Mitsubishi LGH 15-200RX3, U-042 Service Manual [eng]

LOSSNAY
HAND BOOK
(For EUROPE and OTHERS)
Issued January 2002 No. U-042
Model:
LGH-15RX
3-E
LGH-25RX
3-E
LGH-35RX
-E
LGH-50RX
3-E
LGH-80RX3-E LGH-100RX
3-E
LGH-100RX
3-E-60
LGH-150RX
3-E
LGH-200RX3-E LGH-200RX
3-E-60
Notice: The term of validity is for a year from the issued date.
MITSUBISHI ELECTRIC CORPORATION
Model name
The picture is shown LGH-100RX3-E
FOR DEALERS

Contents

Safety precautions........................................................................2
1. Specifications...................................................................... 3~6
2. Dimensions ....................................................................... 7~10
3. Wiring diagrams.............................................................. 11~12
4. Maintenance procedures................................................. 13~19
4-1 Blower Parts................................................................. 13~14
4-2 Damper Movement Motor Part (All units available) ............ 15
4-3 Circuit Board Part......................................................... 15~19
5. Parts list .......................................................................... 20~68
LGH-15RX
3-E............................................................... 21~26
LGH-25RX3-E............................................................... 27~32
LGH-35RX3-E............................................................... 33~38
LGH-50RX3-E............................................................... 39~44
LGH-80RX3-E............................................................... 45~50
LGH-100RX3-E (-60).................................................... 51~56
LGH-150RX
3
-E............................................................. 57~62
LGH-200RX
3-E (-60).................................................... 63~68
—2——2—
Electric shock
Prohibited
Instructions must be followed
Electric shock
If you have to inspect the circuitry while power is being conducted, be sure you do not touch the live parts. (Failure to heed this warning may result in electric shock.)
Modification is prohibited
Do not modify the unit.
(Failure to heed this warning may result in electric shock, bodily injury or fire.)
Proper electric work
The specified electric wires should be used for electric work, which should be done in accor­dance with the "Electrical Installation Engineering Standard," "Indoor Wiring Regulations," and the Installation Work Guide. (Failure to heed this warning may result in elec­tric shock or fire.)
Caution for bodily injury
Do not perform any work at a location where your feet are unstable. (Failure to heed this caution may result in bodily injury.)
Shut off the power supply
Be sure to shut off the breaker before disas­sembling the unit for repair.
(Failure to heed this warning may result in electric shock.)
Use proper parts and tools
For repair, use the parts listed in the service parts list of the applicable unit model and use the proper tools. (Failure to heed this warning may result in electric shock, bodily injury or fire.)
Replace damaged and/or degraded parts
Be sure to replace the power-supply cord and lead wire in the event that they are damaged and degraded. (Failure to heed this warning may result in electric shock and fire.)
Check insulation
Be sure to measure the insulation resistance once the repair work is completed, and turn on the power supply after verifying that insulation resistance of 1 Mor more is obtained. (If an insulation problem exists, it may result in electric shock.)

Safety precautions

Please take a time to read the following safety precautions before commencing with the maintenance work.
They will help to maintain the Lossnay properly and safely.
Warning
Mis-operation could result in serious injury or death.
Caution
Mis-operation could result in injury and/or damage to property.
The symbols used in have the following meanings.
Warning
Caution
• Inspect the grounding wire and repair it if incomplete.
Request
Make sure that the product operates correctly after maintenance.
—3——3—

