Mitsubishi LGH-15...200RX3 TECHNICAL MANUAL

TECHNICAL MANUAL (CONTROLS)
Models Lossnay Unit
LGH-15RX3-E LGH-25RX3-E LGH-35RX3-E LGH-50RX3-E LGH-80RX3-E LGH-100RX3-E LGH-150RX3-E LGH-200RX3-E
■ Lossnay Remote Controller
PZ-41SLB-E PZ-52SF-E
CONTENTS
1. Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2. Applicable Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
3. Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
4. System Features and Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
5. Examples of Applications Using External Control Input Terminals,
Operation Monitor Output Terminals and Malfunction Monitor Output Terminals . . . . . . . . . . . . . . . . . . . . . . . 21
6. Precautions When Designing Systems of M-NET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
7. Cable Installation of the M-NET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
8. System Designs of M-NET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
9. Automatic Ventilation Switching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
10. Cold Weather Area Operation Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
11. Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
12. Installation method (Model LGH-RX3-E series) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
13. Lossnay Remote Controller (PZ-41SLB-E) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
14. Lossnay M-NET Remote Controller (PZ-52SF-E) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
15. Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
* Centralised Controller (MJ-103MTRA)
(Operation setting, Initial setting, Group configuration setting, Interlocked operation setting) . . . . . . . . . . . . 74
* Remote Controllers for Mr. Slim indoor unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
* Network Remote Controller (PAR-F25MA) (Interlocked registration) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
1
1. Summary
This is a technical manual relating to the controls for implementing the following systems of the commercial-type Lossnay (LGH­RX3-E Series).
Possible System Configurations
(1) When using only the Lossnay remote controller. (2)
Linking Lossnay and City Multi units.
(3)
Linking Mr. Slim (A-control, K-control).
(4)
Lossnay central control systems.
(5)
Linking with external equipment (BMS).
2. Applicable Models
Lossnay (LGH-RX
3-E
)
These models have temperature sensors at RA and OA sides. It can automatically switch to the ventilation mode. (Lossnay/By-pass)
Model
LGH-15RX3-E
LGH-25RX3-E
LGH-35RX3-E
LGH-50RX3-E
Model
LGH-80RX3-E
LGH-100RX3-E
LGH-150RX3-E
LGH-200RX3-E
Lossnay Remote Controller (PZ-41SLB-E
)
Use when operating from 1 to 15 Lossnay units together at the same time. When using M-NET transmission to operate from centralised control, use the PZ-52SF-E. It can start and stop the unit, change fan speed, switch the ventilation mode. It also includes indicators that show errors and when filter maintenance is required. Refer to page 63.
Lossnay M-NET Remote Controller (PZ-52SF-E
)
It can be used in combination with Mitsubishi Electric Air conditioner Network system (MELANS). Refer to page 69. Since this remote controller is supplied the power from the M-NET transmission line, it cannot be linked with Mr. Slim and other such systems that do not use M-NET.
Please refer to the technical documentation for the other systems: City Multi, Mr. Slim and the central controller (MELANS).
2
3. Terminology
Interlocked Lossnay
This is a Lossnay linked to City Multi, or Mr. Slim indoor units. This is a Lossnay that has been set to interlocked group set­ting to receive signals and operate via indoor unit’s remote controller indoor unit Lossnay.
Non-interlocked Lossnay
This is a Lossnay that is not set to interlocked group setting with City Multi nor Mr. Slim indoor units. It operates using direct operating signals from the Lossnay remote controller and/or centralised controller.
Ventilation Mode
This mode controls the Lossnay damper and permits selection of heat recovery (Heat ex.), by-pass or auto modes.
Delayed Operation
The Lossnay that has been set to interlocked group setting with the indoor unit will have its operation delayed for 30 minutes after the operation of the indoor unit. When using PZ-41SLB-E, the time setting that can be set for delayed operation are 10, 20, 30, 40, 50, and 60 minutes.
External Control Input
This is an input signal for operating the Lossnay that has been sent from an external device. It is compatible with 12V-24V DC or uncharged a-contact signal.
Operation Mode
This mode is used for selecting enabling/disabling of the on/off control signal from an external device and for setting inter­locked operation of the external device and the Lossnay. Please Refer to page 22 for details.
ON/OFF interlock: Enables both “ON OFF” and “OFF ON” external signals. ON interlock: Enables “OFF ON” external signal. Disables “ON OFF” external signal. OFF interlock: Enables “ON OFF” external signal. Disables “OFF ON” external signal. External priority: Same as on/off interlock but the OFF signal from the remote controller is ignored when the
external control signal is on.
Setting Pulse Input
When the control signal from the external device outputs a pulse such as the one shown below, pulse input setting is per­formed by the Lossnay. (Optional setting DIP switch 2-2 ON
)
200 ms or more
Operation in Cold Areas
When the outdoor air is less than -10°C, continuous operation of the fan for drawing in supply air is cancelled, and intermit­tent operation is started.
RA (Return Air
)
This is the abbreviation for return air, which is the air drawn in from indoor.
OA (Outdoor Air
)
This is the abbreviation for outdoor air, which is the air drawn in from outdoor.
(
3
Classification
Control
Function
Installation
Maintenance
Item
• Multiple unit operation
• Remote controller operation
• External device operation
• External pulse control
• External monitor signal output
• Supply air fan monitor output
• External control operation mode setting
• Delayed start
• Automatic recovery following power sup­ply interruption (*1)
• Power supply start/stop function
• High/low change input
• Remote/Local control change
• The M-NET air conditioning operation.
• Centralised control by Mitsubishi building air control management system
• Interlocked with Mr. Slim
• Lossnay (heat recovery) ventilation/By­pass ventilation automatic switch
• For cold area operation
• Remote controller 2 wires wiring (non-polar)
• Address setting unnecessary
• Test operation switch
• Filter maintenance display (remote controller display)
• Inspection display (remote controller, control board LED)
• M-NET power supply display (control board LED)
Notes/Cautions
Maximum 15 units with PZ-41SLB-E; 16 units with PZ­52SF-E or other M-NET controller.
Last touch priority
Signal form: 12VDC, 24VDC, uncharged a-contact
Ditto
Uncharged a-contact (external monitor/supply air fan monitor change)
Ditto
ON/OFF , ON, OFF and External priority ON/OFF mode.
Delayed time can be varied only when the PZ-41SLB-E is connected.
Return power automatic return is fixed when the PZ­41SLB-E is connected.
Impossible when the PZ-41SLB-E is connected.
Uncharged a-contact (Part sold separately is necessary)
Uncharged a-contact (Part sold separately is necessary) (Connection is impossible when using PZ-41SLB-E)
Only when M-NET transmission cable is connected
Ditto
Can not use the PZ-41SLB-E
When the PZ-41SLB-E is connected: PVC cable ø 0.65 to 1.2 or strand wire 0.3 mm
2
to 1.25 mm2.
When M-NET is connected: shielded wire or equivalent
1.25 mm
2
to 2.00 m2.
Excluding central controller system (except automatic address)
For Lossnay single unit test operation
4. System Features and Examples
4.1 Features
*1 The operation condition is stored, and when the power is turned off and then back on, the operation condition returns to the
previous condition. (When using PZ-41SLB-E, the start/stop condition from an external device is not stored.)
M-NET System
4.2 System Example
Operating with an external device
The operation of the Lossnay will be connected with the operation or stopping of the external device.
Input of level signal or pulse signal (12V DC, 24V DC, uncharged a­contact) is possible.
1 Lossnay with 1 remote controller
This is a simple system. A Lossnay is operated independently with 1 remote controller.
Multiple Lossnay units with 1 remote controller
Up to 15 Lossnay units can be controlled at one time with one remote controller. *
2 remote controller system with 1 Lossnay
The Lossnay can be controlled from 2 remote locations.
The remote controller gives priority to the last touch.
Operating with Mr. Slim (A-control or K-control)
The Remote controller (A-control or K-control) controls the air condi­tioning device and the Lossnay.
When using the A-control remote controller operating or switching fan speed for the Lossnay individually is possible.
4
Basic System (refer to page 9)
Operation with an Air Conditioning Unit
(refer to page 12)
Operating with an External Device
(refer to page 21)
Lossnay
Non-polar 2 wires
Remote controller PZ-41SLB-E
Power supply
Lossnay
Non-polar 2 wires
Power supply
Remote controller PZ-41SLB-E
(Sub)
(Main)
Lossnay
Power supply
Lossnay
Non-polar 2 wires
Remote controller PZ-41SLB-E
Power supply
Air conditioning device and system control
It is possible to operate 16 indoor units per 1 Lossnay
Indoor unit
MA remote controller
Outdoor unit
Indoor unit
MA remote controller
Lossnay
Indoor unit
MA remote controller
Lossnay
Indoor unit
Indoor unit
MA remote controller
Indoor unit
MA remote controller
Lossnay
Indoor unit
MA remote controller
Indoor unit
MA remote controller
Lossnay
Indoor unitIndoor unit
Group 1 Group 5Group 3 Group 4Group 2
Outdoor unit Outdoor unit
Indoor unit
MA remote controller
Lossnay Lossnay
Group 1
Lossnay
Group 2 Group 3
Refrigerant 1 Refrigerant 2
Control of start/stop, fan speed and ventiliation mode is possible from the Lossnay M-NET remote controller.
Control of start/stop, fan speed and ventiliation mode is possible from the centralised controller.
It is possible to set a maximum of 16 units for 1 group.
Lossnay M-NET remote controller
PZ-52SF-E
Lossnay Lossnay
Group 1
Lossnay M-NET remote controller
PZ-52SF-E
Lossnay Lossnay LossnayLossnay
Group 3
Lossnay M-NET remote controller
PZ-52SF-E
Lossnay
Group 4Group 2
Centralised controller
Power supply unit
Lossnay M-NET remote controller
PZ-52SF-E
Lossnay
Group 5
Lossnay
Power supply
Power supply
Remote controller
Mr. Slim
(indoor unit)
Lossnay
Power supply
Power supply
Remote controller
Indoor unit
Remote controller PZ-41SLB-E
Non-polar two wires
City Multi and Lossnay Interlocked System
Centralised Management System
* In the case of LGH-150/200RX
3-E, there are 2 circuit boards installed in each unit, so count each unit as 2 Lossnay units.
Selection of inter­locked operation mode is possible.
Delayed start inter­locked operation is possible.
Use Lossnay M-NET remote controller PZ-52SF-E .
(Do not use PZ-41SLB-E).
Lossnay transmission connection terminal
5
2 remote controller system with multiple Lossnay units
It is also possible to operate 2 remote controller units when using multi­ple Lossnay units.
Power supply
Power supply
Remote controller
PZ-41SLB-E
Interlocking multiple units
When the operation signal is a uncharged a-contact signal
Interlocking/individual joint systems
By making the group setting, interlock settings have become possible. (Joint use of the air conditioner remote controller and Lossnay remote controller is possible.)
Interlocking is possible from multiple air conditioning units, etc. (excluding pulse input) (Separately sold parts are necessary depending on the operation signal).
Applicable indoor units are C type or later (for use with MA remote con­troller) models
Do not set the air conditioning unit and Lossnay unit to be part of the same group.
When the address number has been changed, the data in the memory is automatically reset.
Power suupy Power suupy Power suupy Power suupy
Lossnay
A/C A/C A/C
Remote controller PZ-41SLB-E
Air conditioning unit side remote controller
Air conditioning unit side remote controller
Air conditioning unit side remote controller
Indoor unit (01)
Centralised controller (201)
Outdoor unit (51)
Operation settings
MA remote controller
Lossnay (02)
Lossnay M-NET remote controller (PZ-52SF-E)(102)
Group 1 Group 2
Use Lossnay remote controller PZ-41SLB-E .
(Do not use PZ-52SF-E).
Lossnay transmission connection terminal
ABS65654321
Transmission cable
Transmission cable
Round terminal
M-NET Transmission cable input terminal block
Shielded wire
M-NET
Transmission cable
Remote Controller Input Terminal
Main/Sub switch (SW1)
Main Sub
(Set to Main when shipped from the factory)
( ) address
LGH-15 to 100RX3 LGH-150 and 200RX3
LGH-15 to 100RX3
TB5
LGH-150 and 200RX
3
TB5
Setting
Setting
LGH-15 to 100RX
3 LGH-150 and 200RX3
Upper circuit board [Sub] ex. SA1 = 0, SA2 = 2
Lower circuit board [Main] ex. SA1 = 0, SA2 = 1
ABS A65BS
SA1 SA1
0
1
2
0
SA1 SA2SA1 SA2
1
0
6
4.3 System Selection
Interlocked with City Multi
(
Refer to page 16
)
Lossnay operation when indoor unit is stopped
Lossnay stopping when indoor unit is operating Switching Lossnay fan speed
When interlocked with indoor unit for compatibility with both R22 and R407C
High/Low
When interlocked with indoor unit for other than the above
Fixed to high
Ventilation mode
Fixed to automatic Filter maintenance indicator Lossnay error indicator Delayed operation External control operating mode selection × Number of indoor units for interlocked group setting with one Lossnay unit
16 units
Number of Lossnay units for interlocked group setting with one indoor unit
1 unit
Interlocked with external device (BMS
)
(
Refer to page 21
)
Start/Stop Fan speed switching
Fixed to high Ventilation mode switching
Fixed to automatic Filter maintenance indicator × Lossnay error indicator × Delayed operation External control operating mode selection
Lossnay unit LGH-RX3-E
M-NET transmission cable
Remote controller
City Multi
indoor unit
Interlocked with Mr. Slim
(
Refer to page 12
)
When using A-control remote controller
Lossnay operation when indoor unit is stopped Lossnay stopping when indoor unit is operating × Lossnay fan speed switching High/Low
When using K-control controller
Lossnay operation when indoor unit is stopped × Lossnay stopping when indoor unit is operating × Lossnay fan speed switching
Fixed to high Other common items
Lossnay error indicator × Ventilation mode
Fixed to automatic
Filter maintenance indicator × Delayed operation External control operating mode selection × Number of indoor units for interlocked group setting with one Lossnay unit
1 unit
Number of Lossnay units for interlocked group setting with one indoor unit
1 unit
Slim-Lossnay connecting cable (
Enclosed accessory
)
Remote controller
Mr.Slim (A, K-control
)
indoor unit
Lossnay remote controller cannot be used.
Lossnay unit LGH-RX3-E
Independent Lossnay Unit
(
Not interlocked with
City Multi or Mr. Slim systems.
)
(
Refer to page 9
)
Start/Stop Fan speed switching High/Low
Ventilation mode
Heat ex. /
By-pass/ Auto Filter maintenance indicator Lossnay error indicator Delayed operation External control operating mode selection Number of Lossnay units
15 units
(
In the case of LGH-150/200RX3-E, count each unit as two for calcultion)
Number of remote controllers 2 units
Lossnay remote controller
(PZ41SLB-E)
EXT. signal source for interlocking to the Lossnay
Lossnay unit LGH-RX3-E
EXT. signal source for interlocking to the Lossnay
Lossnay unit LGH-RX3-E
7
Central Con-
troller Sys-
tem
Central Controller System
Centralised Controller
Power supply unit
PAC-SC34KUA
Indoor unit
Lossnay
Indoor unit
Outdoor unit
A-control Mr.Slim outdoor unit
Mr.Slim A-control remote controller
A-control Mr.Slim indoor unit
Lossnay
Lossnay M-NET remote controller (PZ-52SF-E)
EXT. signal source
Lossnay M-NET remote controller (PZ-52SF-E)
Remote controller
K-transmissoin converter
Remote controller
Mr.Slim K-control remote controller
K-control Mr.Slim indoor unit
Lossnay
LossnayLossnay
Lossnay M-NET remote controller (PZ-52SF-E)
Lossnay
Caution:
Lossnay remote controller PZ-41SLB-E can not be used.
8
Reference: Remote controller for the Lossnay and indoor unit.
Refer to the technical documentation related to the Remote controller for the indoor unit.
Remote controllers for City Multi indoor unit
Network remote controller (PAR-20MAA
)
Simple remote controller (PAR-27MEA
)
TIMER SET
PAR-20MAA
ON/OFF
CENTRALLY CONTROLLED
ERROR CODE
CLOCK
ON OFF
ßC
CHECK
CHECK MODE
FILTER
TEST RUN FUNCTION
ßC
1Hr.
NOT AVAILABLE
STAND BY DEFROST
FILTER
CHECK TEST
TEMP.
With Lossnay interlock switches and indicators.
PAR-F27MEA
ON/OFF
CENTRALLY CONTROLLED
DAILY
AUTO OFF
REMAINDER
CLOCK
ON OFF
ßC
CHECK MODE
FILTER
TEST RUN LIMIT TEMP.
ßC
1Hr.
NOT AVAILABLE
STAND BY DEFROST
FILTER
CHECK TEST
TEMP.
TIMER SET
CLOCKONOFF
Without Lossnay interlock switches and indicators.
Remote controllers for Mr. Slim indoor unit
A-control remote controller (PAR-27AA
)
K-control remote controller
ON/OFF
STAND BY DEFROST
INDOOR UNIT ADDRESS NO.
ERROR CODE OA UNIT ADDRESS NO.
CENTRALLY CONTROLLED
CLOCK
ON OFF
˚C
1Hr.
NOT AVAILABLE
˚C
CHECK MODE
FILTER
CHECK
TEST RUN
ON OFFCLOCK
FILTER
CHECK
TEST RUN
REMOTE CONTROLLER
TEMP. TIMER SET
With Lossnay interlock switches and indicators.
ON/OFF
STAND BY DEFROST
CENTRALLY CONTROLLED
CLOCK
ON OFF
˚C
1Hr.
NOT AVAILABLE
CHECK MODE
FILTER
CHECK
TEST RUN
ON OFFCLOCK
FILTER
CHECK
TEST RUN
REMOTE CONTROLLER
TEMP. TIMER SET
˚C
Without Lossnay interlock switches and indicators.
Remote controllers for Lossnay unit
Lossnay remote controller (PZ-41SLB-E) Lossnay M-NET remote controller (PZ-52SF-E)
DELAYSTART
FILTER
PZ-41SLB-E
2CONTROLLERS
BY-PASS
CHECK SETTING
FILTER MIN.DELAYED
AUTO
HEATEX.
INTERLOCKED
With Lossnay interlock switches and indicators.
CENTRAL
HEAT EX. BY-PASS AUTO
CHECK
INTERLOCKED
FILTER
ON/OFF
NOT
AVAILABLE
FILTER
Without Lossnay interlock switches and indicators.
9
4.4 Basic System
4.4.1 System Summary
4.4.2 Operation of Multiple Units
Design Example 1 Basic system
This is a simple system. A Lossnay is operated independently with 1 remote controller.
Lossnay
Non-polar 2 wires
Remote controller PZ-41SLB-E
Power supply
Design Example 2 Lossnay control of multiple units
Up to 15 Lossnay units can be controlled at one time with 1 remote controller switch. (up to 7 units when using LGH­150/200RX
3)
Lossnay
Non-polar 2 wires
Power supply
Remote controller PZ-41SLB-E
(Sub)
(Main)
Lossnay
Power supply
Design Example 3 2 remote controller system
The Lossnay can be controlled from 2 remote locations.
The remote controller gives pri­ority to the last touch.
Lossnay
Non-polar 2 wires
Remote controller PZ-41SLB-E
Power supply
Feature
For LGH-15 to 100RX
3, 1 remote controller can operate from 1 to 15 Lossnay units. For using LGH-
150/200RX3, 1 remote controller can operate from 1 to 7 Lossnay units.
Ordered part
Remote controller PZ-41SLB-E
Also connect the power to the second and following Lossnay units.
Notes
The maximum extension of the transmission cable is 500 m or less (between Lossnay and remote controller switch, between Lossnay and Lossnay).
The main or Sub setting on the Lossnay is necessary.
Note:
The external device operation signal, and pulse signals can only be connected to the Lossnay on the Main setting.
When the M-NET system is connected, do not connect the transmission cable to TM2.
System Example
Lossnay (Main)
Power supply
(Transmission cable extension is 500 m or less) PVC cable ø0.65 to 1.2 or strand wire 0.3 mm
Remote controller PZ-41SLB-E
2
to 1.25 mm2.
Lossnay (Sub)
Power supply
Lossnay (Sub)
up to 15 units
(Be sure to turn on the power for the second and following Lossnay units.)
Power supply
10
Combined Line Method
Connect the transmission cable from the first Lossnay to the second, the second to the third, and so on up to a maximum of 15 units.
(1) Up to four wires can be connected to one signal terminal when a transmission cable is ø0.65 or strand wire 0.3 mm
2
, or up
to 2 wires in other cases.
(2) The signal is non-polar, so it is not necessary to align polarity.
65
65
Lossnay
Power supply
Lossnay
Power supply
Lossnay
Power supply
Remote controller PZ-41SLB-E
Set to Main Set to Sub
Main/Sub selection switch
(SW1)
Main Sub
Transmission cable
Transmission cable
Connect to remote controller (PZ-41SLB-E)
Connect to third Lossnay
Lossnay Main/Sub Setting
Be sure to make the Main/Sub setting when operating multiple Lossnay units. When operating multiple Lossnay units, set the first one to Main,” set the second and following to Sub. Be sure the power is off when making the settings.
Change the Main/Sub switch (SW1) on the control board to Sub for the second and following Lossnay units.
Operation Method
Up to 15 Lossnay units (up to seven units when using LGH-150/200RX3-E) can be operated when running at the same time. (Individual control is not possible)
Note:
In the case of LGH-150/200RX3-E, there are two circuit boards installed in each unit. Therefore, count each unit as two units in calculations when controlling multiple units. For example, 5 LGH-150RX
3-E units would count as 10 units. (For
150/200RX3-E type only, a maximum of seven units is possible.)
(Main)
Lossnay
(Sub)
Lossnay
(Sub)
Lossnay
Power supply Power supply Power supply
Remote controller PZ-41SLB-E
11
4.4.3 Operation with 2 Remote controllers
System Example
Operation Method
(1) When there are 2 remote controllers, 2 CONTROLLERS will display on the LCD readout’s upper region. (2) The operation is the same with each remote controller. In this case, the Lossnay gives operating priority to the last button
push.
