Mitsubishi LGH-15...200RX3 TECHNICAL MANUAL

TECHNICAL MANUAL (CONTROLS)
Models Lossnay Unit
LGH-15RX3-E LGH-25RX3-E LGH-35RX3-E LGH-50RX3-E LGH-80RX3-E LGH-100RX3-E LGH-150RX3-E LGH-200RX3-E
■ Lossnay Remote Controller
PZ-41SLB-E PZ-52SF-E
CONTENTS
1. Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2. Applicable Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
3. Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
4. System Features and Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
5. Examples of Applications Using External Control Input Terminals,
Operation Monitor Output Terminals and Malfunction Monitor Output Terminals . . . . . . . . . . . . . . . . . . . . . . . 21
6. Precautions When Designing Systems of M-NET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
7. Cable Installation of the M-NET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
8. System Designs of M-NET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
9. Automatic Ventilation Switching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
10. Cold Weather Area Operation Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
11. Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
12. Installation method (Model LGH-RX3-E series) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
13. Lossnay Remote Controller (PZ-41SLB-E) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
14. Lossnay M-NET Remote Controller (PZ-52SF-E) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
15. Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
* Centralised Controller (MJ-103MTRA)
(Operation setting, Initial setting, Group configuration setting, Interlocked operation setting) . . . . . . . . . . . . 74
* Remote Controllers for Mr. Slim indoor unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
* Network Remote Controller (PAR-F25MA) (Interlocked registration) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
1
1. Summary
This is a technical manual relating to the controls for implementing the following systems of the commercial-type Lossnay (LGH­RX3-E Series).
Possible System Configurations
(1) When using only the Lossnay remote controller. (2)
Linking Lossnay and City Multi units.
(3)
Linking Mr. Slim (A-control, K-control).
(4)
Lossnay central control systems.
(5)
Linking with external equipment (BMS).
2. Applicable Models
Lossnay (LGH-RX
3-E
)
These models have temperature sensors at RA and OA sides. It can automatically switch to the ventilation mode. (Lossnay/By-pass)
Model
LGH-15RX3-E
LGH-25RX3-E
LGH-35RX3-E
LGH-50RX3-E
Model
LGH-80RX3-E
LGH-100RX3-E
LGH-150RX3-E
LGH-200RX3-E
Lossnay Remote Controller (PZ-41SLB-E
)
Use when operating from 1 to 15 Lossnay units together at the same time. When using M-NET transmission to operate from centralised control, use the PZ-52SF-E. It can start and stop the unit, change fan speed, switch the ventilation mode. It also includes indicators that show errors and when filter maintenance is required. Refer to page 63.
Lossnay M-NET Remote Controller (PZ-52SF-E
)
It can be used in combination with Mitsubishi Electric Air conditioner Network system (MELANS). Refer to page 69. Since this remote controller is supplied the power from the M-NET transmission line, it cannot be linked with Mr. Slim and other such systems that do not use M-NET.
Please refer to the technical documentation for the other systems: City Multi, Mr. Slim and the central controller (MELANS).
2
3. Terminology
Interlocked Lossnay
This is a Lossnay linked to City Multi, or Mr. Slim indoor units. This is a Lossnay that has been set to interlocked group set­ting to receive signals and operate via indoor unit’s remote controller indoor unit Lossnay.
Non-interlocked Lossnay
This is a Lossnay that is not set to interlocked group setting with City Multi nor Mr. Slim indoor units. It operates using direct operating signals from the Lossnay remote controller and/or centralised controller.
Ventilation Mode
This mode controls the Lossnay damper and permits selection of heat recovery (Heat ex.), by-pass or auto modes.
Delayed Operation
The Lossnay that has been set to interlocked group setting with the indoor unit will have its operation delayed for 30 minutes after the operation of the indoor unit. When using PZ-41SLB-E, the time setting that can be set for delayed operation are 10, 20, 30, 40, 50, and 60 minutes.
External Control Input
This is an input signal for operating the Lossnay that has been sent from an external device. It is compatible with 12V-24V DC or uncharged a-contact signal.
Operation Mode
This mode is used for selecting enabling/disabling of the on/off control signal from an external device and for setting inter­locked operation of the external device and the Lossnay. Please Refer to page 22 for details.
ON/OFF interlock: Enables both “ON OFF” and “OFF ON” external signals. ON interlock: Enables “OFF ON” external signal. Disables “ON OFF” external signal. OFF interlock: Enables “ON OFF” external signal. Disables “OFF ON” external signal. External priority: Same as on/off interlock but the OFF signal from the remote controller is ignored when the
external control signal is on.
Setting Pulse Input
When the control signal from the external device outputs a pulse such as the one shown below, pulse input setting is per­formed by the Lossnay. (Optional setting DIP switch 2-2 ON
)
200 ms or more
Operation in Cold Areas
When the outdoor air is less than -10°C, continuous operation of the fan for drawing in supply air is cancelled, and intermit­tent operation is started.
RA (Return Air
)
This is the abbreviation for return air, which is the air drawn in from indoor.
OA (Outdoor Air
)
This is the abbreviation for outdoor air, which is the air drawn in from outdoor.
(
3
Classification
Control
Function
Installation
Maintenance
Item
• Multiple unit operation
• Remote controller operation
• External device operation
• External pulse control
• External monitor signal output
• Supply air fan monitor output
• External control operation mode setting
• Delayed start
• Automatic recovery following power sup­ply interruption (*1)
• Power supply start/stop function
• High/low change input
• Remote/Local control change
• The M-NET air conditioning operation.
• Centralised control by Mitsubishi building air control management system
• Interlocked with Mr. Slim
• Lossnay (heat recovery) ventilation/By­pass ventilation automatic switch
• For cold area operation
• Remote controller 2 wires wiring (non-polar)
• Address setting unnecessary
• Test operation switch
• Filter maintenance display (remote controller display)
• Inspection display (remote controller, control board LED)
• M-NET power supply display (control board LED)
Notes/Cautions
Maximum 15 units with PZ-41SLB-E; 16 units with PZ­52SF-E or other M-NET controller.
