Mitsubishi Electric EMU4-FD1-MB User Manual

Energy Measuring Unit
MODEL
EMU4-FD1-MB
User’s Manual (Details)
Before operating the instrument, you should first read thoroughly this operation manual for
safe operation and optimized performance of the product.
Deliver this user’s manual to the end user.
This manual describes setup and usage for the Energy Measuring Unit. Before using the product, please read this manual
vehicles please refer to our sales representative.(For details, please see at the end of this manual.)
Notations in this manual
Use the following marks in this manual.
Mark
Meaning of the icons
Danger
Caution
Indicates that incorrect handling may result in injury or property damage, ignoring this marking.
Supplement
Indicates that precautions to avoid a malfunction and to work the unit properly.
Indicates that the pages described that related matters.
This unit cannot be used for deal and proof of electric energy measurement stipulated in the

Safety precautions

Thank you for purchasing the Energy Measuring Unit.
carefully to ensure correct use. Especially, in the case of where this unit is to be installed, please read “1. Precautions for Use” to ensure correct use.
Make sure that the end users read this manual and then keep the manual in a safe place for future reference. Make sure to deliver this manual to the end-user. If you are considering using this unit for special purpose such as nuclear power plants, aerospace, medical care or passenger
Indicates that incorrect handling may result in death or severe injury, ignoring this marking.
measurement law. Please use the certified watt-hour meter to be used for deal and proof of electric energy measurement stipulated. When using this unit, make sure to use it in combination with 5A/1A current transformer.

Features

This Energy Measuring unit can measure various types of electric quantity such as voltage, current, electric power and electric
energy.
The measured data can be sent to the high-end device, such as a monitoring device by MODBUS
function.
This Energy Measuring unit has one external input terminal, which can switch between pulse input and contact input.
Production quantity and water, gas, air (other than electricity) can be measured in the pulse input setting. Monitoring of condition and alarm, measurement of operating time and electric energy during operation can be done in the contact input setting.
®
MODBUS
is a registered trademark of SCHNEIDER ELECTRIC USA, INC in the United States.
®
RTU communication
(1/71)

Table of Content

Safety precautions ................................................................................................................................................................. 1
Features ................................................................................................................................................................................... 1
Table of Content ...................................................................................................................................................................... 2
1. Precautions for Use ........................................................................................................................................................... 3
Precautions for Operating Environment and Conditions ..................................................................................................................... 3
Matters concerning the precaution before use ...................................................................................................................................... 3
Installation and Wiring Precautions ........................................................................................................................................................ 3
Precautions for Use .................................................................................................................................................................................. 4
Maintenance Precautions ........................................................................................................................................................................ 4
Storage Precautions ................................................................................................................................................................................. 4
Disposal Precautions ............................................................................................................................................................................... 4
About packaging materials and this manual ......................................................................................................................................... 4
2. Disclaimer ............................................................................................................................................................................ 5
3. Name and function of each part ....................................................................................................................................... 5
4. Attaching and removing the unit ..................................................................................................................................... 7
5. Procedure for wiring ........................................................................................................................................................ 10
Wiring for EMU4-FD1-MB .....................................................................................................................................................................10
System configuration example of MODBUS®RTU communication .................................................................................................13
6. Operating mode ................................................................................................................................................................ 15
7. Setting method ................................................................................................................................................................. 16
Procedures for setting ............................................................................................................................................................................16
Setting menu 1: Phase wire system, primary voltage, primary current, demand time, etc. ...........................................................18
Setting menu 2: MODBUS
Setting menu 3: Contact / pulse input/output, equivalent CO2, harmonic, operating time, etc. .....................................................25
Setting menu 4: Upper / lower limit alarm setting, alarm delay time ,alarm reset, etc. ...................................................................26
Setting menu 5: Setting related to logging unit ....................................................................................................................................28
Setting menu 5: MODBUS
Confirmation menu 1 - 5: Confirmation of setting values in setting menu 1 - 5 ...............................................................................30
Initialization of related items by change of setting ...............................................................................................................................31
Clock setting and logging data clear .....................................................................................................................................................32
Change of date format ...........................................................................................................................................................................33
How to use test mode ............................................................................................................................................................................34
Test menu 1: Discrimination support function for improper connection ...........................................................................................35
Test menu 2: Communication test ........................................................................................................................................................47
Test menu 3: Pulse output test ..............................................................................................................................................................48
Test menu 4: Alarm output test..............................................................................................................................................................48
8. Operation ........................................................................................................................................................................... 49
Operation procedure in operating mode ..............................................................................................................................................49
Measured item indication in operating mode ......................................................................................................................................52
How to use upper/lower limit alarm function ........................................................................................................................................54
Operations of alarm reset ......................................................................................................................................................................55
Preset and all data reset ........................................................................................................................................................................56
9. Device operation ............................................................................................................................................................... 57
Measured items ......................................................................................................................................................................................57
Restrictions of measured data ..............................................................................................................................................................59
10. Reference ......................................................................................................................................................................... 60
In case you think the unit is in failure ....................................................................................................................................................60
About error number ................................................................................................................................................................................60
After-sales service ..................................................................................................................................................................................61
Q&A ..........................................................................................................................................................................................................61
11. Requirement for the compliance with EMC Directives ............................................................................................ 63
12. Specifications ................................................................................................................................................................. 64
Common specifications .........................................................................................................................................................................64
Specifications of MODBUS®RTU communication .............................................................................................................................66
13. Option devices ................................................................................................................................................................ 67
14. External dimensions ...................................................................................................................................................... 70
15. Index ................................................................................................................................................................................. 71
®
RTU communication .............................................................................................................................22
®
TCP communication .............................................................................................................................29
(2/71)

