A04/2005pdpFirst Edition
B07/2005pdpSection 3.8.1Revision of the section "Note on selecting a suitable power
supply ELCB"
C03/2006pdpGeneral
Section 2.4.3
D08/2010aklGeneralAdaption of document version numbers (english, german)
E10/2010aklGeneral
Section 7.2
General
Extension of the capacity classes by the inverters
FR-F740-02600 to 12120
Addition of the inverters FR-F746-00023 to 01160 with
IP54 protection rating
New parameter 299
Addition of a heatsink protrusion attachment
Additions:
• Voltage/current input switch
• Additional explanation to "Causes and corrective actions"
• DC feeding operation permission signal (X70), DC feeding
cancel signal (X71), PID integral value reset signal (X72)
• PID deviation limit signal (Y48), Pulse output of output power
signal (Y79), DC feeding signal (Y85)
New setting values:
• Pr. 29 "Acceleration/deceleration pattern selection" setting
value "6"
• Pr. 30 "Regenerative function selection" setting values "10",
"11", "20", "21"
• Pr. 59 "Remote function selection" setting values "11", "12",
"13"
• Pr. 495 "Remote output selection" setting values "10", "11"
Section 7.6
New parameters:
• Pr. 522 "Output stop frequency"
• Pr. 539 "Modbus-RTU communication check time interval"
• Pr. 653 "Speed smoothing control"
• Pr. 654 "Speed smoothing cutoff frequency"
• Pr. 553 "PID deviation limit", Pr. 554 "PID signal operation
selection", C42 (Pr. 934) "PID display bias coefficient",
C43 (Pr. 934) "PID display bias analog value", C44 (Pr. 935)
"PID display gain coefficient", C45 (Pr. 935) "PID display gain
analog value"
• Pr. 799 "Pulse increment setting for output power"
Partial changes
• Pr. 153 "Zero current detection time" setting range "0 to 10s"
• Check first when you have a trouble
Instruction Manual
Inverter FR-F700 EC
Art. no.: 166461
VersionChanges / Additions / Corrections
F06/2013aklGeneralNew parameters:
• Pr. 147, Pr. 296, Pr. 297, Pr. 390, Pr. 414, Pr. 415, Pr. 498,
Pr. 502, Pr. 505 to Pr. 515, Pr. 561, Pr. 665, Pr. 726 to Pr. 729,
Pr. 753 to Pr. 769, Pr. 774 to Pr. 779, Pr. 826 to Pr. 865, Pr. 870,
Pr. 986, Pr. 997, Pr. 999
New setting values:
• Pr. 30, Pr. 52, Pr. 54, Pr. 128, Pr. 158, Pr. 178 to Pr. 189,
Pr. 190 to Pr. 196, Pr. 331, Pr. 332, Pr. 549, Pr. 573
Additions:
• Option connector 2
• Easy operation mode setting
• Function enhancement of Mitsubishi inverter protocol/
Modbus-RTU protocol communication
This instruction manual provides instructions for advanced use of the FR-F700 series inverters.
Incorrect handling might cause an unexpected fault. Before using the inverter, always read this
instruction manual to use the equipment to its optimum.
Safety instructions
Do not attempt to install, operate, maintain or inspect the inverter until you have read through
this instruction manual carefully and can use the equipment correctly. Do not use the inverter until you have a full knowledge of the equipment, safety information and instructions. In this instruction manual, the safety instruction levels are classified into "WARNING" and "CAUTION".
WARNING:
Assumes that incorrect handling may cause hazardous conditions, resulting in death
or severe injury.
E
CAUTION:
Assumes that incorrect handling may cause hazardous conditions, resulting in medium or slight injury, or may cause physical damage only.
Note that even the CAUTION level may lead to a serious consequence according to conditions.
Please follow strictly the instructions of both levels because they are important to personnel
safety.
FR-F700 EC I
MITSUBISHI ELECTRIC
P
Electric shock prevention
WARNING:
● While power is on or when the inverter is running, do not open the front cover.
Otherwise you may get an electric shock.
● Do not run the inverter with the front cover removed. Otherwise, you may access
the exposed high-voltage terminals or the charging part of the circuitry and get an
electric shock.
● Even if power is off, do not remove the front cover except for wiring or periodic
inspection. You may access the charged inverter circuits and get an electric shock.
