(PLFY-P-VKM-A) (PCFY-P-VGM-A)
Ceiling height 3 3.5 m 2 2.8 m 1 2.3 m
Always after powering
SWA
Ceiling height setting
3 2 1
*The ceiling
height is changed by SWB setting.
3 2 1
SWA
SWA
SWB
SWC
External static pressure setting
For options
Setting of air outlet opening
Airflow control
(PDFY-P20 ~ 80VM-A, PEFY-P20 ~ 80VMM-A)
3 2 1
*
For other models, change the setting of static pressure by replacing the connector.
100Pa
50Pa 30Pa
(PLFY-P-VLMD-A)
3
*As this switch is used by interlocking with SWC,
2 1
(PLFY-P-VKM-A)
refer to the item of SWC for detail.
2-way 3-way 4-way
SWA
SWB
123
2-way 3.5 m 3.8 m 3.8 m 3-way 3.0 m 3.3 m 3.5 m 4-way 2.7 m 3.0 m 3.5 m
(PLFY-P-VKM-A, PCFY-P-VGM-A, PKFY-P-VGM-A, PDFY-P-VM-A)
Option
Standard
*Set to the option to install the high efficiency
filter
Always after powering
Always after powering
Always after powering
Always after powering
–46–
33
3 TEST RUN
33
[1] Before Test Run
(1) Check points before test run
1 Neither refrigerant leak nor loose power source/ transmission lines should be found.
2 Confirm that the resistance between the power source terminal block and the ground exceeds 2M by measur-
ing it with a DC500V megger. Do not run if it is lower than 2MΩ. Note) Never apply the megger to the MAIN board. If applied, the MAIN board will be broken.
3 Confirm that the Ball valve at both gas and liquid sides is being fully opened.
Note) Certainly close the cap.
4 Be sure that the crankcase heater has been powered by turning the main power source on at least 12 hours
before starting the test run. The shorter powering time causes compressor trouble.
(2) Caution at inverter check
Because the inverter power portion in outdoor unit electrical part box have a lot of high voltage portion, be sure to follow the instructions shown below.
During energizing power source, never touch inverter power portion because high voltage (approx. 580V) is
1
applied to inverter power portion.
When checking,
1
Shut off main power source, and check it with tester, etc.
2
Allow 10 minutes after shutting off main power source.
2
Open the MAIN board mounting panel, and check whether voltage of both ends of electrolytic capacitor is
3
20V or less.
–47–
(3) Check points for test run when mounting options
Built-in optional parts Mounting of drain
water lifting-up mechanism
1
2
3
Mounting of perme­able film humidifier
(4) Attention for mounting drain water lifting-up mechanism
Work
Disassembling and assembling of drain water lifting-up mechanism
Check humidifier operations and water supply status in heating (test run) mode.
1
2
Content of test run
Release connector of pump circuit, check error detection by pouring water into drain pan water inlet.
After that, connect connector of circuit.
Check pump operations and drain­age status in cooling (test run) mode.
Content of test run
Lead wire from control box not damaged.
Rubber cap properly inserted to drain water outlet of drain pan?
Check point
Local remote controller displays code No. 2503, and the mechanism stops.
No overflow from drain pan. Drain water comes out by operations of
drain pump. Sound of pump operations is heard, and
drain water comes out. No water leak from connecting portions
of each water piping. Water is supplied to water supply tank,
and float switch is operating.
Check point Result
Insulation pipe
Result
Mounting of float switch
Electric wiring
Insulation pipe of gas and liquid
3
pipes dealt with as shown in the right figure?
Drain pan and piping cover mounted
4
without gap? Drain pan hooked on cut projection
5
of the mechanism?
Float switch installed without contacting with drain pan?
1
No mistakes in wiring? Connectors connected surely and
2
tightly? No tension on lead wire when sliding
3
control box?
No gap
1
Float switch moves smoothly. Float switch is mounted on
2
mounting board straightly without deformation.
Float switch does not contact with
3
copper pipe. Wiring procedure is exactly followed. Connector portion is tightly hooked.
–48–
(5) Check points for system structure
ex. PURY-200YMF-C
Check points from installation work to test run.
Classification
Installation and piping
Power source wiring
Portion
1
2
3
4
5
6
7
8
1
2
3
Check item
Instruction for selecting combination of outdoor unit, and indoor unit followed? (Maximum number of indoor units which can be connected, connecting model name, and total capacity.)
Follow limitation of refrigerant piping length? For ex­ample, 70m or less (total length : 220m) at the farthest.
Connecting piping size of branch piping correct? Refrigerant piping diameter correct? Refrigerant leak generated at connection? Insulation work for piping properly done? Specified amount of refrigerant replenished?
Pitch and insulation work for drain piping properly done? Specified switch capacity and wiring diameter of main
power source used?
Proper grounding work done on outdoor unit? The phases of the L line (L1, L2, L3) correct?
Trouble
Not operate.
Not cool (at cooling). Not heat (at heating).
Not cool, not heat, error stop. Condensation drip in piping. Not cool, not heat, error stop.
Water leak, condensation drip in drain piping.
Error stop, not operate.
Electric shock. Error stop, not operate.
4
L line and N line connected correct?
Some electric parts should be damaged.
49
CENTRALLY CONTROLLED
D A I L Y
AUTO OFF
CHECK
STAND BY DEFROST
TEMP
2 31
PAR-F27MEA
TIMER SET
1Hr.
˚C
ON OFF
CLOCK
REMAINDER
˚C
ERROR CODE
ON OFF
CLOCK
NOT AVAILABLE
CHECK MODE
LIMIT TEMP.
ON/OFF
FILTER
TEST RUN
CHECK TEST
FILTER
PAR-F27MEA
STAND BY DEFROST
CENTRALLY CONTROLLED
D A I L Y
AUTO OFF
CHECK
TEMP
TIMER SET
1Hr.
˚C
ON OFF
CLOCK
REMAINDER
˚C
ERROR CODE
ON OFF
CLOCK
NOT AVAILABLE
ON/OFF
FILTER CHECK MODE TEST RUN LIMIT TEMP.
CHECK TEST
FILTER
Classification Transmission
line
System set
Portion Check item
1
Limitation of transmission line length followed? For example, 200m or less (total length : 500m) at the farthest.
2 1.25mm2 or more transmission line used?
2
(Remote controller 10m or less 0.75mm
)
3 2-core cable used for transmission line?
Transmission line apart from power source line by 5cm or more?
4
5 One refrigerant system per transmission line?
The short circuit connector is changed form CN41 to
6
CN40 on the MAIN board when the system is centralized control? (Just one outdoor unit. Not all outdoor units.)
7 • No connection trouble in transmission line? 8 Connection of wrong remote controller line terminals?
• MA Remote controller : TB15
• M-NET Remote controller : TB5 Address setting properly done? (M-NET Remote
1
controller, indoor unit and outdoor unit.) Setting of address No. done when shutting off power
2
source? Address numbers not duplicated?
3
Tur ned on SW3-8 on indoor unit circuit board when
4
mounting room thermistor sensor?
Trouble
Erroneous operation, error stop.
Erroneous operation, error stop.
Error stop in case multiple-core cable is used.
Erroneous operation, error stop. Not operate. Not operate.
Error stop or not operate. Never finish the initial mode.
Error stop or not operate.
Can not be properly set with power source turned on.
Not operate. Set temperature not obtained at
heating operations (Thermostat stop is difficult)
Before starting
Refrigerant piping ball valve (Liquid pressure pipe, gas
1
pressure pipe) opened?
2
Tur n on power source 12 hours before starting operations?
–50–
Error stop.
Error stop, compressor trouble.
[2] Test Run Method
Operation procedure
Turn on universal power supply at least 12 hours before getting started Displaying “HO” on display panel for
1
about two minutes
2 Press
3 Press selection button Make sure that air is blowing out
4
5 Press
6 Press
7 Make sure that indoor unit fans operate normally 8 Make sure that interlocking devices such as ventilator operate normally if any
9 Press
Note 1: If check code is displayed on remote controller or remote controller does not operate normally.
TEST RUN
Press warm or cold air is blowing out
or button to change wind Make sure that horizontal or downward blow is adjustable.
ON/OFF
2: Test run automatically stops operating after two hours by activation of timer set to two hours. 3: During test run, test run remaining time is displayed on time display section. 4: During test run, temperature of liquid pipe in indoor unit is displayed on remote controller room temperature
display section.
5: When pressing
controller. However, it is not a malfunction.
6: When pressing
remote controller. However, it is not a malfunction.
button twice Displaying “TEST RUN’’ on display panel
select button to change from cooling to heating operation, and vice versa Make sure that
adjust button Make sure that air blow is changed
button to cancel test run Stop operation
adjust button, depending on the model, NOT AVAILABLE” may be displayed on remote
or button, depending on the model, “NOT AVAILABLE may be displayed on
–51–
4
GROUPING REGISTRATION OF INDOOR UNITS WITH M-NET REMOTE CONTROLLER
(1) Switch function
• The switch operation to register with the remote controller is shown below:
1Hr
NOT AVAILABLE
˚C
ON/OFF
C Switch to assign
indoor unit address
F Delete switch G Registered mode
STAND BY DEFROST
CENTRALLY CONTROLLED
D A I L Y
AUTO OFF
CHECK
TEMP
˚C
ON OFF
CLOCK
REMAINDER
ERROR CODE
ON OFF
CLOCK
selector switch
E Confirmation switch
PAR-F27MEA
TIMER SET
H Switch to assign inter-
locked unit address
Name Name of actual switch Description
Registration/ordinary mode selection switch
Symbol
of switch
A + B
FILTER
+
This switch selects the ordinary mode or registered mode (ordinary mode represents that to operate indoor units). * To select the registered mode, press the
switch continuously for over 2 seconds under stopping state. [Note] The registered mode can not be obtained for a while after powering. Pressing the
FILTER
+
CONTROLLED”.
Switch to assign indoor unit address
C
of TEMP
This switch assigns the unit address for “INDOOR UNIT ADDRESS NO.
FILTER
CHECK MODE
TEST RUN
LIMIT TEMP.
FILTER
CHECK TEST
A
Registration/ ordinary mode selector switch
D Registration switch
B
Registration/ ordinary mode selector switch
FILTER
+
switch displays “CENTRALLY
Registration switch
Confirmation switch
Delete switch
Registered mode selector switch
Switch to assign interlocked unit address
D
TEST RUN
E
This switch is used for group/interlocked registration.
This switch is used to retrieve/identify the content of group and inter­locked (connection information) registered.
F
CLOCK → ON → OFF
G
This switch is used to retrieve/identify the content of group and inter­locked (connection information) registered.
This switch selects the case to register indoor units as group (group setting mode) or that as interlocked (interlocked setting mode). *The unit address is shown at one spot for the group setting mode while at two spots for the interlocked setting mode.
H
of TIMER SET
This switch assigns the unit address of OA UNIT ADDRESS NO.
–52–
(2) Attribute display of unit
At the group registration and the confirmation/deletion of registration/connection information, the type (attribute) of the unit is displayed with two English characters.
Display Type (Attribute) of unit/controller
Indoor unit connectable to remote controller Outdoor unit
Local remote controller System controller (MJ)
[Description of registration/deletion/retrieval]
The items of operation to be performed by the remote controller are given below. Please see the relating paragraph for detail.
1 Group registration of indoor unit
The group of the indoor units and operating remote controller is registered.
It is usually used for the group operation of indoor units with different refrigerant system.
2 Retrieval/identification of group registration information of indoor units
The address of the registered indoor units in group is retrieved (identified).
3 Retrieval/identification of registration information
The connection information of any unit (indoor/outdoor units, remote controller or the like) is retrieved (identified).
4 Deletion of group registration information of indoor units
The registration of the indoor units under group registration is released (deleted).
5 Deletion of the address not existing
This operation is to be conducted when 6607 error (No A CK error) is displa y ed on the remote controller caused b y the miss setting at test run, or due to the old memory remained at the alteration/modification of the group composi­tion.
Caution:
When MELANS (MJ-103MTRA for example) is being connected, do not conduct the group/pair registration using the remote controller. The group/pair registration should be conducted by MELANS. (For detail, refer to the instruc­tion exclusively prepared for MELANS.)
–53–
(3) Group registration of indoor unit
1) Registration method
Group registration of indoor unit ........................................................................ 1
The indoor unit to be controlled by a remote controller is registered on the remote controller.
[Registration procedure]
1 With the remote controller under stopping or at the display of “HO, continuously press the
(A + B) at the same time for 2 seconds to change to the registration mode. (See the figure below.)
2 Assign the indoor unit address to “INDOOR UNIT ADDRESS NO.” by operating the
adjustment) (C). Then press the
TEST RUN
switch (D) to register . In the figure below, the INDOOR UNIT ADDRESS NO .” is being set
to 001.
