Energy Measuring Unit
Model EMU4-BD1-MB
User’s Manual (Digest
・Before using this unit, please read both this manual and Details carefully and pay attention to safety to handle this unit correctly.
・Make sure that the end users read this manual and then keep the manual in a safe place for future reference.
ABOUT MANUALS
You can download User’s manual (Details) of this unit from the following site.
http://www.mitsubishielectric.co.jp/haisei/lvs/downloads/handling.htm
EMU4-HD1-MB
)
If you are considering using this unit for special purpose such as nuclear power plants,
aerospace, medical care or passenger vehiclesplease refer to our sales representative.
1. Features
(1)
This Energy Measuring Unit can measure various types of electric quantity such as voltage, current, electric power and electric energy.
(2)
The measurement data can also be transmitted to superior monitoring systems through MODBUS®RTU communication.
(3)
In addition to the provision for measuring the quantity of electricity, the un
With pulse input set, you can measure the production volume or the utility other than electricity, such as water, gas and air.
With contact input set, you can monitor status or alarm and measure the operating time of facility or the operating power.
MODBUS® is registered trademarks of Schneider Electric SA
it has two external input ports supporting both pulse input and contact input by way of switching (EMU4-HD1-MB).
2. Checking package contents
This following items for this device and included in package. Check that no items are missing.
(1)
Energy Measuring Unit
x1
(2)
User’s Manual (Digest) x1
3. Safety Precautions
3.1 Precautions for Operating Environment and Conditions
This unit is premised on being used in pollution degree 2* environment. When used in higher pollution degree, protect this unit from pollution on another device side to be incorporated.
Over voltage category of measuring circuit in this unit is CAT II*, and that of auxiliary power circuit (MA, MB) is CAT II*.
Do not use this product in the places listed below. Failure to f
・Places the Ambient temperature exceeds the range -5 - +55°C. ・Places the average daily temperature exceeds 35°C.
・Altitude exceeds 1000m. ・Dust, corrosive gas, saline and oil smoke exist.
・Places in strong electromagnetic field or places large amounts of external noise exist. ・Vibration and impact exceed the specifications.
・Places exposed to direct sunlight ・Places metal fragments or conductive sub
・Places exposed to rain or water drop. ・Places the Relative humidity exceeds the range 30-85% or places with dewfall.
This unit is the open type device, which are designed to be housed within another device for prevention of electric shock. House this unit within the device such as the control panel before use.
For the precautions for the compliance of the system incorporating this unit with the EMC Directives, refer to the User’s Manual (Details).
*: For the definition of the pollution degree and the over voltage category, refer to EN61010-1/2010.
3.2 Matters concerning the precaution before use
・Use the unit in the specified usage environment and conditions.
・The setting of this unit(phase system, primary voltage and primary current, sensor type) is necessary before use it. Please refer to User’s Manual (Details) about each setting method.
3.3 Installation and Wiring Precautions
Any person who is involved in the installation and the wiring of this unit should be fully competent to do this work.
D
anger
Caution
・Shut off the external power supply for the unit in all phases before installing or wiring. Failure to do so may cause an electric shock or damage of this unit.
・Work under the electric outage condition when installing and wiring. Failure to do so may cause electric shock, a failure of the unit, a fire etc.
・When tapping or wiring, take care not to entering any foreign objects such as chips and wire pieces into this unit.
・Check the connection diagram when wiring. Wrong wiring may cause failure of the unit, a fire or electric shock.
・For protection against noise, transmission lines and input/output lines shall not be placed close
・Strip the wires with proper length. Overlong stripping length may cause short to next wire. Shorter stripping length may cause contact failure.
・Take care not to short to next terminal by a filament. (Do not plate the wires with solder.
・Do not connect more than two wires to one terminal of a terminal block for preventing loose contact and wires dropout.
・Use appropriate size of electric wires. If inappropriate size of electric wire is used, it may cause a fire due to
・Tighten the screw within the specified torque. Under tightening can cause drop of the screw, short circuit or malfunction. Over tightening can damage th e screw and/or unit, resulting in
drop, short circuit or malfunction.
・After tightening the screws, be sure to check all the screws tightened. Loose screw may cause malfunction of the unit, a fire or electric shock.
・Be sure to attach the terminal cover to prevent electric shock.
・Use the crimp-t
device malfunction, a failure, a burnout or a fire.
・FG terminal must be grounded according to the D-type ground (ground resistance is not exceed 100Ω).
