–87–
(5) Refrigerant Amount Adjustment Mode Operations (PURY-(P)200·250YMF-B)
1) Procedure
Follow the procedure shown below when needs to additionally replenish or discharge refrigerant arises depending
on operation status.
When turning on function select switch (SW2-4) on outdoor unit control circuit board, mode is changed to
refrigerant amount adjustment mode followed by the operations shown in the table below.
In addition when setting selfdiagnosis switch (SW1) on control circuit board of outdoor unit to
1ON2345678910
liquid level of accumulator is shown by position of LED light-up.
When LED1 lights up → AL = 0 (No liquid in accumulator)
When LED2 lights up → AL = 1 (Liquid in accumulator)
When LED3 lights up → AL = 2 (Overcharge)
Note 1: Though AL=1 is shown for a while after starting operations in refrigerant amount adjustment mode, it some-
times changes to AL=0 as time goes by (when refrigerant system becomes stable).
1 In the case of genuine AL=1
In case AL=1, subcool of BC controller is 5 degrees or more, and SH of all indoor units are within 5-9
degrees.
2 In case the present AL=1 status will possibly change to AL=0
In case subcool of BC controller is 5 degrees or less, or SH of at least one indoor units 5 degrees or less.
2: Refrigerant amount adjustment in cooling mode can not be performed when high pressure is 14kg/cm
2
G
(1.37MPa) or more. In this case, perform the adjustment in heating mode.
In the case of cooling-only operations in refrigerant amount adjustment mode, if the above 2
is applicable, judge accumulator level (AL) after subcool of BC controller reaches 5 deg or
more, and SH of all indoor units becomes 5~7 degrees.
Monitor subcool of BC controller at LED light-up position, by turning on selfdiagnosis switch
of outdoor unit (SW1-1, 2, 4, 8)
Monitor SH of indoor unit at LED light-up position, by turning on No. 1 unit SW1 -5, 6, 8
No. 2 unit SW1 -1, 5, 6, 7 and No. 3 unit SW1 -2, 5, 6, 8 No. 4 Unit SW1 -1, 2, 5, 6, 8
No. 5 unit SW1 -3, 5, 6, 8 No. 6 unit SW1 -1, 3, 5, 6, 8, No. 7 unit SW1 -1, 2, 3, 5, 6, 8,
No. 8 unit SW1 -4, 5, 6, 8 No. 9 unit SW1 -1, 4, 5, 6, 8, No. 10 unit SW1 -2, 4, 5, 6, and 8.
During cooling-only operations only, LEV3of BC controller is set at fixed opening, with outdoor
unit heat exchanger fully operated (SV3-5 open, SV6 close).
During heating-only operations (or cooling/heating mixed operations), normal operation is
observed.
Operations
1
2
Countermeasure
A
B
C
for PU(H)Y-(P)200·250YMF-B