● Before starting wiring or inspection, check to make sure that the operation panel
indicator is off, wait for at least 10 minutes after the power supply has been switched
off, and check that there are no residual voltage using a tester or the like. The
capacitor is charged with high voltage for some time after power off and it is
dangerous.
● This inverter must be earthed. Earthing must conform to the requirements of
national and local safety regulations and electrical codes. (JIS, NEC section 250,
IEC 536 class 1 and other applicable standards)
● Any person who is involved in the wiring or inspection of this equipment should
be fully competent to do the work.
● Always install the inverter before wiring. Otherwise, you may get an electric shock
or be injured.
● If your application requires by installation standards an RCD (residual current
device) as up stream protection please select according to DIN VDE 0100-530 as
following:
Single phase inverter type A or B
Three phase inverter only type B.
● Perform setting dial and key operations with dry hands to prevent an electric shock.
Otherwise you may get an electric shock. Perform setting dial and key operations
with dry hands to prevent an electric shock. Otherwise you may get an electric
shock.
● Do not subject the cables to scratches, excessive stress, heavy loads or pinching.
Otherwise you may get an electric shock.
● Do not replace the cooling fan while power is on. It is dangerous to replace the
cooling fan while power is on.
● Do no
t touch the printed circuit board or handle the cables with wet hands. You may get
an electric shock.
II
E
E
Fire prevention
CAUTION:
● Install the inverter on a nonflammable wall without holes (so that nobody can touch
the inverter heatsink on the rear side, etc.). Mounting it to or near combustible
material can cause a fire.
● If the inverter has become faulty, switch off the inverter power. A continuous flow
of large current could cause a fire.
● Do not connect a resistor directly to the DC terminals P/+, N/–. This could cause a
fire and destroy the inverter. The surface temperature of braking resistors can far
exceed 100°C for brief periods. Make sure that there is adequate protection against
accidental contact and a safe distance is maintained to other units and system
parts.
Injury prevention
CAUTION:
● Apply only the voltage specified in the instruction manual to each terminal. Otherwise, burst, damage, etc. may occur.
● Ensure that the cables are connected to the correct terminals. Otherwise, burst,
damage, etc. may occur.
● Always make sure that polarity is correct to prevent damage, etc. Otherwise, burst,
damage, etc. may occur.
● While power is on or for some time after power-off, do not touch the inverter as it
is hot and you may get burnt.
FR-F700 EC III
MITSUBISHI ELECTRIC
E
Additional instructions
Also note the following points to prevent an accidental failure, injury, electric shock, etc.
Transportation and installation
CAUTION:
● When carrying products, use correct lifting gear to prevent injury.
● Do not stack the inverter boxes higher than the number recommended.
● Ensure that installation position and material can withstand the weight of the
inverter. Install according to the information in the instruction manual.
● Do not install or operate the inverter if it is damaged or has parts missing. This can
result in breakdowns.
● When carrying the inverter, do not hold it by the front cover or setting dial; it may
fall off or fail.
● Do not stand or rest heavy objects on the product.
● Check the inverter mounting orientation is correct.
● Prevent other conductive bodies such as screws and metal fragments or other
flammable substance such as oil from entering the inverter.
● As the inverter is a precision instrument, do not drop or subject it to impact.
● Use the inverter under the following environmental conditions. Otherwise, the
inverter may be damaged
E
Operating ConditionFR-F740FR-F746
Ambient temperature
Ambient humidity90% RH or less (non-condensing)
Storage temperature−20°C to +65°C
AtmosphereIndoors (free from corrosive gas, flammable gas, oil mist, dust and dirt)
Altitude
Vibration
Temperature applicable for a short time, e.g. in transit.
2.9m/s² or less for the 04320 or more.
Wiring
CAUTION:
● Do not install assemblies or components (e. g. power factor correction capacitors)
on the inverter output side, which are not approved from Mitsubishi.
● The direction of rotation of the motor corresponds to the direction of rotation
commands (STF/STR) only if the phase sequence (U, V, W) is maintained.
−10°C to +40/+50°C (non-freezing)−10°C to +30/+40°C (non-freezing)
The maximum temperature depends on the setting of Pr. 570.
