Mitsubishi LJ61BT11, L26CPU-BT User Manual

SAFETY PRECAUTIONS

(Read these precautions before using this product.)
Before using this product, please read this manual and the relevant manuals carefully and pay full attention to safety to handle the product correctly. The precautions given in this manual are concerned with this product only. For the safety precautions of the programmable controller system, please read the user's manual of the CPU module used.
!
In this manual, the safety precautions are classified into two levels: "
!
WARNING
!
CAUTION
Under some circumstances, failure to observe the precautions given under " serious consequences. Observe the precautions of both levels because they are important for personal and system safety.
Make sure that the end users read this manual and then keep the manual in a safe place for future reference.
Indicates that incorrect handling may cause hazardous conditions, resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous conditions, resulting in minor or moderate injury or property damage.
[Design Precautions]
WARNING" and "! CAUTION".
!
CAUTION" may lead to
!
WARNING
For the operating status of each station after a communication failure, refer to Section 8.2.6 in this manual. Failure to do so may result in an accident due to an incorrect output or malfunction.
When changing data of a running programmable controller from a peripheral connected to the CPU module or from an external device such as a personal computer connected to an intelligent function module, configure an interlock circuit in the program to ensure that the entire system will always operate safely. For other controls to a running programmable controller (such as program modification or operating status change), read relevant manuals carefully and ensure the safety before the operation. Especially, in the case of a control from an external device to a remote programmable controller, immediate action cannot be taken for a problem on the programmable controller due to a communication failure. To prevent this, configure an interlock circuit in the program, and determine corrective actions to be taken between the external device and CPU module in case of a communication failure.
A - 1 A - 1
[Design Precautions]
!
WARNING
Do not write any data to the "system area" of the buffer memory in each intelligent function
module. Also, do not turn on any "use prohibited" signal that is output from the CPU module to the intelligent function module. Writing data to the "system area" or outputting a "use prohibited" signal may cause malfunction of the programmable controller system.
When setting auto refresh parameters, specify "Y" for the remote output RY refresh devices.
Specifying any other than "Y" (for example, M or L) will hold the previous device status in the case of a CPU stop. For how to stop a data link, refer to Section 8.3.8.
Disconnection of a CC-Link dedicated cable may make the line condition unstable, causing
communication errors on multiple stations on the network. Configure an interlock circuit in the program so that the system will operate safely even if these communication errors occur on multiple stations. Failure to do so may result in an accident due to an incorrect output or malfunction.
[Design Precautions]
!
CAUTION
Do not install the control lines or communication cables together with the main circuit lines or
power cables. Keep a distance of 100mm or more between them. Failure to do so may result in malfunction due to noise.
[Installation Precautions]
!
WARNING
Shut off the external power supply for the system in all phases before mounting or removing the module. Failure to do so may result in electric shock or cause the module to fail or malfunction.
A - 2 A - 2
[Installation Precautions]
!
CAUTION
Use the programmable controller in an environment that meets the general specifications shown in "Safety Guidelines", the manual supplied with the CPU module or head module. Failure to do so may result in electric shock, fire, malfunction, or damage to or deterioration of the product.
To interconnect modules, engage the respective connectors and securely lock the module joint levers. Incorrect interconnection may cause malfunction, failure, and drop of the module.
Do not directly touch any conductive part and electronic components of the module. Doing so can cause malfunction or failure of the module.
[Wiring Precautions]
!
WARNING
Shut off the external power supply for the system in all phases before wiring. Failure to do so may result in electric shock or cause the module to fail or malfunction.
After installation and wiring, attach the included terminal cover to the product before turning it on for operation. Failure to do so may result in electric shock.
[Wiring Precautions]
!
CAUTION
Use applicable solderless terminals and tighten them within the specified torque range. If any spade solderless terminal is used, it may be disconnected when a screw on the terminal block comes loose, resulting in failure.
Do not install the control lines or communication cables together with the main circuit lines or power cables. Failure to do so may result in malfunction due to noise.
Place the cables in a duct or clamp them. If not, dangling cable may swing or inadvertently be pulled, resulting in damage to the module or cables or malfunction due to poor contact.
Tighten the terminal block screw within the specified torque range. Undertightening can cause short circuit, fire, or malfunction. Overtightening can damage the screw and/or module, resulting in drop, short circuit, fire, or malfunction.
When disconnecting the cable from the module, do not pull the cable by the cable part. For the cable with connector, hold the connector part of the cable. For the cable connected to the terminal block, loosen the terminal block screws. Pulling the cable connected to the module may result in malfunction and damage to the module or cable.
A - 3 A - 3
[Wiring Precautions]
!
CAUTION
Prevent foreign matter such as dust or wire chips from entering the module. Such foreign matter can cause a fire, failure, or malfunction.
A protective film is attached to the top of the module to prevent foreign matter, such as wire chips, from entering the module during wiring. Do not remove the film during wiring. Remove it for heat dissipation before system operation.
For the CC-Link system, use dedicated cables that are specified by the manufacturer. If any other cable is used, performance of the CC-Link system is not guaranteed. Also, the maximum overall cable length and the station-to-station cable length must meet those specified in Chapter 3. If not, normal data communication is not guaranteed.
[Startup and Maintenance Precautions]
!
WARNING
Do not touch any terminal while power is on. Doing so will cause electric shock or malfunction.
Shut off the external power supply for the system in all phases before cleaning the module or retightening the screws on the terminal block. Failure to do so may result in electric shock.
[Startup and Maintenance Precautions]
!
CAUTION
Do not disassemble or modify the modules. Doing so may cause failure, malfunction, injury, or a fire.
Shut off the external power supply for the system in all phases before connecting or disconnecting the module. Failure to do so may cause the module to fail or malfunction.
Tighten the screws on the terminal block within the specified torque range. Undertightening can cause drop of parts or wires, short circuit, or malfunction. Overtightening can damage the screw and/or module, resulting in drop, short circuit, or malfunction.
After the first use of the module, the number of module connections/disconnections is limited to 50 times. Exceeding the limit (in accordance with IEC 61131-2) may cause malfunction.
Before handling the module, touch a conducting object such as a grounded metal to discharge the static electricity from the human body. Failure to do so may cause the module to fail or malfunction.
A - 4 A - 4
[Disposal Precautions]
!
CAUTION
When disposing of this product, treat it as industrial waste.
A - 5 A - 5

