This Instruction Manual provides instructions for advanced use of the FR-D700 series inverters.
Incorrect handling might cause an unexpected fault. Before using the inverter, always read this instruction manual
and the Installation Guideline [IB-0600367ENG] packed with the product carefully to use the equipment to its
optimum performance.
1. Electric Shock Prevention
This section is specifically about safety matters
Do not attempt to install, operate, maintain or inspect the
inverter until you have read through the Instruction Manual
and appended documents carefully and can use the
equipment correctly. Do not use this product until you have
a full knowledge of the equipment, safety information and
instructions.
In this Instruction Manual, the safety instruction levels are
classified into "WARNING" and "CAUTION".
WARNING
CAUTION
Note that even the level may lead to a serious
consequence according to conditions. Please follow the
instructions of both levels because they are important to
personnel safety.
Assumes that incorrect handling may
cause hazardous conditions, resulting
in death or severe injury.
Assumes that incorrect handling may
cause hazardous conditions, resulting
in medium or slight injury, or may
cause physical damage only.
CAUTION
While power is on or
open the front cover. Otherwise you may get an electric
shock.
Do not run the inverter with the front cover or wiring cover
removed. Otherwise, you may access the exposed highvoltage terminals or the charging part of the circuitry and
get an electric shock.
Even if power is off, do not remove the front cover except
for wiring or periodic inspection. You may access the
charged inverter circuits and get an electric shock.
Before starting wiring or inspection, switch off power,
check to make sure that the operation panel indicator is
off, wait for at least 10 minutes after the power supply has
been switched off, and check that there are no residual
voltage using a tester or the like. The capacitor is charged
with high voltage for some time after power off and it is
dangerous.
This inverter must be earthed (grounded). Earthing
(grounding) must conform to the requirements of national
and local safety regulations and electrical code. (NEC
section 250, IEC 536 class 1 and other applicable
standards)
Use an neutral-point earthed (grounded) power supply for
400V class inverter in compliance with EN standard.
Any person who is involved in the wiring or inspection of
this equipment should be fully competent to do the work.
Always install the inverter before wiring. Otherwise, you
may get an electric shock or be injured.
Perform setting dial and key operations with dry hands to
prevent an electric shock. Otherwise you may get an
electric shock.
Do not subject the cables to scratches, excessive stress,
heavy loads or pinching. Otherwise, you may get an
electric shock.
Do not change the cooling fan while power is on. It is
dangerous to change the cooling fan while power is on.
Do not touch the printed circuit board with wet hands.
Otherwise, you may get an electric shock.
When measuring the main circuit capacitor capacity, the
DC voltage is applied to the motor for 1s at powering off.
Never touch the motor terminal, etc. right after powering
off to prevent an electric shock.
when the inverter is running, do not
2. Fire Prevention
CAUTION
Install the inverter on a nonflammable wall without holes
(so that nobody can touch the inverter heatsink on the rear
side, etc.). Mounting it to or near flammable material can
cause a fire.
If the inverter has become faulty, switch off the inverter
power. A continuous flow of large current could cause a
fire.
When using a brake resistor, make up a sequence that will
turn off power when an alarm signal is output. Otherwise,
the brake resistor may excessively overheat due to
damage of the brake transistor and such, causing a fire.
Do not connect a resistor directly to the DC terminals P/+
and N/-. This could cause a fire.
A-1
3.Injury Prevention
WARNING
CAUTION
Apply only the voltage specified in the instruction manual
to each terminal. Otherwise, burst, damage, etc. may
occur.
Ensure that the cables are connected to the correct
terminals. Otherwise, burst, damage, etc. may occur.
Always make sure that polarity is correct to prevent
damage, etc. Otherwise, burst, damage, etc. may occur.
While power is on or for some time after power-off, do not
touch the inverter as they will be extremely hot. Doing so
can cause burns.
4. Additional Instructions
Also note the following points to prevent an accidental failure,
injury, electric shock, etc.
(1) Transportation and mounting
CAUTION
Transport the product using the correct method that
corresponds to the weight. Failure to observe this could
lead to injuries.
Do not stack the inverter boxes higher than the number
recommended.
Ensure that installation position and material can
withstand the weight of the inverter. Install according to
the information in the instruction manual.
Do not install or operate the inverter if it is damaged or
has parts missing.
When carrying the inverter, do not hold it by the front
cover or setting dial; it may fall off or fail.
Do not stand or rest heavy objects on the product.
Check the inverter mounting orientation is correct.
Prevent other conductive bodies such as screws and
metal fragments or other flammable substance such as oil
from entering the inverter.
As the inverter is a precision instrument, do not drop or
subject it to impact.
Use the inverter under the following environmental
conditions: Otherwise, the inverter may be damaged.
Surrounding
air
temperature
Ambient
humidity
Storage
temperature
Atmosphere
Environment
Altitude/
vibration
∗1 Temperature applicable for a short time, e.g. in transit.
-10°C to +50°C (14°F to 122°F) (non-freezing)
90%RH maximum (non-condensing)
2
or less
(-4°F to 149°F)
-20°C to +65°C
Indoors (free from corrosive gas, flammable gas,
oil mist, dust and dirt)
Maximum 1000m (3280.80feet) above sea level for
standard operation. After that derate by 3% for
every extra 500m (1640.40feet) up to 2500m
(8202feet) (91%).
5.9m/s
*1
(2) Wiring
CAUTION
Do not install a power factor correction capacitor or surge
suppressor/capacitor type filter on the inverter output
side. These devices on the inverter output side may be
overheated or burn out.
The connection orientation of the output cables U, V, W to
the motor will affect the direction of rotation of the motor.
