Mitsubishi Electric F700, FR-F720, FR-F740 Instruction Manual

INVERTER
INSTRUCTION MANUAL (BASIC)
FR-F720-0.75K to 110K FR-F740-0.75K to 560K
Thank you for choosing this Mitsubishi Inverter. This Instruction Manual (basic) is intended for users who "just want to run the inverter". If you are going to utilize functions and performance, refer to the Instruction Manual (applied) [IB-0600177ENG]. The Instruction Manual (applied) is separately available from where you purchased the inverter or your Mitsubishi sales representative.
CONTENTS
PRODUCT CHECKING AND PARTS IDENTIFICATION ..............................1
1
INSTALLATION AND WIRING ......................................................................2
2
2.1 Peripheral devices .....................................................................................................3
2.2 Method of removal and reinstallation of the front cover ............................................5
2.3 Installation of the inverter and instructions ................................................................7
2.4 Wiring.........................................................................................................................8
2.5 Connection of stand-alone option units ...................................................................28
2.6 Power-off and magnetic contactor (MC) .................................................................36
2.7 Precautions for use of the inverter ..........................................................................37
2.8 Failsafe of the system which uses the inverter .......................................................39
DRIVE THE MOTOR ....................................................................................40
3
3.1 Step of operation .....................................................................................................40
3.2 Operation panel (FR-DU07) ....................................................................................41
3.3 Overheat protection of the motor by the inverter (Pr. 9) .........................................46
3.4 When the rated motor frequency is 50Hz (Pr. 3) ....................................................47
3.5 Start/stop from the operation panel (PU operation mode) ......................................48
3.6 Start and stop using terminals (External operation) ................................................57
4
ADJUSTMENT .............................................................................................65
4.1 Simple mode parameter list.....................................................................................65
4.2 Increasing the starting torque (Pr. 0).......................................................................66
4.3 Limiting the maximum and minimum output frequency (Pr. 1, Pr. 2)......................67
4.4 Changing acceleration and deceleration time (Pr. 7, Pr. 8) ....................................68
4.5 Energy saving operation (Pr. 60).............................................................................69
4.6 Selection of the operation command and frequency command locations (Pr. 79).71
4.7 Parameter clear, all parameter clear .......................................................................72
4.8 Parameter copy and parameter verification ............................................................73
4.9 Parameter list...........................................................................................................75
TROUBLESHOOTING ...............................................................................102
5
5.1 Reset method of protective function......................................................................102
5.2 List of fault or alarm display...................................................................................103
5.3 Causes and corrective actions ..............................................................................104
5.4 Correspondences between digital and actual characters .....................................115
5.5 Check and clear of the faults history .....................................................................116
5.6 Check first when you have a trouble .....................................................................118
6
PRECAUTIONS FOR MAINTENANCE AND INSPECTION......................125
6.1 Inspection item.......................................................................................................125
SPECIFICATIONS......................................................................................134
7
7.1 Rating.....................................................................................................................134
7.2 Common specifications .........................................................................................136
7.3 Outline dimension drawings ..................................................................................138
7.4 Heatsink protrusion attachment procedure ...........................................................149
1
2
3
4
5
6
7
This Instruction Manual (Basic) provides handling information and precautions for use of the equipment. Please forward this Instruction Manual (Basic) to the end user.
2. Fire Prevention

This section is specifically about safety matters

Do not attempt to install, operate, maintain or inspect the inverter until you have read through this Instruction Manual (Basic) and appended documents carefully and can use the equipment correctly. Do not use the inverter until you have a full knowledge of the equipment, safety information and instructions. In this Instruction Manual (Basic), the safety instruction levels are classified into "WARNING" and "CAUTION".
WARNING
Incorrect handling may cause hazardous conditions, resulting in death or severe injury.
CAUTION
Incorrect handling may cause hazardous conditions, resulting in medium or slight injury, or may cause only material damage.
CAUTION
The level may even lead to a serious consequence according to conditions. Both instruction levels must be followed
because these are important to personal safety.
1. Electric Shock Prevention
WARNING
While power is ON or when the inverter is running, do not open the front cover. Otherwise you may get an electric shock.
Do not run the inverter with the front cover or wiring cover
Inverter must be installed on a nonflammable wall without
holes (so that nobody touches the inverter heatsink on the rear side, etc.). Mounting it to or near flammable material can cause a fire.
If the inverter has become faulty, the inverter power must be switched OFF. A continuous flow of large current could cause a fire.
Do not connect a resistor directly to the DC terminals P/+ and N/-. Doing so could cause a fire.
3. Injury Prevention
The voltage applied to each terminal must be the ones specified in the Instruction Manual. Otherwise burst, damage, etc. may occur.
The cables must be connected to the correct terminals. Otherwise burst, damage, etc. may occur.
Polarity must be correct. Otherwise burst, damage, etc. may occur.
While power is ON or for some time after power-OFF, do not touch the inverter since the inverter will be extremely hot. Doing so can cause burns.
CAUTION
CAUTION
removed. Otherwise you may access the exposed high-voltage terminals or the charging part of the circuitry and get an electric shock.
Even if power is off, do not remove the front cover except for wiring or periodic inspection. You may access the charged inverter circuits and get an electric shock.
Before wiring, inspection or switching EMC filter ON/OFF connector, power must be switched OFF. To confirm that, LED indication of the operation panel must be checked. (It must be OFF.) Any person who is involved in wiring, inspection or switching EMC filter ON/OFF connector shall wait for at least 10 minutes after the power supply has been switched OFF and check that there are no residual voltage using a tester or the like. The capacitor is charged with high voltage for some time after power OFF, and it is dangerous.
This inverter must be earthed (grounded). Earthing (grounding) must conform to the requirements of national and local safety regulations and electrical code (NEC section 250, IEC 536 class 1 and other applicable standards). A neutral-point earthed (grounded) power supply for 400V class inverter in compliance with EN standard must be used.
Any person who is involved in wiring or inspection of this equipment shall be fully competent to do the work.
The inverter must be installed before wiring. Otherwise you may get an electric shock or be injured.
Setting dial and key operations must be performed with dry hands to prevent an electric shock. Otherwise you may get an electric shock.
Do not subject the cables to scratches, excessive stress, heavy loads or pinching. Otherwise you may get an electric shock.
Do not replace the cooling fan while power is on. It is dangerous to replace the cooling fan while power is on.
Do not touch the printed circuit board with wet hands. You may
4. Additional Instructions
Also the following points must be noted to prevent an accidental failure, injury, electric shock, etc.
(1) Transportation and installation
CAUTION
The product must be transported in correct method that corresponds to the weight. Failure to do so may lead to injuries.
Do not stack the boxes containing inverters higher than the number recommended.
The product must be installed to the position where withstands the weight of the product according to the information in the Instruction Manual.
Do not install or operate the inverter if it is damaged or has parts missing. This can result in breakdowns.
When carrying the inverter, do not hold it by the front cover or setting dial; it may fall off or fail.
Do not stand or rest heavy objects on the product.
The inverter mounting orientation must be correct.
Foreign conductive bodies must be prevented to enter the
inverter. That includes screws and metal fragments or other flammable substance such as oil.
As the inverter is a precision instrument, do not drop or subject it to impact.
The inverter must be used under the following environment: Otherwise the inverter may be damaged.
Surrounding air temperature
Ambient humidity 90% RH or less (non-condensing) Storage temperature -20°C to +65°C
Atmosphere
Environment
Altitude, vibration
-10°C to +50°C (non-freezing)
Indoors (free from corrosive gas, flammable gas, oil mist, dust and dirt)
Maximum 1000m above sea level for standard operation. 5.9m/s2 or less at 10 to
55Hz (directions of X, Y, Z axes)
get an electric shock.
When measuring the main circuit capacitor capacity (Pr. 259 Main circuit capacitor life measuring = "1"), the DC voltage is
applied to the motor for 1s at powering off. Never touch the
*1 Temperature applicable for a short time, e.g. in transit. *2 2.9m/s
2
or less for the 185K or more.
motor terminal, etc. right after powering off to prevent an electric shock.
*1
*2
A-1
(2) Wiring
Do not install a power factor correction capacitor, surge suppressor or capacitor type filter on the inverter output side. These devices on the inverter output side may be overheated or burn out.
The connection orientation of the output cables U, V, W to the motor affects the rotation direction of the motor.
(3) Test operation and adjustment
CAUTION
CAUTION
Before starting operation, each parameter must be confirmed and adjusted. A failure to do so may cause some machines to make unexpected motions.
(4) Operation
Any person must stay away from the equipment when the retry function is set as it will restart suddenly after trip.
Since pressing key may not stop output depending on
the function setting status, separate circuit and switch that make an emergency stop (power OFF, mechanical brake operation for emergency stop, etc.) must be provided.
OFF status of the start signal must be confirmed before resetting the inverter fault. Resetting inverter alarm with the start signal ON restarts the motor suddenly.
The inverter must be used for three-phase induction motors. Connection of any other electrical equipment to the inverter output may damage the equipment.
Do not modify the equipment.
Do not perform parts removal which is not instructed in this
manual. Doing so may lead to fault or damage of the inverter.
WARNING
(5) Emergency stop
A safety backup such as an emergency brake must be provided to prevent hazardous condition to the machine and equipment in case of inverter failure.
When the breaker on the inverter input side trips, the wiring must be checked for fault (short circuit), and internal parts of the inverter for a damage, etc. The cause of the trip must be identified and removed before turning ON the power of the breaker.
When any protective function is activated, appropriate corrective action must be taken, and the inverter must be reset before resuming operation.
(6) Maintenance, inspection and parts replacement
CAUTION
CAUTION
Do not carry out a megger (insulation resistance) test on the control circuit of the inverter. It will cause a failure.
(7) Disposing of the inverter
CAUTION
The inverter must be treated as industrial waste.
General instructions
Many of the diagrams and drawings in this Instruction Manual (basic) show the inverter without a cover or partially open for explanation. Never operate the inverter in this manner. The cover must be always reinstalled and the instruction in this Instruction Manual (basic) must be followed when operating the inverter.
CAUTION
The electronic thermal relay function does not guarantee protection of the motor from overheating. It is recommended to install both an external thermal and PTC thermistor for overheat protection.
Do not use a magnetic contactor on the inverter input for frequent starting/stopping of the inverter. Otherwise the life of the inverter decreases.
The effect of electromagnetic interference must be reduced by using a noise filter or by other means. Otherwise nearby electronic equipment may be affected.
Appropriate measures must be taken to suppress harmonics. Otherwise power supply harmonics from the inverter may heat/ damage the power factor correction capacitor and generator.
When driving a 400V class motor by the inverter, the motor must be an insulation-enhanced motor or measures must be taken to suppress surge voltage. Surge voltage attributable to the wiring constants may occur at the motor terminals, deteriorating the insulation of the motor.
When parameter clear or all parameter clear is performed, the required parameters must be set again before starting operations because all parameters return to the initial value.
The inverter can be easily set for high-speed operation. Before changing its setting, the performances of the motor and machine must be fully examined.
Stop status cannot be hold by the inverter's brake function. In addition to the inverter's brake function, a holding device must be installed to ensure safety.
Before running an inverter which had been stored for a long period, inspection and test operation must be performed.
For prevention of damage due to static electricity, nearby metal must be touched before touching this product to eliminate static electricity from your body.
A-2
— CONTENTS —
1 PRODUCT CHECKING AND PARTS IDENTIFICATION 1
2 INSTALLATION AND WIRING 2
2.1 Peripheral devices...................................................................................................... 3
2.2 Method of removal and reinstallation of the front cover............................................. 5
2.3 Installation of the inverter and instructions.................................................................7
2.4 Wiring.......................................................................................................................... 8
2.4.1 Terminal connection diagram .................................................................................................... 8
2.4.2 EMC filter ................................................................................................................................... 9
2.4.3 Specification of main circuit terminal ....................................................................................... 10
2.4.4 Terminal arrangement of the main circuit terminal, power supply and the motor wiring ......... 10
2.4.5 Control circuit terminals ........................................................................................................... 19
2.4.6 Changing the control logic ....................................................................................................... 22
2.4.7 Wiring of control circuit ............................................................................................................ 24
2.4.8 When connecting the operation panel using a connection cable ............................................ 26
2.4.9 RS-485 terminal block ............................................................................................................. 27
2.4.10 Communication operation........................................................................................................ 27
2.5 Connection of stand-alone option units.................................................................... 28
2.5.1 Connection of the brake unit (FR-BU2) ................................................................................... 28
2.5.2 Connection of the brake unit (FR-BU/MT-BU5) ....................................................................... 30
2.5.3 Connection of the brake unit (BU type) ................................................................................... 32
2.5.4 Connection of the high power factor converter (FR-HC/MT-HC)............................................. 32
2.5.5 Connection of the power regeneration common converter (FR-CV)(55K or less) ................... 34
2.5.6 Connection of the power regeneration converter (MT-RC) (75K or more) .............................. 35
2.5.7 Connection of the power factor improving DC reactor (FR-HEL) ............................................ 35
CONTENTS
2.6 Power-off and magnetic contactor (MC) ..................................................................36
2.7 Precautions for use of the inverter ........................................................................... 37
2.8 Failsafe of the system which uses the inverter ........................................................39
3 DRIVE THE MOTOR 40
3.1 Step of operation......................................................................................................40
3.2 Operation panel (FR-DU07)..................................................................................... 41
3.2.1 Parts of the operation panel (FR-DU07) .................................................................................. 41
3.2.2 Basic operation (factory setting) .............................................................................................. 42
3.2.3 Operation lock (Press [MODE] for an extended time (2s)) ...................................................... 43
3.2.4 Monitoring of output current and output voltage ...................................................................... 44
3.2.5 First priority monitor ................................................................................................................. 44
3.2.6 Setting dial push ...................................................................................................................... 44
3.2.7 Changing the parameter setting value..................................................................................... 45
3.3 Overheat protection of the motor by the inverter (Pr. 9) .......................................... 46
3.4 When the rated motor frequency is 50Hz (Pr. 3) .....................................................47
3.5 Start/stop from the operation panel (PU operation mode).......................................48
3.5.1 Setting the set frequency to operate (example: performing operation at 30Hz) ...................... 48
I
3.5.2 Using the setting dial like a potentiometer at the operation. .................................................... 50
3.5.3 Setting the frequency by switches (three-speed setting) ......................................................... 51
3.5.4 Setting the frequency by analog input (voltage input) ............................................................. 53
3.5.5 Setting the frequency by analog input (current input) .............................................................. 55
3.6 Start and stop using terminals (External operation).................................................57
3.6.1 Setting the frequency by the operation panel (Pr. 79 = 3) ....................................................... 57
3.6.2 Setting the frequency by switches (three-speed setting) (Pr. 4 to Pr. 6) ................................. 59
3.6.3 Setting the frequency by analog input (voltage input) ............................................................. 61
3.6.4 Changing the output frequency (60Hz, initial value) at the maximum voltage
input (5V, initial value) ............................................................................................................ 62
3.6.5 Setting the frequency by analog input (current input) .............................................................. 63
3.6.6 Changing the output frequency (60Hz, initial value) at the maximum current input
(at 20mA, initial value) ............................................................................................................. 64
4 ADJUSTMENT 65
4.1 Simple mode parameter list .....................................................................................65
4.2 Increasing the starting torque (Pr. 0)........................................................................66
4.3 Limiting the maximum and minimum output frequency (Pr. 1, Pr. 2) ......................67
4.4 Changing acceleration and deceleration time (Pr. 7, Pr. 8)..................................... 68
4.5 Energy saving operation (Pr. 60) ............................................................................. 69
4.5.1 Energy saving operation mode (setting "4") ............................................................................ 69
4.5.2 Optimum excitation control mode (setting "9")......................................................................... 69
4.6 Selection of the operation command and frequency command locations (Pr. 79).. 71
4.7 Parameter clear, all parameter clear.................................................................... 72
4.8 Parameter copy and parameter verification......................................................... 73
4.8.1 Parameter copy ....................................................................................................................... 73
4.8.2 Parameter verification.............................................................................................................. 74
4.9 Parameter list.......................................................................................................75
4.9.1 List of parameters classified by the purpose ........................................................................... 75
4.9.2 Display of the extended parameters ........................................................................................ 77
4.9.3 Parameter list .......................................................................................................................... 78
5 TROUBLESHOOTING 102
5.1 Reset method of protective function.......................................................................102
5.2 List of fault or alarm display....................................................................................103
5.3 Causes and corrective actions ...............................................................................104
5.4 Correspondences between digital and actual characters......................................115
5.5 Check and clear of the faults history.................................................................. 116
5.6 Check first when you have a trouble......................................................................118
5.6.1 Motor does not start............................................................................................................... 118
5.6.2 Motor or machine is making abnormal acoustic noise........................................................... 120
5.6.3 Inverter generates abnormal noise........................................................................................ 120
5.6.4 Motor generates heat abnormally.......................................................................................... 120
5.6.5 Motor rotates in the opposite direction .................................................................................. 121
II
5.6.6 Speed greatly differs from the setting .................................................................................... 121
5.6.7 Acceleration/deceleration is not smooth ................................................................................ 121
5.6.8 Speed varies during operation............................................................................................... 122
5.6.9 Operation mode is not changed properly .............................................................................. 122
5.6.10 Operation panel (FR-DU07) display is not operating............................................................. 123
5.6.11 Motor current is too large....................................................................................................... 123
5.6.12 Speed does not accelerate .................................................................................................... 124
5.6.13 Unable to write parameter setting.......................................................................................... 124
5.6.14 Power lamp is not lit .............................................................................................................. 124
6 PRECAUTIONS FOR MAINTENANCE AND INSPECTION 125
6.1 Inspection item ....................................................................................................... 125
6.1.1 Daily inspection ..................................................................................................................... 125
6.1.2 Periodic inspection ................................................................................................................ 125
6.1.3 Daily and periodic inspection................................................................................................. 126
6.1.4 Display of the life of the inverter parts ................................................................................... 127
6.1.5 Cleaning ................................................................................................................................ 129
6.1.6 Replacement of parts ............................................................................................................ 129
6.1.7 Inverter replacement.............................................................................................................. 133
CONTENTS
7 SPECIFICATIONS 134
7.1 Rating .....................................................................................................................134
7.2 Common specifications .......................................................................................... 136
7.3 Outline dimension drawings ...................................................................................138
7.3.1 Inverter outline dimension drawings ...................................................................................... 138
7.4 Heatsink protrusion attachment procedure............................................................149
7.4.1 When using a heatsink protrusion attachment (FR-A7CN) ................................................... 149
7.4.2 Protrusion of heatsink of the FR-F740-185K or more............................................................ 149
APPENDICES 151
Appendix 1 For customers who are replacing the conventional model
with this inverter ..................................................................................... 151
Appendix 1-1 Replacement of the FR-F500 series ......................................................................... 151
Appendix 1-2 Replacement of the FR-A100 <EXCELENT> series ................................................. 152
Appendix 2 Instructions for UL and cUL compliance ............................................... 153
Appendix 3 Instructions for compliance with the EU Directives ............................... 155
III
<Abbreviations> DU: Operation panel (FR-DU07) PU: Operation panel(FR-DU07) and parameter unit (FR-PU04/FR-PU07) Inverter: Mitsubishi inverter FR-F700 series FR-F700: Mitsubishi inverter FR-F700 series Pr.: Parameter Number PU operation: Operation using the PU (FR-DU07/FR-PU04/FR-PU07). External operation: Operation using the control circuit signals Combined operation: Combined operation using the PU (FR-DU07/FR-PU04/FR-PU07) and external operation Standard motor: SF-JR Constant-torque motor: SF-HRCA
<Trademarks>
ONWORKS
L
®
is registered trademarks of Echelon Corporation in the U.S.A. and other countries. DeviceNet is a registered trademark of ODVA (Open DeviceNet Vender Association, Inc.). Company and product names herein are the trademarks and registered trademarks of their respective owners.
IV
1

PRODUCT CHECKING AND PARTS IDENTIFICATION

Unpack the inverter and check the capacity plate on the front cover and the rating plate on the inverter side face to ensure that the product agrees with your order and the inverter is intact.
Inverter Model
FR --F740
Symbol
F720 F740
Connector for plug-in option connection
(Refer to the instruction manual of options.)
Voltage/current input switch
(Refer to page 8)
Operation panel (FR-DU07)
(Refer to page 5)
Power lamp
Lit when the control circuit (R1/L11, S1/L21) is supplied with power.
Alarm lamp
Lit when the inverter is in the alarm status (fault).
Voltage Class Three-phase 200V class Three-phase 400V class
RS-485 terminals
(Refer to page 27)
AU/PTC switchover switch
(Refer to the chapter 4 of the Instruction Manual (applied).)
EMC filter ON/OFF connector
(Refer to page 9)
Front cover
(Refer to page 5)
Capacity plate
Capacity plate
5.5
Indicate inverter capacity (kW)
FR-F740-5.5K
Inverter model
K
Serial number
Control circuit terminal block
(Refer to page 10)
Main circuit terminal block
(Refer to page 19)
Combed shaped wiring cover
(Refer to page 13)
PU connector
(Refer to page 26)
Rating plate
Rating plate
Inverter model
Applied motor
capacity
Input rating
Output rating
Serial number
Cooling fan
(Refer to page 130)
Charge lamp
Lit when power is supplied to the main
(Refer to page 10)
circuit
FR-F740-5.5K
1
Accessory
· Fan cover fixing screws (30K or less)
(Refer to page 155)
Capacity Screw Size (mm) Number
2.2K to 5.5K M3 × 35 1
7.5K to 15K M4 × 40 2
200V
18.5K to 30K M4 × 50 1
· DC reactor supplied (75K or more)
· Eyebolt for hanging the inverter (37K to 315K)
Capacity Eyebolt Size Number
37K M8 2
45K to 160K M10 2
185K to 315K M12 2
3.7K, 5.5K M3 × 35 1
7.5K to 18.5K M4 × 40 2
400V
22K, 30K M4 × 50 1
Harmonic suppression guideline
All models of General-purpose inverters used by specific consumers are covered by "Harmonic suppression guideline for consumers
who receive high voltage or special high voltage". ( For further details, refer to the chapter 3 of the instruction manual (applied) .)
PRODUCT CHECKING AND PARTS IDENTIFICATION
1

2 INSTALLATION AND WIRING

Three-phase AC power supply
Use within the permissible power supply specifications of the inverter.
(Refer to page 134)
Programmable controller
Moulded case circuit breaker (MCCB) or earth leakage circuit breaker (ELB), fuse
The breaker must be selected carefully since an in-rush current flows in the inverter at power on.
(Refer to page 3)
Magnetic contactor(MC)
Install the magnetic contactor to ensure safety. Do not use this magnetic contactor to start and stop the inverter. Doing so will cause the inverter life to be shorten.
(Refer to page 3)
Reactor (FR-HAL, FR-HEL)
Reactors (option) should be used when power harmonics measures are taken, the power factor is to be improved or the inverter is installed near a large power supply system (1000kVA or more). The inverter may be damaged if you do not use reactors. Select the reactor according to the model. For the 55K or less, remove the jumpers across terminals P/+-P1 to connect to the DC reactor.
(Refer to the chapter 2 of the Instruction Manual (applied) .)
RS-485 terminal block
The inverter can be connected with computers such as programmable controller. It supports Mitsubishi inverter protocol and Modbus-RTU (binary) protocol.
Inverter (FR-F700)
The life of the inverter is influenced by surrounding air temperature. The surrounding air temperature should be as low as possible within the permissible range. Especially when mounting the inverter inside an enclosure, take cautions of the surrounding air temperature. (Refer to page 7) Wrong wiring might lead to damage of the inverter. The control signal lines must be kept fully away from the main circuit to protect them from noise.(Refer to page 8) Refer to page 9 for the built-in EMC filter.
AC reactor (FR-HAL)
EMC filter (ferrite core) (FR-BLF)
The 55K or less has a built-in common mode choke.
DC reactor (FR-HEL)
For the 75K or more, a DC reactor is supplied. Always install the reactor.
P/+
P1
R/L1 S/L2 T/L3
N/-P/+
Earth (Ground)
UVW
(ferrite core) (FR-BSF01, FR-BLF)
Install an EMC filter (ferrite core) to reduce the electromagnetic noise generated from the inverter. Effective in the range from about 1MHz to 10MHz. A wire should be wound four turns at a maximum.
Motor
Brake unit
EMC filter
(FR-BU2, FR-BU
*1, MT-BU5*2)
Earth
(Ground)
PR
High power factor converter
*1, MT-HC*2)
(FR-HC
Power supply harmonics can be greatly suppressed. Install this as required.
*1 Compatible with the 55K or less. *2 Compatible with the 75K or more.
Power regeneration common converter
*1)
(FR-CV Power regeneration converter (MT-RC
Greater braking capability is obtained. Install this as required.
*2)
P/+
P/+
PR
Resistor unit
*1, MT-BR5*2)
(FR-BR
The regeneration braking capability of the inverter can be exhibited fully. Install this as required.
Devices connected to the output
Do not install a power factor correction capacitor, surge suppressor or EMC filter (capacitor) on the output side of the inverter. When installing a moulded case circuit breaker on the output side of the inverter, contact each manufacturer for selection of the moulded case circuit breaker.
Earth (Ground)
To prevent an electric shock, always earth (ground) the motor and inverter.
CAUTION
· Do not install a power factor correction capacitor, surge suppressor or capacitor type filter on the inverter output side. This will cause the inverter to trip or the capacitor, and surge suppressor to be damaged. If any of the above devices are connected, immediately remove them.
· Electromagnetic wave interference The input/output (main circuit) of the inverter includes high frequency components, which may interfere with the communication devices (such as AM radios) used near the inverter. In this case, set the EMC filter valid to minimize interference.
(Refer to the chapter 2 of the Instruction Manual (applied).)
· Refer to the instruction manual of each option and peripheral devices for details of peripheral devices.
2
Peripheral devices