Last touch priority
Signal form: 12VDC, 24VDC, uncharged a-contact
Ditto
Uncharged a-contact (external monitor/supply air fan monitor change)
Ditto
ON/OFF , ON, OFF and External priority ON/OFF mode.
Delayed time can be varied only when the PZ-41SLB-E is connected.
Return power automatic return is fixed when the PZ­41SLB-E is connected.
Impossible when the PZ-41SLB-E is connected.
Uncharged a-contact (Part sold separately is necessary)
Uncharged a-contact (Part sold separately is necessary) (Connection is impossible when using PZ-41SLB-E)
Only when M-NET transmission cable is connected
Ditto
Can not use the PZ-41SLB-E
When the PZ-41SLB-E is connected: PVC cable ø 0.65 to 1.2 or strand wire 0.3 mm
2
to 1.25 mm2.
When M-NET is connected: shielded wire or equivalent
1.25 mm
2
to 2.00 m2.
Excluding central controller system (except automatic address)
For Lossnay single unit test operation
4. System Features and Examples
4.1 Features
*1 The operation condition is stored, and when the power is turned off and then back on, the operation condition returns to the
previous condition. (When using PZ-41SLB-E, the start/stop condition from an external device is not stored.)
M-NET System
4.2 System Example
Operating with an external device
The operation of the Lossnay will be connected with the operation or stopping of the external device.
Input of level signal or pulse signal (12V DC, 24V DC, uncharged a­contact) is possible.
1 Lossnay with 1 remote controller
This is a simple system. A Lossnay is operated independently with 1 remote controller.
Multiple Lossnay units with 1 remote controller
Up to 15 Lossnay units can be controlled at one time with one remote controller. *
2 remote controller system with 1 Lossnay
The Lossnay can be controlled from 2 remote locations.
The remote controller gives priority to the last touch.
Operating with Mr. Slim (A-control or K-control)
The Remote controller (A-control or K-control) controls the air condi­tioning device and the Lossnay.
When using the A-control remote controller operating or switching fan speed for the Lossnay individually is possible.
4
Basic System (refer to page 9)
Operation with an Air Conditioning Unit
(refer to page 12)
Operating with an External Device
(refer to page 21)
Lossnay
Non-polar 2 wires
Remote controller PZ-41SLB-E
Power supply
Lossnay
Non-polar 2 wires
Power supply
Remote controller PZ-41SLB-E
(Sub)
(Main)
Lossnay
Power supply
Lossnay
Non-polar 2 wires
Remote controller PZ-41SLB-E
Power supply
Air conditioning device and system control
It is possible to operate 16 indoor units per 1 Lossnay
Indoor unit
MA remote controller
Outdoor unit
Indoor unit
MA remote controller
Lossnay
Indoor unit
MA remote controller
Lossnay
Indoor unit
Indoor unit
MA remote controller
Indoor unit
MA remote controller
Lossnay
Indoor unit
MA remote controller
Indoor unit
MA remote controller
Lossnay
Indoor unitIndoor unit
Group 1 Group 5Group 3 Group 4Group 2
Outdoor unit Outdoor unit
Indoor unit
MA remote controller
Lossnay Lossnay
Group 1
Lossnay
Group 2 Group 3
Refrigerant 1 Refrigerant 2
Control of start/stop, fan speed and ventiliation mode is possible from the Lossnay M-NET remote controller.
Control of start/stop, fan speed and ventiliation mode is possible from the centralised controller.
It is possible to set a maximum of 16 units for 1 group.
Lossnay M-NET remote controller
PZ-52SF-E
Lossnay Lossnay
Group 1
Lossnay M-NET remote controller
PZ-52SF-E
Lossnay Lossnay LossnayLossnay
Group 3
Lossnay M-NET remote controller
PZ-52SF-E
Lossnay
Group 4Group 2
Centralised controller
Power supply unit
Lossnay M-NET remote controller
PZ-52SF-E
Lossnay
Group 5
Lossnay
Power supply
Power supply
Remote controller
Mr. Slim
(indoor unit)
Lossnay
Power supply
Power supply
Remote controller
Indoor unit
Remote controller PZ-41SLB-E
Non-polar two wires
City Multi and Lossnay Interlocked System
Centralised Management System
* In the case of LGH-150/200RX
3-E, there are 2 circuit boards installed in each unit, so count each unit as 2 Lossnay units.
Selection of inter­locked operation mode is possible.
Delayed start inter­locked operation is possible.
Use Lossnay M-NET remote controller PZ-52SF-E .
(Do not use PZ-41SLB-E).
Lossnay transmission connection terminal
5
2 remote controller system with multiple Lossnay units
It is also possible to operate 2 remote controller units when using multi­ple Lossnay units.
Power supply
Power supply
Remote controller
PZ-41SLB-E
Interlocking multiple units
When the operation signal is a uncharged a-contact signal
Interlocking/individual joint systems
By making the group setting, interlock settings have become possible. (Joint use of the air conditioner remote controller and Lossnay remote controller is possible.)
Interlocking is possible from multiple air conditioning units, etc. (excluding pulse input) (Separately sold parts are necessary depending on the operation signal).
Applicable indoor units are C type or later (for use with MA remote con­troller) models
Do not set the air conditioning unit and Lossnay unit to be part of the same group.
When the address number has been changed, the data in the memory is automatically reset.
Power suupy Power suupy Power suupy Power suupy
Lossnay
A/C A/C A/C
Remote controller PZ-41SLB-E
Air conditioning unit side remote controller
Air conditioning unit side remote controller
Air conditioning unit side remote controller
Indoor unit (01)
Centralised controller (201)
Outdoor unit (51)
Operation settings
MA remote controller
Lossnay (02)
Lossnay M-NET remote controller (PZ-52SF-E)(102)
Group 1 Group 2
Use Lossnay remote controller PZ-41SLB-E .