High-voltage protective element is mounted between MA and FG, MB and FG. When applied high voltage, for example during a commercial frequency wi
element works to short between MA and FG, MB and FG.
・Do not directly touch any conductive part of the unit. Doing so can cause electric shock, failure or malfunction of the unit.
・When using this product, make sure to use it in combination with current sensor (EMU-CT50/CT100/CT250/CT400/CT600, EMU2-CT5 and EMU2-CT5-4W).Please not to exceed the
rating of this product for input of current sensor. For further details, please refer
・The dedicated current sensor (EMU-CT50/CT100/CT250/CT400/CT600) is used onl y for low voltage circuit. It cannot be used for a high voltage circuit. EMU2-CT5 and CT5-4W should
be used with the secondary side (5A) of transformer transfixed. If it is connected with a high -voltage circuit by mistake, it may cause a burnout of the device and a fire. It is critically
dangerous
・The dedicated current sensor has a polarity (directionality). Be careful about it when installing the unit.
・The wires to be connected to this unit shall be placed in a duct or fixed together by cramping. If the electric wires are not placed in the duct or cramped together, loosen wires or their
movement or careless stretch may
・If the wires connected to this unit are strongly pulled off, it may cause a malfunction or a breakage to the unit or the wire.
・Do not exceed the specified voltage when doing an insulation resistance test and a commercial frequency withstand voltage test.
・To prevent persons with little knowledge about electric equipment from electric shock, panel must be taken either following measure.
Lock the panel so that only those who get an education about electric equipment and have sufficient knowledge can unlock, or shut off power supply automatically by opening the panel.
Cover the dangerous part of this unit.
ype terminal appropriated for the size of electric wires. If inappropriate crimp-type terminal i s used, a wire breakage or a contact failure may occur, which may caus e a
. For the allowable maximum voltage of current sensor, refer to User’s manual (Details) 13 “Option devices” (1) Specifications.
ollow the instruction may cause malfunctions and a life decrease of product.
stance are flying.
to or bound together with the power lines and high-voltage lines.
)
generated heat.
thstand voltage test, protective
to current sensor manual to maintain the functionality and the accuracy of this product.
cause a breakage of the unit or wire or a malfunction due to poor contact of electric wires.
3.4 Precautions for Use
・Use this unit within the ratings specified in this manual. If it is used outside the ratings, it may cause not only malfunction or failure but also fire burnout.
Caution
3.5 Maintenance Precautions
・Use a soft dry cloth to clean off dirt of the unit surface. Do not let a chemical cloth remain on the surface for an extended period of time nor wipe the surface with thinner or benzene.
・Check for the following items to use this unit properly for long time.
(1)
(2)
Caution
3.6 Storage Precautions
To store this unit, turn off the power and remove wires, and put it in a plastic bag.
For long-time storage, avoid the following places. Failure to follow the instruction may cause a failure and reduced life of the unit.
・Places the Ambient temperature exceeds the range -10 - +60°C. ・Vibration and impact exceed the specifications.
・Places the Relative humidity exceeds the range 30-85% or places with dewfall. ・Places exposed to rain, water drop
・Dust, corrosive gas, saline and oil smoke exist. ・Places metal fragments or conductive substance are flying.
・Places the average daily temperature exceeds 35°C.
3.7 Disposal Precautions
When disposing of this unit, treat it as industrial waste.
3.8 About packaging materials and this manual
For reduction of environment load, packaging materials are produced with cardboard, and this manual is printed on recycled paper.
・Do not disassemble or modify this unit. It may cause failure, malfunction, injury or fire.
・Do not touch the live part such as connection terminal. It may cause electric shock, electric burn injury or burnout of the device. If any exposed conductor is found, stop the operat
immediately, and take an appropriate action such as isolation protection.
Daily maintenance
(a) No damage on this unit
Periodical maintenance (Once every 6 months to 1 year
・No looseness with installation
Do periodical maintenance under the electric outage condition. Failure to do so may cause electric shock, failure of the unit or a fire. Tighten the terminal regularly to prevent a fire. In
case a display unit is attached to a sensor unit, get off the display unit during maintaining or tightening terminals.
(b)
No abnormality with LCD
and wire connection
(c)
)
No abnormal noise, smell or heat
or direct sunlight.
ion
4. Name and function of each part
4.1 Name of each part
(1)
EMU4-BD1-MB
Voltage input terminals
Current input terminals
Frame GND terminal
Power supply terminals
Communication terminals
(
MODBUS® RTU
)
4.2 Functions of operation buttons
Control buttons have many functions as below.