2.1 Peripheral devices

Check the inverter model of the inverter you purchased. Appropriate peripheral devices must be selected according to the capacity. Refer to the following list and prepare appropriate peripheral devices:
200V class
Motor
Output (kW)
*1
Applicable Inverter Model
Breaker Selection*2
Without reactor
connection
With reactor
connection
0.75 FR-F720-0.75K 30AF 10A 30AF 10A S-N10 S-N10
1.5 FR-F720-1.5K 30AF 15A 30AF 15A S-N10 S-N10
2.2 FR-F720-2.2K 30AF 20A 30AF 15A S-N10 S-N10
3.7 FR-F720-3.7K 30AF 30A 30AF 30A S-N20, S-N21 S-N10
5.5 FR-F720-5.5K 50AF 50A 50AF 40A S-N25 S-N20, S-N21
7.5 FR-F720-7.5K 100AF 60A 50AF 50A S-N25 S-N25
11 FR-F720-11K 100AF 75A 100AF 75A S-N35 S-N35
15 FR-F720-15K 225AF 125A 100AF 100A S-N50 S-N50
18.5 FR-F720-18.5K 225AF 150A 225AF 125A S-N65 S-N50
22 FR-F720-22K 225AF 175A 225AF 150A S-N80 S-N65
30 FR-F720-30K 225AF 225A 225AF 175A S-N95 S-N80
37 FR-F720-37K 400AF 250A 225AF 225A S-N150 S-N125
45 FR-F720-45K 400AF 300A 400AF 300A S-N180 S-N150
55 FR-F720-55K 400AF 400A 400AF 350A S-N220 S-N180
75 FR-F720-75K 400AF 400A
90 FR-F720-90K 400AF 400A
110 FR-F720-110K 600AF 500A
*1 Selections for use of the Mitsubishi 4-pole standard motor with power supply voltage of 200VAC 50Hz. *2 Select the MCCB according to the power supply capacity.
Install one MCCB per inverter. For using commercial-power supply operation, select a breaker with capacity which allows the motor to be directly power supplied. For the use in the United States or Canada, provide the appropriate UL and cUL listed Class RK5 or Class L type fuse or UL 489 molded case circuit breaker (MCCB) that is suitable for branch circuit protection.
(Refer to page 153.)
*3 Magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the magnetic
contactor is used for emergency stop during motor driving, the electrical durability is 25 times. When using the MC for emergency stop during motor driving or using on the motor side during commercial-power supply operation, select the MC with class AC-3 rated current for the motor rated current.
Input Side Magnetic
Contactor
Without reactor
connection
S-N300
S-N300
S-N400
*3
With reactor
connection
MCCB INV
MCCB INV
IM
IM
2
CAUTION
When the inverter capacity is larger than the motor capacity, select an MCCB and a magnetic contactor according to the
inverter model and cable and reactor according to the motor output.
When the breaker on the inverter primary side trips, check for the wiring fault (short circuit), damage to internal parts of the
inverter, etc. Identify the cause of the trip, then remove the cause and power on the breaker.
INSTALLATION AND WIRING
3
Peripheral devices
400V class
Motor
Output
(kW)
*1
Applicable Inverter Model
Breaker Selection*2
Without reactor
connection
With reactor
connection
0.75 FR-F740-0.75K 30AF 5A 30AF 5A S-N10 S-N10
1.5 FR-F740-1.5K 30AF 10A 30AF 10A S-N10 S-N10
2.2 FR-F740-2.2K 30AF 10A 30AF 10A S-N10 S-N10
3.7 FR-F740-3.7K 30AF 20A 30AF 15A S-N10 S-N10
5.5 FR-F740-5.5K 30AF 30A 30AF 20A S-N20, S-N21 S-N11, S-N12
7.5 FR-F740-7.5K 30AF 30A 30AF 30A S-N20, S-N21 S-N20, S-N21
11 FR-F740-11K 50AF 50A 50AF 40A S-N20, S-N21 S-N20, S-N21
15 FR-F740-15K 100AF 60A 50AF 50A S-N25 S-N20, S-N21
18.5 FR-F740-18.5K 100AF 75A 100AF 60A S-N25 S-N25
22 FR-F740-22K 100AF 100A 100AF 75A S-N35 S-N25
30 FR-F740-30K 225AF 125A 100AF 100A S-N50 S-N50
37 FR-F740-37K 225AF 150A 225AF 125A S-N65 S-N50
45 FR-F740-45K 225AF 175A 225AF 150A S-N80 S-N65
55 FR-F740-55K 225AF 200A 225AF 175A S-N80 S-N80
75 FR-F740-75K 225AF 225A S-N95
90 FR-F740-90K 225AF 225A S-N150
110 FR-F740-110K 225AF 225A S-N180
132 FR-F740-132K 400AF 400A S-N220
150 FR-F740-160K 400AF 400A S-N300
160 FR-F740-160K 400AF 400A S-N300
185 FR-F740-185K 400AF 400A S-N300
220 FR-F740-220K 600AF 500A S-N400
250 FR-F740-250K 600AF 600A S-N600
280 FR-F740-280K 600AF 600A S-N600
315 FR-F740-315K 800AF 700A S-N600
355 FR-F740-355K 800AF 800A S-N600
400 FR-F740-400K 1000AF 900A S-N800
450 FR-F740-450K 1000AF 1000A
500 FR-F740-500K 1200AF 1200A
560 FR-F740-560K 1600AF 1500A
*1 Selections for use of the Mitsubishi 4-pole standard motor with power supply voltage of 400VAC 50Hz. *2 Select the MCCB according to the power supply capacity.
Install one MCCB per inverter. For using commercial-power supply operation, select a breaker with capacity which allows the motor to be directly power supplied. For the use in the United States or Canada, provide the appropriate UL and cUL listed Class RK5 or Class L type fuse or UL 489 molded case circuit breaker (MCCB) that is suitable for branch circuit protection.
(Refer to page 153.)
*3 Magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the magnetic
contactor is used for emergency stop during motor driving, the electrical durability is 25 times. When using the MC for emergency stop during motor driving or using on the motor side during commercial-power supply operation, select the MC with class AC-3 rated current for the motor rated current.
CAUTION
When the inverter capacity is larger than the motor capacity, select an MCCB and a magnetic contactor according to the
inverter model and cable and reactor according to the motor output.
When the breaker on the inverter primary side trips, check for the wiring fault (short circuit), damage to internal parts of the
inverter, etc. Identify the cause of the trip, then remove the cause and power on the breaker.
Input Side Magnetic
Contactor
Without reactor
connection
1000A Rated product
1000A Rated product
1200A Rated product
*3
With reactor
connection
MCCB INV
MCCB INV
IM
IM
4
Method of removal and reinstallation of the
front cover

2.2 Method of removal and reinstallation of the front cover

Removal of the operation panel
1) Loosen the two screws on the operation panel. (These screws cannot be removed.)
When reinstalling the operation panel, insert it straight to reinstall securely and tighten the fixed screws of the operation panel.
2) Push the left and right hooks of the operation panel and pull the operation panel toward you to remove.
FR-F720-30K or less, FR-F740-30K or less
Removal
1) Loosen the installation screws of the
2) Pull the front cover toward you to remove by pushing an
front cover.
Front cover
Reinstallation
1) Insert the two fixed hooks on the left side of the front cover into the sockets of the inverter.
installation hook using left fixed hooks as supports.
Front cover
Installation hook
2) Using the fixed hooks as supports, securely press the front cover against the inverter. (Although installation can be done with the operation panel mounted, make sure that a connector is securely fixed.)
3) Tighten the installation screws and fix the front cover.
2
Front cover
Front cover
INSTALLATION AND WIRING
Front cover
5
Method of removal and reinstallation of the
front cover
FR-F720-37K or more, FR-F740-37K or more
Removal
1) Remove installation screws on the front cover 1 to remove the front cover 1.
Front cover 1
Reinstallation
1) Insert the two fixed hooks on the left side of the front cover 2 into the sockets of the inverter.
2) Loosen the installation screws of the front cover 2.
Front cover 2
3) Pull the front cover 2 toward you to remove by pushing an installation hook on the right side using left fixed hooks as supports.
Installation hook
2) Using the fixed hooks as supports, securely press the front cover 2 against the inverter. (Although installation can be done with the operation panel mounted, make sure that a connector is securely fixed.)
Front cover 2 Front cover 2
3) Fix the front cover 2 with the installation screws.
Front cover 2
4) Fix the front cover 1 with the installation screws.
Front cover 1
REMARKS
For the FR-F740-185K or more, the front cover 1 is separated into two parts.
CAUTION
1. Fully make sure that the front cover has been reinstalled securely. Always tighten the installation screws of the front cover.
2. The same serial number is printed on the capacity plate of the front cover and the rating plate of the inverter. Before reinstalling the front cover, check the serial numbers to ensure that the cover removed is reinstalled to the inverter from where it was removed.
6
Installation of the inverter and instructions

2.3 Installation of the inverter and instructions

Installation of the Inverter
Installation on the enclosure
30K or less 37K or more
CAUTION
When encasing multiple inverters, install them in
parallel as a cooling measure.
Install the inverter vertically.
Vertical
Fix six positions for the FR-F740­185K to 400K and fix eight positions for the FR-F740-450K to 560K.
Refer to the clearances below.
Install the inverter under the following conditions.
10cm or more
(front)
20cm or more
10cm or more
20cm or more
Clearances (side)
Inverter
5cm
or more *
*1cm or more for 3.7K or less
Surrounding air temperature and humidity
Measurement position
Inverter
5cm
Measurement position
5cm
5cm
Temperature: -10°C to 50°C
Humidity: 90% RH maximum
Leave enough clearances as a cooling measure.
Clearances
55K or less 75K or more
10cm or more
5cm or more *
5cm or more *
10cm or more
*1cm or more for 3.7K or less
REMARKS
For replacing the cooling fan of the FR-F740-185K or more, 30cm of space is necessary in front of the inverter. Refer to page 130 for fan replacement.
The inverter consists of precision mechanical and electronic parts. Never install or handle it in any of the following conditions as doing so could cause an operation fault or failure.
2
Direct sunlight
Vertical mounting (When installing two or
more inverters, install them in parallel.)
Vibration(5.9m/s2 or more at 10 to 55Hz (directions of X, Y, Z axes))*
*2.9m/s2 or more for the 185K or
more
Transportation by holding the front cover
High temperature, high humidity
Oil mist, flammable gas, corrosive gas, fluff, dust, etc.
Horizontal placement
INSTALLATION AND WIRING
Mounting to combustible material
7
Wiring

2.4 Wiring

2.4.1 Terminal connection diagram

N/-
*8
resistor
Resistor unit (Option)
Brake unit (Option)
*7.
CN8
*6
U V W
C1
B1
A1
C2
B2
A2
RUN
Running
SU
Up to frequency
IPF
Instantaneous power failure
OL
Overload
FU
Frequency detection
SE
*
9. It is not necessary
FM
SD
AM
5
TXD+
TXD-
RXD+
RXD-
SG
VCC
*6. A CN8 (for MT-BU5)
connector is provided with the 75K or more.
Do not use PR and PX terminals. Please do not remove the jumper connected to terminal PR and PX.
Motor
*8.
The 200V class 0.75K and 1.5K are not provided with the ON/OFF connector EMC filter.
Relay output
Terminal functions
Relay output 1 (Fault output)
vary with the output terminal assignment (Pr. 195, Pr. 196)
(Refer to the chapter 4 of the Instruction Manual (applied) )
Relay output 2
Open collector output
Terminal functions vary with the output terminal assignment (Pr. 190 to Pr. 194)
(Refer to the chapter 4 of the Instruction Manual (applied))
Open collector output common
/source common
Sink
when calibrating the indicator from the operation panel.
+-
Calibration resistor *9
(+)
(-)
Indicator
(Frequency meter, etc.)
Moving-coil type 1mA full-scale
Analog signal output (0 to 10VDC)
RS-485 terminals
Data transmission
Data reception
GND
(Permissible load
5V
current 100mA)
IM
Earth (ground) cable
Sink logic
Main circuit terminal
Control circuit terminal
Three-phase AC
power supply
*2. To supply power to the
control circuit separately, remove the jumper across R1/L11 and S1/L21.
*1. DC reactor (FR-HEL)
Be sure to connect the DC reactor supplied with the 75K or more. When a DC reactor is connected to the 55K or less, remove the jumper across P1-P/+.
Jumper
MC
*2
MCCB
Earth (Ground)
*1
Earth
Jumper
(ground)
P1
P/+
R/L1 S/L2 T/L3
ON
R1/L11 S1/L21
OFF
Main circuit
Control circuit
Jumper
PR*7
EMC filter ON/OFF connector
PX*7
Control input signals (No voltage input allowed)
Terminal functions vary with the input terminal assignment (Pr. 178 to Pr. 189)
(Refer to the chapter 4 of the Instruction Manual (applied))
Start self-holding selection
Multi-speed selection
Second function selection
*3. AU terminal can be
used as PTC input terminal.
Terminal 4 input selection
(Current input selection)
Selection of automatic restart
after instantaneous
Contact input common
(Common for external power supply transistor)
Frequency setting signal (Analog)
Frequency setting
potentiometer
1/2W1k
*5
*
4. Terminal input specifications can be changed by analog input specifications switchover (Pr. 73, Pr. 267). Set the voltage/current input switch in the OFF position to select voltage input (0 to 5V/0 to 10V) and ON to select current input (0 to 20mA).
(Refer to the chapter 4 of the Instruction Manual (applied) )
Forward
rotation
start
Reverse
rotation
start
High speed
Middle speed
Low speed
Jog mode
Output stop
Reset
power failure
24VDC power supply
3
2
Ω
1
Auxiliary
input
Terminal
4 input
(Current
input)
(+) (-)
(+) (-)
Connector for plug-in option
STF
STR
STOP
RH
RM
RL
JOG
RT
MRS
RES
*3
AU
AU
PTC
CS
SD
SOURCE
PC
*4
Voltage/current
10E(+10V)
10(+5V)
0 to 5VDC
2
0 to 10VDC 0 to 20mADC
5
(Analog common)
0 to ±10VDC
1
0 to ±5VDC
4 to 20mADC
4
0 to 5VDC 0 to 10VDC
SINK
input switch
2
4
ON
OFF
Initial value
selected
Initial value
selected
Initial value
*
selected
*
4
*
4
4
PU connector
connection
*
5. It is recommended to use
2W1kΩ when the frequency setting signal is changed frequently.
Option connector 1
Terminating
CAUTION
· To prevent a malfunction due to noise, keep the signal cables more than 10cm away from the power cables. Also separate the main circuit wire of the input side and the output side.
· After wiring, wire offcuts must not be left in the inverter. Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean. When drilling mounting holes in an enclosure etc., take care not to allow chips and other foreign matter to enter the inverter.
· Set the voltage/current input switch correctly. Operation with a wrong setting may cause a fault, failure or malfunction.
8
Wiring
r
r

2.4.2 EMC filter

This inverter is equipped with a built-in EMC filter (capacitive filter) and common mode choke. The EMC filter is effective for reduction of air-propagated noise on the input side of the inverter. The EMC filter is factory-set to disable (OFF). To enable it, fit the EMC filter ON/OFF connector to the ON position. The input side common mode choke, built-in the 55K or less inverter, is always valid regardless of ON/OFF of the EMC filter ON/OFF connector.
0.75K to 5.5K
EMC filter OFF EMC filter OFF EMC filter OFFEMC filter ON EMC filter ON EMC filter ON
(initial setting) (initial setting) (initial setting)
FR-F720-2.2K to 5.5K
FR-F740-0.75K to 5.5K
FR-F720-7.5K, 11K FR-F740-7.5K, 11K
FR-F720-15K FR-F740-15K, 18.5K
7.5K, 11K
FR-F720-18.5K to 30K
FR-F740-22K, 30K
15K or more
FR-F720- 37K or more FR-F740- 37K or more
VUW
EMC filte ON/OFF connecto
The FR-F720-0.75K and 1.5K are not provided with the EMC filter ON/OFF connector. (Always ON)
<How to disconnect the connector>
(1) Before removing a front cover, check to make sure that the indication of the inverter operation panel is off, wait for
at least 10 minutes after the power supply has been switched off, and check that there are no residual voltage using a tester or the like. (For the front cover removal method, refer to page 5.)
(2) When disconnecting the connector, push the fixing tab and pull the connector straight without pulling the cable or
forcibly pulling the connector with the tab fixed. When installing the connector, also engage the fixing tab securely. If it is difficult to disconnect the connector, use a pair of long-nose pliers, etc.
2
EMC filter
ON/OFF connector
(Side view)
Disengage connector fixing tab With tab disengaged,
pull up connector straight.
CAUTION
Fit the connector to either ON or OFF.
Enabling (turning on) the EMC filter increase leakage current. (Refer to the chapter 3 of the Instruction Manual (applied))
WARNING
While power is on or when the inverter is running, do not open the front cover. Otherwise you may get an electric shock.
INSTALLATION AND WIRING
9
Wiring

2.4.3 Specification of main circuit terminal

Termina l
Symbol
R/L1, S/L2, T/L3
Terminal Name Description
Connect to the commercial power supply.
AC power input
Keep these terminals open when using the high power factor converter (FR-HC, MT-HC) or power regeneration common converter (FR-CV).
U, V, W Inverter output Connect a three-phase squirrel-cage motor.
Connected to the AC power supply terminals R/L1 and S/L2. To retain the fault display and fault output or when using the high power factor converter (FR-HC, MT-HC) or power regeneration common converter (FR-CV), remove the jumpers from terminals R/L1-R1/L11 and S/L2-S1/L21 and
R1/L11, S1/L21
P/+, N/-
P/+, P1
Power supply for control circuit
Brake unit connection
DC reactor connection
apply external power to these terminals. The power capacity necessary when separate power is supplied from R1/ L11 and S1/L21 differs according to the inverter capacity.
15K or less 18.5K 22K or more
200V class 60VA 80VA 80VA
400V class 60VA 60VA 80VA
Connect the brake unit (FR-BU2, FR-BU, BU and MT-BU5), power regeneration common converter (FR-CV), high power factor converter (FR­HC and MT-HC) or power regeneration converter (MT-RC).
For the 55K or less, remove the jumper across terminals P/+ - P1 and connect the DC reactor. (Be sure to connect the DC reactor supplied with the 75K or more.)
PR, PX Please do not remove or use terminals PR and PX or the jumper connected.
Earth (ground) For earthing (grounding) the inverter chassis. Must be earthed (grounded).