3 After completing the registration, press the
FILTER
+ switch (A + B) at the same time for 2 seconds to
change to the original ordinary mode (with the remote controller under stopping).
Ordinary mode
Remote controller under stopping HO under displaying
FILTER
+ switch
(Room temperature
˚C
INDOOR UNIT ADDRESS NO
Group setting mode
˚C
TEMP
PAR-F27MEA
TIMER SET
ERROR CODE OA UNIT ADDRESS NO
1
ERROR CODE OA UNIT ADDRESS NO
ON OFF
CLOCK
ON/OFF
CHECK TEST
FILTER
1
2 + 3
˚C
INDOOR UNIT
ERROR CODE
ADDRESS NO
OA UNIT ADDRESS NO
Registration complete
Indicates the type of unit (Indoor unit in this case)
˚C
ERROR CODE OA UNIT ADDRESS NO
Registration error
88 flickers indicating registra­tion error. (when the indoor unit registered is not existing)
˚C
ERROR CODE OA UNIT ADDRESS NO
2 Assign the
address (C)
System example
Remote controller
1 Change to the
registration mode (A + B)
Indoor units
3 Press the
registration switch (D)
Group
Confirm the indoor unit address No.
Confirm the connection of the transmission line.
54
2) Method of retrieval/confirmation
Retrieval/confirmation of group registration information on indoor unit............... 2
The address of the indoor unit being registered on the remote controller is displayed.
[Operation procedure]
1 With the remote controller under stopping or at the display of “HO, continuously press the
FILTER
+ B) at the same time for 2 seconds to change to the registration mode.
2 In order to confirm the indoor unit address already registered, press
switch (E). (See figure below.) When the group
of plural sets is registered, the addresses will be displayed in order at each pressing of switch (E).
3 After completing the registration, continuously press the
FILTER
+ switch (A + B) at the same time for 2
seconds to change to the original ordinary mode (with the remote controller under stopping).
Registered
+ switch (A
PAR-F27MEA
TEMP
TIMER SET
CLOCK
ON OFF
ON/OFF
CHECK TEST
FILTER
1
1
Indicates the type of unit (Indoor unit in this case)
No registration.
˚C
ERROR CODE OA UNIT ADDRESS NO
˚C
ERROR CODE OA UNIT ADDRESS NO
Note: Only one address will be displayed
1 Press the switch for confirmation (E)
Retrieval/confirmation of registration information ................................................ 3
The registered information on a certain unit (indoor unit, outdoor unit, remote controller or the like) is displayed.
[Operation procedure]
1 With the remote controller under stopping or at the display of “HO, continuously press the
+ B) at the same time for 2 seconds to change to the registration mode.
2 Operate
switch (G) for the interlocked setting mode. (See figure below.)
3 Assign the unit address of which registration information is desired to confirm with the (TIMER SET) switch
(H). Then press the
switch (E) to display it on the remote controller. (See figure below.)
Each pressing of switch (E) changes the display of registered content. (See figure below.)
4 After completing the retrieval/confirmation, continuously press the
FILTER
for 2 seconds to change to the original ordinary mode (with the remote controller under stopping).
when the registration is one even the switch is how often pressed
FILTER
+ switch (A
+ switch (A + B) at the same time
–55–
PAR-F27MEA
TEMP
TIMER SET
CLOCK
ON OFF
ON/OFF
CHECK TEST
FILTER
1 + 2
Registered
˚C
(Alternative
display)
˚C
˚C
(Alternative
display)
2
2 Press the switch for
confirmation (E)
1 Set the address
INDOOR UNIT ADDRESS NO
˚C
˚C
ERROR CODE OA UNIT ADDRESS NO
* Same display will appear when
No registration
the unit of “007” is not existing.
˚C
ERROR CODE
3) Method of deletion
Deletion of group registration information of indoor unit ...................................... 4
[Operation procedure]
1 With the remote controller under stopping or at the display of “HO, continuously press the
switch (A + B) at the same time for 2 seconds to change to the registration mode.
2 Press the switch (E) to display the indoor unit address registered. (As same as 2) 3 In order to delete the registered indoor unit being displayed on the remote controller, press the
two times continuously. At completion of the deletion, the attribute display section will be shown as “ – – “.
(See figure below.) Note: Completing the deletion of all indoor units registered on the remote controller returns to “HO” display.
4 After completing the registration, continuously press the
FILTER
+ switch (A + B) at the same time for 2
seconds to change to the original ordinary mode (with the remote controller under stopping).
OA UNIT ADDRESS NO
FILTER
CLOCK → ON → OFF
+
(F) switch
TEMP
ON OFF
CLOCK
PAR-F27MEA
TIMER SET
1 Press the switch for confirmation (F)
twice continuously.
ON/OFF
CHECK TEST
FILTER
1
In case group re­gistration with other indoor unit is existing
1
In case no group registration with other indoor unit is existing
56
Deletion completed
˚C
INDOOR UNIT ADDRESS NO
“– –” indicates the deletion completed.
Deletion completed
INDOOR UNIT ADDRESS NO
ERROR CODE OA UNIT ADDRESS NO
˚C
ERROR CODE OA UNIT ADDRESS NO
4) Deletion of information on address not existing
Deletion of information on address not existing................................................... 5
This operation is to be conducted when “6607” error (No ACK error) is displayed on the remote controller caused by the miss setting at test run, or due to the old memory remained at the alteration/modification of group composition, and the address not existing will be deleted. Note: The connection information (connection between indoor unit and outdoor unit) on the refrigerant system can
not be deleted. An example to delete the system controller of “250” from the indoor unit of “007” is shown below.
[Operation procedure]
1 With the remote controller under stopping or at the display of “HO, continuously press the
FILTER
+ switch (A
+ B) at the same time for 2 seconds to change to the registration mode.
2 Operate
switch (G) for the interlocked setting mode ( ii ). (See the figure below.)
3 Assign the unit address existing to “OA UNIT ADDRESS No. with the (TIMER SET) switch (H), and press
switch (E) to call the address to be deleted. (See the figure below .) As the error display on the remote controller is usually transmitted from the indoor unit, OA UNIT ADDRESS No. is used as the address of the indoor unit.
4 Press the 5 After completing the deletion, continuously press the
CLOCK → ON → OFF
switch (F) twice. (See the figure below.)
FILTER
+ switch (A + B) at the same time for 2 seconds
to return to the original ordinary mode (with the remote controller under stopping).
Deletion completed
When both indoor
INDOOR UNIT ADDRESS NO
˚C
ERROR CODE OA UNIT ADDRESS NO
(Alternative
display)
unit and interlocked unit addresses are existing
3
INDOOR UNIT ADDRESS NO
˚C
ERROR CODE OA UNIT ADDRESS NO
(Alternative
display)
INDOOR UNIT ADDRESS NO
PAR-F27MEA
2 Press the switch for
confirmation (E)
˚C
ERROR CODE OA UNIT ADDRESS NO
1 + 2
TEMP
ON OFF
CLOCK
TIMER SET
3 Press the deletion switch (F) twice
1 Set the address (H)
ON/OFF
CHECK TEST
FILTER
3
Deletion of address not existing
˚C
INDOOR UNIT ADDRESS NO
Deletion completed
˚C
INDOOR UNIT ADDRESS NO
INDOOR UNIT ADDRESS NO
(Alternative
˚C
ERROR CODE OA UNIT ADDRESS NO
*
ERROR CODE OA UNIT ADDRESS NO
display)
ERROR CODE OA UNIT ADDRESS NO
*
57
55
5 CONTROL
55
[1] Control of Outdoor Unit
(1) Initial processing
• When turning on power source, initial processing of microcomputer is given top priority.
• During initial processing, control processing corresponding to operation signal is suspended. The control process­ing is resumed after initial processing is completed. (Initial processing : Data processing in microcomputer and initial setting of each LEV opening, requiring approx. 2 minutes at the maximum.)
(2) Control at staring
• In case unit is started within 2 hours after turning on power source at low ambient temperature (+5˚C or less), the unit does not start operating for 30 minutes at the maximum.
(3) Bypass, capacity control
• Solenoid valve consists of bypass solenoid valve (SV1, SV2) bypassing between high pressure side and low pressure sider. The following operation will be provided.
1) Bypass solenoid valves SV1 and SV2 (both “open” when turned on)
• PU(H)Y-200·250YMF-C : Y
• PU(H)Y-P200·250YMF-C : Y-P
• PURY-200·250YMF-C : R2
• PURY-P200·250YMF-C : R2-P
Item
When starting compressor After thermost “ON is returned
and after 3 minutes restart When compressor stops in
cooling or heating mode After operation stops During defrosting operations During oil recovery opera-
tions
During 20Hz operations, at fall in low pressure or low pressure saturation tempera­ture. (3minutes or more after starting)
When high pressure rises (Pd)
When high pressure rises (Pd) during 20Hz operations (3 minutes after starting)
When discharge temperature rises (3 minutes after starting)
SV1
ON (Open) OFF (Close)
Turned on for 4 minutes Turned on for 4 minutes
Always turned on
Turned on for 3 minutes Always turned on Always turned on. Always turned on.
When Pd reaches
27.5kg/cm2G (2.70MPa) or more
When Pd is 24kg/cm2G (2.35MPa) or less 30 seconds
ON (Open) OFF (Close)
Turned on for 4 minutes Turned on for 4 minutes
When Ps is 1.5kg/ cm2G (0.15MPa) or less
When low TH2 is –30˚C or less
When Pd reaches
26.5kg/cm2G (2.60MPa) or more
When Pd reaches
25.5kg/cm2G (2.50MPa) or more
Turned on when high pressure (Pd) ex­ceeds pressure limit
When temp. exceeds 130˚C and Pb reaches 15kg/cm2G (1.47MPa) or more
SV2
– Always turned on. Always turned on.
When Ps is 2.5kg/ cm2G (0.25MPa) or more
When TH2 is –15˚C or more
When Pd is 23.5kg/ cm2G (2.30MPa) or less after 30 seconds
When Pd is 23kg/ cm2G (2.25MPa) or less after 30 seconds
When high pressure (Pd) is 20kg/cm2G (1.96MPa) or less
When discharge temp. is 115˚C or less
Object
Y Y-P R2 R2-P
❍❍❍❍ ❍❍❍❍
❍❍❍❍
❍❍❍❍ ❍❍❍❍
❍❍
❍❍❍
❍❍
❍❍❍❍
❍❍❍❍
❍❍
❍❍
Compressor
Bypass solenoid valve (SV1)
Start
(4-minute)
Thermo. OFF
Thermo. ON
(2-minute) (4-minute) (3-minute)
Defrost­ing time (*1)
Stop
–58–
(4) Frequency control
Depending on capacity required, capacity control change and frequency change are performed to keep constant evaporation temperature in cooling operations, and high pressure saturation temperature in heating operation.
Frequency change is perfprmed at the rate of 2Hz/second across 20 ~ 105Hz range.
1) Frequency control starting
60Hz is the upper limit for 3 minutes after starting.
75Hz is the upper limit within 30 minutes at the first starting compressor after turning on power source.
2) Pressure limit The upper limit of high pressure (Pd) is set for each frequency. When the limit is exceeded, frequency is reduced every 10 seconds. (Frequency decrease rate (Hz) : 22% of the present value)
<(P)200YMF-C> <(P)250YMF-C>
3) Discharge temperature limit Discharge temperature (Td) of compressor is detected during operation. If the upper limit is exceeded, the frequency is reduced. (Change rate : 5% of the present value)
30 seconds after starting compressor, control is performed every minute.
Operation temperature is 130˚C.
4) Periodical frequency control Frequency controll is periodically performed except for the frequency controls at operation start, status change, and protection.
1 Cycle of periodical frequency control
Periodical frequency control is performed every minute after the time specified below has passed.
20 sec after starting compressor or finishing defrostoing operations
20 sec after frequency control by discharge temperature or pressure limit
2 Amount of frequency change
The amount of frequency change is controlled corresponding to evaporation temperature and high pressure saturation temperature.
3-1 Back up of frequency control by bypass valve (PU(H)Y-200·250YMF-C)
During 20Hz operations, frequency is backed up by turning on (opening) bypass valve (SV2).
Cooling During 20Hz operations 3 minutes after starting compressor, bypass valve is turned on when TH2 is -30˚C or less, and turned off when TH2 is –15˚C or more.
Heating During 20Hz operations 3 minutes after starting compressor, SV2 turned on when high pressure (Pd) exceeds pressure limit and turned off when Pd falls to 20kg/cm
2
G (1.96MPa) or less.
ON OFF
30˚C 15˚C
59
ON OFF
20kg/cm2G 22kg/cm2G (1.96MPa) (2.16MPa)
3-2 Back up of frequency control by bypass valve (PUHY-P200·250YMF-B, PURY-(P)200·250YMF-C)
During 20Hz operations, frequency is backed up by turning on (opening) bypass valve (SV2).