Maximum 1000m above sea level for standard operation. After that derate by 3% for
every extra 500m up to 2500m (91%)
5.9m²
or less at 10 to 55Hz (directions of X, Y, Z axes)
IV
P
Operation
WARNING:
● When you have chosen the retry function, stay away from the equipment as it will
restart suddenly after an alarm stop.
● Since pressing STOP/RESET key may not stop output depending on the function
setting status, provide a circuit and switch separately to make an emergency stop
(power off, mechanical brake operation for emergency stop, etc.).
● Make sure that the start signal is off before resetting the inverter alarm. A failure
to do so may restart the motor suddenly.
● The inverter can be started and stopped via the serial port communications link or
the field bus. However, please note that depending on the settings of the
communications parameters it may not be possible to stop the system via these
connections if there is an error in the communications system or the data line. In
configurations like this it is thus essential to install additional safety hardware that
makes it possible to stop the system in an emergency (e.g. controller inhibit via
control signal, external motor contactor etc). Clear and unambiguous warnings
about this must be posted on site for the operating and service staff.
● The load used should be a three-phase induction motor only. Connection of any
other electrical equipment to the inverter output may damage the inverter as well
as the equipment.
● Do not modify the equipment.
● Do not perform parts removal which is not instructed in this manual. Doing so may
lead to fault or damage of the inverter.
FR-F700 EC V
MITSUBISHI ELECTRIC
E
CAUTION:
● The electronic thermal relay function does not guarantee protection of the motor
from overheating. It is recommended to install both an external thermal and PTC
thermistor for overheat protection.
● Do not use a magnetic contactor on the inverter input for frequent starting/stopping
of the inverter. Otherwise, the life of the inverter decreases.
● Use a noise filter to reduce the effect of electromagnetic interference and follow
the accepted EMC procedures for proper installation of frequency inverters. Otherwise nearby electronic equipment may be affected.
● Take appropriate measures regarding harmonics. Otherwise this can endanger
compensation systems or overload generators.
● Use a motor designed for inverter operation. (The stress for motor windings is
bigger than in line power supply).
● When parameter clear or all clear is performed, set again the required parameters
before starting operations. Each parameter returns to the initial value.
● The inverter can be easily set for high-speed operation. Before changing its setting,
fully examine the performances of the motor and machine.
● The DC braking function of the frequency inverter is not designed to continuously
hold a load. Use an electro-mechanical holding brake on the motor for this purpose.
● Before running an inverter which had been stored for a long period, always perform
inspection and test operation.
● For prevention of damage due to static electricity, touch nearby metal before
touching this product to eliminate static electricity from your body.
E
E
Diagnosis and settings
CAUTION:
● Before starting operation, confirm and adjust the parameters. A failure to do so
may cause some machines to make unexpected motions.
Emergency stop
CAUTION:
● Provide a safety backup such as an emergency brake which will prevent the
machine and equipment from hazardous conditions if the inverter fails.
● When the breaker on the inverter primary side trips, check for the wiring fault (short
circuit), damage to internal parts of the inverter, etc. Identify the cause of the trip,
then remove the cause and power on the breaker.
● When the protective function is activated (i. e. the frequency inverter switches off
with an error message), take the corresponding corrective action as described in
the inverter manual, then reset the inverter, and resume operation.
VI
E
E
Maintenance, inspection and parts replacement
CAUTION:
● Do not carry out a megger (insulation resistance) test on the control circuit of the
inverter. It will cause a failure.
Disposing the inverter
CAUTION:
● Treat as industrial waste.
General instructions
Many of the diagrams and drawings in instruction manuals show the inverter without a cover, or
partially open. Never run the inverter in this status. Always replace the cover and follow this instruction manual when operating the inverter.
FR-F700 EC VII
MITSUBISHI ELECTRIC
Symbols used in the manual
Use of instructions
Instructions concerning important information are marked separately and are displayed as follows:
NOTEText of instruction
Use of examples
Examples are marked separately and are displayed as follows:
Example 쑴Example text쑶
Use of numbering in the figures
Numbering within the figures is displayed by white numbers within black circles and is explained
in a table following it using the same number, e.g.:
Use of handling instructions
Handling instructions are steps that must be carried out in their exact sequence during startup,
operation, maintenance and similar operations.
They are numbered consecutively (black numbers in white circles):
Tex t.
Tex t.
Tex t.
