Mitsubishi Electronics LMAP03U-E User Manual

Version3.04 2003.02.05
AIR CONDITIONER INTERFACE
LM ADAPTER
MODEL: LMAP03U-E
Network Variables Specification
03_NVspec_ver304e
Specification P.2 - 3
1
2
SNVT Table P.10 - 13
3
Network Variables P.14 - 35
4
Configuration Properties P.36 - 48
5
Node Object P.49
6
Appendix A: Fahrenheit conversion of Centigrade data
ProgramID: 9-000A2-0076-0003-03
XIF: 0303lm30.xif
*1.LONWORKS® , and the Echelon logo are trademarks of Echelon   Corporation registered in the United States and other countries.
*2.This product is not LONMARK product.
*3.Please contact the dealer about obtaining XIF. MITSUBISHI ELECTRIC CORPORATION
*4.XIF is of operation check settled in LonMaker for Windows 3.0(SP2). AIR-CONDITIONING & REFRIGERATION SYSTEMS WORKS
WSN02-2124 - 1 -
MITSUBISHI ELECTRIC
1.Specification
.
y
m
S
n
y
S
e
h
l
)
e
n
y
l
)
e
d
Y
n
y
s
s
Y
s
.
d
t
.
n
y
V
s
s
n
s
1-1.Object Model
These specifications apply to the communication interface used to connect the LonWorks network and the Mitsubishi Electric M-NET compatible products.
<Model name>
1. Multiple split type air conditioners CITY MULTI
2. Split-type air conditioners Mr.SLIM
NOTE:A-M Converter(PAC-SF48MA-E) is necessary.
3. Heat recovery ventilators LOSSNAY
NOTE:LOSSNAY Adapter(PZ-53ADF-E) is necessary.
1-2.Explanation of Function Setting
This product requires a function setting switch because of the connected model, system configuration and control functions.
SW NO. switch name Function Note
SW1-1
SW1-2
SW1-3
SW1-4
SW1-5
SW1-7
SW1-8
SW1-9
SW3-2
Function switch of local prohibit ON local prohibit effective
Used together with MELAN switch
Indoor temperature stat interval switc
Reset Filtersign/Select enable/disable operation duration
Function switch of LOSSNAY ON
Function switch of SNVT_switch ON SNVT standard
Select enable/disable force thermostat OFF
Indoor units test run switch ON
Initialization switch of the air conditioners units
Notes:
Always use together with the local remote controller or system controller.
*1:
*2: Always register the LM ADAPTER as a system controller when using together with the system controller. *3: The functions used with the LM ADAPTER are changed. The air conditioner and LOSSNAY cannot be set to interlock with the LM ADAPTER.
Set with the system controller or local remote controller.
*4: Carry out an instruction input at the unit of the lowest address unit in the same group. The instructions to other units are disregarded.
However, a state output is output for every unit. Forced thermostat OFF needs an instruction input for every unit. *5: Input the same instructions to all the units in the same group. *6: Make a monitor interval into 1 minute, and when you use both the functions of "local prohibit", and the "forced thermostat OFF", give 25 sets or less.
Operation local prohibit NV input from L
ONWORKS becomes Effective when switch ON
OFF local prohibit ineffective
ON used together with MELANS *4 OFF
not used together with MELAN
*2 OFF
*5 Transmission interva
ON
(1minutes or more Transmission interva
OFF
(10 minutes or more
ON
effective
OFF ineffective
LOSSNAY is operate from LONWORKS. LOSSNAY interlock
*3 OFF
with indoor unit
OFF original
ON effective
OFF ineffective
ON (test run) is transmitted to the indoor unit OFF is transmitted
OFF
to the indoor unit Connected cancellatio
ON
command is transmitted to the indoor unit
OFF None
Operation local prohibit NV input fro LONWORKS becomes invalid when switch OFF
*The number of indoor units connected should b 30 or less *6
When "ON",the reset filter sign input and the operation duration output are enabled.
When "OFF",the reset filter sign input and th operation duration output are disabled Please turn on the switch when LOSSNA is operated from LONWORKS. Please turn off the switch when LOSSNA interlocks with indoor units
When "ON",the specifications of the NV using the SNVT_switch comply with the SNVT Standards.
When "OFF",the NV using the SNVT_switch ha original specifications When "ON",the forced thermo OFF NV input/outpu are enabled When "OFF",the forced thermo OFF N input/output are disabled
03_NVspec_ver304e
Factory
setting
OFF
OFF
OFF
OFF
OFF
OFF
OFF Always
OFF Always
Set timing
Before turning on the power suppl
Before turning o the power suppl
Before turning o the power suppl
Before turning on the power supply
Before turning o the power suppl
Before turning on the power supply
Before turning o the power suppl
WLN02-2124 - 2 -
1-3.Functions
v
03_NVspec_ver304e
Operation Request All Off
Request On/Off
Request Mode
Setpoint
Request LOSSNAY Mode
Request FanSpeed
Request Local Prohibit On/Off
Request Local Prohibit Mode
Request Local Prohibit SetPoint
Request Collective Local Prohibit
Request Forced Thermostat OFF
Filter Sign Reset
Time Stamp
Request Limit Temperature Setting Range
Request Simplified Locking
Monitor Emergency state
Item
n
No.
