Mitsubishi FX3U User Manual

JY997D18801K(ENGLISH)
FX3U SERIES PROGRAMMABLE
CONTROLLERS
HARDWARE MANUAL
Manual Number JY997D18801
Revision K
Date May 2011
This manual describes the part names, dimensions, mounting, cabling and specifications for the product. This manual is extracted from FX3U Series User's Manual - Hardware Edition. Refer to FX3U Series User's Manual - Hardware Edition for more details. Before use, read this manual and manuals of relevant products fully to acquire proficiency in the handling and operating the product. Make sure to learn all the product information, safety information, and precautions. And, store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward it to the end user. Registration The company name and the product name to be described in this manual are the registered trademarks or trade marks of each company.
Effective May 2011 Specifications are subject to change without notice.
© 2005 Mitsubishi Electric Corporation

Safety Precaution (Read these precautions before use.)

This manual classifies the safety precautions into two categories:
and .
Indicates that incorrect handling may cause hazardous conditions, resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous conditions, resulting in medium or slight personal injury or physical damage.
Depending on the circumstances, procedures indicated by may also cause severe injury. It is important to follow all precautions for personal safety.
.
STARTUP AND MAINTENANCE PRECAUTIONS
Do not touch any terminal while the PLC's power is on. Doing so may cause electric shock or malfunctions.
Before cleaning or retightening terminals externally cut off all phases of the power supply. Failure to do so may cause electric shock.
STARTUP AND MAINTENANCE PRECAUTIONS
Use the battery for memory backup correctly in FX3U Series User's Manual - Hardware Edition.
- Use the battery only for the specified purpose.
- Connect the battery correctly.
- Do not charge, disassemble, heat, put in fire, short-circuit,
connect reversely, weld, swallow or burn the battery, or apply excessive forces (vibration, impact, drop, etc.) to the battery.
- Do not store or use the battery at high temperatures or
expose to direct sunlight.
- Do not expose to water, bring near fire or touch liquid
leakage or other contents directly.
- Incorrect handling of the battery may cause heat excessive
generation, bursting, ignition, liquid leakage or deformation, and lead to injury, fire or failures and malfunctions of facilities and other equipment.
Before modifying or disrupting the program in operation or running the PLC, carefully read through this manual and the associated manuals and ensure the safety of the operation. An operation error may damage the machinery or cause accidents.
STARTUP AND MAINTENANCE PRECAUTIONS
Turn off the power to the PLC before attaching or detaching the memory cassette. If the memory cassette is attached or detached while the PLC's power is on, the data in the memory may be destroyed, or the memory cassette may be damaged.
Do not disassemble or modify the PLC. Doing so may cause fire, equipment failures, or malfunctions. For repair, contact your local Mitsubishi Electric distributor.
Turn off the power to the PLC before connecting or disconnecting any extension cable. Failure to do so may cause equipment failures or malfunctions.
Turn off the power to the PLC before attaching or detaching the following devices. Failure to do so may cause equipment failures or malfunctions.
- Display module, peripheral devices, expansion boards, and
special adapters
- Connector conversion adapter, extension blocks, and FX
Series terminal blocks
- Battery and memory cassette
DISPOSAL PRECAUTIONS
Please contact a certified electronic waste disposal company for the environmentally safe recycling and disposal of your device. When disposing of batteries, separate them from other waste according to local regulations. (For details of the Battery Directive in EU countries, refer to FX3U Series User's Manual - Hardware Edition.)
TRANSPORTATION AND STORAGE PRECAUTIONS
Before transporting the PLC, turn on the power to the PLC to check that the BATT LED is off. If the PLC is transported with the BATT LED on or the battery exhausted, the battery-backed data may be unstable during transportation.
TRANSPORTATION AND STORAGE PRECAUTIONS
The PLC is a precision instrument. During transportation, avoid impacts larger than those specified in Section 2.1. Failure to do so may cause failures in the PLC. After transportation, verify the operations of the PLC.
When transporting lithium batteries, follow required transportation regulations. (For details of the regulated products, refer to FX3U Series User's Manual - Hardware Edition.)

Marine standard

Please consult with Mitsubishi Electric for the information on marine standard practices and the corresponding types of equipment.

Certification of UL, cUL standards

FX3U series main units, FX3U series special adapters and FX2N series input/output extension units/blocks supporting UL, cUL standards are as follows:
UL, cUL file number :E95239 Models : MELSEC FX3U series manufactured
Models : MELSEC FX2N series manufactured
FX3U-MR/ES(-A) FX3U-MT/ES(-A) FX3U-MT/ESS Where  indicates:16,32,48,64,80,128 FX3U-MR/DS FX3U-MT/DS FX3U-MT/DSS Where  indicates:16,32,48,64,80 FX3U-MR/UA1 FX3U-MS/ES Where  indicates:32,64 FX3U-232ADP(-MB) FX3U-485ADP(-MB) FX3U-4AD-ADP FX3U-4DA-ADP FX3U-3A-ADP FX3U-4AD-PT-ADP FX3U-4AD-PTW-ADP FX3U-4AD-PNK-ADP FX3U-4AD-TC-ADP
FX3U-4HSX-ADP FX3U-2HSY-ADP FX3U-CF-ADP
FX2N-ER-ES/UL FX2N-ET-ESS/UL Where  indicates:32,48 FX2N-48ER-DS FX2N-48ET-DSS FX2N-48ER-UA1/UL FX2N-8ER-ES/UL FX2N-8EX-ES/UL FX2N-8EYR-ES/UL FX2N-8EYR-S-ES/UL FX2N-8EYT-ESS/UL FX2N-8EX-UA1/UL FX2N-16EX-ES/UL FX2N-16EYR-ES/UL FX2N-16EYT-ESS/UL FX2N-16EYS

Compliance with EC directive(CE Marking )

This document does not guarantee that a mechanical system including this product will comply with the following standards. Compliance to EMC directive and LVD directive of the entire mechanical system should be checked by the user / manufacturer. For more details please contact the local Mitsubishi Electric sales site.