2.4.4 Terminal arrangement of the main circuit terminal, power supply and the motor wiring

200V class
FR-F720-0.75K, 1.5K FR-F720-2.2K to 5.5K
Jumper
Screw size (M4)
R/L1
S/L2
R1/L11
S1/L21
Power supply
Jumper
T/L3
N/-
P/+
IM
Motor
As this is an inside cover fixing screw, do not remove it.
PX
Screw size
(M4)
PR
Charge lamp
Jumper
Screw size (M4)
R/L1 S/L2 T/L3
R1/L11 S1/L21
Power supply
IM
Motor
N/-
Screw size
(M4)
Jumper
PR
P/+
PX
Charge lamp
10
FR-F720-7.5K, 11K FR-F720-15K
r
Wiring
Charge lamp
Jumper
Screw size
(M5)
**
R1/L11 S1/L21
R/L1 S/L2 T/L3
N/-
P/+
PR
*
PX
Jumpe
*
Charge lamp
Screw size (M5)
IM
Power supply
* Screw size of terminal
R1/L11, S1/L21, PR and PX is M4.
Screw size (M5)
FR-F720-18.5K to 30K FR-F720-37K to 55K
Screw size (M4)
Screw size (18.5K:M6, 22K/30K:M8)
Charge lamp
Jumper
Motor
R1/L11 S1/L21
Screw size
(M4)
PR
R1/L11 S1/L21
R/L1 S/L2 T/L3
Power supply
R1/L11 S1/L21
Screw size
Charge lamp
Jumper
(M4)
Jumper
Jumper
P/+
N/-
PR
Screw size (M5)
IM
Motor
R/L1 S/L2 T/L3
Power supply
FR-F720-75K to 110K
R/L1 S/L2 T/L3
IM
Motor
Screw size (M6)
R1/L11 S1/L21
Screw size (M4)
N/-
N/-
Jumper
Charge lamp
Jumper
Screw size (M12)
P/+
P/+
R/L1 S/L2 T/L3
Power supply
Screw size(37K:M8, 45K/55K:M10)
N/-
P/+
Jumper
Screw size
(37K:M6, 45K/55K:M8)
2
IM
Motor
INSTALLATION AND WIRING
Power supply
Screw size (M12)
(for option)
P/+
Screw size (M10)
P/+
DC reactor
IM
Motor
11
Wiring
r
400V class
FR-F740-0.75K to 5.5K FR-F740-7.5K, 11K
Jumper
PR
P/+
PX
Charge lamp
Jumper
Screw size
Jumper
Screw size (M4)
R/L1 S/L2 T/L3
R1/L11 S1/L21
Power supply
IM
Motor
N/-
Screw size
(M4)
FR-F740-15K, 18.5K FR-F740-22K, 30K
R1/L11 S1/L21
Screw size
(M4)
Charge lamp
Screw size (M5)
Jumper
Jumper
Screw size (M6)
P/+
R/L1 S/L2 T/L3
R1/L11 S1/L21
(M4)
R/L1 S/L2 T/L3
Power supply
Charge lamp
Charge lamp
N/-
IM
Motor
Screw size
(M4)
Screw size (M4)
Jumper
P/+
PR
R1/L11 S1/L21
N/-
Jumpe
PX
PR
P/+
R/L1 S/L2 T/L3
N/-
PR
Power supply
IM
Power supply
Screw size (M5)
FR-F740-37K to 55K FR-F740-75K to 110K
R1/L11 S1/L21
Screw size(M4)
Charge lamp
Jumper
Screw size (37K: M6, 45K/55K: M8)
N/-
R/L1 S/L2 T/L3
Power supply
Screw size
(37K: M6, 45K/55K: M8)
P/+
Jumper
IM
Motor
Motor
R1/L11 S1/L21
Screw size (M4)
Screw size
(75K: M8, 90K/110K: M10)
R/L1 S/L2 T/L3
Power supply
IM
Motor
Screw size (M6)
Charge lamp
Jumper
Screw size (M10)
N/-
P/+
P/+
DC reactor
Jumper
Screw size
(75K: M8, 90K/110K: M10)
IM
Motor
Screw size (75K: M8, 90K/110K: M10)
12
FR-F740-132K to 220K FR-F740-250K to 560K
R1/L11 S1/L21
Screw size (M4)
R1/L11 S1/L21
Wiring
Screw size (M4)
Charge lamp
Jumper
Screw size (M12)
P/+
R/L1 S/L2 T/L3
P/+
N/-
Screw size (M10)
Charge lamp
Jumper
Screw size (132K/160K: M10 185K/220K: M12)
P/+
P/+
R/L1 S/L2 T/L3
N/-
IM
Power supply
Screw size (M12)
(for option)
DC reactor
Motor
Power supply
CAUTION
· The power supply cables must be connected to R/L1, S/L2, T/L3. (Phase sequence needs not to be matched.) Never connect the power cable to the U, V, W of the inverter. Doing so will damage the inverter.
· Connect the motor to U, V, W. At this time, turning on the forward rotation switch (signal) rotates the motor in the counterclockwise direction when viewed from the motor shaft.
· When wiring the inverter main circuit conductor of the 250K or more, tighten a nut from the right side of the conductor. When wiring two wires, place wires on both sides of the conductor. (Refer to the drawing below.) For wiring, use bolts (nuts) provided with the inverter.
P/+
IM
Motor
DC reactor
Screw size (M10)
Handling of the wiring cover (FR-F720-18.5K, 22K, FR-F740-22K, 30K) For the hook of the wiring cover, cut off the necessary parts using a pair of long-nose pliers etc.
CAUTION
Cut off the same number of lugs as wires. If parts where no wire is put through has been cut off (10mm or more), protective structure (JEM1030) becomes an open type (IP00).
2
INSTALLATION AND WIRING
13
Wiring
(1) Cable sizes etc., of the main control circuit terminals and earth (ground) terminals
Select the recommended cable size to ensure that a voltage drop will be 2% max. If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop will cause the motor torque to decrease especially at the output of a low frequency. The following table indicates a selection example for the wiring length of 20m.
200V class (when input power supply is 220V)
Cable Sizes
AWG /MC M *2
R/L1, S/L2,
T/L3
U, V, W
PVC, etc. (mm2) *3
R/L1, S/L2,
T/L3
U, V, W
(Ground)
Earth
cable
Applicable Inverter
Type
FR-F720-0.75K to
2.2K
Crimping
Terminal
Screw Size *4
Tightening
Tor que
N·m
Term inal
R/L1, S/L2,
T/L3
U, V, W
HIV, etc. (mm2) *1
R/L1, S/L2,
T/L3
U, V, W
Earth
(Ground)
cable
M4 1.5 2-4 2-4 2 2 2 14 14 2.5 2.5 2.5
FR-F720-3.7K M4 1.5 5.5-4 5.5-4 3.5 3.5 3.5 12 12 4 4 4
FR-F720-5.5K M4 1.5 5.5-4 5.5-4 5.5 5.5 5.5 10 10 6 6 6
FR-F720-7.5K M5 2.5 14-5 8-5 14 8 5.5 6 8 16 10 16
FR-F720-11K M5 2.5 14-5 14-5 14 14 14 6 6 16 16 16
FR-F720-15K M5 2.5 22-5 22-5 22 22 14 4 6 (
*5)2525 16
FR-F720-18.5K M6 4.4 38-6 38-6 38 38 22 2 2 35 35 25
FR-F720-22K M8 (M6) 7.8 38-8 38-8 38 38 22 2 2 35 35 25
FR-F720-30K M8 (M6) 7.8 60-8 60-8 60 60 22 1/0 1/0 50 50 25
FR-F720-37K M8 (M6) 7.8 80-8 80-8 80 80 22 3/0 3/0 70 70 35
FR-F720-45K
FR-F720-55K
FR-F720-75K
FR-F720-90K
FR-F720-110K
*1 The cable size is that of the cable (HIV cable (600V class 2 vinyl-insulated cable) etc.) with continuous maximum permissible temperature of
75°C. Assumes that the surrounding air temperature is 50°C or less and the wiring distance is 20m or less.
*2 The recommended cable size is that of the cable (THHW cable) with continuous maximum permissible temperature of 75°C. Assumes that the
surrounding air temperature is 40°C or less and the wiring distance is 20m or less. (Selection example for use mainly in the United States.)
*3 For the 15K or less, the recommended cable size is that of the cable (PVC cable) with continuous maximum permissible temperature of 70°C.
Assumes that the surrounding air temperature is 40°C or less and the wiring distance is 20m or less. For the 18.5K or more, the recommended cable size is that of the cable (XLPE cable) with continuous maximum permissible temperature of 90°C. Assumes that the surrounding air temperature is 40°C or less and wiring is performed in an enclosure. (Selection example for use mainly in Europe.)
*4 The terminal screw size indicates the terminal size for R/L1, S/L2, T/L3, U, V, W, and a screw for earthing (grounding).
A screw for earthing (grounding) of the 22K or more is indicated in ( ).
*5 When connecting the option unit to P/+, P1, N/-, use THHN cables for the option and terminals R/L1, S/L2, T/L3, U, V, W.
M10 (M8)
M10 (M8)
M12 (M10)
M12 (M10)
M12 (M10)
14.7 100-10 100-10 100 100 38 4/0 4/0 95 95 50
14.7 100-10 100-10 100 100 38 4/0 4/0 95 95 50
24.5 150-12 150-12 125 125 38 MCM250 MCM250 ⎯⎯ ⎯
24.5 150-12 150-12 150 150 38 2×4/0 2×4/0 ⎯⎯⎯
24.5 100-12 100-12 2×100 2×100 38 2×4/0 2×4/0 ⎯⎯⎯
14
400V class (when input power supply is 440V)
Wiring
Applicable
Inverter Type
FR-F740-0.75K to
3.7K
Crimping
N·m
R/L1, S/L2,
(Compression)
Terminal
U, V, W
T/L3
HIV, etc. (mm2) *1
R/L1, S/L2,
T/L3
U, V, W
Earth
(Ground)
cable
Ter min al
Screw Size *4
Tightening
Tor qu e
M4 1.5 2-4 2-4 2 2 2 14 14 2.5 2.5 2.5
Cable Sizes
AWG/MCM *2
R/L1, S/L2,
T/L3
U, V, W
PVC, etc. (mm2) *3
R/L1, S/L2,
T/L3
U, V, W
Earth
(Ground)
cable
FR-F740-5.5K M4 1.5 2-4 2-4 2 2 3.5 12 14 2.5 2.5 4 FR-F740-7.5K M4 1.5 5.5-4 5.5-4 3.5 3.5 3.5 12 12 4 4 4 FR-F740-11K M4 1.5 5.5-4 5.5-4 5.5 5.5 8 10 10 6 6 10 FR-F740-15K M5 2.5 8-5 8-5 8 8 8 8 8 10 10 10 FR-F740-18.5K M5 2.5 14-5 8-5 14 8 14 6 8 16 10 16 FR-F740-22K M6 4.4 14-6 14-6 14 14 14 6 6 16 16 16 FR-F740-30K M6 4.4 22-6 22-6 22 22 14 4 4 25 25 16 FR-F740-37K M6 4.4 22-6 22-6 22 22 14 4 4 25 25 16 FR-F740-45K M8 7.8 38-8 38-8 38 38 22 1 2 50 50 25 FR-F740-55K M8 7.8 60-8 60-8 60 60 22 1/0 1/0 50 50 25 FR-F740-75K M8 7.8 60-8 60-8 60 60 38 1/0 1/0 50 50 25 FR-F740-90K M10 14.7 60-10 60-10 60 60 38 3/0 3/0 50 50 25 FR-F740-110K M10 14.7 80-10 80-10 80 80 38 3/0 3/0 70 70 35 FR-F740-132K M10 14.7 100-10 100-10 100 100 38 4/0 4/0 95 95 50 FR-F740-160K M10 14.7 150-10 150-10 125 125 38 250 250 120 120 70 FR-F740-185K FR-F740-220K FR-F740-250K FR-F740-280K FR-F740-315K FR-F740-355K FR-F740-400K FR-F740-450K FR-F740-500K FR-F740-560K
*1 For the FR-F740-55K or less, the recommended cable size is that of the cable (e.g. HIV cable (600V class 2 vinyl-insulated cable)) with continuous
maximum permissible temperature of 75°C. Assumes that the surrounding air temperature is 50°C or less and the wiring distance is 20m or less. For the FR-F740-75K or more, the recommended cable size is that of the cable (e.g. LMFC (heat resistant flexible cross-linked polyethylene insulated cable)) with continuous maximum permissible temperature of 90°C. Assumes that the surrounding air temperature is 50°C or less and wiring is performed in an enclosure.
*2 For the FR-F740-45K or less, the recommended cable size is that of the cable (THHW cable) with continuous maximum permissible temperature of 75°C.
Assumes that the surrounding air temperature is 40°C or less and the wiring distance is 20m or less. For the FR-F740-55K or more, the recommended cable size is that of the cable (THHN cable) with continuous maximum permissible temperature of 90°C. Assumes that the surrounding air temperature is 40°C or less and wiring is performed in an enclosure. (Selection example for use mainly in the United States.)
*3 For the FR-F740-45K or less, the recommended cable size is that of the cable (PVC cable) with continuous maximum permissible temperature of 70°C.
Assumes that the surrounding air temperature is 40°C or less and the wiring distance is 20m or less. For the FR-F740-55K or more, the recommended cable size is that of the cable (XLPE cable) with continuous maximum permissible temperature of 90°C. Assumes that the surrounding air temperature is 40°C or less and wiring is performed in an enclosure. (Selection example for use mainly in the Europe.)
*4 The terminal screw size indicates the terminal size for R/L1, S/L2, T/L3, U, V, W
A screw for earthing (grounding) of the 185K or more is indicated in ( ).
M12 (M10) M12 (M10) M12 (M10) M12 (M10) M12 (M10) M12 (M10) M12 (M10) M12 (M10) M12 (M10) M12 (M10)
24.5 150-12 150-12 150 150 38 300 300 150 150 95
24.5 100-12 100-12 2×100 2×100 38 2×4/0 2×4/0 2×95 2×95 95
24.5 100-12 100-12 2×100 2×100 38 2×4/0 2×4/0 2×95 2×95 95
24.5 150-12 150-12 2×125 2×125 38 2×250 2×250 2×120 2×120 120
24.5 150-12 150-12 2×150 2×150 38 2×300 2×300 2×150 2×150 150
24.5 200-12 200-12 2×200 2×200 60 2×350 2×350 2×185 2×185 2×95
24.5 C2-200 C2-200 2×200 2×200 60 2×400 2×400 2×185 2×185 2×95
24.5 C2-250 C2-250 2×250 2×250 60 2×500 2×500 2×240 2×240 2×120
24.5 C2-250 C2-250 2×250 2×250 100 2×500 2×500 2×240 2×240 2×120
24.5 C2-200 C2-200 3×200 3×200 100 3×350 3×350 3×185 3×185 2×150
,
and a screw for earthing (grounding).
The line voltage drop can be calculated by the following formula:
2
line voltage drop [V]=
3 × wire resistance[mΩ/m] × wiring distance[m] × current[A]
1000
Use a larger diameter cable when the wiring distance is long or when it is desired to decrease the voltage drop (torque reduction) in the low speed range.
CAUTION
· Tighten the terminal screw to the specified torque. A screw that has been tighten too loosely can cause a short circuit or malfunction. A screw that has been tighten too tightly can cause a short circuit or malfunction due to the unit breakage.
· Use crimping terminals with insulation sleeve to wire the power supply and motor.
15
INSTALLATION AND WIRING
Wiring
(2) Notes on earthing (grounding)
• Leakage currents flow in the inverter. To prevent an electric shock, the inverter and motor must be earthed (grounded). This inverter must be earthed (grounded). Earthing (Grounding) must conform to the requirements of national and local safety regulations and electrical codes. (NEC section 250, IEC 536 class 1 and other applicable standards) A neutral-point earthed (grounded) power supply for 400V class inverter in compliance with EN standard must be used.
• Use the dedicated earth (ground) terminal to earth (ground) the inverter. (Do not use the screw in the casing, chassis, etc.)
• Use the thickest possible
14
, 15 and minimize the cable length. The earthing (grounding) point should be as near as possible to the inverter.
To be compliant with the EU Directive (Low Voltage Directive), earth (ground) the inverter according to
the instructions on page 155.
(3) Total wiring length
The overall wiring length for connection of a single motor or multiple motors should be within the value in the table below.
earth (ground)
cable. Use the cable whose size is equal to or greater than that indicated in
page
Pr. 72 PWM frequency selection Setting
(carrier frequency)
2 (2kHz) or less 300m 500m 500m
3 to 15 (3kHz to 14.5kHz) * 200m 300m 500m
0.75K 1.5K 2.2K or More
* For the 75K or more, the setting range of Pr. 72 PWM frequency selection is "0 to 6".
Total wiring length (1.5K or more)
500m or less
300m
300m
300m + 300m = 600m
When driving a 400V class motor by the inverter, surge voltages attributable to the wiring constants may occur at the motor terminals, deteriorating the insulation of the motor. Take the following measures 1) or 2) in this case.
1) Use a "400V class inverter-driven insulation-enhanced motor" and set frequency in Pr. 72 PWM frequency selection according to wiring length
Wiring Length
50m or less 50m to 100m exceeding 100m
Pr. 72 PWM frequency selection Setting
(carrier frequency)
14.5kHz or less 9kHz or less 4kHz or less
2) Connect the surge voltage suppression filter (FR-ASF-H) to the 55K or less and the sine wave filter (MT-BSL/BSC)
to the 75K or more on the inverter output side.
CAUTION
· Especially for long-distance wiring, the inverter may be affected by a charging current caused by the stray capacitances of the
wiring, leading to a malfunction of the overcurrent protective function or fast response current limit function or a malfunction or fault of the equipment connected on the inverter output side. If fast-response current limit function malfunctions, disable this function. (For Pr.156 Stall prevention operation selection, refer to the chapter 4 of the Instruction Manual (applied).)
· For details of Pr. 72 PWM frequency selection , refer to the chapter 4 of the Instruction Manual (applied). (When using an optional sine
wave filter (MT-BSL/BSC) for the 75K or more, set "25" in Pr.72 (2.5kHz)).
· For explanation of surge voltage suppression filter (FR-ASF-H) and sine wave filter (MT-BSL/BSC), refer to the manual of each
option.
16
Wiring
(4) Cable size of the control circuit power supply (terminal R1/L11, S1/L21)
· Terminal Screw Size: M4
· Cable size: 0.75mm
· Tightening torque: 1.5N·m
(5) When connecting the control circuit and the main circuit separately to the power supply
<Connection diagram> When fault occurs, opening of the electromagnetic contactor (MC) on the
MC
Remove the jumper
FR-F720-0.75K to 5.5K, FR-F740-0.75K to 5.5K
2
to 2mm
R/L1
S/L2
T/L3
R1/L11
S1/L21
2
Inverter
inverter power supply side results in power loss in the control circuit, disabling the fault output signal retention. Terminals R1/L11 and S1/L21 are provided for when retention of a fault signal is required. In this case, connect the power supply terminals R1/L11 and S1/L21 of the control circuit to the primary side of the MC. Do not connect the power cable to incorrect terminals. Doing so may damage the inverter.
1)Loosen the upper screws.
2)Remove the lower screws.
3)
3)Remove the jumper
4)Connect the separate power supply cable for the control circuit to the lower terminals
1)
(R1/L11, S1/L21).
2)
4)
R1/L11
FR-F720-7.5K, 11K, FR-F740-7.5K, 11K
1)Remove the upper screws.
2)Remove the lower screws.
3)Remove the jumper.
4)Connect the separate power supply cable for the control circuit to the upper terminals (R1/L11, S1/L21).
R/L1
S/L2
T/L3
S1/L21
Main circuit terminal block
3)
1)
R1/L11
2)
S1/L21
R1/L11
S1/L21
R1/L11
2
S1/L21
INSTALLATION AND WIRING
4)
R/
S/
L1
T/
L2
L3
Main circuit terminal block
17
Wiring
FR-F720-15K, FR-F740-15K or more
1)Remove the upper screws.
2)Remove the lower screws.
3)Pull the jumper toward you to remove.
4)
Connect the separate power supply cable for the control circuit to the upper terminals (R1/L11, S1/L21)
.
R/L1
MC
S/L2
T/L3
R1/ L11
S1/ L21
Power supply terminal block for the control circuit
3)
Power supply terminal block for the control circuit
R1/L11
S1/L21
Main power supply
Power supply terminal block for the control circuit
FR-F720-15K FR-F740-15K, 18.5K
FR-F720-18.5K to 30K FR-F740-22K, 30K
1)
2)
4)
FR-F720-37K or more FR-F740-37K or more
VUW
CAUTION
· Be sure to use the inverter with the jumpers across terminals R/L1-R1/L11 and S/L2-S1/L21 removed when supplying power from other sources. The inverter may be damaged if you do not remove the jumper.
· The voltage should be the same as that of the main control circuit when the control circuit power is supplied from other than the primary side of the MC.
· The power capacity necessary when separate power is supplied from R1/L11 and S1/L21 differs according to the inverter capacity.
15K or less 18.5K 22K or more
200V class 60VA 80VA 80VA
400V class 60VA 60VA 80VA
· If the main circuit power is switched off (for 0.1s or more) then on again, the inverter resets and a fault output will not be held.
18

2.4.5 Control circuit terminals

indicates that terminal functions can be selected using Pr. 178 to Pr. 196 (I/O terminal function selection) (Refer to the chapter 4 of
the Instruction Manual (applied).)
(1) Input signals
Wiring
Terminal
Symbol
Type
STF
STR
STOP
RH,
RM, RL
JOG
RT
MRS Output stop
RES Reset
AU
Contact input
CS
SD
PC
Terminal
Name
Forward rotation start
Reverse rotation start
Star t self­holding selection
Multi-speed selection
Jog mode selection
Second function selection
Terminal 4 input selection
PTC input
Selection of automatic restart after instantaneous power failure
Contact input common (sink) (initial setting)
External transistor common (source)
24VDC power supply common
External transistor common (sink) (initial setting)
Contact input common
(source) 24VDC power
supply
Description
Turn on the STF signal to start forward rotation and turn it off to stop.
Turn on the STR signal to start reverse rotation and turn it off to stop.
Turn on the STOP signal to self-hold the start signal. *2
Multi-speed can be selected according to the combination of RH, RM and RL signals.
Turn on the JOG signal to select Jog operation (initial setting) and turn on the start signal (STF or STR) to start Jog operation.
Turn on the RT signal to select second function. When the second function such as "second torque boost" and "second V/F (base frequency)" are set, turning on the RT signal selects these functions.
Turn on the MRS signal (20ms or more) to stop the inverter output. Use to shut off the inverter output when stopping the motor by electromagnetic brake.
Used to reset fault output provided when fault occurs. Turn on the RES signal for more than 0.1s, then turn it off. Initial setting is for reset always. By setting Pr.75, reset can be set to enabled only at fault occurrence. Inverter recovers about 1s after the reset is released.
Terminal 4 is valid only when the AU signal is turned on. (The frequency setting signal can be set between 0 and 20mADC.) Turning the AU signal on makes terminal 2 (voltage input) invalid.
AU terminal is used as PTC input terminal (thermal protection of the motor). When using it as PTC input terminal, set the AU/PTC switch to PTC.
When the CS signal is left on, the inverter restarts automatically at power restoration. Note that restart setting is necessary for this operation. In the initial setting, a restart is disabled.
(Refer to Pr. 57 Restart coasting time in the chapter 4 of the Instruction Manual (applied).)
Common terminal for contact input terminal (sink logic) and terminal FM.
When connecting the transistor output (open collector output), such as a programmable controller, when source logic is selected, connect the external power supply common for transistor output to this terminal to prevent a malfunction caused by undesirable currents.
Common output terminal for 24VDC 0.1A power supply (PC terminal). Isolated from terminals 5 and SE.
When connecting the transistor output (open collector output), such as a programmable controller, when sink logic is selected, connect the external power supply common for transistor output to this terminal to prevent a malfunction caused by undesirable currents.
Common terminal for contact input terminal (source logic).
Can be used as 24VDC 0.1A power supply.
When the STF and STR signals are turned on simultaneously, the stop command is given.
Rated
Specifications
Input resistance
4.7kΩ Voltage at opening: 21 to 27VDC Contacts at short-circuited: 4 to 6mADC
-------------- ------
Power supply voltage range
19.2 to 28.8VDC Permissible load current 100mA
Refer to
57
59
*2
*2
*2
102
63
*2
*2
23
2
INSTALLATION AND WIRING
19
Wiring
Terminal
Symbol
Typ e
10E
10
Ter minal
Name
Frequency setting power supply
Description
When connecting the frequency setting potentiometer at an initial status, connect it to terminal 10. Change the input specifications of terminal 2 when connecting it to terminal 10E. (Refer to Pr. 73 Analog input selection in the chapter
4 of the Instruction Manual (applied).)
Rated
Specifications
10VDC
Permissible load
current 10mA
5VDC
Permissible load
current 10mA
Voltage input: Input resistance
Inputting 0 to 5VDC (or 0 to 10V, 0 to 20mA) provides the
2
setting (voltage)
Frequency
maximum output frequency at 5V (10V, 20mA) and makes input and output proportional. Use Pr. 73 to switch from among input 0 to 5VDC (initial setting), 0 to 10VDC, and 0 to 20mA. Set the voltage/current input switch in the ON position to select current input (0 to 20mA).
*1
10kΩ ± 1kΩ Maximum permissible voltage 20VDC Current input: Input resistance 245Ω ± 5Ω Maximum permissible current 30mA
Frequency setting
Inputting 4 to 20mADC (or 0 to 5V, 0 to 10V) provides the maximum output frequency at 20mA (5V, 10V) makes input and
4
setting (current)
Frequency
output proportional. This input signal is valid only when the AU signal is on (terminal 2 input is invalid). Use Pr. 267 to switch from among input 4 to 20mA (initial setting), 0 to 5VDC, and 0 to 10VDC. Set the voltage/current input switch in the OFF position to select voltage input (0 to 5V/0 to 10V).
*1
(Refer to the chapter 4 of the Instruction Manual (applied).)
Voltage/current
input switch
Switch 1 Switch 2
2
4
Input resistance
1
setting auxiliary
Frequency
Inputting 0 to ±5 VDC or 0 to ±10VDC adds this signal to terminal 2 or 4 frequency setting signal. Use Pr.73 to switch between the input 0 to ±5VDC and 0 to ±10VDC (initial setting).
10kΩ ± 1kΩ Maximum permissible voltage ± 20VDC
5
setting common
*1 Set Pr. 73, Pr. 267, and a voltage/current input switch correctly, then input an analog signal in accordance with the setting.
Applying a voltage signal with voltage/current input switch on (current input is selected) or a current signal with switch off (voltage input is selected) could cause component damage of the inverter or analog circuit of signal output devices.
*2 Refer to the chapter 4 of
Frequency
Common terminal for frequency setting signal (terminal 2, 1 or 4) and analog output terminal AM. Do not earth (ground).
the Instruction Manual (applied).
-------------- ------ ------
Refer to
*2
53, 61
53, 61
55, 63
*2
20
(2) Output signals
Wiring
Terminal
Symbol
Type
A1, B1, C1
Relay
A2, B2, C2
RUN
SU
OL
Open collector
IPF
FU
SE
FM For meter
Pulse
AM
Relay output 1 (Fault output)
Relay output 2 1 changeover contact output *
Inverter running
Up to frequency
Overload warning
Instantaneous power failure
Frequency detection
Open collector output common
Analog signal output
Terminal
Name
Description
1 changeover contact output indicates that the inverter protective function has activated and the output stopped. Fault: No conduction across B-C (Across A-C Continuity), Normal: Across B-C Continuity (No conduction across A-C)
Switched low when the inverter output frequency is equal to or higher than the starting frequency (initial value 0.5Hz). Switched high during stop or DC injection brake operation.
Switched low when the output frequency reaches within the range of ±10% (initial value) of the set frequency. Switched high during acceleration/ deceleration and at a stop.
Switched low when stall prevention is activated by the stall prevention function. Switched high when stall prevention is cancelled.
Switched low when an instantaneous power failure and under voltage protections are activated.
Switched low when the inverter output frequency is equal to or higher than the preset detected frequency and high when less than the preset detected frequency.
C o m m o n t e r m i n a l f o r t e r m i n a l s R U N , S U , O L , I P F, F U -------------------- -----
Select one e.g. output frequency from monitor items. (Not output during inverter reset.) The output signal is proportional to the magnitude of the corresponding monitoring item.
Alarm code (4bit) output
Output item: Output frequency (initial setting)
Output item: Output frequency (initial setting)
Rated
Specifications
Contact capacity: 230VAC 0.3A (Power factor=0.4) 30VDC 0.3A
Permissible load 24VDC (27VDC maximum) 0.1A (A voltage drop is
3.4V maximum when the signal is on.)
Low is when the open collector output transistor is on (conducts). High is when the transistor is off (does not conduct).
Permissible load current 2mA 1440 pulses/s at 60Hz
Output signal 0 to 10VDC Permissible load current 1mA (load impedance 10kΩ or more) Resolution 8 bit
Refer to
*
*
*
*
*
*
*
2
*
* Refer to the chapter 4 of the Instruction Manual (applied).
(3) Communication
Typ e
RS-485
Terminal
Symbol
TXD+
TXD-
RXD+
RXD-
RS-485 terminals
SG
Terminal
Name
PU connector
Inverter transmission terminal
Inverter reception terminal
Earth (Ground)
With the PU connector, communication can be made through RS-485. (for connection on a 1:1 basis only) Conforming standard : EIA-485 (RS-485) Transmission format : Multidrop link Communication speed : 4800 to 38400bps Overall length : 500m
With the RS-485 terminals, communication can be made through RS-485. Conforming standard : EIA-485 (RS-485) Transmission format : Multidrop link Communication speed : 300 to 38400bps Overall length : 500m
Description Refer to
26
27
21
INSTALLATION AND WIRING
Wiring

2.4.6 Changing the control logic

The input signals are set to sink logic (SINK) when shipped from the factory. To change the control logic, the jumper connector on the back of the control circuit terminal block must be moved to the other position. (The output signals may be used in either the sink or source logic independently of the jumper connector position.)
1)Loosen the two installation screws in both ends of the control circuit terminal block. (These screws cannot be removed.) Pull down the terminal block from behind the control circuit terminals.
2)Change the jumper connector set to the sink logic (SINK) on the rear panel of the control circuit terminal block to source logic (SOURCE).
Jumper connector
3)Using care not to bend the pins of the inverter's control circuit connector, reinstall the control circuit terminal block and fix it with the mounting screws.
CAUTION
1. Make sure that the control circuit connector is fitted correctly.
2. While power is on, never disconnect the control circuit terminal block.
22
4) Sink logic and source logic
r
In sink logic, a signal switches on when a current flows from the corresponding signal input terminal.
Terminal SD is common to the contact input signals. Terminal SE is common to the open collector output signals.
In source logic, a signal switches on when a current flows into the corresponding signal input terminal.
Terminal PC is common to the contact input signals. Terminal SE is common to the open collector output signals.
Wiring
Current flow concerning the input/output signal when sink logic is selected
Sink logic
Current
STF
STR
SD
Inverter
RUN
SE
R
R
TB1
-
+
TB17
24VDC
Current flow
DC input (sink type) <Example: QX40>
R
R
Sink connector
Current flow concerning the input/output signal when source logic is selected
Source logic
PC
Current
STF
R
STR
R
Inverter
SE
RUN
+
24VDC
Current flow
DC input (source type) <Example: QX80>
TB1
R
-
TB18
Source connecto
R
When using an external power supply for transistor output
Sink logic type
Use terminal PC as a common terminal, and perform wiring as shown below. (Do not connect terminal SD of the inverter with terminal 0V of the external power supply. When using terminals PC-SD as a 24VDC power supply, do not install a power supply in parallel in the outside of the inverter. Doing so may cause a malfunction due to undesirable current.)
QY40P type transistor
output unit
Constant
voltage
circuit
TB1
TB2
TB17
TB18
STF
STR
24VDC
Inverter
24VDC (SD)
PC
SD
Current flow
Source logic type
Use terminal SD as a common terminal, and perform wiring as shown below. (Do not connect terminal PC of the inverter with terminal +24V of the external power supply. When using terminals PC-SD as a 24VDC power supply, do not install an external power supply in parallel with the inverter. Doing so may cause a malfunction in the inverter due to undesirable currents.)
QY80 type transistor
output unit
Constant
voltage
circuit
Fuse
TB1
TB2
TB17
TB18
Current flow
PC
STF
STR
24VDC
SD
Inverter
24VDC (SD)
2
INSTALLATION AND WIRING
23
Wiring

2.4.7 Wiring of control circuit

(1) Control circuit terminal layout
A1 B1 C1 A2
RUN
SE
OLIPFSU
B2 C2
AURTRHRMRL
10E
10
STOP
RES
MRS
STF
SDSDFU PCCS
254
SD
STR
AMFM
JOG
Terminal screw size: M3.5 Tightening torque: 1.2N.m
1
(2) Common terminals of the control circuit (SD 5, SE)
Control circuit terminal
Terminals SD, 5, and SE are all common terminals (0V) for I/O signals and are isolated from each other. Do not earth(ground) these terminals. Avoid connecting the terminal SD and 5 and the terminal SE and 5. Terminal SD is a common terminal for the contact input terminals (STF, STR, STOP, RH, RM, RL, JOG, RT, MRS, RES, AU, CS) and frequency output signal (FM). The open collector circuit is isolated from the internal control circuit by photocoupler. Terminal 5 is a common terminal for frequency setting signal (terminal 2, 1 or 4) and analog output terminal AM. It should be protected from external noise using a shielded or twisted cable. Terminal SE is a common terminal for the open collector output terminal (RUN, SU, OL, IPF, FU). The contact input circuit is isolated from the internal control circuit by photocoupler.
(3) Signal inputs by contactless switches
The contacted input terminals of the inverter (STF, STR, STOP, RH, RM, RL, JOG, RT, MRS, RES, AU, CS) can be controlled using a transistor instead of a contacted switch as shown on the right.
External signal input using transistor
+24V
STF, etc
Inverter
SD
24
(4) Wiring instructions
Wiring
1) It is recommended to use the cables of 0.75mm2 gauge for connection to the control circuit terminals. If the cable gauge used is 1.25mm
the cables are run improperly, resulting in an operation panel contact fault.
2) The maximum wiring length should be 30m (200m for terminal FM).
3) Use two or more parallel micro-signal contacts or twin contacts to prevent a contact faults when using contact inputs since the control circuit input signals are micro-currents.
4) Use shielded or twisted cables for connection to the control circuit terminals and run them away from the main and power circuits (including the 200V relay sequence circuit).
5) Do not apply a voltage to the contact input terminals (e.g. STF) of the control circuit.
6) Always apply a voltage to the fault output terminals (A, B, C) via a relay coil, lamp, etc.
2
or more, the front cover may be lifted when there are many cables running or
Micro signal contacts Twin contacts
z Wiring of the control circuit of the 75K or more
For wiring of the control circuit of the 75K or more, separate away from wiring of the main circuit. Make cuts in rubber bush of the inverter side and lead wires.
<Wiring>
Rubber bush
(view from the inside)
Make cuts along the lines inside with a cutter knife and such.
2
INSTALLATION AND WIRING
25
Wiring

2.4.8 When connecting the operation panel using a connection cable

Having an operation panel on the enclosure surface is convenient. With a connection cable, you can mount the operation panel (FR-DU07) to the enclosure surface, and connect it to the inverter.
Parameter unit connection cable (FR-CB2)(option)
Operation panel(FR-DU07)
Operation panel connection connector (FR-ADP)(option)
CAUTION
Do not connect the PU connector to the computer's LAN port, FAX modem socket or telephone connector. The inverter and machine could be damaged due to differences in electrical specifications.
REMARKS
Refer to page 5 for removal method of the operation panel.
When using a commercially available connector and cable as a parameter unit connection cable, refer to the chapter 2 of the
Instruction Manual (applied).
The inverter can be connected to the computer and FR-PU04/FR-PU07.
26

2.4.9 RS-485 terminal block

Conforming standard: EIA-485(RS-485)Transmission format: Multidrop linkCommunication speed: MAX 38400bpsOverall length: 500mConnection cable:Twisted pair cable
(4 pairs)
OPEN
100Ω
TXD
RDA1
(RXD1+)
SDA1
(TXD1+)
Terminating resistor switch
Factory-set to "OPEN". Set only the terminating resistor switch of the remotest inverter to the "100Ω" position.
RDB1
RDA2
RDB2
SDB2
(TXD2-)
RXD
(RXD1-)
SDB1
(TXD1-)
(RXD2+)
SDA2
(TXD2+)
(RXD2-)
Wiring

2.4.10 Communication operation

Using the PU connector or RS-485 terminal, you can perform communication operation from a personal computer etc. When the PU connector is connected with a personal, FA or other computer by a communication cable, a user program can run and monitor the inverter or read and write to parameters. For the Mitsubishi inverter protocol (computer link operation), communication can be performed with the PU connector and RS-485 terminal. For the Modbus RTU protocol, communication can be performed with the RS-485 terminal.
For further details, refer to the chapter 4 of the Instruction Manual (applied).
P5S
(VCC)SG(GND)
Programmable controller
P5S
(VCC)SG(GND)
Inverter Inverter Inverter
VCC
Multidrop link
2
(32 inverters maximum are connectable)
27
INSTALLATION AND WIRING
Connection of stand-alone option units
r

2.5 Connection of stand-alone option units

The inverter accepts a variety of stand-alone option units as required. Incorrect connection will cause inverter damage or accident. Connect and operate the option unit carefully in accordance with the corresponding option unit manual.

