Side
B
JY997D32901A
Side
A
JAPANESE ENGLISH
Side
B
GT1045-QSBD, GT1040-QBBD
GT10 General Description
Manual Number JY997D32901A
Date Aug 2008
This manual describes the specifications of the product. Before use, read this
manual and manuals of relevant products fully to acquire proficiency in handling
and operating the product. Make sure to learn all the product information, safety
information, and precautions.
And, store this manual in a safe place so that you can take it out and read it
whenever necessary. Always forward it to the end user.
Registration
The company name and the product name to be described in this manual are
the registered trademarks or trademarks of each company.
Effective Aug 2008
Specifications are subject to change without notice.
Safety Precaution
Before using this product, please read this manual and the relevant manuals introduced
in this manual carefully and pay full attention to safety to handle the product correctly.
The precautions given in this manual are concerned with this product.
In this manual, the safety precautions are ranked as "DANGER" and "CAUTION".
Indicates that incorrect handling may cause hazardous
conditions, resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous
conditions, resulting in medium or slight personal injury
Depending on circumstances, procedures indicated by "CAUTION" may also be
linked to serious results.
In any case, it is important to follow the directions for usage.
DESIGN PRECAUTIONS
• Some failures of the GOT or cable may keep the outputs on or off.
An external monitoring circuit should be provide d to check for output signals
which may lead to a serious accident.
Not doing so can cause an accident due to false output or malfunction.
• If a communication fault (including cable disconnection) occurs during
monitoring on the GOT, communication between the GOT and PLC CPU is
suspended and the GOT becomes inoperative.
A system where the GOT is used should be configured to perform any
significant operation to the sys tem by using the switches of a devi ce other
than the GOT on the assumption that a GOT communication fault will occur.
Not doing so can cause an accident due to false output or malfunction.
•
Do not use the GOT as the warning device that may cause a serious accident.
An independent and redundant hardware or mechanical interlock is required to
configure the device that displays and outputs serious warning.
Failure to observe this instruction may result in an accident due to incorrect
output or malfunction.
• Incorrect operation of the touch switch(s) may lead to a serious accident if the
GOT backlight is gone out.
When the GOT backlight go es out, causes the monitor sc reen to appear
blank, while the input of the touch switch(s) remains active.
This may confuse an operator in thinking that the GOT is in "screensaver"
mode, who then tries to release the GOT from this mode by touching the
display section, which may cause a touch switch to operate.
DESIGN PRECAUTIONS
• Do not bundle the control and communication cables with main-circuit, power
or other wiring.
Run the above cables separately from such wiring and keep them a minimum
of 100mm (3.94in.) apart.Not doing so noise can cause a malfunction.
MOUNTING
PRECAUTIONS
• Be sure to shut off all phases of the external power supply used by the
system before mounting or removing the GOT to/from the panel.
Not doing so can cause the unit to fail or malfunction.
•
When installing the battery wear an earth band etc. to avoid the static electricity.
The static electricity can cause the unit to fail or malfunction.
or physical damage.
© 2008 Mitsubishi Electric Corporation
(Read these precautions before using.)
MOUNTING PRECAUTIONS
• Use the GOT in the environment that satisfies the general specifications
described in this manual. Not doing so can cause an electric shock, fire,
malfunction or product damage or deterioration.
• When mounting the GOT to the control panel, tighten the mounting screws in the
specified torque range. Undertightening can cause the GOT to drop, short circ uit
or malfunction. Overtightening can caus e a drop, short circuit or malfunc tion due
to the damage of the screws or the GOT.
WIRING PRECAUTIONS
• Be sure to shut off all phases of the external power supply used by the system
before wiring. Failure to do so may result in an electric shock, product damage or
malfunctions.
• Please make sure to ground FG terminal of the GOT power supply section by
applying 100 or less which is used exclusively for the GOT. Not doing so may
cause an electric shock or malfunction.
• Correctly wire the GOT power supply section after confirming the rated voltage
and terminal arrangement of the product. Not doing so can cause a fire or failure.