CONDITIONS OF USE FOR THE PRODUCT

(1) Mitsubishi programmable controller ("the PRODUCT") shall be used in conditions;
i) where any problem, fault or failure occurring in the PRODUCT, if any, shall not lead to any major or serious accident; and ii) where the backup and fail-safe function are systematically or automatically provided outside of the PRODUCT for the case of any problem, fault or failure occurring in the PRODUCT.
(2) The PRODUCT has been designed and manufactured for the purpose of being used in general
industries. MITSUBISHI SHALL HAVE NO RESPONSIBILITY OR LIABILITY (INCLUDING, BUT NOT LIMITED TO ANY AND ALL RESPONSIBILITY OR LIABILITY BASED ON CONTRACT, WARRANTY, TORT, PRODUCT LIABILITY) FOR ANY INJURY OR DEATH TO PERSONS OR LOSS OR DAMAGE TO PROPERTY CAUSED BY the PRODUCT THAT ARE OPERATED OR USED IN APPLICATION NOT INTENDED OR EXCLUDED BY INSTRUCTIONS, PRECAUTIONS, OR WARNING CONTAINED IN MITSUBISHI'S USER, INSTRUCTION AND/OR SAFETY MANUALS, TECHNICAL BULLETINS AND GUIDELINES FOR the PRODUCT. ("Prohibited Application") Prohibited Applications include, but not limited to, the use of the PRODUCT in; y Nuclear Power Plants and any other power plants operated by Power companies, and/or any other
cases in which the public could be affected if any problem or fault occurs in the PRODUCT.
y Railway companies or Public service purposes, and/or any other cases in which establishment of a
special quality assurance system is required by the Purchaser or End User.
y Aircraft or Aerospace, Medical applications, Train equipment, transport equipment such as Elevator
and Escalator, Incineration and Fuel devices, Vehicles, Manned transportation, Equipment for Recreation and Amusement, and Safety devices, handling of Nuclear or Hazardous Materials or Chemicals, Mining and Drilling, and/or other applications where there is a significant risk of injury to the public or property.
Notwithstanding the above, restrictions Mitsubishi may in its sole discretion, authorize use of the PRODUCT in one or more of the Prohibited Applications, provided that the usage of the PRODUCT is limited only for the specific applications agreed to by Mitsubishi and provided further that no special quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are required. For details, please contact the Mitsubishi representative in your region.
A - 6 A - 6

INTRODUCTION

Thank you for purchasing the Mitsubishi MELSEC-L series programmable controllers. This manual explains the functions and programming required to use the L26CPU-BT built-in CC-Link system master/local function and the LJ61BT11 CC-Link system master/local module (hereinafter referred to as the L series master/local module).
Before using the product, please read this manual and the relevant manuals carefully and develop familiarity with the functions and performance of the MELSEC-L series programmable controller to handle the product correctly. When applying the program examples introduced in this manual to the actual system, ensure the applicability and confirm that it will not cause system control problems.
Please make sure that the end users read this manual.
REMARK
The program examples shown in this manual are the examples in which the L
series master/local module is assigned to the I/O No. X/Y00 to X/Y1F unless otherwise specified. When using program samples described in the manual, the assignment of I/O No. is required. For the assignment of I/O No., refer to the following manual. MELSEC-L CPU Module User's Manual (Function Explanation, Program Fundamentals)
This manual explains the operation using GX Works2. When using GX Developer,
refer to Appendix 7.
A - 7 A - 7

COMPLIANCE WITH THE EMC AND LOW VOLTAGE DIRECTIVES

(1) For programmable controller system
To configure a system meeting the requirements of the EMC and Low Voltage Directives when incorporating the Mitsubishi programmable controller (EMC and Low Voltage Directives compliant) into other machinery or equipment, refer to "Safety Guidelines", the manual supplied with the CPU module or head module. The CE mark, indicating compliance with the EMC and Low Voltage Directives, is printed on the rating plate of the programmable controller.
(2) For the product
For the compliance of this product with the EMC and Low Voltage Directives, refer to "Safety Guidelines", the manual supplied with the CPU module or head module.
A - 8 A - 8