2.5.1 Connection of the brake unit (FR-BU2)

Connect the brake unit (FR-BU2) as shown below to improve the braking capability at deceleration.
(1) Connection example with the GRZG type discharging resistor
OCR contact
OFFON
*2
Three-phase AC power supply
MCCB
MC
R/L1 S/L2 T/L3
Inverter
T
P/+ N/-
MC
U V
Motor
IM
OCR
External thermal relay
W
*3
*1
5m or less
*3
MC
GRZG type discharging resistor
RR
*4
FR-BU2
PR
P/+ N/-
A B C
BUE SD
*5
*1 Connect the inverter terminals (P/+, N/-) and brake unit (FR-BU2) terminals so that their terminal names match with each other.
(Incorrect connection will damage the inverter and brake unit.) *2 When the power supply is 400V class, install a step-down transformer. *3 Keep a wiring distance of within 5m between the inverter, brake unit (FR-BU2) and discharging resistor. Even when the wiring
is twisted, the cable length must not exceed 10m. *4 It is recommended to install an external thermal relay to prevent overheat of discharging resistors.
Refer to FR-BU2 manual for connection method of discharging resistor.
*5
<Recommended external thermal relay>
Brake Unit Discharging Resistor Recommended External Thermal Relay
FR-BU2-1.5K
FR-BU2-3.7K
FR-BU2-7.5K
FR-BU2-15K
FR-BU2-H7.5K
FR-BU2-H15K
FR-BU2-H30K
GZG 300W-50Ω (one) TH-N20CXHZ 1.3A
GRZG 200-10Ω (three in series) TH-N20CXHZ 3.6A
GRZG 300-5Ω (four in series) TH-N20CXHZ 6.6A
GRZG 400-2Ω (six in series) TH-N20CXHZ 11A
GRZG 200-10Ω (six in series) TH-N20CXHZ 3.6A
GRZG 300-5Ω (eight in series) TH-N20CXHZ 6.6A
GRZG 400-2Ω (twelve in series) TH-N20CXHZ 11A
CAUTION
Set "1" in Pr. 0 Brake mode selection of the FR-BU2 to use GRZG type discharging resistor.Do not remove a jumper across terminal P/+ and P1 except when connecting a DC reactor.
1/L1 5/L3
2/T1 6/T3
To the brake unit terminal P/+
TH-N20
To a resisto
28
(2) FR-BR-(H) connection example with resistor unit
*2
T
Connection of stand-alone option units
OFFON
MC
MC
MCCB
Three phase AC power supply
MC
R/L1 S/L2 T/L3
U V
W
Motor
IM
*3
Inverter
P/+ N/-
*1 Connect the inverter terminals (P/+, N/-) and brake unit (FR-BU2) terminals so that their terminal names match with each other.
(Incorrect connection will damage the inverter and brake unit.) *2 When the power supply is 400V class, install a step-down transformer. *3 The wiring distance between the inverter, brake unit (FR-BU) and resistor unit (FR-BR) should be within 5m. Even when the
wiring is twisted, the cable length must not exceed 10m. *4 Normal: across TH1-TH2...close, Alarm: across TH1-TH2...open
*1
5m or less
*3
CAUTION
Do not remove a jumper across terminal P/+ and P1 except when connecting a DC reactor.
(3) Connection example with MT-BR5 type resistor unit
*2
T
FR-BR
P
TH1
PR
TH2
FR-BU2 PR
P/+ N/­BUE SD
*4
A B C
MCCB
Three phase AC power supply
*1 Connect the inverter terminals (P/+, N/-) and brake unit (FR-BU2) terminals so that their terminal names match with each other.
(Incorrect connection will damage the inverter and brake unit.) *2 When the power supply is 400V class, install a step-down transformer. *3 The wiring distance between the inverter, brake unit (FR-BU2) and resistor unit (MT-BR5) should be within 5m. If twisted wires
are used, the distance should be within 10m. *4 Normal: across TH1-TH2...open, Alarm: across TH1-TH2...close *5 CN8 connector used with the MT-BU5 type brake unit is not used.
MC
R/L1 S/L2
W
T/L3
P/+
N/-
Inverter
Motor
U V
IM
*1
*3
*5
MC
P
N
PR
BUE SD
Brake unit
FR-BU2
P
CAUTION
Set "2" in Pr. 0 Brake mode selection of the FR-BU2 to use MT-BR5 type resistor unit.
OFFON
5m or less
CR1
MC
*3
TH1 P PR
TH2
Resistor unit
MT-BR5
2
CR1
*4
INSTALLATION AND WIRING
29
Connection of stand-alone option units

2.5.2 Connection of the brake unit (FR-BU/MT-BU5)

When connecting the brake unit (FR-BU(H)/MT-BU5) to improve the brake capability at deceleration, make connection as shown below. (1) Connection with the FR-BU (55K or less)
OFFON
T *2
MC
MCCB
Three-phase AC
power supply
*1 Connect the inverter terminals (P/+, N/-) and brake unit (FR-BU (H)) terminals so that their terminal signals match
with each other. (Incorrect connection will damage the inverter.) *2 When the power supply is 400V class, install a step-down transformer. *3 The wiring distance between the inverter, brake unit (FR-BU) and resistor unit (FR-BR) should be within 5m. If
twisted wires are used, the distance should be within 10m.
MC
R/L1
S/L2
T/L3
Inverter
U
V
W
P/+
N/
MC
Motor
IM
*1
*3
5m or less
FR-BR
P
PR
FR-BU
PR
P/+
N/
TH1
TH2
HA
HB
HC
CAUTION
If the transistors in the brake unit should become faulty, the resistor can be unusually hot, causing a fire. Therefore, install a
magnetic contactor on the inverter’s input side to configure a circuit so that a current is shut off in case of fault.
Do not remove a jumper across terminal P/+ and P1 except when connecting a DC reactor.
30
Connection of stand-alone option units
A
(2) Connection with the MT-BU5 (75K or more) After making sure that the wiring is correct, set "1" in Pr.30 Regenerative function selection. (Refer to the chapter 4 of the
Instruction Manual (applied).)
T
*1
OFFON
MCCB
Three-phase
C power
supply
*1 When the power supply is 400V class, install a step-down transformer. *2 The wiring length between the resistor unit and brake resistor should be 10m maximum when wires are
twisted and 5m maximum when wires are not twisted.
MC
R/L1
S/L2
T/L3
Inverter
CN8
P/+ N/
U
V
W
Motor
IM
PR
PR
Brake unit
MT-BU5
MC
*2
5m or less
P
P
CAUTION
Install the brake unit in a place where a cooling air reaches the brake unit heatsink and within a distance of the cable supplied
with the brake unit reaches the inverter.
For wiring of the brake unit and inverter, use an accessory cable supplied with the brake unit. Connect the main circuit cable to
the inverter terminals P/+ and N/- and connect the control circuit cable to the CN8 connector inside by making cuts in the rubber bush at the top of the inverter for leading the cable.
The brake unit which uses multiple resistor units has terminals equal to the number of resistor units. Connect one resistor unit
to one pair of terminal (P, PR).
<Inserting the CN8 connector>
Make cuts in rubber bush of the upper portion of the inverter and lead a cable.
1) Make cuts in the rubber bush for leading the CN8 connector cable with a nipper or cutter knife.
Rubber bushes
CR1 CR2
P
PR
P
PR
Resistor unit
MT-BR5
TH1
TH2
TH1
TH2
MC
CR1
CR2
2
Make cuts in rubber bush
2) Insert a connector on the MT-BU5 side through a rubber bush to connect to a connector on the inverter side.
CN8 connector
Wire clamp
Insert the connector until you hear a click sound.
INSTALLATION AND WIRING
CAUTION
Clamp the CN8 connector cable on the inverter side with a wire clamp securely.
31
Connection of stand-alone option units
A
A
r

2.5.3 Connection of the brake unit (BU type)

Connect the brake unit (BU type) correctly as shown below. Incorrect connection will damage the inverter. Remove the jumper across terminals HB-PC and terminals TB-HC of the brake unit and fit it to across terminals PC-TB.
OFFON
T*1
MC
Three-phase
C power
supply
MCCB
MC
R/L1
S/L2
T/L3
Inverter
W
N/-
P/+
Motor
U
V
IM
MC
Brake unit
N
(BU type)
OCR
Remove the jumper
TB
HC
HB
Discharging resistor
OCR
PR
HA
PC
Fit a jumper
P
*1 When the power supply is 400V class, install a step-down transformer.
CAUTION
The wiring distance between the inverter, brake unit and discharging resistor should be within 2m. If twisted wires are used, the
distance should be within 5m.
If the transistors in the brake unit should become faulty, the resistor can be unusually hot, causing a fire. Therefore, install a
magnetic contactor on the inverter's power supply side to shut off a current in case of fault.
Do not remove a jumper across terminal P/+ and P1 except when connecting a DC reactor.

2.5.4 Connection of the high power factor converter (FR-HC/MT-HC)

When connecting the high power factor converter (FR-HC) to suppress power harmonics, perform wiring securely as shown below. Incorrect connection will damage the high power factor converter and inverter. After making sure that the wiring is correct, set "2" in Pr. 30 Regenerative function selection. (Refer to the chapter 4 of the Instruction Manual (applied).)
(1) Connection with the FR-HC (55K or less)
High power factor converter
Reactor2
(FR-HCL02)
R3
R4 S4
S3
T4
T3
(FR-HC)(FR-HCB)
MC1 MC2
R4 S4 T4
R S T
Y1orY2
RDY
RSO phase detection
SE
Inverter
R/L1
*1
S/L2 T/L3
P
P/+
N
*4
*2
N/­X11
*3
X10
*3
RES SD R1/L11 S1/L21
*1
Moto
U V W
IM
Three-phase
C power
supply
MCCB
MC
Reactor1
(FR-HCL01)
R2
R
S2
S T
T2
Outside box
R2 S2 T2
MC1 MC2
R3 S3 T3
*1 Remove the jumpers across the inverter terminals R/L1-R1/L11, S/L2-S1/L21, and connect the control circuit power supply to the R1/L11 and S1/
L21 terminals. Always keep the power input terminals R/L1, S/L2, T/L3 open. Incorrect connection will damage the inverter. (E.OPT (option fault)
will occur. (Refer to page 112.)) *2 Do not insert the MCCB between terminals P/+ − N/- (P/+ − P/+, N/- N/-). Opposite polarity of terminals N/-, P/+ will damage the inverter. *3 Use Pr. 178 to Pr. 189 (input terminal function selection) to assign the terminals used for the X10 (X11) signal. (Refer to the chapter 4 of the Instruction
Manual (applied).)
For communication where the start command is sent only once, e.g. RS-485 communication operation, use the X11 signal when making setting to
hold the mode at occurrence of an instantaneous power failure. (Refer to the chapter 4 of the Instruction Manual (applied).) *4 Be sure to connect terminal RDY of the FR-HC to the X10 signal or MRS signal assigned terminal of the inverter, and connect terminal SE of the
FR-HC to terminal SD of the inverter. Without proper connecting, FR-HC will be damaged.
CAUTION
The voltage phases of terminals R/L1, S/L2, T/L3 and terminals R4, S4, T4 must be matched.Use sink logic (initial setting) when the FR-HC is connected. The FR-HC cannot be connected when source logic is selected.Do not remove a jumper across terminal P/+ and P1 except when connecting a DC reactor.
32
(2) Connection with the MT-HC (75K or more)
A
Connection of stand-alone option units
Three-phase
C power
supply
MCCB
*1 Remove the jumper across terminals R-R1, S-S1 of the inverter, and connect the control circuit power
*2 Do not insert the MCCB between terminals P/+ N/- (P/+ P/+, N/- N/-). Opposite polarity of terminals
*3 Use Pr. 178 to Pr. 189 (input terminal function selection) to assign the terminals used for the X10 (X11) signal.
*4 Connect the power supply to terminals R1 and S1 of the MT-HC via an isolated transformer. *5 Be sure to connect terminal RDY of the MT-HC to the X10 signal or MRS signal assigned terminal of the
MC
supply to the R1 and S1 terminals. The power input terminals R/L1, S/L2, T/L3 must be open. Incorrect connection will damage the inverter. (E.OPT (option fault) will occur. (Refer to page 112.)
N, P will damage the inverter.
(Refer to the chapter 4 of the Instruction Manual (applied).) For communication where the start command is sent only once, e.g. RS-485 communication operation, use the X11 signal when making setting to hold the mode at occurrence of an instantaneous power failure. (Refer to the chapter 4 of the Instruction Manual (applied).)
inverter, and connect terminal SE of the MT-HC to terminal SD of the inverter. Without proper connecting, MT-HC will be damaged.
MT-HCL01 MT-HCB
R
R2
S
S2
T
T2
R2
S2
T2
R1 S1
MT-HCL02 MT-HC Inverter
R3
S3
T3
88R
88S
R3
S3
T3
R4
S4
T4
R4
S4
T4
88R
88S
R
S
T
P
N
RDY
RSO
SE
R1 S1
MT-HCTR Isolated transformer
R/L1
U
*1
S/L2
V
T/L3
W
P/+
*2
N/
*5
*3
X10
RES
SD
*1
R1/
S1/
L11
L21
*4
CAUTION
Use sink logic (initial setting) when the MT-HC is connected. The MT-HC cannot be connected when source logic is
selected.
The voltage phases of terminals R/L1, S/L2, T/L3 and terminals R4, S4, T4 must be matched.When connecting the inverter to the MT-HC, do not connect the DC reactor provided to the inverter.
Motor
IM
2
INSTALLATION AND WIRING
33
Connection of stand-alone option units

2.5.5 Connection of the power regeneration common converter (FR-CV)(55K or less)

When connecting the power regeneration common converter (FR-CV), make connection so that the inverter terminals (P/+, N/-) and the terminal symbols of the power regeneration common converter (FR-CV) are the same. After making sure that the wiring is correct, set "2" in Pr. 30 Regenerative function selection.
Instruction Manual (applied).)
(Refer to the chapter 4 of the
Three-phase
AC power
supply
*1 Remove the jumpers across terminals R/L1-R1/L11 and S/L2-S1/L21 of the inverter, and connect the
*2 Do not insert an MCCB between the terminals P/+ N/- (between P/L+ P/+, between N/L- − N/-).
*3 Assign the terminal for X10 signal using any of Pr. 178 to Pr. 189 (input terminal function selection).
*4 Be sure to connect the power supply and terminals R/L11, S/L21, T/MC1.
*5 Be sure to connect terminal RDYB of the FR-CV to the X10 signal or MRS signal assigned terminal of the
R/L1
*1
S/L2 T/L3
R1/L11
*5
S1/L21
Inverter
P/+
*2
N/
PC SD
X10
*3
RES
Dedicated stand-alone reactor (FR-CVL)
MCCB
control circuit power supply across terminals R1/L11-S1/L21. Always keep the power input terminals R/ L1, S/L2, T/L3 open. Incorrect connection will damage the inverter. (E.OPT (option fault) will occur. (Refer to page 112.))
Opposite polarity of terminals N/-, P/+ will damage the inverter.
(Refer to the chapter 4 of the Instruction Manual (applied).)
Operating the inverter without connecting them will damage the power regeneration common converter.
inverter, and connect terminal SE of the FR-CV to terminal SD of the inverter. Without proper connecting, FR-CV will be damaged.
MC1
R/L11 S/L21 T/L31
R2/L12
S2/L22
T2/L32
FR-CV type Power regeneration common converter
R2/L1 S2/L2 T2/L3
R/L11 S/L21 T/MC1
P/L+ N/L
P24
*4
SD
RDYA
RDYB
RSO
SE
U
V
W
IM
CAUTION
The voltage phases of terminals R/L11, S/L21, T/MC1 and terminals R2/L1, S2/L2, T2/L3 must be matched.Use sink logic (initial setting) when the FR-CV is connected. The FR-CV cannot be connected when source logic is
selected.
Do not remove a jumper across terminal P/+ and P1.
34
Connection of stand-alone option units
A

2.5.6 Connection of the power regeneration converter (MT-RC) (75K or more)

When connecting a power regeneration converter (MT-RC), perform wiring securely as shown below. Incorrect connection will damage the regeneration converter and inverter. After connecting securely, set "1" in Pr. 30 Regenerative function selection and "0" in Pr. 70 Special regenerative brake duty.
Three-phase
C power
supply
MCCB
MC1
MT-RCL
R
S
T
MC2
DCL
R2
S2
T2
P1
P
R/L1
S/L2
T/L3
R1/L11
S1/L21
P1
R2
S2
T2
R
S
T
R1
S1
Inverter
P/+
P
U
V
W
N/
N
RES
STF
SD
C
B
A
RDY
SE
IM
Reset signal
Alarm signal
Ready signal
2
MT-RC
CAUTION
When using the FR-F700 series together with the MT­RC, install a magnetic contactor (MC) at the input side of
Inverter input power supply (MC2)
ON
the inverter so that power is supplied to the inverter after 1s or more has elapsed after powering on the MT-RC. When power is supplied to the inverter prior to the MT­RC, the inverter and the MT-RC may be damaged or the MCCB may trip or be damaged.
MT-RC power supply (MC1)
ON
1s or more
Refer to the MT-RC manual for precautions for
connecting the power coordination reactor and others.

2.5.7 Connection of the power factor improving DC reactor (FR-HEL)

When using the DC reactor (FR-HEL), connect it between terminals P1-P/+. For the 55K or less, the jumper connected across terminals P1-P/+ must be removed. Otherwise, the reactor will not exhibit its performance. For the 75K or more, a DC reactor is supplied. Always install the reactor.
P/+
P1
FR-HEL
Remove the jumper.
CAUTION
The wiring distance should be within 5m.
The size of the cables used should be equal to or larger than that of the power supply cables (R/L1, S/L2, T/L3).
(Refer to page 14)
INSTALLATION AND WIRING
35
Power-off and magnetic contactor (MC)

2.6 Power-off and magnetic contactor (MC)

(1) Inverter input side magnetic contactor (MC)
On the inverter input side, it is recommended to provide an MC for the following purposes.
Refer to page 3 for selection.)
(
1)To release the inverter from the power supply when the fault occurs or when the drive is not functioning (e.g.
emergency stop operation). To prevent any accident due to an automatic restart at restoration of power after an inverter stop made by a power failure
2)
3)While the power is ON, inverter is consuming a little power even during inverter stop. When stopping the inverter for
an extended period of time, powering OFF the inverter will save power slightly.
4)To separate the inverter from the power supply to ensure safe maintenance and inspection work
The inverter's input side MC is used for the above purpose, select class JEM1038-AC3MC for the inverter input side current when making an emergency stop during normal operation.
REMARKS
Since repeated inrush current at power on will shorten the life of the converter circuit (switching life is 100 million times (about 500,000 times for the 200V class 37K or more)), frequent starts/stops must be avoided. Turn on/off the inverter start controlling terminals (STF, STR) to run/stop the inverter.
• Inverter start/stop circuit example
As shown on the left, always use the start signal
To the
(ON or OFF of STF (STR) signal) to make a start
motor
or stop.
*1 When the power supply is 400V class, install a step-
down transformer.
*2 Connect the power supply terminals R1/L11, S1/L21
of the control circuit to the primary side of the MC to hold an alarm signal when the inverter's protective circuit is activated. At this time, remove jumpers across terminals R/L1-R1/L11 and S/L2-S1/L21. (Refer to page 17 for removal of the jumper.)
Operation preparation
OFF
Start/Stop
MC
Start
Power supply
ON
MC
MCCB
MC
RA
MC
*1
T
RA
R/L1
S/L2
T/L3
R1/L11
S1/L21
Inverter
STF(STR) SD
U
V
W
*2
C1
B1
A1
Stop
RA
(2) Handling of the inverter output side magnetic contactor
Switch the magnetic contactor between the inverter and motor only when both the inverter and motor are at a stop. When the magnetic contactor is turned on while the inverter is operating, overcurrent protection of the inverter and such will activate. When an MC is provided to switch to a commercial power supply, for example, it is recommended to
use bypass operation Pr. 135 to Pr. 139 (Refer to the chapter 4 of the Instruction Manual (applied)).
36
Precautions for use of the inverter

2.7 Precautions for use of the inverter

The FR-F700 series is a highly reliable product, but incorrect peripheral circuit making or operation/handling method may shorten the product life or damage the product. Before starting operation, always recheck the following items.
(1) Use crimping terminals with insulation sleeve to wire the power supply and motor.
(2) Application of power to the output terminals (U, V, W) of the inverter will damage the inverter. Never perform such wiring.
(3) After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean. When drilling mounting holes in an enclosure etc., take care not to allow chips and other foreign matter to enter the inverter.
(4) Use cables of the size to make a voltage drop 2% maximum.
If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop will cause the motor torque to decrease especially at the output of a low frequency. Refer to page 14 for the recommended cable sizes.
(5) The overall wiring length should be 500m maximum.
Especially for long distance wiring, the fast-response current limit function may decrease or the equipment connected to the secondary side may malfunction or become faulty under the influence of a charging current due to the stray capacity of the wiring. Therefore, note the overall wiring length. (Refer to page 16.)
(6) Electromagnetic wave interference
The input/output (main circuit) of the inverter includes high frequency components, which may interfere with the communication devices (such as AM radios) used near the inverter. In this case, set the EMC filter valid to minimize
interference.
(7) Do not install a power factor correction capacitor, surge suppressor or capacitor type filter on the inverter output side.
This will cause the inverter to trip or the capacitor and surge suppressor to be damaged. If any of the above devices is installed, immediately remove it.
(8) For some short time after the power is switched off, a high voltage remains in the smoothing capacitor. When accessing the
inverter for inspection, wait for at least 10 minutes after the power supply has been switched off, and then make sure that the voltage across the main circuit terminals P/+-N/- of the inverter is not more than 30VDC using a tester, etc.
(9) A short circuit or earth (ground) fault on the inverter output side may damage the inverter modules.
· Fully check the insulation resistance of the circuit prior to inverter operation since repeated short circuits caused by peripheral circuit inadequacy or an earth (ground) fault caused by wiring inadequacy or reduced motor insulation resistance may damage the inverter modules.
· Fully check the to-earth (ground) insulation and phase to phase insulation of the inverter output side before power-on. Especially for an old motor or use in hostile atmosphere, securely check the motor insulation resistance etc.
(10) Do not use the inverter input side magnetic contactor to start/stop the inverter.
Always use the start signal (ON/OFF of STF and STR signals) to start/stop the inverter.
(11) Do not apply a voltage higher than the permissible voltage to the inverter I/O signal circuits.
Application of a voltage higher than the permissible voltage to the inverter I/O signal circuits or opposite polarity may damage the I/O devices. Especially check the wiring to prevent the speed setting potentiometer from being connected incorrectly to short terminals 10E-5.
(Refer to page
9)
(Refer to page
8)
2
(12) Provide electrical and mechanical interlocks for MC1 and
MC2 which are used for bypass operation. When the wiring is incorrect or if there is an electronic bypass circuit as shown on the right, the inverter will be damaged when the power supply is connected to the inverter U, V, W terminals due to arcs generated at the time of switch-over or chattering caused by a sequence error.
Power supply
R/L1 S/L2 T/L3
Inverter
MC1
U V
W
Undesirable current
MC2
Interlock
IM
INSTALLATION AND WIRING
37
Precautions for use of the inverter
(13) If the machine must not be restarted when power is restored after a power failure, provide a magnetic contactor in the
inverter's input side and also make up a sequence which will not switch on the start signal. If the start signal (start switch) remains on after a power failure, the inverter will automatically restart as soon as the power is restored.
(14) Instructions for overload operation
When performing an operation of frequent start/stop of the inverter, increase/decrease in the temperature of the transistor element of the inverter may repeat due to a continuous flow of large current, shortening the life from thermal fatigue. Since thermal fatigue is related to the amount of current, the life can be increased by reducing bound current, starting current, etc. Decreasing current may increase the life. However, decreasing current will result in insufficient torque and the inverter may not start. Therefore, increase the inverter capacity to have enough allowance for current.
(15) Make sure that the specifications and rating match the system requirements.
(16) If electromagnetic noise generated from the inverter causes frequency setting signal to fluctuate and motor rotation
speed to be unstable when changing motor speed with analog signal, the following countermeasures are effective.
· Do not run the signal cables and power cables (inverter I/O cables) in parallel with each other and do not bundle them.
· Run signal cables as far away as possible from power cables (inverter I/O cables).
· Use shield cables as signal cables.
· Install a ferrite core on the signal cable (Example: ZCAT3035-1330 TDK).
38
Failsafe of the system which uses
the inverter

2.8 Failsafe of the system which uses the inverter

When a fault occurs, the inverter trips to output a fault signal. However, a fault output signal may not be output at an inverter
fault occurrence when the detection circuit or output circuit fails, etc. Although Mitsubishi assures best quality products,
provide an interlock which uses inverter status output signals to prevent accidents such as damage to machine when the
inverter fails for some reason and at the same time consider the system configuration where failsafe from outside the inverter,
without using the inverter, is enabled even if the inverter fails.
(1) Interlock method which uses the inverter status output signals
By combining the inverter status output signals to provide an interlock as shown below, an inverter alarm can be
detected.
No Interlock Method Check Method Used Signals Refer to Page
Inverter protective
1) function operation
2) Inverter running status Operation ready signal check
3) Inverter running status
4) Inverter running status
Operation check of an alarm contact Circuit error detection by negative logic
Logic check of the start signal and running signal
Logic check of the start signal and output current
Fault output signal ALM signal
Operation ready signal (RY signal)
Start signal (STF signal, STR signal) Running signal (RUN signal)
Start signal (STF signal, STR signal) Output current detection signal Y12 signal
Refer to the chapter
4 of the Instruction
Manual (applied)).
Refer to the chapter
4 of the Instruction
Manual (applied)).
Refer to the chapter
4 of the Instruction
Manual (applied)).
Refer to the chapter
4 of the Instruction
Manual (applied)).
(2) Backup method outside the inverter
Even if the interlock is provided by the inverter status signal, enough failsafe is not ensured depending on the failure
status of the inverter itself. For example, when the inverter CPU fails, even if the interlock is provided using the inverter
fault signal, start signal and RUN signal, there is a case where a fault signal is not output and RUN signal is kept output
even if an inverter fault occurs.
Provide a speed detector to detect the motor speed and current detector to detect the motor current and consider the
backup system such as checking up as below according to the level of importance of the system.
1) Start signal and actual operation check
Check the motor running and motor current while the start signal is input to the inverter by comparing the start signal to
the inverter and detected speed of the speed detector or detected current of the current detector. Note that the motor
current runs as the motor is running for the period until the motor stops since the inverter starts decelerating even if the
start signal turns off. For the logic check, configure a sequence considering the inverter deceleration time. In addition, it is
recommended to check the three-phase current when using the current detector.
2) Command speed and actual operation check
Check if there is no gap between the actual speed and commanded speed by comparing the inverter speed command
and detected speed of the speed detector.
Controller
System failure
2
INSTALLATION AND WIRING
Inverter
Sensor
(speed, temperature,
air volume, etc.)
To the alarm detection sensor
39
Step of operation
Step of operation
p