Requirement for Compliance with EMC directive

The following products have shown compliance through direct testing (of the identified standards below) and design analysis (through the creation of a technical construction file) to the European Directive for Electromagnetic Compatibility (2004/108/EC) when used as directed by the appropriate documentation.
Attention
This product is designed for use in industrial applications.
Note
Manufactured by: Mitsubishi Electric Corporation 2-7-3 Marunouchi, Chiyoda- ku, Tokyo, 100-8310 Japan
Manufactured at: Mitsubishi Electric Corporation Himeji Works 840 Chiyoda-machi, Himeji, Hyogo, 670-8677 Japan
Authorized Representative in the European Community: Mitsubishi Electric Europe B.V. Gothaer Str. 8, 40880 Ratingen, Germany.
Type : Programmable Controller (Open Type Equipment) Models : MELSEC FX3U series manufactured
from May 1st, 2005 FX3U-MR/ES(-A)
from June 1st, 2005 FX3U-232ADP FX3U-485ADP
from November 1st, 2005 FX3U-MT/ES(-A)
from February 1st, 2006 FX3U-128MR/ES(-A) FX3U-128MT/ES(-A)
from April 1st, 2007 FX3U-232ADP-MB FX3U-485ADP-MB from December 1st, 2007 FX3U-4AD-PTW-ADP
from June 1st, 2009 FX3U-3A-ADP FX3U-CF-ADP from August 1st, 2010 FX3U-8AV-BD from September 1st, 2010
from May 1st, 2011
Standard Remark
EN61131-2:2007
Programmable controllers
-Equipment requirements and tests
Models : MELSEC FX2N series manufactured
from July 1st, 1997 FX2N-ER-ES/UL FX2N-ET-ESS/UL
from April 1st, 1998 FX from August 1st, 1998 FX2N-48ER-UA1/UL from August 1st, 2005 FX
from September 1st, 2010 For the products above, PLCs manufactured
before March 31st, 2002 are compliant with EN50081-2 (EN61000­6-4) and EN50082-2 from April 1st, 2002 to April 30th, 2006 are compliant with EN50081­2 (EN61000-6-4) and EN61131-2:1994+A11:1996+A12:2000 after May 1st, 2006 are compliant with EN61131-2:2007
Where  indicates:16,32,48,64,80 FX3U-4HSX-ADP FX3U-2HSY-ADP FX3U-FLROM-16 FX3U-FLROM-64L FX3U-7DM
FX3U-4AD-ADP FX3U-4DA-ADP FX3U-4AD-PT-ADP FX3U-4AD-TC-ADP FX3U-232-BD FX3U-422-BD FX3U-485-BD FX3U-USB-BD FX3U-FLROM-64 FX3U-CNV-BD
FX3U-MT/ESS Where  indicates:16,32,48,64,80
FX3U-128MT/ESS FX3U-MR/DS FX3U-MT/DS FX3U-MT/DSS Where  indicates:16,32,48,64,80
FX3U-4AD-PNK-ADP
FX3U-MR/UA1 FX3U-MS/ES Where  indicates:32,64 FX3U-FLROM-1M
Compliance with all relevant aspects of the standard. EMI
Radiated Emission
Conducted Emission
EMS
Radiated electromagnetic field
Fast Transient burst
Electrostatic discharge
High-energy surge
Voltage drops and interruptions
Conducted RF
Power frequency magnetic field
Where  indicates:32,48 FX2N-16EX-ES/UL FX2N-16EYR-ES/UL FX2N-16EYT-ESS/UL
2N-48ER-DS FX2N-48ET-DSS
2N-8ER-ES/UL FX2N-8EX-ES/UL
FX2N-8EYR-ES/UL FX2N-8EYT-ESS/UL FX2N-8EYR-S-ES/UL
Standard Remark
EN61000-6-4:2007
- Generic emission standard
Industrial environment
EN50081-2:1993
Electromagnetic compatibility
EN50082-2:1995
Electromagnetic compatibility
- Generic immunity standard
Industrial environment
EN61131-2:1994 /A11:1996 /A12:2000
Programmable controllers
-Equipment requirements and tests
EN61131-2:2007
Programmable controllers
-Equipment requirements and tests
Compliance with all relevant aspects of the standard.
Emission-Enclosure port
Emission-Low voltage AC mains
port
Emission-Telecommunications/ network port
Compliance with all relevant aspects of the standard.
RF immunity
Fast Transients
ESD
Conducted
Power magnetic fields
Compliance with all relevant aspects of the standard.
Radiated electromagnetic field
Fast transient burst
Electrostatic discharge
Damped oscillatory wave
Compliance with all relevant aspects of the standard. EMI
Radiated Emission
Conducted Emission
EMS
Radiated electromagnetic field
Fast Transient burst
Electrostatic discharge
High-energy surge
Voltage drops and interruptions
Conducted RF
Power frequency magnetic field

Requirement for Compliance with LVD directive

The following products have shown compliance through direct testing (of the identified standards below) and design analysis (through the creation of a technical construction file) to the European Directive for Low Voltage (2006/95/EC) when used as directed by the appropriate documentation.
Type : Programmable Controller (Open Type Equipment) Models : MELSEC FX3U series manufactured
from May 1st, 2005 FX3U-MR/ES(-A)
from November 1st, 2005 FX3U-MT/ES(-A)
from February 1st, 2006 FX3U-128MR/ES(-A)
from September 1st, 2010
Standard Remark
EN61131-2:2007
Programmable controllers
-Equipment requirements and tests
Where  indicates:16,32,48,64,80
FX3U-MT/ESS Where  indicates:16,32,48,64,80
FX3U-128MT/ES(-A) FX3U-128MT/ESS FX3U-MR/DS Where  indicates:16,32,48,64,80 FX3U-MR/UA1 FX3U-MS/ES Where  indicates:32,64
The equipment has been assessed as a component for fitting in a suitable enclosure which meets the requirements of EN61131-2:2007
Models :MELSEC FX2N series manufactured
from July 1st, 1997 FX2N-ER-ES/UL FX2N-ET-ESS/UL
from April 1st, 1998 FX2N-48ER-DS from August 1st, 1998 FX2N-48ER-UA1/UL from August 1st, 2005 FX2N-8ER-ES/UL FX2N-8EYR-ES/UL from September 1st, 2010
For the products above, PLCs manufactured before March 31st, 2002 are compliant with IEC1010-1 from April 1st, 2002 to April 30th, 2006 are compliant with EN61131­2:1994+A11:1996+A12:2000 after May 1st, 2006 are compliant with EN61131-2:2007
Where  indicates:32,48 FX2N-16EYR-ES/UL
FX2N-8EYR-S-ES/UL
Standard Remark
IEC1010-1:1990 /A1:1992
Safety requirements for electrical equipment for measurement, control, and laboratory use
- General requirements
EN61131-2:1994 :2007 /A12:2000 /A11:1996
Programmable controllers
- Equipment requirements and tests
The equipment has been assessed as a component for fitting in a suitable enclosure which meets the requirements of IEC 1010-1: 1990+A1:1992
The equipment has been assessed as a component for fitting in a suitable enclosure which meets the requirements of EN61131-2: 1994+A11:1996+A12:2000, :2007

Caution for compliance with EC Directive

Installation in Enclosure
Programmable logic controllers are open-type devices that must be installed and used within conductive control boxes. Please use the FX3U Series programmable logic controllers while installed in conductive shielded control boxes. Please secure the control box lid to the control box (for conduction). Installation within a control box greatly affects the safety of the system and aids in shielding noise from the programmable logic controller.
Caution for Analog Products in use
The analog special adapters have been found to be compliant to the European standards in the aforesaid manual and directive. However, for the very best performance from what are in fact delicate measuring and controlled output device Mitsubishi Electric would like to make the following points; As analog devices are sensitive by nature, their use should be considered carefully. For users of proprietary cables (integral with sensors or actuators), these users should follow those manufacturers installation requirements. Mitsubishi Electric recommend that shielded cables should be used. If NO other EMC protection is provided, then users may experience temporary induced errors not exceeding +10%/-10% in very heavy industrial areas. However, Mitsubishi Electric suggest that if adequate EMC precautions are followed with general good EMC practice for the users complete control system, users should expect normal errors as specified in this manual.
- Sensitive analog cable should not be laid in the same trunking or cable conduit as high voltage cabling. Where possible users should run analog cables separately.
- Good cable shielding should be used. When terminating the shield at Earth - ensure that no earth loops are accidentally created.
- When reading analog values, EMC induced errors can be smoothed out by averagin g the readings. This can be achieved either through functions on the analog special adapter/block or through a users program in the FX3U Series PLC main unit.
Associated manuals
FX3U Series PLC (main unit) comes with this document (hardware manual). For a detailed explanation of the FX3U Series hardware and information on instructions for PLC programming and special extension unit/block, refer to the relevant documents.
Manual name Manual No. Description
FX3U Series User's Manual
- Hardware Edition
FX3G/FX3U/ FX3UC Series Programming Manual
- Basic & Applied Instruction Edition
MELSEC-Q/L/F Structured Programming Manual (Fundamentals)
FXCPU Structured Programming Manual [Device & Common]
FXCPU Structured Programming Manual [Basic & Applied Instruction]
FXCPU Structured Programming Manual [Application Functions]
FX Series User’s Manual - Data Communication Edition
FX3G/FX3U/ FX3UC Series User's Manual
- Analog Control Edition
FX3G/FX3U/
3UC Series
FX User's Manual
- Positioning Control Edition
How to obtain manuals
For the necessary product manuals or documents, consult with the Mitsubishi Electric dealer from where you purchase your product.
JY997D16501
MODEL CODE:
09R516
JY997D16601
MODEL CODE:
09R517
SH-080782
MODEL CODE:
13JW06
JY997D26001
MODEL CODE:
09R925
JY997D34701
MODEL CODE:
09R926
JY997D34801
MODEL CODE:
09R927
JY997D16901
MODEL CODE:
09R715
JY997D16701
MODEL CODE:
09R619
JY997D16801
MODEL CODE:
09R620
Explains FX3U Series PLC specification details for I/O, wiring, installation, and maintenance.
Describes PLC programming for basic/ applied instructions STL/ SFC programming and devices.
Programming methods, specifications, functions, etc. required to create structured programs.
Devices, parameters, etc. provided in structured projects of GX Works2.
Sequence instructions provided in structured projects of GX Works2.
Application functions provided in structured projects of GX Works2.
Explains N:N link, parallel link, computer link, no protocol communication by RS instructions/FX2N- 232IF.
Describes specifications for analog control and programming methods for FX3G/FX3U/FX3UC Series PLC.
Explains the specifications for positioning control of FX
3G/FX3U/FX3UC Series
and programming procedures

