Mitsubishi Electric LMAP04-E Installation Manual

Page 1
Building Air-Conditioners Control System
Model : LMAP04-E
Contents
Safety Precautions···················································1,2
1
.Parts Include ····························································3
2
.Specifications···························································3
2
2
-2 Environment Specifications ·····························3
2
-3 Connected Air Conditioning Equipment ··········4
2
-4 LONWORKS®Network Specifications ················4
2
-5 Network Variable Specifications·······················5
3.Installation ·······························································6 3
-1 Locally Procured Parts ·····································6
3
-2 Installation Method ···········································7
3
-3 Wiring Methods ················································8
3
-4 Electrical Wiring ···············································9
4
.System Settings ·····················································11
4
-1 If not used together with system controller·····11
4
-2 If used together with system controller···········12
4
-3
Initialization Settings of LONWORKS®Network
···13
5
.Confirming Operation·············································14
5
-1 Flow of Onsite Adjustments····························14
5
-2
Preparation Material for Onsite Adjustments
·····14
5
-3 Preparation and Setting ·································14
5
-4 Test Run·························································15
6
.Troubleshooting······················································16
6
-1 Abstract ··························································16
6
-2 Troubleshooting ·············································17
6
-3 Error Code list ················································19
Appendix : Test run check sheet······························20
Before using the unit, please read this Installation Manual carefully to ensure correct operation. Store this Installation Manual in a location that is easy to find. Echelon®,LON®,LONWORKS®,Neuron®,3150®and the Echelon logo are trademarks of Echelon Corporation registered in the United States and other countries. LonMaker™ and the Lon Users logo are trademarks of Echelon Corporation.
Installation Manual
LM ADAPTER
Page 2
Page 3
1
Safety Precautions
• Before installing this unit,make sure you read all the “Safety Precautions”.
• This manual describes the installation of LM ADAPTER and wiring to the outdoor unit.
• Please read the installation manual of air-conditioning units with regards to the installation method of air-conditioning units.
• The “Safety Precautions” provide very important points regarding safety. Make sure you follow them.
Symbols and Terms
Statements identify condition or practices that could result in personal injury or loss of life. Statements identify condition or practices that could result in damage to the unit or other
property.
WARNING
WARNING CAUTION
Ask your dealer or technical representative to install.
Any deficiency cased by your own installation may result in an electric shock and fire.
Ensure that installation work is done correctly following that installation manual.
Any deficiency caused by installation may result in an electric shock or fire.
Install in a place which is strong enough to withstand the weight of the unit
Any lack of the strength may cause the unit to fall down, resulting in a personal injury. Any deficiency caused by installation may result in an electric shock, fire or incorrect operation.
All electrical work must be performed by a licenced technician, according to local regulations and the instructions given in this manual.
Any lack of electric circuit or any deficiency caused by installation may result in an electric shock or fire.
Wire and connect using the desired cables securely so that any external force exerted on the cable is not imparted on to the terminal connections.
Imperfect connection and fixed may result in heating or fire.
Securely install the cover (panel) of the LM ADAPTER.
If the cover (panel) is not installed properly, dust or water may enter the unit and fire or electric shock may result.
Never modify or repair the unit by yourself.
Any deficiency caused by your modification or repair may result in an electric shock or fire. Consult with your distributor for repair.
Do not move and re-install the unit yourself.
Any deficiency caused by installation may result in an electric shock or fire. Ask your distributor or special vender for moving and installation.
Make sure that the unit is powered by a dedicated line.
Other appliances connected to the same line could cause an overload.
Make sure that there is a main power switch.
A ready accessible breaker for power source line helps reduce the risk of electric shocks.Installation of a breaker is mandatory in same areas.
If it is assumed that moisture advances into the unit, such as the time of rainy weather, do not perform any work on electric circuits.
It may become the cause of damage of a fire and the unit by an electric shock or corrosion.
• After reading this installation manual, keep it in a place where the final user can see it anytime he or she wants to it. When someone moves, repairs or uses the LM ADAPTER, make sure that this manual is forwarded to the final user.
Symbols used in the illustrations
: Indicates a part which must be grounded. : Indicates that the main switch must be turned off before servicing.
(This symbol is displayed on the main unit label.) <Color: Blue> : Beware of electric shock.(This symbol is displayed on the main unit label) <Color: Yellow> : Please pay attention to electric shock fully because this is not Safety Extra Low-Voltage (SELV)
circuit.
And at servicing,please shut down the power supply for LM ADAPTER.
Page 4
2
CAUTION
Do not install the unit where combustible gas may leak.
If the gas leaks and accumulates around the unit, an explosion may result.
Do not use in any special environment.
Using in any place exposed to oil(including machine oil), steam and sulfuric gas may deteriorate the performances significantly or given damage to the component parts.
When installing the unit in a hospital, communication station, or similar place, provide sufficient protection against noise.
The inverter equipment, private power generator, high­frequency medical equipment, or radio communication equipment may cause the air conditioner to operate erroneously, or fail to operate. On the other hand, the air conditioner may affect such equipment by creating noise that disturbs medical treatment or image broadcasting.
Do not wash with water.
Doing so may cause an electric shock or a malfunction.
Do not install in any steamy place such as bath room or kitchen.
Avoid any place where moisture is condensed into dew. Doing so may cause an electric shock or a malfunction.
Do not touch any PCB(Printed Circuit Board) with your hand or tools. Do not have dust collected on the PCB.
Doing so may cause an electric shock or fire.
Do not install in any place where acidic or alkaline solution or special spray are other be used.
Doing so may cause an electric shock or a malfuction.
Do not install in any place at a temperature of more then 43 ˚C or less than -15˚C.
It may become the cause of modification and failure.
Safety dispose of the packing materials.
Tear apart and throw away plastic packaging bags so that children will not play with them. If children play with a plastic bag which was not torn apart, they face the risk of suffocation.