• Tighten the terminal screws of the GOT power supply section in the specified
torque range. Undertightening can cause a short circuit or malfunction.
Overtightening can cause a short circuit or malfunction due to the damage of the
screws or the GOT.
• Exercise care to avoid foreign matter such as chips and wire offcuts entering the
GOT. Not doing so can cause a fire, failure or malfunction.
WIRING PRECAUTIONS
• Plug the communication cable into the connector of the connected unit and
tighten the mounting and terminal screws in the specified torque range.
Undertightening can cause a short circuit or malfunction. Overtightening can
cause a short circuit or malfunction due to the damage of the screws or unit.
TEST OPERATION
PRECAUTIONS
• Before performing the test operations of the user creation monitor screen (such as
turning ON or OFF bit device, changing the word device current value, changing
the settings or current values of the timer or counter), read through the manual
carefully and make yourself familiar with the operation method.
During test operation, never change the data of the devices which are used to
perform significant operation for the sys tem. False output or malfunction can
cause an accident.
STARTUP/MAINTENANCE
PRECAUTIONS
• When power is on, do not touch the terminals.
Doing so can cause an electric shock or malfunction.
• Connect the battery correctly.
Do not discharge, disassemble, heat, short, solder or throw the battery into the fi re.
Incorrect handling may cause the battery to generate heat, burst or take fire,
resulting in injuries or fires.
• Before starting cleaning or terminal screw retightening, always switch off the
power externally in all phases. Not switching the power off in all phases can cause
a unit failure or malfunction . Undertightening can cau se a short circuit or
malfunction. Overtightening can cause a short circuit or malfunction due to the
damage of the screws or unit.
STARTUP/MAINTENANCE
PRECAUTIONS
• Do not disassemble or modify the unit.
Doing so can cause a failure, malfunction, injury or fire.
• Do not touch the conductive and electronic parts of the unit directly.
Doing so can cause a unit malfunction or failure.
• The cables connected to the unit must be run in ducts or clamped.
Not doing so can cause the unit or cable to be damaged due to the dangling,
motion or accidental pulling of the cables or can cause a malfunction due to a
cable connection fault.
• When unplugging the cable connected to the unit, do not hold and pull the cable
portion. Doing so can cause the uni t or cable to be damaged or can cause a
malfunction due to a cable connection fault.
• Do not drop or apply any impact to the battery.
If any impact has been applied, discard the battery and never use it.
The battery may be damaged by the drop or impact.
• Before touching the unit, always touch grounded metal, etc. to discharge static
electricity from human body, etc.
Not doing so can cause the unit to fail malfunction.
DISPOSAL PRECAUTIONS
• When disposing of the product, handle it as industrial waste.
TRANSPORTATION
PRECAUTIONS
• Before transporting the GOT, turn the GOT power on and check that the battery
voltage status is normal on the Time setting & display screen (utilities screen). In
addition, confirm that the adequate battery life remains on the rating plate.
Transporting the GOT with the low battery v oltage or the battery the reached
battery life may unstabilize the backup data unstable during transportation.
• Make sure to transport the GOT main unit and/or relevant unit(s) in the manner
they will not be exposed to the impact exceeding the impact resistance
described in the general specifications of this manual, as they are precision
devices. Failure to do so may cause the unit to fail.
Check if the unit operates correctly after transportation.
Compliance with EC directive (CE Marking)
This note does not guarantee that an entire mechanical module produced in
accordance with the contents of this note will comply with the following standards.
Compliance to EMC directive for the entire mechanical module should be checked by
the user / manufacturer. For more details please contact the local Mitsubishi Electric
sales site.
Requirement for Compliance with EMC directive
The following products have shown compliance through direct testing (to the
identified standards) and design analysis (forming a technical construction file) to the
European Directive for Electromagnetic Compatibility (89/336/EEC) when used as
directed by the appropriate documentation.
Type :Programmable Controller (Open Type Equipment)
Standard Remark
Compliance with all relevant aspects of the
EMI
standard.