1. Specifications

Model Control signal Heat recovery system Heat recovery module material Cladding Heat insulating material Motor Blower Filter material Operating environment (Supply air) Functions Weight Power supply Ventilation mode Fan speed Current Power consumption
Air volume
External static pressure Temperature recovery efficiency
Enthalpy recovery efficiency (%)
Noise (dB) Starting current
Insulation resistance Dielectric strength
LGH-15RX3-E Serial single communication (M-NET transmission) Air-to-air total heat (sensible heat + latent heat) recovery Partition, spacing plate-special treated paper Galvanized steel sheet Self-extinguishing urethane foam Totally enclosed capacitor permanent split-phase induction motor, 4 poles, 2 units 180 mm dia.centrifugal fan Non-woven fabrics filter (Gravitational method 82 %)
-10 °C to 40 °C, RH 80 % or less (-15 °C (*1) to +40 °C, RH 80 % or less) Lossnay ventilation/Bypass ventilation High (Extra high)-Low switching 17 kg
Single phase 220-240 V/50 Hz Single phase 220 V/60 Hz
Lossnay ventilation Bypass ventilation Lossnay ventilation Bypass ventilation
Extra high High Low Extra high High Low Extra high High Low Extra high High Low
0.48-0.52 0.34-0.35 0.24-0.25 0.48-0.52 0.34-0.36 0.24-0.25 0.57 0.39 0.27 0.58 0.40 0.27
104-122 74-83 52-59 104-123 74-85 52-59 119 85 58 120 85 58
150 150 120 150 150 120 150 150 110 150 150 110
42 42 33 42 42 33 42 42 31 42 42 31
9.2 4.1 2.6 9.2 4.1 2.6 12.2 6.1 3.6 12.2 6.1 3.6 90 40 25 90 40 25 120 60 35 120 60 35 77 77 80 - - - 77 77 81 - - ­69 69 72 - - - 69 69 73 - - -
62.5 62.5 66 - - - 62.5 62.5 67 - - ­26-27 24-25 21-22 26-27 24-25 21-22 28 25 22 28 25.5 22 33-34 31-32 26-27 33-34 31-32 26-27 35 32 27 35 32.5 27
Under 0.8/0.7 A or less 10 Mor more (500 V megger) AC 1500 V 1 minute
[A]
[W]
[m3/h]
[L/s]
[mmH2O]
[Pa]
[%] Heating Cooling
Measured at 1.5 m under the center of panel
Air outlets
Model Control signal Heat recovery system Heat recovery module material Cladding Heat insulating material Motor Blower Filter material Operating environment (Supply air) Functions Weight Power supply Ventilation mode Fan speed Current Power consumption
Air volume
External static pressure Temperature recovery efficiency
Enthalpy recovery efficiency (%)
Noise (dB) Starting current
Insulation resistance Dielectric strength
LGH-25RX3-E Serial single communication (M-NET transmission) Air-to-air total heat (sensible heat + latent heat) recovery Partition, spacing plate-special treated paper Galvanized steel sheet Self-extinguishing urethane foam Totally enclosed capacitor permanent split-phase induction motor, 4 poles, 2 units 180 mm dia.centrifugal fan Non-woven fabrics filter (Gravitational method 82 %)
-10 °C to 40 °C, RH 80 % or less (-15 °C (*1) to +40 °C, RH 80 % or less) Lossnay ventilation/Bypass ventilation High (Extra high)-Low switching 21 kg
Single phase 220-240 V/50 Hz Single phase 220 V/60 Hz
Lossnay ventilation Bypass ventilation Lossnay ventilation Bypass ventilation
Extra high High Low Extra high High Low Extra high High Low Extra high High Low
0.51-0.54 0.42-0.44 0.25-0.27 0.52-0.55 0.42-0.45 0.25-0.27 0.63 0.49 0.28 0.63 0.50 0.27
111-128 91-104 54-64 112-130 91-105 54-64 131 106 60 132 107 58
250 250 165 250 250 165 250 250 150 250 250 150
69 69 46 69 69 46 69 69 42 69 69 42
6.6 4.1 2.0 6.6 4.1 2.0 10.2 5.1 2.0 10.2 5.1 2.0 65 40 20 65 40 20 100 50 20 100 50 20 78 78 83 - - - 78 78 84 - - ­69 69 74 - - - 69 69 75 - - -
62.5 62.5 68 - - - 62.5 62.5 70 - - -
26.5-27.5 25-26 21-22 27-28 25.5-26.5 21-22 28.5 25.5 21 29 26 21
33.5-34.5 32-33 26-27 34-35 32.5-33.5 26-27 35.5 32.5 26 36 33 26 Under 0.8/0.7 A or less 10 Mor more (500 V megger) AC 1500 V 1 minute
[A]
[W]
[m3/h]
[L/s]
[mmH2O]
[Pa]
[%] Heating Cooling
Measured at 1.5 m under the center of panel
Air outlets
—4——4—
Model Control signal Heat recovery system Heat recovery module material Cladding Heat insulating material Motor Blower Filter material Operating environment (Supply air) Functions Weight Power supply Ventilation mode Fan speed Current Power consumption
Air volume
External static pressure Temperature recovery efficiency
Enthalpy recovery efficiency (%)
Noise (dB) Starting current
Insulation resistance Dielectric strength
LGH-35RX3-E Serial single communication (M-NET transmission) Air-to-air total heat (sensible heat + latent heat) recovery Partition, spacing plate-special treated paper Galvanized steel sheet Self-extinguishing urethane foam Totally enclosed capacitor permanent split-phase induction motor, 4 poles, 2 units 220 mm dia.centrifugal fan Non-woven fabrics filter (Gravitational method 82 %)
-10 °C to 40 °C, RH 80 % or less (-15 °C (*1) to +40 °C, RH 80 % or less) Lossnay ventilation/Bypass ventilation High (Extra high)-Low switching 30 kg
Single phase 220-240 V/50 Hz Single phase 220 V/60 Hz
Lossnay ventilation Bypass ventilation Lossnay ventilation Bypass ventilation
Extra high High Low Extra high High Low Extra high High Low Extra high High Low
0.78-0.79 0.71-0.71 0.46-0.48 0.81-0.82 0.72-0.73 0.46-0.49 0.99 0.83 0.46 1.00 0.83 0.46
169-187 154-167 97-110 176-192 156-172 97-111 215 180 97 217 180 97
