This manual describes the part names, dimensions, mounting,
cabling and specifications for the product. This manual is extracted
3G Series User's Manual - Hardware Edition. Refer to FX3G
from FX
Series User's Manual - Hardware Edition for more details. Before
use, read this manual and manuals of relevant products fully to
acquire proficiency in the handling and operating the product. Make
sure to learn all the product information, safety information, and
precautions.
And, store this manual in a safe place so that you can take it out and
read it whenever necessary. Always forward it to the end user.
Registration
Phillips is a registered trademark of Phillips Screw Company.
The company name and the product name to be described in this
manual are the registered trad emarks or trademarks of each
company.
Effective December 2017
Specifications are subject to change without notice.
Safety Precaution (Read these precautions before use.)
If the equipment is used in a manner not specified by the
manufacturer, the protection provided by the equipment may be
impaired.
This manual classifies the safety precautions into two categories:
and .
Indicates that incorrect handling may cause
hazardous conditions, resulting in death or
severe injury.
Indicates that incorrect handling may cause
hazardous conditions, resulting in medium or
slight personal injury or physical damage.
Depending on the circumstances, procedures indicated by
may also cause severe injury.
It is important to follow all precautions for personal safety.
STARTUP AND
MAINTENANCE
PRECAUTIONS
• Do not touch any terminal while the PLC's power is on.
Doing so may cause electric shock or malfunctions.
• Before cleaning or retightening terminals externally cut off all
phases of the power supply.
Failure to do so may cause electric shock.
• Use the battery for memory backup correctly in FX
User's Manual - Hardware Edition.
- Use the battery only for the specified purpose.
- Connect the battery correctly.
- Do not charge, disassemble, heat, put in fire, short-circuit,
connect reversely, weld, swallow or burn the battery, or apply
excessive forces (vibration, impact, drop, etc.) to the battery.
- Do not store or use the battery at high temperatures or
expose to direct sunlight.
- Do not expose to water, bring near fire or touch liquid
leakage or other contents directly.
- Incorrect handling of the battery may cause heat excessive
generation, bursting, ignition, liquid leakage or deformation,
and lead to injury, fire or failures and malfunctions of facilities
and other equipment.
- When replacing the battery, make sure to use our specified
product (FX
- When a battery error occurs ("ALM" LED is lit in red), follow
the description in FX
Edition.
• Before modifying or disrup ting the program in operatio n or
running the PLC, carefully read through this manual and the
associated manuals and ensure the safety of the operation.
An operation error may damage the machinery or cause accidents.
STARTUP AND
MAINTENANCE
PRECAUTIONS
• Turn off the power to the PLC before attaching or detaching the
memory cassette. If the memory cassette is attached or
detached while the PLC's power is on, the data in the memory
may be destroyed, or the memory cassette may be damaged.
• Do not disassemble or modify the PLC.
Doing so may cause fire, equipment failures, or malfunctions.
For repair, contact your local Mitsubishi Electric representative.
•
Turn off the power to the PLC before connecting or disconnecting
any extension cable.
Failure to do so may cause equipment failures or malfunctions.
• Turn off the power to the PLC before attaching or detaching the
following devices.
Failure to do so may cause equipment failures or malfunctions.
- Peripheral devices, Display module, expansion boards, and
special adapters
- Connector conversion adapter, extension blocks, and FX
Series terminal blocks
- Battery and memory cassette
• Do not use the chemicals for cleaning.
• If there is the possibility of touching the PLC inside a control
panel in maintenance, make sure to discharge to avoid the
influence of static electricity.
DISPOSAL
PRECAUTIONS
• Please contact a certified electronic waste disposal company
for the environmentally safe recycling and disposal of your
device. When disposing of batteries, separate them from other
waste according to local regulations.
(For details of the Battery Directive in EU countries, refer to
FX3G Series User's Manual - Hardware Edition.)
3U-32BL).
3G Series User's Manual - Hardware
3G Series
TRANSPORTATION
AND STORAGE
PRECAUTIONS
• When transporting the FX3G Series PLC incorporating the
optional battery, turn on the PLC before shipment, confirm that
the battery mode is set using a parameter and the ALM LED is
OFF, and check the battery life.
If the PLC is transported with the ALM LED on or the battery
exhausted, the battery-backed data may be unstable during
transportation.
• The PLC is a precision instrument. During transportation, avoid
impacts larger than those specified in Section 2.1 by using
dedicated packaging boxes and shock-absorbing palettes.
Failure to do so may cause failures in the PLC.
After transportation, verify operation of the PLC and check for
damage of the mounting part, etc.
• When transporting lithium batteries, follow required
transportation regulations.
(For details of the regulated products, refer to FX
User's Manual - Hardware Edition.)
3G Series
Associated manuals
How to obtain manuals
For the necessary product manuals or documents,
consult with your local Mitsubishi Electric representative.
