GT25 Wide Model
GT2507
142(5.59)
180(7.09)
142(5.59)
133(5.24)
48(1.89)
6
GT2510
203(7.99)
194(7.64)
185(7.28)
10 10
48(1.89)
6
243(9.57)
10
10
203(7.99)
252(9.92)
145(5.71)
189(7.44)
24.5
Unit : mm (inch)
(0.39)
(0.39) (0.39)
(0.24)
(0.96)
(0.39)
(0.24)
General Description
GT2510-WXTBD
GT2507-WTBD
Thank you for purchasing Mitsubishi Electric Graphic Operation
Te rm i na l.
Prior to use, please read both this manual and the
detailed manual thoroughly to fully understand the
product.
(Always read these precautions before using this equipment.)
Before using this product, please read this manual and the relevant
manuals introduced in this manual carefully and pay full attention to
safety to handle the product correctly.
The precautions given in this manual are concerned with this
product.
In this manual, the safety precautions are ranked as "WARNING"
and "CAUTION".
Note that the CAUTION level may lead to a serious accident
according to the circumstances.
Always follow the instructions of both levels because they are
important to personal safety.
Please save this manual to make it accessible when required and
always forward it to the end user.
[DESIGN PRECAUTIONS]
Some failures of the GOT or cables may keep the outputs on or off.
Some failures of a touch panel may cause mal function of the input objects
such as a touch switch .
An external monitoring circuit should be provid ed to check for output signals
which may lead to a serious accident.
Not doing so can cause an accident due to false output or malfunction.
Do not use the GOT as the warning device that may cause a serious
accident.
An independent and redundant hardware or mechanic al interlock is required
to configure the device that displays and outputs serious warning.
Failure to observe this instruction may result in an accident due to inc orrect
output or malfunction.
The GOT backlight failure disables the operation on the touch switch(s).
When the GOT backlight has a failure, the POWER LED blinks (orange/blue)
and the display section dims. In such a case, the input by the touch switch(s)
is disabled.
The display section of the GOT is an analog-resistive type touc h panel.
When multiple points of the display section ar e touched simultaneously, an
accident may occur due to incorrect output or ma lfunction.
Do not touch the display section in 2 points or more si multaneously.
If you touch the display section simultaneously in 2 points or more, the switch
that is located around the center of the touched poin t, if any, may operate.
Doing so may cause an accident due to incorrect output or malfunction.
When programs or parameters of the controller (such as a PLC) tha t is
monitored by the GOT are changed, be sure to reset the GOT, or turn on the
unit again after shutting off the power as soon as possible.
Not doing so can cause an accident due to false output or malfunction.
If a communication fault (including cable disconnection) occurs during
monitoring on the GOT, communication between the GOT and PLC CPU is
suspended and the GOT becomes inoperative.
A system where the GOT is used should be configured to perform any
significant operation to the system by using the switc hes of a device other
than the GOT on the assumption that a GOT communication fault will occ ur.
Not doing so can cause an accident due to false output or malfunction.
GT2510-WXTSD
GT2507-WTSD
MODEL GT25-W-U-GD-E
Model
code
1D7MS5
IB(NA)-0800564ENG-B(1804)MEE
© 2017MITSUBISHI ELECTRIC CORPORATION
SAFETY PRECAUTIONS
Indicates that incorrect handling may cause
hazardous conditions, resulting in death or
severe injury.
Indicates that incorrect handling may cause
hazardous conditions, resulting in medium or
slight personal injury or physical damage.
1
2
3
To maintain the safety of the system incorporating the GOT, take measures
against unauthorized access from external d evices via a network.
4
To maintain the safety against unauthorized access via the Internet, take
5
measures such as installing a firewall.
Products with the Cl.I, DIV.2 mark on the rating plate are suitable for use in
6
Class I, Division 2, Groups A, B, C and D hazardous locations, or
7
nonhazardous locations only.
This mark indicates that the product is certified for use in the Class I,
8
Division2 environment where flammable gase s, vapors, or liquids are not
9
likely to exist under normal conditions.
When using the products in the Class I, Division 2 environment, observe the
0
following to reduce the risk of explosion.
• This device is open-type and is to be i nstalled in an enclosure suitable for
the environment and require a tool or key to open.
1
• Warning - Explosion Hazard - Substitution of any compone nt may impair
suitability for Class I, Division 2.
2
• Warning - Explosion Hazard - Do not disconnect equip ment unless power
3
has been removed or the area is known to be non- hazardous.
• The wireless LAN communication unit interface of this dev ice cannot be
4
used in Class I, Division 2 environment.
5
Les produits marqués Cl.I, DIV.2 sur la plaque signalétique peuvent être
utilisés en Class I, Division 2, local dangereux de groupe A, B, C et D, ou
6
uniquement en local non dangereux.
Ce logo indique que le produit est homologué pour utilisation en
7
environnement de Class I, Division 2 où, dans de s circonstances anormales,
8
il peut y avoir présence de gaz, vapeurs ou liquides inflammables.
Si le produit est utilisé en environnement de Class I, Division 2, observer les
9
précautions suivantes pour réduire le risque d 'explosion.
0
• Cet appareil est de type ouvert et il doit être installé dans une enceinte
appropriée à l'environnement et ne pouvant être o uverte qu'au moyen
d'une clé ou d'un outil.
• Avertissement - Danger d'explosion - Toute substitution de composant
peut compromettre l'aptitude à l'utilisation en Cla ss I, Division 2.
• Avertissement - Danger d'explosion - Ne pas déconnecter l'équipement
quand le circuit est sous tension, ni avant de d'être assuré de l'absence
d'atmosphère inflammable.
• L’interface de l'unité de communication LAN sans fil de cet équipement ne
peut pas être utilisée dans les environnements d e Classe I, Division 2.
Do not bundle the control and communication cables with main-circuit, power
or other wiring.
Run the above cables separately from such wiring and keep them a minimum
of 100 mm apart.
Not doing so noise can cause a malfunction.