Cooling During 20Hz operations 3 minutes after starting compressor, bypass valve is turned on when, Ps is 1.5kg/cm
2
G (0.15MPa) or less and turned off when Ps is 2.5kg/cm2G (0.25MPa) or more.
Heating During 20Hz operations 3 minutes after starting compressor, SV2 turned on when high pressure (Pd) exceeds pressure limit and turned off when Pd falls to 20kg/cm
ON
OFF
1.5kg/cm2G 2.5kg/cm2G (0.15MPa) (0.25MPa)
ON OFF
20kg/cm2G 27kg/cm2G (1.96MPa) (2.65MPa)
2
G (1.96MPa) or less.
(5) Oil return control (Electronic expansion valve <SLEV>)
Oil return LEV (SLEV) opening is dependent on compressor frequency and ambient temperature.
SLEV is closed (0) when compressor stops, and SLEV is set (64) for 10 minutes after starting compressor.
(6) Subcool coil control (electronic expansion valve <LEV1>) : PU(H)Y-200·250YMF-B, PUHY-P200·250YMF-C
The amount of super heat detected from the bypass outlet temperature of subcool coil (TH8) is controlled to be within a certain range for each 60 sec.
The opening angle is corrected and controlled depending on the outlet/inlet temperature of subcool coil (TH5, TH7) and the discharge temperature.
However, the valve will be closed (0) at heating and compressor stopping.
It will fully open at defrosting.
(7) Defrost operation control
1 PU(H)Y-(P)200·250YMF-C
1) Starting of defrost operations
After integrated 39 min : P-YMF-C, 43 min : YMF-C of compressor operations, defrosting operations start when – 4˚C
or less : P-YMF-C, –2˚C or less : YMF-C of piping temperature (TH5) is detected for 3 consecutive minutes.
Forcible defrosting operations start by turning on forcible defrost switch (SW2-7) if 3 minutes have already elapsed after compressor start or completion of defrosting operations.
2) Completion of defrosting operations Defrosting operations stop when 10 min : P-YMF-C, 15 min : YMF-C have passed since start of defrosting operation, or piping temperature (TH5) reaches 8˚C or more. (Defrosting operations do not stop for 2 minutes after starting, except when piping temperature exceeds 20˚C.)
3) Defrosting prohibition Defrosting operations do not start during oil recovery, and for 10 minutes after starting compressor.
4) Trouble during defrosting operations When trouble is detected during defrosting operations, the defrosting operations stop, and defrosting prohibition time decided by integrated operation time of compressor is set to be 20 minutes.
5) Change in number of operating indoor units during defrosting operations
In case number of operating indoor units changes during defrosting operations, the defrosting operations continue,
and control of unit number change is performed after the defrosting operations are finished.
Even in case all indoor units stop or thermostat is turned off during defrosting operations, the defrosting operations
do not stop until expected defrosting activities are completed.
–60–
2 PURY-(P)200·250YMF-C
1) Starting of defrost operations
• After integrated 43 minutes of compressor operations, defrosting operations start when –8˚C : P-YMF-C, –6˚C : YMF-C or less of piping temperature (TH7) is detected for 3 consecutive minutes.
Forcible defrosting operations start by turning on forcible defrost switch (SW2-7) if 3 minutes have already elapsed after compressor start or completion of defrosting operations.
2) Completion of defrosting operations Defrosting operations stop when 10 minutes have passed since start of defrosting operation, or piping temperature (TH5) reaches 8˚C or more. (Defrosting operations do not stop for 4 minutes after starting, except when piping temperature exceeds (TH5 and TH7) 20˚C and Pd >10kg/cm
3) Defrosting prohibition Defrosting operations do not start during oil recovery, and for 10 minutes after starting compressor.
4) Trouble during defrosting operations When trouble is detected during defrosting operations, the defrosting operations stop, and defrosting prohibition time decided by integrated operation time of compressor is set to be 20 minutes.
5) Change in number of operating indoor units during defrosting operations
In case number of operating indoor units changes during defrosting operations, the defrosting operations continue,
and control of unit number change is performed after the defrosting operations are finished.
Even in case all indoor units stop or thermostat is turned off during defrosting operations, the defrosting operations
do not stop until expected defrosting activities are completed.
2
G (0.98MPa).)
(8) Control of liquid level detecting heater
Detect refrigerant liquid level in accumulator, and heat refrigerant with liquid level heater for judging refrigerant amount. 6 steps of duty control is applied to liquid level heater depending on frequency and outdoor air temperature, 1minute after starting compressor.
(9) Judgement of refrigerant amount
Inlet
LD1 ON
LD1 OFF
LD2
Float
LD1
LD2 OFF AL=1 AL=0
Outlet
Oil return
AL=2
AL=1
AL=0
LD2 ON
AL=2
LD : Liquid level Detected Switch
–61–
(10) Refrigerant recovery control (PU(H)Y-(P)200·250YMF-C)
Refrigerant recovery is conducted to prevent refrigerant from accumulating in the stopped unit (fan unit), the unit under cooling mode and that with heating thermostat being turned off.
1) Start of refrigerant recovery 1 Refrigerant recovery is started when the two items below are fully satisfied.
15 minutes has passed after finishing refrigerant recovery.
The discharge temparature is high.
2) Refrigerant recovery operation
Refrigerant is recovered by opening LEV of the objective indoor units (indoor units under stop. fan, and cooling
modes, and that with heating thermostat being turned off) for 30 seconds.
LEV opening at refrigerant recovery (Indoor unit LEV opening 500 pulse)
LEV opening before change
Starts
30 seconds
Finish
The regular capacity control of the outdoor unit and the regular LEV control of the indoor unit are not applied
during refrigerant recovery operation, but are fixed with the value before the recovery operation. These controls will be conducted one minute after finishing the recovery operation.
Defrosting operation is prohibited during the recovery operation, and it will be conducted after finishing the recov-
ery operation.
(11) Control of outdoor unit fan and outdoor unit heat exchanger capacity
1 PU(H)Y-200·250YMF-C
1) Control system Depending on capacity required, control outdoor fan flow rate with phase control, for maintaining evaporation temperature (0˚C when Pd
15kg/cm2G (1.47MPa), lower than 0˚C when Pd < 15kg/cm2G (1.47MPa) in cooling
operations, and high pressure 18kg/cm2G (1.76MPa) in heating operations.
2) Control
Outdoor unit fan stops when compressor stops.
Fan is in full operation for 5 seconds after starting.
Outdoor unit fan stops during defrosting operations.
2 PUHY-P200·250YMF-B, PURY-(P)200·250YMF-C
1) Control system Depending on capacity required, control outdoor fan flow rate with phase control, for maintaining evaporation temperature (0˚C) in cooling operations, and high pressure saturated temperature (49˚C) in heating operations.
2) Control
Outdoor unit fan stops when compressor stops.
Fan is in full operation for 5 seconds after starting.
Outdoor unit fan stops during defrosting operations.
62
[2] Control of BC Controller
(1) Control of SVA, SVB and SVC
SVA, SVB and SVC are turned on and off depending on connection mode.
Mode
Connection
SVA ON OFF OFF OFF SVB OFF ON OFF OFF
SVC ON OFF OFF OFF
(2) Control of SVM
SVM is turned on and off corresponding to operation mode.
Operation mode Cooling-only Cooling-main Heating-only Heating-main Stop
SVM ON OFF OFF OFF OFF
(3) Control of LEV
LEV opening (sj) is controlled corresponding to operation mode as follows: (Number of pulse)
Operation mode Cooling-only Heating-only Cooling-main Heating-main Stop
LEV1
LEV3
Cooling Heating Stop Defrost
* SVM is not built in depending on models.
2000
Superheat
control *1
60
Differential
Pressure control
*2
Liquid level control *3
Differential pressure control
*2
60
Differential
Pressure control
*2
2000
60
Superheat
*1
control
Differential
*2
pressure control
*3
* Please confirm that the above parts of BC controllers are being color-corded and shown with the name plate inside
the BC controller unit.
Control every minute so that superheat amount detected by bypass inlet and oulet temperatures (TH12, TH15) stay in the specified range.
Control every minute so that detected differential pressure (PS1, PS3) stay in the specified range.
60 or more pulses are sometimes detected because of rise in liquid side pressure (PS1).
–63–
[3] Operation Flow Chart
(1) Outdoor unit
Start
HO blinks on the remote
controller
Oil return LEV, SC coil LEV
(PUHY) fully closed
1. 52C OFF
2. Inverter output 0Hz
3. Outdoor fan Stop
4. All solenoid valve OFF
NO
Fan
dress No. to remote
NO
Breaker
turned on
YES
Set indoor ad-
controller
YES
Operation command
YES
Operation
mode
Error mode
NO
NO
Normal operations Trouble observed Stop
Note : 1
Cooling-only, Heating-only, Cooling/heating mixed
Note : 2
YES
Error stop
52C ON
Note : 3
Operation
mode
Cooling (Cooling-
only) operations
Note : 1 For about 3 minutes after turning on power source, address and group information of outdoor unit, BC, controller indoor unit,
Note : 2 T w o trouble modes included indoor unit side troub le, (BC controller trouble) and outdoor unit side troub le. In the case of indoor
Note : 3 On PUHY system, operation mode conforms to mode command by indoor unit. However, when outdoor unit is being under
Note : 4 In case BC controller issues cooling/heating mixed operation mode, outdoor unit decides operation mode of cooling-main
and remote controller are retrieved by remote controller, during which “HO” blinks on and off on remote controller. In case indoor unit is not grouped to remote controller, “HO” display on remote controller continues blinking even after 3 minutes after turning on power source.
unit side trouble, error stop is observed in outdoor unit only when all the indoor units are in trouble. However, if one or more indoor units are operating normally, outdoor unit shows only LED display without undergoing stop.
cooling operation, the operation of indoor unit will be prohibited even b y setting a part of indoor units under operation, or indoor unit under stopping or fan mode to heating mode. Re versely when outdoor unit is being heating oper ation, the same condition will be commenced. On PURY system, operation mode conforms to mode command by BC controller.
operation or heating-main operation.
Heating (Heating-
only) operations
Operation mode command to (BC controller) outdoor unit
Cooling/heating mixed (only for PURY)
Note : 4
Operation
mode
Cooling-main
operations
Heating-main
operations
Error code blinks on the outdoor controller board
Error command to
BC controller
Error code blinks on the
remote controller
–64–
(2) BC controller (for PURY)
Start
Breaker
turned on
YES
Operation
NO
1.Operation mode judgement
2.Transmission to outdoor unit
Receiving operation mode
command from outdoor unit
command
YES
(cooling-only, heating-only, cooling/heating mixed)
Note : 1
Error mode
YES
NO
Normal operations Trouble observed Stop
NO
Fan
Solenoid valve OFF,
LEV fully closed.
Cooling-only
operations
Note : 1 Two error modes include indoor unit side trouble, BC controller trouble, and outdoor unit side trouble. In the case of indoor
unit side trouble, error stop is observed in the concerned indoor unit only, and in the cases of BC controller and outdoor unit side troubles, error stop is observed in all the indoor units, BC controller, and outdoor unit.
Operation mode
Operation mode
Heating-only
operations
Cooling/heating mixed
Operation mode
Cooling-main
operations
Heating-main
operations
Error stop
Error code blinks on the outdoor controller board
Error command to
BC controller
Error code blinks on the
remote controller
–65–
(3) Indoor unit
Start
Breaker
turned on
YES
NO
Normal operations Trouble observed Stop
YES
3-minute drain
pupm ON
Operation SW
turned on
NO
1. Protection function self-holding cancelled.
2. Indoor unit LEV fully closed.
Remove controller display extinguished
FAN stop
Drain pump
ON
NO
YES
Note :1
Note :2
Error mode
YES
Error stop
Error code blinks on the remote controller
Error command to outdoor unit
Indoor unit LEV fully closed
Note :1
Error code blinks on the outdoor controller board
NO
Cooling mode
Cooling
display
Prohibition Prohibition
Heating
mode
Heating
display
YES
NO
Cooling operations
Heating operations
Operation mode
YES
NO
Dry operation
Prohibition Remote controller blinking
only for PURY
Dry mode
Dry display
Cooling/heating automatic mode
Cooling/heating automatic display
Note :3Note :3 Note :3
NO
YES
NO
Cooling/heating automatic operations
Prohibition Prohibition
Fan mode
Fan display
YES
Fan operations
Note : 1 Indoor unit LEV fully closed : Opening 60 Note : 2 Two error modes include indoor unit trouble, (BC controller trouble) and outdoor unit side trouble. In the case of indoor unit
trouble, error stop is observed in the concerned indoor unit only, and in the cases of (BC controller and) outdoor unit side troubles, error stop is observed in all the indoor units connected.
Note : 3 “Prohibition” status is observed (when several indoor units are connected to one connection, of BC controller and) when
connection mode is different from indoor unit operation mode. (Operation mode display on the remote controller blinks on and off, fan stops, and indoor unit LEV is fully closed.)