(3) Trial run
CAUTION
Before starting operation, confirm and adjust the
parameters. A failure to do so may cause some machines
to make unexpected motions.
(4) Usage
When you have chosen the retry function, stay away from
the equipment as it will restart suddenly after trip.
Since pressing key may not stop output depending
on the function setting status, provide a circuit and switch
separately to make an emergency stop (power off,
mechanical brake operation for emergency stop, etc).
Make sure that the start signal is off before resetting the
inverter alarm. A failure to do so may restart the motor
suddenly.
The load used should be a three-phase induction motor only.
Connection of any other electrical equipment to the
inverter output may damage the equipment.
Do not modify the equipment.
Do not perform parts removal which is not instructed in this
manual. Doing so may lead to fault or damage of the product.
CAUTION
The electronic thermal relay function does not guarantee
protection of the motor from overheating. It is recommended
to install both an external thermal and PTC thermistor for
overheat protection.
Do not use a magnetic contactor on the inverter input for
frequent starting/stopping of the inverter. Otherwise, the
life of the inverter decreases.
Use a noise filter to reduce the effect of electromagnetic
interference. Otherwise nearby electronic equipment may
be affected.
Take measures to suppress harmonics. Otherwise power
supply harmonics from the inverter may heat/damage the
power factor correction capacitor and generator.
When a 400V class motor is inverter-driven, please use an
insulation-enhanced motor or measures taken to
suppress surge voltages. Surge voltages attributable to
the wiring constants may occur at the motor terminals,
deteriorating the insulation of the motor.
When parameter clear or all parameter clear is performed,
reset the required parameters before starting operations.
Each parameter returns to the initial value.
The inverter can be easily set for high-speed operation.
Before changing its setting, fully examine the
performances of the motor and machine.
In addition to the inverter’s holding function, install a
holding device to ensure safety.
Before running an inverter which had been stored for a
long period, always perform inspection and test
operation.
For prevention of damage due to static electricity, touch
nearby metal before touching this product to eliminate
static electricity from your body.
A-2
(5) Emergency stop
CAUTION
Provide a safety backup such as an emergency brake
which will prevent the machine and equipment from
hazardous conditions if the inverter fails.
When the breaker on the inverter input side trips, check
for the wiring fault (short circuit), damage to internal parts
of the inverter, etc. Identify the cause of the trip, then
remove the cause and power on the breaker.
When any protective function is activated, take the
appropriate corrective action, then reset the inverter, and
resume operation.
(6) Maintenance, inspection and parts replacement
CAUTION
Do not carry out a megger (insulation resistance) test on
the control circuit of the inverter. It will cause a failure.
(7) Disposal
CAUTION
Treat as industrial waste.
General instruction
Many of the diagrams and drawings in this Instruction
Manual show the inverter without a cover, or partially open.
Never operate the inverter in this manner. Always replace
the cover and follow this Instruction Manual when operating
the inverter.
A-3
CONTENTS
1 OUTLINE1
1.1Product checking and parts identification......................................... 2
1.2Inverter and peripheral devices.......................................................... 3
This chapter explains the "OUTLINE" for use of this product.
Always read the instructions before using the equipment
1.1Product checking and parts identification ................................. 2
1.2Inverter and peripheral devices................................................... 3
1.3Removal and reinstallation of the cover..................................... 5
1.4Installation of the inverter and enclosure design ...................... 8
<Abbreviations>
PU .................................................. Operation panel and parameter unit (FR-PU04
Inverter ........................................... Mitsubishi inverter FR-D700 series
D700 ........................................ Mitsubishi inverter FR-D700 series
FR-
Pr.................................................... Parameter number
PU operation .................................. Operation using the PU (operation panel/FR-PU04/FR-PU07)
External operation .......................... Operation using the control circuit signals
Combined operation ....................... Operation using both the PU (operation panel/FR-PU04/FR-
PU07) and external operation
Operation panel for E500, PA02..... FR-E500 series operation panel (FR-PA02-02)
Mitsubishi standard motor .............. SF-JR
Mitsubishi constant-torque motor ... SF-HRCA
<Trademarks>
Microsoft and Visual C++ are registered trademarks of Microsoft Corporation in the United States
and/or other countries.
Company and product names herein are the trademarks and registered trademarks of their
respective owners.
<Mark>
/FR-PU07)
1
2
3
4
5
REMARKS :Additional helpful contents and relations with other functions are stated
NOTE:Contents requiring caution or cases when set functions are not
activated are stated.
POINT:Useful contents and points are stated.
Parameters referred to : related parameters are stated.
6
7
1
Product checking and parts identification
1.1Product checking and parts identification
Unpack the inverter and check the capacity plate on the front cover and the rating plate on the inverter side face to ensure that
the product agrees with your order and the inverter is intact.
Inverter type
--
FR
D740036
- NA
Symbol Voltage class
D720
D740
D720S
Operation panel
(Refer to page 52)
Voltage/current input switch
(Refer to page 20)
PU connector
(Refer to page 21)
Front cover
(Refer to page 5)
Three-phase 200V class
Three-phase 400V class
Single-phase 200V class
Displays the rated
current
Cooling fan
(Refer to page 267)
Control circuit terminal
block
(Refer to page 20)
Control logic switchover
jumper connector
(Refer to page 22)
Capacity plate
036 NA
Inverter type
Serial number
• Accessory
· Fan cover fixing screws (M3 × 35mm)
These screws are necessary for compliance with the European Directive
TypeNumber
FR-D720-070 to 165
FR-D740-036 to 080
FR-D720S-070, 100
FR-D720-120, 160
FR-D740-120, 160
1
2
Rating plate
Inverter type
Input rating
Output rating
Serial number
Main circuit
terminal block
(Refer to page 15)
Combed shaped
wiring cover
(Refer to page 7)
FR-D740-036-NA
(
Refer to Installation Guideline
)
2
1.2Inverter and peripheral devices
Inverter and peripheral devices
AC reactor (FR-HAL)
Three-phase AC power supply
Use within the permissible power supply
specifications of the inverter. To ensure
safety, use a moulded case circuit breaker,
earth leakage circuit breaker or magnetic
contactor to switch power ON/OFF.