EN61131-2 : 2003
Programmable
controllers- Equipment,
requirement and tests
For more details please contact the local Mitsubishi Electric sales site.
Notes for compliance to EMC regulation
1) General notes on the use of communication cables
Any device which utilizes a data communication function is susceptible to the
wider effects of local EMC noise. Therefore, when installing any communication
cables care should always be taken with the routing and location of those c ables.
The GOT units identified on the previous chapter are compliant with the EMC
requirement when the following communication cables are used.
GOT Unit Existing Cables User Made Cables
GT1045-QSBD
and
GT1040-QBBD
Ex.1
F = Ferrite core
Ex. NEC TOKIN - ESD-R-17S or similar
Programmable
controller
(Radiated Emissions)
Compliance with all relevant aspects of the
standard.
EMS
(ESD, RF electromagnetic field, EFTB, Surge, RF
conducted disturbances and Power frequency
magnetic field)
GT01-C30R4-8P
modified as
shown in EX.1
(9.84inch)
140mm
(5.51inch)
Those cables need to be independently
tested by the user to demonstrate EMC
compatibility when they are used with
Mitsubishi GOT unit and FX
Programmable Controllers.
GT01-C30R4-8P
F F F
Comes equipped
Added by user
Added by user
100mm250mm
(3.93inch)
3U
GOT units
2) General notes on Power supply
The GT1045-QSBD and GT1040-QBBD unit
requires an additional ferrite filter to be
attached to the 24V DC power supply
cables. The filter should be attached in a
similar manner as shown in the figure
opposite, i.e. the power cables are wrapped
around the filter. However, as with all EMC
situations the more correctly applied
precautions the better the systems Electromagnetic Compatibility. The ferrite
recommended is a TDK ZCAT3035-1330 or
similar. The ferrite should be placed as near
to the 24V DC terminals of the GT1045QSBD and GT1040-QBBD as possible
(which should be within 75mm of the GOT
terminal).
Associated Manuals
The following manuals are relevant to this product. When these loose manuals are
required, please consult with our local distributor.
Manual name Contents
Describes the GT10 hardware-relevant
GT10 User's Manual
(sold separately)
GOT1000 Series
Connection Manual
1/3, 2/3, 3/3
(sold separately)
GT Designer2 Version2
Basic Operation/Data
Transfer Manual
(For GOT1000 Series)
(sold separately)
GT Designer2 Version2
Screen Design Manual
(For GOT1000 Series)
1/3, 2/3, 3/3
(sold separately)
*1 Stored in the GT Works 2/GT Designer2 in PDF format.
For details of a PLC to be connected, refer to the PLC user's manual respectively.
content such as part names, external
dimensions, mounting, power supply
wiring, specifications, and introduction
to option devices
Describes system configurations of the
connection method applicable to
GOT1000 series and cable creation
*1
method
Describes methods of the GT
Designer2 installation operation, basic
operation for drawing and transmitting
data to GOT1000 series
*1
Describes specifications and settings
of the object functions used in GT
Designer2
*1
Up to
75mm
(2.95inch)
TDK
Manual Number
(Model Code)
JY997D24701
(09R819)
SH-080532ENG
(1D7M26)
SH-080529ENG
(1D7M24)
SH-080530ENG
(1D7M25)
Bundled Items
Model Name Remark
GT1045-QSBD
GT1040-QBBD
Panel Mounting Bracket (with M4 × 20 screws) 4
Panel Mounting Packing 1
GT10 General Description (This manual) 1
Explanation of the GOT model name
GT10 4 0 -
GOT main unit
(The maintenance supplies below are packed with the product.)