RELEVANT MANUALS

(1) CPU module user's manual
<Manual number, Model code>
MELSEC-L CPU Module User's Manual (Hardware Design, Maintenance and Inspection)
MELSEC-L CPU Module User's Manual (Function Explanation, Program Fundamentals)
Manual name
<SH-080890ENG, 13JZ36>
<SH-080889ENG, 13JZ35>
(2) Head module user's manual
<Manual number, Model code>
MELSEC-L CC-Link IE Field Network Head Module User's Manual
Manual name
<SH-080919ENG, 13JZ48>
(3) Operating manual
<Manual number, Model code>
GX Works2 Version1 Operating Manual (Common)
GX Developer Version 8 Operating Manual
Manual name
<SH-080779ENG, 13JU63 >
<SH-080373E, 13JU41>
Description
Specifications of the CPU modules, power supply module, display unit, SD memory cards, and batteries, information on how to establish a system, maintenance and inspection, and troubleshooting
Functions and devices of the CPU module, and programming
Description
Specifications of the head module, procedure before the operation, system configuration, installation and wiring, setting, and troubleshooting
Description
System configuration, parameter settings, and online operations (common to Simple project and Structured project) of GX Works2 Operating methods of GX Developer, such as programming, printing, monitoring, and debugging
A - 9 A - 9