–66–
(4) Cooling operation
Cooling operation
NO
YES
4-way valve OFF
Indoor unit fan
operations
Test run start
NO
Thermostat ON
YES
3-minute
restart
prevention
NO
Normal operations Test run Stop
YES
1.Inverter output 0Hz
2.Indoor unit LEV, oil return LEV, Subcool coil bypass LEV fully closed
3.Solenoid valve OFF
4.Outdoor unit fan stop
5.BC controller solenoid valve OFF (PURY)
6.BC controller LEV fully closed (PURY)
1.Inverter frequency control
2.Indoor unit LEV, oil return LEV control
3.Solenoid valve control
4.Outdoor unit fan control
5.BC controller solenoid valve control (PURY)
6.BC controller LEV control (PURY)
–67–
(5) Heating operation
Heating operation
4-way valve ON
NO
Thermostat ON
YES
Note : 1 Note : 2
Defrosting
operation
NO
Test run start
NO
YES
3-minute
restart
prevention
Normal operations Defrosting operations Stop Test run
YES
4-way valve OFF
YES
1.Indoor unit fan stop
2.Inverter defrost frequency control
3.Indoor unit LEV fully opened, oil return LEV fully closed
4.Solenoid valve control
5.Outdoor unit fan stop
6.BC controller solenoid valve control (PURY)
7.BC controller LEV control (PURY)
NO
1.Indoor unit fan very low speed operations
2.Inverter output 0Hz
3.Indoor unit LEV, oil return LEV fully closed
4.Solenoid valve OFF
5.Outdoor unit fan stop
6.BC controller solenoid valve OFF (PURY)
7.BC controller LEV fully closed (PURY)
Note : 1 When outdoor unit starts defrosting, it transmits defrost operations command to (BC controller and) indoor unit, and the
Note : 2 1 PUHY-(P)200·250YMF-C
indoor unit starts defrosting operations. Similarly when defrosting operation stops, indoor unit returns to heating operation after receiving defrost end command of outdoor unit.
Defrosting start condition : After integrated 39 minutes : P-YMF-C, 43 minutes : YMF-C of compressor operations, Defrosting end condition : After 10 minutes : P-YMF-C, 15 minutes : YMF-C of defrosting operation or the outdoor unit
2 PURY-(P)200·250YMF-C
Defrosting start condition : After integrated 43 minutes of compressor operations, and –8˚C:P-YMF-C, –6˚C:YMF-C or Defrosting end condition : After 15 minutes of defrosting operation or the outdoor unit coil temperature (TH5 and TH7)
1.Indoor and outdoor unit fan control
2.Inverter frequency control
3.Indoor unit LEV, oil return LEV control
4.Solenoid valve control
5.BC controller solenoid valve control (PURY)
6.BC controller LEV control (PURY)
and – 4˚C : P-YMF-C, –2˚C : YMF-C or less outdoor unit coil temperature. coil temperature having risen to 8˚C or more.
less outdoor unit coil temperature. (TH7) having risen to 8˚C or more.
–68–
(6) Dry operation
Dry operations
4-way valve OFF
Normal operations Thermostat ON Stop
1.Indoor unit fan stop
2.Inverter output 0Hz
3.Indoor unit LEV, oil return LEV closed
4.Solenoid valve OFF
5.Outdoor unit fan stop
6.BC controller solenoid valve OFF (PURY)
7.BC controller LEV fully closed (PURY)
Test run start
NO
NO
Inlet temp. 18˚C
YES
1.Outdoor unit (Compressor) intermit­tent operations
2.Indoor unit fan intermittent opera­tions
YES
(Synchronized with compressor : low speed, OFF operations)
YES
Note : 1
Note : 2
Thermostat ON
Note : 1 When indoor unit inlet temperature exceeds 18˚C, outdoor unit (compressor) and indoor unit fan start intermittent operations
Note : 2 Thermostat is always kept on in test run, and indoor and outdoor unit intermittent operation (ON) time is a little longer than
synchronously. Operations of outdoor unit, BC controller (PURY), indoor unit LEV and solenoid valve accompanying compressor are the same as those in cooling operations.
normal operations.
–69–
[4] List of Major Component Functions
Name Application Specification Check method Object
Compres­sor
High pressure sensor
Low pressure sensor
Pressure switch
Symbol
(function)
MC
63HS
63LS
63H
Adjust refrigerant circulation by controlling operating frequency and capacity control valve with operating pressure.
1) High press. detection.
2) Frequency control and high pressure protection
1) Detects low pressure
2) Calculates the refrigerant circula­tion configuration.
3) Protects the low pressure
1) High pressure detection
2) High pressure protection
Low pressure shell scroll type with capacity control mechanism Winding resistance: Each phase 0.388 (20˚C)
Pressure
Con­nector
Con­nector
63HS
63LS
0~30 kg/cm (0~2.94MPa) Vout 0.5~3.5 V
Gnd (black) Vout (white) Vc (DC5V) (red)
Pressure 0~10 kg/cm (0~0.98MPa) Vout 0.5~3.5 V
Gnd (black) Vout (white) Vc (DC5V) (red)
2
G
2
G
Setting 30kg/cm2G (2.94MPa) OFF
Continuity check
• PU(H)Y­(P)200·250YMF-C
• PURY­(P)200·250YMF-C
• PU(H)Y­P200·250YMF-C
• PURY­(P)200·250YMF-C
• PU(H)Y­(P)200·250YMF-C
• PURY-
Thermistor
TH1 (discharge)
1) Discharge temperature detection
2) High pressure protection 20˚C :250k 70˚C : 34k
30˚C : 160k 80˚C : 24kΩ 40˚C : 104k 90˚C : 17.5kΩ
R120=7.465k B25/120=4057
Rt = 7.465exp {4057( - )}
1
273+t
1
273+120
Resistance value check
(P)200·250YMF-C
50˚C : 70k 100˚C : 13.0kΩ 60˚C : 48k 110˚C : 9.8kΩ
Outdoor unit
TH2 (low pressure saturation temperature)
TH5 (piping temperature)
TH6 (outdoor air tempera­ture)
TH7 (subcool coil outlet temperature)
TH8 (subcool coil bypass outlet temperature)
1) Detects the saturated vapor temperature.
2) Calculates the refrigerant circula­tion configuration.
3) Controls the compressor fre­quency.
4) Controls the outdoor unit’s fan air volume.
1) Frequency control
2) Defrost control and liquid level detection at heating
1) Outdoor air temperature detection
2) Fan control, liquid level heater, and opening setting for oil return
Subcool coil bypass LEV (LEV1) control
Subcool coil bypass LEV (LEV1) control
R0=33k B0/100=3965 Rt = 33exp{3965( - )}
1
273+t
1
273+0
-20˚C : 92k
-10˚C : 55k 0˚C : 33k 10˚C : 20k 20˚C : 13k 30˚C : 8.2k
R0=15k B0/100=3460 Rt = 15exp{3460( - )}
1
273+t
1
273+0
0˚C : 15k 10˚C : 9.7k 20˚C : 6.4k 25˚C : 5.3k 30˚C : 4.3k 40˚C : 3.1k
Resistance value check
• PU(H)Y­(P)200·250YMF-C
• PURY­P200·250YMF-C
• PU(H)Y­(P)200·250YMF-C
• PURY­(P)200·250YMF-C
• PU(H)Y­(P)200·250YMF-C
TH9
1) Detects the CS circuit fluid temperature.
2) Calculates the refrigerant circulation configuration.
• PU(H)Y­P200·250YMF-C
• PURY­P200·250YMF-C
–70–
Name Application Specification Check method Object
Thermistor
Symbol
(function)
TH10 (P-YMF-C only)
1) Detects the compressor shell temperature.
2) Provides compressor shell overheating protection.
R120=7.465k B25/120=4057 Rt =
7.465exp {4057( - )}
1
273+t
1
273+120
PU(H)Y­P200·250 YMF-C
PURY­P200·250 YMF-C
20˚C : 250k 70˚C : 34k 30˚C : 160k 80˚C : 24k 40˚C : 104k 90˚C : 17.5k 50˚C : 70k 100˚C : 13.0k 60˚C : 48k 110˚C : 9.8k
Solenoid valve
Outdoor unit
Linear expansion valve
Liquid level detection switch
Linear expansion valve
THHS
SV1 (discharge ­suction bypass)
SV2 (discharge ­suction
bypass) SV3 ~ 5
SV3 ~ 6
SLEV
LEV1 (SC coil)
LD1 LD2
LEV
1) Detects the inverter cooling fin temperature.
2) Provides inverter overheating protection.
3) Controls the control box cooling fan.
1) High/low press. bypass at starting/ stopping and capacity control at low load
2) Discharge press. rise suppression
Capacity control and high press. rise suppression (backup for frequency control)
Control of heat exchanger capacity.
Control of heat exchanger capacity.
Adjustment of liquid refrigerant (oil) return foam accumulator
Adjustment bypass flow rate from outdoor unit liquid line at cooling.
Detection of refrigerant liquid level in accumulator
1) Adjust superheat of outdoor unit heat exchanger outlet at cooling.
2) Adjust subcool of indoor unit heat exchanger at heating.
R50=17k B25/50=4170 Rt = 17exp{4170( - )}
273+t
1
1
273+50
-20˚C : 605.0k50˚C : 17.0k
-10˚C : 323.3k60˚C : 11.5k 0˚C : 180.9k70˚C : 8.0k 10˚C : 105.4k80˚C : 5.7k 20˚C : 63.8k90˚C : 4.1k 30˚C : 39.9k100˚C : 3.0k 40˚C : 25.7k
AC 220~240V Open at energizing and close at deenergizing
DC12V stepping motor drive Valve opening 0~480 pulse
LD2 LD1
5.1k
243
5.1k
CN05
DC12V Opening of stepping motor driving valve 60~2,000 pulses
Continuity check by tester
Temperature of inlet and outlet.
Resistance value check
Continuity check with tester for white-red-orange yellow-brown-blue
PU(H)Y­(P)200·250 YMF-C
PURY­(P)200·250 YMF-C
PU(H)Y­P200·250YMF-C
PURY­(P)200·250YMF-C
PU(H)Y­(P)200·250YMF-C
PURY­(P)200·250YMF-C
PU(H)Y­(P)200·250YMF-C
PU(H)Y­(P)200·250YMF-C
PURY­(P)200·250YMF-C
Thermistor
Indoor unit
TH21 (inlet air temperature)
TH22 (piping temperature)
TH23 (gas side piping temperature)
Indoor unit control (thermostat)
1) Indoor unit control (freeze prevention, hot adjust, etc.)
2) LEV control in heating operation (Subcool detection)
LEV control in cooling operation (Superheat detector)
–71–
R0 = 15k B0/100 = 3460
Rt = 15exp {3460 ( - )}
1
273+t
1
273+0
0°C : 15k 10°C : 9.7k 20°C : 6.4k 25°C : 5.3k 30°C : 4.3k 40°C : 3.1k
Resistance value check
Name Application Specification Check method Object
Pressure sensor
Symbol
(function)
PS1
PS3
1) Liquid pressure (high-pressure) detection
2) LEV control
1) Intermediate pressure detection
2) LEV control
Con­nector
PS1 PS3
Pressure 0~30 kg/cm (0~2.94MPa) Vout 0.5~3.5 V
Gnd (black) Vout (white) Vc (DC5V) (red)
2
G
Thermistor
BC controller
Solenoid valve
Electronic expansion valve
TH11 (liquid inlet temperature)
TH12 (bypass outlet pressure)
TH15 (bypass outlet temperature)
TH16 (bypass inlet temperature)
SVM *1 SVA
SVB
SVC
LEV1
LEV3
LEV control (liquid refrigerant control)
LEV control (superheat control)
LEV control (superheat control)
LEV control (subcool control)
Opens for cooling-only, defrosting. Supplies refrigerant to cooling indoor
unit. Supplies refrigerant to heating indoor
unit. Supplies refrigerant to cooling indoor
unit. Liquid level control
pressure control Liquid level control
pressure control
R0=15k B0/100=3460 Rt = 15exp{3460( - )}
1
273+t
1
273+0
0˚C : 15k 10˚C :9.7k 20˚C :6.4k 25˚C :5.3k 30˚C :4.3k 40˚C :3.1k
AC 220~240V Open when energized Closed when de-energized
12V DC stepping motor drive 0 to 2000 valve opening pulse
Continuity check by a tester
Same as LEV of indoor unit.
*1. SVM is not built in depending on models.
