Automatic switch to backup heat source operation
Back-up heat source operation (*1) will automatically run when the outdoor unit stops abnormally. To enable the function, switch DIP SW 2-5 to ON. During the backup operation, an error code(s) and the contact number will be displayed alternately. External output (OUT11) will be available.
To clear the fault(s), reset the power breakers on the indoor and outdoor units.
<Applicable error codes (*2)>
E6 to E9, ED, P6, P8, U1 to U8, UD, UE, UF, UL, UP
(*1) Prolonged running of the back-up operation may affect the life of the heat source.
(*2) For safety reasons, this function is not available for certain faults. (System operation must be stopped and only pump keeps running.)
6-7. DIP switch setting
Located on the FTC printed circuit board are 4 sets of small white switches
known as DIP switches. The DIP switch number is printed on the circuit board
next to the relevant switches. The word ON is printed on the circuit board and on
the DIP switch block itself. To move the switch you will need to use a pin or the
corner of a thin metal ruler or similar.
DIP switch settings are listed below in the table below.
Before changing any switch settings, ensure power supplies to indoor and outdoor units are isolated/powered off.
DIP switch Function OFF ON
Default settings:
Indoor unit model
SW1
SW1-1 Boiler WITHOUT Boiler WITH Boiler OFF
SW1-2 Heat pump maximum outlet water temperature 55ºC 60ºC ON *1
SW1-3 DHW tank WITHOUT DHW tank WITH DHW tank ON
SW1-4 Immersion heater WITHOUT Immersion heater WITH Immersion heater
OFF:
EH*T20*-*C
ON : EH*T20*-*HC*
SW1-5 Booster heater WITHOUT Booster heater WITH Booster heater
OFF:
EH*T20*-M*C*
ON :
EH*T20*-*M 2/6/9*C
SW1-6 Booster heater function For heating only For heating and DHW
OFF:
EH*T20*-M*C*
ON :
EH*T20*-*M 2/6/9*C
SW1-7 Outdoor unit type Split type Packaged type
OFF: EHST20*-*M**C*
ON :
EHPT20X-*M**C*
SW1-8 Wireless remote controller
WITHOUT Wireless remote controller
WITH Wireless remote controller OFF
SW2
SW2-1 Room thermostat1 input (IN1) logic change
Zone1 operation stop at thermostat short
Zone1 operation stop at thermostat open
OFF
SW2-2 Flow switch1 input (IN2) logic change Failure detection at short Failure detection at open OFF
SW2-3 Booster heater capacity restriction Inactive Active
OFF: Except
EH*T20*-VM2*C
ON : EH*T20*-VM2*C
SW2-4 — — — OFF
SW2-5
Automatic switch to backup heat source operation
(When outdoor unit stops by error)
Inactive Active *2 OFF
SW2-6 Mixing tank WITHOUT Mixing tank WITH Mixing tank OFF
SW2-7 2-zone temperature control Inactive Active *6 OFF
SW2-8 Flow sensor WITHOUT Flow sensor WITH Flow sensor ON
SW3
SW3-1 Room thermostat 2 input (IN6) logic change
Zone2 operation stop at thermostat short
Zone2 operation stop at thermostat open
OFF
SW3-2 Flow switch 2 input (IN3) logic change Failure detection at short Failure detection at open OFF
SW3-3 Flow switch 3 input (IN7) logic change Failure detection at short Failure detection at open OFF
SW3-4 Electric energy meter WITHOUT Electric energy meter WITH Electric energy meter OFF
SW3-5 Heating mode function *3 Inactive Active ON
SW3-6 2-zone valve ON/OFF control Inactive Active OFF
SW3-7 Heat exchanger for DHW Coil in tank External plate HEX ON
SW3-8 Heat meter WITHOUT Heat meter WITH Heat meter OFF
SW4
SW4-1 — — — OFF
SW4-2 — — — OFF
SW4-3 — — — OFF
SW4-4
Indoor unit only operation (during installation work) *4
Inactive Active OFF
SW4-5 Emergency mode (Heater only operation) Normal
Emergency mode (Heater only operation)
OFF *5
SW4-6 Emergency mode (Boiler operation) Normal Emergency mode (Boiler operation) OFF *5
SW5
SW5-1 — — — OFF
SW5-2 — — — OFF
SW5-3
SW5-4
SW5-5
SW5-6
SW5-7
SW5-8 — — — OFF
Note: *1. When the cylinder unit is connected with a PUHZ-RP/SUHZ-SW outdoor unit of which maximum outlet water temperature is 55ºC, DIP SW1-2
must be changed to OFF.
*2. External output (OUT11) will be available. For safety reasons, this function is not available for certain errors. (In that case, system operation
must be stopped and only the water circulation pump keeps running.)
*3. This switch functions only when the cylinder unit is connected with a PUHZ-FRP outdoor unit. When another type of outdoor unit is con-
nected, the heating mode function is active regardless of the fact that this switch is ON or OFF.
*4. Space heating and DHW can be operated only in indoor unit, like an electric boiler. (Refer to "Indoor unit only operation" in page 44. )
*5. If emergency mode is no longer required, return the switch to OFF position.
*6. Active only when DIP SW3-6 is set to OFF.
SW1
SW3
SW4
SW2
SW5
SW5-3 SW5-4 SW5-5 SW5-6 SW5-7
EHST20C-*M*C* ON ON ON ON OFF
EHST20D-*M*C* ON OFF OFF ON OFF
EHPT20X-*M*C* OFF OFF OFF OFF OFF
Capacity code