Do not press the GOT display section with a pointed material as a pen or
driver.
Doing so can result in a damage or failure of the displ ay section.
When the GOT is connected to the Ethernet network, the available IP
address is restricted according to the system con figuration.
When a GOT2000 series model and a GOT100 0 series model are on an
Ethernet network, do not set the IP address 192.168.0.18 for the GOTs and
the controllers on this network.
Doing so can cause IP address duplication at the GOT startup, adv ersely
affecting the communication of the device with the I P address 192.168.0.18.
The operation at the IP address duplication depends on the devices and the
system.
When using the Ethernet interface, set a different network for port 1 and
port 2.
Turn on the controllers and the network devices to be ready for
communication before they communicate with the G OT.
Failure to do so can cause a communication error on the GOT.
When the GOT is subject to shock or vibration, or some colors appear on the
screen of the GOT, the screen of the GOT might flicker.
[MOUNTING PRECAUTIONS]
Be sure to shut off all phases of the external power supply used by the
system before mounting or removing the GOT main unit to/fr om the panel.
Not doing so can cause the unit to fail or malfunction.
Be sure to shut off all phases of the external power supply used by the
system before mounting or removing the option unit o nto/from the GOT.
Use the GOT in the environment that satisfies the general speci fications
described in this manual.
Not doing so can cause an electric shock, fire, malfunction or product
damage or deterioration.
When mounting the GOT to the control panel, tighten the mounting screws in
the specified torque range (0.36 N•m to 0.48 N•m) with a Phillips-head
screwdriver No.2.
Undertightening can cause the GOT to drop, short circuit o r malfunction.
Overtightening can cause a drop, short circuit o r malfunction due to the
damage of the screws or the GOT.
When mounting the wireless LAN communication unit on the GOT, fit it to the
wireless LAN communication unit interface and tig hten the mounting screws
in the specified torque range (0.10 N•m to 0.14 N•m) with a Phillips-head
screwdriver No.1.
Under tightening can cause the GOT to drop, short circuit o r malfunction.
Overtightening can cause a drop, failure or malfunction due to the damage of
the screws or unit.
hen closing the USB environmental protection co ver, fix the cover to the
W
GOT by pushing the [PULL] mark on the latch firmly to comply wit h the
protective structure.
Remove the protective film of the GOT.
When the user continues using the GOT with the protective film, the film may
not be removed.
Operate and store the GOT in environments without direct sunlight, hi gh
temperature, dust, humidity, and vibrations.
[WIRING PRECAUTIONS]
Be sure to shut off all phases of the external power supply used by the
system before wiring.
Failure to do so may result in an electric shock, p roduct damage or
malfunctions.
Make sure to ground the FG terminal of the GOT power supply section solely
for the GOT (ground resistance: 100 Ω or less, ground cabl e diameter: 1.6
mm or more).
Not doing so may result in an electric shock or ma lfunction.
When tightening the terminal screws, use a Phillips-head sc rewdriver No.2.
Terminal screws which are not to be used must be tightened always at torque
0.5 N•m to 0.8 N•m.
Otherwise there will be a danger of short circu it against the solderless
terminals.
Use applicable solderless terminals and tighten them with the specified
torque. If any solderless spade terminal is used, i t may be disconnected
when the terminal screw comes loose, resulting in failure.
Correctly wire the GOT power supply section after confirming the rated
voltage and terminal arrangement of the product.
Not doing so can cause a fire or failure
Tighten the terminal screws of the GOT power supply section in the specified
torque range (0.5 N•m to 0.8 N•m). Undertightening can cause a short circuit
or malfunction. Overtightening can cause a short circuit or malfunction due to
the damage of the screws or the GOT.
Exercise care to avoid foreign matter such as chips and wire offcuts entering
the GOT. Not doing so can cause a fire, failure or malfunction.
The module has an ingress prevention label on its top to p revent foreign
matter, such as wire offcuts, from entering the module during wiring.
Do not peel this label during wiring. Before starting system operation, be sure
to peel this label because of heat dissipation.
Plug the communication cable into the GOT interface or the connector of the
connected unit, and tighten the mounting screws and the terminal screws in
the specified torque range. Undertightening c an cause a short circuit or
malfunction. Overtightening can cause a s hort circuit or malfunction due to
the damage of the screws or unit.
[TEST OPERATION PRECAUTIONS]
Before performing the test operations of the user creation monitor screen
(such as turning ON or OFF bit device, changing th e word device current
value, changing the settings or current values of the timer or counter, and
changing the buffer memory current value), read through the ma nual
carefully and make yourself familiar with the op eration method.
During test operation, never change the data of the devices which a re us ed to
perform significant operation for the system.
False output or malfunction can cause an accident.
[STARTUP/MAINTENANCE PRECAUTIONS]
When power is on, do not touch the terminals.
Doing so can cause an electric shock or malfun ction.
Correctly connect the battery connector.Do not charge, disassemble, heat,
short-circuit, solder, or throw the battery into the fire.Doing so will cause the
battery to produce heat, explode, or ignite, resulti ng in injury and fire.
Before starting cleaning or terminal screw retightening, alw ays switch off the
power externally in all phases. Not switching the p ower off in all phases can
cause a unit failure or malfunction. Underti ghtening can cause a short circuit
or malfunction. Overtightening can cause a short circuit or malfunction due to
the damage of the screws or unit.
Do not disassemble or modify the unit.
Doing so can cause a failure, malfunction, injury or fire.
ot touch the conductive and electronic parts of the unit directly.
Do n
Doing so can cause a unit malfunction or failure.
The cables connected to the unit must be run in ducts or clamped.
Not doing so can cause the unit or cable to be damaged due to the dangling,
motion or accidental pulling of the cables or can cause a malfunction due to a
cable connection fault.
When unplugging the cable connected to the unit, do not hold and pul l from
the cable portion. Doing so can cause the unit or cable to be damaged or can
cause a malfunction due to a cable connection fault.
Do not drop the module or subject it to strong shock. A module damage may
result.