Stops the operation of all air conditioners.
nv1
The ON/OFF operation is invalid during emergency stop.
nv1n Run and stop operation.
nv3n Sets the operation mode.
nv5n Sets the temperature.
nv7n Sets the LOSSNAY operation mode.
nv9n Sets the fan speed.
nv11n Sets the local remote controller to operation prohibit (On/Off).
nv13n Sets the local remote controller to operation prohibit (operation mode).
nv15n Sets the local remote controller to operation prohibit (temperature setting).
Sets the local remote controllers of all air conditioners to operation prohibit
nv4
(On/Off, operation mode, temperature setting).
nv17n Forcibly turns the air conditioner thermostat OFF.
nv19n The run time (for filter) of air conditioner is reset.
nv12 Sets the local remote controller time.
nv13 Sets the temperature setting range of local remote controller.
Sets the local remote controller switch's simple lock, and displays the mode and
nv14
intake temperature.
nv3 Output the emergency stop state.
Description
On/Off state
Collective On/Off state
Mode state
Setpoint State
LOSSNAY Mode State
FanSpeed state
Local Prohibit On/Off State
Local Prohibit Mode State
Local Prohibit SetPoint State
Collective Local Prohibit State
Forced Thermostat OFF State
Run Time for Filter
Space Temperature State
Defrost State
Group Number
Alarm State
Collective Alarm for Indoor Unit
Collective Alarm for LM ADAPTER
Error Code
nv2n Outputs the On/Off state.
nv2 Outputs the On/Off state for all air conditioners.
nv4n Outputs the operation mode setting state.
nv6n Outputs the temperature setting state.
nv8n Outputs the LOSSNAY operation mode setting state.
nv10n Outputs the fan speed setting state.
n12n Outputs the local remote controller operation prohibit (On/Off) state.
nv14n Outputs the local remote controller operation prohibit (operation mode) state.
Outputs the local remote controller operation prohibit (temperature setting)
nv16n
state.
nv5 Outputs the local remote controller collective operation prohibit state.
nv18n Outputs the forced thermostat OFF state.
nv20n Outputs the run time (for filter) of air conditioner.
nv21n Outputs the intake temperature of air conditioner.
nv9 Outputs the defrosting state of indoor unit or outdoor unit.
nv29n Outputs the group number of the indoor unit.
nv22n Outputs the presence of air conditioner errors.
nv6 Outputs the presence of errors in all air conditioners.
Outputs the presence of communication errors between the LM ADAPTER and
nv7
air conditioner.
nv23n Outputs the presence of air conditioner errors content (error code).
Error Address
Thermo On/Off state_1 (*1)
Thermo On/Off state_2 (*1)
Model Code (*1)
Note
*1: This product does not have a charge function.
The charge (apportioning) function must be prepared separately in the master system.
WSN02-2124 - 3 -
nv24n Outputs the error source (M-NET address) when an air conditioner error occurs.
nv25n Outputs the air conditioner operation, thermostat and auxiliary heater states.
nv26n Outputs the thermostat state.
nv28n Outputs the air conditioner model code.
.Object Details
2-1.Overview
The LM adaptor has the node object, Indoor [0] and Indoor [1] to Indoor [50] objects. Each object contains the network variables
or configuration properties for all models.
Refer to each object (2.4 to 2.6) for the network variables that can be used with each model (unit).
03_NVspec_ver304e
Node Object
Object Type #0
Network Variables
Indoor[0]
Network Variables
Configuration Properties
Indoor[1]
Network Variables
・ ・ ・ ・ ・
Indoor[50]
Network Variables
Node Object
Indoor[0]
Indoor[1]
Indoor[2]
::
Indoor[50]
WSN02-2124 - 4 -
Includes network variables of Node Object. Includes collective network variables and configuration properties. Includes network variables of 1st Indoor unit. Includes network variables of 2nd Indoor unit.
Includes network variables of 50th Indoor unit.