1. Precautions for Use

Precautions for Operating Environment and Conditions

Matters concerning the precaution before use

Installation and Wiring Precautions

Caution
<Precautions for Electric work>
Condition
Distance
Power line 600V or less Other power line
300mm or longer 600mm or longer
If the wires connected to this unit are strongly pulled off, it may cause a malfunction or a breakage to the unit or the wire.
This unit is premised on being used in pollution degree 2* environment. When used in higher pollution degree, protect this unit
from pollution on another device side to be incorporated.
Over voltage category of measuring circuit in this unit is C AT Ⅲ*, and that of auxiliary power circuit (MA, MB) is C AT Ⅲ*. ・ Do not use this product in the places listed below. Failure to follow the instruction may cause malfunctions and a life decrease
of product.
- Places the Ambient temperature exceeds the range -5 - +55°C.
- Places the average daily temperature exceeds +35°C.
- Places the Relative humidity exceeds the range 30-85% or places with dewfall.
- Vibration and impact exceed the specifications.
- Dust, corrosive gas, saline and oil smoke exist.
- Places exposed to direct sunlight.
- Places exposed to rain or water drop.
- Places in strong electromagnetic field or places large amounts of external noise exist.
- Places metal fragments or conductive substance are flying.
- Altitude exceeds 2000m.
< For prevention of electric shock>
This unit is designed to be housed within another device for prevention of electric shock. House this unit within the device
such as the grounded control panel before use.
To prevent persons with little knowledge about electric equipment from electric shock, panel must be taken either following
measure.
- Lock the panel so that only those who get an education about electric equipment and have sufficient knowledge can unlock, or shut off power supply automatically by opening the panel.
- Cover the dangerous part of this unit. (Required protection code is higher than IP2X.)
*: For the definition of the pollution degree and the over voltage category, refer to EN61010-1/2010.
Use the unit in the specified usage environment and conditions. The setting of this unit (phase system, primary voltage, primary current) is necessary before use it.
Make sure to read this manual carefully before Installation and Wiring.
Any person who is involved in the installation and the wiring of this unit should be fully competent to do this work. Work under the electric outage condition when installing and wiring. Failure to do so may cause electric shock, a failure of
the unit, a fire etc.
When tapping or wiring, take care not to entering any foreign objects such as chips and wire pieces into this unit. Check the connection diagram when wiring. Wrong wiring may cause failure of the unit, a fire or electric shock.
For protection against noise, transmission lines and input/output lines shall not be placed close to or bound
together with the power lines and high-voltage lines.
The wires to be connected to this unit shall be placed in a duct or fixed together by cramping. If the electric wires are not
placed in the duct or cramped together, loosen wires or their movement or careless stretch may cause a breakage of the unit or wire or a malfunction due to poor contact of electric wires.
If transmission lines and input/output lines are placed close to or bound together with the power lines and high-voltage
lines, keep distance as below between them.
<Connection of terminal block> Strip the wires with proper length. Overlong stripping length may cause short to next wire. Shorter stripping length may
cause contact failure.
Take care not to short to next terminal by a filament. (Do not plate the wires with solder.) Do not connect three or more wires to one terminal of a terminal block for preventing loose contact and wires dropout. Use appropriate size of electric wires. If inappropriate size of electric wire is used, it may cause a fire due to generated
heat.
Circuits connected to an auxiliary power circuit (MA, MB) need to be used the over current protection device (fuse, circuit
breaker, etc.) to prevent shorting connecting wires. (Select an appropriate rating to prevent burnout of the wires.)
Tighten the screw within the specified torque. Over tightening can damage the screw and/or terminal. After tightening the screws, be sure to check all the screws tightened. Loose screw may cause malfunction of the unit, a
fire or electric shock.
Be sure to attach the terminal cover to prevent electric shock. Do not directly touch any conductive part of the unit. Doing so can cause electric shock, failure or malfunction of the unit.
(3/71)
<Connection of frame GND terminal>
Do not exceed the specified voltage when doing an insulation resistance test and a commercial frequency withstand

Precautions for Use

Danger
Do not touch the live part. It may cause electric shock, electric burn injury or damage of the device. Work under the electric outage condition when installing and wiring.
Caution
Do not disassemble or modify this unit. It may cause failure, malfunction, injury or fire.
damaged, and burnout may be caused.