CONTENTS

SAFETY PRECAUTIONS..............................................................................................................................A- 1
CONDITIONS OF USE FOR THE PRODUCT .............................................................................................A- 6
INTRODUCTION............................................................................................................................................A- 7
COMPLIANCE WITH THE EMC AND LOW VOLTAGE DIRECTIVES.......................................................A- 8
RELEVANT MANUALS .................................................................................................................................A- 9
CONTENTS....................................................................................................................................................A-10
TERMS ...........................................................................................................................................................A-16
PACKING LIST...............................................................................................................................................A-18
1 CC-Link SYSTEM
1.1 About CC-Link System............................................................................................................................ 1- 1
1.2 Overview of Communication................................................................................................................... 1- 2
2 PART NAMES
3 SPECIFICATIONS
3.1 General Specifications ............................................................................................................................ 3- 1
3.2 Performance Specifications .................................................................................................................... 3- 1
3.2.1 Maximum number of connected stations ........................................................................................ 3- 3
3.2.2 Maximum overall cable distance ..................................................................................................... 3- 6
3.2.3 Ver.1.10 compatible CC-Link dedicated cable................................................................................ 3- 7
3.3 Function List ............................................................................................................................................ 3- 8
3.4 Mode Selection ....................................................................................................................................... 3-11
3.4.1 Expanded cyclic setting ................................................................................................................... 3-13
3.5 I/O Signal List .......................................................................................................................................... 3-19
3.6 Buffer Memory List .................................................................................................................................. 3-20
4 PROCEDURE BEFORE OPERATION
5 SYSTEM CONFIGURATION
5.1 System Configuration.............................................................................................................................. 5- 1
5.1.1 System configuration of the L series master/local modules ...........................................................5- 1
5.1.2 System configuration on CC-Link .................................................................................................... 5- 2
5.2 Applicable System................................................................................................................................... 5- 3
5.2.1 Applicable modules and number of connectable modules............................................................. 5- 3
5.2.2 Restrictions on use with the head module ......................................................................................5- 3
5.2.3 Precautions on the system configuration ........................................................................................5- 4
A - 10 A - 10
6 INSTALLATION AND CONNECTION
6.1 Module Installation Environment and Position ....................................................................................... 6- 1
6.1.1 Handling precautions ....................................................................................................................... 6- 1
6.2 Hardware Test......................................................................................................................................... 6- 3
6.3 Connecting Modules with Ver.1.10 Compatible CC-Link Dedicated Cables ........................................6- 5
6.3.1 Wiring check..................................................................................................................................... 6- 7
6.4 T-Branch Connection .............................................................................................................................. 6- 9
6.4.1 T-branch system configuration ........................................................................................................6- 9
6.4.2 T-branch communication specifications list .................................................................................... 6-10
6.5 Loop Test................................................................................................................................................. 6-11
6.5.1 Loop test 1........................................................................................................................................ 6-12
6.5.2 Loop test 2........................................................................................................................................ 6-14
7 PARAMETER SETTINGS
7.1 Parameter List ......................................................................................................................................... 7- 3
7.2 Parameter Settings in Remote Net Ver.1 Mode .................................................................................... 7- 4
7.2.1 Operation setting .............................................................................................................................. 7-10
7.2.2 Station information setting ...............................................................................................................7-11
7.3 Parameter Settings in Remote Net Ver.2 Mode .................................................................................... 7-13
7.3.1 Operation setting .............................................................................................................................. 7-17
7.3.2 Station information setting ...............................................................................................................7-18
7.4 Parameter Settings in Remote Net Additional Mode ............................................................................. 7-21
7.4.1 Operation setting .............................................................................................................................. 7-26
7.4.2 Station information setting ...............................................................................................................7-27
7.5 Parameter Settings in Remote I/O Net Mode ........................................................................................7-30
7.5.1 Operation setting .............................................................................................................................. 7-33
7.6 Precautions on Parameter Setting ......................................................................................................... 7-34
8 FUNCTIONS
8.1 Basic Functions ....................................................................................................................................... 8- 1
8.1.1 Communication with remote I/O stations ........................................................................................ 8- 1
8.1.2 Communication with remote device stations................................................................................... 8- 3
8.1.3 Communication with local stations ..................................................................................................8- 8
8.1.4 Communication with intelligent device stations............................................................................... 8-15
A - 11 A - 11
8.2 Functions for Improving System Reliability ............................................................................................. 8-22
8.2.1 Slave station cut-off function............................................................................................................ 8-22
8.2.2 Automatic return function................................................................................................................. 8-23
8.2.3 Data link status setting in case of master station programmable controller CPU failure............... 8-24
8.2.4 Setting the status of input data from a data link faulty station ........................................................8-25
8.2.5 Slave station refresh/compulsory clear setting in case of programmable controller CPU STOP . 8-27
8.2.6 Station status at error occurrence ................................................................................................... 8-29
8.2.7 Standby master function ..................................................................................................................8-31
8.2.8 Data link start by standby master station ........................................................................................8-44
8.2.9 Block guarantee of cyclic data per station....................................................................................... 8-47
8.2.10 Secured 32-bit data........................................................................................................................ 8-51
8.3 Handy Functions ...................................................................................................................................... 8-52
8.3.1 Remote device station initialization procedure registration function ..............................................8-52
8.3.2 Event issuance for the interrupt program ........................................................................................ 8-60
8.3.3 Automatic CC-Link startup............................................................................................................... 8-63
8.3.4 Reserved station function ................................................................................................................8-65
8.3.5 Error invalid station setting function................................................................................................. 8-66
8.3.6 Temporary error invalid station setting function .............................................................................. 8-67
8.3.7 Scan synchronous function.............................................................................................................. 8-69
8.3.8 Data link stop/restart ........................................................................................................................ 8-73
8.3.9 Remote I/O station points setting .................................................................................................... 8-75
8.3.10 Master station duplication error cancel function ............................................................................ 8-77
9 DEDICATED INSTRUCTIONS AND PROGRAMMING
9.1 Dedicated Instructions ............................................................................................................................ 9- 1
9.1.1 Dedicated instruction list, applicable devices, and precautions ..................................................... 9- 1
9.1.2 G(P).RIRD ........................................................................................................................................9- 3
9.1.3 G(P).RIWT........................................................................................................................................ 9- 9
9.1.4 G(P).RIRCV...................................................................................................................................... 9-15
9.1.5 G(P).RISEND ................................................................................................................................... 9-20
9.1.6 G(P).RIFR ........................................................................................................................................ 9-25
9.1.7 G(P).RITO ........................................................................................................................................9-28
9.1.8 G(P).RLPASET ................................................................................................................................ 9-31