03_NVspec_ver304e
2-2.Node Object(*1
nv1
Note
SNVT_obj_request
stencil for LonMaker:Node Object
*1:
nviRequest
Node Object
Network Variables
nv2
nvoStatus
SNVT_obj_status
WSN02-2124 - 5 -
2-3.Collective operations/monitoring and Configuration Properties(*1)
Indoor[0]
Network Variables
03_NVspec_ver304e
(*3)
(*2)
(*2)
(*2)
nv1
nv4
nv12
nv13
nv14
nviAllOff
SNVT_switch
nviAllPro
SNVT_switch
nviRmTime
SNVT_time_stamp
nviRmLim
SNVT_switch
nviRmLck
SNVT_switch
Configuration Properties
nv2
nv3
nv5
nv6
nv7
nv9
nvoAllOnOff
SNVT_switch
nvoAllOff
SNVT_switch
nvoAllPro
SNVT_switch
nvoAllAlarm
SNVT_switch
nvoAllAlarmLMAP
SNVT_switch
nvoDefrost
SNVT_switch
(*3)
nciMinOutTm Minimum Send Time (nc15)
nciStartHrtBt Send Heartbeat Start Time (nc16)
nciStartOutTm Send Start Time (nc17)
nciInitStartTm Initialize Start Time (nc18)
nciInitOutTm_1 Initialize Send Time_1 (nc19)
nciInitOutTm_2 Initialize Send Time_2 (nc20)
nciSndHrtBt_1 Send Heartbeat_1 (nc21)
nciSndHrtBt_2 Send Heartbeat_2 (nc22)
nciAnalogWidth Spacetemp Width (nc23)
nciAnlgMonTm Monitoring Time (nc25)
nciRcvHrtBt_1 Receive Heartbeat_1 (nc26)
nciRcvHrtBt_2 Receive Heartbeat_2 (nc27)
nciEffectTm_1 Effective time_1 (nc28)
nciEffectTm_2 Effective time_2 (nc29)
nciPollFetch Effective PollFetch (mc30)
nciOffline Effective Offline Mode (nc31)
nciCoolLrSetP Lower Setpoint Cooling (nc34)
nciHeatUpSetP Upper Setpoint Heating (nc35)
nciRmOpLck Local Operation Lock (nc36)
nciRmDsp_1 Local Display_1 (nc37)
nciRmDsp_2 Local Display_2 (nc38)
nciSet_1 Communication Timing (nc39)
Notes
*1: stencil for LonMaker:Indoor[0] *2: It is possible to use with an "ME" remote controller. *3: It is possible to use with an "MA" remote controller.
WSN02-2124 - 6 -
2-4.Indoor unit
03_NVspec_ver304e
Indoor[1]-[50]
Network Variables
nv1n
nv3n
nv5n
nv9n
*3,4,5 nv11n
*3,4,5 nv13n
*3,4,5 nv15n
*6 nv17n
*7 nv19n
nviOnOff_n
SNVT_switch
nviMode_n
SNVT_hvac_mode
nviSetP_n
SNVT_temp_p
nviFanSpeed_n
SNVT_switch
nviProOnOff_n
SNVT_switch
nviProMode_n
SNVT_switch
nviProSetP_n SNVT_switch
nviThermoOff_n
SNVT_switch
nviFiltReset_n
SNVT_switch
nv2n
nv4n
nv6n
nv10n
nv12n
nv14n
nv16n
nv18n
nv20n
nv21n
nv22n
nvoOnOff_n
SNVT_ switch
nvoMode_n
SNVT_hvac_mode
nvoSetP_n
SNVT_temp_p
nvoFanSpeed_n
SNVT_switch
nvoProOnOff_n
SNVT_switch
nvoProMode_n
SNVT_switch
nvoProSetP_n
SNVT_switch
nvoThermoOff_n
SNVT_switch
nvoOnTime_n
SNVT_time_hour
nvoSpaceTemp_n
SNVT_temp_p
nvoAlarm_n
SNVT_switch
*3,4,5
*3,4,5
*3,4,5
*6
*7
nv23n
nv24n
nv25n
nv26n
nv28n
nc29n
Notes
*1: stencil for LonMaker:Indoor[1]-[50] *2: "n" of the network variable shows M-NET address of indoor units. *3: It may be unable to be used by the system configuration of air-conditioners units. *4: It is possible to use with an "MA" remote controller. *5: For the use of this function, turn ON the switch(SW1-1) on LM ADAPTER.(Factory setting "OFF") *6: For the use of this function, turn ON the switch(SW1-8) on LM ADAPTER.(Factory setting "OFF") *7: For the use of this function, turn ON the switch(SW1-4) on LM ADAPTER.(Factory setting "OFF") *8: It is possible to use with other system controller.