Characteristics
Remote controller
Note
Lossnay can be operated from two remote locations. • Use only up to 2 remote controller
Lossnay conditions can be checked from two remote Lossnay remote controller (Operation will not go normally if 3
locations. PZ-41SLB-E remote controller switches are con
The remote controller gives priority to the last touch. nected.)
Lossnay
Power supply
Lossnay
Power supply
Transmission
cable extension
is 500 m or less
PVC cable
ø0.65 to 1.2 or
strand wire
0.3 mm2 to 1.25 mm2.
Remote controller PZ-41SLB-E
Transmission cable extension is 500 m or less
PVC cable
ø0.65 to 1.2 or
strand wire
0.3 mm2 to 1.25 mm2.
Lossnay up to 15 units, or 7 units for LGH 150/200 type (Be sure to turn on the power for the second and following Lossnay units.)
Lossnay
Power supply
Lossnay
Power supply
Lossnay
Power supply
Lossnay
Power supply
Remote controller PZ-41SLB-E
Remote controller PZ-41SLB-E
Remote controller PZ-41SLB-E
Lossnay up to 15 units, or 7 units for LGH 150/200 type (Be sure to turn on the power for the second and following Lossnay units.)
Lossnay
2CONTROLLERS
BY-PASS
AUTO
HEAT EX.
Remote controller
Remote controller
Close-up of display region
12
4.5 Interlocking with Mr. Slim
4.5.1 Interlocked Mr. Slim and Lossnay System
Features
Interlocked operation with Mitsubishi air-conditioners is possible.
System Example
Slim-Lossnay connection cable (
Enclosed accessory
)
A-control or K-control Mr.Slim indoor unit
A-control or K-control Mr.Slim outdoor unit
A-control or K-control
remote controller
Lossnay unit LGH-RX
3-E
Lossnay Function Table (Interlocked settings
)
Item
Number of indoor units that can be set to interlocked opera­tion with 1 Lossnay unit in each group
Number of Lossnay units that can be set to interlocked oper­ation with 1 indoor unit
Operation of Lossnay unit only (
When indoor unit is stopped
)
A-control
K-control
Independent Lossnay unit start and stop (
When indoor unit is operating
)
A-control
K-control
Delayed operation (
Optional setting
)
Fan speed switching A-control
K-control
Ventilation mode
Filter indicator
Error
Restrictions and precautions
Details
1 unit
1 unit
Possible
Not possible
Not possible
Not possible
30 minute delayed operation when indoor unit cooling/heating is started
High/Low
Fixed to high
Fixed to automatic
Not possible
Not possible
* The Lossnay remote controller cannot be used on systems
interlocked with Mr. Slim. When connecting a PZ-41SLB-E to a Lossnay unit, ON/OFF and High/Low operation by the PZ-41SLB-E can­not be reflected to the display of the Mr. Slims A-control remote controller.
13
Controller Function Table especially regarded to the Lossnay unit
Lossnay remote
controller
PZ-41SLB-E, PZ-52SF-E
K-control
remote
controller
«
×
× (Automatic)
×
«
×
×
×
×
×
×
A-control remote
controller
PAR-S27AA
« «
× (Automatic)
×
« «
×
×
×
×
×
Local Remote
Model
Start/Stop
Fan speed switching
Ventilation mode switching
Priority instructions. Local permitted/prohibited
Status (Operation/Stop
)
Fan speed switching
Ventilation mode
Error
Error content
Filter sign
Local permitted/prohibited
Not used to the interlocked
Lossnays
Monitoring Operation
Switched and display
«
: Group only (or function available)× : Not available
For details about the operation or display of the A-control remote controller (PAR-27AA), refer to page 81.
14
4.6 Combination with City Multi
4.6.1 Independent Lossnay System with Lossnay M-NET Remote Controller and MELANS
Features
The Mitsubishi Electric air-conditioner network system (MELANS)can operate and monitor each group of Lossnay units and air-conditioners.
Can also perform operations using Lossnay M-NET remote controller.
System Examples: 1
The following groups can be configured.
Lossnay
(001)
Centralised controller
(
000
)
Power supply unit
Lossnay M-NET remote
controller PZ-52SF-E
(106)
(103)
( )
address
Group1
Group6
Group2 Group3 Group4 Group5
Lossnay M-NET remote
controller PZ-52SF-E
(156)
(101)
Lossnay
(013)
Group8
Lossnay M-NET remote
controller PZ-52SF-E
(114)
Lossnay
(014)
Lossnay
(015)
Lossnay
(002)
Lossnay
(004)
Lossnay
(005)
Lossnay
(006)
Lossnay
(003)
Lossnay
(010)
Lossnay
(008)
Lossnay M-NET remote
controller PZ-52SF-E
(107)
(157)
Lossnay
(007)
Lossnay M-NET remote
controller PZ-52SF-E
Indoor unit (009)
MA Remote controller
Group7
Indoor unit (011)
Indoor unit
(012)
MA Remote controller
Group9
Indoor unit (016)
MA Remote controller
Outdoor unit
(059)
Group 1 : Group of 1 Lossnay unit and 1 Lossnay M-NET remote controller. Group 2 : Group without Lossnay M-NET remote controller. Group 3 : Group of multiple Lossnay units and 1 Lossnay M-NET remote controller. Group 4 : Group of 1 Lossnay unit and 2 Lossnay M-NET remote controllers. Group 5 : Group of multiple Lossnay units and 2 Lossnay M-NET remote controllers. Group 6 : Group of 1 indoor unit and 1 Lossnay unit in interlocked operation. Group 7 : Group of multiple indoor units and 1 Lossnay unit in interlocked operation. Group 8 : Group of multiple Lossnay units connected to 1 indoor unit transmission cable and 1 Lossnay M-NET
remote controller.
Group 9 : Group with no Lossnay units.
Caution:
Lossnay remote controller PZ-41SLB-E can not be used.
15
Lossnay Function Table (Group Setting
)
Controller Function Table
Item
Number of Lossnay remote controllers and/or MELANS units that can be connected to 1 Lossnay unit
Operation of 2 remote controllers in 1 group
Fan speed switching
Ventilation mode
Filter indicator
Error
Details
5 units (
Number of Lossnay remote controller is 2 units max.
)
Possible
High/Low
Heat ex. / By-pass / Automatic
3000 hours / 1500 hours / 4500 hours / No display
Display
Centralised
controller
MJ-180A
100 Groups/
100 Units
*200 Groups/
200 Units
n
«
n
n
« « « « « « « «
6
42
1
«
Centralised
controller
MJ-103MTRA
50 Groups/
50 Units
n n n
n
« « « « « « « «
3
21
10
«
MA remote
controller
PAR-20MAA
ME remote
controller
PAR-F27MEA
Lossnay M-
NET remote
controller
PZ-52SF-E
1 Group/
16 Units
« « «
×
« « « « « « «
×
×
×
×
×
No. of controllable (Groups/Units
)
Local Remote
Model
MELANS Series
Start/Stop
Fan speed switching
Ventilation mode switching
Priority instructions. Local permitted/prohibited
Status (Operation/Stop
)
Fan speed switching
Ventilation mode
Error
Error content
Filter sign
Local permitted/prohibited
Weekly
Stop/Starts per day
Stop/Starts per week
Minimum setting (minutes
)
Error record
Scheduling/
Recording
Monitoring
Operation
Switches and display
n
: Group/batch
«
: Group only (or function available
)
× : Not available
* Can be expanded to 200 units by using 2 gateway units.
For details about the operation or display of the Lossnay M-NET remote controller (PZ-52SF-E) refer to page 69.
For details about the operation or display of the Centralised controller (MJ-103MTRA) refer to page 74.
Not used to
the non-interrocked Lossnay
16
4.6.2 City Multi and Lossnay Interlocked System
Characteristics
Interlocked operation with Mitsubishi air-conditioners is possible.
Can also perform independent Lossnay operations using MA remote controller or ME remote controller.
System Examples
The following groups can be configured.
Single Refrigerant System
Group1
Lossnay
(005)
Group3
Lossnay
(007)
Lossnay
(009)
Lossnay
(002)
Indoor unit (001)
MA Remote controller
Indoor unit (010)
MA Remote controller
Group2
Indoor unit (003)
Indoor unit
(004)
MA Remote controller
Group4 Group5
Indoor unit (006)
Indoor unit (008)
MA Remote controller
MA Remote controller
Outdoor unit (051)
( ) address
Lossnay remote controller PZ-41SLB-E can not be used with any group.
Multiple Refrigerants System
Group1
Lossnay
(004)
Group3
Lossnay
(008)
Lossnay
(002)
Indoor unit (001)
MA Remote controller
Group2
Indoor unit (003)
Indoor unit
(005)
Indoor unit
(007)
MA Remote controller
Indoor unit (006)
MA Remote
controller
Outdoor unit (051) Outdoor unit (055)
( ) address
Refrigerant 1 Refrigerant 2
Group 1 : Group of 1 indoor unit and 1 Lossnay in interlocked operation. Group 2 : Group of multiple indoor units and 1 Lossnay unit in interlocked operation. Group 3 : Group of 1 indoor unit with 2 remote controllers and 1 Lossnay unit in interlocked operation. Group 4, 5 : Group of multiple groups and 1 Lossnay unit in interlocked operation.
Group 1 : Group of 1 indoor unit and 1 Lossnay in interlocked operation. Group 2 : Group of multiple indoor units (with different refrigerants) and 1 Lossnay unit in interlocked operation. Group 3 : Group of multiple indoor units (with same refrigerant) and 1 Lossnay unit in interlocked operation.
17
Lossnay Function Table (Interlocked Settings)
Controller Function Table especially regarded to the Lossnay unit
Item
Number of indoor units that can be set to interlocked opera­tion with 1 Lossnay unit in each group
Number of Lossnay units that can be set to interlocked oper­ation with 1 indoor unit
Independent start/stop of ventilation (Lossnay)
Delayed operation (Optional setting)
Fan speed switching Indoor unit compatible with both R22
and R407C
Units other than the above
Ventilation mode
Filter maintenance indicator
Error
Restrictions and precautions
Details
16 units per group
1 unit
Possible
30 minute delayed operation when indoor unit cooling/heat­ing is started
High/Low
Fixed to high
Fixed to automatic
3000 hours / 1500 hours / 4500 hours / No display
Display
* Lossnays cannot be interlocked to the indoor units using K-
transmission converter.
MA remote
controller
PAR-20MAA
« «
× (Automatic)
×
« «
×
« « « «
×
2
×
10
×
ME remote
controller
PAR-F27MEA
« «
× (Automatic)
×
« «
×
« « « «
× (Dayly)
2
×
10
×
Lossnay
M-NET remote
controller
PZ-52SF-E
« « «
×
« « « « « « «
×
×
×
×
×
Local Remote
Model
Start/Stop
Fan speed switching
Ventilation mode switching
Priority instructions. Local permitted/prohibited
Status (Operation/Stop
)
Fan speed switching
Ventilation mode
Error
Error content
Filter sign
Local permitted/prohibited
Weekly
Stop/Starts per day
Stop/Starts per week
Minimum setting (minutes
)
Error record
Scheduling/
Recording
Monitoring Operation
Switches and display
«
: Function available × : Not available
For details about the operation or display of the remote controller (PAR-F27MEA, PAR-20MAA), please refer to those Manuals.
18
4.6.3 MA Remote Controller/ME Remote Controller in Combination with Lossnay M-NET Remote Controller
System
The MA remote controller, ME remote controller, and Lossnay M-NET remote controller can be used in combination.
Combination of Air Conditioner Remote Control and Lossnay Remote Control
Indoor unit (001)
Lossnay
(002)
Lossnay M-NET remote controller PZ-52SF-E (102)
MA remote controller (101)
Centralised
controller
(201)
Outdoor unit
(051)
Power supply unit
Group1 Group2
Interlocked operation setting
( ) address
Indoor Unit Lossnay LGH-RX3-E
Model for MA remote control (Type C or later) «
Model for other than MA remote control (Type B or earlier) ×
«
: Compatible × : Incompatible
System Examples: 1
Setting Method
(1) Make the Group setting for the indoor unit. (2) Make the Group setting for the Lossnay unit. (3) Set the indoor unit and Lossnay unit in interlocked operation. When using the centralised controller, make both the Group setting and operation setting for the previously mentioned units. Though the MJ-180A cannot set interlocked settings, it should set at MA/ME remote controllers.
Characteristics
(1) When the indoor unit is set for interlocked operation in 1 group:
Interlocked operation with the indoor unit from the air conditioner remote controller is possible and can switch between High/Low/Off. From the air conditioner remote controller it is possible to switch the Lossnay only between High/Low/Off. From the Lossnay remote controller it is possible to switch the Lossnay between High/Low/Off.
(2) When the 2 or more indoor units with different group are set for interlocked operation, the Lossnay will operate if at least 1
group operates. The Lossnay will stop operation if all groups stop operation. From an air conditioner remote controller it is possible to switch the Lossnay only between High/Low when other groups are operating. From the Lossnay remote controller it is possible to switch the Lossnay between High/Low/Off.
Note:
If the display on the MA remote controller/ME remote controller, or other air conditioner remote controller, is cancelled, the air
conditioner remote controller will not show the ventilation display even if you operate the Lossnay from the Lossnay M-NET remote controller.
Note:
Transmission cable power control for indoor units Be sure usage is within the following boundaries.
Indoor units + ME remote controllers (compact remote controllers) + Lossnay M-NET remote controllers is less than or equal
to 40 units.
Indoor units are less than or equal to 20 units.
(The numbers of MA remote controllers and Lossnay units are not included in the above number of units.)
19
System Examples: 2
A mixed system including the City Multi can also be configured.
Note:
Do not use Lossnay remote controller PZ-41SLB-E in case of a system using M-NET transmission cable.
(
109
)
(
103
)
(
106
)(
107
)
(
157
)
(
111
)
(
114
)
(
116
)
Indoor unit
(011)
Group1 Group2
Group6 Group7 Group8 Group9
Group3 Group4 Group5
Centralised controller (000
)
Outdoor unit
(
059
)
Power supply unit
Lossnay M-NET remote
controller PZ-52SF-E
Lossnay M-NET remote
controller PZ-52SF-E
Lossnay M-NET remote
controller PZ-52SF-E
Lossnay M-NET remote
controller PZ-52SF-E
Lossnay M-NET remote
controller PZ-52SF-E
ME
remote controller
ME
remote controller
ME
remote controller
( )
address
(
101
)
(
156
)
Lossnay
(001)
Lossnay
(010)
Lossnay
(013)
Lossnay
(014)
Lossnay
(015)
Lossnay
(002)
Lossnay
(003)
Lossnay
(004)
Lossnay
(005)
Lossnay
(006)
Lossnay
(007)
Lossnay(008)
Indoor unit
(009)
Indoor unit
(012)
Indoor unit
(016)
Group 1 : Group of 1 Lossnay unit and 1 Lossnay M-NET remote controller. Group 2 : Group with no Lossnay M-NET remote controller. Group 3 : Group of multiple Lossnay units and 1 Lossnay M-NET remote controller. Group 4 : Group of 1 Lossnay unit and 2 Lossnay M-NET remote controllers. Group 5 : Group of multiple Lossnay units and 2 Lossnay M-NET remote controllers. Group 6 : Group of 1 indoor unit and 1 Lossnay unit in interlocked operation. Group 7 : Group of multiple indoor units and 1 Lossnay unit in interlocked operation. Group 8 : Group of multiple Lossnay units connected to an indoor unit transmission cable and 1 Lossnay M-NET
remote controller.
Group 9 : Group with no Lossnay units.
Lossnay
(01)
Lossnay
(02)
Lossnay
(03)
Centralised controller (000)
Power supply unit
Group1
M-NET transmission cable
Lossnay remote controller
PZ-41SLB-E
Use PZ-52SF-E to connect M-NET transmission cable
(101)
( ) address
20
Operation
Observation
Contents
ON/OFF Change fan to High/Low Change ventilation mode Local prohibit ON/OFF Operation condition Fan speed Ventilation mode (conditions) Errors Filter maintenance sign Local prohibit ON/OFF state
Individual Lossnay (Lossnay not set for interlocked operation)
« « « « « « « « « «
Interlocked Lossnay (Lossnay set for interlocked opera­tion with City Multi)
× × × × × × ×
«
× ×
4.6.4
When Using the LONWORKS®Compatible Adaptor (LMAP02-E) to Connect to LONWORKS
®
By using the LON®adaptor (model name: LMAP02-E), it is possible to control and observe Lossnays on a building management system using the LONWORKS
®
.
* For specifications and functions of the LON
®
adaptor, refer to the materials regarding the LONWORKS®compatible adaptor.
Table of Functions
System Example
(Using M-NET)
Lossnay Lossnay
Building management system
LMAP02-E
Lossnay M-NET remote controller PZ-52SF-E
Lossnay M-NET remote controller PZ-52SF-E
M-NET
LONWORKS
®
M-NET
Lossnay Lossnay
LMAP02-E
Lossnay M-NET remote controller PZ-52SF-E
Lossnay M-NET remote controller PZ-52SF-E
Connect the M-NET transmission cable to TB5 A,B of the Lossnay terminal block. (Refer to page 58). The Lossnay remote controller (PZ-41SLB-E) can not be used with this system. Up to 50 units can be connected with 1 LMAP02-E (The LGH-150, 200RX
3
-E type should be counted as two). For details about the system or connection cables of the LMAP02-E, refer to the technical materials, etc., regarding the LMAP02-E.
* LONWORKS
®
is a registered international trademark, registered in the U.S.A to the Echelon Corporation.
21
5.
Examples of Applications Using Exter­nal Control Input Terminals, Operation Monitor Output Terminals and Malfunc­tion Monitor Output Terminals
Various applications are possible by using the input/output termi­nals as shown below.
Input/Output Specifications
1
2
3
Terminal
External control input ter­minal block
(
TM2 123
)
Operation monitor output terminal block
(
TM3 90
)
Malfunction monitor out­put terminal block
(
TM3 78
)
Specification
This is the input terminal block for start/stop the Lossnay unit using external equipment, such as a Mr. Slim (A-control or K-control)indoor unit or the BMS (Building Management System). Signal input can be by voltage (12V-24V DC)or uncharged a-contact signal.
(
Both voltage and no-votage signals are compatible with pulse input. Set DIP
switch 2-2 to ON. A pulse signal duration of 200 ms or more is needed.
)
Output terminal during Lossnay unit operation. (uncharged a-contact signal output
.)
Contact point rating: 2A/240V AC
Within 2A/24V DC
Output terminal during Lossnay unit malfunction. (uncharged a-contact sig­nal output.
)
Contact point rating: 1A/240V AC
Within 1A/24V DC
Page
22/24·25·26
25/27
26 to 27
Lossnay Main/Sub Setting
For a multiple Lossnay system that will begin operation from one signal from an air conditioner or the like, make sure the unit connected to the signal cable from the air conditioner is set to Main,” and all the others are set to “Sub.
Lossnay
Power supply
Power supply
Remote
controller
PZ-41SLB-E
Air conditioner
up to 15 Lossnay units
Set to "Main"
Set to "Sub"
Air conditioner remote controller
Lossnay
Lossnay
22
5.1 External Control Operating Mode Selection
There are four modes when operating using signals from external equipment.
1. ON/OFF interlock (the last trigger from either external signal or remote control switch has priority
)
2. ON interlock
3. OFF interlock
4. External priority ON/OFF interlock
Operating Signal
Mode
ON/OFF
inter-
lock
ON
inter-
lock
OFF
inter-
lock
External
priority
ON/OFF
inter-
lock
This mode does not exist.
When external signal is level signal.
When external signal is pulse signal.
(
Optional setting
)
External signal
Remote controller [ON/OFF] button pressed
Operating condition
Operating Stopped
External signal
Remote controller [ON/OFF] button pressed
Operating condition
Operating Stopped
External signal
Remote controller [ON/OFF] button pressed
Operating condition
External signal
Remote controller [ON/OFF] button pressed
Operating condition
External signal
Remote controller [ON/OFF] button pressed
Operating condition
Operating Stopped
Operating Stopped
External signal
Remote controller [ON/OFF] button pressed
Operating condition
Operating Stopped
Operating Stopped
External signal
Remote controller [ON/OFF] button pressed
Operating condition
Operating Stopped
Setting Method
When PZ-41SLB-E is used . . . . . . Set with the remote controller. (Refer to page 67)
When PZ-41SLB-E is Not used . . . Set with the dip switch. (Refer to page 61)
23
5.2 Delayed Interlocked Operation (PZ-41SLB-E, M-NET)
(1) It is possible to delay operation of the Lossnay with respect to the operation of the external device. (Energy saving effect.) (2) The times that can be set for delayed operation are 10, 20, 30, 40, 50, and 60 minutes. (3) Delayed operation does not occur if the Lossnay operation was cancelled within the last 2 hours.
(If turned off for a short time, for example during a lunch break, if the direction to restart operation is given within 2 hours, the Lossnay will restart immediately.)
(4) If an operation button is pressed on the remote controller while the delay timer is operating, the delayed operation is can-
celled and normal operation begins.
Setting Method
When PZ-41SLB-E is used . . . . . . Set with the remote controller. (Refer to page 67)
When PZ-41SLB-E is Not used . . . Set with the dip switch but fixed only for 30 minutes. (Refer to page 60)
5.3 Multiple External device Operation (PZ-41SLB-E, M-NET)
System Example
When the Operation Signal is a Uncharged a-contact Level Signal
When there are multiple air conditioners or other external devices
Characteristics Ordered parts Notes
Lossnay operates when any of the external devices operate.
Remote controller External signals that can be
received are listed below.
Level signal, uncharged a-contact
If the external device is a pulse sig­nal or charged signal multiple con­nections can not be made.
Uncharged a-contact Uncharged a-contact
Lossnay
Power supply Power supply Power supply Power supply
Uncharged a-contact
Remote controller PZ-41SLB-E
* Illustration shows an example when using PZ-41SLB-E.
Air conditioner remote controller
Air condi­tioner 1
Air condi­tioner 2
Air condi­tioner 4
Air conditioner remote controller
Air conditioner remote controller
(Signal cable for space between Lossnay and remote controller is less than 500 m.) PVC cable φ 0.65 to 1.2 or strand wire 0.3 mm
2
to 1.25 mm2.