Maintenance Precautions

Do periodical maintenance under the electric outage condition. Failure to do so may cause electric shock, failure of the unit or a fire. Tighten the terminal regularly to prevent a fire.

Storage Precautions

Disposal Precautions

About packaging materials and this manual

voltage test. Do not connect to frame GND terminal during the insulation resistance test and pressure test.
Use the crimp-type terminal appropriated for the size of electric wires. If inappropriate crimp-type terminal is used, a wire
breakage or a contact failure may occur, which may cause a device malfunction, a failure, a burnout or a fire.
Frame GND terminal must be grounded according to the D-type ground (ground resistance is not exceed 100Ω).
This unit cannot be used for deal and proof of electric energy measurement stipulated in the measurement law. Before operating the product, check that active bare wire and so on does not exist around the product. If any bare wire exists,
stop the operation immediately, and take an appropriate action such as isolation protection.
In the event of a power outage during the setting, the unit is not set correctly. Please set again after power recovery.
・ ・
・ ・ Use this unit within the ratings specified in this manual. If it is used outside the ratings, it may cause not only malfunction
or failure but also fire burnout.
When using this product, make sure to use it in combination with 5A current transformer(max 30V AC).
Do not open the secondary side of the CT circuit. If the CT is not connected properly or if the secondary side of the CT is
open, it may result in high voltage on the secondary side of the CT, the insulation of the secondary winding wire may be
Use a soft dry cloth to clean off dirt of the unit surface. Do not let a chemical cloth remain on the surface for an extended
period of time nor wipe the surface with thinner or benzene.
Check for the following items to use this unit properly for long time.
(1) Daily maintenance
(a) No damage on this unit (b) No abnormality with LCD indicators (c) No abnormal noise, smell or heat
(2) Periodical maintenance (Once every 6 months to 1 year)
- No looseness with installation and wire connection
Caution
To store this unit, turn off the power and remove wires, and put it in a plastic bag. For long-time storage, avoid the following places. Failure to follow the instruction may cause a failure and reduced life of the unit.
- Places the Ambient temperature exceeds the range -10 - +60°C.
- Places the average daily temperature exceeds +35°C.
- Places the Relative humidity exceeds the range 30-85% or places with dewfall.
- Vibration and impact exceed the specifications.
- Dust, corrosive gas, saline and oil smoke exist.
- Places metal fragments or conductive substance are flying.
- Places exposed to rain, water drop or direct sunlight.
When disposing of this unit, treat it as industrial waste.
For reduction of environment load, packaging materials are produced with cardboard, and this manual is printed on recycled paper.
(4/71)

2. Disclaimer

Contact/ pulse input terminals
Contact/ pulse output terminals
Frame GND terminal
Power supply termin als
Voltage input terminals
LCD display
Operation button
Communication terminal s
(MODBUS® RTU)
Current input termi nals
IEC
rail fixture
Terminal symbols
Function
Description
P1/P1, P2/P0, P3/P3, NC/P2
Input voltage
Connect the voltage input wire of the measuring circuit.
Frame GND (FG)
Connect to ground. (D-type ground)
MA, MB
Auxiliary power
Connect the auxiliary power supply.
1k, 1L, 2k, 2L,
Input current
Connect the secondary output of the
the measurement circuit’s current wire.
485+, 485-
MODBUS®
Connect the communication wire (MODBUS® RTU).
SLD
Connect to ground. (D-type ground)
Ter
Connect with “485-“ terminals (the unit at end of the link) page 13
X1, COMX
Pulse input/ contact input
Connect pulse input/contact input wires.
Y1, COMY
Pulse output/ contact output
Connect pulse output/contact output wires.
Sign and function of the terminal block
It is prohibited to reprint or copy all contents of this document in any form without our permission. ‧ The contents of this document will be updated to follow revisions to software and hardware, however under unavoidable
circumstances it may not be synchronized.

