•This manual contains text, diagrams and explanations which will guide the reader in the correct installation
and operation of the FX
install or use the unit.
-8AD Analog input block. It should be read and understood before attempting to
2N
•Further information can be found in the FX
/FX1N/FX2N/FX
0N
Series Hardware Manual for connecting main
2NC
unit, and the FX Series Programming Manual(ΙΙ).
•If in doubt at any stage of the installation of FX
-8AD Analog input block always consult a professional
2N
electrical engineer who is qualified and trained to the local and national standards that applies to the
installation site.
•If in doubt about the operation or use of FX2N-8AD Analog input block please consult the nearest Mitsubishi
Electric distributor.
•This manual is subject to change without notice.
FX2N-8AD Analog input block
FX
2N
-8AD Analog input block
USER’S MANUAL
Manual number: JY992D86001
Manual revision: C
Date: April 2003
FX2N-8AD Analog input block
ii
FX2N-8AD Analog input block
Guidelines for the Safety of the User and Protection of the FX2N-8AD Analog
input block.
This manual provides information for the use of the FX2N-8AD Analog input block. The manual
has been written to be used by trained and competent personnel. The definition of such a
person or persons is as follows:
a) Any engineer who is responsible for the planning, design and construction of automatic
equipment using the product associated with this manual, should be of a competent
nature, trained and qualified to the local and national standards required to fulfill that
role. These engineers should be fully aware of all aspects of safety with regards to
automated equipment.
b) Any commissioning or service engineer must be of a competent nature, trained and
qualified to the local and national standards required to fulfill that job. These engineers
should also be trained in the use and maintenance of the completed product. This
includes being completely familiar with all associated documentation for said product. All
maintenance should be carried out in accordance with established safety practices.
c) All operators of the completed equipment (see Note) should be trained to use this
product in a safe manner in compliance to established safety practices. The operators
should also be familiar with documentation which is associated with the actual operation
of the completed equipment.
Note :
The term ‘completed equipment’ refers to a third party constructed device which
contains or uses the product associated with this manual.
iii
FX2N-8AD Analog input block
Notes on the Symbols Used in this Manual
At various times throughout this manual certain symbols will be used to highlight points which
are intended to ensure the users personal safety and protect the integrity of equipment.
Whenever any of the following symbols are encountered its associated note must be read and
understood. Each of the symbols used will now be listed with a brief description of its meaning.
Hardware Warnings
1) Indicates that the identified danger
2) Indicates that the identified danger could
damage.
3) Indicates a point of further interest or further explanation.
Software Warnings
4) Indicates special care must be taken when using this element of software.
5) Indicates a special point which the user of the associate software element should
be aware.
6) Indicates a point of interest or further explanation.
WILL
cause physical and property damage.
POSSIBLY
cause physical and property
iv
FX2N-8AD Analog input block
•Under no circumstances will Mitsubishi Electric be liable responsible for any consequential
damage that may arise as a result of the installation or use of this equipment.
•All examples and diagrams shown in this manual are intended only as an aid to understanding
the text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for actual
use of the product based on these illustrative examples.
•Please contact a Mitsubishi Electric distributor for more information concerning applications
in life critical situations or high reliability.
9.2Adjustment of I/O characteristics.....................................................................9-7
10. Example program..............................................................................10-1
Appendix A
Associated Manuals List........................................................................... A -1
viii
FX2N-8AD Analog input block
1.Introduction
The FX2N-8AD analog input block (hereafter referred to as "FX2N-8AD") converts 8 points of
analog input values (voltage input, current input and temperature input) into digital values, and
transfers them to the PLC main unit.
Introduction 1
The FX
-8AD can be connected to FX0N, FX1N, FX2N and FX
2N
Series PLC.
2NC
1) Analog inputs can be selected from the voltage input, the current input and the thermocouple
input (temperature input) by the input mode setting by the TO instruction given by the PLC
main unit and the connection method.
At this time, a different analog input can be selected for each channel.
2) The voltage input can be selected within the range from -10 to +10 V. The current input can
be selected within the range from -20 to +20 mA and from +4 to +20 mA. The input
characteristics can be adjusted for each channel (except while the analog value direct
displa y is used).
The thermocouple input can be selected among the K type, J type and T type. (The input
characteristics cannot be adjusted when the thermocouple input is used.)
3) The resolution is 0.63 mV (20 V × 1/32,000) or 2.50 mV (20 V × 1/8,000) when the voltage
input is used, 2.50 µA (40 mA × 1/16,000) or 5.00 µA (40 mA × 1/8,000) when the current
input is used, and 0.1 °C when the thermocouple input is used.
1-1
FX2N-8AD Analog input blockIntroduction 1
4) Up to two FX2N-8AD units can be connected to FX0N main unit, FX0N extension unit, FX
main unit.
Up to eight FX
8AD units can be connected to one FX
(For connection to the FX
Data transfer with the PLC is performed to buffer memories of the FX
-8AD units can be connected to one FX2N Series PLC. Up to four FX2N-
Lit while 5 V power is normally
supplied from PLC.