Be sure to shut off the power source of the unit and all the other unit to connected to the unit before wiring.
Doing so may cause an electric shock or a malfunction.
Use only an earth leakage breaker and fuse of the specified capacity.
If no earth leakage breaker is installed, it may cause an electric shock. Using fuse and wire or copper wire with too large capacity may cause a malfunction of unit or fire.
A power-supply line and a transmission line do not band together, or are not contained in the same metal pipe.
Doing so may cause a malfunction of unit.
This appliance must be earthed.
Make sure to install a protective earth(PE) line. Do not connect the protective earth line to gas or water pipes, lightning conductors or telephone grounding lines. Improper grounding may cause an electric shock.
Wire so that it dose not received any tension.
Tension may caused wire breakage, heating or fire.
Use standard wires in compliance with the current capacity.
A failure to this may result in an electric leakage, heating or fire.
Never connect the power source to the transmission line.
Doing so may caused a malfunction or a failture.
Do not touch the switches with wet fingers.
Touching a switch with wet fingers can cause electric shock.
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
Page 5
3
1. Parts Include
2. Specifications
Verify that the following parts are appended to the product.
2-2 Environment Specifications
2-1 External View
Name
Shape
Quantity
Main Unit
Binding band
1
3
Installation manual
1
· The external interface file (XIF) is necessary for the product. Upon verifying the 16-digit program ID (PID) which is bonded on the board, please contact your dealer.
R
Detail of A
A
TB1
Power supply terminal
2-ø4.5 hole
TB2
M-NET transmission terminal
TB21
LONWORKS® transmission terminal
Unit : mm (in)
10
7.5
(5/16)
ø10(ø13/32)
4.5(3/16)
9.6
(3/8)
59.6(2 3/8)
340(13 7/16)
325(12 13/16)
60(2 3/8)240(9 1/2)
360(14 3/16)
(2-ø3/16 hole)
(13/32)
Item
Power Source Current Consumption
Dimensions Net Weight
Operation Environment
Installation Environment
Description
~ 220 - 240V (50 / 60 Hz)
50 mA (Maximum)
340 (H) x 360 (W) x 59.6 (D) mm / 13 7/16 (H) x 14 3/16 (W) x 2 3/8 (D) in
3.3 kg
Temperature
Operating Range
Storage Range
Humidity
In the metal control box
30% to 95% RH (No condensation)
-15 to 43˚C
-20 to 60˚C
Page 6
4
2-3 Connected Air Conditioning Equipment
2-4 L
ONWORKS
®
Network Specifications
* The proper communication is not obtainable when communication intervals exceed its performance,
assure sufficeint intervals. * ACK Service is recommended for the network service. * Detailed specifications for the LONWORKS®network can be found in “FT3120/FT3150 Smart Transceiver
Data Book” by Echelon Corporation.
Item Description
Connected Equipment
Number of Units LM ADAPTER can control 50 indoor units (including LOSSNAY)
Item Description
FT3150-P20 (10MHz)
Neuron CHIP
FT-X1 (Free Topology 78kbps)
Network Transformer
Performance
2.5 inputs/second
Average communication capacity
50 inputs/second (for one second)
Peak communication capacity
CITY MULTI
LOSSNAY
OA Processing Units
A-control unit (Mr.Slim)
AK-control unit (Mr.Slim)
K-control unit Room air conditioner (RAC)
Housing air conditioner (HAC) Air To Water Booster unit / Air To Water HEX unit
Dedicated Outside Air System
S series
Y series
HP series
R2 series
WY series
WR2 series
HVRF series
Model
: Supported
*1 Functions are limited. For details on each function, please consult your dealer.
Function (Monitor/Operation)
(Requires an adapter)
*1
(Requires an adapter)
: Not supported
Page 7
5
Indoor[1]-[50]
Network Variables
nv1n
nviOnOff_n
SNVT_switch
nv2n
nvoOnOff_n
SNVT_switch
nv3n
nviMode_n
SNVT_hvac_mode
nv4n
nvoMode_n
SNVT_hvac_mode
(*8)
nv5n
nviSetP_n
SNVT_temp_p
nv6n
nvoSetP_n
SNVT_temp_p
(*8)
(*9)
nv7n
nviCoolSetP_n SNVT_temp_p
nv8n
nvoCoolSetP_n
SNVT_temp_p
(*9)
(*9)
nv9n
nviHeatSetP_n SNVT_temp_p
nv10n
nvoHeatSetP_n
SNVT_temp_p
(*9)
(*9,10,11)
nv11n
nviAutoSetP_n SNVT_temp_p
nv12n
nvoAutoSetP_n
SNVT_temp_p
(*9,10,11)
nv19n
nviFanSpeed_n
SNVT_switch
nv20n
nvoFanSpeed_n
SNVT_switch
(*2,3,4)
nv21n
nviProOnOff_n
SNVT_switch
nv22n
nvoProOnOff_n
SNVT_switch
(*2,3,4)
(*2,3,4)
nv23n
nviProMode_n
SNVT_switch
nv24n
nvoProMode_n
SNVT_switch
(*2,3,4)
(*2,3,4)
nv25n
nviProSetP_n SNVT_switch
nv26n
nvoProSetP_n
SNVT_switch
(*2,3,4)
(*5)
nv27n
nviThermoOff_n
SNVT_switch
nv28n
nvoThermoOff_n
SNVT_switch
(*5)
(*6)
nv29n
nviFiltReset_n
SNVT_switch
nv30n
nvoOnTime_n
SNVT_time_hour
(*6)
nv31n
nvoSpaceTemp_n
SNVT_temp_p
nv32n
nvoAlarm_n
SNVT_switch
nv33n
nvoErrCode_n
SNVT_count
nv34n
nvoErrAdrs_n
SNVT_count
nv35n
nvoThermoSt_n
SNVT_state
nv36n
nvoThermo_n
SNVT_switch
nv38n
nvoIcMdlSize_n
SNVT_count
nv39n
nvoGroupNo_n
SNVT_count
(*7)
Notes
*1: “n” of the network variable shows M-NET address of indoor units. *2: It may be unable to be used by the system configuration of indoor units. *3: It is possible to use with an “MA or ME” remote controller. *4: For the use of this function, turn ON the switch(SW1-1) on LM ADAPTER.(Factory setting “OFF”) *5: For the use of this function, turn ON the switch(SW1-8) on LM ADAPTER.(Factory setting “OFF”) *6: For the use of this function, turn ON the switch(SW1-4) on LM ADAPTER.(Factory setting “OFF”) *7: It is possible to use with other system controller. *8: This function is available only for the conventional indoor units which don't support the dual setpoint.