DISP button
+/PHASE button
-/RESET button
SET button
Meaning of symbol: ○ (Press), □ (Press more than 1 sec), ◎ (Press more than 2 sec), - (Press both at the same time
Mode
Operation
Mode
Contact display
Integrated value
display
Menu display
Setting mode /
Setting display
Setting mode /
Confirmation
mode
Confirmation
mode / Setting
display
Confirma
display of setting
reflection
5. Procedures for setting
Operation mode
Measurement display
"End" display
Fix change of
setting value
"CANCEL" display
Cancel change
of setting value
Transition automatically
Example of display on
setting mode
"-" + "DISP"
Factroy default
Example of display on
confirmation mode
<Note>
For details of setting menu 1, 2, 3, 4, 5 and 6, refer to User's manual (Details).
LCD
display
Operation
button
Operation
SET -/RESET +/ PHASE DISP
◎
◎ ◎
◎ ◎
○
○
□
○
□
○
tion
Setting menu 1 Setting menu 2 Setti ng menu 3 Setting menu 4 Setting menu 5
Basic setting Communication setting Alarm setting Logging settingEnd of setting menu
*1
*2
For the case of special voltage (SP
(Not available for 1P3W
Primary voltage
(VT voltage)
Primary special
Secondary
special voltage
(2)
EMU4-HD1-MB
Voltage input terminals
Current input terminals
Name of Button
○
◎
◎
◎ ◎
○ ○
(□) (□)
○ ○
(□) (□)
○ ○
◎ ◎
Phase wire
system
Primary voltage
(with or without
VT)
Primary voltage
(with VT or direct
connection)
Sensor type
Primary
current
Current
demand time
limit
Power demand
time limit
)
voltage
○
)
Frame GND terminal
Power supply terminals
LCD
display
Operation
button
Contact/ pulse output terminals
Contact/ pulse input terminals
Communication terminals (MODBUS® RTU
)
)
Input/output setting
Contact/pulse
input
on or off
*5
Reset method
of contact input
Contact/pulse
output
on or off
*6
Unit of pulse
output
Display CO2 or
*7
CO2 conversion
setting
Display harmonic
current or not
Display harmonic
voltage or not
Display operating
time or not
Count method of
operating time
Event
)
)
)
*4 *4
not
*4
Change measurement items
○
Change phase
Change harmonic order (at harmonic display
Clear alarm (at alarm generation display with alarm keeping
Transition to confirmation m ode
Transition to setting mode
Clear contact latch
Transition to preset display
Transition to reset display of all data
Enter setting menu
Moving up or
down of menu number
(
Move at fast speed when pressing more than 1sec
Change of setting items (forward
Transition to setting menu number (at final setting item
Moving up or down of setting value
(
Move at fast speed when pressing more than 1sec
Change setting items (backward
○
Transition to setting menu number (at beginning setting item
Back to setting menu
Change setting items (forward
Transition to setting menu number (at final setting item
Change setting items (backward
○
*3
For the case of
special current (SP
Sensor type
Primary special
to setting menu number (at beginning setting item
Transition
Transition to setting menu
At "END" display, memorize changed setting and transition to operation
mode
At "CANCEL" display, throw away changed setting and transition to
operation mode
Moving up or down of setting value
Reset setting values to factory default (only effective at CANCEL display
Setting mode or confirmation mode
®
MODBUS
address
®
MODBUS
baud rate
®
MODBUS
parity
®
MODBUS
stop bit
)
voltage
(3)
Back view
IEC rail
fixture
)
Names of signals of terminal block (EMU4-BD1-MB
Terminal
symbol
P1、P2、P3
MA、MB
1k、1L、3k、3L
485+、485-
SLD Connect to ground (D type ground).
Ter Connect the “ 485- “ terminal(the unit at end of
Names of signals of terminal block (EMU4-HD1-MB
Terminal
symbol
P1/P1、P2/P0、
P3/P3、NC/P2
MA、MB
1k、1L、2k、2L、
3k、3L
485+、485-
SLD Connect to ground (D type ground).
Ter Connect the “ 485- “ terminal (the unit at end of
X1、COM
Y1、COM
Description
Connect the voltage inp ut wire for t he
measurement circuit.
Connect to ground (D type ground).
Connect the auxiliary power supply.
Connect the secondary output of the dedicated
current sensor connected to the measurement
circuit’s current wire.
Connect the communication wir e (MODBUS
RTU).
the link).