350 350 230 350 350 230 350 350 210 350 320 210
97 97 64 97 97 64 97 97 58 97 89 58
15.3 7.1 2.6 15.3 7.1 2.7 19.4 5.1 2.0 19.4 5.1 2.0 150 70 25 150 70 26 190 50 20 190 50 20
79 79 84 - - - 79 79 85 - - -
68.5 68.5 75.5 - - - 68.5 68.5 76.5 - - -
65.5 65.5 72 - - - 65.5 65.5 73 - - -
31-32 28-30 23-24 31.5-32.5 28-30 23-24 32.5 27 21 33.5 28 21
39-40 35-37 29-30 39.5-40.5 35-37 29-30 40.5 34 27 41.5 35 27 Under 1.6/1.5 A or less 10 Mor more (500 V megger) AC 1500 V 1 minute
[A]
[W]
[m3/h]
[L/s]
[mmH2O]
[Pa]
[%] Heating Cooling
Measured at 1.5 m under the center of panel
Air outlets
Model Control signal Heat recovery system Heat recovery module material Cladding Heat insulating material Motor Blower Filter material Operating environment (Supply air) Functions Weight Power supply Ventilation mode Fan speed Current Power consumption
Air volume
External static pressure Temperature recovery efficiency
Enthalpy recovery efficiency (%)
Noise (dB) Starting current
Insulation resistance Dielectric strength
LGH-50RX3-E Serial single communication (M-NET transmission) Air-to-air total heat (sensible heat + latent heat) recovery Partition, spacing plate-special treated paper Galvanized steel sheet Self-extinguishing urethane foam Totally enclosed capacitor permanent split-phase induction motor, 4 poles, 2 units 222 mm dia.centrifugal fan Non-woven fabrics filter (Gravitational method 82 %)
-10 °C to 40 °C, RH 80 % or less (-15 °C (*1) to +40 °C, RH 80 % or less) Lossnay ventilation/Bypass ventilation High (Extra high)-Low switching 33 kg
Single phase 220-240 V/50 Hz Single phase 220 V/60 Hz
Lossnay ventilation Bypass ventilation Lossnay ventilation Bypass ventilation
Extra high High Low Extra high High Low Extra high High Low Extra high High Low
0.94-0.95 0.89-0.90 0.57-0.60 0.95-0.96 0.90-0.93 0.58-0.60 1.21 1.05 0.60 1.22 1.05 0.60
204-225 193-214 123-142 206-228 196-221 125-142 262 231 130 263 228 130
500 500 350 500 500 350 500 500 300 500 500 300 139 139 97 139 139 97 139 139 83 139 139 83
15.3 6.1 3.1 15.3 6.1 3.1 20.4 6.1 2.0 20.4 6.1 2.0 150 60 30 150 60 30 200 60 20 200 60 20
77 77 82 - - - 77 77 83.5 - - ­67 67 73 - - - 67 67 75 - - -
61.5 61.5 68 - - - 61.5 61.5 70 - - -
32.5-33.5 30-31 23.5-24.5 33.5-34.5 30.5-31.5 23.5-24.5 32.5 28.5 23 33.5 29.5 23
40.5-41.5 38-39 29.5-30.5 41.5-42.5 38.5-39.5 30.5-30.5 40.5 36.5 29 41.5 37.5 29 Under 1.9/1.7 A or less 10 Mor more (500 V megger) AC 1500 V 1 minute
[A]
[W]
[m3/h]
[L/s]
[mmH2O]
[Pa]
[%] Heating Cooling
Measured at 1.5 m under the center of panel
Air outlets
—5——5—
Model Control signal Heat recovery system Heat recovery module material Cladding Heat insulating material Motor Blower Filter material Operating environment (Supply air) Functions Weight Power supply Ventilation mode Fan speed Current Power consumption
Air volume
External static pressure Temperature recovery efficiency
Enthalpy recovery efficiency (%)
Noise (dB) Starting current
Insulation resistance Dielectric strength
LGH-80RX3-E Serial single communication (M-NET transmission) Air-to-air total heat (sensible heat + latent heat) recovery Partition, spacing plate-special treated paper Galvanized steel sheet Self-extinguishing urethane foam Totally enclosed capacitor permanent split-phase induction motor, 4 poles, 2 units 245 mm dia.centrifugal fan Non-woven fabrics filter (Gravitational method 82%)
-10 °C to 40 °C, RH 80 % or less (-15 °C (*1) to +40 °C, RH 80 % or less) Lossnay ventilation/Bypass ventilation High (Extra high)-Low switching 61 kg
Single phase 220-240 V/50 Hz Single phase 220 V/60 Hz
Lossnay ventilation Bypass ventilation Lossnay ventilation Bypass ventilation
Extra high High Low Extra high High Low Extra high High Low Extra high High Low
1.8-1.8 1.7-1.7 1.4-1.4 1.7-1.7 1.6-1.6 1.4-1.4 2.1 1.9 1.5 2.0 1.8 1.4
392-418 368-396 304-332 370-394 348-374 298-330 455 405 315 425 390 305
800 800 670 800 800 670 800 800 660 800 800 660 222 222 186 222 222 186 222 222 183 222 222 183
14.3 10.2 7.1 14.3 10.2 7.1 23.5 12.2 8.2 23.5 12.2 8.2 140 100 70 140 100 70 230 120 80 230 120 80
78 78 80.5 - - - 78 78 81 - - ­71 71 73 - - - 71 71 73.5 - - -
64.5 64.5 68 - - - 64.5 64.5 68.5 - - -
33.5-34.5 32-33 30-31 34.5-35.5 33-34 30.5-31.5 35 31 29 36 32 29.5
44.5-45.5 43-44 40-41 45.5-46.5 44-45 40.5-41.5 46 42 39 47 43 39.5 Under 3.8/3.1 A or less 10 Mor more (500 V megger) AC 1500 V 1 minute
[A]
[W]
[m3/h]
[L/s]
[mmH2O]
[Pa]
[%] Heating Cooling
Measured at 1.5 m under the center of panel
Air outlets
Model Control signal Heat recovery system Heat recovery module material Cladding Heat insulating material Motor Blower Filter material Operating environment (Supply air) Functions Weight Power supply Ventilation mode Fan speed Current Power consumption
Air volume
External static pressure Temperature recovery efficiency
Enthalpy recovery efficiency (%)
Noise (dB) Starting current
Insulation resistance Dielectric strength
LGH-100RX3-E,LGH-100RX3-E-60 Serial single communication (M-NET transmission) Air-to-air total heat (sensible heat + latent heat) recovery Partition, spacing plate-special treated paper Galvanized steel sheet Self-extinguishing urethane foam Totally enclosed capacitor permanent split-phase induction motor, 4 poles, 2 units 245 mm dia.centrifugal fan Non-woven fabrics filter (Gravitational method 82 %)