Incorporated Items

Check if the following product and items are included in the package:
Included Items
Main units
Product 1 unit
FX3U-16M to FX3U-128M
Dust proof protection sheet 1 sheet
Manuals [Japanese version, English version]
1 manual
each
Input/output extension units
FX2N-32E, FX2N-48E
Product 1 unit
Extension cable 1 cable
Input/output number label 1 sheet
Input/output extension blocks
FX2N-8E, FX2N-16E
Product 1 unit
Input/output number label 1 sheet

1. Outline

1.1 Part names

[1] [2] [3]
X40VS/S
X6 X10 X12 X14 X16 X20
X40VS/S
X6 X10 X12 X14 X16 X20
X5X0X1X2X3 X7
N24V
L X27X23 X25X15 X17 X21
X5X0X1X2X3 X7
N24V
L
[4]
[5]
[6] [7]
FX3U-48MR/ES
FX3U-48MR/ES
FX3U-48MFX
3U
FX3U-48MFX
3U
Y4Y2Y0
Y4Y2Y0
COM1
COM2Y3Y1
COM1
COM2Y3Y1
Y7 Y11 Y13Y5
COM3 Y15 Y17COM4 Y23 Y25 Y27Y21
Y7 Y11 Y13Y5
R
R
COM3 Y15 Y17COM4 Y23 Y25 Y27Y21
[8]
X24 X26X22
X24 X26X22
X13
X13 X11
X11
0312
645217
20 2422 23 2625
0312
645217
20 2422 23 2625
IN
IN
10 11 1312 1614 15 17
10 11 1312 1614 15 17
POWER
POWER
RUN
RUN
BATT
BATT
ERROR
ERROR
0312 645217
20 2422 23 2625
OUT
OUT
10 11 1312 1614 15 17 0312 645217
20 2422 23 2625
10 11 1312 1614 15 17
Y12Y10 Y16Y14 Y22Y20 Y26 COM5
Y24Y6
Y12Y10 Y16Y14 Y22Y20 Y26 COM5
Y24Y6
No. Name
[1] Top cover
[2] Battery cover
[3] Special adapter connecting hooks (2 places)
[4] Expansion board dummy cover
[5] RUN/STOP switch
[6] Peripheral device connecting connector
[7] DIN rail mounting hooks
[8] Model name (abbreviation)
[9] Input display LEDs (Red)
[10] Terminal block covers
[11] Extension device connecting connector cover
Operation status display LEDs
POWER Green On while power is on the PLC.
RUN Green On while the PLC is running.
[12]
BATT Red Lights when the battery voltage drops.
ERROR
Red Flashing when a program error occurs.
Red Lights when a CPU error occurs.
[13] Output display LEDs (Red)
[9] [10]
X27X23 X25X15 X17 X21
27
27
[11]
[12]
27
27
[13]
With terminal cover open
[2] [3]
X40VS/S
L X27X23 X25X15 X17 X21
L
FX3U-48MFX
3U
FX3U-48MFX
3U
COM1
COM1
R
R
[1]
N 24V
N 24V
FX3U-48MR/ES
FX3U-48MR/ES
COM2Y3Y1
COM2Y3Y1
Y4Y2Y0
Y4Y2Y0
X6 X10 X12 X14 X16 X20
X40VS/S
X6 X10 X12 X14 X16 X20
X5X0X1X2X3 X7
X5X0X1X2X3 X7
OUT
OUT
Y7 Y11 Y13Y5
COM3 Y15 Y17COM4 Y23 Y25 Y27Y21
Y7 Y11 Y13Y5
COM3 Y15 Y17COM4 Y23 Y25 Y27Y21
X24 X26X22
X24 X26X22
X13
X13 X11
X11
0312
645217
20 2422 23 2625
0312
645217
20 2422 23 2625
IN
IN
10 11 1312 1614 15 17
10 11 1312 1614 15 17
POWER
POWER
RUN
RUN
BATT
BATT
ERROR
ERROR
0312 645217
20 2422 23 2625
0312 645217
20 2422 23 2625 27
10 11 1312 1614 15 17
Y12Y10 Y16Y14 Y22Y20 Y26 COM5
Y24Y6
Y12Y10 Y16Y14 Y22Y20 Y26 COM5
Y24Y6
X27X23 X25X15 X17 X21
[4]
27
27
27
[3] [5]
No. Name
[1] Protective terminal covers (FX3U-M/-A is excluded)
[2] Power supply, Input (X) terminals
Terminal block mounting screws
[3]
(FX3U-16M terminal block cannot be installed/removed)
[4] Terminal names
[5] Output (Y) terminals

1.2 External dimensions and weight

2- 4.5-diam mounting holes (FX3U-16M , FX3U-32M ) 4- 4.5-diam mounting holes (FX FX3U-16M and FX3U-32M do not have the (*)-marked mounting holes.
N 24V
L X27X23 X25X15 X17 X21
N 24V
L
FX3U-48MR/ES
FX3U-48MFX
3U
FX3U-48MFX
3U
Y4Y2Y0
Y4Y2Y0
COM1
COM2Y3Y1
COM1
COM2Y3Y1
R
R
*
22
(0.87")
X40VS/S
X6 X10 X12 X14 X16 X20
X40VS/S
X6 X10 X12 X14 X16 X20
X5X0X1X2X3 X7
X13
X5X0X1X2X3 X7
X13 X11
X11
0312
0312
IN
IN
10 11 1312 1614 15 17
10 11 1312 1614 15 17
0312 645217
OUT
OUT
10 11 1312 1614 15 17 0312 645217
10 11 1312 1614 15 17
Y12Y10 Y16Y14 Y22Y20 Y26 COM5
Y12Y10 Y16Y14 Y22Y20 Y26 COM5
Y7 Y11 Y13Y5
COM3 Y15 Y17COM4 Y23 Y25 Y27Y21
Y7 Y11 Y13Y5
COM3 Y15 Y17COM4 Y23 Y25 Y27Y21
W1
W
3U
-48M , FX3U-64M ,FX3U-80M ,FX3U-128M )
2
*
*
X24 X26X22
X24 X26X22
X27X23 X25X15 X17 X21
645217
20 2422 23 2625
27
645217
20 2422 23 2625
27
POWER
POWER
RUN
RUN
BATT
BATT
ERROR
ERROR
20 2422 23 2625
27
20 2422 23 2625
27
Y24Y6
Y24Y6
*1 FX3U-32MR/UA1 uses 4-φ4.5 mounting holes.
*2 Except FX3U-32MR/UA1
Model name
W:
mm (inches)
mm (inches)
Direct mounting
hole pitches
FX3U-16M 130 (5.12”) 103 (4.06”) 0.6 (1.32lbs)
*3
FX3U-32M
150 (5.91”) 123 (4.85”) 0.65 (1.43lbs)
FX3U-48M 182 (7.17”) 155 (6.11”) 0.85 (1.87lbs)
*4
FX3U-64M
220 (8.67”) 193 (7.6”) 1.00 (2.2lbs)
FX3U-80M 285 (11.23”) 258 (10.16”) 1.20 (2.64lbs)
FX3U-128M
350 (13.78”) 323 (12.72”) 1.80 (3.96lbs)
*3 FX3U-32MR/UA1 is equivalent to FX3U-48M.
*4 FX3U-64MR/UA1 is equivalent to FX3U-80M.
Installation
35-mm-wid e DIN rail or Direct (screw) mo unti ng (M 4)
1
*
Unit:mm(inches)
90(3.55")
80(3.15")
Mounting hole pitches
86(3.39")
W1:
9(0.36")
MASS (Weight) kg (lbs)