(Refer to page 281)
Moulded case circuit breaker
(MCCB) or earth leakage circuit
breaker (ELB), fuse
The breaker must be selected carefully
since an in-rush current flows in the
inverter at power on.
(Refer to page 4)
Magnetic contactor (MC)
Install the magnetic contactor to ensure
safety. Do not use this magnetic contactor
to start and stop the inverter. Doing so will
cause the inverter life to be shorten.
(Refer to page 44)
Reactor (FR-HAL, FR-HEL option)
Reactors (option) must be used when
power harmonics measures are taken,
the power factor is to be improved or the
inverter is installed near a large power
supply system (500kVA or more). The
inverter may be damaged if you do not
use reactors. Select the reactor according
to the model. Remove the jumpers across
terminals P/+ and P1 to connect the DC reactor.
DC reactor (FR-HEL)
Noise filter
(FR-BSF01, FR-BLF)
Install a noise filter to reduce
the electromagnetic noise
generated from the inverter.
Effective in the range from
about 1MHz to 10MHz. When
more wires are passed
through, a more effective result
can be obtained. A wire should
be wound four turns or more.
P/+
P1
Parameter unit (FR-PU07)
By connecting the connection cable
(FR-CB2) to the PU connector,
operation can be performed from
FR-PU07.
(Refer to page 29)
Inverter (FR-D700)
Capacitor type
filter
(FR-BIF)
Reduces the
radio noise.
RS-485 RS-232C
R/L1 S/L2T/L3
Converter
Earth (Ground)
N/-
P/+
P/+
PR
UW
V
RS-232C - RS-485 converter is
required when connecting to PC
with RS-232C interface.
(Refer to page 180)
S1
S2
SC
Brake resistor (FR-ABR,
MRS type, MYS type)
Braking capability can be
improved.
(FR-D720-025 or more,
FR-D740-012 or more,
FR-D720S-025 or more)
(Refer to page 31)
Noise filter
(FR-BSF01, FR-BLF)
Install a noise filter to reduce the
electromagnetic noise generated
from the inverter.
Effective in the range from about
1MHz to 10MHz. A wire should be
wound four turns at a maximum.
Safety relay module
Required for
compliance with
safety standard.
Motor
1
OUTLINE
Brake unit
(FR-BU2)
Earth (Ground)
High power factor
converter (FR-HC)
Power supply harmonics
can be greatly suppressed.
Install this as required.
Power regeneration
common converter
(FR-CV)
Great braking capability
is obtained.
Install this as required.
PR
P/+
P/+
PR
Resistor unit (FR-BR)
Discharging resistor (GZG, GRZG)
The regenerative braking capability
of the inverter can be exhibited fully.
Install this as required.
Devices connected to the output
Do not install a power factor correction capacitor,
surge suppressor or capacitor type filter on the output
side of the inverter. When installing a moulded case
circuit breaker on the output side of the inverter,
contact each manufacturer for selection of the
moulded case circuit breaker.
Earth (Ground)
To prevent an electric shock, always earth (ground)
the motor and inverter. For reduction of induction noise
from the power line of the inverter, it is recommended
to wire the earth (ground) cable by returning it to the
earth (ground) terminal of the inverter.
NOTE
The life of the inverter is influenced by surrounding air temperature. The surrounding air temperature should be as low as
possible within the permissible range. This must be noted especially when the inverter is installed in an enclosure.
Wrong wiring might lead to damage of the inverter. The control signal lines must be kept fully away from the main
circuit to protect them from noise. (Refer to page 14)
Do not install a power factor correction capacitor, surge suppressor or capacitor type filter on the inverter output
side. This will cause the inverter to trip or the capacitor and surge suppressor to be damaged. If any of the above
devices are connected, immediately remove them.
Electromagnetic wave interference
The input/output (main circuit) of the inverter includes high frequency components, which may interfere with the
communication devices (such as AM radios) used near the inverter. In this case, install the FR-BIF optional capacitor type
filter (for use in the input side only) or FR-BSF01 or FR-BLF common mode filter to minimize interference.
Refer to the instruction manual of each option and peripheral devices for details of peripheral devices.
(
Refer to page 8
(Refer to page 40).
)
3
Inverter and peripheral devices
1.2.1Peripheral devices
Check the inverter type of the inverter you purchased. Appropriate peripheral devices must be selected according to the
capacity.
Refer to the following list and prepare appropriate peripheral devices:
∗1 Select an MCCB according to the power supply capacity.
Install one MCCB per inverter.
∗2 For installations in the United States or Canada, use the class T type fuse certified by the UL and cUL.
∗3 Magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the magnetic contactor is
used for emergency stop during motor driving, the electrical durability is 25 times.
When using the MC for emergency stop during motor driving or using on the motor side during commercial-power supply operation, select the MC with class
AC-3 rated current for the motor rated current.
MCCBINV
MCCBINV
IM
IM
NOTE
When the inverter capacity is larger than the motor capacity, select an MCCB and a magnetic contactor according to the inverter type
and cable and reactor according to the motor output.
When the breaker on the inverter primary side trips, check for the wiring fault (short circuit), damage to internal parts of the inverter,
etc. Identify the cause of the trip, then remove the cause and power on the breaker.