*9: These functions are available for the indoor units which support the dual setpoint. *10: This function is available for the DOAS was manufactured in October, 2012 or later, when it uses with the DOAS. *11: This function is available when the auto mode should be controlled by single set point like the conventional one.
Group Number
Model Code
Thermo On/Off State
Thermo On/Off State
Local Prohibit On/Off
Local Prohibit Mode
Local Prohibit SetPoint
Error Address
Error Code
Alarm State
Indoor Temperature State
Filter Sign
Thermostat Off
On/Off
Mode
Set Point from network
(Both cool and heat)
Set Point from network
(cooling)
Set Point from network
(heating)
Set Point from network
(auto)
Fan Speed
2-5 Network Variable Specification
The following are applied to the CITY-MULTI type indoor unit of the Multiple split type air conditioners CITY MULTI. When Mr.SLIM, LOSSNAY, or Air To Water is used, please refer to the “Network Variable Specification” in details. Please contact your dealer to obtain the XIF file and the Network Variable Specification.
Page 8
3. Installation
<Notes>
Prepare the following prior to installing the unit.
Read and understand “Safety Precautions ” before performing the installation.
3-1 Locally Procured Parts
6
Contents
Power wire and ground wire
M-NET transmission wire
Screw To install the main body, prepare four M4 screws which are suitable for the installation area.
Use a breaker with a contact distance of 3mm or more.
Main Power Switch (Circuit Breaker)
Locally procured parts
Use sheathed vinyl cord or wire. Wire type
………
Wire should not be lighter than ordinary PVC sheathed flexible cord IEC 60227 (designation 60227 IEC 53) Wire size
………
0.75mm
2
to 1.25mm2 (AWG18 to 16)
Use the sheathed vinyl cord or wire. Wire type
………
CPEVS, CVVS or equivalent" Wire size
………
Solid wire : ø1.2mm to ø1.6mm
Twist type : 1.25mm
2
to 2mm2 (AWG16 to 14)
Use the wire which is recommended by Echelon Corporation. For details, refer to “FT3120/FT3150 Smart Transceiver Data Book”. For reference, Cable Types and Typical Parameters.
L
ONWORKS
®
Network
transmission wire
Cable type
Breaker for wiring
Breaker for Current Leakage
3A
3A 30mA
0.1 sec or less
Wire
dia /AWG
Rloop
/km
C
nF/km
Vprop % of C
Belden 85102, single twisted pair, standed 19/29, unshielded, 150˚C
Belden 8471, single twisted pair, standed 19/29, unshielded, 60˚C
Level IV 22AWG, twisted pair, typically solid & unshielded
JY(St) Y 2X2X0.8, 4-wire herical twist, solid, shielded
TIA568A category 5 24AWG, twisted pair
If a shielded cable is used, the shield should be connected to earth ground via a single 470k, 1/4 W, ≤10%, metal film resistor to prevent static charge build-up.
28
28
106
73
168
56
72
49
98
46
62
55
67
41
58
1.3mm/16
1.3mm/16
0.65mm/22
0.8mm/20.4
0.51mm/24
Outdoor unit
TB7 TB3
Outdoor unit
TB7 TB3
LM ADAPTER
TB21 TB2
M-NET transmission line (Centralized control line)
M-NET transmission line (Indoor / outdoor transmission line)
M-NET transmission line (Indoor / outdoor transmission line)
LONWORKS® network transmission line
Page 9
7
3-2 Installation Method
• LM ADAPTER is not waterproof type.
• LM ADAPTER shall be installed in a control panel box (steel : thickness 1 mm (3/64 in) or more). Please prepare the control panel box in consideration with installation space as shown in the Fig. (Install in an area capable of withstanding a 3.3 kg load.)
The unit shall be also installed in vertical direction only indicated by arrow making on the cover as shown in the
Fig.
• Use M4 screws as shown in Fig. below to fix the product.
To prevent the product from falling, make sure to fix at four places.
UP
Unit : mm (in)
20
20
(13/16)(13/16)
(13/16)
20
(13/16)
20
Installation space
Page 10
8
3-3 Wiring Methods
Use wire clamps provided to secure the wires and prevent external force from being conveyed by the wire to the wire connections. * External force could cause deformation or damage to the terminal blocks.
Use a small screwdriver to connect diameter 0.2 to 2.5 mm2(AWG24 to 12) cable for terminal block (TB21) on the unit. Tightening torque is 0.5 to 0.6 Nm. Up to two wires can be connected to one terminal block.
Binding band
20mm
(13/16 in)
80mm (3 3/16 in)
8mm (5/16 in)
For LONWORKS®transmission wire
SAUPB
N
L
P.B.
L.B.
4
LON TB21
31
CN405
CN65
CN45
CN32
CN21
CN71
CN31
CN33
CNS3
CN605
CNL12
CN702
TB21
2
Connect LONWORKS®signal wire to “1”, “2” or “3”, “4” of signal wire terminal block (TB21).
• TB21-“1” and “3” as well as “2” and “4” of TB21 are connected inside the circuit board.
Connect the power supply wires and grounding wire to “L”, “N” and “grounding” of terminal block (TB1).