nvoErrCode_n
SNVT_count
nvoErrAdrs_n
SNVT_count
nvoThermoSt_n
SNVT_state
nvoThermo_n
SNVT_switch
nvoIcMdlSize_n
SNVT_count
nvoGroupNo_n
SNVT_count
*8
WSN02-2124 - 7 -
2-5.Mr.SLIM
03_NVspec_ver304e
Indoor[1]-[50]
Network Variables
nv1n
nv3n
nv5n
nv9n
*3,4,5 nv11n
*3,4,5 nv13n
*3,4,5 nv15n
*6 nv17n
*7 nv19n
nviOnOff_n
SNVT_switch
nviMode_n
SNVT_hvac_mode
nviSetP_n
SNVT_temp_p
nviFanSpeed_n
SNVT_switch
nviProOnOff_n
SNVT_switch
nviProMode_n
SNVT_switch
nviProSetP_n SNVT_switch
nviThermoOff_n
SNVT_switch
nviFiltReset_n
SNVT_switch
nv2n
nv4n
nv6n
nv10n
nv12n
nv14n
nv16n
nv18n
nv21n
nv22n
nvoOnOff_n
SNVT_ switch
nvoMode_n
SNVT_hvac_mode
nvoSetP_n
SNVT_temp_p
nvoFanSpeed_n
SNVT_switch
nvoProOnOff_n
SNVT_switch
nvoProMode_n
SNVT_switch
nvoProSetP_n
SNVT_switch
nvoThermoOff_n
SNVT_switch
nvoSpaceTemp_n
SNVT_temp_p
nvoAlarm_n
SNVT_switch
*3,4,5
*3,4,5
*3,4,5
*6
nv23n
nv24n
nv25n
nv26n
nv28n
nc29n
*1: stencil for LonMaker:MrSLIM[1]-[50] *2: "n" of the network variable shows M-NET address of Mr.SLIM. *3: It may be unable to be used by the system configuration of air-conditioners units. *4: It is possible to use with an "MA" remote controller. *5: For the use of this function, turn ON the switch(SW1-1) on LM ADAPTER.(Factory setting "OFF") *6: For the use of this function, turn ON the switch(SW1-8) on LM ADAPTER.(Factory setting "OFF") *7: For the use of this function, turn ON the switch(SW1-4) on LM ADAPTER.(Factory setting "OFF") *8: It is possible to use with other system controller.
nvoErrCode_n
SNVT_count
nvoErrAdrs_n
SNVT_count
nvoThermoSt_n
SNVT_state
nvoThermo_n
SNVT_switch
nvoIcMdlSize_n
SNVT_count
nvoGroupNo_n
SNVT_count
*8
WSN02-2124 - 8 -
2-6.LOSSNAY
(1)LOSSNAY interlocks with the indoor unit.(*1,3)
Indoor[1]-[50]
Network Variables
03_NVspec_ver304e
(2)LOSSNAY is operated from L
nv1n
*4 nv7n
nv9n
ONWORKS.(*5,6,7)
nviOnOff_n
SNVT_switch
nviLCMode_n SNVT_switch
nviFanSpeed_n
SNVT_switch
Indoor[1]-[50]
Network Variables
nv22n
nv23n
nv24n
nv2n
nv8n
nv10n
nvoAlarm_n
SNVT_switch
nvoErrCode_n
SNVT_count
nvoErrAdrs_n
SNVT_count
nvoOnOff_n
SNVT_ switch
nvoLCMode_n
SNVT_switch
nvoFanSpeed_n
SNVT_switch
*4
(*4)
*8,9,10 nv11n
*11 nv19n
Notes:
nviProOnOff_n
SNVT_switch
nviFiltReset_n
SNVT_switch
*1: stencil for LonMaker:iLOSSNAY[1]-[50] *2: "n" of the network variable shows M-NET address of LOSSNAY. *3: LOSSNAY is not controlled from a LONWORKS network. *4: It may be unable to be used by the system configuration of air-conditioners units or the model of LOSSNAY. *5: LOSSNAY is controlled from a LONWORKS network. *6: stencil for LonMaker:LOSSNAY[1]-[50] *7: Please turn ON the switch(SW1-5) when LOSSNAY is operation from LONWORKS.(Factory setting "OFF") *8: There is a case which cannot be used with the system configuration of the air-conditioners units.
*9: It is possible to use with an "MA" remote controller. *10: For the use of this function, turn ON the switch(SW1-1) on LM ADAPTER.(Factory setting "OFF") *11: For the use of this function, turn ON the switch(SW1-8) on LM ADAPTER.(Factory setting "OFF") *12: It is possible to use with other system controller.
nv12n
nv20n
nv22n
nv23n
nv24n
nc29n
nvoProOnOff_n
SNVT_switch
nvoOnTime_n
SNVT_time_hour
nvoAlarm_n
SNVT_switch
nvoErrCode_n
SNVT_count
nvoErrAdrs_n
SNVT_count
nvoGroupNo_n
SNVT_count
(*8,9,10)
(*11)
(*4)
*12
WSN02-2124 - 9 -
03_NVspec_ver304e
3.SNVT Table
3-1.The network variables for individual operation/monitoring.
Model
nv No.