9.2 Precautions on Programming ................................................................................................................. 9-46
10 EXAMPLE OF COMMUNICATION BETW EEN THE MASTER STATION AND
REMOTE I/O STATIONS
10.1 When Remote I/O Net Mode is Used................................................................................................. 10- 1
10.1.1 Configuring a system ...................................................................................................................10- 1
10.1.2 Parameter setting......................................................................................................................... 10- 3
10.1.3 Creating a program ...................................................................................................................... 10- 5
10.1.4 Performing the data link............................................................................................................... 10- 7
A - 12 A - 12
11 EXAMPLE OF COMMUNICATION BETW EEN THE MASTER STATION AND
REMOTE DEVICE STATIONS
11.1 When Remote Net Ver.1 Mode is Used ............................................................................................. 11- 1
11.1.1 Configuring a system ...................................................................................................................11- 1
11.1.2 Parameter setting......................................................................................................................... 11- 3
11.1.3 Creating a program ...................................................................................................................... 11- 7
11.1.4 Performing the data link............................................................................................................... 11-10
11.2 When Remote Net Ver.2 Mode is Used ............................................................................................. 11-12
11.2.1 Configuring a system ...................................................................................................................11-12
11.2.2 Parameter setting......................................................................................................................... 11-15
11.2.3 Creating a program ...................................................................................................................... 11-19
11.2.4 Performing the data link............................................................................................................... 11-23
11.3 When Remote Net Additional Mode is Used ..................................................................................... 11-25
11.3.1 Configuring a system ...................................................................................................................11-25
11.3.2 Parameter setting......................................................................................................................... 11-28
11.3.3 Creating a program ...................................................................................................................... 11-32
11.3.4 Performing the data link............................................................................................................... 11-36
12 EXAMPLE OF COMMUNICATION BETW EEN THE MASTER STATION AND
LOCAL STATIONS
12.1 When Remote Net Ver.1 Mode is Used ............................................................................................. 12- 1
12.1.1 Configuring a system ...................................................................................................................12- 1
12.1.2 Setting the master station parameters ........................................................................................12- 2
12.1.3 Setting the local station parameters ............................................................................................ 12- 4
12.1.4 Creating a program ...................................................................................................................... 12- 6
12.1.5 Performing the data link............................................................................................................... 12-10
12.2 When Remote Net Ver.2 Mode is Used ............................................................................................. 12-12
12.2.1 Configuring a system ...................................................................................................................12-12
12.2.2 Setting the master station parameters ........................................................................................12-13
12.2.3 Setting the local station parameters ............................................................................................ 12-15
12.2.4 Creating a program ...................................................................................................................... 12-19
12.2.5 Performing the data link............................................................................................................... 12-22
12.3 When Remote Net Additional Mode is Used ..................................................................................... 12-24
12.3.1 Configuring a system ...................................................................................................................12-24
12.3.2 Setting the master station parameters ........................................................................................12-25
12.3.3 Setting the local station parameters ............................................................................................ 12-27
12.3.4 Creating a program ...................................................................................................................... 12-31
12.3.5 Performing the data link............................................................................................................... 12-34
13 COMMUNICATION BETWEEN THE MASTER STATION AND
INTELLIGENT DEVICE STATIONS
A - 13 A - 13
14 EXAMPLE OF COMMUNICATION WHEN USING THE HEAD MODULE
14.1 System Configuration Example .......................................................................................................... 14- 1
14.2 Image of Link Scan and Link Refresh by Cyclic Transmission ......................................................... 14- 2
14.3 Parameter Settings ............................................................................................................................. 14- 3
14.3.1 Setting parameters of the CC-Link IE field network master station ........................................... 14- 3
14.3.2 Setting parameters of the head module ...................................................................................... 14- 5
14.4 Program Example of CC-Link IE Field Network Master Station........................................................ 14- 8
15 TROUBLESHOOTING
15.1 Troubleshooting Procedures .............................................................................................................. 15- 2
15.1.1 Flowcharts for troubleshooting by LEDs ...................................................................................... 15- 2
15.1.2 Flowcharts for troubleshooting by GX Works2 ............................................................................15- 4
15.2 List of Problems .................................................................................................................................. 15- 9
15.2.1 When disconnecting a slave station............................................................................................ 15- 9
15.2.2 When cyclic data are faulty.......................................................................................................... 15-14
15.2.3 When transient data are faulty..................................................................................................... 15-17
15.2.4 When operation of the master station is faulty............................................................................ 15-18
15.3 Error Codes ......................................................................................................................................... 15-19
15.3.1 How to check error codes............................................................................................................ 15-19
15.3.2 Error code list ............................................................................................................................... 15-23
15.4 CC-Link Diagnostics ...........................................................................................................................15-33
15.4.1 Host monitoring/Other station monitoring ................................................................................... 15-33
15.4.2 Loop test/Obtain transmission speed setting .............................................................................. 15-36
15.4.3 Status logging .............................................................................................................................. 15-38
15.4.4 Creating a check sheet ................................................................................................................15-40
15.4.5 H/W information ........................................................................................................................... 15-42
APPENDIXES
Appendix 1 Details of the I/O Signals .......................................................................................................App- 1
Appendix 2 Buffer Memory Details ...........................................................................................................App- 3
Appendix 3 Link Special Relays and Registers (SB/SW) ........................................................................App-21
Appendix 3.1 Link special relays (SB) ..................................................................................................App-22
Appendix 3.2 Link special registers (SW).............................................................................................App-28
A - 14 A - 14
Appendix 4 Data Link Processing Time ...................................................................................................App-40
Appendix 4.1 Link scan time .................................................................................................................App-40
Appendix 4.2 Transmission delay time of master station Appendix 4.3 Transmission delay time of master station
(Ver.1 compatible slave station) ..................................................................................App-46
Appendix 4.4 Transmission delay time of master station
(Ver.2 compatible slave station) ..................................................................................App-48
Appendix 4.5 Transmission delay time of master station
(Ver.1 compatible slave station) ..................................................................................App-50
Appendix 4.6 Transmission delay time of master station
(Ver.2 compatible slave station) ..................................................................................App-52
Appendix 4.7 Transmission delay time of master station Appendix 4.8 Processing time for dedicated instructions of master station Appendix 4.9 Processing time for dedicated instructions of local station Appendix 4.10 Processing time for dedicated instructions of master station
device station................................................................................................................App-60
Appendix 4.11 Link refresh time of master station/local station ..........................................................App-62
Appendix 5 How to Confirm the Serial No. and Function Version...........................................................App-66
Appendix 6 Differences Between the L Series Master/Local Module and QJ61BT11N ........................App-67
Appendix 6.1 Specification comparisons..............................................................................................App-67
Appendix 6.2 Precautions when utilizing the program.........................................................................App-67
Appendix 7 When Using the GX Developer.............................................................................................App-68
Appendix 7.1 Compatible software package........................................................................................App-68
Appendix 7.2 Operation comparison ....................................................................................................App-68
Appendix 8 External Dimensions..............................................................................................................App-74
remote I/O station .................................App-44
remote device station
remote device station
local station
local station
intelligent device station .......................App-54
local station...............App-55
local station ..................App-58
intelligent
INDEX
REVISIONS
WARRANTY
A - 15 A - 15