4
Removal and reinstallation of the cover
1.3Removal and reinstallation of the cover
1.3.1Front cover
FR-D720-165 or less
FR-D740-080 or less
FR-D720S-008 to 100
Removal (Example of FR-D740-036)
1) Loosen the installation screws of the front cover. (The screws cannot be removed.)
2) Remove the front cover by pulling it like the direction of arrow.
1)
Installation screw
Reinstallation (Example of FR-D740-036)
1) Place the front cover in front of the inverter, and install it straight.
2) Tighten the installation screws on the front cover.
1)2)
2)
1
OUTLINE
Installation screw
5
Removal and reinstallation of the cover
FR-D720-238, 318 and FR-D740-120, 160
Removal (Example of FR-D740-160)
1) Loosen the installation screws of the front cover. (The screws cannot be removed.)
2) Remove the front cover by pulling it like the direction of arrow with holding the installation hook on the front cover.
Installation hook
1)2)
Installation
screw
Reinstallation (Example of FR-D740-160)
1) Insert the two fixed hooks on the lower side of the front cover into the sockets of the inverter.
2) Tighten the installation screws on the front cover.
1)2)
Installation screw
Fixed hook
Socket of the inverter
NOTE
Fully make sure that the front cover has been reinstalled securely.
The same serial number is printed on the capacity plate of the front cover and the rating plate of the inverter. Since
these plates have the same serial numbers, always reinstall the removed cover onto the original inverter.
6
1.3.2Wiring cover
r
r
r
Removal and reinstallation
FR-D720-165 or less and FR-D740-080 or less and FR-D720S-008 to 100
Hold the side of the wiring cover, and pull it downward for
removal.
To reinstall, fit the cover to the inverter along the guides.
Guide
Wiring cover
Example of FR-D740-036
Removal and reinstallation of the cover
Also pull the wiring cover downward with holding a
frontal part of the wiring cover.
Wiring cove
Example of FR-D740-036
See below diagram for wiring cover of FR-D720-165.
Hold the dent of the wiring cover (marked with an
arrow) with thumb and the side with other fingers and
pull downward for removal.
1
Wiring cove
FR-D720-238, 318 and FR-D740-120, 160
The cover can be removed easily by pulling it toward you.
To reinstall, fit the cover to the inverter along the guides.
Guide
OUTLINE
Guide
Wiring cove
Example of FR-D740-160
7
Installation of the inverter and enclosure design
1.4Installation of the inverter and enclosure design
When an inverter panel is to be designed and manufactured, heat generated by contained equipment, etc., the environment of
an operating place, and others must be fully considered to determine the panel structure, size and equipment layout. The
inverter unit uses many semiconductor devices. To ensure higher reliability and long period of operation, operate the inverter
in the ambient environment that completely satisfies the equipment specifications.
1.4.1Inverter installation environment
As the inverter installation environment should satisfy the standard specifications indicated in the following table, operation in
any place that does not meet these conditions not only deteriorates the performance and life of the inverter, but also causes a
failure. Refer to the following points and take adequate measures.
Environmental standard specifications of inverter
ItemDescription
Surrounding air
temperature
Ambient humidity90%RH maximum (non-condensing)
AtmosphereFree from corrosive and explosive gases, free from dust and dirt
Maximum altitude1,000m (3280.80 feet) or less
Vibration
-10 to +50
5.9m/s
(1) Temperature
The permissible surrounding air temperature of the inverter is between -10 and +50°C
inverter within this temperature range. Operation outside this range will considerably shorten the service lives of the
semiconductors, parts, capacitors and others. Take the following measures so that the surrounding air temperature of the
inverter falls within the specified range.
1) Measures against high temperature
Use a forced ventilation system or similar cooling system. (Refer to page 10)
Install the panel in an air-conditioned electrical chamber.
Block direct sunlight.
Provide a shield or similar plate to avoid direct exposure to the radiated heat and wind of a heat source.
Ventilate the area around the panel well.
°C (14°F to 122°F)(non-freezing)
2
or less
(14°F to 122°F). Always operate the
2) Measures against low temperature
Provide a space heater in the enclosure.
Do not power off the inverter. (Keep the start signal of the inverter off.)
3) Sudden temperature changes
Select an installation place where temperature does not change suddenly.
Avoid installing the inverter near the air outlet of an air conditioner.
If temperature changes are caused by opening/closing of a door, install the inverter away from the door.
(2) Humidity
Normally operate the inverter within the 45 to 90% range of the ambient humidity. Too high humidity will pose problems of
reduced insulation and metal corrosion. On the other hand, too low humidity may produce a spatial electrical breakdown. The
insulation distance specified in JEM1103 "Control Equipment Insulator" is defined as humidity 45 to 85%.
1) Measures against high humidity
Make the panel enclosed, and provide it with a hygroscopic agent.
Take dry air into the enclosure from outside.
Provide a space heater in the enclosure.
2) Measures against low humidity
What is important in fitting or inspection of the unit in this status is to discharge your body (static electricity)
beforehand and keep your body from contact with the parts and patterns, besides blowing air of proper humidity into
the enclosure from outside.
3) Measures against condensation
Condensation may occur if frequent operation stops change the in-enclosure temperature suddenly or if the outside-
air temperature changes suddenly.
Condensation causes such faults as reduced insulation and corrosion.
Take the measures against high humidity in 1).
Do not power off the inverter. (Keep the start signal of the inverter off.)
8
Installation of the inverter and enclosure design
(3) Dust, dirt, oil mist
Dust and dirt will cause such faults as poor contact of contact points, reduced insulation or reduced cooling effect due to
moisture absorption of accumulated dust and dirt, and in-enclosure temperature rise due to clogged filter. In the atmosphere
where conductive powder floats, dust and dirt will cause such faults as malfunction, deteriorated insulation and short circuit in
a short time.