Associated manuals
FX3G Series PLC (main unit) comes with this document (hardware
manual).
For a detailed explanation of the FX3G Series hardware and
information on instructions for PLC programming and special
extension unit/block, refer to the relevant documents.
Manual nameManual No.Description
3G Series
FX
User's Manual
- Hardware Edition
FX3S/FX3G/FX3GC/
FX3U/FX3UC Series
Programming Manual
Explains FX3G Series
PLC specification details
for I/O, wiring,
installation, and
maintenance.
Describes PLC
programming for basic/
applied instructions STL/
SFC programming and
devices.
Programming methods,
specifications, functions,
etc. required to create
structured programs.
Devices, parameters,
etc.
provided in structured
projects of GX Works2.
Sequence instructions
provided in structured
projects of GX Works2.
Application functions
provided in structured
projects of GX Works2.
Manual nameManual No.Description
FX Series
User’s Manual
- Data
Communication
Edition
FX3S/FX3G/FX3GC/
3U/FX3UC Series
FX
User's Manual
- Analog Control
Edition
3S/FX3G/FX3GC/
FX
FX3U/FX3UC Series
User's Manual
- Positioning Control
Edition
JY997D16901
MODEL CODE:
09R715
JY997D16701
MODEL CODE:
09R619
JY997D16801
MODEL CODE:
09R620
Explains N:N link,
parallel link, computer
link, no protocol
communication by RS
instructions/FX2N-232IF.
Describes specifications
for analog control and
programming methods
for FX3S/FX3G/FX3GC/
FX
3U/FX3UC Series
PLC.
Explains the
specifications for
positioning control of
FX3S/FX3G/FX3GC/
FX3U/FX3UC Series and
programming procedures
Certification of UL, cUL standards
Please consult with Mitsubishi Electric for information on UL, cUL
standard practices and the corresponding types of equipment.
Compliance with EC directive(CE Marking )
This product complies with EC directive, however, this document
does not guarantee that a mechanical system including this product
will comply with EC directive.
Compliance to EMC directive and LVD directive of the entire
mechanical system should be checked by the user / manufacturer.
For more details please contact the local Mitsubishi Electric sales
site.
Caution for compliance with EC Directive
• Please use the FX3G Series programmable controllers while
installed in conductive shielded control panels under a general
industrial environment.
• Programmable controllers are open-type devices that must be
installed and used within conductive control panels. Please
secure the control box lid to the control box (for conduction).
Installation within a control box greatly affects the safety of the
system and aids in shielding noise from the programmable
controller.
• For the control panel, use the product having sufficient strength,
fire protectiveness and shielding property to an installation
environment.
• 24 V DC of the power supply must be supplied from the circuit
double/reinforced insulated from the main power supply (MAINS).
Caution for compliance with the LVD directive (EN61010-2201:2013)(*1)
• To an external connection port other than AC power supply
terminal and AC input/output terminal, connect the circuit
separated from a dangerous voltage by a double/reinforced
insulation.
• Between the commons having the adjacent relay output
terminals, if an external power supply is higher than 120 V AC,
the insulation is basic. Therefore, when using 120 V AC or higher
external power supply and 30 V DC/AC or lower external power
supply between the adjacent commons, do not handle 30 V DC/
AC or lower external power supply as a touchable part, (When
handling 30 V DC/AC or lower external power supply as a
touchable part, add a basic insulation.)
• Do not wire two or more crimp terminals to one terminal. (If the
wiring with two or more wires is needed, take an appropriate
action such as adding an external terminal.)
• For crimp terminals to be used for the wiring applied with 30 V AC
or higher, use the products with insulating sleeves.
• Cutoff device such as a breaker or a circuit protector should be
installed in accordance with the following precautions.
- Use EN60947-1 or EN60947-3 standards.
- Place the cutoff device so that it can be operated easily.
- Specify that the cutoff device is for this equipment.
(*1) For the time of compliance with the LVD directive (EN61010-
2-201:2013), refer to FX
Edition.
3G Series User's Manual - Hardware
Incorporated Items
Check if the following product and items are included in the package:
Main units
FX3G-14M to
3G-60M
FX
Input/output powered extension units
FX2N-32E
FX2N-48E
Input/output extension blocks
FX2N-8E
FX2N-16E
(*1) The FX3G-M/ES-A becomes Chinese version.
Product1 unit
Dust proof protection sheet1 sheet
Manuals [Japanese(*1)/English]
Product1 unit
,
Extension cable1 cable
Input/output number label1 sheet
Product1 unit
Input/output number label1 sheet
Included Items
1 manual
1. Outline
For the input/output extension units/blocks, refer to the following
manual.
→ Refer to FX3G Series User's Manual - Hardware Edition.