Doing so may damage the battery, causing the battery fluid to leak inside the
battery. If the battery is dropped or given an impact, dispose of it without
using.
Before touching the unit, always touch grounded metals, etc. to discharge
static electricity from human body, etc.
Not doing so can cause the unit to fail or malfunction.
Use the battery manufactured by Mitsubishi Electric Corporation.
Use of other batteries may cause a risk of fire or explosion.
Dispose of used battery promptly.
Keep away from children.Do not disassemble and do not dispose of in fire.
Be sure to shut off all phases of the external power supply before replacing
the battery or using the dip switch of the terminating resistor. Not doing so
can cause the unit to fail or malfunction by static ele ctricity.
[TOUCH PANEL PRECAUTIONS]
For the analog-resistive film type touch panels, normally the adjustment is not
required.
However, the difference between a touched position and the object positi on
may occur as the period of use elapses.
When any difference between a touched position and the object position
occurs, execute the touch panel calibration.
When any difference between a touched position and the object position
occurs, other object may be activated.
This may cause an unexpected operation due to incorrect output or
malfunction.
[PRECAUTIONS WHEN THE DATA STORAGE IS IN
USE]
If the SD card is removed from drive A of the GOT while being accessed by
the GOT, the GOT may stop processing data for about 20 seconds.The GOT
cannot be operated during this period. The functions that ru n in the
background including a screen updating, alar m, logging, scripts, and others
are also interrupted. Since this interruption makes an impact to the system
operation, it might cause failure.After checking the light off of SD card access
LED, remove the SD card.
If the data storage is removed from the GOT while being accessed by the
GOT, the data storage and files may be damaged. Before removing the data
storage from the GOT, check the SD card access LED, system signal, or
others to make sure that the data storage is not accessed.
Turning off the GOT while it accesses the SD card results in damage to the
SD card and files.
When inserting a SD card into the GOT, make sure to close the SD card
cover. Failure to do so causes the data not to be read or written.
When removing the SD card from the GOT, make sure to support the SD card
by hand as it may pop out.Failure to do so may cause the SD card to drop
from the GOT, resulting in a failure or break.
When inserting a USB device into a USB interface of the GOT, make sure to
insert the device into the interface firmly.Failure to do so may cause the USB
device to drop from the GOT, resulting in a failure or break
Before removing the USB device from the GOT, follow the procedure for
removal on the utility screen of the GOT. After the successful completion
dialog is displayed, remove the USB device by h and carefully. Failure to do
so may cause the USB device to drop from the GO T, resulting in a failure or
break.
[PRECAUTIONS FOR USE]
Do not touch the edges of the touch panel (display section) repeatedly.
Doing so may result in a failure.
Do not turn off the GOT while data is being written to the storage memory
(ROM) or SD card.
Doing so may corrupt the data, rendering the GOT inoperativ e.
[PRECAUTIONS FOR REMOTE CONTROL]
Remote control is available through a network by using GOT functions,
including theSoftGOT-GOT link function, the remote personal computer
operation function, the VNC server function, and the GOT Mobile function.
If these functions are used to perform remote control of control equi pment,
the field operator may not notice the remote control, possibly l eading to an
accident.
In addition, a communication delay or interr uption may occur depending on
the network environment, and remote control of control equipment cannot be
performed normally in some cases.
Before using the above functions to perform remote control, full y grasp the
circumstances of the field site and ensure safety.
[PRECAUTIONS FOR EXCLUSIVE AUTHORIZATION CONTROL]
Make sure to fully understand the GOT network interaction funct ion before
using this function to control the authorization among pieces o f equipment to
prevent simultaneous operations.
The exclusive authorization control of the GOT network interaction
can be enabled or disabled for each screen. (For all screens, the exclusive
authorization control is disabled by default .)
Properly determine the screens for which the exclusiv e authorization control
is required, and set the control by screen.
A screen for which the exclusive authorization control is disab led can be
operated simultaneously from pieces of equipment. M ake sure to determine
the operation period for each operator, fully grasp the circumstances of the
field site, and ensure safety to perform operati ons.
function
[DISPOSAL PRECAUTIONS]
When disposing of this product, treat it as industrial waste .
When disposing of batteries, separate them from other wa stes according to
the local regulations.
(Refer to the GOT2000 Series User’s Manual (Har dware) for details of the
battery directive in the EU member states.)
[TRANSPORTATION PRECAUTIONS]
When transporting lithium batteries, make sure to treat them based on the
transport regulations.
(Refer to the GOT2000 Series User’s Manual (Hardware) for de tails of the
regulated models.)
Make sure to transport the GOT main unit and/or relevant unit(s) in the
manner they will not be exposed to the impact exceedi ng the impact
resistance described in the general specifications of this manual, as they are
precision devices.
Failure to do so may cause the unit to fail.
Check if the unit operates correctly after transportat ion.
When fumigants that contain halogen materials such as fluor ine, chlorine,
bromine, and iodine are used for disinfecting and protecting wooden
packaging from insects, they cause malfunction wh en entering our products.
Please take necessary precautions to ensure that r emaining materials from
fumigant do not enter our products, or treat packaging with method s other
than fumigation (heat method).
Additionally, disinfect and protect wood from insects before packing products.
The following shows manuals relevant to this product.
GOT2000 Series User’s Manual (Hardware)
GOT2000 Series User’s Manual (Utility)
For detailed manuals and relevant manuals, r efer to the Help or the PDF
manuals stored in the DVD-ROM for the drawing software used.
The latest manuals are also available from MITSUBIS HI ELECTRIC FA Global
Website (http://www.MitsubishiElectric.com/fa/).
Manual name Manual number (Model c ode)
Compliance with the new China RoHS directive
GOT 相关的 基于 “ 电器电子产品有害物质限制使用管理办法 ” 要求的表示方法
Note: This symbol mark is for China only.