Connect M-NET signal wire to “A” and “B” of terminal block (TB2).
• Connect the M-NET transmission wire to transmission terminal block (TB7) of the centralized control.
Attach the appended binding band to the power wire and transmission wire, and fasten it, positioning the area at inner side than the wire clamp. Make sure that the ground wire is longer than the other wires.
Note1
Binding band
Grounding wire
Power wire 35mm (1 3/8 in ) M-NET 20mm (13/16 in )
For power wire and M-NET transmission wire
Note1
Note1
Note1
Page 11
9
P.B.
L.B.
TB1
PE
L N
Breaker 3A
Unit Body
Unit Body
CN31
313
AC250V 2A F
ZNR2
F
1
T2
CN33
DSA1
ZNR1
Unit Body
7
3
1 5
CN71
SWL (Service Switch)
(Service
LEDL LED)
1 3
4
3
2
1
5 6
CN45
T1
CN65
2
1
CN21
3
1
CN32
1 2 3 4
CNL12
CN605
5
4
3
2
1
LED402 (5VM)
LED502 (3150RST)
6
4
3
2
1
M-NET Power Supply
CN40
(WDT)
LED009
LED201
CN41
(18007RST)
SW71 (Termination Switch)
12
ON
OFF
312
TO M-NET transmission line (Centralized control line)
CNS3
AB
TB2
13
CN405
CN702
1 2
Unit Body
LONWORKS® transmission line
TB21
S
12
4
SW4
101
OFF
ON
OFF
ON
SW2
SW1
16
SW3
61
ON
OFF
0
1
5
2
3
4
6
7
8
9
0
1
5
2 3
4
6
7
8
9
SWU1
(1st digit)
SWU2
(2nd digit)
LED001
LED002
LED003
LED004
(Wink)
Power supply
220-240V~/N 50/60Hz
3-4 Electrical Wiring
Transformer
Switch Function selection
M-NET address switch
Termination selection switch (
LONWORKS
®
)
SYMBOL EXPLANATION
Power circuit boardP.B
L.B LM ADAPTER main board
F
SWU1, 2
Service switch (
LONWORKS
®
)SWL
Fuse AC250V 2A F
NAMESYMBOL
SW1, 2, 3
T1.2
SW71
LONWORKS
®
transmission line
Grounding terminal
M-NET transmission line
Power source
LED
TB21
Power Supply switch connectorCN40/CN41
TB2
TB1
Maintenance LED Use LED001 as Wink (
LONW
ORKS
®
) at SW2-1 ˜ 6 OFF
LED001 ˜ 004
Status LED
LED009/201/502/402
Service LED (LONWORKS® )LEDL
NAMESYMBOL
Terminal block
Service Switch (SWL)
Service LED (LEDL)
Power supply terminal
LM ADAPTER main circuit board
LON connection terminal
M-NET terminal
Power supply circuit board
Power supply transformer
[ Top Cover Removed ]
Service Switch (SWL)
Service LED (LEDL)
[ Exterior of LM ADAPTER ]
Page 12
10
Note: Function switch setting of LM ADAPTER is different according to the management item of the
equipment connected with LONWORKS®. Carefully set the system.
SW1-1
ON
OFF
Function switch of local prohibit
local prohibit effective local prohibit invalidity
ON
OFF
LOSSNAY is operated from
LONWORKS
®
LOSSNAY interlocks with the indoor unit
Switch name Function
OFF
Factory
setting
Operation local prohibit nv input from
LONWORKS
®
becomes Effective when switch is ON.
Operation local prohibit nv input from
LONWORKS
®
becomes invalid when switch is OFF.
Note
SW1-5 Function switch
of LOSSNAY
SW1-7 Function switch
of SNVT_switch
OFFPlease turn on the switch when LOSSNAY
is operation from
LONWORKS
®
. Please turn off the switch when LOSSNAY interlocks with the indoor units.
ON
OFF
Enable forced thermo OFF Disable forced thermo OFF
SW1-8 Select enable/
disable forced thermo OFF
OFFWhen “ON”, the forced thermo OFF nv
input/output are enabled. When “OFF”, the forced thermo OFF nv
input/output are disabled.
When “ON”, the LMAP collective alarm detection maximum time become the same as the LMAP03U (60 minutes)
Before power supply
Before power supply
ON
OFF
Enable Disable
SW1-4 Reset filter sign/
Select enable/ disable operation duration
OFF Before power
supply
Before power supply
Before power supply
Before power supply
ON
OFF
ON(test run) is transmitted to the indoor units
OFF is transmitted and indoor units stop test run
SW1-9 Indoor units
test run switch
OFF Always
ON
OFF
Enable
Disable
SW1-10
LMAP collective alarm detection time switch
OFF Before power
supply
ON
OFF
Connected cancellation command is transmitted to the indoor units
None
SW3-2 Initialization
switch of air conditioner units
OFF Always
SW1-3
ON
OFF
Indoor temperature state interval switch
Transmission interval (1minutes or more)
Transmission interval (10 minutes or more)
OFF
SW1-2
ON
OFF
Used together with system controller switch
used together with system controller not used together with system controller
OFF
Set timingSW
*number of indoor units that should be connected is 30 or less
When “ON”, the reset filter sign input and the operation duration output are enabled.
When “OFF”, the reset filter sign input and the operation duration output are disabled.
ON
OFF
SNVT Standard Original
OFF Before power
supply
When “ON”, the specifications of the nv using the SNVT_switch comply with the SNVT Standards.
When “OFF”, the nv using t
he SNVT_switch
has original specifications.
SW1-6 Single set point
mode switch
ON
OFF
Enable single set point mode
Enable dual set point mode
OFF Before power
supply
When “ON”, whole M-NET system operates in single set point mode. For example, if BMS does not support dual set point, apply this switch.
When “OFF”, the LMAP is detected as a device supports the dual set point.