Use of footnotes in tables
Instructions in tables are explained in footnotes underneath the tables (in superscript). There is
a footnote character at the appropriate position in the table (in superscript).
If there are several footnotes for one table then these are numbered consecutively underneath
the table (black numbers in white circle, in superscript):
Product checking and part identificationInverter type
SymbolVoltage Class
F740
Three-phase
400V class
SymbolType num ber
00023
to
12120
5-digit display
SymbolVoltage Class
F746
Three-phase
400V class
waterproof structure IP54
(standard IEC 60529: 2001)
specification
SymbolType num ber
00023
to
01160
5-digit display
1Product checking and part identification
Unpack the inverter and check the capacity plate on the front cover and the rating plate on the
inverter side face to ensure that the product agrees with your order and the inverter is intact.
1.1 Inverter type
I001331E
Fig. 1-1: Inverter Type FR-F740 EC
Fig. 1-2: Inverter type FR-F746 EC
I001393E
FR-F700 EC 1 - 1
Description of the caseProduct checking and part identification
Capacity plate
Capacity plate
Front cover
Overload current
rating
Ambient
temperature
Inverter type
Inverter typeSerial number
RS485 terminal
PU connector
(refer to section 3.5)
Rating plate
Comb shaped
wiring cover
(refer to section 2.3)
Control c ircuit
terminal block
(refer to section 3.4)
Main circuit terminal
block (refer to section
3.3)
CHARGE lamp
Lit when power is
supplied to the main
circuit.
POWER lamp
Lit when the control circuit
(R1/L11, S1/L21) is supplied
with power.
ALARM lamp
Lit when the inverter
is in the alarm status
(major fault)
(refer to chapter 7)
Connector with/without EMC filter
(refer to section 3.8.3)
AU/PTC-switchover
(refer to section 3.4)
Connector for plug-in option connection
(Refer to the instruction manual of options)
There are two connection connectors, called
connector 1 and connector 2 from the top.
Cooling fan
(refer to section 8.1.7)
Operation panel FR-DU07
(refer to section 4.3)
Output rating
Voltage/current input switch
(refer to section 3.2)
Input rating
Serial number
Production year-month
1.2 Description of the case
NOTEFor removal and reinstallation of covers, refer to section 2.2.
FR-F740-00126-EC
Fig. 1-3: Appearance and Structure
FR-F740-00126-EC
LD 120% 60s, 150% 3s 50 C
SLD 110% 60s, 120% 3s 40 C
LD (50 C) XXA
SLD (40 C) XXA
I000990E_F
1 - 2
Product checking and part identificationDescription of the case
1.2.1 Accessory
Fan cover fixing screws
CapacityScrew Size[mm]Number
00083/00126M3 × 351
00170 to 00380M4 × 402
00470/00620M4 × 501
Tab. 1-1: Fan cover fixing screws
NOTESThe fan cover fixing screws are not delivered with models 00620 or less.
For removal and reinstallation of the cooling fans, refer to section 8.1.7.
DC reactor
For models 01800 or more the supplied DC reactor has to be installed.
Eyebolts
Eyebolts for hanging the inverter are delivered with the models 00770 to 06830.
CapacityEyebolt sizeNumber
00770M82
00930 to 03610M102
04320 to 06830M122
Tab. 1-2: Size of the delivered eyebolts
FR-F700 EC 1 - 3
Description of the caseProduct checking and part identification
1 - 4
InstallationRemoval and reinstallation of the operation panel
Loosen the screws
Remove operation panel
2Installation
CAUTION:
Check that packing is not removed at removal or reinstallation of a cover. If packing
E
2.1 Removal and reinstallation of the operation panel
E
is removed, contact the sales representative. If the inverter is used with packing
removed, the inverter does not conform to IP54.
CAUTION:
● If the operation panel of the inverter FR-F746 is removed from the front cover, the
inverter does not conform to IP54.
● The operation panel (FR-DU07) is designed to IP54 specifications. Do not install
the FR-DU07 mounted on the FR-F740 EC.
Loosen the two screws on the operation panel. (These screws cannot be removed.)
Push the left and right hooks of the operation panel and pull the operation panel toward you
to remove.
I000991E
Fig. 2-1:Removal and reinstallation of the operation panel
When reinstalling the operation panel, insert it straight to reinstall securely and tighten the
FR-F700 EC 2 - 1
fixed screws of the operation panel.