3. Name and function of each part

Name of each part
Back view
3k, 3L
current transformer (CT) connected to
communication
(5/71)
Function of operation buttons
Mode
Name of Button
SET
-/RESET
+/PHASE
DISP
Change measured items
Change phase
Change harmonic order (at harmonic display)
Clear alarm (at alarm keeping)
Transition to confirmation mode
Transition to setting mode
display
Integrated
display
Enter setting menu
(Move at fast speed when pressing more than 1sec)
Change of setting items (forward) Transition to setting menu number (at final setting item)
Moving up or down of setting value (Move at fast speed when pressing more than 1sec)
Change setting items (backward)
item)
Go back to setting menu
Change setting items (forward) Transition to setting menu number (at final setting item)
Change setting items (backward)
item)
At "END" display, memorize changed setting and transition
to operating mode
Moving up or down of setting value
Reset setting values to factory default (only effective at CANCEL display)
No.
Indicator
Description
1
Measured value
Display measured value digitally.
2
Measured item
Display measured item displayed on indicator 1.
3
Communication
Light when connecting communication unit.
4
Energy Measurement
Light when measuring electric energy
5
Setting
Indicator lights on setting mode.
Indicator lights on confirmation mode.
2
1
3
4
5
SET button
Control buttons have many functions as below. (How to change mode page 15.)
DISP button
+/PHASE button
-/RESET button
Meaning of symbol: (Press), (Press more than 1 sec), (Press more than 2 sec), ― (Press both at the same time)
Setting mode
Confirmation
Operating
Mode
/
mode
Operation
Contact
value
Menu
display
Setting mode
/ Setting display
Confirmation
mode / Setting display
(□)
(□)
(□)
(□)
Function
Clear contact latch
Transition to preset display
Transition to reset display of all data
Moving up or down of menu number
Transition to setting menu number (at beginning setting
Transition to setting menu number (at beginning setting
Transition to setting menu
Confirmation
display of
setting
reflection
to operating mode At "CANCEL" display, annul changed setting and transition
Functions of LCD
(6/71)

4. Attaching and removing the unit

Caution
Any person who is involved in the installation and the wiring of this unit should be fully competent to do this work.
(2) Catch
IEC rail
(4) Push the IEC rail
fixture upward.
(3) Push in
(1) Hold the unit and pull IEC rail
fixture downward.
(2) Pull the unit
(1) Pull IEC rail fixture downward.
More than 7.3
There are two installation methods, surface mounting and panel mounting
Surface mounting
(1) How to attach to the IEC rail
Applicable IEC rail Attaching Removing
*1: When showing the display part by cutting the panel face in mounting the IEC rail, cut the panel at where it is more than 50mm away from the fulcrum of the open/close of the door.
(7/71)
Plate mounting
Dimensions of hole panel(76×44.5)
Attaching
Dimensions of hole panel(101×44.5
Attaching
Plate
Attach the plate by using 2 screws. Tight
Mounting screws
Outline of the measuring unit
Outline of the option unit
Attach the plate by using 2 screws. Tight
Mounting screws
Plate
cross recessed head screw with captive washer
M3×10 2pcs
Outline of the measuring unit
*Panel cut dimensions are made larger than the product considering
*Panel cut dimensions are made larger than the product considering
(1) Screw mounting (Measuring unit)
tolerance in panel cut.
If you want to prevent dust and other intrusion the gap of panel cut,
cut the panel according to the product to be mounted.
(2) Screw mounting (Measuring unit + optional unit)
ening torque: 0.63N・m
Recommended screws
and flat washer
ening torque: 0.63N・m
tolerance in panel cut.
If you want to prevent dust and other intrusion the gap of panel cut,
cut the panel according to the product to be mounted.
(8/71)
(3) Screw mounting (When using the measuring unit and the attachment for panel mounting)
Dimensions of hole panel(76×44.5
Attaching
Dimensions of hole panel (101×44.5)
Attaching
Tightening torque: 0.63N・m
Plate
Attachment for panel mounting
Attach the plate by using 2 screws, then install the attachment on the plate. Tight
Mounting screws
Screws for panel
Plate
Attachment for panel mounting
Mounting screws
Screws for panel
*Please screw up the panel mounting attachment where there are high
Outline of the measuring unit
*Please screw up the panel mounting attachment where there are high
Outline of the measuring unit
Outline of the option unit
*Panel cut dimensions are made larger than the product considering
cut the panel according to the product to be mounted.
*Panel cut dimensions are made larger than the product considering
tolerance in panel cut.
If you want to prevent dust and other intrusion the gap of panel cut,
cut the panel according to the product to be mounted.
mounting
ening torque: 0.63N・m
levels of vibration.
*The screws (mounting screws and screws for panel mounting
attachment) are supplied with panel mounting attachment.
attachment
(4) Screw mounting (Measuring unit + optional unit, when using the attachment for panel mounting)
tolerance in panel cut.
If you want to prevent dust and other intrusion the gap of panel cut,
Attach the plate by using 2 screws, then install the attachment on the plate (Use the attachment to cut the three points as below).
Attachment for panel mounting
Cut off
mounting attachment
levels of vibration.
*The screws (mounting screws and screws for panel mounting
attachment) are supplied with panel mounting attachment.
(9/71)