TERMS

The following shows the terms used in this manual.
Term
LJ61BT11 Built-in CC-Link function L series master/local module
Master/local module
Master module Local module
Remote module
Intelligent device module
AnUCPU QnACPU QCPU LCPU Head module GX Works2 GX Developer
Intelligent function module
Special function module
Cyclic transmission
Transient transmission
Master station
Local station
Remote I/O station
Remote device station
Remote station
Intelligent device station
Standby master station
Slave station
Abbreviation for the LJ61BT11 CC-Link system master/local module. Abbreviation for the L26CPU-BT built-in CC-Link system master/local function. Generic term for the Built-in CC-Link function and LJ61BT11. Generic term for the L series master/local module, QJ61BT11N, A1SJ61BT11, and
A1SJ61QBT11. Generic term for master/local modules when they are used as master station. Generic term for master/local modules when they are used as local station. Generic term for AJ65BTB1-16D, AJ65SBTB1-16D, AJ65BT-64AD, AJ65BT-64DAV, AJ65BT-64DAI, and GT15-J61BT13. Generic term for the stations that can perform transient transmission, such as the AJ65BT-R2N (including local module). Another term for the MELSEC-AnU series CPU module. Another term for the MELSEC-QnA series CPU module. Another term for the MELSEC-Q series CPU module. Another term for the MELSEC-L series CPU module.
Abbreviation for the LJ72GF15-T2 CC-Link IE field network head module
Product name of the software package for the MELSEC programmable controllers.
Generic term for MELSEC-Q/L series modules which have functions other than I/O, such as A/D, D/A conversion module. Generic term for MELSEC-QnA/A series modules which have functions other than I/O, such as A/D, D/A conversion module. Transmission method by which data of remote I/O and remote registers are refreshed periodically. Transmission method by which 1:1 communication can be performed with the target specified and at any timing. Station that controls the data link system. One master station is required for each system. Station having a programmable controller CPU and the ability to communicate with the master and other local stations. Remote station that handles bit data only. (Performs input and output with external devices.) (AJ65BTB1-16D, AJ65SBTB1-16D) Remote station that handles bit and word data. (Performs input and output with external devices, and analog data conversion.) (AJ65BT-64AD, AJ65BT-64DAV, AJ65BT-64DAI) Generic term for remote I/O station and remote device station. (Controlled by the master station) Generic term for the stations that can perform transient transmission, such as the AJ65BT-R2N (including local stations). Backup station for data link control when the link to the master station is disconnected due to a programmable controller CPU or power supply problem. Generic term for remote I/O station, remote device station, local station, intelligent device station and standby master station.
Description
A - 16 A - 16
Term
Remote I/O net mode
Remote net mode
Remote net ver.1 mode
Remote net ver.2 mode
Remote net additional mode
Ver.1 compatible slave station Ver.2 compatible slave station
SB
SW
RX
RY
RWw
RWr
Online
Offline
Description
Dedicated mode for sending and receiving data to and from remote I/O stations at high speed. Mode that allows communication with all stations on CC-Link (remote I/O station, remote device station, local station, intelligent device station, and standby master station). There are three different modes: remote net ver.1 mode, remote net ver.2 mode, and remote net additional mode. Mode in which complete compatibility with the conventional module (ver.1 compatible station) is achieved. Select this mode when the number of link points need not be increased. Select this mode when increasing the number of link points and configuring a new system. Select this mode when adding a ver.2 compatible station to the existing system configured by only ver.1 compatible station to increase the number of link points. Slave station compatible with the remote net ver.1 mode.
Slave station compatible with the remote net ver.2 mode. Link special relay (for CC-Link)
Bit information that indicates the module operating status and data link status of the master station/local station. Link special register (for CC-Link) 16-bit information that indicates the module operating status and data link status of the master station/local station. Remote input (for CC-Link) Information input in bit units from the slave station to the master station. Remote output (for CC-Link) Information output in bit units from the master station to the slave station. Remote register (Write area for CC-Link) Information output in 16-bit units from the master station to the slave station. Remote register (Read area for CC-Link) Information input in 16-bit units from the slave station to the master station. Status that remote net ver.1 mode, remote net ver.2 mode, remote net additional mode or remote I/O net mode is selected in the mode setting of network parameter. Status that offline, loop test or H/W test is selected in the mode setting of network parameter.
A - 17 A - 17

PACKING LIST

The LJ61BT11 package contains the following items. Before using the product, check if all of them are in the package. For the packaged items for L26CPU-BT, refer to MELSEC-L CPU Module User's Manual (Hardware Design, Maintenance and Inspection).
A - 18 A - 18

1 CC-Link SYSTEM

1 CC-Link SYSTEM

1.1 About CC-Link System

The CC-Link system is a system that connects distributed modules such as I/O modules, intelligent function modules, and special function modules using dedicated cables so that these modules can be controlled by a programmable controller CPU.
(1) By connecting each module separately to equipment such as a conveyor line or a
machine, the number of wires can be reduced in the entire system.
(2) Each module’s on/off information of input/output and numeric data can easily be
sent and received at high-speed.
(3) By connecting multiple programmable controller CPUs, a simple distributed
system can be configured.
(4) Since various devices from Mitsubishi's partner manufacturers can be connected,
the system can provide flexible solutions depending on the user’s requirements.
GX Works2
Ethernet
In factory (information control)
1
CC-Link IE
controller network
Between lines (production control)
CC-Link
In line (equipment control)
CC-Link/LT
In board and equipment (device control and I/O control)
1 - 1 1 - 1