3 DRIVE THE MOTOR

3.1 Step of operation

The inverter needs frequency command and start command. Frequency command (set frequency) determines the rotation speed of the motor. Turning ON the start command starts the motor to rotate. Refer to the flow chart below to perform setting.
Step of operation
o
: Initial setting
Installation/mounting
{Refer to page 7}
Frequency command
Inverter output
Frequency
(Hz)
Frequency command
Start command with
on the operation panel (PU)
Set from the PU (FR-DU07/ FR-PU04/FR-PU07).
(PU)
{Refer to page 48} {Refer to page 51} {Refer to page 55} {Refer to page 53}
frequency
ON
How to
give a frequency
command?
Change frequency with ON/OFF switches connected to terminals (multi-speed setting)
Time (S)
(External) (External) (External)
Wiring of the power
supply and motor
How
to give a start
command?
Perform frequency setting by a current output device (Connection across
terminals 4-5)
{Refer to page 10}
Start command using the PU connector and RS-485 terminal of the inverter and plug-in option (Communication)
Refer to the chapter 4 of the Instruction Manual (applied)
Connect a switch, relay, etc. to the control circuit terminal block of the inverter to give a start command. (External)
Perform frequency setting by a voltage output device (Connection across
terminals 2-5)
How to
give a frequency
command?
Set from the PU (FR-DU07/ FR-PU04/FR-PU07).
(PU) (External) (External) (External)
{Refer to page 57} {Refer to page 59} {Refer to page 63} {Refer to page 61}
Change of frequency with ON/OFF switches connected to terminals (multi-speed setting)
Perform frequency setting by a current output device (Connection across terminals 4-5)
Perform frequency setting by a voltage output device (Connection across terminals 2-5)
CAUTION
Check the following points before powering on the inverter.
· Check that the inverter is installed correctly in a correct place. (Refer to page 7)
· Check that wiring is correct. (Refer to page 8)
· Check that no load is connected to the motor.
·When protecting the motor from overheat by the inverter, set Pr.9 Electronic thermal O/L relay (Refer to
page 46)
·When the rated frequency of the motor is 50Hz, set Pr.3 Base frequency (Refer to page 47)
40

3.2 Operation panel (FR-DU07)

3.2.1 Parts of the operation panel (FR-DU07)

Operation mode indication
PU: Lit to indicate PU operation mode. EXT: Lit to indicate External operation mode. NET: Lit to indicate Network operation mode.
Unit indication
· Hz: Lit to indicate frequency.
· A: Lit to indicate current.
· V: Lit to indicate voltage.
(Flicker when the set frequency monitor is displayed.)
Operation panel (FR-DU07)
Rotation direction indication
FWD: Lit during forward rotation REV: Lit during reverse rotation
On: Forward/reverse operation Flickering: When the frequency command is
not given even if the forward/reverse command is given. When the MRS signal is input.
Monitor indication
Lit to indicate monitoring mode.
Monitor(4-digit LED)
Shows the frequency, parameter number, etc.
Setting dial
(Setting dial: Mitsubishi inverter dial)
Used to change the frequency setting and parameter values.
Mode switchover
Used to change each setting mode.
No function
Start command forward rotation
Start command reverse rotation
Stop operation
Used to stop Run command. Fault can be reset when protective function is activated (fault).
Used to set each setting. If pressed during operation, monitor changes as below;
Running frequency
* Energy saving monitor is displayed when the
energy saving monitor of Pr. 52 is set.
Output current
Output voltage
3
*
Operation mode switchover
Used to switch between the PU and External operation mode. When using the External operation mode (operation using a separately connected frequency setting potentiometer and start signal), press this key to light up the EXT indication. (Change the Pr.79 value to use the combined mode.) PU: PU operation mode EXT: External operation mode
DRIVE THE MOTOR
41
Operation panel (FR-DU07)

3.2.2 Basic operation (factory setting)

Operation mode switchover
At powering on (External operation mode)
PU Jog operation mode
PU operation mode
(output frequency monitor)
Monitor/frequency setting
Parameter setting mode
Parameter settingFaults history
(Refer to page 45)
Output current monitor
Value change
Value change
(Example)
and frequency flicker.
Frequency setting has been written and completed!!
Output voltage monitor
Displays the present setting
(Example)
Parameter and a setting value flicker alternately.
Parameter write is completed!!
42
Parameter clear Parameter
[Operation for displaying faults history]
Past eight faults can be displayed.
(The latest fault is ended by ".".)
When no fault history exists, is displayed.
all clear
(Refer to page 116)
Fault clear
Parameter copy
Operation panel (FR-DU07)
Turn until (

3.2.3 Operation lock (Press [MODE] for an extended time (2s))

Operation using the setting dial and key of the operation panel can be invalid to prevent parameter change, and unexpected start or frequency setting.
· Set "10 or 11" in Pr. 161, then press for 2s to make the setting dial and key operation invalid.
· When the setting dial and key operation are invalid, appears on the operation panel.
If dial and key operation is attempted while dial and key operation are invalid, appears. (When dial or key is not touched for 2s, the monitor display appears.)
· To make the setting dial and key operation valid again, press for 2s.
POINT
Set "0" (extended mode parameter valid) in Pr.160 User group read selection. Set "10 or 11" (key lock valid) in Pr.161 Frequency setting/key lock operation selection.
Operation
1.Screen at powering on
The monitor display appears.
2.Press to choose the PU
operation mode.
3.Press to choose the parameter
setting mode.
4.
Pr. 160) appears.
5.Press to read the currently set value.
" "(initial value) appears.
6.Turn to change
it to the setting value of " ".
7.Press to set.
Display
PU indication is lit.
The parameter number read previously appears.
3
Flicker ··· Parameter setting complete!!
Release the operation lock to release the PU stop by key operation.
8.Change Pr. 161 to the setting value of " "
in the similar manner. (Refer to step 4 to 7.)
9.Press for 2s to show the key lock.
Functions valid even in the operation lock status
Stop and reset with .
CAUTION
Flicker ··· Parameter setting complete!!
Press for 2s.
DRIVE THE MOTOR
43
Operation panel (FR-DU07)

3.2.4 Monitoring of output current and output voltage

POINT
Monitor display of output frequency, output current and output voltage can be changed by pushing during
monitoring mode.
Operation
Display
1.Press during operation to choose the output
frequency monitor
2.Independently of whether the inverter is running
in any operation mode or at a stop, the output
current monitor appears by pressing .
3.Press to show the output voltage monitor.

3.2.5 First priority monitor

Hold down for 1s to set monitor description to be appeared first in the monitor mode.
(To return to the output frequency monitor, hold down for 1s after displaying the output frequency monitor.)

3.2.6 Setting dial push

Push the setting dial ( ) to display the set frequency currently set.
44

3.2.7 Changing the parameter setting value

Turn to change it to the set
value " ".
Changing example Change the Pr. 1 Maximum frequency .
Operation panel (FR-DU07)
Operation
1.Screen at powering on
The monitor display appears.
2.Press to choose the PU operation
mode.
3.Press to choose the parameter
setting mode.
4. Pr. 1) appears.
5.Press to read the present set value.
" "(initial value) appears.
6.
7.Press to set.
· Turn to read another parameter.
· Press to show the setting again.
· Press twice to show the next parameter.
· Press twice to return the monitor to frequency monitor.
Display
PU indication is lit.
The parameter number read previously appears.
Flicker ··· Parameter setting complete!!
to
For details refer to page 104.
REMARKS
The number of digits displayed on the operation panel (FR-DU07) is four. Only the upper four digits of values can be displayed
and set. If the values to be displayed have five digits or more including decimal places, the fifth or later numerals cannot be displayed nor set.
(Example) When Pr.1 When 60Hz is set, 60.00 is displayed. When 120Hz is set, 120.0 is displayed. The second decimal places cannot be displayed nor set.
are displayed ... Why?
appears. ...... Write disable error
appears. ......Write error during operation
appears. ...... Calibration error
appears. ...... Mode designation error
3
DRIVE THE MOTOR
45
Overheat protection of the motor by the inverter (Pr. 9)

3.3 Overheat protection of the motor by the inverter (Pr. 9)

Set the rated motor current in Pr. 9 Electronic thermal O/L relay to protect the motor from overheat.
Parameter
Number
9 Electronic thermal O/L relay
*1 Refer to page 134 for the rated inverter current value. *2 The minimum setting increments are 0.01A for the 55K or less and 0.1A for the 75K or more.
Changing example
Name Initial Value Setting Range *2 Description
*1
55K or less
75K or more
Rated inverter
current
Change the Pr. 9 Electronic thermal O/L relay setting to 2.0A according to the motor rated current. (FR-F740-0.75K)
Operation
1.Screen at powering on
The monitor display appears.
2.Press to choose the PU
operation mode.
PU indication is lit.
3.Press to choose the parameter
setting mode.
4.Turn until " "(Pr. 9
Electronic thermal O/L relay) appears.
5.Press to show the present
set value.
(2.1A for 0.75K)
0 to 500A
0 to 3600A
Set the rated motor current.
Display
The parameter number read previously appears.
Refer to page 134 for initial
value of the inverter rated current.
6.Turn to change
the set value to
" ". (2.0A)
7.Press to set.
Flicker ··· Parameter setting complete!!
· By turning , you can read another parameter.
· Press to show the setting again.
· Press twice to show the next parameter.
CAUTION
· Protective function by electronic thermal relay function is reset by inverter power reset and reset signal input. Avoid unnecessary reset and power-off.
· When two or more motors are connected to the inverter, they cannot be protected by the electronic thermal relay function. Install an external thermal relay to each motor.
· When the difference between the inverter and motor capacities is large and the setting is small, the protective characteristics of the electronic thermal relay function will be deteriorated. In this case, use an external thermal relay.
· A special motor cannot be protected by the electronic thermal relay function. Use an external thermal relay.
· PTC thermistor output built-in the motor can be input to the PTC signal (AU terminal). For details, refer to the chapter 4 of the Instruction Manual (applied).
· Electronic thermal relay may not function when 5% or less of inverter rated current is set to electronic thermal relay setting.
46
When the rated motor frequency is 50Hz
(Pr. 3)

3.4 When the rated motor frequency is 50Hz (Pr. 3)

First, check the motor rating plate. If a frequency given on the rating plate is "50Hz" only, always set Pr. 3 Base frequency to "50Hz". If it remains at "60Hz", the voltage may become too low and torque shortage occurs, resulting in an overload trip. It may result in an inverter trip (E.OC) due to overload.
Parameter
Number
3 Base frequency
Changing example Change Pr. 3 Base frequency to 50Hz according to the motor rated frequency.
1.Screen at powering on
The monitor display appears.
2.Press to choose the PU operation
mode.
3.Press to choose the parameter
setting mode.
4.Turn until Pr. 3 Base frequency
appears.
5.Press to show the present set
value. (60Hz)
6.Turn to change the set
value to " ". (50Hz)
Name Initial Value Setting Range Description
60Hz 0 to 400Hz
Operation
PU indication is lit.
Set the frequency when the motor rated torque is generated.
Display
The parameter number read previously appears.
7.Press to set.
·
· Press to show the setting again.
· Press twice to show the next parameter.
Flicker ··· Parameter setting complete!!
3
DRIVE THE MOTOR
47
Start/stop from the operation panel (PU
operation mode)

3.5 Start/stop from the operation panel (PU operation mode)

POINT
From where is the frequency command given?
· Operation at the frequency set in the frequency setting mode of the operation panelRefer to 3.5.1 (Refer to page 48)
· Operation using the setting dial as the potentiometerRefer to 3.5.2 (Refer to page 50)
· Change of frequency with ON/OFF switches connected to terminalsRefer to 3.5.3 (Refer to page 51)
· Frequency setting using voltage input signalRefer to 3.5.4 (Refer to page 53)
· Frequency setting using current input signalRefer to 3.5.5 (Refer to page 55)

3.5.1 Setting the set frequency to operate (example: performing operation at 30Hz)

POINT
Operation panel (FR-DU07) is used to give both of frequency and start commands in PU operation.
Operation panel
(FR-DU07)
Operation example
Performing operation at 30Hz.
Operation
1.Screen at powering on
The monitor display appears.
2.Press to choose the PU
operation mode.
3.Turn to show the frequency " "
(30.00Hz) you want to set. The frequency flickers for about 5s.
4.While the value is flickering,
press to set the frequency.
If you do not press , the value flickers for about 5s
and the display then returns to " " (0.00Hz). At this time, return to "Step 3" and set the frequency again. After the value flickered for about 3s,
the display returns to " " (monitor display).
5.Start acceleration constant speed
Press or to start running.
The frequency on the indication increases by
the Pr.7 Acceleration time, and " "
(30.00Hz) appears.
Display
PU indication is lit.
Flickers for
about 5s
Flicker ··· Frequency setting complete!!
After 3s, the monitor display appears.
/
48
6.To change the set frequency, perform the operation in above steps 3 and 4.
(Starting from the previously set frequency.)
Stop
7.Deceleration Stop
Press to stop. The frequency on the indication decreases by the Pr. 8 Deceleration time, and the motor stops rotating with " " (0.00Hz) displayed on the indication.
Start/stop from the operation panel (PU
Operation cannot be performed at the set frequency ... Why?
Did you carry out step 4 within 5s after step 3? (Did you press within 5s after turning ?)
The frequency does not change by turning ... Why?
Check to see if the operation mode selected is the External operation mode. (Press to change to the PU operation mode.)
Operation does not change to the PU operation mode ... Why?
Check that "0" (initial value) is set in Pr. 79 Operation mode selection.
Check that the start command is not on. Change acceleration time Pr. 7 (Refer to page 68) Change deceleration time Pr. 8 (Refer to page 68)
For example, limit the motor speed to 60Hz maximum. Set "60Hz" in Pr. 1. (Refer to page 67)
REMARKS
· Press to show the set frequency.
· can also be used like a potentiometer to perform operation. (Refer to page 50)
operation mode)
49
3
DRIVE THE MOTOR
Start/stop from the operation panel (PU
Turn until " " appears.
The flickering frequency is the set frequency.
operation mode)

3.5.2 Using the setting dial like a potentiometer at the operation.

POINT
Set "0" (extended mode parameter valid) in Pr. 160 User group read selection. Set "1" (setting dial potentiometer mode) in Pr. 161 Frequency setting/key lock operation selection.
Operation example Change the frequency from 0Hz to 60Hz during operation
DisplayOperation
1. Screen at powering on
The monitor display appears.
2. Press to choose the PU operation
mode.
3. Press to choose the parameter
setting mode.
4. Turn until (Pr. 160) appears.
5. Press to read the present set value.
" " (initial value) appears.
6. Turn to change it to
the setting value of " ".
7. Press to set.
8. Change Pr. 161 to the setting value of " "
in the similar manner.
(Refer to step 4 to 7.)
9. Mode/monitor check
Press twice to choose monitor/frequency monitor.
PU indication is lit.
The parameter number previously read appears.
Flicker ··· Parameter setting complete!!
Flicker ··· Parameter setting complete!!
10. Press (or ) to start the inverter.
11.
You need not press .
REMARKS
· If flickering "60.00" turns to "0.0", the Pr. 161 Frequency setting/key lock operation selection setting may not be "1".
· Independently of whether the inverter is running or at a stop, the frequency can be set by merely turning .
CAUTION
· When using setting dial, the frequency goes up to the set value of Pr. 1 Maximum frequency (initial value is 120Hz (55K or less)/ 60Hz (75K or more)). Adjust Pr. 1 Maximum frequency setting according to the application.
50
The frequency flickers for about 5s.
Start/stop from the operation panel (PU
Turn until (
Turn to change it to the
setting value " ".
operation mode)

3.5.3 Setting the frequency by switches (three-speed setting)

POINT
· To give a start command, or of the operation panel (FR-DU07) is used.
· To give a frequency command, terminal between SD and terminal RH, RM, or RL is turned ON. (three-speed setting)
· Pr. 79 Operation mode selection must be set to "4" (External/PU combination operation mode 2)
[Connection diagram]
High speed Middle speed Low speed
RH RM RL SD
Inverter
Operation panel
(FR-DU07)
Speed 1
(High speed)
Speed 2 (Middle speed)
Output frequency (Hz)
ON
RH
RM
RL
ON
Speed 3 (Low speed)
ON
Operation example
Operate in low-speed (10Hz)
1. Screen at powering on
The monitor display appears.
2. Press to choose the parameter setting
mode.
3.
Pr. 79) appears.
4. Press to read the present set value.
" "(initial value) appears.
5.
6. Press to set.
7. Mode/monitor check
Press twice to change to monitor / frequency monitor. [PU] indication and [EXT] indication are lit.
DisplayOperation
The parameter number read previously appears.
3
Flicker ··· Parameter setting complete!!
8. Start
Turn ON the low-speed switch (RL).
High speed
Middle speed
Low speed
ON
DRIVE THE MOTOR
51
Start/stop from the operation panel (PU
operation mode)
Operation Display
9. Acceleration constant speed
Press or to start running.
The frequency on the indication increases
by the Pr.7 Acceleration time, and " "
(10.00Hz) appears.
/
10. Deceleration
Press to stop. The frequency on the indication decreases by the Pr. 8 Deceleration time, and the motor stops rotating with " " (0.00Hz) displayed on the indication.
11. STOP
Turn OFF the low-speed switch (RL).
60Hz for the RH, 30Hz for the RM and 10Hz for the RL are not output when they are turned on ... Why?
Check for the setting of Pr. 4, Pr. 5, and Pr. 6 once again. Check for the setting of Pr. 1 Maximum frequency and Pr. 2 Minimum frequency once again.
(Refer to page 67.) Check that Pr. 180 RL terminal function selection = "0", Pr. 181 RM terminal function selection = "1", Pr.
182 RH terminal function selection ="2", and Pr. 59 Remote function selection = "0". (all are initial values)
[FWD (or REV)] lamp is not lit ... Why?
Check that wiring is correct. Check the wiring once again. Check for the Pr. 79 setting once again. (Pr. 79 must be set to "4".)
(Refer to page 71.)
Change the frequency of the terminal RL, RM, and RH. ... How?
Refer to page 59 to change the running frequency at each terminal in Pr. 4 Multi-speed setting (high speed), Pr. 5 Multi-speed setting (middle speed), and Pr. 6 Multi-speed setting (low speed).
High speed
Middle speed
Low speed
OFF
Stop
REMARKS
· Initial value of terminal RH, RM, and RL are 60Hz, 30Hz, and 10Hz. (To change, set Pr. 4, Pr. 5, and Pr. 6.)
· In the initial setting, when two or more of multi-speed settings are simultaneously selected, priority is given to the set frequency of the lower signal. For example, when RH and RM signals turn ON, RM signal (Pr. 5) has a higher priority.
· Maximum of 15-speed operation can be performed.
(Refer to the chapter 4 of the Instruction Manual (applied).)
52
Start/stop from the operation panel (PU
Turn until (
Turn to change it to
the setting value " ".

3.5.4 Setting the frequency by analog input (voltage input)

POINT
· To give a start command, or of the operation panel (FR-DU07) is used .
· Frequency command is given from the potentiometer. (by connecting terminal 2 and 5.)
· Pr. 79 Operation mode selection must be set to "4" (External/PU combination operation mode 2). [Connection diagram]
(The inverter supplies 5V of power to the frequency setting potentiometer.(Terminal 10)
Inverter
Operation panel
Frequency setting potentiometer
Operation example Performing operation at 60Hz.
10
2 5
(FR-DU07)
DisplayOperation
operation mode)
)
1. Screen at powering on
The monitor display appears.
2. Press to choose the parameter setting
mode.
3.
Pr. 79) appears.
4. Press to read the present set value.
" "(initial value) appears.
5.
6. Press to set.
7. Mode/monitor check
Press twice to choose the monitor/frequency monitor. [PU] indication and [EXT] indication are lit.
8. Start
Press or . [FWD] or [REV] is flickering as no frequency command is given.
The parameter number read previously appears.
3
Flicker ··· Parameter setting complete!!
/
Flickering
9. Acceleration constant speed
DRIVE THE MOTOR
Turn the potentiometer (frequency setting potentiometer) clockwise slowly to full. The frequency value on the indication increases according to Pr. 7 Acceleration
time until " "(60Hz) is displayed.
53
Start/stop from the operation panel (PU
operation mode)
Deceleration
10.
Turn the potentiometer (frequency setting potentiometer) counterclockwise slowly to full. The frequency on the indication decreases by the Pr. 8 Deceleration time, and the motor stops rotating with " " (0.00Hz) displayed on the indication. [FWD] indication or [REV] indication flickers.
11. Stop
Press .
indication
[FWD]
Change the frequency (60Hz) of the maximum value of potentiometer (at 5V)
Adjust the frequency in Pr. 125 Terminal 2 frequency setting gain frequency. (Refer to page 62.)
Change the frequency (0Hz) of the minimum value of potentiometer (at 0V)
Adjust the frequency in calibration parameter C2 Terminal 2 frequency setting bias frequency. (Refer to the
chapter 4 of the Instruction Manual (applied).)
or [REV] indication turns OFF.
DisplayOperation
Flickering
Stop
54
Start/stop from the operation panel (PU
Turn until (
Turn to change it to the setting
alue "
".
operation mode)

3.5.5 Setting the frequency by analog input (current input)

POINT
· To give a start command, or of the operation panel (FR-DU07) is used.
· Frequency command is given from the current signal source (4 to 20mA). (by connecting terminal 4 and 5.)
· Turn the AU signal on.
· Pr. 79 Operation mode selection must be set to "4" (External/PU combination operation mode 2).
[Connection diagram]
Inverter
AU signal
Current signal
source
(4 to 20mADC)
Operation example Performing operation at 60Hz.
AU
SD
4 (+)
5 (-)
Operation panel
(FR-DU07)
1.
Screen at powering on The monitor display appears.
2.
Press to choose the parameter setting mode.
3.
4.
Press to read the present set value. " "(initial value) appears.
Pr. 79) appears.
5.
v
6.
7.
Press to set.
Mode/monitor check Press twice to choose the monitor/frequency monitor. [PU] indication and [EXT] indication are lit.
DisplayOperation
The parameter number read previously appears.
3
Flicker ··· Parameter setting complete!!
Start
8.
Check that the terminal 4 input selection signal (AU) is on. Press or . [FWD] or [REV] is flickering as no frequency command is given.
/
Flickering
DRIVE THE MOTOR
55
Start/stop from the operation panel (PU
operation mode)
9.
Acceleration constant speed Perform 20mA input. The frequency on the indication increases by the Pr. 7 Acceleration time and
60.00Hz) appears.
(
10.
Deceleration Input 4mA or less.
The frequency on the indication decreases by the Pr. 8 Deceleration time, and the motor stops rotating with " " (0.00Hz) displayed on the indication.
[FWD] indication or [EXT] indication flickers.
11.
Stop Press . [FWD] indication or [REV] indication turns OFF.
" "
Current signal
source
(20mADC)
Current signal
source
(4mADC)
DisplayOperation
Flickering
Stop
REMARKS
Pr. 184 AU terminal function selection must be set to "4" (AU signal) (initial value). (Refer to the chapter 4 of the Instruction Manual (applied).)
Change the frequency (60Hz) at the maximum current input (at 20mA, initial value)
Adjust the frequency in Pr. 126 Terminal 4 frequency setting gain frequency. (Refer to page 64.)
Change the frequency (0Hz) at the minimum current input (at 4mA, initial value)
Adjust the frequency in calibration parameter C5 Terminal 4 frequency setting bias frequency. (Refer to
the chapter 4 of the Instruction Manual (applied).)
56
Start and stop using terminals (External
Turn until (
Turn to change it to the
".
operation)

3.6 Start and stop using terminals (External operation)

POINT
From where is the frequency command given?
· Operation at the frequency set in the frequency setting mode of the operation panel Refer to 3.6.1(Refer to page 57)
· Give a frequency command by switch (multi-speed setting) Refer to 3.6.2 (Refer to page 59)
· Perform frequency setting using voltage input signal Refer to 3.6.3 (Refer to page 61)
· Perform frequency setting using current input signal Refer to 3.6.5 (Refer to page 63)

3.6.1 Setting the frequency by the operation panel (Pr. 79 = 3)

POINT
· Switch STF(STR) signal on to give a start command.
· Use ( ) on the operation panel (FR-DU07) to give a frequency command.
· Pr. 79 Operation mode selection must be set to "3" (External/PU combination operation mode 1).
[Connection diagram]
Inverter
Forward rotation start
Reverse rotation start
Operation example
Performing operation at 30Hz.
Operation
1.Screen at powering on
The monitor display appears.
2.Press to choose the PU
operation mode.
3.Press to choose the parameter
setting mode.
4.
Pr. 79) appears.
STF STR
SD
Operation panel
(FR-DU07)
Display
PU indication is lit.
3
The parameter number read previously appears.
5.Press to read the present set value.
" "(initial value) appears.
6.
setting value "
7.Press to set.
8. Mode/monitor check
DRIVE THE MOTOR
Flicker ··· Parameter setting complete!!
Press twice to choose the monitor/frequency monitor. [PU] indication and [EXT] indication are lit.
57
Start and stop using terminals (External
operation)
Operation
9. Turn to show the selected
frequency, " " (30.00Hz).
The frequency flickers for about 5s.
10.While the value is flickering,
press to set the frequency.
If you do not press ,the value flickers for about 5s and the display then returns to (display) Hz. At this time, return to "Step 8" and set the frequency again.
After about 3s of flickering of the value,
the indication goes back to " " (monitor display).
11.Start acceleration constant speed
Turn ON the start switch (STF or STR). The frequency on the indication increases by the Pr.7 Acceleration time, and " " (30.00Hz) appears. [FWD] indication is lit during forward rotation, and [REV] indication is lit during reverse rotation.
CAUTION
When both of STF and STR signals are turned ON, the inverter cannot start. If both are turned ON while the inverter is running, the inverter decelerates to a stop.
Forward rotation
ON
Display
Flickers for about 5s
Flicker ··· Frequency setting complete!!
After 3s, the monitor display appears.
Reverse rotation
12.To change the set frequency, perform the operation in above steps 9 and 10.
(Starting from the previously set frequency.)
OFF
Forward rotation
Reverse rotation
Stop
13.Deceleration Stop
Turn OFF the start switch (STF or STR). The frequency on the indication decreases by the Pr. 8 Deceleration time, and the motor stops rotating with " " (0.00Hz) displayed on the indication.
REMARKS
· Pr. 178 STF terminal function selection must be set to "60" (or Pr. 179 STR terminal function selection must be set to "61"). (all are initial values)
· When Pr. 79 Operation mode selection is set to "3", multi-speed operation (refer to page 59) is also valid.
When the inverter is stopped by of the operation panel (FR-DU07), and are
displayed alternately.
1. Turn the start switch (STF or STR) off.
2. The display can be reset by .
Flickering
58
Start and stop using terminals (External
operation)