5. Procedure for wiring

Wiring for EMU4-FD1-MB

Rating voltage for every phase wire system
Phase wire type
Type
Rating voltage
Figure
3-phase 4-wire type
STAR
max AC277V(L-N)/480V(L-L)
Figure 1
DELTA
max AC220V(L-L)
Figure 2
STAR
max AC440V(L-L)
Figure 3
1-phase 3-wire type
max AC110V(L-N)/220V(L-L)
Figure 4
1-phase 2-wire type
(Note)
DELTA
max AC220V(L-L)
Figure 5
STAR
max AC440V(L-L)
Figure 6
maximum rating is “AC440V”.
3-phase 3-wire type
Note. In case of a circuit which is wired from the delta connection of a 3-phase 3-wire type, a circuit of a transformer of a
1-phase 2-wire type or a 1-phase 3-wire type, the maximum rating is “AC220V”.
In case of a circuit which is wired from a 3-phase 4-wire type or the star connection of a 3-phase 3-wire type, the
(10/71)
* Fuse is required to conform to UL.
grounding the secondary side of VT and CT.
*2,3,4(refer to next page)
*1,4(refer to next page)
*2,3,4(refer to next page)
*1,4(refer to next page)
*1,4(refer to next page)
(See*3)
(See*4)
(See*4)
(See*3)
(See*2)
k
l
l
k
l
l
k
l
l
k
l
l
k
l
l
k
l
l
k
l
l
k
l
l
k
l
l
k
l
l
k
l
l
Note 1: For low voltage circuits, do not connect to
(11/71)
Applicable wire
Tightening torque
Recommended crimp-type terminal
Auxiliary power, voltage
stranded wi re: AW G26-14(0.13~2.0mm2) single wire : AW G26-14(φ0.41~1.62mm)
0.8~1.0N・m
For M3.5 screw of external diameter below 5.6mm
Current input terminals
stranded wi re: AW G18-14(0.82~2.0mm2) *5 single wire : AW G18-14(φ1.03~1.62mm)
0.5~0.6N・m
For M3 screw of external diameter below 5.6mm
Input and output terminals
stranded wire : AWG22-14(0.33~2.0mm2) single wire : AW G22-14(φ0.65~1.62mm)
0.5~0.6N・m
For M3 screw of external diameter below 5.6mm
*1 For low voltage circuits, do not connect to grounding the secondary side of VT and CT.
Condition
distance
Power line 600V or less
300mm or longer
Other power line
600mm or longer
No-voltage a-contact Use an appropriate type for 5V DC 7mA switching.
No-voltage a-contact Use an appropriate type for 5V DC 7mA switching.
No-voltage a-contact 35V DC 24V AC 75mA (power factor : 1)
No-voltage a-contact 35V DC 24V AC 7 5m A (power factor : 1)
Transmitter
Counter
Relay
Caution
*2 When this unit is used at a high voltage circuit, the terminal P0 (P2) must be connected to ground. *3 When grounding a CT line, please make the L side of the CT a common line and connect 1L,2L,3L terminal
for the unit side by the shortest course.
*4 When connecting the L side of the CT by a common line, please connect 1L, 2L, 3L terminal for the unit
side by the shortest course.
For protection against noise, transmission lines and input/output lines shall not be placed close to or bound
together with the power lines and high-voltage lines. Keep distance as below between them. (except for the terminal block)
For the actual usage, connect the FG terminal to ground. (D-type ground: Type 3) Connect it directly to the
ground terminal. This is being bonded to the conductive part of the product for safety reasons and being connected to the terminal which is connected the outside protection grounding system.
Do not connect to FG terminal during the insulation resistance test and pressure test. Do not connect together more than one EMU4-FD1-MB on the secondary side of a current transformer. Do not connect together other units and EMU4-FD1-MB on the secondary side of a current transformer.
Use appropriate crimp-type terminal. Appropriate crimp-type terminal is as below. Use electric wires as below, and tighten the terminal screws by the torque as below.
input terminals
*5: If the diameter of the wire is small, the conductor resistance of the wire will be high and the consumption VA of the wire will increase.
Maximum voltage of the circuit connected to this unit directly is 277 / 480V. For the circuit over this voltage, use the transformer.
Decide wire diameter and wire length so that it does not exceed the rated burden of CT to be connected.
Using the transformer, primary voltage is configurable up to 6600V. (Primary voltage of VT can be set up to 6600V, and secondary voltage of VT can be set up to220V as optional setting.)
®
For MODBUS
NET transmission from MODBUS
RTU communication wiring, recommended to have the extra length wires about 200mm (When extended to B /
®
communication, use of MODBUS
When screwing the terminals at both ends of the terminal block, be careful not to touch the projection of the terminal block cover. In case using external input and/or external output, refer to the following.
External input:For the case of contact input External input: For the case of pulse input
External output:For the case of contact output External output: For the case of pulse output
75mA or,
®
RTU communication wiring is possible).
75mA or,
(12/71)