含有有害 6 物质的名称、含有量、含有部件
本产品中所含有的有害 6 物质的名称、含有量、 含有部件如下表所示。
部件名称
电路板组件 × ○ ○ ○ ○ ○
树脂壳体、电缆、膜材 ○ ○ ○ ○ ○ ○
钣金部件、螺丝等金属部件 × ○ ○ ○ ○ ○
本表格依据 S J/T11364 的规定 编制。
○ : 表示该有害物质在该部件所有均质材料中的含量均在 GB/T26572 规定的限量要
求以下。
×: 表示该有害物质 至少在该部件的某一均质材料中的含量超出 GB/T26572 规定的
限量要求。
Referenced Standard: GB/T15969.2
(Requirement of Chinese standardized law)
Before using the GOT
Connect the connector of the GOT to the connector of the batte ry.
Refer to the GOT 2000 Series User’s Manual (Hardware) f or the co nnection
instructions.
For details on the GOT specifications, installing i nstructions, wiring, maintenance
and inspection, or checking procedure for the version and the compatible standard,
refer to the GOT2000 Series User’s Manual (Hardware).
Manual
产品中有害物质的名称及含量
铅
(Pb)汞(Hg)镉(Cd)
有害物质
六价铬
(Cr(VI))
SH-081194ENG (1D7MJ5)
SH-081195ENG (1D7MJ6)
多溴联苯
(PBB)
多溴二苯醚
(PBDE)
Packing List
The GOT product package includes the following :
Battery (GT11-50BAT) (Attached to the GOT) 1
GT25 Wide Model General Description (This manual) 1
Description Quantity
GT25 Wide Model 1
Installation fitting 4
GT25 ワイドモデル本体概要説明書
1
1. FEATURES
(1) Abundant standard equipment
• Variety of connection with FA devices
• SD card interface compatibl e with the SDHC card having a large capacity
and allowing high-speed communication
• Connection wit h various peripheral devices with the USB host
• One sound output inter face
• Two Ethernet interfaces
(2) Improved usability
• Abundant troubles hooting
• Easy and clear s creen creation
• PC-like operation screen
• Support for the ver tical installation
(3) Enhanced compatibility with Mitsubishi FA devices
(4) LED backlight
2. Part Names and Settings
The following shows the part names for GT2510 and GT 2507.
GT2510
1)2)
5)
13)
16)
24)
3)
4)
11)12)
5)
22)
21)
18)19) 17)
20)
GT2507
1)2)
5)
13)
16)
24)
3)
4)
5)
11)12)
21)
18)19) 17)
22)
No. Name Description
1) Display screen Displays the utility and the user-created screen.
2) Touch panel
USB interface (Device
3)
/Front face)
4) POWER LED
5) Unit installation fitting Mounting fixtures for fixing the GOT to the control panel
6) Reset switch Hardware reset switch
7) Installation switch Used for OS installations at the GOT startup
8) SD card access LED
9) SD card inter face For ins talling a SD card
10) SD card cover
20)
For operating the t ouch switches in the utility and th e usercreated screen
For connecting a personal computer (connector type: MiniB)
Lit in blue : Power is properly supplied.
Lit in orange : Screen saving
Blinks in orange/bl ue : Backlight failure
Not lit : Power is not supplied
Lit: SD card mounted
Blinking: SC card accessed
No lit: SD card not mounted or SD card mounted
(removable)
With a switching function for accepting and stopping the
access to the SD card
When the cover is o pened : Access is prohibited
When the cover is closed : Access is allowed
5)
7)
6)
23)
5)
5)
7)
6)
23)
5)
9)
10)
8)
14)
15)
9)
10)
14)
15)
No. Name Description
11) Battery holder Houses the battery
Terminating resistor
12)
setting switch
(Inside cover)
Wireless LAN
13)
communication unit
interface
USB interface
14)
(Host/Back face)
Hole for attaching a
15)
cable clamp
Vertical installation
16)
arrow mark
17) Power terminal Power input terminal, FG terminal
Ethernet interface
18)
(port 1)
Ethernet interface
19)
(port 2)
Ethernet
20)
communication status
LED
21) RS-422/485 interface
22) RS-232 interface
23) Sound output interface
24) Rating plate -
For switching on and off of the terminating resistor for the
RS-422/485 communication port (Default (Off))
For installing a communication unit
For connecting a USB mouse, a USB keyboard, or a USB
barcode reader, and transferring or saving data
(connector type: TYPE-A)
For a ttac hing a cabl e clam p to pr even t the U SB ca ble or the
sound output cable from being accidentally pulled out
(Recommended product: RSG-130-V0 made by
KITAGAWA INDUSTRIES CO.,LTD)
For the vertical installation, install the GOT so that the arrow
points upward.
For communicating wit h a controller or connecting a
personal computer (connector type: RJ-45 (modular jack))
SD/RD LED ON : Data sent or received
SD/RD LED OFF: Data not sent or received
SPEED LED ON : Communicating at 100 Mbps
SPEED LED OFF: Communicating at 10 Mbps or
disconnected
For communicating with a controller (Connector type: D sub
9-pin (female))
For communicating with a controller (Connector type: D sub
9-pin (male))
For outputting sounds (applicable plug: Φ3.5 stereo miniplug (3-prong))
3. Specifications
3.1 General Specifications
Item Specifications
Operating ambient
*1
temperature
Température
ambiante de
fonctionnement
Storage ambient
temperature
Operating ambient
humidity
Storage ambient
humidity
Vibration resistance
8)
Shock resistance
Operating
atmosphere
Operating altitude
Installation location Inside control panel
Overvoltage
category
Pollution degree
Cooling method Self-cooling
Grounding
*1: The operating ambient temperature incl udes the temperature inside the
*2: Do not use or store the GOT under press ure higher than the atmospheric
*3: This indicates the section of the power supply to which the equipment is
*4: This index indicates the degree to which conductive material is generated in the
*1
Under
Compliant
intermittent
with JIS B
vibration
3502 and
IEC
61131-2
Under
continuous
vibration
Compliant with JIS B 3502 and IEC 61131-2 147 m/s2(15G),
No greasy fumes, corrosive gas, flammable gas, excessive
conductive dust, and direct sunlight (Same as storage atmosphere)
*2
*3
*4
Grounding with a ground resistance of 100 Ω or less by using a ground
cable that has a cross-sectional area of 2 mm
If impossible, connect the ground cable to the control panel.
enclosure of the control panel to which the GOT is installed.