Maintenance Supplies Quantity
* * * *
Power type
Panel color type
Display device type
Resolution
Display color type
Screen size type
GOT1000 series GT10
D:24VDC
L:5VDC
B:Black
S:STN color
L:STN
B:STN
Q:320 × 240(QVGA)
Blank:less than 320 × 240
5:256 colors supported
0:Monochrome(black/white)
5:5.7"
4:4.7"
3:4.5"
2:3.7"
monochrome(black/white)
monochrome(blue/white)
1. Specifications
1.1 General Specifications
Item
Operating ambient
temperature
Display section 0 to 50°C
Other than display section 0 to 55°C (When mounted horizontally), 0 to 50°C (When mounted vertically)
Storage ambient temperature -20 to 60°C
Operating ambient humidity 10 to 90% RH, non-condensing (The wet bulb temperature is 39°C or less.)
Storage ambient humidity 10 to 90% RH, non-condensing (The wet bulb temperature is 39°C or less.)
Vibration resistance
Shock resistance
Operating atmosphere
Operating altitude
*1
Conforms to JIS
B3502 and
IEC61131-2
Conforms to JIS B3502, IEC 61131-2 (147m/s
Must be free of lamp black, corrosive gas, flammable gas, or excessive amount of electroconductive dust particles and
must be no direct sunlight. (Same as for saving)
2000 m (6562 ft) max.
Under intermittent
vibration
Under continuous
vibration
Installation location Inside control panel
Overvoltage category
Pollution degree
*3
*2
II or less
2 or less
Cooling method Self-cooling
Grounding Class D grounding (100Ω or less). To be connected to the panel when grounding is not possible
*1 Do not use or store the GOT under pressure higher than the atmospheric pressure of al titude 0m (0ft.). Failure to observe this instruction may cause a malfunction.
*2 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power distribution network and the
machinery within the premises.
Category II applies to equipment for which electrical power is supplied from fixed facilities.
The surge voltage withstand level for up to the raged voltage of 300 V is 2500 V.
*3 This index indicates the degree to which conductive material is generated in t he environment where the equipment is used.
In pollution degree 2, only non-conductive pollution occurs but temporary conductivity may be produced due to condensation.
1.2 Performance Specifications
Item
Type STN color liquid crystal STN monochrome (white/blue) liquid crystal
Screen size 4.7"
Resolution 320 × 240 dots (Horizontal format)
Display size W96(3.77) × H72(2.83) [mm](inch) (Horizontal format)
Display character 16-dot standard font: 40 characters × 15 lines, 12-dot standard font: 53 characters × 20 lines (Horizontal format)
Display
Display color 256 colors Monochrome (white/blue), 16 scales
*1
section
Display angle
Left/Right: 50 degrees, Top: 40 degrees, Bottom: 70 degrees
(Horizontal format)
Contrast adjustment 16-level adjustment
Intensity of LCD only
2
] 300 [cd/m2]
150 [cd/m
Life Approx. 50,000h. (Time for display intensity to become 1/5 at operating ambient temperature of 25°C)
Backlight LED Backlight off/screen saving time can be set.
Number of touch keys Maximum 50 keys/screen (Matrix resistive film touch panel)
Key size Minimum 16 × 16 dots (per key)
Touch
Simultaneous pressing of
panel
two (or more) areas
(2-point press)
Enable
Life 1 million times or more (operating force 0.98N max.)
Memory
User memory
Life
(Number of write times)
*2
Flash memory ROM (Internal), for storing project data (3M bytes or less) and OS
100,000 times
Battery GT11-50BAT lithium battery
Backup target Clock data, alarm history and recipe data
Life Approx. 5 years (Operating ambient temperature of 25)
Buzzer output
(a buzzer that sounds when touch
keys are pressed)
Environmental protective structure
Single tone (LONG/ SHORT/ OFF adjustable)
*3
Equivalent to IP67 (JEM1030) (front section)
External dimensions W139(5.47) × H112(4.4) × D41(1.61)[mm](inch) (Excluding mounting fixtures) (Horizontal format)
GT1045-QSBD GT1040-QBBD
Specifications
GT1045-QSBD/GT1040-QBBD
Frequency Acceleration Half-amplitude Sweep Count
5 to 9Hz -- 3.5mm
9 to 150Hz 9.8m/s
5 to 9Hz -- 1.75mm
9 to 150Hz 4.9m/s
2
, 11 ms, Sine half-wave pulse, 3 times each in the X, Y, and Z directions.)