Description
Connect the voltage inp ut wire for t he
measurement circuit.
Connect to ground (D type ground).
Connect the auxiliary power supply.
Connect the secondary output of the dedic ated
current sensor connected to the measurement
circuit’s current wire.
Connect the communication wire (MODBUS
RTU).
the link).
Connect the contact/ pulse input wir e.
X
Connect the contact/ pulse output wir e.
Y
)
®
)
®
4.3 Functions of LCD
)
)
)
)
)
)
)
)
Upper and lower
limit alarm
on or off
Upper and lower
limit alarm item
Upper and lower
limit alarm value
Alarm delay time
Alarm reset
method
Symbol
No display
2
3
4
5
No. Indicator Description
1 Measured value Display measured value digitally.
2 Measured item Display measured item displayed on indicator No.1.
3 Communication Light when connecting communication unit.
4 Energy
Measurement
5 Setting Indicator lights on setting mode.
)
*8
Logging module
ID setting
Clear logging
data
*1: On confirmation mode, transition to operation mode.
*2: Transition only when selecting "SP" for "Primary current (VT)".
(For 3P4W, only special voltage is available when using VT.
*3: Transition only when selecting "SP" for "Primary current (5A)".
*4: Setting available for EMU4-HD1-MB only.
*5: Transition only when selecting "CO.P." for "Contact/pulse input on or off" .
*6: Transition only when selecting "PLS" for "Contact/pulse output on or off".
*7: Transition only when selecting "on" for "Display CO2
*8: Transition only when connecting logging module.
*9: Not displayed on setting mode.
Transition from operation mode to setting mode.
Tr
ansition from operation mode to confirmat ion mode.
Enter each setting display or transition to next item.
Memorize changed setting and transition to operation
Behavior
Select menu number or "End".
Back to previous settting display.
Select setting value.
Transition to "End" display.
mode.
Select "CANCEL".
Cancel change of setting value.
Skip other items during setting.
Reset setting values to factory default.
Light when measuring electric energy (consumption).
Indicator lights on confirmation mode.
Setting menu 6
Test mode
*9
Test mode
)
or not".
Operation of control button
"SET" + "-"
same time for 2 sec
"SET"
"+" or "-"
Press several times
"SET"
"DISP"
"+" or "-"
Press several times
"SET"
"SET"
"+" or "-"
"SET"
"SET"
"SET"
Press both at the
Press for 2 sec
Press once
Press once
Press once
Press once
Press once
Press once
Press for 1 sec
Press once
1

6.1 Mounting on IEC rail
6.2 Mounting on the panel
Recommended
screws
cross recessed h ead screw with captive washer
and flat washer
M3×10 2pcs
Panel
Panel
Panel m ounting
attachment
Mount the m odule to mounting plate by mounting screws
(
M3×10), then mount the panel mounting attachment.
Tightening torque : 0.63N・m
*Please screw up the pan el mounting attachment wher e there are
high levels of vibration.
*The screws (mounting screws and screws for panel mounting
attachment) are supplied with panel mounting attachment.
・Dimensions of hole panel
The panel hole dimensions are as shown below.
And it can be attached to a pane
l of thickness
1.6 – 4.5mm.
・Mounting ・Mounting
・Dimensions of hole panel
The panel hole dimensions are as shown below.
And it can be attached to a panel of thick ness
1.6 – 4.5mm.
Attached to the panel with screws (2 pcs).
Tightening torque : 0.63N・m
Outline of the unit
Outline of the unit
Mounting screws
Mounting screws
Screws for panel
mounting
attachment
7.1 Wiring
Follow the wiring diagram for external connections of this unit.
When using this unit, current sensor (EMU-CT50/CT100/CT250/CT400/CT600, EMU2-CT5 or EMU2-CT5-4W) is necessary.
1P2W (for low voltage circuit
)
1
2
Power source side
Load side
K
L
RS485 (MODBUS
®
)
EMU-CT*** model
split current sensor
(50/100/250/400/600)
1P3W/3P3W (for low voltage circuit
)
11N
2
Power source side
Load side
K
L
RS485 (MODBUS®)
EMU-CT*** model
split current sensor
(50/100/250/400/600)
3
3
L
K
3P3W (for high voltage circuit
)
RS485 (MODBUS®)
1
2
Power source side
3
5A current sensor
EMU2-CT5
5A current sensor cable
EMU2-CB-Q5B
Current
transformer ***/ 5A
K
L
Load side
K
L
Contact/
pulse output
Contact/
Pulse input
3P4W (for high voltage circuit
)
1 2
Power source side
Load side
K
L
RS485 (MODBUS®)
Current
transformer ***/ 5A
3
L
K
N
L
K
5A current sensor
EMU2-CT5-4W
5A current sensor cable
EMU2-CB-Q5B-4W
Contact
/pulse output
Contact
/pulse input
・Make sure that before connecting the cable, the orientation of the current sensor is correct for attachment. K to L is the correct direction.