24
5.4 Multiple Lossnay Units in Interlocked Opera­tion with One Indoor Unit. (M-NET only)
[
Example: System 1
]
Set the Main/Sub switch of the Lossnay connected to the M-NET transmission cable to Main, set the second and following Lossnay units to “Sub,” and connect 5 and 6 of the Lossnay remote controller’s (PZ-41SLB-E) transmission cable terminal
(TM2) to the corresponding point on the next unit.
(
One Point Advice
)
Register the first Lossnay unit and the indoor unit to be interlocked. It is not necessary to set the address or direct control for the second or following Lossnay units. Malfunctions of the Lossnay units after the second unit will not appear on the remote controller.
[
Example: System 2
]
Use the Lossnay remote controller to set the air conditioners and Lossnay units to separate groups. Both interlocked operation of an air conditioner and Lossnay units can be performed independently by connecting the remote display output for the indoor unit and the external control input for the Lossnay unit.
(
One Point Advice
)
Do not register the indoor unit and Lossnay unit to be interlocked. In addition, ventilation switch on the MA remote controller will be invalid, and the Lossnays error indicator will appear only on the Lossnay remote controller.
5.5
Interlocked Operation of Equipment such as the Electrically Operated Damper and Booster Fan. (M-NET only)
[
Example: System 3
]
Indoor unit
M-NET transmission cable
MA remote controller
Lossnay
(Main)
Lossnay
(Sub)
Lossnay
(Sub)
TM2 TM2 TM2
Lossnay remote controller (PZ-52SF-E)
Indoor unit
M-NET transmission cable
Remote display output
External control input
MA remote controller
Lossnay Lossnay Lossnay
Lossnay
M-NET transmission cable
Indoor unit
MA remote controller
Operation moniter output
Electrically operated damper Booster fan
25
5.7 Connection Method (PZ-41SLB-E, M-NET)
5.6
To Pick Up an Error Signal Externally (PZ-41SLB-E, M-NET)
[
Example System
]
1. Using a Mr. Slim (A­control or K-con­trol) indoor unit
Lossnay
M-NET transmission cable
Indoor unit
MA remote controller
Lamp on monitoring unit
Operation moniter output
TM2
Example:
Mitsubishi Mr.Slim indoor unit CN2L
Example:
Slim-Lossnay connection cable (Lossnays enclosed accessory
)
Lossnay External control input
If other models are used, refer to the operating manual for those models.
500 m
0.5mm2 to 1mm2 sheathed PVC cable
No more than
1
2
3
Lossnay External control input
Overall extension length of connection (
Follow the guidance provided in the operators manual.
)
[
When voltage pulse signal (12V DC or 24V DC) is used
]
Connect the signal output to between TM2 1 and 2. (
Non-polar
)
External device
1
2
3
TM2
0.5mm2 to 1mm2 sheathed PVC cable
TM2
Lossnay External control input
External device
0.5mm2 to 1mm2 sheathed PVC cable
No more than
500 m
1
2
3
If an optocoupler or any other type of polar coupler is used at the uncharged a-contact, connect the + to 3 and the - to 1.
2. Using a 12V DC or 24V DC voltage sig­nal
3. Uncharged a-con­tact
External device
Power
External device operation switch
External device
Power
External device operation switch
External device
Power
External device operation switch
External device
Power
External device operation switch
1 2 3
Components for taking remote output
500 m or less
External control input (TM2)
Lossnay
4.
Many uncharged a­contacts.
Connect 1 and 3 of the exter­nal control input terminal (TM2) through the component for tak­ing remote output at the uncharged a-contact.
Note:
If an optocoupler or any other type of polar contact is used at the uncharged a-contact, connect the + to 3 and the
- to 1.
26
Maximum 200 milliseconds
5. Connecting to equipment such as an electrically operated damper and picking up the operating signals.
Connect the power supply cable from the electrically operat­ed damper to 9 and 0 of the operation monitor output ter-
minal (TM3).
Note
:
The response time to an external control input signal is shown in the table below.
6. Picking up an error signal.
Lossnay
Operation monitor output (
TM3
)
Max. 240V AC 2A
24V DC 2A
Min. 220V AC 100mA
5V DC 100mA
Power supply
Lamp
Electrically operated damper
9
10
Connect to 7 and 8 of Malfunction monitor output terminal (
TM3
)
Lossnay
Malfunction monitor output (
TM3
)
Power supply
Lamp or control equipment
7
8
Max. 240V AC 1A
24V DC 1A
Min. 220V AC 100mA
5V DC 100mA
External Signal Type Response Type
Level signal Maximum 7 seconds
Pulse signal
5.8 High/Low Change Input (PZ-41SLB-E, M-NET)
The fan speed of the Lossnay can be changed externally by using a commercially available CO
2 sensor, etc. The separately
sold remote ON/OFF adaptor (PAC-SE55RA-E) is necessary for connection.
Connection Method
CO2 sensor, etc.
(when CO
2
increases: close)
Remote
ON/OFF adaptor
(PAC-SE55RA-E)
(sold separately)
Lossnay control
board
Switch1
Orange 1
Red 2
Brown 3
High/Low
change
CN16
Securely break off so as not to use
Wiring length maximum 10 m
Switch 1: High operation switch (when closed: High operation)
CO2 sensor, etc.
(when CO
2
increases: close)
Remote
ON/OFF adaptor
(PAC-SE55RA-E)
(sold separately)
Lossnay control
board
Switch1
Orange 1
Red 2
Brown 3
High/Low
change
CN16
Securely break off so as not to use
Wiring length maximum 10 m
Switch 1: Low operation switch (when closed: Low operation)
When switch 1 is ON, the Lossnay operates at the "High" fan speed regardless of the remote controller setting. If you usually ventilate at "Low" fan speed operation, switch to "High" fan speed operation when the external sensor shows the air quality going down.
When switch 1 is ON, the Lossnay operates at the "Low" fan speed regardless of the remote controller setting. If you usually ventilate at "High" fan speed operation, switch to "Low" fan speed operation when the external sensor shows few impurities in the air.
Externally Directed High fan speed Operation
Externally Directed Low fan speed Operation
27
2 When using M-NET for a group of multiple units
For multiple groups, connect the sensor to each Lossnay.
Even if the units are in the same group, you can only change Lossnay units connected to the sensor between High/Low
operation.
5.9 Remote/Local control Change and ON/OFF Input (M-NET only)
The separately sold remote ON/OFF adaptor (PAC-SE55RA-E) is necessary for connection. Remote/Local changing is impossi­ble when using PZ-41SLB-E.
Insert the separately sold remote ON/OFF adaptor (PAC-SE55RA-E) into CN32 on the Lossnay control table
Note:
External control input and Remote/Local changing can not be used at the same time.
Lossnay Lossnay Lossnay
PZ-52SF-E
CO2 sensor CO2 sensor CO2 sensor
Group
Remote ON/OFF adaptor (PAC-SE55RA-E)
Lossnay control table
Orange 1
Red 2
Brown 3
CN32
Wiring length maximum 10 m
Switch1
Switch2
X
Y
X
Y
Remote control circuit Relay circuit
Relay power
Switch 1 : When on, can not use the local remote controller
(PZ-52SF-E) to turn ON/OFF. * When using PZ-41SLB-E, Remote/Local changing
is impossible.
Switch 2 : When Switch 1 is ON, you can turn Switch 2 ON to
operate the Lossnay, or turn Switch 2 to OFF to turn off the Lossnay.
Switch 1 : Remote/Local change switch Switch 2 : ON/OFF switch
X, Y : Relay (Contact rating DC 1 mA)
1 When using PZ-41SLB-E to connect multiple units
Connect the sensor to the Lossnay with the Main setting.
It is not necessary to connect to any Lossnay with the Sub setting.
Connect any sensor, etc., connected to external change input to the Lossnay with the Main setting.
Any Lossnay with the Sub setting will operate at the same High/Low setting as the Lossnay with the Main setting when
there is sensor signal input.
Lossna
(Main)
Lossnay
(Sub)
Lossnay
(Sub)
PZ-41SLB-E
Main Sub Sub
CO2 sensor
Note:
When using the M-NET system, the fan speed being input by this sensor signal will not be displayed on the remote controller.
28
6. Precautions When Designing Sys­tems of M-NET
6.1
Power Supply of the M-NET Transmission Cable
On an M-NET system, the remote controller or central controller operate on power received from the transmission cable. Accord­ingly, there is need to provide power to the transmission cable. There are two systems for supplying power. The central system is supplied by a power supply unit. The indoor unit system is supplied by a outdoor unit. The Lossnay and the Lossnay remote controller can be connected to either system.
6.2 Restrictions When the Lossnay Units are Con-
nected to the Central Controller M-NET Trans­mission Cable.
Due to the limited capacity of the power supply unit, the number of Lossnay remote controllers is restricted when the Lossnay M­NET remote controllers and Lossnay units are connected to the central controller transmission cable. This does not apply to Lossnay units that do not receive power from the central controller transmission cable.
The central system The indoor unit system
Central controller
transmission cable
Indoor unit transmission cable
Power supply unit
Outdoor unit
Indoor unit
Lossnay
Lossnay
TB7 TB3
MA remote controller
Lossnay remote controller (PZ-52SF-E)
Centralised controller
Transmission cable
Power supply unit
(PAC-SC34KUA)
Lossnay M-NET remote controller
(PZ-52SF-E)
Lossnay M-NET remote controller
(PZ-52SF-E)
Lossnay Lossnay Lossnay Lossnay
Centralised controller
Number of centralised controllers
Non 1 unit 2 units 3 units 4 units
Number of Lossnay M-NET remote controllers that can be connected.
Max. 30 units
Power supply unit PAC-SC34KUA
Max. 26 units Max. 22 units Max. 18 units Max. 14 units
Max. 50 units
Transmission Booster PAC-SF46EPA
Max. 46 units Max. 42 units Max. 38 units Max. 34 units
In the case that a greater number of Lossnay remote controllers than that shown above is connected due to the use of a
power supply unit (PAC-SC34KUA), a transmission booster (PAC-SF46EPA) becomes necessary.
Transmission Booster (PAC-SF46EPA) can be used without a power supply unit (PAC-SC34KUA) if TB2 (OUTDOOR UNIT
SIDE) is opened, and the M-NET transmission cable is connected to TB3 (ADDITIONAL INDOOR UNIT SIDE).
29
6.3 Wiring Example
Example
<Centalised controller and Lossnay units>
Note:
This unit cannot be used to extend the transmission cable.
Power
supply unit
Lossnay remote controller
Lossnay unit
Centralised controller
Lossnay remote controller
Lossnay unit
Lossnay remote controller
Lossnay unit
Lossnay remote controller
Lossnay unit
Lossnay remote controller
Lossnay unit
Lossnay remote controller
Lossnay unit
Transmission booster
Lossnay remote controller
ADDITIONAL INDOOR UNIT SIDE
OUTDOOR
UNIT SIDE
Lossnay unit
Lossnay remote controller
Lossnay unit
Lossnay remote controller
Lossnay unit
S
TB2
Ground
Ground
TB3
S
30
6.4 Power Supply to the Indoor Unit Transmission
Cable.
In principle, the number of indoor units ME remote controllers and Lossnay M-NET remote controllers that can be connected to one outdoor unit will depend on the type of outdoor unit. The following are the general guidelines when connecting multiple indoor units and Lossnay units to an outdoor unit.
Indoor units + Remote controllers (Simple remote controllers)+ Lossnay M-NET remote controllers 35 * MA remote controllers and Lossnay unit’s are Not counted.
Centralised controller
Transmission cable
Power supply unit
Lossnay M-NET remote controller (PZ-52SF-E)
ME remote controller
ME remote controller
Indoor unit Indoor unit Indoor unit
Outdoor unit
The sum of indoor units and remote controllers should be 35 or less.
Lossnay
31
7. Cable Installation of the M-NET
7.1 Precautions When Installing Wiring.
1. When routing transmission cable outside of the unit, position it 5 cm or more away cable for the power supply so that it will not pick up electrical noise. (Never use multi­core cable or place the transmission cable in the same conduit as the power supply cable.
)
2. Never connect the power cable to the terminal block for the transmission cable. This erroneous connection will burn out the circuit board.
3. Always use 2-core cable for the transmission cable. Routing this transmission cable with the transmission cable from another system on the same multi-core cable will result in erroneous sending and receiving of signals which will cause misoperation.
Outdoor unit
Indoor unit
2-core cable
2-core cable
Multi-core cable
Indoor unit
Lossnay
Indoor unit Indoor unit
Lossnay
Indoor unit Indoor unit
Lossnay
Indoor unit Indoor unit
Lossnay
Outdoor unit
Outdoor unit
Outdoor unit
Lossnay M-NET
remote controller
(PZ-52SF-E)
Lossnay M-NET
remote controller
(PZ-52SF-E)
Air conditioner
remote controller
Air conditioner
remote controller
Air conditioner
remote controller
Air conditioner
remote controller
Lossnay M-NET
remote controller
(PZ-52SF-E)
Lossnay M-NET
remote controller
(PZ-52SF-E)
32
7.2 Electrical Wiring
Types of control cables
1. Wiring the M-NET transmission cables
• Types of transmission cables Design cable in accordance with the following <Table 1>.
• Cross-sectional area
1.25 mm2to 2.00 mm
2
<
Table 1
>
System configuration
Shielded cable, such as CVVS or CPEVS.
All facilities.
2. Lossnay M-NET remote controller (PZ-52SF-E)
Lossnay M-NET remote controller
Type of cables
Non-shielded cable up to 10 m in length sheathed PVC (2-core)0.75 mm
2
to 1.25 mm2or equiva-
lent. (The same specifications as table 1 for more than 10 m.
)
Length
Add any portion exceeding 10 m up to the longest permissible transmission cable length of 200 m. (
Shielded sections shall have a cross-sectional area of 1.25 mm
2
to 2.00 mm2.
)
Single-refrigerant system Multi-refrigerant system
Transmission cable length
Type of facility
(Electrical noise potential)
Type of facility
(Electrical noise potential)
Private residence or facility with no electri­cal noise.
VCTF, VCTFK, CVV, CVS, VVR, VVF, or sheilded cable such as CVVS or CPEVS
Building free of electri­cal noise caused by inverters, electrical generators and/or high­frequency equipment
(
such as hospitals and
radio stations.
)
Less than 120 m More than 120 m
Regardless of length
33
7.3 Length of Control Cable
Maximum power supply cable length. (L1 + L2, L1 + L3, L1 + L4): The longest length of the cable from the power supply unit or the indoor unit to the farthest terminal shall be less than 200 m.
Maximum distance between ends (L2 + L3, L2 + L4, L3 + L4): The length of cable between ends shall be less than 500 m.
Remote controller cable length (o): The distance between the remote controller and the terminal connected to it shall be 10
m or less.
System Example
When using Lossnay remote controller or ME remote controller.
Lossnay M-NET remote controller (PZ-52SF-E)
Lossnay M-NET remote controller (PZ-525F-E)
Lossnay M-NET remote controller (PZ-525F-E)
Lossnay
Lossnay
Transmission
booster
Power supply unit
Lossnay
Lossnay Lossnay
L2
L1
L3
Ground
Centralised controller
L4
T B 2
T
B
3
Lossnay M-NET remote controller (PZ-52SF-E)
Lossnay M-NET remote controller (PZ-52SF-E)
Outdoor unit
Indoor unitLossnay
Lossnay Lossnay Lossnay
L2L1
L3
Air conditioner remote controller
Ground
Transmission
booster
T B 2
T B 3
Please:
Always install the ground cable for the transmission cables in the following way. Route the central control system through the power supply unit. Route the indoor unit system through the ground terminal on the outdoor unit.
If the cable length (o) for the remote controller exceeds 10 m, use 0.75 mm
2
, change the section exceeding 10 m to the cable
having a cross-sectional area of 1.25 mm
2
to 2.0 mm2. Add the exceeding section within the maximum power supply cable
length restriction of 200 m and the maximum distance between ends restriction of 500 m.
If the cable exceeds the maximum cable length and overall extended length, voltage will drop and cause malfunctioning.
34
8. System Designs of M-NET
8.1 Address Definitions
An address is a unique number used to identify each air conditioner and controller.
Device
Note:
There is no need to set the address unless the Lossnay is connected to the M-NET transmission cable.
System configuration example
Description Address definition range
Indoor unit
Set to specify in order each refrigerant system.
001 to 050
Lossnay Set to specify in order each refrigerant system.
001 to 050 (Note
)
Outdoor unit
Minimum address of the indoor unit within the same refrigerant system. (+50
)
051 to 100
Local remote controller (master
)
Minimum address of an indoor unit or a Lossnay unit within the same group. (+100
)
101 to 150
Local remote controller (
secondary
)
Minimum address of the indoor unit or a Lossnay unit inside the same group. (+150
)
151 to 200
Branch controllers Minimum address of an outdoor unit. (+1
)
052 to 100
Central controller
When the K-control unit is in control. (000
)
0, 201 to 250
K-transmission converter
Minimum address of the K-control type indoor unit. (
+200)This cannot overlap with a system controller.
201 to 250
(
013
)
(
015
)(
016
)
(
010
)
(
014
)
(
005
) (
006
) (
007
)
(
004
)
(
003
)
(
002
)
(
001
)
(
101
)
(
105
)(
106
)(
107
)
(
103
)
(
051
)
(
213
)
Centralised controller (
000
)
Power supply unit for
transmission cable
K-transmission converter
Outdoor unit
Indoor unit Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Lossnay
Lossnay
LossnayLossnay
( )
address
ME remote controller ME remote controller
Lossnay M-NET remote controller
(PZ-52SF-E)
Lossnay M-NET remote controller
(PZ-52SF-E)
Lossnay M-NET remote controller
(PZ-52SF-E)
K-control remote controllerK-control remote controller
K-control remote controllerK-control remote controller
Mr.Slim A-control remote controller
M-NET compatile A-control Mr.Slim outdoor unit
A-control Mr.Slim indoor unit
35
8.3
Precautions When Performing Interlock Settings (
when interlocked with City Multi indoor unit
)
8.2
Precautions When Performing Group Settings (
when not interlocked with City Multi indoor unit
)
Precautions
1
The maximum number of Lossnay units in one group is 16. (Refer to page 15.
)
2
When two remote controllers are used within the same group, set one remote controller as the master (address 101 to 150)and the other as the slave (address 151 to 200). (Refer to page 14.
)
3
Group settings:
1
Perform group settings at the centralised controller MJ-103MTRA when being used. If 2 or more centralised con­ntrollers are being used in combination, perform the group settings at the host one. (Refer to page 76.
)
2 If a centralised controller is not being used, use the Lossnay remote controller to perform the settings. (Refer
to page 72.
)
4
Do not set air conditioners and Lossnay units in the same group. If these units are set to the same group, the indoor unit or Lossnay will not operate.
5
Turn on the power source for the Lossnay when performing group settings.
6
If the group settings are performed by MELANS, be sure to also set the address for the Lossnay remote controllers to the group setting. If the remote controller address is not registered, H0 remains displayed and the system does not start up.
7
No more than three Lossnay remote controllers can be set to the same group in a system using a central con­troller.
Precautions
1
The maximum number of indoor units that can be interlocked is 16. (Refer to page 17.
)
2
1 Lossnay can be interlocked with an indoor unit. (Refer to page 17.
)
3
Interlock settings:
1
When a centralised controller (MJ-103 MTRA)is being used: if 2 or more centralised controllers are being used in combination, perform the group settings at the host one. (Refer to page 76.)
2 When MA or ME remote controllers are being used except above 1: Use the MA or ME remote controller for
the interlock settings. (Inerlock settings cannot be performed with the MJ-180A.
)
(
If 1 or 2 do not apply, interlock settings cannot be made.
)
4
Do not register the Lossnay units in a group to be interlocked. Lossnay units that have been set to interlocked operation within the same group will not operate.
5
When performing the settings using a MA or ME remote controller, always set for interlocked operation to the smallest address indoor unit in a group. If the setting is not made in this manner, the message This function is not available will appear when operating the ventilation button and interlocking with the Lossnay unit will not be possible.
6
Turn on the power source for the Lossnay when performing interlock settings.
36
9. Automatic Ventilation Switching
9.1 Effect of Automatic Ventilation Mode
The automatic damper mode automatically provides the correct ventilation for the conditions in the room. It eliminates the need for troublesome switch operations when setting the Lossnay ventilator to By-pass ventilation. The following shows the effect By-pass ventilation will have under various conditions.
1. Reduces cooling load
If the air outside is cooler than the air inside the building during the cooling season (such as early morning or at night), By­pass ventilation will draw in the cooler outside air and reduce the cooling load on the system.
2. Cooling using outdoor air
During cooler seasons (such as between spring and summer or between summer and fall), if the people in a room cause the temperature of the room to rise, By-pass ventilation draw in the cool outside air and use it as is to cool the room.
3. Night purge
By-pass ventilation can be used to release hot air from inside the building that has accumulated in buildings a business dis­trict during the hot summer season.
4. Office equipment room cooling
During cold season, outdoor air can be drawn in and used as is to cool rooms where the temperature has risen due to the use of office equipment. (Only when interlocked with City Multi and Mr. Slim indoor unit)
9.2 Switching between Heat Recovery and By­pass in the Automatic Ventilation Mode
Control of the automatic ventilation mode is performed according to the table below and automatic algorithm temperature maps. Note that operation is fixed at heat recovery when the fan is stopped or when there is an abnormality with the thermistor.
Conditions
Temperature Map
When in automatic ventilation mode when not interlocked with City Multi or Mr. Slim indoor unit. (Including when interlocked by external control input.
)
According to (a).
When the outside temperature has been 28°C or higher in the last 24 hours. According to (b).
Interlocked with City Multi indoor unit
Fan mode operation for all interlocked indoor units.
Fixed to Lossnay ventilation.
Interlocked with Mr. Slim indoor unit
Mr. Slim in fan mode. Fixed to Lossnay ventilation.
Mr. Slim in heating mode. According to (c).
Mr. Slim in ventilation mode. According to (a
) or (d)
.
Conditions other than the above. According to (d).
Heating mode for one or more inter­locked indoor units.
According to (c).
Conditions other than the above. According to (d).
When indoor units are stopped and only Lossnay unit is operated.
Fixed to Lossnay ventilation.
Note:
There is a maximum delay of 30 seconds during damper switching.