LED001 , LED002 LED003 , LED004
( )
LON connection terminal
Neuron Chip
[ LM ADAPTER Main Circuit Board (L.B) ]
LON LED (LED502)
M-NET address switch (Factory setting: 47)
Maintenance LED
Function selection switch (Factory setting: All OFF)
CPU power supply LED (LED009)
M-NET LED (LED201)
LON transformer: FT-X1
CN 41 M-NET transmission power supply off (Factory setting)
CN 40 M-NET transmission power supply on
Power supply LED (LED402)
Host CPU
EPROM (Program ID)
Neuron ID
Explanation of function switch
Page 13
11
4. System Settings
<Notes>
This chapter only describes the system settings of this product. For the installation work and electrical work, refer to the last chapter “3. Installation”.
Read and understand the contents of Chapter 1 “Safety Precautions” before performing the installation.
4-1 If not used together with system controller. (MELANS)
The system setting is different depending on the system configuration connected. Check the system configuration.
1. When the system controllers are not used together.
2. When the system controllers are used together.
SW1-2 [OFF]
TB2
CN41
CN41
CN40
E
TB7
TB3
TB7
TB3
OC
OC
SW2-1 [OFF]
SW2-1 [OFF]
M-NET transmission line (Centralized control line)
as is
Factory setting
247
CN41
OFF OFF
CN41
M-NET transmission line (Indoor/outdoor transmission line)
M-NET transmission line (Indoor/outdoor transmission line)
as is
CN41
M-NET address of LM ADAPTER LM ADAPTER power switch connector Combined switch for LM ADAPTER / system controller OC central control (SC) on/off switch OC power supply connector
SWU2, 1 [201 to 250] CN41 to CN40 (supplies power) SW1 - 2 [OFF] (Not used together with system controller) SW2 -1 [OFF] (No central control) CN41 as is (power not supplied)
Iteam
Setting
OC : Outdoor Unit
: Switch Position
LM ADAPTER
Switch the short-circuit connector from CN41 to CN40.
M-NET address 201 to 250 [factory setting 247] (* Setting of position 100 not required.)
(Note 1)Change the LM ADAPTER power supply switch connector CN41 to CN40.
The LM ADAPTER can not supply enough power for the MN converter.
(Note 2)When connecting LOSSNAY, settings must be made in the LM ADAPTER.
1) Do not sequence LOSSNAY to the air conditioner. (Independent LOSSNAY) Or when operation is to be controlled from
LONWORKS
®
(BMS etc.) connected to the LOSSNAY remote controller.
LOSSNAY selection switch. (SW1-5)[ON]
2) When sequencing LOSSNAY to the air conditioner (sequenced LOSSNAY), and not controlling operation from
LONWORKS
®
.
(BMS etc.) LOSSNAY selection switch. (SW1-5)[OFF] When sequencing LOSSNAY to the air conditioner, the indoor unit and LOSSNAY sequence must be registered from the remote controller.(Refer to the remote controller installation manual for details on registering.)
(Note 3)When changing the system configuration, such as the M-NET address, always carry out the following steps.
1) Turn the LM ADAPTER service switch (SW2-1) [ON]. Change the LM ADAPTER system information delete switch (SW3-2) from [OFF] to [ON].
2) When erasing the system information, the maintenance LED “System Information Erase LED (LED001)” will turn ON.
3) When the system information has been erased, the maintenance LED “System Information Erase LED (LED001)” will turn OFF, and the maintenance LED “System Information Erase Complete LED (LED002)” will turn ON.
4) Turn the LM ADAPTER service switch (SW2-1) [OFF]. Change the LM ADAPTER system information delete switch (SW3-2) from [ON] to [OFF].
5) Turn the LM ADAPTER power OFF.
6) Make changes to change the unit system.(Addition of indoor unit, change of M-NET address, change of group, etc.)
7) To change the LM ADAPTER M-NET address and settings, carry out the changing work.
8) Turn the LM ADAPTER power ON.
(Note 4)Refer to the “System Design and Construction Manual” for the outdoor unit for details on the M-NET wiring length. (Note 5)Set the M-NET address so that it is not duplicated with other units.
Shielded line ground
ON
OFF
12345678910
123456789
12345678910
10
ON
OFF
ON
OFF
Page 14
12
4-2 If used together with system controller.
(Note 1) When the LOSSNAY is interlocked, it should be configured from the shared system controller. (Note 2) When changing the system configuration, such as the M-NET address, system controller being shared
must be registered or changed.
(Note 3) Refer to the “System Design and Construction Manual” for the outdoor unit for details on the M-NET wiring length. (Note 4) Set the M-NET address so that it is not duplicated with other units. (Note 5) When setting the shared system controller, configure LM ADAPTER as a system controller in each group.
SW1-2 [ON]
E
SW2-1 [ON]
Shielded wire ground
Centralized controller
(System controller)
Power supply unit
M-NET transmission line (Centralized control line)
M-NET address 201 to 250 [factory setting 247] (* Setting of position 100 not required.)
Factory setting
247
CN41
OFF OFF
CN41
M-NET address of LM ADAPTER LM ADAPTER power switch connector Combined switch for LM ADAPTER / system controller OC central control (SC) on/off switch OC power supply connector
SWU2, 1 [201 to 250] CN41 as is (power not supplied) SW1 - 2 [ON] (Used together with system controller) SW2 -1 [ON] (Central control) CN41 as is (power not supplied)
Item
Setting
ON
OFF
12345678910
ON
OFF
12345678910
ON
OFF
12345678910
SW2-1 [OFF]
as is
OC : Outdoor Unit
: Switch Position
M-NET transmission line (Indoor/outdoor transmission line)
M-NET transmission line (Indoor/outdoor transmission line)
LM ADAPTER
TB2
CN41
CN41
TB7
TB3
TB7
TB3
OC
OC
as is
as is
CN41
Page 15
13
4-3 Initialization Settings of LONWORKS®Network
(2) System Specifications
(1) Termination of LONWORKS
®
• Up to 64 FT-X1 Transformers and FT Smart Transceivers are allowed per network segment.