Removal and reinstallation of the front coverInstallation
Loosen the screws
Remove front cover
Installation hook
Insert hooks into the socketsPress front cover against
the inverter
Tighten the installation
screws
2.2 Removal and reinstallation of the front cover
2.2.1 FR-F740-00023 to 00620-EC
Removal
Loosen the installation screws of the front cover.
Pull the front cover toward you to remove by pushing an installation hook using left fixed
hooks as supports.
Fig. 2-2:Removal of the front cover
Reinstallation
Insert the two fixed hooks on the left side of the front cover into the sockets of the inverter.
Using the fixed hooks as supports, securely press the front cover against the inverter.
(Although installation can be done with the operation panel mounted, make sure that a
connector is securely fixed.)
Tighten the installation screws and fix the front cover.
I000992E
2 - 2
I000993E
Fig. 2-3:Reinstallation of the front cover
InstallationRemoval and reinstallation of the front cover
Loosen the screw of front
cover 1
Remove front cover
Installation hook
Cover 1
Cover 2
Loosen the screw of front
cover 2
2.2.2 FR-F740-00770 to 12120-EC
Removal
Loosen the installation screws of the front cover 1.
Loosen the installation screws of the front cover 2.
Pull the front cover 2 toward you to remove by pushing an installation hook on the right side
using left fixed hooks as supports.
Fig. 2-4:Removal of the front cover
I000994E
FR-F700 EC 2 - 3
Removal and reinstallation of the front coverInstallation
Insert hooks into the sockets
Press front cover 2 against the inverter
Fix front cover 2 with the
installation screws
Fix front cover 1 with the
installation screws
Reinstallation
Insert the two fixed hooks on the left side of the front cover 2 into the sockets of the inverter.
Using the fixed hooks as supports, securely press the front cover 2 against the inverter.
(Although installation can be done with the operation panel mounted, make sure that a
connector is securely fixed.)
Fix the front cover 2 with the installation screws.
Fix the front cover 1 with the installation screws.
Fig. 2-5:Reinstallation of the front cover
NOTESFor the FR-F740-04320 or more, the front cover 1 is separated into two parts.
Fully make sure that the front cover has been reinstalled securely. Always tighten the installation screws of the front cover.
The same serial number is printed on the capacity plate of the front cover and the rating
plate of the inverter. Before reinstalling the front cover, check the serial numbers to ensure
that the cover removed is reinstalled to the inverter from where it was removed.
I000995E
2 - 4
InstallationRemoval and reinstallation of the front cover
Metal chain
Removal/installation
hook
Connection cable
2.2.3 FR-F746-00023 to 01160-EC
Removal
Loosen the installation screw of the front cover.
Since the metal chain is mounted to the front cover, remove the front cover slowly.
Remove the connection cable from the PU connector.
Remove the hook of metal chain end from the inverter.
Remove the front cover.
Fig. 2-6:
Removal of the front cover
I001394E
Reinstallation
Install the hook of metal chain end to the inverter.
Connect the connection cable to the PU connector.
Fix the front cover using the installation screws securely. When installing the front cover,
be careful not to pinch the connection cable or the metal chain.
Fig. 2-7:
Reinstallation of the front cover
I001395E
FR-F700 EC 2 - 5
MountingInstallation
00023 to 00620CAUTION:
When encasing multiple inverters, follow the
instructions on page 2-11.
00770 to 12120
R
e
f
e
r
t
o
F
i
g
.
2
-
1
0
Fix six positions for the FR-F740-04320
to 08660 and fix eight positions for the
FR-F740-09620 to 12120.
Direct sunlightVibration (≥ 5,9 m/s²)
(≥ 2.9m/s² for the 04320 or more)
High temperature,
high humidity
Horizontal placement
Vertical mounting
(When installing two or more
inverters, install them in
parallel.)
Transportation by holding
the front cover
Oil mist, flammable gas,
corrosive gas, fluff, dust, etc.
Mounting to combustible
material
2.3 Mounting
I000997E
Fig. 2-8:Installation on the panel
The inverter consists of precision mechanical and electronic parts. Never install or handle it in
any of the following conditions as doing so could cause an operation fault or failure.
I000998E
Fig. 2-9:Conditions, that could cause an operation fault or failure
2 - 6
Loading...
+ 650 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.