Even if By-pass is selected by the Lossnay remote controller, Lossnay ventilation will be performed if the outdoor tempera-
ture is 8°C or less. This is to prevent condensation.
When multiple City Multi indoor units are connected in a group, the average set temperature for each indoor unit will be the
target temperature. The set temperature is the target temperature for the Mr. Slim indoor unit.
In the case of (b)when the indoor unit is stopped for the winter, cooling with outdoor air is performed because equipment in
the room may cause a rise in indoor temperature.
37
50
45
40
35
30
25
20
15
10
5
0
5
24°C
10°C
10°C
8°C
(°C)
T
OA
(°C)
T
OA
TOA
(°C)
T
RA TRA
(°C)
T
RA
10 15 20 25 30 35 40 45 50
(°C)
50
(°C)
50
50
45
40
35
30
25
20
15
10
5
0
5 10152025 30354045
50
45
40
35
30
25
20
15
10
5
0
51015202524 30 35 40 45
TOA = TRA
TOA = TRA
4°C
4°C
4°C
TOA = TRA
Free Heating
Free cooling
4°C
4°C
6°C
2°C
Lossnay ventilation
By-pass ventilation
Comfortzone (Maintains the condition held prior to entering the range.
)
(a)
When there is no target temperature
(c)
When there is a target temperature (Heating
)
(b)
When there is no target temperature and the outside temperature has been 28°C or higher in the last 24 hours.
Target temperature
4°C
10°C
8°C
(°C)
T
OA
TRA
(°C)
50
50
45
40
35
30
25
20
15
10
5
0
5 10152025 30354045
TOA = TRA
4°C
2°C
(d)
When there is a target temperature (Cooling
)
Or the outside temperature has been 28°C or higher in the last 24 hours when interlocked with Mr.Slim and Mr.Slim in ventilation mode.
Target temperature
8°C
TOA: Outdoor air temperature
T
RA: Indoor air temperature
The indoor air and outdoor air temperature are detected by the two temperature sensors (thermistors) built into the main Lossnay unit.
10. Cold Weather Area Operation Specifications
When the OA temperature falls below -10°C during operation, the SA fan will change to intermittent operation, off for 10 minutes, on for 60 minutes. However, intermittent operation can not take place for 60 minutes after starting operation.
38
11. Troubleshooting
11.1 Service Flow
Confirmation items 1 Condition of trouble – remote controller dis-
play, etc.
2 Frequency of trouble – date of start of opera-
tion and occurrence
3 Occurrence timing 4 Existence of drawings, equipment (including
controllers and equipment sold separately), cables, wiring, and settings.
Applicable models Lossnay LGH-15 to 200RX
3
-E
Remote controller PZ-41SLB-E PZ-52SF-E
Trouble Mode 1 The system will not start properly.
Check the initialization checklist from installation to operation (table 1-1).
Check the system checklist (table 1-2).
Trouble Mode 2
The check code display appears on the remote controller.
The LED of the Lossnay circuit board is blinking.
Check with the check code list (table 2).
Trouble Mode 3
The remote controller does not operate or operates irregularly.
The Lossnay does not operate or operates irregularly.
Trouble Mode 4
Check with the remote controller checklist (table 3).
Check with the Lossnay checklist (table 4).
Precautions when diagnosing malfunctions
When removing a transistor or printed circuit board, make sure the breaker is thrown.
When removing the circuit board, always hold it at both ends and remove carefully so as not to apply force to the surface
mounted parts.
When removing the circuit board, be careful of the metal edges on the board.
When removing or inserting the connectors for the circuit board, hold the entire housing section. Never pull on the lead wires.
When servicing, be sure to recreate the malfunction 2 to 3 times before starting repairs.
If a malfunction of the printed circuit board is suspected, check for disconnected wires in the print pattern, burnt parts or dis-
coloration.
If the printed circuit board is replaced, make sure that the switch settings on the new board are the same as the old board.
39
Unit error
Error item
11.1.1 Error List
«
« « «
« «
«
« « «
«
«
«
«
«
«
« « « «
« « «
« « «
« « ««
« « «
« « «
«
« « «
2 times
3 times
4 times
5 times
9 times
6 times
8 times
1 - 5
times
LED 6
turn off
4000/4116
*1)
3602
5101
5102
0900
6600
6607
6608
6607/6608
6602/6603/
6604
6608
Cancellation
Cancel damper operation
Other controls as normal
Lossnay ventilation fixed (for “Auto modes)
Other controls as normal
Lossnay ventilation fixed (for “Auto modes)
Other controls as normal
Fan: High speed
Lossnay ventilation fixed
Cancellation
Cancellation
Fan motor operation device error
Damper motor error
OA temperature sensor error
RA temperature sensor error
Test operation
Dual address
No ACK
No response
Controller communication error
Communication circuit error
Polarity not set
PZ-41SLB-E communica­tion error
Classification
Communication error
Measures taken by Loss-
nay
Remote
controller
display
error code
LED 1 (green) Display
(No. of blinks)
LED 2
(red)
Display
(No. of blinks)
Error
monitor
output
Reset power
supply
Change
address
Stop
Start
Error
delete
Cancellation measures
*1) 4000 is displayed on PZ-41SLB-E only.
40
Do the capacity of the main power supply on/off unit and wiring span meet specification?
Checkpoint
11.2 Items to Check
Trouble Mode 1: The system will not start properly.
Initialization checklist from installation to operation (Table 1-1)
After checking the system, check the points below up to operation.
1
No.
2 Is the specified power supplied to the Lossnay power terminal (TM1)? (refer to page 54)
3 Is the wiring length of the transmission cable within specifications?
When using PZ-41SLB-E: Overall extension within 500 m
When using M-NET: Maximum power supply length within 200 m, maximum distance between ends
within 500 m (refer to page 33)
4 Does the transmission cable meet regulations? (Type, diameter) (refer to page 56)
5 Is the transmission cable wired at least 5 cm away from the power supply cable?
6 Are multiple transmission or signal cables wired to the same power cable duct?
7 Are multiple transmission cables wired with multi core cables?
8 Is the transmission cable connected to the terminal unit?
(PZ-41SLB-E to TM2 5, 6; M-NET to TB5 A, B)
9 Is the transmission cable securely connected to the Lossnay terminal unit? (refer to page 56, 58)
10 When not using M-NET
If using 1 Lossnay unit, is the Main/Sub change switch (SW1) on the Lossnay circuit board set to Main”?
If using 2 or more Lossnay units, is the Main/Sub switch set to “Main” on only one unit, and the other units are set to Sub? (refer to page 57)
11 When using M-NET
Is the address switch on the Lossnay circuit board (SA1, SA2) set to the correct number? (refer to page 59)
12 When using external control input
Do the specifications of the external signal match specifications of signals that can be input to the Lossnay? (refer to page 56)
13 When the external input signal is a pulse signal
Is the pulse input switch (SW2-2) on the Lossnay circuit board set to ON? (refer to page 57)
14 When the external signal is 12V DC, 24V DC, or Mr. Slim (A-control or K-control) signal
Is it connected to 1, 2 on the Lossnay external control input terminal unit (TM2)?
15 When the external signal is an uncharged a-contact signal
Is it connected to 1, 3 on the Lossnay external control input terminal unit (TM2)?
16 When M-NET is not being used
Is the external input signal connected to the Lossnay set to Main”?
17 Is the signal cable length within wiring specifications?
12V DC, 24V DC signal: Within limitation of the external device
Uncharged a-contact signal: Within 500 m
Mr. Slim (A-control or K-control) signal: Within 500 m
18 Is the signal cable wired at least 5 cm away from the power supply cable?
19 Is the output capacity of the Lossnay operation monitor/error monitor within specifications?
Operation monitor output: Maximum 240V AC/24V DC 2A, minimum 220V AC/5V DC 100 mA
Error monitor output: Maximum 240V AC/24V DC 1A, minimum 220V AC/5V DC 100 mA
20 Are the power supply cable, transmission cable, signal cable, etc., securely connected to the proper terminals?
21 Are the settings for the Mai/Sub switch, address switch, and function select switch correct?
41
« Check the power supply to the
Lossnay.
« Set the Main/Sub (SW1) switch
to Main.” (refer to page 57)
« Check the length of the trans-
mission cable wiring.
« Connect the transmission cable
to TM2 56. (refer to page 56)
« Change to the PZ-41SLB-E
remote controller.
1
No.
Remote controller display does not appear.
« Power is not supplied to the Lossnay, or power
outside specifications is connected.
« When using only 1 Lossnay, the Main/Sub switch
(SW1) on the Lossnay circuit board is set to Sub.
« The overall wiring length of the transmission cable
is longer than specifications (longer than 500 m).
« The remote controller is connected to TB5 (M-NET
transmission cable).
« PZ-52SF-E is connected to the Lossnay local
remote controller.
2 Remote controller
does not operate (Communication error display)
« When using multiple Lossnay units, the Main/Sub
switch (SW1) on the Lossnay circuit board of the second or following unit is set to Main.
« The overall wiring length of the transmission cable
is longer than specifications (longer than 500 m).
« Multiple transmission cables are wired with multi
core cables.
«
Set the Main/Sub switch (SW1) of the second and following Lossnay units to Sub.
(refer to page 57)
« Check the length of the trans-
mission cable wiring.
« For the applied transmission
cable, wire the transmission cables away from the other transmission cable.
3 Interlocked operation
with external device does not occur.
« The type of external signal does not match the
connected terminal unit (charged, uncharged, Mr. Slim signal).
« The type of external signal does not match the
pulse input switch (SW2-2) setting (level signal, pulse signal).
« The external device signal is not being input. « The external device and signal cable wiring is
longer than specifications
12V DC, 24V DC: Longer than limitations of
external device Uncharged a-contact: Longer than 500 m Mr. Slim signal: Longer than 500 m
« The Delayed Start mode is set at the remote con-
troller (PZ-41SLB-E).
« The ON Interlocked Operation mode or OFF Inter-
locked Operation mode is set at the remote con­troller (PZ-41SLB-E).
« When using multiple Lossnay units, the external
control input signal is connected to a unit with the Sub setting made.
«
Check the connection to the exter­nal control input terminal (TM2) for the type of external signal.
(refer
to page 56, 57)
«
Check the type of external signal and the setting of the pulse input switch (SW2-2). (refer to page 57)
« Check the external device. « Check the length of the signal
cable wiring.
« Check the Delayed Start mode
setting at the remote controller (PZ-41SLB-E). (refer to page 64)
« Check the Interlocked Operation
mode setting at the remote con­troller (PZ-41SLB-E). (refer to page 64)
« Connect the external control
input signal to the Lossnay unit set to Main.
Symptom Cause Corrective action
System checklist
(1) Use this checklist when using a PZ-41SLB-E or an external device (Table 1-2-1)
42
«
Check remote control unit number limitations when using a power supply unit (refer to page 28).
« Check the length of the trans-
mission cable wiring.
« Check the Lossnay address, and
set for an address correspond­ing to interlocked operation. (refer to “15. Appendix”)
« Check the length of the trans-
mission cable wiring.
«
Change to the PZ-52SF-E remote controller (PZ-41SLB-E can not be used with the M-NET).
(2) System checklist when using the M-NET (Table 1-2-2)
1
No.
Does not interlock with City Multi. (The Lossnay cannot be operated by the ventilation switch on the ME remote controller, MA remote controller, or MELANS.)
« The Lossnay is not set for interlocked opera-
tion, or is set for interlocked operation at the wrong address.
« The length of the M-NET transmission cable
wiring from the outdoor unit or the system’s overall wiring length is longer than specifica­tions. (Longer than 200 m from the outdoor unit, longer than 500 m between ends.)
« PZ-41LSB-E is connected to the Lossnay local
remote controller.
2 Cannot operate using the
MELANS or Lossnay remote controller.
« The address that has been set for the group in
MELANS and the address for the Lossnay are different.
« The length of the M-NET transmission cable
wiring from the power supply unit or the sys­tems overall wiring length is longer than speci­fications. (Longer than 200 m from the power supply unit, longer than 500 m between ends.)
« PZ-41LSB-E is connected to the Lossnay local
remote controller.
«
Check the registered address in MELANS. (refer to “15. Appendix”)
« Check the length of the trans-
mission cable wiring.
«
Change to the PZ-52SF-E remote controller (PZ-41SLB-E can not be used with a M-NET system).
3 A unit should operate
independently by MELANS or the Lossnay remote controller, but it interlocks with another City Multi unit.
« It has been set for interlocked operation with
the City Multi unit.
« Cancel the interlocked operation
setting. (refer to “15. Appendix”)
4 Cannot perform group
settings for the Lossnay using MELANS, ME remote controller, or MA remote controller. (The remote controller shows 88 at the time of regis­tration.)
« Power is not supplied to the Lossnay, or power
outside specifications is connected.
« The M-NET transmission cable is connected to
TM2 56.
« The transmission cable is not properly con-
nected to the MELANS or the City Multi.
«
The length of the transmission cable wiring is longer than specifications (longer than maximum 200 m from the power supply unit, longer than 500 m between ends.)
«
Check the power for the Lossnay and perform the registration again. (refer to 15. Appendix”)
« Connect the transmission cable
to TB5 A, B. (refer to page 58)
« Check the transmission cable
connection. (refer to page 58)
« Check the length of the trans-
mission cable wiring.
5 When power is supplied
to the system, the Loss­nay remote controller continues to display HO and does not start. (Group registration infor­mation disappears.)
« The Group setting was made on a Lossnay
remote controller in a system connected to a centralised controller MELANS.
« The length of the transmission cable wiring is
longer than specifications (longer than maxi­mum 200 m from the power supply unit, longer than 500 m between ends.)
«
In a system connected to MELANS, make the group setting with the MELANS (Do not make the group set­ting with the Lossnay remote controller). (refer to 15. Appendix or page 72)
« Check the length of the trans-
mission cable wiring.
6 When power is supplied
to the system, the remote control display goes blank and the sys­tem does not start.
« Over the number of units that can be controlled
with the Lossnay remote controller.
« The length of the transmission cable wiring is
longer than specifications (longer than maxi­mum 200 m from the power supply unit, longer than 500 m between ends.)
Symptom Cause Corrective action
43
« Check the power to the Lossnay. « Check the Lossnay remote con-
troller address registration with the MELANS (HO displays for 3 – 10 minute when electricity is supplied to the system). (refer to 15. Appendix)
« Connect the transmission cable
to TB5 A, B. (refer to page 58)
« Check the Lossnay registration
with the Lossnay remote con­troller. (refer to 15. Appendix”)
7
No.
The power display “” does not display when power is supplied to the system.
1 When using City Multi and Lossnay interlocked
system (connected to the indoor unit system)
« The transmission cable is not correctly con-
nected to the Lossnay remote controller.
« The power is not turned on for the outdoor unit. « The length of wiring for the outdoor units M-
NET transmission cable is longer than specifi­cation (longer than 200 m).
« Check the transmission cable
connection. (refer to page 70)
«
Check the power to the outdoor unit.
« Check the length of the trans-
mission cable wiring.
8 The HO on the remote
controller continues to flash when the power is supplied to the system.
« Lossnay is Not supplied with specified power. « The address for the Lossnay remote controller
does not have a group setting at the MELANS.
« The M-NET transmission cable is connected to
TM2 56.
«
For a Lossnay individual system with no MELANS,
Lossnay registration has not been
performed by the Lossnay remote controller.
9 LC 6608 displays on
the remote controller and the Lossnay does not operate.
« The remote controller is PZ-41LSB-E and con-
nected to the TB5 A, B.
« Change to the PZ-52SF-E
remote controller (PZ-41SLB-E can not be used with a M-NET system).
10 The operation specified
by the centralised con­troller differs from the operation of the Lossnay.
« The remote controller is PZ-41SLB-E and con-
nected to the TM2 5-6.
« Change to the PZ-52SF-E
remote controller (PZ-41SLB-E can not be used with a M-NET system).
2 When using a Lossnay individual system or
City Multi and Lossnay interlocked system con­nected to the central system.
« The power supply unit is not connected to the
transmission cable.
« The power to the power supply unit is not
turned on.
« The length of wiring of the M-NET transmission
cable from the power supply unit is longer than specification (longer than 200 m).
« Connect to the power supply
unit. (refer to page 59)
« Check the power to the power
supply unit.
« Check the length of the trans-
mission cable wiring.
Symptom Cause Corrective action
Trouble Mode 2
An error code displays on the remote controller.
Lossnay circuit board LED is flashing or lit up.
An error code displayed on the remote controller (PZ-41SLB-E, PZ-52SF-E) or the M-NET controller and blinking or illumination of LED1 (green) or LED2 (red) on the circuit board shows the type of error. The LED blink interval is 0.25 seconds for both on and off. The display duration is approximately 5 seconds.
Error display example: Fan motor operation device error
0.25S 0.25S 0.25S
5S
OFF
ON
44
(1) Checklist of error codes displayed on the PZ-41SLB and LED displays
LC 6608
Error code
LED1
(green)
LED 2
(red)
Lossnay communi­cation error
«
When using multiple Lossnay units, the main/sub setting has not been made for the second unit and following units.
« Multiple transmission cables have
been wired using multi core wires.
« Transmission cable and power cable
are too close.
« Transmission cable is not securely
connected.
« The length of wiring of the transmis-
sion cable is longer than specifica­tion (longer than 500 m).
«
Turn off the main power supply and set the Main/Sub switch (SW1) (first unit to main, sec­ond and following units to sub). (refer to page 57)
« Wire the transmission cable away
from the other transmission cable.
«
Wire the transmission cable at least 5 cm away from the power supply cable.
« Check the transmission cable con-
nection. (refer to page 56)
« Check the length of the transmission
cable wiring.
RC6608
SRC 6608
Communi­cation error between remote con­trollers (when 2 remote con­trollers are connected)
« Multiple transmission cables have
been wired using multi core wires.
« Transmission cable and power sup-
ply cable are too close.
« Transmission cable is not securely
connected.
« The length of wiring of the transmis-
sion cable is longer than specifica­tion (longer than 500 m).
« Wire the transmission cable away
from the other transmission cable.
«
Wire the transmission cable at least 5 cm away from the power supply cable.
« Check the transmission cable con-
nection. (refer to page 67)
« Check the length of the transmission
cable wiring.
LC 0900
SLC 0900
Lossnay
trial opera­tion
« Trial operation switch on the Loss-
nay circuit board (SW 2-1 or SW 2-
3) is set to ON board.
« Check the test operation switch.
(refer to page 62)
LC 4000
SLC 4000
2
blinks
Fan motor operation device error
« Lossnay fan will not stop. « Replace the table.
LC 3602
SLC 3602
3
blinks
Damper
related error
« Damper board operation is not cor-
rect.
« Connectors for the damper unit are
not correctly connected.
« Remove the load and check or
move the damper board by hand.
«
Check the connection of the lead wire’s connectors and the circuit connector.
LC 5101
SLC 5101
4
blinks
OA thermis­tor related error
« Connectors for the thermistor are
not correctly connected.
« Check the connection of the lead
wires connectors and the circuit connector.
LC 5102
SLC 5102
5
blinks
RA thermis­tor related error
« Connectors for the thermistor are
not correctly connected.
« Check the connection of the lead
wires connectors and the circuit connector.
——— 9
blinks
Remote
controller communi­cation error
« Multiple transmission cables have
been wired using multi core wires.
« Transmission cable and power sup-
ply cable are too close.
« Transmission cable is not securely
connected.
« The length of wiring of the transmis-
sion cable is longer than specifica­tion (longer than 500 m).
« Wire the transmission cable away
from the other transmission cable.
«
Wire the transmission cable at least 5 cm away from the power supply cable.
« Check the transmission cable con-
nection. (refer to page 56, 57)
« Check the length of the transmission
cable wiring.
Filter blink-
ing
Warning to clean air filter by comulative operation time
« Interval for cleaning Lossnay air fil-
ter has elapsed.
« After cleaning the air filter press the
Filter button on the remote con­troller 2 times.
HO blinking blink-
ing
System is
starting
«
LED1 blinks at 1 second intervals during starting operation (maximum of 45 seconds.)
« There is no error.
Symptom Cause Corrective action
*1 LC: Lossnay set to Main SLC: Lossnay set to Sub RC, SRC: remote controller (PZ-41SLB-E) *2 Because the LGH-150/200RX
3-E is loaded with 2 control circuit units, SLC may display even with only 1 Lossnay.
When SLC displays, check and perform maintenance on the upper side circuit.
45
(2) Checklist of error codes displayed on the PZ-52SF-E, M-NET controllers, and LED dis-
plays (Table 2-2)
6600
Error code
LED1
(green)
6
blinks
LED 2
(red)
Multiple address error
«
There is another unit with the same address setting.
« Check the addresses of devices in
the system.
6607
6608
8
blinks
No ACK error
No answer error (M­NET com­munication error)
«
Power supply to Lossnay is not turned on.
« Lossnay address was changed. « Multiple transmission cables have
been wired using multi core wires.
« Transmission cable is not securely
connected.
«
The length of wiring of the transmission cable is longer than specifications (longer than maximum 200 m from the power sup­ply unit, longer than 500 m between ends).
« Check the power to the Lossnay. « Check the Lossnay address. « Wire the transmission cable away
from the other transmission cable.
« Check the transmission cable con-
nection. (refer to page 58)
« Check the length of the transmission
cable wiring.
0900 Lossnay
trial opera­tion
« Trial operation switch on the Loss-
nay circuit board (SW 2-1 or SW 2-
3) is set to ON.
« Check the trial operation switch.
(refer to page 62)
4116 2
blinks
Fan motor operation device error
« Lossnay fan will not stop. « Replace the table.
3602 3
blinks
Damper
related error
« Damper board operation is not cor-
rect.
« Connectors for the damper unit are
not correctly connected.
« Remove the load and check or
move the damper board by hand.
«
Check the connection of the lead wires connectors and the circuit connector.
5101 4
blinks
OA thermis­tor related error
« Connectors for the thermistor are
not correctly connected.
« Check the connection of the lead
wires connectors and the circuit connector.
5102 5
blinks
RA thermis­tor related error
« Connectors for the thermistor are
not correctly connected.
« Check the connection of the lead
wires connectors and the circuit connector.