2. Installation (general specifications)

As for installation of the input/output extension units/blocks, special adapters and expansion boards, refer to FX3U Series User's Manual
- Hardware Edition.
INSTALLATION PRECAUTIONS
Use the product within the generic environment specifications described in section 2.1 of this manual. Never use the product in areas with excessive dust, oily smoke, conductive dusts, corrosive gas (salt air, Cl2, H2S, SO2 or NO2), flammable gas, vibration or impacts, or exposed to high temperature, condensation, or rain and wind. If the product is used in such conditions, electric shock, fire, malfunctions, deterioration or damage may occur.
Do not touch the conductive parts of the product directly to avoid failure or malfunctions.
Install the product securely using a DIN rail or mounting screws.
Install the product on a flat surface. If the mounting surface is rough, undue force will be applied to the PC board, thereby causing nonconformities.
When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits. Failure to do so may cause fire, equipment failures or malfunctions.
Be sure to remove the dust proof sheet from the PLC's ventilation port when installation work is completed. Failure to do so may cause fire, equipment failures or malfunctions.
Connect the extension cables, peripheral device cables, input/ output cables and battery connecting cable securely to their designated connectors. Unsecured connection may cause malfunctions.
Turn off the power before attaching or detaching the following devices. Failure to do so may cause device failures or malfunctions.
- Peripheral devices, display modules, expansion boards and
special adapters
- Extension units/blocks and the FX Series terminal block
- Battery and memory cassette
INSTALLATION PRECAUTIONS
:
Connect the extension cables, peripheral device cables, input/ output cables and battery connecting cable securely to their designated connectors. Unsecured connection may cause malfunctions.
Turn off the power before attaching or detaching the following devices. Failure to do so may cause device failures or malfunctions.
- Peripheral devices, display modules, expansion boards and
special adapters
- Extension units/blocks and the FX Series terminal block
- Battery and memory cassette
WIRING PRECAUTIONS
Cut off all phases of the power supply externally before installation or wiring work in order to avoid damage to the product or electric shock.

2.1 Generic specifications

Item Specification
Ambient temperature
Ambient humidity
Vibration resistance
Shock resistance
Noise resistance
Dielectric withstand voltage
Insulation resistance
Grounding
Working atmosphere
Working altitude
*1 The criterion is shown in IEC61131-2.
*2 Dielectric withstand voltage and insulation resistance are
0 to 55°C (32 to 131°F) when operating and -25 to 75°C (-13 to 167°F) when stored
5 to 95%RH (no condensation) when operating
Accele-
Fre-
ration
quency
(Hz)
When
10 to 57 - 0.035
installed
*1
on DIN
57 to 150
rail
When
10 to 57 - 0.075
installed
57 to 150
directly
147 m/s2 Acceleration, Action time: 11ms, 3 times by
*1
half-sine pulse in each direction X, Y, and Z
By noise simulator at noise voltage of 1,000 Vp-p, noise width of 1 µs, rise time of 1 ns and period of 30 to 100 Hz
1.5kV AC for one minute
500V AC for one
*2
minute
5M or more by
*2
500V DC megger
Class D grounding (grounding resistance: 100 Ω or less) <Common grounding with a heavy electrical system is not allowed.>
Free from corrosive or flammable gas and excessive conductive dusts
*4
<2000m
amplitude
(m/s2)
4.9 -
9.8 -
Between each terminals and ground terminal
*3
shown in the following table.
Half
(mm)
Sweep Count for X, Y, Z: 10 times (80 min in each direction)
Terminal
Dielectric
strength
Insulation resistance
Main units, Input/output extension units/blocks
Between power supply terminal (AC power) and ground terminal
Between power supply terminal (DC power) and ground terminal
Between 24V DC service power supply connected to input terminal (24V DC) and ground terminal
Between input terminal (100V AC) and ground terminal
Between output terminal (relay) and ground terminal
Between output terminal (transistor) and ground terminal
Between output terminal (triac) and ground terminal
Expansion boards, Special adapters, Special function units/blocks
Between terminal of expansion board and ground terminal
Between terminal of special adapter and ground terminal
1.5 kV AC for one minute
500V AC for
one minute
500V AC for
one minute
1.5 kV AC for one minute
1.5 kV AC for one minute
500V AC for
one minute
1.5 kV AC for one minute
5M or more by 500V DC megger
Not allowed Not allowed
500V AC for
1min
5M or more by 500V DC megger
Special function unit/block Each manual
For dielectric with stand voltage test and insulation resistance test of each product, refer to the following manual.
Refer to FX3U Series User's Manual - Hardware Edition.
*3 For common grounding, refer to section 3.3.
*4 The PLC cannot be used at a pressure higher than the
atmospheric pressure to avoid damage.
Notes
When a dust proof sheet is supplied with an extension unit/ block, keep the sheet applied to the ventilation slits during installation and wiring work.
To prevent temperature rise, do not install the PLC on a floor, a ceiling or a vertical surface. Install it horizontally on a wall as shown in section 2.2.
Keep a space of 50 mm (1.97”) or more between the unit main body and another device or structure (part A). Install the unit as far away as possible from high-voltage lines, high-voltage devices and power equipment.

2.2 Installation location

-48MR/ES
12
12
Y10
COM3
Y17
COM4
Y21
X13
X14
12
12
Y10
COM3
Y17
COM4
Y21
X13
X14
Install the PLC in an envi ronment conforming to the generic specifications (section 2.1), installation precautions and notes.
For more details, refer to FX3U Series User's Manual - Hardware Edition.
Installation location in enclosure
Space in enclosure
Extension devices can be connected on the left and right sides of the main unit of the PLC. If you intend to add extension devices in the future, keep necessary spaces on the left and right sides.
Configuration without extension cable
A
FX
3U
A
Series
main
unit
A
A
A
-16EX
-16EYT
2N
2N
FX
FX
-ES/UL
-ESS/UL
50mm (1.97")
Configuration in 2 stages with extension cable
A
A
Another
equipment
-CNV-BC
A
2N
FX
Another equipment
FX3U Series
main unit
-4AD-ADP
3U
FX
Input/output
powered
-16EX extension
2N
FX
-ES/UL
A
A
unit
-16EX-ES/UL
-16EYT-ESS/UL
2N
2N
FX
FX
-10PG
-8AD
2N
2N
FX
FX
A
-4AD
-16EYR-ES/UL
2N
2N
FX
FX
Extension cable
0N
·FX
0N
·FX
A
Another
equipment
50mm (1.97")
A
-65EC
-30EC

2.2.1 Affixing The Dust Proof Sheet

The dust proof sheet should be affixed to the ventilation port before beginning the installation and wiring work.
For the affixing procedure, refer to the instructions on the
Be sure to remove the dust proof sheet when the installation and wiring work is completed.
dust proof sheet.

2.3 Procedures for installing to and detaching from DIN rail

The products can be installed on a DIN46277 rail [35mm (1.38”) wide]. This section explains the installations of the main units. For the input/output extension units/blocks and special adapters, refer to the following manual.
Refer to FX3U Series User’s Manual - Hardware Edition.

2.3.1 Installation

1) Connect the expansion boards and special adapters to the main
unit.
2) Push out all DIN rail mounting hooks (below fig.A)
C
2)
2)2)
A
3) Fit the up per edge of the DIN rail
mounting groove (right fig.C) onto the DIN rail.
4) Lock the DIN rail mounting hooks (below fig.D) while pressing the
PLC against the DIN rail.
X40VS/S
X6 X10 X12 X14
X16 X20
X24 X26X22
X40VS/S
X6 X10 X12 X14
X16 X20
X24 X26X22
X24 X26X22
X40VS/S
X6 X10 X12 X14 X16 X20
X24 X26X22
X40VS/S
X6 X10 X12 X14 X16 X20
N 24V
L X27X23 X25X15 X17 X21
N 24V
L X27X23 X25X15 X17 X21
X5X0X1X2X3 X7
X13
X5X0X1X2X3 X7
X13
X27X23 X25X15 X17 X21
X5X0X1X2X3 X7
X13
N 24V
L X27X23 X25X15 X17 X21
X5X0X1X2X3 X7
X13
N 24V
L
X11
X11
X11
X11
0 31 2
64 5217
20 2422 23 2625
0 31 2
64 5217
20 2422 23 2625
0312
645217
20 2422 23 2625
27
0312
645217
20 2422 23 2625
27
27
27 IN
IN
IN
IN
1011 1312
1011 1312
1011 1312 1614 15 17
1011 1312 1614 15 17
1614 15 17
1614 15 17
POWER
POWER
POWER
POWER
RUN
RUN
RUN
RUN
BATT
BATT
BATT
BATT
ERROR
ERROR
ERROR
ERROR
0312 645217
20 2422 23 2625
27 OUT
OUT
OUT
OUT
1011 1312 1614 15 17 0 31 2 64 5217
20 2422 23 2625
0 31 2 64 5217
20 2422 23 2625
0312 645217
20 2422 23 2625
27
27
Y4Y2Y0
Y4Y2Y0
Y4Y2Y0
Y4Y2Y0
Y7 Y11 Y13Y5
Y7 Y11 Y13Y5
Y7 Y11 Y13Y5
Y7 Y11 Y13Y5
1011 1312
1011 1312
1011 1312 1614 15 17
Y12Y10
Y12Y10
Y12Y10 Y16Y14 Y22Y20 Y26 COM5
Y12Y10 Y16Y14 Y22Y20 Y26 COM5
Y15 Y17
COM4
Y15 Y17
COM4
COM3
COM3
COM3 Y15 Y17COM4 Y23 Y25 Y27Y21
COM3 Y15 Y17COM4 Y23 Y25 Y27Y21
D
1614 15 17
1614 15 17
Y16Y14 Y22Y20 Y26 COM5
Y16Y14 Y22Y20 Y26 COM5
Y23 Y25 Y27Y21
Y23 Y25 Y27Y21
27
Y24Y6
Y24Y6
Y24Y6
Y24Y6
4)
FX3U-48M
FX3U-48M
FX3U-48M
FX3U-48M
COM1
COM1
COM1
COM1
COM2Y3Y1
COM2Y3Y1
COM2Y3Y1
COM2Y3Y1
R
R
R
R
D
4)