(Do not use PZ-52SF-E).
Lossnay transmission connection terminal
ABS65654321
Transmission cable
Transmission cable
Round terminal
M-NET Transmission cable input terminal block
Shielded wire
M-NET
Transmission cable
Remote Controller Input Terminal
Main/Sub switch (SW1)
Main Sub
(Set to Main when shipped from the factory)
( ) address
LGH-15 to 100RX3 LGH-150 and 200RX3
LGH-15 to 100RX3
TB5
LGH-150 and 200RX
3
TB5
Setting
Setting
LGH-15 to 100RX
3 LGH-150 and 200RX3
Upper circuit board [Sub] ex. SA1 = 0, SA2 = 2
Lower circuit board [Main] ex. SA1 = 0, SA2 = 1
ABS A65BS
SA1 SA1
0
1
2
0
SA1 SA2SA1 SA2
1
0
6
4.3 System Selection
Interlocked with City Multi
(
Refer to page 16
)
Lossnay operation when indoor unit is stopped
Lossnay stopping when indoor unit is operating Switching Lossnay fan speed
When interlocked with indoor unit for compatibility with both R22 and R407C
High/Low
When interlocked with indoor unit for other than the above
Fixed to high
Ventilation mode
Fixed to automatic Filter maintenance indicator Lossnay error indicator Delayed operation External control operating mode selection × Number of indoor units for interlocked group setting with one Lossnay unit
16 units
Number of Lossnay units for interlocked group setting with one indoor unit
1 unit
Interlocked with external device (BMS
)
(
Refer to page 21
)
Start/Stop Fan speed switching
Fixed to high Ventilation mode switching
Fixed to automatic Filter maintenance indicator × Lossnay error indicator × Delayed operation External control operating mode selection
Lossnay unit LGH-RX3-E
M-NET transmission cable
Remote controller
City Multi
indoor unit
Interlocked with Mr. Slim
(
Refer to page 12
)
When using A-control remote controller
Lossnay operation when indoor unit is stopped Lossnay stopping when indoor unit is operating × Lossnay fan speed switching High/Low
When using K-control controller
Lossnay operation when indoor unit is stopped × Lossnay stopping when indoor unit is operating × Lossnay fan speed switching
Fixed to high Other common items
Lossnay error indicator × Ventilation mode
Fixed to automatic
Filter maintenance indicator × Delayed operation External control operating mode selection × Number of indoor units for interlocked group setting with one Lossnay unit
1 unit
Number of Lossnay units for interlocked group setting with one indoor unit
1 unit
Slim-Lossnay connecting cable (
Enclosed accessory
)
Remote controller
Mr.Slim (A, K-control
)
indoor unit
Lossnay remote controller cannot be used.
Lossnay unit LGH-RX3-E
Independent Lossnay Unit
(
Not interlocked with
City Multi or Mr. Slim systems.
)
(
Refer to page 9
)
Start/Stop Fan speed switching High/Low
Ventilation mode
Heat ex. /
By-pass/ Auto Filter maintenance indicator Lossnay error indicator Delayed operation External control operating mode selection Number of Lossnay units
15 units
(
In the case of LGH-150/200RX3-E, count each unit as two for calcultion)
Number of remote controllers 2 units
Lossnay remote controller
(PZ41SLB-E)
EXT. signal source for interlocking to the Lossnay
Lossnay unit LGH-RX3-E
EXT. signal source for interlocking to the Lossnay
Lossnay unit LGH-RX3-E
7
Central Con-
troller Sys-
tem
Central Controller System
Centralised Controller
Power supply unit
PAC-SC34KUA
Indoor unit
Lossnay
Indoor unit
Outdoor unit
A-control Mr.Slim outdoor unit
Mr.Slim A-control remote controller
A-control Mr.Slim indoor unit
Lossnay
Lossnay M-NET remote controller (PZ-52SF-E)
EXT. signal source
Lossnay M-NET remote controller (PZ-52SF-E)
Remote controller
K-transmissoin converter
Remote controller
Mr.Slim K-control remote controller
K-control Mr.Slim indoor unit
Lossnay
LossnayLossnay
Lossnay M-NET remote controller (PZ-52SF-E)
Lossnay
Caution:
Lossnay remote controller PZ-41SLB-E can not be used.
8
Reference: Remote controller for the Lossnay and indoor unit.
Refer to the technical documentation related to the Remote controller for the indoor unit.
Remote controllers for City Multi indoor unit
Network remote controller (PAR-20MAA
)
Simple remote controller (PAR-27MEA
)
TIMER SET
PAR-20MAA
ON/OFF
CENTRALLY CONTROLLED
ERROR CODE
CLOCK
ON OFF
ßC
CHECK
CHECK MODE
FILTER
TEST RUN FUNCTION
ßC
1Hr.
NOT AVAILABLE
STAND BY DEFROST
FILTER
CHECK TEST
TEMP.
With Lossnay interlock switches and indicators.
PAR-F27MEA
ON/OFF
CENTRALLY CONTROLLED
DAILY
AUTO OFF
REMAINDER
CLOCK
ON OFF
ßC
CHECK MODE
FILTER
TEST RUN LIMIT TEMP.
ßC
1Hr.
NOT AVAILABLE
STAND BY DEFROST
FILTER
CHECK TEST
TEMP.
TIMER SET
CLOCKONOFF
Without Lossnay interlock switches and indicators.
Remote controllers for Mr. Slim indoor unit
A-control remote controller (PAR-27AA
)
K-control remote controller
ON/OFF
STAND BY DEFROST
INDOOR UNIT ADDRESS NO.
ERROR CODE OA UNIT ADDRESS NO.
CENTRALLY CONTROLLED
CLOCK
ON OFF
˚C
1Hr.
NOT AVAILABLE
˚C
CHECK MODE
FILTER
CHECK
TEST RUN
ON OFFCLOCK
FILTER
CHECK
TEST RUN
REMOTE CONTROLLER
TEMP. TIMER SET
With Lossnay interlock switches and indicators.