-10 °C to 40 °C, RH 80 % or less (-15 °C (*1) to +40 °C, RH 80 % or less) Lossnay ventilation/Bypass ventilation High (Extra high)-Low switching 72 kg
Single phase 220-240 V/50 Hz Single phase 220 V/60 Hz
Lossnay ventilation Bypass ventilation Lossnay ventilation Bypass ventilation
Extra high High Low Extra high High Low Extra high High Low Extra high High Low
2.3-2.3 2.3-2.3 2.2-2.2 2.3-2.3 2.3-2.2 2.1-2.1 2.8 2.6 1.7 2.8 2.6 1.7
500-525 495-515 465-475 505-525 500-515 455-485 600 555 365 595 550 365
1000 1000 870 1000 1000 870 1000 1000 720 1000 1000 720
278 278 242 278 278 242 278 278 200 278 278 200
16.3 10.2 8.2 16.3 10.2 8.2 20.4 11.2 6.1 20.4 11.2 6.1 160 100 80 160 100 80 200 110 60 200 110 60
79 79 81 - - - 79 79 83 - - ­70 70 73 - - - 70 70 76 - - -
64.5 64.5 67 - - - 64.5 64.5 71 - - -
36-37 34-35 31.5-32.5 37-38 35-36 33-34 36 34 30 37 35 31
47-48 45-46 41.5-42.5 48-49 46-47 43-44 47 45 40 48 46 41 Under 5.7/5.0 A or less 10 Mor more (500 V megger) AC 1500 V 1 minute
[A]
[W]
[m3/h]
[L/s]
[mmH2O]
[Pa]
[%] Heating Cooling
Measured at 1.5 m under the center of panel
Air outlets
Model Control signal Heat recovery system Heat recovery module material Cladding Heat insulating material Motor Blower Filter material Operating environment (Supply air) Functions Weight Power supply Ventilation mode Fan speed Current Power consumption
Air volume
External static pressure Temperature recovery efficiency
Enthalpy recovery efficiency (%)
Noise (dB)
Measured at 1.5 m under the center of panel
Air outlets Starting current Insulation resistance Dielectric strength
LGH-150RX3-E Serial single communication (M-NET transmission) Air-to-air total heat (sensible heat + latent heat) recovery Partition, spacing plate-special treated paper Galvanized steel sheet Self-extinguishing urethane foam Totally enclosed capacitor permanent split-phase induction motor, 4 poles, 4 units 245 mm dia.centrifugal fan Non-woven fabrics filter (Gravitational method 82 %)
-10 °C to 40 °C, RH 80 % or less (-15 °C (*1) to +40 °C, RH 80 % or less) Lossnay ventilation/Bypass ventilation High (Extra high)-Low switching 154 kg
Single phase 220-240 V/50 Hz Single phase 220 V/60 Hz
Lossnay ventilation Bypass ventilation Lossnay ventilation Bypass ventilation
Extra high High Low Extra high High Low Extra high High Low Extra high High Low
3.3-3.3 3.1-3.1 2.7-2.8 3.2-3.2 3.0-3.0 2.6-2.6 4.2 3.7 2.9 4.2 3.7 2.9
[A]
720-785 670-730 585-660 695-760 650-705 565-615 915 805 630 905 800 630
[W]
[m3/h]
[L/s]
[mmH2O]
Heating Cooling
1500 1500 1200 1500 1500 1200 1500 1500 1200 1500 1500 1200
417 417 333 417 417 333 417 417 333 417 417 333
14.0 10.2 5.1 14.0 10.2 5.1 21.0 12.0 7.0 21.0 12.0 7.0
[Pa]
[%]
137 100 50 137 100 50 206 118 69 206 118 69
79 79 81 - - - 79 79 81 - - ­72 72 75 - - - 72 72 75 - - -
65.5 65.5 69 - - - 65.5 65.5 69 - - -
36.5-37.5 35.5-36.5 32.5-33.5 36.5-37.5 35.5-36.5 32.5-33.5 37 36 33 37 36 33
47.5-48.5 46.5-47.5 43.5-44.5 47.5-48.5 46.5-47.5 43.5-44.5 48 47 44 48 47 44 Under 6.8/5.9 A or less 10 Mor more (500 V megger) AC 1500 V 1 minute
Model Control signal Heat recovery system Heat recovery module material Cladding Heat insulating material Motor Blower Filter material Operating environment (Supply air) Functions Weight Power supply Ventilation mode Fan speed Current Power consumption
Air volume
External static pressure Temperature recovery efficiency
Enthalpy recovery efficiency (%)
Noise (dB)
Measured at 1.5 m under the center of panel
Air outlets Starting current Insulation resistance Dielectric strength
LGH-200RX3-E,LGH-200RX3-E-60 Serial single communication (M-NET transmission) Air-to-air total heat (sensible heat + latent heat) recovery Partition, spacing plate-special treated paper Galvanized steel sheet Self-extinguishing urethane foam Totally enclosed capacitor permanent split-phase induction motor, 4 poles, 4 units 245 mm dia.centrifugal fan Non-woven fabrics filter (Gravitational method 82 %)
-10 °C to 40 °C, RH 80 % or less (-15 °C (*1) to +40 °C, RH 80 % or less) Lossnay ventilation/Bypass ventilation High (Extra high)-Low switching 179 kg
Single phase 220-240 V/50 Hz Single phase 220 V/60 Hz
Lossnay ventilation Bypass ventilation Lossnay ventilation Bypass ventilation
Extra high High Low Extra high High Low Extra high High Low Extra high High Low
4.6-4.3 4.6-4.3 4.1-3.8 4.4-4.2 4.4-4.1 4.1-3.8 5.4 5.2 3.3 5.3 5.0 3.3
[A]
[W]
[m3/h]
[L/s]
[mmH2O]
[Pa]
[%] Heating Cooling
1000-1020
995-1020 900-905 960-995 955-975 885-900 1175 1130 735 1155 1090 720
2000 2000 1400 2000 2000 1400 2000 2000 1400 2000 2000 1400
556 556 389 556 556 389 556 556 389 556 556 389
14.0 8.2 8.5 14.0 8.2 8.5 20.0 9.0 7.0 20.0 9.0 7.0 137 80 83 137 80 83 196 88 69 196 88 69
79 79 83 - - - 79 79 83 - - ­70 70 76 - - - 70 70 76 - - -
64.5 64.5 71 - - - 64.5 64.5 71 - - -
39-40 37-38 35.5-36.5 39.5-40.5 37.5-38.5 36-37 38.5 36.5 34.5 38.5 36.5 34.5
50-51 48-49 46.5-47.5 50.5-51.5 48.5-49.5 47-48 49.5 47.5 45.5 49.5 47.5 45.5 Under 13.0/9.7 A or less 10 Mor more (500 V megger) AC 1500 V 1 minute
—6——6—