Since oil mist will cause similar conditions, it is necessary to take adequate measures.
Countermeasures
Place in a totally enclosed enclosure.
Take measures if the in-enclosure temperature rises. (Refer to page 10)
Purge air.
Pump clean air from outside to make the in-enclosure pressure higher than the outside-air pressure.
(4) Corrosive gas, salt damage
If the inverter is exposed to corrosive gas or to salt near a beach, the printed board patterns and parts will corrode or the
relays and switches will result in poor contact.
In such places, take the measures given in Section 3.
(5) Explosive, flammable gases
As the inverter is non-explosion proof, it must be contained in an explosion proof enclosure. In places where explosion may be
caused by explosive gas, dust or dirt, an enclosure cannot be used unless it structurally complies with the guidelines and has
passed the specified tests. This makes the enclosure itself expensive (including the test charges). The best way is to avoid
installation in such places and install the inverter in a non-hazardous place.
(6) Highland
Use the inverter at the altitude of within 1000m (3280.80 feet). If it is used at a higher place, it is likely that thin air will reduce
the cooling effect and low air pressure will deteriorate dielectric strength.
Maximum 1000m (3280.80feet) above sea level for standard operation. After that derate by 3% for every extra 500m
(1640.40feet) up to 2500m (8202feet) (91%).
(7) Vibration, impact
The vibration resistance of the inverter is up to 5.9m/s2 at 10 to 55Hz frequency and 1mm amplitude. Vibration or impact, if
less than the specified value, applied for a long time may make the mechanism loose or cause poor contact to the connectors.
Especially when impact is imposed repeatedly, caution must be taken as the part pins are likely to break.
Countermeasures
Provide the panel with rubber vibration isolators.
Strengthen the structure to prevent the enclosure from resonance.
Install the enclosure away from sources of vibration.
1
OUTLINE
9
Installation of the inverter and enclosure design
1.4.2Cooling system types for inverter enclosure
From the enclosure that contains the inverter, the heat of the inverter and other equipment (transformers, lamps, resistors,
etc.) and the incoming heat such as direct sunlight must be dissipated to keep the in-enclosure temperature lower than the
permissible temperatures of the in-panel equipment including the inverter.
The cooling systems are classified as follows in terms of the cooling calculation method.
1) Cooling by natural heat dissipation from the enclosure surface (totally enclosed type)
2) Cooling by heat sink (aluminum fin, etc.)
3) Cooling by ventilation (forced ventilation type, pipe ventilation type)
4) Cooling by heat exchanger or cooler (heat pipe, cooler, etc.)
Cooling SystemEnclosure StructureComment
Natural
cooling
Forced
cooling
Natural ventilation
(enclosed, open type)
Natural ventilation
(totally enclosed type)
Heatsink cooling
Forced ventilation
Heat pipeTotally enclosed type for enclosure downsizing.
Heatsink
INV
INV
INV
INV
Heat pipe
INV
Low in cost and generally used, but the enclosure size
increases as the inverter capacity increases. For relatively
small capacities.
Being a totally enclosed type, the most appropriate for hostile
environment having dust, dirt, oil mist, etc. The enclosure size
increases depending on the inverter capacity.
Having restrictions on the heatsink mounting position and
area, and designed for relative small capacities.
For general indoor installation. Appropriate for enclosure
downsizing and cost reduction, and often used.
10
Installation of the inverter and enclosure design
1.4.3Inverter placement
(1)Installation of the inverter
Enclosure surface mounting
Remove the front cover and wiring cover to fix the inverter to the surface.
FR-D720-008 to 042
FR-D720S-008 to 042
Front cover
FR-D720-070 or more
FR-D740-012 or more
FR-D720S-070, 100
Front cover
Wiring cover
Wiring cover
NOTE
When encasing multiple inverters, install them in parallel as a
cooling measure.
Install the inverter vertically.
Refer to the clearances below.
Vertical
(2) Clearances around inverter
To ensure ease of heat dissipation and maintenance, leave at least the shown clearances around the inverter. At least the
following clearances are required under the inverter as a wiring space, and above the inverter as a heat dissipation space.
Surrounding air temperature and humidity
Measurement
position
5cm
(1.97inches)
Measurement
Inverter
position
5cm
(1.97inches)
5cm (1.97inches)
Temperature: -10 C to +50 C
(14 F to 122 F)
Humidity: 90% RH maximum
Leave enough clearances and take
cooling measures.
Clearances (front)
10cm
(3.94inches)
1cm
(0.39inches)
* When using the inverters at the surrounding air
temperature of 40 C (
be installed without any clearance between them
0inch)
(0cm (
When surrounding air temperature exceeds 40 C
104 F)
, clearances between the inverters should be
(
(0.39inches)
1cm
for the FR-D720-238 or more and FR-D740-120 or
more).
or more*
clearance).
or more (5cm
or more
1cm
(0.39inches)
or more*
10cm
(3.94inches)
or more
104 F)
or less, the inverters can
(1.97inches)
or more
Clearances (side)
1cm
(0.39
Inverter
inches)
or more
*
* 5cm
(1.97inches)
the FR-D720-238 or more
and FR-D740-120 or more
or more for
1
OUTLINE
(3) Inverter mounting orientation
Mount the inverter on a wall as specified. Do not mount it horizontally or any other way.
(4) Above inverter
Heat is blown up from inside the inverter by the small fan built in the unit. Any equipment placed above the inverter should be
heat resistant.