3.6.2 Setting the frequency by switches (three-speed setting) (Pr. 4 to Pr. 6)

POINT
· Start command by terminal STF (STR)
· Frequency command by terminal RH, RM, RL and STR
· [EXT] must be lit. (When [PU] is lit, switch it to [EXT] with .)
· The initial values of the terminals RH, RM, RL are 60Hz, 30Hz, and 10Hz. (Use Pr. 4, Pr. 5 and Pr. 6 to change.)
· Operation at 7-speed can be performed by turning two (or three) terminals simultaneously. (Refer to the chapter 4 of
the Instruction Manual (applied).)
[Connection diagram]
Speed 1
(High speed)
Speed 2 (Middle speed)
Output frequency (Hz)
ON
RH
RM
RL
ON
Speed 3 (Low speed)
ON
Forward rotation start
Reverse rotation start
Changing example
Inverter
STF STR
High speed
Middle speed
Low speed
RH RM RL SD
Operation at high speed (60Hz).
1. Screen at powering on
The monitor display appears.
2. Turn ON the high-speed switch (RH).
3.
Acceleration constant speed
urn ON the start switch (STF or STR). The
T frequency on the indication increases by the Pr. 7 Acceleration time, and " " (60.00Hz) appears. [FWD] indication is lit during forward rotation, and [REV] indication is lit during reverse rotation.
When RM is turned ON, 30Hz is displayed. When RL is turned ON, 10Hz is displayed.
CAUTION
When both of STF and STR signals are turned ON, the inverter cannot start. If both are turned ON while the inverter is running, the inverter decelerates to a stop.
4. Turn OFF the start switch (STF or STR).
The frequency on the indication decreases by the Pr. 8 Deceleration time, and the motor stops rotating with " " (0.00Hz) displayed on the indication. [FWD] indication or [REV] indication turns OFF.
5. Stop
Turn OFF the high-speed switch (RH).
ON
High speed
ON
ON
OFF
High speed
OFF
Middle speed
Low speed
Forward rotation
Reverse rotation
Forward rotation
Reverse rotation
Middle speed
Low speed
DisplayOperation
3
DRIVE THE MOTOR
Stop
59
Start and stop using terminals (External
operation)
[EXT] is not lit even when is pressed ... Why?
Switchover of the operation mode with is valid when Pr. 79 = "0" (initial value).
60Hz, 30Hz and 10Hz are not output from RH, RM and RL respectively when they are turned on. ... Why?
Check for the setting of Pr. 4, Pr. 5, and Pr. 6 once again. Check for the setting of Pr. 1 Maximum frequency and Pr. 2 Minimum frequency once again. (Refer to
page 67)
Check for the Pr. 79 setting once again. (Pr. 79 must be set to "0" or "2".) (Refer to page 71) Check that Pr. 180 RL terminal function selection = "0", Pr. 181 RM terminal function selection = "1",
Pr. 182 RH terminal function selection = "2" and Pr. 59 Remote function selection = "0". (all are initial values)
[FWD (or REV)] is not lit. ... Why?
Check that wiring is correct. Check it again. Check that "60" is set in Pr. 178 STF terminal function selection (or "61" is set in Pr. 179 STR terminal
function selection)? (all are initial values)
How is the frequency setting from 4 to 7 speed ?
In the initial setting, when two or more of multi-speed settings are simultaneously selected, priority is given to the set frequency of the lower signal. For example, when RH and RM signals turn ON, the RM signal (Pr. 5) has a higher priority. By setting Pr. 24 to Pr. 27 (multi-speed setting), up to 7- speed
can be set by combinations of RH, RM, and RL signals. Refer to the chapter 4 of the Instruction
Manual (applied).
Perform multi-speed operation more than 8 speed. ... How?
Use the REX signal to perform the operation. Maximum of 15-speed operation can be performed.
Refer to the chapter 4 of the Instruction Manual (applied).
REMARKS
· External operation is fixed by setting "2" (External operation mode) in Pr. 79 Operation mode selection when you do not want to take
time pressing or when you want to use the current start command and frequency command. (Refer to page 71)
60
Start and stop using terminals (External

3.6.3 Setting the frequency by analog input (voltage input)

POINT
· To give a start command, terminal between SD and STF (STR) is turned ON.
· Frequency command is given from the potentiometer (by connecting terminal 2 and 5).
[Connection diagram]
(The inverter supplies 5V of power to frequency setting potentiometer. (Terminal 10))
Inverter
operation)
Operation example
1.Screen at powering on
The monitor display appears.
2.Start
Turn the start switch (STF or STR) on. [FWD] or [REV] is flickering as no frequency command is given.
CAUTION
When both of STF and STR signals are turned ON, the inverter cannot start. If both are turned ON while the inverter is running, the inverter decelerates to a stop.
Forward rotation start
Reverse rotation start
Frequency setting potentiometer
Performing operation at 60Hz.
ON
Forward rotation
ON
STF STR SD
10
2 5
DisplayOperation
Reverse rotation
Flickering
3. Acceleration → constant speed
Turn the potentiometer (frequency setting potentiometer) clockwise slowly to full.
The frequency on the indication increases by the Pr.7
Acceleration time, and " " (60.00Hz) appears. [FWD] indication is lit during forward rotation, and [REV] indication is lit during reverse rotation.
4. Deceleration
Turn the potentiometer (frequency setting potentiometer) counterclockwise slowly to full. The frequency on the indication decreases by the Pr. 8 Deceleration time, and the motor stops rotating with " " (0.00Hz) displayed on the indication. [FWD] indication or [EXT] indication flickers.
5.Stop
Turn the start switch (STF or STR) off. [FWD] indication or [REV] indication turns OFF.
Forward rotation
OFF
Reverse rotation
When you want to operate in the External operation mode always at powering on or when you want to
Flickering
Stop
3
DRIVE THE MOTOR
save the trouble of input, set "2" (External operation mode) in Pr. 79 Operation mode selection to choose External operation mode always.
61
Start and stop using terminals (External
operation)
REMARKS
Pr. 178 STF terminal function selection must be set to "60" (or Pr. 179 STR terminal function selection must be set to "61"). (all are initial values)
The motor will not rotate ... Why?
Check that [EXT] is lit. [EXT] is valid when Pr. 79 = "0" (initial value).
Use to lit [EXT].
Check that wiring is correct. Check once again.
Change the frequency (0Hz) of the minimum value of potentiometer (at 0V)
Adjust the frequency in calibration parameter C2 Terminal 2 frequency setting bias frequency. (Refer to the
chapter 4 of the Instruction Manual (applied).)
When you want to compensate frequency setting, use terminal 1. For details, refer to the chapter 4 of the Instruction Manual (applied).

3.6.4 Changing the output frequency (60Hz, initial value) at the maximum voltage input (5V, initial value)

<How to change the maximum frequency>
Changing example
When you use the 0 to 5VDC input to change frequency at 5V from 60Hz (initial value) to 50Hz, set "50Hz" in Pr. 125.
DisplayOperation
1.
Turn until (Pr. 125) appears.
2.
Press to show the present set value.
" "(60.00Hz)
3.
Turn to change the set value
to " ". (50.00Hz)
4.
Press to set.
···
5.
Mode/monitor check
Press twice to choose the monitor/frequency monitor
6.
To check the setting, turn the start switch (STF or STR) on
and input 5V (turn the potentiometer clockwise slowly to full.)
(Refer to 3.6.3 steps 2 to 5)
Flicker
.
The frequency meter (indicator) connected across terminals FM-SD does not indicate exactly 50Hz ... Why?
The meter can be adjusted by calibration parameter C0 FM terminal calibration. (Refer to the chapter 4
of the Instruction Manual (applied).)
Set frequency at 0V using calibration parameter C2 and adjust the indicator using
60Hz
calibration parameter C0.
(Refer to the chapter 4 of the Instruction Manual (applied).)
(Hz)
50Hz output at 5V input complete!!
Initial value
Output frequency
Bias
C2
(Pr. 902)
C3 (Pr. 902) C4 (Pr. 903)
0 05V
Frequency setting signal
0
100%
10V
Gain
Pr.125
REMARKS
As other adjustment methods of frequency setting voltage gain, there are methods to adjust with a voltage applied to across terminals 2-5 and adjust at any point without a voltage applied.
(Refer to the chapter 4 of the Instruction Manual (applied) for the setting method of calibration parameter C4.)
62
Start and stop using terminals (External

3.6.5 Setting the frequency by analog input (current input)

POINT
· Switch terminal STF(STR)-SD on to give a start command.
· Turn the AU signal on.
· Set "2" (External operation mode) in Pr. 79 Operation mode selection
[Connection diagram]
Inverter
operation)
Forward rotation start Reverse rotation start
Current signal
source
(4 to 20mADC)
1.Screen at powering on
The monitor display appears.
2.Start
Check that the terminal 4 input selection signal (AU) is ON. Turn the start switch (STF or STR) on. [FWD] or [REV] is flickering as no frequency command is given.
CAUTION
When both of STF and STR signals are turned ON, the inverter cannot start. If both are turned ON while the inverter is running, the inverter decelerates to a stop.
ON
Forward rotation
ON
STF STR
AU
SD
4(+)
5(-)
DisplayOperation
Reverse rotation
Flickering
3.Acceleration → constant speed
Perform 20mA input. The frequency on the indication increases by the Pr.7 Acceleration time, and " " (60.00Hz) appears. [FWD] indication is lit during forward rotation, and [REV] indication is lit during reverse rotation.
4.Deceleration
Input 4mA or less. The frequency on the indication decreases by the Pr. 8 Deceleration time, and the motor stops rotating with " " (0.00Hz) displayed on the indication. [FWD] indication or [EXT] indication flickers.
5.Stop
Turn the start switch (STF or STR) off. [FWD]
indication
REMARKS
Pr. 184 AU terminal function selection must be set to "4" (AU signal) (initial value). (Refer to the chapter 4 of the Instruction Manual (applied).)
or [REV] indication turns OFF.
Current signal
source
(20mADC)
Current signal
source
(4mADC)
Forward rotation
OFF
Reverse rotation
Flickering
Stop
3
DRIVE THE MOTOR
63
Start and stop using terminals (External
Turn until (
operation)
The motor will not rotate ... Why?
Check that [EXT] is lit. [EXT] is valid when Pr. 79 = "0" (initial value).
PU
Use to lit [EXT].
EXT
Check that the AU signal is on. Turn the AU signal on.
Check that wiring is correct. Check it again.
Change the frequency (0Hz) of the minimum value of potentiometer (at 4mA)
Adjust the frequency in calibration parameter C5 Terminal 4 frequency setting bias frequency.
(Refer to the chapter 4 of the Instruction Manual (applied).)

3.6.6 Changing the output frequency (60Hz, initial value) at the maximum current input (at 20mA, initial value)

<How to change the maximum frequency>
Changing example
When you use the 4 to 20mA input and want to change the frequency at 20mA from 60Hz (initial value) to 50Hz, set "50Hz" in Pr. 126.
DisplayOperation
1.
Pr. 126) appears.
2.Press to show the present set value.
" "(60.00Hz)
3.Turn to change the set value to " ".
(50.00Hz)
4.Press to set the value.
Flicker ··· 50Hz output at 20mA input complete!!
5.Mode/monitor check
Press twice to choose the
monitor/frequency monitor.
6.
To check the setting, turn the start switch (STF or STR)
on and input 20mA.
The frequency meter (indicator) connected across terminals FM-SD does not indicate exactly 50Hz ... Why?
The meter can be adjusted by calibration parameter C0 FM terminal calibration.
(Refer to the chapter 4 of
Set frequency at 4mA using calibration parameter C5 and adjust the indicator using calibration parameter C0.
(Refer to the chapter 4 of the Instruction Manual (applied).)
(Refer to 3.6.5 steps 2 to 5)
the Instruction Manual (applied).)
Initial value
60Hz
(Hz)
REMARKS
As other adjustment methods of frequency setting voltage gain, there are methods to adjust with a voltage applied to across terminals 4-5 and adjust at any point without a voltage applied.
(Refer to the chapter 4 of the Instruction Manual (applied) for the setting method of calibration parameter C7.)
64
Output frequency
Bias
C5
(Pr. 904)
Gain
20
0 0
4 20mA
Frequency setting signal
C6 (Pr. 904) C7 (Pr. 905)
100%
Pr. 126
Simple mode parameter list

4 ADJUSTMENT

4.1 Simple mode parameter list

For simple variable-speed operation of the inverter, the initial setting of the parameters may be used as they are. Set the necessary parameters to meet the load and operational specifications. Parameter setting, change and check can
be made from the operation panel (FR-DU07). For details of parameters, refer to the chapter 4 of the Instruction
Manual (applied).
POINT
Only simple mode parameters are displayed by the initial setting of Pr. 160 User group read selection. Set Pr. 160 User group read selection as required. (Refer to page 45 for parameter change.)
Pr. 160 Description
9999
(Initial Value)
0 Simple mode and extended mode parameters can be displayed.
1 Only the parameters registered in the user group can be displayed.
Only the simple mode parameters can be displayed.
Simple mode parameter list
Parameter
Number
0 Torque boost 0.1%
1
2
3 Base frequency
4
6
7 Acceleration time 0.1s 5/15s*3 0 to 3600s Acceleration/deceleration time can be set.
8 Deceleration time
9
60
79
125
126
160
Name
Maximum frequency
Minimum frequency
Multi-speed setting (high speed)
Multi-speed setting (middle speed)
Multi-speed setting (low speed)
Electronic thermal O/L relay
Energy saving control selection
Operation mode selection
Terminal 2 frequency setting gain frequency
Terminal 4 frequency setting gain frequency
User group read selection
Incre
ments
0.01Hz
0.01Hz 0Hz 0 to 120Hz
0.01Hz 60Hz 0 to 400Hz
0.01Hz 60Hz 0 to 400Hz
0.01Hz 30Hz 0 to 400Hz
0.01Hz 10Hz 0 to 400Hz
0.1s 10/30s*3 0 to 3600s
0.01/
0.1A
0.01Hz 60Hz 0 to 400Hz
0.01Hz 60Hz 0 to 400Hz
Initial Value
6/4/3/2/
1.5/1%
120/
60Hz
*2
Rated
inverter
*4
current
100, 4, 9
1 0 0, 1, 2, 3, 4, 6, 7
1 9999 0, 1, 9999 Make extended parameters valid
Range Applications
Set to increase a starting torque or when the motor with a load will not rotate, resulting in an
0 to 30%
*1
0 to 120Hz
0 to 500/ 0 to 3600A
alarm [OL] and a trip [OC1]
*1 Initial values differ according to the inverter
capacity. (0.75K/1.5K to 3.7K/5.5K, 7.5K/11K to 37K/45K, 55K/75K or more)
Set when the maximum output frequency need to be limited.
*2 Initial values differ according to the inverter
capacity. (55K or less/75K or more)
Set when the minimum output frequency need to be limited.
Set when the rated motor frequency is 50Hz. Check the motor rating plate.
Set when changing the preset speed in the parameter with a terminal.
*3 Initial values differ according to the inverter
capacity. (7.5K or less/11K or more)
Protect the motor from overheat by the inverter. Set the rated motor current.
*4 Setting increments and setting range differ
*4
according to the inverter capacity. (55K or less/75K or more)
The inverter output voltage is minimized when using for fan and pump applications.
Select the start command location and frequency setting location.
Frequency for the maximum value of the potentiometer (at 5V) can be changed.
Frequency at 20mA input can be changed. 64
Refer
to
66
67
47
595
68
4
46
69
71
ADJUSTMENT
62
65
Increasing the starting torque (Pr. 0)
P P

4.2 Increasing the starting torque (Pr. 0)

Set this parameter when "the motor with a load will not rotate", "an alarm [OL] is output, resulting in an inverter trip due to [OC1], etc.
Parameter
Number
0 Torque boost
Changing example
1.Screen at powering on
The monitor display appears.
2.Press to choose the PU operation mode.
Name Initial Value
0.75K
1.5K to 3.7K
5.5K, 7.5K
11K to 37K
45K, 55K
75K or more
When the motor with a load will not rotate, increase the Pr. 0 value 1% by 1% unit by looking at the motor movement. (The guideline is for about 10% change at the greatest.)
Operation
Setting
Range
6% 4% 3%
0 to 30%
2%
1.5% 1%
100%
Output voltage
r. 0
Setting
r.46
range
Display
PU indication is lit.
Description
Motor torque in the low­frequency range can be adjusted to the load to increase the starting motor torque.
0
Output frequency (Hz)
Base frequency
3.Press to choose the parameter
setting mode.
The parameter number read previously appears.
4. Pr. 0) appears.
5.Press to read the present set value.
" "(initial value is 6% for the 0.75K) appears.
The initial value differs according to the capacity.
6.Turn to change it to the set value
" ".
7.Press to set.
Flicker ··· Parameter setting complete!!
· By turning , you can read another parameter.
· Press to show the setting again.
· Press twice to show the next parameter.
REMARKS
· A too large setting may cause the motor to overheat, resulting in an overcurrent trip (OL (overcurrent alarm) then E.OC1 (Overcurrent trip during acceleration)), thermal trip (E.THM (Motor overload trip), and E.THT (Inverter overload trip)). When a fault (E.OC1) occurs, release the start command, and decrease the Pr. 0 value 1% by 1% to reset. (Refer to page 108.)
POINT
If the inverter still does not operate properly after the above measures, adjust Pr. 80 Motor capacity(Simple magnetic
flux vector control) [extended mode]. (Refer to the chapter 4 of the Instruction Manual (applied).)
66
Limiting the maximum and minimum
y
Turn to change it to the set
value " ".
output frequency (Pr. 1, Pr. 2)

4.3 Limiting the maximum and minimum output frequency (Pr. 1, Pr. 2)

Parameter
Number
Name Initial Value
1 Maximum frequency
2 Minimum frequency
Changing example
Limit the frequency set by the potentiometer, etc. to 60Hz maximum. (Set "60"Hz in Pr. 1 Maximum frequency.)
1.Screen at powering on
The monitor display appears.
2.Press to choose the PU operation
mode.
3.Press to choose the parameter
setting mode.
Operation
55K or less
75K or more
0Hz 0 to 120Hz
Setting
Range
120Hz
60Hz
0 to 120Hz
Output frequency (Hz)
Pr.1 Pr.18
Pr.2
Clamped at the minimum frequency
PU indication is lit.
Description
Set the upper limit of the output frequency.
Set the lower limit of the output frequency.
Clamped at the maximum frequenc
Frequency setting
0
(4mA)
5, 10V
(20mA)
Display
The parameter number read previously appears.
4. Pr. 1) appears.
5.Press to read the present set value.
" "(initial value) appears.
6.
7.Press to set.
Flicker ··· Parameter setting complete!!
· By turning , you can read another parameter.
· Press to show the setting again.
· Press twice to show the next parameter.
REMARKS
· The output frequency is clamped by the Pr. 2 setting even if the set frequency is lower than the Pr. 2 setting (The frequency will not decrease to the Pr. 2 setting.) Note that Pr. 15 Jog frequency has higher priority than the minimum frequency.
· When the Pr. 1 setting is changed, frequency higher than the Pr. 1 setting can not be set by .
· When performing a high speed operation at 120Hz or more, setting of Pr. 18 High speed maximum frequency is necessary.
(Refer to the chapter 4 of the Instruction Manual (applied).)
4
ADJUSTMENT
If the Pr. 2 setting is higher than the Pr. 13 Starting frequency value, note that the motor will run at the set frequency according to the acceleration time setting by merely switching the start signal on, without entry of the command frequency.
CAUTION
67
Changing acceleration and deceleration time
(Pr. 7, Pr. 8)

4.4 Changing acceleration and deceleration time (Pr. 7, Pr. 8)

Set in Pr. 7 Acceleration time a larger value for a slower speed increase and a smaller value for a faster speed increase. Set in Pr. 8 Deceleration time a larger value for a slower speed decrease and a smaller value for a faster speed decrease.
Parameter
Number
7 Acceleration time
8 Deceleration time
* Depends on the Pr. 21 Acceleration/deceleration time increments setting. The initial value for the setting range is "0 to 3600s" and setting increments is
"0.1s".
Name Initial Value
7.5K or less
11K or more
7.5K or less
11K or more
5s
15s
10s
30s
Setting
Range
0 to 3600/
360s
*
0 to 3600/
*
360s
Description
Set the motor acceleration time.
Set the motor deceleration time.
Changing example Change the Pr. 7 Acceleration time setting from "5s"
to "10s".
Operation
Pr.20
(60Hz)
(Hz)
Output
frequency
Acceleration time
Display
Pr.7
Running frequency
Deceleration time
Time
Pr.8
1.Screen at powering on
The monitor display appears.
2.Press to choose the PU operation
mode.
PU indication is lit.
3.Press to choose the parameter
setting mode.
4. Pr. 7) appears.
5.Press to read the present set value.
" "(initial value) appears.
6.Turn to change it to the set
value " ".
7.Press to set.
· By turning , you can read another parameter.
· Press to show the setting again.
· Press twice to show the next parameter.
The parameter number read previously appears.
The initial value differs according to the capacity.
Flicker ··· Parameter setting complete!!
68
Energy saving operation (Pr. 60)

4.5 Energy saving operation (Pr. 60)

Without a fine parameter setting, the inverter automatically performs energy saving operation. This inverter is appropriate for fan and pump applications
Parameter
Number
Name
60 Energy saving control selection
Initial Value
0
Setting
Range
0 Normal operation mode
4 Energy saving operation mode
9 Optimum excitation control mode
Remarks

4.5.1 Energy saving operation mode (setting "4")

· When "4" is set in Pr. 60, the inverter operates in the energy saving operation mode.
· In the energy saving operation mode, the inverter automatically controls the output voltage to minimize the inverter output voltage during a constant operation.
REMARKS
· For applications a large load torque is applied to or machines repeat frequent acceleration/deceleration, an energy saving effect is not expected.

4.5.2 Optimum excitation control mode (setting "9")

· When "9" is set in Pr. 60, the inverter operates in the Optimum excitation control mode.
· The Optimum excitation control mode is a control method which controls excitation current to improve the motor efficiency to maximum and determines output voltage as an energy saving method.
REMARKS
· When the motor capacity is too small as compared to the inverter capacity or two or more motors are connected to one inverter, the energy saving effect is not expected.
CAUTION
· When the energy saving mode and Optimum excitation control mode are selected, deceleration time may be longer than
the setting value. Since overvoltage alarm tends to occur as compared to the constant-torque load characteristics, set a longer deceleration time.
· The energy saving mode and Optimum excitation control functions only under V/F control.
When a value other than "9999" is set in Pr. 80 Motor capacity (simple magnetic flux control), the energy saving mode and Optimum excitation control does not function.
(For Simple magnetic flux vector control, refer to the chapter 4 of the Instruction Manual (applied).)
POINT
When you want to check the energy saving effect, refer to the chapter 4 of the Instruction Manual (applied) to check the energy saving effect monitor.
4
ADJUSTMENT
69
Energy saving operation (Pr. 60)
Turn until (
appears
Turn to change it to the set
value " ".
Operation
1.Screen at powering on
The monitor display appears.
2.Press to choose the PU operation
mode.
3.Press to choose the parameter
setting mode.
4.
.
Pr. 60)
5.Press to read the present set value.
" "(initial value) appears.
6.
7.Press to set.
Flicker ··· Parameter setting complete!!
8. Perform normal operation.
When you want to check the energy saving effect, refer to the chapter 4 of the Instruction Manual (applied) to check the energy saving effect monitor.
Display
PU indication is lit.
The parameter number previously read appears.
· By turning , you can read another parameter.
· Press to show the setting again.
· Press twice to show the next parameter.
REMARKS
If the motor decelerates to stop, the deceleration time may be longer than the set time. Since overvoltage tends to occur as compared to the constant-torque characteristics, set a longer deceleration time.
70
Selection of the operation command and
frequency command locations (Pr. 79)

4.6 Selection of the operation command and frequency command locations (Pr. 79)

Select the start command location and frequency command location.
Parameter
Number
79
Name
Operation mode selection
Initial Val ue
0
Setting
Range
Use external/PU switchover mode (press to switch
between the PU and External operation mode. (Refer to
0
page 48)) At power on, the inverter is in the External operation mode.
1 Fixed to PU operation mode
Fixed to External operation mode
2
Operation can be performed by switching between the external and NET operation mode.
External/PU combined operation mode 1
Running frequency Start signal
PU (FR-DU07/FR-PU04/ FR-PU07) setting or
3
external signal input (multi­speed setting, across terminals 4-5 (valid when AU signal turns on)).
External/PU combined operation mode 2
Running frequency Start signal
4
External signal input (Terminal 2, 4, 1, JOG, multi-speed selection, etc.)
Description
External signal input (terminal STF, STR)
*1
Input from the PU (FR­DU07/FR-PU04/FR-PU07)
(, )
LED Indication
: Off : On
External operation mode
PU operation mode
External operation mode
NET operation mode
PU operation mode
Switchover mode
6
Switch among PU operation, external operating, and NET operation while keeping the same operating status.
External operation mode (PU operation interlock) X12 signal ON
Operation mode can be switched to the PU operation
7
*1 The priorities of the frequency commands when Pr. 79 = "3" are "Multi-speed operation (RL/RM/RH/REX) > PID control (X14) > terminal 4 analog
input (AU) > digital input from the operation panel".
*2 For the terminal used for the X12 signal (PU operation interlock signal) input, set "12" in Pr. 178 to Pr. 189 (input terminal function selection) to assign
functions.
For Pr. 178 to Pr. 189, refer to the chapter 4 of the Instruction Manual (applied). When the X12 signal is not assigned, function of the MRS signal switches from MRS (output stop) to PU operation interlock signal.
mode. (output stop during external operation)
X12 signal OFF
Operation mode can not be switched to the PU operation mode.
*2
*2
External operation mode
NET operation mode
PU operation mode
External operation mode
4
ADJUSTMENT
71
Parameter clear, all parameter clear
r

4.7 Parameter clear, all parameter clear

POINT
· Set "1" in Pr. CL parameter clear, ALLC All parameter clear to initialize parameters. (Parameters are not cleared when "1" is set in Pr. 77 Parameter write selection.)
· Refer to the parameter list on page 78 for parameters to be cleared with this operation.
Operation
1.
Screen at powering on
The monitor display appears.
2.
Press to choose the PU operation
mode.
3.
Press to choose the parameter
setting mode.
4.
Turn until " ", " "
appears.
5.
Press to read the currently set value.
" "(initial value) appears.
6.
Turn to change it to
the setting value " ".
7.
Press to set.
· Turn to read another parameter.
Display
PU indication is lit.
The parameter number read previously appears.
Parameter clear All parameter clear
Parameter clear
Flicker ··· Parameter setting complete!!
All parameter clea
· Press to show the setting again.
· Press twice to show the next parameter.
and are displayed alternately ... Why?
The inverter is not in the PU operation mode.
1. Press .
is lit and the monitor (4 digit LED) displays "0" (Pr. 79 = "0" (initial value)).
2. Carry out operation from step 6 again.
72
Parameter copy and parameter verification

4.8 Parameter copy and parameter verification

PCPY Setting Description
0 Cancel 1 Copy the source parameters to the operation panel. 2 Write the parameters copied to the operation panel into the destination inverter. 3 Verify parameters in the inverter and operation panel. (Refer to page 74.)
REMARKS
· When the copy destination inverter is not the FR-F700 series or parameter copy write is performed after parameter copy read is
stopped, "model error ( )" is displayed.
· Refer to the parameter list on
· When the power is turned off or an operation panel is disconnected, etc. during parameter copy write, perform write again or check the values by parameter verification.
page 78 and later for availability of parameter copy.
4.8.1

Parameter copy

Parameter settings can be copied to multiple inverters.
Operation
1.Connect the operation panel to the
copy source inverter.
Connect it during a stop.
2.Press to choose the parameter
setting mode.
3.Turn until (parameter copy)
appears.
4.Press to to read the present set value.
" "(initial value) appears.
5.Turn to change it to
the setting value " ".
6.Press to copy the source parameters
to the operation panel.
Display
The parameter number previously read appears.
The frequency flickers for about 30s
About 30s later
7.Connect the operation panel to the
copy source inverter.
8.After performing steps 2 to 5,
turn to change it to " ".
9.Press to write the parameters copied to
the operation panel to the destination inverter.
10.When copy is completed,
" " and " " flicker.
11.After writing the parameter values to the copy
destination inverter, always reset the inverter, e.g. switch power off once, before starting operation.
Flicker ··· Parameter copy complete!!
4
The frequency flickers for about 30s
ADJUSTMENT
Flicker ··· Parameter copy complete!!
73
Parameter copy and parameter verification
appears...Why? Parameter read error. Perform operation from step 3 again.
appears...Why? Parameter write error. Perform operation from step 8 again.
and flicker alternately
Appears when parameters are copied between the inverter of
1. Set "0" in Pr. 160 User group read selection.
2. Set the following setting (initial value) in Pr. 989 Parameter copy alarm release.
55K or less 75K or more
Pr. 989 Setting 10 100
3. Reset Pr. 9, Pr. 30, Pr. 51, Pr. 52, Pr. 54, Pr. 56, Pr. 57, Pr. 70, Pr. 72, Pr. 80, Pr. 90, Pr. 158, Pr. 190 to Pr. 196, Pr. 557, Pr. 893.
55K or less and 75K or more.