2.4 Procedures for installing directly (with M4 screws)

The product can be installed directly on the panel (with screws). This section explains the installation of the main units. As for the details of the installation/detaching for input extension
units/blocks and special adapters, refer to the following manual.
C
A
-48M
3U
FX
RUN
STOP
X40VS/S
X40VS/S
X5X0X1X2X3 X7
N24V
L X27X23 X25X15 X17 X21
X5X0X1X2X3 X7
N24V
L
FX3U-48M
FX3U-48M
Y4Y2Y0
Y4Y2Y0 COM1
COM1
COM2Y3Y1
COM2Y3Y1
Y7 Y11 Y13Y5
COM3 Y15 Y17COM4 Y23 Y25 Y27Y21
Y7 Y11 Y13Y5
COM3 Y15 Y17COM4 Y23 Y25 Y27Y21
R
R
2)
1
0
IN
11
10
FX
3U
-48M
-48MR/ES
3U
FX
X6 X10 X12 X14 X16 X20
X6 X10 X12 X14 X16 X20
X13
X13 X11
X11
0312
645217
0312
645217 IN
IN
1011 1312 1614 15 17
1011 1312 1614 15 17
0312 645217 OUT
OUT
1011 1312 1614 15 17
0312 645217
1011 1312 1614 15 17
Y12Y10 Y16Y14 Y22Y20 Y26 COM5
Y12Y10 Y16Y14 Y22Y20 Y26 COM5
27
26
25
24
23
22
21
20
7
6 5 4
3
2
17 16 15
14
13
12
POWER
RUN
BATT
ERROR
27
26
25
24
23 22 21
20 7
6
5
4 3 2
1
0
OUT
17
16
15
14
13 12
11
10
X24 X26X22
X24 X26X22
X27X23 X25X15 X17 X21
20 2422 23 2625
27
20 2422 23 2625
27
POWER
POWER
RUN
RUN
BATT
BATT
ERROR
ERROR
20
27
2223
24
2625
20 2422 23 2625
27
Y24Y6
Y24Y6
Refer to FX3U Series User's Manual - Hardware Edition.

2.4.1 Mounting hole pitches

Refer to the External Dimensions (section 1.2) for the product's mounting hole pitch informatio n. As for the details of the mounting hole pitches for extension unit/ block and special adapters, refer to the following manual.
Refer to FX3U Series User's Manual - Hardware Edition.

2.4.2 Installation

1) Make mounting holes in the mounting surface referring to the external dimensions diagram.
2) Fit the main unit (A in the right figure) based on the holes, and secure it with M4 screws (B in the right figure). The mounting hole pitches and number of screws depend on the product. Refer to the external dimensions diagram.
B
FX
FX
3U
3U
3U
3U
-48MFX
-48MFX
0
IN
1
2
10
3
11
4
12
5
13
6
14
7
15
20
16
21
17
22
23 24
25
26
OUT
0
POWER
27
POWER
1
2
10
3
11
RUN
4
12
RUN
5
13
6
14
BATT
7
15
BATT
20
16
21
ERROR
17
ERROR
22
23 24
2625
27
A
B
3. Power supply/input/output specifications
and examples of external wiring
As for the details of the power supply wiring and input/output wiring, refer to FX3U Series User's Manual - Hardware Edition.
DESIGN PRECAUTIONS
Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during external power supply problems or PLC failure. Otherwise, malfunctions may cause serious accidents.
1) Most importantly, have the following: an emergency stop
circuit, a protection circuit, an interlock circuit for opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the equipment at the upper and lower positioning limits).
2) Note that when the PLC CPU detects an error, such as a
watchdog timer error, during self-diagnosis, all outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output control block, output control may be disabled. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
3) Note that when an error occurs in a relay, triac or transistor
output device, the outpu t could be held either on or o ff. For output signals that may lead to serious accidents, external circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
DESIGN PRECAUTIONS
Do not bundle the control line together with or lay it close to the main circuit or power line. As a guideline, lay the control line at least 100mm (3.94") or more away from the main circuit or power line. Noise may cause malfunctions.
Install module so that excessive force will not be applied to the built-in programming connectors, power connectors or I/O connectors. Failure to do so may result in w ire damage/breakage or PLC failure.
Notes
Simultaneously turn on and off the power supplies of the main unit and extension devices.
Even if the AC power supply causes an instantaneous power failure for less than 10 ms, the PLC can continue to operate.
Even if the DC power supply causes an instantaneous power failure for less than 5ms, the PLC can continue to operate.
If a long-time power failure or an abnormal voltage drop occurs, the PLC stops, and output is turned off. When the power supply is restored, it will automatically restart (when the RUN input is on).
WIRING PRECAUTIONS
Cut off all phases of the power supply externally before installation or wiring work in order to avoid damage to the product or electric shock.
WIRING PRECAUTIONS
Connect the AC power supply to the dedicated terminals specified in this manual. If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out.
Do not wire vacant terminals externally. Doing so may damage the product .
Use class D grounding (grounding resistance of 100 or less) with a wire of 2mm2 or thicker on the grounding termina l of the
FX3U Series main unit. However, do not connect the ground terminal at the same point as a heavy electrical system.
When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits. Failure to do so may cause fire, equipment failures or malfunctions.
Make sure to properly wire to the terminal in accordance with the following precautions. Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or damage to the product.
- The disposal size of the cable end should follow the
dimensions described in the manual.
- Tightening torque should follow the specifications in the
manual.
Notes
Input/output wiring 50 to 100 m (164’1” to 328’1”) long will cause almost no problems of noise, but, generally, the wiring length should be less than 20 m (65’7”) to ensure the safety.
Extension cables are easily affected by noise. Lay the cables at a distance of at least 30 to 50 mm (1.19” to 1.97”) away from the PLC output and other power lines.

3.1 Wiring

3.1.1 Cable end treatment and tightening torque

For the terminals of FX3U series PLC, M3 screws are used. The electric wire ends should be treated as shown below. Tighten the screws to a torque of 0.5 to 0.8 N•m. Do not tighten terminal screws exceeding the specified torque. Failure to do so may cause equipment failures or malfuncti ons.
When one wire is connected to one term inal
6.2 mm (0.24") or less
6.2 mm (0.24") or less
φ3.2 (0.13")
φ3.2 (0.13")
Terminal screw
Terminal
Solderless terminal
<Reference>
Terminal
Manufacturer
JAPAN SOLDERLESS TERMINAL MFG CO LTD (JST)
Type No. Certification
FV1.25-B3A
UL Listed YA-1(JST)
FV2-MS3
Pressure
Bonding Tool
When two wires are connected to one terminal
6.2 mm (0.24") or less
6.2 mm (0.24") or less
φ3.2 (0.13")
6.3 mm(0.25") or more
φ3.2 (0.13")
6.3 mm(0.25") or more
Terminal screw
Terminal
Solderless terminal
<Reference>
Terminal
Manufacturer
JAPAN SOLDERLESS TERMINAL MFG CO LTD (JST)