2
2
--
--
10 times each in X,
Y and Z directions
Specifications
Left/Right: 45 degrees, Top: 20 degrees, Bottom: 40 degrees
(Horizontal format)
Specifications
Built-in
interface
RS-422
RS-232
USB
Item
RS-422 1ch
GT1045-QSBD GT1040-QBBD
Transmission speed: 115,200/57,600/38,400/19,200/9,600/4,800bps
Connector shape : D-sub 9-pin (Female)
Application : PLC communication
RS-232 1ch
Transmission speed : 115,200/57,600/38,400/19,200/9,600/4,800bps
Connector shape : D-sub 9-pin (Male)
Application : PLC communication, bar code read er connection, PC communication
USB (Full Speed 12Mbps) 1ch
Connector shape: Mini-B (Receptacle)
Application: PC communication (Project data upload/download, OS installation, transparent function)
(Project data upload/download, OS installation, transparent function)
GT10-50FMB For connecting GT10-50FMB memory board
Panel cutting dimensions W130 (5.11”) × H103(4.05”) [mm] (inch) (Horizontal format)
Weight 0.45kg (Excluding mounting fixtures)
Compatible software package GT Designer2 Version 2.85P or later
*1 Bright dots (always lit) and dark dots (unlit) may appear on a liquid crystal display panel. It is impossible to completely avoid this symptom, as the liquid crystal display
comprises of a great number of display elements. Flickers may be observed depending on the display color.
Please note that these dots appear due to its characteristic and are not caused by product defect.
When the same screen is displayed for a long time, an incidental color or partial discoloration is generated on the screen due to heat damage, and it may not disappear.
To prevent heat damage, the screen saver function is effective.
For details on the screen saver function, refer to the following.
→ GT10 User's Manual
*2 ROM in which new data can be written without deleting the written data.
*3 Note that this does not guarantee all users' operation environment.
1.3 Power Supply Specifications
(For details on power supply wiring, such as the allowable cable size and tightening
torque, refer to the additional manual, "GT10 User's Manual".)
Item
Input power supply
voltage
Fuse (built-in, not
exchangeable)
Power
consumption,
(At backlight off)
GT1045-QSBD GT1040-QBBD
24VDC (+10% -15%)
1.0A
3.6W (150mA/24VDC) or less,
(2.9W (120mA/24VDC) or less)
Specifications
Inrush current 15A or less (26.4VDC) 2ms
Permissible
instantaneous
power failure time
Noise immunity
Dielectric withstand
voltage
Insulation
resistance
*1 The GOT continues to operate even upon 5ms or shorter instantaneous
power failure.
The GOT stops operating if there is extended power failure or voltage drop,
while it automatically resumes operation as soon as the power is restored.
Within 5ms
*1
Noise voltage: 1000Vp-p, Noise width: 1µs (by noise
simulator of 30 to 100Hz noise frequency)
500VAC for 1 minute (across power supply terminals and
earth)
10MΩ or larger by insulation resistance tester (across power
supply terminals and earth)
This manual confers no industrial property rights or any rights of any other kind,
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
Warranty
Mitsubishi will not be held liable for damage caused by factors found not to be
the cause of Mitsubishi; opportunity loss or lost profits caused by faults in the
Mitsubishi products; damage, secondary damage, accident compensation
caused by special factors unpredictable by Mitsubishi; damages to products
other than Mitsubishi products; and to other duties.
For safe use
•
This product has been manufactured as a general-purpose part for general
industries, and has not been designed or manufactured to be incorporated in
a device or system used in purposes related to human life.
Before using the product for special purposes such as nuclear power, electric
•
power, aerospace, medicine or passenger movement vehicles, consult with
Mitsubishi Electric.
•
This product has been manufactured under strict quality control. However
when installing the product where major accidents or losses could occur if the
product fails, install appropriate backup or failsafe functions in the system.
HEAD OFFICE
: TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310,
JAPAN
HIMEJI WORKS