4.8.2 Parameter verification

Whether same parameter values are set in other inverters or not can be checked.
Operation
1.Move the operation panel to the
inverter to be verified.
Move it during a stop.
2.Screen at powering on
The monitor display appears.
3.Press to choose the parameter
setting mode.
4.Turn until (parameter copy)
appears.
5.Press to read the present set
value. " "(initial value) appears.
6.Turn to change it to the set value
" "(parameter copy verification mode).
7.Press to read the parameter setting
of the verified inverter to the operation panel.
Display
The parameter number read previously appears.
The frequency flickers for about 30s
If different parameters exist, different
parameter numbers and flicker.
Hold down to verify.
Flickering
8.If there is no difference, and
flicker to complete verification.
Flicker ··· Parameter verification complete!!
REMARKS
When the copy destination inverter is not the FR-F700 series, "model error ( )" is displayed.
flickers ... Why?
Set frequencies, etc. may be different. Check set frequencies.
74
Parameter list

4.9 Parameter list

4.9.1 List of parameters classified by the purpose

Set the parameters according to the operating conditions. The following list indicates purpose of use and corresponding parameters.
Purpose of Use Parameter Number
Manual torque boost Pr. 0, Pr. 46
Adjust the output torque of the motor (current)
Limit the output frequency
Set V/F pattern
Frequency setting with terminals (contact input)
Acceleration/deceleration time/pattern adjustment
Selection and protection of a motor
Motor brake and stop operation
Function assignment of external terminal and control
Monitor display and monitor output signal
Detection of output frequency and current
Simple magnetic flux vector control Pr. 80, Pr. 90
Slip compensation Pr. 245 to Pr. 247
Stall prevention operation
Maximum/minimum frequency Pr. 1, Pr. 2, Pr. 18
Avoid mechanical resonance points (frequency jump) Pr. 31 to Pr. 36
Base frequency, voltage Pr. 3, Pr. 19, Pr. 47
V/F pattern matching applications Pr. 14
Adjustable 5 points V/F Pr. 71, Pr. 100 to Pr. 109
Multi-speed setting operation
Jog operation Pr. 15, Pr. 16
Input compensation of multi-speed and remote setting Pr. 28
Remote setting function Pr. 59
Acceleration/deceleration time setting
Starting frequency Pr. 13, Pr. 571
Acceleration/deceleration pattern and backlash measures Pr. 29, Pr. 140 to Pr. 143
Regeneration avoidance functions at deceleration Pr. 882 to Pr. 886
Motor protection from overheat (electronic thermal relay function)
Use the constant-torque motor (applied motor) Pr. 71
DC injection brake Pr. 10 to Pr. 12
Selection of regeneration unit Pr. 30, Pr. 70
Selection of motor stopping method Pr. 250
Decelerate the motor to a stop at instantaneous power failure Pr. 261 to Pr. 266
Motor coasts to a stop when the output frequency from the inverter falls to the specified output frequency or lower.
Function assignment of input terminal Pr. 178 to Pr. 189
Start signal selection Pr. 250
Logic selection of output stop signal (MRS) Pr. 17
Selection of action conditions of the second function signal (RT) Pr. 155
Terminal assignment of output terminal Pr. 190 to Pr. 196
Detection of output frequency (SU, FU, FU2 signal) Pr. 41 to Pr. 43, Pr. 50
Detection of output current (Y12 signal) Detection of zero current (Y13 signal)
Remote output function (REM signal) Pr. 495 to Pr. 497
Pulse train output of output power (Y79 signal) Pr. 799
Speed display and speed setting Pr. 37, Pr. 144
Change of DU/PU monitor descriptions Cumulative monitor clear
Change of the monitor output from terminal FM and AM
Adjustment of terminal FM and AM (calibration) C0 (Pr. 900), C1 (Pr. 901)
Energy saving monitor Pr. 891 to Pr. 899
Detection of output frequency (SU, FU, FU2 signal) Pr. 41 to Pr. 43, Pr. 50
Detection of output current (Y12 signal) Detection of zero current (Y13 signal)
Pr. 22, Pr. 23, Pr. 48, Pr. 49, Pr. 66, Pr. 148, Pr. 149, Pr. 154, Pr. 156, Pr. 157
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to Pr. 239
Pr. 7, Pr. 8, Pr. 20, Pr. 21, Pr. 44, Pr. 45
Pr. 9, Pr. 51
Pr. 522
Pr. 150 to Pr. 153, Pr. 166, Pr. 167
Pr. 52, Pr. 170, Pr. 171, Pr. 563, Pr. 564, Pr. 891
Pr. 54 to Pr. 56, Pr. 158, Pr. 867
Pr. 150 to Pr. 153, Pr. 166, Pr. 167
4
ADJUSTMENT
75
Parameter list
Operation selection at power failure and instantaneous power failure
Operation setting at fault occurrence
Energy saving operation
Reduction of the motor noise Measures against noise and leakage currents
Frequency setting by analog input
Misoperation prevention and parameter setting restriction
Selection of operation mode and operation location
Communication operation and setting
Special operation and frequency control
Useful functions
Setting from the parameter unit and operation panel
Purpose of Use Parameter Number
Restart operation after instantaneous power failure/Flying start
Decelerate the motor to a stop at instantaneous power failure Pr. 261 to Pr. 266
Retry function at fault occurrence Pr. 65, Pr. 67 to Pr. 69
Output function of fault code Pr. 76
Input/output phase loss protection selection Pr. 251, Pr. 872
Regeneration avoidance function Pr. 882 to Pr. 886
Energy saving control selection Pr. 60
How much energy can be saved (energy saving monitor) Pr. 891 to Pr. 899
Carrier frequency and SoftPWM selection Pr. 72, Pr. 240, Pr. 260
Noise elimination at the analog input Pr. 74
Reduce mechanical resonance (speed smoothing control) Pr. 653, Pr. 654
Analog input selection Pr. 73, Pr. 267
Override function Pr. 73, Pr. 252, Pr. 253
Noise elimination at the analog input Pr. 74
Change of analog input frequency, adjustment of voltage, current input and frequency (calibration)
Compensation at the analog input Pr. 242, Pr. 243
Reset selection, disconnected PU detection Pr. 75
Prevention of parameter rewrite Pr. 77
Prevention of reverse rotation of the motor Pr. 78
Displays necessary parameters only. (user group) Pr. 160, Pr. 172 to Pr. 174
Control of parameter write by communication Pr. 342
Operation mode selection Pr. 79
Operation mode when power is on Pr. 79, Pr. 340
Operation command source and speed command source during communication operation
Selection of the NET mode operation control source Pr. 550
Selection of the PU mode operation control source Pr. 551
PU connector communication
Control of parameter write by communication Pr. 342
ModbusRTU communication specifications Pr. 343
Operation command source and speed command source during communication operation
Selection of the NET mode operation control source Pr. 550
ModbusRTU protocol (communication protocol selection) Pr. 549
PID control
Switch between the inverter operation and commercial power-supply operation to use
Free parameter Pr. 888, Pr. 889
Increase cooling fan life Pr. 244
To determine the maintenance time of parts. Pr. 255 to Pr. 259, Pr. 503, Pr. 504
How much energy can be saved (energy saving monitor) Pr. 60, Pr. 891 to Pr. 899
Parameter unit language switchover Pr. 145
Operation selection of the operation panel Pr. 161
Buzzer control of the operation panel Pr. 990
Contrast adjustment of the parameter unit Pr. 991
Pr. 57, Pr. 58, Pr. 162 to Pr. 165, Pr. 299, Pr. 611
Pr. 125, Pr. 126, Pr. 241, C2 to C7 (Pr. 902 to Pr. 905)
Pr. 338, Pr. 339
Pr. 117 to Pr. 124, Pr. 331 to Pr. 337, Pr. 341, Pr. 539
Pr. 338, Pr. 339
Pr. 127 to Pr. 134, Pr. 553, Pr. 554, Pr. 575 to Pr. 577, C42 (Pr. 934) to C45 (Pr.
935)
Pr. 135 to Pr. 139, Pr. 159
76

4.9.2 Display of the extended parameters

appears.
1. Screen at powering on
The monitor display appears.
Parameter list
DisplayOperation
2. Press to choose
the PU operation mode.
3. Press to choose the parameter
setting mode.
4. Tu
Pr. 160)
5. Press to read the currently set value.
" " (initial value) appears.
6. Turn to change it to the set value
" ".
7. Press to set.
· By turning , you can read another parameter.
· Press to show the setting again.
· Press twice to show the next parameter.
PU indication is lit.
The parameter number read previously appears.
Flicker ··· Parameter setting complete!!
After parameter setting is completed, press once to show the alarm history and press twice to return to the monitor display. To change settings of other parameters, perform the operation in above steps 3 to 7.
Error display?
If the operation panel does not have the write precedence
REMARKS
If the setting has not been changed, the value does not flicker and the next parameter number appears.
Pr. 160 Description
9999
(Initial Value)
0 Simple mode and extended mode parameters can be displayed.
1 Only the parameters registered in the user group can be displayed.
Only the simple mode parameters can be displayed.
4
ADJUSTMENT
77
Parameter list