La température ambiante de fonctionnement inclut la te mpérature à l'intérieur
du boîtier du tableau de commande sur lequel le GOT est installé.
pressure of altitude 0 m (0ft.).
Failure to observe this instruction may cause a m alfunction.
When an air purge is made inside the control pan el by adding pressure, there
may be a clearance between the surface sheet and the screen making it difficult
to use the touch panel, or the sheet may come off.
assumed to be connected between the public electr ical power distribution
network and the machinery within the premises.
Category II applies to equipment for which electrical power is su pplied from
fixed facilities.
The surge voltage withstand level for up to the rated voltage of 300 V is 2500 V.
environment where the equipment is used.
In pollution degree 2, only non-conductive po llution occurs but temporary
conductivity may be produced due to condensat ion.
0 to 55
0 à 55
-20 to 60
10 to 90% RH, non-c ondensing
10 to 90% RH, non-c ondensing
Frequency
Acceleration
9.8 m/s
4.9 m/s
amplitude
-
2
1.75 mm
-
2
5 to
8.4 Hz
8.4
to
150 Hz
5 to
8.4 Hz
8.4
to
150 Hz
3 times each in X, Y and Z directions
2000 m (6562 ft) max.
II or less
2 or less
Half-
3.5 mm
-
-
2
or more.
Sweep
count
10 times
each in X,
Y and Z
directions
-
Point
Refer to the GOT2000 Series User’s Manual (Hardware) for details on the performance
specifications of eac h GOT.
3.2 Power Supply Specifications
The following indicates the power supply specification s for GT25 wide model.
Note
Operation at momen tary failure
• If an instantaneous power failure occurs in the power supply and continues for more
than the permissible period, the GOT will be reset.
• Make sure to power on the unit more than 5 seconds after power-off.
Item
Power supply voltage DC24V (+25%, -20%)
maximum load 16 W or less 16 W or less
Power
Stand alone 9 W 9 W
consum
Stand alone with
ption
backlight off
Inrush current
Allowable momentary po wer
failure time
Noise immunity
Dielectric withstand voltage 350 VAC for 1 minute across power terminals and earth
Insulation resistance
Applicable wire size 0.75[mm
Applicable solderless terminal
Applicable tightening torque
(Terminal block terminal screw)
GT2510-WXTSD,
GT2510-WXTBD
59 A or less (2 ms, operating ambient temperature 25,
500 Vp-p noise voltage, 1 s noise width (when
measuring with a noise simulator under 25 to 60 Hz
noise frequency)
10 M or more across power terminals and earth by a 500
V DC insulation resistance tester
Solderless terminal f or M3 screw RAV1.25-3, V2-S3.3,
Specifications
GT2507-WTSD,
GT2507-WTBD
5 W 5 W
maximum load)
5 ms or less
2
] to 2[mm2]
V2-N3A, FV2-N3A
0.5[N•m] to 0.8[N•m ]
3.3 External Dimensions
4. EMC DIRECTIVE
Unit: mm (inch)
*Panel thickness : 1.6 to 4 mm
(0.06 to 0.16 inch)
GOT A B
GT
2507
180.5 (7.11)
+1 (0.04)
0 (0)
133.5 (5.26)
+1 (0.04)
0 (0)
GT
2510
243.5 (9.59)
+1 (0.04)
0 (0)
185.5 (7.30)
+1 (0.04)
0 (0)
B
B
Horizontal
Vertical
A
A
For the products sold in European countries, the conformance to the
EMC Directive, which is one of the European Directives, has been a
legal obligation since 1996. Also, conformance to the Low Voltage.
Directive, another European Directives, has been a legal obligation since
1997.
Manufacturers who recognize their products must conform to the EMC
and Low Voltage Directive are required to declare that their products
conform to these Directives and put a "CE mark" on their products.
• Authorized representative in Europe
Authorized representative in Europe is shown below.
Name :Mitsubishi Electric Europe BV
Address :Mitsubishi-Electric-Platz 1, 40882 Ratingen, Germany
4.1 Requirements to Meet EMC Directive
EMC Directives are those which require "any strong electromagnetic
force is not output to the external.:Emission (electromagnetic
interference)" and "It is not influenced by the electromagnetic wave from
the external.: Immunity (electromagnetic sensitivity)".
Items4.1.1 through4.1.3 summarize the precautions to use GOT and
configure the mechanic al unit in order to match the EMC directi ves.
Though the data described herein are produced with our best on the
basis of the requirement items and standards of the restrictions gathered
by Mitsubishi, they do not completely guaranteed that all mechanical unit
manufactured according to the data do not always match the above.
4.1.1 EMC directiveThe standards of the EMC
Directive are shown below.
Applied
standard
EN61131-2
: 2007
*1: The GOT is an open type device (device installed t o another device) and must
*2: When using the sound output cable, the cable length must be 30 m (1181.1 in.)
*3: QP (Quasi-Peak): Quasi-peak value, Mean: Average value
*4: The above test items are conducted in the following conditions.
Test standard Test details Standard value
Electromagnetic
*1, *2
*1, *2
*1, *2
*1, *2
*1, *2
*1, *2
emissions from the
product are
measured.
Immunity test in
which static
electricity is applied
to the cabinet of the
equipment.
Immunity test in
which field is
irradiated to the
product.
Immunity test in
which burst noise is
applied to the power
line and signal lines.
Immunity test in
which lightening
surge is applied to
the product.
Immunity test in
which a noise
inducted on the
power and signal
lines is applied.
Test for checking
normal operations
under the
circumstance
exposed to the
ferromagnetic field
noise of the power
supply frequency
(50/60 Hz).