3.1.2 Removal and installation of quick-release terminal block

Removal Unscrew the terminal block mounting screw [both right
Installation Place the terminal block in the specified position, and
Type No. Certification
FV1.25-B3A UL Listed YA-1(JST)
and left screws] evenly, and remove the terminal block.
tighten the terminal block mounting screw evenly [both right and left screws]. Tightening torque 0.4 to 0.5 N•m Do not tighten the terminal block mounting screws exceeding the specified torque. Failure to do so may cause equipment failures or malfunctions.
* Pay attention so that the center of the terminal block
is not lifted.
Pressure
Bonding Tool

3.2 Power supply specifications and example of external wiring

As for the details of the power sup ply specifications and example of external wiring, refer to the following manual.
Refer to FX3U Series User's Manual - Hardware Edition.
3.2.1 Power supply specifications
[Main unit, Input/output extension units]
Item
Specification
AC power type
DC power type
Supply voltage 100 - 240V AC 24 V DC
Allowable supply voltage range
Main unit
FX2N-32E, FX2N-48E
85 to 264V AC
16.8 to 28.8V DC
24V DC +20%,
-30%
Rated frequency 50/60Hz
Allowable instantaneous power failure time
FX3U-16M to
*7
32M
Power fuse
FX3U-48M to 128M
Operation can be continued upon occurrence of instantaneous power failure for 10 ms or less.
250V 3.15A
250V 5A
Operation can be continued upon occurrence of instantaneous power failure for 5
*4
ms or less.
FX2N-32E 250V 3.15A -
FX2N-48E 250V 5A 250V 5A
30A max. 5ms or
Rush current
Main unit
FX2N-32E, FX2N-48E
less/100V AC 65A max. 5ms or less/200V AC
40A max. 5ms or less/100V AC 60A max. 5ms or less/200V AC
35A max. 0.5ms or less/24V DC
-
FX3U-16M 30W 25W
FX3U-32M 35W 30W
FX3U-48M 40W 35W
Power consumption
*1
FX3U-64M 45W 40W
FX3U-80M 50W 45W
FX3U-128M
65W
FX2N-32E 30W(35VA)
FX2N-48E 35W(45VA) 30W
24V DC service power supply
FX3U-16M to 32M
FX3U-48M to 128M
*2
FX2N-32E 250mA
400mA or less
600mA or less
FX2N-48E 460mA
5V DC builtin power supply
Main unit 500 mA or less
FX2N-32E
*3
FX2N-48E
690mA or less
*1 Does not include the power consumption of extension units /
special extension units, and of the extension blocks / special extension blocks connected to those units. For the power (current) consumed by the extension units/ blocks for input/output, refer to FX3U Series User's Manual ­Hardware Edition. For the power consumed by the special extension units/blocks, refer to the appropriate manu al.
*2 When input/output extension blocks are connected, the 24V
DC service power supply is consumed by the blocks, and the
*6
*5
current value to be used by the main unit is reduced. The AC power (AC input) type and DC power type do not have a service power supply.
*3 Cannot be used to supply power to an external destination.
The power is supplied to input/output extension blocks, special extension blocks, special adapters and expansion boards. The following manual shows further information.
Refer to FX3U Series User’s Manual - Hardware Edition.
*4 When the supply voltage is 200 V AC, the time can be changed
to 10 to 100 ms by editing the user program.
*5 When supply voltage is DC 16.8-19.2V, the connectable
extension equipment decreases. The following manual shows further information.
Refer to FX3U Series User’s Manual - Hardware Edition.
*6 When attaching high-speed input/output special adapter
(FX3U-4HSX-ADP, FX3U-2HSY-ADP) and special function block (FX0N-3A, FX2N-2AD, FX2N-2DA), the number of connectable modules to the main unit is limited, due to the current consumption (internal 24V DC) at startup. The following manual shows further information.
Refer to FX3U Series User’s Manual - Hardware Edition.
*7 250V 5A is specified for the power fuse of FX3U-32MR/UA1.

3.2.2 Example of external wiring (AC power type)

100 to 240V AC power is supplied to the main unit and input/output extension units. For the details of wiring work, refer to section 3.1.
PLC
100 to 240V AC
Main unit
L
*
N
PL
Input/output extension unit
L
Fuse
MC
N
*Class D grounding
See section 3.3 for details.
DC AC
Power supply for loads connected to PLC output terminals
Breaker
Power on
MC
DC power supply
Emer­gency

3.2.3 Example of external wiring (DC power type)

24V DC power is supplied to the main unit and input/output extension unit. For the details of wiring work, refer to section 3.1.
PLC
24V DC
Main unit
Circuit protector
Input/output extension unit
*
Fuse
PL
MC
Power on
MC
Emer­gency
MCMC
* Class D grounding
See section 3.3 for details.
Power supply for loads connected to PLC output terminals

3.3 Grounding

Ground the PLC as stated below.
Perform class D grounding. (Grounding resistance: 100 Ω or less)
Ground the PLC independently if possible. If it cannot be grounded independently, ground it jointly as shown below.
Independent grounding
Another
PLC
equipment
(Best condition)
Another
PLC
equipment
Shared grounding
(Good condition)
Another
PLC
equipment
Common grounding
(Not allowed)
Use ground wires thicker than AWG14 (2 mm2).
Position the grounding point as close to the PLC as possible to
decrease the length of the ground wire.

3.4 Input specifications and external wiring

As for the details of the input specifications and external wiring, refer to the following manual.
Refer to FX3U Series User's Manual - Hardware Edition.

3.4.1 Input specifications (24V DC input type)

MCMC
Number of input points
Item Specification
FX2N-8ER
FX3U-16M, FX2N-8EX
FX3U-32M, FX2N-16EX,
2N
-32E
FX
FX3U-48M, FX2N-48E
FX3U-64M
32 points
FX3U-80M
40 points
FX3U-128M
64 points
4 points (8 points)
8 points
16 points
24 points
*1
Item Specification
Input connecting type Refer to FX3U Series
Input form
Input signal voltage
Input impedance
Input signal current
ON input sensitivity current
OFF input sensitivity current 1.5mA or less
Input response time Approx. 10ms
Input signal form
Input circuit insulation
Input operation display
*1 Each value inside ( ) indicates the number of occupied points.
Main units
Input/output extension unit
Main units
Input/output extension unit/block
Main units
Input/output extension unit/block
Main units
Input/output extension unit/block
AC power Type 24V DC +10%, -10%
DC power Type
AC power Type 24V DC +10%, -10%
DC power Type
X000 to X005 3.9k
X006, X007 3.3k
X010 or more
X000 to X005 6mA/24V DC
X006, X007 7mA/24V DC
X010 or more
X000 to X005 3.5mA or more
X006, X007 4.5mA or more
X010 or more
User's Manual ­Hardware Edition
24V DC +20%, -30%
24V DC +20%, -30%
4.3k (Does not apply to FX3U-16M.)
4.3k
5mA/24V DC (Does not apply to FX3U-16M.)
5mA/24V DC
3.5mA or more (Does not apply to FX3U-16M.)
3.5mA or more/24V DC
Sink input: No-voltage contact input NPN open collector transistor
Source input: No-voltage contact input PNP open collector transistor
Photocoupler insulation
LED on panel lights when photocoupler is driven.

3.4.2 Examples of 24V DC input wiring[AC power type]

1. Sink input type 2. Source input type
[1] [1]
Fuse
L
*
N
100 to 240V AC
S/S
0V
24V
X000 X001 X002 X003
[2] [2]
S/S
X000
*Class D grounding
See section 3.3 for details.
[1]:Main unit, Input/output extension unit (Common to both sink and source inputs)
[2]:Input/output extension block (Common to both sink and source inputs)
3-wire type
sensor
L
N
S/S
0V
24V
X000 X001 X002 X003
S/S
X000
Fuse
*
100 to 240V AC
3-wire type sensor

3.4.3 Examples of 24V DC input wiring[DC power type]

1.Sink input type 2.Source input type
[1] [1]
Fuse
*1
S/S
(0V)
*2
(24V)
X000 X001 X002 X003
[2] [2]
S/S
X000
*1 Class D grounding
See section 3.3 for details.
*2
Do not connect the (0V), (24V) terminals with others, since they are not available.
[1]:Main unit, Input/output extension unit (Common to both sink and source inputs)
[2]:Input/output extension block (Common to both sink and source inputs)
3-wire type sensor
S/S
(0V)
(24V)
X000 X001 X002 X003
S/S
X000
*1
*2
Fuse
24V DC24V DC
3-wire type sensor