2. Dimensions

SA
(supply air)
RA
(return air)
OA
(outside air)
EA
(exhaust air)
10
Ceiling suspension fixture
Position where Ceiling suspension fixture is changed
Power cord opening
275
90
Maintenance space for heat exchanger, air filters, and fans
Position where duct direction is changed
High-performance filter (sold separately attachment position)
Heat exchanger (Lossnay core)
Air exhaust fan
Damper plate
Maintenance cover
Control box
Air supply fan
Ceiling suspension fixture
54 780 54
φ 110
φ 97.5
600 or more
450
610
119
150 to 250
119
64122
700
119
Air filters
Inspection
opening
()
102
700
102
735
530
22
765
10
275
90
63 780 63
102
φ 160
φ 142
SA
(supply air)
RA
(return air)
OA
(outside air)
EA
(exhaust air)
Ceiling suspension fixture
Maintenance space for heat exchanger, air filters, and fans
Heat exchanger (Lossnay core)
Air exhaust fan
Damper plate
Maintenance cover
Control box
Air supply fan
Ceiling suspension fixture
600 or more
150 to 250
Air filters
Inspection
opening
Power cord opening
Position where duct direction is changed
High-performance filter (sold separately attachment position)
Position where Ceiling suspension fixture is changed
()
LGH-15RX3-E
Unit (mm)
Attention
*
1. If condensation is expected to form, heat up the fresh outside air using a duct heater, etc.
2. An inspection port (450 × 450 – 600 × 600 mm) must be installed on the filter and Lossnay core removing side.
3. The two outdoor ducts must be covered with heat-insulating material in order to prevent condensation from forming. The two indoor ducts may be covered with heat-insulation if Lossnay is to be installed in the circumstance of higher tem­perature in summer.
4. Installing the duct damper is preferred also to prevent the outdoor air introduced to room if there has strongthern wind, when the unit operates or stops.
5. The outside ducts must be tilted at a gradient (1/30 or more) down toward the outdoor area from Lossnay unit.
* Specifications subject to change without notice.
LGH-25RX3-E
Attention
*
1. If condensation is expected to form, heat up the fresh outside air using a duct heater, etc.
2. An inspection port (450 × 450 – 600 × 600 mm) must be installed on the filter and Lossnay core removing side.
3. The two outdoor ducts must be covered with heat-insulating material in order to prevent condensation from forming.
Unit (mm)
The two indoor ducts may be covered with heat-insulation if Lossnay is to be installed in the circumstance of higher tem­perature in summer.
4. Installing the duct damper is preferred also to prevent the outdoor air introduced to room if there has strongthern wind, when the unit operates or stops.
5. The outside ducts must be tilted at a gradient (1/30 or more) down toward the outdoor area from Lossnay unit.
—7——7—
* Specifications subject to change without notice.
—8——8—
Unit (mm)
Unit (mm)
SA
(supply air)
RA
(return air)
OA
(outside air)
EA
(exhaust air)
40
Ceiling suspension fixture
317
90
Maintenance space for heat exchanger, air filters, and fans
Heat exchanger (Lossnay core)
Air exhaust fan
Damper plate
Maintenance cover
Control box
Air supply fan
Ceiling suspension fixture
63 888 63
φ 160
φ 142
600 or more
650
874
124
150 to 250
124
90622
790
124
Air filters
Inspection
opening
Power cord opening
Position where duct direction is changed
High-performance filter (sold separately attachment position)
Position where Ceiling suspension fixture is changed
()
SA
(supply air)
RA
(return air)
OA
(outside air)
EA
(exhaust air)
40 317
90
Maintenance space for heat exchanger, air filters, and fans
Air exhaust fan
Damper plate
Maintenance cover
Control box
Air supply fan
Ceiling suspension fixture
79 888 79
φ 208
φ 192
600 or more
745
1016
124
150 to 250
124
104822
790
124
Inspection
opening
Power cord opening
Position where duct direction is changed
Ceiling suspension fixture
Heat exchanger (Lossnay core)
Air filters
High-performance filter (sold separately attachment position)
Position where Ceiling suspension fixture is changed
()
LGH-35RX3-E
LGH-50RX3-E
*
Attention
1. If condensation is expected to form, heat up the fresh outside air using a duct heater, etc.
2. An inspection port (450 × 450 – 600 × 600 mm) must be installed on the filter and Lossnay core removing side.
3. The two outdoor ducts must be covered with heat-insulating material in order to prevent condensation from forming. The two indoor ducts may be covered with heat-insulation if Lossnay is to be installed in the circumstance of higher tem­perature in summer.
4. Installing the duct damper is preferred also to prevent the outdoor air introduced to room if there has strongthern wind, when the unit operates or stops.
5. The outside ducts must be tilted at a gradient (1/30 or more) down toward the outdoor area from Lossnay unit.
*
Attention
1. If condensation is expected to form, heat up the fresh outside air using a duct heater, etc.
2. An inspection port (450 × 450 – 600 × 600 mm) must be installed on the filter and Lossnay core removing side.
3. The two outdoor ducts must be covered with heat-insulating material in order to prevent condensation from forming. The two indoor ducts may be covered with heat-insulation if Lossnay is to be installed in the circumstance of higher tem­perature in summer.
4. Installing the duct damper is preferred also to prevent the outdoor air introduced to room if there has strongthern wind, when the unit operates or stops.
5. The outside ducts must be tilted at a gradient (1/30 or more) down toward the outdoor area from Lossnay unit.
* Specifications subject to change without notice.