–72–
[5] Resistance of Temperature Sensor
Thermistor for low temperature Thermistor Ro= 15kΩ ± 3% (TH3 ~ 9) Thermistor R120 = 7.465kΩ ± 2% (TH1, 10)
t = 15exp {3460 ( - )} Rt = 7.465exp {4057 ( - )}
R
1
273+t
1
273+0
1
273+t
273+120
1
50
40
30
20
Resistance (kΩ)
10
0
–20 –10 10 20 30 40 500
25
20
15
10
Resistance (kΩ)
5
0
90 100 110 120
Temperature (˚C) Temperature (˚C)
Thermistor R Rt = 33exp {3965 ( - )} Rt = 17exp {4170 ( - )}
o = 33kΩ ± 1% (TH2) Thermistor R50 = 17kΩ ± 2% (THHS)
1
273+t
1
273+0
1
273+t
1
273+50
Resistance (kΩ)
Resistance (kΩ)
Temperature (˚C) Temperature (˚C)
–73–
66
6 REFRIGERANT AMOUNT ADJUSTMENT
66
Clarify relationship between the refrigerant amount and operating characteristics of CITY MULTI, and perform service activities such as decision and adjustment of refrigerant amount on the market.
[1] Refrigerant Amount and Operating Characteristics
The followings are refrigerant amount and operating characteristics which draw special attention.
During cooling operations, required refrigerant amount tends to increase (refrigerant in accumulator decreases)
1
in proportion to increase in the number of operating indoor units. However, the change of increase rate is small.
During heating operations, liquid level of accumulator is the highest when all the indoor units are operating.
2
Discharge temperature hardly changes when increasing or decreasing refrigerant amount with accumulator
3
filled with refrigerant.
During cooling operations, discharge temperature tends to rise at overload than low temperature.
Tendency of
4
discharge temperature
During heating operations, discharge temperature tends to rise at low temperature than overload.
The lower operating frequency is, the higher discharge temperature tends to become of deteriorated compressor efficiency.
Comparison including control system
Compressor shell temperature is 20~70 degrees higher than low pressure saturation temperature (Te) when refrigerant amount is appropriate.
5
Judged as over replenishment when temperature difference from low pressure saturation temperature (Te) is 10 degrees or less.
[2] Adjustment and Judgement of Refrigerant Amount
(1) Symptom
The symptoms shown in the table below are the signs of excess or lack of refrigerant amount. Be sure to adjust refrigerant amount in refrigerant amount adjustment mode, by checking operation status, judging refrigerant amount, and performing selfdiagnosis with LED, for overall judgement of excess or lack of refrigerant amount.
Emergency stop at 1500 remote controller display (excessive
1
refrigerant replenishment) Operating frequency does not fully increase, thus resulting in
2
insufficient capacity Emergency stop at 1102 remote controller display (discharge
3
temperature trouble) Emergency stop occurs when the remote control display is at
4
1501. (insufficient refrigerant)
Excessive refrigerant replenishment
Insufficient refrigerant replenishment
Insufficient refrigerant
–74–
for PU(H)Y-(P)200·250YMF-C
(2) Refrigerant Volume Adjustment Operation (PU(H)Y-(P)200·250YMF-C)
1) Operating Characteristics Refrigerant Volume Characteristic items related to operating characteristics and the refrigerant volume are shown below.
If the number of indoor units in operation increases during cooling, the required volume of refrigerant tends to
1
increase (the amount of refrigerant in the accumulator tends to decrease), but the change is minimal. The liquid level in the accumulator is at its highest when all the indoor units are operating during heating.
2
If there is refrigerant in the accumulator, even if the volume of refrigerant is increased or decreased, there is practi-
3
cally no change in the outlet temperature.
During cooling, the discharge temperature rises more easily when there is an overload than when the temperature is low.
Tendency of
4
discharge Temperature
5
The compressor shell temperature becomes 20~70 deg. higher than the low pressure saturation temperature (TH2) if the refrigerant volume is appropriate. If the difference with the low pressure saturation temper ature (TH2) is 10 deg. or less, it can be judged that the refrigerant is overcharged.
During heating, the discharge temperature rises more easily when the tempera­ture is low than when there is an overload.
The lower the operating frequency, the less efficient the compressor is, making it easier for the discharge temperature to rise.
Comparison when control is included.
2) Adjusting and Judging the Refrigerant Volume
1 Symptoms
Overcharging with refrigerant can be considered as the cause of the following symptoms. When adjusting the refrigerant volume, be sure that the unit is in the operating condition, and carry out refrigerant volume judgment and self-diagnosis by the LEDs, judging overall whether the volume of refrigerant is in excess or is insufficient. Perform adjustments by running the unit in the refrigerant volume adjustment mode.
Emergency stop occurs when the remote control display is at 1500 (refrigerant
1
overcharge).
2
The operating frequency doesnt rise high enough and capacity is not achieved. Emergency stop occurs when the remote control display is at 1102 (outlet
3
temperature overheating). Emergency stop occurs when the remote control display is at 1501 (insufficient
4
refrigerant).
2 Refrigerant Volume a Checking the Operating Condition
Operate all the indoor units on cooling or on heating, checking the discharge temperature, sub-cooling, low pres­sure saturation temperature, inlet temperature, shell bottom temperature, liquid level, liquid step, etc. and rendering an overall judgment.
Refrigerant overcharge
Insufficient refrigerant
Insufficient refrigerant
Condition 1 Outlet temperature is high. (125°C or higher) 2 Low pressure saturation temperature is extremely low. 3 Inlet superheating is high (if normal, SH = 20 deg or lower). 4 Shell bottom temperature is high (the difference with the low pressure saturation
temperature is 70 deg. or greater)
5 Shell temperature is low (the difference with the low pressure saturation tem-
perature is 10 deg. or lower).
6 Dischange superheating is low (if normal, SH = 20 deg or higher).
–75–
Judgement
Refrigerant volume tends toward insufficient.
Rifrigerant volume tends toward overcharge.
for PU(H)Y-(P)200·250YMF-C
b Check the refrigerant volume by self-diagnosis using the LED.
Set the self-diagnosis switch (SW1) as shown below and check the past information (history) concerning the refrigerant volume.
1234567 8910
Set SW1 as shown in he figure at right.
ON
If LD8 lights up, it indicates the refrigerant charge abnormal delay state just before emergency stop due to refriger­ant overcharge (1500).
3 Additional Refrigerant Charge Volume
At the time of shipping from the factory, the outdoor unit is charged with the amount of coolant shown in the follow­ing table, but since no extension piping is included, please carry out additional charging on-site.
Outdoor Unit Model Name PU(H)Y-200YMF-C PU(H)Y-P200YMF-C PU(H)Y-250YMF-C
PU(H)Y-P250YMF-C
Refrigerant Charge Volume 6.5kg 7.0kg 8.0kg 8.5kg
Calculation Formula Calculate the additional refrigerant volume by calculating the size of the extension liquid piping and its length (units: m).
Additional Refrigerant Volume (kg) = (0.12 × L
1) + (0.06 × L2) + (0.024 × L3) + α
L
1: Length of ø12.7 liquid pipe (m)
L2: Length of ø9.52 liquid pipe (m) L
3: Length of ø6.35 liquid pipe (m)
α: refer to the calculation table.
In the calculation results, round up fractions smaller than 0.01 kg. (Example: 18.54 kg 18.6 kg)
(α Calculation Table)
Total Capacity of
Connected Indoor Units
α
~90 1.0 kg
91~180 1.5
181~370 2.0
Caution : (PUHY-P200·250YMF-C)
When charging with refrigerant, be sure to charge from the liquid side. If charging from the gas side, it will cause the refrigerant composition to change inside the unit and the composition of the refrigerant remaining in the canister will also change.
–76–
for PU(H)Y-(P)200·250YMF-C
3) Refrigerant Volume Adjustment Mode Operation 1 Procedure
Depending on the operating conditions, it may be necessary either to charge with supplementary refrigerant, or to drain out some, but if such a case arises, please follow the procedure given below flow chart.
Notes 1 As the refrigerant volume can not be adjusted in the heating mode, retrieve the refrigerant, evacu-
ate air and then fill the specified volume of refrigerant if it is necessary to adjust the refrigerant volume in the winter season.
Notes 2 A refrigerant volume adjustment performed in the cooling mode must be done with a gauge reading of 13 kg/cm2G or
higher. If the pressure does not reach refrigerant cannot be collected halfway. Therefore, collect used refrigerant and evacuate the unit completely, and then fill new refrigerant up to a specified quantity.
Notes 3 Judgment by the AL is at best only a rough guideline. Please do not add refrigerant based on the
AL reading alone. (Be sure to obtain calculations of the correct amount before adding refrigerant.)
Notes 4 When supplementing the refrigerant volume, please be careful to charge with liquid refrigerant.
TH1 Self-diagnosis Switch TH5 Self-diagnosis Switch Pd (High pressure)
12345678910
ON
TH7 Self-diagnosis Switch Tc Self-diagnosis Switch
12345678910
ON
12345678910
ON
12345678910
ON
12345678910
ON
Using these, judge TH1, Tc - TH5 and Tc - TH7.
–77–
In case of PUHY-200, 250YMF-C
for PU(H)Y-(P)200·250YMF-C
Adjustment starts.
Start cooling operation of all indoor units in a test run mode. Note 1
Has the
compressor been
operated for more than
30min?
Was the operation condition stabilized?
The high pressure > 13kg/cm2G?
*Operate for 5 minutes after adjusting the refrigerant and make a judgement.
TH1 115˚C?
3 TH8-TH2 13deg?
Fill refrigerant little by little from the low-pressure side service port.
YES
NO
Note 1) As the refrigerant volume can not be adjusted in the heating mode,
retrieve the refrigerant, evacuate air and then fill the specified volume of refrigerant if it is necessary to adjust the refrigerant volume in the winter season.
Is the
thermostat turned
on/off in order for the indoor
unit to prevent from
frosting?
Stop the refrigerant volume adjustment and retrieve the refrigerant. After evacuating air, fill the specified volume of refrigerant.
Are all indoor units SHs more than 2deg?
3deg Tc-TH5 10deg?
Tc-TH7 > 15deg?
TH1-Tc > 25deg?
Is the LEV opening
degree stable when SH
< 2deg?
*Operate for 5 minutes after adjusting the refrigerant and make a judgement.
Tc-TH5 < 3deg?
TH8-TH2>13deg?
Retrieve the refrigerant little by little from the low-pressure side service port.
Fill refrigerant little by little from the low-pressure side service port.
Fill refrigerant little by little from the low-pressure side service port.
Retrieve the refrigerant little by little from the low-pressure side service port.
Fill refrigerant little by little from the low-pressure side service port.
*Operate for 5 minutes after adjusting the
refrigerant and make a judgement.
*Operate for 5 minutes after adjusting the
refrigerant and make a judgement.
*Operate for 5
minutes after adjusting the refrigerant and make a judgement.
TH1 110˚C?
Fill refrigerant little by little from the low-pressure side service port.
*Operate for 5 minutes after adjusting the
refrigerant and make a judgement.
Adjustment completed.
Caution :
Do not let the drained out refrigerant escape to the outside atmosphere.
Always be sure to charge with refrigerant from the liquid phase side. (PUHY-P200·250YMF-C)
78
In case of PUHY-P200, 250YMF-C
for PU(H)Y-(P)200·250YMF-C
Adjustment starts.
Start cooling operation of all indoor units in a test run mode. Note 1
Has the
compressor been
operated for more than
30min?
Was the operation condition stabilized?
The high pressure > 13kg/cm2G?
*Operate for 5 minutes after adjusting the refrigerant and make a judgement.
TH1 115˚C?
7 TH8-TH2 17deg?
Fill refrigerant little by little from the low-pressure side service port.
YES NO
Note 1)As the refrigerant volume can not be adjusted in the heating mode,
retrieve the refrigerant, evacuate air and then fill the specified volume of refrigerant if it is necessary to adjust the refrigerant volume in the winter season.
Is the
thermostat turned
on/off in order for the indoor
unit to prevent from
frosting?
Stop the refrigerant volume adjustment and retrieve the refrigerant. After evacuating air, fill the specified volume of refrigerant.
Are all indoor units SHs more than 6deg?
3deg Tc-TH5 10deg?
Tc-TH7 > 15deg?
TH1-Tc > 25deg?
Is the LEV opening
degree stable when SH
< 6deg?
*Operate for 5 minutes after adjusting the refrigerant and make a judgement.
Tc-TH5 < 3deg?
TH8-TH2>17deg?
Retrieve the refrigerant little by little from the low-pressure side service port.
Fill refrigerant little by little from the low-pressure side service port.
Fill refrigerant little by little from the low-pressure side service port.
Retrieve the refrigerant little by little from the low-pressure side service port.
Fill refrigerant little by little from the low-pressure side service port.
*Operate for 5 minutes after adjusting the
refrigerant and make a judgement.
*Operate for 5 minutes after adjusting the
refrigerant and make a judgement.
*Operate for 5
minutes after adjusting the refrigerant and make a judgement.
TH1 110˚C?
Fill refrigerant little by little from the low-pressure side service port.