ON/OFF
STAND BY DEFROST
CENTRALLY CONTROLLED
CLOCK
ON OFF
˚C
1Hr.
NOT AVAILABLE
CHECK MODE
FILTER
CHECK
TEST RUN
ON OFFCLOCK
FILTER
CHECK
TEST RUN
REMOTE CONTROLLER
TEMP. TIMER SET
˚C
Without Lossnay interlock switches and indicators.
Remote controllers for Lossnay unit
Lossnay remote controller (PZ-41SLB-E) Lossnay M-NET remote controller (PZ-52SF-E)
DELAYSTART
FILTER
PZ-41SLB-E
2CONTROLLERS
BY-PASS
CHECK SETTING
FILTER MIN.DELAYED
AUTO
HEATEX.
INTERLOCKED
With Lossnay interlock switches and indicators.
CENTRAL
HEAT EX. BY-PASS AUTO
CHECK
INTERLOCKED
FILTER
ON/OFF
NOT
AVAILABLE
FILTER
Without Lossnay interlock switches and indicators.
9
4.4 Basic System
4.4.1 System Summary
4.4.2 Operation of Multiple Units
Design Example 1 Basic system
This is a simple system. A Lossnay is operated independently with 1 remote controller.
Lossnay
Non-polar 2 wires
Remote controller PZ-41SLB-E
Power supply
Design Example 2 Lossnay control of multiple units
Up to 15 Lossnay units can be controlled at one time with 1 remote controller switch. (up to 7 units when using LGH­150/200RX
3)
Lossnay
Non-polar 2 wires
Power supply
Remote controller PZ-41SLB-E
(Sub)
(Main)
Lossnay
Power supply
Design Example 3 2 remote controller system
The Lossnay can be controlled from 2 remote locations.
The remote controller gives pri­ority to the last touch.
Lossnay
Non-polar 2 wires
Remote controller PZ-41SLB-E
Power supply
Feature
For LGH-15 to 100RX
3, 1 remote controller can operate from 1 to 15 Lossnay units. For using LGH-
150/200RX3, 1 remote controller can operate from 1 to 7 Lossnay units.
Ordered part
Remote controller PZ-41SLB-E
Also connect the power to the second and following Lossnay units.
Notes
The maximum extension of the transmission cable is 500 m or less (between Lossnay and remote controller switch, between Lossnay and Lossnay).
The main or Sub setting on the Lossnay is necessary.
Note:
The external device operation signal, and pulse signals can only be connected to the Lossnay on the Main setting.
When the M-NET system is connected, do not connect the transmission cable to TM2.
System Example
Lossnay (Main)
Power supply
(Transmission cable extension is 500 m or less) PVC cable ø0.65 to 1.2 or strand wire 0.3 mm
Remote controller PZ-41SLB-E
2
to 1.25 mm2.
Lossnay (Sub)
Power supply
Lossnay (Sub)
up to 15 units
(Be sure to turn on the power for the second and following Lossnay units.)
Power supply
10
Combined Line Method
Connect the transmission cable from the first Lossnay to the second, the second to the third, and so on up to a maximum of 15 units.
(1) Up to four wires can be connected to one signal terminal when a transmission cable is ø0.65 or strand wire 0.3 mm
2
, or up
to 2 wires in other cases.
(2) The signal is non-polar, so it is not necessary to align polarity.
65
65
Lossnay
Power supply
Lossnay
Power supply
Lossnay
Power supply
Remote controller PZ-41SLB-E
Set to Main Set to Sub
Main/Sub selection switch
(SW1)
Main Sub
Transmission cable
Transmission cable
Connect to remote controller (PZ-41SLB-E)
Connect to third Lossnay
Lossnay Main/Sub Setting
Be sure to make the Main/Sub setting when operating multiple Lossnay units. When operating multiple Lossnay units, set the first one to Main,” set the second and following to Sub. Be sure the power is off when making the settings.
Change the Main/Sub switch (SW1) on the control board to Sub for the second and following Lossnay units.
Operation Method
Up to 15 Lossnay units (up to seven units when using LGH-150/200RX3-E) can be operated when running at the same time. (Individual control is not possible)
Note:
In the case of LGH-150/200RX3-E, there are two circuit boards installed in each unit. Therefore, count each unit as two units in calculations when controlling multiple units. For example, 5 LGH-150RX
3-E units would count as 10 units. (For
150/200RX3-E type only, a maximum of seven units is possible.)
(Main)
Lossnay
(Sub)
Lossnay
(Sub)
Lossnay
Power supply Power supply Power supply
Remote controller PZ-41SLB-E
11
4.4.3 Operation with 2 Remote controllers
System Example
Operation Method
(1) When there are 2 remote controllers, 2 CONTROLLERS will display on the LCD readout’s upper region. (2) The operation is the same with each remote controller. In this case, the Lossnay gives operating priority to the last button
push.
Characteristics
Remote controller
Note
Lossnay can be operated from two remote locations. • Use only up to 2 remote controller
Lossnay conditions can be checked from two remote Lossnay remote controller (Operation will not go normally if 3
locations. PZ-41SLB-E remote controller switches are con
The remote controller gives priority to the last touch. nected.)
Lossnay
Power supply
Lossnay
Power supply
Transmission
cable extension
is 500 m or less
PVC cable
ø0.65 to 1.2 or
strand wire
0.3 mm2 to 1.25 mm2.
Remote controller PZ-41SLB-E
Transmission cable extension is 500 m or less
PVC cable
ø0.65 to 1.2 or
strand wire
0.3 mm2 to 1.25 mm2.
Lossnay up to 15 units, or 7 units for LGH 150/200 type (Be sure to turn on the power for the second and following Lossnay units.)