* Specifications subject to change without notice.
—9——9—
LGH-80RX3-E
LGH-100RX3-E,LGH-100RX3-E-60
*
Attention
1. If condensation is expected to form, heat up the fresh outside air using a duct heater, etc.
2. An inspection port (450 × 450 – 600 × 600 mm) must be installed on the filter and Lossnay core removing side.
3. The two outdoor ducts must be covered with heat-insulating material in order to prevent condensation from forming. The two indoor ducts may be covered with heat-insulation if Lossnay is to be installed in the circumstance of higher tem­perature in summer.
4. Installing the duct damper is preferred also to prevent the outdoor air introduced to room if there has strongthern wind, when the unit operates or stops.
5. The outside ducts must be tilted at a gradient (1/30 or more) down toward the outdoor area from Lossnay unit.
*
Attention
1. If condensation is expected to form, heat up the fresh outside air using a duct heater, etc.
2. An inspection port (450 × 450 – 600 × 600 mm) must be installed on the filter and Lossnay core removing side.
3. The two outdoor ducts must be covered with heat-insulating material in order to prevent condensation from forming. The two indoor ducts may be covered with heat-insulation if Lossnay is to be installed in the circumstance of higher tem­perature in summer.
4. Installing the duct damper is preferred also to prevent the outdoor air introduced to room if there has strongthern wind, when the unit operates or stops.
5. The outside ducts must be tilted at a gradient (1/30 or more) down toward the outdoor area from Lossnay unit.
Unit (mm)
Unit (mm)
* Specifications subject to change without notice.
* Specifications subject to change without notice.
Position where duct direction is changed
Air exhaust fan
149
Damper plate
1030
Ceiling suspension fixture
RA
(return air)
1036
SA
(supply air)
Power cord opening
22
Air supply fan
Control box
Maintenance cover
φ 258
φ 242
90
10
398
EA
(exhaust air)
690
1004
OA
(outside air)
Maintenance space for heat exchanger, air filters, and fans
Heat exchanger (Lossnay core)
Position where Ceiling suspension
()
fixture is changed
Ceiling suspension fixture
149
Inspection
600 or more
150 to 250
79 1164 79
opening
High-performance filter (sold separately attachment position)
149
Air filters
Position where duct direction is changed
Maintenance space for heat exchanger, air filters, and fans
Position where Ceiling suspension
()
fixture is changed
Ceiling suspension fixture
Air exhaust fan
EA
(exhaust air)
920
1231
OA
(outside air)
600 or more
150 to 250
Heat exchanger (Lossnay core)
79 1164 79
Damper plate
149
1030
149
Inspection
opening
149
Air filters
Ceiling suspension fixture
RA
(return air)
1263
SA
(supply air)
Power cord opening
22
Air supply fan
Control box Maintenance cover
High-performance filter (sold separately attachment position)
φ 258
φ 242
90
10
398
—10——10—
LGH-200RX3-E,LGH-200RX3-E-60
LGH-150RX3-E
*
Attention
1. If condensation is expected to form, heat up the fresh outside air using a duct heater, etc.
2. An inspection port (450 × 450 – 600 × 600 mm) must be installed on the filter and Lossnay core removing side.
3. The two outdoor ducts must be covered with heat-insulating material in order to prevent condensation from forming. The two indoor ducts may be covered with heat-insulation if Lossnay is to be installed in the circumstance of higher tem­perature in summer.
4. Installing the duct damper is preferred also to prevent the outdoor air introduced to room if there has strongthern wind, when the unit operates or stops.
5. The outside ducts must be tilted at a gradient (1/30 or more) down toward the outdoor area from Lossnay unit.
*
Attention
1. If condensation is expected to form, heat up the fresh outside air using a duct heater, etc.
2. An inspection port (450 × 450 – 600 × 600 mm) must be installed on the filter and Lossnay core removing side.
3. The two outdoor ducts must be covered with heat-insulating material in order to prevent condensation from forming. The two indoor ducts may be covered with heat-insulation if Lossnay is to be installed in the circumstance of higher tem­perature in summer.
4. Installing the duct damper is preferred also to prevent the outdoor air introduced to room if there has strongthern wind, when the unit operates or stops.
5. The outside ducts must be tilted at a gradient (1/30 or more) down toward the outdoor area from Lossnay unit.
Unit (mm)
Unit (mm)
* Specifications subject to change without notice.
* Specifications subject to change without notice.
Air exhaust fan
Damper plate 1030
Ceiling suspension fixture
964
Air supply fan
φ 350
1046
26
705
RA
(return air)
SA
(supply air)
800
100
EA
(exhaust air)
1004
OA
(outside air)
600 or more
Maintenance space for heat exchanger, air filters, and fans
Ceiling suspension fixture
510
Inspection
Air filters
opening
1662 1164
150 to 250
Heat exchanger (Lossnay core)
249130 249 130
Control box
Maintenance cover
High-performance filter (sold separately attachment position)
Power cord opening
(exhaust air)
(outside air)
Maintenance space for heat exchanger, air filters, and fans
Air exhaust fan
EA
740
1231
OA
600 or more
150 to 250
Heat exchanger (Lossnay core)
Ceiling suspension fixture
Damper plate
1030
Inspection
opening
Air filters
1662 1164
249130 249 130
Ceiling suspension fixture
Air supply fan
Control box
Maintenance cover
High-performance filter (sold separately attachment position)
Power cord opening
1194
RA
(return air)
1273
SA
(supply air)
26
705
φ 350
800
100
—11——11—

