Mitsubishi Electric MODBUS TCP, EMU4-CM-MT User Manual

4. Name and function of each part
MODBUS®TCP Communication Unit for Energy Measuring Unit (EMU4-FD1-MB)
Model EMU4-CM-MT
User's Manual
Before using the product, please read this manual carefully to ensure correct use.Make sure that the end users read this manual and then keep the manual in a safe place for future reference.Make sure to deliver this manual to the end-user.
1. Features
This Unit is the optional dedicated product for Energy Measuring Unit (EcoMonitorLight Model: EMU4-FD1-MB)This Unit enables to transfer measured data to programmable controllers for data acquisition via MODBUS
2. Checking package content
These following items for this device are included in package. Check that no items are missing. (1) MODBUS
3. Safety Precautions
3.1 Precautions for Operating Environment and Conditions
This Unit is premised on being used in pollution degree II environment. When used in higher pollution degree, protect this Unit from pollution on another device side to be incorporated. For the definition of the pollution degree and the over voltage category, refer to EN61010-1/2010. Do not use this product in the places listed below. Failure to follow the instruction may cause malfunctions or decrease of product-life.
Places the Ambient temperature exceeds the range-5-+55°CDust, corrosive gas, saline and oil smoke existPlaces the Relative humidity exceeds the range 30-85% or places with dewfallPlaces exposed to rain or water dropOperating altitude exceeds 2000m Vibration and impact exceed the specificationsPlaces metal fragments or conductive substance are flyingPlaces the average daily temperature exceeds +35°C Places in strong electromagnetic field or places large amounts of external noise existPlaces exposed to direct sunlight
This unit is the open type device, which are designed to be housed within another device for prevention of electric shock. House this unit within the device such as the control panel before use. (Indoor use)
3.2 Matters concerning the precaution before use
Use the Unit in the specified usage environment and conditions.Before using this Unit, set MODBUS
※Please refer to “user’s manual of EMU4-FD1-MB”.
3.3 Installation Precautions
DANGER
CAUTION
®
TCP Communication Unit×1 (2) User’s manual ×1
®
TCP IP address, Subnet mask, Default gateway existence and Default gateway address.
For installation and wiring works, make sure that the power source is shut off for all outside phases. If all phases are not turned off, it may cause an electric shock or product damages.
Any person who is involved in installation and wiring of this Unit should be fully competent to do this work.Work under the electric outage condition when installing and wiring. Failure to do so may cause electric shock or a failure of the Unit, a fire etc.
If you are considering using this module for special purpose such as nuclear power plants, aerospace, medical care or passenger vehicles please refer to our sales representative.
®
TCP communication.
Front view Left-side view Back view
1)
2)
<Name and function of each part>
No.
1)
LED
2)
Connector for MODBUS
3)
IEC rail stop
4)
Connection stop
Name of part
®
TCP communication
Operation status of MODBUS
10BASE-T/100BASE-TX connector (RJ45)
This is used to fix to an IEC rail.
This is used to connect the MODBUS®TCP communication Unit to the Energy Measuring Unit.
4)
4)
5. How to wire
Connect the MODBUS®TCP communication Unit to the Energy Measuring Unit. *This unit can be attached to EcoMonitorLight in below.
(1) Remove the blank label stuck to the side of the Energy Measuring Unit.
Blank label
(2) Insert the connector of the MODBUS Unit into the connector of the Energy Measuring Unit and make these Units closely-attached.
®
TCP communication is displayed.
®
TCP communication
DISP
+/PHASE
/RESET
Model
EMU4-FD1-MB
SET
Functions
3)
(3) Slide the connection stops (green-colored) of upper and lower of the MODBUS Unit to lock it.
®
TCP communication
In 100Mbps communication by the 100BASE-TX connection, a communication error may occur under the influence of high frequency noise from devices other than this device in the installation environment. Take the following action to prevent the influence of high frequency noise in the construction of a network system. (1) Wiring connection
CAUTION
3.4 Precautions for Use
Before operating the product, check that active bare wire and so on does not exist around the product. If any exposed conductor is found, stop the operation immediately and take
an appropriate action such as isolation protection
In the event of a power outage during the setting, the Unit is not set correctly. Please set again after power recovery. When you connect to Energy Measuring Unit of the Unit, Contrast of the LCD display of Energy Measuring Unit is reduced to small.
DANGER
CAUTION
3.5 Maintenance Precautions
Use a soft dry cloth to clean off dirt of the Unit surface. Do not let a chemical cloth remain on the surface for an extended period of time nor wipe the surface with thinner or benzene.Check for the following items to use this Unit properly for long time.
<Daily maintenance>
(1) No damage on this Unit (2) No abnormality with LED indicators (Check item No.4 under the power failure condition. Failure to do so may cause electric shock, failure of the Unit or a fire.)
3.6 Storage Precautions
To store this Unit, put it in a plastic bag. For long-time storage, avoid the following places. Failure to follow the instruction may cause a failure and reduced life of the Unit.
Places the ambient tempe rature exceeds the range -10-+60°CPlaces the average daily temperature exceeds +35°C Places exposed to rain, water drop or direct sunlightPlaces the Relative humidity exceeds the range 30-85% or places with dewfall
3.7 Disposal Precautions
When disposing of this Unit, treat it as industrial waste.
3.8 About packaging materials and this manual
For reduction of environment load, packaging materials are produced with cardboard, and this manual is printed on recycled paper.
Do not install a twisted pain cable together with the main circuit and power cables, etc.Place the twisted pair cable in a duct.