(*1)
1n
Request On/Off
2n
On/Off run state
3n
4n
Mode state
5n (*6) (*6)
SetPoint
6n (*5) (*5)
SetPoint state
7n
Request LOSSNAY Mode
8n
LOSSNAY Mode state
9n (*6) (*6)INRequest Fanspeed
10n (*6) (*6) (*6)
FanSpeed state
11n (*7,8) (*7)
Request Local Prohibit On/Off
12n (*7,8) (*7)
Local Prohibit On/Off state
13n (*7,8) (*7)IN
Request Local Prohibit Mode
14n (*7,8) (*7)
Local Prohibit Mode state
15n (*7,8) (*7)
Request Local Prohibit SetPoint
16n (*7,8) (*7)
Local Prohibit SetPoint state
17n
Request Forced Thermostat OFF
18n
Forced Thermostat OFF state
19n Filter Sign Reset
20n
Filter Run Time
21n
Space Temperature
22n (*2) (*2) (*2)
Alarm state
Error Code
23n (*2) (*2)
24n (*2) (*2) (*2) (*2)
Error Unit Address
25n
Thermo On/Off state_1
26n
28n Model Code OUT (*4) (*4) 28
29n (*10) (*10)OUTGroup Number
Notes:
*1: The value "n" is M-NET address of indoor unit
ex) Request On/Off to the 20th indoor unit. nvNo :120
Name :nviOnOff_020 *2: The air conditioner maintenance error (minor fault) is not output. *3: It may be unable to be used by the system configuration of air-conditioners units or the model of LOSSNAY. *4: This is not output with LONWORKS network. Monitoring with Poll request or Fetch request is required. *5: The monitor interval must be set in M-NET with the configuration properties (CP). *6: The range (temperature setting, operation mode, wind speed setting) will differ according to the connected devices. *7: It is possible to use with an "MA" remote controller (PAR-20MAU) . *8: When some of the models marketed in July 2002 are used, either MA(PAR-20MAU) or ME(PAR-F27MEA-US) remote controller is required. *9: The interlocked LOSSNAY is run and stopped with operations to each indoor unit.
*10: It is possible to use with other system controller.
Name (*1) I/O
nviOnOff_n
SNVT_switch
nvoOnOff_n
SNVT_switch
nviMode_n
SNVT_hvac_mode
nvoMode_n
SNVT_hvac_mode
nviSetP_n
SNVT_temp_p
nvoSetP_n
SNVT_temp_p
nviLCMode_n
SNVT_switch
nvoLCMode_n
SNVT_switch
nviFanSpeed_n
SNVT_switch
nvoFanSpeed_n
SNVT_switch
nvoProOnOff_n
SNVT_switch
nvoProOnOff_n
SNVT_switch
nviProMode_n
SNVT_switch
nvoProMode_n
SNVT_switch
nviProSetP_n
SNVT_switch
nvoProSetP_n
SNVT_switch
nviThermoOff_n
SNVT_switch
nvoThermoOff_n
SNVT_switch
nviFiltReset_n
SNVT_switch
nvoOnTime_n
SNVT_time_hour
nvoSpaceTemp_n
SNVT_temp_p
nvoAlarm_n
SNVT_switch
nvoErrCode_n
SNVT_count
nvoErrAdrs_n
SNVT_count
nvoThermoSt_n
SNVT_state
nvoThermo_n
SNVT_switch
nvoIcMdlSize_n
SNVT_count
nvoGroupNo_n
SNVT_count
IN
OUT
OUT
IN
OUT
IN
OUT
OUT
IN
OUT
OUT
IN
OUT
IN
OUT
IN
OUT
OUT
OUT
OUT
OUT
OUT
OUTThermo On/Off state_2
CITY
MULTI
(*6) (*6)INRequest Mode
Mr.SLIM
○○
○○
○○
○○
○○
○○
○○
○○
○○
○○
interlocks with the indoor unit
WSN02-2124
(*9)
(*9)
(*2)
(*2)
LOSSNAY
operation from
LonWorks
(*3)
(*3)
(*6)
(*7)
(*7)
(*2)
(*10)
Page.
14
14
15
15
16
16
17
17
18
18
19
19
20
20
21
21
22
22
23
23
24
25
25
26
27
27
29
- 10 -
3-2.The network variables for collective operation/monitoring.
y
d
nv No.