System configuration example of MODBUS®RTU communication

Installation in the middle of the
Installation at the end of the
MODBUS®RTU
Connection of MODBUS®RTU communication terminals:
1. Use the twisted shielded pair cable for transmission lines.(Recommended cable page 66.)
2. About the terminal resistance of the MODBUS
®
RTU transmission line
Please get terminal resistance of 120 Ω to the apparatus of transmission line both ends.
(Termination resistances of 120Ω can be used by short-circuiting “485-” and “Ter” terminals.)
When you are connected to the PLC on transmission line one, please get terminal resistance of 110 Ω in the PLC side.
(Please refer to Page14, "Wiring for MODBUS
®
UNIT(QJ71MB91) and EMU4-FD1-MB "
for the details.)
When you are connected to the GOT on transmission line one, please get terminal resistance of 110 Ω in the GOT side.
(Please refer to Page14, "Wiring for GOTGOT1000and EMU4-FD1-MB " for the details.)
3. Connect to ground by using thick wires to decrease impedance.
4. MODBUS
®
RTU transmission lines shall not be placed close to or bound together with the high-voltage lines.
5. Ground the “SLD” terminal at one end.
・wiring terminal
EMU4-FD1-MB
485+
SLD
485-
Ter
・Procedure for wiring
transmission rout
Connect to Terminal
transmission rout
(13/71)
・Wiring for MODBUS®UNIT(QJ71MB91) and EMU4-FD1-MB
Note) The terminal resistance of the MODBUS
®
unit (QJ71MB91) side, please connect "110Ω 1/2W".
For details, please refer to "Mitsubishi frequent use sequencer MELSEC-Q Series (QJ71MB91)
MODBUS
®
interface unit (details).
・Wiring for GOT(GOT1000) and EMU4-FD1-MB
Note) Please set the terminal resistance of the GOT(GOT1000) "110 Ω".
Please of the setting method refer to " GOT1000 Series Connection Manual (Microcomputer, MODBUS
Products, Peripherals) for GT Works3".
(14/71)

6. Operating mode

This unit has the operating modes. Switch these modes according to the purposes. The operating mode is displayed
Mode
Function
Reference
Operating mode
Display measured value digitally. It can display the condition of contact input and present time (*1) other than the present value of the measured values.
Setting mode
Set basic setting for phase wire method, primary voltage, primary current and alarm monitoring for alarm output elements.
Confirmation
Mode to confirm the setting value for each setting item.
Display useful to discriminate for incorrect wiring such as phase angle display of voltage,
Send back fixed numerical data without measurement (voltage and current) input.
Reset mode / Preset mode
Reset: Integrated values (electric energy, operating time, etc.) can be zeroed. Preset: Preset of electric energy and reactive energy.
Preset mode
Operating mode
Present value
display
Press both at the s ame time for 2 sec
SET
-
Press for 2 s ec
When selecting "End"
on the menu
SET
SET
CANCEL
display
Cancel change of
setting value
SET
End
display
Fix change of s etting value
When selecting
"End" on the menu
SET
SET
Setting mode
immediately after the auxiliary power loading.
page 49
page 16
mode (Test mode)
(The Setting cannot be changed in this mode, so it can be prevented setting change by human error.) In addition, this unit
has the test function that can be used for such as set up of an equipment.
Discrimination support display for incorrect wiring:
current.
Pulse, Alarm test:
Switch pulse output contact and alarm contact without measurement (voltage and current) input.
Communication test:
*1: Only when connecting logging unit.
page 30 page 34
page 56
(15/71)