Lossnay
Power supply
Lossnay
Power supply
Lossnay
Power supply
Lossnay
Power supply
Remote controller PZ-41SLB-E
Remote controller PZ-41SLB-E
Remote controller PZ-41SLB-E
Lossnay up to 15 units, or 7 units for LGH 150/200 type (Be sure to turn on the power for the second and following Lossnay units.)
Lossnay
2CONTROLLERS
BY-PASS
AUTO
HEAT EX.
Remote controller
Remote controller
Close-up of display region
12
4.5 Interlocking with Mr. Slim
4.5.1 Interlocked Mr. Slim and Lossnay System
Features
Interlocked operation with Mitsubishi air-conditioners is possible.
System Example
Slim-Lossnay connection cable (
Enclosed accessory
)
A-control or K-control Mr.Slim indoor unit
A-control or K-control Mr.Slim outdoor unit
A-control or K-control
remote controller
Lossnay unit LGH-RX
3-E
Lossnay Function Table (Interlocked settings
)
Item
Number of indoor units that can be set to interlocked opera­tion with 1 Lossnay unit in each group
Number of Lossnay units that can be set to interlocked oper­ation with 1 indoor unit
Operation of Lossnay unit only (
When indoor unit is stopped
)
A-control
K-control
Independent Lossnay unit start and stop (
When indoor unit is operating
)
A-control
K-control
Delayed operation (
Optional setting
)
Fan speed switching A-control
K-control
Ventilation mode
Filter indicator
Error
Restrictions and precautions
Details
1 unit
1 unit
Possible
Not possible
Not possible
Not possible
30 minute delayed operation when indoor unit cooling/heating is started
High/Low
Fixed to high
Fixed to automatic
Not possible
Not possible
* The Lossnay remote controller cannot be used on systems
interlocked with Mr. Slim. When connecting a PZ-41SLB-E to a Lossnay unit, ON/OFF and High/Low operation by the PZ-41SLB-E can­not be reflected to the display of the Mr. Slims A-control remote controller.
13
Controller Function Table especially regarded to the Lossnay unit
Lossnay remote
controller
PZ-41SLB-E, PZ-52SF-E
K-control
remote
controller
«
×
× (Automatic)
×
«
×
×
×
×
×
×
A-control remote
controller
PAR-S27AA
« «
× (Automatic)
×
« «
×
×
×
×
×
Local Remote
Model
Start/Stop
Fan speed switching
Ventilation mode switching
Priority instructions. Local permitted/prohibited
Status (Operation/Stop
)
Fan speed switching
Ventilation mode
Error
Error content
Filter sign
Local permitted/prohibited
Not used to the interlocked
Lossnays
Monitoring Operation
Switched and display
«
: Group only (or function available)× : Not available
For details about the operation or display of the A-control remote controller (PAR-27AA), refer to page 81.
14
4.6 Combination with City Multi
4.6.1 Independent Lossnay System with Lossnay M-NET Remote Controller and MELANS
Features
The Mitsubishi Electric air-conditioner network system (MELANS)can operate and monitor each group of Lossnay units and air-conditioners.
Can also perform operations using Lossnay M-NET remote controller.
System Examples: 1
The following groups can be configured.
Lossnay
(001)
Centralised controller
(
000
)
Power supply unit
Lossnay M-NET remote
controller PZ-52SF-E
(106)
(103)
( )
address
Group1
Group6
Group2 Group3 Group4 Group5
Lossnay M-NET remote
controller PZ-52SF-E
(156)
(101)
Lossnay
(013)
Group8
Lossnay M-NET remote
controller PZ-52SF-E
(114)
Lossnay
(014)
Lossnay
(015)
Lossnay
(002)
Lossnay
(004)
Lossnay
(005)
Lossnay
(006)
Lossnay
(003)
Lossnay
(010)
Lossnay
(008)
Lossnay M-NET remote
controller PZ-52SF-E
(107)
(157)
Lossnay
(007)
Lossnay M-NET remote
controller PZ-52SF-E
Indoor unit (009)
MA Remote controller
Group7
Indoor unit (011)
Indoor unit
(012)
MA Remote controller
Group9
Indoor unit (016)
MA Remote controller
Outdoor unit
(059)
Group 1 : Group of 1 Lossnay unit and 1 Lossnay M-NET remote controller. Group 2 : Group without Lossnay M-NET remote controller. Group 3 : Group of multiple Lossnay units and 1 Lossnay M-NET remote controller. Group 4 : Group of 1 Lossnay unit and 2 Lossnay M-NET remote controllers. Group 5 : Group of multiple Lossnay units and 2 Lossnay M-NET remote controllers. Group 6 : Group of 1 indoor unit and 1 Lossnay unit in interlocked operation. Group 7 : Group of multiple indoor units and 1 Lossnay unit in interlocked operation. Group 8 : Group of multiple Lossnay units connected to 1 indoor unit transmission cable and 1 Lossnay M-NET
remote controller.
Group 9 : Group with no Lossnay units.
Caution:
Lossnay remote controller PZ-41SLB-E can not be used.
15
Lossnay Function Table (Group Setting
)
Controller Function Table
Item
Number of Lossnay remote controllers and/or MELANS units that can be connected to 1 Lossnay unit
Operation of 2 remote controllers in 1 group
Fan speed switching
Ventilation mode
Filter indicator
Error
Details
5 units (
Number of Lossnay remote controller is 2 units max.
)
Possible
High/Low
Heat ex. / By-pass / Automatic
3000 hours / 1500 hours / 4500 hours / No display
Display
Centralised
controller
MJ-180A
100 Groups/
100 Units
*200 Groups/
200 Units
n
«
n
n
« « « « « « « «
6
42
1
«
Centralised
controller
MJ-103MTRA
50 Groups/
50 Units
n n n
n
« « « « « « « «
3
21
10
«
MA remote
controller
PAR-20MAA
ME remote
controller
PAR-F27MEA
Lossnay M-
NET remote
controller
PZ-52SF-E
1 Group/
16 Units
« « «
×
« « « « « « «
×
×
×
×
×
No. of controllable (Groups/Units
)
Local Remote
Model
MELANS Series
Start/Stop
Fan speed switching
Ventilation mode switching
Priority instructions. Local permitted/prohibited
Status (Operation/Stop
)
Fan speed switching
Ventilation mode
Error
Error content
Filter sign
Local permitted/prohibited
Weekly
Stop/Starts per day
Stop/Starts per week
Minimum setting (minutes
)
Error record
Scheduling/
Recording
Monitoring
Operation
Switches and display
n
: Group/batch
«
: Group only (or function available
)
× : Not available
* Can be expanded to 200 units by using 2 gateway units.