1.1 Part names
[3] [4]
[2]
[1]
[11]
No.Name
[1] Peripheral device connecting connector cover
Terminal names
[2]
[3] Top cover(S) (40points, 60points type only)
[4] Top cover
[5] Terminal block covers
[6] Input display LEDs (red)
[10]
shows a function grounding terminal.
[5]
[6]
[7]
[8]
[9]
[12]
No.Name
[7] Extension device connecting connector cover
Operation status display LEDs
POWGreen On while power is on the PLC.
RUNGreen On while the PLC is running.
[8]
ERR
ALMRed
[9] Output display LEDs (red)
[10] Model name (abbreviation)
[11] DIN rail mounting hooks
Nameplate printing
[12]
appropriate temperature rating(80°C or more) for wiring.
Lights when the battery voltage drops.
(When the optional battery is used)
is a mark that instructs to use the cable with an
[6] [7] [8]
[5]
[14][13]
[7]
[9]
[10]
[11]
[12]
1.2 External dimensions and weight
→ For the input/output extension units/blocks,
refer to FX3G Series User's Manual - Hardware Edition.
2-f4.5 mounting holes
82(3.23")
W1
W
Mounting hole pitches
Model name
3G-14M90 (3.55”)82 (3.23”)
FX
FX3G-24M90 (3.55”)82 (3.23”)
FX3G-40M130 (5.12”)122 (4.81”)
FX3G-60M175 (6.89”)167 (6.58”)
Installation
• 35-mm-wide DIN rail or Direct (screw) mounting (M4)
W:
mm (inches)
mm (inches)
Direct mounting
hole pitches
90(3.55")
W1:
Unit: mm(inches)
86(3.39")
MASS (Weight)
8(0.32")
kg (lbs)
Approx. 0.50
(1.10lbs)
Approx. 0.55
(1.21lbs)
Approx. 0.70
(1.54lbs)
Approx. 0.85
(1.87lbs)
2. Installation (general specifications)
As for installation of the input/output extension units/blocks, special
adapters and expansion boards, refer to the following manual.
→ Refer to FX3G Series User's Manual - Hardware Edition.
INSTALLATION
PRECAUTIONS
• Use the product within the generic environment specifications
described in section 2.1 of this manua l.
Never use the product in areas with excessive dust, oily smoke,
conductive dusts, corrosive gas (salt air, Cl2, H2S, SO2 or
NO2), flammable gas, vibration or impacts, or exposed to high
temperature, condensation, or rain and wind.
If the product is used in such conditions, electric shock, fire,
malfunctions, deterioration or damage may occur.
•
Do not touch the conductive parts of the product directly to avoid
failure or malfunctions.
:
• Install the product securely using a DIN rail or mounting screws.
• Install the product on a flat surface.
If the mounting surface is rough, undue force will be applied to
the PC board, thereby causing nonconformities.
• When drilling screw holes or wiring, make sure cutting or wire
debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or
malfunctions.
• Be sure to remove the dust proof sheet from the PLC's
ventilation port when installation work is completed. Failure to
do so may cause fire, equipment failures or malfunctions.
• Connect the extension cables, peripheral device cables, input/
output cables and battery connecting cable securely to their
designated connectors.
Unsecured connection may cause malfunctions.
• Turn off the power before attaching or detaching the following
devices.
Failure to do so may cause device failures or malfunctions.
- Peripheral devices, display modules, expansion boards and
special adapters
- Extension units/blocks and the FX Series terminal block
- Battery and memory cassette
Notes
• When a dust proof sheet is supplied with an extension unit/
block, keep the sheet applied to the ventilation slits during
installation and wiring work.
• To prevent temperature rise, do not install the PLC on a floor, a
ceiling or a vertical surface.
Install it horizontally on a wall as shown in section 2.2.
• Keep a space of 50mm (1.97”) or more between the unit main
body and another device or structure (part A). Install the unit as
far away as possible from high-voltage lines, high-voltage
devices and power equipment.
Failure to do so may cause fire, equipment failures or
malfunctions.
WIRING
PRECAUTIONS
• Cut off all phases of the power supply externally before
installation or wiring work in order to avoid damage to the
product or electric shock.
• The temperature rating of the cable should be 80°C or more.
2.1 Generic specifications
Other equipment
Other
equipment
Other equipment
FX3G Series
main unit
FX
2N
-16EYT
FX
3U
-4AD-
ADP
Input/output
powered
extension
unit
FX
3G
-CNV-
ADP
Configuration in 2 stages with extension cable
50mm (1.97")
Extension
cable
·FX0N-65EC
·FX0N-30EC
FX
3U
-64CCL
FX
2N
-16EX
FX
2N
-CNV-
BC
≥
A
A
A
A
A
A
A
A
ItemSpecification
Ambient
temperature
Ambient
humidity
Vibration
resistance
(*1)
Shock
resistance
1)
(
*
Noise
resistance
Dielectric
withstand
voltage
(*2)
Insulation
resistance
(*2)
Grounding
Working
atmosphere
Working
altitude
Installation
location
Over
voltage
category
Pollution
degree
(*1) The criterion is shown in IEC61131-2.