1.2 Overview of Communication

1 CC-Link SYSTEM
1
The overview of CC-Link communication is described below.
(1) Remote I/O station communication
The remote I/O station is a remote station that handles bit data only. The ON/OFF information of a switch or indicator lamp is sent or received using the remote input RX and remote output RY (refer to Section 8.1.1).
Programmable controller CPU
Master station
Remote I/O station
X
Y
Automatic refresh
Automatic refresh
Remote input
RX
Remote output
RY
Link scan
Link scan
Input
Output
(2) Remote device station communication
Programmable controller CPU
The remote device station is a remote station that handles bit and word data. Signals for handshaking with the remote device station (initial request, error occurred flag, etc.) are communicated using the remote input RX and remote output RY. The setting data to the remote device station are communicated using remote registers RWw and RWr (refer to Section 8.1.2).
Master station
Remote device station
X
Automatic refresh
Remote
input
(RX)
Link scan
Remote
input
(RX)
Y
Automatic refresh
W
Automatic refresh
W
Automatic refresh
Remote
output
(RY)
Remote
register
(RWw)
Remote
register
(RWr)
Link scan
Link scan
Link scan
Remote
output
(RY)
Remote
register
(RWw)
Remote
register
(RWr)
V
Voltmeter
1 - 2 1 - 2
Programmable controller CPU
1 CC-Link SYSTEM
(3) Local station communication
The local station is a station having a programmable controller CPU and the ability to communicate with the master and other local stations. Communication between a master station and a local station uses two types of transmission methods: cyclic transmission and transient transmission (refer to Section 8.1.3).
(a) Cyclic transmission
Data communication between programmable controller CPUs can be performed in N:N mode using bit data (remote input RX and remote output RY) and word data (remote registers RWw and RWr).
Master station
Local station
Programmable controller CPU
Programmable controller CPU
X
Y
W
W
G(P).RIWT
G(P).RIRD
Automatic refresh
Automatic refresh
Automatic refresh
Automatic refresh
Remote
input (RX)
Remote
output
(RY)
Remote
register
(RWw)
Remote
register
(RWr)
Link scan
Link scan
Link scan
Link scan
Remote
output
(RY)
Remote
input
(RX)
Remote
register
(RWr)
Remote
register
(RWw)
Automatic refresh
Automatic refresh
Automatic refresh
Automatic refresh
(b) Transient transmission
Read (G(P).RIRD) or write (G(P).RIWT) operation of the local station buffer memory and CPU device can be performed at any timing.
Programmable
Master station
Transient
transmission
area
Transient transmission
Transient transmission
Transient transmission
Transient transmission
Local station
Transient
transmission
area
Buffer
memory
controller CPU
Y
X
W
W
W
1 - 3 1 - 3
Programmable controller CPU
1 CC-Link SYSTEM
(4) Intelligent device station communication
The intelligent device station is a station that can handle bit and word data. Communication between a master station and an intelligent device station uses two types of transmission methods: cyclic transmission and transient transmission (refer to Section 8.1.4).
(a) Cyclic transmission
Signals for handshaking with the intelligent device station (positioning start, positioning complete, etc.) are communicated using the remote input RX and remote output RY. Numeric data (positioning start number, present feed value, etc.) is communicated using remote registers RWw and RWr.
Master station
Intelligent device station
Servo amplifier
X
Y
W
W
Automatic refresh
Automatic refresh
Automatic refresh
Automatic refresh
Remote
input
RX
Remote
output
RY
Remote
register
RWw
Remote
register
RWr
Link scan
Link scan
Link scan
Link scan
Remote
input
RX
Remote
output
RY
Remote register
RWw
Remote register
RWr
(b) Transient transmission
Reading (G(P).RIRD) or writing (G(P).RIWT) of buffer memory data in an
Programmable controller CPU
intelligent device station is available at any timing.
Master station
Intelligent device station
G(P).RIWT
Transient
transmission
area
G(P).RIRD
Transient transmission
Buffer memory
Transient transmission
1 - 4 1 - 4
2 PART NAMES

2. PART NAMES

The following describes the parts names of the L series master/local modules.
(1) L26CPU-BT
For parts other than those for the built-in CC-Link functions, refer to the following manual. MELSEC-L CPU Module User's Manual (Hardware Design, Maintenance and Inspection)
4)
1)
2)
2
5)
4)3)
(2) LJ61BT11
1)
2)
3) 4)
4)
5)
2 - 1 2 - 1
Number Name Description
2
1) LED indicators
The data link status can be checked with each ON/OFF status.
LED name Description
RUN
L RUN On: Data link is being executed
MST On: Operating as a master station. (in data link control)
S MST On: Operating as a standby master station. (in standby status)
SD On: Data being sent
RD On: Data being received
ERR.
L ERR.
B RATE
STATION
NO.
On : Operating normally Off : Watchdog timer error
On: All stations have a communication error This LED also turns on when the following errors occur.
There are more than one master station on the same line. There is an error in the parameter settings. The data link monitoring timer was activated. The cable is disconnected.
The transmission path is affected by noise. To check the source of the error, refer to Section 15.3. Or, refer to Appendix 3.2 for details on SW0058 (detailed LED display status). Flashing: A communication error station identified, or remote
station No. duplicated. On : Communication error (host) Flashing: The terminating resistor is not attached. The module or
CC-Link Ver.1.10 compatible cable is affected by
noise.
On : Operating at the indicated transmission speed.
All off: Transmission speed auto following up
(When succeeded, the LED of the followed transmission
speed turns on.)
The module station number setting is indicated.
<Range>
Master station : 0 (All off)
Local station and standby master station : 1 to 64
(Example) When the station number 15 is indicated
: On : Off
2 PART NAMES
5
10
10 + 5 = 15
2 - 2 2 - 2
Operating as a master station (data link control) Operating as a standby master station (standby)
Master station
MST
S MST
Station type and ON/OFF status of the "MST" and "S MST" LEDs
Operating status
Standby master
station
MST
S MST
Local station Master station
MST
S MST
MST
S MST
Standby master
station
S MST
MST
Number Name Description
2) Terminal block
A CC-Link dedicated Ver.1.10 compatible cable is connected for data linking.
For the connection method, refer to Section 6.3.
Terminals SLD and FG are connected inside the module.
Since a 2-piece type terminal block is used, the module can be replaced
without disconnecting the signal lines to the terminal block.
(Shut off the external power supply for the system in all phases before
replacing the module.)
2 PART NAMES
Local station
MST
S MST
: On, : Off
3) Serial No. display part Displays the serial No. of the rating plate.
4) Module joint lever Fixes the connected modules.
5) DIN rail hook Used to install the module to the DIN rail.
2 - 3 2 - 3