CISPR16-2-3
Radiated noise
IEC61000-4-2
Electrostatic
immunity
IEC61000-4-3
Radiated
electromagnetic
field AM
modulation
IEC61000-4-4
Fast transient burst
*1, *2
noise
IEC61000-4-5
Surge immunity
IEC61000-4-6
Conducted RF
immunity
IEC61000-4-8
Power supply
frequency magnetic
field immunity
be installed in a conductive control panel.
The above test items are conducted in the condition where the GOT is installed
on the conductive control panel and combined wi th the Mitsubishi PLC.
or shorter.
30 M-230 MHz QP : 40 dB V/m (10m in measurement range)
230 M-1000 MHz QP : 47 dB V/m (10m in measurement range)
30 M-230 MHz QP:
30 dB V/m (30 m in
measurement range)
230 M-1000 MHz QP:
37 dB V/m(30 m in
measurement range)
4 kV Contact discharge
8 kV Aerial discharge
80-1000 MHz: 10 V/m
1.4-2 GHz: 3 V/m
2.0-2.7 GHz: 1 V/m
80%AM modulation@1 kHz
Power line: 2 kV
Digital I/O: 1 kV
Analog I/O: 1 kV
Signal lines: 1 kV
DC power type
Power line (between line and
ground) : 0.5 kV
Power line (between lines)
: 0.5 kV
Data communication port
: 1 kV
Power line: 10 V
Data communication port: 10 V
30 A/m
*3, *4
*3, *4
4.1.2 Control panel
The GOT is an open type device (device installed to another device) and
must be installed in a conductive control panel.
It not only assure the safety but also has a large effect to shut down the
noise generated from GOT, on the control panel.
(1) Control Panel
(a) The control panel must be conductive.
(b) When fixing a top or bottom plate of the control panel with bolts,
do not coat the plate and bolt surfaces so that they will come into
contact.
And connect the door and box using a thick grounding cable in
order to ensure the low impedance under high frequency.
(c) When using an inner plate to ensure electric conductivity with the
control panel, do not coat the fixing bolt area of the inner plate
and control panel to ensure conductivity in the largest area as
possible.
(d) Ground the control panel using a thick grounding cable in order to
ensure the low impedance under high frequency.
(e) The diameter of cable holes in the control panel must be 10 cm
(3.94 in.). In order to reduce the chance of radio waves leaking
out, ensure that the space between the control panel and its door
is small as possible.
Paste the EMI gasket directly on the painted surface to seal the
space so that the leak of electric wave can be suppressed.
Our test has been carried out on a panel having the damping
characteristics of 37 dB max. and 30dB mean (measured by 3 m
method with 30 to 300 MHz).
(2) Connection of power and ground wires
Ground and power supply wires for the GOT must be connected as
described below.
(a) Provide a ground point near the GOT. Short-circuit the FG
terminal of the GOT, and ground it with the thickest and shortest
cable possible. (The cable length must be 30 cm (11.81 in.) or
shorter.)
The FG terminal function is to pass the noise generated in the PC
system to the ground, so an impedance that is as low as possible
must be ensured. As the wires are used to relieve the noise, the
wire itself carries a large noise content and thus short wiring
means that the wire is prevented from acting as an antenna.
Note) A long conductor will become a more efficient antenna at
high frequency.
(b) The earth wire led from the earthing point must be twisted with
the power supply wires.
By twisting with the earthing wire, noise flowing from the power
supply wires can be relieved to the earthing. However, if a filter is
installed on the power supply wires, the wires and the earthing
wire may not need to be twisted.
4.1.3 Noise filter (power supply line filter)
The noise filter (power supply line filter) is a device effective to reduce
conducted noise. Except some models, installation of a noise filter onto
the power supply lines is not necessary. However conducted noise can
be reduced if it is installed. (The noise filter is generally effective for
reducing conducted noise in the band of 10 MHz or less.) Usage of the
following filters is recommended.
Model name FN343-3/05 FN660-6/06 RSHN-2003
Manufacturer SCHAFFNER SCHAFFNER TDK
Rated current 3 A 6 A 3 A
Rated voltage 250 V
The precautions required when installing a noise filter are described
below.
(1) Do not install the input and output cables of the noise filter together
to prevent the output side noise will be inducted into the input side
cable where noise has been eliminated by the noise filer.
Input side
(power supply side)
Filter
• Installing the input and output cables
together will cause noise induction.
(2) Connect the noise filter's ground terminal to the control panel with
the shortest cable as possible (approx. 10 cm (3.94 in.) o r less).
Induction
Output side
(device side)
Input side
(power supply side)
Filter
Output side
(device side)
• S eparate the input cable from the output
cable.
5. INSTALLATION
5.1 Control Panel Inside Dimensions for
Mounting GOT
Install the GOT o n the control panel out of the wa y for th e equipment
inside the control panel. Do not install the GOT and the unit in
prohibited areas for the installation.
Point
Applicable cable
Some cables may need to be longer than the specified dimensions when connecting to the
GOT. Therefore, consider the connector dimensions and bending radius of the cable as
well for installation.
5.2 Panel Cutting Dimensions
5.3 Mounting Position
When mounting the GOT, the following clearances must be maintained
from other structures and devices.
Some cables may need to be longer than the specified dimensions when
connecting to the GOT.
Therefore, consider the connector dimensions and bending radius of the
cable as well for installation.
For the lead-in allowance for cables at the bottom of the GOT, refer to
the GOT2000 Series User’s Manual (Hardware) .
For the vertical installation, install the GOT so that the vertical installation
arrow printed on the GOT rear face points upward.
B
A
Horizontal
Item
DE
Panel thickness:
1.6 to 4mm
51(2.01) or more
[23(0.91) or more]
53(2.09) or more
[23(0.91) or more]
C
(0.06 to 0.16 inch)
According to the dimensions in the following table, leave clearances
between the GOT and the other devices. The values enclosed in
square brackets apply to the case where no other equipment
generating radiated noise (such as a contactor) or heat is installed
near the GOT. However, keep the ambient temperature of the GOT
to 55 °C or lower.