3.4.4 Instructions for connecting input devices

1) In the case of no-voltage contact: The input current of this PLC is 5 to 7 mA/24V DC. Use input devices applicable to this minute current. If no-voltage contacts (switches) for large current are used, contact failure may occur.
<Example> Products of OMRON
LED
4Rp
15-Rp
15 k
or more
Model name
Models Z, V and D2RV
Model TL
)
(k
Rb
Rp
Type Model name
Operation switch
Photoelectric switch
Source input
0V
S/S
24V
Source input
X
S/S
24V
0V
X
LED
15 k
or more
Model A3P
Model E3S
Rb
Rp
Type
Microswitch
Proximity switch
2) In the case of input device with built-in series diode: The voltage drop of the series diode should be approx. 4 V or less. When lead switches with a series LED are used, up to two switches can be connected in series. Also make sure that the input current is over the input-sensing level while the switches are ON.
Sink input
24V
S/S
X
0V
3) In the case of input device with built-in parallel resistance: Use a device having a parallel resistance, Rp, of 15 kor more. When the resistance is less than 15 k, connect a bleeder resistance, Rb, obtained from the formula as shown in the following figure.
Rb
Sink input
24V
S/S
X
0V
4) In the case of 2-wire proximity switch: Use a two-wire proximity switch whose leakage current, , is
1.5 mA or less when the switch is off. When the current is 1.5 mA or more, connect a bleeder resistance, Rb, obtained from formula as shown in the following figure.
6
)
I
-1.5
(k
Source input
0V
Rb
2-wire proximity sensor
I
S/S
24V
Rb
2-wire proximity sensor
X
I
Rb
Sink input
24V
S/S
X
0V

3.4.5 Input specifications (100V AC input type)

Item Specification
Number of input points
Input connecting type
Input form
Input signal voltage
Input impedance
Input signal current
ON input sensitivity current
OFF input sensitivity current 1.7mA or less
Input response time
Input signal form Contact input
Input circuit insulation Photocoupler insulation
Input operation display
FX2N-8EX-UA1/UL
FX3U-32MR/UA1
FX2N-48ER-UA1/UL
FX3U-64MR/UA1
8 points
16 points
24 points
32 points
Refer to FX3U Series User's Manual - Hardware Edition
100V AC to 120V +10%, -15% 50/60Hz
Approx. 21kΩ/50Hz Approx. 18kΩ/60Hz
4.7mA/100V AC 50Hz
6.2mA/110V AC 60Hz (70% or less when turned on simultaneously)
3.8mA or more
Approx. 25ms to 30ms (A high speed receiving is improper)
LED on panel lights when photocoupler is driven.
I

3.4.6 Examples of 100V AC input wiring

[1]
Fuse
L
*1
N
COM
Fuse
100-240V AC
X000 X001 X002
COM
Fuse
[2]
100-120V AC
X000 X001
MC
*2
*1 Class D grounding See section 3.3 for details.
*2 Do not take input signals from loads generating surge.
[1]:Main unit, Input/output extension unit (100V AC input type)
[2]:Input extension block (100V AC input type)

3.5 Relay output specifications and example of external wiring

As for the details of Instructions for connecting input devices, refer to the following manual.
Refer to FX3U Series User's Manual - Hardware Edition.

3.5.1 Relay output specifications

Item Specification
FX2N-8ER
FX3U-16MR, FX2N-8EYR
FX3U-32MR/,
2N-32ER
Number of output points
Output connecting type
Output form Relay
External power supply
Max. load
Min. load 5V DC, 2mA (reference value)
Open circuit leakage current -
Response time
Circuit insulation Mechanical insulation
Display of output operation
FX FX2N-16EYR
FX3U-48MR,
2N-48ER
FX
FX3U-64MR/32 points
FX3U-80MR
FX3U-128MR/ES
Resistance load
Inductive load
OFFON Approx. 10ms
ONOFF Approx. 10ms
4 points (8 points)
8 points
,
16 points
24 points
40 points
64 points
Refer to FX3U Series User's Manual
- Hardware Edition
30V DC or less 240V AC or less ("250V AC or less" if not a CE, UL, cUL compliant item)
2A/point
80VA
LED on panel lights when power is applied to relay coil.
*1
*2
*1 Each value inside ( ) indicates the number of occupied points. *2 The total load current of resistance loads per common terminal
should be the following value or less.
- 1 output points/common terminal : 2A
- 4 output points/common terminal : 8A
- 8 output points/common terminal : 8A As for the number of outputs per common terminal, refer to “Chapter 4 interpretation of partition” and the following manual.
Refer to FX3U Series User's Manual - Hardware Edition.

3.5.2 Life of relay output contact

The product life of relay contacts considerably varies depending on the load type used. Take care that loads generating reverse electromotive force or rush current may cause poor contact or deposition of contacts which may lead to considerable reduction of the contact product life.
1) Inductive load Inductive loads generate large reverse electromotive force between contacts at shutdown which may cause arcing. At a fixed current consumption, as the power factor (phase between current and voltage) gets smaller, the arc energy gets larger. The standard life of the contact used for Inductive loads, such as contactors and solenoid valves, is 500 thousand operations at 20VA. The following table shows the approximate life of the relay based on the results of our operation life test.
Test condition: 1 sec. ON / 1 sec.OFF.
Load capacity Contact life
20VA
35VA
80VA
The product life of relay contacts becomes considerably shorter than the above conditions when the rush overcurrent is shut down.
Some types of inductive loads generate rush current 5 to 15 times the stationary current at activation. Make sure that the rush current does not exceed the current corresponding to the maximum specified resistance load.
2) Lamp load Lamp loads generally generate rush current 10 to 15 times the stationary current. Make sure that the rush current does not exceed the current corresponding to the maximum specified resistance load.
3) Capacitive load Capacitive loads can generate rush current 20 to 40 times the stationary current. Make sure that the rush current does not exceed the current corresponding to the maximum specified resistance load. Capacitive loads such as capacitors may be present in electronic circuit loads including inverters.
0.2A/100V AC
0.1A/200V AC
0.35A/100V AC
0.17A/200V AC
0.8A/100V AC
0.4A/200V AC
For countermeasures while using inductive loads,
For the maximum specified resistance load,
3 million times
1 million times
2 hundred thousand times
refer to Subsection 3.5.4.
refer to Subsection 3.5.1.

3.5.3 Example of relay output wiring

Load
Y000 Y001
Fuse
COM1
24V DC
Load
Y010 Y011
Fuse
100V AC
COM2
PLC

3.5.4 Cautions in external wiring

For cautions in external wiring, refer to the following manual.
Refer to FX3U Series User's Manual - Hardware Edition.
Protection circuit for load short-circuiting
When a load connected to the output terminal short-circuits, the printed circuit board may be burnt out. Fit a protective fuse on the output circuit.
Protection circuit of contact when inductive load is used
An internal protection circuit for the relays is not provided for the relay output circuit. It is recommended to use inductive loads with built-in protection circuits. When using loads without built-in protection circuits, insert an external contact protection circuit, etc. to reduce noise and extend the product life.
1) DC circuit Connect a diode in parallel with the load. Use a diode (for commutation) having the following specifications.
Item Standard
Reverse voltage 5 to 10 times the load voltage
Forward current Load current or more
2) AC circuit Connect the surge absorber (combined CR components such as a surge killer and spark killer, etc.) parallel to the load. Select the rated voltage of the surge absorber suitable to the output used. Refer to the table below for other specifications.
Item Standard
Electrostatic capacity Approx. 0.1µF
Resistance value Approx. 100 to 200
Interlock
Loads, such as contactors for normal and reverse rotations, that must not be turned on simultaneously should have an interlock in the PLC program and an external interlock.
Common mode
Use output contacts of the PLC in the common mode.

3.6 Transistor output specifications and example of external wiring

As for the details of the transistor output specifications and external wiring, refer to the following manual.
Refer to FX3U Series User's Manual - Hardware Edition.