(*1)
Request All Off
1
32Emergency state
Collective On/Off state
Request Collective Operation Prohibit
4 (*2,3) (*2)
Collective Local Prohibit state
5
Collective Alarm for Indoor Unit
6
Collective Alarm for LM Adapter
7 OUT
9 Defrost State OUT
Time Stamp
12 (*5)
13 (*4,5)
Request Limit Temperature Setting Range
14 (*5)
Request Simplified Locking
Name (*1)
nviAllOff
SNVT_switch
nvoAllOff
SNVT_switch
nvoAllOnOff
SNVT_switch
nviAllPro
SNVT_switch
nvoAllPro
SNVT_switch
nvoAllAlarm
SNVT_switch
nvoAllAlarmLMAP
SNVT_switch
nvoDefrost
SNVT_switch
nviRmTime
SNVT_time_stamp
nviRmLim
SNVT_switch
nviRmLck
SNVT_switch
I/O
IN
OUT
OUT
IN
OUT
OUT
IN
IN
IN
CITY
MULTI
○○
○○
○○
○○
○○
○○
Mr.SLIM
03_NVspec_ver304e
Model
LOSSNAY
interlocks with the indoor unit
○○
(*1)
○○
○○
operation from
LonWorks
Page.
30
30
31
32
32
33
33
34
34
35
35
*1: The interlocked LOSSNAY is run and stopped with operations to each indoor unit. *2: It is possible to use with an "MA" remote controller (PAR-20MAU) . *3: When some of the models marketed in Jul
for the local remote controller. (The M-NET small remote controller cannot be used.) *4: The cool lower limit value and heat upper limit value must be set with the configuration properties (CP). *5: ME remote control is used , and it can be used when an air-conditioning is a standard mode.
2002 are used, either the MA (PAR-20MAU) or ME (PAR-F27ME) remote controller can be use
WSN02-2124
- 11 -
03_NVspec_ver304e
0(display) 4721 nc38
48
0(initialize)
46
46
46
43
43
44
41
41
42
39
39
40
36
37
37
38
6553.5 seconds (As 1800 seconds)2 nc16
6553.5 seconds(invalid)
40
6553.5 seconds (As 600.0 seconds)
6553.5 seconds (invalid)
-0.01(As 1.0)
42
0.0 second (As 1800.0 seconds)nc27
0.0 second (As 1800.0 seconds)
6553.5 seconds (As 600.0 seconds)
6553.5 seconds (As 600.0 seconds)
45
- 0.01(As 19)
0(disable) *Always effectivenc31
0(disable) *Always effective
- 0.01(As 28)
47
0(display)
0(All button)
Name Valid Range Unit, Default Page.
nc
No.
1.0 to 600.0 seconds 1sec
1200.0 to 6540.0 seconds 60sec
SNVT_time_sec
SNVT_time_sec
nciMinOutTm
nciStartHrtBt
SNVT_time_sec
SNVT_time_sec
nciStartOutTm
nciInitStartTm
0.0 second0.1 to 1.0 seconds 0.1sec
SNVT_time_sec
SNVT_time_sec
nciInitOutTm_1
nciInitOutTm_2
nciSndHrtBt_1
10sec
0.0 second600.0 to 6540.0 seconds 60sec
0.5 to 2.0 0.5
SW1-3 is ON0.0 second60.0 to 6540.0 seconds
SW1-3 is OFF0.0 second600.06540.0 seconds
SNVT_time_sec
SNVT_temp_p
SNVT_time_sec
nciSndHrtBt_2
nciAnalogWidth
nc24
nc22 6553.5 seconds (invalid)
10sec
seconds
600.0 to 6540.0 seconds 60sec
SW1-3 is OFF0.0 second600.0 to 6540.0
SNVT_time_sec
SNVT_time_sec
nciAnlgMonTm
nciRcvHrtBt_1
nciRcvHrtBt_2
nc26
60sec
600.0 to 6540.0 seconds 60sec
60.0 to 600.0 seconds 60sec
60.0 to 6540.0 seconds
SNVT_time_sec
SNVT_time_sec
SNVT_time_sec
nciEffectTm_1
nciEffectTm_2
nc29
State=0(disable)1(enable) --
State=0(Response)1(non-response) --15
SNVT_switch
SNVT_switch
nciPollFetch
nciOffline
nc30
19.0 to 30.0 1.0
17.0 to 28.0 1.0
SNVT_temp_p
SNVT_temp_p
nciCoolLrSetP
nciHeatUpSetP
State=0(All button)、1(except Start/Stop button) --
State=0(display)1(no display) --
SNVT_switch
SNVT_switch
nciRmOpLck
nciRmDsp_1
nc37
nc36
State=0(initialize)、1(setting time) --
State=0(display)1(no display) --
SNVT_switch
SNVT_switch
nciRmDsp_2
nciSet_1
Description
Set the start time of network variable change at power ON.
Set the automatic update start time at power ON.
Set the start time of initial output change at power ON.
Set the minimum transmission interval between output network variables.
Item
Minimum Send Time
Send Heartbeat Start Time
3-3.Configuration Properties
1 nc15 6553.5 seconds (invalid)
Set the minimum transmission interval between output network variables
Initialize Send Time_1
3 nc17 6553.5 seconds (As 1800 seconds)1200.0 to 6540.0 seconds 60secSend Start Time
5 nc19 6553.5 seconds (invalid)
4 nc18 0.0 second1200.0 to 3600.0 seconds 60secInitialize Start Time
at initial output.