(2) Communication system
Increase the number of communication retries if necessary.Change the hub used for connection into a 10Mbps hub, and make communication at a transmission speed of 10Mbps.
Do not touch the live part. It may cause electric shock, electric burn injury or burnout of the device. ・Work under the electric outage condition when installing and wiring.
Do not disassemble or modify this Unit It may cause failure, malfunction, injury or fire.Do not touch the MODBUSPush the RESET switch with an appropriate force (1.6N). The addition of force than necessary, it may cause a malfunction or failure of the Unit.
®
TCP communication connectors when communicating. It may cause a malfunction or failure of the Unit.
(3) No abnormal noise, smell or heat (4) No looseness with installation and wire connection
Vibration and impact exceed the specificationsPlaces metal fragments or conductive substance are flyingPlaces where dust, corrosive gas, saline and oil smoke exist
CAUTION
Work under the electric outage condition when connecting the Energy Measuring Unit. Failure to do so may cause electric shock, a failure of the Unit, a fire etc.
6. Mounting the Unit
There are two mounting methods, surface mounting and panel mounting.
6.1 Mounting the Unit on an IEC rail
*This unit can be attached to EcoMonitorLight in below. This unit can be attached to EcoMonitorPlus as well.
Applicable IEC rail
35
1
27
More than 7.3
Mounting How to remove
(3) Push the Unit
(1) Hold the module and pull the stopper of IEC rail down.
(2) Hook on the rail
IEC rail
(4) Push the stopper of the IEC rail above.
(2) Pull tha module
(1) Hold the module and pull the stopper of IEC rail down.
6.2 Screw mounting
Panel cut dimension
External dimensions of MODBUS
®
TCP communication Unit
External dimensions of Energy Measuring Unit
(Measuring unit)
●Attachment
(Measuring unit)
6.3 Screw mounting (When using the attachment for panel mounting)
Panel cut dimension
External dimensions of MODBUS
®
TCP communication Unit
(Attachment)
External dimensions of Energy Measuring Unit
(Measuring unit)
Attach the plate by screws (M3×10). Tightening torque:0.63N
m
Mounting screw
Attachment
Recommended mounting screw
Cross recessed pan-head screw with captive spring or plain washer JIS B 1188 Two screws (M3×10)
Attachment
Mount on the plate by screws (M3×10), then mount the panel mounting attachment on the plate. Tightening torque:0.63Nm
Mounting screw (*1)
Attachment for panel mounting
Screws for fixing the attachment (*1)
Cut (
*2)
Attachment plate
9. Specifications
<Basic Specifications>
Item Specifications
®
Product
Model
Accommodating model
Standard
Operating temperature
Operating humidity
Storage temperature
Usage
environment
Operating altiude
Mass
<MODBUS
®
TCP Communication specifications>
Energy Measuring Unit (EMU4-FD1-MB) MODBUS
EMU4-CM-MT
Energy Measuring Unit EcoMonitorLight Model:EMU4-FD1-MB
EMC:EN-61326-1:2013
from -5 to +55°C (average daily temperature is not more than +35°C)
30-85% RH (No condensation)
from -10 to +60°C
Not more than 2000m
®
0.1kg ※Mass of the MODBUS
TCP Communication Unit only
Item Specifications
Interface
Transmission method
Number of cascade connection stages *1
Maximum node-to-node distance
Maximum segment length *2
Connector applicable for external wiring
Cable
10BASE-T
100BASE-TX
Protocol
Number of simultaneously connection
Functions supported
1 port (10BASE-T/100BASE-TX)
Base band
Max. 4 stages (10BASE-T), Max. 2 stages (100BASE-TX)
200m (656.16ft.)
100m (328.08ft.)
RJ45
Cable compliant with the IEEE802.3 10BASE-T Standard (unshielded twisted pair cable (UTP cable), Category 3 or more)
Cable compliant with the IEEE802.3 100BASE-T Standard (shielded twisted pair cable (STP cable), Category 5 or more)
MODBUS
®
TCP (Port number 502)
Max. 4 connection
Auto negotiation (10BASE-T/100BASE-TX automatically detected) Auto MDIX function (straight/crossover cable automatically detected)
*1. This is the maximum number of cascade connection stages when a repeater hub is used. For the maximum number of cascade connection stages, contact to the manufacturer for the switching hub used. *2. Length between a hub and a node.
TCP Communication Unit
7. External dimensions
8. Wiring Diagram
(Measuring unit)
(Attachment)
4.590
4.5
*1. The mounting screws and the screws for fixing the attachment are included in Attachment (optional part). *2. Before use, you need to cut each part of the attachment.
10. After-sales service
If you have any questions or the product is broken down, contact our sales representative near you
The charge-free warranty is effective until the earlier of 1 year after the date of your purchase or 18 months after manufacturing.The gratis warranty shall apply if the product fails even though it is being used properly in the conditions, with the methods and under the environments in accordance with the
terms and precautions described in the catalogs, the instruction manual, caution label on the product, etc.
25
6.6
60
4
Unit:mm
15
Regardless of Gratis Warranty Period, our company shall not be liable to compensate for any loss arising from events not attributable to our company, opportunity loss and lost earning of the customer due to failure of the product, and loss, secondary loss, accident compensation, damage to other products besides our products and other operations caused by a special reason regardless of our company's predictability. If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
CAUTION
If an abnormal sound, bad-smelling smoke, fever break out from this Unit, switch it off promptly and don't use it.
11. Customer Service
4
17.6
35.427
HEAD OFFICE: TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, Japan Please refer to "catalog" or “user’s manual (Details)” for more detail.