• LPT-10 transceivers may be used on network segments with FTT-10A transceivers and FT Smart Transceivers, but are subject to additional constraints, particularly on distance.
See the LONWORKS®LTP-10 Link Power Transceiver User's Guide for more information.
• The average temperature of the wire must not exceed +55˚C, although individual segments of wire may be as hot as +85˚C.
Maximum bus length
Belden 85102 Belden 8471 Level IV 22AWG
Units
JY(St)Y 2X2X0.8 TIA Category 5
2700(8,858) 2700(8,858) 1400(4,593) meters (feet)
900(2,953) 900(2,953)
Maximum node-to-node distance
Belden 85102 Belden 8471 Level IV 22AWG
Units
JY(St)Y 2X2X0.8 TIA Category 5
Maximum total wire length
500(1,640) 400(1,312) 400(1,312) meters (feet) 320(1,050)
250(820)
500(1,640) 500(1,640) 500(1,640) 500(1,640) 450(1,476)
The free topology transmission specification includes two components which must both be met for proper system operation. The distance from each transceiver to all other transceiver and to the termination (including the LPI-10 termination, if used) must not exceed maximum node-to-node distance. If multiple paths exist, e.g., a loop topology, then the longest path should be used for the calculations. The maximum total wire length is the total amount of wire connected per segment.
For details, refer to “FT3120/FT3150 Smart Transceiver Data Book” of Echelon Corporation. For reference, the system specifications and Transmission specifications are described.
(3) Transmission Specifications
Doubly-Terminated Bus Topology Specifications
Free Topology Specifications
The product can be set with the termination of LONWORKS®.
SW71-1
OFF
ON
OFF
ON
SW71-2
OFF OFF
ON ON
Termination Resistance Value
– ( Factory setting)
100 ± 1%
50 ± 1%
Termination Switch (SW71)
For details, refer to “FT3120/FT3150 Smart Transceiver Data Book” of Echelon Corporation. For reference, the system specifications and Transmission specifications are described.
Page 16
14
5. Confirming Operation
5-1 Flow of Onsite Adjustments
……
……
……
Test run by unit and local remote controller
Refer to 5-4 (1)
Test run by LM ADAPTER
Refer to 5-4 (2)
Test run from the
LONWORKS
®
network
Refer to 5-4 (3)
There are the following two methods to perform a test run from the
LONWORKS
®
network.
Test run by
LONWORKS
®
tools
If the bindings to other machines have not been performed, use the
LONWORKS
®
tools as described by the procedure
given in 5-4 (3) and confirm that operation can be performed from a
LONWORKS
®
network.
Test run from building management system
If the bindings to other machines have been performed, or if you do not have the
LONWORKS
®
tools, follow the building
management system test run procedure to confirm that operation can be performed from the
LONWORKS
®
network.
5-2 Preparation Material for Onsite Adjustments
(1) Preparation material for onsite adjustment
Tester Onsite adjustment tools (
LONWORKS
®
tools, M-NET onsite adjustment tool)
Please consult your dealer for details.
* LONWORKS
®
tools
The
LONWORKS
®
tools are listed below. Contact your dealer for more information.
• LONWORKS
®
network interface (U-10 USB Network Interface (FT-10) etc.)
• Cables for the above interface
• nodeutil (Free software from Echelon)
* M-NET onsite adjustment tool
(2) Reference materials
LM ADAPTER Installation Manual LM ADAPTER Network Variable Specifications LM ADAPTER Technical Manual
5-3 Preparation and Settings
(1) Perform the previous operations described in Chapter 3 “Installation”, Chapter 4 “System Settings”. (2)If being used together with system controller, perform the installation and electrical installation for system controller. (3) Perform the initial processing for the LM ADAPTER.
Turn on the power supply for LM ADAPTER.
If being used together with system controller, perform the initialization settings. The indoor units will be idle until the LM ADAPTER initialization has been completed (LED002 goes out).
* This requires approximately 5 to 10 minutes.(If being used together with system controller, it will be approximately 3 minutes after the completion of the initialization settings.) If you connect the power to the LM ADAPTER before connecting the power supply to the indoor units, the LED002 might stay lit. If this case arises, reset the power supply to the LM ADAPTER.
Confirm that the LM ADAPTER’S maintenance LED (LED003, 004) are not lit.
* If the LM ADAPTER’S maintenance LED (LED003, 004) are lit, refer to the next chapter “6. Troubleshooting”.
(Note 1) Always refer to the previous chapter “4. System Settings” before changing the system configuration, such as the M-NET address. * After confirming the above details, always refer to the following section “ 5-4 Test Run ” and make confirmations
with trial operations. (Note 2) Turn all of the switches in the service switch (SW2) [OFF] to confirm the ON/OFF status of the above maintenance
LED (LED002, LED003 and LED004).
(4) After confirming the above, always perform the test run as described in the next section “5-4. Test Run”.
Maintenance Tool for .NET (Ver. 5.08 or later)
1
2
1 2
3
4
Page 17
15
5-4 Test Run
Perform the test run according to the test procedure of the test run check list. (1) Test run of indoor units by local remote controller
* Confirm that all indoor units are running normally.
(2) Test-operation of the indoor unit from LM ADAPTER
Turn on SW1-9 of LM ADAPTER.
Finally turn off SW1-9, and verify that all indoor units are stopped.
* If there is even one indoor unit that is not running, the LM ADAPTER may not correctly recognize the indoor unit. Refer to the next chapter “ 6. Troubleshooting ”.
(3) Test-operation of the indoor unit from
LONWORKS
®
If there is any tool which corresponds to LONWORKS
®
,verify that it can be operated from LONWORKS
®
network according to
the follwing procedure.
