Overview
This manual describes the specifications, handling and programming meth­ods for the PROFIBUS DP Master Module ME1PB1-L which is used with the pro­grammable controllers of the MELSEC-L series. The ME1PB1-L operates as a DP-Master (Clas s 1) on PR OFI BUS DP n etwo rks and is used for connecting MELSEC-L series programmable controllers to PROFIBUS DP.
Installation and Wiring
m
Turn off all phases of the power supply for the PLC and other external sources before starting the installation or wiring work.
DANGER
Mounting the Modules on a DIN rail
Pull down DIN rail hooks on the back of the modules until they click.
Installation Manual for PROFIBUS DP Master Module ME1PB1-L
Art.no.: 270468 ENG, Version A, 02102013
Safety Information
This manual is only intended for use by properly trained and qualified electri­cal technicians who are fully acquainted with automation technology safety standards. All work with the hardware described, including system design, installation, setup, maintenance, service and testing, may only be performed by trained electrical technicians with approved qualifications who are fully acquainted with the applicable automation technology safety standards and regulations.
Proper use of equipment
The programmable controllers (PLC) of the MELSEC-L series are only intended for the specific applications explicitly described in this manual or the manuals listed below. Please take care to observe all the installation and operating parameters specified in the manual. All products are designed, manufactured, tested and documented in agreement with the safety regulations. Any modi­fication of the hardware or software or disregarding of the safety warnings given in this manual or printed on the product can cause injury to persons or damage to equipment or other property. Only peripherals and expansion equipment specifically recommended and approved by Mitsubishi Electric may be used with the programmable controllers of the MELSEC-L series. Any other use or application of the products is deemed to be improper.
Relevant safety regulations
All safety and accident prevention regulations relevant to your specific appli­cation must be observed in the system design, installation, setup, mainte­nance, servicing and testing of these products. In this manual special warnings that are important for the proper and safe use of the products are clearly identified as follows:
DANGER:
Personnel health and injury warnings. Failure to observe the precautions described here can result
m
in serious health and injury hazards.
CAUTION:
Equipment and property damage warnings. Failure to observe the precautions described here can result
b
in serious damage to the equipment or other property.
Further information
The following manuals contain further information about the module:
MELSEC-L PROFIBUS DP Master Module ME1PB1-L User‘s Manual
MELSEC-L CPU Module User‘s Manual
(Hardware Design, Maintenance and Inspection)
MELSEC-Q/L Programming Manual
Safety Guidelines for MELSEC L CPU
These manuals are available free of charge through the internet (www.mitsubishi-automation.com).
If you have any questions concerning the installation, configuration or opera­tion of the equipment described in this manual, please contact your relevant sales office or department.
Part Names
No. Description
Module joint lever (for connecting two modules)
Normal operation
RUN
SD/RD
PRM
TKN
LEDs
ERR
R ERR.
RDY
TST
PROFIBUS interface connector (D-sub 9-pin connector, female)
: LED ON, : LED flashing, : LED OFF
The LED flashes at intervals based on the value set in the Master Parameters.
The LED flashes at the time of request or response in acyclic communication.
The LED status during token passing varies depending on the number of DP-Mas­ters within the same network and the transmission speed setting.
1 Master: TKN LED is ON regardless of the transmission speed.
More than 1 Master: –Transmission speed 19.2 kbps or less: The TKN LED is flashing. – Transmission speed 93.75 kbps or more: The TKN LED is ON or OFF.
– Hardware error (watchdog timer error)
–Power failure
– Communication with PROFIBUS/DP-Slave – Acyclic communication
communication
No
Parameter setting mode
The written parameters are invalid.
No parameter setting mode
Token being passed
No token passing
Error
Normal operation
Communication error
No communication error
– Ready to communicate
– Communication being performed
Not ready; no communication
–Self-diagnostic
– Flash ROM initialization
Self-diagnostic
No self-diagnostics, no flash ROM
initialization
b
Use the product in the environment that meets the "GENERAL SPECIFI­CATIONS" in the manual "Safety Guidelines" included in the CPU mod­ule or head module. Failure to do so may result in electric shock, fire, malfunction, or damage to or deterioration of the product.
Prevent foreign matter such as dust or wire chips from entering the module. Such foreign matter can cause a fire, failure, or malfunction.
Before handling modules, touch a grounded metal object to discharge the static electricity from the human body. Not doing so may cause failure or malfunctions of the module.
CAUTION
Mounting
b
Modules must be mounted on a DIN rail.
Connect an END cover on the last module on the right side.
Do not drop the module or subject it to heavy impact.
Do not open or modify a module. Doing so can cause a failure, mal-
function, injury or fire.
Do not directly touch any conductive parts and electronic components of the module.
To interconnect modules, engage the respective connectors and securely lock the module joint levers. Incorrect interconnection may
cause malfunction, failure, or drop of the module.