7. Setting method

Procedures for setting

Setting menu 5 related to the logging Unit is shifted to Setting mode from Operating mode, and
Please check them beforehand.
page 31
Phase wire system
Factory default
Primary v oltage
(use or non-use of
VT)
Primary v oltage
(With VT o r Direct)
Primary current
Secondaryc urrent
Curre nt demand
ti me
Model Name
MODBUS®RTU
addre ss
MODBUS®RTU
baud ra te
MODBUS®RTU
pari ty
MODBUS®RTU
sto p bit
Contac t / pulse
input
Reset method
of c ontact inp ut
Contac t / pulse
output
"End" display
Unit amount o f
pulse output
3
Equival ent CO2
indication
4
CO2 conversion
fact or
5
Harmonic current
indication
Harmonic voltage
indication
Operating time
indication
Counting method
of operating time
2
Primary spec ial
voltage
Secondary special
voltage
Primary v oltage
(VT voltage)
1
2
Opera ting mode
Meas urement dis play
Fix of setting value cha nge
Canc el o f se tting value cha nge
"CANCEL" di spla y
Transition automatically
Example of s ett ing mode dis play
Example of confirmation mode dis play
End of setting menu
Setting menu 1
Basic setting
Setting menu 2
Comm unication s etting
Setting menu 3
Input/output s etting
For the special voltage (SP)
(Not available for 1P3W)
11
- / RESET
SET
+ / PHASE
- / RESET
SET
SET
SET
Set items such as phase wire system, primary voltage, and primary current in the setting mode to measure and monitor. Under normal use, it shall be sufficient to set the setting menu 1 (Basic setting) only. For details, refer to after the following page.
<How to set>
(1) Go into the setting mode by pressing both and at the same time for 2 sec.
(2) Select the setting menu number by pressing or .
(3) Determine the setting menu number by pressing .
(4) Set each setting item.
(5) After all setting are done, select “End” on the setting menu and press . (6) When prompted for End display, select “End” and press .
Caution
Please go in a procedure to set only Setting menu 5.
If you change setting, related setting items and measured data are initialized.
page
(16/71)
28
Procedures for setting
Function
Operation
Supplement
Press or .
After setting value is confirmed, transition to next item.
Go back the previous setting item
Press .
Go back to setting menu during setting
Press for one second.
Reset setting values to factory default.
"DISP"
""
Press once
Canc el cha nge of setting v alue.
"SET"
Press once
Skip o ther ite ms during s etting.
"SET"
Press for 1 sec
Memorize changed setting and transition to operating
mode.
"SET"
Press once
Select "CANCEL".
"+" or "-"
Press once
No dis play
Sele ct s ett ing v alue.
"+" or "-"
Press several times
Trans iti on to "End" dis play.
"SET"
Press once
Enter each setting display or transition to next item.
"SET"
Press once
Go bac k to previ ous set ting di splay.
"DISP"
Press once
Transition from operating mode to confirmation mode
"SET"
Press for 2 sec
Sele ct menu number or "E nd".
"+" or "-"
Press several times
Sy mbol
Behavior
Operation of control button
Transition from operating mode to setting mode.
"SET" + "-"
Pres s both at t he
same time for 2 sec
Use of upper /
lower limit alarm
Upper / lower limit
alarm el eme nt
Upper / lower limit
alarm value
Alarm delay time
Alarm rese t
method
Logging module
ID
Logging data clear
conf irmation
Test mode
6
10
Setting menu 4
Alarm s etting
Setting menu 5
MODB US®TCP setti ng / Logging setting
Setting menu 6
Test mode
Setting mode or confirmation mode
1: On confirmation mode, transition to operating mode.
2: Transition only when selecting "SP" for "Primary v oltage
(VT or direct voltage)" on Setting menu 1.
(For 3P4 W, only spe cia l volt age i s ava ilable when usi ng VT.)
3: Tra nsit ion only whe n s electi ng "CO. P." for "Cont act /puls e
input".
4: Trans iti on o nly whe n s elec ti ng "PLS" for "Co ntac t/pulse
output ".
5: Transi tio n only whe n se lect ing "on" f or "Equiva lent CO2
indic ati on".
6: Trans iti on only when s elec ting "o n" for "Use of upper/lo wer
li mit ala rm".
7: Trans iti on only when c onnec ting MODBUS®T CP module.8: Trans iti on only when s elec ting "o n" for MODBUS®TC P
Default G/W existence".
9: Transi tio n only whe n co nnect ing loggi ng module.10: Not dis play ed o n se tti ng mode.11: The followi ng data is not c lear ed.
Elec tri c ene rgy (consumptio n, r egene rat ion) , Reactive energy, Equiv alent C O2 (hi de), Operation time (hide)
Whe n sele ct ing "CO. P."f or "Count ing metho d of ope rat ing
7
US®TCP
9
ault G/W
ault G/W
Reset
8
DISP
+ / PHASE
- / RESET
SET
SET
Basic operations in setting
Choose setting value
confirm setting value
Press .
Press for more than one second to fast-forward
Setting value of the last item before return is effective.
(17/71)

Setting menu 1: Phase wire system, primary voltage, primary current, demand time, etc.

