Mitsubishi MAC-640BH-U,MAC-642BH-U1,PAC-645BH-E,PAC-646BH-E,PAC-SJ20BH-E Submittal

Page 1
DRAIN PAN HEATERS
LOW AMBIENT BASE P
System Reference: Date:

AVAILABLE MODELS

AN HEATERS
PAC-645BH-E
MAC-640BH-U
MAC-642BH-U1
PAC-646BH-E
PAC-SJ20BH-E

GENERAL FEATURES

• Controlled by outdoor unit
• Works during defrost operation and energizes when outdoor temperature drops below 36ºF
• MAC-640BH-U connects to CN722 on control board of MUZ-FH06,09,12NA, MUZ-GL09,12,15NA, MUZ­HM09,12,15,18NA, MUZ-WR09,12,18NA, SUZ­KA09,12,15NA2
• PAC-645BE-E connects to CN-714 on MXZ-3C24/3C30/4C36/5C42NA
• MAC-642BH-U1 connects to CN601 on control board of MUZ-FH15,18NA, MUZ-GL18,24NA, MUZ-HM24NA, MUZ-WR24NA, SUZ-KA18,24,30,36NA2
• PAC-646BH-E connect to CN714 on MXZ-2C20NA2
• PAC-SJ20BH-E connects SS on Control board of MXZ-8C48NA, 8C60NA, PUZ-A36,42NKA7, PUZ­HA42NKA, PUMY-P36,48,60NKMU2

INSTALLATION NOTES

• For MUZ-A models, the power board needs to be replaced with board included with pan heater
• Use of drain pan heaters is recommended when ambient temperatures are expected to be below freezing for periods longer than 72 hours straight; or when continuous sub-zero outdoor ambient conditions are expected to last longer than 24 hours
• Outdoor unit must not be installed directly on the ground, but on a raised platform, such as on mini-split stands, to suppress freezing
Specifications are subject to change without notice. © 2019 Mitsubishi Electric Trane HVAC US LLC
• Recommended installation of a Ground Fault Interrupt (GFI) circuit breaker, depending on installation area to prevent electric shock
• See corresponding installation instructions, and outdoor unit technical service manual for further details on installation
Page 2

APPLICABLE MODELS: DRAIN PAN HEATERS

Table 1.
Drain Pan Heater Kits Outdoor Unit Models Rated Voltage Power Input
MAC-640BH-U MUZ-GL09/12/15NA
208 / 230 V 106 / 130 W MUZ-FH06/09/12NA MUZ-HM09/12/15/18NA MUZ-WR09/12/18NA SUZ-KA09/12/15NA2
MAC-642BH-U1 MUZ-FH15NA
208 / 230 V 98 / 120 W MUZ-FH18NA2 MUZ-GL18/24NA MUZ-HM24NA MUZ-WR24NA SUZ-KA18/24/30/36NA2
PAC-645BH-U MXZ-3C24/3C30/4C36/5C42NA 230 V 80 W
PAC-646BH-E MXZ-2C20NA2 230 V 120 W
PAC-SJ20BH-E MXZ-8C48/8C60NA 230 V 150 W
1340 Satellite Boulevard, Suwanee, GA
30024
oll Free: 800-433-4822
T
www
.mehvac.com
FORM# Drain Pan Heaters - 201906
Specifications are subject to change without notice. © 2019 Mitsubishi Electric Trane HVAC US LLC