Lit while 24 V power is normally
supplied to “24+” and “24-”
terminals of FX
-8AD.V
2N
Terminal arrangement
V1+I1+
24+24-V2+I2+V4+I4+
COM6
V6+
V5+I5+
I6+
COM5
COM1
COM2
V8+I8+
V7+I7+
V3+I3+
COM7
COM8
COM3
COM4
• For wiring, refer to Section 6.
• Never perform wiring to terminals.
•
3-1
FX2N-8AD Analog input blockPart Name 3
MEMO
3-2
FX2N-8AD Analog input block
4.Installation
Install the FX2N-8AD to the right side of a main unit, extension unit, extension block or special
Installation 4
block of the FX
The FX
-8AD can be installed with a DIN rail (DIN46277 of 35 mm in width) or directly
2N
/FX1N/FX2N/FX
0N
Series PLC.
2NC
installed with screws M4. For the details, refer to the handy manual supplied together with the
PLC main unit.)
4-1
FX2N-8AD Analog input blockInstallation 4
Figure 4.1: Installation with DIN rail
•The FX2N-8AD can be installed on a DIN rail
I1+V1+
COM1COM3
V3+
24+
V5+
24-
FX2N-8AD
I6+
V6+
I5+
V2+
COM6
COM5
I2+
POWER
24V
V7+
I3+
I4+
COM2
V8+
I7+
COM4
V4+
I8+
COM8
COM7
Hook for DIN rail
Figure 4.2: Direct installation
Installation
screw M4
(DIN46277) of 35 mm in width as it is. For
removal, pull down on the DIN rail mounting
hook, then remove the FX
2N
-8AD.
•The FX2N-8AD can be installed directly by
inserting screws (M4) into installation holes.
For the pitch and the position of installation
holes, re fer to the figure on the le ft.
67(2.64)
Dimensions: mm(inch)
98(3.86)
4-2
FX2N-8AD Analog input block
5.Connection to PLC
Connect the FX2N-8AD to the right side of a main unit, extension unit or extension block of
Connection to PLC 5
FX
For c onnection t o a basic unit or extension block o f the FX
, FX1N, FX2N, FX
0N
Series PLC with an extension cable.
2NC
Series PLC, use an FX
2NC
2NC
-CNVIF.
Please check power supply availability to deter mine the number of FX
be connected to the FX
, FX1N, FX2N or FX
0N
2NC
PLCs.
-8AD blocks that can
2N
A unit No. 0 to 7 is automatically assigned to each special unit or special block connected to a
PLC basic unit from the one nearest to the basic unit.
The data is read from a nd written to the FX
-8AD by FROM/TO instr uctions given by the
2N
basic unit.
5-1
FX2N-8AD Analog input blockConnection to PLC 5
MEMO
5-2
FX2N-8AD Analog input block
6.Wiring
6.1Caution
1) Do not lay signal c ab le near to high voltage power cab le or house them in the same trunking
duct. Effects of noise or surge induction may occur. Keep signal cables a safe distance of
more than 100 mm (3.94") from these power cabl es.
Wiring 6
2) The ter minal screws of the FX
-8AD are M3 (0.12"), therefore cr imp style terminals (see
2N
drawing) suitable for use with these screws should be fitted to the cable for wiring.
Figure 6.1: Crimp Terminals
For M3 (0.12")
6.2 mm (0.24" )
or less
For M3 (0.12")
6.2 mm (0.24")
or less
3) The terminal tightening torque is 0.5 to 0.8 Nžm. Tighten securely to avoid malfunction.
4) Cut off all phases of power source before installation or perfor ming wiring work in order to
avoid electric shock or damage of product.
5) Replace the provided terminal cover before supplying power and operating the unit after
installation or wiring work in order to avoid electric shock.
6-1
FX2N-8AD Analog input blockWiring 6
Figure 6.2: Wiring
FX2N-8AD
*6
Thermocouple
(K, J or T type)
*1 Shielded cabl e
Current input
Voltage input
*5
DC24V
*4 Connected to terminal
of PLC main unit
Class D grounding
*3
*2
V3+
I3+
COM3
V2+
I2+
COM2
V1+
I1+
COM1
24+
24-
250
250
250
Ω
Ω
Ω
5.8k
200k
200k
5.8k
200k
AG
Ω
Ω
5.8k
Ω
Ω
Ω
Ω
DC/DC
converter
CH3
CH2
CH1
Note:Use solderless terminals of the following size (M3).
+15V
AG
-15V
Tighten them securely at the tightening torque of 0.5 to 0.8 N•m.
Figure 6.3: Crimp Terminals
For M3 (0.12")
6.2 mm (0.24" )
or less
For M3 (0.12")
6.2 mm (0.24")
or less
6-2
FX2N-8AD Analog input blockWiring 6
*1 Use a two-core, twisted, shielded cable for the analog input line, and separate it from
other power lines or a lines easily induced.
*2 If there is voltage ripple in the input or there is noise in the external wiring, connect a
capacitor of approximately 0.1 to 0.47 µF, 25 V.