For details about the operation or display of the Lossnay M-NET remote controller (PZ-52SF-E) refer to page 69.
For details about the operation or display of the Centralised controller (MJ-103MTRA) refer to page 74.
Not used to
the non-interrocked Lossnay
16
4.6.2 City Multi and Lossnay Interlocked System
Characteristics
Interlocked operation with Mitsubishi air-conditioners is possible.
Can also perform independent Lossnay operations using MA remote controller or ME remote controller.
System Examples
The following groups can be configured.
Single Refrigerant System
Group1
Lossnay
(005)
Group3
Lossnay
(007)
Lossnay
(009)
Lossnay
(002)
Indoor unit (001)
MA Remote controller
Indoor unit (010)
MA Remote controller
Group2
Indoor unit (003)
Indoor unit
(004)
MA Remote controller
Group4 Group5
Indoor unit (006)
Indoor unit (008)
MA Remote controller
MA Remote controller
Outdoor unit (051)
( ) address
Lossnay remote controller PZ-41SLB-E can not be used with any group.
Multiple Refrigerants System
Group1
Lossnay
(004)
Group3
Lossnay
(008)
Lossnay
(002)
Indoor unit (001)
MA Remote controller
Group2
Indoor unit (003)
Indoor unit
(005)
Indoor unit
(007)
MA Remote controller
Indoor unit (006)
MA Remote
controller
Outdoor unit (051) Outdoor unit (055)
( ) address
Refrigerant 1 Refrigerant 2
Group 1 : Group of 1 indoor unit and 1 Lossnay in interlocked operation. Group 2 : Group of multiple indoor units and 1 Lossnay unit in interlocked operation. Group 3 : Group of 1 indoor unit with 2 remote controllers and 1 Lossnay unit in interlocked operation. Group 4, 5 : Group of multiple groups and 1 Lossnay unit in interlocked operation.
Group 1 : Group of 1 indoor unit and 1 Lossnay in interlocked operation. Group 2 : Group of multiple indoor units (with different refrigerants) and 1 Lossnay unit in interlocked operation. Group 3 : Group of multiple indoor units (with same refrigerant) and 1 Lossnay unit in interlocked operation.
17
Lossnay Function Table (Interlocked Settings)
Controller Function Table especially regarded to the Lossnay unit
Item
Number of indoor units that can be set to interlocked opera­tion with 1 Lossnay unit in each group
Number of Lossnay units that can be set to interlocked oper­ation with 1 indoor unit
Independent start/stop of ventilation (Lossnay)
Delayed operation (Optional setting)
Fan speed switching Indoor unit compatible with both R22
and R407C
Units other than the above
Ventilation mode
Filter maintenance indicator
Error
Restrictions and precautions
Details
16 units per group
1 unit
Possible
30 minute delayed operation when indoor unit cooling/heat­ing is started
High/Low
Fixed to high
Fixed to automatic
3000 hours / 1500 hours / 4500 hours / No display
Display
* Lossnays cannot be interlocked to the indoor units using K-
transmission converter.
MA remote
controller
PAR-20MAA
« «
× (Automatic)
×
« «
×
« « « «
×
2
×
10
×
ME remote
controller
PAR-F27MEA
« «
× (Automatic)
×
« «
×
« « « «
× (Dayly)
2
×
10
×
Lossnay
M-NET remote
controller
PZ-52SF-E
« « «
×
« « « « « « «
×
×
×
×
×
Local Remote
Model
Start/Stop
Fan speed switching
Ventilation mode switching
Priority instructions. Local permitted/prohibited
Status (Operation/Stop
)
Fan speed switching
Ventilation mode
Error
Error content
Filter sign
Local permitted/prohibited
Weekly
Stop/Starts per day
Stop/Starts per week
Minimum setting (minutes
)
Error record
Scheduling/
Recording
Monitoring Operation
Switches and display
«
: Function available × : Not available
For details about the operation or display of the remote controller (PAR-F27MEA, PAR-20MAA), please refer to those Manuals.
18
4.6.3 MA Remote Controller/ME Remote Controller in Combination with Lossnay M-NET Remote Controller
System
The MA remote controller, ME remote controller, and Lossnay M-NET remote controller can be used in combination.
Combination of Air Conditioner Remote Control and Lossnay Remote Control
Indoor unit (001)
Lossnay
(002)
Lossnay M-NET remote controller PZ-52SF-E (102)
MA remote controller (101)
Centralised
controller
(201)
Outdoor unit
(051)
Power supply unit
Group1 Group2
Interlocked operation setting
( ) address
Indoor Unit Lossnay LGH-RX3-E
Model for MA remote control (Type C or later) «
Model for other than MA remote control (Type B or earlier) ×
«
: Compatible × : Incompatible
System Examples: 1
Setting Method
(1) Make the Group setting for the indoor unit. (2) Make the Group setting for the Lossnay unit. (3) Set the indoor unit and Lossnay unit in interlocked operation. When using the centralised controller, make both the Group setting and operation setting for the previously mentioned units. Though the MJ-180A cannot set interlocked settings, it should set at MA/ME remote controllers.
Characteristics
(1) When the indoor unit is set for interlocked operation in 1 group:
Interlocked operation with the indoor unit from the air conditioner remote controller is possible and can switch between High/Low/Off. From the air conditioner remote controller it is possible to switch the Lossnay only between High/Low/Off. From the Lossnay remote controller it is possible to switch the Lossnay between High/Low/Off.