6602
6603
6604
1 - 5
blinks
Communi­cation cir­cuit sec­tion error
« Error with transmission cable. « Controller where error originally
occurred is defective.
« Lossnay board is defective.
« Check transmission cable relations. « Check the controller where the error
occurred.
« Replace the circuit board.
——— Lit No M-NET
connection information
« Lossnay does not have Group set-
ting (registration) made.
«
Check the Lossnay address and con­firm that the group setting is made. (refer to page 72 or “15. Appendix”)
Filter blinking
Warning to clean air filter by comulative operation time
« Interval for cleaning Lossnay air fil-
ter has elapsed.
« After cleaning the air filter press the
Filter button on the remote con­troller 2 times.
——— Lit In delayed
start oper­ation
« Delayed start operation is set at the
function select switch (SW 5-1) on the Lossnay circuit board.
« There is no error.
——— LED6 (red)
off
No power to M-NET transmis­sion cable
« Power supply is not supplied to the
M-NET transmission cable.
« Wiring length of the transmission
cable is from the power supply unit or the outdoor unit is longer than specification (maximum extension 200 m).
« Check the connection of the power
supply unit, outdoor unit and trans­mission cable.
« Check the length of the transmission
cable wiring.
Symptom Cause Corrective action
*1 The letters “LC” that display with the error code show a Lossnay unit type, and the number in the third column shows the
address.
*2 Because the LGH-150/200RX
3-E is loaded with 2 control circuit units, 1 Lossnay unit has 2 addresses. Check and perform
maintenance on the table related to the address set at the address switch (SA1, SA2).
46
Trouble Mode 3: The remote controller does not operate or operates irregularly.
(1) Checklist for when using the PZ-41SLB-E (Table 3-1)
(2) Checklist for when using PZ-52SF-E (Table 3-2)
1
No.
Nothing displays on the LCD.
« Transmission cable is connected to the wrong
terminal
« No Lossnay is set to “Main.”
« Power supply to the Lossnay is not turned on. « Lossnay is connected to a power supply with a
rating outside specification.
« Transmission cable is not securely connected.
«
The length of wiring of the transmission cable is longer than specification (longer than 500 m).
«
Check the transmission cable connection (connected to 56 of terminal unit TM2 on the Loss­nay board). (refer to page 56)
«
Turn off the main power supply and set the Main/Sub switch (SW1) (first unit to main, second and following units to sub). (refer to page 57)
«
Check the power supply to the Lossnay.
« Check the power supply.
« Check the transmission cable
connection. (refer to page 56)
« Check the length of the trans-
mission cable wiring.
2 Starts or stops, or the
display changes, by itself.
« Multiple transmission cables have been wired
using multi core wires.
« Transmission cable and power supply cable
are too close.
«
Wire the transmission cable away from the other transmission cable.
«
Wire the transmission cable at least 5 cm away from the power supply cable.
3 Displays a error code
that is not in the check list.
« Letters on the remote controller LCD are dim. « The release of the Delay Start button or the Fil-
ter Reset button is not good.
« Replace the remote control. « Replace the remote control.
4 Cannot stop the Lossnay
with the remote controller (display shows “Interlocked”).
« External priority ON/OFF setting is made. « Check the interlocked operation
mode setting. (refer to page 64)
5 Cannot switch fan speed
with the remote con­troller.
« High/Low change input (CN16) is ON.
«
The function select switch (SW2-4.5) on the Loss­nay circuit has the fixed high or fixed low speed set.
« Check the High/Low change
input (CN16). (refer to page 58)
« Check the function select switch
(SW 2-4.5) (refer to page 60)
6 Lossnay operates when
the main power supply turns on and the remote controller displays.
« Main power supply was cut during Lossnay
operation.
« Stop the Lossnay with the
remote controller, then wait at least 10 second and turn off the main power supply .
Symptom Cause Corrective action
1
No.
Nothing displays on the LCD.
« Transmission cable is connected to the wrong
terminal
« There is no power supply unit (for Lossnay only
systems).
« The power supply unit is not turned on.
« Transmission cable is not securely connected.
« Wiring length of the transmission cable is from
the power supply unit or the outdoor unit is longer than specifications (maximum extension 200 m).
« Check the transmission cable
connection (connected to A, B of terminal unit TB5 on the Loss­nay board). (refer to page 58)
« Install the power supply unit.
« Check the power to the power
supply unit.
« Check the transmission cable
connection. (refer to page 58)
« Check the length of the trans-
mission cable wiring.
Symptom Cause Corrective action
47
« After supplying power to the sys-
tem, HO blinks for a maximum of about 10 minutes. (This is not an error.)
«
Make the group setting (registra­tion). If using a system with a cen­tralised controller, register at the centralised controller. If there is only the Lossnay remote controller, register at the remote controller. (refer to “15. Appendix” or page 72)
«
Check the group setting at the MELANS. (refer to “15. Appendix”)
« Check the power supply to the
Lossnay.
(refer to page 54)
« Check the power supply.
« Check the transmission cable
connection (connected to A, B of terminal unit TB5 on the Loss­nay board).
(refer to page 58)
« Check the Lossnay address.
(refer to page 59)
« If the board has been replaced,
reset the group settings. (refer to “15. Appendix”)
« Check the length of the trans-
mission cable wiring.
2
No.
Displays “HO” and does not start.
« It is less than 10 minutes since the power was
supplied to the system.
« Group setting (registration) has not been
made.
«
Remote control address has not been registered in the group setting by the
centralised controller.
« Power supply to the Lossnay is not turned on.
« Lossnay is connected to a power supply with a
rating outside specification.
« Lossnay transmission cable connection termi-
nal is wrong.
« Lossnay address was changed.
« Lossnay board was changed.
«
The length of wiring of the transmission cable is longer than specifications (longer than maximum 200 m from the power supply unit, longer than 500 m between ends).
3 Cannot register the Loss-
nay from the remote con­troller or the controller.
« Power supply to the Lossnay is not turned on.
« Lossnay is connected to a power supply with a
rating outside specification.
« Transmission cable to the Lossnay is not con-
nected.
« Lossnay transmission cable connection termi-
nal is wrong.
« Lossnay address is wrong.
«
The length of wiring of the transmission cable is longer than specifications (longer than maximum 200 m from the power supply unit, longer than 500 m between ends).
« Check the power supply to the
Lossnay.
(refer to page 54)
« Check the power supply.
« Check the transmission cable
connection.
(refer to page 58)
« Check the transmission cable
connection (connected to A, B of terminal unit TB5 on the Loss­nay table). (refer to page 58)
« Check the Lossnay address.
(refer to page 59)
« Check the length of the trans-
mission cable wiring.
4
Starts or stops, or the dis­play changes, by itself.
« Set for interlocked operation with City Multi. « Cancel interlocked operation
setting. (refer to “15. Appendix” )
5
Displays a error code that is not in the checklist.
« Letters on the remote controller LCD are dim. « Replace the remote controller.
6
Cannot stop the Lossnay with the remote controller (display shows “Central”).
« “Cancel Operation” setting is made from the
MELANS.
« External priority ON/OFF setting is made.
« Remote/nearby switch input (CN32) is set to
“Remote.”
« Check the settings of the
MELANS.
« Check the interlocked operation
mode setting. (refer to page 61)
« Check the remote/nearby
change input (CN32).
Symptom Cause Corrective action
48
Trouble Mode 4: The Lossnay does not operate or operates irregularly.
Lossnay checklist (Table 4).
1
No.
The fan does not operate.
The fan does not operate normally.
« Connectors for the fan connection or connec-
tors for the control circuit section connection are not secure.
« Power supply is not supplied to the Lossnay, or
power outside specifications is connected.
« Lossnay group setting is not made by using the
M-NET. (LED2 lights)
« Check the lead wire connectors
and the control circuit section connectors.
« Check the power supply. (refer to
page 54)
« Check the Lossnay address and
the group setting (LED2 lights when not using M-NET. This is no error.)
3 Fan will not stop. « The trial operation switch (SW 2-1) is ON. « Check the test operation switch
(SW2-1). (refer to page 62)
4 Lossnay operates when
main power is turned on.
« The PZ-41SLB-E is being used.
«
By using the M-NET, the power supply ON/OFF setting is set to ON at the function select switch (SW 2-6) on the Lossnay circuit board.
« By using the M-NET, the automatic recovery
following power supply interruption (refer to page 61) setting is made at the function select switch (SW 5-4) on the Lossnay circuit board.
«
When the main power supply is turned off while the Lossnay is operating from the remote con­troller, the Lossnay will resume operation when the main power is turned back on (this is no error).
«
Check the power supply ON/OFF setting of the function select switch (SW2-6). (refer to page 60)
«
Check the automatic recovery fol­lowing power supply interruption setting of the function select switch (SW5-4). (refer to page 61)
2 Interlocked operation
with external device (air conditioner) does not occur.
« The type of external signal does not match the
connected terminal unit (charged, uncharged, Mr. Slim signal).
« The type of external signal does not match the
pulse input switch (SW2-2) setting (level signal, pulse signal).
« The external device signal is not being input. « The external device and signal cable wiring is
longer than specifications
(12V DC, 24V DC:
Longer than limitations
of external device Uncharged a-contact: Longer than 500 m Mr. Slim signal: Longer than 500 m)
« The Delayed Start mode is set at the remote
controller (PZ-41SLB-E) or the function select switch (SW 5-1) on the Lossnay circuit board.
« The ON Interlocked Operation mode or OFF
Interlocked Operation mode is set at the remote controller (PZ-41SLB-E) or the function select switch (SW 5-7,8) on the Lossnay circuit board.
« When using multiple Lossnay units, the exter-
nal control input signal is connected to a unit with the “Sub” setting made.
« In a group of multiple Lossnay units with the M-
NET, the external control input signal is con­nected to a Lossnay unit other than the one with the smallest address.
« There is a communication error with the
remote controller or controller.
«
Check the external signal type and the external control input terminal (TM2) connection. (refer to page 56, 57)
«
Check the external signal type and the pulse input switch (SW2-2) setting. (refer to page 57)
« Check the external device. « Check the wiring length of the
signal cable.
«
Check the delayed start settings of the remote controller (PZ41SLB-E) and the function select switch (SW5-1). (refer to page 60, 64)
«
Check the interlocked operation mode settings of the remote controller (PZ41SLB-E) and the function select switch (SW5-7, 8). (refer to page 61, 64)
« Connect the external control
input signal to the Lossnay set to “Main.”
(refer to page 57)
« Connect the external control
input signal to the Lossnay in the group with the lowest address.
« Check the remote controller or
controller.
Symptom Cause Corrective action
49
5
No.
Supply air fan periodical­ly stops operating.
« When the outdoor air temperature is -10°C or
less, operation stops after a fixed period of about 10 minutes to keep the Lossnay Core from freezing. (Cold weather area spec)
« When connected to a Mr. Slim or a City Multi
by a duct, operation stops when the air condi­tioner is defrosting.
« This is no error.
« This is no error.
6 Takes in air from out-
doors during interlocked operation with a Mr. Slim or a City Multi, but supply air fan doesn’t stop oper­ating when defrosting.
« The indoor unit’s outside air intake selection is
invalid.
« Set the outdoor air intake selec-
tion of a indoor unit to “ON.”
7 The supply air fan and
exhaust fan both periodi­cally stop operating.
« When connected to Mr. Slim or City Multi by a
duct and the function select switch (SW 5-3) on the Lossnay circuit board is ON, operation stops when the air conditioner is defrosting.
« Check the function select switch
(SW5-3). (refer to page 60)
8 Fan speed will not
change.
« The High/Low switching extermary input
(CN16) is set to ON.
«
The function select switch (SW2-4.5) on the Lossnay cir­cuit board is set to the high fixed or low fixed fan speed.
« The trial operation switch (SW2-1) is turned
ON.
« Check the High/Low change
input (CN16). (refer to page 58)
« Check the function select switch
(SW2-4,5). (refer to page 60)
« Check the trial operation switch
(SW2-1). (refer to page 62)
9 Damper board does not
operate.
« The outside air temperature is less than 8°C. « The damper board operation is defective.
« The thermistor related connectors are not
securely connected.
« The damper related connectors are not
securely connected.
« The trial operation switch (SW2-1 or SW2-3) is
turned ON.
« When using the remote controller to change
ventilation mode, there may be a delayed start of up to 30 seconds depending on the timing.
«
Check the outdoor air temperature.
«
Remove the load and check or move the damper board by hand.
« Check the connections of the
lead wire connectors and the cir­cuit connectors.
« Check the connections of the
lead wire connectors and the control circuit connectors.
«
Check the trial operation switch (SW2­1 or SW2-3). (refer to page 62)
« This is no error.
10
Operation monitor output is late with regard to exter­nal control input ON/OFF.
« When using the PZ-41SLB-E there is a maxi-
mum delay of 7 seconds, or without using there is a maximum delay of 3 seconds.
«
This is
no error.
11 Operation monitor output
is OFF during operation.
« When the function select switch (SW 5-2) on
the Lossnay circuit board is ON, for operation monitor output for interlocked operation with the supply air fan, it turns OFF when the out­side air is -10°C or less or when the air condi­tioner is defrosting.
«
Check the function select switch (SW5-2). (refer to page 60)
12 Delayed start operation
does not work when Delayed start is set.
« When using the PZ-41SLB-E, the circuit func-
tion select switch is set for delayed start.
«
Set delayed start at the remote controller (the circuit board switch is not in effect when using the PZ-41SLB-E). (refer to page 64)
13
Lossnay does not operate when power is on even when the power on/off setting is made.
« Using the PZ-41SLB-E. « The power supply ON/OFF set-
ting is not in effect when using PZ-41SLB-E.
14 Interlocked operation is
different from the set­tings.
« When using the PZ-41SLB-E, the circuit func-
tion select switch is set for interlocked opera­tion.
«
Set interlocked operation at the remote controller (the circuit board switch is not in effect when using the PZ-41SLB-E). (refer to page 64)
Symptom Cause Corrective action
50
Temperaturers vs. thermistor resistance table
Temperature
(°C)
Resistance
value (kΩ)
Temperature
(°C)
Resistance
value (kΩ)
Temperature
(°C)
Resistance
value (kΩ)
Temperature
(°C)
Resistance
value (kΩ)
Temperature
(°C)
Resistance
value (kΩ)
-40 88.85 - -7 17.92 8 9.57 23 5.38 38 3.17
. . .
. . .
. . .
. . .
-6 17.16 9 9.20 24 5.19 39 3.06
-20 32.43 -5 16.43 10 8.84 25 5.00 40 2.96
-19 30.92 -4 15.74 11 8.49 26 4.82 41 2.86
-18 29.50 -3 15.08 12 8.17 27 4.65 42 2.77
-17 28.14 -2 14.45 13 7.85 28 4.49 43 2.68
-16 26.87 -1 13.86 14 7.55 29 4.33 44 2.59
-15 25.65 0 13.29 15 7.27 30 4.18 45 2.51
-14 24.51 1 12.74 16 6.99 31 4.03 46 2.43
-13 23.42 2 12.22 17 6.73 32 3.89 47 2.35
-12 22.39 3 11.72 18 6.48 33 3.76 48 2.28
-11 21.41 4 11.25 19 6.24 34 3.63 49 2.21
-10 20.48 5 10.80 20 6.01 35 3.51 50 2.14
-9 19.58 6 10.37 21 5.79 36 3.39
-8 18.73 7 9.96 22 5.58 37 3.28 87.5 - 0.72 - 0
51
11.3 Circuit Test Point
LED1 (green)
• When blinking, there is an error with the Lossnay unit (number of blinks indicates the type of error).
• Blinks at 1 second intervals when starting.
• Lit during delayed start, normally off at other times.
LED2 (red)
• Blinking indicates M-NET communication error (number of blinks indicated the type of error).
• Lit when not connected to other M-NET units (registered).
Exhaust fan operation unit (combined)
Fuse (6.3 A/250 V)
Supply fan operation unit (combined)
Power supply 220 V to 240 V AC: up to 50 Hz 220 V AC: up to 60 Hz (60 Hz is not used in EU)
Transformer input
Damper motor operation unit 220 V - 240 V AC
5 V DC 12 V DC
Transformer output 11 V to 20 V AC
GND
LED4 (red)
• lit when power is supplied to circuit
12 V DC
Thermistor (outdoor air) Thermistor (return air)
Damper position detector
• during Lossnay ventilation: 12 V DC
• during by-pass ventilation: 0 V
LED6 (red)
• lit when power is supplied to M-NET
M-NET transmission cable (shielded)
M-NET transmission cable (PZ-52SF-E, MELANS, power supply unit or City Multi)
Not in use For external device connection
During operation: 0 When stopped: OPEN
During error: 0 Normal: OPEN
Remote control switch (PZ-41SLB-E) and
Lossnay spanning transmission cable
9 V to 15 V DC
Exhaust fan operation unit 220 V to 240 V AC: up to 50 Hz 220 V AC: up to 60 Hz
Supply fan operation unit 220 V to 240 V AC: up to 50 Hz 220 V AC: up to 60 Hz
Extra
high
High Low
Extra
high
High Low
52
12.
Installation method (Model LGH-RX
3
-E series)
12.1 Electrical installation
With this product, the wiring installation method will vary according to the design of the system. Perform electrical installation for each of the required sections.
12.1.1 Names of components in control box
LGH-15 to LGH-100RX3 LGH-150 and LGH-200RX3
SW5
Earth pole
TM1
LED4
LED1
LED2
LED6
TB5 SA2 SA1
Bush
SW4 SW3
SW1
TM3
TM2
SW2
PE
L
N
DC 24V 2A DC 5V 100mA
AC240V 2A AC220V 100mA
MAX MIN
Operation monitor output
DC 24V 1A DC 5V 100mA
AC240V 1A AC220V 100mA
MAX MIN
Malfunction monitor output
M2
M1
7
8
9
31
SBA654132
cable
TH2 (RA)
(Invalid in EU)
220V - 60HZ
220-240V - 50HZ
POWER SUPPLY
CN5
LS
M-NET-transmissiion cable
a-contact
TR
C
C
ZNR101
250V6.3A
FUSE
C101
DSA1
ZNR102
BROWN
CN8-2
RED
CN8-1
5
1
5
1
SW4
HIGH
EXTRA
×
3
×
4
×
1
FAN MOTOR
SUPPLY
HIGH
CN9
CN10
FAN MOTOR
EXHAUST
BLACK GREY YELLOW
ORANGE
WHITE
BLUE
HIGH
EXTRA
HIGH
×
5
×
2
SW3
×
8
×
7
TM3
10
External control input
3
Shield wire
a-contact
TM2
(non-polar)
Mr. Slim
24V DC
12V or
Uncharged
41SLB-E
52SF-E
Transmissiion
Lossnay unit Max 15 units
TB5
CN32
GREEN/YELLOW
TM1
S2
S1
1
1
6
CN1
CN6
CN2
CN7
High/Low select connector
Unchaged
Low
High
CN16
GM
CN16
PZ-
PZ-
TH1 (OA)
BREKER
BLUE
BROWN
YELLOW
RED
BROWN
BROWN
ORANGE
ORANGE
GREY GREY
BLUE
BLUE
WHITE
WHITE
SW1
SW2
SW5
SA2
SA1
N
L
SW1
SW4
SW3
SW4 SW3
TM1
Cord Clip
LED6
SA1
SA2
SA2 SA1 LED2
TM3
TM3
LED1 TB5 TM2
Bush
SW5 SW2
SW1 SW5 SW2
LED4
12.1.2 Wire connection diagram ----­Models LGH-15 to 100RX3
* Connect the wires shown as dotted lines. * Be sure to connect the grounding wire. * Breaker should be provided by the customer.
Symbol explanation
• PZ-41SLB-E and PZ-52SF-E cannot be used simultaneously.
M1: Motor for exhaust fan M2: Motor for supply fan C: Capacitor GM: Motor for Bypass move-
ment LS: Microswitch TH1: Thermistor for outside air TH2: Thermistor for return air SW1: Switch
(Main/Sub change)
SW2,5: Switch (Function selec-
tion) SW3: High/E.High select switch
(Exhaust fan) SW4: High/E.High select switch
(Supply fan) TM1: Terminal block
(Power supply) TM2: Terminal block
(Transmission cable and
external control input) TM3: Terminal block (Monitor
output) TB5: Terminal block
(M-NET Transmission
cable) S1,S2: Connector (Power sup-
ply) TR: Control circuit trans-
former X7: Relay contact (For opera-
tion monitor output)
X8: Relay contact (For mal-
function monitor output)
CN1: Connector
(Transformer primary)
CN2: Connector
(Transformer secondary)
CN5: Connector
(Thermistor)
CN6: Connector
(Microswitch)
CN7: Connector (Motor for
bypass operation)
CN8-1: Tab connector
(Fan motor)
CN8-2: Tab connector
(Fan motor) CN9: Connector (Fan motor) CN10: Connector (Fan motor) CN16: Connector (High/Low
switch) CN32: Connector (Remote
control selection) SA1: Address setting rotary
switch
(10 digit) SA2: Address setting rotary
switch
(1 digit) LED1: Inspection indicator lamp LED2: Inspection indicator lamp LED4: Power supply indicator
lamp LED6: M-NET indicator lamp
MARK : Indicates ter-
minal block
: Connector
: Board inser­tion connector or fastening connec­tor of control board
M1: Motor for exhaust fan M2: Motor for supply fan C: Capacitor GM: Motor for Bypass movement LS: Microswitch TH1: Thermistor for outside air TH2: Thermistor for return air SW1: Switch(Main/Sub change) SW2,5: Switch (Function selection) SW3: High/E.High select switch
(Exhaust fan)
SW4: High/E.High select switch
(Supply fan)
TM1: Terminal block (Power supply) TM2: Terminal block (Transmission
cable and external control input)
TM3:
Terminal block (Monitor output)
TB5: Terminal block (M-NET
Transmission cable) S1,S2: Connector (Power supply) TR: Control circuit transformer X7: Relay contact (For operation
monitor output) X8: Relay contact (For malfunction
monitor output)
CN1: Connector (Transformer
primary)
CN2: Connector (Transformer sec-
ondary) CN5: Connector (Thermistor) CN6: Connector (Microswitch) CN7: Connector (Motor for bypass
operation) CN8-1: Tab connector (Fan motor) CN8-2: Tab connector (Fan motor) CN9: Connector (Fan motor) CN10: Connector (Fan motor) CN16: Connector (High/Low switch)
CN32: Connector (Remote control
selection)
SA1: Address setting rotary switch
(10 digit)
SA2: Address setting rotary switch
(1 digit)
MARK
: Indicates terminal block : Connector : Board insertion connector or
fastening connector of control board
53
12.1.3 Wire connection diagram ----- Models LGH-150 and 200RX3
* Connect the wires shown as dotted lines. * Be sure to connect the grounding wire. * Breaker should be provided by the customer.