Set the LM ADAPTER to the Configured.
If the LM ADAPTER has been already bound to a BMS (Building Management System) (the service LED is not ON), don't apply any new binding.
During the test operation, use “ nv1n Reguest ON/OFF ” to verify that the indoor unit can be operated. For details of “ nv1n Reguest ON/OFF ” , refer to the following.
nv1n Request ON/OFF command input
This input network variable is used to allow On Request or Off Request of the indoor unit to be changed via the network.
When the ventilator (LOSSNAY) Interlocks with the indoor unit, it becomes the same operation as the indoor unit.
Valid range (SW1-7 OFF)
value field: not used
state field: 0 = indoor unit or ventilator unit is “ OFF ” state field: 1 = indoor unit or ventilator unit is “ ON ”
: Else = Indoor unit or ventilator unit is “ OFF ”
_n: ------------ Indoor unit address (M-NET)
* Refer to the index in the table below when performing update and poll (confirm state) of the network variable for the
LONWORKS
®
tools (nodeutil etc.).
ON/OFF Reguest
ON/OFF run state
nv name nv name
Finally set the LM ADAPTER to the “ Unconfigured ”, and end the test operation.
Contact your dealer for details on trial operation from the
LONWORKS
®
network.
Perform the test run of the indoor units by using the local remote controller or system controller.
1
1
1
2
2
3
index
1 2
49 50
51 52
99
100
nviOnOff_001 nviOnOff_002
nviOnOff_049 nviOnOff_050
nvoOnOff_001 nvoOnOff_002
nvoOnOff_049 nvoOnOff_050
index
network input SNVT_switch nviOnOff_n;
::::
Page 18
16
6. Troubleshooting
(WDT)
(5VM)
LED009
Item
ON
Normal state Contents to check
Check the Main Power Switch to the LM ADAPTER is not turned off, any connectors (CN605, CN65, CN32, CN33, CN31, CN71) are disconnected and for a blown fuse (F).
LED402
ON
Check the Main Power Switch to the LM ADAPTER is not turned off, any connectors (CN405, CN45, CN21, CN31, CN71) are disconnected and for a blown fuse (F).
(3150RST)
LED502
OFF
(18007RST)
LED201
OFF
Service LED
It blinks when it is not binding. At this time, operation is unavailable from the network side from L
ONWORKS
®
.
Binding the equipment which corresponds to L
ONWORKS
®
network.
LED002 OFF
If it is ON when the dip switch SW2 are all OFF, the LM ADAPTER is incompletely initialized. Wait for 15 minutes after the power supply is turned on (Until the initializing process is completed).
LED004 OFF
If it is ON when the dip switch SW2 are all OFF, there may be trouble at the indoor unit. Check the connection and setting of all indoor units.
CN40/41
If the power supply unit is connected, insert the jumper connector to CN41. If the power supply unit is not connected, insert the jumper connector to CN40.
SW71
L
ONWORKS
®
The switch sets the termination of LONWORKS®
network.
According to the system design of L
ONWORKS
®
network, check whether it is properly
set or not.
M—NET Address switch SWU1, SWU2
If system controller is used, check whether M-NET address is overlapped or not. Initial setting of LM ADAPTER is 247.
Dip switch SW1, SW2, SW3
Check whether system controller is present or not (SW1-2), and whether the independent/combined LOSSNAY (SW1-5) is properly set or not. Moreover, verify that all other switches are all off.
LED003 OFF
If it is ON when the dip switch SW2 are all OFF, check the setting of the switches and so on, and turn on the power supply again.
The LM ADAPTER’S initial processing has not been completed. Wait for 15 minutes after the power supply is turned on (Until the initializing process is completed).
The LM ADAPTER’S initial processing has not been completed. Wait for 2 minutes after the power supply is turned on (Until the initializing process is completed).
6-1 Abstract
If LM ADAPTER does not properly operate, first check the following contents.
Page 19
17
(1)The LM ADAPTER is not completely
initialized.
(2)Setting on M-NET side is not properly
completed.
(3)If system controller is used together
LM ADAPTER is not registered to system controller.
Turn OFF all SW2. After verifying that LED002 is OFF, test the operation again.
Verify that the test operation of the air conditioner is properly completed. Verify that M-NET transmission line is properly connected. In system controller, register LM ADAPTER as the sub system controller.
Error content Cause Checking method and remedy
(1)The LM ADAPTER is not completely
initialized.
(2)Setting on M-NET side is not properly
completed.
(3)If system controller is used in
combination, LM ADAPTER is not registered to system controller.
(4)The independent/interlocked
LOSSNAY of LM ADAPTER is not set.
Refer to 2-(1).
Refer to 2-(2).
Refer to 2-(3).
Turn on SW1-5 of LM ADAPTER, and reset the power supply.
(1)The LM ADAPTER is not completely
initialized.
(2)Setting on M-NET side is not properly
completed.
(3)If system controller is used in
combination, LM ADAPTER is not registered to system controller.
(4)L
ONWORKS
®
network transmission
line is not properly connected.
(5)The termination of L
ONWORKS
®
network is not properly set.
(6) Binding of L
ONWORKS
®
network is
not properly ended.
Refer to 2-(1).
Refer to 2-(2).
Refer to 2-(3).
Check for disconnection on TB21, short-circuit and wire breakage on the network wire and so on.
Verify that the termination of LONWORKS® network is properly set according to the system design.
Apply the binding again.
Even if it is operated with the remote controller/system controller, it is not informed to the host on LON side.
2
1
No.
3
4
LED002 is ON
(1) It takes time for the initial processing to complete (normal).
(2)Setting on M-NET side is not properly completed.
(3) M-NET power supply switch has not been set.
(4) The power supply to the air conditio­ ner unit is disconnected.
It can take about 15 minutes for the initial processing to complete. Wait until the initial processing finishes.