Set the minimum transmission interval between each unit during initial
output.
Set the output network variable's update interval.
Set the output network variable's update interval.
Set the minimum fluctuation width of the output when the indoor
temperature state output changes.
Set the set time monitor interval of the indoor temperature for the indoor
unit.
Set the maximum elapse time from the previous update.
Set the maximum elapse time from the previous update.
Set the effective time for the emergency stop command.
Set the effective time for the collective operation prohibit command.
Set the presence of a response for poll (Fetch) requests in respect to the
output network variables.
Set the validity of the offline mode at power ON.
Spacetemp Width
Monitoring Time
Receive Heartbeat_1
Receive Heartbeat_2
Effective Time_1
Effective Time_2
Effective PollFetch
Initialize Send Time_2
6 nc20 6553.5 seconds (invalid)0.0 second5.0 to 50.0 seconds 1.0sec
Send Heartbeat_2
Send Heartbeat_1
9
8
7 nc21
10 nc25
14
13 nc28
12
11
Effective Offline Mode
16
Set the cool/dry lower limit temperature setting value for the local remote
controller.
Set the heat upper limit temperature setting value for the local remote
controller.
Set the simple lock setting value for the local remote controller.
Set the validity of the automatic actual operation mode display for the local
Upper Setpoint Heating
Local Operation Lock
Local Display_1
18 nc35
17 nc34Lower Setpoint Cooling
19
20
Set the networks communication start timing.
remote controller.
Set the validity of the intake temperature display for the local remote
controller.
Local Display_2
Communication Timing
22 nc39
WSN02-2124 - 12 -
03_NVspec_ver304e
p
g
p
Defrost
Collective
Collective
Alarm for LM
Alarm for
Collective
Local
Collective
Emergency
On/Off
Collective
Group
Number
Mode Code
Saving
Capacity
Thermo
On/Off 2
ADAPTER
Indoor Unit
Prohibit
Locking
Simplified
Limit
Range
Setting
Temperature
Time Stamp
Local
Prohibit
Collective
All Off
Reset
Filter Sign
OFF
Forced
Thermostat
Local
Prohibit
SetPoint
operation (request)
Local
Mode
Prohibit
Local
On/Off
Prohibit
Fanspeed
Mode
LOSSNAY
Thermo
On/Off 1
Address
Error Unit
monitoring (state)
Alarm Error Code
Space
Temperature
Time
Filter Run
OFF
Forced
Thermostat
Local
Prohibit
SetPoint
Local
Mode
Prohibit
Local
On/Off
Prohibit
FanSpeed
Mode
LOSSNAY
erties and Network Variables
uration Pro
nv1n nv3n nv5n nv7n nv9n nv11n nv13n nv15n nv17n nv19n nv1 nv4 nv12 nv13 nv14
ondence lists of Confi
3-4.The corres
Functions On/Off Mode SetPoint
nc15
nc16
nc17
nc18
Minimum Send Time
Send Heartbeat Start Time
Send Start Time
Initialize Start Time
1
2
3
4
nc19
nc20
nc21
nc22
Initialize Send Time_1
Initialize Send Time_2
Send Heartbeat_1
Send Heartbeat_2
5
6
7
8
nc24
nc25
nc26 ●●●
nc27
nc28
nc29
Spacetemp Width
Monitoring Time
Receive Heartbeat_1
Receive Heartbeat_2
Effective time_1
9
10
Effective time_2
11
12
13
14
nc30
nc31
nc34
Effective PollFetch
Effective Offline Mode
Lower Setpoint Cooling
15
16
17
nc35
nc36
nc37 ●●
nc38 ●●
nc39
Upper Setpoint Heating
Local Operation Lock
Local Display_1
Local Display_2
19
20
21
Communication Timing
22
18
nv2n nv4n nv6n nv8n nv10n nv12n nv14n nv16n nv18n nv20n nv21n nv22n nv23n nv24n nv25n nv26n nv27n nv28n nv29n nv2 nv3 nv5 nv6 nv7 nv9
nc15 ●●●●●●●●●● ●●● ●●●● ■■■■■■
nc16 ●●●●●
nc17 ●●●●●●●●●● ●●● ●●●● ●●●●●●
nc18 ●●●●●● ●● ●●
nc19 ●●●●●● ●● ●●●
nc20 ●●●●●● ●● ●●●
nc21 ●●●●●
nc22
nc24
nc25
nc26
Functions On/Off Mode Setpoint
Minimum Send Time
Send Heartbeat Start Time
Send Start Time
Initialize Start Time
Initialize Send Time_1
Initialize Send Time_2
Send Heartbeat_1
Send Heartbeat_2
Spacetemp Width
Monitoring Time
1
2
3
4
5
6
7
8
9
10
Receive Heartbeat_1
11
nc27
nc28
nc29
nc30 ●●●●●●●●●● ●●● ●●●●●
Receive Heartbeat_2
Effective time_1
Effective time_2
Effective PollFetch
12
13
14
15
nc31 ●●●●●●●●●● ●●● ●●●●●●●●●●●●
nc34
nc35
nc36
nc37
nc38
nc39
Effective Offline Mode
Lower Setpoint Cooling
Upper Setpoint Heating
Local Operation Lock
Local Display_1
Local Display_2
Communication Timing
16
17
18
19
:Effective between collective output variable.