K: power source side, L: load side
・EMU-CT50/100/250/400/600 is used only for low voltage circuit.(Maximum voltage: 460V)It cannot be used for a high voltage circuit. EMU2-CT5 and EMU2-CT5-4W
should be used with the secondary side (5A) of transformer transfixed. If they are used for the circuit directly, they
should be used under 200V. (Maximum voltage: 260V
)
・Maximum voltage of the circuit connected to this unit directly is 260V for EMU4-BD1-MB, or 277 / 480V for EMU4-HD1-MB. For the circuit over this voltage, use the
transformer. Using the transformer, primary voltage is configurable up to 6600V.
・
・For MODBUS
®
communication wiring, recommended to have the extra length wires about 200mm (When extended to B / NET transmission from MODBUS® communication,
use of MODBUS
®
communication wiring is possible).
When screwing the terminals at both ends of the terminal block, be careful not to touch the projection of the terminal block cover.
●EM
U4-BD1-MB ●EMU4-HD1-MB
Unit [mm]
・The charge-free warranty is effective until the earlier of 1 year after the date of your purchase or 18 months after manufacturing. Repair shall be charged for the case failures
occur due to your intent or fault even during the charge-free warranty period.
・Our company shall not be liable to compensate for any loss arising from events not attributable to our company, opportunity loss and lost earning of the c
ustomer due to failure
of the product, and loss, secondary loss, accident compensation, damage to other products besides our products and other operations caused by a special reason regardless
of our company’s predictability.
If an abnormal sound, bad-smelling smoke, fever break out from this unit, switch it off promptly and don’t use it
Please contact us at the following locations.
1-8 Midori-cho, Fukuyama-shi, Hiroshima, 720-8647, Japan
Phone: +81-84-926-8142
・For protection against noise, transmission lines and input/output lines shall not be placed close
to or bound together with the power lines and high-voltage lines. Keep distance as below
between them. (except for the terminal block
)
Condition distance
High-voltage line 600V or less 300mm or longer
Other high-voltage line 600mm or longer
・For the actual usage, connect the FG terminal to ground. (D-type ground: Type 3) Connect it
directly to the ground terminal.
・Do not connect to FG terminal during the insulation resistance test and pressure test.
Item Specifications
Model EMU4-BD1-MB EMU4-HD1-MB
Phase-wire system
single-phase 2-wire / single-phase 3-wire /
three-phase 3-wire
single-phase 2-wire / single-phase 3-wire /
three-phase 3-wire / three-phase 4-wire
Measurement item
Electric energy (consumption, regeneration), Current,
Current demand, Voltage, Electric power, Electric power
demand, Reactive power, Power factor, Frequency,
Reactive energy, Operating time
Electric energy (consumption, regeneration), Current, Current
demand, Voltage, Electric power, Electric power demand, Reactive
power, Apparent power, Power factor, Frequency, Harmonic
current, Harmonic voltage, Reactive ener
gy, Periodic electric
energy, Pulse count value, Operating time, Equivalent CO
2
Rating
Voltage
circuit
single-phase 2-wire,
three-phase 3-wire
110V, 220V AC 110V, 220V, 440V AC
single-phase 3-wire
AC110V(b/w 1- and 2-side, 2- and 3-side),
AC220V(b/w 1- and 3-side)
AC110V(b/w 1- and 2-side, 2- and 3-side),
AC220V(b/w 1- and 3-side)
three-phase 4-wire Non-compliant Min: AC63.5V/110V, Max: AC277V/480V
Current circuit
50A, 100A, 250A, 400A, 600A AC
(
The dedicated split type current sensor is used. Each value refers to the current at the primary side of the current sensor
)
5A AC
(
The dedicated split type current sensor is used. 5A current sensor is used together with the current transformer (CT), and the
primary-side current is configurable up to 6000A.