11
Installation of the inverter and enclosure design
(5) Arrangement of multiple inverters
When multiple inverters are placed in the same
enclosure, generally arrange them horizontally as shown
in the right figure (a). When it is inevitable to arrange
them vertically to minimize space, take such measures as
to provide guides since heat from the bottom inverters
can increase the temperatures in the top inverters,
causing inverter failures.
When mounting multiple inverters, fully take caution not
to make the surrounding air temperature of the inverter
higher than the permissible value by providing ventilation
and increasing the enclosure size.
(6) Arrangement of ventilation fan and inverter
Heat generated in the inverter is blown up from the bottom of
the unit as warm air by the cooling fan. When installing a
ventilation fan for that heat, determine the place of ventilation
fan installation after fully considering an air flow. (Air passes
through areas of low resistance. Make an airway and airflow
plates to expose the inverter to cool air.)
(a) Horizontal arrangement
InverterInverter
EnclosureEnclosure
Arrangement of multiple inverters
InverterInverter
Inverter
GuideGuide
Inverter
Inverter
Inverter
(b) Vertical arrangement
Guide
<Good example><Bad example>
Arrangement of ventilation fan and inverter
12
2 WIRING
This chapter describes the basic "WIRING" for use of this
product.
Always read the instructions before using the equipment
2.4Connection of stand-alone option unit ....................................... 31
1
2
3
4
5
13
6
7
Wiring
2.1Wiring
2.1.1Terminal connection diagram
Sink logic
Main circuit terminal
Control circuit terminal
Single-phase power input
MCCBMC
Single-phase
AC power
supply
MCCBMC
Three-phase
AC power
supply
Earth
(Ground)
Control input signals (No voltage input allowed)
Terminal functions vary
with the input terminal
assignment (Pr. 178 to Pr. 182)
Multi-speed selection
*2 When using terminals PC-
SD as a 24VDC power
supply, take care not to
short across terminals
PC-SD.
(Common for external power supply transistor)
Forward
rotation start
Reverse
rotation start
High
speed
Middle
speed
Low
speed
Contact input common
24VDC power supply
R/L1
S/L2
*1. DC reactor (FR-HEL)
When connecting a DC reactor, remove the
jumper across P1-P/+
Earth
(Ground)
Jumper
R/L1
S/L2
T/L3
*1
P1P/+
Inrush current
limit circuit
R
*7
PR
*6
Main circuit
Control circuit
STF
STR
RH
RM
PC
RL
SD
*2
SOURCE
SINK
24V
N/-
Brake unit
(Option)
C
B
A
RUN
SE
*6 A brake transistor is not built-in to the
FR-D720-008, 014 and FR-D720S-008,
014.
*7 Brake resistor (FR-ABR, MRS type, MYS
type)
Install a thermal relay to prevent an
overheat and burnout of the brake resistor.
(The brake resistor can not be connected
to the FR-D720-008, 014 and FR-D720S008, 014.)
U
V
W
Relay output
Terminal functions vary
Relay output
(Fault output)
by Pr. 192 A,B,C terminal
function selection
Open collector output
Terminal functions vary by
Running
Pr. 190 RUN terminal function
selection
Open collector output common
Sink/source common
Motor
IM
Earth (Ground)
Frequency setting signals (Analog)
*3 Terminal input specifications
can be changed by analog
input specifications
switchover (Pr. 73).
Terminal 10 and terminal 2
are used as PTC input
terminal (Pr. 561).
*4 Terminal input
specifications can be
changed by analog input
specifications switchover
(Pr. 267). Set the
voltage/current input
switch in the "V" position
to select voltage input (0
to 5V/0 to10V) and "I"
(initial value) to select
current input (4 to 20mA).
*5 It is recommended to use 2W1kΩ
when the frequency setting signal
is changed frequently.
Frequency
setting
potentiometer
1/2W1kΩ
Safety stop signal
Output shutoff (Line 1)
Output shutoff (Line 2)
Common terminal
*5
Terminal 4
input
(Current
input)
3
2
1
(+)
(-)
Shorting
10(+5V)
2 0 to 5VDC
5(Analog common)
4 4 to 20mADC
VI
Voltage/current
input switch
S1
wire
S2
SC
(0 to 10VDC)
0 to 5VDC
0 to 10VDC
Output shutoff
circuit
*3
AM
5
(+)
Analog signal output
(-)
PU
connector
*4
*4
SO
Safety monitor output *8
For manufacturer setting
*8 Common terminal of
terminal SO is terminal SC. (Connected to terminal SD inside of the inverter.)
NOTE
To prevent a malfunction caused by noise, separate the signal cables more than 10cm (3.94inches) from the power
cables. Also separate the main circuit wire of the input side and the output side.
After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean. When drilling mounting holes
in an enclosure etc., take care not to allow chips and other foreign matter to enter the inverter.
The output of the single-phase power input specification is three-phase 200V.
(0 to 10VDC)
14
Main circuit terminal specifications
r
2.2Main circuit terminal specifications
2.2.1Specification of main circuit terminal
Ter mina l
Symbol
R/L1,
S/L2,
T/L3 *
U, V, WInverter outputConnect a three-phase squirrel-cage motor.
P/+, PRBrake resistor connection
P/+, N/-Brake unit connection
P/+, P1DC reactor connectionRemove the jumper across terminals P/+ and P1 and connect a DC reactor.
* When using single-phase power input, terminals are R/L1 and S/L2.
AC power input
Earth (Ground)For earthing (grounding) the inverter chassis. Must be earthed (grounded).
Terminal NameDescription
Connect to the commercial power supply.
Keep these terminals open when using the high power factor converter (FR-HC) or
power regeneration common converter (FR-CV).
Connect a brake resistor (FR-ABR, MRS type, MYS type) across terminals P/+ and PR.
(The brake resistor can not be connected to the FR-D720-008 and 014 and FR-
D720S-008 and 014.)