20
21
22
WSN02-2124 - 13 -

4.Network Variables

r
r
1n
Request On/Off
network input SNVT_switch nviOnOff_n;
This input network variable is used to run or stop the indoor unit or ventilator (during independent non-interlocked operation). When the ventilator (LOSSNAY) is registered as interlocking with indoor unit, it will turn the indoor unit ON (for high speed) and OFF. Instructions according to this network variable in under nvoAllOff's output of the state of "Emergency Off" are disregarded.
Valid Range
indoor unit interlocked ventilato
OFF
ON
Unit State
SW1-7OFF
state value state value
OFF
ON(high) 0 100% (*1,3)
ON(high)
*1:The value field is set in 0% usually. *2:The setting to state=0x02-0xFE is interpreted as state=0x01. The setting to state=0xFF is invalid. *3:The setting to over 100% is interpreted as 100%.
0
1
else
0% to 99.5 % (*1)
not used
not used
03_NVspec_ver304e
SW1-7O
0 not used
1 (*2) 0
1 (*2) 0.5% to 100% (*3)
Default Value
The default value is determined by the state of the air conditioner (indoor unit). This variable becomes value = 0 until the value is updated after the power supply of LM ADAPTER.
2n
On/Off run state
network output SNVT_switch nvoOnOff_n;
This output network variable indicates the present On/Off state of the indoor unit or ventilator. When the ventilator (LOSSNAY) is registered interlocking with the indoor unit, the state of the ventilator will not be output, but it will operate (On/Off) the same as the indoor unit.
Valid Range
Unit State
indoor unit interlocked ventilato
OFF
ON
When Transmitted
This variable is transmitted promptly as its state changes. This variable is also transmitted as the state changes by the operation from the local side such as a local remote controller. This variable is output by the ncilnitStartTm (Initialize Start Time) at the powering of LM ADAPTER.
SW1-7OFF SW1-7O
state value state value
OFF 0 0%
ON(low) 0 50%
ON(high) 0 100%
any
10
00
1 100%
Update Rate
The value defined by nciSndHrtBt_1 (Send Heartbeat_1) and nciMinOutTm (Minimum Send Time) is valid.
Default Service Type
Acknowledged
WSN02-2124 - 14 -
3n
Request mode
network input SNVT_hvac_mode nviMode_n;
This input network variable is used to change the operation mode of the indoor unit. Some operation modes may not be compatible depending on the model.
Valid Range
value definition Active mode
0 HVAC_AUTO Auto mode
1 HVAC_HEAT Heat mode
3 HVAC_COOL Cool mode
5 HVAC_PRE_COOL Dry mode
9 HVAC_FAN_ONLY Fan mode
else - Fan mode
Default Value
The default value is determined by the state of the air conditioner (indoor unit). This variable becomes value = 0 until the value is updated after the power supply of LM ADAPTER.
4n
Mode state
03_NVspec_ver304e
network output SNVT_hvac_mode nvoMode_n;
This output network variable indicates the present mode of the indoor unit.
Valid Range
value definition Active mode
0 HVAC_AUTO Auto mode
1 HVAC_HEAT Heat mode
3 HVAC_COOL Cool mode
5 HVAC_PRE_COOL Dry mode
9 HVAC_FAN_ONLY Fan mode
FF HVAC_NUL value not available
   *The value is 0 while LM ADAPTER is initialized.
When Transmitted
This variable is transmitted promptly as the state changes. This variable is also transmitted as the state changes by the operation from the local side such as a local remote controller. This variable is output by the ncilnitStartTm (Initialize Start Time) at the powering of LM ADAPTER.
Update Rate
The value defined by nciSndHrtBt_1 (Send Heartbeat_1) is valid.
Default Service Type
Acknowledged
NOTE:
1: It is necessary to make all the indoor units in the same refrigerant system into the same operation mode depending
on a model. "HVAC_NUL" may be outputted when it is set as different operation mode.
2: Depending on the change timing, "HVAC_NUL" may be outputted temporarily.
WSN02-2124 - 15 -
Loading...
+ 35 hidden pages