*Operate for 5 minutes after adjusting the
refrigerant and make a judgement.
Adjustment completed.
Caution: (PUHY-P200·250YMF-C)
Always be sure to charge with refrigerant from the liquid phase side.
–79–
for PU(H)Y-(P)200·250YMF-C
(3) Refrigerant Amount Adjustment Mode Operations (PURY-(P)200·250YMF-C)
1 Procedure
Depending on the operating conditions, it may be necessary either to charge with supplementary refrigerant, or to drain out some, but if such a case arises, please follow the procedure given below flow chart.
Notes 1 As the refrigerant volume can not be adjusted in the heating mode, retrieve the refrigerant, evacu-
ate air and then fill the specified volume of refrigerant if it is necessary to adjust the refrigerant volume in the winter season.
Notes 2 A refrigerant volume adjustment performed in the cooling mode must be done with a gauge reading of 13 kg/cm2G or
higher. If the pressure does not reach refrigerant cannot be collected halfway. Therefore, collect used refrigerant and evacuate the unit completely, and then fill new refrigerant up to a specified quantity.
Notes 3 Judgment by the AL is at best only a rough guideline. Please do not add refrigerant based on the
AL reading alone. (Be sure to obtain calculations of the correct amount before adding refrigerant.)
Notes 4 When supplementing the refrigerant volume, please be careful to charge with liquid refrigerant.
TH1 SC11
12345678910
ON
12345678910
ON
SC16 Pd (High pressure)
12345678910
ON
12345678910
ON
–80–
In case of PURY-200, 250YMF-C
for PURY-(P)200·250YMF-C
Adjustment starts.
Start cooling operation of all indoor units in a test run mode. Note 1
Has the
compressor been
operated for more than
30min?
Was the operation condition stabilized?
The high pressure > 13kg/cm2G?
*Operate for 5 minutes after adjusting the refrigerant and make a judgement.
TH1 115˚C?
Fill refrigerant little by little from the low-pressure side service port.
YES NO
Note 1)As the refrigerant volume can not be adjusted in the heating mode,
retrieve the refrigerant, evacuate air and then fill the specified volume of refrigerant if it is necessary to adjust the refrigerant volume in the winter season.
Is the
thermostat turned
on/off in order for the indoor
unit to prevent from
frosting?
Stop the refrigerant volume adjustment and retrieve the refrigerant. After evacuating air, fill the specified volume of refrigerant.
Are all indoor units SHs more than 2deg?
*Operate for 5 minutes after adjusting the refrigerant and make a judgement.
5deg SC11?
Note 2
10 SC16 30deg?
Note 3
Is the LEV opening
degree stable when SH
< 2deg?
Fill refrigerant little by little from the low-pressure side service port.
*Operate for 5 minutes after adjusting the refrigerant and make a judgement.
Retrieve the refrigerant little by little
30deg < SC16?
from the low-pressure side service port.
Fill refrigerant little by little from the low-pressure side service port.
*Operate for 5 minutes after adjusting the refrigerant and make a judgement.
TH1 110˚C?
Adjustment completed.
Fill refrigerant little by little from the low-pressure side service port.
–81–
Note 2)SC11 : Liquid refrigerant sub-cool for BC controller inlet Note 3)SC16 : Liquid refrigerant sub-cool for BC controller outlet
In case of PURY-P200, 250YMF-C
for PURY-(P)200·250YMF-B
Adjustment starts.
Start cooling operation of all indoor units in a test run mode. Note 1
Has the
compressor been
operated for more than
30min?
Was the operation condition stabilized?
The high pressure > 13kg/cm2G?
*Operate for 5 minutes after adjusting the refrigerant and make a judgement.
TH1 115˚C?
Fill refrigerant little by little from the low-pressure side service port.
YES NO
Note 1)As the refrigerant volume can not be adjusted in the heating mode,
retrieve the refrigerant, evacuate air and then fill the specified volume of refrigerant if it is necessary to adjust the refrigerant volume in the winter season.
Is the
thermostat turned
on/off in order for the indoor
unit to prevent from
frosting?
Stop the refrigerant volume adjustment and retrieve the refrigerant. After evacuating air, fill the specified volume of refrigerant.
Are all indoor units SHs more than 6deg?
*Operate for 5 minutes after adjusting the refrigerant and make a judgement.
5deg SC11?
Note 2
10 SC16 30deg?
Note 3
Is the LEV opening
degree stable when SH
< 6deg?
Fill refrigerant little by little from the low-pressure side service port.
*Operate for 5 minutes after adjusting the refrigerant and make a judgement.
Retrieve the refrigerant little by little
30deg < SC16?
from the low-pressure side service port.
Fill refrigerant little by little from the low-pressure side service port.
*Operate for 5 minutes after adjusting the refrigerant and make a judgement.
TH1 110˚C?
Adjustment completed.
Fill refrigerant little by little from the low-pressure side service port.
–82–
Note 2)SC11 : Liquid refrigerant sub-cool for BC controller inlet Note 3)SC16 : Liquid refrigerant sub-cool for BC controller outlet
for PURY-(P)200·250YMF-C
1 Time required for reco vering refrigerant from low pressure service port (minute)
Low pressure
2
(kg/cm
Refrigerant amount
G) (MPa)
3.5~4.5 4.5~5.5 5.5 ~ 7.5
(0.34~0.44) (0.44~0.54) (0.54~0.74)
to be drawn out (kg)
1 4.0 3.5 3.5 2 8.0 7.0 6.5 3 12.0 10.5 10.0 4 16.0 14.0 13.0 5 20.0 18.0 16.5 6 24.0 21.5 19.5 7 28.0 25.0 23.0 8 32.0 28.5 26.0
9 36.0 32.0 29.5 10 40.0 35.5 32.5 11 44.0 39.0 36.0
2 Additional evacuation, refrigerant replacement, and refrigerant replacement
R2 series has unique refrigerant circuit structure which makes possible 2-pipe cooling-heating simultaneous operations. Therefore, in the case of total replacement or replenishment of refrigerant in this system, the following evacuation and refrigerant replenishment procedures are required. 1 Perform evacuation by connecting to system analyzer joint of service port of high pressure ball valve and high
pressure charge plug, and joint of service port of low pressure ball valve and low pressure charge plug.
2 Perform refrigerant charge from low pressure circuit only, after finishing evacuation, closing vacuum pump valve,
shutting off high pressure circuit of system analyzer, and opening valve of refrigerant cylinder. (In case service port of ball valve and charge plug can not be jointed as shown in the figure, use two vacuum pumps and evacuate high pressure side and low pressure side circuits separately.)
Note 1: Though refrigerant gas itself is harmless, airtight room should be opened before gas release for preventing
oxygen shortage.
2: When releasing gas, use blotting paper, etc. so that oil spouted with the gas does not spread out.
D
F
A
C
B
A Ball valve of the high pressure side B Service port C Ball valve of the low pressure side D Charge plug E High pressure F Low pressure G Evacuation H Evacuation I Replenish of refrigerant J System analyzer K Lo knob L Hi knob
E
G
H
I
N Valve O Valve P Flon 22 cylinder Q R407C cylinder R Scale S Vacuum pump
T A high-precision gravimeter measurable up to 0.1kg
J
HI
LO
K
L
M
P
Q
O
R
P-YMF-B
R
N
S
T
P-YMF-B : Use a vacuum pump with a reverse flow
check valve
should be used. If you are unable to prepare such a high-precision gravimeter, you may use a charge cylinder.
M 3-way joint
–83–
77
7 TROUBLESHOOTING
77
[1] Principal Parts
Pressure Sensor
(1) Judging Failure
1) Check for failure by comparing the sensing pressure according to the high pressure/low pressure pressure sensor and the pressure gauge pressure. Turn on switches 1, 3, 5, 6 (High) and 2, 4, 5, 6 (Low) of the digital display select switch (SW1) as shown below, and the sensor pressure of the high pressure/low pressure sensors is displayed digitally by the light emitting diode LD1.
12345678910
High Pressure
Low Pressure
1 In the stopped condition, compare the pressure readings from the gauge and from the LD1 display.
(a) If the gauge pressure is 0~1 kg/cm (b) If the pressure according to the LD1 display is 0~1 kg/cm2G (0.098MPa), there is faulty contact at the connec-
tor, or it is disconnected. Proceed to 4. (c) If the pressure according to the LD1 display is 32 kg/cm (d) If other than (a), (b) or (c), compare the pressure readings during operation. Proceed to 2.
ON
12345678910
ON
2
G (0.098MPa), the internal pressure is dropping due to gas leakage.
2
G (3.14MPa) or higher, proceed to 3.
2 Compare the pressure readings from the gauge and from the LD1 display while in the running condition.
(a) If the difference between the two pressures is within 1 kg/cm
2
G (0.098MPa), both the affected pressure sensor
and the main MAIN board are normal. (b) If the difference between the two pressures exceeds 1 kg/cm
2
G (0.098MPa), the affected pressure sensor is
faulty (deteriorating performance). (c) If the pressure reading in the LD1 display does not change, the affected pressure sensor is faulty.
3 Disconnect the pressure sensor from the MAIN board and check the pressure according to the LD1 display.
(a) If the pressure is 0~1 kg/cm
2
G (0.098MPa) on the LD1 display, the affected pressure sensor is faulty.
(b) If the pressure is 32 kg/cm2G (3.14MPa) (in the case of the low pressure sensor, 10 kg/cm2G (0.98MPa)) or
higher, the MAIN board is faulty.
4 Disconnect the pressure sensor from the MAIN board and short out the No. 2 and No. 3 pins of the connector
(63HS, 63LS), then check the pressure by the LD1 display. (a) If the pressure according to the LD1 display is 32 kg/cm
2
G (3.14MPa) (in the case of the low pressure sensor,
10 kg/cm2G (0.98MPa)) or higher, the affected pressure sensor is faulty. (b) If other than (a), the MAIN board is faulty.
2) Pressure sensor configuration. The pressure sensors are configured in the circuit shown in the figure at right. If DC 5 V is applied between the red and black wires, a voltage corresponding to the voltage between the white and black wires is output and this voltage is picked up by the microcomputer. Output voltages are as shown below.
High Pressure 0.1 V per 1 kg/cm
2
G (0.098MPa)
Low Pressure 0.3 V per 1 kg/cm2G (0.098MPa)
–84–
Connector
63HS/
63LS
Vout 0.5~3.5 V
GND (Black) Vout (White) Vcc (DC5V) (Red)
* Connector connection specifications on the pressure sensor body side.
The connectors pin numbers on the pressure sensor body side differ from the pin numbers on the main circuit board side.
Sensor Body Side MAIN Board Side
Vcc Pin 1 Pin 3
Vout Pin 2 Pin 2
GND Pin 3 Pin 1
Solenoid Valve (SV1, SV2) (PU(H)Y-200, 250YMF-C)
Check if the control boards output signals and the operation of the solenoid valves match. Setting the self-diagnosis switch (SW1) as shown in the figure below causes the ON signal of each relay to be output to the LED’s. Each LED shows whether the relays for the following parts are ON or OFF. When a LED lights up, it indicates that the relay is ON.
SW1
12345678910
ON
12345678
LED
SV2SV1
1) In the case of SV1 (Bypass Valve) (a) When the compressor starts, SV1 is ON for 4 minutes, so check operation by whether the solenoid valve is
emitting an operating noise.
(b) Changes in the operating condition by solenoid valve operation can be confirmed by the temperature of the
bypass circuit and the sound of the refrigerant.
2) In the case of SV2 (Bypass) (a) SV2 goes ON in accordance with the rise in the high pressure in the cooling mode and heating mode, so check
its operation by the LED display and the operating noise emitted by the solenoid valve.
(b) Changes in the operating condition by solenoid valve operation can be confirmed by the temperature of the
bypass circuit and the sound of the refrigerant.
PU(H)Y-P200, 250YMF-C
12345678910
ON
1 2 3 4 5 6 7 8
LED
SV2SV1
SV4SV3
1) In the case of SV1 (Bypass Valve) (a) When the compressor starts, SV1 is ON for 4 minutes, so check operation by whether the solenoid valve is
emitting an operating noise.
(b) Changes in the operating condition by solenoid valve operation can be confirmed by the temperature of the
bypass circuit and the sound of the refrigerant.
2) In the case of SV2 (Bypass) (a) SV2 goes ON in accordance with the rise in the high pressure in the cooling mode and heating mode, so check
its operation by the LED display and the operating noise emitted by the solenoid valve.
(b) Changes in the operating condition by solenoid valve operation can be confirmed by the temperature of the
bypass circuit and the sound of the refrigerant.
3) SV3, 4 (Control of heat exchanger capacity) (a) Operations can be confirmed by LED display and operating sound of solenoid valve, because one or more of
SV3, 4 are turned on depending on conditions during cooling-only operations.