In this menu, set phase wire system, primary voltage, primary current, demand time, etc.
- / RESET
SET
In operating mode, press both and at the same time for more than two seconds to transition to setting
mode and enable the following operations.
Setting menu
Choose the setting menu 1. (As shown in the left figure)
SET
DISP
(1) Phase wire system
SET
DISP
(2) Primary voltage
(Use or non-use of VT)
SET
DISP
Set according to the phase wire system for the measured circuit.
3P4: Three-phase 4-wire 1P2: Single-phase 2-wire
1P3: Single-phase 3-wire 3P3: Three-phase 3-wire
Supplement: The underlined values are the defaults. (The same shall apply hereinafter.)
If you measure directly (i.e. without VT):
Choose “no” and press to transition to (3) Primary voltage (Direct).
SET
If you measure with VT:
Choose “yES” and press to transition to (4) Primary voltage (VT).
no
Supplement:
“VT” means Voltage Transformer.
yES
SET
<In case you choose “1P3” in (1) Phase wire system> You can use direct measurement only. Setting of primary voltage is skipped and setting is started from (7) Primary current Rated voltage between 1- and 2-phase and 2- and 3-phase is 110V, and that between 1- and 3-phase is 220V.
Set the direct voltage according to voltage of the measured circuit
In case you choose “3P4”in (1) Phase wire system
(3) Primary voltage
(Direct)
63.5V/110V 100V/173V 105V/182V
110V/190V
115V/199V 120V/208V 127V/220V 200V/346V
220V/380V 230V/400V 240V/415V 242V/420V 250V/430V 254V/440V 265V/460V 277V/480V
In case you choose “3P3” or “1P2”in (1) Phase wire system
SET
DISP
110V 220V 440V
(18/71)
Setting menu 1: Phase wire system, primary voltage, primary current, demand time, etc.
(4) Primary voltage
Set the primary voltage of combined VT
690V 1100V 2200V 3300V 6600V SP
(with VT)
SET
(5) Special primary
voltage
DISP
Caution: If there is no values above you want to set to, choose “SP” to enable the special primary voltage and the special secondary voltage. In case you choose “3P4” (three-phase 4-wire system) in (1) Phase wire system, the special voltage is only available.
If you choose “SP”, transition to “ (5) Special primary voltage”.
If you choose the value except for “SP”, transition to “(7) Primary current ”.
(In this case, secondary voltage is fixed to 110V.)
Set the special primary voltage of combined VT.
Setting range: 1V to 6600V
Default value is 690V
Setting of special primary voltage
Press or to choose the value at flashing digit. Press for the setting digit (flashing digit) to shift to lower. Press for the setting digit (flashing digit) to shift to upper. You can set the upper three digit of the value to the range of 1V to 6600V.
Press at the lowest digit to transition to “(6) Special secondary voltage”.
SET
DISP
Caution: In case you set the value except for between 1V and 6600V, indicate the error (E005).
When indicating the error, press to check the setting values and set the new value again.
SET
The values set the upper fourth digit and lowers to are rounded down. After setting value flashes
three times, transition to “ (6) Special secondary voltage”.
- / RESET + / PHASE
SET
(6) Special secondary
SET DISP
voltage
SET DISP
Set the special secondary voltage of combined VT.
Setting range: 1V to 220V
Default value is 110V (for three phase 3-wire system and single-phase 2-wire system), or 64V (for three-phase 4-wire system).
Setting of special secondary voltage
Press or to choose the value at flashing digit. Press for the setting digit (flashing digit) to shift to lower. Press for the setting digit (flashing digit) to shift to upper. You can set the value to the range of 1V to 220V.
Press at the lowest digit to transition to “(7) Primary current”.
SET
DISP
Caution: In case you set the value except for between 1V and 220V, indicate the error (E005).
When indicating the error, press to check the setting values and set the new value again.
SET
- / RESET + / PHASE
SET
(19/71)
Setting menu 1: Phase wire system, primary voltage, primary current, demand time, etc.
(7) Primary current
Set the primary current of combined CT.
1A 5A 6A
7.5A
8A
10A 12A 15A 20A 25A
30A
40A 50A 60A 75A 80A
100A 120A 150A 200A
250A 300A 400A 500A 600A 750A
800A 1000A 1200A 1250A
1500A 1600A 2000A 2500A 3000A 4000A 5000A 6000A
SP
Supplement: “CT” means Current Transformer.
Supplement: If there is no values above you want to set to, choose “SP” to
enable the special primary current.
If you choose “SP”, transition to “(8) Special primary current”.
If you choose the value except for “SP”, transition to “(9) Secondary current”.
SET
DISP
Set the special primary current of combined CT.
Setting range: 1A to 6000A (Default: 100.0A)
Setting of special primary current
Press or to choose the value at flashing digit.
(8) Special primary
current
Press for the setting digit (flashing digit) to shift to lower. Press for the setting digit (flashing digit) to shift to upper. You can set the value in the range from 1A to 6000A.
Press at the lowest digit to transition to “(9) Secondary Current”.
SET
DISP
(9) Secondary current
Set the secondary current of combined CT.
- / RESET + / PHASE
SET
DISP
If the value is less than 10A, you can set upper two digits of it. If the value is 10A or more, you can set upper three digits of it.
Caution: In case you set the value except for the range from 1A and 6000A, indicate the error
(E005). When indicating the error, press to check the setting values and set
the new value again.
SET
SET
5A 1A
SET DISP
(20/71)
Setting menu 1: Phase wire system, primary voltage, primary current, demand time, etc.
(10) Current demand
Set the current demand time. On setting display, “s” means “second” and “M” means “minute”.
time
SET
(11) Electric power
demand time
SET
(12) Model code
DISP
DISP
0s 10s 20s
Set the electric power demand time. On setting display, “s” means “second” and “M” means “minute”.
The model code can be confirmed.
(This is only display, and settings cannot be changed.)
30s
0s 10s 20s 30s
40s 50s
1M 2M
40s 50s
1M 2M
3M 4M 5M 6M
3M 4M 5M 6M
7M 8M 9M
10M
7M 8M 9M
10M
11M 12M 13M 14M
11M 12M 13M 14M
15M 20M 25M 30M
15M 20M 25M 30M
SET
Setting menu
DISP
Complete the setting or continue in other menu according to procedures for setting.
For procedures for setting, page 16
(21/71)
Loading...
+ 51 hidden pages