3. Wiring diagrams

GM
231456AB
S
13
9 8 7
M1
M2
Operation monitor output MAX MIN
AC 240 V 2A AC 220 V 100 mA DC 24 V 2A DC 5 V 100 mA
Malfunction monitor output MAX MIN
AC 240 V 1A AC 220 V 100 mA DC 24 V 1A DC 5 V 100 mA
N L
PE
SA1
SA2
SW5
SW2
SW1
WHITE
WHITE
BLUE BLUE
GREY
GREY
ORANGE ORANGE
BROWN BROWN
RED
YELLOW
BROWN
BLUE
Breker
TH1(OA)
PZ-41SLB
PZ-52SF
CN16
CN16
High Low
Unchaged a-contact
High/Low select connector
CN7
CN2
CN6
CN1
6
1
1
S1
S2
TM1
GREEN/YELLOW
CN32
TB5
Transmission cable
Uncharged a-contact
12V or
24V DC
(non-polar)
TM2
Shield wire
3
External control input
10
TM3
SW3
X2
X1
X5
High
Extra high
BLUE
Exhaust fan motor
CN10
CN9
High
Supply fan motor
WHITE
ORANGE
YELLOW
GREY
BLACK
X4
X3
Extra high
SW4
1
5
1
5
CN8-1
RED
CN8-2
BROWN
ZNR102
DSA1
C101
Fuse 250V 6.3A
ZNR101
C
C
TR
M-NET-transmission cable
LS
CN5
TH2(RA)
Lossnay unit MAX 15 units
Mr.Slim
X8
X7
N L
Power supply 220-240 V ~50Hz 220 V ~60Hz
* Specifications subject to change without notice.
Symbol explanation
M1 : Motor for exhaust fan M2 : Motor for supply fan C : Capacitor GM : Motor for Bypass movement LS : Microswitch TH1 : Thermistor for outside air TH2 : Thermistor for return air SW1 : Switch (Main/Sub change) SW2, 5
: Switch (Function selection)
SW3 : High/E.high select switch
(Exhaust fan)
SW4 : High/E.high select switch
(Supply fan) TM1 : Terminal block (Power supply) TM2 : Terminal block (Transmission
cable and external control input) TM3 : Terminal block (Monitor output) TB5 : Terminal block
(M-NET Transmission cable) S1, S2
: Connector (Power supply) TR : Control circuit transformer X7 : Relay contact
(For operation monitor output)
X8 : Relay contact
(For malfunction monitor output)
CN1 :
Connector (Transformer primary)
CN2 :
Connector
(Transformer secondary) CN5 : Connector (Thermistor) CN6 : Connector (Microswitch) CN7 : Connector
(Motor for Bypass operation) CN8-1
: Tab connector (Fan motor)
CN8-2
: Tab connector (Fan motor) CN9 : Connector (Fan motor) CN10 : Connector (Fan motor) CN16 : Connector (High/Low switch) CN32 :
Connector (Remote control selection)
SA1 : Address setting rotary switch
(10 digit)
SA2 : Address setting rotary switch
(1 digit)
MARK
: Indicates terminal block
: Connector
: Board insertion connector or fas-
tening connector of control board
*1
*1
*1
*
Attention
1. This must be used with Mitsubishi Electric Air-Conditioner Network System. (MELANS)
2. External control input (TM2) is impossible to use on the Lossnay addressed to “Sub” (SW1) unit.
3. PZ-41SLB and PZ-52SF cannot be used simultaneously.
NOTE
1. TM1, TM2, TM3, TB5 shown in bold lines are field work.
2. Breaker should be provided by the customer.
3. Be sure to connect the grounding wire.
LGH-15RX
3
-E,LGH-25RX3-E,LGH-35RX3-E,LGH-50RX3-E,LGH-80RX3-E,LGH-100RX3-E,LGH-100RX3-E-60
—12——12—
NL
PE
2
3 1
4
5
6
A
B
S
9
87
10
C
Supply fan motor
Exhaust fan motor
Supply fan motor
Exhaust fan motor
C
M2
M1
M2
M1
ABS65
LS
GM
LS
GM
TM3
CN10 CN9
1
5
1
5
CN8-1
CN8-2
ZNR102
DSA1
C
TB5TM2
TM1
GREEN/YELLOW
BROWN RED
BLACK
GREY
YELLOW
ORANGE
BLUE
WHITE
GREEN/YELLOW
X3
X4
X1
X2
WHITE
SA1
SA2
SW5SW2
SW1(Main)
CN16
CN7 CN2 CN6
CN1
611
S1 S2
CN32
(TB5)
TM2
3
C101
ZNR101
C
TR
CN5
TH2(RA)
TH1(OA)
BROWN
BLUE
ORANGE
ORANGE
GREY
GREY
BLUE
BLUE
BROWN
BROWN
RED
YELLOW
WHITE
Fuse 250V 6.3A
X5
X7 X8
31
CN16
High
Low
Unchaged a-contact
High/Low select connector
Uncharged a-contact
Shield wire M-NET-transmission
cable
External control input
Transmission cable Lossnay unit
MAX 7 units
Breker
Mr.Slim
(non-polar)
24V DC
12V or
PZ-41SLB
PZ-52SF
2
3 1
4
5
6
A
B
S
9
87
10
(TM3)
CN10 CN9
Extra high
1
5
1
5
CN8-1
CN8-2
ZNR102
DSA1
BROWN
High
Extra high
High
SW4
BLACK
GREY
YELLOW
ORANGE
BLUE
WHITE
SW3
Extra high
High
Extra high
High
SW4 SW3
X3
X4
X1
X2
WHITE
SA1
SA2
SW5SW2
SW1(Sub)
(CN16)
CN7 CN2 CN6
CN1
611
S1 S2
(CN32)
(TB5)
(TM2)
3
C101
ZNR101
TR
CN5
TH2(RA)
TH1(OA)
BROWN
BLUE
ORANGE
ORANGE
GREY
GREY
BLUE
BLUE
BROWN
BROWN
RED
YELLOW
WHITE
Fuse 250V 6.3A
X5
X7 X8
Power supply 220-240 V ~50Hz 220 V ~60Hz
NL
Operation monitor output MAX MIN AC 240 V 2A AC 220 V 100 mA DC 24 V 2A DC 5 V 100 mA
Malfunction monitor output MAX MIN AC 240 V 1A AC 220 V 100 mA DC 24 V 1A DC 5 V 100 mA
* Specifications subject to change without notice.
Symbol explanation
M1 : Motor for exhaust fan M2 : Motor for supply fan C : Capacitor GM : Motor for Bypass movement LS : Microswitch TH1 : Thermistor for outside air TH2 : Thermistor for return air SW1 : Switch (Main/Sub change) SW2, 5
: Switch (Function selection)
SW3 : High/E.high select switch
(Exhaust fan)
SW4 : High/E.high select switch
(Supply fan) TM1 : Terminal block (Power supply) TM2 : Terminal block (Transmission
cable and external control input) TM3 : Terminal block (Monitor output) TB5 : Terminal block
(M-NET Transmission cable) S1, S2
: Connector (Power supply) TR : Control circuit transformer X7 : Relay contact
(For operation monitor output)
X8 : Relay contact
(For malfunction monitor output)
CN1 :
Connector (Transformer primary)
CN2 :
Connector
(Transformer secondary) CN5 : Connector (Thermistor) CN6 : Connector (Microswitch) CN7 : Connector
(Motor for Bypass operation) CN8-1
: Tab connector (Fan motor)
CN8-2
: Tab connector (Fan motor) CN9 : Connector (Fan motor) CN10 : Connector (Fan motor) CN16 : Connector (High/Low switch) CN32 :
Connector (Remote control selection)
SA1 : Address setting rotary switch
(10 digit)
SA2 : Address setting rotary switch
(1 digit)
MARK
: Indicates terminal block
: Connector
: Board insertion connector or fas-
tening connector of control board
*1
*1
*1
*
Attention
1. This must be used with Mitsubishi Electric Air-Conditioner Network System. (MELANS)
2. External control input (TM2) is impossible to use on the Lossnay addressed to Sub (SW1) unit.
3. PZ-41SLB and PZ-52SF cannot be used simultaneously.
NOTE 1. TM1, TM2, TM3, TB5 shown in bold lines are field work.
2. Breaker should be provided by the customer.
3. Be sure to connect the grounding wire.
LGH-150RX
3
-E,LGH-200RX3-E,LGH-200RX3-E-60
—13——13—