(*2) Dielectric withstand voltage and insulation resistance are
0 to 55°C (32 to 131°F) when operating and -25 to
75°C (-13 to 167°F) when stored
5 to 95%RH (no condensation) when operating
Accele-
Fre-
ration
quency
(Hz)
(m/s2)
When
10 to 57-0.035
installed
57 to 150
on DIN rail
When
10 to 57-0.075
installed
57 to 150
directly
147m/s2 Acceleration, Action time: 11ms, 3 times by
half-sine pulse in each direction X, Y, and Z
By noise simulator at noise voltage of 1,000Vp-p,
noise width of 1μs, rise time of 1ns and period of 30 to
100Hz
1.5kV AC for one
minute
500V AC for one
minute
5MΩ or higher by
500V DC insulation
resistance tester
Class D grounding (grounding resistance: 100Ω or
less) <Common grounding with a hea vy electrical
system is not allowed.>(*3)
Free from corrosive or flammable gas and excessive
conductive dusts
<2000m(*4)
Inside a control panel (*5)
ΙΙ or less
2 or less
shown in the following table.
4.9-
9.8-
Between each terminals(*2) and
ground terminal
ampli-
Half
tude
(mm)
Sweep Count
for X, Y, Z: 10
times
(80 min in
each
direction)
Terminal
Main units, Input/output extension units/blocks
Between power supply
terminal (AC power) and
ground terminal
Between power supply
terminal (DC power) and
ground terminal
Between input terminal
(24V DC) and ground
terminal
Between input terminal
(100V AC) and ground
terminal(*6)
Between output terminal
(relay) and ground
terminal
Between output terminal
(transistor) and ground
terminal
Between output terminal
(triac) and ground
terminal(*6)
Expansion boards, Special function adapters, Special
function blocks
Between terminal of
expansion board (except
FX3G-4EX-BD and
FX3G-2EYT-BD) and
ground terminal
Between FX3G-4EX-BD
input terminal (24 V DC)
and ground terminal
Between FX3G-2EYT-
BD output terminal
(transistor) and ground
terminal
Between terminal of
special adapter and
ground terminal
Special function blockEach manual
For dielectric with stand voltage test and insulation resistance test of
each product, refer to the following manual.
→ Refer to FX3G Series User's Manual - Hardware Edition.
(*3) For common grounding, refer to section 3.3.
(*4) The PLC cannot be used at a pressure higher than the
atmospheric pressure to avoid damage.
(*5) The programmable controller is assumed to be installed in an
environment equivalent to indoor.
(*6) Input/output extension units/blocks only.
Dielectric
strength
1.5kV AC for
one minute
500V AC for
one minute
1.5kV AC for
one minute
500V AC for
one minute
1.5kV AC for
one minute
Not allowedNot allowed
500V AC for
1min
Insulation
resistance
5MΩ or higher by
500V DC insulation
resistance tester
5MΩ or higher by
500V DC insulation
resistance tester
2.2 Installation location
Install the PLC in an environment conforming to th e generic
specifications (section 2.1), installatio n precautions and notes.
For more details, refer to FX3G Series User's Manual - Har dware
Edition.
Installation location in enclosure
Space in enclosure
Extension devices can be connected on the left and right sides of the
main unit of the PLC.
If you intend to add extension devices in the future, keep necessary
spaces on the left and right sides.
Configuration without extension cable
A
A
FX3G Series
main unit
A
A
≥ 50mm (1 .97 ")
A
FX2N-16EX
FX2N-16EYT
2.2.1 Affixing The Dust Proof Sheet
The dust proof sheet should be affixed to the ventilation port before
beginning the installation and wiring work.
→ For the affixing procedure, refer to the instructions on the
Be sure to remove the dust proof sheet when the installation and
wiring work is completed.
dust proof sheet.
2.3 Procedures for installing to and detaching from
DIN rail
The products can be installed on a DIN46277 rail [35 mm (1.38”)
wide].
This section explains the installations of the main units.
For the input/output extension units/blocks and special adapters,
refer to the following manual.
→ Refer to FX
3G Series User's Manual - Hardware Edition.
2.3.1 Installation
1) Push out all DIN rail mounting hooks (below fig.A).
1)1)
1)1)
A
2) Fit the upper edge of the DIN rail
mounting groove (right fig.C)
onto the DIN rail.
3) Lock the DIN rail mounting hooks
(below fig.D) while pressing the PLC against the DIN rail.
DD
3)3)