Connect the brake unit (FR-BU2), power regeneration common converter (FR-CV)
or high power factor converter (FR-HC).
2.2.2Terminal arrangement of the main circuit terminal, power supply and the motor
wiring
Three-phase 200V class
FR-D720-008 to 042FR-D720-070 to 165
Screw size (M3.5)
N/-
R/L1 S/L2 T/L3
Jumpe
N/-
P/+PR
PR
P/+
R/L1 S/L2 T/L3
Jumper
Screw size (M4)
2
Screw size
(M4)
IM
Motor
FR-D720-238, 318
Screw size (M5)
N/-
Jumper
P/+ PR
Screw size
(M3.5)
R/L1 S/L2 T/L3
MotorPower supply
IM
Power supply
Screw size (M5)
IM
Power supply Motor
* For wiring to earth (ground) terminals of FR-D720-238 and 318, use the earthing cable wiring space (marked with an arrow) to route the wires.
WIRING
15
Main circuit terminal specifications
r
Three-phase 400V class
FR-D740-012 to 080FR-D740-120, 160
N/-
P/+
R/L1 S/L2 T/L3
Jumper
Screw size (M4)
Jumper
N/-
PR
Screw size
(M4)
IM
MotorPower supply
Single-phase 200V class
FR-D720S-008 to 042FR-D720S-070, 100
Screw size (M3.5)
N/-
R/L1 S/L2
Screw size
(M3.5)
P/+PR
IM
MotorPower supply
Jumpe
N/-
PR
NOTE
Make sure the power cables are connected to the R/L1, S/L2, T/L3. (Phase need not be matched.) Never connect the
power cable to the U, V, W of the inverter. Doing so will damage the inverter.
Connect the motor to U, V, W. Turning on the forward rotation switch (signal) at this time rotates the motor
counterclockwise when viewed from the load shaft.
P/+
R/L1 S/L2 T/L3
P/+
PR
Jumper
Screw size (M4)
R/L1 S/L2
Screw size (M4)
IM
MotorPower supply
Screw size
(M4)
Screw size
(M4)
IM
MotorPower supply
16
Main circuit terminal specifications
2.2.3Cables and wiring length
(1) Applied wire size
Select the recommended cable size to ensure that a voltage drop will be 2% max.
If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop will cause the motor torque to
decrease especially at the output of a low frequency.
The following table indicates a selection example for the wiring length of 20m (65.61feet).
Three-phase 200V class (when input power supply is 220V)
Crimping
Applicable Inverter
Model
FR-D720-008 to 042M3.51.22-3.52-3.522214142.52.52.5
FR-D720-070, 100M41.52-42-422214142.52.52.5
FR-D720-165M41.55.5-45.5-43.53.53.51212444
FR-D720-238M52.55.5-55.5-55.55.55.51010666
FR-D720-318M52.514-58-51485.56816106
Ter minal
Screw
Size ∗4
Tightening
Torqu e
·
m
N
Ter minal
R/L1
S/L2
T/L3
U, V, W
HIV Cables, etc. (mm2) ∗1
R/L1
S/L2
T/L3
U, V, W
Earth
(ground)
cable
Three-phase 400V class (when input power supply is 440V)
Crimping
Applicable Inverter
Model
FR-D740-012 to 080M41.52-42-422214142.52.52.5
FR-D740-120M41.55.5-42-43.523.5121442.54
FR-D740-160M41.55.5-45.5-43.53.53.51212444
Ter minal
Screw
Size ∗4
Tightening
Torqu e
·
m
N
Ter minal
R/L1
S/L2
T/L3
U, V, W
HIV Cables, etc. (mm2) ∗1
R/L1
S/L2
T/L3
U, V, W
Earth
(ground)
cable
Cable Size
AWG ∗2
R/L1
U, V, W
S/L2
T/L3
Cable Size
AWG ∗2
R/L1
U, V, W
S/L2
T/L3
PVC Cables, etc. (mm2)
R/L1
S/L2
T/L3
PVC Cables, etc. (mm2)
R/L1
S/L2
T/L3
∗3
U, V, W
∗3
U, V, W
Earth
(ground)
cable
Earth
(ground)
cable
Single-phase 200V class (when input power supply is 220V)
Crimping
Applicable Inverter
Model
FR-D720S-008 to 042M3.51.22-3.52-3.522214142.52.52.5
FR-D720S-070M41.52-42-422214142.52.52.5
FR-D720S-100M41.55.5-42-43.523.5121442.54
∗1 The cable size is that of the cable (HIV cable (600V class 2 vinyl-insulated cable) etc.) with continuous maximum permissible temperature of 75°C (167°F).
Assumes that the surrounding air temperature is 50°C (122°F) or less and the wiring distance is 20m (65.61feet) or less.
∗2 The recommended cable size is that of the cable (THHW cable) with continuous maximum permissible temperature of 75°C (167°F). Assumes that the
surrounding air temperature is 40°C (104°F) or less and the wiring distance is 20m (65.61feet) or less.
(Selection example for use mainly in the United States.)
∗3 The recommended cable size is that of the cable (THHW cable) with continuous maximum permissible temperature of 70°C (158°F). Assumes that the
surrounding air temperature is 40°C (104°F) or less and the wiring distance is 20m (65.61feet) or less.
(Selection example for use mainly in Europe.)
∗4 The terminal screw size indicates the terminal size for R/L1, S/L2, T/L3, U, V, W, PR, P/+, N/-, P1 and a screw for earthing (grounding).
For single-phase power input, the terminal screw size indicates the size of terminal screw for R/L1, S/L2, U, V, W, PR, P/+, N/-, P1 and a screw for earthing (grounding).