)
Frequency 50Hz-60Hz
Auxiliary power supply rating 100-240V AC (+10%, -15%), 50Hz-60Hz
Measurable circuit count 1 circuit
External input
Input signal type
None
No voltage a-contact 1 input
Rated input
voltage/current
5V DC 7mA
External output
Output signal type
None
No voltage a-contact 1 output
Rated open/close
voltage/current
35V DC 75mA or 24V AC 75mA (Power factor = 1)
Operating temperature -5 - +55℃(Under the conditions indicated in section 3.1
)
Operating humidity 30 - 85%RH(No condensation
)
Storage temperature -10 - +60℃
Operating altitude 1000m or below
Standard
EMC: EN61326-1: 2006
LVD: EN-61010-1: 2010
Product life expectancy 10 years (Under the conditions indicated in section 3.1
)
7.2 How to connect wires
・Use appropriate crimp-type terminal.
・Use electric wires as below, and tighten the terminal screws by the torque as below.
【EMU4-BD1-MB】
Applicable wire Tightening torque Recommended
crimp-type terminal
Power supply terminals,
voltage input terminals
AWG24 - 16
(single wire / stranded wire)
0.8 N・m
For M3 screw of
external diameter
below 5.6mm
Current input terminals,
input/ output terminals
AWG22 - 14
(single wire / stranded wire)
0.5 - 0.6N・m
For M3 screw of
external diameter
below 5.6mm
【EMU4-HD1-MB】
Applicable wire Tightening torque Recommended
crimp-type terminal
Power supply terminals,
voltage input terminals
AWG26 - 14
(single wire / stranded wire)
0.8 - 1.0 N・m
For M3.5 screw of
external diameter
below 5.6mm
Current input terminals,
input/ output terminals
AWG22 - 14
(single wire / stranded wire)
0.5 - 0.6N・m
For M3 screw of
external diameter
below 5.6mm
(2)
Pull the unit
6. Attachingand removing the unit
CL
2×
φ
4
22.5 53.5
67
77
26.5 45.5
67
53.5
2×
φ
4
2×
φ
4
22 54.5
106
28
45.5
26.5
77
(75)
7. How to wire
l
P1 P2 P3 MA MB
1k 3k
485+
SLD
Ter
3L1L
485-
l
l
P1 P2 P3 MA MB
1k 3k
485+
SLD
Ter
3L1L
485-
1k1l3k
3l
P1/P1
P2/P0
P3/P3
NC/P2
MA MB
1k 2k
1L 2L3k3L
X1 Y1
485+
485-
SLD
Ter
COMx COM
Y
P1/P1 P2/P0 P3/P3
NC/P2
MA MB
1k 2k
1L 2L3k3L
X1 Y1
485+
485-
SLD
Ter
COMx COM
Y
1k1l3k3l2k
2l
Caution
8. Dimensions
9. Specifications
10. Warranty
11. Customer Service
Caution
COMMUNICATION RS485(MODBUS RTU)
35V DC 75mA
2400-38400bps
AUX.SUPPLY 100-240V~ 50/60Hz 10VA
CONTACT OUTPUT No Voltage a-contact
5V DC 7mA
CONTACT INPUT No Voltage contact
MEASUREMENT ITEM A,V,W,var,VA,Hz,PF,Wh,varh
ENERGY MEASURING UNIT
ELECTRIC
MITSUBISHI
MODEL
EMU4-HD1-MB
P1,P2,P3,RATED 110,220,440V AC(~1P2W,1P3W,3P3W)
1k,1l,2k,2l,3k,3l RATED 66,66mA AC~ 50/60Hz
LY303N900H11
MADE IN JAPAN
MITSUBISHI ELECTRIC CORPORATION
REFER TO
MANUAL
P1,P2,P3,P0 RATED 277/480V AC(~3P4W)
15 60
27.5 43.5
27 35.4
MEASUREMENT ITEM A,V,W,var,Hz,PF,Wh,varh
ENERGY MEASURING UNIT
ELECTRIC
MITSUBISHI
MODEL
EMU4-BD1-MB
P1,P2,P3,RATED 110/220V AC(~1P2W,1P3W,3P3W)
1k,1l,3k,3l RATED 66,66mA AC~ 50/60Hz
LY303N900H01
MADE IN JAPAN
MITSUBISHI ELECTRIC CORPORATION
2400-38400bps
COMMUNICATION RS485(MODBUS RTU)
AUX.SUPPLY 100-240V~ 50/60Hz 10VA
REFER TO
MANUAL
6015
27.5 43.5
27 35.4
CL
90
75
67
4
22.5
53.5
90
22.5
4 75
CL
53.5
67