*3 F or the current input, mak e sure to sho rt-circuit the “V O+” terminal and the “IO+” terminal
(O: input channel No.).
*4 Make sure to connect the terminal to the terminal of the PLC main unit to
which Class D grounding (100 Ω or less) is performed.
*5 The 24 V DC service power supply of the PLC is also available.
*6 Use an isolated type thermocouple.
-When using the thermocouple input, use compensating conductors suitable to the
thermocouple.
-Never perform wiring to terminals.
•
-For the terminal arrangement, refer to Section 3.
6-3
FX2N-8AD Analog input blockWiring 6
MEMO
6-4
FX2N-8AD Analog input block
7.Specifications
Table 7.1:General specifications
ItemSpecifications
Specifications 7
Ambient temperature
0 to +55 °C during operation, -20 to +70 °C during storage
range
Ambient humidity35 to 85 % RH during operation (Dew condensation shall not be allowed.)
In conformance to JIS C0040
F requency 10 to 57 Hz, half amplitude 0.075 mm, 57 to 150 Hz, acceleration 9.8
Vibration resistance
2
m/s
, 10 times in each of X, Y and Z directions (80 times in total)
(For product installed with DIN rail: F requency 10 to 57 Hz, half amplitude 0.035
2
mm, 57 to 150 Hz, acceleration 4.9 m/s
)
In conformance to JIS C0041
Impact resistance
147 m/s
2
for 11 ms, 3 times in each of X, Y and Z directions with half-sine pulses
By noise simulator of noise voltage 1,000 Vp-p, noise width 1 µs and frequency
Noise resistance
30 to 100 Hz
500 V AC for 1 min
Withstand voltage
(between analog input ter m inal and each terminal of PLC main unit)
In conformance to JEM-1021
Insulation resistance
5 MΩ or more by 500 V DC Megger (between all terminals as a whole and case)
Operating
atmosphere
Corrosive gas and much dusts shall not be detected.
7-1
FX2N-8AD Analog input blockSpecifications 7
Table 7.2:Power supply specifications
ItemSpecifications
Interface driving
24 V DC±10%, 80 mA (maximum), supplied via terminal from outside
power supply
CPU driving power
5 V DC, 50 mA, supplied via extension cable from PLC main unit
supply
Table 7.3:Performance specifications
ItemSpecifications
• When only voltage input and current input are used
500 µs x Number of used channels
• When thermocouple input is used for 1 or more channels
Conv ersion speed
Insulation method
Channel for voltage/current input: 1 ms x Number of used channels
Channel for thermocouple input: 40 ms x Number of use d channels
(Number of used channels indicates number of all channels used for voltage
input, current input or thermocouple input.)
Photocoupler insulates analog inpu t area from PLC.
DC/DC converter insulates power supply from analog I/O.
Channels are not insulated each other.
Number of occupied
8 points (including input points and output points)
I/O points
0N
FX
, FX1N, FX2N, FX
Applicable PLC
(For connection to FX
Built-in memoryEEPROM
2NC
Series PLC
2NC
Series PLC, FX
2NC
-CNV-IF is required.)
7-2
FX2N-8AD Analog input blockSpecifications 7
Table 7.4:Voltage/current input specifications
ItemVoltage inputCurrent input
-10 to +10 V DC
(input resistance: 200 kΩ)
Adjustment is ena b led in following condition:
Offset value: -10 to +9 V
Analog input range
Digital outputSigned 16-bit binarySigned 16-bit binary
Resolution
Gain val ue: 10 V or less
"Gain - Offset": > 1 V
(Resolution is constant.)
However, change is disabled while an alog
value direct display is used.
Maximum absolute input: ±15 V
0.63 mV (20 V × 1/32000)
•
2.5mV (20 V × 1/8000)
•
-20 to +20 mA DC, +4 to +20 mA DC
(input resistance: 250 Ω)
Adjustment is enabled in following condit ion:
Offset v alue: -20 to +17 mA
Gain value: 30 mA or less
"Gain - Offset": > 3 mA
(Resolution is constant.)
However, change is disabled while analog
value direct displa y is used.
Maximum absolute input: ±30 mA
2.50 µA (40 mA × 1/16,000)
•
during input of -20 to +20 mA
5.00 µA (40 mA × 1/8,000)
•
during input of -20 to +20 mA
2.00 µA (16 mA × 1/8,000)
•
during input of +4 to +20 mA
4.00 µA (16 mA × 1/4,000)
•
during input of +4 to +20 mA
Total accuracy
Ambient temperature: 25 °C ± 5 °C
±0.3% (±60 mV) against full scale 20 V
Ambient temperature: 0 to +55 °C
±0.5% (±100 mV) against full sc ale 20 V
Ambient temperature: 25 °C ± 5 °C
µ
±0.3% (±120
+4 to +20mA input is same (±120
Ambient temperature: 0 to +55 °C
±0.5% (±200
+4 to +20mA input is same (±200
A) against full scale 40 mA
µ
A) against full scale 40 mA
7-3
µ
µ
A)
A)
Loading...
+ 61 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.