Ter minal
Screw
Size ∗4
Tightening
Torqu e
·
m
N
Ter minal
R/L1
S/L2
U, V, W
HIV Cables, etc. (mm2) ∗1
R/L1
S/L2
U, V, W
Earth
(ground)
cable
Cable Size
AWG ∗2
R/L1
U, V, W
S/L2
PVC Cables, etc. (mm2)
R/L1
S/L2
∗3
U, V, W
Earth
(ground)
cable
NOTE
Tighten the terminal screw to the specified torque. A screw that has been tightened too loosely can cause a short
circuit or malfunction. A screw that has been tightened too tightly can cause a short circuit or malfunction due to the
unit breakage.
Use crimping terminals with insulation sleeve to wire the power supply and motor.
2
WIRING
The line voltage drop can be calculated by the following formula:
Use a larger diameter cable when the wiring distance is long or when it is desired to decrease the voltage drop (torque
reduction) in the low speed range.
17
Main circuit terminal specifications
(2) Earthing (Grounding) precautions
Always earth (ground) the motor and inverter.
1) Purpose of earthing (grounding)
Generally, an electrical apparatus has an earth (ground) terminal, which must be connected to the ground before use.
An electrical circuit is usually insulated by an insulating material and encased. However, it is impossible to manufacture
an insulating material that can shut off a leakage current completely, and actually, a slight current flow into the case.
The purpose of earthing (grounding) the case of an electrical apparatus is to prevent operator from getting an electric
shock from this leakage current when touching it.
To avoid the influence of external noises, this earthing (grounding) is important to audio equipment, sensors, computers
and other apparatuses that handle low-level signals or operate very fast.
2) Earthing (grounding) methods and earthing (grounding) work
As described previously, earthing (grounding) is roughly classified into an electrical shock prevention type and a noise-
affected malfunction prevention type. Therefore, these two types should be discriminated clearly, and the following
work must be done to prevent the leakage current having the inverter's high frequency components from entering the
malfunction prevention type earthing (grounding):
(a)Where possible, use independent earthing (grounding) for the inverter. If independent earthing (grounding) (I) is
impossible, use joint earthing (grounding) (II) where the inverter is connected with the other equipment at an
earthing (grounding) point. Joint earthing (grounding) as in (III) must be avoided as the inverter is connected with the
other equipment by a common earth (ground) cable.
Also a leakage current including many high frequency components flows in the earth (ground) cables of the inverter
and inverter-driven motor. Therefore, they must use the independent earthing (grounding) method and be separated
from the earthing (grounding) of equipment sensitive to the aforementioned noises.
In a tall building, it will be a good policy to use the noise malfunction prevention type earthing (grounding) with steel
frames and carry out electric shock prevention type earthing (grounding) in the independent earthing (grounding)
method.
(b)This inverter must be earthed (grounded). Earthing (Grounding) must conform to the requirements of national and
local safety regulations and electrical codes. (NEC section 250, IEC 536 class 1 and other applicable standards).
Use an neutral-point earthed (grounded) power supply for 400V class inverter in compliance with EN standard.
(c)Use the thickest possible earth (ground) cable. The earth (ground) cable should be of not less than the size indicated
in the table on the previous page 17.
(d)The earthing (grounding) point should be as near as possible to the inverter, and the earth (ground) cable length
should be as short as possible.
(e)Run the earth (ground) cable as far away as possible from the I/O wiring of equipment sensitive to noises and run
them in parallel in the minimum distance.
18
Inverter
(I)Independent earthing.......Best
Other
equipment
Inverter
(II)Common earthing.......Good
Other
equipment
Inverter
(III)Common earthing.......Not allowed
Other
equipment
POINT
To be compliant with the European Directive (Low Voltage Directive), refer to the Installation Guideline.
Main circuit terminal specifications
(3) Total wiring length
The overall wiring length for connection of a single motor or multiple motors should be within the value in the table
below.
200V class
Pr. 72 PWM frequency
selection Setting
(carrier frequency)
1 (1kHz) or less
2 to15
(2kHz to 14.5kHz)
400V class
Pr. 72 PWM frequency
selection Setting
(carrier frequency)
1 (1kHz) or less
2 to15
(2kHz to 14.5kHz)
008014025042070 or More
200m
(656.19feet)
30m
(98.42feet)
012022036050
200m
(656.19feet)
30m
(98.42feet)
Total wiring length (FR-D720-070 or more, FR-D720S-070 or more,
FR-D740-080 or more)
When driving a 400V class motor by the inverter, surge voltages attributable to the wiring constants may occur at the
motor terminals, deteriorating the insulation of the motor.(Refer to page 83)
NOTE
Especially for long-distance wiring, the inverter may be affected by a charging current caused by the stray
capacitances of the wiring, leading to a malfunction of the overcurrent protective function, fast response current limit
function, or stall prevention function or a malfunction or fault of the equipment connected on the inverter output side.
If malfunction of fast-response current limit function occurs, disable this function. If malfunction of stall prevention
function occurs, increase the stall level. (Refer to page 79 for Pr. 22 Stall prevention operation level and Pr. 156 Stall prevention
operation selection )
Refer to page 148 for details of Pr. 72 PWM frequency selection. Refer to the manual of the option for details of surge
voltage suppression filter (FR-ASF-H/FR-BMF-H).
When using the automatic restart after instantaneous power failure function with wiring length exceeding below,
select without frequency search (Pr. 162 = "1, 11"). (Refer to page 136)
Motor capacity
(kW(HP))
Wiring length
0.1K(1/8)0.2K(1/4)0.4K(1/2) or more
20m (65.61feet)50m (164.04feet)100m (323.08feet)
2
WIRING
19