Unit : mm(inch)
A
B
C
D
*1
E
*1: When opening or closing the battery cover: 72(2 .83) or more
D
B
(0.06 to 0.16 inch)
GT2510 GT2507
Horizontal: 81(3.19) or more
Vertical: 53(2.09) or more
Horizontal: 53(2.09) or more
Vertical: 81(3.19) or more
100(3.94) or more [20(0.79) or more]
A
C
Vertical
64(2.52) or more
[23(0.91) or more]
[23(0.91) or more]
53(2.09) or more
[32(1.26) or more]
[23(0.91) or more]
[23(0.91) or more]
E
Panel thickness:
1.6 to 4mm
5.4 Control Panel Inside Temperature and
Installation Angle
When installing the GOT to a panel, set the display section as shown
below.Using the GOT with the installation angle other than the following
deteriorates the GO T earlier.
Installing the GOT horizontally
When installing the GOT with the installation angle between 60 to
105 °, the temperature inside the control panel must be within 55 °C.
When installing the GOT with the installation angle other than
between 60 to 105 °, the temperature inside the control panel must be
within 40 °C.
Installing the GOT vertically
When the GOT is installed a 90 ° angle , the control panel inside
temperature must be within 55 °C. When the GOT is installed at any
angle other than 90°, the control panel inside temperature must be
within 40 °C.
Display section
GOT
Panel or others
Horizontal Vertical
Display section
105°
60°
GOT
90°
Panel or others
5. INSTALLATION
5.1 Dimensions intérieures du tableau de
commande pour le montage du GOT
Installez le GOT sur le tableau de commande en laissant de l'espace
pour le dispositif à l'intérieur du tableau de commande. N'installez
pas le GOT et le module dans des zones où l'installation est interdite.
Point
Câble applicable
Certains câbles peuvent être plus longs que les dimensions spécifiées lors de la
connexion au GOT. Par conséquent, prenez également en compte les dimensions du
connecteur et le rayon de co urbure du câble pour l'installation.
5.2 Cotes de découpe du panneau
*Épaisseur du panneau : 1,6 à 4mm
B
A
B
Horizontal
Vertical
5.3 Position de montage
Lors du montage du GOT, laissez les espaces suivants pour les autres
structures et dispositifs.Certains câbles peuvent être plus longs que les
dimensions spécifiées lors de la connexion au GOT.
Par conséquent, prenez également en compte les dimensions du
connecteur et le rayon de courbure du câble pour l'installation.
Pour connaître l'espace à laisser pour les câbles sous le GOT, référezvous au manuel GOT2000 Series User’s Manual (Hardware).
Pour l’installation à la verticale, installez le GOT de sorte que la flèche
d’installation à la verticale imprimée sur la face arrière du GOT pointe
vers le haut.
B
C
Horizontal
Laissez les espaces entre le GOT et les autres dispositifs en fonction
des dimensions contenues dans le tableau suivant. Les valeurs entre
parenthèses s'appliquent au cas où aucun dispositif générant des
émissions sonores (comme un contacteur) ou de la chaleur n'est installé
près du GOT.
Toutefois, maintenez la température ambiante du GOT à 55°C ou moins.
A
B
C
D
*1
E
*1 : Pour ouvrir ou fermer le couvercle de la batterie : 72 (2,83) ou plus
DE
A
Épaisseur du panneau :
(0,06 à 0,16 pouce) Épaisseur du panneau :
Article
(0,06 à 0,16 pouce)
GOT A B
243.5 (9.59)
GT
+1 (0.04)
A
2510
0 (0)
180.5 (7.11)
GT
+1 (0.04)
2507
0 (0)
Unité : mm (pouce)
D
B
C
1,6 à 4mm
Vertical
GT2510 GT2507
51 (2,01) ou plus
[23 (0,91) ou plus]
Horizontal: 81 (3,19) ou plus
[23 (0,91) ou plus]
Vertical: 53 (2,09) ou plus
[23 (0,91) ou plus]
53 (2,09) ou plus
[23 (0,91) ou plus]
Horizontal: 53 (2,09) ou plus
[23 (0,91) ou plus]
Vertical: 81 (3,19) ou plus
[23 (0,91) ou plus]
100 (3,94) ou plus [20 (0,79) ou plus]
185.5 (7.30)
+1 (0.04)
0 (0)
133.5 (5.26)
+1 (0.04)
0 (0)
A
1,6 à 4mm
(0,06 à 0,16 pouce)
Unité : mm (pouce)
64 (2,52) ou plus
53 (2,09) ou plus
[32 (1,26) ou plus]
5.4 Température intérieure et angle
d'installation du tableau de commande
Lors de l'installation du GOT sur un panneau, réglez la zone d'affichage
comme indiqué ci-dessous.
Si l'angle d'installation est différent de celui indiqué, le GOT se détériore
plus tôt.
Installation du GOT à l’horizontale
Lors de l'installation du GOT avec un angle d'installation compris entre
60 et 105°, la température à l'intérieur du tableau de commande doit
être d'environ 55°C. Lors de l'installation du GOT avec un angle
d'installation non compris entre 60 et 105°, la température à l'intérieur
du tableau de commande doit être d'environ 40°C.
Installation du GOT à la verticale
Lors de l’installation du GOT avec un angle de 90°, la température à
l’intérieur du panneau de commande ne doit pas dépasser 55°C. Lors
de l’installation du GOT avec tout autre angle que 90°, la température
à l’intérieur du panneau de commande ne doit pas dépasser 40°C.
60°
105°
Zone d'affichage
GOT
90°
Tableau ou autres
Zone d'affichage
GOT
Tableau ou autres
Horizontal Vertical
6. MAINTENANCE AND INSPECTION
Refer to the GOT2000 Series User’s Manual (Hardware) for
maintenance and inspection for the GOT.