10
10
(Invalid in EU)
220V - 60HZ
220 - 240V - 50HZ
POWER SUPPLY
LN
PELN 5
6S
B
A
DC 24V 2A DC 5V 100mA
AC240V 2A AC220V 100mA
MAX MIN
Operation monitor output
DC 24V 1A DC 5V 100mA
AC240V 1A AC220V 100mA
MAX MIN
Malfunction monitor output
M
2
M
1
78
9
31
S
B
A
6
5
4
1
3
2
2
3
1
4
5
6
A
B
S
9
87
M
2
M
1
(Subordination)
(Main)
Transmissiion cable
Lossnay unit Max 7 units
TM1 TM2 TB5
M-NET-transmissiion cable
Shield wire
C
C
TH2 (RA)
TH1 (OA)
TH1 (OA)
TH2 (RA)
PZ­52SF-E
PZ-
41SLB-E
CN5
LS
a-contact
TR
C
C
ZNR101
250V6.3A
FUSE
C101
DSA1
ZNR102
BROWN
CN8-2
RED
CN8-1
5
1
5
1
SW4
HIGH
EXTRA
× 3
× 4
× 1
BLACK
GREY
YELLOW
GREEN/YELLOW
ORANGE
WHITE
FAN MOTOR
SUPPLY
HIGH
CN9
CN10
FAN MOTOR
EXHAUST
BLUE
HIGH
EXTRA
HIGH
× 5
× 2
SW3
× 8
× 7
TM3
External control input
3
a-contact
TM2
(non-polar)
24V DC Mr. Slim
12V or
Uncharged
TB5
CN32
S2
S1
1
1
6
CN1
CN6CN2
CN7
High/Low select connector
Unchaged
Low
High
CN16
CN16
YELLOW
RED
BROWN
BROWN
ORANGE
ORANGE
GREY
GREY
BLUE
BLUE
BROWN
BLUE
BROWN
BLUE
WHITE
WHITE
SW1
SW2 SW5
SA2
SA1
SA1
SA2
SW5
SW2
SW1
WHITE
WHITE
BLUE
BLUE
GREY
GREY
ORANGE
ORANGE
BROWN
BROWN
RED
YELLOW
(CN16)
GM
GM
CN7
CN2
CN6
CN1
6
1
1
S1
S2
(CN32)
(TB5)
(TM2)
3
(TM3)
× 7
× 8
SW3
× 2
× 5
HIGH
EXTRA
HIGH
BLUE
EXHAUST FAN MOTOR
CN10
CN9
HIGH
SUPPLY FAN MOTOR
WHITE
ORANGE
YELLOW
GREY
BLACK
× 1
× 4
× 3
EXTRA
HIGH
SW4
1
5
1
5
CN8-1
RED
CN8-2
BROWN
ZNR102
DSA1
C101
FUSE
250V6.3A
ZNR101
C
TR
LS
CN5
Symbol explanation
PZ-41SLB-E and PZ-52SF-E cannot be used simultaneously.
54
12.2 Connecting the power supply cable
1. Remove the screws and open the control box cover
LGH-15 to 100RX3
Control box cover Screw
2. Connecting the power supply cable and transmission cable
Pass the power cable through the bush* and connect to the TM1 terminal block using the round terminals. Connect the grounding wire to the grounding terminal and secure tighten­ing the bush. (*: for PG connection or the like)
(1) Refer to the wiring diagram and screw down the grounding
wire and transmission cables to the terminal block.
(2) Secure the power supply cable and transmission cables
using the cord clamp.
Upon completion of the wiring connections, replace the control box cover.
CAUTION:
Always separate the power supply cable and transmission cable by 5 cm or more to prevent malfunctioning of the unit.
If the length of the stripped power cables wires is too long, the conductors may touch and cause shorting.
LGH-15 to 100RX3
Grounding wire
Power supply cable
Cord clip
Transmission cable
Bush
Insert the cutting
TM1
Power supply cable
PG connection
LGH-150 and 200RX3
Power supply cable Transmission cable
TB5
Control box
Bush
TM2
TM1
Grounding wire
Power supply cable
Cord clamp
TB5
TM2
TM1
Bush
Transmission cables
LGH-150 and 200RX3
Control box cover
Screw
55
3. When installing upside down
CAUTION:
If installing and using this product upside down, the power supply cable outlet will be at the top. Be sure to attach the protective cover so that no drops of water can get inside the control box.
LGH-15 to 100RX3 LGH-150 and 200RX3
Protective cover
Control box
Protective cover
Control box
<When installing upside down> <When installing upside down>
4. Changing the switch for High and Extra High
To increase the air volume, change the switch from “high” to “extra high”.
The factory setting is “High”.
Can be switched for each supply and exhaust separately.
LGH-15 to 100RX3
High and Extra High switch
High
E-High
High
E-High
Exhaust air Supply air
LGH-15 to 100RX3
High and Extra
High switch
High
E-High
High
E-High
Exhaust air
Supply air
56
The following system configuration can be created. Connect the necessary parts.
1. When connecting with remote controller (PZ-41SLB-E).
2. When interlocking with air conditioner or other external device.
3. When interlocking with a pulse output unit.
4. When operating multiple Lossnay units.
5. When connecting to CO2 sensor when switching the High/Low switch externally.
6. When connecting to City Multi, Lossnay remote controller (PZ-52SF-E) or Mitsubishi Electric Air-Conditioner Network System (MELANS).
1. When connecting to remote controller (PZ-41SLB-E)
* The PZ-41SLB-E cannot be used when centralised control
of the Lossnay is used. Then follow the procedure for con­necting the wire shown in 6. and use the Lossnay remote controller (PZ-52SF-E).
Securely connect the transmission cable (PVC insulated PVC jacketed and either between ø0.65 and ø1.2, or between 0.3
mm
2
and 1.25 mm2in cross section) from the remote controller
to 5 and 6 of the input terminal block (TM2). (No polarity)
If there are two remote controllers, connect them in the same way.
Note:
Up to four 0.3 mm2stranded wires or ø0.65 PVC wires can be connected to one input terminal.
For other types of wire up to two can be connected.
2. When interlocked with air conditioner or other external device
(1) Connect the output signal cable from the external device to
the input terminal block (TM2) of the external controller.
LGH-150 and 200RX3 are conected to the lower circuit board. (Main circuit board)
CAUTION:
The connection may vary according to the output signal type of the external device.
When using Mr. Slim air conditioner and (A control or K control) Interlock operation of except Mr. Slim (A control or K control) unit is not possible.
Connect the interlocking cable connector side to CN2L on the circuit board for the indoor Mr. Slim unit and connect the lead wire side to the 1 and 2 of the input terminal block (TM2) for
the Lossnay external controller input. (No polarity)
Always separate the power supply cable and the Slim­Lossnay connection cable for the Lossnay by 5 cm or more to prevent malfunctioning of the unit.
The Slim-Lossnay connection cable is 0.25 m long.
When wiring, extend it as far as necessary.
Note:
The Lossnay remote controller (PZ-41SLB-E) cannot be used with this system.
The ventilation mode is “automatic ventilation”.
The Slim-Lossnay connection cable may be extended to a
maximum length of 500 m (Extension cable specifications are as detailed below). Ensure that all connections are secure and that the appro­priate insulation is provided.
Extension cable sheathed PVC cable or cable-0.5 mm2to 1.0 mm2.
ABS65654321
Power supply
Remote controller input terminal
Transmission cable
Up to two remote controllers (PZ-41SLB-E) can be used.
Lossnay
Power supply
Within 500 m
Red
White
Power supply
CN2L
Mr. Slim (A control or K control) unit
Printed circuit board
Remote con­troller (PZ-41SLB-E)
Operating switch for external device
Lossnay
External
device
Lossnay External controller input (TM2)
Slim-Lossnay connection cable (Enclosed accessory)
LGH-15 to 100RX3LGH-150 and 200RX
3
57
When the external device has a charged operating signal of 12V DC or 24 V DC
• Connect the operating signal (wire) from the external device via the remote output retrieval component (sold separately) to 1 and 2 on the external control input terminal block (TM2). (No polarity)
When the external device has an uncharged a-contact signal
• Connect the operating signal (wire) from the external device via the remote output retrieval component (sold separately) to 1 and 3 on the external control input terminal block (TM2).
Note:
If an optocoupler or any other type of polar coupler is used
at the uncharged a-contact, connect the positive side to 3 and the negative side to 1.
3. When interlocking with a pulse output
unit
(1) Move the pulse input switch [SW2-2] to the ON position.
On the LGH-150 and 200RX3, set both the upper and lower circuit boards the same.
(2)
Connect the pulse output device (i.e., building management system) to the external control input terminal block [TM2]. The LGH-150 and 200RX3 connected to the lower circuit board. (Main circuit board)
• A pulse width of at least 200 msec will be needed.
(3) Wiring is to be performed in the same way as for item 2
above.
4. When operating multiple Lossnay units
(1) Connect from Lossnay unit 1 to Lossnay unit 2, and from
unit 2 to unit 3 and so on up to a maximum of 15 units (7 units for types 150 and 200) using a transmission cable (PVC insulated PVC jacketed and either between ø0.65
and ø1.2, or between 0.3 mm
2
and 1.25 mm2in cross
section).
(2) Change the setting on the main/sub switch (SW1) on the
second and subsequent Lossnay units to “sub”.
Note:
Up to four 0.3 mm2stranded wires or ø0.65 PVC wires can
be connected to one input terminal.
For other types of wire up to two can be connected.
The operation signal and pulse signal can be connected to
the external device of the main Lossnay only.
Connect the power to each respective Lossnay unit.
External device
12 or 24 VDC
Overall connection extension length
(Follow the operation manual for the external equipment.)
0.5 mm
2
to 1 mm2sheathed PVC cable
Lossnay External control input (TM2)
External device
Uncharge a-contact
Within 500 m
0.5 mm
2
to 1 mm2sheathed PVC cable
Lossnay External control input (TM2)
Operating switch for external device
LGH-15 to 100RX3-E MAX 15 units LGH-150 and 200RX3-E MAX 7 units
Powe r supply
Power supply
External
device
Powe r supply
Powe r supply
Remote controller (PZ-41SLB-E)
12
SW2
ON OFF
345678
65
65
Connect to remote controller (PZ-41SLB-E)
Connect to third Lossnay
Main/Sub selection switch
(SW1)
Transmission cable
(The upper control circuit for LGH-150 and 200RX
3 is normally set to “Sub”.)
Second
Lossnay
Main Sub
First Lossnay
Lossnay
(Main)
Lossnay
(Sub)
Lossnay
(Sub)
58
5. When switching High/Low speed external­ly (when CO
2 sensor or other unit is con-
nected)
If a commercially available CO2 sensor or other such unit is used as shown in the drawing, connect by inserting Remote ON/OFF Adaptor (PAC-SE55RA-E) (sold separately) to the CN16 connector (for switching between High/Low).
* The LGH-150 and 200RX
3 are connected to the lower cir-
cuit unit. (Main circuit board)
* Note that if the remote controller is connected to a CO2
sensor, the actual high and low fan speeds may not match on the remote controller.
To force high speed externally When external switch is “ON” fan speed of the Lossnay will be set to “High”. Regardless of the remote control setting.
To force low speed externally When external switch is “ON” fan speed of the Lossnay will be set to “Low”. Regardless of the remote control setting.
6. When connecting to the City Multi, Lossnay M-NET remote controller (PZ­52SF-E) or Mitsubishi Electric Air­Conditioner Network System (MELANS)
* If centralised control is performed according the wire con-
nection shown in this section, the remote controller (PZ­41SLB-E) cannot be used.
• One shieled wire is connected to the other shieled wire.
(Terminal connection)
Address setting is required. (Refer to function setting section.)
M-NET transmission cable: Connect any of the following --
City Multi indoor unit, Lossnay remote controller (PZ-52SF-E) or Mitsubishi Electric Air­Conditioner Network System (MELANS) - to the Lossnay.
Type: (Shielded wire, CVVS/CPEVS)
Wire diameter: 1.25 mm
2
to 2.0 mm
2
• Securely connect the M-NET transmission cable to A and
B on the transmission cable input terminal block (TB5). (Non-Polar)
CN16
CO2 sensor, etc. (Closed when there is an increase in CO2)
Switch: High operation switch (When closed, high operation)
Remote ON/OFF adaptor (sold separately PAC-SE55RA-E)
Not used. Insulate completely.
Lossnay controller circuit unit
High/Low switching
Orange 1
Switch
Red 2
Brown 3
Wiring length up to a maximum
of 10 m
CN16
CO2 sensor, etc. (Closed when there is an increase in CO
2)
Switch: Low operation switch (When closed, low operation)
Remote ON/OFF adaptor (sold separately PAC-SE55RA-E)
Not used. Insulate completely.
Lossnay controller circuit unit
High/Low switching
Orange 1
Switch
Red 2
Brown 3
Wiring length up to a maximum
of 10 m
ABS A65BS
Round terminal M-NET transmission cable input terminal block
M-NET transmission cable
LGH-15 to 100RX
3
TB5
LGH-150 and 200RX
3
TB5
Switch
Shielded wire
59
When interlocking with the City Multi
• Keep the overall length of the transmission cable within 500 meters. Note that the wiring length between the Lossnay and power supply unit (sold separately) or outdoor unit should be 200 meters or less.
Lossnay M-NET remote controller (PZ-52SF-E) or MELANS
• Connect the power supply unit (PAC-SC34 KUA)
To use the power supply unit
Install the power supply unit on the control panel box as follows. (1) Screw the M4 SCREWS into the control panel box enough
to keep them from falling out of place. Set them towards the top of the box.
(2) Hang the power supply unit (from the top end) on the M4
SCREWS. (3) Lock the bottom end down with the M4 SCREW. (4) Tighten the top end screw securely. (5) Once installed, close the control panel box door for safely
reasons and lock with the key or screw.
For more information, see the installation manual of the power supply unit.
City Multi
City Multi
Lossnay
M-NET transmission cable
Remote controller for City Multi
MELANS
Power
supply unit
M-NET transmission cable
Lossnay M-NET
remote controller
(PZ-52SF-E)
Lossnay
0
1
SA1 SA1
0
2
0
1
SA1 SA2SA1 SA2
12.3 Function settings
You must set the address when connecting to the City Multi, Lossnay M-NET remote controller (PZ-52SF-E) and MELANS.
12.3.1 Setting the address
Use the following procedure when performing the address set­ting for dedicated Lossnay. (The method to be employed in the determination of addresses will be dependent on the existing system. Refer to the appropri­ate technical documents for details.)
(1) Remove the control box cover. (2) Use a straight-blade screwdriver to turn the address setting
switch on the circuit board.
• SA1 indicates the 10 digit and SA2 indicates the 1 digit.
• The factory setting is “00”
On the LGH-150 and 200RX3, each upper and lower circuit board has an address. The lower circuit board takes the smaller number and the upper table takes the larger num­ber.
* When the address number has been changed, the
data in the memory is automatically reset.
Control panel box
Power supply unit
M4 SCREW
Key or screw
LGH-15 to 100RX
3
LGH-150 and 200RX3
Upper circuit board [Sub] ex. SA1 = 0, SA2 = 2
Lower circuit board [Main] ex. SA1 = 0, SA2 = 1
60
OFF ON Mode Operation
6
OFF Stopping and operation is performed according to settings
SW2
(Factory setting) of SW5-4 when the power is on.
6 ON Operation possible by turning power on and off.
OFF ON Mode
SW2
2 No pulse input (factory setting)
2 Pulse input
OFF ON Operation
SW5
3 Exhaust fan operation (factory setting)
3 Exhaust fan stopped
OFF ON Mode
SW5
1 No operation delay (factory setting)
1
Operation delay of 30 minutes * This function is invalid with in 2 hours’ restart
OFF ON Mode
2 Corresponds to operation mode output (TM3 90) exhaust fan (factory setting)
SW5
Corresponds to operation mode output (TM3 90) supply fan
2 (The operation monitor output is off when the supply fan is stopped for operation in
cold regions or during the City Multi or Mr. Slim defrosting.)
OFF ON Mode Operation
4
Normal Switches High/Low by operation of the fan speed from
5
(Factory setting) remote control.
SW2
4
Fixed at high mode Normally operated at high speed.
5
4
Fixed at low mode Normally operated at low speed.
5
12.3.2 Switching function selection switches (SW-2 and 5)
Perform the necessary function settings using the function selection switches (SW-2 and 5).
The setting can be changed at any time.
On the LGH-150 and 200RX
3, set both the upper and lower circuit boards the same.
1. Settings for pulse input
Set as shown when connecting the pulse signal equipment from a building maintenance system to an external input.
2. Setting for selection of fan speed method
Set when operation is fixed at high speed or low speed operation. There are three modes that can be set.
3. Power supply ON/OFF function (cannot be set when PZ-41SLB-E is used)
Set can be switch when operation and stopping is performed by turning the power supply (220-240 V) for the Lossnay on and off.
4. Settings for delay (of operation at start-up of heating or cooling)
This is the mode for delaying the operation of the Lossnay for 30 minutes when the City Multi or Mr. Slim is started and when a external device is started. (If the PZ-41SLB-E is used, set it at the remote control. Refer to page 61.)
6. Stopping exhaust fan when defrosting air conditioner
Sets the operation of the exhaust fan (when the air supply fan is stopped) during defrosting of the air conditioner when Mr. Slim or City Multi indoor unit is connected to a duct.
5. Supply air fan monitor
61
OFF ON Mode Operation
SW5
4
No automatic recovery
Stop after recovery
(factory setting)
4 Automatic recovery Recover to operate in mode used before power outage
7. Settings for automatic recovery following power supply interruption (cannot be set when PZ-41SLB-E is used)
Sets for automatic recovery following power supply interruption.
8. Settings for filter cleaning
Set the time for filter cleaning based on the estimated concentration of dust in the air. The factory setting is unlimited. (If the PZ-41SLB-E is used, set it at the remote control. Refer to page 67.)
The four combinations of settings shown in the drawing to the bottom are available settings for air filter cleaning.
OFF ON Maintenance
5
3000 hours
6
5
1500 hours
SW5
6
5
4500 hours
6
5
Unlimited (No “FILTER” display on remote controller) (factory setting)
6
CAUTION:
When the setting for the cumulative operation time of the Lossnay is exceeded, the filter cleaning display will appear on the air conditioner remote controller or the remote controller for the Lossnay. After cleaning the filter, the filter cleaning display can be reset by following the procedure for canceling the cumulative operation time as shown in the manual.
9. Settings for interlock mode
These settings will indicate how the Lossnay should operate when external devices are started or stopped. (If the PZ-41SLB­E is used, set it at the remote control. Refer to page 67.)
OFF ON Mode Units
The Lossnay will start and stop in accordance with starting
7
ON/OFF interlock
and stopping of an external devices.
8
(Factory setting)
Subsequent operation will be possible using the remote controller for the Lossnay or MELANS.
7
The Lossnay will operate whenever
an
external devices
8
On interlock are operated. Stopping of the Lossnay will be possible
SW5 using its remote controller or MELANS.
7
The Lossnay will stop whenever
an
external devices are
8
Off interlock stopped. Starting of the Lossnay will be possible using its
remote controller or MELANS.
The Lossnay will start and stop in accordance with starting
7
External input given
and stopping of
an
external devices. Control using the
8
priority
remote controller for the Lossnay or MELANS will only be possible when an external devices are stopped.
12.4 Trial operation
After the overall system has been installed, before the ceiling panel is installed, make sure that no wires are wrongly connected, then carry out trial operation, referring to the user’s manual for the remote controller.
12.4.1
Trial operation with the remote controllers (PZ-41SLB-E and PZ-52SF-E)
Follow the procedure shown in the operator’s manual for the remote controller for confirming the following items. (1) Starting operation. (2) Fan speed selection. (3) Function selection. (4) Stopping operation.
62
12.4.2 Lossnay independent trial operation
(1) Remove the control box cover. (2) Turn the trial operation switch (SW2-1and SW2-3) “ON.”
• Operation will start with the “High” setting and with Bypass ventilation operating. (This will take approximately 45 seconds after the power is turned on.)
• On the LGH-150 and 200RX
3, set both the upper and lower circuit boards the same.
(3) Turn the trial operation switch (SW2-1and SW2-3) “OFF.” (4) Install the cover in its original position on the control box.
OFF ON Operation
1
Power supply will be supplied to the motor for the Lossnay fan and operation will be
SW2
performed at the “High” setting.
3
Power supply will be supplied to the motor for the Lossnay by-pass and operation of the damper plate will be performed.
12.4.3 Trial operation within the complete system
Interlock system containing an air conditioner and/or external device
• Use the remote controller for the air conditioner or the operating switches for the external device and confirm that the air conditioner and Lossnay are interlocked.
• If delay time has been set, check that the Lossnay operates after the delay time has passed.
If MELANS System
• Use MELANS to confirm the operation of the Lossnay.
12.4.4 If trouble occurs during trial operation
Symptom
Will not operate even when the operation switch for the remote controller (PZ-41SLB­E) and/or operation switch for the Lossnay remote controller (PZ-52SF-E) is pressed.
“HO” flashes in remote con­troller for Lossnay (PZ-52SF-E).
Does not operate even when the operation switch for remote con­troller for Lossnay (PZ-52SF-E) or MELANS is pressed.
Air conditioner or external device does not interlock.
Lossnay does not stop. The inspection indicator lamp
(LED 1 Green) in the control box flashes.
The inspection indicator lamp (LED 2 Red ) in the control box flashes.
Remedy
• Check the power supply. (The specified power supply is single-phase 220-240 V to 50 Hz and 220 V to 60 Hz.)