3.6.1 Transistor output specifications

Item Specification
Number of output points
FX3U-16MT/, FX2N-8EYT
FX3U-32MT/, FX2N-32ET, FX2N-16EYT
FX3U-48MT/, FX2N-48ET
8 points
16 points
24 points
FX3U-64MT/ 32 points
FX3U-80MT/ 40 points
FX3U-128MT/ES(S) 64 points
Output connecting type
FX3U-MT/S(-A), FX2N-ET, FX2N-48ET-D, FX2N-EYT,
Output
FX2N-8EYT-H
form
FX3U-MT/SS, FX2N-ET-ESS/UL, FX2N-48ET-DSS, FX2N-EYT-ESS/UL
Refer to FX3U Series User's Manual ­Hardware Edition
Transistor(Sink)
Transistor(Source)
External power supply 5 to 30V DC
FX3U-MT/,
Max. load
FX2N-ET, FX2N-ET-,
Resist
FX2N-EYT,
ance
FX2N-EYT-ESS/UL
load
FX2N-8EYT-H
FX2N-16EYT-C
FX3U-MT/, FX2N-ET, FX2N-ET-,
Induct
FX2N-EYT,
ive
FX2N-EYT-ESS/UL
load
FX2N-8EYT-H
FX2N-16EYT-C
*1
0.5A/point
*2
1A/point
*3
0.3A/point
12W/24V DC
24W/24V DC
7.2W/24V DC
*4
*5
*6
Min. load
Open circuit leakage current 0.1mA or less/30V DC
ON voltage 1.5V or less
Item Specification
Y000 to
5µs or less/10mA or more
Y002
(5 to 24V DC)
Y003 or
0.2ms or less/200mA
more
or more (at 24V DC)
0.2ms or less/200mA or more (at 24V DC)
Y000 to
5µs or less/10mA or more
Y002
(5 to 24V DC)
Y003 or
0.2ms or less/200mA
more
or more (at 24V DC)
0.2ms or less/200mA or more (at 24V DC)
Respon se time
Main unit
OFF
ON
Input/output extension units/blocks
Main unit
ON
OFF
Input/output extension units/blocks
*7
*7
Circuit insulation Photocoupler insulation
Display of output operation
*1 The total load current of resistance loads per common terminal
should be the following value or less.
- 1 output point/common terminal : 0.5A
- 4 output point/common terminal : 0.8A
- 8 output point/common terminal : 1.6A As for the number of outputs per common terminal, refer to “Chapter 4 interpretation of partition” and the following manual.
LED on panel lights when photocoupler is driven.
Refer to FX3U Series User's Manual - Hardware Edition.
*2 The total load current of resistance loads per common terminal
should be the following value or less.
- 4 output points/common terminal : 2A As for the number of outputs per common terminal, refer to the following manual.
Refer to FX3U Series User's Manual - Hardware Edition.
*3 The total load current of resistance loads per common terminal
should be the following value or less.
- 16 output point/common terminal : 1.6A As for the number of outputs per common terminal, refer to the following manual.
Refer to FX3U Series User's Manual - Hardware Edition.
*4 The total of inductive loads per common terminal should be th e
following value or less.
- 1 output point/common terminal : 12W/24V DC
- 4 output points/common terminal : 19.2W/24V DC
- 8 output points/common terminal : 38.4W/24V DC As for the number of outputs per common terminal, refer to “Chapter 4 interpretation of partition” and the following manual.
Refer to FX3U Series User's Manual - Hardware Edition.
*5 The total of inductive loads per common terminal should be the
following value or less.
- 4 output points/common terminal : 48W/24V DC As for the number of outputs per common terminal, refer to the following manual.
Refer to FX3U Series User's Manual - Hardware Edition.
*6 The total of inductive loads per common terminal should be the
following value or less.
- 16 output points/common terminal : 38.4W As for the number of outputs per common terminal, refer to the following manual.
Refer to FX3U Series User's Manual - Hardware Edition.
*7 The response time is as follows in the FX2N-8EYT-H.
-OFF→ON : 0.2ms or less/1A
-ON→OFF : 0.4ms or less/1A

3.6.2 External Wiring of Transistor Output

1. External Wiring of Sink Output Type
Load
Y000
Fuse
Y001
24V DC
COM1
Load
Y004
24V DC
Y005
COM2
PLC
Fuse
2. External Wiring of Source Output Type
Load
Fuse
Y000
Y001
24V DC
+V0
Load
Fuse
24V DC
Y004
Y005
+V1
PLC

3.6.3 Cautions in external wiring

For cautions in external wiring, refer to the following manual.
Refer to FX3U Series User's Manual - Hardware Edition.
Protection circuit for load short-circuits
A short-circuit at a load connected to an output terminal could cause burnout at the output element or the PCB. To prevent this, a protection fuse should be inserted at the output. Use a load power supply capacity that is at least 2 times larger than the total rated fuse capacity.
Contact protection circuit for inductive loads
When an inductive load is connected, connect a diode (for commutation) in parallel with the load as necessary. The diode (for commutation) must comply with the following specifications.
Item Guide
Reverse voltage 5 to 10 times of the load voltage
Forward current Load current or more
Interlock
Loads, such as contactors for normal and reverse rotations, that must not be turned on simultaneously should have an interlock in the PLC program and an external interlock.

3.7 Triac output specifications and example of external wiring

As for the details of the triac output specifications and external wiring, refer to the following manual.
Refer to FX3U Series User's Manual - Hardware Edition.

3.7.1 Triac output specifications

Item Specification
Number of output points
FX3U-32MS/ES FX2N-16EYS FX2N-32ES
FX3U-64MS/ES 32 points
Output connecting type
,
,
16 points
Refer to FX3U Series User's Manual - Hardware Edition
Output form Triac (SSR)
External power supply 85 to 242V AC
Max. load
Inductive load
Min. load
Open circuit leakage current
Resistance load
Response time
OFFON 1ms or less
ONOFF 10ms or less
*1
0.3A/point
15VA/100V AC, 30VA/200V AC
0.4VA/100V AC,
1.6VA/200V AC
1mA/100V AC, 2mA/200V AC
Circuit insulation Photo-thyristor insulation
Display of output operation
*1 The total load current of resistance loads per common terminal
should be the following value or less.
- 4 output points/common terminal : 0.8A
- 8 output points/common terminal : 0.8A As for the number of outputs per common terminal, refer to “Chapter 4 interpretation of partition” and the following manual.
LED on panel lights when photo-thyristor is driven.
Refer to FX3U Series User's Manual - Hardware Edition.

3.7.2 External Wiring of Triac Output

Fuse
Fuse
Load
AC power supply
Load
AC power supply
Y000
Y001
COM1
Y004
Y005
COM2
U
U
PLC

3.7.3 Cautions in external wiring

For cautions in external wiring, refer to the following manual.
Refer to FX3U Series User's Manual - Hardware Edition.
Protection circuit for load short-circuits
A short-circuit at a load connected to an output terminal could cause burnout at the output element or the PCB. To prevent this, a protection fuse should be inserted at the output.
Micro current load
The PLC's internal Triac output circuit is equipped with a turn-off C-R absorber. When connecting a very low current load of "0.4VA/100V AC or less, or 1.6VA/200V AC or less", please connect a surge absorber parallel to the load. Select the rated voltage of a surge absorber that is suitable for the load being used. Refer to the table below for other specifications.
Item Guide
Static electricity capacity Approx. 0.1µF
Resistance value Approx. 100 to 200
Interlock
Loads, such as contactors for normal and reverse rotations, that must not be turned on simultaneously should have an interlock in the PLC program and an external interlock.

4. Terminal block layouts

For details on the terminal block layout, refer to the following manual.
Refer to FX3U Series User's Manual - Hardware Edition.
Interpretation of partition
The partition of the output terminals (see following figure) indicates the range of the output connected to the same common.
Example: FX
3U
-48MT/ES
Output terminal
Y0
Y2
Y4
COM1 Y1 COM2Y3
Partition
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual.
Warranty
Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi; opportunity loss or lost profits caused by faults in the Mitsubishi products; damage, secondary damage, accident compensation caused by special factors unpredictable by Mitsubishi; damages to products other than Mitsubishi products; and to other duties.
For safe use
This product has been manufactured as a general-purpose part for general industries, and has not been designed or manufactured to be incorporated in a device or system used in purposes related to human life. Before using the product for special purposes such as nuclear power, electric
power, aerospace, medicine or passenger movement vehicles, consult with Mitsubishi Electric.
This product has been manufactured under strict quality control. However when installing the product where major accidents or losses could occur if the product fails, install appropriate backup or failsafe functions in the system.
HEAD OFFICE
: TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
HIMEJI WORKS
: 840, CHIYODA CHO, HIMEJI, JAPAN
Loading...