E
Warra nty
Mitsubishi Electric will not be held liable for damage caused by
factors found not to be the cause of Mitsubishi Electric; machine
damage or lost profits caused by faults in the Mitsubishi Electric
products; damage, secondary damage, accident compensation
caused by special factors unpredictable by Mitsubishi Electric;
damages to products other than Mitsubishi Electric products; and to
other duties.
For safe use
• This product has been manufactured as a general-purpose part for
general industries, and has not been designed or manufactured to
be incorporated in a device or system used in purposes related to
human life.
• Before using the product for special purposes such as nuclear
power, electric power, aerospace, medicine or passenger
movement vehicles, consult with Mitsubishi Electric.
• This product has been manufactured under strict quality control.
However, when installing the product where major accidents or
losses could occur if the product fails, install appropriate backup or
failsafe functions in the system.
Country/Region Sales office/Tel
USA
Brazil
Mexico
Germany
UK
Italy
Spain
France
Czech
Turkey
Poland
Russia
South Africa
China
Taiwan
Korea
Singapore
Thailand
Indonesia
Vietnam
India
Australia
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
NAGOYA WORKS : 1-14, YADA-MINAMI 5-CHOME, HIGASHI-KU, NAGOYA, JAPAN
When exported from Japan, this manual does not require application to the Ministry
of Economy, Trade and Industry for service transaction permission.
Mitsubishi Electric Automation, Inc.
500 Corporate Woods Parkway, Vernon Hills, IL 60061, U.S.A.
Tel: +1-847-478-2100
Mitsubishi Electric do Brasil Comercio e Servicos Ltda.
Avenida Adelino Cardana, 293, 21 andar, Bethaville, Barueri SP,
Brasil CEP 06401-147
Tel: +55-11-4689-3000
Mitsubishi Electric Automation, Inc. Mexico Branch
Mariano Escobedo #69, Col. Zona Industrial, Tlalnepantla Edo. Mexico, C.P.54030
Tel: +52-55-3067-7511
Mitsubishi Electric Europe B.V. German Branch
Mitsubishi-Electric-Platz 1, 40882 Ratingen, Germany
Tel: +49-2102-486-0
Mitsubishi Electric Europe B.V. UK Branch
Travellers Lane, Hatfield, Hertfordshire, AL10 8XB, U.K.
Tel: +44-1707-28-8780
Mitsubishi Electric Europe B.V. Italian Branch
Centro Direzionale Colleoni - Palazzo Sirio, Viale Colleoni 7,
Agrate Brianza (MB), Italy
Tel: +39-039-60531
Mitsubishi Electric Europe B.V. Spanish Branch
Carretera de Rubi 76-80-Apdo.420, 08190 Sant Cugat del Valles (Barcelona), Spain
Tel: +34-935-65-3131
Mitsubishi Electric Europe B.V. French Branch
25, Boulevard des Bouvets, 92741 Nanterre Cedex, France
Tel: +33-1-55-68-55-68
Mitsubishi Electric Europe B.V. Czech Branch
Avenir Business Park, Radlicka 751/113e, 158 00 Praha 5, Czech Republic
Tel: +420-251-551-470
Mitsubishi Electric Turkey A.S. Umraniye Branch
Serifali Mahallesi Nutuk Sokak No:5, TR-34775 Umraniye / Istanbul, Turkey
Tel: +90-216-526-3990
Mitsubishi Electric Europe B.V. Polish Branch
ul. Krakowska 50, 32-083 Balice, Poland
Tel: +48-12-347-65-00
Mitsubishi Electric (Russia) LLC St. Petersburg Branch
Piskarevsky pr. 2, bld 2, lit “Sch”, BC “Benua”, office 720;
RU-195027 St. Petersburg, Russia
Tel: +7-812-633-3497
Adroit Technologies
20 Waterford Office Park, 189 Witkoppen Road, Fourways, Johannesburg, South Africa
Tel: +27-11-658-8100
Mitsubishi Electric Automation (China) Ltd.
No.1386 Hongqiao Road, Mitsubishi Electric Automation Center, Shanghai, China
Tel: +86-21-2322-3030
SETSUYO ENTERPRISE CO., LTD.
6F, No.105, Wugong 3rd Road, Wugu District, New Taipei City 24889, Taiwan
Tel: +886-2-2299-2499
Mitsubishi Electric Automation Korea Co., Ltd.
7F-9F, Gangseo Hangang Xi-tower A, 401, Yangcheon-ro, Gangseo-Gu,
Seoul 07528, Korea
Tel: +82-2-3660-9530
Mitsubishi Electric Asia Pte. Ltd.
307 Alexandra Road, Mitsubishi Electric Building, Singapore 159943
Tel: +65-6473-2308
Mitsubishi Electric Factory Automation (Thailand) Co., Ltd.
12th Floor, SV.City Building, Office Tower 1, No. 896/19 and 20 Rama 3 Road,
Kwaeng Bangpongpang, Khet Yannawa, Bangkok 10120, Thailand
Tel: +66-2682-6522 to 31
PT. Mitsubishi Electric Indonesia
Gedung Jaya 11th Floor, JL. MH. Thamrin No.12, Jakarta Pusat 10340, Indonesia
Tel: +62-21-3192-6461
Mitsubishi Electric Vietnam Co., LTD. Ho Chi Minh Head Office
Unit 01-04, 10th Floor, Vincom Center, 72 Le Thanh Ton Street, District 1,
Ho Chi Minh City, Vietnam
Tel: +84-8-3910-5945
Mitsubishi Electric India Pvt. Ltd. Pune Branch
Emerald House, EL -3, J Block, M.I.D.C., Bhosari, Pune - 411026, Maharashtra, India
Tel: +91-20-2710-2000
Mitsubishi Electric Australia Pty. Ltd.
348 Victoria Road, P.O. Box 11, Rydalmere, N.S.W. 2116, Australia
Tel: +61-2-9684-7777
Specifications subject to change without notice.
Printed in Japan, April 2018.