• Check for a short circuit or disconnection in the transmission cable. (Check that the voltage between terminals in the transmis­sion cables is 9 to 15 V DC for the PZ-41SLB-E and 20 to 30 V DC for the PZ-52SF-E.)
Check that the there is 5 cm or more separating the transmission cable from the power supply cable and any other transmission cables
.
• Run the Lossnay independently using the trial operation switch (SW2-1) and check if it runs.
• Check if there are three or more remote controller connected (PZ-41SLB-E). (The maximum is two.)
• Perform the registration operation using the remote controller for the Lossnay (PZ-52SF-E) or MELANS. (Refer to the installation instructions for the remote controller for the Lossnay or MELANS.)
• Check whether or not there is a power supply unit and that the power has been turned on. (On systems with only a Lossnay, a power supply unit is required.)
• Check if the pulse input switch (SW2-2) is off.
• Check the overall length between the air conditioner or external device and Lossnay. (Refer to technical publications or other such documents.)
• Check the connections at the external control input terminal block (TM2). In the case of voltage charged 12 or 24 V DC output unit: Connect to external control input terminals 1 and 2 . In the case of uncharged a-contact output unit: Connect to external control input terminals 1 and 3. In the case of Mr. Slim (A control or K control): Connect to external control input terminals 1 and 2.
• Perform the registration operation using the remote control for the air conditioner or MELANS. (Refer to the installation instruc­tions for the remote control for the air conditioner or MELANS.)
• Check if the delay has been set.
• Check the overall length of the transmission cable between the external device and Lossnay. (Refer to technical publications or other such documents.)
• Check if the transmission cable from the external device has come off of the external control input terminal.
Check, in the case of multiple units, whether the Main/Sub selection switch on the Lossnay unit which is connected to the external con­trol input terminal is set on the Master setting, and check whether the Main/Sub selection switch on other Lossnay units are set to Sub.
• Check that the trial operation switch (SW2-1) is set to off.
Lossnay runs Check the signal cables Lossnay doesn’t run Check the power supply
Operation signal Stop signal
Charged 12 or 24 VDC output unit 12 or 24 V DC 0 V DC Uncharged a-contact output unit Resistance: 0 W Unlimited resistance W Mr. Slim (A control or K control) 2 to 6 V DC 2 to 6 V DC
2 flashes Failure of Lossnay circuit 3 flashes Failure of damper motor system
Turn off the power supply and immediately contact
4 flashes Failure of Lossnay (OA side) motor system
your dealer.
5 flashes Failure of Lossnay (RA side) motor system
ON In delay periodc
If there is no remote controller (PZ-41SLB-E), the lamp will go out after 30 minutes (of operation) has passed.
1 to 8
Error in M-NET communication
Turn off the power and immediately contact your dealer.
flashes
ON Registration operation has not been performed. Use the controller to perform the registration.
When an inspection number blinks on the remote controller, follow the procedures shown in the installation and operating manuals provided with the switch.
If the remote controller is not used, operate approximately 45 seconds after turning on the power for the Lossnay.
63
13.
Lossnay Remote Controller (PZ-41SLB-E)
13.1 Operation
Ventilation Mode Selector Button
Used to select the ventilation mode from among Heat recovery (Heat exchange). By-pass or automatic.
DELAYSTART
FILTER
PZ-41SLB-E
2CONTROLLERS
BY-PASS
CHECK SETTING
FILTER MIN.DELAYED
AUTO
HEATEX.
INTERLOCKED
[2-CONTROLLERS] Display
Displayed when two Lossnay remote controllers operate the Lossnay unit(s). Note that the most recent button operations of either one will be given priority in such a case.
[INTERLOCKED] Display
Displayed when the Lossnay starts off by interlocked indoor unit or external signal.
Fan Speed Display
Displays the selected fan speed.
[FILTER] Display
Displayed when the accumulated operating time reaches at the time set for air filter maintenance.
Operation lamp
On during operation. Flashes when a malfunction occurs.
Ventilation Modes
Indicates the ventilation mode status.
Heat recovery (Heat exchange)
HEAT EX.
By-pass BY-PASS
Automatic (Heat ex./By-pass)
Power Display
Displayed while the Lossnay remote controller is powered on.
[CHECK] Display
Displayed together with the malfunctioning unit (3 digits) and an error code (4 digits).
Delay time Display
Displays delay time.
Delay setting SETTING
XX MIN.DELAYED (XX:0-60)
During delay operation
XX MIN.DELAYED (XX:1-60)
[ON/OFF] Button
Switches between run and stop. The lamp on the button stays lit during operation.
Fan Speed Adjustment Button
Used to select the fan speed of either "Low" or "High".
[FILTER] Button
Press two times to reset the filter sign display.
[DELAY START] Button
Used to set for delay time.
BY-PASS
AUTO
HEATEX.
BY-PASS
AUTO
or
Low High
* Entire panel is displayed for explanation.
Note:
When power is restored after an outage or when the corresponding breaker for the distribution box is reset, all modes will return to the condition before the supply of power was interrupted.
64
13.2 Mode of Use
Independent Operation of the Lossnay Unit:
Interlocked Operation with Indoor unit or external signal.
The Lossnay unit can be set up in such a way that it may be turned on and off by external device such as an air conditioners. In such a case, the remote controller's [INTERLOCKED] display will be turned on. Note that the selection of ventilation mode and of fan speed can be performed in the same way as for independent operation of the Lossnay unit.
SSeettttiinnggss ffoorr IInntteerrlloocckkiinngg tthhee LLoossssnnaayy uunniitt wwiitthh aann eexxtteerrnnaall ddeevviiccee
Operation
Relevant button
Relevant display items
Sequence
1.Starting the Lossnay unit
2.Setting the Ventilation mode
3.Selecting the fan speed
4.Stopping the Lossnay unit
Press the ON/OFF button and confirm that the Operation lamp turns on. The 2CONTROLLERS display item will be turned on if a double set of remote controllers is currently in use.
Press the Function selector button: Each time it is pressed, the corresponding display will change in accordance with the sequence [HEAT EX.] (non-auto­matic) [BY-PASS] (non-automatic) [AUTO]. If [AUTO] is selected, the display will change to indicate the current situation after two seconds have passed.
or
Press the Fan Speed selector button to select either Low or High fan speed.
Press the ON/OFF button. (Press the ON/OFF button to turn off the Operation lamp.)
BY-PASS
AUTO
HEATEX.
AUTO
HEATEX.
AUTO
HEATEX.
BY-PASS
AUTO
HEATEX.
AUTO
The above display indicates that the unit is operating in non-auto­matic, bypass ventilation mode.
The above display indicates current operation with a gentle fan speed.
Operation lamp
Operation lamp
Delay time
This setting is used to deter­mine how long will elapse after the start of operation of the external device until the Lossnay unit begins to oper­ate.
Interlocked mode
This setting is used to deter­mine the way in which the Lossnay will respond to start­ing and stopping of Interlocked to an external device such as an air conditioner, etc.
*: Note that the delay time will
be invalidated in situations where a setting of [3] has been selected for the Operation mode or when the Lossnay unit is inter­locked with a building-man­agement system.
Each time the Delay Start button is pressed, the delay time will change in accordance with the repeating sequence
(minutes)
0 10 20 30 40 50 60
When the button is released before 5 seconds have elapsed, the display will turn off and the current delay time will be selected. Note that a delay time of 0 minutes is set before shipment from the manufacturing plant.
1. Press and hold the Function selector button for at least 5 seconds to display the interlock setting. Note that this is set to [1] before ship­ment from the manufacturing plant.
2. Press the Function selector button to change the setting in the repeating sequence
2 3 4 1
When the button is released before 5 seconds have elapsed, the dis­play will turn off and the current setting will be selected.
Setting
Relevant button
Relevant display items
Sequence
The above display indicates a delay time of 30 minutes.
The above indicates a setting of [2].
SETTING MIN.DELAYED
SETTING
SETTING
INTRELOCKED
INTRELOCKED
Delay Start button
DELAY START
Function selector button
65
Mode of Use (cont.)
Interlocked Operation mode types and actions
Display number
1
2
3
4
Interlocked
Operation mode
ON/OFF Interlocking:
Subsequent opera-tion
with the remote controller
possible (factory setting)
ON Interlocking
OFF Interlocking
ON/OFF
Interlocking:
External inputs
have priority
Action (of the external unit)
When the
external device
begins to operate, the Lossnay unit will also begin to operate; when the external air conditioner stops operating, the Lossnay unit will also stop operating.
When the external device begins to operate, the Lossnay unit will also begin to operate; stopping of the Lossnay unit must be per­formed using the remote controller.
When the external device stops operating, the Lossnay unit will also stop operating; starting of the Lossnay unit must be performed using the remote controller.
Same as for setting 1 above; however, it is not possible to stop the Lossnay unit using the remote controller while the external device is operating.
Action
(of the building-management system)
The Lossnay unit toggles between ON and OFF conditions in response to signals (or puls­es) which are input from a building-manage­ment system or the like.
The Lossnay unit begins to operate in response to a signal (or pulse) which is input from a building-management system or the like; stopping of the Lossnay unit must be per­formed using the remote controller.
The Lossnay unit stops operating in response to a signal (or pulse) which is input from a building-management system or the like; start­ing of the Lossnay unit must be performed using the remote controller.
Same as for setting 1 above.
13.3 Care and Upkeep
AAccttiioonnss rreeqquuiirreedd wwhheenn tthhee FFiilltteerr CClleeaanniinngg ddiissppllaayy bbeeggiinnss ttoo ffllaasshh::
Filter reset
i.e., clearing the total Lossnay-unit operating time
Cleaning of the Lossnay unit's filter
Care of the remote controller
Relevant button
Perform cleaning of the air filter and the Lossnay core in accordance with the instructions in the user's manual which was provided with the Lossnay unit.
To remove dirt from the remote controller's display window, wipe with a cloth to which detergent has been applied, and then wipe with a dry cloth to remove any remaining detergent.
Paint thinner, alcohol, benzene, gasoline, kerosene, spray cleaner, cleaning alkali, etc.
Relevant display items
Sequence
Press the [Filter] button twice in immediate succession and con­firm that the Filter display turns off.
13.4 After-Sales Service
If any of the following inspection numbers should be displayed on the remote controller, please contact the dealer from where this product was purchased for more information.
After-sales servicing of the remote controller unit should be ordered from the retail outlet from where this product was pur­chased.
FILTER
(Press twice)
FILTER
66
Fan Speed Adjustment button
13.5 Component Names and External Dimensions
13.6 Installation Dimensions
Typical System Setup
<Independent operation of the Lossnay unit:>
• When two individual remote controllers have been installed, the most recent control signals will be given priority.
<Interlocked operation with an air conditioners, etc.:>
Lossnay
Lossnay
Remote
Controller(s)
Power supply
Lossnay
A maximum of up to 15 individual Lossnay units may be connected.
Power supply
Remote controller(s)
Power supply
Indoor
unit
Power supply
Mounting holes (x 2)
Display section
Function Selector button
ON/OFF button
Cover
Filter Reset button
Connection terminals
Operation lamp
Delay start
Accessory parts
Screws ........... (x 2) Units: mm
1. Wiring
(1) Perform insertion of a single-unit switch box (without a cover). (2) Lay the wiring duct as far as the switch box. (3) Connect the signal wires from the Lossnay unit to the switch box.
(Note that 2-core telephone cable should be used; furthermore, this cable should be of PVC insulated PVC jacketed and either between
ø0.65 and ø1.2, or between 0.3 mm
2
and 1.25 mm2in cross section.
(4) Use standard putty to create a secure seal so as to prevent frosting
due to the intake of atmospheric air.
Note:
Confirm that the Lossnay unit's power supply is not turned on before con­necting its signal wire to the switch box.
54 44
10
1.5
6
10
20
16 16
40
83.5
102
50
2. Cover removal
To remove the cover, insert the tip of a flat-head screwdriver into the notch and turn.
Note:
Take care during removal of the cover to avoid any damage being caused.
Wiring duct (of 15 to 25-mm nominal diameter)
Lock nut
Signal wires
Bushing
Putty (commercially available)
Units: mm
Switch box
Cover
5. Switching of function selection
(1) Setting for filter maintenance
When Lossnay unit has operated for the time set as the cumula­tive-operation time, the Filter display will begin to flash indicating the cleaning of the filter is required. This setting time should be selected in accordance with the degree of contamination of the air in the unit's installation location. To perform an actual setting, press and hold the FILTER button for at least five seconds to display the setting value and to turn on the Filter display.
Then, press the Filter button to change the setting value in the repeating sequence (factory setting)
3000 4500 OFF 1500
When the button is released before 5 seconds have elapsed, the display will turn off and the current replacement time will be selected. Note that this value is set to [3000] before shipment from the manufacturing plant.
(2) Setting for delayed interlocked operation
The delay-time setting is used to determine the length of the period that will elapse after the start of operation of the external devices until the Lossnay unit begins to operate. To perform an actual setting, press and hold the DELAY START button for at least five seconds while the Lossnay unit is currently stopped to display the setting value as shown in the diagram.
Each time the DELAY START button is pressed, the
delay time will change in accordance with the repeating sequence (factory setting)
0→10 →20 →30 →40 →50 →60 minutes.
(0:original setting at factory shipment) When the button is released before 5 seconds have elapsed, the display will turn off and the current delay time will be selected. Note that a delay time of 0 minutes is set before shipment from the manufacturing plant. Note also that when OFF Interlock mode has been selected, this setting value will be invalidated.
(3) Setting for interlocked mode
The Interlocked-mode setting is used to determine the way in which the Lossnay unit will respond to starting and stopping of interlocked external device such as an air conditioner, etc. To
perform an actual setting, press and hold the button for at least five seconds while the Lossnay unit is currently stopped to display the setting value as shown in the diagram.
Press the switch to change the setting in the repeating
sequence (factory setting) 1 →2 →3 →4
(1:original setting at factory shipment) When the button is released before 5 seconds have elapsed, the display will turn off and the current setting will be selected. Note that this value is set to [1] before ship­ment from the manufacturing plant.
DELAY START
FILTER
67
1
2
3
4
3. Connection of wiring and remote-controller mount­ing:
(1) Fully insert the (non-polar) signal wiring into the connection terminals. (2) Gently tug on the wiring to confirm that it is being securely gripped. (3) Mount the remote controller on the switch box using the two screws
provided as accessory parts.
Press this button to release.
Interlock terminals
Insert the signal wire.
Remote controller
Screws (accessory parts)
Switch box
4. Mounting of the cover
To mount the cover, secure the two hooks at its upper edge and press on its lower section until it is heard to snap into place.
Remote controller
Cover
Hooks
SETTING
3000
FILTER
SETTING
1
INTERLOCKED
SETTING
0
MIN.DELAYED
Interlocked
Operation mode
ON/OFF
Interlocking
ON
Interlocking
OFF
Interlocking
ON/OFF
Interlocking (with external­signal priority)
Action
Starting and stopping of the Lossnay unit will be performed from exter­nal device -- specifically, when the external device begins to operate, the Lossnay unit will also begin to operate; when the external device stops operating, the Lossnay unit will also stop operating. Note that subsequent operation using the remote controller will be possible.
Starting of the Lossnay unit will be performed from external device -- specifically, when the external device begins to operate, the Lossnay unit will also begin to operate. Stopping of the Lossnay unit must be performed using the remote controller.
Stopping of the Lossnay unit will be performed from external device -- specifically, when the external device stops operating, the Lossnay unit will also stop operating. Starting of the Lossnay unit must be performed using the remote controller.
Starting and stopping of the Lossnay unit will be performed from external device -- specifically, when the external device begins to operate, the Lossnay unit will also begin to operate; when the external device stops operating, the Lossnay unit will also stop operating. However, it is not possible to stop the Lossnay unit using the remote controller while the external device is operating.
68
Inspection
number
0900
6608
4000
5101
5102
3602
BY-PASS
AUTO
HEATEX.
Sequence
Initiate the supply of power to the Lossnay unit. (The [HO] display will flash for approximately 40 seconds)
Press the ON/OFF button. The Operation lamp will turn on and the Lossnay unit will begin to operate.
Press the Function selector button: Each time it is pressed, the corre­sponding display will change in accordance with the sequence [HEAT EX.] (non-automatic) [BY-PASS] (non-automatic) [AUTO].
Press the Fan Speed Adjustment button to toggle between Low and High.
Press the Operation switch. The Operation lamp will turn off and the Lossnay unit will stop operating.
13.7 Trial Operation
After installation has been completed, it is of the utmost impor­tance that trial operation of the Lossnay unit and any external device such as an air conditioner is carried out.
When power supply is supplied to the remote controller the [HO] display will flash (for approximately 40 seconds); following this, the system will switch to operation-start mode.
Relevant
button
1
2
3
4
5
Relevant display
items
Note that when the Ventilation Mode selector button is pressed, it will take up to 40 seconds before the operation of the damper changes accordingly.
If an inspection number should be flashed, refer to the following table and take the required action.
Cause
The SW2 trial-operation switch from the Lossnay unit's controll box is On.
If two or more Lossnay units are currently being used together, this number will indicate that the correct set­ting has not been performed using the units' Main/Sub switches.
If two remote controllers are currently being used together, this number may indicate that one of these controllers is not connected.
If two remote controllers are used together, this num­ber may indicate that both of these controllers are not set automatically when the power supply is turned on.
Multi-core cable has been used in place of a number of signal wires.
A circuit abnormality has occurred in the Lossnay unit.
A breakdown has occurred in the Lossnay thermo (OA side).
A breakdown has occurred in the Lossnay thermo (RA side).
A breakdown has occurred in the damper motor.
Required action
Turn off the trial-operation switch. (refer to page 62)
Turn off the power supply and use the Main/Sub switches to specify one Lossnay unit as the Main and the others as Sub. Following this, turn the supply of power back on. Note that all Lossnay units are specified as Main before ship­ment from the manufacturing plant. (refer to page 57)
Turn off the power supply, connect the remote con­troller, and turn the power supply back on. (refer to page 67)
Turn off the power supply and turn the power supply back on.
Switch back to the use of standard wiring and install each signal wire separately.
Turn off the supply of power and contact the retail out­let from where this product was purchased for further instructions.
69
14. Lossnay M-NET Remote Controller (PZ-52SF-E)
14.1 Operation
CENTRAL
HEAT EX. BY-PASS AUTO
CHECK
INTERLOCKED
FILTER
ON/OFF
NOT
AVAILABLE
FILTER
[CENTRAL] Display
Displayed when remote operation is prohibited by a centralised control unit, etc.
Power Display
Displayed while Lossnay remote controller is powered on.
[FILTER] Display
Displayed when the accumulated operating time reaches the time set for air filter maintenance.
[CHECK] Display
Displayed together with the address of the malfunctioning unit (3 digits) and the error code (4 digits). (For detail, refer to the “11.Troubleshooting”)
Operation lamp
On during operation. Flashes when a malfunction occurs.
Ventilation Modes
Indicates the ventilation mode.
Heat recovery (Heat exchange.)
By-pass
Automatic (Heat ex./By-pass)
[NOT AVAILABLE] Display
Displayed when the Lossnay unit cannot perform the function for the button that has been pressed. This display flashes concurrently with the display of the unavailable function.
[ON/OFF] Button
Switches between run and stop. The lamp on the button stays lit during operation.
[Fan Speed Adjustment] Button*
Used to select the fan speed of either "Low" or "High".
[FILTER] Button
Press two times to reset the filter sign display.
HEAT EX.
BY-PASS
AUTO
Low High
[INTERLOCKED] Display
Displayed when the Lossnay unit starts due to interlocked indoor unit or external signal.
[Fan speed] Display
Displays the selected fan speed.
[Function Selector] Button
Used to select the ventilation mode from among heat recovery (Heat exchange), by­pass or automatic.
*Note:
If this button is pressed when trying to switch the fan speed of a Lossnay unit not equipped with the fan speed adjustment, the fan speed display and the “NOT AVAILABLE” display flash and the fan speed does not change.
This remote controller can not be used on Lossnay units set for interlocked operation with Mr. Slim units.
70
14.2
Installing the Lossnay M-NET Remote Controller
14.2.1 Mount the switch box.
1. Install the switch box (purchased separately)as explained below.
Note:
Be sure to install the switch box with the clearance shown in the illustration at the left. (Check the space between the unit and any projections, such as a stud.)
Leave a space of 120 mm or more below the Lossnay M-NET remote controller so that a screwdriver can be used.
2. Purchase the thin copper wiring conduit, lock nuts and bushings separately.
1. Pull out approximately 80 mm of cable from the wall and remove the insulation
at the end.
2. Use putty to seal the cable hole in order to prevent insects from damaging the
wiring and to prevent condensation on the Lossnay M-NET remote controller circuit board. If this hole is not sealed well, the Lossnay M-NET remote con­troller circuit board may be damaged.
3. Connect the cable to the terminal board at the bottom rear of the Lossnay M-
NET remote controller unit.
The cable does not have polarity.
When connecting stranded cable, hold down the tab on the terminal board
while inserting the cable.
The cable connects to the main terminal board when it is inserted into the bot-
tom terminal.
When disconnecting the cable, hold down the tab while pulling out the cable.
After inserting the cable, slightly tug on it to check that it does not easily dis-
connect. If the cable is not securely connected, a short-circuit or malfunction may occur.
4. Remove the Lossnay M-NET remote controller cover using a standard screw-
driver. Attach the Lossnay M-NET remote controller unit to the switch box using the two enclosed cross-recessed pan head screws. Use a standard screwdriver with a blade that is 4 mm or wider to remove the cover.
CAUTION:
Forcing off the cover using a screwdriver that is less than 4 mm wide may
result in damage to the equipment or injuries.
Attach the Lossnay M-NET remote controller to a level surface. Do not over-
tighten the screws. Tight screws could damage or deform the case.
Switch box
Outline of Lossnay remote controller
Projecting object such as a stud
40 mm or more
11 10
80
Leading wire
Insula­tion
Sheath
Wall
Cable
Seal with putty
One switch box (
with cover
)
Wiring plpe
Units : mm
Button: Press here.
Insert the cable.
Lossnay M-NET remote controller cover
14.2.2 Install the Lossnay M-NET Remote Controller.
71
5. Set the Lossnay M-NET remote controller address. Set the Lossnay M-NET remote controller address using the rotary switches SW1 and SW2 on the front of the Lossnay M-NET remote controller.