–85–
Solenoid Valve (SV1~6) (PURY-(P)200·250YMF-C)
Check if the control boards output signals and the operation of the solenoid valves match. Setting the self-diagnosis switch (SW1) as shown in the figure below causes the ON signal of each relay to be output to the LED’s. Each LED shows whether the relays for the following parts are ON or OFF. When a LED lights up, it indicates that the relay is ON.
SW1
12345678910
ON
12345678910
ON
12345678
SV6SV5
LED
SV4SV3SV2SV1
1) In the case of SV1 (Bypass Valve) (a) When the compressor starts, SV1 is ON for 4 minutes, so check operation by whether the solenoid valve is
emitting an operating noise.
(b) Changes in the operating condition by solenoid valve operation can be confirmed by the temperature of the
bypass circuit and the sound of the refrigerant.
2) In the case of SV2 (Bypass) (a) SV2 goes ON in accordance with the rise in the high pressure in the cooling mode and heating mode, so check
its operation by the LED display and the operating noise emitted by the solenoid valve. (Conditions during operation: See Control of Outdoor Unit.)
(b) Changes in the operating condition by solenoid valve operation can be confirmed by the temperature of the
bypass circuit and the sound of the refrigerant.
3) SV3 ~ 6 (Control of heat exchanger capacity) (a) Operations can be confirmed by LED display and operating sound of solenoid valve, because one or more of
SV3 ~5 are turned on depending on conditions during cooling-only operations.
(b) Operation can be confirmed by LED display and operating sound of solenoid valve, because all of SV3 ~ 5 are
turned on during heating-only operations.
(c) Operations can be confirmed by LED display and operating sound of solenoid valve, because one or more of
SV3 ~6 are turned on depending on conditions during cooling-principal and heating-principal operations.
–86–
(d) The refrigerant flow is as following figure. Hot gas (high pressured) flows in cooling mode and cool gas/liquid
(low pressured) flows in heating mode. Please refer to the Refrigerant Circuit Diagram. And, ON/OFF of Solenoid valve is depends on the amount of running indoor units, ambient temperature and so on. So please check by LED Monitor Display. The SV coil is taken off, then it is possible to open caps and check plungers. But the special tool which is on the Service Parts List is needed.
* Closed torque : 13kg·m (1.3N·m)
–87–
Outdoor LEV
The valve opening angle changes in proportion to the number of pulses. (Connections between the outdoor units MAIN board and SLEV, LEV1 (PU(H)Y-(P)200·250YMF-C))
Pulse Signal Output and Valve Operation
Output (phase)
Output states
1234567 8
ø1 ON OFF OFF OFF OFF OFF ON ON ø2 ON ON ON OFF OFF OFF OFF OFF ø3 OFF OFF ON ON ON OFF OFF OFF ø4 OFF OFF OFF OFF ON ON ON OFF
LEV Valve Closing and Valve Opening Operations
Valve Closing
Valve Opening
Valve Opening Angle (Flow Rate)
Fully Open 480 pulses
Output pulses change in the following orders when the
Valve is Closed 1→2→3→4→5→6→7→8→1 Valve is Open 8→7→6→5→4→3→2→1→8
*1. When the LEV opening angle does not change, all the
output phases are off.
2. When the output is out of phase or remains ON continuously, the motor cannot run smoothly, but move jerkily and vibrates.
* When the power is switched ON, a 520 pulse valve
opening signal is output to make sure the valve’s position, so that it is definitely at point A. (The pulse signal is output for approximately 17 seconds.)
* When the valve operates smoothly, there is no sound
from the LEV and no vibration occurs, but when the valve is locked, it emits a noise.
* Whether a sound is being emitted or not can be
determined by holding a screwdriver, etc. against it, then placing your ear against the handle.
* If there is liquid refrigerant inside the LEV, the sound
may become lower.
Pulse Count
–88–
Judgment methods and likely failure mode
Caution:
The specifications of the outdoor unit (outdoor LEV) and indoor unit (indoor LEV) differ. For this reason, there are cases where the treatment contents differ, so follow the treatment specified for the appropriate LEV as indicated in the right column.
Failure Mode Judgment Method Treatment Affected LEV
Microcomputer driver circuit failure
1 Disconnect the control board connector and connect
the check LED as shown in the figure below.
Indoor, BC controller
When the base power supply is turned on, the indoor LEV outputs pulse signals for 10 seconds, the outdoor LEV outputs pulse signals for 17 seconds, and BC controller outputs pulse signals for 10-20 seconds. If the LED does not light up, or lights up and remains on, the driver circuit is abnormal.
Outdoor
In the case of driver circuit failure, replace the control board.
Indoor
BC controller
Outdoor
LEV mechanism is locked.
The LEV motor coils have a disconnected wire or is shorted.
Fully closed failure (valve leaks)
1 If the LEV is locked up, the drive motor turns with no
load and a small clicking sound is generated. Generation of this sound when the LEV is fully closed or fully open is abnormal.
Measure the resistance between the coils (red - white, red
- orange, brown - yellow, brown - blue) using a tester. They are normal if the resistance is within 150Ω ± 10%.
Measure the resistance between the coils (gray - orange, gray - red, gray - yellow, gray - black) using a tester. They are normal if the resistance is within 46Ω ± 3%.
1 If you are checking the indoor unit’s LEV, operate the
indoor units blower and the other indoor units in the cooling mode, then check the piping temperatures (liquid pipe temperatures) of the indoor units by the operation monitor through the heat source unit’s control board. When the fan is running, the linear expansion valve is fully closed, so if there is leakage,
Thermistor liquid pipe (tempera­ture sensor)
Linear Expansion Valve
minimal leakage, it is not necessary to replace the LEV if there are no other effects.
the temperature sensed by the thermistor (liquid pipe temperature sensor) will become low. If the temperature is considerably low compared to the remote control’s intake temperature display, it can be judged that there is a fully closed failure. In the case of
Replace the LEV.
Replace the LEV coils.
Replace the LEV coils.
If there is a large amount of leakage, replace the LEV.
Indoor
BC controller
Outdoor
Indoor
BC controller
Outdoor
Indoor
BC controller
Faulty wire connections in the connector or faulty contact.
1 Check for pins not fully inserted on the connector and
check the colors of the lead wires visually.
2 Disconnect the control board’s connector and conduct
a continuity check using a tester.
–89–
Check the continuity at the places where trouble is found.
Indoor
BC controller
Outdoor
Outdoor LEV (SLEV) Coil Removal Procedure (configuration) As shown in the figure, the outdoor LEV is made in such a way that the coils and the body can be separated.
Coils
Stopper
Lead Wires
<Removing the Coils> Fasten the body tightly at the bottom (Part A in the figure) so that the body will not move, then pull out the coils toward the top. If they catch on the stopper and are difficult to take out, turn the coils left and right until the stoppers are free from the stopper indentations, then pull the coils out. If you take out the coils only without gripping the body, undue force will be applied to the piping and the pipe may be bent over , so be sure to fasten the body in such a w ay that it will not move.
Body
Indentation for Stopper (12 places around the circumference)
Part A
<Installing the Coils> Fasten the body tightly at the bottom (Part A in the figure) so that the body will not move, then insert the coils from the top, inserting the coils stopper securely in one of the indentations on the body. (There are four indentations for the stopper on the body around its circumference, and it doesn’t matter which indentation is used. However, be careful not to apply undue force to the lead wires or twist them around inside the body.) If the coils are inserted without gripping the body, it may exert undue force on the piping, causing it to become bent, so be sure to hold the body firmly so that it wont move when install­ing the coils.
Part A
–90–
Check Valves Block (PURY-(P)200·250YMF-C)
The refrigerant flow in the pipe 6, 7, 8 and 9 are depend on ON/OFF of the SV3, 4, 5 and 6. Please confirm by LED monitor display. You can open the cap of valve A, B and C, but 3 types of hexagon socket screw keys. The size is as follows.
* Closed torque : A : 1.7kg·m (0.17N·m)
B : 20kg·m (2.0N·m) C : 13kg·m (1.3N·m)
–91–
Intelligent Power Module (IPM)
Measure resistances between each terminal of IPM with tester, and use the results for troubleshooting. Specified resistance value is dependent on tester type to be used for resistance measurement, because diode inside IPM has non-linearity, thus difference of impedance and voltage in tester being influential. As the internal impedance of resistance range of analog tester equals to the center value of meter indication, the affect of internal impedance can be minimized if the tester having close center value of resistance range. Because internal voltage is normally 1.5V, the tester to be used for troubleshooting of IPM should satisfy the following conditions.
Internal voltage 1.5V (Power source : one dry cell battery) Central value of resistance range 10 ~ 40
The measured values for troubleshooting are shown in the table below. (Use the minimum range for tester resistance range.)
External view Internal circuit diagram
1471016
B
P
N
Judged value
Tester
+
Tester –
P U V
W
N
W
V
P
UVWN
∞∞∞∞
2~ 100
2~ 100
2~ 100
2~ 1002~1002~1002~100
3
2
Pre-Driver
1 6
5
Pre-Driver
4 9
8
Pre-Driver
U
7 11
13
Pre-Driver
10
14
Pre-Driver
15
Pre-Driver
12
∞ ∞
Over heating
16
protection circuit
P
U
V
W
B N
Diode stack Perform continuity check with tester. Judged as normal if the following characteristics are observed. (Use the minimum range for tester resistance range.)
Tester
Tester -
1 10~50Ω∞ 2 10~50Ω∞ 3 10~50Ω∞
Tester -
Tester
123
1 10~50
+
2 10~50 3 10~50
1 2 3
+–
+–
92
(2) Trouble and remedy of remote controller
Symptom Cause Checking method & countermeasure
1
Despite pressing of remote controller switch, operation does not start with no electronic sound.
(No powering signal
appears.)
2
At about 10 seconds after turning remote controller operation switch ON, the display distinguishes and the operation stops.
1) M-NET transmission power source is not supplied from outdoor unit. 1 Main power source of outdoor unit is not
connected.
2 Slipping off of connector on outdoor unit circuit
board. Main board : CNS1, CNVCC3 INV board : CNAC2, CNVCC1, CNL2
3 Faulty power source circuit of outdoor unit.
Faulty INV board,
Blown fuse (F1 on INV board)
Broken diode stack
Broken resistor (R1) for rush current protection
2) Short circuit of transmission line.
3) Erroneous wiring of M-NET transmission line at outdoor unit. 1 Transmission line disconnection or slipping off from terminal
block.
2 Erroneous connection of indoor/outdoor transmission line to
TB7.
4) Slipping off of transmission wiring at remote controller.
5) Faulty remote controller.
1) Power source is not fed to indoor unit from transformer.
1 Main power source of indoor unit is not turned on. 2 Slipping off of connector (CND, CNT, CN3T) on indoor controller board. 3 Blown fuse on indoor controller board. 4 Faulty or disconnected transformer of indoor unit. 5 Faulty indoor controller board.
2) Faulty outdoor control circuit board or being out of control. As normal transmission is failed between indoor and outdoor units, outdoor unit model can not be recognized.
a) Check transmission terminal block of
remote controller for voltage. i) In case of 17 ~ 30V
Faulty network remote controller
ii) In case of less than 17V
See “Transmission Power Circuit
(30V) Check Procedure”.
The cause of 2) and 3) is displayed with self-diagnosis LED for 7102 error.
Checking method & countermeasure
Check indoor LED3
Lighting?
Lighting
Check for the change of LED display by operating dip switch SW1 for self-diagnosis.
Extinguishing or unable to confirm
Check indoor unit power source terminal block voltage
AC 220~240V?
YES
Check fuse on circuit board
Blown?
NO
Check connector slipping off (CND, CNT, CN3T)
Slipped off?
NO
Check transformer resistance value
Within rated?
YES
Check self-diagnosis function of outdoor unit
Changed?
NO
YES
YES
*1
NO
NO
Check main power source of power source wiring.
Check 220V~240V circuit for short circuit and ground fault.
Improper connector connection
Check cause of trans­former disconnection.
Ground fault on circuit board
Ground fault on sensor, LEV
Apply power source again.
Check self-diagnosis function af­ter powering outdoor unit again.
NO
Faulty outdoor unit control circuit board
Repair faulty point.
YES
Faulty indoor controller board
Changed?
YES
Casual trouble
*1 Check the transformer in accordance with the TROUBLE SHOOTING” in the indoor units service handbook.
–93–
Symptom Cause
3 HO display on re-
mote controller does not disappear and switch is ineffective.
(Without using MELANS)
1) Outdoor unit address is set to “000.
2) Erroneous address.
1 Address setting miss of indoor unit to be coupled with remote controller. 2 Address setting miss of remote controller.
3) Faulty wiring of transmission terminal block TB5 of indoor unit in the same group with remote controller.
4) Centralized control SW2-1 of outdoor unit is turned ON.
5) Setting to interlocking system from indoor unit (Switch 3-1 = OFF), while Fresh Master is intended to use by remote controller operation (indoor unit attribute).