(2) When the 2 or more indoor units with different group are set for interlocked operation, the Lossnay will operate if at least 1
group operates. The Lossnay will stop operation if all groups stop operation. From an air conditioner remote controller it is possible to switch the Lossnay only between High/Low when other groups are operating. From the Lossnay remote controller it is possible to switch the Lossnay between High/Low/Off.
Note:
If the display on the MA remote controller/ME remote controller, or other air conditioner remote controller, is cancelled, the air
conditioner remote controller will not show the ventilation display even if you operate the Lossnay from the Lossnay M-NET remote controller.
Note:
Transmission cable power control for indoor units Be sure usage is within the following boundaries.
Indoor units + ME remote controllers (compact remote controllers) + Lossnay M-NET remote controllers is less than or equal
to 40 units.
Indoor units are less than or equal to 20 units.
(The numbers of MA remote controllers and Lossnay units are not included in the above number of units.)
19
System Examples: 2
A mixed system including the City Multi can also be configured.
Note:
Do not use Lossnay remote controller PZ-41SLB-E in case of a system using M-NET transmission cable.
(
109
)
(
103
)
(
106
)(
107
)
(
157
)
(
111
)
(
114
)
(
116
)
Indoor unit
(011)
Group1 Group2
Group6 Group7 Group8 Group9
Group3 Group4 Group5
Centralised controller (000
)
Outdoor unit
(
059
)
Power supply unit
Lossnay M-NET remote
controller PZ-52SF-E
Lossnay M-NET remote
controller PZ-52SF-E
Lossnay M-NET remote
controller PZ-52SF-E
Lossnay M-NET remote
controller PZ-52SF-E
Lossnay M-NET remote
controller PZ-52SF-E
ME
remote controller
ME
remote controller
ME
remote controller
( )
address
(
101
)
(
156
)
Lossnay
(001)
Lossnay
(010)
Lossnay
(013)
Lossnay
(014)
Lossnay
(015)
Lossnay
(002)
Lossnay
(003)
Lossnay
(004)
Lossnay
(005)
Lossnay
(006)
Lossnay
(007)
Lossnay(008)
Indoor unit
(009)
Indoor unit
(012)
Indoor unit
(016)
Group 1 : Group of 1 Lossnay unit and 1 Lossnay M-NET remote controller. Group 2 : Group with no Lossnay M-NET remote controller. Group 3 : Group of multiple Lossnay units and 1 Lossnay M-NET remote controller. Group 4 : Group of 1 Lossnay unit and 2 Lossnay M-NET remote controllers. Group 5 : Group of multiple Lossnay units and 2 Lossnay M-NET remote controllers. Group 6 : Group of 1 indoor unit and 1 Lossnay unit in interlocked operation. Group 7 : Group of multiple indoor units and 1 Lossnay unit in interlocked operation. Group 8 : Group of multiple Lossnay units connected to an indoor unit transmission cable and 1 Lossnay M-NET
remote controller.
Group 9 : Group with no Lossnay units.
Lossnay
(01)
Lossnay
(02)
Lossnay
(03)
Centralised controller (000)
Power supply unit
Group1
M-NET transmission cable
Lossnay remote controller
PZ-41SLB-E
Use PZ-52SF-E to connect M-NET transmission cable
(101)
( ) address
20
Operation
Observation
Contents
ON/OFF Change fan to High/Low Change ventilation mode Local prohibit ON/OFF Operation condition Fan speed Ventilation mode (conditions) Errors Filter maintenance sign Local prohibit ON/OFF state
Individual Lossnay (Lossnay not set for interlocked operation)
« « « « « « « « « «
Interlocked Lossnay (Lossnay set for interlocked opera­tion with City Multi)
× × × × × × ×
«
× ×
4.6.4
When Using the LONWORKS®Compatible Adaptor (LMAP02-E) to Connect to LONWORKS
®
By using the LON®adaptor (model name: LMAP02-E), it is possible to control and observe Lossnays on a building management system using the LONWORKS
®
.
* For specifications and functions of the LON
®
adaptor, refer to the materials regarding the LONWORKS®compatible adaptor.
Table of Functions
System Example
(Using M-NET)
Lossnay Lossnay
Building management system
LMAP02-E
Lossnay M-NET remote controller PZ-52SF-E
Lossnay M-NET remote controller PZ-52SF-E
M-NET
LONWORKS
®
M-NET
Lossnay Lossnay
LMAP02-E
Lossnay M-NET remote controller PZ-52SF-E
Lossnay M-NET remote controller PZ-52SF-E
Connect the M-NET transmission cable to TB5 A,B of the Lossnay terminal block. (Refer to page 58). The Lossnay remote controller (PZ-41SLB-E) can not be used with this system. Up to 50 units can be connected with 1 LMAP02-E (The LGH-150, 200RX
3
-E type should be counted as two). For details about the system or connection cables of the LMAP02-E, refer to the technical materials, etc., regarding the LMAP02-E.
* LONWORKS
®
is a registered international trademark, registered in the U.S.A to the Echelon Corporation.
21
5.
Examples of Applications Using Exter­nal Control Input Terminals, Operation Monitor Output Terminals and Malfunc­tion Monitor Output Terminals
Various applications are possible by using the input/output termi­nals as shown below.
Input/Output Specifications
1
2
3
Terminal
External control input ter­minal block
(
TM2 123
)
Operation monitor output terminal block
(
TM3 90
)
Malfunction monitor out­put terminal block
(
TM3 78
)
Specification
This is the input terminal block for start/stop the Lossnay unit using external equipment, such as a Mr. Slim (A-control or K-control)indoor unit or the BMS (Building Management System). Signal input can be by voltage (12V-24V DC)or uncharged a-contact signal.
(
Both voltage and no-votage signals are compatible with pulse input. Set DIP
switch 2-2 to ON. A pulse signal duration of 200 ms or more is needed.