4. Maintenance procedures

4-1 Blower Parts

1Remove the cover fixing screw. 2Pull back the hinged clip.
2Open the door and lift off of the hinge brackets.
3Remove Filters from the unit. 4Remove Cores from the unit.
LGH-15RX3-E~LGH-100RX3-E type
Hinge Maintenance Cover
LGH-15RX
3-E~LGH-100RX3-E type
Core
Screw Screw
Filter Filter Control Box Cover
LGH-150RX
3-E,LGH-200RX3-E type
Hinge Maintenance Cover
LGH-150RX
3-E,LGH-200RX3-E type
Core
—14——14—
5Remove screw from the core-guide,Remove core-
guide.
6Remove separator from the blower portion.
7Remove screws from the motor base.
8Remove the pre-assembled blower.
Core Guide
Separator
Motor Base Motor
Pre-assembled Blower
—15——15—

4-2 Damper Movement Motor Part (All units available)

4-3 Circuit Board Part

(1)LGH-15RX3-E~LGH-100RX3-E type
1Remove (3) screws from the control box cover.
1Remove (2) screws out from the damper motor
cover.
2Take the damper movement motor out of the cover.
Damper Motor Cover
Damper Movement Motor
Control Box Cover
—16——16—
2Remove (2) screws from capacitors.
3Remove all harnesses connected to the circuit
board.
4Take the circuit board out.
Capacitors
Circuit Board
—17——17—
(2)
LGH-150RX3-E,LGH-200RX3-E (-60) type
1Remove (4) screws from the control box cover.
2Remove all harnesses connected to the circuit
board.
3Take the circuit board out.
—18——18—
Address setting switches (SA1 and SA2)
(The factory setting is "0".)
Function selection switch
(The factory setting is SW5 and SW6 set to "ON", and all others set to "OFF".)
(Sub)
Blue
To motor (capacitor)
To motor (capacitor)
Transformer
PCB Ground wire
P section
Must be securely grounded.
*When inserting the PCB ASSY into the spacer,
press down on the circuit board near the spacer before inserting it.
To motor and GM ground
Special High/High selection switch
(The factory setting is "Special High".)
To motor and GM ground
Brown
Main/Sub selection switch
(The factory setting is "Sub".)
Main/Sub selection switch
(The factory setting is "Main".)
Function selection switch
(The factory setting is SW5 and SW6 set to "ON", and all others set to "OFF".)
Address setting switches (SA1 and SA2)
(The factory setting is "0".)
CAUTION Unit : LGH-150RX3-E,LGH-200RX3-E All settings should be re-set the same as
previous.
a.Main/Sub change switch (SW1)
Upper PCB : Main
Lower PCB : Sub b.Address switch (SA1,SA2) c.Function switch (SW2,SW5) d.Fan speed selection switch (SW3,SW4)
—19——19—
—20——20—

5. Parts list

Please note the following when using the parts list.
1. To order parts, contact the nearest office of MITSUBISHI ELECTRIC Cor
poration.
2. When ordering parts, always indicate the part number, part name, and number of parts required.
3. Parts are not always available, and it may take time for you to receive them.
4. There may be specification improvements or prices changes.
5. Specifications and prices are as of January 2002.
6. Parts marked are critical for safety. To maintain safety and performance, always replace these parts with the parts prescribed.
7. The numbers that are circled in the exploded view are the same as the reference number for the part being indicated.
Description of screw abbreviations
Screw
4 × 16
Abbreviation
PC screw PRC screw PP screw SW · PP screw PPT screw PCT screw PTT screw PT screw SET screw SQ · SET screw P · SET screw PMT screw HS · SET screw P · R · W screw P · C · W screw P · R · C . W screw R · W screw PW · PP screw SW-PW · PP screw
Description
Cross recess flat head machine screw Cross recess oval head machine screw Cross recess pan head machine screw Cross recess pan head screw with spring washer Cross recess tapping screw Cross recess flat head tapping screw Cross recess truss head tapping screw Cross recess truss head machine screw Slotted head stop screw Square head stop screw Pan head stop screw Primer truss head screw Hexagon head stop screw Cross recess round wood screw Cross recess flat head wood screw Cross recess round and flat wood screw Slotted round wood screw Cross recess pan head screw with small washer Cross recess pan head machine screw with spring washer and flat washer
Screw diameter Length
Loading...
+ 49 hidden pages