3 SPECIFICATIONS

3 SPECIFICATIONS

3.1 General Specifications

This chapter provides the specifications of the L series master/local modules.
For the general specifications of the L series master/local modules, refer to the following manual. "Safety Guidelines", the manual supplied with the CPU module or head module

3.2 Performance Specifications

3
Transmission speed Can be selected from 156 kbps/ 625 kbps/ 2.5 Mbps/ 5 Mbps/ 10 Mbps
Maximum overall cable distance (Maximum transmission distance)
Maximum number of connected stations (master station)
Number of occupied stations (local station)
Maximum number of link points per system
1
Number of link points per station 1
(remote station/local station/intelligent device station/standby master station)
Communication method Broadcast polling method
Synchronous method Frame synchronization method
Encoding method NRZI method
Transmission path Bus (RS-485)
Transmission format Conforms to HDLC
Error control system CRC (X16 + X12 + X5 + 1)
Connection cable Ver.1.10 compatible CC-Link dedicated cable
RAS function
Number of occupied I/O points 32 points (I/O assignm ent: Intelligent 32 points)
5V DC internal current consumption 2 0.46A
Weight 2 0.15kg
Item
The following shows the performance specifications of the L series master/local module.
Specification
Built-in CC-Link function LJ61BT11
Varies according to the transmission speed (Refer to Section 3.2.2)
64 (Refer to S ection 3.2.1)
1 to 4 stations The number of stations can be switched by GX Works2 parameter setting.
Remote I/O (RX, RY) : 2048 points
Remote register (RWw) : 256 points (master station remote device station/local station/ intelligent
device station/standby master station)
Remote register (RWr) : 256 points (remote device station/local station/ intelligent device station/standby
Remote I/O (RX, RY) : 32 points (local station is 30 points)
Remote register (RWw) : 4 points (master station remote device station/local station/ intelligent
Remote register (RWr) : 4 points (remote device station/local station/ intelligent device station/standby
Automatic return function Slave station cut-off function Error detection by the link special relay/register
master station
device station/standby master station)
master station
master station)
master station)
1 Indicates the number of link points in remote net ver.1 mode. For the number of link points in remote net
Ver.2 mode and remote net additional mode, refer to Section 3.2 (1).
2 For the 5V DC internal current consumption and weight, refer to the following manual.
MELSEC-L CPU Module User's Manual (Hardware Design, Maintenance and Inspection)
3 - 1 3 - 1
3 SPECIFICATIONS
(1) Number of link points in remote net ver.2 mode or remote net
Item Specifications
Maximum No. of link points per system
Expanded cyclic setting Single Double Quadruple Octuple
No. of link
points per
station
Number
of link
points per
number of
occupied
stations
Remote I/O (RX/RY)
Remote register (RWw) 4 points 8 points 16 points 32 points
Remote register (RWr) 4 points 8 points 16 points 32 points
Occupies
1 station
Occupies
2 stations
Occupies
3 stations
Occupies
4 stations
additional mode
Remote I/O
(RX/RY)
Remote
register (RWw)
Remote
register (RWr)
Remote I/O
(RX/RY)
Remote
register (RWw)
Remote
register (RWr)
Remote I/O
(RX/RY)
Remote
register (RWw)
Remote
register (RWr)
Remote I/O
(RX/RY)
Remote
register (RWw)
Remote
register (RWr)
Remote I/O (RX/RY) : 8192 points
Remote register (RWw) : 2048 points (master station
station/local station/intelligent device
station/standby master station)
Remote register (RWr) : 2048 points (remote device station/local
station/intelligent device station/standby
master station
32 points
(30 points
for local
station)
32 points 32 points 64 points 128 points
4 points 8 points 16 points 32 points
4 points 8 points 16 points 32 points
64 points 96 points 192 points 384 points
8 points 16 points 32 points 64 points
8 points 16 points 32 points 64 points
96 points 160 points 320 points 640 points
12 points 24 points 48 points 96 points
12 points 24 points 48 points 96 points
128 points 224 points 448 points 896 points
16 points 32 points 64 points 128 points
16 points 32 points 64 points 128 points
32 points
(30 points
for local
station)
master station)
64 points
(62 points
for local
station)
remote device
128 points
(126 points
for local
station)
3
3 - 2 3 - 2

3.2.1 Maximum number of connected stations

(1) Remote net ver.1 mode
A total of 64 slave stations can be connected to a single master station.
Condition 1 {(1 a) + (2 b) + (3 c) + (4 d)} 64
Condition 2 {(16 A) + (54 B) + (88 C)} 2304
However, the following conditions must all be satisfied.
3 SPECIFICATIONS
a: Number of modules occupying 1 station b: Number of modules occupying 2 stations c: Number of modules occupying 3 stations d: Number of modules occupying 4 stations A: Number of remote I/O stations B: Number of remote device stations C: Number of local stations, standby master stations
and intelligent device stations
64
42
26
3 - 3 3 - 3
Loading...
+ 420 hidden pages