6) Disconnection or faulty wiring of indoor unit transmission line.
7) Disconnection between indoor unit M-NET transmission line terminal block (TB5) and connector CN2M.
8) More than 2 sets of power supply connector (CN40) are inserted into centralized control transmis­sion line of outdoor unit.
9) Faulty outdoor unit control circuit board.
10)Faulty indoor controller board.
11)Faulty remote controller.
(Interlocking control with MELANS)
12)No grouping registration from MELANS (Neglecting to set the relation between indoor unit and network remote controller).
13)Slipping off of centralized control transmission line (TB7) at outdoor unit.
14)At system connected with MELANS, power supply connector (CN40) is inserted to centralized control transmission line of outdoor unit.
Checking method & countermeasure
(Indoor unit = remote controller - 100.)
(Remote controller = indoor unit + 100.)
In case no MELANS used
Same symptom for all units in a single refriger­ant system?
YES
Check outdoor unit address
51 ~ 100?
YES
Check centralized control switch SW2-1 at outdoor unit
ON?
NO
Faulty outdoor unit control circuit board
NO
NO
YES
Outdoor unit address set­ting miss
Switch setting miss Make it ON OFF
Address setting miss of remote controller
Indoor address setting miss
T r ansmission line wiring miss of in­door unit M-NET
Slipping off of CN2M connector
Confirm address of remote controller with “HO” displayed
Indoor unit + 100?
Check address of coupling indoor unit
Remote controller
-100? YES
Check voltage of indoor unit M­NET transmission terminal block
17 ~ 30V?
Check connection between indoor unit M-NET trans­mission terminal block (TB5) and connector CN2M
YES
Check Fresh Master SW3-1
YES
Slipping off?
NO
NO
Faulty indoor controller board or remote controller
ON?
YES
Repair spot in trouble
Setting miss of Fresh Master SW3-1
In case with MELANS used
When MELANS is used, “HO” display on the remote controller will disappear at the group registration of the indoor unit and local remote controller. If HO does not disappear after the registration, check the items 12) ~ 14) in the Cause column.
–94–
Symptom Cause Checking method & countermeasure
4 88 appears on re-
mote controller at the registration and access remote controller
[Generates at registration and confirmation]
1) Erroneous address of unit to be coupled.
2) Slipping off of transmission line of unit to be coupled (No connection).
3) Faulty circuit board of unit to be coupled.
4) Installation miss of transmission line.
a) Confirm the address of unit to be
coupled.
b) Check the connection of transmission
line.
c) Check the transmission terminal block
voltage of unit to be coupled. i) Normal if voltage is DC17 ~ 30V ii) Check the item d) in case other than i).
[Confirmation of different refrigerant system controller]
5) Breaking of power source of outdoor unit to be confirmed.
6) Slipping off of centralized control transmission line (TB7) of outdoor unit.
7) Power supply connector (CN40) is not inserted into centralized control transmission line in grouping with different refrigerant system without using MELANS.
8) More than 2 sets of power supply connector are inserted into the centralized control transmission line of outdoor unit.
9) In the system connected with MELANS, power supply connector (CN40) is inserted into the centralized control transmission line of outdoor unit.
10)Short circuit of centralized control transmission line.
d) Confirm the power source of outdoor unit
to be coupled with the unit to be confirmed.
e) Confirm that the centralized control
transmission line (TB7) of outdoor unit is not slipped off.
f) Confirm the voltage of centralized control
transmission line. i) Normal in case of 10V ~ 30V ii) Check the items 7) ~ 10) left in case
that other than i).
–95–
Transmission Power Circuit (30 V) Check Procedure If “” is not displayed by the remote control, investigate the points of the trouble by the following procedure and correct it.
No. Check Item Judgment Response
1
Disconnect the transmission line from TB3 and check the TB3 voltage.
DC24~30 V
Check the transmission line for the following, and correct any defects. Broken wire, short circuit, grounding, faulty contact.
2
Check if the following connectors are disconnected in the outdoor units control box. MAIN Board: CNS1, CNVCC3, CNVCC4 INV Board: CNVCC2, CNVCC4, CNL2, CNR, CNAC2
3
Disconnect the wires from CNVCC3 on the Main board and check the voltage between pins 1 and 3 on the wire side of the CNVCC3.
Tester + ..... 1 pin
Tester - ..... 3 pin
4
Disconnect the wiring from CNVCC2 on the INV board and check the voltage between pins 1 and 3 of CNVCC2.
Tester + ..... 1 pin
Tester - ..... 3 pin
5
Disconnect the wiring from CNL2 on the INV board, and check the resistance at both ends of choke coil L2.
6
Disconnect the wiring from CNR on the INV board, and check the resistance at both ends of R7.
Except the above-mentioned Connector disconnected
Except the above-mentioned
DC24~30 V
Except the above-mentioned DC24~30 V
Except the above-mentioned
0.5~2.5 Except the above-mentioned 19~25 Except the above-mentioned
to No. 2 Connect the connectors as shown on the electric
wiring diagram plate. to No. 3
Check the wiring between CNS1 and TB3 for the following, and correct any defects. Broken wire, short circuit, grounding, faulty contact. If there is no trouble, replace the Main board.
to No. 4 Check the wiring between CNVCC2 and
CNVCC3 for the following, and correct any defects. Broken wire, short circuit, grounding, faulty contact.
to No. 5 to No. 6 Replace choke coil L2. to No. 7 Replace R7.
7
Check the resistance at both ends of F01 on the INV board.
8
Check the voltage between pins 1 and 3 of CNAC2 on the INV board.
9
Check the voltage between L2 and N on power supply terminal block TB1.
0 Except the above-mentioned AC198~264 V Except the above-mentioned AC198~264 V
Except the above-mentioned
to No. 8 Replace F01 Replace the INV board. to No. 9 Check the wiring to CNAC2 for the following and
correct any defects. Broken wire, faulty contact.
Check the power supply wiring and base power supply, and correct any defects.
–96–
(3) Investigation of transmission wave shape/noise
Control is performed by exchanging signals between outdoor unit, indoor unit and remote controller by M-NET transmission. If noise should enter into the transmission line, the normal transmission will be hindered causing erroneous operation.
1) Symptom caused by the noise entered into transmission line
Cause Erroneous operation Error code
Noise entered into transmission line
Signal changes and is misjudged as the signal of other address.
Transmission wave shape changes to other signal due to
6600
6602
noise. Transmission wave shape changes due to noise, and can
6607
not be received normally thus providing no reply (ACK). Transmission can not be made continuously due to the
6603
entry of fine noise. Transmission can be made normally, but reply (ACK) or
answer can not be issued normally due to noise.
6607 6608
2) Method to confirm wave shape
No fine noise allowed *1
<with transmission>
<without transmission>
VHL
52 µs Logical
VBN
52 µs value 0
Logical
52 µs value 1
52 µs52 µs
No fine noise allowed *1
Check the wave shape of transmission line with an oscilloscope to confirm that the following conditions are being satisfied.
1 The figure should be 104µs/bit ± 1%. 2 No finer wave shape (noise) than the transmission signal (52µs ± 1%) should be allowed. *1 3 The sectional voltage level of transmission signal should be as follows.
Logic value Transmission line voltage level
0VHL = 2.0V or more 1VBN = 1.3V or less
*1 However, minute noise from the DC-DC converter or inverter operation may be picked up.
–97–
3) Checking and measures to be taken
(a) Measures against noise
Check the items below when noise can be confirmed on wave shape or the error code in the item 1) is generated.
Items to be checked Measures to be taken
1 Wiring of transmission and power lines in
crossing.
2 Wiring of transmission line with that of other
system in bundle.
3 Use of shield wire for transmission line (for
both indoor unit control and centralized control).
4 Repeating of shield at the repeating of
transmission line with indoor unit.
Checking for wiring method
5 Are the unit and transmission lines grounded
as instructed in the INSTALLATION MANUAL?
6 Earthing of the shield of transmission line (for
indoor unit control) to outdoor unit.
7 Arrangement for the shield of transmission line
(for centralized control).
Check for earthing
Isolate transmission line from power line (5cm or more). Never put them in a same conduit.
Wire transmission line isolating from other transmission line. Wiring in bundle may cause erroneous operation like crosstalk.
Use specified transmission wire.
Type : Shield line CVVS/CPEVS Wire diameter : 1.25mm2 or more
The transmission line is wired with 2-jumper system. Wire the shield with jumper system as same for transmission line. When the jumper wiring is not applied to the shield, the effect against noise will be reduced.
Connect to ground as shown in the INSTALLATION MANUAL.
One point earthing should be made at outdoor unit. Without earthing, transmission signal may be changed as the noise on the transmission line has no way to escape.
For the shield earth of the transmission line for centralized control, the effect of noise can be minimized if it is from one of the outdoor units in case of the group operation with different refrigerant systems, and from the upper rank controller in case the upper rank controller is used. However, the environment against noise such as the distance of trans­mission line, the number of connecting sets, the type of connecting con­troller, and the place of installation, is different for the wiring for central­ized control. Therefore, the state of the work should be checked as fol­lows. a) No earthing
Group operation with different refrigerant systems One point earthing at outdoor unit
Upper rank controller is used Earthing at the upper rank controller
b) Error is generated even though one point earth is being con-
nected. Earth shield at all outdoor units.
Connect to ground as shown in the users manual.
(b) When the wave height value of transmission wave shape is low, 6607 error is generated, or remote controller is
under the state of “HO.
Items to be checked Measures to be taken
8 The farthest distance of transmission line is
exceeding 200m.
9 The types of transmission lines are different.
0 No transmission power (30V) is being supplied
to the idoor unit or the remote control.
A Faulty indoor unit/remote controller.
Confirm that the farthest distance from outdoor unit to indoor unit/ remote controller is less than 200m.
Use the transmission wire specified.
Type of transmission line : Shield wire CVVS/CPEVS Wire dia. of transmission line : 1.25mm2 or more
Refer to Transmission Power Supply (30V) Circuit Check Procedure.
Replace outdoor unit circuit board or remote controller.
–98–
4) Treatment of Inverter and Compressor Troubles If the compressor does not work when error codes 4240, 4250, 4340 or 4350 are detected, determine the point of malfunction by following the steps in the LED monitor display and countermeasures depending on the check code displayed, then perform the procedures below.
No. Check Item Symptoms Treatment
How many hours was the power kept on before
1
operation?
1 If it was kept on for 12 hours or
longer as specified.
2 It was kept on for less than the
specified period.
Go to [2].
Go to [2] after keeping the power on for the specified time.
When it is restarted, does
2
the trouble reappear?
3
Run the outdoor unit with the wiring to the compressor disconnected. At this time, change SW1-1 on the INV board to ON. Note) The terminals of the 3 disconnected wires should be isolated from each other.
*1 [Cautions when measuring the voltage and current of the inverters power circuit.]
1 The compressor stops and the
same error code is displayed.
1 The Inverter stops and the same
error code is displayed.
2 If the inverter’s output voltage is
output with good balance, *1.
3 If the balance in the inverter’s
output voltage is not good or if the inverters output voltages are all 0 V (a digital tester cannot be used) *1.
Perform the check of wiring shown in the explanation of each error code.
Check the IPM is faulty. (Go to “Individual Parts Failure Judgment Methods.”)
Check the coil resistance and insulation resistance of the compressor, and if it is normal, run it again, and if the trouble occurs again, replace the compressor. * Insulation resistance : 2M or more
Coil resistance : 0.359 ~ 0.716
Check the IPM. Judge that the IPM is faulty. (Go to “Indi- vidual Parts Failure Judgment Methods.”) If the IPM is normal, replace the G/A board, then perform this item again with SW1-1 ON. If the problem is not solved, replace the INV board. If the problem is solved and you connect the compressor again, turn SW1-1 OFF again. Check the compressor’s coil resistance and insulation resistance.
Since the voltage and current on the inverter’s power supply side and its output side do not have a sine waveform, the measurement values will differ depending on the measuring instrument and the circuit measured. In particular, as the inverters output voltage has a pulse waveform, the output frequency also changes, so differences in measurement values will be great depending on the measuring instrument.
1 When checking if the inverters output voltage is unbalanced or not (relative comparison of the voltages between
each of the lines), if you are testing with a portable tester, be sure to use an analog tester. Use a tester of a type which can be used to judge if the IPM or diode module is faulty. In particular, in cases where the inverters output frequency is low, there are cases where the variations in measured voltage values between the different wires will be great when a portable digital tester is used, when in actuality they are virtually equal, and there is danger of judging that the inverter is faulty.
2 It is recommended when checking the inverter’s output voltage values (when measuring absolute values), that, if a
measuring device for business frequencies is used, a rectified voltage meter (with a Correct measurement values cannot be obtained with an ordinary portable tester. (either analog or digital)
symbol) be used.
–99–
Loading...