)
Output terminal during Lossnay unit operation. (uncharged a-contact signal output
.)
Contact point rating: 2A/240V AC
Within 2A/24V DC
Output terminal during Lossnay unit malfunction. (uncharged a-contact sig­nal output.
)
Contact point rating: 1A/240V AC
Within 1A/24V DC
Page
22/24·25·26
25/27
26 to 27
Lossnay Main/Sub Setting
For a multiple Lossnay system that will begin operation from one signal from an air conditioner or the like, make sure the unit connected to the signal cable from the air conditioner is set to Main,” and all the others are set to “Sub.
Lossnay
Power supply
Power supply
Remote
controller
PZ-41SLB-E
Air conditioner
up to 15 Lossnay units
Set to "Main"
Set to "Sub"
Air conditioner remote controller
Lossnay
Lossnay
22
5.1 External Control Operating Mode Selection
There are four modes when operating using signals from external equipment.
1. ON/OFF interlock (the last trigger from either external signal or remote control switch has priority
)
2. ON interlock
3. OFF interlock
4. External priority ON/OFF interlock
Operating Signal
Mode
ON/OFF
inter-
lock
ON
inter-
lock
OFF
inter-
lock
External
priority
ON/OFF
inter-
lock
This mode does not exist.
When external signal is level signal.
When external signal is pulse signal.
(
Optional setting
)
External signal
Remote controller [ON/OFF] button pressed
Operating condition
Operating Stopped
External signal
Remote controller [ON/OFF] button pressed
Operating condition
Operating Stopped
External signal
Remote controller [ON/OFF] button pressed
Operating condition
External signal
Remote controller [ON/OFF] button pressed
Operating condition
External signal
Remote controller [ON/OFF] button pressed
Operating condition
Operating Stopped
Operating Stopped
External signal
Remote controller [ON/OFF] button pressed
Operating condition
Operating Stopped
Operating Stopped
External signal
Remote controller [ON/OFF] button pressed
Operating condition
Operating Stopped
Setting Method
When PZ-41SLB-E is used . . . . . . Set with the remote controller. (Refer to page 67)
When PZ-41SLB-E is Not used . . . Set with the dip switch. (Refer to page 61)
23
5.2 Delayed Interlocked Operation (PZ-41SLB-E, M-NET)
(1) It is possible to delay operation of the Lossnay with respect to the operation of the external device. (Energy saving effect.) (2) The times that can be set for delayed operation are 10, 20, 30, 40, 50, and 60 minutes. (3) Delayed operation does not occur if the Lossnay operation was cancelled within the last 2 hours.
(If turned off for a short time, for example during a lunch break, if the direction to restart operation is given within 2 hours, the Lossnay will restart immediately.)
(4) If an operation button is pressed on the remote controller while the delay timer is operating, the delayed operation is can-
celled and normal operation begins.
Setting Method
When PZ-41SLB-E is used . . . . . . Set with the remote controller. (Refer to page 67)
When PZ-41SLB-E is Not used . . . Set with the dip switch but fixed only for 30 minutes. (Refer to page 60)
5.3 Multiple External device Operation (PZ-41SLB-E, M-NET)
System Example
When the Operation Signal is a Uncharged a-contact Level Signal
When there are multiple air conditioners or other external devices
Characteristics Ordered parts Notes
Lossnay operates when any of the external devices operate.
Remote controller External signals that can be
received are listed below.
Level signal, uncharged a-contact
If the external device is a pulse sig­nal or charged signal multiple con­nections can not be made.
Uncharged a-contact Uncharged a-contact
Lossnay
Power supply Power supply Power supply Power supply
Uncharged a-contact
Remote controller PZ-41SLB-E
* Illustration shows an example when using PZ-41SLB-E.
Air conditioner remote controller
Air condi­tioner 1
Air condi­tioner 2
Air condi­tioner 4
Air conditioner remote controller
Air conditioner remote controller
(Signal cable for space between Lossnay and remote controller is less than 500 m.) PVC cable φ 0.65 to 1.2 or strand wire 0.3 mm
2
to 1.25 mm2.
24
5.4 Multiple Lossnay Units in Interlocked Opera­tion with One Indoor Unit. (M-NET only)
[
Example: System 1
]
Set the Main/Sub switch of the Lossnay connected to the M-NET transmission cable to Main, set the second and following Lossnay units to “Sub,” and connect 5 and 6 of the Lossnay remote controller’s (PZ-41SLB-E) transmission cable terminal
(TM2) to the corresponding point on the next unit.
(
One Point Advice
)
Register the first Lossnay unit and the indoor unit to be interlocked. It is not necessary to set the address or direct control for the second or following Lossnay units. Malfunctions of the Lossnay units after the second unit will not appear on the remote controller.
[
Example: System 2
]
Use the Lossnay remote controller to set the air conditioners and Lossnay units to separate groups. Both interlocked operation of an air conditioner and Lossnay units can be performed independently by connecting the remote display output for the indoor unit and the external control input for the Lossnay unit.
(
One Point Advice
)
Do not register the indoor unit and Lossnay unit to be interlocked. In addition, ventilation switch on the MA remote controller will be invalid, and the Lossnays error indicator will appear only on the Lossnay remote controller.
5.5
Interlocked Operation of Equipment such as the Electrically Operated Damper and Booster Fan. (M-NET only)
[
Example: System 3
]
Indoor unit
M-NET transmission cable
MA remote controller
Lossnay
(Main)
Lossnay
(Sub)
Lossnay
(Sub)
TM2 TM2 TM2
Lossnay remote controller (PZ-52SF-E)
Indoor unit
M-NET transmission cable
Remote display output
External control input
MA remote controller
Lossnay Lossnay Lossnay
Lossnay
M-NET transmission cable
Indoor unit
MA remote controller
Operation moniter output
Electrically operated damper Booster fan
Loading...
+ 63 hidden pages