4.9.3 Parameter list

indicates simple mode parameters.
Parameter
ion t
Func
Manual torque boost
frequency
Maximum/minimum
Base frequency, voltage
Multi-speed setting operation
Related
parameters
0
46
1
2
18
3
19
47
4
5
6
24
to
27
232
to
239
Name
Torque boost
Second torque boost
Maximum frequency
Minimum frequency
High speed maximum frequency
Base frequency
Base frequency voltage
Second V/F (base frequency)
Multi-speed setting (high speed)
Multi-speed setting (middle speed)
Multi-speed setting (low speed)
Multi-speed setting (4 speed to 7 speed)
Multi-speed setting (8 speed to 15 speed)
Para
meter
clear
All
para
meter
clear
Incre
ments
Initial Value
Range Description
Para
meter
copy
{: enabled
× : disabled
Set the output voltage at 0Hz as %.
0.1%
0.1% 9999
0.01Hz
0.01Hz 0Hz 0 to 120Hz Set the lower limit of the output frequency. {{{
0.01Hz
0.01Hz 60Hz 0 to 400Hz
0.01Hz 9999
0.01Hz 60Hz 0 to 400Hz Set frequency when the RT signal is on.
0.01Hz 30Hz 0 to 400Hz
0.01Hz 10Hz 0 to 400Hz
0.01Hz 9999
0.01Hz 9999
6/4/3/2/
1.5/1%
*1
120/
60Hz
120/
60Hz
0.1V 9999
0 to 30%
0 to 30%
9999 Without second torque boost
0 to 120Hz
*2
120 to 400Hz
*3
0 to 1000V Set the base voltage.
8888 95% of power supply voltage
9999 Same as power supply voltage
0 to 400Hz
9999 Second V/F is invalid
0 to 400Hz, 9999
0 to 400Hz, 9999
*1 Initial values differ according to the
inverter capacity. (0.75K
5.5K, 7.5K or more)
Set the torque boost when the RT signal is on.
Set the upper limit of the output frequency.
*2 The setting depends on the inverter
capacity. (55K or less/75k or more)
Set when performing the operation at 120Hz or more.
*3 The setting depends on the inverter
capacity. (55K or less/75k or more)
Set the frequency when the motor rated torque is generated. (50Hz/60Hz)
/ 11K to 37K / 45K, 55K / 75K
/ 1.5K to 3.7K /
{{{
{{{
{{{
{{{
{{{
{{{
Set the base frequency when the RT signal is on.
{{{
{{{
Set frequency when the RM signal is on. {{{
Set frequency when the RL signal is on. {{{
Frequency from 4 speed to 15 speed can be set according to the combination of the RH, RM, RL and REX signals. 9999: not selected
{{{
{{{
78
Parameter list
Motor protection
ion t
Func
Acceleration/deceleration time setting
from overheat
(electronic thermal
DC injection brake
Starting frequency
Parameter
7
8
9
relay function)
10
11
12
13
Name
Related
parameters
Acceleration time
Deceleration time
Acceleration/
20
deceleration reference frequency
Acceleration/
21
deceleration time increments
Second
44
acceleration/ deceleration time
Second
45
deceleration time
Electronic thermal
O/L relay
Second electronic
51
thermal O/L relay
DC injection brake operation frequency
DC injection brake operation time
DC injection brake operation voltage
Starting frequency
Holding time at a
571
start
Incre
ments
0.01s
0.01s
0.01Hz 60Hz 1 to 400Hz
0.01s
0.01s
0.01/
0.1A
0.01/
0.1A
0.01Hz 3Hz
0.1%
0.01Hz 0.5Hz 0 to 60Hz Starting frequency can be set.
Initial Value
0.1/
0.1/
10
0.1/
0.1/
*6
*7
0.1s 0.5s
0.1s 9999
5/15s
10/30s
*5
5s
9999
Rated
inverter
current
9999
4/2/1%
*8
*4
Range Description
0 to 3600/ 360s
0 to 3600/ 360s
0
1
0 to 3600/ 360s
0 to 3600/ 360s
9999 Acceleration time = deceleration time
0 to 500/ 0 to 3600A
*6
0 to 500A/ 0 to 3600
*7
9999 Second electronic thermal O/L relay invalid
0 to 120Hz
9999
0 DC injection brake disabled
0.1 to 10s
0 DC injection brake disabled
0.1 to 30%
0.0 to 10.0s
9999 Holding function at a start is invalid
Set the motor acceleration time.
*4 Initial values differ according to the inverter
capacity. (7.5K or less/11K or more)
Set the motor deceleration time.
*5 Initial values differ according to the inverter
capacity. (7.5K or less/11K or more)
Set the frequency referenced as acceleration/deceleration time. Set the frequency change time from stop to Pr. 20 for acceleration/deceleration time.
Increments: 0.1s Range: 0 to 3600s
Increments: 0.01s Range: 0 to 360s
Set the acceleration/deceleration time when the RT signal is on.
Set the deceleration time when the RT signal is on.
Set the rated motor current.
*6 The setting depends on the inverter
capacity (55K or less/75k or more)
Valid when the RT signal is on. Set the rated motor current.
A
*7 The setting depends on the inverter
capacity (55K or less/75k or more)
Set the operation frequency of the DC injection brake.
Operate when the output frequency becomes less than or equal to Pr.13 Starting frequency.
Set the operation time of the DC injection brake.
Set the DC injection brake voltage (torque).
*8 Initial values differ according to the
inverter capacity. (7.5K or less/11K to 55K/75K or more)
Set the holding time of Pr.13 Starting frequency.
Increments and setting range of acceleration/ deceleration time setting can be changed.
Para
meter
clear
All
para
meter
clear
Para
meter
copy
{: enabled
× : disabled
{{{
{{{
{{{
{{{
{{{
{{{
{{{
{{{
{{{
{{{
{{{
{{{
{{{
Parameter list
4
V/F pattern matching
applications
14
Load pattern selection
0 For constant-torque load
11
1 For reduced-torque load
{{{
ADJUSTMENT
79
Parameter list
Logic selection
ion t
Func
Jog operation
signal (MRS)
of output stop
Stall prevention operation
Parameter
Related
15
16
17
18 19
20,21
22
23
48
49
66
148
149
154
156
157
24 to 27
Name
parameters
Jog frequency
Jog acceleration/ deceleration time
MRS input selection
Refer to Pr.1 and Pr.2.
Refer to Pr.3.
Refer to Pr.7 and Pr.8.
Stall prevention operation level
Stall prevention operation level compensation factor at double speed
Second stall prevention operation current
Second stall prevention operation frequency
Stall prevention operation reduction starting frequency
Stall prevention level at 0V input
Stall prevention level at 10V input
Voltage reduction selection during stall prevention operation
Stall prevention operation selection
OL signal output timer
Refer to Pr. 4 to Pr. 6.
Incre
ments
0.01Hz 5Hz 0 to 400Hz Set the frequency for jog operation.
0.01s
0.1% 120%
0.1% 9999
0.1% 120%
0.01Hz 0Hz
0.01Hz 60Hz 0 to 400Hz
0.1% 120% 0 to 150%
0.1% 150% 0 to 150%
Initial Value
0.1/
0.1s 0s
0.5s
10
11
10
Range Description
Set the acceleration/deceleration time for jog operation. Set the time taken to reach
the frequency set in Pr.20 Acceleration/ 0 to 3600/ 360s
0 Open input always
2
0
0.1 to 150%
9999 Analog variable
0 to 200%
9999 Constant according to Pr. 22
0
0.1 to 150%
0 Second stall prevention operation invalid
0.01 to 400Hz
9999 Pr. 48 is valid when the RT signal is on.
0
1
0 to 31, 100, 101
0 to 25s
9999 Without the OL signal output
deceleration reference frequency for
acceleration/deceleration time. (Initial value
is 60Hz)
In addition, acceleration/deceleration time
can not be set separately.
Normally closed input (NC contact input
specifications)
Stall prevention operation selection
becomes invalid.
Set the current value at which stall
prevention operation is started.
The stall operation level can be reduced
when operating at a high speed above the
rated frequency.
Second stall prevention operation invalid
The stall prevention operation level can be
set.
Set the frequency at which stall prevention
operation of Pr. 48 is started.
Set the frequency at which the stall
operation level is started to reduce.
Stall prevention operation level can be
changed by the analog signal input to
terminal 1.
With voltage
reduction
Without voltage
reduction
Pr. 156 allows you to select whether to use
stall prevention or not according to the
acceleration/deceleration status.
Set the output start time of the OL signal
output when stall prevention is activated.
You can select whether to use output voltage reduction during stall prevention operation or not.
Para
meter
clear
All
para
meter
clear
Para
meter
copy
{: enabled
× : disabled
{{{
{{{
{{{
{{{
{{{
{{{
{{{
{{{
{{{
{{{
{{{
{{{
{{{
80
Parameter list
Input compensation
Acceleration/
ion t
Func
remote setting
of multi-speed and
deceleration
pattern and backlash measures
Selection of regeneration unit
Parameter
Related
28
29
140
141
142
143
30
70
Name
parameters
Multi-speed input compensation selection
Acceleration/ deceleration pattern selection
Backlash acceleration stopping frequency
Backlash acceleration stopping time
Backlash deceleration stopping frequency
Backlash deceleration stopping time
Regenerative function selection
Special regenerative brake duty
Para
meter
clear
All
para
meter
clear
Incre
ments
Initial Value
Range Description
Para
meter
copy
{: enabled
× : disabled
0 Without compensation
10
1 With compensation
0 Linear acceleration/ deceleration
1 S-pattern acceleration/deceleration A
10
0.01Hz 1Hz 0 to 400Hz
0.1s 0.5s 0 to 360s
0.01Hz 1Hz 0 to 400Hz {{{
0.1s 0.5s 0 to 360s
2 S-pattern acceleration/deceleration B
3 Backlash measures
6 Variable-torque acceleration/deceleration
Set the stopping frequency and time for backlash measures. Valid when Pr.29="3"
Inverter without regenerative function,
0
brake unit (FR-BU2, FR-BU, BU)
{{{
{{{
{{{
{{{
{{{
Brake unit (MT-BU5), power regeneration converter (MT-RC)
1
Setting is available for the models with 75K or more.
High power factor converter (FR-HC, MT-HC),
2
power regeneration common converter (FR-CV)
Inverter without regenerative
10
function, brake unit (FR-BU2,
10
FR-BU, BU)
Brake unit (MT-BU5) power regeneration converter (MT-RC)
11
Setting is available
DC feeding mode 1
,
(operated by DC feeding only)
{{{
for the models with 75K or higher.
Inverter without regenerative
20
function, brake unit (FR-BU2, FR-BU, BU)
Brake unit (MT-BU5) power regeneration converter (MT-RC)
21
Setting is available
DC feeding mode 2 (operated by
,
switching between AC and DC)
for the models with 75K or higher.
Set this parameter when a brake unit or
0.1% 0% 0 to 10%
power regeneration converter is used. Setting can be made for the 75K or
{{{
more.
Parameter list
4
ADJUSTMENT
81
Parameter list
ion t
Func
(frequency jump)
resonance points
Avoid mechanical
speed setting
Speed display and
(SU, FU, FU2 signal)
Detection of output frequency
Cumulative monitor clear
Change of DU/PU monitor descriptions
Parameter
Related
31
32
33
34
35
36
37
144
41
42
43
50
44, 45 46 47
48, 49 50 51
52
170
171
268
563
564
891
Name
parameters
Frequency jump 1A
Frequency jump 1B
Frequency jump 2A
Frequency jump 2B
Frequency jump 3A
Frequency jump 3B
Speed display
Speed setting switchover
Up-to-frequency sensitivity
Output frequency detection
Output frequency detection for reverse rotation
Second output frequency detection
Refer to Pr. 7 and Pr. 8.
Refer to Pr. 0.
Refer to Pr. 3.
Refer to Pr. 22 and Pr. 23.
Refer to Pr. 41 to Pr. 43.
Refer to Pr. 9.
DU/PU main display data selection
Watt-hour meter clear
Operation hour meter clear
Monitor decimal digits selection
Energization time carrying-over times
Operating time carrying-over times
Cumulative power monitor digit shifted times
Incre
ments
0.01Hz 9999
0.01Hz 9999
0.01Hz 9999
0.01Hz 9999
0.01Hz 9999
0.01Hz 9999
0.1% 10% 0 to 100% Set the level where the SU signal turns on.
0.01Hz 6Hz 0 to 400Hz
0.01Hz 9999
0.01Hz 30Hz 0 to 400Hz
Initial Value
10
14
10
1 9999
1 9999 0, 9999
1 9999
1 0 0 to 65535
1 0 0 to 65535
1 9999
Range Description
0 to 400Hz, 9999
0 to 400Hz, 9999
0 to 400Hz, 9999
0 to 400Hz, 9999
0 to 400Hz, 9999
0 to 400Hz, 9999
0 Frequency display, setting
1 to 9998 Set the machine speed at 60Hz.
0, 2, 4, 6, 8, 10, 102, 104, 106, 108, 110
0 to 400Hz
9999 Same as Pr.42 setting
0, 5, 6, 8 to 14, 17, 20, 23 to 25, 50 to 57, 100
0
10
9999
0 Displays the monitor as integral value.
1 Displays the monitor in increments of 0.1.
9999 No fixed decimal position
0 to 4
9999
1A to 1B, 2A to 2B, 3A to 3B is frequency jumps 9999: Function invalid
Set the number of motor poles when displaying the motor speed.
Set the frequency where the FU signal turns on.
Set the frequency where the FU signal turns on in reverse rotation.
Set the frequency where the FU2 signal turns on.
Select the monitor to be displayed on the operation panel and parameter unit. The setting value of "9" is available only for the 75K or more.
Set "0" to clear the watt-hour meter monitor.
Set the maximum value when monitoring from communication to 0 to 9999kWh.
Set the maximum value when monitoring from communication to 0 to 65535kWh.
Set "0" to clear the operation time monitor. Setting "9999" has no effect.
The numbers of cumulative energization time monitor exceeded 65535h is displayed. Reading only
The numbers of operation time monitor exceeded 65535h is displayed. Reading only
Set the number of times to shift the cumulative power monitor digit. Clamps the monitor value at maximum.
No shift Clears the monitor value when it exceeds the maximum value.
Para
meter
clear
All
para
meter
clear
Para
meter
copy
{: enabled
× : disabled
{{{
{{{
{{{
{{{
{{{
{{{
{{{
{{{
{{{
{{{
{{{
{{{
{{{
××{
×××
{{{
×××
×××
{{{
82
Parameter list
ion t
Func
output from terminal
Change of the monitor
Restart operation
after instantaneous
Parameter
54
55
56
FM and AM
57
58
power failure
Name
Related
parameters
FM terminal function selection
Frequency monitoring reference
Current monitoring reference
AM terminal
158
function selection
867
AM output filter
Restart coasting time
Restart cushion time
Automatic restart after instantaneous
162
power failure selection
First cushion time
163
for restart First cushion
164
voltage for restart Stall prevention
165
operation level for restart
Rotation direction
299
detection selection at restarting
Acceleration time at
611
a restart
Para
meter
clear
All
para
meter
clear
Incre
ments
Initial Value
Range Description
Para
meter
copy
{: enabled
× : disabled
Rated
1 to 3, 5, 6, 8 to 14, 17, 21, 24, 50, 52, 53
0 to 500/ 0 to 3600A
*9
1 to 3, 5, 6, 8 to 14, 17, 21, 24, 50, 52, 53
11
0.01Hz 60Hz 0 to 400Hz
0.01/ inverter
*9
0.1A
0.01s 0.01s 0 to 5s Set the output filter of terminal AM.
current
11
Select the monitor output to terminal FM. The setting value of "9" is available only for
75K or more.
the
Set the full-scale value to output the output frequency monitor value to terminal FM and AM.
Set the full-scale value to output the output current monitor value to terminal FM and AM.
*9 The setting depends on the inverter
capacity (55K or less/75K or more)
Select the monitor output to terminal AM. The setting value of "9" is available only for the 75K or more.
{{{
{{{
{{{
{{{
{{{
The coasting time is as follows:
1.5K or less................................... 0.5s,
0
2.2K to 7.5K.................................. 1.0s,
11K to 55K .................................... 3.0s,
0.1s 9999
0.1 to 5s/
0.1 to 30s
*10
9999 No restart
0.1s 1s 0 to 60s Set a voltage starting time at restart. {{{
0 With frequency search
10
0.1s 0s 0 to 20s
0.1% 0% 0 to 100%
0.1% 120% 0 to 150%
1 9999
0.1s 5/15s *11
1
10 Frequency search at every start
11 Reduced voltage at every start
0 Without rotation direction detection
1 With rotation direction detection
9999
0 to 3600s
9999
75K or more .................................. 5.0s
Set the waiting time for inverter-triggered restart after an instantaneous power failure.
*10 The setting depends on the inverter
capacity (55K or less/75k or more)
Without frequency search (reduced voltage system)
Set a voltage starting time at restart. Consider according to the magnitude of load (moment of inertia/torque).
Consider the rated inverter current as 100% and set the stall prevention operation level during restart operation.
When Pr. 78="0", the rotation direction is detected. When Pr. 78="1","2", the rotation direction is not detected.
Set the acceleration time to reach the
Pr. 20 Acceleration/ deceleration refe rence f requen cy at
a restart.
Acceleration time for restart is the normal acceleration time (e.g. Pr. 7).
*11 The setting
depends on the inverter capacity (55K or less/75k or more)
{{{
{{{
{{{
{{{
{{{
{{{
{{{
Parameter list
4
ADJUSTMENT
83
Parameter list
ion t
Func
Remote setting function
Energy saving
control selection
Retry function at alarm occurrence
torque motor
(applied motor)
Use the constant-
selection
and SoftPWM
Carrier frequency
Parameter
Related
59
60
65
67
68
69
66
67 to 69
70
71
72
240
260
Name
parameters
Remote function selection
Energy saving control selection
Retry selection
Number of retries at fault occurrence
Retry waiting time
Retry count display erase
Refer to Pr.22 and Pr.23.
Refer to Pr.65.
Refer to Pr.30.
Applied motor
PWM frequency selection
Soft-PWM operation selection
PWM frequency automatic switchover
Incre
ments
Initial Value
10
10
1 0 0 to 5 A fault for retry can be selected.
10
0.1s 1s 0 to 10s
100
10
12
11
11
Range Description
RH, RM, RL signal function
0
1
2 Not used
3
11
12 Not used
13
0 Normal operation mode
4 Energy saving operation mode
9 Optimum excitation control mode
0 No retry function
1 to 10
101 to 110
0 Thermal characteristics of a standard motor
1
2
20
0 to 15/ 0 to 6, 25
*12
0 Soft-PWM invalid
1
0
1
Multi-speed setting
Remote setting
Remote setting (These setting values enable deceleration to the frequency lower than the set frequency.)
Set the number of retries at fault occurrence. A fault output is not provided during retry operation.
Set the number of retries at fault occurrence. (The setting value - 100 is the number of retries.) A fault output is provided during retry operation.
Set the waiting time from when an inverter fault occurs until a retry is made.
Clear the number of restarts succeeded by retry.
Thermal characteristics of the Mitsubishi constant-torque motor
Thermal characteristic of standard motor Adjustable 5 points V/F
Mitsubishi standard motor (SF-JR 4P
1.5kW or less)
PWM carrier frequency can be changed. The setting displayed is in [kHz].
Note that 0 indicates 0.7kHz, 15 indicates 14.5kHz and 25 indicates
2.5kHz.
*12 The setting depends on the inverter
capacity (55K or less/75k or more)
When Pr. 72="0 to 5" ("0 to 4" for the 75K or more), Soft-PWM is valid.
PWM carrier frequency is constant independently of load. When the carrier frequency is set to 3kHz or more (Pr. 72 3), perform continuous operation at less than 85% of the rated inverter current.
Decreases PWM carrier frequency automatically when load increases.
Frequency setting storage function
Used
No (Turning STF/ STR off clears remotely-set frequency.)
Used
Not used (Turning STF/STR OFF clears remotely-set frequency.)
Para
meter
clear
All
para
meter
clear
Para
meter
copy
{: enabled
× : disabled
{{{
{{{
{{{
{{{
{{{
{{{
{{{
{{{
{{{
{{{
84
Parameter list
Reset selection,
ion t
Func
Analog input selection
Noise elimination
disconnected PU
at the analog input
detection
Parameter
Related
73
242
243
252
253
267
74
75
Name
parameters
Analog input selection
Terminal 1 added compensation amount (terminal 2)
Terminal 1 added compensation amount (terminal 4)
Override bias
Override gain
Terminal 4 input selection
Input filter time constant
Reset selection/ disconnected PU detection/PU stop selection
Incre
ments
0.1% 100% 0 to 100%
0.1% 75% 0 to 100%
0.1% 50% 0 to 200%
0.1% 150% 0 to 200%
Initial Value
11
10
1 1 0 to 8
114
Range Description
0 to 7, 10 to 17
0
1
2
0 to 3, 14 to 17
You can select the input specifications of terminal 2 (0 to 5V, 0 to 10V, 0 to 20mA) and input specifications of terminal 1 (0 to ±5V, 0 to ±10V). To change the terminal 2 to the voltage input specification (0 to 5V/ 0 to 10V), turn OFF(initial status) the voltage/current input switch 2. To change it to the current input(0 to 20mA), turn ON the voltage/current input switch 2. Override and reversible operation can be selected.
Set the ratio of added compensation amount when terminal 2 is the main speed.
Set the ratio of added compensation amount when terminal 4 is the main speed.
Set the bias side compensation value of override function.
Set the gain side compensation value of override function.
Turn ON the
Terminal 4 input 4 to 20mA
voltage/current input switch 1 (initial status).
Terminal 4 input 0 to 5V
Terminal 4 input 0 to 10V
The primary delay filter time constant for the analog input can be set. A larger setting results in slower response.
You can select the reset input acceptance, disconnected PU (FR-DU07
) connector detection function and
PU07
PU stop function. For the initial value, reset always enabled, without disconnected PU detection, and with PU stop function are set.
Turn OFF the voltage/current input switch 1.
/FR-PU04/FR-
Para
meter
clear
All
para
meter
clear
Para
meter
copy
{: enabled
× : disabled
{ × {
{{{
{{{
{{{
{{{
{ × {
{{{
{ ××
Parameter list
0 Without fault code output
76
of fault code
Output function
77
Prevention of
parameter rewrite
78
of the motor
Prevention of
reverse rotation
Fault code output selection
Parameter write selection
Reverse rotation prevention selection
10
2 Fault code output at fault occurrence only
0 Write is enabled only during a stop
10
10
1 Parameter write is disabled.
2
0 Both forward and reverse rotations allowed
2 Forward rotation disallowed
Parameter write is enabled in any operation mode regardless of operating status.
{{{1 With fault code output
{{{
{{{1 Reverse rotation disallowed
4
ADJUSTMENT
85
Parameter list
Simple magnetic
ion t
Func
Operation mode selection
control
flux vector
Adjustable 5 points V/F
Parameter
79
340
80
90
100
101
102
103
104
105
106
107
108
109
Name
Related
parameters
Operation mode selection
Communication startup mode selection
Motor capacity(Simple magnetic flux vector control)
Motor constant (R1)
V/F1(first frequency)
V/F1(first frequency voltage)
V/F2(second frequency)
V/F2(second frequency voltage)
V/F3(third frequency)
V/F3(third frequency voltage)
V/F4(fourth frequency)
V/F4(fourth frequency voltage)
V/F5(fifth frequency)
V/F5(fifth frequency voltage)
71
Refer to page 84.
Para
meter
clear
All
para
meter
clear
Incre
ments
Initial Value
Range Description
Para
meter
copy
{: enabled
× : disabled
0 External/PU switchover mode
1 Fixed to PU operation mode
2 Fixed to External operation mode
10
10
0.01kW/
0.1kW
*13
0.001Ω/
Ω
*
0.01m
0.01Hz 9999
0.1V 0V 0 to 1000V
0.01Hz 9999
0.1V 0V 0 to 1000V
0.01Hz 9999
0.1V 0V 0 to 1000V {{{
0.01Hz 9999
0.1V 0V 0 to 1000V
0.01Hz 9999
0.1V 0V 0 to 1000V
3 External/PU combined operation mode 1
4 External/PU combined operation mode 2
6 Switchover mode
7
0 As set in Pr.79.
1, 2
10, 12
0.4 to 55/ 0 to 3600kW
9999
*13
9999 V/F control is performed
0 to 50 0 to 400m
*14
9999
9999
0 to 400Hz, 9999
0 to 400Hz, 9999
0 to 400Hz, 9999
0 to 400Hz, 9999
0 to 400Hz, 9999
External operation mode (PU operation interlock)
Started in the network operation mode. When the setting is "2", it will resume the pre­instantaneous power failure operation mode after an instantaneous power failure occurs.
Started in the network operation mode. Operation mode can be changed between the PU operation mode and network operation mode from the operation panel. When the setting is "12", it will resume the pre­instantaneous power failure operation mode after an instantaneous power failure occurs.
To select the Simple magnetic flux vector control, set the capacity of the motor used.
*13 The setting depends on the inverter
capacity (55K or less/75k or more)
Used to set the motor primary resistance value.
Ω/
(Normally setting is not necessary.)
Ω
*14 The setting depends on the inverter
capacity (55K or less/75k or more)
Use the Mitsubishi motor (SF-JR, SF­HRCA) constants
Set each points (frequency, voltage) of V/F pattern. 9999: No V/F setting
{{{
{{{
{{{
{ × {
{{{
{{{
{{{
{{{
{{{
{{{
{{{
{{{
{{{
86
Parameter list
ion t
Func
PU connector communication
Parameter
117
118
119
120
121
122
123
124
342
551
Name
Related
parameters
PU communication station number
PU communication speed
PU communication stop bit length
PU communication parity check
Number of PU communication retries
PU communication check time interval
PU communication waiting time setting
PU communication CR/LF selection
Communication EEPROM write selection
PU mode operation command source selection
Incre
ments
Initial Value
1 0 0 to 31
1 192
11
12
11
0.1s 9999
1 9999
11
10
12
Range Description
Specify the inverter station number. Set the inverter station numbers when two or more inverters are connected to one personal computer.
Set the communication speed.
48, 96, 192, 384
0 1bit 8bit
1 2bit 8bit
10 1bit 7bit
11 2bit 7bit
0 Without parity check
2 With even parity check
0 to 10
9999
0 No PU connector communication
0.1 to 999.8s
9999 No communication check
0 to 150ms
9999 Set with communication data.
0 Without CR/LF
2 With CR/LF
0
1
1
2
The setting value × communication speed. For example, the communication speed is 19200bps when the setting value is "192".
Stop bit length data length
Set the permissible number of retries at occurrence of a data receive error. If the number of consecutive errors exceeds the permissible value, the inverter will come to trip.
If a communication error occurs, the inverter will not come to trip.
Set the communication check time interval. If a no-communication state persists for longer than the permissible time, the inverter will come to trip.
Set the waiting time between data transmission to the inverter and response.
Parameter values written by communication are written to the EEPROM and RAM.
Parameter values written by communication are written to the RAM.
Select the RS-485 terminals as the PU operation mode control source.
Select the PU connector as the PU operation mode control source.
100 equals the
Para
meter
clear
All
para
meter
clear
Para
meter
copy
{: enabled
× : disabled
{{{
{{{
{{{
{{{1 With odd parity check
{{{
{{{
{{{
{{{1 With CR
{{{
{{{
Parameter list
87
4
ADJUSTMENT
Parameter list
Parameter
ion t
Func
Change of analog input frequency,
adjustment of voltage, current input and frequency (calibration)
125
126
Name
Related
parameters
Terminal 2 frequency setting
gain frequency Terminal 4
frequency setting
gain frequency Analog input display
241
unit switchover Terminal 2
C2
frequency setting
(902)
bias frequency Terminal 2
C3
frequency setting
(902)
bias Terminal 2
C4
frequency setting
(903)
gain Terminal 4
C5
frequency setting
(904)
bias frequency Terminal 4
C6
frequency setting
(904)
bias Terminal 4
C7
frequency setting
(905)
gain
Incre
ments
0.01Hz 60Hz 0 to 400Hz
0.01Hz 60Hz 0 to 400Hz
0.01Hz 0Hz 0 to 400Hz
0.1% 0% 0 to 300%
0.1% 100% 0 to 300%
0.01Hz 0Hz 0 to 400Hz
0.1% 20% 0 to 300%
0.1% 100% 0 to 300%
Initial Value
10
0 Displayed in %
1 Displayed in V/mA
Range Description
Set the frequency of terminal 2 input gain (maximum).
Set the frequency of terminal 4 input gain (maximum).
Select the unit for analog input display.
Set the frequency on the bias side of terminal 2 input.
Set the converted % of the bias side voltage (current) of terminal 2 input.
Set the converted % of the gain side voltage of terminal 2 input.
Set the frequency on the bias side of terminal 4 input.
Set the converted % of the bias side current (voltage) of terminal 4 input.
Set the converted % of the gain side current (voltage) of terminal 4 input.
The parameter number in parentheses is the one for use with the parameter unit (FR-PU04/FR-PU07).
Para
meter
clear
All
para
meter
clear
Para
meter
copy
{: enabled
× : disabled
{ × {
{ × {
{{{
{ × {
{ × {
{ × {
{ × {
{ × {
{ × {
88
Parameter list
ion t
Func
PID control
Parameter
127
128
129
130
131
132
133
Name
Related
parameters
PID control automatic switchover frequency
PID action selection
PID proportional band
PID integral time
PID upper limit
PID lower limit
PID action set point
Incre
ments
0.01Hz 9999
0.1% 100%
0.1% 9999
0.1% 9999
0.01% 9999
Initial Value
110
0.1s 1s
Range Description
0 to 400Hz
9999 Without PID automatic switchover function
10, 110 PID reverse action
11, 111 PID forward action
20, 120 PID reverse action Measured value
21, 121 PID forward action
50 PID reverse action
51 PID forward action
60 PID reverse action
61 PID forward action
0.1 to 1000%
9999 No proportional control
0.1 to 3600s
9999 No integral control.
0 to 100%
9999 No function
0 to 100%
9999 No function
0 to 100% Used to set the set point for PID control.
9999 Terminal 2 input voltage is the set point.
Set the frequency at which the control is automatically changed to PID control.
Deviation value signal (terminal 1)
input (terminal 4) Set value (terminal 2 or Pr. 133)
Deviation value signal input
(LONW
ORKS
ORKS
, CC-Link
, CC-Link
communication)
Measured value, set value input
(LONW communication)
If the proportional band is narrow (parameter setting is small), the manipulated variable varies greatly with a slight change of the measured value. Hence, as the proportional band narrows, the response sensitivity (gain) improves but the stability deteriorates, e.g. hunting occurs. Gain K = 1/proportional band
When deviation step is input, time (Ti) is the time required for integral (I) action to provide the same manipulated variable as the proportional (P) action. As the integral time decreases, the set point is reached earlier but hunting occurs more easily.
Set the upper limit value. If the feedback value exceeds the setting, the FUP signal is output. The maximum input (20mA/5V/10V) of the measured value (terminal 4) is equivalent to 100%.
Set the lower limit value. If the measured value falls below the setting range, the FDN signal is output. The maximum input (20mA/5V/10V) of the measured value (terminal 4) is equivalent to 100%.
Para
meter
clear
All
para
meter
clear
Para
meter
copy
{: enabled
× : disabled
{{{
{{{
{{{
{{{
{{{
{{{
{{{
Parameter list
4
89
ADJUSTMENT
Parameter list
Parameter
ion t
Func
PID control
134
Name
Related
parameters
PID differential time
553
PID deviation limit
PID signal
554
operation selection
Output interruption
575
detection time
Output interruption
576
detection level Output interruption
577
cancel level
PID display bias
C42
(934)
coefficient
PID display bias
C43
(934)
analog value
PID display gain
C44
(935)
coefficient
PID display gain
C45
(935)
analog value
Incre
ments
0.01s 9999
0.1% 9999
0.01Hz 0Hz 0 to 400Hz
0.1% 1000%
0.1% 20%
0.1% 100%
Initial Value
10
0.1s 1s
0.01 9999
0.01 9999
Range Description
0.01 to
10.00s
9999 No differential control.
0 to 100.0%
9999 No function
0 to 3, 10 to 13
0 to 3600s
9999 Without output interruption function
900 to 1100%
0 to 500.00
9999 Displayed in %.
0 to 300.0%
0 to 500.00
9999 Displayed in %.
0 to 300.0%
For deviation lamp input, time (Td) required for providing only the manipulated variable for the proportional (P) action. As the differential time increases, greater response is made to a deviation change.
Y48 signal is output when the absolute value of deviation amount exceeds the deviation limit value.
Select the operation to be performed at the detection of upper, lower, and deviation limit for the measured value input. The operation for PID output suspension function can be selected.
If the output frequency after PID operation remains lower than the Pr. 576 setting for longer than the time set in Pr. 575, the inverter stops operation.
Set the frequency at which the output interruption processing is performed.
Set the level (Pr.577 - 1000%) to release the PID output interruption function.
Set the coefficient on bias side (minimum) of terminal 4 input.
Set the converted % on bias side (minimum) current /voltage of terminal 4 input.
Set the coefficient on gain side (maximum) of the terminal 4 input.
Set the converted % on gain side (maximum) of current/voltage of terminal 4 input.
The parameter number in parentheses is the one for use with the parameter unit (FR-PU04/FR-PU07).
Para
meter
clear
All
para
meter
clear
Para
meter
copy
{: enabled
× : disabled
{{{
{{{
{{{
{{{
{ × {
{ × {
{ × {
{ × {
90
Parameter list
Switch between the inverter operation and bypass operation to use
Parameter unit
ion t
Func
language switchover
Parameter
135
136
137
138
139
159
140
to
143
144
145
148,149
Name
Related
parameters
Electronic bypass sequence selection
MC switchover interlock time
Start waiting time
Bypass selection at a fault
Automatic switchover frequency from inverter to bypass operation
Automatic switchover frequency range from bypass to inverter operation
Refer to Pr.29.
Refer to Pr.37.
PU display language selection
Refer to Pr.22 and Pr.23.
Incre
ments
0.01Hz 9999
0.01Hz 9999
Initial Value
10
0.1s 1s 0 to 100s
0.1s 0.5s 0 to 100s
10
10
Range Description
0 Without electronic bypass sequence
1 With electronic bypass sequence
0
1
0 to 60Hz
9999 Without automatic switchover
0 to 10Hz
9999
0 Japanese
1 English
2 Germany
3 French
4 Spanish
5Italian
6Swedish
7 Finnish
Set the operation interlock time of MC2 and MC3.
Set the time slightly longer (0.3 to 0.5s or so) than the time from when the ON signal enters MC3 until it actually turns on.
Inverter output is stopped (motor coast) at inverter fault.
Operation is automatically switched to bypass operation at inverter fault (Not switched when an external thermal relay operation (E.OHT) or CPU fault (E.CPU) occurs)
Set the frequency to switch inverter operation to bypass operation.
Valid during automatic switchover operation (Pr.139 9999) When the frequency command decreases below (Pr.139 - Pr.159) after operation is switched from inverter operation to bypass operation, the inverter automatically switches operation to inverter operation and operates at the frequency of frequency command. When the inverter start command (STF/ STR) is turned off, operation is switched to inverter operation also.
Valid during automatic switchover operation (Pr.139 9999) When the inverter start command (STF/ STR) is turned off after operation is switched from inverter operation to bypass operation, operation is switched to inverter operation and the motor decelerates to stop.
Para
meter
clear
All
para
meter
clear
Para
meter
copy
{: enabled
× : disabled
{{{
{{{
{{{
{{{
{{{
{{{
{ ××
Parameter list
4
91
ADJUSTMENT
Parameter list
ion t
Func
Detection of zero current (Y13 signal)
Detection of output current (Y12 signal)
second function
conditions of the
Selection of action
Display of applied
parameters and user
Operation selection
of the operation panel
Parameter
150
151
152
153
154
155
156, 157
158 159
160
group function
161
Name
Related
parameters
Output current detection level
Output current detection signal delay time
Zero current detection level
Zero current detection time
Output current
166
detection signal retention time
Output current
167
detection operation selection
Refer to Pr.22 and Pr.23.
RT signal function validity condition selection
Refer to Pr.22 and Pr.23.
Refer to Pr.54 to Pr.56.
Refer to Pr.135 to Pr.139.
User group read
selection
User group
172
registered display/ batch clear
User group
173
registration
174
User group clear
Frequency setting/ key lock operation selection
Incre
ments
0.1% 120% 0 to 150%
0.1% 5% 0 to 150%
0.01s 0.5s 0 to 10s
Initial Value
0.1s 0s 0 to 10s
0.1s 0.1s
10
10
1 9999
10
1 9999
1 9999
10
Range Description
0 to 10s
9999
0
1 Fault stop (E.CDO) Operation continued
10 Operation continued Fault stop (E.CDO)
11 Fault stop (E.CDO) Fault stop (E.CDO)
0
10
9999
1
0
(0 to 16)
9999 Batch clear the user group registration
0 to 999, 9999
0 to 999, 9999
0
1
10
11
Set the output current detection level. 100% is the rated inverter current.
Set the output current detection period. Set the time from when the output current has risen above the setting until the output current detection signal (Y12) is output.
Set the zero current detection level. Suppose that the rated inverter current is 100%.
Set this parameter to define the period from when the output current drops below the Pr.152 value until the zero current detection signal (Y13) is output.
Set the retention time when the Y12 signal is on.
The Y12 signal on status is retained. The signal is turned off at the next start.
Y12 Signal - ON
Operation continued Operation continued
Second function is immediately valid with on of the RT signal.
Second function is valid only during the RT signal is on and constant speed operation. (Invalid during acceleration/deceleration)
Only the simple mode parameters can be displayed.
Only the parameters registered in the user group can be displayed.
Simple mode and extended mode parameters can be displayed.
Displays the number of cases registered as a user group (reading only).
Set the parameter numbers to be registered to the user group. Read value is always "9999".
Set the parameter numbers to be cleared from the user group. Read value is always "9999".
Setting dial frequency setting mode
Setting dial potentiometer mode
Setting dial frequency setting mode
Setting dial potentiometer mode
Y13 Signal - ON
Key lock invalid
Key lock valid
Para
meter
clear
All
para
meter
clear
Para
meter
copy
{: enabled
× : disabled
{{{
{{{
{{{
{{{
{{{
{{{
{{{
{{{
{ ××
{ ××
{ ××
{ × {
92
Parameter list
Function assignment of input terminal
ion t
Func
Parameter
Related
162 to 165 166, 167 168, 169 170, 171 172 to 174
178
179
180
181
182
183
184
185
186
187
188
189
Name
parameters
Incre
ments
Initial Value
Range Description
Refer to Pr.57 and Pr.58.
Refer to Pr.150 to Pr.153.
Parameter for manufacturer setting. Do not set.
Refer to Pr.52.
Refer to Pr.160.
0 to 8, 10 to
STF terminal function selection
STR terminal function selection
RL terminal function selection
RM terminal function selection
RH terminal function selection
RT terminal function selection
AU terminal function selection
JOG terminal function selection
CS terminal function selection
MRS terminal function selection
STOP terminal function selection
RES terminal function selection
160
161
10
11 { × {
12 { × {
13 { × {
14
15
16
124
125
162
12, 14, 16, 24, 25, 60, 62, 64 to 67, 70 to 72, 9999
0 to 8, 10 to 12, 14, 16, 24, 25, 61, 62, 64 to 67, 70 to 72, 9999
0 to 8, 10 to 12, 14, 16, 24, 25, 62, 64 to 67, 70 to 72, 9999
0 to 8, 10 to 12, 14, 16, 24, 25, 62 to 67, 70 to 72, 9999
0 to 8, 10 to 12, 14, 16, 24, 25, 62, 64 to 67, 70 to 72, 9999
0: Low-speed operation command (RL) 1: Middle-speed operation command (RM) 2: High-speed operation command (RH) 3: Second function selection (RT) 4: Terminal 4 input selection (AU) 5: Jog operation selection (JOG) 6: Selection of automatic restart after
instantaneous power failure (CS) 7: External thermal relay input (OH) 8: Fifteen speed selection (REX) 10: Inverter operation enable signal (FR-
HC, MT-HC, FR-CV connection) (X10) 11: FR-HC, MT-HC connection,
instantaneous power failure detection
(X11) 12: PU operation external interlock (X12) 14: PID control valid terminal (X14) 16: PU-external operation switchover (X16) 24: Output stop (MRS) 25: Start self-holding selection (STOP) 60: Forward rotation command (STF)
(assigned to STF terminal (Pr.178) only) 61: Reverse rotation command (STR)
(assigned to STR terminal (Pr.179) only) 62: Inverter reset (RES) 63: PTC thermistor input (PTC) (assigned
to AU terminal (Pr.184) only) 64: PID forward/reverse action switchover
(X64) 65: PU-NET operation switchover (X65) 66: External-NET operation switchover
(X66) 67: Command source switchover (X67) 70: DC feeding operation permission (X70) 71: DC feeding cancel (X71) 72: PID integral value reset (X72) 9999: No function
Para
Para
meter
meter
copy
clear
{: enabled
× : disabled
{ × {
{ × {
{ × {
{ × {
{ × {
{ × {
{ × {
{ × {
{ × {
All
para
meter
clear
Parameter list
93
4
ADJUSTMENT
Loading...