Verify that the test operation of the air conditioner is properly completed. Verify that M-NET transmission line is properly connected.
Follow the instructions in “4. System Setting” and check the power supply unit setting, and the LM ADAPTER power supply switch connector setting.
Verify
that the air conditioner unit power supply is not disconnected. * Use a tester to check the voltage of the terminal (TB2). DC17-30 V
The air conditioner unit does not operate even by performing a test run using the LM ADAPTER’S
switch
SW1-9.
The LOSSNAY unit does not operate even by performing a test run using the LM ADAPTER’S switch SW1-9.
6-2 Troubleshooting
Page 20
18
(1)The LM ADAPTER is not completely
initialized.
(2)Setting on M-NET side is not properly
completed.
(3)If system controller is used together
LM ADAPTER is not registered to system controller.
(4)The independent/interlocked
LOSSNAY of LM ADAPTER is not set.
(5)L
ONWORKS
®
network transmission
wire is not properly connected.
(6)The termination of L
ONWORKS
®
network is not properly set.
(7) Binding of L
ONWORKS
®
network is
not properly ended.
Refer to 2-(1).
Refer to 2-(2).
Refer to 2-(3).
Refer to 3-(4).
Refer to 4-(4).
Refer to 4-(5).
Refer to 4-(6).
Error content Cause Checking method and remedy
Independent/interl ocked LOSSNAY can not be operated from the LON side.
(1)The LM-ADAPTER is not completely
initialized.
(2)Setting on M-NET side is not properly
completed.
(3)If system controller is used together
LM ADAPTER is not registered to system controller.
(4)L
ONWORKS
®
network transmission
wire is not properly connected.
(5)The termination of L
ONWORKS
®
network is not properly set.
(6) Binding of L
ONWORKS
®
network is
not properly ended.
Refer to 2-(1).
Refer to 2-(2).
Refer to 2-(3).
Refer to 4-(4).
Refer to 4-(5).
Refer to 4-(6).
Air conditioner can not be operated from the LON side.
5
6
7
8
Prohibit local remote controller operation cannot be set from the LON side.
Forced thermo OFF cannot be set from the LON side.
(1) Perform the LM ADAPTER’S prohibit local remote controller operation setting.
(1) Perform the LM ADAPTER’S forced thermo OFF setting.
Turn on SW1-8 of LM ADAPTER, and reset the power supply.
Turn on SW1-1 of LM ADAPTER, and reset the power supply.
Page 21
19
6600
6601
6607
• If it has been confirmed that a unit with the same M-NET
address is transmitting.
• When discrimination of the polarity of the M-NET transmission wire.
If there is no response (ACK) from the recipient after a
transmission.
• If there are two or more units with the same M-NET address at the unit and controller.
• Interrupted power supply, Connectors (CN405, CN45, CN21, CN71).
Damage to transformer
(T2).
• Interrupted power supply for M-NET transmission wire.
If recipient of transmission
is LM ADAPTER.
• Defect in transmission line (TB2)between LM ADAPTER.
• Interrupted power LM ADAPTER power supply (TB1).
• Blown fuse (F1) in LM ADAPTER
disconnection on the loose connector (CN605, CN65, CN32, CN33, CN31).
Damage transformer in
LM ADAPTER
(T1, T2).
Damage circuit board (L.B, P.B).
• Check that there are no duplicate addresses. After correcting problem, reset power supply.
• Check for defects. Once corrected, reset the power supply.
• Check these areas. After correcting problem, reset power supply.
Error code
Error content Symptom Cause
Checking method and remedy
M-NET duplication error
M-NET polarity not set error
No ACK error
7302
7303
7305
Display of trouble
M-NET remote controller, MA remote controller, system controller
M-NET remote controller, MA remote controller, system controller
M-NET remote controller, MA remote controller, system controller or building control system
M-NET remote controller, MA remote controller, system controller
M-NET remote controller, MA remote controller, system controller
M-NET remote controller, MA remote controller, system controller
M-NET connection error (no connection to indoor unit or LOSSNAY unit)
M-NET connection error (no connection to master system controller)
DIP SW1-2 is OFF and the system con
troller is connected. DIP SW1-2 is ON and the system controller is not connected.
Initialization error
Could not connect to any indoor units or LOSSNAY units.
Initialization of the LM ADAPTER failed.
Reset the power supply. If the same error occurs again, the controller is faulty.
Damage in LM ADAPTER.
• M-NET transmission cable is not connected.
• Power supply is not connected to M-NET transmission cable.
• The DIP SW1-2 setting is different to the system configuration.
• Power supply is not connected to indoor unit or LOSSNAY unit.
• M-NET transmission cable is not connected.
• Power supply is not connected to M-NET transmission cable.
• Check these areas. After correcting problem, reset power supply.
• Check these areas. After correcting problem, reset power supply.
6-3 Error code list
Page 22
20
Test run check sheet
ON OFFON OFF
Operation from LONW
ORKS
®
network
Confirmation of operating status
Error
Operation
mode
Set
temperature
ON OFF
Operation
mode
Set
temperature
temperature
Intake
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
* Check the building control system functions beforehand and check off each operation as it is tested. For the check list, you can either copy this sheet or make a new check list based on this sheet.
Unit
address
MEMO
Test run of units (SW1-9)
Appendix : Test run check sheet
Page 23
Page 24
WT07000X01
HEAD OFFICE Authorized representative in EU: MITSUBISHI ELECTRIC EUROPE B.V.
HARMAN HOUSE, 1 GEORGE STREET
, UXBRIDGE, MIDDLESEX UB8 1QQ, U.K.
: TOKYO BLDG. , 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
This product is designed and intended for use in the residential,
commercial and light-industrial environment.
The product at hand is based on the following EU regulations:
Low Voltage Directive 2006/95/EC
Electromagnetic Compatibility Directive
2004/108/EC
Restriction of Hazardous Substances
2011/65/EC
Loading...