CAUTION
Connecting the modules
The procedure for connecting modules is shown with an example of how to connect the L02CPU to the power supply module L61P.
To release the module joint
levers located at the top and bottom of the L02CPU:
Slide the levers toward the front side of the module.
Insert the connector of the
CPU module into that of the power supply so that they are securely engaged.
To lock the module joint
levers: Slide the levers toward the
back side of the module. Make sure that the modules
are securely connected.
Hang the upper tabs of the
modules on a DIN rail, and push the modules in posi­tion.
Lock the DIN rail hooks to
the DIN rail to secure the modules in the position.
Pull the hooks up until they click. If the hooks are beyond the reach, use a tool such as a driver.
Mount stoppers on the DIN rail beside the leftmost and rightmost module,
to avoid lateral sliding.
NOTE
Do not slide modules from the edge of the DIN rail when mounting. Doing so may damage the metal part located on the back of the module.
Wiring
b
Do not lay PROFIBUS cables close to the main circuit, high-voltage power lines, or load lines.
Otherwise effects of noise or surge induction are likely to take place. Keep a safe distance of more than 100 mm from the above when wiring.
When disconnecting the PROFIBUS cable, do not pull it by holding the cable part.
Be sure to hold its connector which is plugged into the module. Pulling the cable with it connected to the module may damage the module and/or cable, or cause malfunctions due to poor contact of the cable.
Applicable Cable and Connector
To connect the ME1PB1-L to a PROFIBUS/DP network, use only the PROFIBUS connector and shielded twisted pair PROFIBUS cable complying with EN50170.
Wiring precautions
Keep the PROFIBUS cable away from I/O module cables as much as possible.
CAUTION
Mitsubishi Electric Europe B.V. /// FA - European Business Group /// Germany /// Tel.: +49(0)2102-4860 /// Fax: +49(0)2102-4861120 /// www.mitsubishi-automation.com
Page 2
Pin Configuration
5
1
6
9 . . .
.
.
.
.
Threaded hole to fix PROFIBUS connector
3
8
ME1PB1-L
RxD/TxD-P
RxD/TxD-N
Red Green
PROFIBUS cable
VP (6)
R
u
= 390 : ±2 %, 1/4 W
R
d
= 390 : ±2 %, 1/4 W
R
tA
= 220 : ±2 %, 1/4 W
RxD/TxD-P (3)
RxD/TxD-N (8)
DGND (5)
DIN rail centre
4545
90 4
4
95
28.5
All dimensions are in "mm".
4
Connection of the PROFIBUS/DP cable
Specifications
NOTE
An inch screw thread (#4-40UNC) is used to fix the connector to the ME1PB1-L.
Signal
Pin
code
1— —Not used
2— —Not used
3 B/B' RxD/TxD-P Receive/send data -P Red
4— —Not used
5C/C'
6—
7— —Not used
8 A/A' RxD/TxD-N Receive/send data -N Green
9— —Not used
Signal used to connect the bus terminator.
Name Description Wire color
DGND
Data Ground
Voltage +
VP
Bus Terminator
Each end of the PROFIBUS DP network must be terminated with a resistor. Since the ME1PB1-L is not equipped with a built-in terminating resistor, use a PROFIBUS connector with built-in bus terminator if the ME1PB1-L is situated at the beginning or end of a network.
It is recommended to use a bus terminator with the following specifications:
General Specifications
Item ME1PB1-L
Internal current consumption (5 V DC) 0.55 A
Weight 0.14 kg
Performance Specifications
Item ME1IPB1-L
PROFIBUS DP station type PROFIBUS DP Master Class 1
Electrical standard EIA-RS485 compliant
Medium Shielded twisted pair cable
Network topology
Data link method
Encoding method NRZ
Transmission speed 9.6 kbps to 12 Mbps
Transmission data size
Number of repeaters per communica­tion path
Input data
Output data
Number of stations per segment max. 32 (including repeaters)
Number of slaves per ME1PB1-L max. 125
Transmission speed
9.6 kbps
Segment length and bus length
93.75 kbps
187.5 kbps 1000 m 4000 m
500 kbps 400 m 1600 m
1.5 Mbps 200 m 800 m
3 Mbps
12 Mbps
This is also the maximum bus length when no repeater is used.
With each repeater installed in the PROFIBUS DP network, the transmission dis­tance is extended by the length of one segment.
Bus (tree topology when repeat­ers are used)
Between DP-Master and DP-
Master: Token passing method
Between DP-Master and DP-
Slave: Polling method
Max. 8192 bytes (max. 244 bytes/slave)
Max. 8192 bytes (max. 244 bytes/slave)
max. 3
Segment length
Max. bus length when using 3 repeaters
1200 m 4800 m19.2 kbps
100 m 400 m6 Mbps
External dimensions