Setting range: 101 to 200
Rotary switch SW1 indicates the tens column and SW2 indicates the ones
column. In addition, 100 is automatically added to the setting as shown below.
The address is set to 01 when the Lossnay M-NET remote controller is shipped from the manufacturer.
CAUTION:
The address must be set if the Lossnay M-NET remote controller is to be used as a part of a multi-unit system. Set the address according to its position in the system. In addition, refer to page 59 for more information concering the setting of the addresses.
6. After setting the Lossnay M-NET remote controller address, attach the Lossnay M-NET remote controller cover. When attaching the Lossnay M-NET remote controller cover, set the top of the cover onto the two top hooks and then push in the at the bottom of the cover until it snaps into place. If the bottom of the cover is attached first, the top of the cover cannot be attached. Forcefully pushing in the top of the cover to attach it may break the hooks.
0
9
8
7
6
5
4
3
2
1
SW1
0
9
8
7
6
5
4
3
2
1
SW2
Rotary switches
Rotary switch setting 01 – 99 00
Lossnay M-NET remote controller address 101 – 199 200
72
14.3 Registering the Lossnay Unit with the Lossnay M-NET Remote Controller
Initial registration mode operation
A Lossnay unit must be registered with the Lossnay M-NET remote controller in a group arrangement. Register a Lossnay unit using the initial registration mode as shown below. In addition, the initial registration mode can be used to search for a Lossnay unit registered to the group or to delete a registration.
Setting Procedure
1
Turn off the unit. (Perform the following operation after HO flashes on the display.)
2
Hold down both and for more than 2 seconds. This starts the initial registration mode and the set Lossnay M-NET remote controller address flashes on the display.
FILTER
CENTRAL
HEAT EX. BY-PASS AUTO
CHECK
INTERLOCKED
FILTER
ON/OFF
NOT
AVAILABLE
FILTER
3 52
17
4
6
3
Press to select the address of the Lossnay unit that you wish to register with this Lossnay M-NET remote controller.
After the button is pressed once, the Lossnay M-NET remote controller address and then the Lossnay unit address is displayed. Afterwards, each press of the button increase the Lossnay unit address by 1 as shown below. Holding down the button changes the address more quickly.
[
101
][
– – –
][
001
][
002
]
. . .
[
098
][
099
]
(
Set Lossnay M-NET remote controller address
)
Flashes
4
When the address of the Lossnay unit that you wish to register is displayed, press to begin registering. If the registration is completed correctly, the display appears as shown below.
If the registration is not completed correctly, “” flashes in the display. Check that the selected Lossnay unit address and the wiring are correct. In the case of LGH-150/200RX
3-E, there are 2 circuit boards installed in each unit. Because of this, set a separate address
for each of the circuit boards, and register both of those addresses at the remote control.
5
After registering, hold down both and for more than 2 seconds to end the initial registration mode and the nor­mal display appears.
FILTER
The Lossnay unit type, LC, is displayed.
73
Confirmation of registered address
6
To display the addresses of the Lossnay units that are registered with this Lossnay M-NET remote controller. Each press of in step 2 or 4 displays the address of a registered Lossnay unit and its type, LC”.
If no Lossnay unit is registered, --- appears in the address display and no type is displayed.
Address deletion
7
To delete the address of a Lossnay unit registered with this Lossnay M-NET remote controller. Hold down [ON/OFF] twice for 2 seconds each time in either step 4 or after the registration is completed to delete the regis­tration of the Lossnay unit that is currently displayed.
FILTER
When the display appears as shown above, hold down [ON/OFF] for 2 seconds each time.
If the registration is deleted correctly, “ – – ” appears in the display. If the registration is not deleted correctly, “” flashes in the display. Check that the select-
ed Lossnay unit addresses and the wiring are correct.
Note:
In the case of LGH-15 to 100RX
3-E, up to 16 Lossnay units can be registered. In the case of LGH-150/200RX3
-E, up to 8
units can be registered.
If the registration cannot be completed or deleted correctly, either the set address or the wiring of the Lossnay unit whose registration you wish to add or delete may be incorrect. Check the wiring and the address that is set.
1263
GROUP SELECT
MODE
TEST RUN
AIR
DIRECTION
FAN SPEED
ON/OFF
0
87
54
CLOCK/
PATTERN
PROHIBITION
TIMER
MODE
TEMP.
REMOTE
9
INS.
DEL.
SCREEN
BACK
ENTER
VENTILATION
RESET
8 Group select button
3 Fan speed button
2 Operation mode button
4Ventilation setting button
6Timer mode button
7Reset button
1 ON/OFF button
5Remote operation
prohibit button
Operation panel
74
15. Appendix
15.1 Centralised Controller (MJ-103MTRA)
15.1.1 Operation setting
There are two methods for the operation, performing the operation classified by groups or collective operation.
Group operation setting
Current time displayGroup number display
Display
Operation condition display
Remote operation prohibition/permission display
Operation mode display
Fan speed display
Ventilatior operationdisplay
External input condition display
Filter sign display
Timer operation display Function area
G01
1F1ROOM
OPERATION SETTING
(HEAT RECOVERY)
ON
FAN
REMOTE CONTROL PROHIBIT
MON. PROH. COL. M MR
TIMER
ON
FILTER
PROHI­BITED
MJ-103MTRA
CENTRAL CONTROLLER
ON/OFF
Display
Operation panel
G01
1F1ROOM
OPERATION SETTING
(HEAT RECOVERY)
ON
FAN
REMOTE CONTROL PROHIBIT
MON. PROH. COL. M MR
TIMER
ON
FILTER
PROHI­BITED
1263
GROUP SELECT
MODE
TEST RUN
AIR
DIRECTION
FAN SPEED
ON/OFF
0
87
54
CLOCK/
PATTERN
PROHIBITION
TIMER MODE
TEMP.
REMOTE
9
INS.
DEL.
SCREEN
BACK
ENTER
VENTILATION
RESET
Display
Operation status display [ON] [OFF]
* When there is an interlocked Lossnay
unit, turning this switch ON starts opera­tion in a [High] fan speed state.
On the group composed of independent Lossnay units, operation mode is selected in a sequence that goes from HEAT RECOVERY, AUTO, BYPASS and back to HEAT RECOVERY.
→→
AUTO BYPASS
Fan speed display
→→
* In the case of a group composed only of
Lossnay units this does not display.
Ventilation volume setting display
→→ →
PROHIBIT : Local remote control specified on
the prohibit setting screen is not possible.
PERMIT : Local remote control is possible.
Timer operation display
[ON] [OFF]
Filter display
[ FFiilltteerr ] → No display
Group number display
This switch displays 1 to 50 group numbers. The switch can also display group names.
(Ventilation off)
(High)
(Low)
FAN
FAN
(HEAT RECOVERY)
Function
The ON/OFF condition of the displayed group is switched.
Used to the type of the operation mode selection.
The Fan speed can be selected as high or low.
The operation mode of the interlocked Lossnay unit can be performed. *
Where there is no interlocked Lossnay unit, the operation of this button is invalid.
Used to prohibit for the local remote control.
The timer operation can be performed according to a previously set operation pattern.
The filter sign display reset is performed. The reset processing is completed by pressing this button two times.
The display group is changed.
No.
1
2
3
4
5
6
7
8
75
Name of switches
ON/OFF button
Operation mode button
Fan speed button
Ventilation setting button
Remote operation
prohibit button
Timer more button
Reset button
Group select button
76
2. Rotary switch setting
The address of this controller is set by the rotary switch.
When this controller is shipped from the factory, the address is set to 000”.
Setting range: 000, 201-250
(Always set the address to 000 when K-transmission converter is being controlled.)
15.1.2 Initial setting
DIP switch and rotary switch setting
Remove the cover from the controller and perform the DIP switch and rotary switch setting.
Rotary switches
DIP switch
Cover
1
Remove the cover screw.
Note:
When this controller is shipped from the factory, the screw is contained in the same package.
2
Insert a standard screwdriver into the slot and twist it to remove the cover from the upper case.
1. DIP switch setting
The functions of this controller are set according to the DIP switch settings.
Each switch is set to the OFF and ON positions as shown below.
The functions of this controller are selected by DIP switch.
The DIP switches are set to OFF when the controller is shipped from the factory.
DIP switch
OFF ON
1 2 3 4 5 6 7 8
ON
OFF: User operation mode
OFF: Master system controller
OFF: No K-transmission converter installed
OFF: Operation prohibit setting valid
ON: Initial setting mode
ON: Slave system controller
ON: K-transmission converter installed
ON: Operation prohibit setting invalid
Reserved for future use (Leave this switch set to OFF
)
External input changeover
The range of a controller which the operation is prohibited
OFF: Both of the system controller and the local remote controller ONJ: Only the local remote controller
2
1
0
9
8
7
6
5
4
3
100digit
2
1
0
9
8
7
6
5
4
3
10digit
2
1
0
9
8
7
6
5
4
3
1digit
(
Example: Address setting: 000
)
77
GROUP SETTING
ADDRESS
UNIT
001 002
REMOTE CONTROLLER
101
SYSTEM CONTROLLER
G01
15.1.3 Group configuration setting
Registration can be made for the indoor units, local remote controllers and slave system controllers in the same group.
Registration can also be performed for the group that is composed of only Lossnay.
Example of a group configuration
Supply the power from the power supply unit (PAC-SC34KUA) through the M-NET transmission cable.
Perform the following procedures to set the group configuration because the interlocked operation setting will not be per-
formed for the group configuration settings that have not been set.
Outdoor unit
Indoor unit
Local remote controller
Lossnay unit
M-NET Transmission cable
006005
051
004002 003001
103
105
Group 2
101
Group 1
Group 3
Independent Lossnay group
Air conditioner group
1 GROUP SETTING
MENU
1
When the power is supplied to the controller, the screen shown on the left is displayed.
2
Press the button to select 1 GROUP SETTING”.
1
GROUP SETTING
ADDRESS UNIT
REMOTE CONTROLLER
SYSTEM CONTROLLER
G01
The configuration setting screen is displayed.
3
Press the button to display the group number to be set.
4
Press the button to move the cursor to the address
display position to be set.
5
Use the numeric keypad to set the address of the indoor unit, local remote controller, and slave system controller in the display group number.
Operation example
For an indoor unit with an address of 012.
1) Input “0”
2) Input “1”
3) Input “2”
4) Press the button. 012 * It is also possible to enter “1” “2”.
When the input is incorrect
Press the button and continue to input the data. After pressing the
button, move the cursor to the addresses to be deleted and press the
button to delete these addresses.
RESET
DEL.
012
01
0
GROUP SELECT
Note:
Do not set Lossnay units with the intention of interlocked operation, such as Lossnay, on this group setting menu.
Even if the addresses are input in a non-sequential order, they will be switched to sequential order starting with the lowest
address.
The independent Lossnay unit cannot be set to the indoor unit group and it cannot be set as an interlocked Lossnay unit.
78
This is the procedure for registering all units and controllers in the displayed group number.
6
Repeat operation 3 to 5 to set all the groups controlled by this controller.
7
When all settings have been completed, press the button.
Note:
Be sure to set the local remote controller address when there is a local remote controller in the system. The local remote controller will not operate if the address setting is not performed.
BACK SCREEN
GROUP SETTING
ADDRESS
UNIT
005 006
REMOTE CONTROLLER
SYSTEM CONTROLLER
G03
PLEASE WAIT
8
The initial setting screen is displayed. Registration processing for the group configuration information and initial set up processing for each unit and each controller is executed when DIP switch No. 1 is set to OFF. (This process takes approximately five minutes.)
Note:
If DIP switch No. 1 is set to ON at this time, the initial setting menu screen is displayed without the initial setting screen.
9
The user operation menu is displayed. Once the group configuration settings are completed, user operation can be performed. Refer to Section 14.4 Interlocked Operation Setting when per­forming interlock operation settings.
Additions:
Deleting all group configuration data.
Display “G00on the group configuration setting screen and press the button two times consecutively to delete all group configuration data and all interlocked operation data.
Note:
Group registration cannot be made when this unit is set to the slave system controller by the DIP switch No. 2. However, con-
firmation of the contents of the group registration is possible.
To change the group configuration setting, set DIP switch No. 1 in the cover to ON. This will bring up the initial setting menu
screen. From that screen, select 1 GROUP SETTING on the setting menu screen. Wait for the screen to appear and then change the setting.
DEL.
79
15.1.4 Interlocked operation setting
This is the procedure for registering the interlocked operation of an Lossnay unit with a single or multiple indoor units. All indoor units to be interlocked with an Lossnay unit for operation should be registered as group before- hand.
Example of an interlocked group configuration
Outdoor unit
Indoor unit
Local remote controller
Lossnay unit
M-NET Transmission cable
005
051
004
002
003
001
Duct
103101
1 OPERATION MONITOR 2 OPERATION SETTING 3 SCHEDULE SETTING 4 MALFUNCTION
MONITOR
5 CURRENT TIME
SETTING
WED 15:29MENU
1
Set DIP switch No. 1 in the cover to ON.
Note:
Always uses the DIP switch No. 1 to change the setting. This operation will be invalid if performed on another screen.
1 GROUP SETTING 2 INTERLOCKED
SETTING
3 REFRIGERANT
MONITOR
4 MALFUNCTION LOG
MONITOR
5 USER SETTING
MENU
2
The initial menu screen is displayed.
3
Press the button to select 2 INTERLOCKED SETTING”.
2
INTERLOCKED SETTING
UNIT ADDRESS
INTERLOCKED UNIT
ADDRESS 005
4
The interlocked setting screen is displayed. The minimum address of the interlocked processing unit that can be set to interlocked operation with an indoor unit is displayed in INTERLOCKED UNIT ADDRESS. The cursor is displayed in the unit address display position.
5
Press the button to display the address number of the interlocked Lossnay unit that the setting will be performed on.
GROUP SELECT
80
INTERLOCKED SETTING
UNIT ADDRESS
INTERLOCKED UNIT
ADDRESS 005
6
Use the numeric keypad to set the address of the indoor unit to operate with the displayed Lossnay unit.
Operation example
For an indoor unit with an address of 012.
1) Input “0”.
2) Input “1”.
3) Input “2”.
4) Press the button. 012 * It is also possible to enter “1” “2”.
When the input is incorrect
Press the button and continue to input the data. After pressing the
button, move the cursor to the addresses to be deleted and press the
button to delete these addresses.
RESET
DEL.
012010
INTERLOCKED SETTING
UNIT ADDRESS
INTERLOCKED UNIT
ADDRESS 005
001 002 003 004
7
Set the indoor units to operate with the displayed interlocked Lossnay unit.
8
Repeat operation 5 to 7 to set the indoor units in interlocked operation con­trolled by this controller.
9
When all settings are completed, press the button.
BACK SCREEN
1 GROUP SETTING 2 INTERLOCKED
SETTING
3 REFRIGERANT
MONITOR
4 MALFUNCTION
MONITOR
5 USER SETTING
MENU
Initial setting screen is displayed. This ends the interlocked operation setting. Return to where user operations are performed to set DIP switch No. 1 to OFF. After the initial settings processing has been completed, the initial setting screen will be displayed.
Note:
The interlocked operation settings cannot be adjusted when this unit is set to being a slave system controller by the DIP switch No. 2. However, monitoring of the contents of the interlocked operation settings is possible.
Please refer to the related documentation for details about the centralised controller.
81
15.2 Remote Controllers for Mr. Slim indoor unit
A-control remote controller (PAR-27AA)
Without Lossnay interlock switches and indicators.
15.2.1 Method for operating Lossnay with A-control remote con­troller (when interlocked with Mr. Slim
When operating Lossnay separately
Press the ON/OFF button A.
Press the Selecting operation button B. The display will show .
Use when you only want ventilation and there is no need for heating or cooling operation.
The does not display when the unit is not connected for interlocked operation with a ventilation unit.
When changing Lossnay fan speed
Press the “Ventilation button C.
ON/OFF
STAND BY DEFROST
INDOOR UNIT ADDRESS NO.
ERROR CODE OA UNIT ADDRESS NO.
CENTRALLY CONTROLLED
CLOCK
ON OFF
˚C
1Hr.
NOT AVAILABLE
˚C
CHECK MODE
FILTER
CHECK
TEST RUN
ON OFFCLOCK
FILTER
CHECK
TEST RUN
REMOTE CONTROLLER
TEMP. TIMER SET
A
B
C
[Ventilation] Display Displayed during ventilation (Lossnay) operation.
Lossnay fan speed
“Low”
Lossnay fan speed
“High”
The setting changes each time you press the button.
When running interlocked ventilation operation
Press the ON/OFF button A.
If there is a ventilation unit connected for interlocked operation, the ventilation unit will start operating automatically.
Press the Ventilation button C.
The Lossnay fan speed can be set to High or Low.
82
15.3.1 Method for Operating Lossnay with Network remote Controller (When Interlocked with City Multi Indoor Unit)
Operation method is same as A-control remote controller. Refer to page 81.
15.3.2 Initial registration mode
This is the procedure for registering the address of the indoor unit with the remote controller.
1
Stop the remote controller by pressing the [ON/OFF] button.
If not indoor unit is registered, the “HO” display appears in the room temperature display. In this condition, registration can be performed as follows.
2
Display “INDOOR UNIT ADDRESS NO.”
Press and hold down both the [FILTER] button (shown as A) and the “Louver” button (shown as B) at the same time for 2 seconds. The following display will appear.
15.3 Network Remote Controller (PAR-F25MA)
INDOOR UNIT ADDRESS NO.
INDOOR UNIT ADDRESS NO.
OA UNIT ADDRESS NO.
INDOOR UNIT ADDRESS NO.
OA UNIT ADDRESS NO.
Both INDOOR UNIT ADDRESS NO. and OA UNIT ADDRESS NO. will appear simultaneously.
ON/OFF
STAND BY DEFROST
INDOOR UNIT ADDRESS NO.
ERROR CODE OA UNIT ADDRESS NO.
CENTRALLY CONTROLLED
CLOCK
ON OFF
˚C
1Hr.
NOT AVAILABLE
˚C
CHECK MODE
FILTER
CHECK
TEST RUN
ON OFFCLOCK
FILTER
CHECK
TEST RUN
REMOTE CONTROLLER
NETWORK
PAR-F25MA
TEMP. TIMER SET
F
E
CH
B
D
A
G
Use the and [TEMP] buttons (shown as C) to select the address of the indoor unit. Set it to the address of the indoor unit to be interlocked.
Use the and [TIMER SET] buttons (shown as H) to select the address of the Lossnay unit to be regis- tered.
15.3.3 Interlocked registration
3
Display the OA UNIT ADDRESS NO.
Press the Operation mode button (shown as G) and the following display will appear. Press once again to return to INDOOR UNIT ADDRESS NO. shown in Step 2.
83
4
To register the interlocked operation of the Lossnay unit and the indoor unit.
Use the [TEST RUN] buttons (shown as D) to register the relationship of the interlock between the Lossnay indicated in
OA UNIT ADDRESS NO. and the indoor unit indicated in INDOOR UNIT ADDRESS NO.”
5
To return to the normal operation mode.
Press and hold down both the [FILTER] button (shown as A) and the Louver button (shown as B) at the same time.
This returns the unit to the normal operation mode. (OFF)
Note:
Be sure to set the indoor unit to the lowest address number in a group followed by the Lossnay unit. If this is not performed, the Lossnay unit will not operate.
If there are multiple indoor units to be interlocked with the Lossnay unit, perform Steps 3 and 4 above for each of them.
15.3.4 Searching for interlocked registered units
6
Display the indoor unit address No. at OA UNIT ADDRESS NO.
Press the Operation mode button (shown as G) and the following display will appear.
Press once again to return to INDOOR UNIT ADDRESS NO. shown in Step 2.
7
Use the and [TIMER SET] buttons (shown as H) to select the address of the indoor unit to be registered. Select the indoor unit address number to be confirmed.
8
Press the Timer/continuous button (shown as E). The display alternates between the two displays shown here.
INDOOR UNIT ADDRESS NO.
OA UNIT ADDRESS NO.
INDOOR UNIT ADDRESS NO.
OA UNIT ADDRESS NO.
(Alternation)
When registration has been completed suc­cessfully, the display alternates between the two displays shown in the figure.
If there is an error in the registration, “” will flash. This indicates the number of the unit.
INDOOR UNIT ADDRESS NO.
OA UNIT ADDRESS NO.
INDOOR UNIT ADDRESS NO.
OA UNIT ADDRESS NO.
Address of the registered unit
INDOOR UNIT ADDRESS NO.
INDOOR UNIT ADDRESS NO.
OA UNIT ADDRESS NO.
(Alternation)
OA UNIT ADDRESS NO.
84
9
Press the Timer/continuous button (shown as E) once again. The display will now alternate between the registered unit and the address of the next registered unit. (The way of display is the same as in step 8.)
0
To return to the normal operation mode. Press and hold down both the [FILTER] button (shown as A) and the Louver button (shown as B) at the same time. This returns the unit to the normal operation mode (OFF).
15.3.5 To delete linked unit entries
A
From the initial registration mode display, perform an address search for linked units. Display the addresses of the Lossnay units to be deleted. Press the Time conversion button (shown as F) twice to delete these units which are displayed according to their address number with the indoor unit.
When the above is displayed, press the Time conversion button (shown as F) twice.
If the transmission is faulty, the properties will flash as “”. Check the wiring and the address definitions and then do the above operation again.
B
To return to the normal operation mode. Press and hold down both the [FILTER] button (shown as A) and the Louver button (shown as B) at the same time. This returns the unit to the normal operation mode (OFF).
INDOOR UNIT ADDRESS NO.
OA UNIT ADDRESS NO.
INDOOR UNIT ADDRESS NO.
OA UNIT ADDRESS NO.
(Alternation)
Address of another registered unit
Address of the registered unit
INDOOR UNIT ADDRESS NO.
INDOOR UNIT ADDRESS NO.
OA UNIT ADDRESS NO.
(Alternation)
OA UNIT ADDRESS NO.
Address of the
INDOOR UNIT ADDRESS NO.
OA UNIT ADDRESS NO.
registered unit
(Alternation)
INDOOR UNIT ADDRESS NO.
OA UNIT ADDRESS NO.
MEMO
MEMO
01.03<MEE>
Loading...